1. Status indicator (Power, RUN and ERROR)
2. Model name
3. DIN rail clip
4. I/O terminals
5. I/O point indicator
6. Mounting hole of the expansion unit
7. Nameplate

http://www.delta.com.tw/products/plc.asp

DVP04DA-S
DVP04DA-S

2.3

Analog Output Module

1

voltage output
0V~+10V

AC drive, recorder,
scale valve...

AC drive, recorder,
scale valve...

The DC input power must be OFF before any maintenance.
This is an OPEN-TYPE built-in DVP04DA-S, and the DVP04DA-S is certified to meet IEC
61131-2 (UL 508) safety requirements when installed in the enclosure to prevent high
temperature, high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or
metallic particles. Also, it is equipped with protective methods such as some special tool or key to
open the enclosure, in order to prevent the hazard to users or any damage to the DVP04DA-S.
Do not connect the AC power to any of the input/output terminals, or it may damage the
DVP04DA-S. Make sure that all the wiring is well conducted prior to power on.

2

CH4

shielding cable *1

V+
I+
COM
FG

CH1

V+
I+
COM
FG

CH4

DC24V

*3
system grounding

wiring.
Note 2: If noise interference from loaded input

.
.
.
.
.

terminal wiring is significant, please connect
capacitor with 0.1~0.47µF 25V for noise
filtering.

2.4

and

+15V

DC/DC

24+
24-

system earth point and make system earth

AG
-15V

converter

point be grounded or connects to machine
cover.
Warning: DO NOT wire to the No function terminal ●.

DVP02DA-S

V+
I+
COM
FG
V+
I+
COM
FG

Model Explanation and Peripherals

DVP04DA-S

V+
I+
COM
FG
V+
I+
COM
FG

V+
I+
COM
FG
V+
I+
COM
FG

Thank you for choosing DELTA DVP PLC Series. The analog output module of DVP04DA-S series
can read/write the data of analog output module by using commands FROM / TO via DVP-PLC

analog output module terminal to

Terminal of analog module layout

DVP04AD-S

to prevent any electromagnetic noise.

power module terminal

Note 3: Please connect

class 3 grounding
(100 or less)

INTRODUCTION

2.1

CH1

terminal of
power module

Do not touch the internal circuit for at least 1 minute after the power is OFF.
Make sure that the DVP04DA-S is properly grounded

Note 1: Please isolate analog output and other power

shielding cable *1

current output

WARNING
Please carefully read this instruction thoroughly prior to use the DVP04DA-S.

RS-485
CR
Parameters Latched
Register Name
No
Address
#0
H 4032 ○ R Model type
#1
H 4033 ○ R/W Output mode setting

External wiring
*2

Instruction Sheet

DVP04DA-S Analog Output Module

8. Expansion port
9. Expansion unit clip
10. DIN rail (35mm)
11. RS-485 Communication port
12. Mounting rail of the expansion unit
13. DC Power input
14. Expansion port

DVP04PT-S

V+
I+
COM
FG
V+
I+
COM
FG

L+
LIFG
L+
LIFG

V+
I+
COM
FG
V+
I+
COM
FG

L+
LIFG
L+
LIFG

DVP04TC-S

DVP06XA-S

DVP08RT-S

V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM

L+
LSLG
L+
LSLG
L+
LSLG
L+
LSLG

L+
LL+
LL+
LL+
LL+
LL+
LL+
LL+
L-

SS/SA/SX MPU program. The analog output module receives 12-bit digital data of 4 groups from
PLC MPU and converts it into 4 points analog output signal either in voltage or in current.
The Software version of DVP04DA-S analog output module can be updated via RS-485
communication. Power unit and module are separate. Size is small and easy to install.
Users can select output from voltage or current via wiring. Voltage output range is 0V ~ +10V DC

3
3.1

STANDARD SPECIFICATIONS
Specifications

Digital/Analog (2D/A) Module

Voltage Output

Current Output

(resolution is 2.5 mV). Current output range is 0mA ~ 20mA (resolution is 5 µA).

