Carrier 50Ej Users Manual
50EK to the manual e71e33d9-7fd7-4603-8a4e-5bd3e13ed5f2
2015-01-24
: Carrier Carrier-50Ej-Users-Manual-310623 carrier-50ej-users-manual-310623 carrier pdf
Open the PDF directly: View PDF .
Page Count: 56
Download | ![]() |
Open PDF In Browser | View PDF |
50EJ,EK,EW,EY024-048 Single-Package Rooftop Units Electric Cooling with Electric Heat Option Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 1 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31 Step 1 — Provide Unit Support . . . . . . . . . . . . . . 1 • ROOF CURB • ALTERNATE UNIT SUPPORT Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . 8 • POSITIONING • ROOF MOUNT Step 3 — Field Fabricate Ductwork . . . . . . . . . . . 11 Step 4 — Make Unit Duct Connections . . . . . . . 11 Step 5 — Trap Condensate Drain . . . . . . . . . . . . . 11 Step 6 — Controls Options . . . . . . . . . . . . . . . . . . 12 • CONSTANT VOLUME APPLICATIONS • VARIABLE AIR VOLUME (VAV) APPLICATIONS Step 7 — Make Electrical Connections . . . . . . . 15 • POWER WIRING • FIELD POWER SUPPLY • FIELD CONTROL WIRING Step 8 — Make Outdoor-Air Inlet Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 • ECONOMIZER • ECONOMIZER SETTINGS Step 9 — Position Power Exhaust/ Barometric Relief Damper Hood . . . . . . . . . . . . . 29 Step 10 — Install Accessories . . . . . . . . . . . . . . . 30 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-42 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-45 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 46-51 START-UP CHECKLIST . . . . . . . . . . . . . . . CL-1, CL-2 SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. IMPORTANT — READ BEFORE INSTALLING IMPORTANT: Due to upgrades in unit control software and hardware, units produced currently are slightly different than original design units. The unit control software (which has changed) is designated with a sticker on the unit control board, chip U8 (the large chip in the center of the board), which states the software Version number. Version 1.0 is the original version. Version 2.0 is the current version. Differences in installation, configuration, and start-up procedures in this manual will be identified by Version number. INSTALLATION Step 1 — Provide Unit Support All panels must be in place when rigging. Unit is not designed for handling by fork truck. ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with the curb. Accessory roof curb and information required to field fabricate a roof curb or horizontal adapter are shown in Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be secured to roof curb before unit is set in place. IMPORTANT: The gasketing of the unit to the roof curb is critical for a leak-proof seal. Install gasket supplied with the roof curb as shown in Fig. 1. Improperly applied gasket can result in air leaks and poor unit performance. Curb should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is shown in Fig 1 and 2. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material. ALTERNATE UNIT SUPPORT — When the curb or adapter cannot be used, support unit with sleepers using unit curb or adapter support area. If sleepers cannot be used, support long sides of unit (refer to Fig. 3-6) with a minimum number of equally spaced 4-in. x 4-in. pads as follows: 50EJ,EK,EW,EY024-034 units require 3 pads on each side; 50EJ,EK,EW,EY038-048 require 4 pads on each side. Unit may sag if supported by corners only. Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 535-006 Printed in U.S.A. Form 50E-3SI Pg 1 8-96 Replaces: 50E-1SI Tab 1b NOTE: To prevent standing water in the drain pan of the indoor section and the heat exchangers, UNIT CAN ONLY BE PITCHED AS SHOWN. UNIT LEVELING TOLERANCES DIMENSIONS* (Degrees and Inches) NOTES: 1. Unless otherwise specified, all dimensions are to outside of part. 2. Roof curb accessory is shipped disassembled. 3. All roof curb parts are to be 16 ga galvanized steel. 4. Dimensions are in inches. A Deg. 1.0 B in. 2.9 Deg. .50 *From edge of unit to horizontal. Fig. 1 — Roof Curb (Sizes 024-034) 2 in. .75 NOTES: 1. Unless otherwise specified, all dimensions are to outside of part. 2. Roof curb accessory is shipped disassembled. 3. All roof curb parts are to be 16 ga galvanized steel. 4. Dimensions are in inches. NOTE: To prevent standing water in the drain pan of the indoor section and the heat exchangers, UNIT CAN ONLY BE PITCHED AS SHOWN. UNIT LEVELING TOLERANCES DIMENSIONS* (Degrees and Inches) A Deg. 1.0 B in. 2.9 Deg. .50 *From edge of unit to horizontal. Fig. 2 — Roof Curb (Sizes 038-048) 3 in. .75 NOTES: 1. Weights include economizer (Std) 2. Center of gravity. 3. Do not locate adjacent units with discharge facing economizer inlet. Minimum clearances to be: Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for removal of evaporator coil) 4. For smaller service and operational clearances, contact Carrier Application Engineering department. 5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on accessory roof curb. 6. Dimensions are in inches. Dimensions in [ ] are in millimeters. 7. For units with electric heat, a fieldsupplied 90° elbow must be installed in the supply ductwork below the unit discharge. LEGEND VFD — Variable Frequency Drive UNIT SIZE 50EJ/EK OPERATING WEIGHT (lb) 024 028 030 034 4016 4102 4102 4102 A B ft-in. 5-113⁄8 5- 81⁄2 5- 81⁄2 5- 81⁄2 ft-in. 3-511⁄16 3-75⁄8 3-75⁄8 3-75⁄8 CORNER WEIGHT (lb) 1 2 3 4 823 914 1199 1080 844 859 1210 1189 844 859 1210 1189 844 859 1210 1189 Fig. 3 — Base Unit Dimensions, 50EJ/EK024-034 4 NOTES: 1. Weights include economizer (Std) 2. LEGEND VFD — Variable Frequency Drive Center of gravity. 3. Do not locate adjacent units with discharge facing economizer inlet. Minimum clearances to be: Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for removal of evaporator coil) 4. For smaller service and operational clearances, contact Carrier Application Engineering department. 5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on accessory roof curb. 6. Dimensions are in inches. Dimensions in [ ] are in millimeters. 7. For units with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discharge. UNIT SIZE OPERATING WEIGHT 50E (lb) J038 J/K044 J048 4282 4508 4795 A B ft-in. ft-in. 7-75⁄16 3-101⁄2 7-313⁄16 3-111⁄2 7-23⁄16 3-103⁄32 CORNER WEIGHT (lb) 1 2 3 4 961 858 1162 1302 973 868 1258 1409 1007 915 1368 1505 Fig. 4 — Base Unit Dimensions, 50EJ038-048 and 50EK044 5 NOTES: 1. Weights include economizer (Std) 2. LEGEND VFD — Variable Frequency Drive Center of gravity. 3. Do not locate adjacent units with discharge facing economizer inlet. Minimum clearances to be: Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for removal of evaporator coil) 4. For smaller service and operational clearances, contact Carrier Application Engineering department. 5. Dimensions are in inches. Dimensions in [ ] are in millimeters. 6. For units equipped with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discharge. 7. For side-supply/return applications, a single return and supply ductwork connection is recommended for covering both return and both supply openings. UNIT SIZE 50EW/EY OPERATING WEIGHT (lb) 024 028 030 034 4016 4102 4102 4102 A B ft-in. 5-113⁄8 5- 81⁄2 5- 81⁄2 5- 81⁄2 ft-in. 3-511⁄16 3-75⁄8 3-75⁄8 3-75⁄8 Fig. 5 — Base Unit Dimensions, 50EW/EY024-034 6 CORNER WEIGHT (lb) 1 2 3 4 823 914 1199 1080 844 859 1210 1189 844 859 1210 1189 844 859 1210 1189 NOTES: 1. Weights include economizer (Std) 2. LEGEND VFD — Variable Frequency Drive Center of gravity. 3. Do not locate adjacent units with discharge facing economizer inlet. Minimum clearances to be: Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for removal of evaporator coil) 4. For smaller service and operational clearances, contact Carrier Application Engineering department. 5. Dimensions are in inches. Dimensions in [ ] are in millimeters. 6. For units equipped with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discharge. 7. For side-supply/return applications, a single return and supply ductwork connection is recommended for covering both return and both supply air openings. UNIT SIZE 50E OPERATING WEIGHT (lb) W038 W/Y044 W048 4282 4508 4795 A ft-in. ft-in. 7-75⁄16 3-101⁄2 7-313⁄16 3-111⁄2 7-23⁄16 3-103⁄32 Fig. 6 — Base Unit Dimensions, 50EW038-048 and 50EY044 7 B CORNER WEIGHT (lb) 1 2 3 4 961 858 1162 1302 973 868 1258 1409 1007 915 1368 1505 Four lifting lugs are provided on the unit base rails as shown in Fig. 7. Refer to rigging instructions on unit. POSITIONING — Provide clearance around and above unit for airflow, safety, and service access (Fig. 3-6). Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. Although unit is weatherproof, guard against water from higher level runoff and overhangs. Step 2 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright, and do not drop. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is shown in Fig. 1 and 2. See Fig. 7 for additional information. Unit weight is shown in Table 1. NOTE: On retrofit jobs, ductwork may be attached to old unit instead of roof curb. Be careful not to damage ductwork when removing unit. Attach existing ductwork to roof curb instead of unit. NOTICE TO RIGGERS: ALL PANELS MUST BE IN PLACE WHEN RIGGING. NOTE: Rig with four cables and spread with two 92 in. (2337 mm) spreader bars. Maintain a distance of 74 in. (1880 mm) from top of unit to eyehook. NOTE: Add 32 lb Add 312 lb Add 346 lb Add 250 lb Add 220 lb Add 285 lb Add 380 lb MODEL 50EJ/EK/EW/EY 024 028 030 034 038* 044 048* A (14.5 kg) for domestic crating. (142 kg) for export crating (024-034 units). (157 kg) for export crating (038-048 units). (113 kg) for power exhaust. (100 kg) for copper condenser coil (024-034 units). (129 kg) for copper condenser coil (038-044 units). (172 kg) for copper condenser coil (048 unit). WEIGHT lb kg 4016 1822 in. 87.68 mm 2227 in. 71.4 B mm 1814 in. 41.7 mm 1059 4102 1860 87.68 2227 68.5 1740 43.6 1107 4282 4508 4795 1942 2045 2175 150 3810 91.3 87.8 86.2 2319 2230 2189 46.5 46.5 46.1 1181 1181 1171 *Sizes 038 and 048 are 50EJ,EW units only. Fig. 7 — Rigging Label 8 C Table 1 — Physical Data UNIT 50EJ,EK,EW,EY NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb)* Unit Al/Al† Al/Cu† Roof Curb (14-in. curb) COMPRESSOR Type Ckt 1 Ckt 2 Number of Refrigerant Circuits Oil (oz) (Ckt1, Ckt 2) REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1** Circuit 2 CONDENSER COIL Quantity Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp (1075 Rpm) EVAPORATOR COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.) Type Drive Nominal Cfm Motor Hp Motor Frame Size Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Nominal Fan Shaft Diameter (in.) Belt, Quantity...Type Belt, Length (in.) Pulley Center Line Distance (in.) Factory Speed Setting (rpm) HIGH-PRESSURE SWITCH (psig) Cutout Reset (Auto.) LOW-PRESSURE SWITCH (psig) Cutout Reset (Auto.) RETURN-AIR FILTERS Quantity...Size (in.) OUTDOOR-AIR FILTERS Quantity...Size (in.) POWER EXHAUST Motor, Quantity...Hp Fan, Diameter...Width (in.) 024 20 028 25 030 27 034 30 4016 4236 365 4102 4322 365 4102 4322 365 4102 4322 365 06D328 06D818 2 115, 88 06D328 06D328 2 115 ea. 06D537 06D328 2 115 ea. 06D537 06D537 2 115 ea. R-22 25-0 31-0 5 S184T 4.6 11⁄8 11.1 1...BX59 62 16.0-18.7 725 25-0 25-0 25-0 25-0 3 Cross-Hatched ⁄89 Copper Tubes, Aluminum Lanced or Copper Fins 1 1 1 4...15 4...15 4...15 33.3 33.3 33.3 Propeller Type 13,420 13,420 13,420 2...30 2...30 2...30 1 1 1 Cross-Hatched 3⁄89 Copper Tubes, Aluminum or Copper Plate Fins, Intertwined Circuits 4...15 4...15 4...15 31.7 31.7 31.7 Centrifugal Type 2...20x15 2...20x15 2...20x15 Belt Belt Belt 8,000 10,000 11,000 10†† 15 7.5 10†† 15 10 15†† 20 10 S215T S254T S213T S215T S254T S215T S254T S256T S215T Ball Ball Ball 1200 1200 1200 6.6 6.9 4.9 6.1 7.1 6.6 6.7 7.5 6.4 13⁄8 15⁄8 13⁄8 13⁄8 15⁄8 13⁄8 15⁄8 15⁄8 13⁄8 12.5 11.1 11.1 11.1 11.1 13.7 11.1 11.1 12.5 111⁄16 111⁄16 111⁄16 1...BX60 1...5VX590 1...BX56 1...BX56 1...5VX590 1...BX62 1...5VX590 1...5VX600 1...BX60 63 59 59 59 59 65 59 60 63 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.6-18.4 924 1088 773 962 1119 843 1056 1182 896 1 4...15 33.3 13,420 2...30 1 4...15 31.7 2..20x15 Belt 12,000 15†† 20 S254T S256T Ball 1200 6.9 7.5 15⁄8 15⁄8 11.1 11.1 111⁄16 1...5VX590 1...5VX600 59 60 15.0-17.9 1088 1182 426 320 426 320 426 320 426 320 7 22 7 22 7 22 7 22 10...20x24x2 10...20x24x2 10...20x24x2 10...20x24x2 8...16x25 8...16x25 8...16x25 8...16x25 4...20x25 4...20x25 4...20x25 4...20x25 Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired For High Speed) and Forward Curved Fan 4...1 11...10 NOTES: 1. See Table 2 for evaporator fan motor data. 2. Sizes 038 and 048 are 50EJ,EW units only. LEGEND Al — Cu — 25-0 25-0 Aluminum Copper *Weight of unit does not include variable frequency drive (VFD), barometric relief, or power exhaust. If a VAV unit (a VFD is installed), add the VFD weight in the table at right. †Evaporator coil fin material/condenser coil fin material. **Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils. ††Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more drive information, see Table 2. VFD (Hp) 9 VFD WEIGHTS (lb) 460 v 22 37 61 5 7.5 10 208/230 v 20 51 51 575 v 60 64 64 15 20 61 63 63 111 109 109 25 30 105 172 112 118 174 180 Table 1 — Physical Data (cont) UNIT 50EJ,EK,EW,EY NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb)* Unit Al/Al† Al/Cu† Roof Curb (14-in. curb) COMPRESSOR Type Ckt 1 Ckt 2 Number of Refrigerant Circuits Oil (oz) (Ckt1, Ckt 2) REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1** Circuit 2 CONDENSER COIL Quantity Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp (1075 Rpm) EVAPORATOR COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.) Type Drive Nominal Cfm Motor Hp Motor Frame Size Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Nominal Fan Shaft Diameter (in.) Belt, Quantity...Type Belt, Length (in.) Pulley Center Line Distance (in.) Factory Speed Setting (rpm) HIGH-PRESSURE SWITCH (psig) Cutout Reset (Auto.) LOW-PRESSURE SWITCH (psig) Cutout Reset (Auto.) RETURN-AIR FILTERS Quantity...Size (in.) OUTDOOR-AIR FILTERS Quantity...Size (in.) POWER EXHAUST Motor, Quantity...Hp Fan, Diameter...Width (in.) 038 35 044 40 048 45 4282 4567 410 4508 4793 410 4795 5175 410 06D537 06D537 2 115 ea. 06EA250 06EA250 2 224 ea. R-22 06EA265 06EA250 2 304, 224 34-0 34-0 35-0 41-0 35-0 41-0 Cross-Hatched ⁄ 9 Copper Tubes, Aluminum Lanced or Copper Fins 2 2 1 1 3...15 3...15 4...15 3...15 58.3 58.3 66.7 Propeller Type 27,064 27,064 27,064 4...30 4...30 4...30 1 1 1 Cross-Hatched 3⁄89 Copper Tubes, Aluminum or Copper Plate Fins, Intertwined Circuits 3...15 3...15 4...15 34.7 34.7 34.7 Centrifugal Type 2..20x15 2...20x15 2...20x15 Belt Belt Belt 14,000 16,000 18,000 15†† 20 15 20†† 25 20 25†† 30 S254T S256T S254T S256T S284T S256T S284T S286T Ball Ball Ball 1200 1200 1200 6.9 7.5 6.9 8.1 9.1 5.3 5.9 7.5 15⁄8 15⁄8 15⁄8 15⁄8 11⁄8 15⁄8 17⁄8 17⁄8 12.5 12.5 12.5 13.7 13.7 9.1 9.1 11.1 111⁄16 111⁄16 111⁄16 1...5VX630 1...5VX650 1...5VX630 1...5VX670 2...5VX680 1...5VX550 2...5VX560 2...5VX610 63 65 63 67 68 55 56 59 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 14.6-17.6 14.6-17.6 966 1050 1066 1035 1162 1019 1135 1182 38 10 S215T 4.1 13⁄8 9.1 1...BX51 54 15.6-18.4 788 426 320 426 320 426 320 7 22 7 22 7 22 10...20x24x2 10...20x24x2 10..20x24x2 8...16x25 8...16x25 8...16x25 4...20x25 4...20x25 4...20x25 Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired For High Speed) and Forward Curved Fan 4...1 11...10 NOTES: 1. See Table 2 for optional evaporator fan motor data. 2. Sizes 038 and 048 are 50EJ,EW units only. LEGEND Al — Aluminum Cu — Copper *Weight of unit does not include variable frequency drive (VFD), barometric relief, or power exhaust. If a VAV unit (a VFD is installed), add the VFD weight in the table at right. †Evaporator coil fin material/condenser coil fin material. **Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils. ††Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more drive information, see Table 2. VFD (Hp) 10 VFD WEIGHTS (lb) 460 v 22 37 61 5 7.5 10 208/230 v 20 51 51 575 v 60 64 64 15 20 61 63 63 111 109 109 25 30 105 172 112 118 174 180 Table 2 — Evaporator Fan Motor Data UNIT SIZE 024 028 030 034 038 044 048 MOTOR HP MOTOR SHAFT DIAMETER (in.) FAN SHAFT SPEED (rpm) MOTOR SHEAVE 5 10 15 7.5 10 15 10 15 20 10 15 20 10 15 20 15 20 25 20 25 30 1.12 1.38 1.62 1.38 1.38 1.62 1.38 1.62 1.62 1.38 1.62 1.62 1.38 1.62 1.62 1.62 1.62 1.88 1.62 1.88 1.88 725 924 1088 773 962 1119 843 1056 1182 896 1088 1182 788 966 1050 966 1035 1162 1019 1135 1182 BK52 BK72 1B5V68 BK55H BK67H 1B5V70 BK72 1B5V66 1B5V74 BK70H 1B5V68 1B5V74 2BK47 1B5V68 1B5V74 1B5V68 1B5V80 1B5V90 2B5V52 2B5V58 2B5V76 MOTOR SHEAVE PITCH DIAMETER (in.) 4.6 6.6 6.9 4.9 6.1 7.1 6.6 6.7 7.5 6.4 6.9 7.5 4.1 6.9 7.5 6.9 8.1 9.1 5.3 5.9 7.5 BUSHING DIAMETER (in.) FAN SHEAVE None-1.125 None-1.375 B-1.625 H-1.375 H-1.375 B-1.625 None-1.375 B-1.625 B-1.625 H-1.375 B-1.625 B-1.625 None-1.375 B-1.625 B-1.625 B-1.625 B-1.625 B-1.875 B-1.625 B-1.875 B-1.875 1B5V110 1B5V124 1B5V110 1B5V110 1B5V110 1B5V110 1B5V136 1B5V110 1B5V110 1B5V124 1B5V110 1B5V110 2B5V90 1B5V124 1B5V124 1B5V124 1B5V136 1B5V136 2B5V90 2B5V90 2B5V110 FAN SHEAVE PITCH DIAMETER (in.) 11.1 12.5 11.1 11.1 11.1 11.1 13.7 11.1 11.1 12.5 11.1 11.1 9.1 12.5 12.5 12.5 13.7 13.7 9.1 9.1 11.1 BUSHING DIAMETER (in.) BELT OUTSIDE BELT LENGTH BELT TENSION (Lb @ .24 in.) B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 B-1.6875 BX59 BX60 5VX590 BX56 BX56 5VX590 BX62 5VX590 5VX600 BX60 5VX590 5VX600 BX51 5VX630 5VX650 5VX630 5VX670 5VX680 5VX550 5VX560 5VX610 62 63 59 59 59 59 65 59 60 63 59 60 54 63 65 63 67 68 55 56 59 5.02 7.05 9.38 6.87 7.26 9.17 6.96 9.60 11.67 7.20 9.38 11.17 5.49 9.22 10.02 9.54 10.37 10.88 7.93 8.66 9.07 NOTE: Motor shaft speed is 1750 rpm. The fan shaft diameter is 111⁄16 inches. ROOF MOUNT — Check building codes for weight distribution requirements. Step 3 — Field Fabricate Ductwork — Secure all ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. To attach ductwork to roof curb, insert ductwork approximately 10 to 11 in. up into the curb. Connect ductwork to 14-gage roof curb material using sheet metal screw driven from inside the duct. The units with electric heat require a 1-in. clearance for the first 24 in. of ductwork. NOTE: A 90-degree elbow must be provided in the ductwork to comply with UL (Underwriters’ Laboratories) codes for use with electric heat. Outlet grilles must not lie directly below unit discharge. Fig. 8 — Air Distribution — Thru-the-Bottom Step 4 — Make Unit Duct Connections 50EJ,EK UNITS — Unit is shipped for through-the-bottom duct connections. Ductwork openings are shown in Fig. 3 and 4. Attach all ductwork to roof curb. Air distribution is shown in Fig. 8. Refer to installation instructions shipped with accessory roof curb for more information. 