Carrier 90Ma Mf Mu Users Manual
90MAMFMU to the manual c112a3fa-0b29-4e88-9797-c9aaf91a4c40
2015-01-24
: Carrier Carrier-90Ma-Mf-Mu-Users-Manual-310586 carrier-90ma-mf-mu-users-manual-310586 carrier pdf
Open the PDF directly: View PDF
.
Page Count: 24
| Download | |
| Open PDF In Browser | View PDF |
Models 90MA/MF/MU, Design Series Two Beginning Serial Number C00400 62--10458--00 INSTALLATION OPERATION & SERVICE Marine/Industrial Single Package Cooling Unit OPERATION AND SERVICE MANUAL MARINE/INDUSTRIAL SINGLE PACKAGE COOLING UNIT MODELS 90MA/MF/MU, Design Series Two Beginning Serial Number C00400 Carrier Refrigeration Operations, A member of the United Technologies Corporation family. Stock symbol UTX. Carrier Transicold, Carrier Corporation, P.O. Box 4805, Syracuse, N.Y. 13221 U. S. A. Carrier Corporation 2000 D Printed in U. S. A. 0700 SAFETY SUMMARY GENERAL SAFETY NOTICES The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. The general safety notices are presented in the following three sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings and cautions appearing elsewhere in the manual follows the general safety notices. FIRST AID An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately. OPERATING PRECAUTIONS Always wear safety glasses. Keep hands, clothing and tools clear of the evaporator and condenser fans. No work should be performed on the unit until all circuit breakers, start-stop switches are turned off, and power supply is disconnected. Always work in pairs. Never work on the equipment alone. In case of severe vibration or unusual noise, stop the unit and investigate. MAINTENANCE PRECAUTIONS Beware of unannounced starting of the evaporator fan. Do not open the evaporator access panels before turning power off, disconnecting and securing the power source. Be sure power is turned off before working on motors, controls, solenoid valves and electrical control switches. Tag circuit breaker and power supply to prevent accidental energizing of circuit. Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems with the system should be diagnosed, and any necessary repairs performed, by qualified service personnel. In case of electrical fire, open circuit switch and extinguish with CO2 (never use water). SPECIFIC WARNING AND CAUTION STATEMENTS To help identify the label hazards on the unit and explain the level of awareness each one carries, an explanation is given with the appropriate consequences: WARNING -- means to warn against hazards or unsafe conditions which could result in severe personal injury or death. CAUTION -- means to warn against potential hazard or unsafe practice which could result in product or property damage. The statements listed below are applicable to the unit and appear elsewhere in this manual. These recommended precautions must be understood and applied during operation and maintenance of the equipment covered herein. WARNING Never reach into unit while fan is running. Lock open and tag unit disconnect before working on fan. Remove fuses and take them with you after noting this on tag. WARNING Follow all Safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. WARNING Lock open and tag unit disconnect before working on fan motor. Remove fuses and take them with you after noting this on tag. CAUTION Compressor crankcase heater must be energized for 24 hours prior to start up to prevent compressor bearing damage. Safety-1 62--10458--00 CAUTION Sharp edges of coil fins are exposed. To prevent injury, cover top of evaporator with cardboard or a few layers of heavy tape. CAUTION To avoid coil damage, cover evaporator face with plywood or other rigid sheet material. If any coil fins are mashed or bent, straighten with a coil fin comb of the proper tooth spacing (refer to “coil fins/inch” in Table 1 through Table 2). Check for refrigerant leaks. CAUTION Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage. 62--10458--00 Safety-2 TABLE OF CONTENTS PARAGRAPH NUMBER Page GENERAL SAFETY NOTICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1 FIRST AID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1 OPERATING PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1 MAINTENANCE PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1 SPECIFIC WARNING AND CAUTION STATEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1 1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2. MODEL CHART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.1 Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.2 Protect Unit from Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.3 Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.4 Install Accessory Heating Coil (if applicable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.5 Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.6 Install Accessory Plenum (If Supplied) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.7 Install Ventilation--Air Ductwork (If required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.8 Install Return Air Ductwork (If required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3.9 Check Return--Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3.10 Align Fan Shaft and Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3.11 Check Compressor Spring Mounts (008 & 012 size only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.12 Make Condenser Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.13 Install Condensate Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3.14 Make Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4. OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.1 To Start Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.2 To Shut Down Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.3 Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 5. SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.1 Return--Air Grille Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.2 Access Panel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.3 Evaporator Fan Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.4 Return--Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.5 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.6 Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.7 Water Regulating Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.8 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.9 Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.10 Evaporator Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.11 Pressure Relief Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.12 Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.13 Cycle--LocTM -- Protection Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.14 