Carrier 38Au Users Manual 09SI
38AU to the manual c37178b3-8344-4c06-a11a-0df7c3c65dfd
2015-01-24
: Carrier Carrier-38Au-Users-Manual-310588 carrier-38au-users-manual-310588 carrier pdf
Open the PDF directly: View PDF .
Page Count: 56
Download | |
Open PDF In Browser | View PDF |
38AU Air Cooled Condensing Units 60 Hz With PuronR (R---410A) Refrigerant Sizes 16---25 Installation, Start---Up and Service Instructions CONTENTS SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 2 Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 INSTALLATION GUIDELINES . . . . . . . . . . . . . . . . . . 2 Servicing Systems on Roofs with Synthetic Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Replacement/Retrofit — R-- 22 to Puron . . . . . . . . . . . 2 Liquid Line Filter Drier . . . . . . . . . . . . . . . . . . . . . . . 34 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 22 Field Refrigerant Access Ports . . . . . . . . . . . . . . . . . . 34 Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Factory High-- Flow Access Ports . . . . . . . . . . . . . . . . 34 Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . . 11 Comfort Alert Diagnostic Module . . . . . . . . . . . . . . . 35 Step 2 - Complete Pre-- Installation Checks . . . . . . . . 11 Compressor Protection . . . . . . . . . . . . . . . . . . . . . . . . 37 Step 3 – Prepare Unit Mounting Support . . . . . . . . . . 12 Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Step 4 – Rig and Mount the Unit . . . . . . . . . . . . . . . . 12 Low-- Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . 37 Step 5 – Complete Refrigerant Piping Connections . . . 12 High-- Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . 37 Step 6 – Install Accessories . . . . . . . . . . . . . . . . . . . . 17 Outdoor Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Step 7 – Complete Electrical Connections . . . . . . . . . 18 Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Coil Type Identification . . . . . . . . . . . . . . . . . . . . . . . 42 System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 NOVATIONtCoil Cleaning and Maintenance . . . . . 42 Turn On Crankcase Heater . . . . . . . . . . . . . . . . . . . . . 23 Repairing NOVATION Condenser Tube Leaks . . . . . 42 Preliminary Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Replacing NOVATION Condenser Coil . . . . . . . . . . . 43 START-- UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 - 31 Routine Cleaning of Round-Tube Plate Fin (RTPF) Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Start Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 OPERATING SEQUENCE . . . . . . . . . . . . . . . . . . . . . . 32 Indoor (Supply) Fan . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Cooling, Unit Without Economizer . . . . . . . . . . . . . . 32 Cooling, Unit With Economizer . . . . . . . . . . . . . . . . . 32 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 ROUTINE SYSTEM MAINTENANCE . . . . . . . . . . . . 33 Fastener Torque Values . . . . . . . . . . . . . . . . . . . . . . . . 44 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . 44 - 45 APPENDIX A Air Conditioner & Heat Pump with PuronR — Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . 46 APPENDIX B Wiring Diagram List . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Quarterly Inspection (and 30 days after initial start) . . . 33 APPENDIX C Low Ambient Option — Factory Installed . . . . . . . . . . 47 Seasonal Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 33 START-- UP CHECKLIST . . . . . . . . . . . . . . . . . . . 55 - 56 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 - 44 Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . 33 1 SAFETY CONSIDERATIONS ! 38AU Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions package PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause in personal injury or death. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements. ! ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause in personal injury or death. Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch. ! WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause in personal injury,death and/or equipment damage. PuronR (R-- 410A) refrigerant systems operate at higher pressures than standard R-- 22 systems. Do not use R-- 22 service equipment or components on Puron refrigerant equipment. CAUTION CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing 38AU units. It is important to recognize safety information. This is the . When you see this symbol on the safety-- alert symbol unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. WARNING INSTALLATION GUIDELINE Replacement/Retrofit — R--22 to PuronR Replacement/retrofit installations require change-out of outdoor unit, metering device, and filter driers. Change-out of indoor coil (evaporator) and interconnecting tubing is recommended. Existing evaporator coil – If the existing evaporator coil may be re-used, check with the coil manufacturer to verify the coil construction is suitable for operation with the higher pressures of PuronR (R-410A). Also determine if the existing TXV valve is compatible with R-410A, replace if necessary. The minimum factory test pressure rating must be 250 psig (1725 kPa). Existing coil will need to be purged with Nitrogen to remove as much mineral oil as possible to eliminate cross contamination of oils. Acid test – If the existing system is being replaced because of a compressor electrical failure, assume acid is in system. If system is being replaced for any other reason, use an approved acid test kit to determine acid level. If even low levels of acid are detected, install a 100 percent activated alumina suction-line filter drier in addition to the replacement liquid-line filter drier. Remove the suction line filter drier as soon as possible, with a maximum of 72 hr of operation. Recommendation: Install a ball valve in the liquid line at the filter drier location when installing a suction filter in the suction line. Existing refrigeration piping – Reuse of existing refrigerant piping involves three issues: quality (strength) of existing tubing, cleanliness and tube size. Inspect all tube segments and joints for signs of damage, corrosion or poor brazing. Flush the interconnecting piping system with dry Nitrogen to eliminate as much trace of mineral oil as possible. 2 5. Install a new field-supplied liquid-line filter drier at the indoor coil just upstream of the TXV or fix orifice metering device. 6. If a suction line filter drier is also to be installed, install suction line drier downstream of suction line service valve at condensing unit. Same tube sizes are capable of handling higher flowrates (expressed as tons of cooling capacity) with Puron refrigerant compared to R--22 at constant pressure drops. For example, a 1/2- inch OD liquid line is rated at 33% higher tons with PuronR than with R--22 (at 5_F pressure drop). A 1 1/8- inch OD suction line is rated at 53% higher tons with Puron than with R--22 (at 2_F pressure drop). Refrigeration lines selected for R--22 use are typically oversized for Puron applications. Carefully check the existing suction line size against the table for maximum size (see Table 7); replace vertical riser segments if necessary. Check existing liquid line size against sizing data in Table 5 or 6; replace with smaller lines when feasible. ! CAUTION Installation – 1. Remove the existing evaporator coil or fan coil and install the replacement coil when appropriate. 2. Drain oil from low points and traps in suction line tubing (and hot gas bypass tubing if appropriate) and evaporator if they were not replaced. Removing oil from evaporator coil may require purging of the tubing with dry nitrogen. 3. Unless indoor unit is equipped with a Puron® approved metering device, change the metering device to a thermal expansion valve (TXV) designed for PuronR (R-410A). 4. Remove the existing outdoor unit. Install the new outdoor unit according to these installation instructions. 7. If required, install a 100% activated alumina suction line filter drier at the outdoor unit. 8. Evacuate and charge the system according to the instructions in this installation manual. 9. Operate the system for 10 hr. Monitor the pressure drop across the suction line filter drier. If pressure drop exceeds 3 psig (21kPa), replace suction-line and liquid-line filter driers. Be sure to purge system with dry nitrogen and evacuate when replacing filter driers. Continue to monitor the pressure drop across suction-line filter drier. Repeat filter changes is necessary. Never leave suction-line filter drier in system longer than 72 hr (actual time). 3 38AU UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Never install suction-- line filter drier in the liquid-- line of a PuronR system. 38AU C10942 UNIT Standard Weight Corner A Corner B Corner C Corner D Unit Height Center of Gravity lbs. kg. lbs. kg. lbs. kg. lbs. kg. lbs. kg. X Y Z H 38AUZ*16 (MCHX) 633 288 220 100 134 61 135 61 144 65.5 38 [965.2] 19 [482.6] 15 [381] 50 3/8 [1279.2] 38AUD*16 (MCHX) 633 288 220 100 134 61 135 61 144 65.5 38 [965.2] 19 [482.6] 15 [381] 50 3/8 [1279.2] 38AUZ*16 (RTPF) 731 332 237 107 172 78 135 61 186 84 38 [965.2] 19 [482.6] 17 [431.8] 50 3/8 [1279.2] 38AUD*16 (RTPF) 731 332 237 107 172 78 135 61 186 84 38 [965.2] 19 [482.6] 17 [431.8] 50 3/8 [1279.2] LEGEND: MCXH = Novation™ coil RTPF = Round Tube/Plate Fin coil Fig. 1 - 38AU**16 Unit Dimensions 4 38AU C10943 UNIT Standard Weight Corner A Corner B Corner C Corner D Unit Height Center of Gravity lbs. kg. lbs. kg. lbs. kg. lbs. kg. lbs. kg. X Y Z H 38AUZ*25 (RTPF) 978 444 360 163 188 85 147 67 283 128 38 [965.2] 23 [584.2] 17 [431.8] 50 3/8 [1279.2] 38AUD*25 (RTPF) 978 444 360 163 188 85 147 67 283 128 38 [965.2] 23 [584.2] 17 [431.8] 50 3/8 [1279.2] LEGEND: RTPF = Round Tube/Plate Fin coil Fig. 2 - 38AU**25 Unit Dimensions 5 Table 1A — Physical Data — 38AUZ*16-25 Units — 60 Hz English UNIT SIZE 38AU Z*16 Z*25 15 20 NOVATION™ Coil (Al Tube) 633 --- Round Tube/Plate Fin Coil (Cu/Al) 731 900 NOMINAL CAPACITY (tons) OPERATING WEIGHTS (lb) REFRIGERANT TYPE‡ R-410A NOVATION Operating Charge, Typical (lb)† 24.6 --- 12.2 --- 43.0 38.0 32.0 28.0 2...Scroll 2...Scroll 60 110 Qty...Rpm 3...1100 4...1100 Motor Hp 1/ 1/ Diameter 22 22 9,000 12,000 970 1150 NOVATION Shipping Charge (lb) RTPF Operating Charge, Typical (lb)† RTPF Shipping Charge (lb) 38AU COMPRESSOR Qty...Type Oil Charge (oz) CONDENSER FANS Nominal Airflow (Cfm Total) Watts (Total) 4 4 RTPF CONDENSER COIL Material (Tube/Fin) Cu / Al 3/ --- in 8 Coil Type Rows/Fins per inch (FPI) Face Area (sq ft total) Cu / Al 3/ --- in 8 RTPF RTPF 2 / 17 2 / 17 47.0 50.0 Al / Al --- Novation --- 1 / 17 --- 50.0 --- NOVATION CONDENSER COIL Material (Tube/Fin) Coil Type Rows/Fins per inch (FPI) Face Area (sq ft total) CONTROLS Pressurestat Settings (psig) High Cutout 630 ± 10 Cut-in 505 ± 20 Low Cutout 54 ± 3 Cut-in 117 ± 5 PIPING CONNECTIONS (in. ODS) Qty...Suction 1...13/8 1...15/8 Qty...Liquid 1...5/ 1...5/8 LEGEND RTPF — Round Tube/Plate Fin ODS — Outside Diameter Sweat (socket) ‡ † Unit is factory-supplied with partial charge only. Typical operating charge with 25 ft of interconnecting piping. 6 8 Table 1B — Physical Data — 38AUZ*16-25 Units — 60 Hz SI UNIT SIZE 38AU Z*16 Z*25 NOMINAL CAPACITY (kW) 52.7 70.3 NOVATION™ Coil (Al Tube) 288 --- Round Tube/Plate Fin Coil (Cu/Al) 332 409 OPERATING WEIGHT (kg) R-410A NOVATION Operating Charge, Typical (kg)† NOVATION Shipping Charge (kg) RTPF Operating Charge, Typical (kg)† RTPF Shipping Charge (kg) 11.1 --- 5.4 --- 19.5 17.2 14.5 12.7 COMPRESSOR Scroll Qty...Type Oil Charge (L) 2...Scroll 2...Scroll 1.7 3.2 3...18 4...18 CONDENSER FANS Qty...r/s Motor Hp NEMA 1/ 1/ Diameter (mm) 560 560 Nominal Airflow (L/s) 4248 5663 Watts (Total) 970 1150 4 4 RTPF CONDENSER COIL (Qty) Material (Tube/Fin) Cu / Al 3/ --- in 8 Coil Type Rows/Fins per Meter (Fins/m) Face Area (sq m total) Cu / Al RTPF 3/ --- in 8 RTPF 1...670 2...670 4.4 4.6 Al / Al --- Novation --- 1...670 --- 4.6 --- NOVATION CONDENSER COIL Material (Tube/Fin) Coil Type Rows/Fins per Meter (Fins/m) Face Area (sq m total) CONTROLS Pressurestat Settings (kPa) High Cutout 4347 ± 70 Cut-in 3482 ±138 Low Cutout 372 ± 21 Cut-in 807 ± 34 PIPING CONNECTIONS (mm ODS) Qty...Suction 1...34.9 1...38.7 Qty...Liquid 1...13.3 1...13.3 LEGEND RTPF — Round Tube/Plate Fin NEMA — National Electrical Manufacturers Association ODS — Outside Diameter Sweat (socket) ‡ † Unit is factory-supplied with partial charge only. Typical operating charge with 7.62 m of interconnecting piping. 