Carrier Aquasnap Air Cooled Chillers With Comfortlink Controls 30Rap010 060 Users Manual 30rap 2t
30RAP010-060 to the manual 556e3ae9-fcb8-42ef-b900-abf4bd5d8276
2015-01-24
: Carrier Carrier-Aquasnap-Air-Cooled-Chillers-With-Comfortlink-Controls-30Rap010-060-Users-Manual-310468 carrier-aquasnap-air-cooled-chillers-with-comfortlink-controls-30rap010-060-users-manual-310468 carrier pdf
Open the PDF directly: View PDF .
Page Count: 124
Download | |
Open PDF In Browser | View PDF |
30RAP010-060 Air-Cooled Chillers with COMFORTLINK™ Controls AQUASNAP® Controls, Start-Up, Operation, Service, and Troubleshooting CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .2 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18 Conventions Used in this Manual. . . . . . . . . . . . . . . . . . . .3 Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-44 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Energy Management Module (EMM) . . . . . . . . . . . . . . . .19 Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . . . .19 AUX Board (AUX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Expansion Valve Board (EXV) . . . . . . . . . . . . . . . . . . . . . .19 Enable/Off/Remote Contact Switch . . . . . . . . . . . . . . . . .19 Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . .19 Board Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Control Module Communication . . . . . . . . . . . . . . . . . . . .19 Carrier Comfort Network® (CCN) Interface . . . . . . . . . .19 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 • COOLER LEAVING FLUID SENSOR • COOLER ENTERING FLUID SENSOR • COMPRESSOR RETURN GAS TEMPERATURE SENSOR • OUTDOOR-AIR TEMPERATURE SENSOR (OAT) • DISCHARGE TEMPERATURE THERMISTOR (DTT) • REMOTE SPACE TEMPERATURE SENSOR OR DUAL LEAVING WATER TEMPERATURE SENSOR Energy Management Module . . . . . . . . . . . . . . . . . . . . . . .29 Loss-of-Cooler Flow Protection. . . . . . . . . . . . . . . . . . . . .29 Electronic Expansion Valves (EXV) . . . . . . . . . . . . . . . . .29 Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 • MINUTES LEFT FOR START • MINUTES OFF TIME • LEAD/LAG DETERMINATION • CAPACITY CONTROL OVERRIDES Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 Operation of Machine Based on Control Method and Cooling Set Point Selection Settings. . . . . . . . .32 Cooling Set Point Select. . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Low Sound Mode Operation . . . . . . . . . . . . . . . . . . . . . . . .34 Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Optional Factory-Installed Hydronic Package. . . . . . .34 Cooler Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Cooler Pump Sequence of Operation . . . . . . . . . . . . . . .35 Configuring and Operating Dual Chiller Control . . . .36 Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 • DEMAND LIMIT (2-Stage Switch Controlled) • EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA Controlled) • DEMAND LIMIT (CCN Loadshed Controlled) Cooling Set Point (4 to 20 mA). . . . . . . . . . . . . . . . . . . . . .43 Digital Scroll Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 • DIGITAL SCROLL OPERATION • DIGITAL COMPRESSOR CONFIGURATION PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44,45 Page System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 START-UP AND OPERATION . . . . . . . . . . . . . . . . . . . . 45,46 Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Check Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . 45 Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 • TEMPERATURES • LOW AMBIENT OPERATION • VOLTAGE — ALL UNITS OPERATION SEQUENCE . . . . . . . . . . . . . . . . . . . . . .46,47 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-63 Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 • CONTROL COMPONENTS Electronic Expansion Valve (EXV) . . . . . . . . . . . . . . . 47 EXV Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . 47 • FIELD SERVICING INSTRUCTIONS • VALVE REPLACEMENT • VALVE REASSEMBLY Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . 49 Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 • BRAZED-PLATE COOLER HEAT EXCHANGER REPLACEMENT • BRAZED-PLATE COOLER HEAT EXCHANGER CLEANING Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Check Refrigerant Feed Components . . . . . . . . . . . . . . 50 • FILTER DRIER • MOISTURE-LIQUID INDICATOR • MINIMUM LOAD VALVE • PRESSURE RELIEF DEVICES Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 • HIGH-PRESSURE SWITCH • PRESSURE TRANSDUCERS • COOLER FREEZE-UP PROTECTION • HEATER CABLE • WINTER SHUTDOWN Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Pressure Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Chilled Water Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . 53 Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Motormaster® V Controller . . . . . . . . . . . . . . . . . . . . . . . . . 58 • GENERAL OPERATION • CONFIGURATION • DRIVE PROGRAMMING • EPM CHIP • LOSS OF CCN COMMUNICATIONS • REPLACING DEFECTIVE MODULES Hydronic Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63,64 Recommended Maintenance Schedule . . . . . . . . . . . . . 63 Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64-73 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg 1 12-10 Replaces: 30RAP-1T CONTENTS (cont) WARNING Page Complete Unit Stoppage and Restart . . . . . . . . . . . . . . 64 • GENERAL POWER FAILURE • UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS OFF • CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN • OPEN 24-V CONTROL CIRCUIT BREAKERS • COOLING LOAD SATISFIED • THERMISTOR FAILURE • LOW SATURATED SUCTION • COMPRESSOR SAFETIES Alarms and Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 APPENDIX A — DISPLAY TABLES . . . . . . . . . . . . . . 74-89 APPENDIX B — CCN TABLES . . . . . . . . . . . . . . . . . . 90-100 APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS. . . . . . . . . . . . . . . . 101 APPENDIX D — OPTIONAL BACNET COMMUNICATONS WIRING . . . . . . . . . . . . . . . . . 102-109 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS . . . . . . . . . . . . . . . . . . . . . . . . . . 110-113 START-UP CHECKLIST FOR 30RAP LIQUID CHILLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CL-1 to CL-10 DO NOT attempt to unbraze factory joints when servicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use compressor oil. CAUTION This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components. CAUTION To prevent potential damage to heat exchanger, always run fluid through heat exchanger when adding or removing refrigerant charge. Use appropriate brine solutions in cooler fluid loop to prevent the freezing of brazed plate heat exchanger, optional hydronic section and/or interconnecting piping when the equipment is exposed to temperatures below 32 F (0 °C). Proof of flow switch and strainer are factory installed on all models. Do NOT remove power from this chiller during winter shutdown periods without taking precaution to remove all water from heat exchanger and optional hydronic system. Failure to properly protect the system from freezing may constitute abuse and may void warranty. SAFETY CONSIDERATIONS Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location (roof, elevated structures, mechanical rooms, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment. When working on this equipment, observe precautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components. WARNING CAUTION Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed. Compressors and optional hydronic system pumps require specific rotation. Test condenser fan(s) first to ensure proper phasing. Swap any two incoming power leads to correct condenser fan rotation before starting any other motors. WARNING CAUTION DO NOT VENT refrigerant relief valves within a building. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration and Air Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous. Refrigerant charge must be removed slowly to prevent loss of compressor oil that could result in compressor failure. CAUTION Puron® refrigerant (R-410A) systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment. If service equipment is not rated for Puron refrigerant, equipment damage or personal injury may result. 2 Control System for 30RAP units. The display has up and down arrow keys, an ENTER key, and an ESCAPE key. These keys are used to navigate through the different levels of the display structure. Press the ESCAPE key until the highest operating level is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 1 and Tables 2-14. GENERAL This publication contains Controls, Start-Up, Operation, Service, and Troubleshooting information for the 30RAP AquaSnap® air-cooled chillers. See Table 1. These chillers are equipped with ComfortLink™ controls and electronic expansion valves (EXVs). WARNING Once within a mode or sub-mode, pressing the ENTER and ESCAPE keys simultaneously will put the scrolling marquee display into expanded text mode where the full meaning of all sub-modes, items and their values can be displayed for the current selection. Press the ENTER and ESCAPE keys to return the scrolling marquee display to its default menu of rotating display items (those items in Run StatusVIEW). In addition, the password will be disabled, requiring that it be entered again before changes can be made to password protected items. Press the ESCAPE key to exit out of the expanded text mode. This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out or bypass components or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the board or electrical component. Table 1 — Unit Sizes UNIT 30RAP010 30RAP015 30RAP018 30RAP020 30RAP025 30RAP030 30RAP035 30RAP040 30RAP045 30RAP050 30RAP055 30RAP060 NOMINAL CAPACITY (TONS) 10 14 16 19 24 28 34 39 43 48 53 56 NOTE: When the Language Selection (Configuration DISPLANG), variable is changed, all appropriate display expansions will immediately change to the new language. No power-off or control reset is required when reconfiguring languages. When a specific item is located, the item name alternates with the value. Press the ENTER key at a changeable item and the value will be displayed. Press ENTER again and the value will begin to flash indicating that the value can be changed. Use the up and down arrow keys to change the value, and confirm the value by pressing the ENTER key. Conventions Used in This Manual — The follow- ing conventions for discussing configuration points for the local display (scrolling marquee or Navigator™ accessory) will be used in this manual. Point names will be written with the mode name first, then any sub-modes, then the point name, each separated by an arrow symbol (. Names will also be shown in bold and italics. As an example, the Lead/Lag Circuit Select Point, which is located in the Configuration mode, Option sub-mode, would be written as Configuration OPTNLLCS. This path name will show the user how to navigate through the local display to reach the desired configuration. The user would scroll through the modes and sub-modes using the and keys. The arrow symbol in the path name represents pressing ENTER to move into the next level of the menu structure. MODE Run Status Service Test Temperature Pressures Setpoints Inputs Alarm Status Outputs Configuration Time Clock ESCAPE ENTER Operating Modes Alarms Fig. 1 — Scrolling Marquee Display Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press ENTER so that the item value flashes. Use the arrow keys to change the value or state and press the ENTER key to accept it. Press the ESCAPE key to return to the next higher level of structure. Repeat the process as required for other items. When a value is included as part of the path name, it will be shown at the end of the path name after an equals sign. If the value represents a configuration setting, an explanation will be shown in parenthesis after the value. As an example, ConfigurationOPTNLLCS = 1 (Circuit A leads). Pressing the ESCAPE and ENTER keys simultaneously will scroll an expanded text description of the point name or value across the display. The expanded description is shown in the local display tables but will not be shown with the path names in text. Items in the Configuration and Service Test modes are password protected. The words ‘PASS’ and ‘WORD’ will alternate on the display when required. The default password is 0111. Press ENTER and the 1111 password will be displayed. Press ENTER again and the first digit will begin to flash. Use the arrow keys to change the number and press ENTER to accept the digit. Continue with the remaining digits of the password. The password can only be changed through CCN operator interface software such as ComfortWORKS®, ComfortVIEW™ and Service Tool. The CCN (Carrier Comfort Network®) point names are also referenced in the local display tables for users configuring the unit with CCN software instead of the local display. The CCN tables are located in Appendix B of the manual. Basic Controls Usage SCROLLING MARQUEE DISPLAY — The scrolling marquee display is the standard interface display to the ComfortLink See Tables 2-14 and Appendix A for further details. 3 the Navigator module, press the ESCAPE key until the display reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press ENTER to obtain access to this mode. The display will read: ACCESSORY NAVIGATOR™ DISPLAY MODULE — The Navigator module provides a mobile user interface to the ComfortLink™ control system, which is only available as a field-installed accessory. The display has up and down arrow keys, an ENTER key, and an ESCAPE key. These keys are used to navigate through the different levels of the display structure. Press the ESCAPE key until ‘Select a Menu Item’ is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 2. > TEST OFF METR OFF LANG ENGLISH Pressing ENTER will cause the “OFF” to flash. Use the up or down arrow to change “OFF” to “ON”. Pressing ENTER will illuminate all LEDs and display all pixels in the view screen. Pressing ENTER and ESCAPE simultaneously allows the user to adjust the display contrast. Use the up or down arrows to adjust the contrast. The screen’s contrast will change with the adjustment. Press ENTER to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus. Once within a Mode or sub-mode, a “>” indicates the currently selected item on the display screen. Pressing the ENTER and ESCAPE keys simultaneously will put the Navigator module into expanded text mode where the full meaning of all sub-modes, items and their values can be displayed. Pressing the ENTER and ESCAPE keys when the display says ‘Select Menu Item’ (Mode LED level) will return the Navigator module to its default menu of rotating display items (those items in Run StatusVIEW). In addition, the password will be disabled, requiring that it be entered again before changes can be made to password protected items. Press the ESCAPE key to exit out of the expanded text mode. Adjusting the Backlight Brightness — The backlight of the display can be adjusted to suit ambient conditions. The factory default is set to the highest level. To adjust the backlight of the Navigator module, press the ESCAPE key until the display reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press ENTER to obtain access to this mode. The display will read: > TEST OFF METR OFF LANG ENGLISH Pressing ENTER will cause the “OFF” to flash. Use the up or down arrow keys to change “OFF” to “ON”. Pressing ENTER will illuminate all LEDs and display all pixels in the view screen. Pressing the up and down arrow keys simultaneously allows the user to adjust the display brightness. Use the up or down arrow keys to adjust screen brightness. Press ENTER to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus. NOTE: When the Language Selection (Configuration DISPLANG), variable is changed, all appropriate display expansions will immediately change to the new language. No power-off or control reset is required when reconfiguring languages. When a specific item is located, the item name appears on the left of the display, the value will appear near the middle of the display and the units (if any) will appear on the far right of the display. Press the ENTER key at a changeable item and the value will begin to flash. Use the up and down arrow keys to change the value, and confirm the value by pressing the ENTER key. Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press ENTER so that the item value flashes. Use the arrow keys to change the value or state and press the ENTER key to accept it. Press the ESCAPE key to return to the next higher level of structure. Repeat the process as required for other items. Com fortL Items in the Configuration and Service Test modes are password protected. The words Enter Password will be displayed when required, with 1111 also being displayed. The default password is 1111. Use the arrow keys to change the number and press ENTER to enter the digit. Continue with the remaining digits of the password. The password can only be changed through CCN operator interface software such as ComfortWORKS, ComfortVIEW and Service Tool. MOD Run ink E Alarm Status Status Servic e Tes t Tem peratu res Pressu res Setpo ints Inputs Outpu ts Config uration Time Clock Opera ting Modes Alarm s ENTE Adjusting the Contrast — The contrast of the display can be adjusted to suit ambient conditions. To adjust the contrast of ESC R Fig. 2 — Accessory Navigator™ Display Module 4 Table 2 — Scrolling Marquee Display Menu Structure* MODE RUN STATUS Auto View of Run Status (VIEW) Unit Run Hour and Start (RUN) SERVICE TEST TEMPERATURES PRESSURES SET POINTS INPUTS OUTPUTS CONFIGURATION TIME CLOCK OPERATING MODES ALARMS Service Test Mode (TEST) Ent and Leave Unit Temps (UNIT) Pressures Ckt A (PRC.A) Cooling Setpoints (COOL) General Inputs (GEN.I) General Outputs (GEN.O) Display Configuration (DISP) Time of Day (TIME) Modes (MODE) Current (CRNT) Outputs and Pumps (OUTS) Temperatures Ckt A (CIR.A) Pressures Ckt B (PRC.B) Compressor Ciruit A Comp Run Hours Test (HOUR) (CMPA) SUB-MODE Temperatures Ckt B (CIR.B) Head Pressure Setpoint (HEAD) Brine Freeze Setpoint (FRZ) Circuit Inputs (CRCT) 4-20mA Inputs (4-20) Outputs Circuit A EXV (A.EXV) Outputs Circuit B EXV (B.EXV) Unit Configuration (UNIT) Unit Options 1 Hardware (OPT1) Compressor Ciruit B Comp Starts Test (STRT) (CMPB) Outputs Circuit A (CIR.A) Unit Options 2 Controls (OPT2) Preventive Maintenance (PM) Outputs Circuit B (CIR.B) CCN Network Configuration (CCN) Software Version (VERS) Head Pressure Comp. Delta (HP.A) Head Pressure Comp. Delta (HP.B) Cir. A EXV Configuration (EXV.A) Cir. B EXV Configuration (EXV.B) Motormaster Configuration (MM) Reset Cool Temp (RSET) Set Point and Ramp Load (SLCT) Service Configuration (SERV) Broadcast Configuration (BCST) LEGEND Ckt — Circuit *Throughout this text, the location of items in the menu structure will be described in the following format: Item Expansion (Mode NameSub-mode NameITEM) For example, using the language selection item: Language Selection (ConfigurationDISPLANG) 5 Month, Date, Day, and Year (DATE) Daylight Savings Time (DST) Local Holiday Schedules (HOL.L) Local Occupancy Schedule (SCH.L) Schedule Override (OVR) Reset Alarms (RCRN) Alarm History (HIST) Table 3 — Run Status Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY VIEW ENTER EWT XXX.X F ENTERING FLUID TEMP LWT XXX.X F LEAVING FLUID TEMP SETP XXX.X F ACTIVE SETPOINT CTPT XXX.X F CONTROL POINT LOD.F XXX LOAD/UNLOAD FACTOR STAT X CONTROL MODE SUB-ITEM DISPLAY SUB-ITEM DISPLAY LD.PM RUN HOUR STRT PM ENTER ENTER ENTER ENTER ENTER ITEM EXPANSION COMMENT 0 = Service Test 1 = Off Local 2 = Off CCN 3 = Off Time 4 = Off Emrgcy 5 = On Local 6 = On CCN 7 = On Time 8 = Ht Enabled 9 = Pump Delay LEAD PUMP OCC YES/NO OCCUPIED LS.AC YES/NO LOW SOUND ACTIVE MODE YES/NO OVERRIDE MODES IN EFFECT CAP XXX % PERCENT TOTAL CAPACITY STGE X REQUESTED STAGE ALRM XXX CURRENT ALARMS & ALERTS TIME XX.XX TIME OF DAY 00.00-23.59 MNTH XX MONTH OF YEAR 1 = January, 2 = February, etc. DATE XX DAY OF MONTH 01-31 YEAR XX YEAR OF CENTURY HRS.U XXXX HRS MACHINE OPERATING HOURS STR.U XXXX MACHINE STARTS HR.P1 XXXX.X PUMP 1 RUN HOURS HR.P2 XXXX.X PUMP 2 RUN HOURS HRS.A XXXX HRS CIRCUIT A RUN HOURS HRS.B XXXX HRS CIRCUIT B RUN HOURS HR.A1 XXXX HRS COMPRESSOR A1 RUN HOURS HR.A2 XXXX HRS COMPRESSOR A2 RUN HOURS HR.B1 XXXX HRS COMPRESSOR B1 RUN HOURS See Note HR.B2 XXXX HRS COMPRESSOR B2 RUN HOURS See Note See Note ST.A1 XXXX COMPRESSOR A1 STARTS ST.A2 XXXX COMPRESSOR A2 STARTS ST.B1 XXXX COMPRESSOR B1 STARTS See Note ST.B2 XXXX COMPRESSOR B2 STARTS See Note PUMP PUMP MAINTENANCE SI.PM XXXX HRS PUMP SERVICE INTERVAL P.1.DN XXXX HRS PUMP 1 SERVICE COUNTDOWN P.2.DN XXXX HRS PUMP 2 SERVICE COUNTDOWN P.1.MN YES/NO PUMP 1 MAINTENANCE DONE User Entry P.2.MN YES/NO PUMP 2 MAINTENANCE DONE User Entry NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. 6 Default: 8760 Table 3 — Run Status Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM PM (cont) DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY PMDT P.1.M0 MM/DD/YY HH:MM P.1.M1 MM/DD/YY HH:MM P.1.M2 MM/DD/YY HH:MM P.1.M3 MM/DD/YY HH:MM P.1.M4 MM/DD/YY HH:MM P.2.M0 MM/DD/YY HH:MM P.2.M1 MM/DD/YY HH:MM P.2.M2 MM/DD/YY HH:MM P.2.M3 MM/DD/YY HH:MM P.2.M4 MM/DD/YY HH:MM STRN ENTER STRAINER MAINTENANCE SI.ST XXXX HRS STRAINER SRVC INTERVAL S.T.DN XXXX HRS STRAINER SRVC COUNTDOWN S.T.MN YES/NO STRAINER MAINT. DONE ST.DT S.T.M0 MM/DD/YY HH:MM S.T.M1 MM/DD/YY HH:MM S.T.M2 MM/DD/YY HH:MM S.T.M3 MM/DD/YY HH:MM S.T.M4 MM/DD/YY HH:MM COIL ENTER SI.CL XXXX HRS COIL SRVC INTER C.L.DN XXXX HRS COIL SERVICE COUNTDOWN C.L.MN YES/NO COIL MAINT. DONE ENTER *Press ENTER Default: 8760 User Entry COIL MAINTENANCE DATES C.L.M0 MM/DD/YY HH:MM C.L.M1 MM/DD/YY HH:MM C.L.M2 MM/DD/YY HH:MM C.L.M3 MM/DD/YY HH:MM C.L.M4 MM/DD/YY HH:MM MBB CESR131460-xx-xx xx-xx is Version number* EXV CESR131172-xx-xx xx-xx is Version number* AUX1 CESR131333-xx-xx xx-xx is Version number* EMM CESR131174-xx-xx xx-xx is Version number* MARQ CESR131171-xx-xx xx-xx is Version number* NAVI CESR130227-xx-xx xx-xx is Version number* ENTER and User Entry COIL MAINTENANCE CL.DT VERS Default: 8760 STRAINER MAINT. DATES ENTER ENTER COMMENT PUMP MAINTENANCE DATES ENTER ENTER ITEM EXPANSION ESCAPE simultaneously to obtain version number. 7 Table 4 — Service Test Mode and Sub-Mode Directory SUB-MODE TEST KEYPAD ENTRY ITEM ITEM EXPANSION SERVICE TEST MODE DISPLAY ON/OFF ENTER OUTS COMMENT To Enable Service Test Mode, move Enable/Off/Remote Contact switch to OFF. Change TEST to ON. Move switch to ENABLE. OUTPUTS AND PUMPS ENTER EXV.A 0 to 100% EXV A % OPEN EXV.B 0 to 100% EXV B % OPEN FAN1 ON/OFF FAN 1 RELAY FAN2 ON/OFF FAN 2 RELAY FAN3 ON/OFF FAN 3 RELAY FAN4 ON/OFF FAN 4 RELAY FAN5 ON/OFF FAN 5 RELAY FAN6 ON/OFF FAN 6 RELAY V.HPA 0 to 100% VAR HEAD PRESS % V.HPB 0 to 100% VAR HEAD PRESS % CLP.1 ON/OFF COOLER PUMP 1 RELAY CLP.2 ON/OFF COOLER PUMP 2 RELAY UL.TM 0 to 15 COMP A1 UNLOAD TIME CL.HT ON/OFF COOLER/PUMP HEATER RMT.A ON/OFF REMOTE ALARM RELAY CMPA CIRCUIT A COMPRESSOR TEST ENTER CC.A1 ON/OFF COMPRESSOR A1 RELAY UL.TM 0 to 15 COMP A1 UNLOAD TIME CC.A2 ON/OFF COMPRESSOR A2 RELAY CC.A3 ON/OFF COMPRESSOR A3 RELAY CC.A4 ON/OFF COMPRESSOR A4 RELAY MLV ON/OFF MINIMUM LOAD VALVE RELAY CMPB CIRCUIT B COMPRESSOR TEST ENTER CC.B1 ON/OFF COMPRESSOR B1 RELAY CC.B2 ON/OFF COMPRESSOR B2 RELAY CC.B3 ON/OFF COMPRESSOR B3 RELAY CC.B4 ON/OFF COMPRESSOR B4 RELAY NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. 8 See Note Table 5 — Temperature Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION ENT AND LEAVE UNIT TEMPS ENTER CEWT XXX.X F COOLER ENTERING FLUID CLWT XXX.X F COOLER LEAVING FLUID OAT XXX.X F OUTSIDE AIR TEMPERATURE SPT XXX.X F SPACE TEMPERATURE DLWT XXX.X F UNIT COMMENT LEAD/LAG LEAVING FLUID CIR.A TEMPERATURES CIRCUIT A ENTER SCT.A XXX.X F SATURATED CONDENSING TMP SST.A XXX.X F SATURATED SUCTION TEMP RGT.A XXX.X F COMPR RETURN GAS TEMP D.GAS XXX.X F DISCHARGE GAS TEMP SH.A XXX.X ^F SUCTION SUPERHEAT TEMP TEMPERATURES CIRCUIT B See Note SCT.B XXX.X F SATURATED CONDENSING TMP See Note SST.B XXX.X F SATURATED SUCTION TEMP See Note RGT.B XXX.X F COMPR RETURN GAS TEMP See Note SH.B XXX.X ^F SUCTION SUPERHEAT TEMP See Note CIR.B ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 6 — Pressure Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION PRESSURES CIRCUIT A ENTER DP.A XXX.X PSIG DISCHARGE PRESSURE SP.A XXX.X PSIG SUCTION PRESSURE PRESSURES CIRCUIT B See Note DP.B XXX.X PSIG DISCHARGE PRESSURE See Note SP.B XXX.X PSIG SUCTION PRESSURE See Note PRC.A PRC.B ENTER COMMENT NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 7 — Set Points Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COOLING SETPOINTS ENTER CSP.1 XXX.X F COOLING SETPOINT 1 Default: 44 F CSP.2 XXX.X F COOLING SETPOINT 2 Default: 44 F CSP.3 XXX.X F ICE SETPOINT Default: 32 F COOL HEAD COMMENT HEAD PRESSURE SETPOINTS ENTER H.DP XXX.X F HEAD SETPOINT Default: 95 F F.ON XXX.X F FAN ON SETPOINT Default: 95 F F.OFF XXX.X F FAN OFF SETPOINT Default: 72 F B.OFF XXX.X F BASE FAN OFF DELTA TEMP Default: 23 F F.DLT XXX.X F FAN STAGE DELTA Default: 15 F BR.FZ XXX.X F FRZ BRINE FREEZE SETPOINT ENTER BRINE FREEZE POINT 9 Default: 34 F Table 8 — Inputs Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION GENERAL INPUTS ENTER STST STRT/STOP START/STOP SWITCH FLOW ON/OFF COOLER FLOW SWITCH PM.F.1 OPEN/CLSE COOLER PUMP 1 INTERLOCK PM.F.2 OPEN/CLSE COOLER PUMP 2 INTERLOCK HT.RQ ON/OFF HEAT REQUEST DLS1 ON/OFF DEMAND LIMIT SWITCH 1 DLS2 ON/OFF DEMAND LIMIT SWITCH 2 ICED ON/OFF ICE DONE DUAL ON/OFF DUAL SETPOINT SWITCH FKA1 ON/OFF COMPRESSOR A1 FEEDBACK FKA2 ON/OFF COMPRESSOR A2 FEEDBACK FKA3 ON/OFF COMPRESSOR A3 FEEDBACK FKA4 ON/OFF COMPRESSOR A4 FEEDBACK FKB1 ON/OFF COMPRESSOR B1 FEEDBACK See Note FKB2 ON/OFF COMPRESSOR B2 FEEDBACK See Note FKB3 ON/OFF COMPRESSOR B3 FEEDBACK See Note FKB4 ON/OFF COMPRESSOR B4 FEEDBACK See Note DMND XX.X MA 4-20 MA DEMAND SIGNAL RSET XX.X MA 4-20 MA RESET SIGNAL CSP XX.X MA 4-20 MA COOLING SETPOINT GEN.I CRCT COMMENT CIRCUITS INPUTS ENTER 4-20 4-20 MA INPUTS ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 9 — Outputs Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION GENERAL OUTPUTS ENTER FAN1 ON/OFF FAN 1 RELAY FAN2 ON/OFF FAN 2 RELAY FAN3 ON/OFF FAN 3 RELAY FAN4 ON/OFF FAN 4 RELAY FAN5 ON/OFF FAN 5 RELAY FAN6 ON/OFF FAN 6 RELAY V.HPA ON/OFF FAN SPEED CIRCUIT A V.HPB ON/OFF FAN SPEED CIRCUIT B C.WP1 ON/OFF COOLER PUMP RELAY 1 C.WP2 ON/OFF COOLER PUMP RELAY 2 CLHT ON/OFF COOLER/PUMP HEATER MLV.R ON/OFF MINIMUM LOAD VALVE RELAY GEN.O 10 COMMENT Table 9 — Outputs Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION OUTPUTS CIRCUIT A EXV ENTER EXV.A 0 to 100% EXV % OPEN APPR ON/OFF CIRCUIT A APPROACH A.EXV AP.SP APPROACH SETPOINT X.SH.R SH RESET AT MAX UNL-DIG S.SH.R DIGLOAD TO START SH RST SH_R AMOUNT OF SH RESET OVR.A EXVA OVERRIDE SPH.A SUCTION SUPERHEAT TEMP ASH.S ACTIVE SUPERHEAT SETPT AMP.S ACTIVE MOP SETPT PLM.A CIR A EXV POSITION LIMIT SPR.1 COMMENT SPARE 1 TEMPERATURE B.EXV OUTPUTS CIRCUIT B EXV ENTER EXV.B 0 to 100% EXV % OPEN APPR ON/OFF CIRCUIT B APPROACH AP.SP APPROACH SETPOINT OVR.B EXVB OVERRIDE SPH.B SUCTION SUPERHEAT TEMP ASH.S ACTIVE SUPERHEAT SETPT AMP.S ACTIVE MOP SETPT PLM.B CIR B EXV POSITION LIMIT SPR.2 SPARE 2 TEMPERATURE CIR.A OUTPUTS CIRCUIT A ENTER CC.A1 ON/OFF COMPRESSOR A1 RELAY DPE.R ON/OFF COMP A1 LOAD PERCENT CC.A2 ON/OFF COMPRESSOR A2 RELAY CC.A3 ON/OFF COMPRESSOR A3 RELAY CC.A4 ON/OFF COMPRESSOR A4 RELAY CC.B1 ON/OFF COMPRESSOR B1 RELAY CC.B2 ON/OFF COMPRESSOR B2 RELAY CC.B3 ON/OFF COMPRESSOR B3 RELAY CC.B4 ON/OFF COMPRESSOR B4 RELAY CIR.B OUTPUTS CIRCUIT B (See Note) ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 10 — Configuration Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION DISPLAY CONFIGURATION ENTER TEST ON/OFF TEST DISPLAY LEDS METR ON/OFF METRIC DISPLAY LANG X LANGUAGE SELECTION DISP COMMENT Off = English; On = Metric Default: 0 0 = English 1 = Espanol 2 = Francais 3 = Portuguese PAS.E ENBL/DSBL PASSWORD ENABLE Default: Enable PASS xxxx SERVICE PASSWORD Default: 1111 NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. 11 Table 10 — Configuration Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY UNIT ENTER ITEM EXPANSION ITEM DISPLAY COMMENT SIZE XX UNIT SIZE SZA.1 XX COMPRESSOR A1 SIZE Unit Dependent SZA.2 XX COMPRESSOR A2 SIZE Unit Dependent SZA.3 XX COMPRESSOR A3 SIZE Unit Dependent SZA.4 XX COMPRESSOR A4 SIZE Unit Dependent SZB.1 XX COMPRESSOR B1 SIZE Unit Dependent SZB.2 XX COMPRESSOR B2 SIZE Unit Dependent SZB.3 XX COMPRESSOR B3 SIZE Unit Dependent SZB.4 XX COMPRESSOR B4 SIZE Unit Dependent SH.SP XX.X F SUPERHEAT SETPOINT Default: 9 F UNIT CONFIGURATION FAN.S NUMBER OF FANS 1 = One Fan 2 = Two Fans 3 = Three Fans 4 = Four Fans EXV YES/NO EXV MODULE INSTALLED? Default: Yes A1.TY YES/NO COMPRESSOR A1 DIGITAL? Default: No Yes = A1 Compressor is Digital Scroll MAX.T 0 to 12 MAXIMUM A1 UNLOAD TIME Default: 7 Max 12 010,015 Max 10 018-060 OPT1 UNIT OPTIONS 1 HARDWARE ENTER Default: Water 1 = Water 2 = Medium Temperature Brine FLUD X COOLER FLUID MLV.S YES/NO MINIMUM LOAD VALVE SELECT D.G.EN ENBL/DSBL DISCHARGE GAS TEMP ENABLE CSB.E ENBL/DSBL CSB BOARDS ENABLE CPC ON/OFF COOLER PUMP CONTROL PM1E YES/NO COOLER PUMP 1 ENABLE PM2E YES/NO COOLER PUMP 2 ENABLE PM.P.S YES/NO COOLER PMP PERIODIC STRT PM.SL X COOLER PUMP SELECT PM.DY XX MIN COOLER PUMP SHUTDOWN DLY PM.DT XXXX HRS PUMP CHANGEOVER HOURS ROT.P YES/NO ROTATE COOLER PUMPS NOW EMM YES/NO EMM MODULE INSTALLED CND.T 0,1 COND HX 0 = RTPF 1 = MCHX Default MCHX MOPS XX EXV MOP SET POINT Range: 40 - 80 Default: 50 APPR XX CONFIG APPROACH SETPOINT Range: 5 - 40 Default: 9.0 12 Default: No Default: Off Default: No Default: Automatic 0 = Automatic 1 = Pump 1 Starts first 2 = Pump 2 Starts first 0 to 10 minutes, Default: 1 min. Default: 500 hours User Entry Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY CTRL X ITEM EXPANSION UNIT OPTIONS 2 CONTROLS CONTROL METHOD LOAD X LOADING SEQUENCE SELECT LLCS X LEAD/LAG CIRCUIT SELECT LCWT XX.X F HIGH LCW ALERT LIMIT DELY XX MINUTES OFF TIME Default: 0 Minutes Range: 0 to 15 Minutes ICE.M ENBL/DSBL ICE MODE ENABLE Default: Disable LS.MD X LOW SOUND MODE SELECT LS.ST 00:00 LOW SOUND START TIME Default: 00:00 LS.ND 00:00 LOW SOUND END TIME Default: 00:00 LS.LT XXX % LOW SOUND CAPACITY LIMIT CCNA XXX CCN ADDRESS Default: 1 Range: 1 to 239 CCNB XXX CCN BUS NUMBER Default: 0 Range: 0 to 239 BAUD X CCN BAUD RATE OPT2 ENTER CCN COMMENT Default: Switch 0 = Enable/Off/Remote Switch 2 = Occupancy 3 = CCN Control Default: Equal 1 = Equal 2 = Staged Default: Automatic 1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads Default: 60 Range: 2 to 60 F Default: 0 0 = Mode Disable 1 = Fan Noise Only 2 = Fan/Compressor Noise Default: 100% Range: 0 to 100% CCN NETWORK CONFIGURATION ENTER HP.A Default: 9600 1 = 2400 2 = 4800 3 = 9600 4 = 19,200 5 = 38,400 HEAD PRESSURE CMP DELTA ENTER A1.DT XX A2.DT XX HP.B SCT DELTA FOR COMP A1 Range: 0 - 50 Default: 12 SCT DELTA FOR COMP A2 Range: 0 - 50 Default: 12 HEAD PRESSURE CMP DELTA ENTER B1.DT XX SCT DELTA FOR COMP B1 Range: 0 - 50 Default: 12 B2.DT XX SCT DELTA FOR COMP B2 Range: 0 - 50 Default: 12 13 Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION CIR A EXV CONFIGURATION ENTER STR.A XXX EXV CIRC.A START POS Range: 0 - 100 Default: 30 MIN.A XXX EXV CIRC.A MIN POSITION Range: 0 - 100 Default: 8 RNG.A XXXXX EXVA STEPS IN RANGE SPD.A XXXXX EXVA STEPS PER SECOND POF.A XXX EXVA FAIL POSITION IN % MIN.A XXXXX EXVA MINIMUM STEPS Range: 0 - 65535 Default: 0 MAX.A XXXXX EXVA MAXIMUM STEPS Range: 0 - 65535 Default: * OVR.A XXX EXVA OVERRUN STEPS Range: 0 - 65535 Default: 167 TYP.A 0,1 EXVA STEPPER TYPE H.SCT XXX HIGH SCT THRESHOLD X.PCT XX OPEN EXV X% ON 2ND COMP Range: 0 - 30 Default: 10 X.PER XX MOVE EXV X% ON DISCRSOL Range: 0 - 30 Default: 5 A.PCT XXX PRE-OPEN EXV - FAN ADDING Range: 0 - 100 Default: 10 M.PCT XXX PRE-CLOSE EXV - FAN SUB Range: 0 - 100 Default: 10 S.PCT XXX PRE-CLOSE EXV - LAG SHUT Range: 0 - 100 Default: 10 DELY XXX LAG START DELAY Range: 0 - 100 Default: 10 STR.B XXX EXV CIRC.B START POS Range: 0 - 100 Default: 50 MIN.B XXX EXV CIRC.B MIN POSITION Range: 0 - 100 Default: 8 RNG.B XXXXX EXVB STEPS IN RANGE SPD.B XXXXX EXVB STEPS PER SECOND POF.B XXX EXVB FAIL POSITION IN % MIN.B XXXXX EXVB MINIMUM STEPS Range: 0 - 65535 Default: 0 MAX.B XXXXX EXVB MAXIMUM STEPS Range: 0 - 65535 Default: * OVR.B XXX EXVB OVERRUN STEPS Range: 0 - 65535 Default: 167 TYP.B 0,1 EXVB STEPPER TYPE MMR.S YES/NO MOTORMASTER SELECT P.GAN XX HEAD PRESSURE P GAIN Range: -20 - 20 Default: 1.0 I.GAN XX HEAD PRESSURE I GAIN Range: -20 - 20 Default: 0.1 D.GAN XX HEAD PRESSURE D GAIN Range: -20 - 20 Default: 0.0 MIN.S XXX MINIMUM FAN SPEED Range: 0 - 100 Default: 5.0 EXV.A EXV.B COMMENT Range: 0 - 65535 Default: * Range: 0 - 65535 Default: 200 Range: 0 - 100 Default: 0 0 = UNIPOLAR 1 = BIPOLAR Default: 1 Range: 50 - 140 Default: 115 CIR B EXV CONFIGURATION ENTER MM Range: 0 - 65535 Default: * Range: 0 - 65535 Default: 200 Range: 0 - 100 Default: 0 0 = UNIPOLAR 1 = BIPOLAR Default: 1 MOTORMASTER CONFIGURATION ENTER * Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, and 050-060, default is 2500. 14 Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY CRST X ITEM EXPANSION RESET COOL TEMP COOLING RESET TYPE MA.DG XX.X F 4-20 - DEGREES RESET RM.NO XXX.X F REMOTE - NO RESET TEMP Default: 125F (51.7C) Range: 0° to 125F RM.F XXX.X F REMOTE - FULL RESET TEMP Default: 0.0F (-17.8C) Range: 0 to 125F RM.DG XX.X F REMOTE - DEGREES RESET Default: 0.0F Range: –30 to 30F RT.NO XXX.X F RETURN - NO RESET TEMP Default: 10.0F (5.6C) Range: 0 to 125F COOLER T RT.F XXX.X F RETURN - FULL RESET TEMP Default: 0.0F (0.0C) Range: 0 to 125F COOLER T RT.DG XX.X F RETURN - DEGREES RESET DMDC X DEMAND LIMIT SELECT DM20 XXX % DEMAND LIMIT AT 20 MA SHNM XXX LOADSHED GROUP NUMBER SHDL XXX % LOADSHED DEMAND DELTA Default: 0% Range: 0 to 60% SHTM XXX MAXIMUM LOADSHED TIME Default: 60 minutes Range: 0 to 120 minutes DLS1 XXX % DEMAND LIMIT SWITCH 1 Default: 80% Range: 0 to 100% DLS2 XXX % DEMAND LIMIT SWITCH 2 Default: 50% Range: 0 to 100% LLEN ENBL/DSBL LEAD/LAG CHILLER ENABLE Default: Disable MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master SLVA XXX SLAVE ADDRESS Default: 0 Range: 0 to 239 LLBL X LEAD/LAG BALANCE SELECT LLBD XXX LEAD/LAG BALANCE DELTA LLDY XXX LAG START DELAY PARA YES PARALLEL CONFIGURATION CLSP X SETPOINT AND RAMP LOAD COOLING SETPOINT SELECT RL.S ENBL/DSBL RAMP LOAD SELECT CRMP X.X COOLING RAMP LOADING SCHD XX SCHEDULE NUMBER Z.GN X.X DEADBAND MULTIPLIER EN.A1 ENBL/DSBL ENABLE COMPRESSOR A1 Unit dependent EN.A2 ENBL/DSBL ENABLE COMPRESSOR A2 Unit dependent EN.B1 ENBL/DSBL ENABLE COMPRESSOR B1 Unit dependent EN.B2 ENBL/DSBL ENABLE COMPRESSOR B2 Unit dependent RSET ENTER ENTER SLCT ENTER SERV COMMENT Default: No Reset 0 = No Reset 1 = 4 to 20 mA Input 2 = Outdoor Air Temperature 3 = Return Fluid 4 = Space Temperature Default: 0.0F Range: –30 to 30F Default: 0.0F Range: –30 to 30F (–34.4 to -1.1 C) Default: None 0 = None 1 = Switch 2 = 4 to 20 mA Input 3 = CCN Loadshed Default: 100% Range: 0 to 100% Default: 0 Range: 0 to 99 Default: Master Leads 0 = Master Leads 1 = Slave Leads 2 = Automatic Default: 168 hours Range: 40 to 400 hours Default: 5 minutes Range: 0 to 30 minutes Default: YES (CANNOT BE CHANGED) Default: Single 0 = Single 1 = Dual Switch 2 = Dual CCN Occupied 3 = 4 to 20 mA Input (requires EMM) Default: Enable Default: 1.0 Range: 0.2 to 2.0 Default: 1 Range: 1 to 99 Default: 1.0 Range: 1.0 to 4.0 SERVICE CONFIGURATION ENTER 15 Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ENTER T.D.BC ON/OFF CCN TIME/DATE BROADCAST OAT.B ON/OFF CCN OAT BROADCAST G.S.BC ON/OFF GLOBAL SCHEDULE BROADCAST BC.AK ON/OFF CCN BROADCAST ACK’ER BCST ITEM EXPANSION BROADCAST CONFIGURATION COMMENT Table 11 — Time Clock Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ENTER HH.MM XX.XX SUB-ITEM ITEM EXPANSION TIME OF DAY DISPLAY TIME HOUR AND MINUTE DATE COMMENT Military (00:00 – 23:59) MONTH,DATE,DAY AND YEAR ENTER MNTH XX MONTH OF YEAR 1-12 (1 = January, 2 = February, etc) DOM XX DAY OF MONTH Range: 01-31 DAY X DAY OF WEEK 1-7 (1 = Sunday, 2 = Monday, etc) YEAR XXXX YEAR OF CENTURY STR.M XX MONTH Default: 4, Range 1 – 12 STR.W X WEEK Default: 1, Range 1 – 5 STR.D X DAY Default: 7, Range 1 – 7 MIN.A XX MINUTES TO ADD Default: 60, Range 0 – 99 STP.M XX MONTH Default: 10, Range 1 – 12 STP.W XX WEEK Default: 5, Range 1 – 5 STP.D XX DAY Default: 7, Range 1 – 7 MIN.S XX DST DAYLIGHT SAVINGS TIME ENTER HOL.L ENTER MINUTES TO SUBTRACT Default: 60, Range 0 – 99 LOCAL HOLIDAY SCHEDULES HD.01 through HD.30 MON XX HOLIDAY START MONTH Range 0 – 12 DAY XX START DAY Range 0 – 31 LEN XX DURATION (DAYS) Range 0 - 99 SCHEDULE NUMBER Default: 1, Range 1 – 99 SCH.N XX SCH.L LOCAL OCCUPANCY SCHEDULE ENTER PER.1 ENTER OCCUPANCY PERIOD 1* OCC.1 XX:XX PERIOD OCCUPIED TIME Military (00:00 – 23:59) UNC.1 XX.XX PERIOD UNOCCUPIED TIME Military (00:00 – 23:59) MON.1 YES/NO MONDAY IN PERIOD TUE.1 YES/NO TUESDAY IN PERIOD WED.1 YES/NO WEDNESDAY IN PERIOD THU.1 YES/NO THURSDAY IN PERIOD FRI.1 YES/NO FRIDAY IN PERIOD SAT.1 YES/NO SATURDAY IN PERIOD SUN.1 YES/NO SUNDAY IN PERIOD HOL.1 YES/NO HOLIDAY IN PERIOD * Repeats for Occupancy Periods 2 through 8. 16 Table 11 — Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ENTER OVR.T X TIMED OVERRIDE HOURS Default: 0, Range 0-4 hours OVR.L X OVERRIDE TIME LIMIT Default: 0, Range 0-4 hours T.OVR YES/NO TIMED OVERRIDE User Entry SUB-ITEM ITEM EXPANSION SCHEDULE OVERRIDE DISPLAY OVR COMMENT Table 12 — Operating Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION MODES CONTROLLING UNIT ENTER MD01 ON/OFF CSM CONTROLLING CHILLER MD02 ON/OFF WSM CONTROLLING CHILLER MD03 ON/OFF MASTER/SLAVE CONTROL MD05 ON/OFF RAMP LOAD LIMITED MD06 ON/OFF TIMED OVERRIDE IN EFFECT MD07 ON/OFF LOW COOLER SUCTION TEMPA MD08 ON/OFF LOW COOLER SUCTION TEMPB MD09 ON/OFF SLOW CHANGE OVERRIDE MD10 ON/OFF MINIMUM OFF TIME ACTIVE MD13 ON/OFF DUAL SETPOINT MD14 ON/OFF TEMPERATURE RESET MD15 ON/OFF DEMAND/SOUND LIMITED MD16 ON/OFF COOLER FREEZE PROTECTION MD17 ON/OFF LOW TEMPERATURE COOLING MD18 ON/OFF HIGH TEMPERATURE COOLING MD19 ON/OFF MAKING ICE MD20 ON/OFF STORING ICE MD21 ON/OFF HIGH SCT CIRCUIT A MD22 ON/OFF HIGH SCT CIRCUIT B MD23 ON/OFF MINIMUM COMP ON TIME MD24 ON/OFF PUMP OFF DELAY TIME MD25 ON/OFF LOW SOUND MODE MODE CSM SCT WSM — — — COMMENT LEGEND Chillervisor System Manager Saturated Condensing Temperature Water System Manager Table 13 — Alarms Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM EXPANSION ITEM CRNT ENTER AXXX OR TXXX CURRENTLY ACTIVE ALARMS RCRN ENTER YES/NO RESET ALL CURRENT ALARMS HIST ENTER AXXX OR TXXX ALARM HISTORY 17 COMMENT Alarms are shown as AXXX. Alerts are shown as TXXX. Alarms are shown as AXXX. Alerts are shown as TXXX. Table 14 — Operating Modes MODE NO. ITEM EXPANSION DESCRIPTION 01 CSM CONTROLLING CHILLER Chillervisor System Manager (CSM) is controlling the chiller. 02 WSM CONTROLLING CHILLER Water System Manager (WSM) is controlling the chiller. 03 MASTER/SLAVE CONTROL Ramp load (pull-down) limiting in effect. In this mode, the rate at which leaving fluid temperature is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling Ramp Loading (ConfigurationSLCTCRMP). The pull-down limit can be modified, if desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute. TIMED OVERRIDE IN EFFECT Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed schedule, forcing unit to Occupied mode. Override can be implemented with unit under Local (Enable) or CCN (Carrier Comfort Network®) control. Override expires after each use. LOW COOLER SUCTION TEMPA Circuit A cooler Freeze Protection mode. At least one compressor must be on, and the Saturated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If the saturated suction temperature is less than the Brine Freeze Point (Set PointsFRZ BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F (7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the saturated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for 90 seconds, a stage of capacity will be removed from the circuit. The control will continue to decrease capacity as long as either condition exists. LOW COOLER SUCTION TEMPB Circuit B cooler Freeze Protection mode. At least one compressor must be on, and the Saturated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If the saturated suction temperature is less than the Brine Freeze Point (Set PointsFRZ BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F (7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the saturated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for 90 seconds, a stage of capacity will be removed from the circuit. The control will continue to decrease capacity as long as either condition exists. 