Discharge and Suction Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.15 Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 i 62--10458--00 LIST OF ILLUSTRATIONS FIGURE NUMBER Page Figure 1 Base Unit Interior Details (Typical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 2 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3 Horizontal Wheel Centering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4 Concentric Wheel Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 5 Connection Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 6 Typical Condenser Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 7 Condensate Drain Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 8 Fan Pulley Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 9 Gravity Flow Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 10 Forced Circulation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 11 Charging Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 12 Mounting Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 13 Wiring Schematic -- 90MA/MF/MU004/006 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 14 Component Arrangement -- 90MA/MF/MU004/006 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 15 Wiring Schematic -- 90MA/MF/MU008/012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 16 Component Arrangement -- 90MA/MF/MU008/012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 5 5 5 6 6 7 9 10 11 11 13 14 15 16 17 LIST OF TABLES TABLE NUMBER Page Table 1 90MA/MF/MU Physical Data -- Refrigerant 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Table 2 90MA/MF/MU Physical Data -- Refrigerant 407C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Table 3 90MA/MF Physical Data -- Refrigerant 134a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Table 4 Recommended Line Sizes, Remote Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62--10458--00 ii 2 3 4 7 3.1 1. INTRODUCTION Inspect Unit The 90M series single--package cooling units (See Figure 1) are designed to provide air conditioning aboard marine vessels and in industrial applications. The 90MA units are fitted with sea water cooled condensers while the 90MF units are fitted with fresh water cooled condensers. Both units are factory charged, wired and piped. The 90MU units are similar except they are configured for use with a remote mounted condenser. Check unit against shipping order. Inspect carefully for concealed shipping damage. If shipment is damaged or incomplete, file claim with transportation company and advise Carrier Transicold immediately. An accessory discharge plenum may be installed to provide free--blow into the conditioned space. Also, an accessory electric, hot water or steam coil heater may be installed to provide comfort heating. Refer to Figure 2 and Table 1 through Table 2 for unit size and weight. If desired, construct a frame of I--beams or angle iron that adequately supports unit. See Figure 12. 3.2 Protect Unit from Damage To maintain warranty, protect unit against adverse weather, theft, or vandalism on job site. 3.3 3.4 Provide Unit Support Install Accessory Heating Coil (if applicable) Electric heaters are installed at the top of the unit. Water or steam coil must be installed through the back of the unit as described in the Installation Instructions shipped with the accessory coil. 3.5 Rig and Place Unit NOTE Install accessories before placing unit. a. Provide space around unit for service, filter access, and overhead clearance as indicated in Figure 2. b. Move and store unit in upright position. c. Use slings with spacer under base skid to prevent panel damage when using hoist. d. Units as shipped are adequately dampened against vibration. If additional dampening is desired, place sponge rubber or rubber mat, between deck and base of unit or install vibration isolators. e. Unit should be level. Unit leveling tolerance is 1/8 inch per linear foot in any direction. (90MA/MF ONLY) Figure 1 Base Unit Interior Details (Typical) 2. MODEL CHART This manual covers 90M design series two units as shown in the following model chart. 1 2 3 4 5 6 7 8 9 10 11 9 0 M A 3 1 2 --- 6 2 3.6 Use plenum as template to mark hole locations in top panel. Drill 5/32--in. (0.4 cm) holes in top panel at marked locations and attach plenum with screws supplied. 1 3.7 PRODUCT CODE MA MF MU MODEL - 90/10 Copper Nickel Condenser - Copper Condenser - Condenserless 2 - R-22 3 - R-134a 4 - R-407C NOMINAL COOLING CAPACITY (R--22) 3. Install Accessory Plenum (If Supplied) Install Ventilation--Air Ductwork (If required) Connect ventilation ducts to flanges on outside--air supply opening (See Figure 2) using a flexible connection. Attach ductwork to ship structure and insulate with fiberglass and vapor barrier to reduce sound transmission and prevent vapor condensation. Weatherproof external ductwork, joints, and openings in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. VOLTAGE 5 - 208/230-3-60 6 - 460-3-60 9 - 400-3-50 DESIGN SERIES PACKAGING 3.8 Install Return Air Ductwork (If required) The unit back panel is to be field cut for alternate return--air (or outdoor--air inlet) opening as indicated in Figure 2. To install ductwork: a. Cut out the alternate return--air opening as required. INSTALLATION To install the unit, do the following: 1 62--10458--00 Table 1 90MA/MF/MU Physical Data -- Refrigerant 22 R--22 -- English Units BASE UNIT 90MA/MF/MU UNITS NOMINAL CAPACITY OPERATING WEIGHT Base Unit -- 90MA/MF Base Unit -- 90MU Discharge Plenum COMPRESSOR TYPE LEGEND FPT = Female Pipe Thread English (Metric) 204 206 208 212 204 206 208 212 Tons (kW) 3 5 7.5 10 10.5 17.6 26.4 35.1 Pounds (kg) Pounds (kg) Pounds (kg) Quantity of Cylinders Quantity of Unloading Cylinders Quantity of Capacity Steps DISCHARGE PRESSURE SWITCH Opens -- 90MA/MF Closes -- 90MA/MF Opens -- 90MU Closes -- 90MU SUCTION PRESSURE SWITCH Opens Closes OPERATING CHARGE -- 90MA/MF CONDENSER -- 90MA/MF Number & Type Water Volume EVAPORATOR AIR FAN Nominal Flow Standard Speed Range Maximum Allowable RPM Belt Quantity / Pulley Pitch Diameter Motor Pulley Pitch Diameter Range Motor Nominal Rating(@60 Hz)...Frame Size Standard Alternate (See Note 1) Alternate (See Note 1) EVAPORATOR COIL Tube Type Quantity of Rows...fin Spacing Face Area RETURN AIR FILTERS Quantity...Size CONDENSER CONNECTIONS Water Inlet (bottom) & Outlet (top) Maximum Working Pressure (refrigerant side) CONDENSATE DRAIN CONNECTIONS ACCESSORY HEATING COILS HOT WATER Quantity of Rows...fin spacing Face Area Water Inlet (top) & Outlet Connection (bottom) STEAM Quantity of Rows...fin spacing Face Area Water Inlet (top) & Outlet Connection (bottom) R--22 -- Metric Units 390 427 330 360 