Power Supply Voltage

24 VDC (20.4VDC~28.8VDC) ( –15%~+20%)

Nameplate Explanation

Analog Input Channel

2 channels / each module

Analog Output Range

0~10V

0~20mA

Digital Data Range

0~4000

0~4000

Resolution

12 bits (1LSB=2.5 mV)

12 bits (1LSB=5 µA)

Model Name
Input power supply spec.

20.4VDC ~ 28.8VDC
0V ~ + 10V or 0mA ~ +20mA

Analog input/output module spec.
Barcode

2.5mV or 5 A
V X .X X

Output Impedance

04 DA -S0 T32 500 03
MADE I N XXXXX X

Overall Accuracy

Model Explanation
Serial Number

Model

Product Series
Input + Output points

S: for SS series MPU
P: for EP series MPU
H: for EH series MPU

Model type
AD: Analog input module
DA : Analog output module
PT: Platinum temperature sensors (PT-100)
TC: Thermocouple sensors (Type J/K)

2.2

Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model

XA: Analog input/output mixed module
RT: Resistor Thermocouple
HC: Input module of high-speed counter
PU: single axis positioning unit

5
3.00

25.20

60.00
V+

3.4

6
11

7

10

90.00

V+
I+ C
H
COM4
FG

2

-

-

0~500Ω

Digital Data Format
Isolation Method

2’s complementary of 16-bit, 13 Significant Bits
Isolation between digital area and analog area. But no isolation among
channels.
Voltage output has short circuit protection but a long period short circuit
may cause internal wire damage and current output break.
Yes, communication formats are (4800 / 9600 / 19200 / 38400 / 57600 /
115200bps) Communication format: ASCII mode is 7Bit, even bit, 1
stop bit (7 E 1). Communication format of RTU mode is 8Bit, even bit, 1
stop bit (8 E 1). When connecting to PLC MPU in series, RS-485 can’t
be used.
If DVP04DA-S modules are connected to MPU, the modules are
numbered from 0 – 7. 0 is the closest and 7 is the furthest to the MPU.
8 modules is the max and they do not occupy any digital I/O points of
the MPU.

Connect to DVP-PLC MPU in
Series

12
14

●

V+
C
I+
H
COM 3
FG

20mA (1KΩ~2MΩ)

Tolerance Carried Impedance

60.00

8

FG

Max. Output Current

3.00

I+ C
H
COM 1
FG
V+
I+ C
H
COM 2

3 ms × channels

Communication Mode
(RS-485)

4
1

Response Time

Protection

Product Profile and Outline

9

13
3

●

3

90.00

0.5Ω or lower
±0.5% of full scale of 25℃(77℉).
±1% of full scale during 0~55℃ (32~131℉).

3.2

Other Specification

24 VDC (20.4VDC~28.8VDC) (-15%~+20%), 4W, supply from
external power
Environment Condition and Wiring Follow the DVP-PLC MPU
Spec of Prevent Static Electricity
All places between terminals and ground comply with the spec
Max. Rated Consuming Power

4.00

Unit: mm

4

CR (Control Register)

#2 ~ #5
#6
H 4038
#7
H 4039
#8
H 403A
#9
H 403B
#10 ~ #17
#18 H 4044
#19 H 4045
#20 H 4046
#21 H 4047
#22 ~ #23
#24 H 404A
#25 H 404B
#26 H 404C
#27 H 404D
#28 ~ #29
#30 H 4050

○
○
○
○

R/W
R/W
R/W
R/W

CH1 output value
CH2 output value
CH3 output value
CH4 output value

○
○
○
○

R/W
R/W
R/W
R/W

To adjust OFFSET value of CH1
To adjust OFFSET value of CH2
To adjust OFFSET value of CH3
To adjust OFFSET value of CH4

○
○
○
○

R/W
R/W
R/W
R/W

To adjust GAIN value of CH1
To adjust GAIN value of CH2
To adjust GAIN value of CH3
To adjust GAIN value of CH4

Explanation
b15 b14 b13 b12 b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

System used, data length is 8 bits (b7~b0). DVP-04DA model code=H 89
Reserved
CH4
CH3
CH2
CH1
Output mode setting: factory setting is H0000.
Mode 0: output voltage mode (0V~10V).
Mode 1: output voltage mode (2V~10V).
Mode 2: output current mode (4mA~20mA).
Mode 3: output current mode (0mA~20mA).
Mode 4: none use.
Reserved
The output setting range of channel CH1~CH4 is K0~K4000. Factory
setting is K0 and unit is LSB.
Reserved
It is used to set the OFFSET value of CH1~CH4. The setting range is
K-2000~K2000. The factory setting is K0 and unit is LSB.
Reserved
It is used to set the GAIN value of CH~CH4. The setting range is
K-1600~K8000. The factory setting is K2000 and unit is LSB.