05 06 07 08 09 10 SLOW CHANGE OVERRIDE MINIMUM OFF TIME ACTIVE DUAL SETPOINT 13 DEMAND/SOUND LIMITED Demand limit is in effect. This indicates that the capacity of the chiller is being limited by demand limit control option. Because of this limitation, the chiller may not be able to produce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs or a 4 to 20 mA signal. COOLER FREEZE PROTECTION Cooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section for definition). The chiller will be shut down when either fluid temperature falls below the Freeze point. LOW TEMPERATURE COOLING Chiller is in Cooling mode and the rate of change of the leaving fluid is negative and decreasing faster than -0.5° F per minute. Error between leaving fluid and control point exceeds fixed amount. Control will automatically unload the chiller if necessary. HIGH TEMPERATURE COOLING Chiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing. Error between leaving fluid and control point exceeds fixed amount. Control will automatically load the chiller if necessary to better match the increasing load. 16 17 18 MAKING ICE STORING ICE Chiller is in an unoccupied mode and is using Cooling Set Point 3 (Set PointsCOOL CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open. Chiller is in an unoccupied mode and is controlling to Cooling Set Point 2 (Set PointsCOOL CSP.2). The ice done input to the Energy Management Module (EMM) is closed. HIGH SCT CIRCUIT A Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing condensing temperature. HIGH SCT CIRCUIT B Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing condensing temperature. MINIMUM COMP ON TIME Cooling load may be satisfied, however control continues to operate compressor to ensure proper oil return. May be an indication of oversized application, low fluid flow rate or low loop volume. PUMP OFF DELAY TIME Cooling load is satisfied, however cooler pump continues to run for the number of minutes set by the configuration variable Cooler Pump Shutdown Delay (ConfigurationOPT1 PM.DY). 21 22 23 24 25 Chiller is being held off by Minutes Off Time (ConfigurationOPT2DELY). Dual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set PointsCOOL CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2) during unoccupied periods. Temperature reset is in effect. In this mode, chiller is using temperature reset to adjust leaving fluid set point upward and is currently controlling to the modified set point. The set point can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to 20 mA signal. 15 20 Slow change override is in effect. The leaving fluid temperature is close to and moving towards the control point. TEMPERATURE RESET 14 19 Dual Chiller control is enabled. RAMP LOAD LIMITED LOW SOUND MODE Chiller operates at higher condensing temperature and/or reduced capacity to minimize overall unit noise during evening/night hours (ConfigurationOPT2LS.MD). 18 set to ‘On’ for these boards. The auxiliary board (AUX) has an 8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’ CONTROLS General — The 30RAP air-cooled scroll chillers contain the ComfortLink™ electronic control system that controls and monitors all operations of the chiller. The control system is composed of several components as listed in the sections below. See Fig. 3-5 for typical control box drawings. See Fig. 6 and 7 for control schematics. Control Module Communication RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light-emitting diodes). When operating correctly, the red status LEDs should be blinking in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the main base board (MBB) is supplied with the current software. If necessary, reload current software. If the problem still persists, replace the MBB. A red LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced. GREEN LED — The MBB has one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED which should be blinking whenever power is on. Check LEN connections for potential communication errors at the board J3 and/or J4 connectors. Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB provides both power and communication directly to the marquee display only. YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network (CCN) LED will blink during times of network communication. Main Base Board (MBB) — See Fig. 8. The MBB is the heart of the ComfortLink control system. It contains the major portion of operating software and controls the operation of the machine. The MBB continuously monitors input/output channel information received from its inputs and from all other modules. The MBB receives inputs from the discharge and suction pressure transducers and thermistors. See Table 15. The MBB also receives the feedback inputs from each compressor current sensor board and other status switches. See Table 16. The MBB also controls several outputs. Relay outputs controlled by the MBB are shown in Table 17. Information is transmitted between modules via a 3-wire communication bus or LEN (Local Equipment Network). The CCN (Carrier Comfort Network) bus is also supported. Connections to both LEN and CCN buses are made at the LVT (low voltage terminal). See Fig. 8. Energy Management Module (EMM) — The EMM module is available as a factory-installed option or as a fieldinstalled accessory. The EMM module receives 4 to 20 mA inputs for the leaving fluid temperature reset, cooling set point and demand limit functions. The EMM module also receives the switch inputs for the field-installed 2-stage demand limit and ice done functions. The EMM module communicates the status of all inputs with the MBB, and the MBB adjusts the control point, capacity limit, and other functions according to the inputs received. Carrier Comfort Network® (CCN) Interface — The 30RAP chiller units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is supplied and installed in the field. See Table 18. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made at LVT. Consult the CCN Contractor’s Manual for further information. NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. Wire manufactured by Alpha (2413 or 5463), American (A22503), Belden (8772), or Columbia (02525) meets the above mentioned requirements. It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables containing different colored wires. At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network: 1. Turn off power to the control box. 2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.) Current Sensor Board (CSB) — The CSB is used to monitor the status of the compressors by measuring current and providing an analog input to the main base board (MBB) or compressor expansion module (CXB). AUX Board (AUX) — The AUX is used with the digital scroll option and the low ambient head pressure option. It provides additional inputs and outputs for digital scroll control along with analog outputs to control head pressure control fan speeds. Expansion Valve Board (EXV) — The EXV board communicates with the MBB and directly controls the expansion valves to maintain the correct compressor superheat. Enable/Off/Remote Contact Switch — The Enable/ Off/Remote Contact switch is a 3-position switch used to control the chiller. When switched to the Enable position the chiller is under its own control. Move the switch to the Off position to shut the chiller down. Move the switch to the Remote Contact position and a field-installed dry contact can be used to start the chiller. The contacts must be capable of handling a 24 vac, 50-mA load. In the Enable and Remote Contact (dry contacts closed) positions, the chiller is allowed to operate and respond to the scheduling configuration, CCN configuration and set point data. See Fig. 9. Emergency On/Off Switch — The Emergency On/Off switch should only be used when it is required to shut the chiller off immediately. Power to the MBB, EMM, and marquee display is interrupted when this switch is off and all outputs from these modules will be turned off. Board Addresses — The main base board (MBB) has a 3-position instance jumper that must be set to ‘1.’ The electronic expansion valve board (EXV) and energy management board (EMM) have 4-position DIP switches. All switches are 19 3. Connect the red wire to (+) terminal on LVT of the plug, the white wire to COM terminal, and the black wire to the (–) terminal. 4. The RJ14 CCN connector on LVT can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool). Table 18 — CCN Communication Bus Wiring MANUFACTURER Alpha American Belden Columbia Manhattan Quabik IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus. Sensors — The electronic control uses 4 to 7 thermistors to sense temperatures for controlling chiller operation. See Table 15. These sensors are outlined below. Thermistors RGTA, RGTB, EWT, LWT, and OAT are identical in temperature versus resistance and voltage drop performance. The dual chiller thermistor is 5 kat 77 F (25 C)thermistor. Space temperature thermistor is a 10 kat 77 F (25 C). The DTT thermistor is an 86 kat 77 F (25 C)thermistor. See Thermistors section for temperature-resistance-voltage drop characteristics. COOLER LEAVING FLUID SENSOR — The thermistor is installed in a well in the factory-installed leaving fluid piping coming from the bottom of the brazed-plate heat exchanger. COOLER ENTERING FLUID SENSOR — The thermistor is installed in a well in the factory-installed entering fluid piping coming from the top of the brazed-plate heat exchanger. COMPRESSOR RETURN GAS TEMPERATURE SENSOR — These thermistors are installed in a well located in the suction line of each circuit. OUTDOOR-AIR TEMPERATURE SENSOR (OAT) — This sensor is factory installed on a bracket which is inserted through the base pan of the unit. DISCHARGE TEMPERATURE THERMISTOR (DTT) — This sensor is only used on units with a digital compressor. The sensor is mounted on the discharge line close to the discharge of the digital compressor. It attaches to the discharge line using a spring clip and protects the system from high discharge gas temperature when the digital compressor is used. This sensor is a connected to the AUX board. REMOTE SPACE TEMPERATURE SENSOR OR DUAL LEAVING WATER TEMPERATURE SENSOR — One of two inputs can be connected to the LVT. See appropriate sensor below. Remote Space Temperature Sensor — Sensor (part no. 33ZCT55SPT) is an accessory sensor that is remotely mounted in the controlled space and used for space temperature reset. The sensor should be installed as a wall-mounted thermostat would be (in the conditioned space where it will not be subjected to either a cooling or heating source or direct exposure to sunlight, and 4 to 5 ft above the floor). Space temperature sensor wires are to be connected to terminals in the unit main control box. The space temperature sensor includes a terminal block (SEN) and a RJ11 female connector. The RJ11 connector is used access into the Carrier Comfort Network® (CCN) at the sensor. To connect the space temperature sensor (Fig. 10): 1. Using a 20 AWG twisted pair conductor cable rated for the application, connect 1 wire of the twisted pair to one SEN terminal and connect the other wire to the other SEN terminal located under the cover of the space temperature sensor. 2. Connect the other ends of the wires to terminals 5 and 6 on TB5 located in the unit control box. Table 15 — Thermistor Designations THERMISTOR LWT EWT RGTA RGTB OAT SPT DTT PIN CONNECTION THERMISTOR INPUT POINT J8-13,14 (MBB) Cooler Leaving Fluid J8-11,12 (MBB) Cooler Entering Fluid J8-1,2 (MBB) Circuit A Return Gas Temperature J8-3,4 (MBB) Circuit B (035-060 only) Return Gas Temperature J8-7,8 (MBB) Outdoor-Air Temperature Sensor J8-5,6 (MBB) Accessory Remote Space TB5-5,6 Temperature Sensor or Dual LWT Sensor J6-1,2 (AUX) Discharge Temperature Thermistor LEGEND LWT — Leaving Water Temperature MBB — Main Base Board Table 16 — Status Inputs STATUS SWITCH Chilled Water Pump 1 Chilled Water Pump 2 Remote On/Off Cooler Flow Switch Compressor Fault Signal, A1 Compressor Fault Signal, A2 Compressor Fault Signal, B1 Compressor Fault Signal, B2 PIN CONNECTION POINT J7-1,2 J7-3,4 LVT-13,14 J7-9,10 J9-11,12 J9-5,6 J9-8,9 J9-2,3 Table 17 — Output Relays RELAY NO. K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 PART NO. Regular Wiring Plenum Wiring 1895 — A21451 A48301 8205 884421 D6451 — M13402 M64430 6130 — DESCRIPTION Energize Compressor A1 (010-030) Energize Compressor A1 and Condenser Fan Contactor 3 (055,060) Energize Compressor A2 (all but 010, 015 60 Hz) Energize Chilled Water Pump 1 Output Energize Chilled Water Pump 2 Output Energize Compressor B1 (035-050) Energize Compressor B1 and Condenser Fan Contactor 3 (055,060) Energize Compressor B2 (035-060) Alarm Relay Cooler/Pump Heater Energize Condenser Fan Contactor 1 (018-060) Energize Condenser Fan Contactor 2 (018-060) Minimum Load Valve 20 3. Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor. 4. Insert and secure the black (–) wire to terminal 2 of the space temperature sensor. 5. Connect the other end of the communication bus cable to the remainder of the CCN communication bus. Dual Leaving Water Temperature Sensor — For dual chiller applications (parallel only are supported), connect the dual chiller leaving fluid temperature sensor (refer to Configuring and Operating Dual Chiller Control section on page 36) to the space temperature input of the Master chiller. If space temperature is required for reset applications, connect the sensor to the Slave chiller and configure the slave chiller to broadcast the value to the Master chiller. Units on the CCN can be monitored from the space at the sensor through the RJ11 connector, if desired. To wire the RJ11 connector into the CCN (Fig. 11): IMPORTANT: The cable selected for the RJ11 connector wiring MUST be identical to the CCN communication bus wire used for the entire network. Refer to Table 18 for acceptable wiring. 1. Cut the CCN wire and strip ends of the red (+), white (ground), and black (–) conductors. (If another wire color scheme is used, strip ends of appropriate wires.) 2. Insert and secure the red (+) wire to terminal 5 of the space temperature sensor terminal block. LEGEND FOR FIG. 3-7 ALMR AUX BR C CB CCB CH CHC COMP CSB CWFS CWP DGS DPT DTT DUS EMM EXV FB FC FCB FIOP FR GND HPS LON LVT MBB MLV MM MP MS NEC OAT OFM RGT SCCR SPT SW TB TNKR TRAN UPC — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Alarm Relay Auxilliary Boiler Relay Contactor, Compressor Circuit Breaker Compressor Circuit Breaker Crankcase Heater Cooler/Pump Heater Contactor Compressor Current Sensor Board Chilled Water Flow Switch Chilled Water Pump Digital Scroll Compressor Discharge Pressure Transducer Discharge Temperature Thermistor Digital Unloader Solenoid Energy Management Electronic Expansion Valve Fuse Block Fan Contactor Fan Circuit Breaker factory Installed Option Fan Relay Ground High-Pressure Switch Local Operating Network Low Voltage Terminal Block Main Base Board Minimum Load Valve Motormaster Motor Protector Manual Starter National Electrical Code Outdoor-Air Thermistor Outdoor Fan Motor Return Gas Thermistor Short Circuit Current Rating Suction Pressure Transducer Switch Terminal Block Storage Tank Heater Relay Transformer Unitary Protocol Converter Terminal Block Terminal (Unmarked) Terminal (Marked) Splice Factory Wiring Field Wiring Accessory or Option Wiring To indicate common potential only; not to represent wiring. 21 LOCATED OVER EMM AND EXV EMM EXV FB-1 CHC TRAN CCB AUX CSB-A1 LON UPC DISCONNECT OPTION/TB TB1 TB4 FAN 1 C-A1 MBB COMPRESSOR MS- MSCWP1 CWP2 CWP1 CWP2 MM A1 CONTROL BOX a30-4962 Fig. 3 — Typical Control Box for 30RAP010,015 FB-1 EXV EMM AUX LON CHC CCB-1 FB-3 TRAN TB1 CSB-A1 CCB-2 CSB-A2 UPC TB4 MBB DISCONNECT OPTION/TB MS- MSCWP1 CWP2 C-A1 FC1/MM CWP1 CWP2 FC2 Fig. 4 — Typical Control Box for 30RAP018-030 a30-4963 22 C-A2 TRAN-2 FR-1 CB-1 C-A1 CSB-A1 TRAN-1 FR-2 C-A2 CSB-A2 CB-2 FC-1 MM 23 FC-3 AUX MBB UPC TB4 TB1 LOCATED OVER EMM AND EXV LON EXV CHC B1 B2 CONTROL BOX END A1 A2 COMPRESSORS FAN 2 FAN 1 FR-4 CSB-B2 CB-4 C-B2 055,060 UNIT ONLY CWP1 CWP2 FAN 4 FR-3 MS- MSCWP1 CWP2 FAN 3 C-B1 CSB-B1 CB-3 Fig. 5 — Typical Control Box for 30RAP035-060 FC-2 FCB-1/2/3 EMM DISCONNECT OPTION/TB a30-4964 STANDARD TERMINAL BLOCK OPTIONAL DISCONNECT CB1A TB1A PER NEC TO FUSED DISCONNECT PER NEC 2 3 21 11 TO FUSED DISCONNECT 1 CCB-1 22 12 23 13 BLK BLK BLK YEL YEL YEL 11 12 22 BLU 13 23 YEL BLU BLK CCB-2 BLK 11 21 YEL 12 22 BLU 13 23 H2 H3 HF ~ TRAN3 H1 SECONDARY 115V X1 YEL BLU GRN/YEL XF GFI-CO FIOP/ACCESSORY 2 BLK 2 BLK 22 YEL 13 23 BLU 1 T1 2 COMP A1 T2 3 T3 GRN/YEL CH-A2 11 21 BLK 12 22 YEL 13 23 BLU 1 T1 2 COMP A2 T2 3 T3 CHILLED WATER PUMP FIOP CWP1 GRN/YEL BLK L1 T1 L1 T1 BLK L1 YEL L2 T2 L2 T2 BLK L2 T3 BLU L3 T3 L3 BLK L3 BLK L1 T1 L1 T1 BLK L1 YEL L2 T2 L2 T2 BLK L2 BLU L3 T3 L3 T3 BLK L3 MS-CWP2 FU4 21 12 CA2 CSB-A2 MS-CWP1 1 1 11 BLU BLK BLK ~ ~ FU6 BLK RED X3 BLU 208/230V ONLY FU5 H4 YEL YEL BLU BLU BLU CA1 BLK 21 BLK BLU EQUIP GND WHT BLK YEL CH-A1 BLU BLK 380V,460V,575V ONLY CSB-A1 CWP2 CWP1 WATER PUMP GRN/YEL CWP2 WATER PUMP GRN/YEL LINE BRASS SCREW SILVER SCREW RESET TEST GRN-YEL LOAD VOLTAGE SERIES TERMINAL CONNECTIONS FOR PRIMARY SIDE TERMINAL CONNECTIONS FOR SECONDARY SIDE 575-3-60 100 H1-H2 XF-X2 230-3-60 400,500 H2-H4 FB3 XF-X2 208-3-60 500 H3-H4 XF-X2 460-3-60 600 H1-H4 XF-X2 FB1 11 21 BLK 11 21 BLK 11 21 BLK-1 YEL 12 22 YEL 12 22 YEL 12 22 BLK-2 BLU 13 23 BLU 13 23 BLU 13 23 BLK-3 BLK 11 21 BLK-1 YEL 12 22 BLK-2 BLU 13 23 BLK-3 HIGH SCCR ONLY FUSE NUMBER TRAN SIZE UNIT VOLTAGE 208/230-3-60 200VA 575-3-60 FU3 (24V) 460-3-60,575-3-60 FU5 & FU6 500VA 208/230-3-60,230-3-60 380-3-60,460-3-60,575-3-60 FB1 (WITH MM) 380-3-60,460-3-60,575-3-60 FNM-6 NONE LP-CC-20 NONE KTK-R-15 KTK-R-20 208/230-3-60 380-3-60,460-3-60,575-3-60 FB2 208/230-3-60 380-3-60,460-3-60,575-3-60 FB3 FNQ-R-3.5 208/230-3-60 NONE LP-CC-20 NONE LP-CC-20 8 6 LOW AMBIENT OPERATION (MOTORMASTER V) 1 1 BLK BLK 11 21 BLK L1 T1 BLK-1 22 YEL 12 22 YEL L2 T2 BLK-2 BLU 13 23 BLU 13 23 BLU L3 T3 BLK-3 2 25 YEL VIO 11 240 2 FB2 1/4W 2 11 21 BLK 11 21 BLK-1 22 YEL 12 22 BLK-2 BLU 13 23 BLU 13 23 BLK-3 BLK WHT COOLER/PUMP HEATERS (380,460,575V) 6 BLK VOLTAGE HZ 1 208/230/460/575 60 380 60 1 2 OFM2 3 1 GRN/YEL 3 2 BLK 1 BLK COOLER/PUMP HEATERS (208/230,230V) ~ 8 ~ ~ CHC YEL TB 13A ~ ~ ~ 2 * MM SIGNAL CONNECTION FROM AUX-J4 12 CHC 3 GRN/YEL MMR 14 RED YEL 4 WHT 2 OFM1 3 BLK BLK 1 BLK COOLER/PUMP HEATERS (208/230,230V) 2 BLK BLK FC2 BLK 3 1 21 YEL 12 *1 GRN/YEL FIOP/ACCESSORY BLK 11 HIGH SCCR ONLY OFM2 3 MM-A FB1 FB3 GRN/YEL 2 COOLER/PUMP HEATERS (380,460,575V) CHC YEL OFM1 3 WHT FNQ-R-2.5 500VA 208/230-3-60 2 1 2 ~ 208/230-3-60 FB1 (NO MM) 4 ~ ~ 380-3-60,460-3-60,575-3-60 FU4 (115V) BLK BLK BLU FNM-10 200VA 208/230-3-60 CHC YEL FNQ-R-2 FNQ-R-1.5 380-3-60,460-3-60,575-3-60 FC2 ~ ~ 380-3-60 460-3-60 FU1 & FU2 REPLACE WITH FNQ-R-3.5 FNQ-R-2.5 FC1 BLK WHT 2 3 TABLE 1 VOLTAGE SERIES TERMINAL CONNECTIONS FOR PRIMARY SIDE 575-3-60 100 H1 & H2 380-3-60 200 H1 & H2 230-3-60 500 H2 & H4 208-3-60 500 H3 & H4 460-3-60 600 H1 & H4 CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 1 TB4 7 RED BLK FU2 YEL B1 3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF 2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING. 4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED-THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE PHASE CONDITIONS. 5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC 1 MA TO 20 MA LOAD. SECONDARY 24V XF FU3 X2 X1 8. IF CHILLED WATER PUMP INTERLOCK IS USED, REMOVE JUMPER FROM TERMINAL 11 TO 17 AND WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17. 9. MP-A1 NOT USED IN THE FOLLOWING UNITS: 018,020: ALL UNITS 025,030: 460V UNITS WITHOUT DIGITAL SCROLL 10. MP-A2 NOT USED IN THE FOLLOWING UNITS: 018-020: ALL UNITS 025,030: 460V UNITS 11. JUMPER PLUG REQUIRED WHEN MP NOT USED 6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE, TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4. H4 GRN/YEL RED A1 1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS. ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES. C MIN WIRE FOR FIELD POWER SUPPLY. FU1 TRAN1 PRIMARY H3 H2 H1 NOTES: TB4 5 TB1 C RED BRN 7. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY, FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR. BRN SW2 C1 C TB1 BRN 3 UPC FIOP VIO BRN 24VAC CB3 3.2 AMPS VIO TB4 6 BRN 2 GND VIO 1 HOT RED UPC 2 1 3 2 1 FIOP/ACCESSORY VIO 3 BRN VIO 3 2 2 1 1 J1 MBB J2 3 2 1 3 3 2 2 1 BRN RED 1 3 2 1 J1 EMM J2 3 2 1 1 3 2 1 3 2 1 DGS FIOP 3 2 J1 EXV J2 BRN RED 2 1 12 11 AUX J1 a30-4965 BRN 1 VIO BRN 3 CWFS BLU BRN Fig. 6A — Typical Wiring Schematic, 30RAP018-030 Units — Power Wiring 24 CB1 3.2 AMPS RED TRAN1 MBB TB4 5 ORN J10A 1 1 RLY 11 9 BRN BRN GRA ORN 21 FC1 23 24 RED 18 1 BLK BLK BLK ORN SEE NOTE 7 BRN A2 FC2 FC2 BRN A2 FC1 BRN A2 FC3 BRN C TB1 C TB1 A2 GRA M2 VIO 19 7 M1 SEE NOTE 11 M2 VIO 5 TNK R A1 CHC A2 BRN ORN A1 CA1 A2 BRN C TB1 BRN A2 CA2 A2 CA1 TB1 GRA VIO LVT VIO J12 RED 6 5 GRA 4 HR ALMR VIO BR BRN HEAT/BOILER FIELD INSTALLED WIRING A1 CA2 A2 BRN 1 25 A1 CWP 1 A2 BRN C BRN A2 2 24 RED CWP2 BRN A2 CWP1 A1 CWP 2 A2 J11 CWFS 4 BLK 2 2 1 10 WHT 6 5 4 3 SEE NOTES ON PAGE 24. FIELD INSTALLED MAX LOAD-5VA SEALED 10VA INRUSH J6 2 1 10 4 3 1 CWPI J3 4 2 3 4 9 ORN 11 9 1 2 J4 12 3 4 5 13 6 14 8 RED 9 7 SW1 A1 ENABLE RED C1 B1 OFF 7 8 MAIN BASE BOARD 1 2 3 4 5 J9 7 RED RED 6 GRA 7 9 6 5 GRA 5 13 14 CWP2 RED RED 4 3 13 14 CWP1 VIO VIO 2 1 6 11 12 J7 LEN (+) CCN (COM) (-) WHT BLK SHIELD J1 1 BLK 2 WHT 3 RED 4 BRN 5 RED 6 BLK 7 WHT 8 RED BRN RED BLK WHT RED BLK WHT RED UPC RED PORT 2 1 NET + BLK 2 NET 3 N/C 4 N/C 5 SIGNAL PORT 1A 1 NET + 5 1 2 4 3 4 3 5 6 2 7 8 1 9 9 8 7 6 5 4 3 2 1 11 10 J8 9 8 5 4 13 14 7 6 12 J5 15 16 3 17 2 18 1 19 20 LON OPTION 21 J3 GND 22 NET J4 1 2 23 24 25 2 NET 2 3 SHIELD 10 UPC OPT 3 4 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 RED BLK WHT WHT BLK RED 3 2 1 4 J3 3 2 EXV 1 2 J7 1 3 4 5 RED RED WHT WHT BLK BLK BRN RED RED BRN RED 2 ORN 3 BRN 1 RED 2 ORN 3 BRN 1 RED 2 ORN 3 BRN 1 RED 2 ORN 3 BRN 1 1 1 2 2 3 4 5 4 MARQUEE DISPLAY BLK 3 WHT 4 RED 3 2 1 4 1 J4 3 2 5 6 2 J6 1 3 4 5 6 CSB B2 6 CSB A2 5 4 CSB B1 BLK WHT RED CSB A1 3 2 1 3 - 2 G 1 + 3 - 2 G 1 + AUX J2 J9 J6 DGS OR MM FIOP OFF 10 J13 1 2 - 7 CH1 8 26 1 2 1 2 3 4 5 6 7 8 RGTA RED DARK = SWITCH LOCATION 1 2 3 4 5 1 2 3 4 5 7 8 PL-EXVA BLK BLK YEL WHT EXV-A GRY GRN RED RED PL50-1 VIO DUS RED BRN BLK PL50-2 CH11 - 1 2 1 2 PL50-3 RED DTT RED BLK BLK PL50-4 J4 CH9 1 - 2 J5 CH10 ON LVT WHT 6 8 8 10 RED J12 VIO 17 GRA 2 BRN BRN BRN PL1-6 MP-A2 VIO 15 18 LVT 21 VIO PL1-5 16 ALM R ORN J12 6 MP-A2 T1 PL1-8 BRN FIOP OR FIELD INSTALLED OPTION 20 16 T2 RED BRN PL1-2 MP-A1 M1 VIO SEE NOTE 11 3 DUAL SETPOINT A2 CWP1 PL1-4 MP-A1 T1 SEE NOTE 10 BLK PL1-1 14 27 15 BRN CA2 RED ORN ORN 13 25 14 A2 CA1 A2 ACCESSORY STORAGE TANK HEATER RELAY HPS-A 12 26 REMOTE ON-OFF SWITCH (SEE NOTE 5) A2 CHC BRN BRN MAX LOAD-5VA SEALED 10VA INRUSH LVT J11 11 22 13 RED LVT J12-5 BRN T2 RED PL1-7 TB4 4 RED 10 RED 20 11 EXV J1-2 A2 A1 ORN 9 19 SEE NOTE 8 BRN SEE NOTE 9 PL1-3 RED MLV ACCSY A1 PNK 8 18 LVT GRA PNK 7 RED 17 17 CWFS 3 RED MLV-A 5 16 LVT BRN BRN 6 15 HEAT UPC GND 4 14 RLY 4 BRN 3 13 RLY 3 BRN MBB J1-2 2 12 RLY 2 GRN/YEL 1 11 RLY 1 X2 C GRA 9 10 RLY 8 SECONDARY 24V X1 FU3 BRN 8 8 RLY 7 XF 7 7 RLY 6 RED BLK 6 RED 6 RLY 5 RED 5 5 RLY 10 B2 C2 TB4 4 TB1 RED TB4 7 4 4 J10B ORN SW2 RED 3 RED 3 RLY 9 ORN 2 2 A2 CB2 5.2 AMPS - 1 2 1 2 RED BLK TO MM-A 1 2 BLK 3 LVT 4 5 6 1 2 J12 T55 BLU 3 23 BLU 4 22 OAT RED LVT SEN T-55 ACCSY SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT BLK 3 4 BLK WHT RED 3 2 1 4 3 2 J3 1 EMM 2 3 4 1 5 6 4 1 2 3 4 EVAPORATOR ENTERING FLUID TEMP RED 4 BLK BLK EVAPORATOR LEAVING FLUID TEMP RED WHT RED 3 2 1 J7 4 3 2 J4 7 8 9 10 11 1 12 BLK 1 13 2 14 FIOP/ ACCESSORY 3 1 4 2 5 3 4 6 7 8 9 10 11 12 RED GRN BLK RED GRN BLK 5 B C A + J6 DPTA - 6 7 8 9 B C + A - 10 11 SPTA 12 1 2 3 4 5 6 7 J10 17 GRA 16 2 RED 15 3 RED 14 4 BLU 13 5 BLU 12 6 11 8 ICE DONE DLS STEP 1 DLS STEP 2 9 10 11 12 13 14 10 1 2 3 4 5 6 9 7 8 8 7 BRN 6 5 ORN + DEMAND LIMIT - 4-20mA 9 + TEMP RESET - 4-20mA 10 + COOLING SETPOINT - 4-20mA 4 3 7 8 9 VIO 2 PNK 1 10 11 12 Fig. 6B — Typical Wiring Schematic, 30RAP018-030 Units — Control Wiring 25 1 GRA a30-4966 STANDARD TERMINAL BLOCK OPTIONAL DISCONNECT CB1A CCB-1 TB1A PER NEC TO FUSED DISCONNECT PER NEC 2 3 11 TO FUSED DISCONNECT 1 12 21 BLK BLK BLK BLK BLK 22 YEL YEL YEL YEL YEL 13 23 BLU YEL BLU BLK CCB-2 BLK 11 21 YEL 12 22 BLU 13 23 CCB-3 ~ ~ FU6 BLK RED 1 1 H2 H3 HF ~ TRAN3 H1 11 YEL 12 22 BLU 13 23 YEL BLU BLK BLK 2 LINE SERIES TERMINAL CONNECTIONS FOR PRIMARY SIDE 575-3-60 100 H1-H2 XF-X2 230-3-60 400,500 H2-H4 XF-X2 208-3-60 500 H3-H4 XF-X2 460-3-60 600 H1-H4 XF-X2 VOLTAGE TEST GRN-YEL LOAD BLU 11 21 YEL 12 22 TRAN SIZE UNIT VOLTAGE 208/230-3-60 380-3-60 460-3-60 200VA 575-3-60 BLU 13 23 TERMINAL CONNECTIONS FOR SECONDARY SIDE 500VA FB1 (NO MM) 380-3-60,460-3-60,575-3-60 FB1 (WITH MM) 380-3-60,460-3-60,575-3-60 208/230-3-60 208/230-3-60 575-3-60 21 BLK 12 22 YEL 13 23 BLU 1 YEL BLU 11 21 BLK 12 22 YEL 13 23 BLU 1 NONE LP-CC-20 NONE KTK-R-15 KTK-R-20 NONE LP-CC-20 NONE LP-CC-20 21 BLK 12 22 YEL 13 23 BLU 1 3 L1 T1 BLK L1 T2 L2 T2 BLK L2 T3 BLU L3 T3 L3 BLK L3 BLK L1 T1 L1 T1 BLK L1 YEL L2 T2 L2 T2 BLK L2 BLU L3 T3 L3 T3 BLK L3 CWP2 FB1 FC1 BLK 11 21 BLK 11 21 BLK 11 21 BLK-1 YEL 12 22 YEL 12 22 YEL 12 22 BLK-2 BLU 13 23 BLU 13 23 BLU 13 23 BLK-3 CHC BLK TABLE 1 BLK 11 YEL 12 BLU 13 4 2 SERIES 575-3-60 100 H1 & H2 575-3-60 100 COM & 575 380-3-60 200 H1 & H2 380-3-60 200 COM & 380 230-3-60 500 H2 & H4 230-3-60 500 COM & 230 208-3-60 500 H3 & H4 208-3-60 500 COM & 208 460-3-60 600 H1 & H4 460-3-60 600 COM & 460 FU1 BLK FU2 YEL BLK 11 22 YEL 23 BLU 21 BLK BLK BLU 11 21 BLK-1 YEL 12 22 BLK-2 BLU 13 23 BLK-3 RED UPC 2 1 3 2 1 3 2 1 3 3 2 2 1 BRN RED 1 3 2 1 J1 EMM J2 3 BRN BLU 13 23 BLU 13 23 BLU L3 T3 BLK-3 2 1 2 1 2 1 BRN RED 2 1 12 11 240 4 1 OFM4 (055,060 ONLY) 3 GRN/YEL 2 OFM3 (035-050) OFM4 (055,060) 3 1/4W RED GRN/YEL * MM SIGNAL CONNECTION FROM AUX-J4 BLK 2 SEE NOTE 7 3 BLK 11 YEL 12 BLU 13 BLK 11 22 YEL 23 BLU 21 8 FC2 BLK 3 COOLER/PUMP HEATERS (380,460,575V) 6 2 BLK 21 BLK-1 1 12 22 BLK-2 13 23 BLK-3 FC1 11 21 BLK-1 12 22 BLK-2 BLU 13 23 BLK-3 60 380 60 1 BLK COOLER/PUMP HEATERS (208/230,230V) WHT 2 3 OFM1 GRN/YEL 1 OFM2 3 GRN/YEL 1 2 3 OFM3 (055,060 ONLY) GRN/YEL BRN Fig. 7A — Typical Wiring Schematic, 30RAP035-060 Units — Power Wiring 26 HZ BLK 2 BLK-3 YEL 208/230/460/575 3 BLK-2 BLK VOLTAGE 1 2 BLK-1 AUX J1 TB 13A 1 2 (055,060 ONLY) BLU GRN/YEL 2 MMR VIO 11 14 CHC 3 OFM2 3 YEL 2 YEL 3 CWFS BLK-2 DGS FIOP 3 1 2 WHT J1 EXV J2 GRN/YEL ~ VIO BLK-1 T2 CHC BRN 1 T1 L2 BLK BRN BRN OFM1 3 ~ 1 L1 YEL ~ ~ 2 BLK 22 FCB2/FB2 FIOP/ACCESSORY 1 21 YEL 12 GRN/YEL 3 J1 MBB J2 BLK 11 22 SECONDARY 24V RED 2 1 21 YEL 12 575 460 400 380 230 3 FIOP/ACCESSORY BLK 11 2 TRAN2 PRIMARY 208 WHT 2 1 MM-A FB1 *1 24VAC 3 FC3 BLK 1 BLK (055,060 ONLY) C TB1 1 HOT BLK-3 25 UPC FIOP 2 GND BLK-2 23 BLK COOLER/PUMP HEATERS (208/230,230V) 2 BLK-3 RED BRN VIO 22 13 YEL FB3 GRN/YEL BRN 12 ~ ~ X2 BRN BLK-1 OFM3 GRN/YEL 3 BLK 21 YEL COM SECONDARY 24V SW2 6 FC2 BLK CB4 3.2 AMPS X1 8 HIGH SCCR ONLY H4 RED VIO GRN/YEL 3 BLK-2 TERMINAL CONNECTIONS FOR PRIMARY SIDE CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 2 TRAN1 PRIMARY H3 H2 BRN CWP2 WATER PUMP 1 COOLER/PUMP HEATERS (380,460,575V) LOW AMBIENT OPERATION (MOTORMASTER V) VOLTAGE 2 GRN/YEL 2 BLK-1 TABLE 2 TERMINAL CONNECTIONS FOR PRIMARY SIDE 3 CWP1 WATER PUMP ~ SEE NOTE 7 BLK SERIES VIO GRN/YEL T1 ~ ~ 10. MP-A1 NOT USED IN THE FOLLOWING UNITS: 035-045: ALL UNITS 050-060: 460V UNITS WITHOUT DIGITAL SCROLL 11. MP-A2 NOT USED IN THE FOLLOWING UNITS: 035-045: ALL UNITS 050-060: 460V UNITS 12. MP-B1 NOT USED IN THE FOLLOWING UNITS: 035,040: ALL UNITS 045-060: 460V UNITS 13. MP-B2 NOT USED IN THE FOLLOWING UNITS: 035,040: ALL UNITS 045-060: 460V UNITS 14. JUMPER PLUG REQUIRED WHEN MP NOT USED VOLTAGE TB4 6 T3 L2 YEL VIO COMP B2 T2 YEL FCB2/FB2 9. IF CHILLED WATER PUMP INTERLOCK IS USED, REMOVE JUMPER FROM TERMINAL 11 TO 17 AND WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17. 8. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY, 030-050: FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR. 055,060: FAN CONTACTOR FC3 IS REPLACED WITH MOTORMASTER RELAY MMR.. VIO T1 2 L1 HIGH SCCR ONLY 6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE, TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4. 7. FOR 575-3-60V UNITS, FAN CIRCUIT BREAKER FCB2 IS REPLACED WITH FUSE BLOCK FB2. CB3 3.2 AMPS GRN/YEL CH-B2 FNM-6 3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF 2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING. 4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED-THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE PHASE CONDITIONS. 5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC 1 MA TO 20 MA LOAD. C1 T3 BLK FB3 FNQ-R-3.5 1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS. ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES. 2. USE 75 C MIN WIRE FOR FIELD POWER SUPPLY. B1 COMP B1 T2 3 11 CHC A1 GRN/YEL T1 2 CHILLED WATER PUMP FIOP CWP1 YEL FU3 T3 FNM-10 FNQ-R-2.5 NOTES: XF COMP A2 T2 3 WHT TB4 7 RED T1 2 ~ 208/230-3-60 H1 GRN/YEL CH-B1 ~ ~ 380-3-60,460-3-60,575-3-60 CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 1 T3 FNQ-R-2 500VA 208/230-3-60 FB3 COMP A1 T2 3 11 CB2 CSB-B2 MS-CWP1 REPLACE WITH FNQ-R-3.5 FNQ-R-2.5 200VA 208/230-3-60 460-3-60,575-3-60 208/230-3-60,230-3-60 380-3-60,460-3-60,575-3-60 FB2 T1 2 FNQ-R-1.5 380-3-60,460-3-60,575-3-60 FU4 (115V) 1 CH-A2 BLU BLK BLK MS-CWP2 FU3 (24V) BLU CB1 BLK 208/230V ONLY BRASS SCREW RESET FU5 & FU6 23 BLU BLK YEL CCB-4 XF GFI-CO FIOP/ACCESSORY FU1 & FU2 13 FU4 GRN/YEL FUSE NUMBER YEL YEL X1 2 SILVER SCREW BLK 22 CA2 CSB-A2 BLK 21 21 12 BLU BLK 380V,460V,575V ONLY CSB-B1 BLK 11 BLU BLK SECONDARY 115V X3 BLU CA1 BLK YEL 208/230V ONLY FU5 WHT 22 21 YEL EQUIP GND H4 11 12 BLK BLU BLU BLU BLU BLU BLU 23 13 BLK YEL CH-A1 BLU BLK 380V,460V,575V ONLY CSB-A1 a305283 CB1 3.2 AMPS a30-5284 RED TRAN1 MBB TB4 5 ORN J10A 1 1 RLY 11 4 5 10 ORN ORN BLU BLK BLK PL2-1 M2 M1 VIO M2 SEE NOTE 14 21 23 24 PNK LVT 18 1 HPS-A BLK BLK BLK M1 VIO M2 SEE NOTE 14 PL1-5 M1 VIO SEE NOTE 14 M2 VIO 17 GRA LVT VIO J12 TAN 18 GRA VIO VIO RED 1 25 2 24 RED 4 19 7 6 GRA 5 GRA 4 3 HR ALMR VIO BR BRN HEAT/BOILER FIELD INSTALLED WIRING LVT 1 6 4 3 J6 2 (055,060 ONLY) PNK TAN CWFS 4 BLK 1 10 WHT A1 CB1 A2 1 FR3 0 A1 CB2 A2 1 FR4 0 1 J3 4 2 3 4 9 ORN 11 11 9 1 2 J4 12 3 4 5 13 6 14 13 REMOTE ON-OFF SWITCH (SEE NOTE 5) 7 SW1 A1 ENABLE RED C1 B1 OFF 7 8 MAIN BASE BOARD 1 2 3 4 5 J9 7 RED RED 6 GRA 7 9 6 5 GRA 5 16 13 14 CWP2 RED RED 4 3 13 14 CWP1 VIO VIO 2 1 6 11 12 J7 LEN (+) CCN 1 WHT (COM) BLK (-) RED SHIELD J1 BRN BLK 2 WHT 3 RED 4 BRN 5 RED 6 BLK 7 WHT 8 RED RED BLK WHT RED BLK WHT RED UPC RED PORT 2 1 NET + BLK 2 NET 3 N/C 4 N/C 5 SIGNAL PORT 1A 1 NET + 5 1 2 4 3 4 3 5 6 2 7 8 1 9 9 8 7 6 5 4 3 2 1 11 10 J8 9 8 6 5 4 12 13 14 7 J5 15 16 3 17 2 18 1 19 20 LON OPTION 21 J3 GND 22 NET J4 1 2 23 24 25 2 NET 2 3 SHIELD 10 UPC OPT FC3 BRN C TB1 BRN A2 CB2 BRN A2 CB1 BRN C TB1 BRN C TB1 BRN C TB1 BRN A2 CA2 BRN A2 CA1 BRN C TB1 BRN A2 CWP2 BRN A2 CWP1 BRN A2 FC2 ACCSY ALMR AUX BR C CB CCB CH CHC CO COMP CSB CWFS CWP CWPI DGS DLS DPT DTT DUS EMM EWT EXV FB FC FCB FIOP FR FU GND HPS HR LVT LWT MBB MLV MM MMR MP MS OAT OFM PL R RGT RLY SAT SCCR SPT SW TB TNKR TRAN UPC BRN (055,060 ONLY) LVT J12 5 21 TNK R A2 A2 1 FR1 0 A1 CA2 A2 1 FR2 0 A1 CWP 1 A2 BRN (055,060 ONLY) BRN (055,060 ONLY) A2 2 A1 PNK 1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 26 1 2 3 4 5 6 1 2 FC3 A2 RED BLK WHT WHT BLK RED 3 2 1 4 J3 3 2 EXV 1 2 J7 1 3 4 5 RED RED WHT WHT BLK BLK BRN RED RED BRN RED 2 ORN 3 BRN 1 RED 2 ORN 3 BRN 1 RED 2 ORN 3 BRN 1 RED 2 ORN 3 BRN 1 1 1 2 2 3 4 5 4 MARQUEE DISPLAY BLK 3 WHT 4 RED 3 2 1 4 1 J4 3 2 2 J6 1 5 6 3 4 5 6 CSB B2 6 CSB A2 5 4 CSB B1 BLK WHT RED CSB A1 3 2 1 3 - 2 G 1 + 3 - 2 G 1 + AUX J2 J9 J6 DGS OR MM FIOP 1 2 3 4 5 6 7 8 RGTA RED J4 DARK = SWITCH LOCATION J5 3 4 1 2 3 4 5 6 7 8 9 10 11 12 BRN PL2-8 BRN BRN TERMINAL BLOCK TERMINAL (UNMARKED) TERMINAL (MARKED) SPLICE FACTORY WIRING FIELD WIRING ACCESSORY OR OPTION WIRING TO INDICATE COMMON POTENTIAL ONLY,NOT TO REPRESENT WIRING ACCESSORY ALARM RELAY AUXILIARY BOILER RELAY CONTACTOR, COMPRESSOR CIRCUIT BREAKER COMPRESSOR CIRCUIT BREAKER CRANKCASE HEATER COOLER/PUMP HEATER CONTACTOR CONVENIENCE OUTLET COMPRESSOR CURRENT SENSOR BOARD CHILLED WATER FLOW SWITCH CHILLED WATER PUMP CHILLED WATER PUMP INTERLOCK DIGITAL SCROLL DEMAND LIMIT SWITCH DISCHARGE PRESSURE TRANSDUCER DISCHARGE TEMPERATURE THERMISTOR DIGITAL UNLOADER SOLENOID ENERGY MANAGEMENT ENTERING WATER TEMPERATURE EXPANSION VALVE CONTROL BOARD FUSE BLOCK FAN CONTACTOR FAN CIRCUIT BREAKER FACTORY INSTALLED OPTION FAN RELAY FUSE GROUND HIGH PRESSURE SWITCH HEAT RELAY LOW VOLTAGE TERMINAL LEAVING WATER TEMPERATURE MAIN BASE BOARD MINIMUM LOAD VALVE MOTORMASTER MOTORMASTER RELAY MODULAR MOTOR PROTECTOR MANUAL STARTER OUTDOOR AIR THERMISTOR OUTDOOR FAN MOTOR PLUG RELAY RETURN GAS TEMPERATURE RELAY SUPPLY AIR TEMPERATURE SHORT CIRCUIT CURRENT RATING SUCTION PRESSURE TRANSDUCER SWITCH TERMINAL BLOCK STORAGE TANK HEATER RELAY TRANSFORMER UNITARY PROTOCOL CONVERTER - 7 CH1 8 1 2 3 4 5 1 2 3 4 5 7 8 PL-EXVB BLK BLK YEL WHT EXV-B GRY GRN RED RED PL-EXVA BLK BLK YEL WHT EXV-A GRY GRN RED RED PL50-1 VIO DUS RED BRN BLK PL50-2 CH11 - 1 2 1 2 PL50-3 RED DTT RED BLK BLK PL50-4 CH9 1 - 2 CH10 - 1 2 1 2 RED BLK TO MM-A 1 2 RGTB RED LVT BLK J12 T55 BLU 3 23 BLU 4 22 OAT RED LVT SEN T-55 ACCSY SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT BLK 4 BLK WHT RED 3 2 1 4 3 2 J3 1 EMM 2 3 4 1 5 6 4 2 MP-B2 T1 BRN PL2-4 BRN BLK 3 1 SEE NOTE 13 T2 RED BRN (055,060 ONLY) SEE NOTE 8 OFF 10 J13 FC1 A2 ON LVT WHT 6 8 8 10 15 DUAL SETPOINT RED 9 14 8 A2 BRN (055,060 ONLY) 4 SEE NOTE 9 BRN X 2 (055,060 ONLY) 3 MP-B1 T1 BRN PL1-8 FR1 10 CWPI MP-A2 T1 SEE NOTE 12 T2 RED PL1-4 BRN LEGEND X BRN ALM R CWP 2 T2 RED PL2-7 (055,060 ONLY) PNK TAN 2 A2 A1 MP-A1 T1 SEE NOTE 11 PL2-3 FR2 4 2 4 J11 2 17 2 FC2 CA1 RED RED FIELD INSTALLED MAX LOAD-5VA SEALED 10VA INRUSH FR3 5 4 2 (055,060 ONLY) PNK TAN J12 6 A1 CHC T2 RED PL1-7 FIOP OR FIELD INSTALLED OPTION FR4 LVT A2 CWP1 FC2 PL1-6 MP-A2 GRA 16 ORN BRN CA2 A1 ORN VIO VIO A2 CA1 A2 PL1-2 MP-A1 ORN A2 CHC BRN SEE NOTE 10 PL1-3 RED LVT J12-5 BRN A2 BLK PL1-1 RED A2 CB1 BRN A1 ORN 15 27 CWFS 3 BRN RED ORN 14 26 BRN A2 ACCESSORY STORAGE TANK HEATER RELAY ORN 13 25 20 FC1 MAX LOAD-5VA SEALED 10VA INRUSH J11 12 22 PNK VIO VIO RED 11 UPC GND SEE NOTE 8 PL2-6 MP-B2 PNK TB4 4 VIO VIO PL2-5 RED VIO VIO 9 20 BRN BRN PL2-2 MP-B1 M1 VIO SEE NOTE 14 10 RED 19 MBB J1-2 RED BLU VIO 8 18 HEAT A1 PNK HPS-B 7 RED 17 RLY 4 MLV ACCSY PNK BRN BRN GRA 5 6 16 RLY 3 GRA MLV-A 5 15 RLY 2 BRN BRN BRN GRA 4 14 RLY 1 GRN/YEL C 3 13 RLY 8 X2 BLU 2 12 RLY 7 SECONDARY 24V X1 FU3 4 1 11 RLY 6 XF BLK 9 9 RLY 5 RED 8 8 J10B RED 7 7 RLY 10 B2 C2 TB4 4 TB1 RED TB4 7 RED 6 RED 6 ORN SW2 BRN 3 RED 3 RLY 9 ORN 2 2 A2 CB2 5.2 AMPS EVAPORATOR ENTERING FLUID TEMP RED 4 BLK BLK EVAPORATOR LEAVING FLUID TEMP RED WHT RED 3 2 1 J7 4 3 2 J4 GRN BLK RED GRN BLK RED GRN BLK RED GRN BLK 8 9 10 11 1 12 BLK RED 7 B C A 13 + 14 FIOP/ ACCESSORY DPTB - 1 B C + A - 2 3 SPTB 4 5 B C A + J6 DPTA - 6 7 8 9 B C + A - 10 11 SPTA 12 1 2 3 4 5 6 7 J10 17 GRA 16 2 RED 15 3 RED 14 4 BLU 13 5 BLU 12 6 11 8 ICE DONE DLS STEP 1 DLS STEP 2 9 10 11 12 13 14 10 1 2 3 4 5 6 9 7 8 8 7 BRN 6 5 ORN + DEMAND LIMIT - 4-20mA 9 + TEMP RESET - 4-20mA 10 + COOLING SETPOINT - 4-20mA 4 3 7 8 9 VIO 2 PNK 1 10 11 12 Fig. 7B — Typical Wiring Schematic, 30RAP035-060 Units — Control Wiring 27 1 GRA RED LED - STATUS GREEN LED LEN (LOCAL EQUIPMENT NETWORK) YELLOW LED CCN (CARRIER COMFORT NETWORK) INSTANCE JUMPER CEPL130346-01 K11 J1 J4 K8 STATUS J2 K7 K10 K9 K5 K6 J10 LEN J3 K4 K3 K1 K2 CCN J5 J6 J7 J9 J8 Fig. 8 — Main Base Board a30-4967 Fig. 9 — Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations T-55 SPACE SENSOR a30-4968 SPT (T10) PART NO. 33ZCT55SPT 6 SENSOR SEN SEN LVT TO CCN COMM 1 BUS (PLUG) AT UNIT 3 CCN+ 5 CCN GND 4 3 CCN- 4 2 1 Fig. 10 — Typical Space Temperature Sensor Wiring Fig. 11 — CCN Communications Bus Wiring to Optional Space Sensor RJ11 Connector 28 compressor to start next. If no compressors have been running for more than 30 minutes and the leaving fluid temperature is greater than the saturated condensing temperature, the wear factor is still used to determine which compressor to start next. If the leaving fluid temperature is less than the saturated condensing temperature, then the control will start either compressor A1 or compressor B1 first, depending on the user-configurable circuit lead-lag value. For units with the minimum load control valve, the A circuit with the minimum load valve is always the lead circuit. The A circuit is also always the lead for units with the digital compressor option. On units with the digital scroll option, the A1 compressor operates continuously, providing close leaving chilled water control. For this reason, on/off cycling of the unit’s compressors is dramatically reduced, which in turn reduces wear associated with compressor start/stop cycles. The EXVs will provide a controlled start-up. During startup, the low pressure logic will be bypassed for 21/2 minutes to allow for the transient changes during start-up. As additional stages of compression are required, the processor control will add them. See Table 19. If a circuit is to be stopped, the compressor with the lowest wear factor will be shut off first except when a digital compressor is used. The digital compressor is always the last compressor to shut off. The capacity control algorithm runs every 30 seconds. The algorithm attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from –100 to +100%. If the next stage of capacity is a compressor, the control starts (stops) a compressor when the ratio reaches +100% (–100%). If installed, the minimum load valve solenoid will be energized with the first stage of capacity. Minimum load valve value is a fixed 30% in the total capacity calculation. The control will also use the minimum load valve solenoid as the last stage of capacity before turning off the last compressor. A delay of 90 seconds occurs after each capacity step change. Refer to Table 19. MINUTES LEFT FOR START — This value is displayed only in the network display tables (using Service Tool, ComfortVIEW™ or ComfortWORKS® software) and represents the amount of time to elapse before the unit will start its initialization routine. This value can be zero without the machine running in many situations. This can include being unoccupied, ENABLE/OFF/REMOTE CONTACT switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time (DELY, see below) may be in effect. The machine should start normally once the time limit has expired. MINUTES OFF TIME (ConfigurationOPT2 DELY) — This user-configurable time period is used by the control to determine how long unit operation is delayed after power is applied/restored to the unit. Typically, this time period is configured when multiple machines are located on a single site. For example, this gives the user the ability to prevent all the units from restarting at once after a power failure. A value of zero for this variable does not mean that the unit should be running. This factory-installed option (FIOP) or field-installed accessory is used for the following types of temperature reset, demand limit, and/or ice features: • 4 to 20 mA leaving fluid temperature reset (requires field-supplied 4 to 20 mA generator) • 4 to 20 mA cooling set point reset (requires fieldsupplied 4 to 20 mA generator) • Discrete inputs for 2-step demand limit (requires fieldsupplied dry contacts capable of handling a 24 vac, 50 mA load) • 4 to 20 mA demand limit (requires field-supplied 4 to 20 mA generator) • Discrete input for Ice Done switch (requires fieldsupplied dry contacts capable of handling a 24 vac, 50 mA load) See Demand Limit and Temperature Reset sections on pages 41 and 37 for further details. Energy Management Module (Fig. 12) — CAUTION Care should be taken when interfacing with other manufacturer’s control systems due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used. A proof-ofcooler flow device is factory installed in all chillers. It is recommended that proper operation of the switch be verified on a regular basis. Loss-of-Cooler Flow Protection — Electronic Expansion Valves (EXV) — All units are equipped from the factory with EXVs. Each refrigeration circuit is also supplied with a factory-installed liquid line filter drier and sight glass. The EXV is set at the factory to maintain 9° F (5.0° C) suction superheat leaving the cooler by metering the proper amount of refrigerant into the cooler. The superheat set point is adjustable, but should not be adjusted unless absolutely necessary. The EXV is designed to limit the cooler saturated suction temperature to 50 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overloading the compressor. Capacity Control — The control system cycles compressors, digital scroll modulting solenoid (if equipped), and minimum load valve solenoids (if equipped) to maintain the user-configured leaving chilled fluid temperature set point. Entering fluid temperature is used by the main base board (MBB) to determine the temperature drop across the cooler and is used in determining the optimum time to add or subtract capacity stages. The chilled fluid temperature set point can be automatically reset by the return fluid temperature, space, or outdoor-air temperature reset features. It can also be reset from an external 4 to 20-mA signal (requires energy management module FIOP or accessory). The standard control has an automatic lead-lag feature built in which determines the wear factor (combination of starts and run hours) for each compressor. If all compressors are off and less than 30 minutes has elapsed since the last compressor was turned off, the wear factor is used to determine which 29 J2 LEN J3 TEST 1 PWR J4 J1 STATUS CEPL130351-01 CEBD430351-0396-01C J5 J7 J6 RED LED - STATUS TEST 2 GREEN LED LEN (LOCAL EQUIPMENT NETWORK) ADDRESS DIP SWITCH Fig. 12 — Energy Management Module when the control is attempting to remove the last stage of capacity. Slow Change Override — The control prevents the capacity stages from being changed when the leaving fluid temperature is close to the set point (within an adjustable deadband) and moving towards the set point. Ramp Loading — Ramp loading (ConfigurationSLCTCRMP) limits the rate of change of leaving fluid temperature. If the unit is in a Cooling mode and configured for Ramp Loading, the control makes 2 comparisons before deciding to change stages of capacity. The control calculates a temperature difference between the control point and leaving fluid temperature. If the difference is greater than 4° F (2.2° C) and the rate of change (°F or °C per minute) is more than the configured Cooling Ramp Loading value (CRMP), the control does not allow any changes to the current stage of capacity. Low Entering Fluid Temperature Unloading — When the entering fluid temperature is below the control point, the control will attempt to remove 25% of the current stages being used. If exactly 25% cannot be removed, the control removes an amount greater than 25% but no more than necessary. The lowest stage will not be removed. Minimum Load Control — If equipped, the minimum load control valve is energized only when one compressor is running on circuit A. If the close control feature is enabled the minimum load control valve may be used as needed to obtain leaving fluid temperature close to set point. LEAD/LAG DETERMINATION — This is a configurable choice and is factory set to be automatic for all units unless the unit is equipped with a digital scroll compressor or minimum load, then circuit A is lead (ConfigurationOPT2 LLCS). The value can be changed to Circuit A or Circuit B leading as desired. Set at automatic, the control will sum the current number of logged circuit starts and one-quarter of the current operating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are also made when total machine capacity is at 100% or when there is a change in the direction of capacity (increase or decrease) and each circuit’s capacity is equal. CAPACITY CONTROL OVERRIDES — The following overrides will modify the normal operation of the routine. Deadband Multiplier — The user configurable Deadband Multiplier (ConfigurationSLCTZ.GN) has a default value of 1.0. The range is from 1.0 to 4.0. When set to other than 1.0, this factor is applied to the capacity Load/Unload Factor. The larger this value is set, the longer the control will delay between adding or removing stages of capacity. Figure 13 shows how compressor starts can be reduced over time if the leaving water temperature is allowed to drift a larger amount above and below the set point. This value should be set in the range of 3.0 to 4.0 for systems with small loop volumes. First Stage Override — If the current capacity stage is zero, the control will modify the routine with a 1.2 factor on adding the first stage to reduce cycling. This factor is also applied 30 Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve CONTROL STEPS 30RAP UNIT SIZE 010 015 1 1 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 018 020 025 030 035 040 045 050 055 060 CAPACITY STEPS % Displacement 100 100 100 50 20* 100 50 24* 100 50 29* 100 50 32* 100 77 50 23 9* 100 73 50 23 11* 100 74 50 24 12* 100 75 50 25 14* 100 73 50 23 13* 100 75 50 25 16* *Minimum Load Valve energized. CAPACITY % Circuit A 100 100 Circuit B — — 100 — 100 — 100 — 100 — 54 46 47 53 47 53 50 50 46 54 50 50 NOTE: These capacity steps may vary due to different capacity staging sequences. 