7 38AU REFRIGERANT TYPE‡ Table 2A — Physical Data — 38AUD*16-25 Units — 60 Hz English UNIT SIZE 38AU D*16 D*25 15 20 NOVATION™ Coil (Al Tube) 633 --- Round Tube/Plate Fin Coil (Cu/Al) 731 900 NOMINAL CAPACITY (tons) OPERATING WEIGHTS (lb) REFRIGERANT TYPE‡ R-410A NOVATION Operating Charge A/B, Typical (lb)† NOVATION Shipping Charge A/B (lb) RTPF Operating Charge A/B, Typical (lb)† 12.0 / 12.0 --- 6.0 / 6.0 --- 22.0 / 22.0 19.0 / 19.0 16.0 / 16.0 14.0 / 14.0 2...Scroll 2...Scroll 60 / 60 110 / 110 Qty...Rpm 3...1100 4...1100 Motor Hp 1/4 1/ Diameter 22 22 9,000 12,000 970 1150 RTPF Shipping Charge A/B (lb) 38AU COMPRESSOR Qty...Type Oil Charge A/B (oz) CONDENSER FANS Nominal Airflow (Cfm Total) Watts (Total) 4 RTPF CONDENSER COIL Material (Tube/Fin) Cu / Al 3/ --- in 8 Coil Type Face Area (sq ft total) Rows/Fins per inch (FPI) Cu / Al 3/ --- in 8 RTPF RTPF 47 50 2 / 17 2 / 17 Al / Al --- Novation --- 50 --- 1 / 17 --- NOVATION CONDENSER COIL Material (Tube/Fin) Coil Type Face Area (sq ft total) Rows/Fins per inch (FPI) CONTROLS Pressurestat Settings (psig) High Cutout 630 ± 10 Cut-in 505 ± 20 Low Cutout 54 ± 3 Cut-in 117 ± 5 PIPING CONNECTIONS (in. ODS) Qty...Suction 2...13/8 2...13/8 Qty...Liquid 2...1/ 2...1/2 LEGEND RTPF — Round Tube/Plate Fin ODS — Outside Diameter Sweat (socket) ‡ † Unit is factory-supplied with partial charge only. Typical operating charge with 25 ft of interconnecting piping. 8 2 Table 2B — Physical Data — 38AUD*16-25 Units — 60 Hz SI UNIT SIZE 38AU D*16 D*25 NOMINAL CAPACITY (kW) 52.7 70.3 NOVATION™ Coil (Al Tube) 288 --- Round Tube/Plate Fin Coil (Cu/Al) 332 409 R-410A R-410A 5.4 / 5.4 --- 2.7 / 2.7 --- 10.0 / 10.0 8.6 / 8.6 7.3 / 7.3 6.8 / 6.8 Qty...Type 2...Scroll 2...Scroll Oil Charge A/B (L) 1.7 / 1.7 3.2 / 3.2 OPERATING WEIGHT (kg) REFRIGERANT TYPE‡ NOVATION Operating Charge A/B, Typical (kg)† NOVATION Shipping Charge A/B (kg) RTPF Operating Charge A/B, Typical (kg)† RTPF Shipping Charge A/B (kg) CONDENSER FANS Qty...r/s 3...18 4...18 Motor Hp NEMA 1/ 1/ Diameter (mm) 560 560 Nominal Airflow (L/s) 4248 5663 Watts (Total) 970 1150 4 4 RTPF CONDENSER COIL (Qty) Material (Tube/Fin) Cu / Al 3/ --- in 8 Coil Type Rows/Fins per Meter (Fins/m) RTPF Cu / Al 3/ --- in 8 RTPF 1...670 2...670 4.4 4.6 Al / Al --- Novation --- 1...670 --- 4.6 --- High Cutout 4347 ± 70 4347 ± 70 Cut-in 3482 ±138 3482 ±138 Low Cutout 372 ± 21 372 ± 21 Cut-in 807 ± 34 807 ± 34 Qty...Suction 2...34.9 2...34.9 Qty...Liquid 2...12.7 2...12.7 Face Area (sq m total) NOVATION CONDENSER COIL Material (Tube/Fin) Coil Type Rows/Fins per Meter (Fins/m) Face Area (sq m total) CONTROLS Pressurestat Settings (kPa) PIPING CONNECTIONS (mm ODS) LEGEND RTPF — Round Tube/Plate Fin NEMA — National Electrical Manufacturers Association ODS — Outside Diameter Sweat (socket) ‡ † Unit is factory-supplied with partial charge only. Typical operating charge with 7.62 m of interconnecting piping. 9 38AU COMPRESSOR 1 2 3 8 A U Z A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 5 A 0 G 6 A 0 A 0 A 0 Model Type Packaging 38AU= Carrier Condensing Unit Puron® R--- 410A Refrigerant 1 = LTL 0 = Standard Type of Coil Z = Single Circuit, A/C Scroll Compressor D = Dual Circuit, A/C Scroll Compressor Electrical Options A = None C = Non-Fused Disconnect Service Options 0 = None 1 = Un-powered Convenience Outlet 2 = Powered Convenience Outlet Refrigerant Options A = None B = Low Ambient 38AU Nominal Tonnage 16 = 15 Tons 25 = 20 Tons Not Used A = Place Holder Not Used A = Not Used Base Unit Controls 0 = Electro-Mechanical Controls Not Used 0 = Not Used Design Rev A = Initial Release Voltage 1 = 575/3/60 5 = 208/230/3/60 6 = 460/3/60 Coil Options NOVATION™ (Size 16 only) G= Al/Al K = E-Coat Al/Al T = Al/Al with Hail Guard W= E-Coat Al/Al with Hail Guard RTPF (Sizes 16 & 25) A= Cu/Al B = Precoat (Cu/Al) C = E-Coat (Cu/Al) M = Cu/Al with Hail Guard N = Precoat (Cu/Al) with Hail Guard P = E-Coat (Cu/Al) with Hail Guard C10944 Fig. 3 - Model Number Nomenclature POSITION NUMBER TYPICAL 1 0 2 5 POSITION 1–2 3–4 5 6 – 10 3 1 4 0 5 U 6 1 7 2 8 3 9 4 10 5 DESIGNATES Week of manufacture (fiscal calendar) Year of manufacture ("10" = 2010) Manufacturing location (U = Monterrey, Mexico) Sequence number Fig. 4 - Serial Number Nomenclature 10 C101041 Matching 38AU Model To Evaporator Coil The Model 38AUZ is a single-circuit unit design, requiring one set of refrigeration piping. This model can be connected to an evaporator coil with one circuit or with two circuits (by manifolding the evaporator connections into a single piping system). The Model 38AUD is a dual-circuit unit design that requires two sets of refrigeration piping between the outdoor unit and the evaporator coil (or coils). This model can only be connected to an evaporator coil that has two refrigeration circuits (or to two separate evaporator coils). The Model 38AUD CANNOT be connected to a single-circuit evaporator coil. The Model 38AUD CANNOT be field-converted to a single-circuit design. Evaluate the path and required line length for interconnecting refrigeration piping, including suction riser requirements (outdoor unit above indoor unit), liquid line lift (outdoor unit below indoor unit) and hot gas bypass line. Relocate sections to minimize the length of interconnecting tubing. DO NOT BURY REFRIGERATION LINES. Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit. REAR: Min 18” (457 mm) requried for service RIGHT: Min 18” (457 mm) requried for service Evaporator Coil has Connect to Model Single Circuit 38AUZ ONLY 38AUZ Two Circuits Notes LEFT: Min 18” (457 mm) requried for service Manifold evaporator circuits into single piping system Note: Observe requirements for 39” (914 mm) operating clearance on either Left or Rear coil opening. Or 38AUD FRONT: 42” (1067 mm) Use two separate piping systems Before unpacking this new 38AU model, compare the evaporator coil design to the 38AU model. INSTALLATION . Jobsite Survey Complete the following checks before installation. 1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installation requirements. 2. Determine unit location (from project plans) or select unit location. 3. Check for possible overhead obstructions which may interfere with unit lifting or rigging. Step 1 — Plan for Unit Location Select a location for the unit and its support system (pad, rails or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 5. NOTE: Consider also the effect of adjacent units on airflow performance and control box safety clearance. Do not install the outdoor unit in an area where fresh air supply to the outdoor coil may be restricted or when recirculation from the condenser fan discharge is possible. Do not locate the unit in a well or next to high walls. C10201 Fig. 5 - Service Clearance Dimensional Drawing Step 2 — Complete Pre-Installation Checks Check Unit Electrical Characteristics: Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided. Un-- crate Unit: Remove unit packaging except for the top skid assembly, which should be left in place until after the unit is rigged into its final location. Inspect Shipment: File a claim with shipping company if the shipment is damaged or incomplete. Consider System Requirements: S Consult local building codes and National Electrical Code (NEC, U.S.A.) for special installation requirements. S Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit. See Fig.1 and Fig. 2 for unit dimensions and weight distribution data. S Locate the unit so that the outdoor coil (condenser) airflow is unrestricted on all sides and above. S The unit may be mounted on a level pad directly on the base channels or mounted on raised pads at support points. See Tables 1A through 2B for unit operating weights. See Fig. 1 and Fig. 2 for weight distribution based on recommended support points. NOTE: If vibration isolators are required for a particular installation, use the data in Fig. 1 and Fig. 2 to make the proper selection. 11 38AU Table 3 – Evaporator Coil Connections Step 3 — Prepare Unit Mounting Support Slab Mount — Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. Table 4 – Equivalent Lengths for Common Fittings (ft) 90° Std 90° Lrad 90° Street 45° Std 3/ Step 4 — Rig and Mount the Unit ! Raise from above to lift the unit from the rails or pad when unit is in its final position. After the unit is in position, remove all shipping materials and top crating. Step 5 — Complete Refrigerant Piping Connections IMPORTANT: Do not bury refrigerant piping underground. IMPORTANT: A refrigerant receiver is not provided with the unit. Do not install a receiver. Provide Safety Relief — If local codes dictate an additional safety relief device, purchase locally and install locally. Installation will require the recovery of the factory shipping charge before the factory tubing can be cut and the supplemental relief device is installed. Model 38AUD has two separate refrigeration systems. If required, each circuit will require a field-supplied/installed supplemental relief device. 38AU 8 1.3 0.8 2.2 0.6 1 2 1.4 0.9 2.3 0.7 1.1 5/ 8 1.6 1 2.5 0.8 1.3 4 1.8 1.2 2.9 0.9 1.5 7/ 8 2 1.4 3.2 0.9 1.6 11/8 2.6 1.7 4.1 1.3 2.1 13/ 3.3 2.3 5.6 1.7 3 15/8 4 2.6 6.3 2.1 3.4 21/8 5 3.3 8.2 2.6 4.5 8 Tees Nominal Tube OD Rigging: These units are designed for overhead rigging. Refer to the rigging label for preferred rigging method. Spreader bars are not required if top crating is left on the unit. All panels must be in place when rigging. As further protection for coil faces, plywood sheets may be placed against the sides of the unit, behind cables. Run cables to a central suspension point so that the angle from the horizontal is not less than 45 degrees. Raise and set the unit down carefully. If it is necessary to roll the unit into position, mount the unit on longitudinal rails, using a minimum of 3 rollers. Apply force to the rails, not the unit. If the unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to the unit. 45° Street 1/ 3/ CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not designed for handling by fork truck. Elbows Nominal Tube OD Straight-Thru Branch Flow No Reduct Reduce 25% Reduce 50% 3/ 8 2.6 0.8 1.1 1.3 1/ 2 2.7 0.9 1.2 1.4 5/ 8 3 1 1.4 1.6 3/ 4 3.5 1.2 1.7 1.8 7/ 8 4 1.4 1.9 2 11/ 8 5 1.7 2.3 2.6 13/8 7 2.3 3.1 3.3 8 2.6 3.7 4 10 3.3 4.7 5 15/ 8 21/8 Check 38AU Model with Evaporator Coil Connections — Confirm before installation of unit that the evaporator coil connections are consistent with this 38AU model. See Table 3 on page 11. Determine Refrigerant Line Sizes — Select the recommended line sizes for 38AUZ and 38AUD unit from the appropriate tables. Determine the linear length of interconnecting piping required between the outdoor unit and indoor unit (evaporator). Consider and identify also the arrangement of the tubing path (quantity and type of elbows in both lines), liquid line solenoid size, filter drier and any other refrigeration specialties located in the liquid line. Refer to the indoor unit installation instructions for additional details on refrigeration specialties devices. Determine equivalent line length adjustments for path and components and add to linear line lengths. See Table 4, Equivalent Lengths for Common Fittings, for usual fitting types. Also identify adjustments for refrigeration specialties. Refer to Part 3 of the Carrier System Design Manual for additional data and information on equivalent lengths. NOTE: Equivalent line lengths will vary based on tube diameter. Calculate equivalent line length for each pipe by adding equivalent length adjustments to linear lengths for each pipe. 12 Enter the appropriate table to select the recommended line sizes. Model: Line Sizes Table Quantity of Line Sets 38AUZ 5 1 38AUD 6 2 line tube size if necessary. If maximum available tube size cannot provide the required lift distance on this installation, relocate the outdoor unit to reduce the equivalent line length or the lift requirement. Suction Riser — A liquid lift condition exists when the outdoor unit is located below the indoor (evaporator) unit and liquid flows vertically up in a portion of the liquid line. The vertical column of liquid reduces the available state point subcooling at the evaporator coil’s thermal expansion valve. This effect reduces the length of liquid lift (feet of elevation) that a liquid line size can accommodate. Longer linear tube lengths will also reduce the amount of liquid lift possible. Check Tables 5 (38AUZ) and 6 (38AUD) for maximum liquid lift capabilities for line sizes. Reselect the liquid A suction riser condition exists when the outdoor unit is located above the indoor (evaporator) unit and suction vapor must flow vertically up to return to the compressor. Oil return is a concern when the suction tube size is too large to produce the minimum refrigerant velocity to ensure oil return at minimum load conditions. Check Table 7 for maximum suction tube size for 38AU units at minimum load conditions. Consider suction speed riser (reduced tube size for vertical segment only) or double suction riser arrangement if the recommended suction tube size does not provide necessary minimum flowrates for this riser. Table 5 – 38AUZ 16-25 Piping Recommendations (Single-Circuit Unit) R-410A Equivalent Length Ft 0-38 38-75 75-113 113-150 150-188 m 0-12 12-23 23-34 34-46 46-57 Ft 0-25 25-50 50-75 75-100 100-125 m 0-8 8-15 15-23 23-30 30-38 Liquid Line 5/ 5/ 5/ 5/ 5/ Max Lift 25 50 75 100 125 Suction Line 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 Novation 24.3 27.5 30.6 33.7 37.8 RTPF 42.7 45.9 49.0 52.1 56.2 Liquid Line 5/ 5/ 5/ 5/ 5/ Max Lift 25 Suction Line 1-1/8 Charge (lbs) 37.8 Linear Length Model 38AUZ*16 8 8 8 8 8 1-5/8 Charge (lbs) 38AUZ*25 8 1-3/8 8 8 50 71 1-3/8 1-3/8 40.8 44.6 1-5/8 8 8 77 63 1-5/8 1-5/8 47.8 51.1 Legend: Equivalent Length Equivalent tubing length, including effects of refrigeration specialties devices Linear Length Typical linear tubing length, (50% added to linear to define Equivalent Length for this table) Liquid Line Tubing size, inches OD. Max Lift Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop — S Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV S Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV Suction Line Tube size, inches OD Charge Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where applicable) NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local Carrier representative. 