Corbin Russwin Visio Set Pair ED4000/5000 X M94 2 6900 Powermatic Wall Plates By MKA Key Switch To Disable Exterior Ac 120867

User Manual: Corbin Russwin Pair ED4000/5000 x M94 x 2- 6900 Powermatic x 2 Wall Plates By MKA Key Switch to Disable Exterior Ac Wiring Diagrams and Instructions

Open the PDF directly: View PDF PDF.
Page Count: 1

DownloadCorbin Russwin Visio- Set Pair ED4000/5000 X M94 2- 6900 Powermatic 2 Wall Plates By MKA Key Switch To Disable Exterior Ac 120867
Open PDF In BrowserView PDF
Richard McKeown

Pair ED4000/5000 x M94 x 2- 6900 Powermatic x 2 Wall Plates
By MKA Key Switch to Disable Exterior Actuator

NOTE: ALL LOW
VOLTAGE WIRING TO BE
18 GAUGE MINIMUM
STRANDED, EITHER
SINGLE OR MULTICONDUCTOR COLOR
CODED WITHOUT
SPLICES. (A MINIMUM OF
TWO SPARE
CONDUCTORS IS
SUGGESTED) ALL WIRING
MUST CONFORM TO
NATIONAL, STATE, AND
LOCAL CODES FOR
CLASS 2 FIRE
PROTECTION AND
CONTROL DEVICES.

13 & 14 Input for
actuators

120 VAC
Input

N

Hot Grd

24 NO COM NC
1
GRD VDC 1
1

1

2

3

4

5

14

13

13

12

12

11

11

10

10

9

9

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

1 2 3 4 5 6 7 8 9

7

11

12

8

C White

C White

ASSA ABLOY

Exterior

16

17

- Black
+ Red

Latch Retraction M94

18

NO Blue

NOTE: ALL LOW VOLTAGE WIRING TO BE 18
GAUGE MINIMUM STRANDED, EITHER SINGLE
OR MULTI-CONDUCTOR COLOR CODED
WITHOUT SPLICES. (A MINIMUM OF TWO
SPARE CONDUCTORS IS SUGGESTED) ALL
WIRING MUST CONFORM TO NATIONAL,
STATE, AND LOCAL CODES FOR CLASS 2 FIRE
PROTECTION AND CONTROL DEVICES.

NC Red

Interior

15

Latch Retraction M94

NC Red

660 wall
Switch

14

- Black
+ Red

MKA2

660 wall
Switch

13

To NC
Fire Alarm
Contacts

NO COM NC
2
2
2

6

10

Power Transfer

JP4 TERMINAL
STRIP

14

Power Transfer

6900 PowerMatic Operator

JP 1 Terminal Strip

Drawing #120867

Wire Gauge Requirements
between 781N
and Latch Retraction Exit
Device:

NO Blue

16 Gauge up to 1' - 40'
14 Gauge up to 40' - 60'
12 Gauge up to 60' - 100' MAX

Black GRD
Red

ASSA ABLOY Applications
Web: www.assaabloydss.com Phone: 800-810-WIRE Email: 800810WIRE@assaabloyusa.com

Green

Point-To-Point Diagram

Date

06/28/10

Drawn By

RLM

Revision

A



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Format                          : application/pdf
Creator                         : rmckeown
Title                           : Visio-Complete Set.vsd
Create Date                     : 2010:06:28 09:50:27-04:00
Creator Tool                    : PScript5.dll Version 5.2
Modify Date                     : 2010:06:28 09:50:27-04:00
Producer                        : Acrobat Distiller 8.2.2 (Windows)
Document ID                     : uuid:9d4d9112-e7af-4bca-8213-8adb2eeae64b
Instance ID                     : uuid:e361c7d2-2b93-4ca0-a151-b3cec38bb5a6
Page Count                      : 1
Author                          : rmckeown
EXIF Metadata provided by EXIF.tools

Navigation menu