Danfoss A S TYPE-CFR15 Wireless Floor Heating Control System User Manual cfm cfr install oper

Danfoss A/S Wireless Floor Heating Control System cfm cfr install oper

User manual

Download: Danfoss A S TYPE-CFR15 Wireless Floor Heating Control System User Manual cfm cfr install oper
Mirror Download [FCC.gov]Danfoss A S TYPE-CFR15 Wireless Floor Heating Control System User Manual cfm cfr install oper
Document ID324166
Application IDbpuFsccEMMdxsId77aIcWA==
Document DescriptionUser manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize42.46kB (530798 bits)
Date Submitted2003-05-08 00:00:00
Date Available2003-05-08 00:00:00
Creation Date0000-00-00 00:00:00
Producing SoftwareAcrobat Distiller 3.0 for Windows
Document Lastmod0000-00-00 00:00:00
Document Titlecfm-cfr_install_oper
Document CreatorAdobe PageMaker 6.5
Document Author: f08661

Installation and operation
Wireless floorheating controller and room thermostat, type CF
Temperature setting
Set room temperature on the thermostat dial. On
the right-hand side of the thermostat is a function switch with 3 possible settings:
Sun: The room temperature will be as set on the
thermostat.
Clock: Used only if the zone regulator is engaged. The temperature will be as set on the
room thermostat, but in accordance with the
consumption pattern entered.
The consumption pattern in the zone regulator
can be overridden by moving the switch to sun or
moon.
Moon: The room temperature will be as set on
the thermostat - minus 5°C.
Limitation of the setting range
Behind the button for temperature setting are two
lock-pins. These can be placed in the setting
knob as shown in fig. 4 if the thermostat setting
range is to be narrowed.
Putting into operation
Each room thermostat has a unique ID number
preventing conflicts with other thermostats.
A single room thermostat is capable of regulating
several heating outputs, provided these outputs
are assigned to the thermostat.
Assigning thermostats to output(s)
-The installation cable between room thermostat
and CFM (fig. 2) must be connected in assigning
each thermostat to the respective output(s).
-In the LED array the first available output will
flash. The LED in the CFR will also flash. Outputs already assigned will not be lit (fig. 2). By
pressing OK the thermostat will be assigned to
that output. If the room thermostat is to be assigned under another lit output, scroll to the output by means of the +/- keys, then press OK.
-When the installation cable is removed, the red
LED behind the front panel (fig. 4) will flash for at
least 4 minutes. See “Test of room thermostat”
Removal of assigned thermostat
-It is not necessary to have the installation
cable in place when removing an assigned thermostat. Once a thermostat has been removed, it
may be reassigned to another output.
-Removal of room thermostat is done by pressing
OK for 5 seconds, then the entire LED array will
be lit. Scroll to the specific room thermostat to
be removed with the +/- button,and press OK for
5 seconds. The thermostat has now been removed.
Test of room thermostat
If a defect in a room thermostat is suspected, the
following test may be carried out:
Troubleshooting
- Set the thermostat to the highest temperature.
- Move the function switch on the side of the
room thermostat to a new position.
- If the LED behind the front panel (fig. 4)
flashes quickly for 4 minutes, the room thermostat is OK.
Battery change
If the battery is getting low, the LED will flash 6
times every 6 seconds. See fig. 4.
Appearance
Problem
CFM controller output array blinks
specifically from a
row and column(s)
Lack or excessive heat
to floor heating system
The connection cable is 5 m. Cable lengths up
to 100 m are permitted (available from your
electrical items supplier).
Solution
Comments
Distance between room and
master is too far.
Reposition thermostat in
room until signal is clear.
Degradation of signal due to
reinforced concrete or foil
faced insulation between
floors.
Reposition external antenna, however if signal is
still unclear move external
antenna to the
same floor as
thermostat(s)
If signal is
continuosly
poor contact
Danfoss
External antenna mounted
close to metal parts or wires.
Master regulator CFM
This regulator governs the individual heat circuits via wireless communication with the associated room thermostats. Connection of 8 heat
circuits is enabled.
If more heat circuits are required, connect one
or max. two slave regulators CFS, each with
connection for 8 circuits. This allows max. 24
heat circuits to be governed.
The master/slave is to be fitted immediately
above the distributor pipe on the wall or in a distribution cabinet. Easy access to plugs and terminals should be ensured. See instruction drawing on the opposite page.
If two slave regulators are connected, move the
jumper in “slave 2” to position 2. See instruction
drawing.
The connection cable for the slave regulator is 1
m. Cable lengths of up to 100 m are enabled
(available from your electrical items wholesaler)
Alarm
There are 2 options with respect to alarms given
by the master regulator:
-Integral acoustic signal can be selected by
moving the jumper marked “buzzer” from OFF
to ON. See installation drawing.
-External alarm generator can be connected to
the output marked .
Technical data
Max. ambient temperature 60°C.
Enclosure IP40
Zone regulator CFZ
The zone regulator governs a maximum of 6
heat zones. For each heat zone, individual timing programmes can be connected. For reading
and operating convenience, it is recommended
to place the regulator at eye height.