13 38AU Liquid Lift — Table 6 – 38AUD 16-25 Piping Recommendations (Two-Circuit Unit) NOTE: 38AUD requires TWO sets of refrigeration piping R-410A Equivalent Length Ft 0-38 38-75 75-113 113-150 150-188 m 0-12 12-23 23-34 34-46 46-57 Ft 0-25 25-50 50-75 75-100 100-125 m 0-8 8-15 15-23 23-30 30-38 Liquid Line 1/ 1/ 1/ 1/ 1/ Max Lift 25 50 75 100 125 Suction Line 7/ 8 11/8 11/8 11/8 11/8 Novation 11.7 13.8 15.7 17.6 19.6 RTPF 21.7 23.8 25.7 27.6 Liquid Line 1/ 1/ 1/ Max Lift 25 50 54 Suction Line 11/8 11/8 11/8 Charge (lbs) 1 2 19.3 18.3 21.0 20.3 23.0 22.0 Linear Length Model 38AUD*16 2 2 2 2 2 Charge ea. (lbs) 38AU 38AUD*25 2 2 2 5/ 8 75 26.0 25.0 1/ 2 29.6 5/ 8 1/ 2 60 99 46 11/8 13/8 13/8 25.9 24.9 29.7 28.7 28.0 27.0 5/ 8 95 32.7 31.7 Legend: Equivalent Length Equivalent tubing length, including effects of refrigeration specialties devices Linear Length Typical linear tubing length (50% added to linear to define Equivalent Length for this table) Liquid Line Tubing size, inches OD. Max Lift Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop — S Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV S Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV Suction Line Tube size, inches OD Charge Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where applicable) NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local Bryant representative. Table 7 – 38AU Maximum Suction Pipe Size Model: 38AUZ 38AUD Unit Size Maximum Tube Size 16 15/8 25 15/8 16 15/8 25 15/8 Vertical Separation (outdoor unit above indoor unit) – Vertical elevation difference of 200 ft (60 m) is permitted when the outdoor unit (38AUZ or 38AUD) is located above the indoor unit. Insulate Suction Lines — Apply closed-cell tubular insulation to all suction lines between evaporator coil connection and 38AU unit’s suction service valve. Hot Gas Bypass — Hot gas bypass, if used, should be introduced before the evaporator. (A bypass route that also bypasses the evaporator circuit may lead to oil trapping in the evaporator circuit during low load conditions and then to oil slugging as evaporator load increases.) Model 38AU units do not include a hot gas stub connection; a tee must be field-supplied and installed in the compressor discharge line. Run a 1/2-in OD line between outdoor unit and evaporator coil inlet. Install an Auxiliary Side Connector at the evaporator between TXV and distributor (follow instructions for the side connector part). Insulate the hot gas line. 38AUD: Generally only one hot gas bypass system will be applied on a two-circuit unit. Connect the hot gas bypass system to Circuit 1 (first-on/last-off, connected to the evaporator coil’s bottom circuit). 38AUD Piping Connections — The 38AUD’s two circuits are designated Circuit 1 and Circuit 2. Circuit 1 is controlled by the thermostat’s Y1 (or TC1) contact and will be the first circuit on and last circuit off. Circuit 2 is controlled by the thermostat’s Y2 (or TC2) contact and this circuit is always the “lag” circuit. See Fig. 6 for location of Circuit 1 and Circuit 2 service valves and field piping connections. Circuit 1 is on the left-hand side of the service valve compartment; Circuit 2 is on the right. When a single piece evaporator coil with two separate circuits is connected to a 38AUD, the lower coil circuit should be connected to the 38AUD’s Circuit 1 so that the evaporator’s lower coil segment is first-on/last-off (to avoid re-evaporation of condensate on dry lower coil segments). 14 38AU units include one (38AUZ) or two (38AUD) Puron-duty filter drier(s), shipped in cartons attached to the unit basepan. Remove the filter drier(s) and prepare to install in the liquid line(s) at the evaporator coil. Do not remove connection fitting plugs until ready to connect and braze the filter drier into the liquid line position. CKT 2 CKT 1 CKT 2 CKT 1 Circuit 2 Connections Circuit 1 Connections 1 C10355 2 38AU Fig. 6 - 38AUD Service Valve Locations Plan the Circuit 1 and Circuit 2 tubing segments carefully, mark each segment and check constantly as piping systems are assembled to avoid piping errors. 38AUD unit cannot be single-circuit/tandem system. field-piped as FIRST ON/LAST OFF = 2 VERTICAL INSTALLATION a Connecting 40RU to 38AUD: The 40RU fan coil in sizes 16, 25 and 28 is a face-split coil design that also has its circuits designated as 1 and 2. See Fig. 7. Note that the lower coil segment changes as the arrangement of the 40RU changes. In a vertical arrangement, the 40RU’s lower coil segment is segment 2; this segment should be connected to the 38AUD’s Circuit 1. In a horizontal arrangement, the 40RU’s lower segment is now segment 1; this segment should be connected to the 38AUD’s Circuit 1. 2 1 FIRST ON/LAST OF F = 1 HORIZONTAL INSTALLATIO N C10071 Fig. 7 - Typical Evaporator Coil Connections (40RU) Note that refrigerant suction piping should be insulated. 40RU Arrangement Cooling Stage 40RU Coil Segment Connect to 38AUD Vertical Y1 Y2 2 1 Circuit 1 Circuit 2 Horizontal Y1 Y2 1 2 Circuit 1 Circuit 2 Table 8 – Puron-duty Filter Drier(s) Every unit MUST have a filter drier in the liquid line. 38AUD models require two filter driers (one in each liquid line). Locate the filter drier(s) at the indoor unit, close to the evaporator coil’s thermal expansion valve (TXV) inlets. Qty 38AUZ*16 1 5/ 1 5/ 2 1/ 2 1/ 38AUZ*25 38AUD*16 Install Filter Drier(s) and Moisture Indicator(s) — Liquid Line OD Model-Size 38AUD*25 Desiccant Volume Part Number Ref 8-in 30 cu. in. KH43LG087 8-in 30 cu. in. KH43LG087 2-in 16 cu. in. KH43LG085 2-in 16 cu. in. KH43LG085 Installation of liquid line moisture indicating sightglass in each circuit is recommended. Locate the sightglass(es) between the outlet of the filter drier and the TXV inlet. Refer to Table 9 for recommendations on refrigeration specialties. Table 9 – Refrigerant Specialties Part Numbers. LIQUID LINE SIZE (in.) LIQUID LINE SOLENOID VALVE (LLSV) LLSV COIL SIGHT GLASS 1/ 2 EF680035 EF680037 KM680004 5/ 8 EF680036 EF680037 KM680005 38AUD units require TWO sets of parts. 15 FILTER DRIER provided with unit see Table 8 INDOOR COIL CKT AIRFLOW 15 DIAMS MIN from the indoor unit to the outdoor unit before opening the liquid and suction lines at the outdoor unit. EQUALIZER LINE TXV SENSING BULB SIGHT GLASS A LOCATION FILTER DRIER A LOCATION Install Liquid Line Solenoid Valve — TXV 10 DIAMS 8 DIAMS MIN FLO W LIQUID LINE SOLENOID VALVE Single Circuit Coil Piping Configuration For single compressor condensing units INDOOR COIL CKT 2 38AU AIRFLOW INDOOR COIL CKT 1 AIRFLOW EQUALIZER LINE TXV SENSING BULB 15 DIAMS MIN 10 DIAMS 8 DIAMS MIN SIGHT GLASSES B LOCATION TXV SENSING BULB 15 DIAMS MIN SIGHT GLASS A LOCATION TXV CKT 2 FLO W FILTER DRIERS B LOCATION 10 DIAMS FILTER DRIER A LOCATION LIQUID LINE SOLENOID VALVE TXV CKT 1 8 DIAMS MIN It is recommended that a solenoid valve be placed in the main liquid line (see Figs. 8 & 9) between the condensing unit and the evaporator coil. Locate the solenoid valve at the outlet end of the liquid line, near the evaporator coil connections, with flow direction arrow pointed at the evaporator coil. Refer to Table 9. (A liquid line solenoid valve is required when the liquid line length exceeds 75 ft [23 m].) This valve prevents refrigerant migration (which causes oil dilution) to the compressor during the off cycle, at low outdoor ambient temperatures. Wire the solenoid in parallel with the compressor contactor coil (see Figs. 8 & 9). This means of electrical control is referred to as solenoid drop control. Solenoid drop control wiring: Control the power to the liquid line solenoid through a Solenoid Valve Relay (SVR) in all units. Use part number HN61PC005 (field--supplied, installed). 38AUZ unit requires one SVR; 38AUD unit requires two relays. 38AUD unit also requires a separate control power transformer for the liquid solenoid valve loads. Select transformer part number according to unit power supply. Dual Circuit Coil Piping Configuration For single compressor condensing units C10202 Fig. 8 - Location of Sight Glass(es) and Filter Driers Typical 38AUZ Systems TXV CKT 2 8 DIAMS MIN TXV SENSING BULB AIRFLOW 15 DIAMS MIN 10 DIAMS FLO W SIGHT GLASSES FILTER DRIERS LIQUID LINE SOLENOID VALVE CIRCUIT 2 TXV CKT 1 8 DIAMS MIN SUCTION CIRCUIT 2 208/230 HT01BD202 460 HT01BD702 575 HT01BD902 Mount the SVR (and transformer TRAN3 when used) in unit control box. Connect per wiring schematic label on unit or per Fig. 29 (38AUZ) or Fig. 30 (38AUD). AIRFLOW 10 DIAMS Transformer Part # EQUALIZER LINE TXV SENSING BULB 15 DIAMS MIN Unit Power FLO W LIQUID LINE SOLENOID VALVE CIRCUIT 1 SUCTION CIRCUIT 1 Dual Circuit Coil Piping Configuration For two circuit condensing units C10072 Fig. 9 - Location of Sight Glasses and Filter Driers Typical 38AUD Systems In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses in a single circuit application. One filter drier and sight glass may be installed at A locations (see Fig. 8) or 2 filter driers and sight glasses may be installed at B locations (see Figs. 8 and 9). Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping Capacity Control Liquid Line Solenoid Valve: Evaporator capacity staging control via direct thermostat control of a liquid solenoid valve on the evaporator’s second stage circuit is not possible with 38AU models. If this installation is a retrofit for a unit that included automatic pressure-- operated unloading, check the existing thermostat and liquid solenoid valve wiring for possible direct thermostat control of a solenoid valve; re-- wire per Figs. 17 or 18 and 29 or 30. Selecting an Accumulator – Because all 38AU models use scroll compressors, an accumulator is not required. If an accumulator is to be added, check the accumulator manufacturer’s literature carefully for indication of its suitability for use with R--410A; look for minimum working pressure of 200 psig (1380 kPa). Select the accumulator first on the basis of its cataloged minimum capacity (tons) to ensure oil return from the accumulator, then on tube size or holding capacity. Make Piping Connections — Piping connections at the 38AU unit are ball valves with stub tube extensions. Do not open the unit service valves until all interconnecting tube brazing has been completed. 16 Field Service Access Port (Schrader core) Factory High-Flow Access Port Service Valve with Stem Cap Sweat Connection C10203 Fig. 10 - Typical Piping Connection Assembly When connecting the field tubing to the 38AU service valves, wrap the valves in wet rags to prevent overheating Pressure-test all joints from outdoor unit connections over to the evaporator coil, using nitrogen as pressure and with soap-and-bubbles. When pressure-testing is completed, remove the nitrogen source at the outdoor unit service valves and re-install the two Schrader valve cores. Torque the cores to 2-3 in-lbs (23-34 N-cm). Evacuation/Dehydration — Evacuate and dehydrate the connected refrigeration system(s) (excluding the 38AU unit) to 500 microns using a two-stage vacuum pump attached to the service ports outside the 38AU service valves, following description in GTAC II, Module 4, System Dehydration. ! WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. PuronR (R-- 410A) refrigerant systems operate at higher pressure than standard R-- 22 systems. Do not use R-- 22 service equipment or components on Puron refrigerant equipment. This unit is designed for use with Puron (R-- 410A) refrigerant. Do not use any other refrigerant in this system. Puron (R-- 410A) refrigerant is provided in pink (rose) colored cylinders. These cylinders are available with and without dip tubes; cylinders with dip tubes will have a label indicating this feature. For a cylinder with a dip tube, place the cylinder in the upright position (access valve at the top) when removing liquid refrigerant for charging. For a cylinder without a dip tube, invert the cylinder (access valve on the bottom) when removing liquid refrigerant. Because Puron (R-- 410A) refrigerant is a blend, it is strongly recommended that refrigerant always be removed from the cylinder as a liquid. Admit liquid refrigerant into the system in the discharge line. If adding refrigerant into the suction line, use a commercial metering/expansion device at the gauge manifold; remove liquid from the cylinder, pass it through the metering device at the gauge set and then pass it into the suction line as a vapor. Do not remove Puron (R–410A) refrigerant from the cylinder as a vapor. Preliminary Charge — Before starting the unit, charge R-410A liquid refrigerant into the high side of each 38AU circuit through the liquid service valve(s). The amount of refrigerant added must be at least 80% of the operating charge listed in Tables 5 or 6 for LINEAR line length LESS the factory charge quantity (if factory shipping charge has not been removed). See example below. Allow high and low side pressures to equalize. If pressures do not equalize readily, charge R-410A vapor (using special service manifold with expansion device) into the suction line service port for the low side of system to assure charge in the evaporator. Refer to GTAC II, Module 5, Charging, Recover, Recycling, and Reclamation for liquid charging procedures. Example: 38AUD*25 (RTPF) 60-ft (18.3 m) linear line length Equivalent line length 90-ft (27.4 m) Liquid Lift: 20-ft (6.1 m) Select line sizes from Table 6 (38AUD): Liquid 1/2 in Suction 1-1/8 in. Charge Circuit 1: 23.0 lbs (at 75-ft linear length) Circuit 2: 22.0 lbs 80% of Operating Charge: Circuit 1: 0.80 x 23.0 = 18.4 lbs Circuit 2: 0.80 x 22.0 = 17.6 lbs Factory Shipping Charge: 15 lbs Field-Charge Circuit 1: 18.4 - 15 = 3.4 lbs Circuit 2: 17.6 - 15 = 2.6 lbs For linear line lengths longer than 125 ft (38 m), contact your local Carrier representative for system charge value. Step 6 — Install Accessories Accessories requiring modifications to unit wiring should be completed now. These accessories may include Winter Start controls and Low Ambient controls. Refer to the instructions shipped with the accessory. 