48PG16 Gas Heating/Electric Cooling Single Package Rooftop Units High Altitude Kit Accessory Installation Instructions Part No. CRNGHIAT002A00 HIGH ALTITUDE KIT USAGE AND CONTENTS ACCESSORY PART NO. USAGE CRNGHIAT002A00 48PG16 SAFETY CONSIDERATIONS Read these instructions entirely before installing the accessory high altitude kit into the base rooftop unit. Installation, start-up, and servicing of this equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs). Only trained, qualified installers and service technicians should install, start up, and service this equipment. When working on this equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Also observe any other safety precautions that may apply. Before beginning any modification, close main gas supply shutoff valve. Be certain that the main line electrical disconnect switch is in the OFF position and lockout tag is installed. Electric shock or fire could result. Tag disconnect switch and gas valve with suitable warning labels. GENERAL The high altitude conversion kit is used to install natural gas units at elevations as high as 7000 ft. Recommended orifice sizes will derate the heating input by approximately 4% per 1000 ft of elevation. For elevations above 7000 ft, see Table 1. INSTALLATION Step 1 — Remove Gas Manifold Pipe 1. Close the manual shutoff valve on the gas supply piping. 2. Open gas section access door. See Fig. 1. 3. Set the switch on the main gas valve to the OFF position. See Fig. 2. 4. Shut off power to unit and install lockout tag. 5. Disconnect gas piping at unit gas valve. NOTE: Use a backup wrench to avoid twisting the gas manifold pipe. 6. Remove wires connected to gas valve. Mark each wire to ensure proper reassembly. 7. Remove wires connected to the flame rollout switch. Mark wires. CONTENTS 9 Burner Orifices, Drill Size No. 31, 0.120 in. 9 Burner Orifices, Drill Size No. 32, 0.116 in. 8. Remove wires connected to igniter and flame sensor. Mark wires. 9. Remove the four screws that attach the gas manifold pipe to the burner bracket and rotate the pipe away from the unit. The pipe should NOT be removed from the wire bundle connecting to the IGC (integrated gas controller) board. See Fig. 3. Table 1 — Altitude Compensation* ELEVATION (ft) 0-1,999 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 48PG16 NATURAL GAS ORIFICE† 30 30 31 31 31 31 32 32 32 35 36 37 38 39 *As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft. †Orifices available through your Carrier dealer. Step 2 — Replace Orifice Fittings 1. Remove standard orifice fittings from the manifold pipe. 2. Select the correct orifice size based on local elevation. Refer to Table 1. 3. Install new orifice fittings. NOTE: Pipe sealant is not required. Never use Teflon tape on fitting threads since loose pieces may plug gas orifices. Step 3 — Reinstall Manifold Pipe 1. Attach manifold pipe to the burner bracket using four screws. See Fig. 3. Make sure that all orifice fittings are properly seated in the burner inlets. 2. Reconnect wires to the igniter, flame sensor, flame rollout switch, and gas valve. 3. Reconnect gas piping to the gas valve. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480022-01 Printed in U.S.A. Form 48PG-21SI Pg 1 12-05 Replaces: New Book 1 4 Tab 1a 6a ECONOMIZER HOODS CONDENSER COIL ACCESS PANEL OUTDOOR AIR SCREENS (HIDDEN) BAROMETRIC RELIEF DAMPER HOODS ELECTRICAL OPTIONS PANEL FILTER ACCESS DOOR BASEPAN CONNECTIONS ACCESS PANEL GAS SECTION ACCESS DOOR CONTROL BOX AND COMPRESSOR ACCESS DOOR Fig. 1 — Panel and Filter Locations 4. Set the switch on the main gas valve to the ON position. 5. Call for high stage heat (W2 energized). The unit may require several ignition attempts due to trapped air in the manifold pipe. 6. When main burners ignite check orifice fittings for leaks. Repair if necessary. INDUCED DRAFT MOTOR Never use a match or other open flame to check for leaks. Use a soap and water solution. Fire or serious injury could result. MAIN GAS VALVE HEAT EXCHANGER SECTION If unit is equipped with a 2-stage gas valve, ensure valve has energized second stage (high fire) before adjusting manifold pressure. Improper manifold pressures may cause explosion or injury. COMBUSTION MAIN FAN HOUSING BURNER SECTION 7. Verify that manifold pressure is between 2.7 and 3.0 in. wg while in high fire (W2 energized). Readjust pressure if necessary. Fig. 2 — Typical Gas Heating Section Step 4 — Check Unit Operation and Make Necessary Adjustments This unit is designed to operate at 3.0 in. wg (± 0.3 in. wg) manifold pressure at high fire. Exceeding this pressure will cause explosion or injury. NOTE: Gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection. 1. Remove pressure tap plug from manifold pipe and connect a pressure gage or manometer. 2. Turn on electrical supply. 3. Open the manual shutoff valve on the gas supply piping. Check pipe connection to main gas valve for leaks. 8. Shut down unit by turning down thermostat (units with electro-mechanical control) or putting unit in Service Test mode (units with ComfortLink™ control), shutting off manual gas valve, and shutting down power to unit. 2 9. Remove pressure gage or manometer and replace manifold pressure tap plug. 10. Start up unit. With burners ignited, check pressure tap plug for gas leaks. Repair if necessary. 11. Close and secure gas section access door. 12. Set thermostat to desired temperature (units with electromechanical control). For units with ComfortLink™ control, to test the operation of the gas section, the HEAT submenu of Service Test may be used. See the Controls Start-Up, Operation, Service, and Troubleshooting Instructions for more details on use of Service Test. For normal operation, make sure that the set points are at the normal heat set points. 13. Remove warning tags from disconnect switch and gas supply shutoff valve. MANIFOLD MOUNTING SCREWS MAIN GAS VALVE MANIFOLD PRESSURE TAP PLUG MANIFOLD MOUNTING SCREWS Fig. 3 — Typical Main Burner Section 3 Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480022-01 Printed in U.S.A. Form 48PG-21SI Pg 4 12-05 Replaces: New Book 1 4 Tab 1a 6a
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No Create Date : 2005:12:22 15:21:06 Producer : Acrobat Distiller 4.0 for Windows Author : Carrier Corporation Creator : Adobe Illustrator(R) 8.0 Title : Modify Date : 2005:12:22 15:23:08-05:00 Page Count : 4EXIF Metadata provided by EXIF.tools