2 STARTS DEADBAND EXAMPLE 47 7 6 46 45 LWT (F) LWT (C) 8 44 43 42 5 41 0 200 400 600 TIME (SECONDS) LEGEND LWT — Leaving Water Temperature 800 1000 3 STARTS STANDARD DEADBAND MODIFIED DEADBAND Fig. 13 — Deadband Multiplier 31 be added to the current fan stage. Fan On Set Point (F.ON) equals Head Set Point (Set PointsHEADH.DP) except after a fan stage increase when the Head Set Point is increased by Fan Stage Delta (Set PointsHEADF.DLT). A fan stage is decreased when the SCTs of both circuits are less than the Fan Off Set Point (Set PointsHEAD F.OFF) for two minutes. Table 20 shows the number of fan stages, contactors energized and the fans that are on during the fan stage. Unit sizes 035 to 060 have common fan control. Figure 14 shows the location of each fan and compressor within the unit. MOTORMASTER® V OPTION — Motormaster V is standard on 30RAP010 and 015 size units. For all other units that need low-ambient operation, the lead fan on a circuit can be equipped with the Motormaster V head pressure controller option or accessory. The controller is energized with the first fan stage and adjusts fan speed to maintain a SCT of 72 F (22.2 C). The first stage of fan operation is controlled by the Motormaster V controller. Refer to Fig. 15 for condenser fan layout information. The Motormaster is configured in the Motormaster Select (ConfigurationMMMMR.S) Cooler Freeze Protection — The control will try to prevent shutting the chiller down on a Cooler Freeze Protection alarm by removing stages of capacity. If the cooler fluid selected is Water, the freeze point is 34 F (1.1 C). If the cooler fluid selected is Brine, the freeze point is the Brine Freeze Point (Set PointsFRZBR.FZ). This alarm condition (A207) only references leaving fluid temperature and NOT Brine Freeze point. If the cooler leaving fluid temperature is less than the freeze point plus 2.0° F (1.1° C), the control will immediately remove one stage of capacity. This can be repeated once every 30 seconds. Low Saturated Suction Protection — The control will try to prevent shutting a circuit down due to low saturated suction conditions by removing stages of capacity. These circuit alert conditions (T116, T117) compare saturated suction temperature to the configured Brine Freeze Point (Set PointsFRZBR.FZ). The Brine Freeze point is a userconfigurable value that must be left at 34 F (1.1 C) for 100% water systems. A lower value may be entered for systems with brine solutions, but this value should be set according to the freeze protection level of the brine mixture. Failure to properly set this brine freeze point value may permanently damage the brazed plate heat exchanger. The control will initiate Mode 7 (Circuit A) or Mode 8 (Circuit B) to indicate a circuit’s capacity is limited and that eventually the circuit may shut down. Operation of Machine Based on Control Method and Cooling Set Point Selection Settings — Machine On/Off control is determined by the configuration of the Control Method (ConfigurationOPT2CTRL) and Cooling Set Point Select (ConfigurationSLCTCLSP) variables. All units are factory configured with Cooling Set Point Select set to 0 (single set point). With the control method set to 0, simply switching the Enable/Off/Remote Contact switch to the Enable or Remote Contact position (external contacts closed) will put the chiller in an occupied state. The control mode (Operating ModesMODE) will be 1 (OFF LOCAL) when the switch is Off and will be 5 (ON LOCAL) when in the Enable position or Remote Contact position with external contacts closed. Head Pressure Control — The main base board (MBB) controls the condenser fans to maintain the lowest condensing temperature possible, and thus the highest unit efficiency. The MBB uses the saturated condensing temperature input from the discharge pressure transducer and outside air temperature sensor to control the fans. If OAT is greater than 70 F before a circuit is starting, then all condenser fan stages will be energized. A fan stage is increased based on SCT (saturated condensing temperature). When the highest SCT is greater than the Fan On Set Point (Set PointsHEADF.ON), then an additional stage of fan will 170 160 150 140 130 120 110 SCT (F) 100 90 80 70 60 50 40 30 -30 -20 -10 0 10 20 30 40 50 60 70 80 SST (F) LEGEND SCT SST a30-4969 — Saturated Condensing Temperature — Saturated Suction Temperature Fig. 14 — Operating Envelope for R-410A Compressor 32 OFM1 CONTROL BOX CONTROL BOX a30-4970 OFM1 Top View Sizes 018-030 OFM1 CONTROL BOX CONTROL BOX Top View Sizes 010,015 OFM2 OFM3 OFM2 Top View Sizes 035-050 OFM1 OFM3 OFM2 OFM4 Top View Sizes 055,060 Fig. 15 — 30RAP Condenser Fan Layout Table 20 — Fan Stages 30RAP UNIT SIZE 010,015 018-030 035-050 055,060 FAN STAGES Contactor Energized — FC1 FC1,2 FC1 FC2 FC1,2 FC3 FC1,3 FC3,2 FC1,2,3 Fan Stage Stage 1 Stage 1 Stage 2 Stage 1 Stage 2 Stage 3 Stage 1 Stage 2 Stage 3 Stage 4 Fans Operating OFM1 OFM1 OFM1,2 OFM3 OFM1,2 OFM1,2,3 OFM4 OFM4,3 OFM4,1,2 OFM1,2,3,4 the CHIL_S_S variable is ‘Stop.’ Similarly, the control mode will be 6 when the CHIL_S_S variable is ‘Start.’ Table 20 illustrates how the control method and cooling set point select variables direct the operation of the chiller and the set point to which it controls. The illustration also shows the ON/OFF state of the machine for the given combinations. Two other control methods are available for Machine On/ Off control: OCCUPANCY SCHEDULE (ConfigurationOPT2 CTRL = 2) — The main base board will use the operating schedules as defined under the Time Clock mode in the scrolling marquee display. These schedules are identical. The schedule number must be set to 1 for local schedule. The schedule number can be set anywhere from 65 to 99 for operation under a CCN global schedule. The Enable/Off/ Remote Contact must be in the Enable or Remote Contact position. The control mode (Operating ModesMODE) will be 1 when the switch is Off. The control mode will be 3 when the Enable/Off/Remote Contact switch input is On and the time of day is during an unoccupied period. Similarly, the control mode will be 7 when the time of day is during an occupied period. CCN CONTROL (ConfigurationOPT2CTRL = 3) — An external CCN device such as Chillervisor System Manager controls the On/Off state of the machine. This CCN device forces the variable ‘CHIL_S_S’ between Start/Stop to control the chiller. The control mode (Operating ModesMODE) will be 1 when the switch is Off. The control mode will be 2 when the Enable/Off/Remote Contact switch input is On and Cooling Set Point Select SINGLE — Unit operation is based on Cooling Set Point 1 (Set PointsCOOLCSP.1). DUAL SWITCH — Unit operation is based on Cooling Set Point 1 (Set PointsCOOLCSP.1) when the Dual Set Point switch contacts are open and Cooling Set Point 2 (Set PointsCOOLCSP.2) when they are closed. DUAL CCN OCCUPIED — Unit operation is based on Cooling Set Point 1 (Set PointsCOOLCSP.1) during the Occupied mode and Cooling Set Point 2 (Set PointsCOOLCSP.2) during the Unoccupied mode as configured under the local occupancy schedule accessible only from CCN. Schedule Number in Table SCHEDOVR (See Appendix B) must be configured to 1. If the Schedule Number is set to 0, the unit will operate in a continuous 24-hr Occupied mode. Control method must be configured to 0 (switch). See Table 21. 33 Table 21 — Control Methods and Cooling Set Points CONTROL TYPE (CTRL) 0 (switch) 2 (Occupancy) 3 (CCN) OCCUPANCY STATE Occupied Unoccupied Occupied Unoccupied Occupied Unoccupied 0 (single) ON,CSP1 ON,CSP1 ON,CSP1 OFF ON,CSP1 ON,CSP1 COOLING SET POINT SELECT (CLSP) 1 2 (dual, switch) (dual, occ) ON* ON,CSP1 ON* ON,CSP2 ON* Illegal OFF Illegal ON* ON,CSP1 ON* ON,CSP2 3 (4 to 20 mA) ON† ON ON† OFF ON† ON† *Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed. †Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5. under the COMP mode will stay on for 10 minutes if there is no keypad activity. Compressors will stay on until they are turned off by the operator. The Service Test mode will remain enabled for as long as there is one or more compressors running. All safeties are monitored during this test and will turn a compressor, circuit or the machine off if required. Any other mode or sub-mode can be accessed, viewed, or changed during the TEST mode. The MODE item (Run StatusVIEW) will display “0” as long as the Service mode is enabled. The TEST sub-mode value must be changed back to OFF before the chiller can be switched to Enable or Remote contact for normal operation. 4 TO 20 mA INPUT — Unit operation is based on an external 4 to 20 mA signal input to the Energy Management Module (EMM). Low Sound Mode Operation — All models are factory configured with the Low Sound Mode disabled. In the Configuration mode under sub-mode OPT2, items for Low Sound Mode Select (ConfigurationOPT2LS.MD), Low Sound Start Time (ConfigurationOPT2LS.ST), Low Sound End Time (ConfigurationOPT2LS.ND) and Low Sound Capacity Limit (ConfigurationOPT2LS.LT) are factory configured so that the chiller always runs as quietly as possible. This results in operation at increased saturated condensing temperature. As a result, some models may not be able to achieve rated efficiency. For chiller operation at rated efficiency, disable the low sound mode or adjust the low sound mode start and stop times accordingly or set both times to 00:00 for rated efficiency operation 24 hours per day. In addition, the low sound capacity limit can be used to reduce overall chiller capacity, if required, by limiting the maximum to a userconfigured percentage. Optional Factory-Installed Hydronic Package — If the chiller has factory-installed chilled fluid pumps, specific steps should be followed for proper operation. The pump(s) in the hydronic package come factory pre-wired into the main unit power supply/starter. In order to check proper pump rotation, use the Service Test function to test the condenser fans and observe them for proper rotation. If fans turn correctly, the pumps will rotate correctly. Clockwise rotation of the pump motor cooling fans can also be used to determine that pumps are rotating correctly. Heating Operation — The chiller can be used for pump outputs or optional factory-installed hydronic system operation can be utilized for heating applications. The heating mode is activated when the control sees a field-supplied closed switch input to terminal block LVT-19,20. The control locks out cooling when the heat relay input is seen. A field-supplied boiler relay connection is made using heat relay and alarm relay contacts. Factory-installed ‘BOILER’ connections exist in the control panel near LVT for these applications. Alarms and alerts A189 through A202 are active during heating operation. CAUTION Operation of pump in wrong direction, even for a few seconds, can cause irreversible damage to pump impeller and housing. Always verify correct wiring/pump rotation before operation. Use Service Test function to test operation of pumps. Verify that the flow switch input is made when the pump is running. For dual pump hydronic systems, the control only uses one pump at a time. Consult the Installation Instructions supplied with this chiller and use the circuit setter balancing valve installed in hydronic package to adjust fluid flow rate. Cooler Pump Control — The AquaSnap® 30RAP machines equipped with a factory-installed pump package are configured with the Cooler Pump Control (ConfigurationOPT1CPC) = ON. Machines not equipped with a pump package are configured with the cooler pump control OFF. It is recommended that the machine control the chilled water pump. If not, a 5-minute time delay is required after the command to shut the machine down is sent before the chilled water pump is turned off. This is required to maintain water flow during the shutdown period of the machine. With or without this option enabled, the cooler pump relay will be energized when the machine enters an ON status (i.e., On Local, On CCN, On Time). An A207 - Cooler Freeze Protection Alarm, will energize the cooler pump relay also, as an override. The cooler pump relay will remain energized if the machine is in MODE 10 – Minimum Off Time. Service Test (See Table 4) — Both main power and control circuit power must be on. The Service Test function should be used to verify proper operation of condenser fan(s), compressors, minimum load valve solenoid (if installed), cooler pump(s), EXVs, and remote alarm relay. To use the Service Test mode, the Enable/ Off/Remote Contact switch must be in the OFF position. Use the display keys and Table 4 to enter the mode and display TEST. Press ENTER twice so that OFF flashes. Enter the password if required. Use either arrow key to change the TEST value to the ON position and press ENTER . Press ESCAPE and the button to enter the OUTS or COMP sub-mode. Test the condenser fans, cooler pump(s) and alarm relay by changing the item values from OFF to ON. These discrete outputs are then turned off if there is no keypad activity for 10 minutes. Use the arrow keys to select the desired percentage when testing expansion valves and Motormaster® V controller. When testing compressors, lead compressor must be started first. All compressor outputs can be turned on, but the control will limit the rate by staging one compressor per minute. Compressor unloaders and hot gas bypass relays/solenoids (if installed) can be tested with the compressors on or off. The relays 34 interlock contacts should be rated for dry circuit application capable of handling 5 vdc at 2 mA. SINGLE INTEGRAL PUMP CONTROL — With a single pump, the following options must be configured: • Cooler Pump Control (ConfigurationOPT1CPC) = ON. • Cooler Pump 1 Enable (ConfigurationOPT1 PM1E) = YES. • Cooler Pump 2 Enable (ConfigurationOPT1 PM2E) = NO. With a single integral pump, the Cooler Pump Starter will be energized when the machine is occupied. As part of the factory-installed package, an auxiliary set of contacts is wired to the MBB to serve as Chilled Water Pump Interlock. When the mechanical cooling is called for, the pump interlock and flow switch is checked. If the circuits are closed, the machine starts its capacity routine. If the auxiliary contact interlock does not close within 25 seconds of the ON command, a T190 — Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Alert will be generated and the pump shut down. The unit will not be allowed to start. If the chilled water flow switch does not close within one (1) minute, two alarms will be generated. A T192 — Cooler Pump 1 Failed to Provide Flow at Start-Up Alert and an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start. If the chilled water flow switch opens for at least 3 seconds after initially being closed, a T196 — Flow Lost While Pump 1 Running Alert and an A201 — Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm will be generated and the machine will stop. If the control detects the chilled water pump interlock open for 25 seconds after initially being closed, a T194 — Cooler a30-4979 Pump 1 Contacts Opened During Normal Operation Alert is generated and the unit is shut down. If the control detects the chilled water flow switch circuit closed for at least 5 minutes with the pump output OFF, an A202 — Cooler Pump Interlock Closed When Pump is Off Alarm will be generated and the unit will not be allowed to start. If the control detects that the chilled water pump auxiliary contacts are closed for at least 25 seconds while the pump is OFF, a T198 — Cooler Pump 1 Aux Contacts Closed While Pump Off Alert is generated. The chiller will not be allowed to start. If the control starts a pump and the wrong interlock circuit closes for at least 20 seconds, an A189 — Cooler Pump and Aux Contact Input Miswire Alarm will be generated. The unit will be prevented from starting. As part of a pump maintenance routine, the pump can be started to maintain lubrication of the pump seal. To utilize this function, Cooler Pmp Periodic Start (ConfigurationOPT1 PM.P.S) must be set to YES. This option is set to NO as the factory default. With this feature enabled, if the pump is not operating, it will be started and operated for 2 seconds starting at 14:00 hours. If the pump is operating, this routine is skipped. If the pump has failed and an Alarm/Alert condition is active, the pump will not start that day. DUAL INTEGRAL PUMP CONTROL — With a dual integral pump package, the following options must be configured: • Cooler Pump Control (ConfigurationOPT1CPC) = ON. • Cooler Pump 1 Enable (ConfigurationOPT1 PM1E) = YES. • Cooler Pump 2 Enable (ConfigurationOPT1 PM2E) = YES. Pump Start Selection is a field-configurable choice. Cooler Pump Select (ConfigurationOPT1PM.SL) is factory defaulted to 0 (Automatic). This value can be changed to 1 Cooler Pump Sequence of Operation — At anytime the unit is in an ON status, as defined by the one of the following conditions, the cooler pump relay will be enabled. 1. The Enable-Off-Remote Switch in ENABLE, (CTRL=0). 2. Enable-Off-Remote Switch in REMOTE with a Start-Stop remote contact closure (CTRL=0). 3. An Occupied Time Period from an Occupancy Schedule in combination with items 1 or 2 (CTRL=2). 4. A CCN Start-Stop Command to Start in combination with items 1 or 2 (CTRL=3). As stated before, there are certain alarm conditions and Operating Modes that will turn the cooler pump relay ON. This sequence will describe the normal operation of the pump control algorithm. When the unit cycles from an “On” state to an “Off” state, the cooler pump output will remain energized for the Cooler Pump Shutdown Delay (ConfigurationOPT1PM.DY). This is configurable from 0 to 10 minutes. The factory default is 1 minute. NO INTEGRAL PUMP — SINGLE EXTERNAL PUMP CONTROL — With a single external pump, the following options must be configured: • Cooler Pump Control (ConfigurationOPT1CPC) = OFF. • Cooler Pump 1 Enable (ConfigurationOPT1 PM1E) = NO. • Cooler Pump 2 Enable (ConfigurationOPT1 PM2E) = NO. The maximum load allowed for the Chilled Water Pump Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil is powered from the chiller control system. The starter should be wired between LVT-25 and LVT-21. If equipped, the fieldinstalled chilled water pump starter auxiliary contacts should be connected in series with the chilled water flow switch. The Cooler Pump Relay will be energized when the machine is “On.” The chilled water pump interlock circuit consists of a chilled water flow switch and a field-installed chilled water pump interlock. If the chilled water pump interlock circuit does not close within five (5) minutes of starting, an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start. If the chilled water pump interlock or chilled water flow switch opens for at least three (3) seconds after initially being closed, an A201 — Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm will be generated and the machine will stop. NO INTEGRAL PUMP — DUAL EXTERNAL PUMP CONTROL — With two external pumps, the following options must be configured: • Cooler Pump Control (ConfigurationOPT1CPC) = ON. • Cooler Pump 1 Enable (ConfigurationOPT1 PM1E) = YES. • Cooler Pump 2 Enable (ConfigurationOPT1 PM2E) = YES. The maximum load allowed for the Chilled Water Pump Starters is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil is powered from the chiller control system. The starter for Chilled Water Pump 1 should be wired between LVT-25 and LVT-21. The starter for Chilled Water Pump 2 should be wired between LVT-24 and LVT-21. A field-installed chilled water pump interlock for each pump must be connected to each pump’s interlock points on the main base board. The chilled water pump 1 interlock, CWP1, must be connected to MBBJ7-1 and –2. The chilled water pump 2 interlock, CWP2, must be connected to MBB-J7-3 and –4. The chilled water pump 35 If the control starts a pump and the wrong interlock circuit closes for at least 20 seconds, an A189 – Cooler Pump and Aux Contact Input Miswire Alarm will be generated. The unit will be prevented from starting. The control will allow for pump changeover. Two methods will change the pump sequence. Before the changeover can occur, the unit must be at Capacity Stage 0. During changeover the chilled water flow switch input is ignored for 10 seconds to avoid a nuisance alarm. With Cooler Pump Select (ConfigurationOPT1 PM.SL) set to 0 (Automatic) and when the differential time limit Pump Changeover Hours (ConfigurationOPT1 PM.DT) is reached, the lead pump will be turned OFF. Approximately one (1) second later, the lag pump will start. Manual changeover can be accomplished by changing Rotate Cooler Pump Now (ConfigurationOPT1ROT.P) to YES only if the machine is at Capacity Stage 0 and the differential time limit Pump Changeover Hours (PM.DT) is reached. If the PM.DT is not satisfied, the changeover will not occur. With the machine at Capacity Stage 0, the pumps would rotate automatically as part of the normal routine. With Cooler Pump Select (PM.SL) set to 1 (Pump 1 Starts First) or 2 (Pump 2 Starts First), a manual changeover can be accomplished by changing PM.SL only. The machine RemoteOff-Enable Switch must be in the OFF position to change this variable. The Rotate Cooler Pump Now (ROT.P) feature does not work for these configuration options. As part of a pump maintenance routine, the pumps can be started to maintain lubrication to the pump seal. To utilize this function, Cooler Pmp Periodic Start (ConfigurationOPT1 PM.PS) must be set to YES. This option is set to NO as the factory default. If feature is enabled and the pump(s) are not operating, then the pumps will be operated every other day for 2 seconds starting at 14:00 hours. If a pump has failed and has an active Alert condition, it will not be started that day. (Pump 1 Starts First) or 2 (Pump 2 Starts First). If PM.SL is 0 (Automatic), the pump selection is based on two criteria: the alert status of a pump and the operational hours on the pump. If a pump has an active Alert condition, it will not be considered for the lead pump. The pump with the lowest operational hours will be the lead pump. A pump is selected by the control to start and continues to be the lead pump until the Pump Changeover Hours (ConfigurationOPT1PM.DT) is reached. The Lead Pump (Run StatusVIEWLD.PM) indicates the pump that has been selected as the lead pump: 1 (Pump 1), 2 (Pump 2), 3 (No Pump). The Pump Changeover Hours is factory defaulted to 500 hours. Regardless of the Cooler Pump Selection, any pump that has an active alert will not be allowed to start. With the dual integral pump package, the Cooler Pump Starter will be energized when the machine is in an occupied period. As part of the factory-installed package, an auxiliary set of contacts is wired to the MBB to serve as Chilled Water Pump Interlock, one set for each pump to individual channels on the MBB. With a call for mechanical cooling, the specific pump interlock and flow switch are checked. If the circuits are closed, the machine starts its capacity routine. If Pump 1 starts and the auxiliary contact interlock does not close within 25 seconds of the ON command, a T190 — Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Alert will be generated and the pump shut down. The unit will not be allowed to start. If the chilled water flow switch does not close within 1 minute, two alarms will be generated. A T192 — Cooler Pump 1 Failed to Provide Flow at Start-Up Alert and an A200 — Cooler Flow/ Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start. In either fault case listed above, Pump 2 will be commanded to start once Pump 1 has failed. If Pump 2 starts and the auxiliary contact interlock does not close within 25 seconds of the ON command, a T191 — Cooler Pump 2 Aux Contacts Failed to Close at Start-Up Alert will be generated and the pump shut down. The unit will not be allowed to start. If the chilled water flow switch does not close within one (1) minute, two alarms will be generated. A T193 — Cooler Pump 2 Failed to Provide Flow at Start-Up Alert and an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start. In either fault case listed above, Pump 1 will be commanded to start once Pump 2 has failed. If the chilled water flow switch opens for at least 3 seconds after initially being closed, a T196 — Flow Lost While Pump 1 Running Alert or T197 — Flow Lost While Pump 2 Running Alert for the appropriate pump and an A201 — Cooler Flow/ Interlock Contacts Opened During Normal Operation Alarm will be generated and the machine will stop. If available, the other pump will be started. If flow is proven, the machine will be allowed to restart. If the chilled water pump interlock opens for 25 seconds after initially being closed is detected by the control, the appropriate T194 — Cooler Pump 1 Contacts Opened During Normal Operation Alert or T195 — Cooler Pump 2 Contacts Opened During Normal Operation Alert is generated and the unit is shut down. If available, the other pump will be started. If flow is proven, the machine will be allowed to restart. If the control detects that the chilled water flow switch circuit is closed for at least 5 minutes with the pump output OFF, an A202 — Cooler Pump Interlock Closed When Pump is Off Alarm will be generated and the unit will not be allowed to start. If the control detects that the chilled water pump auxiliary contacts are closed for at least 25 seconds while the pump is OFF, the appropriate T198 — Cooler Pump 1 Aux Contacts Closed While Pump Off or Alert T199 — Cooler Pump 2 Aux Contacts Closed While Pump Off Alert is generated. The chiller will not be allowed to start. Configuring and Operating Dual Chiller Control — The dual chiller routine is available for the control of two units supplying chilled fluid on a common loop. This control algorithm is designed for parallel fluid flow arrangement only. One chiller must be configured as the master chiller, the other as the slave. An additional leaving fluid temperature thermistor (Dual Chiller LWT) must be installed as shown in Fig. 16 and 17 and connected to the master chiller. Refer to Sensors section, page 20, for wiring. The CCN communication bus must be connected between the two chillers. Connections can be made to the CCN screw terminals on LVT. Refer to Carrier Comfort Network® Interface section, page 19, for wiring information. Configuration examples are shown in Tables 22 and 23. Refer to Table 22 for dual chiller configuration. In this example the master chiller will be configured at address 1 and the slave chiller at address 2. The master and slave chillers must reside on the same CCN bus (ConfigurationCCN CCNB) but cannot have the same CCN address (ConfigurationCCNCCNA). Both master and slave chillers must have Lead/Lag Chiller Enable (ConfigurationRSET LLEN) configured to ENBL. Master/Slave Select (ConfigurationRSET MSSL) must be configured to MAST for the master chiller and SLVE for the slave. Also in this example, the master chiller will be configured to use Lead/Lag Balance Select (ConfigurationRSETLLBL) and Lead/Lag Balance Delta (ConfigurationRSETLLBD) to even out the chiller run-times weekly. The Lag Start Delay (ConfigurationRSETLLDY) feature will be set to 10 minutes. This will prevent the lag chiller from starting until the lead chiller has been at 100% capacity for the length of the delay time. Parallel configuration (ConfigurationRSETPARA) can only be configured to YES. The variables LLBL, LLBD and LLDY are not used by the slave chiller. 36 Table 22 — Dual Chiller Configuration (Master Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS ENTER CTRL CONTROL METHOD ENTER 0 SWITCH DEFAULT 0 ESCAPE OPT2 CCN ADDRESS DEFAULT 1 CCN BUS NUMBER DEFAULT 0 DISP UNIT OPT1 OPT2 CTRL CCN CCNA ENTER 1 CCNB CCN CCNB ENTER 0 ESCAPE CCN PROCEED TO SUBMODE RESET RSET ENTER LLEN LLEN MSSL CRST COOLING RESET TYPE LLEN LEAD/LAG CHILLER ENABLE 15 ITEMS ENTER DSBL SCROLLING STOPS ENTER DSBL VALUE FLASHES ENBL SELECT ENBL ENTER ENBL ESCAPE LLEN LEAD/LAG CHILLER ENABLE MSSL MASTER /SLAVE SELECT ENTER MAST MASTER /SLAVE SELECT ESCAPE MSSL CHANGE ACCEPTED DEFAULT MAST RSET SLVA SLVA SLVA SLAVE ADDRESS ENTER 0 SCROLLING STOPS ENTER 0 VALUE FLASHES 2 SELECT 2 ENTER 2 ESCAPE SLVA SLAVE ADDRESS LLBL LLBL CHANGE ACCEPTED LEAD/LAG BALANCE SELECT ENTER 0 SCROLLING STOPS ENTER 0 VALUE FLASHES 2 SELECT 2 - Automatic 37 Table 22 — Dual Chiller Configuration (Master Chiller Example) (cont) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS LLBL ENTER 2 LEAD/LAG BALANCE SELECT CHANGE ACCEPTED ESCAPE LLBL LLBD LLBD LEAD/LAG BALANCE DELTA ENTER 168 LEAD/LAG BALANCE DELTA ESCAPE LLBD LLDY RSET LLDY LLDY PARA DEFAULT 168 LAG START DELAY ENTER 5 SCROLLING STOPS ENTER 5 VALUE FLASHES 10 SELECT 10 ENTER 10 ESCAPE LLDY ESCAPE RSET ENTER YES LAG START DELAY CHANGE ACCEPTED MASTER COMPLETE NOTES: 1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-CCN. 2. Parallel Configuration (PARA) cannot be changed. Dual chiller start/stop control is determined by configuration of Control Method (ConfigurationOPT1CTRL) of the Master chiller. The Slave chiller should always be configured for CTRL=0 (Switch). If the chillers are to be controlled by Remote Contacts, both Master and Slave chillers should be enabled together. Two separate relays or one relay with two sets of contacts may control the chillers. The Enable/Off/ Remote Contact switch should be in the Remote Contact position on both the Master and Slave chillers. The Enable/Off/ Remote Contact switch should be in the Enable position for CTRL=2 (Occupancy) or CTRL=3 (CCN Control). Both chillers will stop if the Master chiller Enable/Off/ Remote Contact switch is in the Off position. If the Emergency Stop switch is turned off or an alarm is generated on the Master chiller the Slave chiller will operate in a Stand-Alone mode. If the Emergency Stop switch is turned off or an alarm is generated on the Slave chiller the Master chiller will operate in a Stand-Alone mode. The master chiller controls the slave chiller by changing its Control Mode (Run StatusVIEWSTAT) and its operating setpoint or Control Point (Run StatusVIEWCT.PT). RETURN FLUID MASTER CHILLER SLAVE CHILLER DIMENSIONS in. (mm) A B 3.10 (78.7) 1.55 (39.4) 4.10 (104.1) 1.28 (32.5) PART NUMBER 10HB50106801 10HB50106802 A 0.505/0.495 0.61 DIA B 1/4 N.P.T. 6” MINIMUM CLEARANCE FOR THERMISTOR REMOVAL Fig. 17 — Dual Leaving Water Thermistor Well Temperature Reset — The control system is capable of handling leaving-fluid temperature reset based on return cooler fluid temperature. Because the change in temperature through the cooler is a measure of the building load, the return temperature reset is in effect an average building load reset method. The control system is also capable of temperature reset based on outdoor-air temperature (OAT), space temperature (SPT), or from an externally powered 4 to 20 mA signal. Accessory sensors must be used for SPT reset (33ZCT55SPT). The energy management module (EMM) must be used for temperature reset using a 4 to 20 mA signal. See Tables 24 and 25. THERMISTOR WIRING* LEAVING FLUID INSTALL DUAL CHILLER LWT LEAVING FLUID TEMPERATURE THERMISTOR (T10) HERE *Depending on piping sizes, use either: • HH79NZ014 sensor/10HB50106801 well (3-in. sensor/well) • HH79NZ029 sensor/10HB50106802 well (4-in. sensor/well) Fig. 16 — Dual Chiller Thermistor Location 38 Table 23 — Dual Chiller Configuration (Slave Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS ENTER CTRL CONTROL METHOD 0 SWITCH DEFAULT 0 CCN ADDRESS SCROLLING STOPS DISP UNIT OPT1 OPT2 CTRL ESCAPE OPT2 CCN CCNA CCNA ENTER 1 ENTER 1 VALUE FLASHES 2 SELECT 2 (SEE NOTE 1) CCN CCNA CCNB ENTER 2 ESCAPE CCN ENTER 0 ESCAPE CCN CCN ADDRESS CHANGE ACCEPTED CCN BUS NUMBER DEFAULT 0 (SEE NOTE 2) PROCEED TO SUBMODE RSET RSET ENTER LLEN LLEN CRST COOLING RESET TYPE LLEN LEAD/LAG CHILLER ENABLE 15 ITEMS ENTER DSBL SCROLLING STOPS ENTER DSBL VALUE FLASHES ENBL SELECT ENBL ENTER ENBL ESCAPE LLEN LEAD/LAG CHILLER ENABLE CHANGE ACCEPTED RSET MSSL MSSL MSSL MASTER /SLAVE SELECT ENTER MAST SCROLLING STOPS ENTER MAST VALUE FLASHES SLVE SELECT SLVE ENTER SLVE ESCAPE MSSL ESCAPE RSET MASTER /SLAVE SELECT CHANGE ACCEPTED SLAVE COMPLETE NOTES: 1. Slave Control Method (CTRL) must be configured for 0. 2. Slave CCN Address (CCNA) must be different than Master. 3. Slave CCN Bus Number (CCNB) must be the same as Master 4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured. 39 Table 24 — 4 to 20 mA Reset SUB-MODE DISPLAY ITEM EXPANSION CRST 1 COOLING RESET TYPE MA.DG 5.0 F (2.8 C) DEGREES COOL RESET KEYPAD ENTRY ITEM ENTER RSET COMMENT 0 = no reset 1 = 4 to 20 mA input 2 = Outdoor air temp 3 = Return Fluid 4 = Space Temperature Default: 0° F (0° C) Reset at 20 mA Range: –30 to 30 F (–16.7 to 16.7 C) NOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required. Table 25 — Menu Configuration of 4 to 20 mA Cooling Set Point Control MODE (RED LED) KEYPAD SUB-MODE KEYPAD ENTRY ENTRY ENTER ITEM DISPLAY ITEM EXPANSION CLSP 0 COOLING SETPOINT SELECT COMMENT DISP UNIT OPT1 OPT2 HP.A HP.B EXV.A EXV.B CONFIGURATION M.MST RSET DMDC SLCT ENTER ENTER 0 Scrolling Stops ENTER 0 Flashing ‘0’ 4 Select ‘4’ 4 Change Accepted ENTER be configured for the type of reset desired. The variable RM.NO should be set to the temperature that no reset should occur. The variable RM.F should be set to the temperature that maximum reset is to occur. The variable RM.DG should be set to the maximum amount of reset desired. Figures 18 and 19 are examples of outdoor air and space temperature resets. To use return reset, four variables must be configured. In the Configuration mode under the sub-mode RSET, items CRST, RT.NO, RT.F and RT.DG must be properly set. See Table 26B — Configuring Return Temperature Reset. This example provides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C) cooler T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler T. The variable RT.NO should be set to the cooler temperature difference (T) where no chilled water temperature reset should occur. The variable RT.F should be set to the cooler temperature difference where the maximum chilled water temperature reset should occur. The variable RM.DG should be set to the maximum amount of reset desired. To verify that reset is functioning correctly proceed to Run Status mode, sub-mode VIEW, and subtract the active set point (Run StatusVIEWSETP) from the control point (Run StatusVIEWCTPT) to determine the degrees reset. IMPORTANT: Care should be taken when interfacing with other control systems due to possible power supply differences: full wave bridge versus half wave rectification. Connection of control devices with different power supplies may result in permanent damage. ComfortLink™ controls incorporate power supplies with half wave rectification. A signal isolation device should be utilized if the signal generator incorporates a full wave bridge rectifier. To use outdoor air or space temperature reset, four variables must be configured. In the Configuration mode under the submode RSET, items (ConfigurationOPT1CRST), (ConfigurationOPT1RM.NO), (ConfigurationOPT1 RM.F), and (ConfigurationOPT1RT.DG) must be properly set. See Table 26A — Configuring Outdoor Air and Space Temperature Reset. The outdoor air reset example provides 0° F (0° C) chilled water set point reset at 85.0 F (29.4 C) outdoor-air temperature and 15.0 F (8.3 C) reset at 55.0 F (12.8 C) outdoor-air temperature. The space temperature reset example provides 0° F (0° C) chilled water set point reset at 72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) reset at 68.0 F (20.0 C) space temperature. The variable CRST should 40 Table 26A — Configuring Outdoor Air and Space Temperature Reset MODE (RED LED) KEYPAD ENTRY SUBMODE ENTER DISP KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT 4 COOLING RESET TYPE 2 = Outdoor-Air Temperature 4 = Space Temperature (Connect to TB5-5,6) 85 °F 72 °F REMOTE - NO RESET TEMP Default: 125.0 F (51.7 C) Range: 0° to125 F RM.F 55 °F 68 °F REMOTE - FULL RESET TEMP Default: 0.0° F (-17.7 C) Range: 0° to 125 F RM.DG 15 °F 6 °F REMOTE - DEGREES RESET ITEM Outdoor Air Space CRST 2 RM.NO* UNIT OPT1 OPT2 HP.A HP.B EXV.A CONFIGURATION EXV.B M.MST RSET ENTER Default: 0° F (0° C) Range: –30 to 30 F (–34.4 to -1.1 °C) *4 items skipped in this example. Table 26B — Configuring Return Temperature Reset MODE (RED LED) KEYPAD KEYPAD SUB-MODE ENTRY ENTRY ITEM DISPLAY ITEM EXPANSION DISP ENTER TEST ON/OFF TEST DISPLAY LEDs UNIT ENTER TYPE X UNIT TYPE OPT1 ENTER FLUD X COOLER FLUID OPT2 ENTER CTRL X CONTROL METHOD ENTER COMMENT HP.A HP.B EXV.A CONFIGURATION EXV.B M.MST RSET ENTER 0 = No Reset 1 = 4 to 20 mA Input (EMM required) (Connect to EMM TB6-2,3) COOLING RESET TYPE 2 = Outdoor-Air Temperature 3 = Return Fluid 4 = Space Temperature (Connect to TB5-5,6) CRST 3 RT.NO* 10.0 F RETURN FLUID - NO RESET TEMP Default: 10.0 F (5.6 C) Range: 0° to10 F COOLER T RT.F 0.0 F RETURN FLUID - FULL RESET TEMP Default: 0 F (–17.8 C) Range: 0° to 30 F COOLER T RT.DG 10.0 F RETURN - DEGREES RESET *4 items skipped in this example. 