Delta Electronics Analog Output Module Dvp02Da S Users Manual 5011613802 02DA

Delta-Analog-Output-Module-Dvp02Da-S-Users-Manual-244562 delta-analog-output-module-dvp02da-s-users-manual-244562

DVP02DA-S to the manual 1e14ddde-65c7-4688-b0f5-57f77ce28d67

2015-01-24

: Delta-Electronics Delta-Electronics-Analog-Output-Module-Dvp02Da-S-Users-Manual-338682 delta-electronics-analog-output-module-dvp02da-s-users-manual-338682 delta-electronics pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

http://www.delta.com.tw/products/plc.asp
DVP02DA-S
DVP02DA-S Analog Output Module
Instruction Sheet
1 WARNING
Please carefully read this instruction thoroughly prior to use the DVP02DA-S.
The DC input power must be OFF before any maintenance.
This is an OPEN-TYPE built-in DVP02DA-S, and the DVP02DA-S is certified to meet the safety
requirements of IEC 61131-2 (UL 508) when installed in the enclosure to prevent high
temperature, high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or
metallic particles. Also, it is equipped with protective methods such as some special tool or key
to open the enclosure, so as to avoid the hazard to users or any damage to the DVP02DA-S.
Do not connect the AC power to any of the input/output terminals, or it may the DVP02DA-S.
Make sure that all the wiring is well conducted prior to power On.
Do not touch the internal circuit for at least 1 minute after the power is Off.
Make sure that DVP02DA-S is properly grounded , to avoid any electromagnetic noise.
2 INTRODUCTION
2.1 Model Explanation and Peripherals
Thank you for choosing DELTA DVP PLC Series. The analog output module of DVP02DA-S series
can read/write the data of analog output module by using commands FROM / TO via DVP-PLC
SS/SA/SX Series MPU program. The analog output module receives 2 group 12-bit digital data
from PLC MPU and converts it into 2 points analog output signal (voltage or current). There are 49
CR (Control Register) in each module and there are 16 bits in each register.
The software version of DVP02DA-S analog output module can be updated via RS-485
communication. Power unit and module are separate. Size is small and easy to install.
Users can select output either voltage or current via wiring. Voltage output range is 0V ~ +10V DC
(resolution is 2.5 mV). Current output range is 0mA ~ 20mA (resolution is 5 µA).
Nameplate Explanation
02DA-S0T3250003VX.XX
20.4VDC ~ 28.8VDC
MADE IN XXXXXX
PLC model
2.5 mV or 5 A
0V ~ + 10V or 0mA ~ +20mA
Input power Supply Spec.
Analog Input /Output Module Spec.
Barcode, series and version
Model Explanation
Serial Number
Model
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU
XA: Analog input/output mixed module
Product Series
Input + Output points
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors (PT-100)
TC: Thermocouple sensors (Type J/K)
Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model
RT: Resistor Thermocouple
HC: Input module of high-speed counter
PU: single axis positioning unit
2.2 Product Profile and Outline
90.00
4.00
3.00 25.20
1
2
3
4
60.00
5
6
7
8
9
3
10
FG
V+
I+
COM
C
H
1
FG
V+
I+
COM
C
H
2
11
12
13
3.4
90.00
60.00
3.00
14
Unit:mm
1. Status indicator (Power, RUN and ERROR) 8. Expansion port
2. Model name 9. Expansion unit clip
3. DIN rail clip 10. DIN rail (35mm)
4. I/O terminals 11. RS-485 Communication port
5. I/O point indicator 12. Mounting rail of the expansion unit
6. Mounting hole of the expansion unit 13. DC Power input
7. Nameplate 14. Expansion port
2.3 External wiring
Voltage output
0V ~ 10V
V+
2
FG
COM
V+
FG
I+
CH1
CH2
24+
24- AG
+15V
-15V
DC/DC
converter
3
System
Grounding
Class 3 Grounding
(100 or less)
Ω
DC24V
I+
Current output
0mA~20m
A
COM
CH1
CH2
Isolation wire 1
Isolation wire 1
AC drive, recorder,
scale valve...
AC drive, recorder,
scale valve...
terminal of
power module
Note 1: Please isolate analog output and other
power wiring.
Note 2: If noise interferes from loaded input wiring
terminal is significant, please connect a
capacitor with 0.1~0.47µF 25V for noise
filtering.
Note 3: Please connect power module
terminal and analog output module
terminal to system earth point and make
system earth point be grounded or
connects to machine cover.