17 38AU The stub tube connections include 1/4-in SAE service fittings with Schrader valve cores (see Fig. 10). Before making any brazed connections to the unit service valves, remove both Schrader valve caps and cores and save for re-installation. Connect a source for nitrogen to one of these service fittings during tube brazing to prevent the formation of copper oxides inside the tubes at brazed joints. Step 7 — Complete Electrical Connections 38AU ! ! WARNING WARNING FIRE HAZARD Failure to follow this warning could cause in personal injury, death and/or equipment damage. Do not connect aluminum wire between disconnect switch and condensing unit. Use only copper wire. (See Fig. 11.) ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes. ELECTRIC DISCONNECT SWITCH COPPER WIRE ONLY ALUMINUM WIRE NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63°F (33°C) rise. Fig. 11 - Disconnect Switch and Unit Field Power Supply — A93033 If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads.. Units Without Factory-Installed Disconnect — Field power wires are connected to the unit at line-side pressure lugs on compressor contactor C and TB1 (see wiring diagram label for control box component arrangement) or at factory-installed option non-fused disconnect switch. Max wire size is #4 AWG (copper only). All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 12 for power wiring connections to the unit contactor and terminal block and equipment ground. NOTE: TEST LEADS - Unit may be equipped with short leads (pigtails) on the field line connection points on contactor C or optional disconnect switch. These leads are for factory run-test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line connection pressure lugs only. When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet. Units with Factory-Installed Disconnect — The factory-installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel. All Units — Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size. All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4 -in. female spade connector from the 230-v connection and moving it to the 208-v 1/4 -in. male terminal on the primary side of the transformer. Refer to unit label diagram for line-side information. 18 and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 13. Units Without Disconnect Option C 11 TB1 13 Convenience Outlet GFCI Disconnect per NEC L1 Pwd-CO Fuse Switch L2 L3 208/230-3-60 460-3-60 575-3-60 Pwd-CO Transformer Units With Disconnect Option 2 L2 4 L3 6 1 Optional Disconnect Switch 3 5 Fig. 13 - Convenience Outlet Location Disconnect factory test leads; discard. Fig. 12 - Power Wiring Connections C10204 Affix the crankcase heater warning sticker to the unit disconnect switch. Convenience Outlets — ! Control Box Access Panel Factory Wiring WARNING C10205 The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit-mounted non-fused disconnect switch; this will provide service power to the unit when the unit disconnect switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect is open. See Fig. 14. ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-out this switch, if necessary. Two types of convenience outlets are offered on 38AU models: Non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 13. C10206 Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle. Unit-powered type: A unit-mounted transformer is factory-installed to stepdown the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box UNIT VOLTAGE CONNECT AS 208, 230 240 460 575 PRIMARY CONNECTIONS TRANSFORMER TERMINALS L1: RED + YEL L2: BLU + GRA H1 + H3 H2 + H4 480 L1: RED Splice BLU + YEL L2: GRA H1 H2 + H3 H4 600 L1: RED L2: GRA H1 H2 Fig. 14 - Powered Convenience Outlet Wiring The unit-powered convenience outlet has a 1000 VA rated transformer. Maximum continuous current must not exceed 8 Amps. 19 38AU L1 NOTICE Convenience Outlet Utilization Maximum Continuous use : 8 Amps 24/7 50HJ542739 B C10207 Fig. 15 - Convenience Outlet Utilization Notice Label 38AU Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition. Fuse on power type: The factory fuse is a Bussman “Fusetron” T-15, non-renewable screw-in (Edison base) type plug fuse. ! WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Using unit-mounted convenience outlets: Units with unit-mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets. Installing Weatherproof Cover: A weatherproof while in use cover for the factory installed convenience outlets is now required by UL standards. This cover cannot be factory mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate. The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket. DISCONNECT ALL POWER CONVENIENCE OUTLET. TO UNIT AND Remove the blank cover plate at the convenience outlet; discard the blank cover. Loosen the two screws at the GFCI duplex outlet, until approximately 1/2--in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not overtighten). Fig. 16 - Weatherproof Cover Installation C09022 All Units — Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Tables 10 and 11. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Tables 10 and 11, Note 5 (see page 22) to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty. Field Control Wiring — 38AU unit control voltage is 24 v. See Fig. 29 (38AUZ) and Fig. 30 (38AUD) for typical field control connections and the unit’s label diagram for field-supplied wiring details. Route control wires to the 38AU unit through the opening in unit’s end panel to the connections terminal board in the unit’s control box. Remainder of the system controls connection will vary according to the specific construction details of the indoor section (air handler or packaged fan coil). Fig. 17 (38AUZ) and Fig. 18 (38AUD) depict typical connections to a Carrier 40RU fan coil unit. Plan for field connections carefully and install control wiring correctly per the project plan. Additional components and supplemental transformer accessory may be required. The 38AU unit requires an external temperature control device. This device can be a thermostat (field-supplied) or a PremierLink controller (available as a field-installed accessory, for use on a Carrier Comfort Network or as a stand alone control). Mount the weatherproof cover to the backing plate as shown in Fig. 16. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching. 20 Thermostat — Install a Carrier-approved accessory thermostat according to installation instructions included with the accessory. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions. The 38AUD is a dual-- circuit, two-stage cooling unit. Select a two—stage cooling thermostat, with or without supplemental heating as needed. Select a thermostat cable or equivalent single leads of different colors with minimum of five leads for 38AUZ or six leads for 38AUD unit. Check the thermostat installation instructions for additional features which might require additional conductors in the cable. For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire (35 C minimum). For over 75 ft. (23 m), use no. 14 AWG insulated wire (35 C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. PremierLink (accessory installation) – Refer to Form 33CS-58SI for details on connecting the PremierLink controller and its various sensors. (Note 1) (Note 3) (Note 3) (Note 2) 38AU The 38AUZ is a single-circuit, two-- stage cooling unit. Select a two—stage cooling thermostat, with or without supplemental heating as needed. Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2. Note 2: Connect only if thermostat requires 24-vac power source. Note 3: Connect W1 and W2 if supplemental heaters are installed Field Wiring C10078 Fig. 18 - Typical Remote Thermostat Connections — 38AUD Control Circuit Wiring — Control voltage is 24 v. See Fig. 12 and the unit’s label diagram for field-- supplied wiring details. Route control wires through the opening in unit’s end panel to the connection in the unit’s control box. Control Transformer Wiring — On multi voltage units, check the transformer primary wiring connections. See Fig. 19 or refer to the unit’s label diagram. (Note 1) (Note 3) If the unit will be operating at 208-3-60 power, remove the black wire (BLK) from the transformer primary connection labelled “230” and move it to the connection labelled “208”. See Fig. 19. (Note 3) (Note 2) Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2. Note 2: Connect only if thermostat requires 24-vac power source. Note 3: Connect W1 and W2 if supplemental heaters are installed Field Wiring C10208 Fig. 17 - Typical Remote Thermostat Connections — 38AUZ Fig. 19 - Control Transformer Wiring 21 C10079 Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data UNIT SIZE 38AU D*16 Z*16 38AU D*25 Z*25 UNIT SIZE 38AU D*16 Z*16 D*25 Z*25 NOMINAL POWER SUPPLY COMPRESSOR VOLTAGE RANGE No. 1 No. 2 OFM POWER SUPPLY DISCONNECT SIZE V--- Ph--- Hz Min Max RLA LRA RLA LRA Qty FLA (ea) MCA FUSE or HACR BRKR 208/230---3---60 187 253 25.0 164 25.0 164 3 1.5 60.8/60.8 80/80 63/63 337/337 460 ---3 ---60 414 506 12.2 100 12.2 100 3 0.8 29.9 40 31 206 575 ---3 ---60 518 633 9.0 78 9.0 78 3 0.7 22.4 30 23 162 208/230---3---60 187 253 30.1 225 30.1 225 4 1.5 73.7/73.7 100/100 76/76 462/462 460 ---3 ---60 414 506 16.7 114 16.7 114 4 0.8 40.8 50 42 236 575 ---3 ---60 518 633 12.2 80 12.2 80 4 0.7 30.3 40 31 168 NOMINAL POWER SUPPLY COMPRESSOR VOLTAGE RANGE No. 1 FLA LRA w/ PWRD C.O. No. 2 OFM POWER SUPPLY DISCONNECT SIZE V--- Ph--- Hz Min Max RLA LRA RLA LRA Qty FLA (ea) MCA FUSE or HACR BRKR FLA LRA 208/230---3---60 187 253 25.0 164 25.0 164 3 1.5 65.6/65.6 90/90 68/68 342/342 460 ---3 ---60 414 506 12.2 100 12.2 100 3 0.8 32.1 40 33 208 575 ---3 ---60 518 633 9.0 78 9.0 78 3 0.7 24.1 30 25 164 208/230---3---60 187 253 30.1 225 30.1 225 4 1.5 78.5/78.5 100/100 82/82 467/467 460 ---3 ---60 414 506 16.7 114 16.7 114 4 0.8 43 50 45 238 575 ---3 ---60 518 633 12.2 80 12.2 80 4 0.7 32 40 33 170 Legend and Notes for Table 10 LEGEND: BRKR CO FLA LRA MCA NO C.O. or UNPWRD C.O. ----------- Circuit breaker Convenient outlet Full Load Amps Locked Rotor Amps Minimum Circuit Amps Protection National Electrical Code Powered convenient outlet Rated Load Amps Unpowered convenient outlet NEC --PWRD CO --RLA --UNPWR CO --NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. The MCA values are calculated in accordance with The NEC. Article 440. 3. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL). Standard 1995. 4. The 575--- v units are UL, Canada--- listed only. 5. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. Example: Supply voltage is 230-3-60 % Voltage Imbalance = 100 x max voltage deviation from average voltage average voltage AB = 224 v BC = 231 v AC = 226 v Average Voltage = = (224 + 231 + 226) 3 = 681 3 227 Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 4 227 = 1.76% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 22 PRE-START-UP ! IMPORTANT: Before beginning Pre-Start-Up or Start-Up, review Start-Up Checklist at the back of this book. The Checklist assures proper start-up of a unit and provides a record of unit condition, application requirements, system information, and operation at initial start-up. UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. Prior to starting compressor, a preliminary charge of refrigerant must be added to avoid possible compressor damage. CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. Do not attempt to start the condensing unit, even momentarily, until the following steps have been completed. Compressor damage may result. System Check 1. The electrical power source must agree with the unit’s nameplate rating. 