Reserved
Data register to save all error status. Please refer to fault code chart for
detail.
#31 H 4051 ○ R/W Communication address setting Used to set RS-485 communication address. The setting range is from 01
to 255 and the factory setting is K1.
#32 H 4052 ○ R/W Communication Baud Rate
Used to set communication baud rate (4800, 9600, 19200, 38400, 57600,
setting
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit
(7 E 1). Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8
E 1).
b0: 4800 bps (bit/sec).
b1: 9600 bps (bit/sec). (Factory setting)
b2: 19200 bps (bit/sec).
b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec).
b5: 115200 bps (bit/sec).
b6-b13: reserved.
b14: exchange low and high byte of CRC check code (RTU mode only)
b15: ASCII / RTU mode selection
#33 H 4053 ○ R/W Reset to factory setting and set b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
characteristics adjustable
Reserved
CH4
CH3
CH2
CH1
priority
Output latched setting, factory setting H0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18,
CR#24). When b0=1, inhibit user to adjust OFFSET and GAIN value of
CH1 (CR#18, CR#24).
2. b1 is used to check if characteristic register is latched. b1=0 latched
(factory setting), b1=1 not latched.
3. When b2 is set to 1, all settings are reset to factory setting.
#34 H 4054 ○ R Software version.
Show software version in hexadecimal. For example: H 010A means 1.0A.
#35~#48
System used
○ means latched.
╳ means not latched.
R means can read data by using FROM command or RS-485.
W means can write data by using TO command or RS-485.
LSB (Least Significant Bit): 1. Voltage output: 1LSB=10V/8000=2.5mV. 2. Current output: 1LSB=20mA/4000=5µA.
╳

R

Error status

Explanation:
1. The content of CR#0 is model type, user can read the data from program to check if there is
expansion module.
2. CR#1 is used to set two internal channels working mode of analog output module. Every channel
has four modes that can be set individually. For example: if setting CH1 to mode 2 (b2~b0=010),
CH2 to mode 1(b5~b3=001). It needs to set CR#1 to H000A. The factory setting of CR#1 is H0000.
3. CR#2 ~ CR#5, CR#10 ~ CR#17, CR#22, CR#23, CR#28, CR#29 Reserved.
4. CR #6 ~ CR#9 display CH1 ~ CH4 output signals. The setting range is K0~K4000. Factory setting is
K0 and unit is LSB.
5. CR#18 ~ CR#21 are used to adjust the OFFSET value of CH1 and CH4. The factory setting is K0
and unit is LSB. If output value equal to 0 after calculation, the adjustable range of analog output
voltage or current is -2000~+2000.
Voltage adjustable range: -5V~+5V(-2000LSB~+2000LSB).
Current adjustable range: -10mA~+10mA (-2000LSB~+2000LSB).
6. CR#24 ~ CR#27 are used to adjust the GAIN value of CH1 and CH4. The factory setting is K2000
and unit is LSB. If output value equal to 2000 after calculation, the adjustable range of analog
output voltage or current is -1600~+8000.
Voltage adjustable range: -4V~+20V(-1600LSB~+8000LSB).
Current adjustable range: -8mA ~+40mA (-1600LSB~+8000LSB).
Please be noticed that GAIN VALUE – OFFSET VALUE = +400LSB ~+6000LSB (voltage or
current). If the value difference comes up small (within range), the output signal resolution is then
slim and the variation is definitely larger. On the contrast, if the value difference exceeds the range,
the output signal resolution becomes larger and the variation is definitely smaller.
7. CR#30 is fault code. Please refer to the following chart.
Fault Description
Content
b15~b8 b7 b6 b5 b4
b3
b2
b1
b0
Power Source Abnormal
K1(H1)
0
0
0
0
0
0
0
1
Analog Input Value Error
K2(H2)
0
0
0
0
0
0
1
0
Setting Mode Error
K4(H4)
0
0
0
0
0
1
0
0
Offset/Gain Error
K8(H8)
0
0
0
0
1
0
0
0
Reserved
Hardware Malfunction
K16(H10)
0
0
0
1
0
0
0
0
Digital Range Error
K32(H20)
0
0
1
0
0
0
0
0
Average Times Setting Error K64(H40)
0
1
0
0
0
0
0
0
Command Error
K128(H80)
1
0
0
0
0
0
0
0
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the
same time. 0 means normal and 1 means having fault.
8. CR#31 is used to set RS-485 communication address. The setting range is from 01 to 255. The
factory setting is K1.
9. CR#32 is used to set RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200

