Carrier Xpower 38Vyx050 Users Manual I_Puron
38VYX050 to the manual f6c77911-50b4-46d9-80dd-5354d41e9291
2015-01-24
: Carrier Carrier-Xpower-38Vyx050-Users-Manual-310915 carrier-xpower-38vyx050-users-manual-310915 carrier pdf
Open the PDF directly: View PDF .
Page Count: 14
Download | |
Open PDF In Browser | View PDF |
R QUALIT TE SURANC E AS • L INSTALLATION MANUAL Y YD'S REGI S LO 38VYX050/38VYX080 IS O 900 1 For operation and maintenance instructions of this unit as well as installation instructions of the indoor unit, refer to the relevant manuals. Contents Precautions for safety .................................................................................................................... Accessory and refrigerant ............................................................................................................. Selection of installation .................................................................................................................. Refrigerant piping . ........................................................................................................................ Evacuating. .................................................................................................................................... Electrical connections .................................................................................................................... Final installation checks ................................................................................................................ Page 2 3 4 5 9/10 10 11/12 ATTENTION INSTALLERS AND SERVICE TECHNICIANS! AIR CONDITIONER WITH R-410A – QUICK REFERENCE GUIDE • R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A. • R-410A refrigerant cylinders are pink. • R-410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical position with the valve at the top. • R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit. • A vacuum pump is not enough to remove moisture from oil. • Oils absorb moisture rapidly. Do not expose oil to atmosphere. • Never open system to atmosphere while it is under vacuum. • When the system must be opened for service, break vacuum with dry nitrogen. • Do not vent R-410A into the atmosphere. • Use only Carrier matching indoor units (Table I). ENGLISH 38VYX050/38VYX080 Heat pump split system outdoor units Table I Heat pump models Cassette “40KQV” Hi-Wall “42PQV” Satellite “40SQV” Console “42VQV” 38VYX 050 38VYX 080 — — 050 080 — — 050 080 — — 050 080 — — 050 080 — — Power supply 220÷240V ~ 50Hz GB - 1 38VYX050/38VYX080 General information Precautions for safety The unit must be installed according to the national plantengineering standards. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer. • Turn off the main power supply switch (or breaker) before the unit maintenance. • Ask the customer to keep the Installation Manual together with the Owner’s Manual. CAUTION: • This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer. The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle. To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are charged from those for the conventional refrigerant. Accordingly the exclusive tools are required for the new refrigerant (R410A). • Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used. Moreover, do not use the existing piping because there are problems with pressure-resistance force and impurity in it. • Check that the impedance of the mains power supply is in conformance with the unit power input indicated in the electric data (EN 61000-3-11). • This unit complies with low-voltage (EEC/73/23) and electromagnetic compatibility (EEC/89/336) directives. • This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm. ) must be used for The installation fuse (25A D type the power supply line of this conditioner. WARNING: • Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner. Inappropriate installation may result in water leakage, electric shock or fire. • Turn off the main power supply switch or breaker before attempting any electrical work. Make sure all power switches are off. Failure to do so may cause electric shock. • Connect the connecting cable correctly. If the connecting cable is connected in a wrong way, electric parts may be damaged. • When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle. If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it may cause pipe burst and injuries on persons. • Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches. • Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts. Do not store it in a wet basement or expose to rain or water. • After unpacking the unit, examine it carefully for possible damage. • Do not install in a