Reason/cause
Master control is placed in
metal enclosure.
Alarm symbol in
zone controller,
CFZ flashes
Acoustic alarm
buzzes (provided
jumper is set to
“ON”)
Interference from electronic
equipment using the same
frequency, 433.92Mhz (i.e.
baby monitors, portable or
wireless headphones)
Room temperature is
below 6oC
(43oF)
Low battery
Problem in heating system
or signal to thermostat
Reposition room thermostat and run test mode
Mount external antenna if
not already installed.
Eliminate interfering electronic equipment
Replace battery and test
thermostat
Check heating supply to
the system and the circulator pump
Max. load for
CFM 6W,
max. Load
for CFS 3W
Check master control,
CFM, is properly wired.
Master or slave
controller row(s)
and entire columns
lit on master output
array
No heat
Blown fuse in master/slave
Loose wire connection between master and slave controller
First check actuators for
proper wiring then replace fuse in
master/slave controller,
1.25A
Check wire and connection between master and
slave
Constant light in
LED array
LED on back of
room thermostat
does not blink during test mode
No heat
Lack or excessive heat
to floor heating system
Defective zone actuator
Replace zone actuator
Lack of heated fluid to system
Check heating supply to
the system and the circulator pump
Faulty battery
Bad contacts between battery and thermostat
Replace battery/
Adjust connection in thermostat to ensure better
contact to battery
Defective room thermostat
Replace room thermostat
Check wiring of power to
CFM
All output LEDs are
unresponsive
No heat
CFM controller out- None
put array blinks rapidly 3 times specifically from a row
and column(s)
Improper wiring
Master controller is defective
Replace master controller.
Normal operation during test
of room thermostat
www.danfoss.com
DKCD 5/2002
CFR
CFZ
CFM 24
CFM 230
T 1.25A
F 4A
CFM
CFS 24
CFS 230
CFS
T 1.25A
+ T 0.5A
F 4A
+ T 0.5A
www.danfoss.com
DKCD 5/2002
GB
DK
FIN
Typical wiring diagram (Europe)
Typischer Schaltplan
Typisk el-diagram
Elanslutning
Kytkentäkaaviomalli
NL
PL
CZ
Diagramme (Europe)
Aansluitschema (Europa)
Typical wiring diagram
(Applies to the USA & Canada)
Przykład schematu połączeń (Europa)
Typické schéma zapojení (Evropa)
L1
L2
Pump: 115V, 1 phase,
60 Hz, 3A max.
L1
L2
T 1.25 A protects outputs
T 0.5 A protects controller
GB
If the regulator is fitted in a metal cabinet or where a wall, a concrete
floor or other structural components attenuate the transmission signal from the
room thermostats to such an extent that a faulty alarm is triggered, an external
antenna, order no. 088H0093, must be used.
Wird der Regler in einem Metallschrank oder an einem Ort montiert,
an dem die Dämpfung des Signals von den Raumthermostaten durch Wände,
Betondecken oder andere Gebäudeteile zu Fehlalarmen führt, so ist eine externe Antenne, Bestellnr. 088H0093, einzusetzen.
DK
Hvis regulatoren monteres i et metalskab eller hvor væg, betondæk
eller andre bygningsdele dæmper sendesignalet fra rumtermostaterne så
meget, at der op står fejlalarm, skal der anvendes en ekstern antenne, best. nr.
088H0093.
Om regulatorn monteras i ett metallskåp, eller där väggar, betonggolv
eller andra byggnadsdelar dämpar sändarsignalen från rumstermostaten så
mycket att larmet löser ut, ska man använda en extern antenn, best.nr
088H0093.
FIN
Jos ohjain asennetaan metallikoteloon tai paikkaan, jossa seinä,
betonilattia tai muut rakennusosat vaimentavat huonetermostaattien
lähettämää viestiä niin paljon, että järjestelmä antaa vikahälytyksen, on
käytettävä ulkopuolista antennia, tuotenumero 088H0093.
En cas d’installation du régulateur dans une armoire métallique ou
bien à tout autre endroit où un mur, une plate-forme en béton ou d’autres
éléments de construction atténuent le signal émis par les thermostats
d’ambiance au point de déclencher une fausse alarme, il convient d’utiliser un
capteur externe, n° de code 088H0093.
NL
Als de regelaar in een metalen behuizing wordt gemonteerd of op
plaatsen waar een wand, beton of andere delen van een gebouw het
zendsignaal van de ruimtethermostaten dusdanig dempt dat er foutalarmen
ontstaan, moet er een externe antenne, best.nr. 088H0093, worden gebruikt.
FCC ID: PGBTYPE-CFR , CAN 3934104209
This device complies with Part 15 of the FCC Rules and with
RSS-210 of Industry Canada and with RSS-210 of Industry
Canada:
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received,
including interference that may cause undesired operation.
Warning: Changes or modifications to this unit not expressly
approved by the party responsible for compliance could void
the user’s authority to operate the equipment.
PL
Jeżeli regulator znajduje się w metalowej obudowie lub betonowe
ściany i stropy osłabiają sygnał wysyłany przez termostaty pokojowe, należy
zastosować zewnetrzną antenę (numer katalogowy 088H0093)
CZ
Pokud je regulátor namontován v kovové skříni nebo na místě, kde
dochází ke snížení kvality signálu /stěna, betonový strop nebo jiné části
budovy/ je třeba instalovat přídavnou anténu, obj. č. 0088H0093.
www.danfoss.com
DKCD 5/2002

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 3
Create Date                     : 1910:20:50 12:35:35
Producer                        : Acrobat Distiller 3.0 for Windows
Author                          : f08661
Title                           : cfm-cfr_install_oper
Subject                         : cfm-cfr_install_oper
Creator                         : Adobe PageMaker 6.5
EXIF Metadata provided by EXIF.tools
FCC ID Filing: PGBTYPE-CFR15

Navigation menu