50EW,EY UNITS — Remove shipping covers from supply and return air openings. Attach field-supplied ductwork to unit. Use a single duct over both return openings and a single duct over both supply openings. See Fig. 5 and 6 for duct opening dimensions. Secure all ducts to the building structure. See Fig. 9. Use flexible duct connectors between unit and ducts as required. Install accessory barometric relief or power exhaust in the field-fabricated return ductwork. Refer to Position Power Exhaust/Barometric Relief Damper Hood Section on page 29 for more information. Fig. 9 — Air Distribution — Thru-the-Side the drain location. One 1-in. FPT coupling is provided inside unit evaporator section for condensate drain connection. A trap at least 4-in. deep must be used. Trap must be installed to prevent freeze-up. Condensate pans are sloped so that water will completely drain from the condensate pan to comply with indoor air quality guidelines. Step 5 — Trap Condensate Drain — See Fig. 3-6 and 10 for drain location. Condensate drain is open to the atmosphere and must be trapped. Install a trapped drain at 11 • control of modulating economizer damper to provide free cooling when outdoor conditions are suitable, using supply air temperature as a control point • control of the economizer damper and indoor fan to obtain unoccupied free cooling • provide power exhaust output to an external power exhaust controller • support a field test for field checkout • control of 2 stages of CV power exhaust • compressor Time Guardt (power up and minimum off and on times) Additional features are provided by accessing the standard unit control board via software with a computer. These features are: • electronic expansion board features (if installed) • compressor lockout during low supply air temperature • control board diagnostics • ability to change supply air set point (economizer control) • ability to change high outdoor air temperature lockout set point (economizer control) • ability to change power exhaust set points NOTE: A CV unit without a thermostat requires a fieldsupplied sensor for operation. Fig. 10 — Condensate Drain Connections (Typical Roof Curb or Slab Mount Shown) Step 6 — Controls Options — The control options that the units can provide are based on the following parameters: CV (constant volume) or VAV (variable air volume) operation; stand-alone unit with field-supplied sensors installed (CV or VAV); as a system via the Carrier Comfort System (TEMP or VVT); optional electronic expansion board installed (CV or VAV); linked to the Carrier Comfort Network; and availability of a computer and software (Comfort Works, Building Supervisor, and Service Tool) to access the base control board. See Table 3. NOTE: Access to the base control board allows unit occupancy schedules, unit timeclock, and various set points to be changed from their factory-defined default settings. Features with Sensor Control of Unit (Stand-Alone Applications — Unit control is limited to CV unoccupied default set points, 90 F for cooling, 55 F for heating. There are 3 sensor options available: • T-57 sensor will monitor room temperature • T-55 sensor will monitor room temperature and provide unoccupied override capability (1 hour) • T-56 sensor will monitor room temperature, provide unoccupied override capability (1 hour), and provide a temperature offset of 5° F. Standard features are: • support of remote occupied/unoccupied input to start and stop the unit • cooling capacity control of 3 stages using economizer and 2 compressors to maintain space temperature to an occupied or unoccupied set point • enable heating (if installed) or cooling during unoccupied periods as required to maintain space temperature within the unoccupied set points • adjustment of space temperature set points of ± 5° F when using a T-56 sensor CONSTANT VOLUME APPLICATIONS — The standard CV unit is capable of being operated with either a Carrierapproved thermostat or a field-supplied sensor. (See Price Pages for ordering information.) Features with Thermostat Control of Unit • two-stage heating (if installed) • two-stage cooling • control of unit using Y1, Y2, W1, W2, and G thermostat inputs • control of the indoor fan • outdoor air temperature/supply air temperature monitoring • control of an outdoor air condenser fan based on outdoor air temperature Table 3 — Controls Options and Configurations (Non-Thermostat Applications) UNIT CONFIGURATION DEFAULT COOLING UNITS RUNNING VERSION 1.0 UNIT CONTROL SOFTWARE Unoccupied Cooling — 90 F (SPT) CV or VAV Unit with SPT Sensor Occupied Cooling — NA CV Unit with SPT Sensor and Remote Unoccupied Cooling — 90 F (SPT) Start/Stop Switch Occupied Cooling — 78 F (SPT) Unoccupied Cooling — NA VAV Unit Remote Start/Switch Only Occupied Cooling — 55 F (SAT) VAV Unit with SPT Sensor and Remote Unoccupied Cooling — 90 F (SPT) Start/Stop Switch Occupied Cooling — 55 F (SAT) UNITS RUNNING VERSION 2.0 UNIT CONTROL SOFTWARE Unoccupied Cooling — 90 F (SPT) CV or VAV Unit with SPT Sensor Occupied Cooling — NA CV Unit with SPT Sensor and Remote Unoccupied Cooling — 90 F (SPT) Start/Stop Switch Occupied Cooling — 78 F (SPT) Unoccupied Cooling — 90 F (RAT) VAV Unit Remote Start/Stop Switch Only Occupied Cooling — 55 F (SAT) VAV Unit with SPT Sensor and Remote Unoccupied Cooling — 90 F (SPT) Start/Stop Switch Occupied Cooling — 55 F (SAT) LEGEND CV — Constant Volume SAT — Supply-Air Temperature NA — Not Available SPT — Space Temperature RAT — Return-Air Temperature VAV — Variable Air Volume DEFAULT HEATING Unoccupied Heating Occupied Heating Unoccupied Heating Occupied Heating Unoccupied Heating Occupied Heating Unoccupied Heating Occupied Heating — 55 F (SPT) — NA — 55 F (SPT) — 68 F (SPT) — NA — NA — 55 F (SPT) — NA Unoccupied Heating Occupied Heating Unoccupied Heating Occupied Heating Unoccupied Heating Occupied Heating Unoccupied Heating Occupied Heating — 55 F (SPT) — NA — 55 F (SPT) — 68 F (SPT) — 55 F (RAT) — 68 F (RAT)* — 55 F (SPT) — 68 F (RAT)* *With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled). NOTE: Space temperature sensor and remote stop/switch are field-supplied. 12 or during unexpected power outages. For complete Carrier Comfort System (CCS) or Carrier Comfort Network (CCN) features and benefits, refer to the product literature. VARIABLE AIR VOLUME (VAV) APPLICATIONS Features with Stand-Alone Applications — A VAV unit is capable of providing unoccupied cooling controlling to a 90 F return-air temperature utilizing the factory-supplied returnair thermistor located below the return-air damper in the returnair section for unit control. The unit will provide unoccupied heating (if electric heat is installed) controlling to a 55 F return-air temperature. Also provided is a morning warm-up which is initiated by the Occupied mode (if electric heat is installed) and continues until the return-air temperature rises to 68 F. The unit will provide occupied cooling with a default temperature of 55 F for the supply air. The supply-air temperature is measured by the supply-air thermistor, located in the indoor fan compartment. Standard features of a VAV unit with a remote start/stop switch are: • control of an outdoor condenser fan based upon outdoor air temperature • control of modulating economizer to provide free cooling when outdoor conditions are suitable, using supply air temperature as a set point • support of remote occupied/unoccupied input to start or stop the unit • provide power exhaust output to an external power exhaust controller • support supply air temperature reset to offset supply air set point • support a field test for field check out • support linkage to DAV systems • cooling capacity control of 6 stages plus economizer with compressors and unloaders to maintain supply air temperature set point during occupied periods • control of one stage of heat to maintain supply air temperature at supply air set point during occupied periods • provide a variable frequency drive high voltage relay output to enable VFD • control of heat interlock relay With the addition of a remote start/stop switch heating or cooling is enabled during unoccupied periods as required to maintain space temperature to within unoccupied set points. Features with sensor control of unit with computer access are: • 365 day timeclock with backup (supports minute, hour, day of week, date, month, and year) • daylight savings time function • occupancy control with 8 periods for unit operation • holiday table containing up to 18 holiday schedules • ability to initiate timed override from T-55 or T-56 sensors • ability to use multiple space temperature sensors to average the space temperature • supply air temperature reset for the supply air temperature set point • temperature compensated start to calculate early start times before occupancy • access to the Display, Maintenance, Configuration, Service, and Set Point data table through network software When the unit is equipped with a field-supplied space temperature sensor and a remote contact closure (remote start/ stop) on the base control board, the occupied default set points will monitor unit operation. The occupied default set points are 78 F cooling and 68 F heating (if electric heat is installed). See Fig. 11 for remote start/stop wiring. NOTE: For units which have not had the base unit control board accessed via software to set an occupancy schedule, the remote start/stop closure will allow the unit to operate in the pre-configured occupied default set points (based on returnair temperature) of 78 F cooling and 68 F heating. Without this feature, the unit will control to the unoccupied default set points of 90 F cooling and 55 F heating (if electric heat is installed). An electronic expansion board may be field-installed to provide the following features: • control of modulating economizer damper to maintain indoor air quality (IAQ) when outdoor conditions are suitable • provide discrete inputs for fan status, filter status, fieldapplied status, and demand limit • provide an output for the external alarm light indicator When the unit is connected to the CCN (Carrier Comfort Network), the following expansion board features can be utilized. • perform Demand Limit functions based on CCN loadshed commands or the state of the discrete input • alarm monitoring of all key parameters • CCN protocol • provides power exhaust fire outputs for direct control of modulated power exhaust stages during fire or smoke modes • smoke control modes including evacuation, smoke purge, pressurization, and fire shutdown (modulating power exhaust required) • provides CCN IAQ participation See Carrier TEMP or VVTt (Variable Volume and Temperature) literature for complete TEMP (single zone) or VVT (multi-zone) application information. Features with Sensor Control of Unit (Network Applications) — The base control board provides, as standard, a connection for use with a Carrier VVT system and can also be integrated into a Carrier Comfort Network. When the unit is accessed via a PC equipped with Comfort Works, Building Supervisor, or Service Tool, the following features can be accessed: • on-board timeclock can be programmed • occupancy schedules can be programmed • unit set points can be changed • alarms can be monitored This access is available on the base control board via a RJ-11 phone jack or a 3-wire connection to the communication bus. See Fig. 12. The timeclock has a 10-hour minimum back-up time to provide for unit power off for servicing unit NOTE: On units running Version 1.0 of the Unit Control Software, the remote start/stop switch is connected to R and Y1. On units running Version 2.0 of the Unit Control Software, the remote start/stop switch is connected to R and W1. Fig. 11 — Field Control Remote Start/Stop 13 14 Fig. 12 — Control Board Diagram CCN — COM — D — N.C. — N.O. — *Where X LEGEND Carrier Comfort Network R — Common SIO — Diode SW — Normally Closed T — Normally Open is the unit control software version (1 or 2). Relay Serial Input/Output Switch Terminal an occupancy schedule, the unit will control to the unoccupied default set points of 90 F (return air) cooling and 55 F (return air) heating (if electric heat is installed). Features with Network Applications — The base control board provides, as standard, a connection for use with a Carrier Comfort System and can also be integrated into a Carrier Comfort Network. When the unit is accessed via a PC equipped with Comfort Works, Building Supervisor, or Service Tool software, the following features can be accessed: • on-board timeclock can be programmed • occupancy schedules can be programmed • unit set points can be changed • alarms can be monitored This access is available on the base control board via a RJ-11 phone jack or a 3-wire connection to the communication bus. See Fig. 12. The timeclock has a 10-hour minimum back-up time to provide for unit power off for servicing unit or during unexpected power outages. For complete Carrier Comfort System (CCS) or Carrier Comfort Network (CCN) features and benefits, refer to the product literature. For units running Version 1.0 of the unit control software, network access software is required to enable occupied heating. For units running Version 2.0 of the unit control software, occupied heating is enabled or disabled by the position of DIP switch no. 5. Additional features may be provided with electronic access to Unit Control Board. These features are: • control board diagnostics • compressor time guard override (power up, minimum off and on times) • compressor lockout during low supply-air temperature • electronic expansion board features (if installed) • field test capability • control of the economizer damper and indoor fan to option unoccupied free cooling • 365 day timeclock with backup (supports minute, hour, day, month, and year) • holiday table containing up to 18 holiday schedules • occupancy control with 8 periods for unit operation • support a set of display, maintenance, configuration, service, and set point data tables for interface with Building Supervisor, Comfort Works, or Service Tool When a VAV unit with a space temperature sensor is accessed via a computer, the following additional features are available: • ability to initiate timed override from T-55 sensors • ability to use multiple space temperature sensors to average space temperature • temperature compensated start to calculate early start time before occupancy • provide space temperature reset to reset the supply air set point upward when the temperature falls below the occupied cooling set point An electronic expansion board may be field-installed to provide the following features: • fan status • filter status • field-applied status • demand limiting • IAQ sensor • OAQ sensor • alarm light When the unit is connected to the CCN (Carrier Comfort Network), the following expansion board features can be utilized: • CCN IAQ (indoor air quality) participation • CCN OAQ (outdoor air quality) participation • CCN demand limit participation • fire unit shutdown • fire pressurization • fire evacuation • fire smoke purge • modulated power exhaust override A field-supplied space temperature sensor can be added to provide the following: • T-57 sensor will monitor room temperature • T-55 sensor will monitor room temperature and provide unoccupied override capability (1 hour) When the unit is equipped with a field-supplied space temperature sensor and a remote contact closure (remote start/ stop), the occupied default set points will monitor unit operation. The occupied default set points are 55 F (supply air) cooling and 68 F (space temperature) heating (if electric heat is installed). See Fig. 11 for remote start/stop wiring. NOTE: For units without a space temperature sensor and which have not had the base unit control board accessed via software to set an occupancy schedule, the remote start/stop closure will allow the unit to operate in the pre-configured occupied default set points of 55 F (supply-air temperature) cooling and 68 F (return-air temperature) heating. Without Step 7 — Make Electrical Connections POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate. The main terminal block is suitable for use with aluminum or copper wires and is sized for single-point electric heat. When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (MOCP [maximum overcurrent protection] of unit is on the informative plate). All field wiring must comply with NEC and all local codes. Size wire based on MCA (minimum circuit amps) on the unit informative plate. See Fig. 13 for power wiring connections to the unit power terminal block and equipment ground. The main power terminal block is suitable for use with aluminum or copper wire. See Fig. 13. Units have circuit breakers for compressors, fan motors, and control circuit. If required by local codes, provide an additional disconnect, per NEC and local codes requirements, of adequate size (Table 4). Whenever external electrical sources are used, unit must be electrically grounded in accordance with local codes, or in absence of local codes, with NEC, ANSI (American National Standards Institute) C1-latest year. All field wiring must comply with NEC and local code requirements. FIELD POWER SUPPLY — Unit is factory wired for voltage shown on nameplate. See Table 4 for electrical data. Field wiring can be brought into the unit from bottom (through basepan and roof curb) or through side of unit (corner post next to control box). LEGEND EQUIP — Equipment GND — Ground NEC — National Electrical Code TB — Terminal Block NOTE: Maximum wire size for TB1 is 500 MCM. Fig. 13 — Field Power Wiring Connections 15 A 31⁄2-in. NPT coupling for field power wiring and a ⁄ -in. NPT coupling for 24-v control wiring are provided in basepan. In the side post, there are two 21⁄2-in. (024-034) or 3-in. (038-048) knockouts for the field power wiring. See Fig. 3-6. If control wiring is to be brought in through the side of unit, a 7⁄8-in. diameter hole is provided in the condenser side post next to the control box. If disconnect box is mounted to corner post, be careful not to drill any screws into the condenser coil. Routing Through Bottom of Unit — If wiring is brought in through bottom of unit, use field-supplied watertight conduit to run power wiring from basepan out through bottom 31⁄2-in. hole to the disconnect box and back into unit to the main control box. Use strain relief going into control box through 21⁄2-in. diameter hole provided. After wires are in unit control box, connect to power terminal block (see Power Wiring section on this page 15). Low-voltage wiring must be run in watertight conduit from the basepan to control box and through 7⁄8-in. diameter hole provided in bottom of unit control box. Field-supplied strain relief must be used going into the box. After wiring is in control box, make connections to proper terminals on terminal blocks (see Field Control Wiring section on this page). Install conduit connector in unit basepan or side panel openings provided. Route power and ground lines through connector to connections in unit control box as shown on unit wiring diagram and Fig. 13. Routing Through Side of Unit — Route power wiring in field-supplied watertight conduit into unit through 21⁄2- or 3-in. hole. Strain relief (field supplied) must be used in hole. See Fig. 13. Use field-supplied strain relief going into control box through 21⁄2- or 3-in. diameter hole provided. After wires are in unit control box, connect to power terminal block (see Power Wiring section on page 15). Bring low-voltage control wiring through factory-drilled 7⁄8-in. diameter hole in condenser side post. Use strain relief going into 7⁄8-in. diameter hole in bottom of unit control box. After wiring is in control box, make connection to proper terminals on terminal blocks (see Field Control Wiring section on this page). IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 34 Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. On 208/230-v units, transformer no. 1 is wired for 230-v. If 208/230-v unit is to be run with 208-v power supply, the transformer must be rewired as follows: 1. Remove cap from red (208-v) wire. 2. Remove cap from spliced orange (230-v) wire. Disconnect orange wire from black unit power wire. 3. Cap orange wire. 4. Splice red wire and black unit power wire. Cap wires. IMPORTANT: Be certain unused wires are capped. Failure to do so may damage the transformers. FIELD CONTROL WIRING — Install either a Carrierapproved accessory thermostat or a CCN (Carrier Comfort Network) compatible temperature sensor. Thermostats are used on CV (constant volume) units only. Control box diagrams are shown in Fig. 14 and 15. Thermostat Wiring (CV Only) — Install a Carrier-approved accessory thermostat assembly (per current price pages) according to the installation instructions included with the accessory or these instructions. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature. Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections as shown on unit label wiring diagram and in Fig. 16. NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. Set heat anticipators settings to 0.1 for all voltages. Settings may be changed slightly to provide a greater degree of comfort for a particular installation. Sensor Wiring (CV or VAV) — The temperature sensor is wired into the unit control board. See Fig. 17. The unit is controlled with a T55, T56 (CV only), or T57 zone sensor. Terminal TH on the sensor is connected to T1 of the base module board. Terminal COM on the sensor is connected to T2 on the base module board. If a T56 set point override sensor is used, the override connection SW on the sensor is connected to T3 on the base module board. VAV units using Version 1.0 of the unit control software may operate without a space temperature sensor during occupied schedules, but unit will not provide unoccupied heating or cooling. VAV Units — VAV units require a field-supplied heat interlock relay (HIR) to drive the air terminal wide open when in heat mode. The HIR part number is HN61KK041. Remote Field Control (Units Running Version 1.0 of Unit Control Software) — A switch closure across terminals R and Y1 on TB-3 will initiate the Occupied mode. This can be done manually as well as through a field-supplied timeclock. IMPORTANT: THE VAV (variable air volume) units incorporate VFD (variable frequency drives) which generate, use, and can radiate radio frequency energy. If units are not installed and used in accordance with these instructions, they may cause radio interference. They have been tested and found to comply with limits of a Class A computing device as defined by FCC (Federal Communications Commission) regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment. The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association). Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2% and the current must be balanced within 10%. Use the formula in Table 4 to determine the percentage of voltage imbalance. 16 Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 UNIT SIZE NOMINAL VOLTAGE (3 Ph 60 Hz) 208/230 024 460 575 FLA HACR IFM LRA MCA MOCP NEC OFM RLA — — — — — — — — — VOLTAGE RANGE Min 187 414 518 Max 254 508 632 COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 39.1 19.9 16.0 228 114 91 25.6 11.5 9.6 160 80 64 OFM Qty 2 2 2 Hp 1 1 1 FLA (ea) 5.3 2.7 2.4 FLA 5 16.7/ 15.2 10 30.8/ 28.0 15 46.2/ 42.0 5 7.6 10 14 15 21 5 6.1 10 11 15 17 FLA — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 LRA — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 ELECTRIC HEAT* kW — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 FLA — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 POWER SUPPLY MCA 101.8/100.3 125.4/123.9 114.7/127.3 144.2/156.8 171.0/192.2 200.5/221.7 115.9/113.1 139.5/136.7 132.3/143.3 161.8/172.8 188.6/208.2 218.1/237.7 131.3/127.1 154.9/150.7 151.6/160.8 181.1/190.3 207.9/225.7 237.4/255.2 49.4 62.0 63.6 79.4 96.1 111.9 55.8 68.4 71.6 87.4 104.1 119.9 62.8 75.4 80.4 96.1 112.9 128.6 40.5 53.1 50.9 66.7 76.9 92.7 45.4 58.0 57.1 72.8 83.0 98.8 51.4 64.0 64.6 80.3 90.5 106.3 MOCP† 125/125 150/150 125/150 150/175 200/225 225/225 150/150 175/175 150/150 175/175 220/225 250/250 150/150 175/175 175/175 200/200 250/250 275/275 60 80 70 80 110 125 70 80 80 90 110 125 80 90 90 100 125 150 50 60 60 70 80 100 60 70 60 80 90 100 60 80 70 90 100 110 deviation from average voltage. 5v 7v 2v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. *Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. †Fuse or HACR circuit breaker. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage % Voltage Imbalance = 100 x average voltage 3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA). 452 + 464 + 455 3 = Hp Determine maximum (AB) 457 − 452 = (BC) 464 − 457 = (AC) 457 − 455 = LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps EXAMPLE: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = POWER EXHAUST IFM 1371 3 = 457 17 Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont) UNIT SIZE NOMINAL VOLTAGE (3 Ph 60 Hz) 208/230 028 460 575 VOLTAGE RANGE Min 187 414 518 Max 254 508 632 COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 39.1 19.9 16.0 228 114 91 39.1 19.9 16.0 228 114 91 OFM Qty 2 2 2 Hp 1 1 1 POWER EXHAUST IFM FLA (ea) 5.3 2.7 2.4 18 Hp FLA 7.5 24.2/ 22.0 10 30.8/ 28.0 15 46.2/ 42.0 7.5 11 10 14 15 21 7.5 9 10 11 15 17 FLA — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 LRA — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 ELECTRIC HEAT* kW — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 FLA — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 POWER SUPPLY MCA 122.8/120.6 146.4/144.2 124.1/135.8 153.6/165.3 180.4/200.7 209.9/230.2 129.4/126.6 153.0/150.2 132.3/143.3 161.8/172.8 188.6/208.2 218.1/237.7 144.8/140.6 168.4/164.2 151.6/160.8 181.1/190.3 207.9/225.7 237.4/255.2 61.2 73.8 67.9 83.6 100.4 116.1 64.2 76.8 71.6 87.4 104.1 119.9 71.2 83.8 80.4 96.1 112.9 128.6 49.8 62.4 54.6 70.3 80.5 96.3 51.8 64.4 57.1 72.8 83.0 98.8 57.8 70.4 64.6 80.3 90.5 106.3 MOCP† 150/150 175/175 150/150 175/175 200/225 225/250 150/150 175/175 150/150 175/175 200/225 225/250 175/175 200/200 175/175 200/200 250/250 275/275 80 90 70 90 110 125 80 90 80 90 110 125 90 100 90 100 125 150 60 70 60 80 90 100 60 80 60 80 90 100 70 80 70 90 100 110 Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont) UNIT SIZE NOMINAL VOLTAGE (3 Ph 60 Hz) 208/230 030 460 575 FLA HACR IFM LRA MCA MOCP NEC OFM RLA — — — — — — — — — VOLTAGE RANGE Min 187 414 518 Max 254 508 632 COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 57.1 25.6 20.5 266 120 96 39.1 19.9 16.0 228 114 91 OFM Qty 2 2 2 Hp 1 1 1 FLA (ea) 5.3 2.7 2.4 FLA 10 30.8/ 28.0 15 46.2/ 42.0 20 59.4/ 54.0 10 14 15 21 20 27 10 11 15 17 20 22 FLA — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 − 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 LRA — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 ELECTRIC HEAT* kW — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 FLA — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.2/173.2 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 POWER SUPPLY MCA 151.9/149.1 175.5/172.7 151.9/149.1 175.5/172.8 188.6/208.2 218.1/237.7 167.3/163.1 190.9/186.7 167.3/163.1 190.9/186.7 207.9/225.7 237.4/255.2 180.5/175.1 204.1/198.7 180.5/175.1 204.1/198.7 224.4/240.7 253.9/270.2 71.3 83.9 71.6 87.4 104.1 119.9 78.3 90.9 80.4 96.1 112.9 128.6 84.3 96.9 87.9 103.6 120.4 136.1 57.4 70.0 57.4 72.8 83.0 98.8 63.4 76.0 64.6 80.3 90.5 106.3 68.4 81.0 70.8 86.6 96.8 112.5 MOCP† 200/200 225/225 200/200 225/225 200/225 225/250 200/200 225/225 200/200 225/225 250/250 275/275 225/225 250/250 225/225 250/250 275/275 300/300 90 100 90 100 110 125 100 110 100 110 125 150 100 110 100 110 125 150 70 90 70 90 90 100 80 90 80 90 100 110 80 100 80 100 110 125 deviation from average voltage. 5v 7v 2v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. *Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. †Fuse or HACR circuit breaker. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage % Voltage Imbalance = 100 x average voltage 3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA). 452 + 464 + 455 3 = Hp Determine maximum (AB) 457 − 452 = (BC) 464 − 457 = (AC) 457 − 455 = LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps EXAMPLE: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = POWER EXHAUST IFM 1371 3 = 457 19 Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont) UNIT SIZE NOMINAL VOLTAGE (3 Ph 60 Hz) 208/230 034 460 575 VOLTAGE RANGE Min 187 414 518 Max 254 508 632 COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 57.1 25.6 20.5 266 120 96 57.1 25.6 20.5 266 120 96 OFM Qty 2 2 2 Hp 1 1 1 POWER EXHAUST IFM FLA (ea) 5.3 2.7 2.4 20 Hp FLA 10 30.8/ 28.0 15 46.2/ 42.0 20 59.4/ 54.0 10 14 15 21 20 27 10 11 15 17 20 22 FLA — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 LRA — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 ELECTRIC HEAT* kW — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 FLA — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 POWER SUPPLY MCA 169.9/167.1 193.5/190.7 169.9/167.1 193.5/190.7 188.6/208.2 218.1/237.7 185.3/181.1 208.9/204.7 185.3/181.1 208.9/204.7 207.9/225.7 237.4/255.2 198.5/193.1 222.1/216.7 198.5/193.1 222.1/216.7 224.4/240.7 253.9/270.2 77.0 89.6 77.0 89.6 104.1 119.9 84.0 96.6 84.0 96.6 112.9 128.6 90.0 102.6 90.0 103.6 120.4 136.1 61.9 74.5 61.9 74.5 83.0 98.8 67.9 80.5 67.9 80.5 90.5 106.3 72.9 85.5 72.9 86.6 96.8 112.5 MOCP† 225/200 250/225 225/200 250/225 225/225 250/250 225/225 250/250 225/225 250/250 250/250 275/275 250/250 275/250 250/250 275/250 275/275 300/300 100 110 100 110 110 125 100 110 100 110 125 150 110 125 110 125 125 150 80 90 70 90 90 100 80 100 80 100 100 110 90 100 90 100 110 125 Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont) UNIT SIZE NOMINAL VOLTAGE (3 Ph 60 Hz) 208/230 038 460 575 FLA HACR IFM LRA MCA MOCP NEC OFM RLA — — — — — — — — — VOLTAGE RANGE Min 187 414 518 Max 254 508 632 COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 57.1 25.6 20.5 266 120 96 57.1 25.6 20.5 266 120 96 OFM Qty 4 4 4 Hp 1 1 1 FLA (ea) 5.3 2.7 2.4 FLA 10 30.8/ 28.0 15 46.2/ 42.0 20 59.4/ 54.0 10 14 15 21 20 27 10 11 15 17 20 22 FLA — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 LRA — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 ELECTRIC HEAT* kW — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 FLA — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 POWER SUPPLY MCA 180.5/177.7 204.1/201.3 180.5/177.7 204.1/201.3 188.6/208.2 218.1/237.7 195.9/191.7 219.5/215.3 195.9/191.7 219.5/215.3 207.9/225.7 237.4/255.2 209.1/203.7 232.7/227.3 209.1/203.7 232.7/227.3 224.4/240.7 253.9/270.2 82.4 95.0 82.4 95.0 104.1 119.9 89.4 102.0 89.4 102.0 112.9 128.6 95.4 108.0 95.4 108.0 120.4 136.1 66.7 79.3 66.7 79.3 83.0 98.8 72.7 85.3 72.7 85.3 90.5 106.3 77.7 90.3 77.7 90.3 96.8 112.5 MOCP† 225/225 250/250 225/225 250/250 225/225 250/250 250/225 275/250 250/225 275/250 250/250 275/275 250/250 275/275 250/250 275/275 275/275 300/300 100 110 100 110 110 125 110 125 110 125 125 150 110 125 110 125 125 150 80 90 80 90 90 100 90 100 80 100 100 110 90 110 90 110 110 125 deviation from average voltage. 