place that might increase the vibration of the unit. • To avoid personal injury (with sharp edges), be careful when handling parts. GB - 2 • Perform installation work properly according to the Installation Manual. Inappropriate installation may result in water leakage, electric shock or fire. • When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occurred in the room does not exceed the critical level. • Install the air conditioner securely in a location where the base can sustain the weight adequately. • Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed correctly, accidents may occur due to the falling unit. • If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate. • After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate. • Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply. An insufficient power supply capacity or inappropriate installation may cause fire. • Use the specified cables for wiring and connect them firmly to the terminals. To prevent external forces applied to the terminals from affecting the terminals. • Be sure to provide grounding. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables. • Conform to the regulations of the local electric company when wiring the power supply. Inappropriate grounding may cause electric shock. • Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks, and stays around the unit, a fire may occur. Required tools for installation work - Philips screw driver Cutter drill (65 mm) Spanner Pipe cutter Cutter Reamer Gas leak detector Meter Thermometer Volt-ohm-milliammeter Electro circuit tester Hexagonal wrench Flare tool Pipe bender Water level Metal saw R410A (Special requirement) - Manometer for pressure measuring (Charge hose : R410A special requirement) - Vacuum pump (Charge hose : R410A special requirement) - Torque wrench: • 1/4 (17 mm) 16 N•m (1,6 kgf•m) • 3/8 (22 mm) 42 N•m (4,2 kgf•m) • 1/2 (26 mm) 55 N•m (5,5 kgf•m) • 5/8 (15,9 mm) 120 N•m (12,0 kgf•m) - Copper pipe gauge adjusting projection margin - Vacuum pump adapter 38VYX050/38VYX080 Accessory and refrigerant ENGLISH Table II: Accessory and Installation Parts Outdoor unit Protective bush Installation manual x 1 (For SM800AT only) Drain nipple Guard material for passage Waterproof rubber cap part (For SM800AT only) Refrigerant Piping • Piping kit used for the conventional refrigerant cannot be used. • Use copper pipe with 0.8 mm or more thickness for Ø 6.4, Ø 9.52, Ø 12.7. Use copper pipe with 1.0 mm or more thickness for Ø 15.87. • Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it. Table III: Length of refrigerant Length of refrigerant pipe connected to indoor/outdoor units. Refrigerant addition 20 m o shorter: for all units Do not add refrigerant at installation site . (1) from 20 m to 30 m (38VYX 050) Add 20 g of refrigerant for every meter of pipe beyond 20 m (2) from 20 m to 50 m (38VYX 080) Add 40 g of refrigerant for every meter of pipe beyond 20 m NOTES: Caution at addition of refrigerant (1) (2) When the total length of refrigerant pipe exceeds 20m, add 20g/m. The pipe total maximum length is 30 m. (Max. amount of additional refrigerant is 200g.). Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor. When the total length of refrigerant pipe exceeds 20m, add 40g/m. The pipe total maximum length is 50 m. (Max. amount of additional refrigerant is 1200g.). Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor. Table IV: Operating limits (1) Cooling (2) outdoor temperature 43°C Maximum conditions indoor temperature 32°C d.b.; 23°C w.b. outdoor temperature -5°C Minimum conditions Heating (2) w.b. - wet bulb indoor temperature 27°C d.b. Minimum conditions outdoor temperature –15°C d.b. Nominal single-phase voltage Operating voltage limits 220÷240V ~ 50Hz min. 198V – max. 264V 1. Data referred to the outdoor unit only. 2. According to prEN14511. d.b. - dry bulb; outdoor temperature 24°C d.b.; 18°C w.b. Maximum conditions Mains power supply Notes: indoor temperature 21°C d.b.; 15°C w.b. WARNING: During heat pump operation unit will undergo several defrost cycles to eliminate ice that might possibly collect on the outdoor unit in very low ambient temperatures. In these cycles, fan speed will automatically reduce and cannot be varied until defrost cycle is completed. GB - 3 38VYX050/38VYX080 Selection of installation Air purge • For air purge, use a vacuum pump. • Do not use refrigerant charged in the outdoor unit for air purge. (The refrigerant for air purge is not contained in the outdoor unit.) Electrical cabling • Be sure to fix the power cables and indoor/outdoor connecting cables with clamps so that they do not contact with the cabinet, etc. Installation Place • A place which provides a