41 Default: 0 F (0 C) Range: –30 to 30°F (–16.7 to 16.7 C) Under normal operation, the chiller will maintain a constant leaving fluid temperature approximately equal to the chilled fluid set point. As the cooler load varies, the entering cooler fluid will change in proportion to the load as shown in Fig. 20. Usually the chiller size and leaving-fluid temperature set point are selected based on a full-load condition. At part load, the fluid temperature set point may be colder than required. If the leaving fluid temperature was allowed to increase at part load, the efficiency of the machine would increase. Return temperature reset allows for the leaving temperature set point to be reset upward as a function of the return fluid temperature or, in effect, the building load. Demand Limit — Demand limit is a feature that allows the unit capacity to be limited during periods of peak energy usage. There are 3 types of demand limiting that can be configured. The first type is through 2-stage switch control, which will reduce the maximum capacity to 2 user-configurable percentages. The second type is by 4 to 20 mA signal input which will reduce the maximum capacity linearly between 100% at a 4 mA input signal (no reduction) down to the user-configurable level at a 20 mA input signal. The third type uses the CCN Loadshed module and has the ability to limit the current operating capacity to maximum and further reduce the capacity if required. NOTE: The 2-stage switch control and 4 to 20-mA input signal types of demand limiting require the energy management module (EMM). LEGEND EWT LWT — Entering Water (Fluid) Temperature — Leaving Water (Fluid) Temperature Fig. 20 — Standard Chilled Fluid Temperature Control — No Reset To use demand limit, select the type of demand limiting to use. Then configure the demand limit set points based on the type selected. DEMAND LIMIT (2-Stage Switch Controlled) — To configure demand limit for 2-stage switch control set the Demand Limit Select (ConfigurationRSETDMDC) to 1. Then configure the 2 Demand Limit Switch points (ConfigurationRSETDLS1) and (ConfigurationRSETDLS2) to the desired capacity limit. See Table 27. Capacity steps are controlled by 2 relay switch inputs field wired to TB6 as shown in Fig. 6 and 7. For demand limit by 2-stage switch control, closing the first stage demand limit contact will put the unit on the first demand limit level. The unit will not exceed the percentage of capacity entered as Demand Limit Switch 1 set point (DLS1). Closing contacts on the second demand limit switch prevents the unit from exceeding the capacity entered as Demand Limit Switch 2 set point. The demand limit stage that is set to the lowest demand takes priority if both demand limit inputs are closed. If the demand limit percentage does not match unit staging, the unit will limit capacity to the closest capacity stage. To disable demand limit configure DMDC to 0. See Table 27. EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA Controlled) — To configure demand limit for 4 to 20 mA control set the Demand Limit Select (ConfigurationRSETDMDC) to 2. Then configure the Demand Limit at 20 mA (ConfigurationRSETDM20) to the maximum loadshed value desired. Connect the output from an externally powered 4 to 20 mA signal to terminal block TB6, terminals 1 and 5. Refer to the unit wiring diagram for these connections to the optional/accessory energy management module and terminal block. The control will reduce allowable capacity to this level for the 20 mA signal. See Table 27 and Fig. 21. LEGEND LWT — Leaving Water (Fluid) Temperature Fig. 18 — Outdoor-Air Temperature Reset CAUTION Care should be taken when interfacing with other manufacturer’s control systems, due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used. LEGEND LWT — Leaving Water (Fluid) Temperature Fig. 19 — Space Temperature Reset 42 length of time that a loadshed condition is allowed to exist. The control will disable the Redline/Loadshed command if no Cancel command has been received within the configured maximum loadshed time limit. DEMAND LIMIT (CCN Loadshed Controlled) — To configure Demand Limit for CCN Loadshed control set the Demand Limit Select (ConfigurationRSETDMDC) to 3. Then configure the Loadshed Group Number (ConfigurationRSETSHNM), Loadshed Demand Delta (ConfigurationRSETSHDL), and Maximum Loadshed Time (ConfigurationRSETSHTM). See Table 27. The Loadshed Group number is established by the CCN system designer. The ComfortLink controls will respond to a Redline command from the Loadshed control. When the Redline command is received, the current stage of capacity is set to the maximum stages available. Should the loadshed control send a Loadshed command, the ComfortLink controls will reduce the current stages by the value entered for Loadshed Demand delta. The Maximum Loadshed Time is the maximum Cooling Set Point (4 to 20 mA) — A field supplied and generated, externally powered 4 to 20 mA signal can be used to provide the leaving fluid temperature set point. Connect the signal to LVT7,8 (+,–). See Table 27 for instructions to enable the function. Figure 22 shows how the 4 to 20 mA signal is linearly calculated on an overall 10 F to 80 F range for fluid types (ConfigurationOPT1FLUD) 1 or 2. The set point will be limited by the fluid (FLUD) type. Be sure that the chilled water loop is protected at the lowest temperature. MAX. ALLOWABLE LOAD (%) 100 50% CAPACITY AT 20 mA 80 60 40 100% CAPACITY AT 4 mA 75% CAPACITY AT 12 mA 20 0 0 2 4 6 12 8 10 14 DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT 16 18 20 Fig. 21 — 4 to 20-mA Demand Limiting 100 (38) 90 (32) 80 (27) SET POINT, F (C) 70 (21) MAXIMUM SET POINT 70 F (21.1 C) 60 (15) 50 (10) 40 (4.4) (FLUD = 1) MINIMUM SET POINT 38 F (3.3 C) 30 (-1) 20 (-7) (FLUD = 2) MINIMUM SET POINT 14 F (-10 C) 10 (-12) 0 (-17) 4 6.3 8.6 10.9 13.1 4 TO 20 mA SIGNAL TO EMM EMM — Energy Management Module Fig. 22 — Cooling Set Point (4 to 20 mA) 43 15.4 17.7 20 Table 27 — Configuring Demand Limit MODE CONFIGURATION KEYPAD ENTRY SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION ENTER DISP ENTER TEST ON/OFF Test Display LEDs UNIT ENTER TYPE X Unit Type OPT1 ENTER FLUD X Cooler Fluid OPT2 ENTER CTRL X Control Method ENTER CRST X Cooling Reset Type COMMENT HP.A HP.B EXV.A EXV.B M.MST RSET Default: 0 0 = None 1 = Switch 2 = 4 to 20 mA Input 3 = CCN Loadshed DMDC* X Demand Limit Select DM20 XXX % Demand Limit at 20 mA Default: 100% Range: 0 to 100 SHNM XXX Loadshed Group Number Default: 0 Range: 0 to 99 SHDL XXX% Loadshed Demand Delta Default: 0% Range: 0 to 60% SHTM XXX MIN Maximum Loadshed Time Default: 60 min. Range: 0 to 120 min. DLS1 XXX % Demand Limit Switch 1 Default: 80% Range: 0 to 100% DLS2 XXX % Demand Limit Switch 2 Default: 50% Range: 0 to 100% *Seven items skipped in this example. (DTT) is installed along with the AUX board for control of the DUS. DIGITAL COMPRESSOR CONFIGURATION — When a digital compressor is installed, the configuration parameter (ConfigurationUNITA1TY) is configured to YES. There is also a maximum unload time configuration, (ConfigurationUNITMAX.T) that is set to 7 seconds, which indicates the maximum unloading for the digital compressor is 47%. This is done to optimize efficiency of the system. Digital Scroll Option — The 30RAP units have a factory-installed option for a digital scroll compressor which provides additional stages of unloading for the unit. The digital compressor is always installed in the A1 compressor location. When a digital compressor is installed, a digital unloader solenoid (DUS) is used on the digital compressor. DIGITAL SCROLL OPERATION — A digital scroll operates in two stages - the "loaded state" when the solenoid valve is normally closed and the "unloaded state" when the solenoid valve is open. During the loaded state, the compressor operates like a standard scroll and delivers full capacity and mass flow. However, during the unloaded state, there is no capacity and no mass flow through the compressor. The capacity of the system is varied by varying the time the compressor operates in an unloaded and loaded state during a 15-second period. If the DUS is energized for 7 seconds, the compressor will be operating at 47% capacity. If the DUS is energized for 10 seconds, the compressor will be operating at approximately 33% of its capacity. Capacity is the time averaged summation of loaded and unloaded states, and its range is continuous from the minimum configured capacity to 100%. Regardless of capacity, the compressor always rotates with constant speed. As the compressor transitions from a loaded to unloaded state, the discharge and suction pressures will fluctuate and the compressor sound will change. The ComfortLink controller controls and integrates the operation of the DUS into the compressor staging routine to maintain temperature control. When a digital compressor is installed, an additional discharge gas temperature thermistor PRE-START-UP IMPORTANT: Before beginning Pre-Start-Up or Start-Up, complete Start-Up Checklist for 30RAP Liquid Chiller at end of this publication (pages CL-1 to CL-10). The checklist assures proper start-up of a unit, and provides a record of unit condition, application requirements, system information, and operation at initial start-up. Do not attempt to start the chiller until following checks have been completed. System Check 1. Check all auxiliary components, such as chilled fluid pumps, air-handling equipment, or other equipment to which the chiller supplies liquid. Consult manufacturer's instructions. Verify that any pump interlock contacts have been properly installed. If the unit If the unit has field-installed accessories, be sure all are properly installed and wired correctly. Refer to unit wiring diagrams. 44 2. Use the scrolling marquee display to adjust the Cooling Set Point. 3. Fill chilled fluid circuit with clean water (with recommended inhibitor added) or other non-corrosive fluid to be cooled. Bleed all air out of the high points of the system. If chilled water is to be maintained at a temperature below 40 F (4.4 C) or outdoor temperatures are expected to be below 32 F (0° C), a brine of sufficient concentration must be used to prevent freeze-up at anticipated suction temperatures. See Table 28. 4. Check tightness of all electrical connections. 5. Oil should be visible in the compressor sightglass(es). See Fig. 23. An acceptable oil level in the compressors is from 1/8 to 3/8 of sight glass. Adjust the oil level as required. See Oil Charge section on page 50 for Carrier approved oils. 6. Electrical power source must agree with unit nameplate. 7. All condenser fan and factory installed hydronic package pump motors are three phase. Check for proper rotation of condenser fans first BEFORE attempting to start pumps or compressors. To reverse rotation, interchange any two of the main incoming power leads. 8. Be sure system is fully charged with refrigerant (see Check Refrigerant Charge section on this page). 9. If unit is a brine unit, check to ensure proper brine concentration is used to prevent freezing. 10. Verify proper operation of cooler and hydronic package heaters (if installed). Heaters operate at the same voltage as the main incoming power supply and are single phase. Heater current is approximately 0.4 amps for 460 and 575 v units. Heater current is approximately 0.8 amps for 230 v units. START-UP AND OPERATION NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-10. Actual Start-Up — Actual start-up should be done only under supervision of a qualified refrigeration mechanic. 1. Be sure all service valves are open. 2. Using the scrolling marquee display, set leaving-fluid set point (Set PointsCOOLCSP.1). No cooling range adjustment is necessary. 3. Start chilled fluid pump (if not configured for cooler pump control). 4. Turn ENABLE/OFF/REMOTE CONTACT switch to ENABLE position. 5. Allow unit to operate and confirm that everything is functioning properly. Check to see that leaving fluid temperature agrees with leaving set point (Set PointsCOOL CSP.1) or (Set PointsCOOLCSP.2), or if reset is used, with the control point (Run StatusVIEW CTPT). 6. Check the cooler leaving chilled water temperature to see that it remains well above 32 F (0° C), or the brine freezing point if the unit is a medium temperature brine unit. 7. Recheck compressor oil level (see Oil Charge section). Check Refrigerant Charge — All 30RAP units are shipped with a complete operating charge of R-410A and should be under sufficient pressure to conduct a leak test after installation. If there is no system pressure, admit nitrogen until a pressure is observed and then proceed to test for leaks. After leaks are repaired, the system must be dehydrated. All refrigerant charging should be done through the ¼-in. Schraeder connection on the liquid line. Do NOT add refrigerant charge through the low-pressure side of the system. If complete charging is required, weigh in the appropriate charge for the circuit as shown on the unit nameplate. If partial charging is required, operate circuit at full load and use an accurate temperature sensor on the liquid line as it enters the EXV. Use the Temperatures mode on the scrolling marquee display to show the circuit saturated condensing temperature (TemperaturesCIR.ASCT.A) or (TemperaturesCIR.B SCT.B). Charging is most accurate at saturated discharge temperatures of 120 to 125 F (49 to 52 C). Block condenser airflow as required to reach this temperature range. Add refrigerant until the system subcooling (SCT.A or SCT.B minus liquid line temperature entering EXV) is approximately 15 to 17 F (–9.4 to –8.3 C). Refrigerant VAPOR only may be added to a circuit through the 1/4-in. suction Schraeder connection on the suction line. a30-4978 OIL SIGHTGLASS Fig. 23 — Sight Glass Location Table 28 — Minimum Cooler Flow Rates and Minimum Loop Volume 30RAP SIZE 010 015 018 020 025 030 035 040 045 050 055 060 MINIMUM COOLER FLOW RATE (gpm) 13 17 20 23 28 33 41 47 53 57 63 68 MAXIMUM COOLER FLOW RATE (gpm) 50 66 78 91 112 133 164 186 209 228 251 270 45 MINIMUM COOLER FLOW RATE (l/s) 0.8 1.1 1.3 1.5 1.8 2.1 2.6 3.0 3.3 3.6 4.0 4.3 MAXIMUM COOLER FLOW RATE (l/s) 3.2 4.2 4.9 5.7 7.1 8.4 10.3 11.7 13.2 14.4 15.8 17.0 Unbalanced 3-Phase Supply Voltage — Never operate a motor where a phase imbalance between phases is greater than 2%. To determine percent voltage imbalance: max voltage deviation from avg voltage % Voltage Imbalance = 100 x average voltage The maximum voltage deviation is the largest difference between a voltage measurement across 2 legs and the average across all 3 legs. Example: Supply voltage is 240-3-60. AB = 243 v BC = 236 v AC = 238 v CAUTION Never charge liquid into low-pressure side of system. Do not overcharge. Overcharging results in higher discharge pressure, possible compressor damage, and higher power consumption. During charging or removal of refrigerant, be sure water is continuously circulating through the cooler to prevent freezing. Operating Limitations TEMPERATURES (See Table 29 for 30RAP standard temperature limits). CAUTION 1. Determine average voltage: Do not operate with cooler leaving chiller water (fluid) temperature (LCWT) below 40 F (4.4 C) for the standard units, or below 15 F (–9.4 C) for units factory built for medium temperature brine. Average voltage = = High Cooler Leaving Chilled Water (Fluid) Temperatures (LCWT) — During start-up with cooler LCWT above approximately 60 F (16 C), the unit expansion valve will limit suction pressure to approximately 90 psig (620 kPa) to avoid overloading the compressor. Low Cooler LCWT — For standard units, the LCWT must be no lower than 40 F (4.4 C). If the unit is the factory-installed optional medium temperature brine unit, the cooler LCWT can go down to 15 F (–9.4 C). 010-030 F C 717 3 = 239 2. Determine maximum deviation from average voltage: (AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v Maximum deviation is 4 v. 3. Determine percent voltage imbalance: Table 29 — Temperature Limits for Standard 30RAP Units UNIT SIZE 30RA Temperature Maximum Ambient Temperature Minimum Ambient Temperature Maximum Cooler EWT* Maximum Cooler LWT Minimum Cooler LWT† 243 + 236 + 238 3 % Voltage Imbalance = 100 x = 1.7% 035-060 F C 120 49 120 49 45 7 32 0 95 70 40 35 21 4.4 95 70 40 35 21 4.4 4 239 This voltage imbalance is satisfactory as it is below the maximum allowable of 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. Do not operate unit until imbalance condition is corrected. LEGEND Control Circuit Power — Power for the control circuit is supplied from the main incoming power through a factoryinstalled control power transformer (TRAN1) for all models. Field wiring connections are made to the LVT. EWT — Entering Fluid (Water) Temperature LWT — Leaving Fluid (Water) Temperature *For sustained operation, EWT should not exceed 85 F (29.4 C). †Unit requires modification below this temperature. LOW-AMBIENT OPERATION — If operating temperatures below 45 F (7 C) on size 018-030 units, and 32 F (0° C) on size 035-060 units are expected, accessory Motormaster® V control must be installed. Operating temperatures can go as low as –20 F (–29 C) on size 010 and 015 units, as standard. Installation of wind baffles is also required. Refer to separate installation instructions for operation using this accessory. Contact your Carrier representative for details. OPERATION SEQUENCE During unit off cycle, the control monitors the outdoor air temperature. If the ambient temperature drops below 40 F (4.4 C), cooler and hydronic system heaters (if either are factory installed) are energized. If power is maintained to the chiller and the EMERGENCY ON/OFF switch is left in the OFF position, these heaters are also energized. The unit is started by putting the ENABLE/OFF/REMOTE CONTACT switch in the ENABLE or REMOTE CONTACT position. When the unit receives a call for cooling (either from the internal control or CCN network command or remote contact closure), the unit stages up in capacity to maintain the leaving fluid set point. The first compressor starts 11/2 to 3 minutes after the call for cooling. The lead circuit can be specifically designated on all models or selected based on compressor run hours and starts depending on field configuration. The unit control will override this selection under certain starting conditions to properly maintain oil return to the compressors. In general, on dual compressor CAUTION Brine duty application (below 40 F [4.4 C] LCWT) for chiller normally requires factory modification. Contact your Carrier representative for applicable LCWT range for standard water-cooled chiller in a specific application. VOLTAGE — ALL UNITS Main Power Supply — Minimum and maximum acceptable supply voltages are listed in the Installation Instructions. 46 determines the saturated temperature of suction gas. The difference between the temperature of the superheated gas and the saturated suction temperature is the superheat. The EXV board controls the position of the electronic expansion valve stepper motor to maintain superheat set point. The MBB controls the superheat leaving cooler to approximately 9° F (5° C). Because EXV status is communicated to the main base board (MBB) and is controlled by the EXV boards, it is possible to track the valve position. The unit is then protected against loss of charge and a faulty valve. Just prior to compressor start, the EXV will open. At low ambient temperatures the EXV is closed at start up. After initialization period, valve position is tracked by the EXV board by constantly monitoring the amount of valve movement. The EXV is also used to limit cooler saturated suction temperature to 50 F (10 C). This makes it possible for the chiller to start at higher cooler fluid temperatures without overloading the compressor. This is commonly referred to as MOP (maximum operating pressure). At ambient temperatures above 110 F, MOP is bypassed at start-up to prevent charge backup in the condenser. If it appears that the EXV module is not properly controlling circuit operation to maintain correct superheat, there are a number of checks that can be made using test functions and initialization features built into the microprocessor control. See the EXV Troubleshooting Procedure section to test EXVs. circuits, the control will most often start the A1 or B1 compressor first, especially after long off periods. The MBB controls fan stages to maintain the head pressure set point and will automatically adjust unit capacity as required to keep compressors from operating outside of the specified envelope. There are no pumpout or pumpdown sequences on these chillers. For all units, if temperature reset is being used, the unit controls to a higher leaving-fluid temperature as the building load reduces. If demand limit is used, the unit may temporarily be unable to maintain the desired leaving-fluid temperature because of imposed power limitations. SERVICE WARNING Electrical shock can cause personal injury and death. Shut off all power to this equipment during service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed. Electronic Components CONTROL COMPONENTS — Unit uses an advanced electronic control system that normally does not require service. For details on controls refer to Operating Data section. Access to the compressors is through latched panels from beneath the control box on all models or from opposite the coil side (sizes 010-030 only). The front door(s) provide access to the compressor(s) and all components of the refrigeration system. For size 010-030 units, access to the controls is through the upper latched outer door above the compressor access door. Similarly, the upper center latched door on sizes 035-060 gives access to the controls. Inner panels are secured in place and should not be removed unless all power to the chiller is off. EXV Troubleshooting Procedure — Follow steps below to diagnose and correct EXV/economizer problems. Check EXV motor operation first. Switch the Enable/Off/ Remote Contact (EOR) switch to the Off position. Press ESCAPE on the Navigator™ display until ‘Select a menu item’ appears on the display. Use the arrow keys to select the Service Test mode. Press ENTER . The display will be: > TEST OFF OUTS COMP Electronic Expansion Valve (EXV) — See Fig. 24 for a cutaway view of the EXV. High-pressure liquid refrigerant enters valve through the top. As refrigerant passes through the orifice, pressure drops and refrigerant changes to a 2-phase condition (liquid and vapor). The electronic expansion valve operates through an electronically controlled activation of a stepper motor. The stepper motor stays in position, unless power pulses initiate the two discrete sets of motor stator windings for rotation in either direction. The direction depends on the phase relationship of the power pulses. The motor directly operates the spindle, which has rotating movements that are transformed into linear motion by the transmission in the cage assembly. The valve includes a positive shut-off when closed. There are two different EXVs. See Table 30 for number of steps. The EXV motor moves at 200 steps per second. Commanding the valve to either 0% or 100% will add extra steps to the move, to ensure the value is open or closed completely. Press ENTER (password entry may be required) and use to change ‘OFF’ to ‘ON’. Switch the EOR switch to Enable. The Service Test mode is now enabled. Move the pointer down to the OUTS sub-mode and press ENTER . Move the pointer to item EXV.A or EXV.B as needed. Press ENTER and the valve position will flash. Use to select 100% valve position (hold for quick movement) and press ENTER . The technician should be able to feel the actuator moving by placing a hand on the EXV. A sight glass is located on the valve body to verify that the sleeve is moving to expose/cover slots in the orifice. A hard knocking should be felt from the actuator when it reaches the top of its stroke (can be heard if surroundings are relatively quiet). Press ENTER again twice if necessary to confirm this. To close the valve, press ENTER , select 0% with and press ENTER . The actuator should knock when it reaches the bottom of its stroke. If it is believed that the valve is not working properly, continue with the checkout procedure below: Table 30 — EXV Steps UNIT SIZE 30RAP 010-020 025,030 035-045 050-060 EXV STEPS 1596 2500 1596 2500 Check the EXV output signals at appropriate terminals on the EXV module (see Fig. 25). Connect positive test lead to red wire (EXV-J6 terminal 3 for Circuit A, EXV-J7 terminal 3 for Circuit B). Set meter to approximately 20 vdc. Using the Service Test procedure above, move the valve output under test to 100%. DO NOT short meter leads together or pin 3 to any other pin as board damage will occur. The EXV board controls the valve. Each circuit has a thermistor located in a well in the suction manifold before the compressor. Suction pressure as measured by the suction pressure transducer is converted to a saturated suction temperature. The thermistor measures the temperature of the superheated gas entering the compressor and the pressure transducer 47 INCLUDED IN CABLE KIT CABLE CABLE CABLE RETAINER MOTOR AND ADAPTER ASSEMBLY MOTOR ADAPTER ASSEMBLY CABLE RETAINER GASKET MOTOR ADAPTER ASSEMBLY SIGHTGLASS SPORLAN FLOW DIRECTION NORMAL FLOW DIRECTION a30-4971 Fig. 24 — Electronic Expansion Valve Details During the next several seconds, carefully connect the negative test lead to pins 1,2,4 and 5 in succession (plug J6 for Circuit A, plug J7 for Circuit B). Digital voltmeters will average this signal and display approximately 6 vdc. If it remains constant at a voltage other than 6 VDC or shows 0 volts, remove the connector to the valve and recheck. FIELD SERVICING INSTRUCTIONS — The EXV valves on sizes 025, 030, 050-060 can be serviced. The EXV valves on all other sizes are hermetic and cannot be disassembled for installation or during service, however, the cable and retainer may be replaced if necessary. Motor kits for the EXV valve are available as replacement parts. To remove the valve from the system, perform the following procedure: 1. Be sure the refrigerant has been recovered from the circuit. 2. Disconnect the line voltage to the valve controller. Disconnect the valve wires from the controller. 3. If the motor fails to operate properly, check the resistance of each motor phase. Resistance between black and white leads or between the red and green leads should be approximately 100 ohms. Differences of more than 10% between phases indicate a defective motor. Resistance between black and red, or any lead and piping, should be infinite or “open”. Any resistance reading will indicate a shorted winding and the valve will need to be replaced. 4. The output of the controller to the valve can be tested with the following procedure: a. Disconnect supply voltage to the controller. Press ENTER and select 0% to close the valve. Check the 4 position DIP switch on the board (all switches should be set to On). If a problem still exists, replace the EXV module. If the reading is correct, the expansion valve and EXV wiring should be checked. Check the EXV terminal strip and interconnecting wiring. 1. Check color coding and wire connections. Make sure they are connected to the correct terminals at the EXV driver and EXV plug and that the cables are not crossed. 2. Check for continuity and tight connection at all pin terminals. 3. Check the resistance of the EXV motor windings. Remove the EXV module plug (J6 for Circuit A, J7 for Circuit B) and check the resistance of the two windings between pins 1 and 2 for one winding and pins 4 and 5 for the other winding (see Fig. 25). The resistance should be 100 ohms ± 10 ohms. 48 CAUTION BLK WHT If the existing motor has been removed for inspection or cleaning, be sure that the piston is fully retracted into the motor assembly before installation on the valve. Failure to do so will permanently damage the drive and motor. Replacement motor assemblies are shipped in the retracted position and may be installed as received. GRN RED Compressor Replacement (Refer to Fig. 26 and 27) — All models contain scroll compressors and have from one to four compressors. The size 010-030 units are a single refrigeration circuit while sizes 035-060 are dual circuit. A compressor is most easily removed from the front of the unit, depending on where clearance space was allowed during unit installation. Remove the junction box cover bolts and disconnect the compressor power and ground connections. Remove the cable from the compressor junction box. Remove the connections from the high-pressure switch. Knock the same holes out of the new compressor junction box and install the cable connectors from the old compressor. The compressors are bolted to rails, which are in turn bolted to the unit basepan for all sizes except 010 and 015 which are directly bolted to the basepan. Remove the 4 bolts holding the compressor to the rail on the basepan. Save the mounting hardware for use with the new compressor. Carefully cut the compressor suction and discharge lines with a tubing cutter as close to the compressor as feasible. Remove high-pressure switch and pressure transducer(s) if required for compressor removal. Lift one corner of the compressor at a time and remove all the rubber mounting grommets (single compressor circuits) or steel spacers (dual compressor circuits). Remove the old compressor from the unit. Slide the new compressor in place on the basepan. Lifting one side of the compressor at a time, replace all of the compressor mounting grommets. Using new tubing as required, reconnect compressor suction and discharge lines. Using hardware saved, reinstall the mounting bolts and washers through the compressor feet. Using proper techniques, braze suction and discharge lines and check for leaks. Reconnect oil equalization line on dual compressor circuit models. Reconnect the compressor power connections and highpressure switch wiring as on the old compressor. Refer to Fig. 26 and 27. Following the installation of the new compressor, tighten all hardware to the following specifications. (See Table 31.) BLK WHT GRN RED a30-4972 Fig. 25 — EXV Cable Connections to EXV Module b. Place a digital voltmeter, on 20-volt AC scale, across the black and white terminals on the controller. Restore power to the controller. For at least 7 seconds, the voltmeter should read approximately 12 to 14 volts. Significant differences mean the controller is defective or not properly configured for the EXV valve. c. Repeat the procedure in Step b above using the red and green terminals on the controller. If the controller responds properly, then the wiring may be damaged or the valve may be plugged with debris or otherwise obstructed. d. The EXV valves on sizes 025, 030, 050-060 may be disassembled for cleaning, inspection or motor assembly replacement. VALVE REPLACEMENT — The valve may be replaced by unsoldering or cutting the piping. A tubing cutter must be used to prevent creating contaminants in the piping. VALVE REASSEMBLY — Perform the following procedure to reassemble the EXV valve: 1. Use Service Test to open the EXV to 100%. This will retract the white polyester driver/piston fully into the driver guide. Remove power from the valve or controller. 2. Lightly oil the threads, and gasket or knife-edge on the new motor adaptor. Carefully seat the adaptor on the valve body or engage and tighten the lock nut if used. Lock nuts should be torqued to approximately 45 ft-lb. One eighth turn more than hand tight is sufficient to achieve a leak proof seal on knife-edge joints. 3. After the motor is tightened, the cable should be replaced on the valve. Care should be taken to ensure engagement of the alignment key. Snap on the cable retainer. 4. Pressurize the system and check for leaks. 5. Reapply power to the ComfortLink™ controller. Since, during service, valve position as calculated by the controller will be lost, the controller should be initialized at least twice. In some instances, cycling power to the controller will accomplish this. Table 31 — Unit Torque Specification FASTENER Compressor Mounting Bolts Compressor Power Connections Compressor Ground Terminal Connections RECOMMENDED TORQUE 7 to 10 ft-lb (9.5 to 13.5 N-m) 24 to 28 in.-lb (2.7- to 3.2 N-m) 14 to 18 in.-lb (1.6 to 2.0 N-m) Cooler BRAZED-PLATE COOLER HEAT EXCHANGER REPLACEMENT — Brazed-plate heat exchangers cannot be repaired if they develop a leak. If a leak (refrigerant or water) develops, the heat exchanger must be replaced. To replace a brazed-plate heat exchanger: 1. Check that the replacement heat exchanger is the same as the original heat exchanger. The unit insulation covers the manufacturer’s part number. Make sure the depths of the replacement and original cooler heat exchangers are the same. 49 Mobil . . . . . . . . . . . . . . . . . . . . . . . . . . .EAL Arctic 32-3MA Uniqema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RL32-3MAF Do not reuse oil that has been drained out, or oil that has been exposed to atmosphere. 2. Disconnect the liquid-in and liquid-out connections at the heat exchanger. 3. Recover the refrigerant from the system, and unsolder the refrigerant-in and refrigerant-out connections. 4. Remove the old heat exchanger. The replacement heat exchanger is supplied fully insulated. It also includes a cooler heater. Use of the heater is not required unless the original cooler contained a factory installed heater. 5. Install the replacement heat exchanger in the unit and attach the mounting bracket hardware to the fan uprights (sizes 010-030) or to the bottom bracket (sizes 035-060) using the hardware removed in Step 4. Reconnect the cooler heater if required. For sizes 010-025, torque the bolts to 7-10 ft-lb. For sizes 030-060, torque the bolts to 30-50 ft-lb. 6. Carefully braze the refrigerant lines to the connections on the heat exchanger. Lines should be soldered using silver as the soldering material with a minimum of 45% silver. Keep the temperature below 1472 F (800 C) under normal soldering conditions (no vacuum) to prevent the copper solder of the brazed plate heat exchanger from changing its structure. Failure to do so can result in internal or external leakage at the connections which cannot be repaired. Braze the liquid lines with a heat sink around the expansion valve to protect it from excess heat. 7. Reconnect the water/brine lines. 8. Dehydrate and recharge the unit. Check for leaks. BRAZED-PLATE COOLER HEAT EXCHANGER CLEANING — Brazed-plate heat exchangers must be cleaned chemically. A professional cleaning service skilled in chemical cleaning should be used. Use a weak acid (5% phosphoric acid, or if the heat exchanger is cleaned frequently, 5% oxalic acid). Pump the cleaning solution through the exchanger, preferably in a backflush mode. After cleaning, rinse with large amounts of fresh water to dispose of all the acid. Cleaning materials must be disposed of properly. The factory-installed strainer screen in front of the water/ brine inlets of the heat exchangers should be cleaned periodically, depending on condition of the chiller water/brine. Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning Recommendations CAUTION Do not apply any chemical cleaners to MCHX condenser coils. These cleaners can accelerate corrosion and damage the coil. Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following steps should be taken to clean MCHX condenser coils: 1. Remove any foreign objects or debris attached to the coreface or trapped within the mounting frame and brackets. 2. Put on personal protective equipment including safetyglasses and/or face shield, waterproof clothing and gloves. It is recommended to use full coverage clothing. 3. Start high pressure water sprayer and purge any soap or industrial cleaners from sprayer before cleaning condenser coils. Only clean, potable water is authorized for cleaning condenser coils. 4. Clean condenser face by spraying the core steady and uniformly from top to bottom while directing the spray straight toward the core. Do not exceed 900 psig or 30 degree angle. The nozzle must be at least 12 in. from the core face. Reduce pressure and use caution to prevent damage to air centers. CAUTION Excessive water pressure will fracture the braze between air centers and refrigerant tubes. Oil Charge Check Refrigerant Feed Components CAUTION FILTER DRIER — The function of the filter drier is to maintain a clean, dry system. The moisture indicator (described below) indicates any need to change the filter drier. The filter drier is a sealed-type drier. When the drier needs to be changed, the entire filter drier must be replaced. NOTE: Dual circuit (035-060 sizes) units have 1 filter drier per circuit. MOISTURE-LIQUID INDICATOR — The indicator is located immediately ahead of the TXV to provide an indication of the refrigerant moisture content. It also provides a sight glass for refrigerant liquid. Clear flow of liquid refrigerant (at full unit loading) indicates sufficient charge in the system. Bubbles in the sight glass (at full unit loading) indicate an undercharged system or the presence of noncondensables. Moisture in the system, measured in parts per million (ppm), changes the color of the indicator as follows: Green (safe) —Moisture is below 75 ppm Yellow-Green (caution) — 75 to 150 ppm Yellow (wet) — above 150 ppm The unit must be in operation at least 12 hours before the moisture indicator gives an accurate reading, and must be in contact with liquid refrigerant. At the first sign of moisture in the system, change the corresponding filter drier. NOTE: Dual circuit (035-060 sizes) units have one indicator per circuit. The compressor in a Puron® refigerant (R-410A) system uses a polyol ester (POE) oil. This is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere. Failure to do so could result in possible equipment damage. Puron refrigerant systems use a polyol ester (POE) oil. Use only Carrier approved compressor oil. Oil should be visible in compressor oil sight glass. An acceptable oil level is from 1/8 to 3/ of sight glass. All compressors must be off when checking 8 oil level. Recommended oil level adjustment method is as follows: ADD OIL — Recover charge from the unit. Add oil to suction line Schrader valve on tandem compressors sets and the compressor Schrader on the trio's and single compressor circuits. (See Fig. 26 and 27.) When oil can be seen at the bottom of the sight glass, add oil in 5 oz increments which is approximately 1/ in oil level. Run all compressors for 20 minutes then shut off 8 to check oil level. Repeat procedure until acceptable oil level is present. NOTE: Use only Carrier approved compressor oil. Approved sources are: Totaline . . . . . . . . . . . . . . . . . . . . . . 3MAF POE, P903-1601 50 DPT HPS SUCTION ACCESS VALVE EWT SPT RGT COMPRESSOR A2 FLOW SWITCH LWT a30-4973 COMPRESSOR A1 DTT Fig. 26 — Compressor Location — 30RAP010-030 DPT HPS SUCTION RGT SPT ACCESS VALVE SPT RGT a30-4974 DISCHARGE ACCESS VALVE EWT DTT A1 A2 B1 B2 OIL SIGHTGLASS DISCHARGE ACCESS VALVE LWT DPT FLOW SWITCH HPS Fig. 27 — Compressor Location — 30RAP035-060 DPT DTT EWT HPS LWT RGT SPT — — — — — — — LEGEND FOR FIG. 26 AND 27 Discharge Pressure Thermostat Discharge Temperature Thermistor Entering Water Thermistor High Pressure Switch Leaving Water Thermistor Return Gas Thermistor Suction Pressure Transducer 51 HEATER CABLE — Optional factory-installed cooler and/or hydronic package heaters are cycled based on the input from the outside-air temperature sensor. These heaters, when installed, are designed to protect the cooler and/or hydronic package from freezing down to –20 F (–29 C). Power for these heaters is supplied from the main unit power. The input from the low pressure transducer provides a backup cooler freeze protection package. The MBB shuts down the unit when a low pressure condition exists that could cause the cooler to freeze up. MINIMUM LOAD VALVE — On units equipped with the factory-installed capacity reduction option, a solenoid valve and discharge bypass valve (minimum load valve) are located between the discharge line and the cooler entering-refrigerant line. The MBB cycles the solenoid to perform minimum load valve function and the discharge bypass valve modulates to the suction pressure set point and the valve. The amount of capacity reduction achieved by the minimum load valve is not adjustable. The total unit capacity with the minimum load valve is shown in Table 19. PRESSURE RELIEF DEVICES — All units have one pressure relief device per circuit located in the liquid line which relieves at 210 F (100 C). CAUTION Do not disconnect main unit power when servicing compressor(s) if ambient temperature is below 40 F (4.4 C). The compressors have either a single circuit breaker or multiple circuit breakers which can be used to shut off power to the compressors. If power to the unit must be off for a prolonged period, drain the cooler, hydronic package (if installed) and internal piping. Add glycol according to Winter Shutdown Step 2 below. Check Unit Safeties HIGH-PRESSURE SWITCH — A high-pressure switch is provided to protect each compressor and refrigeration system from unsafe high pressure conditions. See Table 32 for highpressure switch settings. The high-pressure switch is mounted in the discharge line of each circuit. If an unsafe, high-pressure condition should exist, the switch opens and shuts off the affected circuit. The CSB senses the compressor feedback signal and generates an appropriate alarm. The MBB prevents the circuit from restarting until the alert condition is reset. The switch should open at the pressure corresponding to the appropriate switch setting as shown in Table 32. WINTER SHUTDOWN — At the end of the cooling season: 1. Drain the fluid from the cooler, hydronic package (if installed) and internal piping. 2. Fill the cooler and hydronic package with at least 2 gallons (7.6 L) of inhibited propylene glycol or other suitable inhibited antifreeze solution to prevent any residual water in the cooler and hydronic package/piping from freezing. 3. At the beginning of the next cooling season, refill the cooler and add the recommended inhibitor. Table 32 — Factory Settings, High-Pressure Switch (Fixed) UNIT 30RA CUTOUT Psig kPa 650 4482 CUT-IN Psig 500 kPa 3447 Thermistors — Electronic control uses up to five 5 k thermistors to sense temperatures used to control operation of the chiller. Thermistors EWT, LWT, RGTA, RGTB, and OAT are identical in their temperature and voltage drop performance. The SPT space temperature thermistor has a 10 k input channel and it has a different set of temperature vs. resistance and voltage drop performance. Resistance at various temperatures are listed in Tables 33-37. For dual chiller operation, a dual chiller sensor is required which is a 5 k thermistor. When a digital compressor is used, a DTT (digital temperature thermistor) is used. The DTT is an 86 k thermistor. REPLACING THERMISTORS (EWT, LWT, RGT) — Add a small amount of thermal conductive grease to the thermistor well and end of probe. For all probes, tighten the retaining nut ¼ turn past finger tight. See Fig. 28. THERMISTOR/TEMPERATURE SENSOR CHECK — A high quality digital volt-ohmmeter is required to perform this check. 