Warning: DO NOT wire to the No function terminal
2.4 Terminal of analog module layout
DVP04AD-S DVP02DA-S DVP04DA-S DVP04PT-S DVP04TC-S DVP06XA-S DVP08RT-S
V
+
I+
COM
FG
V
+
I+
COM
FG
I+
COM
FG
V
+
I+
COM
FG
V
+
V
+
I+
COM
FG
V
+
I+
COM
FG
V
+
I+
COM
FG
V
+
I+
COM
FG
V
+
I+
COM
FG
V
+
I+
COM
FG
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
SLD
L+
L-
L+
L-
L+
L-
SLD
SLD
SLD
V
+
I+
COM
V
+
I+
COM
I+
COM
V
+
I+
COM
V
+
V
+
I+
COM
V
+
I+
COM
L1+
L1-
FG
L3+
L3-
L2-
L2+
L4-
L4+
L51
L5-
FG
L7+
L7-
L6-
L6+
L8-
L8+
3 STANDARD SPECIFICATIONS
3.1 Specifications
Digital/Analog (2D/A) Module Voltage Output Current Output
Power Supply Voltage 24 VDC (20.4VDC~28.8VDC) (–15%~+20%)
Analog Input Channel 2 channels / each module
Analog Output Range 0~10V 0~20mA
Digital Data Range 0~4000 0~4000
Resolution 12 bits (1LSB=2.5 mV) 12 bits (1LSB=5 µA)
Output Impedance 0.5 or lower
Overall Accuracy ±0.5% of full scale of 25(77)
±1% of full scale during 0~55 (32~131)
Response Time 3 ms × channels
Max. Output Current 20mA (1KΩ~2MΩ)
Tolerance Carried Impedance 0500Ω
Digital Data Format 2’s complementary of 16-bit, 13 Significant Bits
Isolation Method Isolation between digital area and analog area. But no isolation
among channels.
Protection Voltage output has short circuit protection but a long period of short
circuit may cause internal wire damage and current output break.
Communication Mode (RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 /
9600 / 19200 / 38400 / 57600 / 115200. For ASCII mode, format is
7Bits, even, 1 stop bit (7 E 1), while RTU mode format is 8Bits, even,
1 stop bit (8 E 1). The RS-485 is disabled when the DVP02AD-S is
connected in series with an MPU.
Connect to DVP-PLC MPU in
Series
If DVP02DA-S modules are connected to MPU, the modules are
numbered from 0 – 7. 0 is the closest and 7 is the furthest to the
MPU. 8 modules is the max and they do not occupy any digital I/O
points of the MPU.
3.2 Other Specification
Max. Rated Consuming Power 24 VDC (20.4VDC~28.8VDC) (–15%+20%), 3W, supply from
external power
Environment Condition and Wiring Follow the DVP-PLC MPU
Spec of Prevent Static Electricity All places between terminals and ground comply with the spec
4CR (Control Register)
DVP-02DA Analog Output Module Explanation
CR
No
RS-485
Parameters
Address
Latched Register Name b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0 H 4032 R Model type System used, data length is 8 bits (b7~b0). DVP-04AD model code=H 49
Reserved CH2 CH1 #1 H 4033 R/W Output mode setting
Output mode setting: factory setting is H0000.
Mode 0: output voltage mode (0V~10V).
Mode 1: output voltage mode (2V~10V).
Mode 2: output current mode (4mA~20mA).
Mode 3: output current mode (0mA~20mA).
Mode 4: none use.
#2 ~ #9 Reserved
#10 H 403C R/W CH1 output value
#11 H 403D R/W CH2 output value
The output setting range of channel CH1~CH2 is K0~K4000. Factory setting is K0
and unit is LSB.
#12~#21 Reserved
#22 H 4048 R/W To adjust OFFSET
value of CH1
#23 H 4049 R/W To adjust OFFSET
value of CH2
It is used to set the OFFSET value of CH1~CH2. The setting range is
K-2000~K2000. The factory setting is K0 and unit is LSB.
#24 ~ #27 Reserved
#28 H 404E R/W To adjust GAIN
value of CH1
#29 H 404F R/W To adjust GAIN
value of CH2
It is used to set the GAIN value of CH~CH2. The setting range is K-1600~K8000.
The factory setting is K2000 and unit is LSB.
#30 H 4050 R Error status It is the data register to save all error status. Please refer to fault code chart for detail.
#31 H 4051 R/W Communication
address setting
It is used to set RS-485 communication address. The setting range is from 01 to 255
and the factory setting is K1.