25 25 Welded Hermetic Scroll ---- 895 950 835 890 50 50 Semi--Hermetic Reciprocating ---- 4 0 1 177 194 150 163 11.3 11.3 Welded Hermetic Scroll 6 2 2 ---- 406 431 379 404 22.7 22.7 Semi--Hermetic Reciprocating ---- 4 0 1 psig (kPa) psig (kPa) psig (kPa) psig (kPa) 39510 29520 4267 32020 272569 2034138 293748 2206138 psig (kPa) psig (kPa) pounds (kg) 274 677 18628 46248 2.4 5.1 gallon (liter) cfm (m3/h) RPM 3.1 5.3 525-750 horse power horse power horse power 1/3...56 3/4...56 ---- inches FPT psig (kPa) inches FPT 1.4 4.5 1....Tube In Tube 0.86 2.42 1.48 3.3 9.2 Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60 Hz 1200 2000 3000 4000 1698 2830 4245 5660 1 / 8.0 inches (cm) 10 0.39 inches (cm) inches (cm) fins/inch(cm) sq ft (sq m) 11.2 6 2 2 647-915 495-700 1 / 6.4 1 / 8.5 2.4 to 3.4 600-850 427-652 1050 1 / 7.0 1 / 20.3 593-762 412-583 500-708 1 / 16.3 1 / 21.6 6.1 to 8.6 1 / 17.8 3/4...56 1...56 2...56 .25 / 56 .56 / 56 .75 / 56 1.5 / 56 1...56 2...56 3...56 .56 / 56 .75 / 56 1.5 / 56 2.2 / 56 ---3...56 ---------2.2 / 56 ---3/8 (.95 cm) OD, Copper Tubes, Aluminum Fins Prime 2...14.4 3...14.4 3...12.5 2...5.7 3...5.7 3...4.9 5 5 7.3 8.5 0.46 0.46 0.68 0.79 Factory Supplied, Cleanable 2...16 x 25 x 1 4...16 x 20 x 1 2...40.6x63.5x2.5 4...40.6x50.8x2.5 1/2 3/4 1 1 1/2 3/4 400 3/4 1 1 2758 3/4 fins/inch(cm) sq ft (m) inches (cm) 1...15 1...15 5 5 7/8 ODF 2...14 2...14 6 6 1--1/4 MPT 1...5.9 1...5.9 0.46 0.46 7/8 ODF 2...5.5 2...5.5 0.56 0.56 1--1/4 MPT fins/inch(cm) sq ft (m) inches (cm) See Note 2 See Note 2 See Note 2 1...14 1...14 6.9 6.9 1--1/4 MPT See Note 2 See Note 2 See Note 2 1...5.5 1...5.5 0.64 0.64 1--1/4 MPT MPT = Male Pipe Thread ODF = Outside Diameter Female NOTES: 1. Motors and drives other than those furnished with unit must be purchased separately. Contact your Carrier Transicold representative. 2. Accessory heating coil in 004 and 006 units is combination hot water/steam. See hot water data. 62--10458--00 2 Table 2 90MA/MF/MU Physical Data -- Refrigerant 407C R--407C -- English Units BASE UNIT 90MA/MF/MU UNITS NOMINAL CAPACITY OPERATING WEIGHT Base Unit -- 90MA/MF Base Unit -- 90MU Discharge Plenum COMPRESSOR TYPE LEGEND FPT = Female Pipe Thread English (Metric) 404 406 408 412 404 406 408 412 Tons (kW) 3 5 7.5 10 10.5 17.6 26.4 35.1 Pounds (kg) Pounds (kg) Pounds (kg) Quantity of Cylinders Quantity of Unloading Cylinders Quantity of Capacity Steps DISCHARGE PRESSURE SWITCH Opens -- 90MA/MF Closes -- 90MA/MF Opens -- 90MU Closes -- 90MU SUCTION PRESSURE SWITCH Opens Closes OPERATING CHARGE -- 90MA/MF CONDENSER -- 90MA/MF Number & Type Water Volume EVAPORATOR AIR FAN Nominal Flow Standard Speed Range Maximum Allowable RPM Belt Quantity / Pulley Pitch Diameter Motor Pulley Pitch Diameter Range Motor Nominal Rating(@60 Hz)...Frame Size Standard Alternate (See Note 1) Alternate (See Note 1) EVAPORATOR COIL Tube Type Quantity of Rows...fin Spacing Face Area RETURN AIR FILTERS Quantity...Size CONDENSER CONNECTIONS Water Inlet (bottom) & Outlet (top) Maximum Working Pressure (refrigerant side) CONDENSATE DRAIN CONNECTIONS ACCESSORY HEATING COILS HOT WATER Quantity of Rows...fin spacing Face Area Water Inlet (top) & Outlet Connection (bottom) STEAM Quantity of Rows...fin spacing Face Area Water Inlet (top) & Outlet Connection (bottom) R--407C -- Metric Units 390 427 330 360 25 25 Welded Hermetic Scroll ---- 895 950 835 890 50 50 Semi--Hermetic Reciprocating ---- 4 0 1 177 194 150 163 11.3 11.3 Welded Hermetic Scroll 6 2 2 ---- 406 431 379 404 22.7 22.7 Semi--Hermetic Reciprocating ---- 4 0 1 psig (kPa) psig (kPa) psig (kPa) psig (kPa) 39510 29520 4267 32020 272569 2034138 293748 2206138 psig (kPa) psig (kPa) pounds (kg) 274 677 18628 46248 2.4 5.1 gallon (liter) cfm (m3/h) RPM 3.1 5.3 11.2 525-750 647-915 495-700 1 / 6.4 1 / 8.5 2.4 to 3.4 horse power horse power horse power 1/3...56 3/4...56 ---- 3/4...56 1...56 ---- 1/2 3/4 inches FPT psig (kPa) inches FPT 4.5 1....Tube In Tube 0.86 2.42 1.48 3.3 9.2 Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60 Hz 1200 2000 3000 4000 1698 2830 4245 5660 1 / 8.0 inches (cm) 1.4 0.39 inches (cm) inches (cm) fins/inch(cm) sq ft (sq m) 10.0 6 2 2 600-850 427-652 1050 1 / 7.0 1 / 20.3 593-762 412-583 500-708 1 / 16.3 1 / 21.6 6.1 to 8.6 1 / 17.8 1...56 2...56 .25 / 56 .56 / 56 .75 / 56 1.5 / 56 2...56 3...56 .56 / 56 .75 / 56 1.5 / 56 2.2 / 56 3...56 ---------2.2 / 56 ---3/8 OD, Copper Tubes, Aluminum Fins Prime Prime 2...14.4 3...14.4 3...12.5 2...5.7 3...5.7 3...4.9 5 5 7.3 8.5 0.46 0.46 0.68 0.79 Factory Supplied, Cleanable Factory Supplied, Cleanable 2...16 x 25 x 1 4...16 x 20 x 1 2...40.6x63.5x2.5 4...40.6x50.8x2.5 1 1 1/2 3/4 400 3/4 1 1 2758 3/4 fins/inch(cm) sq ft (m) inches (cm) 1...15 1...15 5 5 7/8 ODF 2...14 2...14 6 6 1--1/4 MPT 1...5.9 1...5.9 0.46 0.46 7/8 ODF 2...5.5 2...5.5 0.56 0.56 1--1/4 MPT fins/inch(cm) sq ft (m) inches (cm) See Note 2 See Note 2 See Note 2 1...14 1...14 6.9 6.9 1--1/4 MPT See Note 2 See Note 2 See Note 2 1...5.5 1...5.5 0.64 0.64 1--1/4 MPT MPT = Male Pipe Thread ODF = Outside Diameter Female NOTES: 1. Motors and drives other than those furnished with unit must be purchased separately. Contact your Carrier Transicold representative. 2. Accessory heating coil in 004 and 006 units is combination hot water/steam. See hot water data. 3 62--10458--00 Table 3 90MA/MF Physical Data -- Refrigerant 134a R--134a -- English Units BASE UNIT 90MA/MF LEGEND FPT = Female Pipe Thread 308 312 308 312 Tons (kW) 5.5 8 19.3 28.1 Pounds (kg) Pounds (kg) 895 50 950 50 English (Metric) NOMINAL CAPACITY OPERATING WEIGHT Base Unit Discharge Plenum COMPRESSOR TYPE -- Reciprocating Quantity of Cylinders Quantity of Unloading Cylinders Quantity of Capacity Steps DISCHARGE PRESSURE SWITCH Opens Closes SUCTION PRESSURE SWITCH Opens Closes OPERATING CHARGE CONDENSER Number & Type Water Volume EVAPORATOR AIR FAN Nominal Flow Standard Speed Range Maximum Allowable RPM Belt Quantity / Pulley Pitch Diameter Motor Pulley Pitch Diameter Range Motor Nominal Rating(@60 Hz)...Frame Size Standard Alternate (See Note 1) Alternate (See Note 1) EVAPORATOR COIL Tube Type Quantity of Rows...fin Spacing Face Area RETURN AIR FILTERS Quantity...Size CONDENSER CONNECTIONS Water Inlet (bottom) & Outlet (top) Maximum Working Pressure (refrigerant side) CONDENSATE DRAIN CONNECTIONS ACCESSORY HEATING COILS HOT WATER Quantity of Rows...fin spacing Face Area Water Inlet (top) & Outlet Connection (bottom) STEAM Quantity of Rows...fin spacing Face Area Water Inlet (top) & Outlet Connection (bottom) R--134a -- Metric Units UNITS Semi--Hermetic 4 0 1 6 2 2 406 431 22.7 22.7 Semi--Hermetic 4 6 0 2 1 2 psig (kPa) psig (kPa) 33510 23520 231069 1620138 psig (kPa) psig (kPa) pounds (kg) 73 225 4821 15235 gallon (liter) cfm (m3/h) RPM inches (cm) inches (cm) horse power horse power horse power fins/inch(cm) sq ft (sq m) inches (cm) 11.2 5.1 4.5 1....Tube In Tube 1....Tube In Tube 2.42 9.2 Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60 Hz 3000 4000 4245 5660 495--700 600--850 412--583 500--708 1050 1 / 8.5 1 / 7.0 1 / 21.6 1 / 17.8 2.4 to 3.4 6.1 to 8.6 1...56 2...56 3...56 2...56 .75 / 56 1.5 / 56 3...56 1.5 / 56 2.2 / 56 ---2.2 / 56 ---3/8 OD(0.95) cm, Copper Tubes, Aluminum Fins Prime 3...12.5 3...14.9 7.3 8.5 0.68 0.79 Factory Supplied, Cleanable 4...16 x 20 x 1 4...40.6 x 50.8 x 2.5 inches FPT psig (kPa) inches FPT 1 fins/inch(cm) sq ft (m) inches (cm) 2...14 6 fins/inch(cm) sq ft (m) inches (cm) 1...14 6.9 MPT = Male Pipe Thread 10 1 1 400 3/4 1 2758 3/4 2...14 6 2...5.5 0.56 1--1/4 MPT 2...5.5 0.56 1--1/4 MPT 1...14 6.9 1--1/4 MPT 1...5.5 0.64 1...5.5 0.64 1--1/4 MPT ODF = Outside Diameter Female NOTES: 1. Motors and drives other than those furnished with unit must be purchased separately. Contact your Carrier Transicold representative. 62--10458--00 4 UNIT A B C D E F G H J K L M N P Q R 004 006 36.19(919) 21.88(556) 59.12(1501) SEE NOTE 2 24(610) 13.81(351) 16.44(418) 13.13(333) 15(381) 0.75(19) 0.75(19) 12.5(318) 10.62(270) 17.06(433) 20.50(521) 17(432) 31.88(810) 2.06(52) 10(254) 15.56(395) 008,012 48(1219) 29.62(752) 69.50(1765) 19.38(492) 17.25(438) 1.31(33) 11.44(291) 23.25(591) 25.37(644) 17(432) 42.62(1083) 3(76) 12.50(318) 16(406) NOTES: 1. Certified dimension drawings available upon request 2. Minimum required clearance at back of unit is zero. Clearance above and at right (90MA008,012 only) and at left of unit depends on space required for accessory plenum, ductwork, condenser piping, accessory heater piping, condensate drain line and power wiring 3. Water connections are located on left side of unit (Refer to “Make Condenser Connections”, Condensate drain connections are located on left side of unit for 004 & 006, and on both sides of unit for 008 & 012. Figure 2 Unit Dimensions 3.10 b. Attach a one--inch (2.5 cm) flange or attach a flanged, flexible duct connection directly to unit. horizontally centered between the inside edges of their fan scroll ventures (Figure 3). Adjust as follows: a. Loosen set screws holding wheel to shaft. b. Center the wheel by sliding it horizontally. c. Re--tighten set screws. CONCENTRIC ALIGNMENT -- Shaft and wheels must be concentrically centered with the venturi (Figure 4). Shaft bearings are supported by bearing supports. If shaft and wheels are concentrically misaligned from shipping shock, it is possible to re--bend bearing support arms to original positions. Replace the bearing support if it has been extensively damaged during shipping. If an outdoor makeup air damper is to be installed, attach it directly to unit back panel and install flexible connection between damper and remaining ductwork. Use accepted ductwork installation procedures. Follow all applicable codes. c. Completely blank off the standard return--air opening with a field--fabricated filler panel. The panel must be removable for service access. Refer to paragraph 5.1. 3.9 Align Fan Shaft and Wheel HORIZONTAL WHEEL CENTERING -- All wheels must be Check Return--Air Filters Ensure filters shipped with unit are in place. Never operate unit without return air filters in place. DIMENSION “D” MUST BE EQUAL ALL AROUND Figure 3 Horizontal Wheel Centering Figure 4 Concentric Wheel Alignment 5 62--10458--00 90MA/MU008/012 UNITS 90MA/MF004/006 UNITS 90MU008/012 UNITS 90MU004/006 UNITS UNIT 90MA/MF004 90MA/MF006 90MA/MF008/012 90MU004 90MU006 90MU008/012 A* 1/2 3/4 1” ---------- B* 1/2 ---1” ---------- C* ---3/4 ------------- D* ¾ FPT E ---------1/2 flare 1/2 flare 5/8 O.D. F ---------1/2 flare 1/2 flare 3/4 O.D. G 1.75 (45) * A = Condenser In, B & C = Condenser Out, D = Condensate, all Female Pipe Thread, E = Liquid Refrigerant (field cut), F = Refrigerant Discharge (field cut), G = Electrical Opening 3.11 Figure 5 Connection Locations Check Compressor Spring Mounts Install water--regulating valve in water supply line (008 & 012 size only) outside cabinet as follows. The compressors are held rigid in shipment by bolts extending through a washer, grommet and compressor foot into a weld nut. Loosen each bolt (4 per compressor) until compressor floats freely on springs. Then re--tighten bolts until there is slight pressure on the neoprene gasket. This will steady the compressor and prevent start and stop rocking. See Figure 5 The compressors have reversible oil pumps that operate in either direction; therefore, the direction of rotation need not be checked. 3.12 Make Condenser Connections -- Condenser water inlet and outlet connections are shown in Figure 5. Piping arrangements for condenser cooling water are shown in Figure 6. UNIT MOUNTED CONDENSER (90MA/MF) Figure 6 Typical Condenser Water Piping a. Route regulating valve capillary with its flare nut to the port on refrigerant discharge line (Figure 1), using any convenient unused opening on side of unit. Use a grommet in panel to prevent chafing of capillary. b. Remove cap from discharge line fitting. c. Remove cotter pin taped to discharge line fitting. Insert pin, split end first, into regulating valve flare. Connect condenser water supply and return lines as indicated. When connecting water lines, hold the condenser inlet and outlet stubs firmly with a wrench at the female pipe thread hex fitting to prevent twisting. Do not use water lines smaller than connection sizes shown in Figure 5. Observe all applicable plumbing and sanitary codes. 62--10458--00 6 UNIT ((90MU)) 004 006 008 012 Table 4 Recommended Line Sizes, Remote Condenser LENGTH OF RUN 0--25 26--50 51--75 DISCH LIQUID DISCH LIQUID DISCH LIQUID 1/2 (1.3) 5/8(1.6) 7/8(2.2) 7/8(2.2) 1/2(1.3) 1/2(1.3) 5/8(1.6) 5/8(1.6) 5/8(1.6) 7/8(2.2) 7/8(2.2) 1-1/8(2.9) 1/2(1.3) 1/2(1.3) 5/8(1.6) 5/8(1.6) 5/8(1.6) 7/8(2.2) 7/8(2.2) 1-1/8(2.9) 1/2(1.3) 1/2(1.3) 5/8(1.6) 5/8(1.6) 76--100 DISCH LIQUID 7/8(2.2) 7/8(2.2) 1-1/8(2.9) 1-1/8(2.9) 1/2(1.3) 1/2(1.3) 5/8(1.6) 5/8(1.6) NOTES: 1. Line sizes given in inches (cm). 