1. Connect the digital voltmeter across the appropriate themistor terminals at the J8 terminal strip on the Main Base Board (see Fig. 29). 2. Using the voltage reading obtained, read the sensor temperature from Tables 33-37. 3. To check thermistor accuracy, measure temperature at probe location with an accurate thermocouple-type temperature measuring instrument. Insulate thermocouple to avoid ambient temperatures from influencing reading. Temperature measured by thermocouple and temperature determined from thermistor voltage reading should be close, ± 5° F (3° C) if care was taken in applying thermocouple and taking readings. If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) using either voltage drop measured across thermistor at the J8 terminal, by determining the resistance with chiller shut down and thermistor Clear the alarm using the scrolling marquee display as described on page 63. The unit should restart after the compressor anti-short-cycle delay, built into the unit control module, expires. PRESSURE TRANSDUCERS — Each refrigerant circuit is equipped with a suction and discharge pressure transducer. These inputs to the MBB are not only used to monitor the status of the unit, but to also maintain operation of the chiller within the compressor manufacturer's specified limits. The input to the MBB from the suction pressure transducer is also used to protect the compressor from operating at low pressure conditions and low superheat conditions. In some cases, the unit may not be able to run at full capacity. The control module will automatically reduce the capacity of a circuit as needed to maintain specified maximum/minimum operating pressures. COOLER FREEZE-UP PROTECTION WARNING On medium temperature brine units, the anti-freeze solution must be properly mixed to prevent freezing at a temperature of at least 15 F (8.3 C) below the leaving-fluid temperature set point. Failure to provide the proper antifreeze solution mixture is considered abuse and may impair or otherwise negatively impact the Carrier warranty. The main base board (MBB) monitors leaving fluid temperature at all times. The MBB will rapidly remove stages of capacity as necessary to prevent freezing conditions due to the rapid loss of load or low cooler fluid flow. When the cooler is exposed to lower ambient temperatures (34 F [1° C] or below), freeze-up protection is required using inhibited ethylene or propylene glycol. 52 necessary, build-up (e.g., lime) can be removed with a common vinegar cleansing agent. The flow sensor cable is provided with (3) LEDs that indicate if 24 vac power is present and also status of the switch contacts. The LEDs are as follows: • Green LED ON – 24 vac present • One Yellow LED ON – Flow sensor switch OPEN • Two Yellow LED ON – Flow sensor switch CLOSED If nuisance trips of the sensor are occurring, follow the steps below to correct the situation: 1. Check to confirm that the factory installed strainer is clean. Use the blow-down valve provided or remove the screen and clean it. For the case of VFD controlled pumps, ensure that the minimum speed setting has not been changed. 2. Measure the pressure drop across the cooler or cooler/ pump system and compare this to the system requirements. 3. Verify that cable connections at the switch and at the terminal block are secure. 4. For factory-installed hydronic systems, verify that: • All air has been purged from the system. • Circuit setter balance valve has been correctly set. 5. Pump impeller has been improperly trimmed and is not providing sufficient flow. 6. Wrong pump motor rotation. Pump must rotate clockwise when viewed from motor end of pump. disconnected from J8. Compare the values determined with the value read by the control in the Temperatures mode using the scrolling marquee display. Pressure Transducers — The suction and discharge transducers are different part numbers and can be distinguished by the color of the transducer body, suction (yellow) and discharge (red). No pressure transducer calibration is required. The transducers operate on a 5 vdc supply, which is generated by the main base board (MBB). See Fig. 29 for transducer connections to the J8 connector on the MBB. TROUBLESHOOTING — If a transducer is suspected of being faulty, first check supply voltage to the transducer. Supply voltage should be 5 vdc ± 0.2 v. If supply voltage is correct, compare pressure reading displayed on the scrolling marquee display module against pressure shown on a calibrated pressure gauge. Pressure readings should be within ± 15 psig. If the two readings are not reasonably close, replace the pressure transducer. Chilled Water Flow Switch — A factory-installed flow switch is installed in the leaving fluid piping for all units without the factory-installed hydronic package. See Fig. 30. Units with the optional hydronic package have the flow switch installed in the entering fluid piping. This is a thermal-dispersion flow switch with no field adjustments. The switch is set for approximately 0.5 ft/sec of flow. The sensor tip houses two thermistors and a heater element. One thermistor is located in the sensor tip, closest to the flowing fluid. This thermistor is used to detect changes in the flow velocity of the liquid. The second thermistor is bonded to the cylindrical wall and is affected only by changes in the temperature of the liquid. The thermistors are positioned to be in close contact with the wall of the sensor probe and, at the same time, to be kept separated from each other within the confines of the probe. In order to sense flow, it is necessary to heat one of the thermistors in the probe. When power is applied, the tip of the probe is heated. As the fluid starts to flow, heat will be carried away from the sensor tip. Cooling of the first thermistor is a function of how fast heat is conducted away by the flowing liquid. The difference in temperature between the two thermistors provides a measurement of fluid velocity past the sensor probe. When fluid velocity is high, more heat will be carried away from the heated thermistor and the temperature differential will be small. As fluid velocity decreases, less heat will be taken from the heated thermistor and there will be an increase in temperature differential. When unit flow rate is above the minimum flow rate, then the output is switched on, sending 24 vac to the MBB to prove flow has been established. For recommended maintenance, check the sensor tip for build-up every 6 months. Clean the tip with a soft cloth. If Strainer — Periodic factory-installed strainer cleaning is required. Pressure drop across strainer in excess of 3 psi (21 kPa) indicates the need for cleaning. Normal (clean) pressure drop is approximately 1 psi (6.9 kPa). Open the factoryinstalled blowdown valve to clean the strainer. If required, shut the chiller down and remove the strainer screen to clean. When strainer has been cleaned, enter ‘YES’ for Strainer Maintenance Done (Run StatusPMS.T.MN). Condenser Fans — Each fan is supported by a formed wire mount bolted to a fan deck and covered with a wire guard. METAL FANS — The exposed end of fan motor shaft is protected from weather by grease and a rubber boot. If fan motor must be removed for service or replacement, be sure to regrease fan shaft and reinstall fan guard. For proper performance with the value sound fan option, fan web should be 0.32 in. (8 mm) below top of orifice on the fan deck to top of the fan hub. (See Fig. 31.) Tighten set screws to 15 ± 1 ft-lb (20 ± 1.3 N-m). IMPORTANT: Check for proper fan rotation (clockwise when viewed from above). If necessary, switch any 2 power leads to reverse fan rotation. 5/8 in. HEX 1/4-18 NPT 6" MINIMUM CLEARANCE FOR THERMISTOR REMOVAL Fig. 28 — Thermistor Well 53 Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) TEMP (F) –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 VOLTAGE DROP (V) 3.699 3.689 3.679 3.668 3.658 3.647 3.636 3.624 3.613 3.601 3.588 3.576 3.563 3.550 3.536 3.523 3.509 3.494 3.480 3.465 3.450 3.434 3.418 3.402 3.386 3.369 3.352 3.335 3.317 3.299 3.281 3.262 3.243 3.224 3.205 3.185 3.165 3.145 3.124 3.103 3.082 3.060 3.038 3.016 2.994 2.972 2.949 2.926 2.903 2.879 2.856 2.832 2.808 2.784 2.759 2.735 2.710 2.685 2.660 2.634 2.609 2.583 2.558 2.532 2.506 2.480 2.454 2.428 2.402 2.376 2.349 2.323 2.296 2.270 2.244 2.217 2.191 2.165 2.138 2.112 2.086 2.060 2.034 2.008 RESISTANCE (Ohms) TEMP (F) 98,010 94,707 91,522 88,449 85,486 82,627 79,871 77,212 74,648 72,175 69,790 67,490 65,272 63,133 61,070 59,081 57,162 55,311 53,526 51,804 50,143 48,541 46,996 45,505 44,066 42,679 41,339 40,047 38,800 37,596 36,435 35,313 34,231 33,185 32,176 31,202 30,260 29,351 28,473 27,624 26,804 26,011 25,245 24,505 23,789 23,096 22,427 21,779 21,153 20,547 19,960 19,393 18,843 18,311 17,796 17,297 16,814 16,346 15,892 15,453 15,027 14,614 14,214 13,826 13,449 13,084 12,730 12,387 12,053 11,730 11,416 11,112 10,816 10,529 10,250 9,979 9,717 9,461 9,213 8,973 8,739 8,511 8,291 8,076 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 VOLTAGE DROP (V) 1.982 1.956 1.930 1.905 1.879 1.854 1.829 1.804 1.779 1.754 1.729 1.705 1.681 1.656 1.632 1.609 1.585 1.562 1.538 1.516 1.493 1.470 1.448 1.426 1.404 1.382 1.361 1.340 1.319 1.298 1.278 1.257 1.237 1.217 1.198 1.179 1.160 1.141 1.122 1.104 1.086 1.068 1.051 1.033 1.016 0.999 0.983 0.966 0.950 0.934 0.918 0.903 0.888 0.873 0.858 0.843 0.829 0.815 0.801 0.787 0.774 0.761 0.748 0.735 0.723 0.710 0.698 0.686 0.674 0.663 0.651 0.640 0.629 0.618 0.608 0.597 0.587 0.577 0.567 0.557 0.548 0.538 0.529 0.520 54 RESISTANCE (Ohms) TEMP (F) 7,686 7,665 7,468 7,277 7,091 6,911 6,735 6,564 6,399 6,238 6,081 5,929 5,781 5,637 5,497 5,361 5,229 5,101 4,976 4,855 4,737 4,622 4,511 4,403 4,298 4,196 4,096 4,000 3,906 3,814 3,726 3,640 3,556 3,474 3,395 3,318 3,243 3,170 3,099 3,031 2,964 2,898 2,835 2,773 2,713 2,655 2,597 2,542 2,488 2,436 2,385 2,335 2,286 2,239 2,192 2,147 2,103 2,060 2,018 1,977 1,937 1,898 1,860 1,822 1,786 1,750 1,715 1,680 1,647 1,614 1,582 1,550 1,519 1,489 1,459 1,430 1,401 1,373 1,345 1,318 1,291 1,265 1,240 1,214 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 VOLTAGE DROP (V) 0.511 0.502 0.494 0.485 0.477 0.469 0.461 0.453 0.445 0.438 0.430 0.423 0.416 0.408 0.402 0.395 0.388 0.381 0.375 0.369 0.362 0.356 0.350 0.344 0.339 0.333 0.327 0.322 0.317 0.311 0.306 0.301 0.296 0.291 0.286 0.282 0.277 0.272 0.268 0.264 0.259 0.255 0.251 0.247 0.243 0.239 0.235 0.231 0.228 0.224 0.220 0.217 0.213 0.210 0.206 0.203 0.200 0.197 0.194 0.191 0.188 0.185 0.182 0.179 0.176 0.173 0.171 0.168 0.165 0.163 0.160 0.158 0.155 0.153 0.151 0.148 0.146 0.144 0.142 0.140 0.138 0.135 0.133 RESISTANCE (Ohms) 1,190 1,165 1,141 1,118 1,095 1,072 1,050 1,029 1,007 986 965 945 925 906 887 868 850 832 815 798 782 765 750 734 719 705 690 677 663 650 638 626 614 602 591 581 570 561 551 542 533 524 516 508 501 494 487 480 473 467 461 456 450 445 439 434 429 424 419 415 410 405 401 396 391 386 382 377 372 367 361 356 350 344 338 332 325 318 311 304 297 289 282 Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) TEMP (C) –32 –31 –30 –29 –28 –27 –26 –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 VOLTAGE DROP (V) 3.705 3.687 3.668 3.649 3.629 3.608 3.586 3.563 3.539 3.514 3.489 3.462 3.434 3.406 3.376 3.345 3.313 3.281 3.247 3.212 3.177 3.140 3.103 3.065 3.025 2.985 2.945 2.903 2.860 2.817 2.774 2.730 2.685 2.639 2.593 2.547 2.500 2.454 2.407 2.360 2.312 2.265 2.217 2.170 2.123 2.076 2.029 RESISTANCE (Ohms) TEMP (C) 100,260 94,165 88,480 83,170 78,125 73,580 69,250 65,205 61,420 57,875 54,555 51,450 48,536 45,807 43,247 40,845 38,592 38,476 34,489 32,621 30,866 29,216 27,633 26,202 24,827 23,532 22,313 21,163 20,079 19,058 18,094 17,184 16,325 15,515 14,749 14,026 13,342 12,696 12,085 11,506 10,959 10,441 9,949 9,485 9,044 8,627 8,231 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 VOLTAGE DROP (V) 1.982 1.935 1.889 1.844 1.799 1.754 1.710 1.666 1.623 1.580 1.538 1.497 1.457 1.417 1.378 1.340 1.302 1.265 1.229 1.194 1.160 1.126 1.093 1.061 1.030 0.999 0.969 0.940 0.912 0.885 0.858 0.832 0.807 0.782 0.758 0.735 0.713 0.691 0.669 0.649 0.629 0.610 0.591 0.573 0.555 0.538 0.522 55 RESISTANCE (Ohms) TEMP (C) 7,855 7,499 7,161 6,840 6,536 6,246 5,971 5,710 5,461 5,225 5,000 4,786 4,583 4,389 4,204 4,028 3,861 3,701 3,549 3,404 3,266 3,134 3,008 2,888 2,773 2,663 2,559 2,459 2,363 2,272 2,184 2,101 2,021 1,944 1,871 1,801 1,734 1,670 1,609 1,550 1,493 1,439 1,387 1,337 1,290 1,244 1,200 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 VOLTAGE DROP (V) 0.506 0.490 0.475 0.461 0.447 0.433 0.420 0.407 0.395 0.383 0.371 0.360 0.349 0.339 0.329 0.319 0.309 0.300 0.291 0.283 0.274 0.266 0.258 0.251 0.244 0.237 0.230 0.223 0.217 0.211 0.204 0.199 0.193 0.188 0.182 0.177 0.172 0.168 0.163 0.158 0.154 0.150 0.146 0.142 0.138 0.134 RESISTANCE (Ohms) 1,158 1,118 1,079 1,041 1,006 971 938 906 876 836 805 775 747 719 693 669 645 623 602 583 564 547 531 516 502 489 477 466 456 446 436 427 419 410 402 393 385 376 367 357 346 335 324 312 299 285 Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop (For SPT) TEMP (F) –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 VOLTAGE DROP (V) 4.758 4.750 4.741 4.733 4.724 4.715 4.705 4.696 4.686 4.676 4.665 4.655 4.644 4.633 4.621 4.609 4.597 4.585 4.572 4.560 4.546 4.533 4.519 4.505 4.490 4.476 4.461 4.445 4.429 4.413 4.397 4.380 4.363 4.346 4.328 4.310 4.292 4.273 4.254 4.235 4.215 4.195 4.174 4.153 4.132 4.111 4.089 4.067 4.044 4.021 3.998 3.975 3.951 3.927 3.903 3.878 3.853 3.828 3.802 3.776 3.750 3.723 3.697 3.670 3.654 3.615 3.587 3.559 3.531 3.503 3.474 3.445 3.416 3.387 3.357 3.328 3.298 3.268 3.238 3.208 3.178 3.147 3.117 3.086 3.056 3.025 RESISTANCE (Ohms) TEMP (F) 196,453 189,692 183,300 177,000 171,079 165,238 159,717 154,344 149,194 144,250 139,443 134,891 130,402 126,183 122,018 118,076 114,236 110,549 107,006 103,558 100,287 97,060 94,020 91,019 88,171 85,396 82,729 80,162 77,662 75,286 72,940 70,727 68,542 66,465 64,439 62,491 60,612 58,781 57,039 55,319 53,693 52,086 50,557 49,065 47,627 46,240 44,888 43,598 42,324 41,118 39,926 38,790 37,681 36,610 35,577 34,569 33,606 32,654 31,752 30,860 30,009 29,177 28,373 27,597 26,838 26,113 25,396 24,715 24,042 23,399 22,770 22,161 21,573 20,998 20,447 19,903 19,386 18,874 18,384 17,904 17,441 16,991 16,552 16,131 15,714 15,317 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 VOLTAGE DROP (V) 2.994 2.963 2.932 2.901 2.870 2.839 2.808 2.777 2.746 2.715 2.684 2.653 2.622 2.592 2.561 2.530 2.500 2.470 2.439 2.409 2.379 2.349 2.319 2.290 2.260 2.231 2.202 2.173 2.144 2.115 2.087 2.059 2.030 2.003 1.975 1.948 1.921 1.894 1.867 1.841 1.815 1.789 1.763 1.738 1.713 1.688 1.663 1.639 1.615 1.591 1.567 1.544 1.521 1.498 1.475 1.453 1.431 1.409 1.387 1.366 1.345 1.324 1.304 1.284 1.264 1.244 1.225 1.206 1.187 1.168 1.150 1.132 1.114 1.096 1.079 1.062 1.045 1.028 1.012 0.996 0.980 0.965 0.949 0.934 0.919 0.905 56 RESISTANCE (Ohms) TEMP (F) 14,925 14,549 14,180 13,824 13,478 13,139 12,814 12,493 12,187 11,884 11,593 11,308 11,031 10,764 10,501 10,249 10,000 9,762 9,526 9,300 9,078 8,862 8,653 8,448 8,251 8,056 7,869 7,685 7,507 7,333 7,165 6,999 6,838 6,683 6,530 6,383 6,238 6,098 5,961 5,827 5,698 5,571 5,449 5,327 5,210 5,095 4,984 4,876 4,769 4,666 4,564 4,467 4,370 4,277 4,185 4,096 4,008 3,923 3,840 3,759 3,681 3,603 3,529 3,455 3,383 3,313 3,244 3,178 3,112 3,049 2,986 2,926 2,866 2,809 2,752 2,697 2,643 2,590 2,539 2,488 2,439 2,391 2,343 2,297 2,253 2,209 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 VOLTAGE DROP (V) 0.890 0.876 0.862 0.848 0.835 0.821 0.808 0.795 0.782 0.770 0.758 0.745 0.733 0.722 0.710 0.699 0.687 0.676 0.666 0.655 0.645 0.634 0.624 0.614 0.604 0.595 0.585 0.576 0.567 0.558 0.549 0.540 0.532 0.523 0.515 0.507 0.499 0.491 0.483 0.476 0.468 0.461 0.454 0.447 0.440 0.433 0.426 0.419 0.413 0.407 0.400 0.394 0.388 0.382 0.376 0.370 0.365 0.359 0.354 0.349 0.343 0.338 0.333 0.328 0.323 0.318 0.314 0.309 0.305 0.300 0.296 0.292 0.288 0.284 0.279 0.275 0.272 0.268 0.264 RESISTANCE (Ohms) 2,166 2,124 2,083 2,043 2,003 1,966 1,928 1,891 1,855 1,820 1,786 1,752 1,719 1,687 1,656 1,625 1,594 1,565 1,536 1,508 1,480 1,453 1,426 1,400 1,375 1,350 1,326 1,302 1,278 1,255 1,233 1,211 1,190 1,169 1,148 1,128 1,108 1,089 1,070 1,052 1,033 1,016 998 981 964 947 931 915 900 885 870 855 841 827 814 800 787 774 762 749 737 725 714 702 691 680 670 659 649 639 629 620 610 601 592 583 574 566 557 Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop (For SPT) TEMP (C) –32 –31 –30 –29 –28 –27 –26 –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 VOLTAGE DROP (V) 4.762 4.748 4.733 4.716 4.700 4.682 4.663 4.644 4.624 4.602 4.580 4.557 4.533 4.508 4.482 4.455 4.426 4.397 4.367 4.335 4.303 4.269 4.235 4.199 4.162 4.124 4.085 4.044 4.003 3.961 3.917 3.873 3.828 3.781 3.734 3.686 3.637 3.587 3.537 3.485 3.433 3.381 3.328 3.274 3.220 3.165 3.111 RESISTANCE (Ohms) TEMP (C) 200,510 188,340 177,000 166,342 156,404 147,134 138,482 130,402 122,807 115,710 109,075 102,868 97,060 91,588 86,463 81,662 77,162 72,940 68,957 65,219 61,711 58,415 55,319 52,392 49,640 47,052 44,617 42,324 40,153 38,109 36,182 34,367 32,654 31,030 29,498 28,052 26,686 25,396 24,171 23,013 21,918 20,883 19,903 18,972 18,090 17,255 16,464 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 VOLTAGE DROP (V) 3.056 3.000 2.944 2.889 2.833 2.777 2.721 2.666 2.610 2.555 2.500 2.445 2.391 2.337 2.284 2.231 2.178 2.127 2.075 2.025 1.975 1.926 1.878 1.830 1.784 1.738 1.692 1.648 1.605 1.562 1.521 1.480 1.439 1.400 1.362 1.324 1.288 1.252 1.217 1.183 1.150 1.117 1.086 1.055 1.025 0.996 0.968 RESISTANCE (Ohms) TEMP (C) 15,714 15,000 14,323 13,681 13,071 12,493 11,942 11,418 10,921 10,449 10,000 9,571 9,164 8,776 8,407 8,056 7,720 7,401 7,096 6,806 6,530 6,266 6,014 5,774 5,546 5,327 5,117 4,918 4,727 4,544 4,370 4,203 4,042 3,889 3,743 3,603 3,469 3,340 3,217 3,099 2,986 2,878 2,774 2,675 2,579 2,488 2,400 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 VOLTAGE DROP (V) 0.940 0.913 0.887 0.862 0.837 0.813 0.790 0.767 0.745 0.724 0.703 0.683 0.663 0.645 0.626 0.608 0.591 0.574 0.558 0.542 0.527 0.512 0.497 0.483 0.470 0.457 0.444 0.431 0.419 0.408 0.396 0.386 0.375 0.365 0.355 0.345 0.336 0.327 0.318 0.310 0.302 0.294 0.287 0.279 0.272 0.265 RESISTANCE (Ohms) 2,315 2,235 2,157 2,083 2,011 1,943 1,876 1,813 1,752 1,693 1,637 1,582 1,530 1,480 1,431 1,385 1,340 1,297 1,255 1,215 1,177 1,140 1,104 1,070 1,037 1,005 974 944 915 889 861 836 811 787 764 742 721 700 680 661 643 626 609 592 576 561 Table 37 — 86K Thermistor vs Resistance (DTT) TEMP (C) TEMP (F) -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 70 -40 -31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 131 140 158 RESISTANCE (Ohms) TEMP (C) TEMP (F) 2,889,600 2,087,220 1,522,200 1,121,440 834,720 627,280 475,740 363,990 280,820 218,410 171,170 135,140 107,440 86,000 69,280 56,160 45,810 37,580 30,990 25,680 21,400 15,070 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 167 176 185 194 203 212 221 230 239 248 257 266 275 284 293 302 311 320 329 338 347 356 57 RESISTANCE (Ohms) 12,730 10,790 9,200 7,870 6,770 5,850 5,090 4,450 3,870 3,350 2,920 2,580 2,280 2,020 1,800 1,590 1,390 1,250 1,120 1,010 920 830 1 2 3 4 5 6 7 8 9 10 11 J8 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 ACCSY DPT LWT LVT OAT RGT SEN SPT 1 RGTA RED 2 LOW SOUND FAN — A shroud and a wire guard provide protection from the rotating fan. The exposed end of the fan motor shaft is protected from weather by grease. If fan motor must be removed for service or replacement, be sure to regrease fan shaft and reinstall fan guard. The fan motor has a step in the motor shaft. For proper performance, fan should be positioned such that it is securely seated on this step. Tighten the bolt to 15 ± 1 ft-lb (20 ± 1.3 N·m). BLK 3 RGTB RED 4 5 6 1 LVT BLK J12 T55 BLU 3 23 BLU 4 22 OAT RED 2 BLK 3 SEN T-55 ACCSY IMPORTANT: Check for proper fan rotation (counterclockwise when viewed from above). If necessary, switch any 2 power leads to reverse fan rotation. SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT 4 1 2 controller is standard on size 010 and 015 units. For other sizes, the optional or accessory Motormaster V controller uses an input signal from the AUX board. See Fig. 32. The controller is factory configured and requires no field programming. If a situation arises where the drive does not function properly, the information provided below and in Table 38 can be used to troubleshoot the drive. BLK 3 EVAPORATOR LEAVING FLUID TEMP RED 4 BLK 1 RED 2 GRN 3 BLK 4 RED 5 GRN 6 BLK 7 RED 8 GRN 9 BLK 10 RED 11 12 — — — — — — — — Motormaster® V Controller — The Motormaster V EVAPORATOR ENTERING FLUID TEMP RED GRN BLK B C A + DPTB - B C + A - WARNING SPTB Hazard of electrical shock. Wait three minutes after disconnecting incoming power before servicing drive. Capacitors retain charge after power is removed. Drive assembly includes externally mounted current limiting resistors. Use extreme caution when servicing the drive. Failure to comply could result in possible personal injury. B C A + DPTA - B C + A - SPTA a30-4975 WARNING LEGEND Accessory Discharge Pressure Transducer Leaving Water Temperature Sensor Low Voltage Terminal Outdoor Air Temperature Sensor Return Gas Temperature Sensor Sensor Terminal Block Space Temperature Sensor When configured as shown in this literature, this equipment is designed to start when it receives line power. Ensure that all personnel are clear of fans and guards are installed before applying power. Failure to comply could result in possible personal injury. CAUTION Fig. 29 — Thermistor Connections to Main Base Board, J8 Connector DO NOT connect incoming AC power to output terminals T1, T2, and T3. Severe damage to the drive will result. Do not continuously cycle input power to the drive more than once every two minutes. Damage to the drive will result. CAUTION If input power has not been applied to the drive for a period of time exceeding three years (due to storage, etc.), the electrolytic DC bus capacitors within the drive can change internally, resulting in excessive leakage current. This can result in premature failure of the capacitors if the drive is operated after such a long period of inactivity or storage. In order to reform the capacitors and prepare the drive for operation after a long period of inactivity, apply input power to the drive for 8 hours prior to actually operating the motor. Before attempting to operate the drive, motor, and driven equipment, be sure all procedures pertaining to installation and wiring have been properly followed. Failure to comply could result in equipment damage. a30-499 Fig. 30 — Chilled Water Flow Switch GENERAL OPERATION — The speed varies in proportion to a 4 to 20 mA signal produced by the ComfortLink™ controls. The MMV output speed is displayed in Hz. The ComfortLink controls must be configured for MMV operation in order for it to operate. This is configured under the Configuration menu (ConfigurationMMMMR.S) and a30-4976 Fig. 31 — Mounted Fan Position 58 VFD. It should not be removed with power applied to the VFD. LOSS OF CCN COMMUNICATIONS — Carrier Comfort Network® (CCN) communications with external control systems can be affected by high frequency electrical noise generated by the Motormaster V control. Ensure unit is well grounded to eliminate ground currents along communication lines. If communications are lost only while Motormaster V control is in operation, order a signal isolator (CEAS420876-2) and power supplies (CEAS221045-01, 2 required) for the CCN communication line. Fault Codes — The drive is programmed to automatically restart after a fault and will attempt to restart three times after a fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or Fo faults). If all three restart attempts are unsuccessful, the drive will trip into FAULT LOCKOUT (LC), which requires a manual reset. Manual Reset — If fault condition has been removed, cycle power to the chiller to reset the VFD. Troubleshooting — Troubleshooting the Motormaster® V control requires a combination of observing system operation and VFD information. The drive provides 2 kinds of troubleshooting modes: a status matrix using the 3-digit display (P57, P58) and real time monitoring of key inputs and outputs. The collective group is displayed through parameters 50-60 and all values are read-only. • P50: FAULT HISTORY — Last 8 faults • P51: SOFTWARE version • P52: DC BUS VOLTAGE — in percent of nominal. Usually rated input voltage x 1.4 • P53: MOTOR VOLAGE — in percent of rated output voltage • P54: LOAD — in percent of drives rated output current rating • P55: VDC INPUT — in percent of maximum input: 100 will indicate full scale which is 5 v • P56: 4-20 mA INPUT — in percent of maximum input. 20% = 4 mA, 100% = 20 mA Manual Starter Trip — If the VFD manual starter (MS-FCHS, MS-FC-A1 or MS-FC-B1 depending on model) trips, locate the inrush current protectors (3 round black disks per motor) and verify their resistance. For units operating at 208 v or 230 v, these devices should measure approximately 7 ohms. For all other voltages, they should measure approximately 20 ohms. Check value with mating plug disconnected, power to chiller off and at ambient temperature (not hot immediately after stopping VFD). These are standard resistances at 77 F (25 C). Resistance values decrease at higher temperatures and increase at lower temperatures. REPLACING DEFECTIVE MODULES — The ComfortLink™ replacement modules are shown in Table 40. If the main base board (MBB) has been replaced, verify that all configuration data is correct. Follow the Configuration mode table and verify that all items under sub-modes UNIT, OPT1 and OPT2 are correct. Any additional field-installed accessories or options (RSET, SLCT sub-modes) should also be verified as well as any specific time and maintenance schedules. Refer to the Start-Up Checklist for 30RAP Liquid Chillers (completed at time of original start-up) found in the job folder. This information is needed later in this procedure. If the checklist does not exist, fill out the current information in the Configuration mode on a new checklist. Tailor the various options and configurations as needed for this particular installation. selecting “YES”. This configuration menu also contains the gains and minimum speed for the Motormaster control logic. CONFIGURATION — The MMV is configured for 1 of 12 operation modes based on the inputs to the control terminal block. The 30RAP units use operating modes 5-8. In these configurations, the MMV follows a 4 to 20 mA speed reference signal present on terminals 25 (+) and 2 (-). One additional jumper is required to configure the drive for 50/60 Hz operation and input voltage. See Table 39 for proper inputs. Once the drive is powered, it will change to the mode selected according to the inputs. See Fig. 33. DRIVE PROGRAMMING CAUTION It is strongly recommended that the user NOT change any programming without consulting Carrier service personnel. Unit damage may occur from improper programming. To enter password and change program values: 1. Press Mode. 2. Upper right decimal point blinks. 3. Display reads “00”. To enter the PROGRAM mode to access the parameters, press the Mode button. This will activate the PASSWORD prompt (if the password has not been disabled). The display will read “00” and the upper right-hand decimal point will be blinking. (See Fig. 33.) 4. Use the and buttons to scroll to the password value (the factory default password is “1111”) and press the Mode button. Once the correct password value is entered, the display will read “P01”, which indicates that the PROGRAM mode has been accessed at the beginning of the parameter menu (P01 is the first parameter). NOTE: If the display flashes “Er”, the password was incorrect, and the process to enter the password must be repeated. 5. Press Mode to display present parameter number. Upper right decimal point blinks. Use the and buttons to scroll to the desired parameter number. Once the desired parameter number is found, press the Mode button to display the present parameter setting. The upper right-hand decimal point will begin blinking, indicating that the present parameter setting is being displayed, and that it can be changed by using the up and down buttons. Use and to change setting. Press Mode to store new setting. Pressing the Mode will store the new setting and also exit the PROGRAM mode. To change another parameter, press the Mode key again to re-enter the PROGRAM mode (the parameter menu will be accessed at the parameter that was last viewed or changed before exiting). If the Mode key is pressed within two minutes of exiting the PROGRAM mode, the password is not required to access the parameters. After two minutes, the password must be entered in order to access the parameters again. To change password: first enter the current password then change parameter P44 to the desired password. To disable automatic control mode and enter manual speed control mode: 1. Change P05 to ‘01- keypad’. 2. Push UP and DOWN arrow key to set manual speed. 3. Set P05 to ‘04 - 4-20mA control’ to restore 4 to 20 mA control. EPM CHIP — The drive uses a electronic programming module (EPM) chip to store the program parameters. This is an EEPROM memory chip and is accessible from the front of the 59 LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY MM-A FB1 FB3 1 BLK 11 21 BLK 11 21 BLK L1 T1 BLK-1 YEL 12 22 YEL 12 22 YEL L2 T2 BLK-2 BLU 13 BLU 23 13 L3 BLU 23 T3 VIO 11 *1 25 240 1/4W 2 FB2 BLK 11 21 BLK 11 YEL 12 22 YEL 12 BLU 13 23 BLU 13 22 BLK-2 BLK-3 BLK WHT LEGEND Auxiliary Fuse Block Motormaster Outdoor Fan Motor Terminal Block 8 6 BLK VOLTAGE HZ 1 208/230/460/575 60 13A 380 60 1 2 OFM2 3 1 GRN/YEL 3 2 BLK BLK COOLER/PUMP HEATERS (208/230,230V) ~ — — — — — YEL ~ ~ CHC a30-4977 AUX FB MM OFM TB COOLER/PUMP HEATERS (380,460,575V) TB ~ 2 ~ ~ 4 * MM SIGNAL CONNECTION FROM AUX-J4 BLK-1 CHC BLK RED 21 23 GRN/YEL MMR 14 BLK FC2 OFM1 3 BLK-3 YEL 2 HIGH SCCR ONLY 2 WHT 1 2 3 CONFIGURATION TABLE MODE NOMINAL VOLTAGE Hz 5 6 208/230/460/575* 208/380 60 60 CONTROL INPUT (PINS 25, 2) External control 4-20 mA External control 4-20 mA *208-v can run in mode 5 or 6. Fig. 32 — Typical Motormaster Wiring EPM L1 L2 L3 Mode DANGER MMV TERMINAL BLOCK T1 T2 T3 B- B+ DISPLAY BUTTONS Mode Fig. 33 — Motormaster® V Mode Buttons and Mode Display 60 START JUMPER TB1-TB2 TB13A-TB2 Table 38 — Fault Codes FAULT CODE AF CF cF CL CURRENT LIMIT: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing the output frequency to reduce the output current. If the drive remains in CURRENT LIMIT too long, it can trip into a CURRENT OVERLOAD fault (PF). Data Fault: User data and OEM defaults in the EPM are corrupted. High DC Bus Voltage Fault: Line voltage is too high; Deceleration rate is too fast; Overhauling load. Serial Fault: The watchdog timer has timed out, indicating that the serial link has been lost. GF HF JF LF OF Low DC Bus Voltage Fault: Line voltage is too low. Output Transistor Fault: Phase to phase or phase to ground short circuit on the output; Failed output transistor; Boost settings are too high; Acceleration rate is too fast. Current Overload Fault: VFD is undersized for the application; Mechanical problem with the driven equipment. PF SF F1 F2-F9, Fo Drive display = 60.0 even though it is cold outside and it should be running slower Drive display = ‘---’ even though drive should be running Drive display = 8.0 even though fan should be running faster VFD flashes 57 and LCS EPM LCS OEM VFD DESCRIPTION High Temperature Fault: Ambient temperature is too high; Cooling fan has failed (if equipped). Control Fault: A blank EPM, or an EPM with corrupted data has been installed. Incompatibility Fault: An EPM with an incompatible parameter version has been installed. — — — — Single-phase Fault: Single-phase input power has been applied to a three-phase drive. EPM Fault: The EPM is missing or damaged. Internal Faults: The control board has sensed a problem Feedback signal is above set point SOLUTION Check cooling fan operation Perform a factory reset using Parameter 48 — PROGRAM SELECTION. Either remove the EPM or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the parameter version of the drive. Check for loose electrical connections. Check for faulty condenser fan motor. Check Parameter P25 from Table 39 is set correctly. Restore factory defaults P48, see section above. If that does not work, replace EPM. Check line voltage — set P01 appropriately Check serial connection (computer) Check settings for PXX. Check settings in communication software to match PXX. Check line voltage — set P01 appropriately Reduce boost or increase acceleration values. If unsuccessful, replace drive. Check line voltage — set P01 appropriately Check for dirty coils Check for motor bearing failure Check input power phasing Consult factory Check for proper set point Check liquid line pressure Start jumper is missing Replace start jumper. See section above Feedback signal is below set point and fan is at minimum speed Feedback or speed signal lost. Drive will operate at 57 Hz until reset or loss of start command. Resetting requires cycling start command (or power). Check for proper set point Check liquid line pressure In stand alone mode: Check transducer wiring and feedback voltage. Feedback voltage displayed on P-69. Pin 6 should be 5 v output. Pin 5 (feedback) should be somewhere between 0 and 5 v. LEGEND Electronic Programming Module Lost Control Signal Outside Equipment Manufacturer Variable Frequency Drive 61 Table 39 — Motormaster® V Program Parameters for Operating Modes PARAMETERS P01 P02 P03 P04 P05 P06 P08 P09 P10 P11 P12 P13 P14 P15 P16 P17 P19 P20 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30 P31 P32 P33 P34 P35 P36 P37 P38 P39 P40 P41 P42 P43 P44 P45 P46 P47 P48 P61 P62 P63 P64 P65 P66 P67 P68 DESCRIPTION Line Voltage: 01 = low line, 02 = high line Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz Startup mode: flying restart Stop mode: coast to stop Standard Speed source: 01= keypad, 04=4-20mA (NO PI), 05= R22, 06=R134a TB-14 output: 01 = none TB-30 output: 01 = none TB-31 Output: 01 = none TB-13A function sel: 01 = none TB-13B function sel: 01 = none TB-13C function sel: 01 = none TB-15 output: 01 = none Control: 01 = Terminal strip Serial link: 02 = enabled 9600,8,N,2 with timer Units editing: 02 = whole units Rotation: 01 = forward only, 03 = reverse only Acceleration time: 10 sec Deceleration time: 10 sec DC brake time: 0 DC BRAKE VOLTAGE 0% Min freq = 8 Hz ~ 100 – 160 rpm Max freq Current limit: (%) Motor overload: 100 Base freq: 60 or 50 Hz Fixed boost: 0.5% at low frequencies Accel boost: 0% Slip compensation: 0% Preset spd #1: speed if loss of control signal Preset spd #2: 0 Preset spd #3: 0 Preset spd 4 default — R22 set point. TB12-2 open Preset spd 5 default — R134a set point. TB12-2 closed Preset spd 6 default Preset spd 7 default Skip bandwidth Speed scaling Frequency scaling 50 or 60 Hz Load scaling: default (not used so NA) Accel/decel #2: default (not used so NA) Serial address Password:111 Speed at min signal: 8 Hz; used when PID mode is disabled and 4-20mA input is at 4 mA Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20mA input is at 20 mA Clear history? 01 = maintain. (set to 02 to clear) Program selection: Program 1 – 12 PI Mode: 05= reverse, 0-5V, 01 = no PID Min feedback = 0 (0V *10) Max feedback = 50 (5V * 10) Proportional gain = 4% Integral gain = .2 PI acell/decel (set point change filter) = 5 Min alarm Max alarm LEGEND NA — Not Applicable PID — Proportional Integral Derivative TB — Terminal Block 62 MODE 5 01 01 06 01 MODE 6 02 01 06 01 MODE 7 01 01 06 01 MODE 8 02 01 06 01 04 04 04 04 01 01 01 01 01 01 01 01 02 02 01 10 10 0 0 8 60 125 100 60 0.5 0 0 57 0 0 01 01 01 01 01 01 01 01 02 02 01 10 10 0 0 8 60 110 100 60 0.5 0 0 57 0 0 01 01 01 01 01 01 01 01 02 02 01 10 10 0 0 8 50 125 100 50 0.5 0 0 47 0 0 01 01 01 01 01 01 01 01 02 02 01 10 10 0 0 8 50 110 100 50 0.5 0 0 47 0 0 18.0 18.0 18.0 18.0 12.6 12.6 12.6 12.6 0 0 0 0 60 200 60 1 111 0 0 0 0 60 200 60 1 111 0 0 0 0 50 200 60 1 111 0 0 0 0 50 200 60 1 111 8 8 8 8 60 60 50 50 01 05 01 0 50 4 .2 5 0 0 01 06 01 0 50 4 .2 5 0 0 01 07 01 0 50 4 .2 5 0 0 01 08 01 0 50 4 .2 5 0 0 uncommon for actual pump duty to be different than what was anticipated at time of selection. In many cases, it may be desirable to make some field modifications to obtain optimum pump performance. Before any pump modifications are made, it is recommended that actual pump performance be verified and compared to the applicable pump curve. See base unit installation instructions. This can be done in a variety of ways: 1. If pump impeller diameter is known: a. Connect a differential pressure gage across the pump at the ports provided on the pump volutes. b. Read GPM from applicable impeller curve. 2. If pump impeller diameter is not known: If pump impeller diameter has been trimmed and the size is not known, it is necessary to determine which impeller curve to read. The easiest way to confirm pump performance is to “dead-head” the pump and read the differential pressure across the pressure ports on the pump. “Dead-heading” can be done by shutting the circuit setter valve on the discharge side of the pump. NOTE: Although not all pumps can be safely “deadheaded”, centrifugal pumps (such as on the 30RAP units) can be “dead-headed” for short amounts of time. It is recommended to keep the time short due to excessive heat build-up in the pump. Since the “dead-head” condition is a no-flow condition, the head will correspond to the intersection of an impeller curve with the vertical axis of the pump chart. The correct impeller diameter is that which corresponds to the measured head. 3. Once the impeller diameter is known, proceed as in Step 1. 4. Water flow rate can be determined by using a differential pressure gage with the Bell & Gossett circuit setter balance valve calculator. (This information is also provided in the installation instructions.) This method will not directly measure pressure differential seen by the pump, but can be used to “double-check” the pump measurement. 5. Verify that cable connections at the switch and at the terminal block are secure. 6. For factory-installed hydronic system, verify that: • All air has been purged from the system. • Circuit setter balance valve has been correctly set. 7. Pump impeller has been improperly trimmed and is not providing sufficient flow. 8. Wrong pump motor rotation. Pump must rotate clockwise when viewed from motor end of pump. PUMP MODIFICATIONS AND IMPELLER TRIMMING — See applicable section in the Installation instructions. RESET OF CHILLER WATER FLOW — See applicable section in the Installation instructions. CHANGING OF PUMP SEALS — See Bell & Gossett service instruction manual provided with the hydronic package. WARNING Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed. 1. Check that all power to unit is off. Carefully disconnect all wires from the defective module by unplugging its connectors. 2. Remove the defective module by removing its mounting screws with a Phillips screwdriver, and removing the module from the control box. Save the screws later use. 3. Verify that the instance jumper (MBB) or address switches (all other modules) exactly match the settings of the defective module. NOTE: Handle boards by mounting standoffs only to avoid electrostatic discharge. 4. Package the defective module in the carton of the new module for return to Carrier. 5. Mount the new module in the unit’s control box using a Phillips screwdriver and the screws saved in Step 2. 6. Reinstall all module connectors. For accessory Navigator replacement, make sure the plug is installed at TB3 in the LEN connector. 7. Carefully check all wiring connections before restoring power. 8. Verify the ENABLE/OFF/REMOTE CONTACT switch is in the OFF position. 9. Restore control power. Verify that all module red LEDs blink in unison. Verify that all green LEDs are blinking and that the scrolling marquee or Navigator™ display is communicating correctly. 10. Verify all configuration information, settings, set points and schedules. Return the ENABLE/OFF/REMOTE CONTACT switch to its previous position. Table 40 — Replacement Modules MODULE Main Base Board (MBB) Scrolling Marquee Display Energy Management Module (EMM) Navigator Display EXV AUX REPLACEMENT PART NO. (with Software) REPLACEMENT PART NO. (without Software) 30RA502134 HK50AA029 HK50AA031 HK50AA030 30GT515218 HK50AA028 HK50AA033 N/A 30GT515217 32GB500442E HK50AA026 N/A Hydronic Package — If the unit is equipped with a factory-installed hydronic package, consult the information below for proper maintenance and service. In addition to this information, each factory-installed hydronic package is supplied with a packet of information supplied by the manufacturer, Bell & Gossett. Carrier Corporation strongly recommends that this information be thoroughly reviewed prior to operation of the chiller. PUMP PERFORMANCE CHECK — The factory-installed pumps in the 30RAP units are shipped with a single impeller size available for that pump. The pump was selected based on the flow and head requirements as provided to Carrier. It is not MAINTENANCE Recommended Maintenance Schedule — The fol- lowing are only recommended guidelines. Jobsite conditions may dictate that maintenance schedule is performed more often than recommended. Routine: For machines with e-coat condenser coils: • Periodic clean water rinse, especially in coastal and industrial applications. 