#32 H 4052 R/W Communication
Baud Rate setting
It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600,
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1),
while RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
b0: 4800 bps (bit/sec). b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec). b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec). b5: 115200 bps (bit/sec).
b6-b13: reserved.
b14: exchange low and high byte of CRC check code (only for RTU mode)
b15: ASCII / RTU mode selection
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Reserved CH2 CH1
#33 H 4053 R/W Reset to factory
setting and set
characteristics
adjustable priority
Output latched setting, factory setting H0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#22, CR#28).
When b1=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#22,
CR#28).
2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1
(not latched).
3. When b2 is set to 1, all settings will be reset to factory setting.
#34 H 4054 R Software version. In hexadecimal to display software version. For example: H 010A means 1.0A.
#35~#48 System used
means latched. , means not latched.
R means can read data by using FROM command via RS-485.
W means can write data by using TO command via RS-485.
LSB (Least Significant Bit): 1. Voltage output: 1LSB=10V/8000=2.5mV. 2. Current output: 1LSB=20mA/4000=5µA.
Explanation:
1. The content of CR#0 is model type, user can read the data from program to check if there is
expansion module.
2. CR#1 is used to set two internal channels working mode of analog output module. Every channel
has four modes to set that can set individually. For example: if set CH1 to mode 2 (b2~b0=010),
CH2 to mode 1(b5~b3=001). It needs to set CR#1 to H000A. The factory setting of CR#1 is H0000.
3. CR#2 ~ CR#9, CR#12 ~ CR#21, CR#24 ~ CR#27 Reserved.
4. CR #10 ~ CR#11 display CH1 and CH2 output signal. The setting range is K0~K4000. Factory
setting is K0 and unit is LSB.
5. R#22 ~ CR#23 means the value to adjust OFFSET value of CH1 and CH2. The factory setting is K0
and unit is LSB. If output value equal to 0 after calculating, the adjustable range of analog output
voltage or current is -2000~+2000.
Voltage adjustable range: -5V~+5V(-2000LSB~+2000LSB).
Current adjustable range: -10mA~+10mA (-2000LSB~+2000LSB).
6. R#28 ~ CR#29 means the value of adjust GAIN value of CH1 and CH2. The factory setting is K2000
and unit is LSB. If output value equal to 2000 after calculating, the adjustable range of analog output
voltage or current is -1600~+8000.
Voltage adjustable range: -4V~+20V(-1600LSB~+8000LSB).
Current adjustable range: -8mA ~+40mA (-1600LSB~+8000LSB).
Please be noticed that GAIN VALUE – OFFSET VALUE = +400LSB ~+6000LSB (voltage or
current). When this value within this range, the resolution of the output signal will be thin and the
value variation will be larger. When this value exceeds this range, the resolution of output signal
will be thick and the variation of value will be smaller.
7. CR#30 is the fault code. Please refer to the following chart.
Fault Description Content b15~b8 b7 b6 b5 b4 b3 b2 b1 b0
Power Source Abnormal K1(H1) 0 0 0 0 0 0 0 1
Analog Input Value Error K2(H2) 0 0 0 0 0 0 1 0
Setting Mode Error K4(H4) 0 0 0 0 0 1 0 0
Offset/Gain Error K8(H8) 0 0 0 0 1 0 0 0
Hardware Malfunction K16(H10) 0 0 0 1 0 0 0 0
Digital Range Error K32(H20) 0 0 1 0 0 0 0 0
Average Times Setting Error K64(H40) 0 1 0 0 0 0 0 0
Command Error K128(H80)
Reserved
1 0 0 0 0 0 0 0
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0
means normal and 1 means fault happened.
8. CR#31 is used to set RS-485 communication address. The setting range is from 01 to 254. The
factory setting is K1.
9. CR#32 is used to set RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200
bps, b0: 4800bps, b1: 9600bps, (factory setting) b2: 19200bps, b3: 38400 bps, b4: 57600 bps, b5:
115200 bps, b6-b13: reserved, b14: exchange low and high byte of CRC check code. (only for RTU
mode) b15=0: ASCII mode, =1: RTU mode.
10. CR#33 is used to set the internal function priority. For example: characteristic register. Output latched
function will save output setting to the internal memory before power loss.
11. CR#34 is software version of model type.
12. CR#35~ CR#48 are used for system.
13. The corresponding parameters address H4032~H4062 of CR#0~CR#48 are provided for user to
read/write data via RS-485.
A. Communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200 bps.
B. Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication
format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
C. Function code: 03H—read data from register. 06H—write one WORD into register.
10H—write multiple WORD into register.
5 Adjust D/A Conversion Characteristic Curve
5.1 Adjust D/A Conversion Characteristic Curve
Voltage output mode
Mode 0 of CR#1: GAIN = 5V(2000LSB),
OFFSET=0V (0LSB)
Mode 1 of CR#1: GAIN = 6V(2400LSB),
OFFSET=2V (800LSB).