2. Line sizes should never be smaller than cooling unit connection size. 3. A nominal number of fittings has been considered in determining line sizes. Smaller line sizes may be considered if run is simple and few fittings are used. d. Hold flare tightly against fitting while connecting flare nut. Round end of cotter pin will depress core of fitting. The opened fitting allows refrigerant pressure to act on water regulating valve. Tighten nut to prevent leakage. Fitting automatically seals when nut is removed. REMOTE MOUNTED CONDENSER (90MU) -- Install remote mounted condenser in accordance with the installation instructions provided with condenser. Connection locations for liquid and discharge lines are shown in Figure 5. Recommended line sizes are given in Table 4. Additional instructions can be found in Carrier System Design Manual, Part 3, for standard refrigeration piping techniques. On 008 and 012 size units, secure discharge line to bracket at unit outlet using proper clamp from supplied fastener package Condenserless (90MU) units are shipped with a refrigerant holding charge. After refrigerant connections are made, leak test, reclaim refrigerant, evacuate, and charge system as described in paragraph 5.9. 3.13 Figure 7 Condensate Drain Trap Do not use drain line smaller than 3/4 inch. Use hole(s) provided in panel for drain line. Pitch drain line downward toward scupper. Installation of a plugged tee is recommended for cleaning. Fill trap with water to make an air seal. Observe all sanitary requirements. Install Condensate Drain Line Install a trapped condensate drain line at unit drain connection. The drain requires standard pipe connected to condensate pan nipple(s). Figure 7 shows proper trap design. 3.14 Make Electrical Connections Provide an adequate fused disconnect switch within sight of the unit. Provision for locking switch open (OFF) is advisable to prevent power from being turned on when unit is being serviced. GENERAL -- Determine design negative static pressure. This pressure is not the same as fan total static pressure, which includes pressure losses downstream as well as upstream from the evaporator air fan. Always assume the worst conditions, such as having return air filters clogged with debris. POWER WIRING -- Conduit opening for all units is on left side of unit near control box. Connect field power wires at the compressor contactor. Supply voltage must be in accordance with nameplate voltage. Voltage between phases must be balanced within 2% and current within 10% with compressor running. Correct improper voltage or phase imbalance. Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and shall void the Carrier warranty. Use the following formula to determine the percent voltage imbalance. Referring to Figure 7, differential 1 must be equal to or larger than negative static pressure at design operating condition. Store enough water in trap to prevent losing seal. Differential 2 must be equal to or larger than one--half the maximum negative static pressure. To avoid loss of seal when the fan starts, differential 3 must be greater than the maximum negative static pressure. 7 62--10458--00 e. Allow crankcase heater to remain energized (unit power on) for at least 24 hours. Open any valves in condenser cooling water supply lines and then set selector switch at COOL position. If room temperature is above thermostat setting compressor will start. On first start--up, set water regulating valve. (Refer to paragraph5.7.) f. Set thermostat for comfort as desired. 4.2 CONTROL WIRING -- On extended voltage (208/230--v) units, the control transformer is factory wired for 208--v usage. If unit is to be used on 230--v system, reconnect primary wiring on transformer. See Figure 13 (004/006 size) or Figure 15 (008/012 size). 4.3 OPERATION CAUTION Compressor crankcase heater must be energized for 24 hours prior to start up to prevent compressor bearing damage. 4.1 To Start Unit a. Thoroughly inspect exterior of unit. Clean and dust up debris, then wash with mild soap and water solution. b. On 008 & 012 size units, ensure compressor discharge, suction and liquid service valves are open. The valves are accessible from the front of the unit. To open valve, turn counterclockwise. After opening, replace and tighten valve cap to prevent leakage. Check oil level in compressor sight glass. If level is below glass, add oil to bring level to approximately 1/4 glass. If level is above bottom of glass, do not remove any oil until the crankcase heater has been energized for at least twenty--four hours. c. With selector switch in OFF position, turn main power on. Leave power on for 24 hours so that crankcase heater can drive off accumulated refrigerant. d. If desired, the selector switch may be placed in the FAN position during the crankcase warm--up period. On first start--up, check fan speed (Table 1 through Table 2) and rotation (Figure 1). If fan requires adjustment, refer to paragraph 5.3. 62--10458--00 Sequence Of Operation Unit operation is dependent on the position of the mode selector switch. (See note 3, Figure 14 or Figure 16.) Operation sequence for each switch position is provided in the following paragraphs. OFF POSITION: With correct voltage supplied at the field power supply terminals, see Figure 13 or Figure 15 power flows through normally closed crankcase heater relay (CHR) contacts (CHR, 4/5) to energize the crankcase heater (CH). TO PLACE THE UNIT IN THE FAN MODE: The switch (SW) is placed in the FAN position to supply 24 volt control power, to energize indoor fan contactor (IFC). Energizing IFC closes contacts (IFC, 11/21, 12/22 & 13/23) to energize the motor. Operation of the crankcase heater is maintained. TO PLACE THE UNIT IN THE COOL MODE: The switch (SW) is placed in the COOL position. With thermostat (T--LOW) calling for cooling (closed to contacts R & W) control power flows from TRAN through T--LOW, SW and compressor lockout (CL) normally closed contacts to the discharge pressure switch (DPS). On 008/012 size units, flow continues through the compressor internal protector (IPC), compressor overloads (OLA & OLB) and the suction pressure switch (SPS), to energize CHR. On 004/006 size units, flow continues directly thorough the suction pressure switch to energize CHR. Energizing CHR opens contacts CHR 4--5 to de--energize CH and closes contacts CHR 1--3 and energize the compressor contactor (CC). Energizing CC closes its contacts to start the compressor motor (C). Operation of the indoor fan motor (IFM) is maintained. On 90MU units, power also flows from terminal TB1--5 to energize condenser fan relay (CFR). Energizing CFR closes its contacts to supply power to the field supplied condenser fan relay. 012 size units are fitted with a two stage cooling system. On these units, if thermostat switch T--HIGH is also calling for cooling, power flows through thermostat On all units, the thermostat is factory installed. A sensing element is provided in the return air. To wire these units to a remote thermostat, or to a remote control switch and thermostat, refer to unit Wiring Diagram or contact your Carrier Transicold representative. 