specified space around the outdoor unit. • A place where the operation noise and discharged air are not given to your neighbors. • A place that is not exposed to a strong wind. • A place that does not block a passage. • When the outdoor unit is installed in an elevated position, be sure to secure its feet. • There must be sufficient space for carrying in the unit. • A place where the drain water does not make any problem. • If the unit is installed in areas where heavy snowfalls may occur, it is necessary to raise its level at least 200 mm above the usual snow level. Knockout procedure • The indoor/outdoor connecting pipes can be connected to 4 directions. Take off the knockout part of the pipe cover in which pipes or wires pass through the base plate. • As shown in the figure, do not remove the pipe cover from the cabinet so that the knockout hole can be easily punched. To knock out, punch the 3 connected parts with a screwdriver and remove the pipe cover by hand. • After marking the knockout hole, remove the burr and mount the attached protective bush and guard material for pass-through part in order to protect pipes and wires. • After connecting the pipes, be sure to mount the pipe cover. The pipe cover is easily mounted by cutting off the slit at the lower part of the cover. 500 How to remove the front panel Strong wind CAUTION: • Install the outdoor unit at a place where discharge air is not blocked. • When an outdoor unit is installed in a place that is always exposed to a strong wind like a coast or on a high storey of a building, secure a normal fan operation by using a duct or a wind shield • When installing the outdoor unit in a place that is constantly exposed to a strong wind such as the upper stairs or rooftop of a building, apply the windproof measures referring to the following examples. • Install the unit so that its discharge port faces the wall of the building. Keep a distance 500 mm or more between the unit and the wall surface. • Supposing the wind direction during the operation season of the air conditioner, install the unit so that the discharge port is set at right angle to the wind direction. • Installation in the following places may result in some troubles. Do not install the unit in such places below. • A place full of machine oil. • A place full of sulphuric gas. • A place where high-frequency radio waves are likely to be generated as from audio equipment, welders, and medical equipment. 1. Remove screws of the front panel. 2. Pull the front panel downward. Removing the front panel, the electric parts appear at the front side. • The power supply cables can be inserted into the pipe holes. Enlarge the pipe holes if they are too small. • Be sure to fix the power cable and indoor/outdoor connecting cable with bundling band sold on the market so that they do not make contact with the compressor and the hot pipes. To ensure good tensile strength, the electric cables must be fastened using the cable-holder on the plate. Strip 38VYX 080 Cover knockout for pipe connection GB - 4 Rear direction Pipe cover Side direction Down direction Front direction Electric parts box Fixing plate Piping hole Cable-holder for electric cables Front panel 38VYX050/38VYX080 Refrigerant piping ENGLISH 38 VYX 050 Pipe forming / positioning • Pipe forming. Form the pipe along with a marked line of the cabinet. • End positioning of pipe. Match the ends of both pipes at a distance of 85 mm apart from the marked line. 85 lign the centres of the connecting pipes and tighten the flare nut as strong as possible with your fingers. Then fix the nut with a spanner and tighten it with torque wrench as shown in the figure. C mm Half union or packed valve Flare nut Internally threaded side Marked line 1. Cut the pipe with a pipe cutter. Externally threaded side C Fix with spanner. D Tighten with torque wrench. • As shown in the figure, use two spanners to unscrew or tighten the valve flare nut, at gas side. If using a single spanner, the nut cannot be tightened with necessary tightening torque. On the contrary, use a single spanner to loosen or tighten the flare nut of the valve at liquid side. Flaring 90˚ D Obliquity Roughness Warp F 2. Insert a flare nut into the pipe, and flare the pipe. As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended. Cover Piping valve Flare nut E Tightened F Loosened E REQUIREMENT: 1. Do not put the spanner on the cap. The valve may be broken. Table V: Pipe outer diameter 0 A +-0,4 mm Outer dia. of copper pipe 2. If applying excessive torque, the nut may be broken according to some installation conditions. R410A R22 6,35 9,1 9,0 9,52 13,2 13,0 12,7 16,6 16,2 15,9 19,7 19,4 • After the installation work, be sure to check gas leak of connecting part of the pipes with nitrogen. • In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.5 mm more than that of R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size. B A Cover • Pressure of R410A is higher than that of R22 (Approx. 