5v 7v 2v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. *Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. †Fuse or HACR circuit breaker. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage % Voltage Imbalance = 100 x average voltage 3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA). 452 + 464 + 455 3 = Hp Determine maximum (AB) 457 − 452 = (BC) 464 − 457 = (AC) 457 − 455 = LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps EXAMPLE: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = POWER EXHAUST IFM 1371 3 = 457 21 Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont) UNIT SIZE NOMINAL VOLTAGE (3 Ph 60 Hz) 208/230 044 460 575 VOLTAGE RANGE Min 187 414 518 Max 254 508 632 COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 69.2 28.8 26.7 345 173 120 69.2 28.8 26.7 345 173 120 OFM Qty 4 4 4 Hp 1 1 1 IFM FLA (ea) 5.3 2.7 2.4 22 Hp FLA 15 46.2/ 42.0 20 59.4/ 54.0 25 74.8/ 68.0 15 21 20 27 25 34 15 17 20 22 25 27 POWER EXHAUST FLA — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 − 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 LRA — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 ELECTRIC HEAT* kW — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 FLA — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.2/173.2 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 POWER SUPPLY MCA 223.1/218.9 246.7/242.5 223.1/218.9 246.7/242.5 223.1/225.7 246.7/255.2 236.3/230.9 259.9/254.5 236.3/230.9 259.9/254.5 236.3/240.7 259.9/270.2 251.7/244.9 275.3/268.5 251.7/244.9 275.3/268.5 251.7/258.2 275.3/287.7 96.6 109.2 96.6 109.2 112.9 128.6 102.6 115.2 102.6 115.2 120.4 136.1 109.6 122.2 109.6 122.2 129.1 144.9 86.7 99.3 86.7 99.3 91.4 106.3 91.7 104.3 91.7 104.3 96.8 112.5 96.7 109.3 96.7 109.3 103.0 118.8 MOCP† 275/275 300/300 275/275 300/300 275/275 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 125 125 125 125 125 150 125 125 125 125 150 150 125 150 125 150 150 175 110 125 110 125 110 125 110 125 110 125 125 125 110 125 110 125 125 125 Table 3 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont) UNIT SIZE NOMINAL VOLTAGE (3 Ph 60 Hz) 208/230 048 460 575 FLA HACR IFM LRA MCA MOCP NEC OFM RLA — — — — — — — — — VOLTAGE RANGE Min 187 414 518 Max 254 508 632 COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 82.1 42.3 34.6 446 223 164 69.2 28.8 26.7 345 173 120 OFM Qty 4 4 4 Hp 1 1 1 IFM FLA (ea) 5.3 2.7 2.4 20 59.4/ 54.0 25 74.8/ 68.0 30 88.0/ 80.0 20 27 25 34 30 40 20 22 25 27 30 32 FLA — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 − 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 — 12.6 LRA — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 41.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 — 23.6 ELECTRIC HEAT* kW — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 29/36 29/36 59/72 59/72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 — — 36 36 72 72 FLA — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.1/173.2 — — 75.1/ 86.6 75.1/ 86.6 150.1/173.2 150.2/173.2 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 43.3 43.3 86.6 86.6 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 — — 34.6 34.6 69.3 69.3 POWER SUPPLY MCA 252.4/247.0 276.0/270.6 252.4/247.0 276.0/270.6 252.4/247.0 276.0/270.6 267.8/261.0 291.4/284.6 267.8/261.0 291.4/284.6 267.8/261.0 291.4/284.6 281.0/273.0 304.6/296.6 281.0/273.0 304.6/296.6 281.0/273.0 304.6/296.6 119.5 132.1 119.5 132.1 120.4 136.1 126.5 139.1 126.5 139.1 129.1 144.9 132.5 145.1 132.5 145.1 136.6 152.4 101.6 114.2 101.6 114.2 101.6 114.2 106.6 119.2 106.6 119.2 106.6 119.2 111.6 124.2 111.6 124.2 111.6 124.2 MOCP† 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 300/300 350/300 300/300 350/300 300/300 350/300 150 150 150 150 150 150 150 175 150 175 150 175 150 175 150 175 175 175 125 125 125 125 125 125 125 150 125 150 125 150 125 150 125 150 125 150 deviation from average voltage. 5v 7v 2v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. *Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. †Fuse or HACR circuit breaker. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage % Voltage Imbalance = 100 x average voltage 3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA). 452 + 464 + 455 3 = FLA Determine maximum (AB) 457 − 452 = (BC) 464 − 457 = (AC) 457 − 455 = LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps EXAMPLE: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = Hp POWER EXHAUST 1371 3 = 457 23 DIP — Dual In-Line Package PEC − Power Exhaust Controller Fig. 14 — Control Box Diagram (Sizes 024-034) DIP — Dual In-Line Package PEC — Power Exhaust Controller Fig. 15 — Control Box Diagram (Sizes 038-048) 24 Conductors and drain wire must be 20 AWG minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of −20 C to 60 C (−4 F to 140 F) is required. Table 5 lists cables that meet the requirements. NOTE: On units running Version 1.0 of the unit control software, the remote start/ stop switch is connected to R and Y1. Table 5 — CCN Connection Approved Shielded Cables MANUFACTURER Alpha American Belden Columbia CABLE PART NO. 2413 or 5463 A22503 8772 02525 IMPORTANT: When connecting the CCN communication bus to a system element, use a color coding system for the entire network to simplify installation and checkout. See Table 6. Fig. 16 — Field Control Thermostat Wiring Table 6 — Color Code Recommendations SIGNAL TYPE Positive (+) Ground Negative (−) NOTE: Sensor part numbers are as follows: T55 — HH51BX001 T56 — HH51BX004 T57 — CEC01215303-01 CCN BUS CONDUCTOR INSULATION COLOR RED WHITE BLACK CCN PLUG PIN NO. 1 2 3 NOTE: If a cable with a different color scheme is selected, a similar color code should be adopted for the entire network. At each system element, the shields of the communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network: 1. Turn off power to the control box. 2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (−) conductors. (If a different network color scheme is used, substitute appropriate colors.) 3. Remove the 3-pin male plug from the base module in the main control box, and connect the wires as follows: a. Insert and secure the red (+) wire to terminal 1 of the 3-pin plug. b. Insert and secure the white (ground) wire to terminal 2 of the 3-pin plug. c. Insert and secure the black (−) wire to terminal 3 of the 3-pin plug. 4. Insert the plug into the existing 3-pin mating connector on the base module in the main control box. Fig. 17 — Field Control Temperature Sensor Wiring Remote Field Control (Units Running Version 2.0 of Unit Control Software) — A switch closure across terminals R and W1 on TB-3 will initiate the Occupied mode. This can be done manually as well as through a field-supplied timeclock. Service Tool, Building Supervisor, and Comfort Works — Access to the control board can be achieved through the terminal marked CCN via a 3-wire bus. IMPORTANT: Default bus address is 0. Default element number is 1. Refer to CCN literature for information on network addressing or changing CCN communication defaults. Step 8 — Make Outdoor-Air Inlet Adjustments ECONOMIZER NOTE: If accessory power exhaust or barometric relief packages are being added to the unit, install power exhaust or barometric relief before installing economizer hoods. Economizer Hood Assembly — The economizer hood is shipped in a package secured to the outside of the unit and must be field-assembled. There are 2 hoods on every unit. The 50EW/EY units are side supply and side return. The return duct limits access to economizer filters from below. Filter tracks (mounting angle without tabs) must be installed correctly to allow access to economizer filters from each side. Perform the following procedure to assemble the economizer hood. Carrier Comfort Network Interface — The 50E units can be connected to the CCN. The communication bus wiring is supplied and installed in the field. Wiring consists of shielded, 3-conductor cable with drain wire. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it, the negative pins must be wired to the negative pins, and the signal pins must be wired to signal ground pins. Wiring connections for CCN should be made at the 3-pin plug (CCN located at the base board. Consult CCN literature for further information. 25 NOTE: Before assembly of the economizer hood, check along the outer edges of the economizer assembly for any seal strip protruding past the flanges. Trim the excess seal strip so that it is flush with the economizer assembly flanges. 1. Apply black seal strip (provided in package) to outside top-edge of hood sides. Wrap seal strip over edge to cover top flange (4 hood sides). Make sure seal strip covers screw holes. Allow strip to overhang 1⁄8-in. past the end opposite the mounting flange. See Fig. 18. 2. Assemble hood sides, top, and cross member with gasketed screws provided. See Fig. 19. 3. Attach 10 green speed clips (provided) to hood top. 4. Apply black seal strip (provided) to mounting flanges of hood sides being sure to cover mounting holes. See Fig. 20. NOTE: Each hood assembly has a slotted side that should be adjacent to the other hood when mounted to the unit. 5. Apply black seal strip (provided) to hood top mounting flange. Seal strip of hood top mounting flange must press tightly against seal strip of hood side mounting flanges. See Fig. 21. 6. Add gray foam strip (provided in package) to cross members on bottom tray. See Fig. 22. 7. Place gray foam strip (provided) on inside of slotted hood side between filter and cross member opposite the mounting end. See Fig. 23. 8. Attach gray foam strip (provided) to block-off baffle on outer face of flange. See Fig. 24. 9. Remove the screws on each end and along top of damper assembly of unit. Remove top 2 screws on each side of filter panel under damper assembly. Set hood assembly in place and attach to unit using these screws. 10. Attach accessory enthalpy bracket on hood side furthest from control box end. Locate bracket on inside upper right-hand corner of economizer hood using hood mounting holes. Mount outdoor-air thermistor to enthalpy bracket (if purchased). Attach and wire enthalpy assembly. Place quick connects on enthalpy wires. 11. Remove screws along bottom of damper assembly. Locate and mount blockoff baffle using these screws. 12. Assemble 2 filter tracks side-by-side with the assembled ends together. 13. Attach mounting angle (without tabs) to the assembled end of the filter track. See Fig. 25. 14. Attach 6 green speed clips (provided) to mounting angles. Engagement section of clip faces inside of rack. NOTE: Left side economizer hood has mounting angle without tabs and filter track assembled end on the opposite side. Fig. 19 — Economizer Hood Assembly (Right-Side Economizer Hood Shown) MOUNTING FLANGE HOOD SIDE Fig. 20 — Adding Seal Strip to Mounting Flange of Hood Sides 15. Attach remaining mounting angle (with tabs) to other end of the filter track with no. 10 screws provided. See Fig. 26. 16. Place filter track assembly in bottom of hood by placing tabbed end into slotted side (with tab on bottom) and attaching opposite end to hood with speed clips and gasketed screws provided. Tabs can be hand bent after they have been inserted into the side. NOTE: The filter track assembly end with screws should face away from the other hood when mounted on the unit. NOTE: Tabs from both filter tracks will be in the same space. After one filter track has been inserted into board, bend the tabs so they will not interfere with installation of the second hood. 17. Attach black seal strip (provided) to filter cover. Seal strip should be applied to the center of the large flange making sure to cover holes. See Fig. 27. 18. Slide two 20 x 25-in. filters into cross members of hood assembly. Attach filter cover over filters with screws and speed clips provided. TOP FLANGE BLACK SEAL STRIP HOOD SIDE Fig. 18 — Adding Seal Strip to Top of Hood Sides 26 HOOD TOP HOOD SIDE BLOCKOFF BAFFLE Fig. 21 — Adding Seal Strip to Hood Top Mounting Flange GRAY FOAM STRIP GRAY FOAM STRIP Fig. 24 — Adding Foam Strip to Blockoff Baffle CROSS MEMBER MOUNTING ANGLE (WITHOUT TABS) FILTER TRACK ASSEMBLY Fig. 25 — Mounting Angle (Without Tabs) Attached to Filter Track Assembly Fig. 22 — Adding Foam Strip to Cross Member HOOD SIDE (SLOTTED) HOOD TOP MOUNTING ANGLE (WITH TABS) Fig. 26 — Mounting Angle (With Tabs) Attached to Filter Track Assembly Fig. 23 — Adding Foam Strip to Hood Side 27 position to go to 10% for 30 seconds, then 20% for 30 seconds, and when it reaches 30% close DIP switch no. 6 during the 30-second period following the 30% position. The minimum outdoor air damper position is now set. ECONOMIZER SETTINGS Accessory Enthalpy Control (Fig. 28) — The control (HH57AC077) is mounted in the economizer hood. See Fig. 19. The enthalpy setting adjustment is on the enthalpy control. For maximum benefit of outdoor air, set enthalpy control to A. See Fig. 29 and 30. Accessory Differential Enthalpy Control — The control (HH57AC077), in conjunction with the accessory enthalpy sensor (HH57AC078), controls economizer operation according to the differential enthalpy. The control is mounted in the economizer hood. The sensor is mounted in the return duct (50EJ/EK) or return air plenum (50EW/EY). Minimum Damper Position Setting — Setting of the outdoor air damper position is performed in conjunction with a shortened version of the field-run test. This is performed by first opening DIP (Dual In-Line Package) switch no. 6 then no. 4. See Fig. 17 and Table 7. The outdoor-air damper closes. The control allows 90 seconds for the damper to close in case it is in the full open position. Next, the indoor-fan contactor will energize. The outdoor-air damper will remain at 0% for 30 seconds. It will then move to the 10% position for another 30 seconds. This will be repeated at every 10% increment for 30 seconds until the damper reaches 100% open. Close DIP switch no. 6 during the 30 seconds immediately after the desired outdoor air minimum damper position. The 30-second time period is to allow time where DIP switch no. 6 can be closed. The default value of the minimum outdoor air damper position is 20%. If the desired minimum position is 30%, allow the damper BLACK SEAL STRIP (CENTERED) FILTER COVER NOTE: Switches shown in high enthalpy state. Terminals 2 and 3 close on enthalpy decrease. Fig. 29 — Wire Connections for Solid State Enthalpy Control (HH57AC077) POINT CONTROL CONTROL (APPROX. DEG.) CURVE AT 50% RH A 73 (23) B 70 (21) C 67 (19) D 63 (17) Fig. 27 — Attaching Seal Strip to Filter Cover HH57AC077 ENTHALPY CONTROL C7400 A1004 + HH57AC078 ENTHALPY SENSOR (USED WITH ENTHALPY CONTROL FOR DIFFERENTIAL ENTHALPY OPERATION) RH — Relative Humidity Fig. 28 — Differential Enthalpy Control and Sensor Fig. 30 — Psychrometric Chart for Enthalpy Control 28 4. With screws saved from Step 1, install brackets on each side of damper assembly. 5. Remove tape from damper blades. VAV DUCT PRESSURE TRANSDUCER — The VAV duct pressure transducer (VAV inverter pressure transducer) is located behind the filter access door on the lower inner panel. See Fig. 32. A section of 1⁄4-in. plastic tubing must be run from the high-pressure tap on the differential pressure switch and connected to a tap in the supply-air duct. The tap is usually located 2⁄3 of the way out on the main supply duct. Remove plug button in panel to route tubing. Step 9 — Position Power Exhaust/Barometric Relief Damper Hood — All electrical connections have been made and adjusted at the factory. The power exhaust blowers and barometric relief dampers are shipped assembled and tilted back into the unit for shipping. Brackets and extra screws are shipped in shrink wrap around the dampers. If ordered, each unit will have 4 power exhaust blowers and motors or 4 barometric relief dampers. 1. Remove 9 screws holding each damper assembly in place. See Fig. 31. Each damper assembly is secured with 3 screws on each side and 3 screws along the bottom. Save screws. 2. Pivot each damper assembly outward until edges of damper assembly rest against inside wall of unit. VAV BUILDING PRESSURE TRANSDUCER — The VAV building pressure transducer (modulating power exhaust pressure transducer) is located behind the filter access door on the inner panel. See Fig. 32. A section of 1⁄4-in. plastic tubing must be run from the high-pressure tap on the differential pressure switch to the conditioned space. The pressure tube must be terminated in the conditioned space where a constant pressure is required. This location is usually in an entrance lobby so that the building exterior doors will open and close properly. Remove plug button in panel to route tubing. Be careful when tilting blower assembly. Hoods and blowers are heavy and can cause injury if dropped. 