4. To Shut Down Unit a. Turn selector switch to OFF position. Do not shut off main power except to service unit. The crankcase heater is operative only when main power is on. (Refer to paragraph 5.12). b. If unit is to be used for winter heating, set selector switch at HEAT position and re--set thermostat at desired setting. c. If unit may be exposed to freezing temperatures, drain water from condenser and water piping. Add a noncorrosive antifreeze to residual water in system. 8 switch T--HIGH to energize liquid line solenoid (LLS) [to activate the full evaporator coil and all compressor cylinders]. If thermostat switch T--HIGH is not calling for cooling, power flows to energize compressor unloader solenoid (US) [to unload compressor cylinders]. 5.2 When room temperature falls to the cutout point of T--LOW, switch T--LOW opens to de--energize CHR, stopping the compressor motor and energizing CH. The machine enters a stand--by state, ready to restart automatically on room thermostat call for cooling. 5.3 a. Remove return--air grille as described above. b. Remove the panel fastening screws now exposed. c. Pull out and down to remove top panel. d. Pull out and up to remove bottom panel. Evaporator Fan Adjustment WARNING Never reach into unit while fan is running. Lock open and tag unit disconnect before working on fan. Remove fuses and take them with you after noting this on tag. If any safety device opens (CLO, SPS, DPS, IP, OLA or, OLB) relay CHR is de--energized, stopping the compressor motor and energizing the crankcase heater. SPEED ADJUSTMENT -- The fan motor pulleys are factory set at the fan speeds listed in Table 1, Table 3 or Table 2. to change fan speed, do the following: a. Shut off unit power supply. b. Loosen fan belt by loosening fan motor from mounting bracket. Do not loosen fan motor mounting bracket from unit. c. Loosen movable pulley flange set screw (Figure 8). d. Screw movable flange toward fixed flange to increase fan speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum allowable fan speed or motor full load amps indicated on motor nameplate. e. Set movable flange set screw at nearest flat of pulley hub and tighten set screw. f. Check pulley alignment and belt tension adjustment as described below. g. Check fan operation. Repeat above procedure as required. TO PLACE THE UNIT IN THE HEAT MODE: The switch (SW) is placed in the HEAT position. With thermostat (T--LOW) calling for heating (closed to contacts R & B), 24 volt control power flows through manual reset temperature cutout MC to energize safety relay H2. Power also flows through air flow switch (AS) and automatic cutout (AC) to energize operating relay (H1). Energizing relays H1 and H2 closes contacts to energize the heaters. Placing SW in the FAN position de--energizes all cooling or heating control circuits in the same manner as activation of a safety switch. Placing SW in the OFF position also de--energizes IFC to stop the indoor fan motor. 5. Access Panel Removal SERVICE WARNING Never reach into unit while fan is running. Lock open and tag unit disconnect before working on fan. Remove fuses and take them with you after noting this on tag. CAUTION Sharp edges of coil fins are exposed. To prevent injury, cover top of evaporator with cardboard or a few layers of heavy tape. CAUTION To avoid coil damage, cover evaporator face with plywood or other rigid sheet material. If any coil fins are mashed or bent, straighten with a coil fin comb of the proper tooth spacing (refer to “coil fins/inch” in Table 1 through Table 2). Check for refrigerant leaks. 5.1 Return--Air Grille Removal Figure 8 Fan Pulley Adjustment a. Pull grille out from top. Shut off unit power supply. Loosen fan motor pulley set screws and slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting bracket (See Figure 8). PULLEY ALIGNMENT -- b. Pull grille up to release hinge pins from lower panel. c. To reassemble, reverse procedure. 9 62--10458--00 BELT TENSION ADJUSTMENT -- Shut off unit power supply. Loosen fan motor from mounting bracket. Do not loosen motor mounting bracket from unit. Move fan motor up or down until proper belt tension is achieved (approximately 3/4--in. deflection with 8--pound tension at midpoint of belt span). Lubrication -- Fan motor and fan shaft bearings are lubricated for the life of the bearings. No re--lubrication is required 5.4 spring tension, decrease water flow and increase pressure. If pressure reading is above operating range, rotate the square head adjusting screw clockwise; this will decrease spring tension, increase water flow and decrease pressure. c. Only the water regulating valve opening point is adjustable. The closing point is 3 to 7 psig below the opening point and is non--adjustable. Return--Air Filter 5.8 Inspect filters twice monthly and clean as required by operating conditions. Filter size and type are listed in Table 1, Table 3 or Table 2. To clean filters flush with hot water or steam or soak in a mild water solution of soap or detergent. Refer to filter manufacturer’s instructions as applicable. Do not operate unit without return--air filters in place. 5.5 WARNING Follow all Safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Condensate Drain Clean condensers with an inhibited hydrochloric acid solution. The acid can stain hands and clothing, attack concrete and, without inhibitor, can attack steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases. Warm solution acts faster, but cold solution is just as effective if applied for a longer period. Clean the drain line and unit drain pan at the start of each cooling season. Check flow by pouring water into drain. Be sure trap is filled as shown in Figure 7 to maintain an air seal. 5.6 Condenser Condensers may require cleaning of water--deposited scale. Evaporator Coil WARNING Never reach into unit while fan is running. Lock open and tag unit disconnect before working on fan. Remove fuses and take them with you after noting this on tag. Remove dirt and debris from evaporator coil as required by condition. Clean coil with a stiff brush, vacuum cleaner or compressed air. Use a fin comb of the correct tooth spacing (Refer toTable 1, Table 3 or Table 2 for coil fins/inch) when straightening mashed or bent coil fins. 5.7 Water Regulating Valve PREPARATION FOR OPERATION. a. Open the water regulating valve inlet and outlet isolation valves. b. Close the water regulating valve bypass valve. ADJUSTMENT a. Figure 9 Gravity Flow Method The compressor discharge pressure is controlled by the water regulating valve and may be monitored by observing liquid line pressure. GRAVITY FLOW METHOD a. Disconnect condenser piping at unit, including isolation valves and water regulating valve. b. Fill condenser as shown in Figure 9. Follow acid manufacturer’s instructions. When condenser is full, allow solution to remain overnight c. Drain condenser and flush with clean water. NOTE Adjustments to the water regulating valve must be made slowly, allowing ample time for response and stabilization. FORCED CIRCULATION METHOD b. Install a calibrated gauge at the liquid line service port. Operating liquid line range for R--22 units is 250 to 270 psig (1724 to 1862 kPa), for R--134a units is 155 to 180 psig (1069 to 1241 kPa) and for R--407C is 267 to 288 psig (1841 to 1986 kPa). If pressure reading is below operating range, rotate the square head adjusting screw counterclockwise; this will increase 62--10458--00 a. Disconnect condenser piping at unit, including isolation valves and water regulating valve. b. Fill system as shown in Figure 10. Follow acid manufacturer’s instructions. Fully open vent pipe when filling system. The vent may be closed when system is full and pump is operating. 