1.6 times). Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor/outdoor units at the specified tightening torque. Incomplete connections may cause not only a gas leak, but also a trouble of the refrigeration cycle. Flare at indoor unit side Flare at outdoor unit side IMPORTANT: Do not apply refrigerating machine oil to the flared surface. GB - 5 38VYX050/38VYX080 Minimum clearances Obstacle at rear side Upper side is free Obstacles at both right and left sides. 150 or more 200 or more Single unit installation 150 or more • 300 or more The height of the obstacle should be lower than the height of the outdoor unit. 200 or more Serial installation of two or more units 150 or more 300 or more 300 or more • 300 or more The height of the obstacle should be lower than the height of the outdoor unit. Obstacle at rear side 500 or more Obstacle also at the upper side 150 or more Obstacle at front side Upper side is free Obstacles at both right and left sides. 500 or more 1000 or more Single unit installation Obstacle at front side 1000 or more GB - 6 1000 or more Obstacle also at the upper side 38VYX050/38VYX080 Minimum clearances ENGLISH Obstacles at both front and rear sides Standard installation Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit. Serial installation of two or more units 300 or more 1000 or more 1000 or more 200 or more 150 or more Single unit installation 300 or more Serial installation at front and rear sides Standard installation Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit. 1000 or more 300 or more 1500 or more 2000 or more 200 or more Installation 38 VYX 050 600 90 38 VYX 080 90 150 430 Drain hole 365 400 76 310 115 330 600 150 Knockout hole Drain nipple mounting hole ø 28 Drain hole 15 mm or less • Before installation, check strength and horizontality of the base so that abnormal sound does not generate. • Set the out margin of the anchor bolt to 15mm or less.. • According to the following base diagram, fix the base firmly with the anchor bolts. (Anchor bolt, nut: M10 x 2 pairs) GB - 7 38VYX050/38VYX080 Installation A Drain nipple Knockout hole Waterproof rubber cap Drain nipple Open Waterproof rubber cap • In case of draining through the drain hose, attach the following drain nipple and the waterproof rubber cap, and use the drain hose (Inner diam.: 16mm) sold on the market. And also seal the screws securely with silicone material, etc. so that water does not drop down. Some conditions may cause dewing or dripping of water. A Waterproof rubber cap Base plate Drain nipple 38 VYX 080 • When there is a possibility of freezing of drain at the cold district or a snowfall area, be careful for drainage ability of drain. The drainage ability increases when a knockout hole on the base plate is opened. (Open the knockout hole to outside using a screwdriver, etc.) 38 VYX 050 Table VI: Optional Installation Parts (local procure) Parts name A Refrigerant piping Liquid side: ø 6,35 mm o ø 9,52 mm Gas side: ø 12,7 mm o ø 15,9 mm B Pipe insulating material (polyethylene foam, 6 mm thick) C Putty, PVC tapes Q’ty Each one 1 Each one CAUTION: IMPORTANT FOR POINTS BELOW FOR PIPING WORK 1. Keep dust and moisture away from inside the connecting pipes. 2. Tightly connect the connection between pipes and the unit. 3. Evacuate the air in the connecting pipes using VACUUM PUMP. 4. Check gas leak at connected points. Table VII: Piping connection Capacity rank Liquid piping Gas piping Outer diameter Thickness 38 VYX 050 ø 6,4 38 VYX 080 ø 9,52 GB - 8 Outer diameter Thickness 0,8 ø 12,7 0,8 0,8 ø 15,87 1,0 38VYX050/38VYX080 Evacuating ENGLISH Table VIII: Air Purge Max. connecting Capacity rank Height difference (m) pipe length (m) Outdoor unit higher than indoor unit Outdoor unit lower than indoor unit 38 VYX 050 30 30 15 38 VYX 080 50 30 15 Hexagonal size wrench 4 mm - This air conditioner can be installed up to the connecting pipe length and height difference in the following table. Air Purge Vacuum pump With respect to the preservation of terrestrial environment, adopt “Vacuum pump” for air purge (Evacuate air in the connecting pipes) when installing the unit. • As shown in the right figure, connect the charge hose after the manifold valves are closed completely. • Attach the connecting port of the charge hose with a projection to push the valve core (setting pin) to the charge port of the set. • Open handle Low fully. • Turn ON the vacuum pump.