3. Secure each damper assembly to unit with 6 screws across top (3 screws provided) and bottom (3 screws from Step 1) of damper. NOTES: 1. Unless otherwise specified, all dimensions are to outside of part. 2. Dimensions are in inches. Fig. 31 — Barometric Relief Damper and Power Exhaust Mounting Details 29 Fig. 33A — Motormaster III Sensor Location (Sizes 024-034) VAV — Variable Air Volume Fig. 32 — Pressure Transducer Locations Step 10 — Install Accessories — After all the factoryinstalled options have been adjusted, install all fieldinstalled accessories. Refer to the accessory installation instructions included with each accessory. MOTORMASTERt III SENSOR LOCATION — Motormaster III sensor locations are shown in Fig. 33A-33C. Refer to the Motormaster III installation instructions for wiring and installation information. 30 Fig. 33C — Motormaster III Sensor Location (Size 048) Fig. 33B — MotormasterT III Sensor Location (Sizes 038 and 044) 31 3. Close the indoor fan circuit breaker. The VFD now is powered but the fan will not operate. 4. On the front of the VFD is a keypad and display which will be used to enter the set point. To access this field, press ‘‘SETUP’’ key, then press the ‘‘SETUP’’ key 6 times to scroll to the sixth parameter, which will display ‘‘Sr1.’’ This is the VFD set point listed in Table 7. 5. Press the ‘‘READ/WRITE’’ key. The set point value will be displayed. Use the up-arrow or down-arrow key to adjust the set point value to the value desired. 6. Press the ‘‘READ/WRITE’’ key again to enter the new value. 7. Open the indoor fan circuit breaker. 8. Replace the jumper between CC and ST on the terminal strip of the VFD. 9. Close the indoor fan circuit breaker, the VFD now is powered and the fan will operate. NOTE: Any field measurement of supply fan amps must be taken with an RMS meter between the fan circuit breaker and fan contactor (upstream of VFD). START-UP Use the following information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up. Unit Preparation — Check that unit has been installed in accordance with these installation instructions and applicable codes. Compressor Mounting — Loosen the compressor holddown bolts until sidewise movement of the washer under each holddown bolt head can be obtained. Do not loosen completely as bolts are self-locking and will maintain adjustment. Service Valves — Ensure that the suction, discharge, and liquid line service valves are open. Damage to the compressor could result if they are left closed. Internal Wiring — Check all electrical connections in unit control boxes; tighten as required. Refrigerant Service Ports — Each refrigerant system has one suction port located in the top of the compressor motor casing. All units also have one service port on the liquid line valve and one on the compressor discharge valve. Be sure that caps on the ports are tight. Table 7 — VFD Set Point Variable Frequency Drive (VFD) — The variable fre- PRESSURE (in. wg) 0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 quency drives are factory set. These settings include factoryinstalled jumpers and software configurations. The only configured set point is duct static pressure. An Operation Manual is shipped with each VAV unit. This manual should be used if the drive needs to be customized for a particular application. To set the duct static pressure, perform the following steps. The factory setting is zero. The duct transducer has a range from 0 to 5 in. wg. The transducer output is 2 to 10 vdc, therefore, 0 to 5 in. wg is proportional to the 2 to 10 vdc and must be expressed to the VFD in terms of percentage of the frequency range. To do this, refer to Table 7. The set point value is a percentage of the maximum output frequency. Locate the duct static pressure closest to that desired and use the corresponding set point value. If necessary, interpolation between duct static pressures is permissible. To set the VFD, the VFD must be powered up, however, since it is located near the indoor air fan, operation of the fan is not desirable. To disable the fan, perform the following procedure: 1. Open the indoor fan circuit breaker. 2. Remove the jumper between CC and ST on the terminal strip of the VFD (see Fig. 34). VOLTAGE (vdc) 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8 5.2 5.6 6.0 6.4 6.8 7.2 7.6 VFD — Variable Frequency Drive NOTE: Terminal strip is located inside the VFD (Variable Frequency Drive) at the bottom. Fig. 34 — VFD Factory-Installed Jumpers 32 VFD SET POINT 12.0 14.4 16.8 19.2 21.6 24.0 26.4 28.8 31.2 33.6 36.0 38.4 40.8 43.2 45.6 At the top of the module are 2 potentiometers. The left potentiometer adjusts the offset. The right potentiometer adjusts differential. The potentiometers are factory set for a nominal 0 in. wg building pressure. The offset set point is defined as the point at which a module turns off a fan, and is measured in terms of percent of the input signal. For control purposes, 0 offset is at an arbitrary ‘‘floor’’ which is established at 10% of the input signal, or 1 vdc. In this example, the first stage will turn off at 30% (3 vdc), and the offset potentiometer will be set at 20%. The second stage will turn off at 50% signal (5 vdc), and the offset potentiometer will be set at 40%. The fourth stage is at the maximum 75% offset, which equates to 85% signal or 8.5 vdc. The offset potentiometer is calibrated in 10% increments. Table 8 relates building pressure to signal level. Power Exhaust — The optional non-modulating power exhaust (CV only) is a two-stage design where the operation of the exhaust fans is linked to economizer position. When the supply fan is running and the economizer is 25% open, the base module closes contacts, activating 2 exhaust fans. When the economizer position reaches 75% open, the base module activates the other 2 exhaust fans. The fans will turn off when the economizer closes below the same points. The economizer position set points that trigger the exhaust fans can be modified, but only through use of the Service Tool, Comfort Works, or Building Supervisor Software. If singlestage operation is desired, adjust the economizer set points to identical values at the desired point to activate all exhaust fans. The optional modulating power exhaust (VAV standard, CV optional) is controlled by a modular electronic sequencer system. This system consists of a model R353 signal input module and 4 model S353 staging modules. The signal input module receives a 0 to 10 vdc signal from the building pressure transducer, which is mounted adjacent to the supply static transducer behind the filter access panel. The modules are mounted just below the unit control board. The left module is the R353, and the 4 modules on the right are S353 modules for stages 1 through 4. On the unit wiring label, the R353 is designated PESC, and the S353 modules are designated PES1 through PES4. The building pressure transducer range is −0.5 to +0.5 in. wg. It is powered by a 0 to 10 vdc signal. A factoryinstalled hose at the ‘‘Lo’’ connection leads to atmosphere, and a field-supplied hose must be connected to the ‘‘Hi’’ connection and led into the building to a point where building pressure is to be controlled. There is a plug button in the bulkhead just above the transducers, for use in leading the hoses into the building via the return air ductwork. There are 3 adjustments at the R353 module, all of which have been factory set. In the center of the circuit board is a set of 4 pins with a jumper, labeled J2. This determines the mode of operation. The bottom 2 pins must be jumpered for direct operation. Direct operation means that the staging modules are activated in sequence as the input signal increases. At the upper right corner of the board is a set of 5 pins and jumper, which determines the time constant for the control. The time constant is the delay in response built into the controls. The jumper should be on the middle or bottom 2 pins, for the maximum time constant. The delay can be decreased, if desired, by moving the jumper progressively upward, always jumpering adjacent pins. At the lower left corner of the board below the terminal strip is a resistor marked R27. This must be removed in order to obtain the 0 to 10 vdc signal output. There will not be a resistor on a factory-supplied module, but a resistor may be present on a replacement module and must be removed. The R353 module has a terminal block with 7 connections available for wiring. The 2 right-hand terminals are for the 24 vac and common connections. The next 2 terminals are for the 0 to 10 vdc signal. Consult the wiring label for wire identification if replacing the module. The 3 left-hand terminals are not used for this application. The S353 module has an LED (light-emitting diode), a set of 4 jumper pins, and 2 potentiometers. The LED will light whenever the module is activated, providing a visual indication of the number of exhaust fans running. The jumper pins are arranged in a square format. Two jumpers are used to determine the mode of operation (direct or reverse). The 2 jumpers must be arranged horizontally for direct action (factory set). Table 8 — Potentiometer Signal Levels BUILDING PRESSURE (in. wg) −0.50 −0.25 0.00 0.25 0.50 SIGNAL LEVEL (vdc) 2 4 6 8 10 If the building pressure is controlled at 0 in. wg, offset of the first stage should be set at 50%, which equates to 60% of the input signal, or 6 vdc. The other stages can then be set as desired between 50% and 75%. The default offset set points for modulating power exhaust are shown in Table 9. Table 9 — Power Exhaust Default Set Points STAGE OFFSET DIFFERENTIAL OFF VOLTAGE ON VOLTAGE 1 2 3 4 50% 55% 60% 64% 3% 3% 3% 3% 6.0 6.5 7.0 7.4 6.3 6.8 7.3 7.7 OFF STATIC PRESSURE (in. wg) 0.00 0.06 0.12 0.18 The differential set point is the difference between the turn off point and the turn on point for each module. It also is calibrated in terms of percent of input signal, and has a range of 1% to 7%. The differential potentiometer is calibrated in 1% increments, and is factory set at approximately 3%. It is recommended to leave the set point at 3%, to minimize cycling of the fans. The offset and differential potentioments have been factory set for atmosphereic pressure. Do not change these settings until there is some experience with the building. In most cases the factory settings will be satisfactory. However, if the building pressure is not being maintained as desired, then some minor adjusting on a trial and error basis can be made. Direct Digital Controls DIP Switch Configuration — The Direct Digital Control (DDC) board must be configured for each application. The DDC board is configured through the DIP switches located on the board. There are 8 DIP switches which configure 8 different applications of the DDC. See Tables 10A and 10B. DIP switch 1 is on the left of the block. DIP switch 8 is on the right of the block. To open a DIP switch, push the switch up with suitable tool (small-blade screwdriver). To close a DIP switch, push the switch down. Factory settings are shown in Tables 11A and 11B. 33 Table 10A — DIP Switch Configuration (Version 1.0 of Unit Control Software) SETTING 1 2 3 OPEN VAV CCN/ Sensors Expansion I/O Board CLOSED CV TSTAT Base Board Only 4 Field Test ON Field Test OFF 5 Modulated Power Exhaust CV Power Exhaust 6 Time Guard Override ON/ Set Min. Damper Pos. ON Time Guard Override OFF/ Set Min. Damper Pos. OFF LEGEND CCN CV I/O POS. TSTAT VAV — — — — — — 7 8 Gas Heat Factory Test ON Electric Heat Factory Test OFF NOTES: 1. The Factory Test DIP switch should not be enabled in the field. 2. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is open. 3. If DIP switch no. 1 is open, DIP switch no. 2 is ignored, since VAV units control to supply-air temperature. Carrier Comfort Network Constant Volume Input/Output Position Thermostat Variable Air Volume Table 10B — DIP Switch Configuration (Version 2.0 of Unit Control Software) SETTING 1 2 3 4 VAV — Space Sensor Installed OPEN VAV Expansion Board Field Test ON Base Control Board Only Field Test OFF CV — CCN or Sensors Used VAV — No Space Sensor CLOSED CV CV — Thermostat 5 VAV — Occupied Heat Enabled CV — Modulated Power Exhaust VAV — Occupied Heat Disabled CV — Constant Volume Power Exhaust LEGEND 6 7 8 Gas Heat Heat Pump Operation Electric Heat Air Conditioner Operation Time Guard Override ON IN CONJUNCTION WITH FIELD TEST — Set Minimum Damper Position Time Guard Override OFF NOTES: 1. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is OPEN. 2. The configuration of DIP switches 2 and 5 are dependent on DIP switch 1. If DIP switch 1 is set to OPEN (VAV operation), then DIP switches 2 and 5 will configure CV functions. 3. When the unit is field-tested (DIP switch 4 to OPEN), the function of DIP switch 6 changes and it is used to set the minimum damper position. CCN — Carrier Comfort Network CV — Constant Volume VAV — Variable Air Volume Table 11A — DIP Switch Factory Settings (Version 1.0 of Unit Control Software) UNIT 50EJ/EW 50EK/EY 1 Closed Open 2 Closed Closed 3 Closed Closed 4 Closed Closed 5 Closed Open 6 Closed Closed 7 Closed Closed 8 Closed Closed Table 11B — DIP Switch Factory Settings (Version 2.0 of Unit Control Software) UNIT 50EJ/EW 50EK/EY 1 Closed Open 2 Closed Closed 3 Closed Closed 4 Closed Closed 34 5 Closed Closed 6 Closed Closed 7 Closed Closed 8 Closed Closed DIP switch configurations for Version 1.0 of the Unit Control Software are as follows: • DIP switch 1 configures the unit to operate as a variable air volume (VAV) or constant volume (CV) unit • DIP switch 2 configures what type of sensors or thermostats are used with the unit • DIP switch 3 configures the DDC for use with the electronic expansion board • DIP switch 4 is used to field test the unit • DIP switch 5 configures the unit to use constant volume or modulated power exhaust • DIP switch 6 configures the Time Guardt override and the minimum damper position • DIP switch 7 configures the unit for gas heat or electric heat • DIP switch 8 is used to factory test the unit The DIP switch configurations for Version 2.0 of the unit control software are as follows: • DIP switch 1 configures the unit to operate as a VAV or CV unit • DIP switch 2 configures the unit to use a space sensor (VAV units) or a thermostat (CV units) • DIP switch 3 configures the DDC for use with an electronic expansion board • DIP switch 4 is used to field test the unit • DIP switch 5 is used to enable occupied heating (VAV units) or specify the type of power exhaust (CV units) • DIP switch 6 configures the Time Guard override and, when used with the field test function, sets the minimum damper position • DIP switch 7 configures the unit for gas heat or electric heat • DIP switch 8 configures the unit for heat pump or air conditioner operation Filter Replacement — To replace filters, open filter access door (marked with label). Remove inner access panel. Remove plastic filter retainer in between filter tracks by sliding and pulling outward. Remove first filter by sliding it out of the opening in filter track. Locate filter removal tool, which is shipped next to the return air dampers. Use the filter removal tool to remove the remaining filters. Outdoor-Air Inlet Screens — Outdoor-air inlet screens must be in place before operating unit. Economizer Adjustment — Remove filter access panel. Check that outdoor-air damper is closed and return-air damper is open. Economizer operation and adjustment is described in Sequence of Operation and Make Outdoor Air Inlet Adjustments sections (this page and page 25), respectively. Sequence of Operation NOTE: Unit is shipped with default values that can be changed through Service Tool or CCN software. COOLING, CONSTANT VOLUME (CV) UNITS — On power up, the control module will activate the initialization software. The initialization software reads DIP switch no. 1 position to determine CV or VAV operation. Next, DIP switch no. 2 is read to determine if the control is TSTAT or sensor type operation. The initialization sequence: clears all alarms and alerts; re-maps the input/output database for CV operation; sets maximum heat stages to 2; and sets maximum cool stages to 3. The control module reads DIP switch no. 3 and determines if the unit will use expansion mode operation. The TSTAT function performs a thermostat based control by monitoring Y1, Y2, W1, W2 and G inputs. These functions control stages: cool1, cool2, heat1, heat2, and the indoor fan respectively. If the TSTAT function is not selected, the control module determines the occupancy state based on the system time schedules or with remote occupied/unoccupied input. If Temperature Compensated Start is active, the unit will be controlled as in the Occupied mode. User defined set points are shown in Table 17. Occupied or unoccupied comfort set points must be selected. Use of the space temperature offset input can also be configured. The control module will set appropriate operating mode and fan control. The control module will turn on indoor fan if in Occupied mode or if the unit is in Unoccupied mode and the space temperature is outside of the unoccupied comfort set points (Unoccupied Heat or Unoccupied Cool). The control module will then monitor space temperature against comfort set points and control heating or cooling stages as required. If the system is in the Occupied mode, the economizer will operate as required. If the system is in Unoccupied mode, the system will perform night time free cool and IAQ (indoor air quality) pre-occupancy purge as required (when functions are enabled via software). Whenever the DX (direct expansion) cooling is requested, the outdoor fan will operate. Crankcase Heater(s) — Heater(s) is energized as long as there is power to the unit, except when the compressors are operating. IMPORTANT: Unit power must be on for 24 hours prior to start-up. Otherwise, damage to compressor may result. Evaporator Fan — Fan belt and fixed pulleys are factoryinstalled. See Tables 12-14 for Fan Performance Data. See Table 15 for Air Quantity Limits. See Table 16 for Motor Limitation data. Be sure that fans rotate in the proper direction. Static pressure drop for power exhaust, barometric relief damper, and electric heat is negligible. To alter fan performance, see Evaporator Fan Performance Adjustment section on page 43. Condenser Fans and Motors — Fans and motors are factory set. Refer to Condenser-Fan Adjustment section (page 44) as required. Return-Air Filters — Check that correct filters are installed in filter tracks. See Table 1. Do not operate unit without return-air filters. 