2. Check all air handler(s) and other equipment auxiliary components. Consult the manufacturer’s instructions regarding any other equipment connected to the condensing unit. If the unit has field-installed accessories, be sure all are properly installed and correctly wired. If used, the airflow switch must be properly installed. 3. Check tightness of all electrical connections. 4. Be sure liquid line and low side of the system are properly leak checked and dehydrated. 5. Be sure the unit is properly charged. See “Preliminary Charge”, below. 6. Open the liquid line and suction line service valves. 7. The crankcase heater must be firmly attached to the compressor crankcase. Be sure the crankcase is warm (heater must be on for 24 hours before starting compressor). Turn On Crankcase Heater — Turn on the crankcase heater for 24 hours before starting the unit to be sure all the refrigerant is out of the oil. To energize the crankcase heater, proceed as follows: 1. Set the space thermostat set point above the space temperature so there is no demand for cooling. 2. Close the field disconnect. START-UP 38AU Units: The compressor crankcase heater must be on for 24 hours before start-up. After the heater has been on for 24 hours, the unit can be started. If no time elapsed since the preliminary charge step was completed, it is unnecessary to wait the 24-hour period. Preliminary Checks 1. Check that electric power supply agrees with unit nameplate data. 2. Verify that the compressor crankcase heater is securely in place. 3. Check that the compressor crankcase heater has been on at least 24 hours. 4. Recheck for leaks using the procedure outlined in the Pre-Start-Up section, Leak Test and Dehydration. If any leaks are detected, repair as required. Evacuate and dehydrate as described in the Leak Test and Dehydration section. 5. Ensure that the preliminary charge has been added as described in the Pre-Start-Up section, Preliminary Charge. 6. All internal wiring connections must be tight, and all barriers and covers must be in place. NOTE: The 38AU units are factory charged with the required amount of oil. If recharging in required, use Emkarate RL 32-3MAF for the 38AU units. Compressor Rotation — On 3--phase units with scroll compressors, it is important to be certain that the compressor is rotating in the proper direction. 38AU units are equipped with a Comfort Alert Diagnostic Module (CADM). Alert Code 7 indicates reverse power phasing. To correct phase order: 1. Turn off power to the unit, tag disconnect. 2. Reverse any two of the unit power leads. 3. Reapply power to the compressor, verify correct pressures. Preliminary Charge — Before starting the unit, charge liquid refrigerant into the high side of the system through the liquid service valve. The amount of refrigerant added must be at least 80% of the operating charge listed in the Physical Data table (Tables 1A through 2B, pages 6 through 9). Allow high and low side pressures to equalize before starting compressor. If pressures do not equalize readily, charge vapor on low side of system to assure charge in the evaporator. Refer to GTAC II, Module 5, Charging, Recover, Recycling, and Reclamation for liquid charging procedures. To verify the compressor is rotating in the proper direction: 1. Connect service gages to the suction and liquid pressure fittings. 2. Energize the compressor. 3. The suction pressure should drop and the liquid pressure should rise, as is normal on any start-- up. 23 38AU ! CAUTION Compressor Overload — Start Unit This overload interrupts power to the compressor when either the current or internal motor winding temperature becomes excessive, and automatically resets when the internal temperature drops to a safe level. This overload may require up to 60 minutes (or longer) to reset. If the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit through the overload with an ohmmeter or continuity tester. Set the space thermostat to a set point above space temperature so that there is no demand for cooling. Close the 38AU disconnect switch. Only the crankcase heater will be energized. Reset the space thermostat below ambient so that a call for cooling is ensured. ! A label located above the terminal box identifies Copeland Scroll compressor models that contain this technology. See Fig. 20. Advanced Scroll Temperature Protection (ASTP) is a form of internal discharge temperature protection, that unloads the scroll compressor when the internal temperature reaches approximately 149_C (300_F). At this temperature, an internal bi--metal disk valve opens and causes the scroll elements to separate, which stops compression. Suction and discharge pressures balance while the motor continues to run. The longer the compressor runs unloaded, the longer it must cool before the bi--metal disk resets. See Fig. 21. C10080 Fig. 20 - Advanced Scroll Temperature Protection Label Recommended Cooling Time* (Minutes) 38AU Advanced Scroll Temperature Protection (ASTP) — 120 110 100 90 80 70 60 50 40 30 20 10 0 CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. Never charge liquid into the low-pressure side of system. Do not overcharge. During charging or removal of refrigerant, be sure indoor-fan system is operating. Ensure both outdoor fan motors are running; bypass any Motormaster function. Adjust Refrigerant Charge — Refer to Cooling Charging Charts, Fig. 23 through Fig. 28. For applications with line lengths greater than 125 ft (38 m), contact Carrier representative. Vary refrigerant until the conditions of the chart are met. Note that the charging charts are different from the type normally used. The charts are based on charging the units to the correct subcooling for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the liquid line service valve. Mount the temperature sensing device on the liquid line close to the liquid line service valve, and insulate it so that outdoor ambient temperature does not affect the reading. Indoor airflow must be within the unit’s normal operating range. Operate the unit for a minimum of 15 minutes. Ensure that pressure and temperature readings have stabilized. Plot the liquid pressure and temperature on chart and add or reduce the charge to meet the curve. Adjust the charge to conform with the charging chart, using the liquid pressure and temperature to read the chart. Using plotted operating point: 0 10 20 30 40 50 60 70 80 90 Compressor Unloaded Run Time (Minutes)* *Times are approximate. NOTE: Various factors, including high humidity, high ambient temperature, and the presence of a sound blanket will increase cool-down times. C10081 Fig. 21 - Recommended Minimum Cool-Down Time After Compressor is Stopped To manually reset ASTP, the compressor should be stopped and allowed to cool. If the compressor is not stopped, the motor will run until the motor protector trips, which occurs up to 90 minutes later. Advanced Scroll Temperature Protection will reset automatically before the motor protector resets, which may take up to 2 hours. 24 If plotted operating condition is - Adjust charge by - BELOW the curve REDUCE charge ABOVE the curve ADD charge 38AUZ*25 Check Compressor Oil Level — After adjusting the refrigerant charge, allow the unit to run fully loaded for 20 minutes. Stop the compressors and check the oil level. Oil level should be 1/3 to 1/2 up on the sight glass (see Fig. 22). 1/2 1/3 (MAX) (MIN) IMPORTANT: Oil level should only be checked when the compressors are off. Add oil only if necessary to bring the oil into view in the sight glass. If oil is added, run the circuit for an additional 10 minutes, then stop and check oil level. If the level remains low, check the piping system for proper design for oil return; also, check the system for leaks. If checking the oil level with unit running in part load, let unit run one hour, then run at full load for 10 minutes. If oil does not return to acceptable sight glass levels, check for correct suction piping and line sizing. Final Checks — Ensure that all safety controls are operating, control panel covers are on, and the service panels are in place. C01377 38AU Fig. 22 - Recommended Oil Level — 38AUZ*25 Fig. 23 - 38AUZ*16 Charging Chart (Novation) 25 C10945 38AU (CIRCUIT 1) (CIRCUIT 2) Fig. 24 - 38AUD*16 Charging Chart (Novation) 26 C10946 38AU Fig. 25 - 38AUZ*16 Charging Chart (RTPF) Fig. 26 - 38AUZ*25 Charging Chart (RTPF) 27 C10947 C10948 38AU Fig. 27 - 38AUD*16 Charging Chart (RTPF) 28 C10949 38AU (CIRCUIT 1) (CIRCUIT 2) Fig. 28 - 38AUD*25 Charging Chart (RTPF) 29 C10950 38AU Fig. 29 - Typical 38AUZ Wiring Diagram - (15 Ton 230V Tandem Unit Shown) 30 C10212A 38AU Fig. 30 - Typical 38AUD Wiring Diagram - (15 Ton 230V Dual Unit Shown) 31 C10213A OPERATING SEQUENCE Base Unit Controls Indoor (Supply) Fan — The indoor fan contactor (IFC) is remotely located at the fan coil or fan section. If the thermostat fan operation is selected as Continuous, the IFC is energized and the indoor (supply) fan motor runs continuously. If the thermostat fan operation is selected as Automatic, the IFC will be energized on a call for Cooling; indoor (supply) fan motor runs. When thermostat call for Cooling is satisfied, the IFC is de-energized and indoor (supply) fan motor stops. Cooling, Unit Without Economizer — 38AU 38AUZ (Single Circuit) On a thermostat call for Cooling, IFC will be energized and indoor (supply) fan motor runs. Thermostat output Y1 is energized; terminal Y1 at 38AUZ unit receives 24-v. 24-v received at CADM1 terminal Y. If anti-recycle time delay period has not expired, CADM1 relay will remain open, de-energizing Solenoid Valve Relay (SVR) and preventing compressor start. When safety pressure switches are closed and CADM1 time delay expires, CADM1 relay closes, SVR and compressor contactor C1 are energized; liquid line solenoid valve LLSV opens, all outdoor fan motors start and Compressor 1 starts. On a thermostat calling for Stage 2 Cooling, thermostat output Y2 is energized; terminal Y2 at 38AUZ unit receives 24-v. 24-v received at CADM2 terminal Y. If anti-recycle time delay period has not expired, CADM2 relay will remain open, preventing Compressor 2 start. When safety pressure switches are closed and CADM2 time delay expires, CADM2 relay closes, compressor contactor C2 is energized; Compressor 2 starts. As space cooling load is satisfied, thermostat outputs Y2 and Y1 are de-- energized, removing 24-v at 38AUZ terminals Y2 and Y1. Compressor 2 stops on Y2 opening. CADM2 begins its three-minute anti-recycle time delay. On Y1 opening, Compressor 1 stops, all outdoor fan motors stop and SVR relay is de-energized. Liquid line solenoid valve is de-energized and valve closes. CADM1 begins its three-minute anti-recycle time delay. 38AUD (Two Circuit) On a thermostat call for Cooling, IFC will be energized and indoor (supply) fan motor runs. Thermostat output Y1 is energized; terminal Y1 at 38AUD unit receives 24-v. 24-v received at CADM1 terminal Y. If anti-recycle time delay period has not expired, CADM1 relay will remain open, de-energizing Solenoid Valve Relay 1 (SVR1) and preventing compressor start. When safety pressure switches are closed and CADM1 time delay expires, CADM1 relay closes, SVR1 and compressor contactor C1 are energized; liquid line solenoid valve LLSV1 opens, all outdoor fan motors start and Circuit 1 compressor starts. On a thermostat calling for Stage 2 Cooling, thermostat output Y2 is energized; terminal Y2 at 38AUD unit receives 24-v. 24-v received at CADM2 terminal Y. If anti-recycle time delay period has not expired, CADM2 relay will remain open, de-energizing Solenoid Valve Relay 2 (SVR2) and preventing compressor start. When safety pressure switches are closed and CADM2 time delay expires, CADM2 relay closes, SVR2 and compressor contactor C2 are energized; liquid line solenoid valve LLSV2 opens and Circuit 2 compressor starts. As space cooling load is satisfied, thermostat outputs Y2 and Y1 are de-- energized, removing 24-v at 38AUD terminals Y2 and Y1. Circuit 2 compressor stops on Y2 opening; SVR2 is de-energized and LLSV2 closes. CADM2 begins its three-minute anti-recycle time delay. On Y1 opening, Circuit 1 compressor stops, all outdoor fan motors stop and SVR1 relay is de-energized. Liquid line solenoid valve LLSV1 is de-energized and valve closes. CADM1 begins its three-minute anti-recycle time delay. All Units If either the Low Pressure Switch or High Pressure Switch opens while thermostat output Y1 or Y2 remain energized, the compressor contactor is de-energized, the compressor stops and liquid line solenoid is de-energized (valve closes). CADM initiates a TRIP event (cooling demand sensed at CADM terminal Y but no current is measured at T1, T2, T3 motor sensors); CADM relay opens and RED LED is illuminated. TRIP condition