10 c. Regulate flow to condenser with a supply line valve. If pump is a non--overloading type, the valve may be fully closed while pump is running. For average scale deposit, allow solution to remain in condenser overnight. For heavy scale deposit, allow 24 hours. d. Drain condenser and flush with clean water. (1607 kPa) for R--407C units. Charge to a clear sight glass. 90MU004 UNITS R--22 90MU006 UNITS R--22 5.9 Figure 10 Forced Circulation Method Refrigerant Charging 90MA/MF -- These units are shipped with a full operating charge. If recharging is necessary (complete charge lost), weigh in amount of refrigerant indicated on unit nameplate and in Table 1, Table 3 or Table 2. If unit has partial charge, it must be recharged by removing existing charge and recharging by weighing in the required amount of refrigerant. 90MU004 & 006 -- These units, used with remote condensers, are shipped with a holding charge only. To charge: a. Open discharge and liquid service valves. b. Leak test, reclaim refrigerant and evacuate. c. Using standard refrigerant charging techniques and charging charts (Figure 11) add refrigerant as required to maintain proper operating conditions. 90MU008 & 012 -- These units, used with remote condensers, are shipped with a holding charge only. To charge: a. Open discharge line, liquid line, compressor discharge and compressor suction service valves. b. Leak test, reclaim refrigerant and evacuate. c. Add sufficient refrigerant vapor to permit continuous operation after starting unit. d. Start unit. Using standard charging techniques, add refrigerant as required to maintain normal operating conditions. Use charging chart supplied with condenser, if available. If information is not available, block off enough of condenser or set water regulating valve as applicable to maintain a discharge pressure of 220 psig (1517 kPa) for R--22 units or 233 psig 2758 2620 2482 2344 2206 2069 1930 1793 1655 1517 1379 1241 COMPRESSOR DISCHARGE PRESS -- PSIG COMPRESSOR DISCHARGE PRESS -- kPa 90MU004 UNITS R--407C 400 380 360 340 320 300 280 260 240 220 200 180 (TEA = TEMPERATURE, ENTERING AIR) TEA120F/49C TEA110F/43C TEA100F/38C TEA90F/32C TEA80F/27C TEA70F/21C TEA60F/16C 70 75 80 85 90 95 100PSIG 483 517 552 587 622 655 690kPa COMPRESSOR SUCTION PRESSURE 2758 2620 2482 2344 2206 2069 1930 1793 1655 1517 1379 1241 COMPRESSOR DISCHARGE PRESS -- PSIG COMPRESSOR DISCHARGE PRESS -- kPa 90MU006 UNITS R--407C 400 380 360 340 320 300 280 260 240 220 200 180 (TEA = TEMPERATURE, ENTERING AIR) TEA110F/43C TEA100F/38C TEA90F/32C TEA80F/27C TEA70F/21C TEA60F/16C 70 75 80 85 90 95 100PSIG 483 517 552 587 622 655 690kPa COMPRESSOR SUCTION PRESSURE Figure 11 Charging Charts 11 62--10458--00 5.10 5.13 Evaporator Fan Motor Removal All units are equipped with Cycle--LOC current--sensing lockout relay. This device will lock out the compressor after any safety trip (discharge pressure switch, suction--pressure switch, or internal overload of the compressor). Check reason for lockout before resetting the device. Refer to unit label wiring diagram. To reset, turn the system switch to OFF, then back to COOL. 5.14 Discharge and Suction Pressure Switches Refer to Table 1 through Table 2 for opening and closing settings for these safety devices. The discharge pressure switch is located on the compressor on the 008 & 012 size units and on the discharge line on all other units. The suction pressure switch is located on top of the compressor on 06DR compressor equipped units and on the suction line on all other units. a. Shut off unit main power supply. WARNING Lock open and tag unit disconnect before working on fan motor. Remove fuses and take them with you after noting this on tag. CAUTION Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage. b. Loosen motor hold down bolts on mounting bracket so that fan belt can be removed. Motor power wires need not be disconnected from motor terminals before motor is removed from unit. 5.15 d. Slide motor/bracket assembly to extreme right, remove bolts and lift out through space between fan scroll and side. Rest motor on a high platform such as a step ladder. Do not allow motor to hang by its power wires. Pressure Relief Device All units are equipped with a fusible--plug type safety relief device on the refrigerant tubing. The relief setting is 197 _F to 203 _F on all units. 5.12 Crankcase Heater A crankcase heater is supplied on the 008 & 012 size units and on all 134a units. The heater prevents liquid refrigerant from accumulating in the compressor crankcase during extended shutdown periods. Heater is automatically energized whenever unit main power is on and compressor is stopped. Heater is de--energized when compressor starts. Do not shut off main power supply for an extended period except for servicing unit. Turn on power supply for at least 24 hours after an extended shutdown before starting compressor. Refer to “Operation”. 62--10458--00 Oil Charge All units are factory charged with oil. On 06D compressors, observe the oil level in the sight glass at start--up. If unit oil level is below sight glass, add oil until level reaches approximately 1/4 sight glass. If oil charge is above sight glass, do not remove any oil until the compressor crankcase heater has been energized for at least 24 hours. When additional oil or a complete charge is required, use only the following Carrier approved oil. R--22 Units Design Series One 204/206 size units Witco part number 999--5170--55 Design Series One 208/212 size units and all Design Series Two Witco -- Suniso 3GS Calumet -- RO--15 R--134a Units Castrol -- Icematic E68 ICI -- Emkarate RL68HP R--407C Units Copeland Ultra 22CC 004 and 006 Mobil Artic EAL 22CC ICI (Virginia KMP) Emkarate RL32C Thermal Zone 22CC Castrol -- Icematic E68 008 and 012 ICI -- Emkarate RL68HP c. Loosen but do not remove the 2 motor mounting bracket bolts on left side of bracket. 