35 Table 12 — Fan Performance, 50EJ/EK024-034 — Vertical Discharge Units FOR EW/EY UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.3 IN. WG AIRFLOW (Cfm) 4,000 5,000 6,000 7,000 8,000 8,250 9,000 10,000 11,000 12,000 12,500 13,000 13,750 14,000 15,000 AIRFLOW (Cfm) 4,000 5,000 6,000 7,000 8,000 8,250 9,000 10,000 11,000 12,000 12,500 13,000 13,750 14,000 15,000 AIRFLOW (Cfm) 4,000 5,000 6,000 7,000 8,000 8,250 9,000 10,000 11,000 12,000 12,500 13,000 13,750 14,000 15,000 0.2 Rpm 322 361 403 448 495 507 543 592 642 693 718 744 783 795 847 Bhp 0.77 1.14 1.62 2.22 2.97 3.18 3.85 4.90 6.10 7.48 8.23 9.03 10.32 10.77 12.71 0.4 Rpm 401 433 468 508 549 560 593 638 685 733 757 781 818 831 880 1.8 Rpm 746 764 785 809 836 843 865 897 931 967 985 1004 1033 1043 1083 Bhp 3.64 4.21 4.89 5.70 6.65 6.91 7.74 8.98 10.37 11.94 12.78 13.67 15.09 15.59 17.70 Bhp 1.09 1.50 2.01 2.65 3.42 3.64 4.34 5.41 6.64 8.04 8.80 9.62 10.92 11.38 13.34 2.0 Rpm 783 800 820 843 869 876 898 928 961 996 1014 1032 1060 1070 1109 Bhp 4.03 4.62 5.32 6.16 7.12 7.39 8.23 9.49 10.91 12.49 13.35 14.25 15.69 16.19 18.32 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 466 1.43 523 1.78 575 2.13 622 2.50 494 1.86 548 2.23 598 2.62 643 3.00 526 2.41 577 2.81 624 3.21 668 3.62 561 3.08 609 3.50 654 3.93 696 4.37 599 3.88 645 4.33 687 4.79 727 5.25 609 4.10 654 4.56 696 5.02 735 5.49 639 4.82 682 5.30 723 5.78 761 6.27 682 5.91 722 6.42 760 6.93 797 7.44 725 7.17 764 7.70 800 8.24 835 8.77 771 8.60 807 9.15 841 9.71 874 10.26 794 9.37 829 9.94 862 10.51 895 11.08 817 10.20 851 10.78 884 11.36 915 11.93 852 11.52 885 12.12 917 12.71 947 13.31 864 11.98 896 12.59 928 13.19 958 13.79 912 13.96 943 14.59 972 15.21 1001 15.83 Rpm 666 686 709 736 765 773 797 832 868 906 926 946 977 987 1029 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 818 4.44 852 4.85 884 5.26 916 5.68 834 5.04 868 5.46 900 5.89 930 6.33 854 5.76 886 6.21 918 6.65 948 7.11 876 6.61 908 7.08 939 7.54 968 8.01 901 7.60 932 8.08 962 8.57 991 9.05 908 7.87 938 8.36 968 8.84 997 9.34 929 8.73 959 9.23 988 9.74 1016 10.24 958 10.01 987 10.53 1016 11.06 1043 11.58 990 11.45 1018 11.99 1046 12.54 1073 13.08 1024 13.06 1051 13.62 1078 14.18 1104 14.75 1041 13.92 1068 14.49 1094 15.07 1120 15.64 1059 14.83 1086 15.42 1111 16.00 1137 16.59 1087 16.29 1112 16.88 1138 17.48 1162 18.08 1096 16.79 1122 17.40 1147 18.00 1171 18.60 1134 18.94 1159 19.56 1183 20.19 — — Rpm 946 960 977 997 1019 1025 1043 1070 1099 1129 1145 1161 1186 1195 — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 Rpm Bhp Rpm Bhp Rpm Bhp 1004 6.97 1032 7.41 1059 7.86 1017 7.67 1045 8.12 1072 8.58 1034 8.49 1061 8.96 1087 9.43 1052 9.44 1079 9.93 1105 10.42 1073 10.54 1099 11.04 1125 11.55 1079 10.84 1105 11.34 1130 11.85 1096 11.78 1122 12.30 1147 12.82 1122 13.18 1147 13.71 1171 14.25 1149 14.73 1173 15.29 1197 15.84 1178 16.45 1202 17.03 — — 1193 17.38 — — — — — — — — — — — — — — — — — — — — — — — — — — — — 1.4 Bhp 2.87 3.40 4.04 4.81 5.71 5.96 6.76 7.95 9.30 10.82 11.64 12.51 13.90 14.39 16.45 1.6 Rpm 707 726 748 773 801 809 832 865 900 937 956 975 1005 1015 1056 3.0 Bhp 6.11 6.77 7.56 8.49 9.55 9.83 10.75 12.11 13.63 15.31 16.22 17.17 18.68 19.21 — Bhp 3.25 3.80 4.46 5.25 6.18 6.43 7.24 8.46 9.84 11.38 12.21 13.09 14.50 14.99 17.08 3.2 Rpm 975 989 1006 1025 1046 1052 1070 1096 1124 1154 1169 1185 — — — Bhp 6.54 7.22 8.02 8.96 10.04 10.33 11.27 12.64 14.18 15.88 16.80 17.76 — — — LEGEND Bhp — Brake Horsepower NOTES: 1. Fan performance is based on wet coils, economizer, roof curb, cabinet losses, and clean 2-in. filters. 2. Conversion — Bhp to watts: Bhp x 746 Watts = Motor efficiency 3. VAV units will operate down to 70 cfm/ton. 36 Table 13 — Fan Performance, 50EJ038,044 and 50EK044 — Vertical Discharge Units For EW/EY UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.5 IN. WG AIRFLOW (Cfm) 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 AIRFLOW (Cfm) 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 AIRFLOW (Cfm) 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 0.2 Rpm 448 492 537 582 629 675 722 770 817 865 913 961 1009 Bhp 2.18 2.87 3.69 4.65 5.75 7.00 8.42 10.00 11.76 13.70 15.83 18.16 20.69 0.4 Rpm 498 537 578 620 664 708 753 798 844 890 937 984 1031 1.8 Rpm 783 803 827 854 883 914 948 983 1019 1057 1096 1135 1176 Bhp 5.70 6.66 7.77 9.03 10.45 12.05 13.83 15.80 17.96 20.33 22.91 25.72 28.75 Bhp 2.87 3.68 4.63 5.75 7.02 8.48 10.11 11.94 13.96 16.19 18.64 21.32 24.22 2.0 Rpm 818 836 858 884 911 942 974 1007 1043 1079 1117 1156 1196 Bhp 6.13 7.11 8.23 9.51 10.96 12.57 14.37 16.36 18.54 20.93 23.53 26.36 29.41 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 544 3.25 589 3.64 631 4.04 671 4.44 580 4.09 621 4.50 660 4.92 698 5.35 617 5.07 655 5.50 692 5.95 727 6.39 657 6.20 692 6.66 726 7.13 759 7.60 698 7.50 730 7.98 763 8.47 794 8.96 739 8.98 770 9.48 800 9.99 830 10.50 782 10.63 811 11.16 840 11.69 868 12.22 826 12.48 853 13.03 880 13.57 907 14.13 870 14.53 896 15.09 922 15.66 947 16.23 915 16.78 940 17.37 964 17.95 988 18.54 961 19.25 984 19.85 1007 20.46 1030 21.07 1006 21.94 1029 22.56 1050 23.19 1072 23.82 1052 24.86 1074 25.50 1095 26.15 1115 26.80 Rpm 710 734 761 792 824 859 895 932 971 1011 1052 1093 1136 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 852 6.56 884 7.00 916 7.45 947 7.90 869 7.56 900 8.02 930 8.48 960 8.95 889 8.70 919 9.18 948 9.66 977 10.15 913 10.00 941 10.50 969 11.00 997 11.50 939 11.47 967 11.98 993 12.50 1020 13.02 968 13.10 994 13.63 1020 14.17 1045 14.71 999 14.92 1024 15.47 1049 16.02 1073 16.58 1032 16.92 1056 17.49 1079 18.06 1102 18.64 1066 19.13 1089 19.71 1111 20.30 1134 20.89 1102 21.53 1124 22.14 1145 22.75 1167 23.35 1138 24.15 1160 24.78 1180 25.40 — — 1176 26.99 1197 27.63 — — — — — — — — — — — — Rpm 978 989 1005 1024 1046 1070 1096 1125 1156 1188 — — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 Rpm Bhp Rpm Bhp Rpm Bhp 1036 9.29 1065 9.76 1092 10.24 1046 10.38 1073 10.87 1100 11.36 1059 11.63 1086 12.13 1112 12.64 1076 13.03 1102 13.55 1127 14.07 1096 14.60 1121 15.13 1145 15.67 1118 16.34 1142 16.89 1165 17.45 1143 18.26 1166 18.83 1188 19.40 1170 20.37 1192 20.96 — — 1199 22.68 — — — — — — — — — — — — — — — — — — — — — — — — — — — — 1.4 Bhp 4.86 5.78 6.85 8.07 9.45 11.01 12.75 14.68 16.81 19.14 21.68 24.45 27.45 1.6 Rpm 747 769 795 823 854 887 922 958 995 1034 1074 1115 1156 3.0 Bhp 8.36 9.42 10.64 12.01 13.54 15.25 17.14 19.21 21.49 23.97 — — — Bhp 5.27 6.22 7.30 8.55 9.95 11.53 13.29 15.24 17.38 19.73 22.30 25.08 28.10 3.2 Rpm 1007 1018 1032 1050 1071 1094 1120 1148 1177 — — — — Bhp 8.82 9.90 11.13 12.52 14.07 15.79 17.70 19.79 22.08 — — — — LEGEND Bhp — Brake Horsepower NOTES: 1. Fan performance is based on wet coils, economizer, roof curb, cabinet losses, and clean 2-in. filters. 2. Conversion − Bhp to watts: Bhp x 746 Watts = Motor efficiency 3. VAV units will operate down to 70 cfm/ton. 37 Table 14 — Fan Performance, 50EJ048 — Vertical Discharge Units FOR EW UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.5 IN. WG AIRFLOW (Cfm) 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 AIRFLOW (Cfm) 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 AIRFLOW (Cfm) 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 0.2 Rpm 683 730 778 826 875 923 972 1021 Bhp 7.10 8.53 10.14 11.93 13.90 16.06 18.42 20.98 0.4 Rpm 715 761 807 853 900 947 995 1042 1.8 Rpm 921 955 991 1028 1066 1106 1146 1187 Bhp 12.18 13.98 15.98 18.17 20.58 23.19 26.04 29.11 Bhp 8.59 10.25 12.10 14.15 16.42 18.90 21.61 24.55 2.0 Rpm 948 981 1015 1051 1089 1127 1166 — Bhp 12.71 14.53 16.54 18.76 21.18 23.82 26.68 — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 747 9.09 777 9.60 808 10.11 837 10.62 790 10.77 819 11.30 847 11.83 875 12.36 834 12.65 862 13.19 888 13.75 915 14.30 879 14.72 905 15.29 931 15.86 955 16.44 925 17.01 949 17.60 973 18.19 997 18.78 971 19.51 994 20.12 1017 20.73 1039 21.34 1017 22.24 1039 22.87 1061 23.50 1083 24.13 1064 25.20 1085 25.85 1106 26.50 1126 27.15 Rpm 866 902 941 980 1020 1062 1104 1147 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 975 13.24 1001 13.77 1026 14.30 1051 14.84 1006 15.08 1031 15.63 1056 16.18 1080 16.74 1040 17.11 1063 17.68 1087 18.25 1110 18.83 1074 19.34 1097 19.93 1120 20.52 1142 21.12 1111 21.78 1133 22.39 1154 23.00 1175 23.61 1148 24.44 1169 25.07 1190 25.69 — — 1187 27.32 — — — — — — — — — — — — — — Rpm 1076 1103 1133 1164 1197 — — — 1.4 Bhp 11.14 12.90 14.86 17.01 19.38 21.96 24.76 27.80 1.6 Rpm 894 929 966 1004 1043 1084 1125 1167 3.0 Bhp 15.39 17.30 19.41 21.71 24.23 — — — Bhp 11.66 13.44 15.42 17.59 19.98 22.58 25.40 28.46 3.2 Rpm 1100 1127 1155 1185 — — — — Bhp 15.93 17.86 19.99 22.31 — — — — LEGEND Bhp — Brake Horsepower AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.6 Rpm Bhp Rpm Bhp Rpm Bhp 1124 16.48 1148 17.03 1171 17.59 1150 18.43 1173 19.00 1195 19.57 1177 20.57 1199 21.16 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — NOTES: 1. Fan performance is based on wet coils, economizer, roof curb, cabinet losses, and clean 2-in. filters. 2. Conversion − Bhp to watts: Bhp x 746 Watts = Motor efficiency 3. VAV units will operate down to 70 cfm/ton. Table 15 — Air Quantity Limits UNIT 50EJ,EK,EW,EY 024 028 030 034 038 044 048 MINIMUM HEATING CFM 6,000 7,500 8,250 9,000 10,500 12,000 13,500 MINIMUM COOLING CFM (VAV) 2000 2500 2750 3000 3500 4000 4500 LEGEND CV — Constant Volume VAV — Variable Air Volume 38 MINIMUM COOLING CFM (CV) 6,000 7,500 8,250 9,000 10,500 12,000 13,500 MAXIMUM CFM 10,000 12,500 13,750 15,000 17,500 20,000 22,500 Table 16 — Motor Limitations STANDARD EFFICIENCY MOTORS Nominal Hp Maximum Bhp 5.9 5.9 8.7 9.5 10.2 11.8 15.3 18.0 22.4 23.4 28.9 29.4 35.6 34.7 5 7.5 10 15 20 25 30 208 17.94 — 25.52 — 26.93 — 42.84 — 59.36 — 76.30 — 92.56 — Maximum Amps 230 460 16.99 — — 8.50 24.36 — — 13.30 25.50 — — 14.75 40.80 — — 24.00 56.00 — — 29.25 72.83 — — 37.04 87.81 — — 42.80 575 — 5.78 — 9.63 — 11.33 — 18.00 — 22.82 — 28.69 — n/a 208 16.76 — — 26.10 — — 28.56 — — 45.08 — — 63.84 — — 80.69 — — 102.65 — — Maximum Amps 230 460 13.92 — — 6.96 — — 22.27 — — 12.16 — — 24.89 — — 14.40 — — 39.17 — — 23.04 — — 55.55 — — 29.02 — — 70.05 — — 35.63 — — 89.00 — — 43.38 — — 575 — — 5.66 — — 9.50 — — 11.68 — — 18.12 — — 23.17 — — 28.81 — — 33.89 Maximum Watts Motor Efficiency 5,348 5,240 7,717 8,549 8,879 10,284 13,686 15,891 19,032 19,950 24,499 25,181 29,378 29,316 82.3 84.0 84.1 82.9 85.7 85.6 83.4 84.5 87.8 87.5 88.0 87.1 90.4 88.3 Maximum Watts Motor Efficiency 5,030 5,030 4,918 7,334 8,008 7,728 8,502 9,836 9,600 12,543 14,756 14,439 18,363 19,183 18,650 23,511 23,918 23,432 28,742 28,015 27,656 87.5 87.5 89.5 88.5 88.5 91.7 89.5 89.5 91.0 91.0 91.0 93.0 91.0 91.0 93.6 91.7 91.7 93.6 92.4 92.4 93.6 HIGH EFFICIENCY MOTORS Nominal Hp Maximum Bhp 5 7.5 10 15 20 25 30 5.9 5.9 5.9 8.7 9.5 9.5 10.2 11.8 11.8 15.3 18.0 18.0 22.4 23.4 23.4 28.9 29.4 29.4 35.6 34.7 34.7 NOTE: Extensive motor and electrical testing on the Carrier units has ensured that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the horsepower ratings shown on the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. LEGEND BHP — Brake Horsepower Table 17 — User Defined Set Points SET POINT OHSP OCSP UHSP UCSP SASP OATL NTLO RTIO LIMT MDP IAQS UHDB UCDB LTMP HTMP PES1 PES2 FORMAT xx.xF xx.xF xx.xF xx.xF xx.xF xx.xF xx.xF xx.x xx.x^F xxx% xxxx xx.x^F xx.x^F xx.xF xx.xF xx.xF xx.xF DESCRIPTION Occupied Heat Set Point Occupied Cool Set Point Unoccupied Heat Set Point Unoccupied Cool Set Point Supply Air Set Point Hi OAT Lockout Temperature Unoccupied OAT Lockout Temperature Reset Ratio Reset Limit Minimum Damper Position IAQ Set Point Unoccupied Heating Deadband Unoccupied Cooling Deadband Low Temp. Min. Position High Temp. Min. Position CV Power Exhaust Stage 1 Point CV Power Exhaust Stage 2 Point LEGEND CV — Constant Volume IAQ — Indoor Air Quality OAT — Outdoor Air Temperature 39 LIMITS 55 to 80 F 55 to 80 F 40 to 80 F 75 to 95 F 45 to 70 F 55 to 75 F 40 to 70 F 0 to 10 0 to 20 F 0 to 100% 1 to 5000 0 to 10 0 to 10 0 to 100 0 to 100 0 to 100 0 to 100 DEFAULT 68 78 55 90 55 65 50 3 10 20 650 1 1 10 35 25 75 The control module will operate economizer, run diagnostics to monitor alarms/alerts at all times, and respond to CCN communications to perform any configured network POC (product outboard control) functions such as time/ outdoor-air temperature broadcast and global occupancy broadcast. When the optional expansion I/O board is employed, it will: perform a periodic scan and maintain a database of expanded I/O points; perform Fire/Smoke control (power exhaust required); if in Occupied mode, perform IAQ control and monitor the fan, filter, demand limit, and field-applied status (with accessories). If thermostats are used to energize the G input, the control module will turn on the indoor fan without delay and open the economizer dampers to minimum position. If thermostats are used to deenergize the G input, the control module will turn off the indoor fan without delay and close the economizer dampers. When cooling, G must be energized before cooling can operate. The control module determines if outdoor conditions are suitable for economizer cooling using the standard outdoor air thermistor. For the economizer to function for outside air cooling: the enthalpy must be below the enthalpy set point; the outdoor-air temperature must be equal to or less than the High Outdoor Air Temperature Lockout (default is 65 F); the SAT (supply-air temperature) thermistor must not be in alarm; and the outdoor air reading is available. When these conditions are satisfied, the control module will use economizer as the first stage of cooling. When Y1 input is energized, the economizer will be modulated to maintain SAT at the defined set point. (The default is 55 F.) When SAT is above the set point, the economizer will be 100% open. When SAT is below the set point, the economizer will modulate between minimum and 100% open position. When Y2 is energized, the control module will turn on compressor 1 and continue to modulate the economizer as described above. If the Y2 remains energized and the SAT reading remains above the set point for 15 minutes, compressor 2 will turn on. If Y2 is deenergized at any time, only the last stage of compression that was energized will be turned off. If outdoor