63 core face. Reduce pressure and use caution to prevent damage to air centers. • Check condenser coils for debris, clean as necessary. Every month: • Check moisture indicating sight glass for possible refrigerant loss and presence of moisture. Every 3 months (for all machines): • Check refrigerant charge. • Check all refrigerant joints and valves for refrigerant leaks, repair as necessary. • Check chilled water flow switch operation. • Check all condenser fans for proper operation. • Check compressor oil level. Every 12 months (for all machines): • Check all electrical connections, tighten as necessary. • Inspect all contactors and relays, replace as necessary. • Check accuracy of thermistors, replace if greater than ± 2° F (1.2° C) variance from calibrated thermometer. • Obtain and test an oil sample. Change oil only if necessary. • Check to be sure that the proper concentration of antifreeze is present in the chilled water loop, if applicable. • Verify that the chilled water loop is properly treated. • Check refrigerant filter driers for excessive pressure drop, replace as necessary. • Check chilled water strainers, clean as necessary. • Check cooler heater operation, if equipped. • Check condition of condenser fan blades and that they are securely fastened to the motor shaft. • Perform Service Test to confirm operation of all components. • Check for excessive cooler approach (Leaving Chilled Water Temperature — Saturated Suction Temperature) which may indicate fouling. Clean cooler vessel if necessary. CAUTION Excessive water pressure will fracture the braze between air centers and refrigerant tubes. TROUBLESHOOTING Complete Unit Stoppage and Restart — Possible causes for unit stoppage and reset methods are shown below and in Table 41. Refer to Fig. 3-7 for component arrangement and control wiring diagrams. GENERAL POWER FAILURE — After power is restored, restart is automatic through normal MBB start-up. UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS OFF — When the switch is OFF, the unit will stop immediately. Place the switch in the ENABLE position for local switch control or in the REMOTE CONTACT position for control through remote contact closure. CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN — After the problem causing the loss of flow has been corrected, reset is manual by resetting the alarm with the scrolling marquee as shown in Table 42. OPEN 24-V CONTROL CIRCUIT BREAKER(S) — Determine the cause of the failure and correct. Reset circuit breaker(s). Restart is automatic after MBB start-up cycle is complete. COOLING LOAD SATISFIED — Unit shuts down when cooling load has been satisfied. Unit restarts when required to satisfy leaving fluid temperature set point. THERMISTOR FAILURE — If a thermistor fails in either an open or shorted condition, the unit will be shut down. Replace EWT, LWT, or OAT as required. Unit restarts automatically, but must be reset manually by resetting the alarm with the scrolling marquee as shown in Table 42. Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning Recommendations CAUTION CAUTION Do not apply any chemical cleaners to MCHX condenser coils. These cleaners can accelerate corrosion and damage the coil. If unit stoppage occurs more than once as a result of any of the safety devices listed, determine and correct cause before attempting another restart. Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following steps should be taken to clean MCHX condenser coils: 1. Remove any foreign objects or debris attached to the coreface or trapped within the mounting frame and brackets. 2. Put on personal protective equipment including safety glasses and/or face shield, waterproof clothing and gloves. It is recommended to use full coverage clothing. 3. Start high pressure water sprayer and purge any soap or industrial cleaners from sprayer before cleaning condenser coils. Only clean, potable water is authorized for cleaning condenser coils. 4. Clean condenser face by spraying the core steady and uniformly from top to bottom while directing the spray straight toward the core. Do not exceed 900 psig or 30 degree angle. The nozzle must be at least 12 in. from the LOW SATURATED SUCTION — Several conditions can lead to low saturated suction alarms and the chiller controls have several override modes built in which will attempt to keep the chiller from shutting down. Low fluid flow, low refrigerant charge and plugged filter driers are the main causes for this condition. To avoid permanent damage and potential freezing of the system, do NOT repeatedly reset these alert and/or alarm conditions without identifying and correcting the cause(s). COMPRESSOR SAFETIES — The 30RAP units with ComfortLink™ controls include a compressor protection board that protects the operation of each of the compressors. Each board senses the presence or absence of current to each compressor. If there is a command for a compressor to run and there is no current, then one of the following safeties or conditions have turned the compressor off: Compressor Overcurrent — All compressors have internal line breaks or a motor protection device located in the compressor electrical box. Compressor Short Circuit — There will not be current if the compressor circuit breaker that provides short circuit protection has tripped. Compressor Motor Over Temperature — The internal linebreak or over temperature switch has opened. 64 High-Pressure Switch Trip — The high pressure switch has opened. Below are the factory settings for the fixed high pressure switch. 30RAP UNIT SIZE 010-060 CUTOUT psig 650 reset automatically before the motor protector resets, which may take up to 2 hours. High Discharge Gas Temperature Protection — Units equipped with digital compressors have an additional thermistor located on the discharge line, If discharge temperature exceeds 265 F (129.4 C), the digital compressor will be shut off. Alarms will also occur if the current sensor board malfunctions or is not properly connected to its assigned digital input. If the compressor is commanded OFF and the current sensor reads ON, an alert is generated. This will indicate that a compressor contactor has failed closed. In this case, a special mode, Compressor Stuck on Control, will be enabled and all other compressors will be turned off. An alarm will then be enabled to indicate that service is required. Outdoor fans will continue to operate. The first outdoor fan stage is turned on immediately. The other stages of fan will be turned on as required by SCT. CUT-IN kPa 4482 psig 500 kPa 3447 ASTP Protection Trip — All non-digital Copeland compressors are equipped with an advanced scroll temperature protection (ASTP). A label located above the terminal box identifies models that contain this technology. See Fig. 34. Alarms and Alerts — These are warnings of abnormal or fault conditions, and may cause either one circuit or the whole unit to shut down. They are assigned code numbers as described in Table 42. Automatic alarms will reset without operator intervention if the condition corrects itself. The following method must be used to reset manual alarms: Before resetting any alarm, first determine the cause of the alarm and correct it. Enter the Alarms mode indicated by the LED on the side of the scrolling marquee display. Press until the sub-menu item RCRN “RESET ENTER and ALL CURRENT ALARMS” is displayed. Press ENTER . The control will prompt the user for a password, by displaying PASS and WORD. Press ENTER to display the default password, 1111. Press ENTER for each character. If the password has been changed, use the arrow keys to change each individual character. Toggle the display to “YES” and press ENTER . The alarms will be reset. Recommended Cooling Time (Minutes) Fig. 34 — Advanced Scroll Temperature Protection Label Advanced scroll temperature protection is a form of internal discharge temperature protection that unloads the scroll compressor when the internal temperature reaches approximately 300 F. At this temperature, an internal bi-metal disk valve opens and causes the scroll elements to separate, which stops compression. Suction and discharge pressures balance while the motor continues to run. The longer the compressor runs unloaded, the longer it must cool before the bi-metal disk resets. See Fig. 35 for approximate reset times. To manually reset ASTP, the compressor should be stopped and allowed to cool. If the compressor is not stopped, the motor will run until the motor protector trips, which occurs up to 90 minutes later. Advanced scroll temperature protection will 120 110 100 90 80 70 60 50 40 30 20 10 0 0 10 20 30 40 50 60 70 80 90 Compressor Unloaded Run Time (Minutes) *Times are approximate. NOTE: Various factors, including high humidity, high ambient temperature, and the presence of a sound blanket will increase cool-down times. Fig. 35 — Recommended Minimum Cool Down Time After Compressor is Stopped* 65 Table 41 — Troubleshooting SYMPTOMS Cooler Circulating Pump Does Not Run CAUSE Power line open Control fuse or circuit breaker open REMEDY Reset circuit breaker. Check control circuit for ground or short. Reset breaker and replace fuse. Check the controls. Find the cause of trip and reset breaker. Check connections. Check wiring and rewire if necessary. Check line voltage — determine location of voltage drop and remedy deficiency. Check motor winding for open or short. Replace compressor if necessary. Replace pump. Repair leak and recharge. Tripped power breaker Loose terminal connection Improperly wired controls Low line voltage Pump motor defective Compressor Cycles Off on Loss of Charge Compressor Cycles Off on Cooler Freeze Protection Compressor Shuts Down on High-Pressure Control Unit Operates Too Long or Continuously Unusual or Loud System Noises Pump seized Low refrigerant charge Thermistor failure System load was reduced faster than controller could remove stages High-pressure control acting erratically Noncondensables in system Condenser dirty Fans not operating System overcharged with refrigerant Low refrigerant charge Control contacts fused Partially plugged or plugged expansion valve or filter drier Defective insulation Damaged compressor Piping vibration Compressor noisy Compressor Loses Oil Hot Liquid Line Frosted Liquid Line Frosted Suction Line Freeze-Up Leak in system Mechanical damage (Failed seals or broken scrolls) Oil trapped in line Shortage of refrigerant due to leak Restricted filter drier Expansion valve admitting excess refrigerant (note: this is a normal condition for brine applications) Stuck EXV Improper charging System not drained for winter shutdown Loose Thermistor 66 Replace thermistor. Unit will restart after fluid temperature rises back into the control band. Avoid rapidly removing system load. Replace control. Evacuate and recharge. Clean condenser. Repair or replace if defective. Reduce charge. Add refrigerant. Replace control. Clean or replace as needed. Replace or repair as needed. Check compressor and replace if necessary. Support piping as required. Check for loose pipe connections or damaged compressor Replace compressor (worn bearings). Check for loose compressor holddown bolts. Repair leak. Replace compressor. Check piping for oil traps. Repair leak and recharge. Replace filter drier. Replace valve if defective. Replace valve if defective. Make sure a full quantity of fluid is flowing through the cooler while charging, and suction pressure in cooler is equal to or greater than pressure corresponding to 32 F (0° C). Recommended that system be filled with an appropriate glycol mixture to prevent freezing of pumps and fluid tubing. Verify thermistors are fully inserted in wells. Table 42 — Alarm and Alert Codes ALARM/ ALERT CODE ALARM OR ALERT DESCRIPTION WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD PROBABLE CAUSE Compressor feedback signal does not match relay state Compressor A1 shut down. Manual High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, noncondensables, operation beyond capability. T051 Alert Circuit A, Compressor 1 Failure A051 Alarm Circuit A, Compressor 1 Failure Respective current sensor board (CSB) feedback signal is ON when the compressor should be off Unit shut down Manual Welded compressor contactor, CSB wiring error. T052 Alert Circuit A, Compressor 2 Failure Compressor feedback signal does not match relay state Compressor A2 shut down. Manual High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, noncondensables, operation beyond capability. A052 Alarm Circuit A, Compressor 2 Failure Respective current sensor board (CSB) feedback signal is ON when the compressor should be off Unit shut down Manual Welded compressor contactor, CSB wiring error. T055 Alert Circuit B, Compressor 1 Failure Compressor feedback signal does not match relay state Compressor B1 shut down. Manual High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, noncondensables, operation beyond capability. A055 Alarm Circuit B, Compressor 1 Failure Respective current sensor board (CSB) feedback signal is ON when the compressor should be off Unit shut down Manual Welded compressor contactor, CSB wiring error. T056 Alert Circuit B, Compressor 2 Failure Compressor feedback signal does not match relay state Compressor B2 shut down. Manual High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, noncondensables, operation beyond capability. A056 Alarm Circuit B, Compressor 2 Failure Respective current sensor board (CSB) feedback signal is ON when the compressor should be off Unit shut down Manual Welded compressor contactor, CSB wiring error. A060 Alarm Cooler Leaving Fluid Thermistor Failure Thermistor outside range of –40 to 245 F (–40 to 118 C) Chiller shut down immediately failure, damaged Automatic Thermistor cable/wire or wiring error. A061 Alarm Cooler Entering Fluid Thermistor Failure Thermistor outside range of –40 to 245 F (–40 to 118 C) Chiller shut down immediately failure, damaged Automatic Thermistor cable/wire or wiring error. T068 None Circuit A Return Gas Thermistor Failure If return gas sensors are enabled (RG.EN) and thermistor is outside range of –40 to 245 F (–40 to 118 C) Circuit A shut down Thermistor failure, damaged Automatic cable/wire or wiring error. T069 None Circuit B Return Gas Thermistor Failure If return gas sensors are enabled (RG.EN) and thermistor is outside range of –40 to 245 F –40 to 118 C) Circuit B shut down failure, damaged Automatic Thermistor cable/wire or wiring error. failure, damaged Automatic Thermistor cable/wire or wiring error. T073 Alert Outside Air Thermistor Failure Thermistor outside range of –40 to 245 F (–40 to 118 C) Temperature reset disabled. Chiller runs under normal control/set points. When capacity reaches 0, cooler/pump heaters are energized. T074 Alert Space Temperature/Dual Chiller Thermistor Failure Thermistor outside range of –40 to 245 F (–40 to 118 C) Temperature reset disabled. Chiller runs under normal control/set points. Automatic Thermistor failure, damaged cable/wire or wiring error. T077 Alert Circuit A Saturated Suction Temperature exceeds Cooler Leaving Fluid Temperature Faulty expansion valve, suction pressure transducer or leaving fluid thermistor. Circuit A shutdown after pumpdown complete. Faulty expansion valve or suction pressure transducer Automatic or leaving fluid thermistor. T078 Alert Circuit B Saturated Suction Temperature exceeds Cooler Leaving Fluid Temperature Faulty expansion valve, suction pressure transducer or leaving fluid thermistor. Circuit B shutdown after pumpdown complete Faulty expansion valve or pressure transducer Automatic suction or leaving fluid thermistor. T079 Alert Lead/Lag LWT Thermistor Failure Thermistor outside range of –40 to 245 F (–40 to 118 C) Chiller runs as a stand alone machine Dual LWT thermistor failure, Automatic damaged cable/wire or wiring error. T090 Alert Circuit A Discharge Pressure Transducer Failure Outside of range (0 to 667 psig) Circuit A shut down Transducer failure, poor Automatic connection to MBB, or wiring damage/error. T091 Alert Circuit B Discharge Pressure Transducer Failure Outside of range (0 to 667 psig) Circuit B shut down Transducer failure, poor Automatic connection to MBB, or wiring damage/error. T092 Alert Circuit A Suction Pressure Transducer Failure Outside of range (0 to 420 psig) Circuit A shut down Transducer failure, poor Automatic connection to MBB, or wiring damage/error. T093 Alert Circuit B Suction Pressure Transducer Failure Outside of range (0 to 420 psig) Circuit B shut down Transducer failure, poor Automatic connection to MBB, or wiring damage/error. T094 Alert Discharge Gas Thermistor Failure Discharge thermistor (DTT) is either open or shorted Digital compressor shut down. failure, damaged Automatic Thermistor cable/wire or wiring error. 67 Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT T110 Alert Circuit A Loss of Charge If the compressors are off and discharge pressure reading is < 26 psig for 30 sec. Circuit not allowed to start. Manual Refrigerant leak or transducer failure T111 Alert Circuit B Loss of Charge If the compressors are off and discharge pressure reading is < 26 psig for 30 sec. Circuit not allowed to start. Manual Refrigerant leak or transducer failure T112 Alert Circuit A High Saturated Suction Temperature Circuit saturated suction temperature pressure transducer > 70 F (21.1 C) for 5 minutes Circuit shut down Manual Faulty Expansion valve, faulty suction pressure transducer or high entering fluid temperature. T113 Alert Circuit B High Saturated Suction Temperature Circuit saturated suction temperature pressure transducer > 70 F (21.1 C) for 5 minutes Circuit shut down Manual Faulty Expansion valve, faulty suction pressure transducer or high entering fluid temperature. T114 Alert Circuit A Low Suction Superheat Suction superheat is less than 5° F (2.8 C) for 5 minutes. T115 Alert Circuit B Low Suction Superheat Suction superheat is less than 5° F (2.8 C) for 5 minutes. T116 Alert Circuit A Low Cooler Suction Temperature Mode 7 caused the compressor to unload 6 consecutive times with less than a Circuit shut down 30-minute interval between each circuit shutdown. T117 Alert Circuit B Low Cooler Suction Temperature Mode 8 caused the compressor to unload 6 consecutive times with less than a Circuit shut down 30-minute interval between each circuit shutdown. T118 Alert High Discharge Gas Temperature Alert Discharge Thermistor (DTT) Compressor A1 shut reading is greater than 250 F down A118 Alarm High Discharge Gas Temperature 3 Discharge Gas Temperature alarms occur within a day T126 Alert DESCRIPTION Circuit A High Discharge Pressure WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL Compressor operation outside of operating envelope. RESET METHOD PROBABLE CAUSE Circuit A shut down. Automatic restart after first daily occurrence. Manual restart thereafter. Faulty expansion valve, faulty suction pressure transducer, faulty suction gas thermistor, circuit overcharged Circuit B shut down. Automatic restart after first daily occurrence. Manual restart thereafter. Faulty expansion valve, faulty suction pressure transducer, faulty suction gas thermistor, circuit overcharged Compressor A1 shut down Manual Faulty expansion valve, low refrigerant charge, plugged filter drier, faulty suction pressure transducer, low cooler fluid flow Manual Faulty expansion valve, low refrigerant charge, plugged filter drier, faulty suction pressure transducer, low cooler fluid flow Automatic Refrigerant charge, plugged filter drier, head pressure control. Manual Refrigerant charge, plugged filter drier, head pressure control. Circuit shut down Automatic, only after first 3 daily occurrences. Manual reset thereafter. Reading from OAT sensor must drop 5 F (2.8 C) before restart Faulty transducer/high pressure switch, low/ restricted condenser airflow Circuit shut down Automatic, only after first 3 daily occurrences. Manual reset thereafter. Reading from OAT sensor must drop 5 F (2.8 C) before restart Faulty transducer/high pressure switch, low/ restricted condenser airflow Circuit shut down Automatic restart after first daily occurrence. Manual restart thereafter. Faulty or sticking EXV, low refrigerant charge, plugged filter drier. Faulty or sticking EXV, low refrigerant charge, plugged filter drier. Alert Circuit B High Discharge Pressure Compressor operation outside of operating envelope. Alert Circuit A Low Suction Pressure Suction pressure below 34 psig for 8 seconds or below 23 psig T134 Alert Circuit B Low Suction Pressure Suction pressure below 34 psig for 8 seconds or below 23 psig Circuit shut down Automatic restart after first daily occurrence. Manual restart thereafter. A140 Alert Reverse Rotation Detected Incoming chiller power leads not phased correctly Chiller not allowed to start. Manual Reverse any two incoming power leads to correct. Check for correct fan rotation first. A150 Alarm Emergency Stop CCN emergency stop command received Chiller shutdown without going through pumpdown. Automatic once CCN command for EMSTOP returns to normal CCN Network command. A151 Alarm Illegal Configuration One or more illegal configurations exists. Chiller is not allowed to start. Manual once configuration errors are corrected Configuration error. Check unit settings. Alarm Unit Down Due to Failure Both circuits are down due to alarms/alerts. Chiller is unable to run. Automatic once alarms/alerts are cleared that prevent the chiller from starting. Alarm notifies user that chiller is 100% down. T127 T133 A152 68 Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD T153 Alert Real Time Clock Hardware Failure Internal clock on MBB fails Occupancy schedule will not be used. Chiller defaults to Local On mode. Automatic when correct clock control restarts. Time/Date/Month/ Day/Year not properly set. A154 Alarm Serial EEPROM Hardware Failure Hardware failure with MBB Chiller is unable to run. Manual Main Base Board failure. T155 Alert Serial EEPROM Storage Failure Configuration/storage failure with MBB No Action Manual Potential failure of MBB. Download current operating software. Replace MBB if error occurs again. A156 Alarm Critical Serial EEPROM Storage Failure Configuration/storage failure with MBB Chiller is not allowed to run. Manual Main Base Board failure. A157 Alarm A/D Hardware Failure Hardware failure with peripheral device Chiller is not allowed to run. Manual Main Base Board failure. A172 Alarm Loss of Communication with EXV Board MBB loses communication with EXV board Chiller is not allowed to run. Automatic Wiring error, faulty wiring or failed EXV board. Automatic Wiring error, faulty wiring or failed Energy Management Module (EMM). Automatic Faulty signal generator, wiring error, or faulty EMM. Automatic Wiring error, faulty wiring or failed AUX board. DESCRIPTION PROBABLE CAUSE T173 Alert Loss of Communication with EMM MBB loses communication with EMM 4 to 20 mA temperature reset disabled. Demand Limit set to 100%. 4 to 20 mA set point disabled. T174 Alert 4 to 20 mA Cooling Set Point Input Failure If configured with EMM and input less than 2 mA or greater than 22 mA Set point function disabled. Chiller controls to CSP1. T175 Alert Loss of Communication with the AUX Board MBB loses communication with AUX Board. T176 Alert 4 to 20 mA Temperature Reset Input Failure If configured with EMM and input less than 2 mA or greater than 22 mA Reset function disabled. Chiller returns to normal set point control. Automatic Faulty signal generator, wiring error, or faulty EMM. Alert 4 to 20 mA Demand Limit Input Failure If configured with EMM and input less than 2 mA or greater than 22 mA Demand limit function disabled. Chiller returns to 100% demand limit control. Automatic Faulty signal generator, wiring error, or faulty EMM. Both pump outputs are turned off. Manual Wiring error, faulty pump contactor auxiliary contacts. T177 A189 Alarm Cooler Pump Auxiliary Contact Inputs Miswired Pump 1 Auxiliary Contacts are closed when Pump 2 output is energized or if Pump 2 Auxiliary Contacts are closed when Pump 1 output is energized. T190 Alert Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Pump 1 Auxiliary Contacts did not close within 26 seconds after pump was started Pump 1 turned off. Pump 2 will be started if available. Manual Wiring error, faulty contacts on pump contactor T191 Alert Cooler Pump 2 Aux Contacts Failed to Close at Start-Up Pump 2 Auxiliary Contacts did not close within 26 seconds after pump was started Pump 2 turned off. Pump 1 will be started if available. Manual Wiring error, faulty contacts on pump contactor T192 Alert Cooler Pump 1 Failed to Provide Flow at Start-Up Pump 1 did not provide flow to close flow switch within 60 seconds Pump 1 turned off. Pump 2 will be started if available. Manual Wiring error, pump circuit breaker tripped, contactor failure T193 Alert Cooler Pump 2 Failed to Provide Flow at Start-Up Pump 2 did not provide flow to close flow switch within 60 seconds Pump 1 turned off. Pump 2 will be started if available. Manual Wiring error, pump circuit breaker tripped, contactor failure T194 Alert Cooler Pump 1 Aux Contacts Opened During Normal Operation Pump 1 Auxiliary Contacts open for 26 seconds after initially made. All compressors shut down. Pump 1 turned off. Pump 2 will be started if available. Chiller allowed to run if Pump 2 successfully starts. Manual Wiring error, faulty contacts on pump contactor Alert Cooler Pump 2 Aux Contacts Opened During Normal Operation Pump 2 Auxiliary Contacts open for 26 seconds after initially made. All compressors shut down. Pump 2 turned off. Pump 1 will be started if available. Chiller allowed to run if Pump 1 successfully starts. Manual Wiring error, faulty contacts on pump contactor Cooler flow switch contacts open for 3 seconds after initially made All compressors shut down. Pump 1 turned off. Pump 2 will be started if available. Chiller allowed to run if Pump 2 successfully starts and flow switch is closed. Manual Wiring error, pump circuit breaker tripped, contactor failure T195 T196 Alert Flow Lost While Pump 1 Running 69 Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT DESCRIPTION WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD Manual PROBABLE CAUSE T197 Alert Flow Lost While Pump 2 Running Cooler flow switch contacts open for 3 seconds after initially made All compressors shut down. Pump 2 turned off. Pump 1 will be started if available. Chiller allowed to run if Pump 1 successfully starts and flow switch is closed. T198 Alert Cooler Pump 1 Aux Contacts Closed While Pump Off Pump 1 Auxiliary Contacts closed for 26 seconds when pump state is off Chiller not allowed to start Automatic when aux contacts open Wiring error, faulty pump contactor (welded contacts) T199 Alert Cooler Pump 2 Aux Contacts Closed While Pump Off Pump 2 Auxiliary Contacts closed for 26 seconds when pump state is off Chiller not allowed to start Automatic when aux contacts open Wiring error, faulty pump contactor (welded contacts) T200 Alert Cooler Flow/Interlock Contacts Failed to Close at Start-Up Cooler flow switch contacts failed to close within 1 minute (if cooler pump control is enabled) or within 5 minutes (if cooler pump control is not enabled) after start-up Chiller not allowed to start. For models with dual pumps, the second pump will be started if available Manual Wiring error, pump circuit breaker tripped, contactor failure, faulty flow switch or interlock A201 Alarm Cooler Flow/Interlock Contacts Opened During Normal Operation Flow switch opens for at least 3 seconds after being initially closed All compressors shut down. For models with dual pumps, the second pump will be started if available Manual Cooler pump failure, faulty flow switch or interlock, pump circuit breaker tripped A202 Alarm Cooler Pump Interlock Closed When Pump is Off If configured for cooler pump control and flow switch input is closed for 5 minutes while pump output(s) are off Chiller shut down Dual chiller control disabled. Chiller runs as a stand-alone machine. Automatic Wiring error, faulty wiring, failed Slave chiller MBB module, power loss at slave chiller, wrong slave address. Automatic Wiring error, faulty wiring, failed master chiller MBB module, power loss at Master chiller. Automatic CCN Address for both chillers is the same. Must be different. Check CCN.A under the OPT2 sub-mode in Configuration at both chillers. Automatic Building load greater than unit capacity, low water/brine flow or compressor fault. Check for other alarms/alerts. T203 Alert Loss of Communication with Slave Chiller Master chiller MBB loses communication with slave chiller MBB T204 Alert Loss of Communication with Master Chiller Slave chiller MBB loses communication with master chiller MBB Dual chiller control disabled. Chiller runs as a stand-alone machine T205 T206 Automatic when aux contacts open Alert Master and Slave Chiller with Same Address Master and slave chiller have the same CCN address (CCN.A) Dual chiller routine disabled. Master/slave run as stand-alone chillers. Alert High Leaving Chilled Water Temperature LWT read is greater than LCW Alert Limit, Total capacity is 100% and LWT is greater than LWT reading one minute ago Alert only. No action taken. Both EWT and LWT must be at least 6 F (3.3 C) above Brine Freeze point (BR.FZ). Automatic for first, Manual reset thereafter. Manual Wiring error, pump circuit breaker tripped, contactor failure Wiring error, faulty pump contactor (welded contacts) A207 Alarm Cooler Freeze Protection Cooler EWT or LWT is less than Brine Freeze (BR.FZ) Chiller shutdown without going through pumpdown. Cooler pump continues to run a minimum of 5 minutes (if control enabled). A208 Alarm EWT or LWT Thermistor failure Cooler EWT is less than LWT by 3° F (1.7° C) for 1 minute after a circuit is started Chiller shutdown. Cooler pump shut off (if control enabled). Cooler Pump 1 Scheduled Maintenance Due Pump 1 Service Countdown (P.1.DN) expired. Complete pump 1 maintenance and enter 'YES' for Pump 1 Maintenance Done (P.1.MN) item. None Automatic Routine pump maintenance required Cooler Pump 2 Scheduled Maintenance Due Pump 2 Service Countdown (P.2.DN) expired. Complete pump 2 maintenance and enter 'YES' for Pump 1 Maintenance Done (P.2.MN) item. None Automatic Routine pump maintenance required T300 T301 Alert Alert 70 Faulty thermistor, low water flow. Faulty cooler pump, low water flow, plugged fluid strainer. Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT DESCRIPTION WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD PROBABLE CAUSE Alert Strainer Blowdown Scheduled Maintenance Due Strainer Service Countdown (S.T.DN) expired. Complete strainer blowdown and enter 'YES' for Strainer Maintenance Done (S.T.MN) item. None Automatic Routine strainer maintenance required T303 Alert Condenser Coil Maintenance Due Coil Service Countdown (C.L.DN) expired. Complete condenser coil cleaning and enter 'YES' for Coil Maintenance Done (C.L.MN) item. None Automatic Routine condenser coil maintenance required T500 Alert Current Sensor Board A1 Failure Alert occurs when CSB output is a constant high value Compressor A1 shut down Automatic CSB failure. Wiring error. T501 Alert Current Sensor Board A2 Failure Alert occurs when CSB output is a constant high value Compressor A2 shut down Automatic CSB failure. Wiring error. T502 Alert Current Sensor Board A3 Failure Alert occurs when CSB output is a constant high value Compressor A3 shut down Automatic CSB failure. Wiring error. T503 Alert Current Sensor Board B1 Failure Alert occurs when CSB output is a constant high value Compressor B1 shut down Automatic CSB failure. Wiring error. T504 Alert Current Sensor Board B2 Failure Alert occurs when CSB output is a constant high value Compressor B2 shut down Automatic CSB failure. Wiring error. T505 Alert Current Sensor Board B3 Failure Alert occurs when CSB output is a constant high value Compressor B3 shut down Automatic CSB failure. Wiring error. T950 Alert Loss of Communication with Water System Manager No communications have been received by the MBB within 5 minutes of last transmission WSM forces removed. Chiller runs under own control Automatic Failed module, wiring error, failed transformer, loose connection plug, wrong address T951 Alert Loss of Communication with Chillervisor System Manager No communications have been received by the MBB within 5 minutes of last transmission CSM forces removed. Chiller runs under own control Automatic Failed module, wiring error, failed transformer, loose connection plug, wrong address T952 Alert Loss of Communication with Hydronic System Manager No communications have been received by the MBB within 5 minutes of last transmission HSM forces removed. Chiller runs under own control Automatic Failed module, wiring error, failed transformer, loose connection plug, wrong address T302 CCN CSB EEPROM EMM EWT EXV HSM LCW LWT MBB OAT SCT WSM — — — — — — — — — — — — — LEGEND FOR TABLE 42 Carrier Comfort Network Current Sensor Board Electronic Eraseable Programmable Read Only Memory Energy Management Module Entering Fluid Temperature Electronic Expansion Valve Hydronic System Manager Leaving Chilled Water Leaving Fluid Temperature Main Base Board Outdoor-Air Temperature Saturated Condensing Temperature Water System Manager Low Refrigerant Charge — If the compressor operates for an extended period of time with low refrigerant charge, the compressor ASTP device will open, which will cause the compressor to trip on its overload protection device. Circuit Breaker Trip — The compressors are protected from short circuit by a breaker in the control box. Wiring Error — A wiring error might not allow the compressor to start. To check out alerts T051-T056: 1. Turn on the compressor in question using Service Test mode. If the compressor does not start, then most likely the problem is one of the following: HPS open, open internal protection, circuit breaker trip, incorrect safety wiring, or incorrect compressor wiring. 2. If the compressor does start, verify it is rotating in the correct direction. COMPRESSOR FAILURE ALERTS T051, T052 (Circuit A Compresser Failures) T055, T056 (Circuit B Compressor Failures) — Alert codes 051, 052, 055, and 056 are for compressors A1, A2, B1, and B2 respectively. These alerts occur when the current sensor (CS) does not detect compressor current during compressor operation. When this occurs, the control turns off the compressor. If the current sensor board reads OFF while the compressor relay has been commanded ON, an alert is generated. POSSIBLE CAUSES Compressor Overload — Either the compressor internal overload protector is open or the external overload protector (Kriwan module) has activated. The external overload protector modules are mounted in the compressor wiring junction box. Temperature sensors embedded in the compressor motor windings are the inputs to the module. The module is powered with 24 vac from the units main control box. The module output is a normally closed contact that is wired in series with the compressor contactor coil. In a compressor motor overload condition, contact opens, deenergizing the compressor contactor. IMPORTANT: Prolonged operation in the wrong direction can damage the compressor. Correct rotation can be verified by a gage set and looking for a differential pressure rise on start-up. 71 of –40 to 245 F (–40 to 118 C). Failure of this thermistor will disable any elements of the control which requires its use. The cause of the alert is usually a faulty thermistor in the T55, or T58 device, a shorted or open thermistor caused by a wiring error, or a loose connection. T090 (Circuit A Discharge Pressure Transducer Failure) T091 (Circuit B Discharge Pressure Transducer Failure) — Alert codes 090 and 091 are for circuits A and B respectively. These alerts occur when the pressure is outside the range of 0.0 to 667.0 psig. A circuit cannot run when this alert is active. Use the scrolling marquee to reset the alert. The cause of the alert is usually a faulty transducer, faulty 5-v power supply, or a loose connection. T092 (Circuit A Suction Pressure Transducer Failure) T093 (Circuit B Suction Pressure Transducer Failure) — Alert codes 092 and 093 are for circuits A and B respectively. These alerts occur when the pressure is outside the range of 0.0 to 420.0 psig. A circuit cannot run when this alert is active. Use the scrolling marquee to reset the alert. The cause of the alert is usually a faulty transducer, faulty 5-v power supply, or a loose connection. T094 (Discharge Gas Thermistor Failure) — This alert occurs for units which have the digital compressor installed on circuit A. If discharge gas temperature is open or shorted, the circuit will be shutoff. The alert will reset itself when discharge temperature is less than 250 F (121.1 C). The cause of the alert is usually low refrigerant charge or a faulty thermistor. T110 (Circuit A Loss of Charge) T111 (Circuit B Loss of Charge) — Alert codes 110 and 111 are for circuits A and B respectively. These alerts occur when the compressor is OFF and the discharge pressure is less than 26 psig. T112 (Circuit A High Saturated Suction Temperature) T113 (Circuit B High Saturated Suction Temperature) — Alert codes 112 and 113 occur when compressors in a circuit have been running for at least 5 minutes and the circuit saturated suction temperature is greater than 70 F (21.1 C). The high saturated suction alert is generated and the circuit is shut down. T114 (Circuit A Low Superheat) T115 (Circuit B Low Superheat) — Alert codes 114 and 115 occur when the superheat of a circuit is less than 5 F (2.8 C) for 5 continuous minutes. The low superheat alert is generated and the circuit is shut down. T116 (Circuit A Low Cooler Suction Temperature) T117 (Circuit B Low Cooler Suction Temperature) — Alert codes 116 and 117 are for circuits A and B respectively. These alerts are generated if the capacity stages are reduced three times without a 30 minute interval between capacity reductions due to operating mode 7 or mode 8. T118 (High Discharge Gas Temperature Alert) A118 (High Discharge Gas Temperature Alarm) — This alert or alarm occurs for units which have the digital compressor installed on circuit A. If discharge gas temperature is greater than 268 F (131.1 C), the circuit will be shut off. The alert will reset itself when discharge temperature is less than 250 F (121.1 C). If this alert occurs 3 times within a day, the A118 alarm will be generated and the alarm must be reset manually. The cause of the alert is usually low refrigerant charge or a faulty thermistor. T126 (Circuit A High Head Pressure) T127 (Circuit B High Head Pressure) — Alert codes 126 and 127 are for circuits A and B respectively. These alerts occur when the appropriate saturated condensing temperature is greater than the operating envelope shown in Fig 14. Prior to the alert, the control will shut down one compressor on a circuit if that circuit's saturated condensing temperature is greater than the maximum SCT minus 5° F (2.7° C). If SCT continues to IMPORTANT: If the CS is always detecting current, verify that the compressor is on. If the compressor is on, check the contactor and the relay on the MBB. If the compressor is off and there is no current, verify the CSB wiring and replace if necessary. IMPORTANT: Return to Normal mode and observe compressor operation to verify that compressor current sensor is working and condenser fans are energized. COMPRESSOR STUCK ON FAILURE ALARMS Circuit A A051, A052 Circuit B A055, A056 — Alarm codes 051, 052, 055, and 056 are for compressors A1, A2, B1, and B2. These alarms occur when the CSB detects current when the compressor should be off. When this occurs, the control turns off the compressor. If the current sensor board reads ON while the compressor relay has been commanded OFF for a period of 4 continuous seconds, an alarm is generated. These alarms are only monitored for a period of 10 seconds after the compressor relay has been commanded OFF. This is done to facilitate a service technician forcing a relay to test a compressor. In addition, if a compressor stuck failure occurs and the current sensor board reports the compressor and the request off, certain diagnostics will take place as follows: 1. If any of the compressors are diagnosed as stuck on and the current sensor board is on and the request is off, the control will command the condenser fans to maintain normal head pressure. 2. The control will shut-off all other compressors. The possible causes include welded contactor or frozen compressor relay on the MBB. To check out alarms A051-A056: 1. Place the unit in Service Test mode. All compressors should be off. 2. Verify that there is not 24-v at the contactor coil. If there is 24 v at the contactor, check relay on MBB and wiring. 3. Check for welded contactor. 4. Verify CSB wiring. 