C Lynx Control Relays Voltage Multi Function Relay 35 Mm Huh Part Number 84872130
2016-06-27
: Crouzet C-Lynx-Control-Relays-Voltage-Control-Multi-Function-Voltage-Control-Relay-35-Mm-Huh-Part Number-84872130 c-lynx-control-relays-voltage-control-multi-function-voltage-control-relay-35-mm-huh-Part number-84872130 english datasheets
Open the PDF directly: View PDF .
Page Count: 5
Multi
-
function voltage control relay
-
35 mm HUH Part number 84872130
Control of AC and DC voltages
Automatic recognition of AC/DC
Measurement ranges from 0.2 V to 600 V
Choice between under and overvoltage
True RMS measurement
Selectable latching (memory) function
Part numbers
Specifications
Type
Functions
Measurement range
Nominal voltage (V)
84872130
HUH
Under/Overvoltage
15V→600V
24→240VAC/DC
Supply
Supply voltage Un
24V→240VAC/DC
Voltage supply tolerance
-15 % / +10 %
Operating range
20,4V→264VAC/DC
Polarity with DC voltage
No
AC supply voltage frequency
50 / 60 Hz
±
10 %
Galvanic isolation of power supply/measurement
Power consumption at Un
3.5 VA in AC/0.6 W in DC
Immunity from micro power cuts
10 ms
Inputs and measuring circuit
Frequency of measured signal
0Hz,40→70Hz
Max. measuring cycle time
30 ms/True RMS measurement
Threshold adjustment
10→100%oftherange
Adjustable hysteresis
5→50%ofdisplayedthreshold
Display precision
±
10 % of full scale
Repetition accuracy with constant parameters
±
0,5 %
Measuring error with voltage drift
< 1 % across the whole range
Measuring error with temperature drift
±
0,05 % / °C
Timing
Delay on thresold crossing Tt
0,1→3s(0,+10%)
Repetition accuracy with constant parameters
±
2 %
Reset time
1500 ms
Delay on pick
-up
< 600 ms
Output
Type of output
1 double changeover relay
Type of contacts
No cadmium
Maximum breaking voltage
250 V AC/ DC
Max. breaking current
5 A AC/DC
Min. breaking current
10 mA / 5 VDC
Electrical life (number of operations)
1 x 105
Breaking capacity (resistive)
1250 VA AC
Maximum rate
360 operations/hour at full load
Operating categories acc. to IEC/EN 60947
-5-1
AC12, AC13, AC14, AC15, DC12, DC13, DC14
Mechanical life (operations)
30 x 106
Insulation
Nominal insulation voltage IEC/EN 60664
-1
250 V
Insulation coordination (IEC/EN 60664
-1)
Overvoltage category III : degree of pollution 3
Rated impulse withstand voltage (IEC/EN 60664
-1)
4 KV (1,2 / 50
μ
s)
Dielectric strength (IEC/EN 60664
-1)
2 KV AC 50 Hz 1 min.
Insulation resistance (IEC/EN 60664
-1)
> 500 M
Ω
/
500 V DC
General characteristics
Display power supply
Green LED
Display relay
Yellow LED
Casing
35 mm
Mounting
On 35 mm symmetrical DIN rail, IEC/EN 60715
Mounting position
All positions
Material : enclosure plastic type VO to UL94 standard
Incandescent wire test according to IEC/EN 60695-2-11
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Accessories
Overview
HUL and HUH control relays are designed to control AC or DC voltages.
They automatically recognise the shape of the DC or AC signal (50 or 60 Hz).
General principle :
The operating mode is set by the user.
A switch is used to select under or overvoltage modes, with or without latching.
The switch position, and hence the operating mode, is read by the product on energisation.
If the switch is set to a non-conforming position, the product goes into fault mode, the output relay stays open, and the LEDs flash to signal the position error.
If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the function selected on energisation prior to the change of position.
The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.
The under or overvoltage threshold value is set by a graduated potentiometer as a percentage of the U scale to be monitored.
The hysteresis is set by a graduated potentiometer from 5 to 50 % of the preset threshold. The hysteresis value cannot be higher than the extremes of the measurement range.
Protection (IEC/EN 60529)
Terminal block : IP 20
Casing : IP 30
Weight
130 g
Connecting capacity IEC/EN 60947
-1
Rigid : 1 x 4
2 - 2 x 2.52
mm
2
1 x 11 AWG - 2 x 14 AWG
Flexible with ferrules : 1 x 2.52 - 2 x 1.52
mm
2
1 x 14 AWG - 2 x 16 AWG
Max. tightening torques
IEC/EN 60947
-1
0,6→1Nm/5,3→8,8Lbf.In
Operating temperature IEC/EN 60068
-2
-
20→+50°C
Storage temperature IEC/EN 60068
-2
-
40→+70°C
Humidity IEC/EN 60068
-2-30
2 x 24 hr cycle 95 % RH max. without condensation 55 °C
Vibrations according to IEC/EN60068
-2-6
10→150Hz,A=0.035mm
Shocks IEC/EN 60068
-2-6
5 g
Standards
Standards
IEC/EN 50178, IEC/EN 61000
-6-
2, IEC/EN 61000
-6-3
Certifications
CE, UL, CSA, GL
Conformity with environmental directives
RoHS, WEEE
Inputs and measuring circuit
Measurement range
15V→600V
E1
-M:15→150V
E2
-M:30→300V
E3
-M:60→600V
Input resistance
E1
-
M : 150
Ω
E2
-
M : 300
Ω
E3
-
M : 600
Ω
Permanent overload at 25 °C
E1
-
M : 250 V
E2
-
M : 500 V
E3
-
M : 700 V
Description
Code
Removable sealable cover for 35 mm casing
84800001
Principles
Principles
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
In overvoltage mode, if the controlled voltage exceeds the preset threshold for longer than the time set on the front face (0.1 to 3 s), the output relay opens and LED R is extinguished. During the
time delay, this LED flashes.
Once the voltage falls below the threshold value minus the hysteresis, the relay closes instantaneously.
In undervoltage mode, if the controlled voltage falls below the preset threshold for longer than the time set on the front face (0.1 to 3 s), the output relay opens and LED R is extinguished. During the
time delay, this LED flashes.
Once the voltage rises above the threshold value plus the hysteresis, the relay closes instantaneously.
If "with memory" mode has been selected, the relay opens and stays in this position when threshold crossing is detected.
The power supply must be disconnected to reset the product.
N
o
Legend
Threshold
Hysteresis
Overvoltage function relay
Undervoltage function relay
Unit power-up
Controlled voltage
Delay on threshold crossing (Tt)
Principles
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
mm
NB :
When controlling DC voltage from the same source supplying terminals A1 and A2, terminal M must be connected directly to the "minus" pole of this power supply.
N
o
Legend
Threshold
Hysteresis
Overvoltage function relay
Undervoltage function relay
Unit power-up
Controlled voltage
Delay on threshold crossing (Tt)
Dimensions (mm)
HUL
-
HUH
Connections
HUL
-
HUH
N
o
Legend
1 A fast-blow fuse or cut-out
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Product adaptations
Customisable colours and labels
Measuring ranges within the generic limits
Fixed threshold in the generic measurement range
Fixed or adjustable time delay
Adjustable hysteresis
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com