conditions are not suitable for economizer cooling, the economizer will go to minimum position and cycle compressors 1 and 2 based on demand from Y1 and Y2 respectively. The compressors will be locked out when the SAT temperature is too low (less than 40 F for compressor 1 and less than 45 F for compressor 2). After a compressor is locked out, it can restart after normal time-guard period. The Time Guardt function maintains a minimum off time of 5 minutes, a minimum on time of 10 seconds, and a minimum delay before starting the second compressor of 10 seconds. When heating, the heat stages respond to the demand from W1 and W2 of the thermostat input. Heating and cooling will be mutually locked-out on demand on a first call basis. The heating and the cooling functions cannot operate simultaneously. COOLING, VARIABLE VOLUME UNITS — On power up, the control module will activate the initialization software. The initialization software reads DIP switch no. 1 position to determine CV or VAV operation. The initialization sequence: clears all alarms and alerts; re-maps the input/ output database for VAV operation; sets maximum heat stages to 1; and sets maximum cool stages to 6. The control module reads DIP switch no. 3 and determines if the unit will use expansion mode operation. Power up takes a random time of 1 to 63 seconds plus 5 minutes the first time power is sent to the control board after a power outage. The control module will determine if an interface (linkage) is active and if the unit will operate in a Digital Air Volume (DAV) mode. In a DAV system, the room terminals are equipped with microprocessor controls that give commands to the base unit module. If a linkage is active, the control module will replace local comfort set points, space and return air temperatures, and occupancy status with the linkage data supplied. The control module will determine occupancy status from Time Schedules (if programmed), Remote Occupied/ Unoccupied input, global occupancy schedules, or DAV. If temperature compensated start is active, the unit will be controlled as in the Occupied mode. NOTE: The temperature compensated start is a period of time calculated to bring the unit on while in Unoccupied mode to reach the occupied set point when occupancy occurs. The control module will set the appropriate operating mode and fan control. The control module will turn on the VFD if Occupied mode is evident. If in Unoccupied mode and a valid space temperature reading is available (either from a sensor or DAV), the control module will monitor SPT (space temperature) against unoccupied heat and cool set points. The control module will start the VFD whenever SPT is outside of the set points (Unoccupied Heat or Unoccupied Cool). The VFD may also be started by nighttime thermostat via remote Occupied/Unoccupied input or by a temperature compensated start algorithm. When the VFD is running in a normal mode, the control module will start heating or cooling as required to maintain supply-air temperature at the supply air set point plus the reset (when enabled). The reset value is determined by SAT (supply-air temperature) reset and/or space temperature reset algorithms. The reset is only available when enabled through software. When cooling, the control module will energize the power exhaust enable output to the external power exhaust controller (when power exhaust is used). The control module will run continuous diagnostics for alarms/alerts; respond to CCN (Carrier Comfort Network) communications; perform any configured network POC (Product Outboard Control) functions such as time/outdoor air temperature broadcast and global broadcast; and perform Fire/ Smoke control. HEATING, CONSTANT VOLUME (CV) UNITS — The control module is powered by 24 vac. If the unit is controlled with a room sensor, the fan will run continuously in the Occupied mode, with the outside-air damper in the minimum position. If the unit is controlled through a room thermostat (with FAN set to AUTO), upon a call for heat the first stage of heat is energized, the indoor-fan motor will turn on, and the outdoor-air damper will move to the minimum position. Upon a call for additional heat (if the unit is equipped with a two-stage heater), the second stage of heat is energized. When the call for heat is satisfied, the heaters will deenergize. The indoor-fan motor will also deenergize (unless controlled by a room sensor) and the outdoor-air damper will move to the closed position. If the unit is controlled with a room sensor the fan will not run in the unoccupied mode. Upon a call for heat, the first stage of heat is energized, the indoor-fan motor will turn on, and the outdoor air damper will move to the Unoccupied IAQ position (generally set to zero in the unoccupied mode). The IAQ feature is enabled through system software. Upon a call for additional heat (if the unit is equipped with a twostage heater), the second stage of heat is energized. When the call for heat is satisfied, the heaters and indoor-fan motor will deenergize and the outdoor-air damper will move to the closed position (if open). HEATING, VARIABLE AIR VOLUME (VAV) UNITS — The control board is powered by 24 vac. When there is a call for heating (from Morning Warm-Up, Unoccupied, or Occupied modes), power is sent from the control module to energize the first stage of electric heat. A field-supplied heat 40 interlock relay signals for the air terminals to fully open. See Fig. 35. In the Occupied mode, the indoor-fan motor will operate continuously and the outdoor-air dampers will be in the minimum position. In the Unoccupied mode, the indoorfan motor will be off, but will energize upon the call for heat. The outdoor-air dampers will move to the IAQ unoccupied position (generally set to zero in the Unoccupied mode). The IAQ feature is enabled through system software. The duct pressure sensor will signal to the variable frequency drive to operate at full speed. Upon a call for additional heat (if the unit is equipped with a two-stage heater), the second stage of heat will be energized. When the call for heat is satisfied, the heaters will deenergize. NOTE: The HIR is not needed in a DAV system. If the unit is in the Unoccupied mode, the indoor-fan motor will deenergize and the outdoor-air damper will move to the closed position (if open). MORNING WARM-UP (VAV ONLY WITH PC ACCESSED/ CCN OPERATION) — Morning warm-up occurs when the control module has been programmed to turn on heat, prior to the Occupied mode, to be ready for the occupancy. Morning warm-up is a condition in VAV systems that occurs when the Temperature Compensated Start algorithm calculates a biased occupied start time and the unit has a demand for heating. The warm-up will continue into the occupied period as long as there is a need for heat. During warm-up, the unit can continue heating into the occupied period, even if occupied heating is disabled. When the heating demand is satisfied, the warm-up condition will terminate. To increase or decrease the heating demand, use the network access software to change the occupied heating set point. NOTE: To utilize morning warm-up mode, the unit occupancy schedule must be accessed via Service Tool, Comfort Works, or Building Supervisor software (units running Version 1.0 of unit control software). MORNING WARM-UP (VAV ONLY WITH STAND-ALONE OPERATION) — When a unit running version 2.0 of the unit control software operates in stand-alone mode, morning warm-up occurs when the unit is energized in Occupied mode and return-air temperature (RAT) is below 68 F. Warm-up will not terminate until the RAT reaches 68 F. The heat interlock relay output is energized during morning warm-up. (A field-installed 24-vdc heat interlock relay is required.) The output will be energized until the morning warm-up cycle is complete. Refer to Fig. 35 for heat interlock relay wiring. SPACE TEMPERATURE RESET (VAV ONLY) — An accessory space temperature sensor is required. Space temperature reset is used to reset the supply-air temperature set point of a VAV system higher, as the space temperature falls below the Occupied Cool set point. As the space temperature falls below the cool set point, the supply-air temperature will be reset upward as a function of the reset ratio. Reset ratio is expressed in degrees change in supply-air temperature per degree of space temperature change. A reset limit will exist which will limit the maximum number of degrees the supply-air temperature may be raised. Both the reset ratio and the reset limit are user definable. The sequence of operation is as follows: 1. The on/off status of the unit supply fan is determined. 2. If the fan is on, the sequence will check if the system is in Occupied mode. 3. If the system is in Occupied mode, the sequence will determine if the reset option is enabled. 4. If the reset option is enabled, the sequence will read the space temperature and compare it to the Occupied Cool set point. If the temperature is below the Occupied Cool set point, the algorithm will compute the reset value and compare this value against the reset limit. If it is greater than the reset limit, the sequence will use the reset limit as the reset value. The field-supplied space temperature sensor input signal (4 to 20 ma and 2 to 10 vdc) enables the space temperature reset function. Refer to Fig. 36 for sensor wiring. POWER EXHAUST OPERATION — The optional power exhaust packages are factory- or field-installed with vertical units and optionally installed in the return air ductwork for horizontal applications. The standard (only offered with constant volume units) and modulating power exhaust (offered on VAV units) are the 2 packages available. The modulating power exhaust package is equipped with a field-adjustable static pressure controller which will control up to 4 power exhaust stages to maintain a building static pressure. The blue sequencer located in the control box below the control board can be adjusted by removing the covers and adjusting the set point dial to the desired building pressure. The standard power exhaust package controls up to 2 stages of power exhaust to maintain building pressure. These power exhaust stages are staged according to a percentage of the economizer damper position. The default values are 25% for Stage 1 and 75% for Stage 2. This package has set points that are adjustable through software (such as Service Tool, Building Supervisor, or Comfort Works). Fig. 35 — Heat Interlock Relay Wiring Fig. 36 — Space Temperature Sensor Wiring 41 MOTORMASTERt III DEVICE — The Motormaster III Solid-State Head Pressure Control is a field-installed accessory, fan speed control device actuated by a temperature sensor. The Motormaster III device is specifically designed for use on Carrier equipment and controls the outdoor-fan motor speed in response to the saturated condensing temperature. For outdoor temperatures down to −20 F, the Motormaster III device maintains condensing temperature at 100 F. CAPACITY CONTROL, COOLING — The cooling capacity staging tables are shown in Tables 18 and 19. Table 18 — Cooling Capacity Staging Table CV Units with 2 Compressors STAGES 0 Compressor 1 Compressor 2 Off Off 1 ECONOMIZER Off Off 2 3 On Off On On NOTE: On CV units that require additional unloading, add suction pressure unloaders on Compressor 1 only. SERVICE Table 19 — Cooling Capacity Staging Table VAV Units with 2 Compressors and 2 Unloaders* STAGES Compressor 1 Unloader 1 Unloader 2 Compressor 2 0 Off Off Off Off 1 On On On Off 2 On On Off Off 3 On Off Off Off 4 On On On On 5 On On Off On Before performing service or maintenance operations on unit, turn off main power switch to unit. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury. 6 On Off Off On Service Access — All unit components can be reached through clearly labelled hinged access doors. These doors are not equipped with tiebacks, so if heavy duty servicing is needed, either remove them or prop them open to prevent accidental closure. Each door is held closed with 3 latches. The latches are secured to the unit with a single 1⁄4-in. - 20 x 1⁄2-in. long bolt. See Fig. 37. To open, loosen the latch bolt using a 7⁄16-in. wrench. Pivot the latch so it is not in contact with the door. Open the door. To shut, reverse the above procedure. NOTE: Disassembly of the top cover may be required under special service circumstances. It is very important that the orientation and position of the top cover be marked on the unit prior to disassembly. This will allow proper replacement of the top cover onto the unit and prevent rainwater from leaking into the unit. *40 ton units have only 1 unloader. FIELD TEST — The field test program is initiated by moving up DIP switch no. 4 to the OPEN position. The outdoorair damper will close. The control allows 90 seconds for the damper to close in case it was in the full open position. Next, the indoor-fan contactor will be energized, and the outsideair damper will begin to open to its default value of 20% and stay at that position for a short period of time. The outdoorair damper will then open to its full open position and stay at that position for a short period of time. The outdoor-air damper will then close. If the unit is equipped with power exhaust, stage 1 will be energized for 5 seconds. If the unit is configured for stage 2 of power exhaust, stage 2 will be energized for 5 seconds after the first stage is deenergized. The first stage of heat will be energized for 30 seconds, after which the second stage heat will be energized for an additional 30 seconds. Heat is then deenergized. The last step is the Cooling mode. Outdoor-fan contactor no. 1 is energized. This is followed by each stage of cooling energized with a 10-second delay between stages. After this is complete, outdoor-fan contactor no. 2 is energized for 10 seconds. The compressors will now deenergize, followed by the outdoor-fan contactors and indoor-fan contactors. The field test is then complete. TIME GUARDt CIRCUIT — The Time Guard function (built into the rooftop’s control module board) maintains a minimum off time of 5 minutes and a minimum on time of 10 seconds. CRANKCASE HEATER — The unit main power supply must remain on to provide crankcase heater operation. The crankcase heater in each compressor keeps oil free of refrigerant while compressor is off. HEAD PRESSURE CONTROL — Each unit has a fan cycling, outdoor thermostat to shut off outdoor-fan motor(s) at 55 F (one outdoor-fan motor on 024-034 units and 2 outdoorfan motors on 038-048 units). The head pressure control permits the unit to operate with correct condensing temperatures down to 35 F outdoor-air temperature. IMPORTANT: After servicing is completed, make sure door is closed and relatched properly, and that the latches are tight. Failure to do so can result in water leakage into the evaporator section of the unit. Fig. 37 — Door Latch 42 CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS — The condenser and evaporator-fan motors have permanently-sealed bearings, so no field lubrication is necessary. Cleaning — Inspect unit interior at beginning of each heating and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior. EVAPORATOR COIL — Clean as required with a commercial coil cleaner. CONDENSER COIL — Clean condenser coil annually and as required by location and outdoor-air conditions. Inspect coil monthly — clean as required. CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drains and traps dry. FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to Table 1 for type and size. NOTE: The unit requires industrial grade throwaway filters capable of withstanding face velocities up to 625 fpm. OUTDOOR-AIR INLET SCREENS — Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens. Evaporator Fan Performance Adjustment (Fig. 38) — Fan motor pulleys are factory set for speed shown in Table 1 (factory speed setting). To change fan speeds, change pulleys. To align fan and motor pulleys: 1. Shut off unit power supply. 2. Loosen fan shaft pulley bushing. 3. Slide fan pulley along fan shaft. 4. Make angular alignment by loosening motor from mounting plate. 