bps. b0: 4800bps, b1: 9600bps, (factory setting) b2: 19200bps, b3: 38400 bps, b4: 57600 bps, b5:
115200 bps, b6-b13: reserved, b14: exchange low and high byte of CRC check code. (RTU mode
only) b15=0: ASCII mode, b15=1: RTU mode. Communication format: ASCII mode is 7Bit, even bit,
1 stop bit (7 E 1), while RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
10. CR#33 is used to set the internal function priority. For example: characteristic register. Output
latched function will save output setting to the internal memory before power loss.
11. CR#34 is software version of model type.
12. CR#35~ CR#48 are used for system.
13. The corresponding parameters address H4032~H4063 of CR#0~CR#48 are provided for user to
read/write data via RS-485.
A. Communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200 bps.
B. Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication
format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
C. Function code: 03H—read data from register. 06H—write one WORD to register. 10H—write
multiple WORD to register.

5

6

INITIAL PLC START-UP

M1000

FROM

ADJUST D/A CONVERSION CHARACTERISTIC CURVE

5.1 Adjust D/A Conversion Characteristic Curve
Mode 0 of CR#1: GAIN = 5V(2000LSB),
OFFSET=0V (0LSB)

mode 1

Mode 1 of CR#1: GAIN = 6V(2400LSB),
OFFSET=2V (800LSB).

mode 0
6V
5V

GAIN:

GAIN

voltage
output
2V
0

+2000

+4000

OFFSET

The setting range of voltage output value when
digital input value is K2000 should be
-4V~+20V(-1600LSB ~+8000 LSB).
OFFSET:
The setting range of voltage output value when
digital input value is K0 should be
-5V~+5V(-2000LSB ~ +2000 LSB).
GAIN-OFFSET: Setting range: +1V~+15V (+400LSB ~ +6000 LSB).

CMP

H89

D0

M0

INC

D100

ADD

D101

K1

79 D

m1
m2
S
n

Command
Explanation

K5

D100

RST

D100

LD=

K4000

D101

RST

D101

D101

Program
Example

M1
TO

K1

K1

H10

K1

K6

D100

K2

M1
TO

K1

Mode 2 of CR#1: GAIN = 12mA (2400LSB),
OFFSET=4mA (800LSB).

mode 2

mode 3
GAIN

current
output
4mA
+2000

+4000

digital input

Mode 3 of CR#1: GAIN = 10mA (2000LSB),
OFFSET=0mA (0LSB).
GAIN:

The setting range of current output when digital
input value is K2000 should be -8mA~+40mA
(-1600LSB ~+8000LSB).
OFFSET:
The setting range of current output when digital
input value is K0 should be -10mA ~+10mA
(-2000LSB ~+2000LSB).
GAIN-OFFSET: Setting range: +2mA~+30mA (+400LSB
~+6000LSB).

END

Explanation:
Read the data of model type from expansion module K1 and distinguish if the data is H89
(DVP04DA-S model type).
D100 will increase K1 and D101 will increase K5 every second.
When value of D100 and D101 attain to K4000, they will be reset to 0.
If the model type is DVP04DA-S, M1 will be on and set the output mode: CH1 mode to 0, CH2 mode
to 2.
Writing output setting CR#6 and CR#7 to D100 and D101. Analog output will vary with D100 and D101
value.