GAIN: The setting range of voltage output value when
digital input value is K2000 should be
-4V~+20V(-1600LSB ~+8000 LSB).
OFFSET: The setting range of voltage output value when
digital input value is K0 should be
-5V~+5V(-2000LSB ~ +2000 LSB).
0+2000 +4000
2V
5V
6V
10V
OFFSET
GAIN
voltage
output
Digital input
mode 0
mode 1
GAINOFFSET: Setting range: +1V~+15V (+400LSB ~ +6000
LSB).
Current output mode
Mode 2 of CR#1: GAIN = 12mA(2400LSB ),
OFFSET=4mA (800LSB).
Mode 3 of CR#1: GAIN = 10mA(2000LSB),
OFFSET=0mA (0LSB).
GAIN: The setting range of current output when digital
input value is K2000 should be -8mA~+40mA
(-1600LSB ~+8000LSB).
OFFSET: The setting range of current output when digital
input value is K0 should be -10mA ~+10mA
(-2000LSB ~+2000LSB).
0+2000 +4000
20mA
OFFSET
GAIN
12mA
10mA
4mA
current
output
digital input
mode 3
mode 2
GAINOFFSET: Setting range: +2mA~+30mA (+400LSB
~+6000LSB).
The charts above are D/A conversion characteristic curve of voltage input mode and current input
mode. Users can adjust conversion characteristic curve by changing OFFSET values (CR#22~CR#23)
and GAIN values (CR#28~CR#29) depend on application.
LSB (Least Significant Bit): 1.voltage input: 1LSB=10V/8000=2.5mV. 2.current input:
1LSB=20mA/4000=5µA.
5.2 Program Example for Adjusting D/A Conversion Characteristics Curve
Example 1: Setting OFFSET value of CH1 to 0V(=K0LSB) and GAIN value is 2.5V(=K1000LSB).
X0
K1000
K28
H18 K1
K1
H0 K1
M1002
K33
K1
K1
K22 K0
TO
TO
TO
TO
K1
K1
K1
K1
Writing H18 into CR#1 of analog output
module#0. Setting CH2 to mode 3
(current output -20mA~ +20mA).
Writing H0 into CR#33 and allow CH2 to
adjust characteristics.
When X0 switches from OFF to ON,
K0LSB of OFFSET value will be written to
CR#22 and K1000LSB of GAIN value will
be written to CR#28.
Example 2: Setting OFFSET value of CH2 to 2mA (=K400 LSB) and GAIN value to 18mA (=K3600LSB).
X0
K3600
K29
H10 K1
K1
H0 K1
M1002
K33
K1
K1
K23 K400
TO
TO
TO
TO
K1
K1
K1
K1
Writing H10 into CR#1 of analog output
module#0. Setting CH2 to mode 2
(current output +4mA~ +20mA).
Writing H0 into CR#33 and allow the
adjust characteristic of CH1 and CH2.
When X0 switches from OFF to ON,
K400LSB of OFFSET value will be written
to CR#23 and K3600LSB of GAIN value
will be written to CR#29.
6 Initial PLC Start-up
Lamp display
1. When power is on, POWER LED will be lit and ERROR LED will be lit for 0.5 second.
2. Normal run: POWER LED should be lit and ERROR LED should turn off. When power supply is
lower than 19.5V, ERROR LED will blink continuously till the power supply is higher than 19.5V.
3. When it connects to PLC MPU in series, RUN LED on MPU will be lit and A/D LED or D/A LED
should blink.
4. After receiving the first RS-485 command during controlling by RS-485, A/D LED or D/A LED
should blink.
5. After converting, ERROR LED should blink if input or output exceeds upper bound or below the
lower bound.
Program example:
M0
K1
M1000
FROM
END
D0
TO
K0K1
D0CMP H49
INC D100
ADD D101 K5
=K4000 RST
H10
K2K10
M1
M1013
D101
D100 D100
= K4000 RST D101D101
K1 K1 K1
TO
M1
K1 D100
Explanation:
Reading the data of model type from expansion module K1 and check to see if the data is H49
(DVP-02DA-S model type).
D100 will increase K1 and D101 will increase K5 every second.
When value of D100 and D101 attain to K4000, they will be reset to 0.
For DVP-02DA-S model, M1 will be on and set the output mode: CH1 mode to 0, CH2 mode to 2.
Writing output setting CR#10 and CR#11 to D100 and D101. Analog output will vary with D100 and
D101 value.