maintains lockout of compressor operation until CADM is manually reset. Reset CADM by cycling unit main power. Complete system shutdown may be caused by loss of main power, open compressor internal overload, open low-pressure or high-pressure switch, or a fault detected by the CADM logic. Compressor operation without cooling may indicate the compressor’s ASTP feature is active; disconnect unit power and allow compressor to cool. See Service section for further details. Cooling, Unit With Economizer — Refer to fan coil unit installation instructions and economizer accessory installation instructions for operating sequences when system is equipped with accessory economizer. Heating — Refer to fan coil unit installation instructions and accessory heating device installation instructions for operating sequences in heating mode. 32 ROUTINE SYSTEM MAINTENANCE Refrigeration System ! Quarterly Inspection (and 30 days after initial start) — EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in damage to equipment. This system uses PuronR refrigerant which has higher pressures than R-22 and other refrigerants. No other refrigerant may be used in this system. Gage set, hoses, and recovery system must be designed to handle Puron. If you are unsure consult the equipment manufacturer. Indoor section S Condenser coil cleanliness checked. S Return air filter replacement S Outdoor hood inlet filters cleaned S Belt tension checked S Belt condition checked S Pulley alignment checked S Fan shaft bearing locking collar tightness checked CAUTION Compressor Oil — S Condensate drain checked ! Seasonal Maintenance — CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in damage to equipment. The compressor in a Puron system uses a polyolester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere. These items should be checked at the beginning of each season (or more often if local conditions and usage patterns dictate): Air Conditioning S Condenser fan motor mounting bolts tightness S Compressor mounting bolts S Condenser fan blade positioning S Control box cleanliness and wiring condition S Wire terminal tightness S Refrigerant charge level Servicing Systems on Roofs With Synthetic Materials — Economizer or Outside Air Damper POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials. Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service which may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include but are not limited to compressor replacement, repairing refrigerants leaks, replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve. S Inlet filters condition Synthetic Roof Precautionary Procedure: S Evaporator coil cleaning S Evaporator blower motor amperage Heating S Power wire connections S Fuses ready S Manual-reset limit switch is closed S Check damper travel (economizer) 1. Cover extended roof working area with an impermeable polyethylene (plastic) drop cloth or tarp. Cover an approximate 10 x 10 ft (3.3 x 3.3 m) area. 2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent run-offs, and protect drop cloth from tears caused by tools or components. 3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run-offs through the louvered openings in the base pan. 4. Perform required service. 5. Remove and dispose of any oil contaminated material per local codes. S Check gear and dampers for debris and dirt 33 38AU These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation: SERVICE Liquid Line Filter Drier — Factory High-Flow Access Ports — The factory-provided filter drier is specifically designed to operate with Puron®. Replace the filter drier with factory-authorized components only with a filter drier with desiccant made from 100% molecular sieve grade XH-11. Filter drier must be replaced whenever the refrigerant system is opened. There are two additional access ports in the system - on the suction tube between the compressor and the suction service valve and on the liquid tube near the liquid service valve (see Figs 35 and 39). These are brass fittings with black plastic caps. The hose connection fittings are standard 1/4-in SAE Male Flare couplings. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system. The brass fittings are two-piece High Flow valves, with a receptacle base brazed to the tubing and an integral spring-closed check valve core screwed into the base. (See Fig. 31) This check valve is permanently assembled into this core body and cannot be serviced separately; replace the entire core body if necessary. Service tools are available from RCD that allow the replacement of the check valve core without having to recover the entire system refrigerant charge. Apply compressor refrigerant oil to the check valve core’s bottom o-ring. Install the fitting body with 96 ±-10 in-lbs (1085 ±23 N-cm) of torque; do not overtighten. 38AU Field Refrigerant Access Ports — Field service access to refrigerant pressures is through the access ports located at the service valves (see Figs 34 and 38). These ports are 1/4-in SAE Flare couplings with Schrader check valves and service caps. Use these ports to admit nitrogen to the field tubing during brazing, to evacuate the tubing and evaporator coil, to admit initial refrigerant charge into the low-side of the system and when checking and adjusting the system refrigerant charge. When service activities are completed, ensure the service caps are in place and secure; check for leaks. If the Schrader check valve must be removed and re-installed, tighten to 2-3 in-lbs (23-34 N-cm). SEAT CORE (Part No. EC39EZ067) 1/2-20 UNF RH 0.596 45° 30° WASHER O-RING 5/8” HEX .47 1/2" HEX This surface provides a metal to metal seal when torqued into the seat. Appropriate handling is required to not scratch or dent the surface. DEPRESSOR PER ARI 720 +.01/-.035 FROM FACE OF BODY 7/16-20 UNF RH C08453 Fig. 31 - CoreMax Access Port Assembly 34 Comfort Alert Diagnostic Module POWER (GRN) The Comfort Alert Diagnostic Module (CADM) monitors and analyzes data from the Copeland Scroll® three-phase compressor and the thermostat demand. The CADM also provides a 3-minute anti-recycle time delay to compressor cycling. Each compressor has a separate CADM module. The CADM detects causes for electrical and system related failures without any sensors. Flashing LEDs communicate the Alert codes to guide service technicians in accurately and quickly troubleshooting the system and determining root cause for the failure. ALERT (YEL) Inputs to the CADM include 24-vac power, thermostat Y1 or Y2, compressor contactor coil (common side) and compressor power leads (from the compressor contactor). Terminal Voltage Control Power R 24-V Control Common C 24-V Cooling Y 24-V Contactor Coil P 24-V Line A T1 Line Line B T2 Line Line C T3 Line Control of the compressor contactor coil is through a normally-closed (power on the module) contact between terminals P and C. Communications of status and alert conditions is through three LEDs located on the top edge of the module housing (see Fig. 32): POWER (green), ALERT (yellow), and TRIP (red). The POWER LED indicates the presence of control power to the CADM. Fig. 32 - CADM Housing/LED Locations C10086 The TRIP LED indicates either a time-delay period is currently active (RED LED is blinking) or the module has locked out the compressor (RED LED is on steady). A lockout condition will occur when the CADM detects a thermostat demand at input Y but there is no power at the compressor line terminals T1 or T2 or T3. This lockout can occur due to a safety switch (LPS or HPS) opening and de-energizing the compressor contactor, the compressor-motor internal overload opens, or other internal power interruption has occurred. Reset of the TRIP LED requires that unit main power be recycled after the loss of power to the compressor condition has been detected and corrected. Simultaneous Blinking of YELLOW and RED LEDs indicates control power input to the CADM is low. Check control circuit transformer and wiring. Troubleshooting the CADM Wiring – Flashing LEDs also indicate wiring problems to the CADM. See Table 12 for discussion of additional LED flash codes and troubleshooting instructions. The ALERT LED indicates an abnormal condition exists in the system through a flash code. The ALERT LED will blink a number of times consecutively, pause and the repeat the process. The number of blinks, defined in Table 11, correlates to a particular abnormal condition; troubleshooting tips are provided for each Alert code. Reset of the ALERT may be automatic or manual. If the fault condition causing the Alert is self-corrected, the Alert code will be removed and the CADM will automatically reset and allow the system to restart normally. Manual reset requires that main power to the 38AU unit be recycled after the cause for the Alert condition has been detected and corrected. 35 38AU Input TRIP (RED) Table 11 – LED Status Codes Status LED Status LED Description Status LED Troubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” LED On Solid Thermostat demand signal Y is present, but the compressor is not running. 1. Compressor protector is open 2. Condensing unit power disconnect is open 3. Compressor circuit breaker or fuse(s) is open 4. Broken supply wires or connector is not making contact 5. Compressor power wires not routed through Comfort Alert 6. Compressor contactor has failed open Red “TRIP” LED Flashing The anti-short cycle timer (3 minutes) in module is preventing compressor restart. 38AU Module locks out compressor when compressor damaging ALERT code appears. Lockout ALERT codes are noted in the Status LED Description. During a compressor lock out, 24VAC power must be removed from module to manually reset. Yellow “ALERT” LED On Solid A short circuit or over current condition exists on PROT terminal. 1. Compressor contactor coil shorted 2. Electrical load too high for PROT circuit (maximum 1 Amp) 3. 24 V AC wired directly to PROT terminal Yellow “ALERT” Flash Code 2 System Pressure Trip Discharge pressure out of limits or compressor overload (if no high pressure switch in system) LOCKOUT 1. High head pressure 2. Condenser coil poor air circulation (dirty, blocked, damaged) 3. Condenser fan is not running 4. If low pressure switch is open: Refer to Code 3 for troubleshooting Short Cycling Compressor is running only briefly (four consecutive cycles of less than three minutes each) LOCKOUT 1. If low pressure switch is open: Yellow “ALERT” Flash Code 3 Yellow “ALERT” Flash Code 4 Locked Rotor LOCKOUT Yellow “ALERT” Flash Code 5 Open Circuit Yellow “ALERT” Flash Code 6 Missing Phase LOCKOUT a. Low refrigerant charge b. Evaporator blower is not running c. Evaporator coil is frozen d. Faulty metering device e. Condenser coil is dirty f. Liquid line restriction (filter drier blocked if present) 2. If high pressure switch is open, go to Flash Code 2 information 3. Intermittent thermostat demand signal 4. System or control board defective 1. Low line voltage to compressor 2. Excessive liquid refrigerant in compressor 3. Compressor bearings are seized 1. Condensing unit power disconnect is open 2. Compressor circuit breaker or fuses are open 3. Compressor contactor has failed open 4. High pressure switch is open and requires manual reset 5. Broken supply wires or connector is not making contact 6. Unusually long compressor protector reset time due to extreme ambient temperature 7. Compressor windings are damaged 1. Compressor fuse is open on one phase 2. Broken wire or connector on one phase 3. Compressor motor winding is damaged 4. Utility supply has dropped one phase Yellow “ALERT” Flash Code 7 Reverse Phase LOCKOUT 1. Compressor running backward due to supply phase reversal Yellow “ALERT” Flash Code 8 Welded Contactor Compressor always runs 1. Compressor contactor has failed closed 2. Thermostat demand signal not connected to module Low Voltage Control circuit < 18VAC 1. Control circuit transformer is overloaded 2. Low line voltage to compressor Yellow “ALERT” Flash Code 9 36 Table 12 – CADM Troubleshooting Recommended Troubleshooting Action Green LED is not on, module does not power up Determine if both R and C module terminals are connected. Verify voltage in present at module’s R and C terminals. NOTE: The CADM requires a constant nominal 24VAC power supply. The wiring to the module’s R and C terminals must be directly from the control transformer. The module cannot receive its power from another device that will interrupt the 24VAC power supply. See the 38AU Wiring Diagram(s) (Fig. 29 and Fig. 30). Green LED Intermittent, module powers up only when compressor runs Determine if R and Y terminals are wired in reverse. Verify module’s R and C terminals have a constant source. See “NOTE” above for details on R and C wiring. TRIP LED is on but system and compressor check OK Verify Y terminal is wired properly per the 38AU wiring diagram (see Fig. 29 and Fig. 30). Verify voltage at contactor coil falls below 0.5VAC when off. Verify 24VAQC is present across Y and C when thermostat demand signal is present. If not, R and C are reverse wired. TRIP LED and ALERT LED flashing together Verify R and C terminals are supplied with 19-28VAC. ALERT Flash Code 3 (Compressor Short Cycling) displayed incorrectly Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off. ALERT Flash Code 5 or 6 (Open Circuit, Missing Phase) displayed incorrectly Check that compressor T1 and T3 wires are through module’s current sensing holes. Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off. Alert Flash Code * (Welded Contactor) displayed incorrectly Determine if module’s Y terminal is connected. Verify Y terminal is connected to 24VAC at contactor coil. Verify 24VAC is present across Y and C when thermostat demand signal is present. If not, R and C are reverse wired. Verify voltage at contactor coil falls below 0.5VAC when off. 38AU Miswired Module Indication Compressor Protection High-- Pressure Switch — Compressor Overtemperature Protection (IP) — The high-- pressure switch is stem mounted on the discharge line. The switch is a fixed, non-adjustable type. A thermostat installed on the compressor motor winding reacts to excessively high winding temperatures and shuts off the compressor. Crankcase Heater — The heater minimizes absorption of liquid refrigerant by oil in the crankcase during brief or extended shutdown periods. The heater is wired to cycle with the compressor; the heater is off when compressor is running, and on when compressor is off. Outdoor Fans — Each fan is supported by a formed-wire mount bolted to the fan deck and covered with a wire guard. Fan motors have permanently lubricated bearings. 1. 2. 3. 4. 5. 6. The crankcase heater will operate as long as the power circuit is energized. The main disconnect must be on to energize the crankcase heater. IMPORTANT: Never open any switch or disconnect that energizes the crankcase heater unless unit is being serviced or is to be shut down for a prolonged period. After a prolonged shutdown on a service job, energize the crankcase heater for 24 hours before starting the compressor. 3.6 mm +0/0/-0.8 Fig. 33 - Outdoor Fan Blade Position Advanced Scroll Temperature Protection (ASTP) — See “Advanced Scroll Temperature Protection (ASTP)” on page 24. Low-Pressure Switch — The 38AU low-pressure switch is stem-mounted on the suction line. Switches are all fixed, non-adjustable type. Shut off unit power supply. Install lockout tag. Remove outdoor fan assembly (grille, motor, and fan). Loosen fan hub setscrews. Adjust fan height as shown in Fig. 33. Tighten setscrews to 84 in--lbs (949 N--cm). Replace outdoor fan assembly. C10103 Lubrication — Fan Motors: The fan motors have sealed bearings. No provisions are made for lubrication. Compressor: The compressor has its own oil supply. Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. 37 38AU Condenser Fans/Motors Access Panel Control Box & Compressors Service Valves Fig. 34 - 38AUD Size 16 Cabinet Fig. 35 - 38AUD*16 Piping 38 C10087 C10095 Equalization 38AU LPS Oil Equalizer Line Fig. 36 - 38AUZ*16 Compressor Assembly (Rear View) Fig. 37 - 38AUD*16 Compressor Assembly (Rear View) 39 C10079 C10214 38AU Condenser Fans/Motors Access Panel Control Box & Compressors Service Valves C10089 Fig. 38 - 38AUZ,D Size 25 Cabinet CKT 1 CKT 2 HPS HPS CKT 1 LPS CKT 2 LPS Fig. 39 - 38AUD*25 Piping 40 C10090 38AU Fig. 40 - 38AUZ*25 Compressor Assembly (Rear View) Fig. 41 - 38AUD*25 Compressor Assembly (Rear View) 41 C10215 C10091 Coil Type Identification 38AU units are available with different coil types. Cleaning methods differ for each type so identifying the coil type is important. Unit model number and appearance can identify the coil type. NOVATIONt Type — The new NOVATION Heat Exchanger Technology is an all--aluminum construction with louvered serpentine fins over single--depth crosstubes. The horizontal crosstubes have large diameter aluminum headers on each end. Various optional coatings are also available. 38AU units use two--row segmented coils. TUBES 38AU FINS Fig. 43 - Pivot and Support Top Cover 3. Carefully remove any foreign objects or debris attached to the coil face or trapped within the mounting frame and brackets. 4. Using a high pressure water sprayer, purge any soap or industrial cleaners from hose and/or dilution tank prior to wetting the coil. Clean condenser face by spraying the coil core steadily and uniformly from top to bottom, directing the spray straight into or toward the coil face. Do not exceed 900 psig or a 45 degree angle; nozzle must be at least 12 in. (30 cm) from the coil face. Reduce pressure and use caution to prevent damage to air centers (fins). Do not fracture the braze between air centers and refrigerant tubes. Allow water to drain from the coil core and check for refrigerant leaks prior to start?up. 5. Replace top cover and rear corner posts. MANIFOLD MICROCHANNELS Fig. 42 - NOVATION Heat Exchanger Coil C07273 Model number designation: See Fig. 3 for general unit model number format. Position 11 indicates the coil type and coating. Position 11 values of G, K, T and W indicate NOVATION coil type is on this unit. Round-- Tube Plate-- Fin (RTPF) Type — This construction uses a series of small diameter copper hairpin tubes running horizontally with vertical plate fins. The plate fins may be aluminum (standard) or copper (optional). Various optional coatings are also available. These coils may be one-- row or two-- row. ! NOVATION Coil Cleaning and Maintenance — Clean the coil as follows: 1. Turn off unit power. 2. Remove screws holding rear corner posts and top cover in place. Pivot top cover up 12 to 18 in. (305 to 457 mm) and support with a rigid support. See Fig. 43. CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. Chemical cleaning should NOT be used on the aluminum microchannel (NOVATION) condenser. Damage to the coil may occur. Only approved cleaning is recommended. Model number designation: See Fig. 3 for general unit model number format. Position 11 indicates the coil type and coating. Position 11 values of A, B, C, M, N and P indicate RTPF coil type is on this unit. To clean the NOVATION condenser coil, chemicals are NOT to be used; only water is approved as the cleaning solution. Only clean potable water is authorized for cleaning NOVATION condensers. C10216 Repairing NOVATION Condenser Tube Leaks — RCD offers service repair kit Part Number 50TJ660007 for repairing tube leaks in the NOVATION coil crosstubes. This kit includes approved braze materials (aluminum fluxcore braze rods), a heat shield, a stainless steel brush, replacement fin segments, adhesive for replacing fin segments, and instructions specific to the NOVATION aluminum coil. See EPIC for instruction sheet 99TA526379. The repair procedure requires the use of MAPP gas and torch (must be supplied by servicer) instead of conventional 42 oxyacetylene fuel and torch. While the flame temperature for MAPP is lower than that of oxyacetylene (and thus provides more flexibility when working on aluminum), the flame temperature is still higher than the melting temperature of aluminum, so user caution is required. Follow instructions carefully. Use the heat shield. ! The service replacement coil is preformed and is equipped with transition joints with copper stub tubes. When brazing the connection joints to the unit tubing, use a wet cloth around the aluminum tube at the transition joint. Avoid applying torch flame directly onto the aluminum tubing. Routine Cleaning of Round-Tube Plate Fin (RTPF) Coils — ! Periodic cleaning with Totaline® environmentally sound coil cleaner is essential to extend the life of RTPF coils. This cleaner is available from Carrier Replacement parts division as part number P902-0301 for a one gallon container, and part number P902-0305 for a 5 gallon container. It is recommended that all RTPF coils be cleaned with the Totaline environmentally sound coil cleaner as described below. Coil cleaning should be part of the unit’s regularly scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment. Avoid the use of: S coil brighteners S acid cleaning prior to painting S high pressure washers S poor quality water for cleaning Totaline environmentally sound coil cleaner is non-flammable, hypoallergenic, non-bacterial, and a USDA accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces, or insulation. Use of non-recommended coil cleaners is strongly discouraged since coil and unit durability could be affected. Totaline Environmentally Sound Coil Cleaner Application Equipment — S 21/2 gallon garden sprayer S water rinse with low velocity spray nozzle CAUTION UNIT RELIABILITY HAZARD Failure to follow this caution may result in reduced unit performance. High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop. Totaline Environmentally Sound Coil Cleaner Application Instructions: NOTE: Proper eye protection such as safety glasses is recommended during mixing and application. 1. Turn off unit power. 2. Remove screws holding rear corner post and top cover in place. Pivot top cover up 12 to 18 inches (305 to 457 mm) and support with a rigid support. See Fig. 43. 3. Remove all surface loaded fibers and dirt with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the fins. NOTE: Use of a water stream, such as a garden hose, against surface loaded coil will drive the fibers and dirt into the coil, making cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse. 4. Using a low velocity garden hose thoroughly wet finned surfaces with clean water. Be careful not to bend the fins. 5. Mix Totaline environmentally sound coil cleaner in a 21/2 gallon garden sprayer according to the instructions included with the cleaner. The optimum solution temperature is 100°F (38°C). NOTE: Do NOT USE water in excess of 130°F (54°C), as the enzymatic activity will be destroyed. 6. Thoroughly apply Totaline® environmentally sound coil cleaner solution to all coil surfaces including the finned area, tube sheets and coil headers. 43 38AU UNIT DAMAGE HAZARD Failure to follow this caution may result in corrosion and damage to the unit. Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils or any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil use the Totaline environmentally sound coil cleaner as described above. Replacing NOVATIONt Condenser Coil — NOTE: Do NOT use Totaline® environmentally sound coil cleaner, or any other coil cleaner on NOVATION coils. See “NOVATION Coil Cleaning and Maintenance” for instructions on cleaning NOVATION coils. CAUTION 38AU 7. Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage. 8. Ensure cleaner thoroughly penetrates deep into finned areas. 9. Interior and exterior finned areas must be thoroughly cleaned. 10. Finned surfaces should remain wet with cleaning solution for 10 minutes. 11. Ensure surfaces are not allowed to dry before rinsing. Reapply cleaner as needed to ensure 10-minute saturation is achieved. 12. Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle. 13. Replace top cover and rear corner posts. FASTENER TORQUE VALUES Table 13 – Torque Values Compressor mounting bolts 65--- 75 in–lbs (734–847 N–cm) Condenser fan motor mounting bolts 20 ±2 in–lbs (226 ±23 N–cm) Condenser fan hub setscrew 84 ±2 in–lbs (949 ±136 N–cm) High-flow service port 96 ±10 in–lbs (1085 ±23 N–cm) Schrader-type service check valve 2–3 in–lbs (23–34 N–cm) Compressor oil sightglass thread 330 ±31 in–lbs (23–34 N–cm) Compressor to Compressor rail torque 120–168 in–lbs (1356–1898 N–cm) Compressor rail to base pan torque 70 ±5 in–lbs (791 ±57 N–cm) TROUBLESHOOTING PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power. 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power. 3. Check control transformer primary connections and circuit breaker. 4. Thermostat circuit open. 4. Check thermostat setting. 5. Safety device lockout circuit active. 5. Reset lockout circuit. 6. Low-pressure switch open. 6. Check for refrigerant undercharge, obstruction of indoor airflow. Make sure liquid line solenoid valve(s) is open. 7. High-pressure switch open. 7. Check for refrigerant overcharge, obstruction of outdoor airflow, air in system. Be sure outdoor fans are operating correctly. 8. Compressor overtemperature switch open. 8. Check for open condition. Allow for reset. Replace compressor if necessary 9. Loose electrical connections. 9. Tighten all connections. 10. Compressor stuck. 10. See compressor service literature. Contactor Closed 1. Compressor leads loose. 1. Check connections. 2. Motor windings open. 2. See compressor service literature. 3. Single phasing. 3. Check for blown fuse. Check for loose connection at compressor terminal. COMPRESSOR STOPS ON HIGH-PRESSURE SWITCH Outdoor Fan On 1. High-pressure switch faulty. 1. Replace switch. 2. Reversed fan rotation. 2. Confirm rotation, correct if necessary. 3. Airflow restricted. 3. Remove obstruction. 4. Air recirculating. 4. Clear airflow area. 5. Noncondensables in system. 5. Recover refrigerant and recharge as required. 6. Refrigerant overcharge. 6. Recover refrigerant as required. 7. Line voltage incorrect. 7. Consult power company. 8. Refrigerant system restrictions. 8. Check or replace filter drier, expansion valve, etc. Outdoor Fan Off 1. Fan slips on shaft. 