5.11 Cycle--LocTM -- Protection Device 12 Figure 12 Mounting Base 13 62--10458--00 40.25 52.00 004/006 SIZE 008/012 SIZE 27.31 22.00 B 50.00 38.25 C D 48.00 36.25 BASED ON DRAWING 50BW400093 A USED ON -- E 1.25 A 45.50 -- F 23.31 18.005 G 0.75 -- H 25.81 -- J -- 3.18 K -- 2.56 L -- 8.75 M -- 2.00 N -- 1.00 P 9.00 5.00 R 6.00 7.50 S 16.50 15.00 T 10.00 15.38 V -- 0.70 W WIRE PASSES THOUGH LOOP OF CL CC FIELD L1 11 21 BLK 1 POWER L2 12 22 BLU 2 SUPPLY L3 G 13 23 YEL 3 GROUND IFC YEL T3 12 22 BLU T2 13 23 BLK T1 11 BLU BLK C IPF 21 YEL IPC IFM GRN BLU CHR BLK BLU H3 H1 H2 TRAN 5 4 ORN BLK VIO BLK H5 H4 CH H6 SEE NOTE 1 GRN RED RED F X1 X2 24VOLT BRN C2 CC SW (SEE NOTE 3) BRN NO NC ORN NO YEL RED ORN T--LOW R TB1--1 VIO IFC RED RED CC BRN CHR TB1--4 C2 CHR BRN 1 3 CC RED BRN TRAN C2 IFC 90MU UNITS ONLY YEL RED CL W TB1--5 RED CFR X 2 BRN LOGIC 1 3 B RED H2 BRN TB1--3 BRN DPS OPTIONAL ELECTRIC DUCT HEATER HEATERS H1 BLU SPS CHR BRN CHR BLU 1 CL BRN IFC FOR HOT WATER/STEAM HEAT SEE NOTE 2 L1 90MU CONDENSER FAN WIRING L2 L3 G TB1--4 GROUND MC AS AC H1 H2 TB1--3 11 21 12 22 13 SHIPS POWER 23 CFR TO FAN SINGLE OR THREE PAHSE AS REQUIRED Figure 13 Wiring Schematic -- 90MA/MF/MU004/006 62--10458--00 14 CONTROL BOX 11 12 13 11 12 13 H1 H3 H2 H4 TRAN X2 21 22 23 21 22 C1 CC C2 DT1 DT1 DT2 B F DT2 1 TB1 4 1 2 3 4 5 CLO X1 23 C1 IFC C2 11 12 13 21 22 23 CONTROL PANEL FAN COOL A W A R ME B R OFF HEAT A CO O LER 3 2 TB1--1 6 5 NO C1 CHR C2 VIEW A--A GROUND X 3 2 1 C1 CFR C2 AS AC C CC CH CFR CHR CL DPS F H1 H2 IFC IFM IPC IPF MC SPS SW T TB TRAN 90MU ONLY LEGEND AIR SWITCH AUTOMATIC CUTOUT COMPRESSOR COMPRESSOR CONTACTOR CRANKCASE HEATER CONDENSER FAN RELAY CRANKCASE HEATER RELAY COMPRESSOR LOCKOUT DISCHARGE PRESSURE SWITCH FUSE CONTROLLING HEAT CONTACTOR BACKUP HEAT CONTACTOR INDOOR FAN CONTACTOR INDOOR FAN MOTOR INTERNAL PROTECTOR--COMPRESSOR INTERNAL PROTECTOR--FAN MOTOR MANUAL (RESET) CUTOUT SUCTION PRESSURE SWITCH SWITCH THERMOSTAT TERMINAL BOARD TRANSFORMER TB1--5 NO TB1--4 NC VIEW B--B NOTES: 1. 208--230/3/60 VOLT UNITS FACTORY WIRED TO TRANSFORMER TERMINAL H2 (208 VOLT TAP). FOR 230 VOLT APPLICATIONS, RE--CONNECT TO TERMINAL H3 (230 VOLT TAP). 460/3/60 VOLT UNITS FACTORY WIRED TO TERMINAL H6. 400/3/50 VOLT UNITS FACTORY WIRED TO TERMINAL H5. 2. CONNECTION POINTS AT TB--1 TERMINALS 3 & 4 MAY BE USED FOR HEAT CONTROLS. MAXIMUM LOAD IS 250 VA INRUSH, 50 VA SEALED. 3. SWITCH CONTACT ARRANGEMENT IS AS SHOWN BELOW. TERMINAL BOARD TERMINAL TERMINAL (MARKED) TERMINAL/SPLICE (UNMARKED) LOCKOUT TERMINAL FACTORY WIRING FIELD WIRING INDICATES COMMON POTENTIAL, DOES NOT REPRESENT WIRING OFF FAN COOL HEAT Figure 14 Component Arrangement -- 90MA/MF/MU004/006 15 62--10458--00 WIRE PASSES THOUGH LOOP OF CL CC FIELD L1 11 21 POWER L2 12 22 BLU SUPPLY L3 G 13 23 YEL GROUND YEL 11 BLU BLK OLB 4 BLK 1 (COLOR VARIES) 2 OLA 4 IFC 3 3 21 YEL T3 12 22 BLU T2 13 23 BLK T1 C 3 (COLOR VARIES) IPF IFM GRN CHR BLU BLU BLK H1 H3 H2 TRAN 4 5 ORN BLK VIO BLK H5 H4 CH H6 SEE NOTE 1 GRN RED SW(SEE NOTE 3) RED F X1 TB1--1 VIO NC RED NO ORN T--LOW R 1 3 ORN 9 IPC TB1--5 DPS BLK B BRN CFR 8 CL RED X 2 LOGIC 1 3 RED BRN RED 2 1 TB1--3 JUMPER TB1--2 BRN 90MA012 UNITS ONLY OLB 1 TRAN BRN BRN BLK OLA 2 CC BRN C2 IFC CC RED 90MU UNITS ONLY YEL W IFC RED CHR TB1--4 RED RED C2 CC BRN BRN C2 CHR NO YEL X2 24VOLT BLU SPS US BRN LLS CHR BRN BRN CHR 1 CL BRN IFC BLU BRN TB1--2 BLK BRN TB1--2 BLU ORN T--HIGH R 90MA012 UNITS ONLY BLU W BLK B H2 C DT1 BLU C DT2 BLU OPTIONAL ELECTRIC DUCT HEATER HEATERS H1 FOR HOT WATER/STEAM HEAT SEE NOTE 2 90MU CONDENSER FAN WIRING L2 TB1--4 US BLK L1 L3 G LLS GROUND MC AS AC 21 12 22 13 H1 H2 11 SHIPS POWER TB1--3 23 CFR TO FAN SINGLE OR THREE PAHSE AS REQUIRED Figure 15 Wiring Schematic -- 90MA/MF/MU008/012 62--10458--00 16 CONTROL BOX 11 12 13 11 12 13 H1 H3 H2 H4 TRAN X2 21 22 23 21 22 C1 CC C2 DT1 DT1 DT2 DT2 1 4 1 2 3 4 5 11 12 B F TB1 CLO X1 23 C1 IFC C2 13 2 5 CONTROL PANEL FAN COOL A W A R ME B R OFF HEAT A CO O LER 3 TB1--1 6 NO C1 CHR C2 VIEW A--A GROUND X 3 2 1 21 22 23 C1 CFR C2 AS AC C CC CH CFR CHR CL DT DPS F H1 H2 IFC IFM IPC IPF LLS OL MC SPS SW T TB TRAN US 90MU ONLY LEGEND AIR SWITCH AUTOMATIC CUTOUT COMPRESSOR COMPRESSOR CONTACTOR CRANKCASE HEATER CONDENSER FAN RELAY CRANKCASE HEATER RELAY COMPRESSOR LOCKOUT DUMMY TERMINAL DISCHARGE PRESSURE SWITCH FUSE CONTROLLING HEAT CONTACTOR BACKUP HEAT CONTACTOR INDOOR FAN CONTACTOR INDOOR FAN MOTOR INTERNAL PROTECTOR--COMPRESSOR INTERNAL PROTECTOR--FAN MOTOR LIQUID LINE SOLENOID OVER LOAD MANUAL (RESET) CUTOUT SUCTION PRESSURE SWITCH SWITCH THERMOSTAT TERMINAL BOARD TRANSFORMER UNLOADER SOLENOID TB1--5 NO TB1--4 NC VIEW B--B NOTES: 1. 208--230/3/60 VOLT UNITS FACTORY WIRED TO TRANSFORMER TERMINAL H2 (208 VOLT TAP). FOR 230 VOLT APPLICATIONS, RE--CONNECT TO TERMINAL H3 (230 VOLT TAP). 460/3/60 VOLT UNITS FACTORY WIRED TO TERMINAL H6. 400/3/50 VOLT UNITS FACTORY WIRED TO TERMINAL H5. 2. CONNECTION POINTS AT TB--1 TERMINALS 3 & 4 MAY BE USED FOR HEAT CONTROLS. MAXIMUM LOAD IS 250 VA INRUSH, 50 VA SEALED. 3. SWITCH CONTACT ARRANGEMENT IS AS SHOWN BELOW. TERMINAL BOARD TERMINAL TERMINAL (MARKED) TERMINAL/SPLICE (UNMARKED) LOCKOUT TERMINAL OFF FACTORY WIRING FIELD WIRING INDICATES COMMON POTENTIAL, DOES NOT REPRESENT WIRING FAN COOL HEAT Figure 16 Component Arrangement -- 90MA/MF/MU008/012 17 62--10458--00 A M Access Panel, 9 Model Chart, 1 Accessory Plenum, 1 Mounting Base, 13 Air Filter, 5, 10 C Component Arrangement, 15, 17 O Oil Charge, 12 Condensate Drain, 7, 10 P Condenser, 10 Condenser Connections, 6 Crankcase Heater, 12 Cycle--Loc, 12 Pressure Relief Device, 12 Pressure Switches, 12 R E Electrical Connections, 7 Refrigerant Charging, 11 Evaporator Coil, 10 Remote Condenser, 7 Return Air, 1 F S Fan Adjustment, 9 Fan Motor, 12 Fan Shaft, 5 H Sequence Of Operation, 8 Shut Down Unit, 8 Spring Mounts, 6 Start Unit, 8 Heating Coil, 1 I Installation, 1 V Ventilation, 1 Introduction, 1 L Line Sizes, 7 W Water Regulating Valve, 10 Wiring Schematic, 14, 16 Index -- 1 62--10458--00
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : 3.1-701 Create Date : 2000:06:30 10:44:40Z Creator Tool : AdobePS5.dll Version 5.0.1 Modify Date : 2005:11:10 09:11:04-05:00 Metadata Date : 2005:11:10 09:11:04-05:00 Producer : Acrobat Distiller 4.0 for Windows Keywords : Format : application/pdf Title : Description : Creator : Carrier Corporation Subject : Document ID : uuid:6644732c-dbf6-4093-9b7a-b9bb471d22d7 Instance ID : uuid:8069af70-1e1c-44f1-bba2-17f2eb74106b Page Count : 24 Author : Carrier CorporationEXIF Metadata provided by EXIF.tools