7 Command Explanation
API Adaptive model
ES EP EH
78
D FROM P
Read special module CR
data
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
m1
¼ ¼
m2
¼ ¼
D ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼
n
¼ ¼
Note: The usage range of operand m1 is 0~7.
The usage range of operand m2: ES/EP: 0-48,
EH: 0-254.
The usage range of operand n: ES/EP: n=
1~(49-m2), EH: 1~(255-m2).
ES series model doesn’t support pulse
execution command (FROMP, DFROMP).
16-bit command (9 STEPS)
FROM Continuous
execution FROMP Pulse
execution
32-bit command (17 STEPS)
DFROM Continuous
execution DFROMP Pulse
execution
Flag: When M1083=On, it allows
to enable interrupt during
FROM/TO. Refer to
following for detail.
Command
Explanation
: the module number you are probing. : the number of Controlled Registers
to be read. : the data register location for storing data. : the number of CRs
to read at one time.
DVP-series PLC uses this command to read CR data of each special module.
: When assigning bit operand, K1~K4 are used for 16-bit and K5~K8 are used
for 32-bit.
Please refer the footnote below for calculation of the special module number.
Program
Example
Read the content of CR#24 and CR#25 of module#0 and save it into D0 and D1,
2pcs data are read in one time when n=2.
The command will be executed when X0=ON. When X0=OFF, nothing will occur and
the stored data has no change.
X0
FROM K0
API Adaptive model
ES EP EH
79 DTO P
Special module CR
data write
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
m1 ¼ ¼
m2 ¼ ¼
S ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼
n ¼ ¼
Note: The usage range of operand m1 is 0~7.
The usage range of operand m2: ES/EP: 0-48,
EH: 0-254.
The usage range of operand n: ES/EP: n=
1~(49-m2), EH: 1~(255-m2).
For ES series, it doesn’t support pulse
execution command (TOP, DTOP)
16-bit command (9 STEPS)
TO Continuous
execution TOP Pulse
execution
32-bit command (17 STEPS)
DTO Continuous
execution DTOP Pulse
execution
Flag: When M1083 On, it allows
to enable interrupt during
FROM/TO. Refer to following for
detail.
Command
Explanation
: the module number you are probing. : the number of Controlled
Registers that will be written to. : the data to write. : the number of CRs
to write to one time.
DVP-series PLC uses this command to write data into Controlled Registers of
special modules.
: When assigning bit operand, K1~K4 are used for 16-bit and K5~K8 are
used for 32-bit.
Program
Example
Using the 32-bit command DTO. The program will write D11 and D10 into CR#3
and CR#2 of special module#0. DTO only allows one group of data to be written at
a time (n=1).
Command is executed when X0=ON, command won’t be executed when X0=OFF,
and the stored data will have no change.
X0
DTO K0
Footnote
The rules for adding multiple special modules to a Main Processing Unit:
m1: The maximum number of special modules attached to an MPU is 8. The
order of module closest to the MPU is 0, and the module furthest from the
MPU is 7.
m2: The number of Controlled Registers (CR) built in is 49. (#0~#48).
FROM/TO command read/write 16-bit CR data in one command, while
DFROM/DTO command to read/write 32-bit CR data in one command.
Example below:
Upper 16-bit Lower 16-bit
Assigned CR numer
(n=2 for 16-bit command and n=1 for 32-bit are equal controlled registers used).
D0
D1
D2
D3
D4
D5
D0
D1
D2
D3
D4
D5
CR#5
CR#6
CR#7
CR#8
CR#9
CR#10
CR#5
CR#6
CR#7
CR#8
CR#9
CR#10
Assigned
Equipment
Assigned
CR
Assigned
Equipment
Assigned
CR
16-bit command when n=6 32-bit command when n=3
In ES series models, flag M1083 is not provided. When FROM/TO command is
executed, all interrupts (including external or internal interrupt subroutines) will be
disabled. All interrupts will be executed after FROM/TO command is completed.
Besides, FROM/TO command also can be executed in the interrupt subroutine.
The function of the flag M1083 (FROM/TO mode exchange) provided in EP/EH
series models:
1. When M1083=Off, all interrupts (including external or internal interrupt
subroutines) will be disabled when FROM/TO command is executed. The
Interrupts will resumed after FROM/TO command complete. Please be
advised FROM/TO command can be executed in the interrupt subroutine.
2. When M1083=On, if an interrupt enable occurs while FROM/TO command are
executing, the interrupt FROM/TO command will be blocked till the requested
interrupt finish. Unlike M1080 off situation, FROM/TO command cannot be
executed in the interrupt subroutine.

Navigation menu