5. Retighten pulley. IMPORTANT: Check to ensure that the unit drive matches the duct static pressure in Tables 12 to 14. Evaporator Fan Service and Replacement 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Lubrication COMPRESSORS — Each compressor is charged with the correct amount of oil at the factory. The correct oil charge is shown in Table 1. If oil is visible in the compressor sight glass, check unit for operating readiness as described in Start-Up section, then start the unit. Observe oil level and add oil, if required, to bring oil level in compressor crankcase up to between 1⁄4 and 1⁄3 of sight glass during steady operation. If oil charge is above 1⁄3 sight glass, do not remove any oil until the compressor crankcase heater has been energized for at least 24 hours with compressor off. When additional oil or a complete charge is required, use only Carrier-approved compressor oil: Petroleum Specialties, Inc. . . . . . . . . . . . . . . . . . Cryol 150 Texaco, Inc. . . . . . . . . . . . . . . . . . . . . . . . . . Capella WF-32 Witco Chemical Corp. . . . . . . . . . . . . . . . . . . . Suniso 3GS Turn off unit power. Remove supply-air section panels. Remove belt and blower pulley. Loosen set screws in blower wheels. Remove locking collars from bearings. Remove shaft. Remove venturi on opposite side of bearing. Lift out wheel. Reverse above procedure to reinstall fan. Check and adjust belt tension as necessary. IMPORTANT: Do not use reclaimed oil or oil that has been exposed to the atmosphere. Refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants section, for procedures to add or remove oil. FAN SHAFT BEARINGS — Lubricate the bearings at least twice annually with suitable bearing grease. Do not over grease. Typical lubricants are show below: MANUFACTURER Texaco Mobil Sunoco Texaco LUBRICANT Regal AFB-2* Mobilplex EP No. 1 Prestige 42 Multifak 2 Fig. 38 — Evaporator-Fan Pulley Alignment and Adjustment *Preferred lubricant because it contains rust and oxidation inhibitors. 43 3. Fully retract motor plate adjusting bolts. 4. Loosen the 2 rear (nearest the evaporator coil) motor plate nuts. 5. Remove the 2 front motor plate nuts and carriage bolts. 6. Slide motor plate to the rear (toward the coil) and remove fan belt(s). 7. Slide motor plate to the front and hand tighten one of the rear motor plate nuts (tight enough to prevent the motor plate from sliding back but loose enough to allow the plate to pivot upward). 8. Pivot the front of the motor plate upward enough to allow access to the motor mounting hex bolts and secure in place by inserting a prop. 9. Remove the nuts from the motor mounting hex bolts and remove motor. 10. Reverse above steps to install new motor. Belt Tension Adjustment — To adjust belt tension: 1. 2. 3. 4. Remove power to unit. Remove motor mount nuts and bolts. Loosen fan motor nuts. See Fig. 39. Turn motor jacking bolts to move motor mounting plate left or right for proper belt tension. A slight bow should be present in the belt on the slack side of the drive while running under full load. 5. Tighten nuts. 6. Adjust bolts and nut on mounting plate to secure motor in fixed position. Recheck belt tension after 24 hours of operation. Adjust as necessary. Condenser-Fan Adjustment 1. 2. 3. 4. Shut off unit power supply. Remove fan guard. Loosen fan hub setscrews. Adjust fan height on shaft using a straightedge placed across venturi and measure per Fig. 40. 5. Tighten setscrews and replace fan guard. 6. Turn on unit power. Power Failure — Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during charging procedure. NO CHARGE — Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 1). Evaporator-Fan Motor Replacement 1. Shut off unit power supply. 2. Remove upper outside panel and open hinged door to gain access to motor. LOW CHARGE COOLING — Using appropriate cooling charging chart (see Fig. 41 and 42), add or remove refrigerant until conditions of the appropriate chart are met. Note that charging chart is different from those normally used. An accurate pressure gage and temperature sensing device are required. Measure liquid line pressure at the liquid line service valve using pressure gage. Connect temperature sensing device to liquid line near the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading. Indoor-air cfm must be within normal operating range of unit. Take outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine correct suction temperature. If intersection point on chart is above the curve, add refrigerant. If intersection point on chart is below curve, carefully recover some of the charge. Recheck suction pressure as charge is adjusted. Filter Drier — Replace whenever refrigerant system is exposed to atmosphere. Thermostatic Expansion Valve (TXV) — Each circuit has one. It is nonadjustable and is factory set to maintain 10 to 13° F superheat leaving the evaporator coil. Controls flow of liquid refrigerant to the evaporator coils. Fig. 39 — Belt Tension Adjustment Protective Devices COMPRESSOR PROTECTION Overcurrent — Each compressor has one manual reset, calibrated trip, magnetic circuit breaker. Do not bypass connections or increase the size of the circuit breaker to correct trouble. Determine the cause and correct it before resetting the breaker. Overtemperature — Each 06D type compressor (024-038 units only) has an internal protector to protect it against excessively high discharge gas temperatures. Fig. 40 — Condenser-Fan Adjustment 44 Crankcase Heater — Each compressor has a crankcase heater to prevent absorption of liquid refrigerant by oil in the crankcase when the compressor is idle. Since power for the crankcase heaters is drawn from the unit incoming power, main unit power must be on for the heaters to be energized. Relief Devices — All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices are installed on the suction line, liquid line, and on the compressor. IMPORTANT: After a prolonged shutdown or service job, energize the crankcase heaters for 24 hours before starting the compressors. tected against overcurrent by a 3.2-amp circuit breaker (CB4). Breaker can be reset. If it trips, determine cause of trouble before resetting. Control Circuit, 24-V — This control circuit is pro- Control Circuit, 115-V — This control circuit is protected against overcurrent by a 5.0-amp circuit breaker (CB3). Breaker can be reset. If it trips, determine cause of trouble before resetting. EVAPORATOR-FAN MOTOR PROTECTION — A manual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker. If the evaporatorfan motor is replaced with a different horsepower motor, resizing of the circuit breaker is required. Contact Carrier Application Engineering. CONDENSER-FAN MOTOR PROTECTION — Each condenser-fan motor is internally protected against overtemperature. HIGH- AND LOW-PRESSURE SWITCHES — If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automatically locked out. To reset, manually move the thermostat setting. Compressor Lockout Logic — If any of the safeties trip, the circuit will automatically reset (providing the safety has reset) and restart the compressor in 15 minutes. If any of the safeties trip 3 times within a 90-minute period, then the circuit will be locked out and will require manual resetting by turning off either the unit disconnect or the control circuit breaker, or opening the thermostat. Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request. FREEZE PROTECTION THERMOSTAT (FPT) — An FPT is located on the evaporator coil for each circuit. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized. Fig. 41 — Cooling Charging Chart, Sizes 024-034 Fig. 42 — Cooling Charging Chart, Sizes 038-048 45 TROUBLESHOOTING Typical refrigerant circuiting diagrams are shown in Fig. 43-45. LEGEND FPS — Freeze Protection Switch HPS — High-Pressure Switch LPS — Low-Pressure Switch Fig. 43 — Typical Refrigerant Circuiting (50EJ,EK,EW,EY024-034) 46 LEGEND FPS — Freeze Protection Switch HPS — High-Pressure Switch LPS — Low-Pressure Switch Fig. 44 — Typical Refrigerant Circuiting (50EJ,EK,EW,EY038,044) 47 LEGEND FPS — Freeze Protection Switch HPS — High-Pressure Switch LPS — Low-Pressure Switch Fig. 45 — Typical Refrigerant Circuiting (50EJ,EW048) 48 to Table 20 below for a description of alarms. The yellow LED blinks during transmission with the CCN (Carrier Comfort Network). The green LED blinks during transmission with the expansion board. Diagnostic LEDs (Light-Emitting Diodes) — There are 3 LEDs (red, yellow, and green) on the lower right hand side of the control board. The red light is used to check unit operation and alarms. A constant pulse is normal unit operation. A series of quick blinks indicates an alarm. Refer Table 20 — Control Board LED Alarms LED BLINKS 1 ERROR CODE DESCRIPTION Normal Operation 2 HF-13 Compressor 1 Safety 3 HF-14 Compressor 2 Safety 4 HF-15 Thermostat Failure 5 HF-05 SAT Thermistor Failure 6 HF-06 OAT Thermistor Failure 7 HF-03 Space Temp. Sen. Failure 8 HF-12 RAT Thermistor Failure 9 SE-05 Loss of Communications with Expansion board 10 HF-16 Control Board Failure 11 HF-17 Expansion Board Failure TROUBLESHOOTING COMMENTS The expansion board and control board flash the red LED in onesecond intervals when the board is operating properly. The high or low pressure safety switch for compressor no. 1 has opened for 3 seconds. The error will be cleared and compressor no. 1 will be allowed to turn on in 15 minutes. If the safeties have been tripped 3 times in 90 minutes, compressor no. 1 will be locked out until the control board has been manually reset. The high or low pressure safety switch for compressor no. 2 has opened for 3 seconds. The error will be cleared and compressor no. 2 will be allowed to turn on in 15 minutes. If the safeties have been tripped 3 times in 90 minutes, compressor no. 2 will be locked out until the control board has been manually reset. The thermostat is calling for both heating and cooling at the same time. The unit will operate on a first call basis and will automatically reset. The supply-air temperature (SAT) sensor has failed. First check for wiring errors, then replace sensor. The outside-air temperature (OAT) sensor has failed. First check for wiring errors, then replace sensor. The space temperature sensor has failed. First check for wiring errors, then replace sensor. The return-air temperature (RAT) sensor has failed. Ensure that the unit is a VAV unit. If NOT a VAV unit set DIP switch position 1 to the closed position and reset power. Then check for wiring errors. Finally, replace sensor. Communications between the expansion board and the control board have been interrupted. Ensure that an expansion board is installed and wired using the wire harness supplied with the expansion module. If an expansion board is not used ensure that DIP switch position 3 is in the closed position, and reset power. Generated when hardware has failed on control board. Replace the control board. Generated when hardware has failed on the expansion board. Replace the expansion board. LEGEND DIP — Dual In-Line Package LED — Light-Emitting Diode VAV — Variable Air Volume 49 Tables 21-23 show the input and output channel designations. Table 21 — I/O Channel Designations Base Module — CV TERMINAL NO. T1-2 T3-4 T5-6 T7-8 T9-10 T11-12 T13-14 T15-16 T17-25 T18-25 T19-25 T20-25 T21-25 T22-25 T23-25 T24-25 T26-27 T28-29 T30-29 T31-32 T33-32 T34-35 T36-35 T37-38 T39-38 K1 K2 K3 Table 22 — I/O Channel Designations Base Module — VAV TERMINAL NO. T1-2 T3-4 T5-6 T7-8 T9-10 T11-12 T13-14 T15-16 T17-25 T18-25 T19-25 T20-25 T21-25 T22-25 T23-25 T24-25 T26-27 T28-29 T30-29 T31-32 T33-32 T34-35 T36-35 T37-38 T39-38 K1 K2 K3 ASSIGNMENT SPT (CCN) — 10KV Thermistor STO (CCN) — 10KV Thermistor OAT — 5KV Thermistor SAT — 5KV Thermistor — SAT Reset — AI (2-10 vdc) — — Y1 or Remote Start/Stop — DI (24 vac) Y2 — DI (24 vac) W1 — DI (24 vac) W2 — DI (24 vac) G — DI (24 vac) Compressor 1 Safety — DI (24 vac) Compressor 2 Safety — DI (24 vac) Outside Air Enthalpy — DI (24 vac) Economizer Pos. — AO (4-20 mA) Heat 1 Relay — DO (24 vac) Heat 2 Relay — DO (24 vac) CV Power Exhaust 1/Modulating Pwr Exht — DO (115 vac) CV Power Exhaust 2 — DO (115 vac) Condenser Fan — DO (115 vac) OFC2 — DO (115 vac) — — Indoor Fan Relay — DO (HV) Compr. 1 — DO (HV) Compr. 2 — DO (HV) LEGEND (Tables 21 and 22) AI AO CCN CV DI DO HV KV OAT OFC RAT SAT SPT STO T VAV — — — — — — — — — — — — — — — — Analog Input Analog Output Carrier Comfort Network Constant Volume Direct Input Direct Output High Voltage Kilo-Ohms Outdoor-Air Temperature Outdoor Fan Contactor Return-Air Temperature Supply-Air Temperature Space Temperature Space Temperature Offset Terminal Variable Air Volume 50 ASSIGNMENT SPT (CCN) — 10KV Thermistor RAT — 5KV Thermistor OAT — 5KV Thermistor SAT — 5KV Thermistor — SAT Reset — AI (2-10 vdc) — — Remote Start/Stop — DI (24 vac) — — — — Compressor 1 Safety — DI (24 vac) Compressor 2 Safety — DI (24 vac) Outside Air Enthalpy — DI (24 vac) Economizer Pos. — AO (4-20 mA) Heat 1 Relay — DO (115 vac) Heat Interlock Relay — DO (115 vac) Modulated Power Exhaust — DO (115 vac) — Condenser Fan — DO (115 vac) OFC2 — DO (115 vac) Unloader 1 — DO (115 vac) Unloader 2 — DO (115 vac) Indoor Fan Relay — DO (HV) Compr. 1 — DO (HV) Compr. 2 — DO (HV) Table 23 — I/O Channel Designations Expansion Module — CV and VAV TERMINAL NO. T1-2 T3-4 T5-6 T7-8 T9-10 T11-12 T13-14 T15-16 T17-25 T18-25 T19-25 T20-25 T21-25 T22-25 T23-25 T24-25 T26-27 T28-29 T30-29 T31-32 T33-32 T34-35 T36-35 T37-38 T39-38 K1 K2 K3 AI DI DO IAQ T — — — — — ASSIGNMENT — — — — — IAQ Indoor — AI (2-10 vdc) IAQ Outdoor — AI (2-10 vdc) — Fan Status — DI (24 vac) Filter Status — DI (24 vac) Field Applied Status — DI (24 vac) Demand Limit — DI (24 vac) Fire — Unit Shutdown — DI (24 vac) Fire — Pressurization — DI (24 vac) Fire — Evacuation — DI (24 vac) Fire — Smoke Purge — DI (24 vac) — — Alarm Light Indicator — DO (24 vac) Power Exhaust Fire #1 — DO (115 vac) Power Exhaust Fire #2 — DO (115 vac) Power Exhaust Fire #3 — DO (115 vac) Power Exhaust Fire #4 — DO (115 vac) — — — — — LEGEND Analog Input Direct Input Direct Output Indoor Air Quality Terminal 51 PACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Installation Overview • Maintenance • Operating Sequence A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions. For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included. Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 535-006 Printed in U.S.A. Form 50E-3SI Pg 54 8-96 Replaces: 50E-1SI Tab 1b START-UP CHECKLIST MODEL NO.: SERIAL NO.: SOFTWARE VERSION (SEE FIG. 15) TECHNICIAN: DATE: PRE-START-UP: M VERIFY THAT DIP SWITCH SETTINGS ARE CORRECT M VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT M REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS M VERIFY INSTALLATION OF ECONOMIZER HOOD M VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES M VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS M VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT M CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE M VERIFY THAT UNIT IS LEVEL WITHIN TOLERANCES M CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW IS TIGHT M VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED M VERIFY THAT SUCTION, DISCHARGE, AND LIQUID LINE SERVICE VALVES ON EACH CIRCUIT ARE OPEN START-UP ELECTRICAL SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 COMPRESSOR AMPS — COMPRESSOR NO. 1 L1 L2 L3 — COMPRESSOR NO. 2 L1 L2 L3 SUPPLY FAN AMPS (CV) EXHAUST FAN AMPS (VAV) * *VAV fan supply amps reading must be taken with a true RMS meter for accurate readings. ELECTRIC HEAT AMPS (IF SO EQUIPPED) L1 L2 TEMPERATURES OUTDOOR-AIR TEMPERATURE F DB (Dry-Bulb) RETURN-AIR TEMPERATURE F DB COOLING SUPPLY AIR F L3 F ELECTRIC HEAT SUPPLY AIR (IF SO EQUIPPED) WB (Wet-Bulb) F PRESSURES REFRIGERANT SUCTION CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 PSIG REFRIGERANT DISCHARGE CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 PSIG M VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 45 CL-1 M ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS M ENSURE DRIVES OPERATE WITHIN LIMITS OF FAN PERFORMANCE TABLES HIGH-PRESSURE SWITCH SETTING PSIG LOW-PRESSURE SWITCH SETTING PSIG MOTOR PULLEY PART NUMBER FAN PULLEY PART NUMBER BELT PART NUMBER BELT SIZE in. FILTER QUANTITY FILTER SIZES in. CUT ALONG DOTTED LINE ADDITIONAL NOTES: CUT ALONG DOTTED LINE GENERAL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - START-UP CHECKLIST (cont) Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 535-006 Printed in U.S.A. Form 50E-3SI Pg CL-2 8-96 Replaces: 50E-1SI Tab 1b
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : 3.1-701 Create Date : 1996:11:10 17:18:21Z Modify Date : 2005:11:11 19:16:06-05:00 Metadata Date : 2005:11:11 19:16:06-05:00 Producer : Acrobat Distiller 2.0 for Windows Keywords : Format : application/pdf Title : Description : Creator : Carrier Corporation Subject : Document ID : uuid:e9c0d921-9d7e-4205-924d-71f9e59a8f7b Instance ID : uuid:1026332c-c5ee-402d-83f8-280c0dc52caf Page Count : 56 Author : Carrier CorporationEXIF Metadata provided by EXIF.tools