(*1) • Loosen the flare nut of the packed valve (Gas side) a little to check the air passes through.(*2) • Tighten the flare nut again. • Execute vacuuming until the compound pressure gauge indicates –101kPa (–76cmHg). (*1) • Close handle Low completely. • Turn OFF the vacuum pump. • Leave the vacuum pump as it is for 1 or 2 minutes, and check the indicator of the compound pressure gauge does not return. • Open fully the valve stem or the valve handle. (First, at liquid side, then gas side) • Disconnect the charge hose from the charge port. • Tighten valve and caps of the charge port surely. • Do not discharge the refrigerant gas to the atmosphere to preserve the terrestrial environment. • Use a vacuum pump to discharge the air (nitrogen, etc.) remained in the set. If the air remains, the capacity may decrease. For the vacuum pump, be sure to use one with backflow preventer so that the oil in the pump does not backflow into the pipe of the air conditioner when the pump stops. (If oil in the vacuum pump is put in an air conditioner including R410A, it may cause trouble on the refrigeration cycle.) 38VYX050 38VYX080 Compound pressure gauge Pressure gauge Manifold valve Handle Hi (Keep fully closed) Charge hose (For R410A only) Vacuum pump adapter for counter-flow prevention (For R410A only) Charge hose (For R410A only) Packed valve (Gas side) Vacuum pump Service port (Valve core (Setting pin)) Handle Lo -101kPa (-76cmHg) Valve unit Flare nut Stopper Charge cap Close Open Flexible charge pipe (only for R410A) Vacuum pump adapter for counter-flow prevention (only for R410A) Flexible charge pipe (only for R410A) Valve rod Charge port Push in handle. Handle Pull out the handle and using cutting pliers, etc. turn it counterclockwise by 90˚. (Open fully) Handle position A closed completely opened fully *1. Use the vacuum pump, vacuum pump adapters, and gauge manifold referring to the manuals attached to each tool before using them. For the vacuum pump, check oil is filled up to the specified line of the oil gauge. *2. While the air is purged, check again that the connecting port of charge hose, which has a projection to push the valve core, is firmly connected to the charge port. GB - 9 38VYX050/38VYX080 Evacuating Valve handling precautions Valve size ø 6,35 14 a 18 N•m (1,4 a 1,8 kgf•m) ø 9,52 33 a 42 N•m (3,3 a 4,2 kgf•m) ø 12,70 33 a 42 N•m (3,3 a 4,2 kgf•m) ø 15,87 20 a 25 N•m (2,0 a 2,5 kgf•m) Service connection 14 a 18 N•m (1,4 a 1,8 kgf•m) • Open the valve stem or the handle until it strikes the stopper. It is unnecessary to apply further force. • Securely tighten the cap with a torque wrench. • Cap tightening torque Electrical connections • Make refrigerant connections before electrical connections. When disconnecting, disconnect electrical connections before refrigerant connections. • The mains supply connecting cable for 38VYX units, must be H07 RN-F type (245 IEC 57) or higher, with synthetic rubber insulation with Neoprene coating, according to EN 60335-2-40 codes. Refer to the indoor unit installation manual for sizing of the power supply wires. IMPORTANT: Make ground connection prior to any other electrical connections. Model 38VYX050 Power supply • The indoor - outdoor unit interconnecting wires must be A07 RN-F type (245 IEC 57) or higher, with synthetic rubber insulation with Neoprene coating, according to EN 60335-2-40 codes. 38VYX080 220÷240 V Single phase 50 Hz Maximum running current 12 A Installation fuse rating 25 A (type D Power cable H07 RN-F (245 IEC 57) 2,5 mm2 2. For inter connecting cable, do not use a wire jointed to another on the way. Use wires long enough to cover the entire length. 15A Terminal block ) 1 2 3 L N All field electrical connections are the responsibility of the installer. WARNING: • Wrong wiring may cause a burn-out to some electrical parts. • Be sure to use the cord clamps attached to the product. • Do not damage or scratch the conductive core and inner insulator of power and inter-connecting cables when peeling them. • Be sure to comply with local regulations of the cable from outdoor unit to indoor unit. (wire size and cabling method etc.) • Use the power and Inter-connecting cables with specified thickness, specified type and protective devices required. Connecting cable Power cable Power cable and connecting cable L N 38VYX050 How to remove the cover 40 30 10 10 1. Remove screws of the valve cover. 2. Pull the valve cover downward to remove it. 1 2 3 10 Piping cover Cord clamp Indoor/outdoor connecting cables Power cable Valve cover Connecting cable Power cable Ground connector 30 (mm) • The installation fuse (25A D type power supply line of this air conditioner. ) must be used for the • Incorrect/incomplete wiring might cause an electrical fire or smoke. • Prepare the exclusive power supply for the air conditioner. 1. Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit. GB - 10 • Ensure that mains supply connection is made through a switch that disconnects all poles, with contact gap of a least 3 mm. 38VYX050/38VYX080 Final installation checks ENGLISH Piping cover Check points of outdoor unit Flare nut connections (Indoor unit) Valve cover Check and Test Operation For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.). • The conventional leak detector for HCFC refrigerant (R22, etc.) cannot be used because its sensitivity for HFC refrigerant lowers to approx. 1/40. • Pressure of R410A is approx. 1.6 times higher than that of R22. If installation work is incompletely finished, a gas leakage may occur when pressure rises during operation. Therefore, be sure to test the piping connections for leakage. • Check gas leakage at the flare nut connections, valve stem cap connections and service port cap fittings with a leak detector or soap water. Useful Functions (38VYX080 only) Self-Diagnosis by LED Indication Troubles of the outdoor unit can be diagnosed by LED indications on the cycle control P.C. board of the outdoor unit. Utilize them for various checks. For the check by remote controller of the indoor unit, refer to the Installation Manual of the outdoor unit. Before a check, confirm each bit of the DIP switch is set to OFF position. LED indication and code checking LED indication Cycle control P.C. board Cause LED indication D800 D801 D802 D803 Heat exchanger sensor (TE) error Suction sensor (TS) error Hot gas discharge sensor (TD) error D800 O: Red High-pressure protection error D801 O: Yellow Outdoor air temperature sensor error (TO) D802 O: Yellow Outdoor motorised fan error DC D803 O: Yellow Communication error between IPDU (Abnormal stop) High-pressure release operation : Flashing Discharge temp. error: hot gas is too high : Off EEPROM error : On Communication error between IPDU (No abnormal stop) G-Tr short-circuit protection Detect circuit error Current sensor error Comp. lock error Comp. break down GB - 11 38VYX050/38VYX080 Final installation checks Installation/Servicing Tools Changes in the product and components In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch) • In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and size of opposite side of flare nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8) Table: New tools for R410A New tools for R410A Gauge manifold Applicable to R22 model As pressure is high, it is impossible to measure by means of conventional gauge. In order to prevent any other refrigerant from being charged, each port diameter is changed. x In order to increase pressure resisting strength, hose materials and port size are changed (to 1/2 UNF 20 threads per inch). When purchasing a charge hose, be sure to check the port size. x Charge hose Changes o As pressure is high and gasification speed is fast, it is difficult to read the indicated value by means of charging cylinder, as air bubbles occur. Torque wrench (nominal diam. 1/2, 5/8) x The size of opposite sides of flare nuts have been increased. Incidentally, a common wrench is used for nominal diameters 1/4 and 3/8. Flare tool o By increasing the clamp bar’s receiving hole, strength of spring in the tool Electronic balance for refrigerant charging (clutch type) Gauge for projection adjustment Vacuum pump has been improved. - o adapter Gas leakage detector x - Used when flare is made with using conventional flare tool. Connected to the conventional vacuum pump. It is necessary to use an adapter to prevent vacuum pump oil from flowing back to the charge hose. The charge hose connecting part has two ports-one for conventional refrigerant (7/16 UNF 20 threads per inch) and one for R410A. If the vacuum pump oil (mineral) mixes with R410A a sludge may occur and damage the equipment. Exclusive for HFC refrigerant. • Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the U,S.’s ARI specified rose color (ARI color code: PMS 507). • Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding to the charge hose’s port size. GB - 12 38VYX 050-080 Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1 The manufacturer reserves the right to change any product specifications without notice. November, 2003. Supersedes July 2003 Printed in Japan
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Create Date : 2003:11:19 12:56:59 Producer : Acrobat Distiller 4.0 for Macintosh Subject : I_Puron Creator : Adobe PageMaker 6.5 Title : I_Puron Author : Osvaldo Modify Date : 2003:11:25 09:57:47+01:00 Page Count : 14EXIF Metadata provided by EXIF.tools