5. Return to Normal mode and observe compressor operation to verify that compressor current sensor is working and condenser fans are energized. A060 (Cooler Leaving Fluid Thermistor Failure) — The sensor reading is outside the range of –40 to 245 F (–40 to 118 C) then the alarm will occur. The cause of the alarm is usually a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection. Failure of this thermistor will shut down the entire unit. A061 (Cooler Entering Thermistor Failure) — If the sensor reading is outside the range of –40 to 240 F (–40 to116 C) then the alarm will occur. The cause of the alarm is usually a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection. Failure of this thermistor will shut down the entire unit. T068, T69 (Circuit A,B Compressor Return Gas Temperature Thermistor Failure) — This alert occurs when the compressor return gas temperature sensor is outside the range of –40 to 240 F (–40 to 116 C). Failure of this thermistor will shut down the appropriate circuit. T073 (Outside Air Temperature Thermistor Failure) — This alert occurs when the outside air temperature sensor is outside the range of –40 to 240 F (–40 to 116 C). Failure of this thermistor will disable any elements of the control which requires its use. T074 (Space Temperature Thermistor Failure) — This alert occurs when the space temperature sensor is outside the range 72 T153 (Real Time Clock Hardware Failure) — A problem has been detected with MBB real time clock hardware. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced. A154 (Serial EEPROM Hardware Failure) — A problem has been detected with the EEPROM on the MBB. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced. T155 (Serial EEPROM Storage Failure Error) — A problem has been detected with the EEPROM storage on the MBB. Try resetting the power and check the indicator lights. If the alert continues, the board should be replaced. A156 (Critical Serial EEPROM Storage Failure Error) — A problem has been detected with the EEPROM storage on the MBB. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced. A157 (A/D Hardware Failure) — A problem has been detected with A/D conversion on the boards. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced. A172 (Loss of Communication with the EXV Board) — This alarm indicates that there are communications problems with the EXV board. The alarm will automatically reset. T173 (Energy Management Module Communication Failure) — This alert indicates that there are communications problems with the energy management. All functions performed by the EMM will stop, which can include demand limit, reset and capacity input. The alarm will automatically reset. T174 (4 to 20 mA Cooling Set Point Input Failure) — This alert indicates a problem has been detected with cooling set point 4 to 20 mA input. The input value is either less than 2 mA or greater than 22 mA. T175 (Loss of Communication with the AUX Board) — This alarm indicates that there are communications problems with the AUX board. All functions performed by the AUX board will stop, which can include digital scroll unloader operation and low ambient head pressure control. The alarm will automatically reset. T176 (4 to 20 mA Reset Input Failure) — This alert indicates a problem has been detected with reset 4 to 20 mA input. The input value is either less than 2 mA or greater than 22 mA. The reset function will be disabled when this occurs. T177 (4 to 20 mA Demand Limit Input Failure) — This alert indicates a problem has been detected with demand limit 4 to 20 mA input. The input value is either less than 2 mA or greater than 22 mA. The reset function will be disabled when this occurs. T500, T501 (Current Sensor Board Failure — A xx Circuit A) T503, T504 (Current Sensor Board Failure — B xx Circuit B) — Alert codes 500, 501, 503, and 504 are for compressors A1, A2, B1, and B2 respectively. These alerts occur when the output of the CSB is a constant high value. These alerts reset automatically. If the problem cannot be resolved, the CSB must be replaced. rise to greater than the maximum SCT, the alert will occur and the circuit's remaining compressor will shut down. The cause of the alarm is usually an overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil, plugged filter drier, or a faulty high-pressure switch. T133 (Circuit A Low Suction Pressure) T134 (Circuit B Low Suction Pressure) — Alert codes 133 and 134 are for circuits A and B respectively. These alerts are generated if one of the two following conditions is satisfied: the circuit suction pressure is below 34 psig (234.4 kPa) for 8 seconds, or the suction pressure is below 23 psig (158.6 kPa). The cause of this alert may be low refrigerant charge, plugged liquid line filter drier, or sticking EXV. Check head pressure operation. If not equipped, consider adding low ambient temperature head pressure control. Add wind baffles if required. A140 (Reverse Rotation Detected) — A test is made once, on power up, for suction pressure change on the first activated circuit. The unit control determines failure as follows: 1. The suction pressure of both circuits is sampled 5 seconds before the compressor is brought on, right when the compressor is brought on and 5 seconds afterwards. 2. The rate of suction pressure change from 5 seconds before the compressor is brought on to when the compressor is brought on is calculated. 3. The rate of suction pressure change from when the compressor is brought on to 5 seconds afterwards is calculated. 4. With the above information, the test for reverse rotation is made. If the suction pressure change 5 seconds after compression is greater than the suction pressure change 5 seconds before compression – 1.25, then there is a reverse rotation error. This alarm will disable mechanical cooling and will require manual reset. A150 (Unit is in Emergency Stop) — If the CCN emergency stop command is received, the alarm is generated and the unit will be immediately stopped. If the CCN point name "EMSTOP" in the system table is set to emergency stop, the unit will shut down immediately and broadcast an alarm back to the CCN, indicating that the unit is down. This alarm will clear when the variable is set back to "enable." A151 (Illegal Configuration) — An A151 alarm indicates an invalid configuration has been entered. The following are illegal configurations. • Invalid unit size has been entered. • Dual thermostat configured for single-circuit unit. • Dual thermostat and switch demand limit configure • AUX board incorrect revision. • Unit configuration set to invalid type. A152 (Unit Down Due to Failure) — Both circuits are off due to alerts and/or alarms. Reset is automatic when all alarms are cleared. This alarm indicates the unit is at 0% capacity. 73 APPENDIX A — DISPLAY TABLES Run Status Mode and Sub-Mode Directory SUB-MODE ITEM EWT LWT SETP CTPT LOD.F DISPLAY ITEM DESCRIPTION AUTO VIEW OF RUN STATUS xxx.x ºF Entering Fluid Temp xxx.x ºF Leaving Fluid Temp xxx.x ºF Active Set Point xxx.x ºF Control Point xxx Load/Unload Factor STAT Control Mode VIEW LD.PM OCC LS.AC MODE CAP STGE ALRM TIME YES/NO YES/NO YES/NO xxx x xxx xx.xx Lead Pump Occupied Low Sound Active Override Modes in Effect Percent Total Capacity Requested Stage Current Alarms & Alerts Time of Day MNTH xx Month of Year DATE YEAR RUN HOUR HRS.U STR.U HR.P1 HR.P2 HRS.A HRS.B HR.A1 HR.A2 HR.B1 HR.B2 xx Day of Month xx Year of Century UNIT RUN HOUR AND START xxxx HRS Machine Operating Hours xxxx Machine Starts xxxx HRS Pump 1 Run Hours xxxx HRS Pump 2 Run Hours CIRC AND COMP RUN HOURS xxxx HRS Circuit A Run Hours xxxx HRS Circuit B Run Hours xxxx HRS Compressor A1 Run Hours xxxx HRS Compressor A2 Run Hours xxxx HRS Compressor B1 Run Hours xxxx HRS Compressor B2 Run Hours 74 COMMENT 0=Service Test 1=Off Local 2=Off CCN 3=Off Time 4=Off Emrgcy 5=On Local 6=On CCN 7=On Time 00:00-23:59 1 - 12 (1 = January, 2 = February, etc.) 01-31 APPENDIX A — DISPLAY TABLES (cont) Run Status Mode and Sub-Mode Directory (cont) SUB-MODE STRT PM VERS ITEM ST.A1 ST.A2 ST.B1 ST.B2 PUMP SI.PM P.1.DN P.2.DN P.1.MN P.2.MN PMDT P.1.M0 P.1.M1 P.1.M2 P.1.M3 P.1.M4 P.2.M0 P.2.M1 P.2.M2 P.2.M3 P.2.M4 STRN SI.ST S.T.DN S.T.MN ST.DT S.T.M0 S.T.M1 S.T.M2 S.T.M3 S.T.M4 COIL SI.CL C.L.DN C.L.MN CL.DT C.L.M0 C.L.M1 C.L.M2 C.L.M3 C.L.M4 MBB EXV AUX1 EMM MARQ NAVI DISPLAY ITEM DESCRIPTION COMPRESSOR STARTS xxxx Compressor A1 Starts xxxx Compressor A2 Starts xxxx Compressor B1 Starts xxxx Compressor B2 Starts PREVENTIVE MAINTENANCE PUMP MAINTENANCE xxxx HRS Pump Service Interval xxxx HRS Pump 1 Service Countdown xxxx HRS Pump 2 Service Countdown YES/NO Pump 1 Maintenance Done YES/NO Pump 2 Maintenance Done PUMP MAINTENANCE DATES MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM STRAINER MAINTENANCE xxxx HRS Strainer Srvc Interval xxxx HRS Strainer Srvc Countdown YES/NO Strainer Maint. Done STRAINER MAINTENANCE DATES MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM COIL MAINTENANCE xxxx HRS Coil Cleaning Srvc Int xxxx HRS Coil Service Countdown YES/NO Coil Cleaning Maint.Done COIL MAINTENANCE DATES MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM MM/DD/YY HH:MM SOFTWARE VERSION NUMBERS CESR131460-XXXXX CESR131172-XXXXX CESR131333-XXXXX CESR131174-XXXXX CESR131171-XXXXX CESR130227-XXXXX 75 COMMENT User Entry User Entry User Entry User Entry APPENDIX A — DISPLAY TABLES (cont) Service Test Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION TEST OUTS CMPA CMPB Service Test Mode EXV.A EXV.B FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 V.HPA V.HPB CLP.1 CLP.2 UL.TM CL.HT RMT.A xxx% xxx% ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF xx xx ON/OFF ON/OFF xx ON/OFF ON/OFF CC.A1 UL.TM CC.A2 MLV ON/OFF xx ON/OFF ON/OFF CC.B1 CC.B2 ON/OFF ON/OFF COMMENT To enable Service Test mode, move Enable/Off/Remote contact switch to OFF. Change TEST to ON. Move switch to ENABLE OUTPUTS EXV % Open EXV % Open Fan 1 Relay Fan 2 Relay Fan 3 Relay Fan 4 Relay Fan 5 Relay Fan 6 Relay Var Head Press % Var Head Press % Cooler Pump Relay 1 Cooler Pump Relay 2 Comp A1 Unload Time Cooler/Pump Heater Remote Alarm Relay CIRCUIT A COMPRESSOR TEST Compressor A1 Relay Comp A1 Unload Time Compressor A2 Relay Minimum Load Valve Relay CIRCUIT B COMPRESSOR TEST Compressor B1 Relay Compressor B2 Relay Temperature Mode and Sub-Mode Directory SUB-MODE UNIT CIR.A CIR.B ITEM DISPLAY ITEM DESCRIPTION ENTERING AND LEAVING UNIT TEMPERATURES xxx.x °F Cooler Entering Fluid xxx.x °F Cooler Leaving Fluid xxx.x °F Outside Air Temperature xxx.x °F Space Temperature xxx.x °F Lead/Lag Leaving Fluid TEMPERATURES CIRCUIT A xxx.x °F Saturated Condensing Tmp xxx.x °F Saturated Suction Temp xxx.x °F Compr Return Gas Temp xxx.x °F Discharge Gas Temp xxx.x ΔF Suction Superheat Temp TEMPERATURES CIRCUIT B xxx.x °F Saturated Condensing Tmp xxx.x °F Saturated Suction Temp xxx.x °F Compr Return Gas Temp xxx.x ΔF Suction Superheat Temp CEWT CLWT OAT SPT DLWT SCT.A SST.A RGT.A D.GAS SH.A SCT.B SST.B RGT.B SH.B COMMENT Pressures Mode and Sub-Mode Directory SUB-MODE ITEM PRC.A DP.A SP.A PRC.B DP.B SP.B DISPLAY ITEM DESCRIPTION PRESSURES CIRCUIT A xxx.x PSIG Discharge Pressure xxx.x PSIG Suction Pressure PRESSURES CIRCUIT B xxx.x PSIG Discharge Pressure xxx.x PSIG Suction Pressure 76 COMMENT APPENDIX A — DISPLAY TABLES (cont) Set Points Mode and Sub-Mode Directory SUB-MODE COOL HEAD FRZ ITEM DISPLAY CSP.1 CSP.2 CSP.3 xxx.x °F xxx.x °F xxx.x °F H.DP F.ON F.OFF B.OFF F.DLT xxx.x °F xxx.x °F xxx.x °F xx.x xxx BR.FZ xx.x °F ITEM DESCRIPTION COOLING SET POINTS Cooling Set Point 1 Cooling Set Point 2 ICE Set Point HEAD PRESSURE SET POINTS Head Set Point Fan On Set Point Fan Off Set Point Base Fan Off Delta Temp Fan Stage Delta BRINE FREEZE SET POINT Brine Freeze Point RANGE COMMENT –20 to 70 –20 to 70 –20 to 32 Default: 44 F Default: 44 F Default: 32 F 85 to 120 10 to 50 0 to 50 Default: 95 F Default: 95 F Default: 72 F Default: 23 F Default: 15 F –20 to 34 Default: 34 F Inputs Mode and Sub-Mode Directory SUB-MODE GEN.I CRCT 4-20 ITEM STST FLOW PM.F.1 PM.F.2 HT.RQ DLS1 DLS2 ICED DUAL FKA1 FKA2 FKA3 FKA4 FKB1 FKB2 FKB3 FKB4 DMND RSET CSP DISPLAY ITEM DESCRIPTION GENERAL INPUTS ON/OFF Start/Stop Switch ON/OFF Cooler Flow Switch ON/OFF Cooler Pump 1 Interlock ON/OFF Cooler Pump 2 Interlock ON/OFF Heat Request ON/OFF Demand Limit Switch 1 ON/OFF Demand Limit Switch 2 ON/OFF Ice Done ON/OFF Dual Set Point Switch CIRCUIT INPUTS ON/OFF Compressor A1 Feedback ON/OFF Compressor A2 Feedback ON/OFF Compressor A3 Feedback ON/OFF Compressor A4 Feedback ON/OFF Compressor B1 Feedback ON/OFF Compressor B2 Feedback ON/OFF Compressor B3 Feedback ON/OFF Compressor B4 Feedback 4-20 MA INPUTS xx.x 4-20 ma Demand Signal xx.x 4-20 ma Reset Signal xx.x 4-20 ma Cooling Set Point 77 COMMENT APPENDIX A — DISPLAY TABLES (cont) Outputs Mode and Sub-Mode Directory SUB-MODE GEN.O A.EXV B.EXV CIR.A CIR.B ITEM FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 V.HPA V.HPB C.WP1 C.WP2 CLHT MLV.R EXV.A APPR AP.SP X.SH.R S.SH.R SH_R OVR.A SPH.A ASH.S AMP.S PLM.A SPR.1 EXV.B APPR AP.SP OVR.B SPH.B ASH.S AMP.S PLM.B SPR.2 CC.A1 DPE.R CC.A2 CC.A3 CC.A4 CC.B1 CC.B2 CC.B3 CC.B4 DISPLAY ITEM DESCRIPTION GENERAL OUTPUTS ON/OFF Fan 1 Relay ON/OFF Fan 2 Relay ON/OFF Fan 3 Relay ON/OFF Fan 4 Relay ON/OFF Fan 5 Relay ON/OFF Fan 6 Relay ON/OFF Fan Speed Circuit A ON/OFF Fan Speed Circuit B ON/OFF Cooler Pump Relay 1 ON/OFF Cooler Pump Relay 2 ON/OFF Cooler/Pump Heater ON/OFF Minimum Load Valve Relay OUTPUTS CIRCUIT A EXV ON/OFF EXV % Open ON/OFF Circuit A Approach ON/OFF Approach Setpoint SH Reset at Max Unl-Dig Digload to Start SH RST Amount of SH Reset ON/OFF EXVA Override ON/OFF Suction Superheat Temp ON/OFF Active Superheat Setpt ON/OFF Active Mop Setpt ON/OFF Cir A EXV Position Limit ON/OFF Spare 1 Temperature OUTPUTS CIRCUIT A EXV ON/OFF EXV % Open ON/OFF Circuit B Approach ON/OFF Approach Setpoint ON/OFF EXVB Override ON/OFF Suction Superheat Temp ON/OFF Active Superheat Setpt ON/OFF Active Mop Setpt ON/OFF Cir B EXV Position Limit ON/OFF Spare 2 Temperature OUTPUTS CIRCUIT A ON/OFF Compressor A1 Relay ON/OFF Comp A1 Load Percent ON/OFF Compressor A2 Relay ON/OFF Compressor A3 Relay ON/OFF Compressor A4 Relay OUTPUTS CIRCUIT B ON/OFF Compressor B1 Relay ON/OFF Compressor B2 Relay ON/OFF Compressor B3 Relay ON/OFF Compressor B4 Relay 78 COMMENT APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory SUB-MODE DISP UNIT OPT1 ITEM DISPLAY ITEM DESCRIPTION DISPLAY CONFIGURATION Test Display LEDs Metric Display TEST METR ON/OFF ON/OFF LANG X PAS.E PASS ENBL/DSBL XXXX SIZE SZA.1 SZA.2 SZA.3 SZA.4 SZB.1 SZB.2 SZB.3 SZB.4 SH.SP FAN.S EXV A1.TY XX XX XX XX XX XX XX XX XX X YES/NO YES/NO MAX.T XX FLUD X MLV.S CSB.E CPC PM1E PM2E PM.P.S PM.SL YES/NO ENBL/DSBL ON/OFF YES/NO YES/NO YES/NO X Minimum Load Valve Select Csb Boards Enable Cooler Pump Control Cooler Pump 1 Enable Cooler Pump 2 Enable Cooler Pmp Periodic Strt Cooler Pump Select PM.DY PM.DT ROT.P EMM CND.T MOPS APPR XX MIN XXXX HRS YES/NO YES/NO X XX XX Cooler Pump Shutdown Dly Pump Changeover Hours Rotate Cooler Pumps Now EMM Module Installed Cnd HX Typ:0=RTPF 1=MCHX EXV MOP Set Point Config Approach Set Point Language Selection Password Enable Service Password UNIT CONFIGURATION Unit Size Compressor A1 Size Compressor A2 Size Compressor A3 Size Compressor A4 Size Compressor B1 Size Compressor B2 Size Compressor B3 Size Compressor B4 Size Suction Superheat Setpt Number of Fans EXV Module Installed Compressor A1 Digital Maximum A1 Unload Time UNIT OPTIONS 1 HARDWARE Cooler Fluid 79 COMMENT Off = English On = Metric Default: 0 0 = English 1 = Espanol 2 = Francais 3 = Portuguese Default: 5 Default: No Default: 7 Max = 12 (010,015) Max = 10 (018-060) Default: Water 1 = Water 2 = Medium Temperature Brine Default: Enable Default: Off Default: No Default: Automatic 0 = Automatic 1 = Pump 1 Starts first 2 = Pump 2 Starts first 0 to 10 minutes, Default: 1 min. Default: 500 hours User Entry APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE OPT2 ITEM DISPLAY ITEM DESCRIPTION UNIT OPTIONS 2 CONTROLS CTRL X Control Method LOAD X Loading Sequence Select LLCS X Lead/Lag Circuit Select LCWT XX High LCW Alert Limit DELY XX Minutes Off Time ICE.M LS.MD ENBL/DSBL X Ice Mode Enable Low Sound Mode Select LS.ST LS.ND 00:00 00:00 Low Sound Start Time Low Sound End Time LS.LT XXX % Low Sound Capacity Limit CCNA XXX CCN Address CCNB XXX CCN Bus Number BAUD X CCN Baud Rate COMMENT Default: 0 0 = Enable/Off/Remote Switch 2 = Occupancy 3 = CCN Control Default: 1 1 = Equal 2 = Staged Default: 1 1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads Default: 60 Range: 2 to 60 F Default: 0 Minutes Range: 0 to 15 Minutes Default: Disable Default: 0 0 = Mode Disable 1 = Fan Noise Only 2 = Fan/Compressor Noise Default: 00:00 Default: 00:00 Default: 100% Range: 0 to 100% CCN NETWORK CONFIGS CCN Default: 1 Range: 0 to 239 Default: 1 Range: 0 to 239 Default: 3 1 = 2400 2 = 4800 3 = 9600 4 =19,200 5 =38,400 HEAD PRESSURE CMP. DELTA HP.A A1.DT XX SCT Delta For Comp A1 A2.DT XX SCT Delta For Comp A2 Default:12 Range: 0 to 50 Default:12 Range: 0 to 50 HEAD PRESSURE CMP. DELTA HP.B B1.DT XX SCT Delta For Comp B1 B2.DT XX SCT Delta For Comp B2 80 Default:12 Range: 0 to 50 Default:12 Range: 0 to 50 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE EXV.A ITEM DISPLAY ITEM DESCRIPTION CIR A EXV CONFIGURATION STR.A XXX EXV CIrc.A Start Pos MIN.A XXX EXV Circ.A Min Position RNG.A XXXXX EXVA Steps In Range SPD.A XXXXX EXVA STeps Per Second POF.A XXX EXVA Fail Position In % MIN.A XXXXX EXVA Minimum Steps MAX.A XXXXX EXVA Maximum Steps OVR.A XXX EXVA Overrun Steps TYP.A 0,1 EXVA Stepper Type H.SCT XXX High SCT Threshold X.PCT XX Open EXV X% On 2nd Comp X.PER XX Move EXV X% On DISCRSOL A.PCT XXX Pre-open EXV - Fan Adding M.PCT XXX Pre-close EXV - Fan Sub S.PCT XXX Pre-close EXV - Lag Shut DELY XXX Lag Start Delay COMMENT Default: 50 0 to 100 Default: 8 0 to 100 0 to 65535 Default: 200 0 to 65535 Default: 0 0 to 100 Default: 0 0 to 65535 0 to 65535 Default: 167 0 to 65535 Default: 1 0 = UNIPOLAR 1 = BIPOLAR Default: 115 50 to 140 Default: 10 0 to 30 Default: 5 0 to 30 Default: 10 0 to 100 Default: 10 0 to 100 Default: 10 0 to 100 Default: 10 0 to 100 CIR B EXV CONFIGURATION STR.B EXV.B XXX EXV CIrc.B Start Pos MIN.B XXX EXV Circ.B Min Position RNG.B XXXXX EXVB Steps In Range SPD.B XXXXX EXVB STeps Per Second POF.B XXX EXVB Fail Position In % MIN.B XXXXX EXVB Minimum Steps MAX.B XXXXX EXVB Maximum Steps OVR.B XXX EXVB Overrun Steps TYP.B 0,1 EXVB Stepper Type 81 Default: 50 0 to 100 Default: 8 0 to 100 0 to 65535 Default: 200 0 to 65535 Default: 0 0 to 100 Default: 0 0 to 65535 0 to 65535 Default: 167 0 to 65535 Default: 1 0 = UNIPOLAR 1 = BIPOLAR APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE MM RSET ITEM DISPLAY ITEM DESCRIPTION MOTORMASTER Motormaster Select MMR.S YES/NO P.GAN XX Head Pressure P Gain I.GAN XX.X Head Pressure I Gain D.GAN XX.X Head Pressure D Gain MIN.S XX Minimum Fan Speed RESET COOL TEMP COMMENT Default: NO Default: 1 Range: 1 to 4 Default: 0.1 Range: -20 to 20 Default: 0.0 Range: -20 to 20 Default: 5 CRST X Cooling Reset Type MA.DG XX.XΔF 4-20 - Degrees Reset RM.NO XXX.X °F Remote - No Reset Temp RM.F XXX.X °F Remote - Full Reset Temp RM.DG XX.X °F Remote - Degrees Reset RT.NO XXX.XΔF Return - No Reset Temp RT.F XXX.XΔF Return - Full Reset Temp RT.DG XX.X °F Return - Degrees Reset DMDC X Demand Limit Select DM20 XXX% Demand Limit at 20 mA SHNM XXX Loadshed Group Number SHDL XXX% Loadshed Demand Delta SHTM XXX Maximum Loadshed Time DLS1 XXX% Demand Limit Switch 1 DLS2 XXX% Demand Limit Switch 2 Default: 0 0 = No Reset 1 = 4 to 20 mA Input 2 = Outdoor Air Temperature 3 = Return Fluid 4 = Space Temperature Default: 0.0 ΔF Range: -30 to 30 ΔF Default: 125 F Range: 0° to125 F Default: 0 F Range: 0° to125 F Default: 0.0 ΔF Range: -30 to 30 ΔF Default: 10.0 ΔF Range: 0° to125 F Default: 0 ΔF Range: 0° to125 F Default: 0.0 ΔF Range: -30 to 30 ΔF Default: 0 0 = None 1 = Switch 2 - 4 to 20 mA Input 3 = CCN Loadshed Default: 100% Range: 0 to 100% Default: 0 Range: 0 to 99 Default: 0% Range: 0 to 60% Default: 60 minutes Range: 0 to 120 minutes Default: 80% Range: 0 to 100% Default: 50% Range: 0 to 100% LLEN ENBL/DSBL Lead/Lag Chiller Enable Default: Disable MSSL SLVE/MAST Master/Slave Select SLVA XXX Slave Address LLBL X Lead/Lag Balance Select LLBD XXX Lead/Lag Balance Delta LLDY XXX Lag Start Delay PARA YES Parallel Configuration Default: Master Default: 2 Range: 0 to 239 Default: Master Leads 0 = Master Leads 1 = Slave Leads 2 = Automatic Default: 168 hours Range: 40 to 400 hours Default: 5 minutes Range: 0 to 30 minutes Default: YES (CANNOT BE CHANGED) 82 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE SLCT SERV BCST ITEM DISPLAY ITEM DESCRIPTION SETPOINT AND RAMP LOAD CLSP X Cooling Set Point Select RL.S ENBL/DSBL Ramp Load Select CRMP ENBL/DSBL Cooling Ramp Loading SCHD XX Schedule Number Z.GN X.X Deadband Multiplier EN.A1 EN.A2 EN.B1 EN.B2 YES/NO YES/NO YES/NO YES/NO T.D.B OAT.B G.S.BC BC.AK ON/OFF ON/OFF ON/OFF ON/OFF SERVICE CONFIGURATION Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 BROADCAST CONFIGURATION CCN Time/Date Broadcast CCN OAT Broadcast Global Schedule Broadcst CCN Broadcast Ack'er 83 COMMENT Default: Single 0 = Single 1 = Dual Switch 2 = Dual CCN Occupied 3 = 4 to 20 mA Input (requires EMM) Default: Enable Default: 1.0 Range: 0.3 to 2 Default: 1 Range: 1 to 99 Default: 1 Range: 1 to 4 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory SUB-MODE TIME DATE ITEM HH.MM XX Month of Year DOM XX Day of Month DAY X Day of Week STR.M STR.W STR.D MIN.A STP.M STP.W STP.D MIN.S HOL.L HD.01 HD.02 HD.03 HD.04 HD.05 HD.06 HD.07 HD.08 ITEM DESCRIPTION TIME OF DAY XX.XX Hour and Minute MONTH, DATE, DAY, AND YEAR MNTH YEAR DST DISPLAY MON DAY LEN XXXX Year of Century DAYLIGHT SAVINGS TIME XX Month X Week X Day XX Minutes to Add XX Month XX Week XX Day XX Minutes to Subtract LOCAL HOLIDAY SCHEDULES HOLIDAY SCHEDULE 01 XX Holiday Start Month XX Start Day XX Duration (days) HOLIDAY SCHEDULE 02 MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX Holiday Start Month DAY LEN XX XX Start Day Duration (days) 84 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 03 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 04 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 05 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 06 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 07 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 08 COMMENT Military (00:00 - 23:59) 1 - 12 (1 = January, 2 = February, etc.) Range: 01 -31 1 - 7 (1 = Sunday, 2 = Monday, etc.) Default: 4 Range 1- 12 Default: 1 Range 1- 5 Default: 7 Range 1- 7 Default: 60 Range 0 - 99 Default: 10 Range 1- 12 Default: 5 Range 1- 5 Default: 7 Range 1- 7 Default: 60 Range 0 - 99 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE HD.09 HD.10 HD.11 HD.12 HD.13 HD.14 HD.15 HD.16 HD.17 HD.18 HD.19 ITEM DISPLAY ITEM DESCRIPTION HOLIDAY SCHEDULE 09 MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX Holiday Start Month DAY LEN XX XX Start Day Duration (days) 85 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 10 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 11 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 12 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 13 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 14 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 15 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 16 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 17 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 18 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 19 COMMENT 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE HD.20 HD.21 HD.22 HD.23 HD.24 HD.25 HD.26 HD.27 HD.28 HD.29 HD.30 ITEM DISPLAY ITEM DESCRIPTION HOLIDAY SCHEDULE 20 MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX DAY LEN XX XX MON XX Holiday Start Month DAY LEN XX XX Start Day Duration (days) 86 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 21 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 22 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 23 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 24 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 25 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 26 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 27 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 28 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 29 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 30 COMMENT 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 1 - 12 (1 = January, 2 = February, etc.) 01-31 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE SCH.N SCH.L PER.1 PER.2 PER.3 PER.4 PER.5 ITEM OCC.1 UNC.1 MON.1 TUE.1 WED.1 THU.1 FRI.1 SAT.1 SUN.1 HOL.1 OCC.2 UNC.2 MON.2 TUE.2 WED.2 THU.2 FRI.2 SAT.2 SUN.2 HOL.2 OCC.3 UNC.3 MON.3 TUE.3 WED.3 THU.3 FRI.3 SAT.3 SUN.3 HOL.3 OCC.4 UNC.4 MON.4 TUE.4 WED.4 THU.4 FRI.4 SAT.4 SUN.4 HOL.4 OCC.5 UNC.5 MON.5 TUE.5 WED.5 THU.5 FRI.5 SAT.5 SUN.5 HOL.5 DISPLAY ITEM DESCRIPTION Schedule Number 0 LOCAL OCCUPANCY SCHEDULE OCCUPANCY PERIOD 1 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period OCCUPANCY PERIOD 2 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period OCCUPANCY PERIOD 3 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period OCCUPANCY PERIOD 4 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period OCCUPANCY PERIOD 5 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period 87 COMMENT Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE PER.6 PER.7 PER.8 OVR ITEM OCC.6 UNC.6 MON.6 TUE.6 WED.6 THU.6 FRI.6 SAT.6 SUN.6 HOL.6 OCC.7 UNC.7 MON.7 TUE.7 WED.7 THU.7 FRI.7 SAT.7 SUN.7 HOL.7 OCC.8 UNC.8 MON.8 TUE.8 WED.8 THU.8 FRI.8 SAT.8 SUN.8 HOL.8 OVR.T OVR.L T.OVR DISPLAY ITEM DESCRIPTION OCCUPANCY PERIOD 6 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period OCCUPANCY PERIOD 7 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period OCCUPANCY PERIOD 8 XX:XX Period Occupied Time XX:XX Period Unoccupied Time YES/NO Monday In Period YES/NO Tuesday In Period YES/NO Wednesday In Period YES/NO Thursday In Period YES/NO Friday In Period YES/NO Saturday In Period YES/NO Sunday In Period YES/NO Holiday In Period SCHEDULE OVERRIDE X Timed Override Hours X Override Time Limit YES/NO Timed Override 88 COMMENT Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Military (00:00 - 23:59) Default: 0 Range 0-4 hours Default: 0 Range 0-4 hours User Entry APPENDIX A — DISPLAY TABLES (cont) Operating Mode and Sub-Mode Directory SUB-MODE MODE ITEM DISPLAY MD01 MD02 MD03 MD05 MD06 MD07 MD08 MD09 MD10 MD13 MD14 MD15 MD16 MD17 MD18 MD19 MD20 MD21 MD22 MD23 MD24 MD25 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ITEM DESCRIPTION MODES CONTROLLING UNIT CSM Controlling Chiller WSM Controlling Chiller Master/Slave Control Ramp Load Limited Timed Override in effect Low Cooler Suction TempA Low Cooler Suction TempB Slow Change Override Minimum OFF time active Dual Set Point Temperature Reset Demand Limited Cooler Freeze Protection Low Temperature Cooling High Temperature Cooling Making Ice Storing Ice High SCT Circuit A High SCT Circuit B Minimum Comp. On Time Pump Off Delay Time Low Sound Mode COMMENT Alarms Mode and Sub-Mode Directory SUB-MODE ITEM CRNT AXXX TXXX PXXX YES/NO RCRN HIST DISPLAY ITEM DESCRIPTION CURRENTLY ACTIVE ALARMS Current Alarms 1-25 COMMENT Alarms are hown as AXXX Alerts are shown as TXXX Reset All Current Alarms ALARM HISTORY AXXX TXXX PXXX Alarm History 1-20 89 Alarms are shown as AXXX Alerts are shown as TXXX APPENDIX B — CCN TABLES CCN DISPLAY TABLES — A_UNIT (General Unit Parameters) DESCRIPTION Control Mode Occupied CCN Chiller Low Sound Active Alarm State Active Demand Limit Override Modes in Effect Percent Total Capacity Requested Stage Active Set Point Control Point Entering Fluid Temp Leaving Fluid Temp Emergency Stop Minutes Left for Start PUMPS Cooler Pump Relay 1 Cooler Pump Relay 2 Cooler Pump 1 Interlock Cooler Pump 2 Interlock Cooler Flow Switch Lead Pump Rotate Cooler Pumps Now Heat/Cool Select VALUE 0 = Test 1 = Local Off 2 = CCN Off 3 = Clock Off 4 = Emergency Stop 5 = Local On 6 = CCN On 7 = Clock On 8 = Heat Enabled 9 = Pump Delay No/Yes Start/Stop No/Yes Normal/Alert/Alarm 0 to 100 No/Yes 0 to 100 0 to 99 –20 to 70 –20 to 70 snnn.n snnn.n Enable/Emstop 00:00 to 15:00 UNITS POINT NAME STAT N OCC CHIL_S_S LSACTIVE ALM DEM_LIM MODE CAP_T STAGE SP CTRL_PNT EWT LWT EMSTOP MIN_LEFT N Y N N Y N N N N Y N N Y N No/Yes COOLPMP1 COOLPMP2 PMP1_FBK PMP2_FBK COOLFLOW LEADPUMP ROT_PUMP N N N N N Y Y Heat/Cool HC_SEL N % % F F F F Enable minutes Off/On Off/On Open/Close Open/Close Open/Close FORCIBLE CCN DISPLAY TABLES — CIRCA_AN (Circuit A Analog Parameters) DESCRIPTION CIRCUIT A ANALOG VALUES Percent Total Capacity Percent Available Cap. Discharge Pressure Suction Pressure Head Setpoint Saturated Condensing Tmp Saturated Suction Temp EXV % Open Var Head Press Output Compr Return Gas Temp Discharge Gas Temp Suction Superheat Temp Spare 1 Temperature VALUE UNITS 0-100 0-100 nnn.n nnn.n nnn.n snnn.n snnn.n nnn nnn.n nnn.n nnn.n nnn.n nnn.n % % PSIG PSIG °F F F % milliamps F °F F °F 90 POINT NAME CAPA_T CAPA_A DP_A SP_A HSP TMP_SCTA TMP_SSTA EXV_A VHP_ACT TMP_RGTA DISGAS SH_A SPR1_TMP FORCIBLE N N N N N N N N N N N N N APPENDIX B — CCN TABLES (cont) CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs) DESCRIPTION CIRC. A DISCRETE OUTPUTS Compressor A1 Relay Compressor A2 Relay Minimum Load Valve Relay VALUE UNITS POINT NAME FORCIBLE On/Off On/Off On/Off K_A1_RLY K_A2_RLY MLV_RLY N N N CIRC. A DISCRETE INPUTS Compressor A1 Feedback Compressor A2 Feedback On/Off On/Off K_A1_FBK K_A2_FBK N N CCN DISPLAY TABLES — CIRCB_AN (Circuit B Analog Parameters) DESCRIPTION CIRCUIT B ANALOG VALUES Percent Total Capacity Percent Available Cap. Discharge Pressure Suction Pressure Head Setpoint Saturated Condensing Tmp Saturated Suction Temp EXV % Open Var Head Press Output Compr Return Gas Temp Suction Superheat Temp Spare 2 Temperature VALUE UNITS 0-100 0-100 nnn.n nnn.n nnn.n snnn.n snnn.n nnn nnn.n nnn.n nnn.n nnn.n % % PSIG PSIG °F F F % milliamps F F °F POINT NAME CAPB_T CAPB_A DP_B SP_B HSP TMP_SCTB TMP_SSTB EXV_B VHP_ACT TMP_RGTB SH_B SPR2_TMP FORCIBLE N N N N N N N N N N N N CCN DISPLAY TABLES — CIRCBDIO (Circuit B Discrete Inputs/Outputs) DESCRIPTION CIRC. B DISCRETE OUTPUTS Compressor B1 Relay Compressor B2 Relay Minimum Load Valve Relay VALUE UNITS On/Off On/Off On/Off K_B1_RLY K_B2_RLY MLV_RLY N N N CIRC. B DISCRETE INPUTS Compressor B1 Feedback Compressor B2 Feedback On/Off On/Off K_B1_FBK K_B2_FBK N N 91 POINT NAME FORCIBLE APPENDIX B — CCN TABLES (cont) CCN DISPLAY TABLES — OPTIONS (Unit Parameters) DESCRIPTION FANS Fan 1 Relay Fan 2 Relay Cooler/Pump Heater VALUE Off/On Off/On Off/On UNIT ANALOG VALUES Cooler Entering Fluid Cooler Leaving Fluid Lead/Lag Leaving Fluid snnn.n snnn.n snnn.n TEMPERATURE RESET 4-20 mA Reset Signal Outside Air Temperature Space Temperature DEMAND LIMIT 4-20 mA Demand Signal Demand Limit Switch 1 Demand Limit Switch 2 CCN Loadshed Signal MISCELLANEOUS Heat Request Dual Setpoint Switch Cooler LWT Setpoint Ice Done UNITS POINT NAME FORCIBLE FAN_1 FAN_2 COOL_HTR N N N F F F COOL_EWT COOL_LWT DUAL_LWT N N N nn.n snnn.n snnn.n mA F F RST_MA OAT SPT N Y Y nn.n Off/On Off/On 0 = Normal 1 = Redline 2 = Loadshed mA LMT_MA DMD_SW1 DMD_SW2 DL_STAT N N N N HEAT_REQ DUAL_IN LWT_SP ICE_DONE N N N N Off/On Off/On snnn.n Off/On F CCN CONFIGURATION TABLES — UNIT (Unit Configuration) DESCRIPTION Unit Size Compressor A1 Size Compressor A2 Size Compressor B1 Size Compressor B2 Size Suction Superheat Setpt Number of Fans Compressor A1 Digital? Maximum A1 Unload Time VALUE nnn nnn nnn nnn nnn nn.n n No/Yes nn DEFAULT 9.0 No 12 UNITS tons tons tons tons tons F sec POINT NAME SIZE SIZE_A1 SIZE_A2 SIZE_B1 SIZE_B2 SH_SP FAN_TYPE CPA1TYPE MAXULTME CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration) DESCRIPTION Cooler Fluid Minimum Load Vlv Select CSB Board Enable Cooler Pump Control Cooler Pump 1 Enable Cooler Pump 2 Enable Cooler Pmp Periodic Strt Cooler Pump Select Cooler Pump Shutdown Dly Pump Changeover Hours EMM Module Installed Cnd HX Typ: 0=RTPF 1=MCHX EXV MOP Set Point Config Approach Setpoint VALUE 1 = Water 2 = Med. Brine No/Yes Dsable/Enable Off/On No/Yes No/Yes No/Yes 0 = Automatic, 1 = Pump 1, 2 = Pump 2 0 to 10 10 to 2000 No/Yes 0/1 nn.n nn.n DEFAULT 1 UNITS No Enable Off No No No 0 1 100 No 1 MLV_FLG CSB_ENA CPC PMP1_ENA PMP2_ENA PUMP_PST PMP_SLCT minutes hours °F °F 92 POINT NAME FLUIDTYP PUMP_DLY PMP_DLTA EMM_BRD COILTYPE MOP_SP IAPPROSP APPENDIX B — CCN TABLES (cont) CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration) DESCRIPTION Control Method Loading Sequence Select Lead/Lag Circuit Select Cooling Setpoint Select Ramp Load Select Heat Cool Select High LCW Alert Limit Minutes off time Deadband Multiplier Ice Mode Enable Low Sound Mode Select Low Sound Start Time Low Sound End Time Low Sound Capacity Limit VALUE 0 = Switch 2 = Occupancy 3 = CCN 1 = Equal Loading 2 = Staged Loading 1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads 0 = Single 1 = Dual, remote switch controlled 2 = Dual CCN occupancy 3 = 4-20 mA input Enable/Dsable Cool/Heat 2 to 60 0 to 15 1.0 to 4.0 Enable/Dsable 0 = Disabled 1 = Fan only 2 = Capacity/Fans 00:00 to 23:59 00:00 to 23:59 0 to 100 DEFAULT 0 UNITS POINT NAME CONTROL 1 SEQ_TYP 1 LEAD_TYP 0 CLSP_TYP Enable Cool 60.0 0 1.0 Dsable 0 RAMP_EBL HEATCOOL LCW_LMT DELAY Z_GAIN ICE_CNFG LS_MODE F min 00:00 00:00 100 % LS_START LS_END LS_LIMIT CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup) DESCRIPTION Schedule Number Override Time Limit Timed Override Hours Timed Override VALUE 0 to 99 0 to 4 0 to 4 No/Yes DEFAULT 1 0 0 No UNITS hours hours POINT NAME SCHEDNUM OTL OVR_EXT TIMEOVER CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit) DESCRIPTION COOLING RESET Cooling Reset Type VALUE DEFAULT UNITS POINT NAME 0 = No Reset 1 = 4-20 mA input 2 = External temp – OAT 3 = Return Fluid 4 = External temp - SPT 0 4-20 MA RESET 4-20 – Degrees Reset –30 to 30 0.0 F 420_DEG REMOTE RESET Remote – No Reset Temp Remote – Full Reset Temp Remote – Degrees Reset 0 to 125 0 to 125 –30 to 30 125.0 0.0 0.0 F F F REM_NO REM_FULL REM_DEG RETURN TEMPERATURE RESET Return – No Reset Temp Return – Full Reset Temp Return – Degrees Reset 0 to 125 0 to 125 –30 to 30 10.0 0.0 0.0 F F F RTN_NO RTN_FULL RTN_DEG 0 = None 1 = External switch input 2 = 4-20 mA input 3 = Loadshed 0 to 100 0 to 99 0 to 60 0 to 120 0 to 100 0 to 100 0 DEMAND LIMIT Demand Limit Select Demand Limit at 20 mA Loadshed Group Number Loadshed Demand Delta Maximum Loadshed Time Demand Limit Switch 1 Demand Limit Switch 2 100 0 0 60 80 50 93 CRST_TYP DMD_CTRL % % minutes % % DMT20MA SHED_NUM SHED_DEL SHED_TIM DLSWSP1 DLSWSP2 APPENDIX B — CCN TABLES (cont) CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings) DESCRIPTION LEAD/LAG Lead/Lag Chiller Enable Master/Slave Select Slave Address Lead/Lag Balance Select Lead/Lag Balance Delta Lag Start Delay Parallel Configuration VALUE Enable/Dsable Master/Slave 0 to 239 0 = None 40 to 400 0 to 30 Yes DEFAULT Dsable Master 2 0 168 5 Yes UNITS POINT NAME LL_ENA MS_SEL SLV_ADDR LL_BAL LL_BAL_D LL_DELAY PARALLEL hours minutes CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP) DESCRIPTION Service Password Password Enable Metric Display Language Selection VALUE nnnn Enable/Disable Off/On 0 = ENGLISH 1 = FRANCAIS 2 = ESPANOL 3 = PORTUGUES DEFAULT 1111 Enable Off 0 UNITS POINT NAME PASSWORD PASS_EBL DISPUNIT LANGUAGE CCN CONFIGURATION TABLES — EXVACONF (EXV Circuit A Configuration) DESCRIPTION EXV Circ. A Start Pos EXV Circ. A Min Position EXVA Steps in Range EXVA Steps Per Second EXVA Fail Position in % EXVA Minimum Steps EXVA Maximum Steps EXVA Overrun Steps EXVA Stepper Type High SCT Threshold Open EXV X% on 2nd Comp Open EXV X% on DISCRSOL Pre-Open EXV - Fan Adding Pre-Close EXV - Fan Sub Pre-Close EXV - Lag Shut Lag Start Delay VALUE nnn.n nnn.n nnnnn nnnnn nnnn.nn nnnnn nnnnn nnnnn nnn nnn.n nnn.n nnn.n nnn.n nnn.n nnn.n nnn DEFAULT 50.0 8.0 1596/2500 200 0 0 1596/2500 167 Bipolar 115 10 5 10 10 10 10 UNITS % % steps steps % steps steps steps °F % % % % % secs POINT NAME EXVASTRT EXVAMINP EVXARANG EXVARATE EXVAPOSF EXVAMINS EXVAMAXS EXVAOVRS EXVATYPE HIGH_SCT EXV_HSCT EXVDISCR EXV_AFAN EXV_MFAN EXV_SLAG DELAYLAG CCN CONFIGURATION TABLES — EXVBCONF (EXV Circuit B Configuration) DESCRIPTION EXV Circ. B Start Pos EXV Circ. B Min Position EXVB Steps in Range EXVB Steps Per Second EXVB Fail Position in % EXVB Minimum Steps EXVB Maximum Steps EXVB Overrun Steps EXVB Stepper Type VALUE nnn.n nnn.n nnnnn nnnnn nnnn.nn nnnnn nnnnn nnnnn nnn DEFAULT 50.0 8.0 1596/2500 200 0 0 1596/2500 167 Bipolar UNITS % % steps steps % steps steps steps POINT NAME EXVBSTRT EXVBMINP EVXBRANG EXVBRATE EXVBPOSF EXVBMINS EXVBMAXS EXVBOVRS EXVBTYPE CCN CONFIGURATION TABLES — MM_CONF (Motormaster Configuration) DESCRIPTION Motormaster Select Head Pressure P Gain Head Pressure I Gain Head Pressure D Gain Minimum Fan Speed VALUE No/Yes nnn.n nnn.n nnn.n nnn.n DEFAULT No 1.0 0.1 0.0 5.0 94 UNITS % POINT NAME MM_SLCT HP_PGAIN HP_IGAIN HP_DGAIN MIN_VHP APPENDIX B — CCN TABLES (cont) CCN SERVICE TABLES — SERVICE DESCRIPTION SERVICE Brine Freeze Point Pump Service Interval COMPRESSOR ENABLE Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 VALUE DEFAULT UNITS F hours nnn.n nnnnn Disable/Enable Disable/Enable Disable/Enable Disable/Enable POINT NAME BRN_FRZ SI_PUMPS ENABLEA1 ENABLEA2 ENABLEB1 ENABLEB2 CCN SETPOINT TABLES — SETPOINT DESCRIPTION COOLING Cooling Setpoint 1 Cooling Setpoint 2 ICE Setpoint –20 to 70 –20 to 70 –20 to 32 44.0 44.0 32.0 RAMP LOADING Cooling Ramp Loading 0.2 to 2.0 1.0 –20 to 34 34.0 Brine Freeze Point Head Setpoint Fan On Set Point Fan Off Set Point Fan Stage Delta Base Fan Off Delta Temp VALUE DEFAULT UNITS F F F POINT NAME CSP1 CSP2 CSP3 CRAMP F F F F F F BRN_FRZ HSP FANONSP FANOFFSP FSTGDLTA B_FANOFF UNITS % delta F delta F POINT NAME EXV_A CIRA_APP APPRA_SP EXVAOVRR SH_A ACTSH_SP ACMOP_SP PLMA CCN MAINTENANCE TABLES — CIRA_EXV DESCRIPTION EXV % Open Circuit A Approach Approach Setpoint EXVA Override Suction Superheat Temp Active Superheat Setpt Active MOP Setpt Cir A EXV Position Limit VALUE nnn nnn.n nnn.n nnnnn nnn.n nn.n nn.n nnn DEFAULT delta F delta F delta F % 95 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — CIRB_EXV DESCRIPTION EXV % Open Circuit B Approach Approach Setpoint EXVB Override Suction Superheat Temp Active Superheat Setpt Active MOP Setpt Cir B EXV Position Limit VALUE nnn nnn.n nnn.n nnnnn nnn.n nn.n nn.n nnn DEFAULT UNITS % delta F delta F delta F delta F delta F % POINT NAME EXV_B CIRB_APP APPRB_SP EXVBOVRR SH_B ACTSH_SP ACMOP_SP PLMB CCN MAINTENANCE TABLES — STRTHOUR DESCRIPTION Machine Operating Hours Machine Starts VALUE nnnnnn nnnnnn UNITS hours POINT NAME HR_MACH CY_MACH Circuit A Run Hours Compressor A1 Run Hours Compressor A2 Run Hours Circuit B Run Hours Compressor B1 Run Hours Compressor B2 Run Hours nnnnnn nnnnnn nnnnnn nnnnnn nnnnnn nnnnnn hours hours hours hours hours hours HR_CIRA HR_A1 HR_A2 HR_CIRB HR_B1 HR_B2 Circuit A Starts Compressor A1 Starts Compressor A2 Starts Circuit B Starts Compressor B1 Starts Compressor B2 Starts nnnnnn nnnnnn nnnnnn nnnnnn nnnnnn nnnnnn PUMP HOURS Pump 1 Run Hours Pump 2 Run Hours nnnnnn nnnnnn CY_CIRA CY_A1 CY_A2 CY_CIRB CY_B1 CY_B2 hours hours HR_PUMP1 HR_PUMP2 CCN MAINTENANCE TABLES — CURRMODS DESCRIPTION CSM controlling Chiller WSM controlling Chiller Master/Slave control Ramp Load Limited Timed Override in effect Low Cooler Suction TempA Low Cooler Suction TempB Slow Change Override Minimum OFF time active Dual Setpoint Temperature Reset Demand/Sound Limited Cooler Freeze Protection Low Temperature Cooling High Temperature Cooling Making ICE Storing ICE High SCT Circuit A High SCT Circuit B Minimum Comp. On Time Pump Off Delay Time Low Sound Mode VALUE On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off POINT NAME MODE_1 MODE_2 MODE_3 MODE_5 MODE_6 MODE_7 MODE_8 MODE_9 MODE_10 MODE_13 MODE_14 MODE_15 MODE_16 MODE_17 MODE_18 MODE_19 MODE_20 MODE_21 MODE_22 MODE_23 MODE_24 MODE_25 96 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — ALARMS DESCRIPTION Active Alarm #1 Active Alarm #2 Active Alarm #3 Active Alarm #4 Active Alarm #5 Active Alarm #6 Active Alarm #7 Active Alarm #8 Active Alarm #9 Active Alarm #10 Active Alarm #11 Active Alarm #12 Active Alarm #13 Active Alarm #14 Active Alarm #15 Active Alarm #16 Active Alarm #17 Active Alarm #18 Active Alarm #19 Active Alarm #20 Active Alarm #21 Active Alarm #22 Active Alarm #23 Active Alarm #24 Active Alarm #25 VALUE Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx Axxx or Txxx POINT NAME ALARM01C ALARM02C ALARM03C ALARM04C ALARM05C ALARM06C ALARM07C ALARM08C ALARM09C ALARM10C ALARM11C ALARM12C ALARM13C ALARM14C ALARM15C ALARM16C ALARM17C ALARM18C ALARM19C ALARM20C ALARM21C ALARM22C ALARM23C ALARM24C ALARM25C CCN MAINTENANCE TABLES — VERSIONS DESCRIPTION VERSION CESR131172CESR131333CESR131460CESR131174CESR131171CESR130227- EXV AUX MBB EMM MARQUEE NAVIGATOR VALUE nn-nn nn-nn nn-nn nn-nn nn-nn nn-nn CCN MAINTENANCE TABLES — LOADFACT DESCRIPTION CAPACITY CONTROL Load/Unload Factor Control Point Entering Fluid Temp Leaving Fluid Temp VALUE snnn.n snnn.n snnn.n snnn.n Ramp Load Limited Slow Change Override Cooler Freeze Protection Low Temperature Cooling High Temperature Cooling Minimum Comp. On Time On/Off On/Off On/Off On/Off On/Off On/Off UNITS F F F POINT NAME SMZ CTRL_PNT EWT LWT MODE_5 MODE_9 MODE_16 MODE_17 MODE_18 MODE_23 97 APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — PM-PUMP DESCRIPTION Pump Service Interval Pump 1 Service Countdown Pump 1 Maintenance Done Pump 2 Service Countdown Pump 2 Maintenance Done Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date VALUE nnnnnn nnnnnn Yes/No nnnnnn Yes/No mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm UNITS hours hours hours POINT NAME SI_PUMPS P1_CDOWN P1_MAINT P2_CDOWN P2_MAINT PMP1_PM0 PMP1_PM1 PMP1_PM2 PMP1_PM3 PMP1_PM4 PMP2_PM0 PMP2_PM1 PMP2_PM2 PMP2_PM3 PMP2_PM4 CCN MAINTENANCE TABLES — PM-STRN DESCRIPTION Strainer Srvc Interval Strainer Srvc Countdown Strainer Maint. Done Strainer Maint. Date Strainer Maint. Date Strainer Maint. Date Strainer Maint. Date Strainer Maint. Date VALUE nnnnnn nnnnnn Yes/No mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm UNITS hours hours POINT NAME SI_STRNR ST_CDOWN ST_MAINT STRN_PM0 STRN_PM1 STRN_PM2 STRN_PM3 STRN_PM4 CCN MAINTENANCE TABLES — PM-COIL DESCRIPTION Coil Cleaning Srvc Inter Coil Service Countdown Coil Cleaning Maint.Done Coil Cleaning Maint.Date Coil Cleaning Maint.Date Coil Cleaning Maint.Date Coil Cleaning Maint.Date Coil Cleaning Maint.Date VALUE nnnnnn nnnnnn Yes/No mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm mm/dd/yy hh:mm UNITS hours hours POINT NAME SI_COIL CL_CDOWN CL_MAINT COIL_PM0 COIL_PM1 COIL_PM2 COIL_PM3 COIL_PM4 CCN MAINTENANCE TABLES — TESTMODE DESCRIPTION Service Test Mode Compressor A1 Relay Compressor A2 Relay Compressor B1 Relay Compressor B2 Relay Fan 1 Relay Fan 2 Relay Cooler Pump Relay 1 Cooler Pump Relay 2 Comp A1 Unload Time Minimum Load Valve Relay Remote Alarm Relay EXV % Open EXV % Open VALUE On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off nn On/Off On/Off nn nn UNITS sec % % 98 POINT NAME NET_CTRL S_A1_RLY S_A2_RLY S_B1_RLY S_B2_RLY S_FAN_1 S_FAN_2 S_CLPMP1 S_CLPMP2 S_A1ULTM S_MLV S_ALM S_EXV_A S_EXV_B APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — RUNTEST DESCRIPTION Percent Total Capacity Percent Available Cap. Discharge Pressure Suction Pressure Head Setpoint Saturated Condensing Tmp Saturated Suction Temp Compr Return Gas Temp Discharge Gas Temp Suction Superheat Temp Compressor A1 Relay Compressor A2 Relay Minimum Load Valve Relay Compressor A1 Feedback Compressor A2 Feedback Percent Total Capacity Percent Available Cap. Discharge Pressure Suction Pressure Head Setpoint Saturated Condensing Tmp Saturated Suction Temp Compr Return Gas Temp Suction Superheat Temp Compressor B1 Relay Compressor B2 Relay Minimum Load Valve Relay VALUE nnn nnn nnn.n nnn.n nnn.n nnn.n nnn.n nnn.n nnn.n nnn.n On/Off On/Off On/Off On/Off On/Off nnn nnn nnn.n nnn.n nnn.n nnn.n nnn.n nnn.n nnn.n On/Off On/Off On/Off Compressor B1 Feedback Compressor B2 Feedback Fan 1 Relay Fan 2 Relay On/Off On/Off On/Off On/Off Outside Air Temperature Space Temperature Cooler Pump Relay 1 Cooler Pump Relay 2 Cooler Pump 1 Interlock Cooler Pump 2 Interlock Cooler Entering Fluid Cooler Leaving Fluid Compressor A1 Size Compressor A2 Size Compressor B1 Size Compressor B2 Size Cooler Flow Switch UNITS % % psig psig F F F F F ^F % % psig psig F F F F ^F POINT NAME CAPA_T CAPA_A DP_A SP_A HSP TMP_SCTA TMP_SSTA TMP_RGTA DISGAS SH_A K_A1_RLY K_A2_RLY MLV_RLY K_A1_FBK K_A2_FBK CAPB_T CAPB_A DP_B SP_B HSP TMP_SCTB TMP_SSTB TMP_RGTB SH_B K_B1_RLY K_B2_RLY MLV_RLY K_B1_FBK K_B2_FBK FAN_1 FAN_2 F F nnn.n nnn.n On/Off On/Off Open/Closed Open/Closed nnn.n nnn.n nnn nnn nnn nnn On/Off F F tons tons tons tons 99 OAT SPT COOLPMP1 COOLPMP2 PMP1_FBK PMP2_FBK COOL_EWT COOL_LWT SIZE_A1 SIZE_A2 SIZE_B1 SIZE_B2 COOLFLOW APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — DUALCHIL DESCRIPTION Dual Chiller Link Good? Master Chiller Role VALUE Yes/No Stand Alone, Lead Chiller, Lag Chiller Stand Alone, Lead Chiller, Lag Chiller snnn.n snnn.n snnn.n UNITS F F F LEAD_CP LAG_CP CTRL_PNT Cool EnteringFluid-Slave Cool Leaving Fluid-Slave Cooler Entering Fluid Cooler Leaving Fluid Lead/Lag Leaving Fluid snnn.n snnn.n snnn.n snnn.n snnn.n F F F F F COOLEWTS COOLLWTS COOL_EWT COOL_LWT DUAL_LWT Percent Avail.Capacity Percent Avail.Cap.Slave 0-100 0-100 % % CAP_A CAP_A_S Lag Start Delay Time Load/Unload Factor Load/Unload Factor-Slave Lead SMZ Clear Commanded Lag SMZ Clear Commanded Lag Commanded Off? hh:mm snnn.n snnn.n Yes/No Yes/No Yes/No Dual Chill Lead CapLimit Dual Chill Lag CapLimit 0-100 0-100 Slave Chiller Role Lead Chiller Ctrl Point Lag Chiller Ctrl Point Control Point POINT NAME DC_LINK MC_ROLE SC_ROLE LAGDELAY SMZ SMZSLAVE LEADSMZC LAG_SMZC LAG_OFF % % 100 DCLDCAPL DCLGCAPL APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS PUMP OPTION PUMP SIZE 1, 8 1.0 HP 2, 9 1.5 HP 3, B 2.0 HP 4, C 3.0 HP 5, 6, D, F 5.0 HP 7, G 7.5 HP UNIT VOLTAGE V-Hz (3 Ph) 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 101 OVERLOAD SETTING 4.0 2.0 1.6 2.4 5.4 2.7 2.2 3.3 6.6 3.3 2.6 4.0 8.8 4.4 3.5 5.3 14.0 7.0 5.6 8.5 22.8 11.4 9.1 13.8 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING Optional BACnet Communications Wiring — 6 5 7 8 2 34 5 6 10's 1 9 0 2 34 7 8 9 0 1 The following section is used to configure the UPC Open controller which is used when the BACnet communications option is selected. The UPC Open controller is mounted in the main control box per unit components arrangement diagrams. TO ADDRESS THE UPC OPEN CONTROLLER — The user must give the UPC Open controller an address that is unique on the BACnet* network. Perform the following procedure to assign an address: 1. If the UPC Open controller is powered, pull the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the address each time power is applied to it. 2. Using the rotary switches (see Fig. A and B), set the controller's address. Set the Tens (10's) switch to the tens digit of the address, and set the Ones (1's) switch to the ones digit. As an example in Fig. B, if the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on the Ones (1's) switch to 5. 