7

Adaptive model
ES EP EH

LSB (Least Significant Bit): 1.voltage output: 1LSB=10V/4000=2.5mV. 2.current output:
1LSB=20mA/4000=5µA.

Bit device
Word device
16-bit command (9 STEPS)
X Y M S K H KnX KnY KnM KnS T C D E F
Continuous
Pulse
FROM
FROMP
m1
¼ ¼
execution
execution
m2
¼ ¼
D
¼
¼
¼ ¼ ¼ ¼ ¼ ¼ 32-bit command (17 STEPS)
n
¼ ¼
Continuous
Pulse
DFROM
DFROMP
Note: The usage range of operand m1 is 0~7.
execution
execution
The usage range of operand m2: ES/EP:
Flag: When M1083 on, it allows enable
0-48, EH: 0-254.
the interrupt during FROM/TO.
The usage range of operand n: ES/EP: n=
Refer to following for detail.
1~(49-m2), EH: 1~(255-m2).
ES series model doesn’t support pulse
execution command (FROMP, DFROMP).

M1002
TO

K1

K1

H10

K1

TO

K1

K33

H0

K1

TO

K1

K18

K0

K1

TO

K1

K24

K1000

K1

X0

Writing H10 to CR#1 of analog output
module#0. Setting CH1 to mode 0
(voltage output 0V~ +10V) and CH2 to
mode 2 (current output 4mA~ +20mA).
Writing H0 to CR#33 and allow CH1 ~
CH4 to adjust characteristic.
When X0 switches from Off to On,
K0LSB of OFFSET value will be written
to CR#18 and K1000LSB of GAIN value
will be written to CR#24.

78

D

FROM

Command
Explanation

TO

K1

K1

H18

K1

TO

K1

K33

H0

K1

TO

K1

K19

K400

K1

TO

K1

K25

K3600

K1

X0

When X0 switches from Off to On,
K400LSB of OFFSET value will be
written to CR#19 and K3600LSB of
GAIN value will be written to CR#25.

: the number for special module.
special module that will be read.

: the number of CR (Control Register) of
: the location to save reading data.

: the

DVP-series PLC uses this command to read CR data of special module.

Writing H10 to CR#1 of analog output
module#0. Setting CH1 to mode 0
(voltage output 0V~ +10V) and CH2 to
mode 3 (current output 0mA~ +20mA).
Writing H0 to CR#33 and allow CH1 ~
CH4 to adjust characteristic.

P

Read special module
CR data

data number of reading ONCE.

Example 2: Setting OFFSET value of CH2 to 2mA (=K400 LSB) and GAIN value to 18mA (=K3600LSB).
M1002

P

: When assign the bit operand, K1~K4 are used for 16-bit and K5~K8 are used for
32-bit.
Please refer the footnote below for calculation the special module number.
Program
Example

Read the content of CR#24 of special module#0 save it to D0 of PLC, and read the
content of CR#25 of special module#0 save it to D1 of PLC. 2 data are read in one
time when n=2.
Command will be executed when X0=ON. Command won’t be executed if X0=OFF
and the content of previous reading data won’t change.
X0
FROM
K0
K24
D0

K2

Adaptive model
ES EP EH

: the number of special module.
: the number of CR (Control Register) of
special module that will be wrote in.
: the data to write in CR.
: the data
number to write in one time.
DVP-series PLC uses this command to write data into CR of special module.
: When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be
used for 32-bit.
Use 32-bit command DTO, program will write D11 and D10 to CR#3 and CR#2 of
special module#0. It only writes one group of data in one time when=1.
Command will be executed when X0=ON, will not be executed when X0=OFF. The
previous write data won’t be changed.
X0
DTO
K0
K2
D0
K1
The rule of command operand
m1: arrangement number of special module. The number of special module
that connects to PLC MPU. The number sequence of special module from the
closest to the furthest of MPU is from 0 to 7. 8 modules is the max and it won’t
occupy I/O point.
m2: the number of CR. There are 49 CR (Control Register) with 16-bit each
built-in memory in the special module. The number of CR uses decimal digital
(#0~#48). All running status and setting values of special module have
included.
FROM/TO command is used to read/write CR data 1pcs at a time, while
DFROM/DTO command is used to read/write CR data 2pcs in one time.