1. Tighten fan hub setscrews. 2. Motor not running. 2. Check power and capacitor. 3. Motor bearings stuck. 3. Replace bearings. 4. Motor overload open. 4. Check overload rating. Check for fan blade obstruction. 5. Motor burned out. 5. Replace motor. 44 TROUBLESHOOTING (cont) PROBLEM SOLUTION COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH Indoor-Air Fan Running 1. Liquid line solenoid valve(s) fails to open. 1. Check liquid line solenoid valve(s) for proper operation. Replace if necessary. 2. Filter drier plugged. 2. Replace filter drier. 3. Expansion valve power head defective. 3. Replace power head. 4. Low refrigerant charge. 4. Add charge. Check low-pressure switch setting. Airflow Restricted 1. Coil iced up. 1. Check refrigerant charge. 2. Coil dirty. 2. Clean coil fins. 3. Air filters dirty. 3. Clean or replace filters. 4. Dampers closed. 4. Check damper operation and position. 1. Electrical connections loose. 1. Tighten all connections. 2. Fan relay defective. 2. Replace relay. 3. Motor overload open. 3. Power supply. 4. Motor defective. 4. Replace motor. 5. Fan belt broken or slipping. 5. Replace or tighten belt. COMPRESSOR RUNNING BUT COOLING INSUFFICIENT Suction Pressure Low 1. Refrigerant charge low. 1. Add refrigerant. 2. Head pressure low. 2. Check refrigerant charge. Check outdoor-air fan thermostat settings. 3. Air filters dirty. 3. Clean or replace filters. 4. Expansion valve power head defective. 4. Replace power head. 5. Indoor coil partially iced. 5. Check low-pressure setting. 6. Indoor airflow restricted. 6. Remove obstruction. Suction Pressure High 1. Heat load excessive. 1. Check for open doors or windows in vicinity of fan coil. UNIT OPERATES TOO LONG OR CONTINUOUSLY 1. Low refrigerant charge. 1. Add refrigerant. 2. Control contacts fused. 2. Replace control. 3. Air in system. 3. Purge and evacuate system. 4. Partially plugged expansion valve or filter drier. 4. Clean or replace. SYSTEM IS NOISY 1. Piping vibration. 1. Support piping as required. 2. Compressor noisy. 2. Replace compressor if bearings are worn. COMPRESSOR LOSES OIL 1. Leak in system. 1. Repair leak. 2. Crankcase heaters not energized during shutdown. 2. Check wiring and relays. Check heater and replace if defective. 3. Improper interconnecting piping design. 3. Check piping for oil return. Replace if necessary. FROSTED SUCTION LINE Expansion valve admitting excess refrigerant. Adjust expansion valve. HOT LIQUID LINE 1. Shortage of refrigerant due to leak. 1. Repair leak and recharge. 2. Expansion valve opens too wide. 2. Adjust expansion valve. FROSTED LIQUID LINE 1. Restricted filter drier. 1. Remove restriction or replace. 2. Liquid line solenoid valve partially closed. 2. Replace valve. 45 38AU Indoor-Air Fan Stopped APPENDIX A Air Conditioner & Heat Pump with PURON® — Quick Reference Guide S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S Puron® (R-410A) refrigerant operates at 50 percent to 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron®. S POE oils may cause damage to certain plastics and roofing materials. S Puron® refrigerant cylinders are rose colored. S A factory approved, liquid-line filter drier is required on every unit. 38AU S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. S Puron® systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating. S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low-side retard. S Wrap all filter driers and service valves with wet cloth when brazing. S Do not use an R-22 TXV. S If indoor unit is equipped with a TXV, it must be changed to a Puron® TXV. S Never open system to atmosphere while it is under a vacuum. S Use hoses with 700 psig service pressure rating. S When system must be opened for service, recover refrigerant, break vacuum with dry nitrogen before opening system. S Leak detectors should be designed to detect HFC refrigerant. S Always replace filter drier after opening system for service. S Puron®, as with other HFCs, is only compatible with POE oils. S Do not vent Puron® into the atmosphere. S Do not use capillary tube coils. S Vacuum pumps will not remove moisture from oil. S Observe all warnings, cautions, and bold text. S Use only factory specified liquid-line filter driers with rated working pressures greater than 600 psig. S All Puron® heat pumps must have indoor TXV. S Do not install a suction-line filter drier in liquid-line. S Do not leave Puron® suction line driers in place for more than 72 hours. APPENDIX B Wiring Diagram List Unit Electrical Characteristics Diagram Number 38AUD*16 208/230-3-60 38AU500540 460-3-60 38AU500541 575-3-60 38AU500542 208/230-3-60 38AU500565 460-3-60 38AU500566 575-3-60 38AU500567 208/230-3-60 38AU500537 460-3-60 38AU500538 575-3-60 38AU500539 208/230-3-60 38AU500568 460-3-60 38AU500569 575-3-60 38AU500570 38AUD*25 38AUZ*16 38AUZ*25 46 APPENDIX C Units with the factory installed low ambient option are equipped with a MotormasterR solid-- state head pressure control which regulates fan speed. A temperature sensor, mounted on circuit 1 of the outdoor coil (see Figs. 44 and 45) controls the speed of approved outdoor fan motors in order to maintain a constant head pressure in the outdoor coil. The control maintains the appropriate head pressure at low ambient temperatures down to - 20_F (-- 28_C). Wind baffles are required to prevent wind cross currents from causing abnormally low condensing temperatures. S Use 20-- gauge sheet metal to fabricate wind baffles (see Fig. 46 and Table 14) and mounting brackets (see Fig. 47). NOTE: Mounting brackets are for use on 15 ton model units only. S Install the wind baffles as show in Fig. 48, for 15 ton units and Fig. 49, for 20 ton units . Operation — Fan on/off control in cooling-- only units (38AUZ, 38AUD) is provided by an outdoor fan relay (OFR). In cooling mode, fan motor speed of outdoor motors OFM1 and OFM3 is regulated by the speed control temperature sensor on outdoor coil 1 for a minimum coil condensing temperature of approximately 100_F (38_C) at higher outdoor ambient temperature and 80_F (27_C) at lower ambient. Additionally, outdoor fan motor OFM2 and OFM4 are turned on/off by the low ambient temperature switch, LAS, operating the low ambient relay (LAR). The LAS control temperatures are open 42_F +/-5_F, close 57_F +/-- 5_F (open 5.5_C +/-- 2.8_C, close 13.9_C +/-- 2.8_C). Troubleshooting — OBSERVATION POSSIBLE REMEDY Fans won’t start All fans: Check power & wiring Check outdoor fan relay (OFR) OFM1, OFM3 only: Check speed control sensor location Check speed sensor resistance OFM2, OFM4 only: Check low ambient switch (LAS) Check low ambient relay (LAR) Cooling --- Center outdoor fans (OFM2, OFM4) off below approximately 60_F (16_C) outdoor ambient. Normal operation Cooling --- Center outdoor fans (OFM2, OFM4) not on above approximately 60_F (16_C) outdoor ambient Check low ambient switch (LAS) Check low ambient relay (LAR) Cooling --- Slow fan speed for outer fans (OFM1, OFM3) at start or during low outdoor ambient Normal operation Cooling --- Slow fan speed for outer fans (OFM1, OFM3) above 85_F (29_F) outdoor ambient (should be full speed) Check speed control sensor location Check speed control sensor resistance Check fan motor capacitor Cooling --- motor current into speed control is greater than motor nameplate FLA Normal operation Up to 30% higher A at partial speed at low ambient 38AU Low Ambient Option — Factory Installed Speed Control Sensor Resistance — TEMPERATURE To override the speed control for full fan speed operation during service or maintenance, either: a. remove sensor and place in hot water >120_F (>49_C), or b. rewire to bypass control by connecting speed control input and output power wires. 47 RESISTANCE _F +/---2_F _C +/---1_C Ohms, nominal --- 22 --- 30 88350 --- 4 --- 20 48485 14 --- 10 27650 32 0 16325 50 10 9950 68 20 6245 77 25 5000 86 30 4028 104 40 2663 122 50 1801 140 60 1244 158 70 876 38AU Motormaster Sensor Must be positioned on Vapor Stub of Circuit 1 coil only. Motormaster Sensor Attach to Circuit 1 coil only. 508 mm (20 in) for Single Circuit 254 mm (10 in) for Dual Circuit Fig. 44 - Motormaster Sensor Location: 38AUZ*16 & 38AUD*16 (Novation) C10093 Fig. 45 - Motormaster Sensor Location: 38AUZ*16/25 & 38AUD*16/25 (RTPF) 48 C10094 Table 14 – Wind Baffle Dimension DIMENSIONS --- INCHES 38AUZ*16 38AUD*16 (MCHX) 38AUZ*16 38AUD*16 (RTPF) 38AUZ*25 38AUD*25 (RTPF) BAFFLE A B C D E F G H J LEFT SIDE 19 3/4 20 1/2 21 1/4 43 1/8 8 3 /8 18 27 1/4 40 --- BACK 80 1/4 81 81 3/4 43 1/8 8 3 /8 18 27 1/4 40 --- 40 --- RIGHT SIDE 38 3/ 4 39 1/ 2 40 1/ 43 4 1/ 8 8 3/ 8 18 27 1/ 4 FRONT 34 1/8 34 7/8 35 5/8 43 1/8 6 7 /8 16 1/2 25 3/4 38 1/2 --- LEFT SIDE 10 3/4 11 1/2 12 1/4 43 1/8 4 1/4 13 1/4 22 1/4 31 1/4 40 1/4 BACK 80 1/4 81 81 3/4 43 1/8 8 3 /8 18 27 1/4 40 --- 8 3/ 18 27 1/4 40 --- RIGHT SIDE 38 3/ 4 27 LEFT SIDE 32 7/8 BACK 47 3/4 RIGHT SIDE 61 1/8 FRONT 20 2 27 3/4 FRONT 1/ 39 1/ 8 40 1/ 43 4 1/ 8 8 28 1/2 43 1/8 3 3 /4 12 3/4 21 3/4 30 3/4 39 3/4 33 5/8 34 3/8 43 1/8 4 1 /4 13 1/4 22 1/4 31 1/4 40 1/4 48 1/2 49 1/4 43 1/8 4 1 /4 13 1/4 22 1/4 31 1/4 40 1/4 61 7/8 62 5/8 43 1/8 3 3 /4 12 3/4 21 3/4 30 3/4 39 3/4 8 8 43 3 12 21 30 20 7/ 21 5/ 1/ 8 3/ 4 3/ 4 3/ 4 3/ 4 39 3/4 DIMENSIONS --- MM UNIT 38AUZ*16 38AUD*16 (MCHX) 38AUZ*16 38AUD*16 (RTPF) 38AUZ*25 38AUD*25 (RTPF) BAFFLE A B C D E F G H J LEFT SIDE 501 520 539 1095 212 457 694 1015 --- BACK 2037 2056 2075 1095 212 457 694 1015 --- RIGHT SIDE 983 1002 1021 1095 212 457 694 1015 --- FRONT 866 885 904 1095 174 419 656 977 --- LEFT SIDE 272 291 310 1095 108 337 565 794 1022 --- BACK 2037 2056 2075 1095 212 457 694 1015 RIGHT SIDE 983 1002 1021 1095 212 457 694 1015 --- FRONT 684 704 723 1095 95 324 552 781 1010 LEFT SIDE 834 853 872 1095 108 337 565 794 1022 BACK 1214 1233 1252 1095 108 337 565 794 1022 RIGHT SIDE 1551 1570 1589 1095 95 324 552 781 1010 FRONT 510 530 549 1095 95 324 552 781 1010 MCHX: NOVATION coil model 49 38AU UNIT 50 Fig. 46 -- Wind Baffles -- Fabrication 38AU C10363A 51 Fig. 47 -- 15 Ton Wind Baffle Brackets -- Fabrication 38AU C10366 52 LEFT RIGHT Fig. 48 -- Wind Baffle Installation — 15 Ton Units FRONT TOP BRACKETS 38AU BACK BOTTOM BRACKET C10367 53 LEFT RIGHT Fig. 49 -- Wind Baffle Installation — 20 Ton Units FRONT 38AU BACK C10368 38AU Copyright 2010 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 11/10 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 54 Catalog No: 38AU ---09SI Replaces: 38AU--- 07SI START-UP CHECKLIST I. PRELIMINARY INFORMATION OUTDOOR: MODEL NO. INDOOR: SERIAL NO. AIRHANDLER MANUFACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES II. PRE-START-UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: (Y/N) CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? HAS THE GROUND WIRE BEEN CONNECTED? 38AU WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) (Y/N) HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) CONTROLS ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING CONNECTIONS MADE AND CHECKED? (Y/N) ARE ALL WIRING TERMINALS (including main power supply) TIGHT? HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N) (Y/N) INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? ARE PROPER AIR FILTERS IN PLACE? (Y/N) (Y/N) HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) (Y/N) HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N) PIPING ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR COILS AS REQUIRED? (Y/N) HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR AND INDOOR COILS, TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N) LOCATE, REPAIR, AND REPORT ANY LEAKS. HAVE LIQUID LINE SERVICE VALVES BEEN OPENED? HAVE SUCTION LINE SERVICE VALVES BEEN OPENED? 55 (Y/N) (Y/N) CHECK VOLTAGE IMBALANCE LINE-TO-LINE VOLTS: AB V AC V (AB + AC + BC)/3 = AVERAGE VOLTAGE = BC V V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! CALL LOCAL POWER COMPANY FOR ASSISTANCE. CHECK INDOOR UNIT FAN SPEED AND RECORD. CHECK OUTDOOR UNIT FAN SPEED AND RECORD. 38AU AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: SUCTION PRESSURE CIR 1: CIR 2: SUCTION LINE TEMP CIR 1: CIR 2: LIQUID PRESSURE CIR 1: CIR 2: LIQUID LINE TEMP CIR 1: CIR 2: ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING-AIR DB (dry bulb) TEMP INDOOR UNIT ENTERING-AIR WB (wet bulb) TEMP INDOOR UNIT LEAVING-AIR DB TEMP INDOOR UNIT LEAVING-AIR WB TEMP COMPRESSOR 1 AMPS (L1/L2/L3) / / COMPRESSOR 2 AMPS (L1/L2/L3) / / NOTES: Copyright 2010 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 11/10 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 56 Catalog No: 38AU ---09SI Replaces: 38AU--- 07SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39 Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2010:11:04 14:40:56-04:00 Create Date : 2010:11:04 14:40:56-04:00 Format : application/pdf Title : 38AU-09SI Creator : bact4qr Producer : Acrobat Distiller 8.1.0 (Windows) Document ID : uuid:be0c6d9b-0c10-4fb0-b277-b0599ee0f2e7 Instance ID : uuid:f2c21594-946e-4818-80af-b4e9411c135b Page Count : 56 Author : bact4qrEXIF Metadata provided by EXIF.tools