1's Fig. B — Address Rotary Switches BACNET DEVICE INSTANCE ADDRESS — The UPC Open controller also has a BACnet Device Instance address. This Device Instance MUST be unique for the complete BACnet system in which the UPC Open controller is installed. The Device Instance is auto generated by default and is derived by adding the MAC address to the end of the Network Number. The Network Number of a new UPC Open controller is 16101, but it can be changed using i-Vu® Tools or BACView device. By default, a MAC address of 20 will result in a Device Instance of 16101 + 20 which would be a Device Instance of 1610120. BT485 TERMINATOR BACNET CONNECTION (BAS PORT) POWER LED Tx1 LED Rx1 LED Tx2 LED Rx2 LED 23 45 01 8 67 9 EIA-485 JUMPERS 01 8 67 9 23 45 BACNET BAUD RATE DIP SWITCHES ADDRESS ROTARY SWITCHES RUN LED ERROR LED Fig. A — UPC Open Controller * Sponsored by ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers). 102 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) CONFIGURING THE BAS PORT FOR BACNET MS/ TP — Use the same baud rate and communication settings for all controllers on the network segment. The UPC Open controller is fixed at 8 data bits, No Parity, and 1 Stop bit for this protocol's communications. If the UPC Open controller has been wired for power, pull the screw terminal connector from the controller's power terminals labeled Gnd and HOT. The controller reads the DIP Switches and jumpers each time power is applied to it. Set the BAS Port DIP switch DS3 to “enable.” Set the BAS Port DIP switch DS4 to “E1-485.” Set the BMS Protocol DIP switches DS8 through DS5 to “MSTP.” See Table A. Fig. C — DIP Switches Table A — SW3 Protocol Switch Settings for MS/TP DS8 Off DS7 Off DS6 Off DS5 Off DS4 On Wire the controllers on an MS/TP network segment in a daisy-chain configuration. Wire specifications for the cable are 22 AWG (American Wire Gage) or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire. The maximum length is 2000 ft. Install a BT485 terminator on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing. See Fig. A, D, and E. To wire the UPC Open controller to the BAS network: 1. Pull the screw terminal connector from the controller's BAS Port. 2. Check the communications wiring for shorts and grounds. 3. Connect the communications wiring to the BAS port’s screw terminals labeled Net +, Net -, and Shield. NOTE: Use the same polarity throughout the network segment. 4. Insert the power screw terminal connector into the UPC Open controller's power terminals if they are not currently connected. 5. Verify communication with the network by viewing a module status report. To perform a module status report using the BACview keypad/display unit, press and hold the “FN” key then press the “.” Key. DS3 Off Verify that the EIA-485 jumpers below the CCN Port are set to EIA-485 and 2W. The example in Fig. C shows the BAS Port DIP Switches set for 76.8k (Carrier default) and MS/TP. Set the BAS Port DIP Switches DS2 and DS1 for the appropriate communications speed of the MS/TP network (9600, 19.2k, 38.4k, or 76.8k bps). See Fig. D and Table B. Table B — Baud Selection Table BAUD RATE 9,600 19,200 38,400 76,800 DS2 Off On Off On DS1 Off Off On On WIRING THE UPC OPEN CONTROLLER TO THE MS/ TP NETWORK — The UPC Open controller communicates using BACnet on an MS/TP network segment communications at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps. Fig. D — Network Wiring 103 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Fig. E — BT485 Terminator Installation temperature rating specifications list two acceptable alternatives. The Halar specification has a higher temperature rating and a tougher outer jacket than the SmokeGard specification, and it is appropriate for use in applications where the user is concerned about abrasion. The Halar jacket is also less likely to crack in extremely low temperatures. NOTE: Use the specified type of wire and cable for maximum signal integrity. To install a BT485 terminator, push the BT485 terminator on to the BT485 connector located near the BACnet connector. NOTE: The BT485 terminator has no polarity associated with it. To order a BT485 terminator, consult Commercial Products i-Vu Open Control System Master Prices. MS/TP WIRING RECOMMENDATIONS — Recommendations are shown in Tables C and D. The wire jacket and UL Table C — MS/TP Wiring Recommendations SPECIFICATION Cable Conductor Insulation Color Code Twist Lay Shielding Jacket DC Resistance Capacitance Characteristic Impedance Weight UL Temperature Rating Voltage Listing AWG CL2P DC FEP NEC O.D. TC UL — — — — — — — — RECOMMMENDATION Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable 22 or 24 AWG stranded copper (tin plated) Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D. Black/White 2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal Aluminum/Mylar shield with 24 AWG TC drain wire SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D. Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D. 15.2 Ohms/1000 feet (50 Ohms/km) nominal 12.5 pF/ft (41 pF/meter) nominal conductor to conductor 100 Ohms nominal 12 lb/1000 feet (17.9 kg/km) SmokeGard 167°F (75°C) Halar -40 to 302°F (-40 to 150°C) 300 Vac, power limited UL: NEC CL2P, or better LEGEND American Wire Gage Class 2 Plenum Cable Direct Current Fluorinated Ethylene Polymer National Electrical Code Outside Diameter Tinned Copper Underwriters Laboratories 104 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table D — Open System Wiring Specifications and Recommended Vendors WIRING SPECIFICATIONS Wire Type RECOMMENDED VENDORS AND PART NUMBERS Connect Air Contractors Belden RMCORP Wire and Cable International Description 22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications. MS/TP Network (RS-485) 24 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications. Rnet 4 conductor, unshielded, CMP, 18 AWG, plenum rated. AWG CL2P CMP FEP TC — — — — — W221P-22227 — 25160PV CLP0520LC W241P-2000F 82841 25120-OR — W184C-2099BLB 6302UE 21450 CLP0442 LEGEND American Wire Gage Class 2 Plenum Cable Communications Plenum Rated Fluorinated Ethylene Polymer Tinned Copper ber and CCN Bus number. The factory default settings for CCN Element and CCN Bus number are 1 and 0 respectively. If modifications to the default Element and Bus number are required, both the ComfortLink and UPC Open configurations must be changed. The following configurations are used to set the CCN Address and Bus number in the ComfortLink control. These configurations can be changed using the scrolling marquee display or accessory Navigator handheld device. Configuration→CCN→CCN.A (CCN Address) Configuration→CCN→CCN.B (CCN Bus Number) The following configurations are used to set the CCN Address and Bus Number in the UPC Open controller. These configurations can be changed using the accessory BACview6 display. Navigation: BACview→CCN Home: Element Comm Stat Element: 1 Bus: 0 LOCAL ACCESS TO THE UPC OPEN CONTROLLER — The user can use a BACview6 handheld keypad display unit or the Virtual BACview software as a local user interface to an Open controller. These items let the user access the controller network information. These are accessory items and do not come with the UPC Open controller. The BACview6 unit connects to the local access port on the UPC Open controller. See Fig. F. The BACview software must be running on a laptop computer that is connected to the local access port on the UPC Open controller. The laptop will require an additional USB link cable for connection. See the BACview Installation and User Guide for instructions on connecting and using the BACview6 device. To order a BACview6 Handheld (BV6H), consult Commercial Products i-Vu Open Control System Master Prices. CONFIGURING THE UPC OPEN CONTROLLER'S PROPERTIES — The UPC Open device and ComfortLink control must be set to the same CCN Address (Element) num- Fig. F — BACview6 Device Connection 105 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) If the UPC Open is used with the chiller application of Lead/Lag/Standby, all chillers and UPC Open's CCN element numbers must be changed to a unique number in order to follow CCN specifications. In this application, there can only be a maximum of 3 UPC Open controllers on a CCN bus. For the CCN Alarm Acknowledger configuration, the UPC Open defaults to CCN Acknowledger. If a Chiller Lead/Lag/ Standby application is being used, then the Carrier technician must change the configuration to only one CCN Acknowledger on the CCN bus. For the CCN Time Broadcaster configuration, the UPC Open defaults to CCN Time Broadcaster. If the Chiller Lead/ Lag/Standby application is used, then the Carrier technician must change the configuration to only one CCN Time Broadcaster on the CCN bus. TROUBLESHOOTING — If there are problems wiring or addressing the UPC Open controller, contact Carrier Technical Support. COMMUNICATION LEDS — The LEDs indicate if the controller is communicating with the devices on the network. See Tables E and F. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs become. See Fig. A for location of LEDs on UPC Open module. REPLACING THE UPC OPEN BATTERY — The UPC Open controller's 10-year lithium CR2032 battery provides a minimum of 10,000 hours of data retention during power outages. IMPORTANT: Power must be ON to the UPC Open when replacing the battery, or the date, time, and trend data will be lost. Remove the battery from the controller, making note of the battery's polarity. Insert the new battery, matching the battery's polarity with the polarity indicated on the UPC Open controller. NETWORK POINTS LIST — The points list for the controller is shown in Table G. Refer to Appendix B for additional information on CCN point name. Table E — LED Status Indicators LED Power Rx Tx Run Error STATUS Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition that caused the fault returns to normal. Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2. Lights when the controller transmits data to the network segment; there is an Rx LED for Ports 1 and 2. Lights based on controller status. See Table F. Lights based on controller status. See Table F. Table F — Run and Error LEDs Controller and Network Status Indication RUN LED 2 flashes per second 2 flashes per second 2 flashes per second 2 flashes per second 2 flashes per second 5 flashes per second 5 flashes per second 7 flashes per second 14 flashes per second ERROR LED Off 2 flashes, alternating with Run LED 3 flashes, then off 1 flash per second On On Off 7 flashes per second, alternating with Run LED 14 flashes per second, alternating with Run LED 106 STATUS Normal Five minute auto-restart delay after system error Controller has just been formatted Controller is alone on the network Exec halted after frequent system errors or control programs halted Exec start-up aborted, Boot is running Firmware transfer in progress, Boot is running Ten second recovery period after brownout Brownout APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table G — Network Points List POINT DESCRIPTION 4-20 ma Demand Signal 4-20 ma Reset Signal Active Demand Limit Active Setpoint Alarm State CCN Chiller CCN Loadshed Signal Circuit A Run Hours Circuit A Starts Circuit B Run Hours Circuit B Starts Coil Cleaning Maint.Done Coil Cleaning Srvc Inter Coil Service Countdown Comp A1 Unload Time Compr Return Gas Temp Compr Return Gas Temp Compressor A1 Feedback Compressor A1 Relay Compressor A1 Run Hours Compressor A1 Starts Compressor A2 Feedback Compressor A2 Relay Compressor A2 Run Hours Compressor A2 Starts Compressor B1 Feedback Compressor B1 Relay Compressor B1 Run Hours Compressor B1 Starts Compressor B2 Feedback Compressor B2 Relay Compressor B2 Run Hours Compressor B2 Starts Control Mode Control Point Cooler Entering Fluid Cooler Flow Switch Cooler Freeze Protection Cooler Leaving Fluid Cooler LWT Setpoint Cooler Pump 1 Interlock Cooler Pump 2 Interlock Cooler Pump Relay 1 Cooler Pump Relay 2 Cooler Pump Select Cooler Pump Shutdown Dly Cooler/Pump Heater Cooling Ramp Loading Cooling Setpoint 1 R W CCN POINT NAME LMT_MA RST_MA DEM_LIM SP READ/ UNITS WRITE R mA R °F R/W % R °F ALM R CHIL_S_S DL_STAT HR_CIRA CY_CIRA HR_CIRB CY_CIRB CL_MAINT SI_COIL CL_CDOWN A1UNLTME TMP_RGTA TMP_RGTB K_A1_FBK K_A1_RLY HR_A1 CY_A1 K_A2_FBK K_A2_RLY HR_A2 CY_A2 K_B1_FBK K_B1_RLY HR_B1 CY_B1 K_B2_FBK K_B2_RLY HR_B2 CY_B2 R/W R R R R R R/W R/W R R R R R R R R R R R R R R R R R R R R CONTROL R CTRL_PNT COOL_EWT COOLFLOW MODE_16 COOL_LWT LWT_SP PMP1_FBK PMP2_FBK COOLPMP1 COOLPMP2 PMP_SLCT PUMP_DLY COOL_HTR CRAMP CSP1 R/W R R R R R R R R R R R/W R R/W R/W DEFAULT VALUE RANGE 100 0 - 100 Start 1 = Normal 2 = Alert 3 = Alarm Start/Stop No 8760 Yes/No 0 - 65535 44.0 1 = Test 2 = Local Off 3 = CCN Off 4 = Clock Off 5 = Emergency Stop 6= Local On 7 = CCN On 8 = Clock On 9 = Heat Enabled 10 = Pump Delay -20 - 70 min 1 0 - 10 °F 1.0 44.0 0.2 - 2.0 -20 - 70 hr hr hr hr °F °F hr hr hr hr °F °F °F °F LEGEND — Read — Write 107 BACNET OBJECT ID AV:36 AV:33 AV:2 AV:4 BACNET OBJECT NAME lmt_ma_1 rst_ma_1 dem_lim_1 sp_1 MSV:1 alm_msv_1 BV:4 AV:37 AV:59 AV:65 AV:62 AV:68 BV:54 AV:50 AV:49 AV:73 AV:20 AV:28 BV:16 BV:13 AV:60 AV:66 BV:17 BV:14 AV:61 AV:67 BV:20 BV:18 AV:63 AV:69 BV:21 BV:19 AV:64 AV:70 chil_s_s_1 dl_stat_1 hr_cira_1 cy_cira_1 hr_cirb_1 cy_cirb_1 cl_maint_1 si_coil_1 cl_cdown_1 a1unltme_1 tmp_rgta_1 tmp_rgtb_1 k_a1_fbk_1 k_a1_rly_1 hr_a1_1 cy_a1_1 k_a2_fbk_1 k_a2_rly_1 hr_a2_1 cy_a2_1 k_b1_fbk_1 k_b1_rly_1 hr_b1_1 cy_b1_1 k_b2_fbk_1 k_b2_rly_1 hr_b2_1 cy_b2_1 MSV:2 stat_msv_1 AV:5 AV:30 BV:11 BV:42 AV:31 AV:38 BV:9 BV:10 BV:7 BV:8 AV:40 AV:41 BV:24 AV:56 AV:53 ctrl_pnt_1 cool_ewt_1 coolflow_1 mode_16_1 cool_lwt_1 lwt_sp_1 pmp1_fbk_1 pmp2_fbk_1 coolpmp1_1 coolpmp2_1 pmp_slct_1 pump_dly_1 cool_htr_1 cramp_1 csp1_1 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table G — Network Points List (cont) POINT DESCRIPTION POINT NAME Cooling Setpoint 2 CSM Controlling Chiller Demand Level 1 Demand Level 2 Demand Level 3 Demand Limit Switch 1 Demand Limit Switch 2 Demand/Sound Limited Discharge Gas Temp Discharge Pressure Discharge Pressure Dual Setpoint Dual Setpoint Switch Element Comm Status Element Communications Alarm Emergency Stop Entering Fluid Temp EXV % Open EXV % Open Fan 1 Relay Fan 2 Relay Head Setpoint Heat Request High SCT Circuit A High SCT Circuit B High Temperature Cooling Ice Done Ice Setpoint EMSTOP EWT EXV_A EXV_B FAN_1 FAN_2 HSP HEAT_REQ MODE_21 MODE_22 MODE_18 ICE_DONE CSP3 R/W R R R R R R R R R R R R/W Lead/Lag Circuit Select LEAD_TYP R/W Lead/Lag Circuit Select Lead/Lag Leaving Fluid Leadpump Leaving Fluid Temp - Prime Variable Loading Sequence Select Local Schedule Low Cooler Suction Temp A Low Cooler Suction Temp B Low Sound Active Low Sound Mode Low Temperature Cooling Machine Operating Hours Machine Starts Making ICE Master/Slave Control Minimum Comp. On Time Minimum Load Valve Relay Minimum OFF Time Active Minutes Off Time Occupied Outside Air Temperature Override Modes in Effect Percent Available Cap. Percent Available Cap. LEAD_TYP DUAL_LWT LEADPUMP R R R °F LWT R °F SEQ_TYPE R R R R R R R R R R R R R R R/W R R R R R R W CSP2 MODE_1 READ/ UNITS WRITE R/W °F R R % R % R % R R R R °F R psig R psig R R R DMD_SW1 DMD_SW2 MODE_15 DISGAS DP_A DP_B MODE_13 DUAL_IN DEFAULT VALUE 44.0 RANGE -20 - 70 R MODE_7 MODE_8 LSACTIVE MODE_25 MODE_17 HR_MACH CY_MACH MODE_19 MODE_3 MODE_23 MLV_RLY MODE_10 DELAY OCC OAT MODE CAP_A CAPB_A Enabled Enabled/Emstop 32.0 -20 - 32 1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads °F % % °F °F 1 hr min 0 °F % % LEGEND — Read — Write 108 0 - 15 BACNET OBJECT ID AV:54 BV:30 AV:75 AV:76 AV:77 BV:25 BV:26 BV:41 AV:15 AV:13 AV:23 BV:39 BV:29 BV:2999 BACNET OBJECT NAME csp2_1 mode_1_1 dmv_lvl_1_perct_1 dmv_lvl_2_perct_1 dmv_lvl_3_perct_1 dmd_sw1_1 dmd_sw2_1 mode_15_1 disgas_1 dp_a_1 dp_b_1 mode_13_1 dual_in_1 element_stat_1 BV:58 comm_lost_alm_1 BV:6 AV:6 AV:18 AV:27 BV:22 BV:23 AV:29 BV:28 BV:47 BV:48 BV:44 BV:27 AV:55 emstop_1 ewt_1 exv_a_1 exv_b_1 fan_1_1 fan_2_1 hsp_1 heat_req_1 mode_21_1 mode_22_1 mode_18_1 ice_done_1 csp3_1 AV:43 lead_typ_1 MSV:6 AV:32 MSV:9 lead_typ_msv_1 dual_lwt_1 leadpump_msv_1 AV:7 lwt_1 AV:74 BV:1 BV:35 BV:36 BV:2 BV:51 BV:43 AV:57 AV:58 BV:45 BV:32 BV:49 BV:15 BV:38 AV:42 BV:3 AV:34 BV:5 AV:12 AV:22 seq_type_1 schedule_1 mode_7_1 mode_8_1 lsactive_1 mode_25_1 mode_17_1 hr_mach_1 cy_mach_1 mode_19_1 mode_3_1 mode_23_1 mlv_rly_1 mode_10_1 delay_1 occ_1 oat_1 mode_1 capa_a_1 capb_a_1 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table G — Network Points List (cont) POINT DESCRIPTION Percent Total Capacity Percent Total Capacity Percent Total Capacity Pump 1 Maintenance Done Pump 1 Run Hours Pump 1 Service Countdown Pump 2 Maintenance Done Pump 2 Run Hours Pump 2 Service Countdown Pump Changeover Hours Pump Off Delay Time Pump Service Interval Ramp Load Limited Requested Stage Rotate Cooler Pumps Now Saturated Condensing Tmp Saturated Condensing Tmp Saturated Suction Temp Saturated Suction Temp Slow Change Override Space Temperature Storing ICE Strainer Maint. Done Strainer Srvc Countdown Strainer Srvc Interval Suction Pressure Suction Pressure Suction Superheat Temp Suction Superheat Temp System Cooling Demand Level System Demand Limiting Temperature Reset Timed Override In Effect User Defined Analog 1 User Defined Analog 2 User Defined Analog 3 User Defined Analog 4 User Defined Analog 5 User Defined Binary 1 User Defined Binary 2 User Defined Binary 3 User Defined Binary 4 User Defined Binary 5 Var Head Press Output WSM Controlling Chiller R W POINT NAME CAP_T CAPA_T CAPB_T P1_MAINT HR_PUMP1 P1_CDOWN P2_MAINT HR_PUMP2 P2_CDOWN PMP_DLTA MODE_24 SI_PUMPS MODE_5 STAGE ROT_PUMP TMP_SCTA TMP_SCTB TMP_SSTA TMP_SSTB MODE_9 SPT MODE_20 ST_MAINT ST_CDOWN SI_STRNR SP_A SP_B SH_A SH_B MODE_14 MODE_6 VHP_ACT MODE_2 READ/ UNITS WRITE R % R % R % R/W R hr R hr R/W R hr R hr R/W hr R R/W hr R R R/W R °F R °F R °F R °F R R/W °F R R/W R hr R/W hr R psig R psig R °^F R °^F DEFAULT VALUE RANGE BACNET OBJECT ID AV:3 AV:11 AV:21 BV:52 AV:71 AV:46 BV:53 AV:72 AV:47 AV:39 BV:50 AV:48 BV:33 AV:9 BV:12 AV:16 AV:25 AV:17 AV:26 BV:37 AV:35 BV:46 BV:55 AV:52 AV:51 AV:14 AV:24 AV:44 AV:45 BACNET OBJECT NAME cap_t_1 capa_t_1 capb_t_1 p1_maint_1 hr_pump1_1 p1_cdown_1 p2_maint_1 hr_pump2_1 p2_cdown_1 pmp_dlta_1 mode_24_1 si_pumps_1 mode_5_1 stage_1 rot_pump_1 tmp_scta_1 tmp_sctb_1 tmp_ssta_1 tmp_sstb_1 mode_9_1 spt_1 mode_20_1 st_maint_1 st_cdown_1 si_strnr_1 sp_a_1 sp_b_1 sh_a_1 sh_b_1 No Yes/No No Yes/No 500 10 - 2000 8760 0 - 65535 No No/Yes 8760 -40.0 - 245 No Yes/No 8760 0 - 65535 R AV:9006 cool_demand_level_1 R R R R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R R BV:57 BV:40 BV:34 AV:2901 AV:2902 AV:2903 AV:2904 AV:2905 BV:2911 BV:2912 BV:2913 BV:2914 BV:2915 AV:19 BV:31 dem_lmt_act_1 mode_14_1 mode_6_1 user_analog_1_1 user_analog_2_1 user_analog_3_1 user_analog_4_1 user_analog_5_1 user_binary_1_1 user_binary_2_1 user_binary_3_1 user_binary_4_1 user_binary_5_1 vhp_act_1 mode_2_1 sq m sq m sq m sq m sq m sq m sq m sq m sq m sq m mA LEGEND — Read — Write 109 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS 30RAP Maintenance Interval Requirements WEEKLY Compressor Check oil level. Economizer Cooler None. Controls Condenser None. Starter None. Review Alarm/Alert History. None. MONTHLY Compressor Check oil level. Cooler None. Condenser None. Economizer Controls Starter None. Inspect sight glass for moisture and refrigerant level. None. QUARTERLY Compressor Cooler Condenser Check oil level Economizer Check refrigerant charge. Check all connections for leaks. None. Controls Starter None. Perform an Automated Controls test. Run all compressors and ensure proper operation. Ensure operation of units flow switch. ANNUALLY Compressor Cooler Condenser Check Oil Level. Obtain and test an oil sample. Check refrigerant charge. Check all connections for leaks. Check approach on unit to determine if tubes need cleaning. Check for temperature drop across filter drier to determine if filter needs replacement. Inspect all coils and clean. Check condenser approach to determine if tubes need to be cleaned. Economizer Verify proper operation of EXVs and TXVs Controls Perform an Automated Controls test. Run all compressors and ensure proper operation. Ensure operation of unit flow switch. Starter Inspect all electrical connections and tighten as needed. Measure current to each compressor and inspect contactors. NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty. 110 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Weekly Maintenance Log Plant ___________________________ Machine Model No. ________________ DATE OIL LEVEL CHECK ALARMS / FAULTS OPERATOR INITIALS REMARKS NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty. 111 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Monthly Maintenance Log Month Date Operator UNIT SECTION Compressor Cooler Condenser Controls Starter 112 System 1 / ACTION Check Oil Level Send Oil Sample Out for Analysis Leak Test Inspect and Clean Cooler Inspect Cooler Heater Leak Test Record Water Pressure Differential (PSI) Inspect Water Pumps Leak Test Inspect and Clean Condenser Coil General Cleaning and Tightening Connections Check Pressure Transducers Confirm Accuracy of Thermistors General Tightening & Cleaning Connections Inspect All Contactors Check Refrigerant Charge Verify Operation Of EXVs And Record Position Record System Super Heat 2 / UNIT yes/no yes/no ppm yes/no amps yes/no PSI yes/no ppm yes/no yes/no yes/no yes/no yes/no yes/no yes/no 0-100% deg. F NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty. / 3 / / 4 / / 5 / / 6 / / 7 / / 8 / ENTRY Annually Every 3 - 5 Years Annually Annually Annually / 9 / / / 10 / / 11 / / 12 / / APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Seasonal Shutdown Log Month Date Operator UNIT SECTION Cooler Controls 1 / 2 / / 3 / ACTION Isolate and Drain Cooler Add Glycol for Freeze Protection Do Not Disconnect Control Power NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty. / 4 / / 5 / / 6 / / 7 / ENTRY / 8 / / 9 / / / 10 / / 11 / / 12 / / 113 Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg 114 12-10 Replaces: 30RAP-1T START-UP CHECKLIST FOR 30RAP LIQUID CHILLER (Remove and use for Job File) I. Project Information JOB NAME ______________________________________________________________________________ ADDRESS _______________________________________________________________________________ CITY ____________________________________________ STATE _______________ ZIP______________ INSTALLING CONTRACTOR ________________________________________________________________ SALES OFFICE ___________________________________________________________________________ START-UP PERFORMED BY ________________________________________________________________ Design Information CAPACITY CEAT EWT LWT FLUID TYPE FLOW RATE P.D. UNIT MODEL ______________________________ SERIAL ________________________________ II. Preliminary Equipment Check IS THERE ANY PHYSICAL DAMAGE? YES NO DESCRIPTION ____________________________________________________________________________ ________________________________________________________________________________________ 1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS. YES NO 2. POWER SUPPLY AGREES WITH THE UNIT NAMEPLATE. YES NO 3. ELECTRICAL POWER WIRING IS INSTALLED PROPERLY. YES NO 4. UNIT IS PROPERLY GROUNDED. YES NO 5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY. YES NO 6. ALL TERMINALS ARE TIGHT. YES NO 7. ALL PLUG ASSEMBLIES ARE TIGHT. YES NO 8. ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES. YES NO 9. ALL THERMISTORS ARE FULLY INSERTED INTO WELLS. YES NO 1. ALL CHILLED WATER VALVES ARE OPEN. YES NO 2. ALL PIPING IS CONNECTED PROPERLY. YES NO 3. ALL AIR HAS BEEN PURGED FROM THE SYSTEM. YES NO 4. CHILLED WATER PUMP IS OPERATING WITH THE CORRECT ROTATION. YES NO Chilled Water System Check Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg CL-1 12-10 Replaces: 30RAP-1T YES NO 6. CHILLED WATER FLOW SWITCH IS OPERATIONAL. YES NO 7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40). YES NO 8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C). YES ANTIFREEZE TYPE _____________________ CONCENTRATION __________%. IF OUTDOOR AMBIENT IS BELOW 32 F (0° C) THEN ITEMS 9-11 HAVE TO BE COMPLETED TO PROVIDE COOLER FREEZE PROTECTION TO –20 F (–29 C). (REFER TO WINTER SHUTDOWN FOR PROPER COOLER WINTERIZATION PROCEDURE.) NO YES NO 10. COOLER HEATERS INSTALLED AND OPERATIONAL. YES NO 11. CHILLED WATER PUMP CONTROLLED BY CHILLER. YES NO 1. COMPRESSOR OIL LEVEL IS CORRECT. YES NO 2. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 7-10 FT-LB. (9.5-13.5 N-M). YES NO 3. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS. YES NO 4. VOLTAGE IS WITHIN UNIT NAMEPLATE RANGE. YES NO 5. CONTROL TRANSFORMER PRIMARY CONNECTION SET FOR PROPER VOLTAGE. YES NO 9. OUTDOOR PIPING WRAPPED WITH ELECTRIC HEATER TAPE, INSULATED AND OPERATIONAL. III. Unit Start-Up 6. CONTROL TRANSFORMER SECONDARY VOLTAGE = 7. CHECK VOLTAGE IMBALANCE: A-B A-C B-C AVERAGE VOLTAGE = (A-B + A-C + B-C)/3 MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = VOLTAGE IMBALANCE = ____________% (MAX. DEVIATION/AVERAGE VOLTAGE) X 100 VOLTAGE IMBALANCE LESS THAN 2%. YES (DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%. CONTACT LOCAL UTILITY FOR ASSISTANCE.) NO YES NO 1. COMPLETE COMPONENT TEST. YES NO 2. CHECK REFRIGERANT AND OIL CHARGE. YES NO 3. RECORD COMPRESSOR MOTOR CURRENT. YES NO 4. RECORD CONFIGURATION SETTINGS. YES NO 5. RECORD OPERATING TEMPERATURES AND PRESSURES. YES NO 8. VERIFY COOLER FLOW RATE. PRESSURE ENTERING COOLER PRESSURE LEAVING COOLER COOLER PRESSURE DROP Psig X 2.31 ft./psi = kPa X 0.334 m/psi COOLER FLOW RATE ________ psig (kPa) ________ psig (kPa) ________ psig (kPa) ________ ft of water ________ m of water ________ gpm (l/s) (See Cooler Pressure Drop Curves from Installation Instructions) Start and Operate Machine. Complete the Following: 6. PROVIDE OPERATING INSTRUCTIONS TO OWNER’S PERSONNEL. CL-2 Instruction Time ________ hours. - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE 5. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER. OPERATING DATA: RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN MACHINE IS IN A STABLE OPERATING CONDITION: PRESSURE/TEMPERATURE CIRCUIT A CIRCUIT B DISCHARGE PRESSURE DP.A DP.B SUCTION PRESSURE SP.A SP.B SATURATED CONDENSING TEMP SCT.A SCT.B SATURATED SUCTION TEMP SST.A SST.B RETURN GAS TEMPERATURE RGT.A RGT.B LIQUID LINE TEMPERATURE* DISCHARGE LINE TEMPERATURE* *Readings taken with a digital thermometer. COOLER EWT EWT COOLER LWT LWT OUTDOOR-AIR TEMPERATURE OAT CONTROL POINT CTPT PERCENT TOTAL CAPACITY CAP LEAD/LAG LEAVING FLUID DLWT (Dual Chiller Control Only) Compressor Running Current — All readings taken at full load. COMPRESSOR MOTOR CURRENT L1 L2 L3 L1 L2 L3 L1 L2 L3 COMPRESSOR A1 COMPRESSOR A2 COMPRESSOR B1 COMPRESSOR B2 CONDENSER FAN MOTOR CURRENT FAN MOTOR 1 FAN MOTOR 2 FAN MOTOR 3 FAN MOTOR 4 COOLER PUMP MOTOR CURRENT COOLER PUMP 1 COOLER PUMP 2 CL-3 SUB-MODE VERS ITEM MBB AUX1 EXV EMM MARQUEE NAVIGATOR DISPLAY ITEM EXPANSION CESR-131460- _ _-_ _ CESR-131333- _ _-_ _ CESR-131172- _ _-_ _ CESR-131174- _ _-_ _ CESR-131171- _ _-_ _ CESR-131227- _ _-_ _ (PRESS ENTER AND ESCAPE SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS) COMMENTS: _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ SIGNATURES: START-UP TECHNICIAN _____________________________ CUSTOMER REPRESENTATIVE _____________________________ DATE ___________________________________ DATE ________________________________________ CL-4 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE Record Software Versions MODE — RUN STATUS III. Unit Start-Up (cont) RECORD CONFIGURATION SETTINGS UNIT (Configuration Settings) SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY UNIT CONFIGURATION UNIT SIZE UNIT SIZE XXX SZA.1 COMPRESSOR A1 SIZE XX SZA.2 COMPRESSOR A2 SIZE XX SZA.3 COMPRESSOR A3 SIZE XX SZA.4 COMPRESSOR A4 SIZE XX SZB.1 COMPRESSOR B1 SIZE XX SZB.2 COMPRESSOR B2 SIZE XX SZB.3 COMPRESSOR B3 SIZE XX SZB.4 COMPRESSOR B4 SIZE XX SH.SP SUPERHEAT SETPOINT XX.X F FAN.S FAN STAGING SELECT X EXV EXV MODULE INSTALLED YES/NO A1.TY COMPRESSOR A1 DIGITAL? YES/NO MAX.T MAXIMUM A1 UNLOAD TIME XX PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW: OPTIONS1 (Options Configuration) SUBMODE ITEM ITEM EXPANSION DISPLAY UNIT OPTIONS 1 HARDWARE FLUD OPT1 COOLER FLUID X MLV.S MINIMUM LOAD VALVE SELECT YES/NO D.G.EN DISCHARGE GAS TEMP ENABLE ENBL/DSBL CSB.E CSB BOARDS ENABLE ENBL/DSBL CPC COOLER PUMP CONTROL ON/OFF PM1E COOLER PUMP 1 ENABLE YES/NO PM2E COOLER PUMP 2 ENABLE YES/NO PM.P.S COOLER PMP PERIODIC STRT YES/NO PM.SL COOLER PUMP SELECT X PM.DY COOLER PUMP SHUTDOWN DLY XX MIN PM.DT PUMP CHANGEOVER HOURS XXXX HRS ROT.P ROTATE COOLER PUMPS NOW YES/NO EMM EMM MODULE INSTALLED YES/NO CND.T CND HX TYP 0=RTPF 1=MCHX 0/1 MOPS EXV MOP SET POINT XX APPR CONFIG APPROACH SETPOINT XX CL-5 ENTRY PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. OPTIONS2 (Options Configuration) SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY UNIT OPTIONS 2 CONTROLS OPT2 CTRL CONTROL METHOD X LOAD LOADING SEQUENCE SELECT X LLCS LEAD/LAG CIRCUIT SELECT X LCWT HIGH LCW ALERT LIMIT XX.X F DELY MINUTES OFF TIME XX ICE.M ICE MODE ENABLE ENBL/DSBL CLS.C CLOSE CONTROL SELECT ENBL/DSBL LS.MD LOW SOUND MODE SELECT X LS.ST LOW SOUND START TIME 00:00 LS.ND LOW SOUND END TIME 00:00 LS.LT LOW SOUND CAPACITY LIMIT XXX % CTRL CONTROL METHOD X CCNA CCN ADDRESS XXX CCNB CCN BUS NUMBER XXX PRESS ESCAPE KEY TO DISPLAY ‘OPT2’. PRESS DOWN ARROW KEY TO DISPLAY ‘CCN’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. CCN (CCN Network Configuration) SUB-MODE CCN ITEM ITEM EXPANSION DISPLAY CCNA CCN ADDRESS XXX CCNB CCN BUS NUMBER XXX BAUD CCN BAUD RATE X ENTRY PRESS ESCAPE KEY TO DISPLAY ‘CCN’. PRESS DOWN ARROW KEY TO DISPLAY ‘HP.A’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. HP.A (Head Pressure Cmp. Delta Configuration) SUB-MODE HP.A ITEM ITEM EXPANSION DISPLAY A1.DT SCT DELTA FOR COMP A1 XX A2.DT SCT DELTA FOR COMP A2 XX ENTRY PRESS ESCAPE KEY TO DISPLAY ‘HP.A’. PRESS DOWN ARROW KEY TO DISPLAY ‘HP.B’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. HP.B (Head Pressure Cmp. Delta Configuration) SUB-MODE HP.B ITEM ITEM EXPANSION DISPLAY B1.DT SCT DELTA FOR COMP B1 XX B2.DT SCT DELTA FOR COMP B2 XX CL-6 ENTRY - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE III. Unit Start-Up (cont) III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘HP.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.A’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. EXV.A (Circuit A EXV Configuration) SUB-MODE EXV.A ITEM ITEM EXPANSION DISPLAY STR.A EXV CIRC.A START POS XXX MIN.A EXV CIRC.A MIN POSITION XXX RNG.A EXVA STEPS IN RANGE XXXXX SPD.A EXVA STEPS PER SECOND XXXXX POF.A EXVA FAIL POSITION IN % XXX MIN.A EXVA MINIMUM STEPS XXXXX MAX.A EXVA MAXIMUM STEPS XXXXX OVR.A EXVA OVERRUN STEPS XXX TYP.A EXVA STEPPER TYPE 0,1 H.SCT HIGH SCT THRESHOLD XXX X.PCT OPEN EXV X% ON 2ND COMP XX X.PER MOVE EXV X% ON DISCRSOL XX A.PCT PRE-OPEN EXV - FAN ADDING XXX M.PCT PRE-CLOSE EXV - FAN SUB XXX S.PCT PRE-CLOSE EXV - LAG SHUT XXX DELY LAG START DELAY XXX ENTRY PRESS ESCAPE KEY TO DISPLAY ‘EXV.A’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.B’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. EXV.B (Circuit B EXV Configuration) SUB-MODE EXV.B ITEM ITEM EXPANSION DISPLAY STR.B EXV CIRC.B START POS XXX MIN.B EXV CIRC.B MIN POSITION XXX RNG.B EXVB STEPS IN RANGE XXXXX SPD.B EXVB STEPS PER SECOND XXXXX POF.B EXVB FAIL POSITION IN % XXX MIN.B EXVB MINIMUM STEPS XXXXX MAX.B EXVB MAXIMUM STEPS XXXXX OVR.AB EXVB OVERRUN STEPS XXX TYP.B EXVB STEPPER TYPE 0,1 ENTRY PRESS ESCAPE KEY TO DISPLAY ‘EXV.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘MM’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. MM (Motormaster Configuration Settings) SUB-MODE MM ITEM ITEM EXPANSION DISPLAY MMR.S MOTORMASTER SELECT YES/NO P.GAN HEAD PRESSURE P GAIN XX I.GAN HEAD PRESSURE I GAIN XX.X D.GAN HEAD PRESSURE D GAIN XX.X MIN.S MINIMUM FAN SPEED XX CL-7 ENTRY PRESS ESCAPE KEY TO DISPLAY ‘MM’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. RSET (Reset Configuration Settings) SUBMODE ITEM RSET ITEM EXPANSION DISPLAY ENTRY RESET COOL TEMP CRST COOLING RESET TYPE X MA.DG 4-20 - DEGREES RESET XX.X °F RM.NO REMOTE - NO RESET TEMP XXX.X °F RM.F REMOTE - FULL RESET TEMP XXX.X °F RM.DG REMOTE - DEGREES RESET XX.X °F RT.NO RETURN - NO RESET TEMP XXX.X °F RT.F RETURN - FULL RESET TEMP XXX.X °F RT.DG RETURN - DEGREES RESET XX.X °F DMDC DEMAND LIMIT SELECT X DM20 DEMAND LIMIT AT 20 MA XXX % SHNM LOADSHED GROUP NUMBER XXX SHDL LOADSHED DEMAND DELTA XXX % SHTM MAXIMUM LOADSHED TIME XXX DLS1 DEMAND LIMIT SWITCH 1 XXX % DLS2 DEMAND LIMIT SWITCH 2 XXX % LLEN LEAD/LAG CHILLER ENABLE ENBL/DSBL MSSL MASTER/SLAVE SELECT SLVE/MAST SLVA SLAVE ADDRESS XXX LLBL LEAD/LAG BALANCE SELECT X LLBD LEAD/LAG BALANCE DELTA XXX LLDY LAG START DELAY XXX PARA PARALLEL CONFIGURATION YES/NO PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW: SLCT (Setpoint and Ramp Load Configuration) SUBMODE ITEM SLCT ITEM EXPANSION DISPLAY SETPOINT AND RAMP LOAD CLSP COOLING SETPOINT SELECT X RL.S RAMP LOAD SELECT ENBL/DSBL CRMP COOLING RAMP LOADING X.X SCHD SCHEDULE NUMBER XX Z.GN DEADBAND MULTIPLIER X.X CL-8 ENTRY - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE III. Unit Start-Up (cont) III. Unit Start-Up (cont) PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS. RECORD CONFIGURATION INFORMATION BELOW: SETPOINT SUBMODE ITEM COOL ITEM EXPANSION DISPLAY COOLING SETPOINTS CSP.1 COOLING SETPOINT 1 XXX.X °F CSP.2 COOLING SETPOINT 2 XXX.X °F ICE SETPOINT XXX.X °F CSP.3 HEAD PRESSURE SETPOINTS HEAD H.DP HEAD SET POINT XXX.X °F F.ON FAN ON SET POINT XXX.X °F F.OFF FAN OFF SET POINT XXX.X °F B.OFF BASE FAN OFF DELTA TEMP XX.X °F FAN STAGE DELTA XX.X °F F.DLT FRZ BRINE FREEZE SETPOINT BR.FZ BRINE FREEZE POINT CL-9 XXX.X °F ENTRY COMPONENT TEST USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’. PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD. AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLUMINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE BELOW. Service Test Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ON/OFF ENTER ITEM EXPANSION SERVICE TEST MODE TEST COMMENT Completed (Yes/No) To Enable Service Test Mode, move Enable/Off/Remote Contact switch to OFF. Change TEST to ON. Move switch to ENABLE. OUTPUTS AND PUMPS ENTER OUTS FAN1 ON/OFF FAN 1 RELAY Condenser fan contactor 1 FAN2 ON/OFF FAN 2 RELAY Condenser fan contactor 2 FAN3 ON/OFF FAN 3 RELAY Condenser fan contactor 3 FAN4 ON/OFF FAN 4 RELAY Condenser fan contactor 4 FAN5 ON/OFF FAN 5 RELAY Condenser fan contactor 5 FAN6 ON/OFF FAN 6 RELAY Condenser fan contactor 6 V.HPA XXX% VAR HEAD PRESS % V.HPB XXX% VAR HEAD PRESS % CLP.1 ON/OFF COOLER PUMP 1 RELAY CLP.2 ON/OFF COOLER PUMP 2 RELAY CL.HT ON/OFF COOLER/PUMP HEATER RMT.A ON/OFF REMOTE ALARM RELAY CC.A1 ON/OFF COMPRESSOR A1 RELAY UL.TM 0 to 15 COMP A1 UnLOAD TIME CC.A2 ON/OFF COMPRESSOR A2 RELAY CC.A3 ON/OFF COMPRESSOR A3 RELAY CC.A4 ON/OFF COMPRESSOR A4 RELAY MLV ON/OFF MINIMUM LOAD VALVE RELAY CC.B1 ON/OFF COMPRESSOR B1 RELAY See Note CC.B2 ON/OFF COMPRESSOR B2 RELAY See Note CC.B3 ON/OFF COMPRESSOR B3 RELAY See Note CC.B4 ON/OFF COMPRESSOR B4 RELAY See Note CIRCUIT A COMPRESSOR TEST ENTER CMPA CIRCUIT B COMPRESSOR TEST ENTER CMPB NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg CL-10 12-10 Replaces: 30RAP-1T - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE III. Unit Start-Up (cont)
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Author : msdt05k Create Date : 2010:12:20 11:14:45-05:00 Modify Date : 2010:12:21 08:21:19-05:00 XMP Toolkit : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04 Creator Tool : PScript5.dll Version 5.2.2 Metadata Date : 2010:12:21 08:21:19-05:00 Format : application/pdf Title : 30rap-2t.fm Creator : msdt05k Producer : Acrobat Distiller 9.4.0 (Windows) Document ID : uuid:69599775-354f-4c60-a62e-6b438f3b6a61 Instance ID : uuid:48636de7-eaa0-4f6d-9583-8bf7da1c2c53 Page Count : 124EXIF Metadata provided by EXIF.tools