Upper 16-bit Lower 16-bit
CR #10

API

Example 1: Setting OFFSET value of CH1 to 0V(=K0LSB) and GAIN value is 2.5V(=K1000LSB).

Special module CR
data write in

COMMAND EXPLANATION

The charts above are D/A conversion characteristic curve of voltage input mode and current input
mode. Users can adjust conversion characteristic curve by changing OFFSET values (CR#18~CR#21)
and GAIN values (CR#24~CR#27) depend on application.

5.2 Program Example for Adjusting D/A Conversion Characteristics Curve

TO

Bit device
Word device
16-bit command (9 STEPS)
X Y M S K H KnX KnY KnM KnS T C D E F
Continuous
Pulse
¼ ¼
TO
TOP
execution
execution
¼ ¼
¼ ¼ ¼
¼
¼
¼ ¼ ¼ ¼ ¼ ¼ 32-bit command (17 STEPS)
¼ ¼
Continuous
Pulse
DTO
DTOP
execution
execution
Note: The usage range of operand m1 is 0~7.
Flag: When M1083 on, it allows to
The usage range of operand m2: ES/EP:
enable the interrupt during
0-48, EH: 0-254.
FROM/TO. Refer to below for
The usage range of operand n: ES/EP:
detail.
1~(49-m2), EH: 1~(255-m2).
For ES series, it doesn’t support pulse
execution command (TOP, DTOP)

Footnote

20mA

OFFSET

D0

K4000

Current output mode

0

K0

LD=

Digital input

12mA
10mA

K1

M1013

Voltage output mode:
10V

API

Lamp display
1. When power is on, POWER LED will be lit and ERROR LED will be lit for 0.5 second.
2. It is normal that POWER LED should be lit and ERROR LED should turn off. When power supply
is lower than 19.5V, ERROR LED will blink continuously till the power voltage is higher than 19.5V.
3. When it connects to PLC MPU in series, RUN LED on MPU will be lit and A/D LED or D/A LED
should blink.
4. After receiving the first RS-485 command during controlling via RS-485, A/D LED or D/A LED
should blink.
5. After converting, ERROR LED should blink if input or output exceeds the upper bound or below
the lower bound.
Program example:

CR #9

Specified CR number

The number of transmission groups n. The meaning of n=2 of 16-bit
command and n=1 of 32-bit are the same.
Specified device

Specified CR

Specified device Specified CR

D0
D1
D2

CR #5

D0
D1
D2

CR #5

CR #6
CR #7

D3
D4

CR #8
CR #9

D3
D4

CR #8
CR #9

D5

CR #10

D5

CR #10

16-bit command when n=6

CR #6
CR #7

32-bit command when n=3

In ES series models, flag M1083 is not provided. All interrupts (including external or
internal interrupt subroutines) will be disabled when FROM/TO command is
executed. Interrupts will be resumed after FROM/TO command complete. Please be
advised FROM/TO command also can be executed in the interrupt subroutine.
The function of the flag M1083 (FROM/TO mode exchange) provided in EP/EH
series models:
A. When M1083=Off, all interrupts (including external or internal interrupt
subroutines) will be disabled when FROM/TO command is executed. The
Interrupts will resumed after FROM/TO command complete. Please be
advised FROM/TO command can be executed in the interrupt subroutine.
B. When M1083=On, if an interrupt enable occurs while FROM/TO command
are executing, the interrupt FROM/TO command will be blocked till the
requested interrupt finish. Unlike M1080 off situation, FROM/TO command
cannot be executed in the interrupt subroutine.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2004:10:04 11:03:02+08:00
Modify Date                     : 2004:10:04 11:03:02+08:00
Page Count                      : 2
Creation Date                   : 2004:10:04 03:03:02Z
Mod Date                        : 2004:10:04 03:03:02Z
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Author                          : MELODY.CHEN
Metadata Date                   : 2004:10:04 03:03:02Z
Creator                         : MELODY.CHEN
Title                           : Microsoft Word - 5011321502-04DA-S.doc
EXIF Metadata provided by EXIF.tools

Navigation menu