Delta Electronics Dtc1000 Series Users Manual 5011635004 DCE4
Delta-Dtc1000-Series-Users-Manual-245024 delta-dtc1000-series-users-manual-245024
DTC1000 Series to the manual ddc5a879-79f5-43c6-a36d-d2b952b7521b
2015-01-24
: Delta-Electronics Delta-Electronics-Dtc1000-Series-Users-Manual-339138 delta-electronics-dtc1000-series-users-manual-339138 delta-electronics pdf
Open the PDF directly: View PDF .
Page Count: 2
Download | |
Open PDF In Browser | View PDF |
Product Profile & Outline Output 3.0 DTC1000R/V/C/L http://www.delta.com.tw/industrialautomation/ 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. DTC 1 Series name 1 Controller position 2 Auxiliary output groups 3 5 4 Optional Main output type 2 3 4 5 DTC: Delta C series temperature controller 1: First controller 2: Controller connected in parallel 0: standard, 2 outputs, no auxiliary output 1: 1 auxiliary output. Not available now. 2: 2 auxiliary outputs. Not available now. 00: Standard 01: CT input. Not available now. 02: EVENT input. Not available now. R: Relay output SPST, 250VAC, 3A V: Voltage pulse output 12V +10% ~ -20% C: Current output 4 ~ 20mA L: Linear voltage output 0 ~ 10V Enclosed functions: DC24V input, 2 outputs, relay output for output 2, RS-485 communication. Function & Specification Power supply Voltage range Power consumption DC24V. Isolated switching power Rated voltage: 90% ~ 110% Rated 24 VDC, Max. 24 W combined, 3W + 3W x number of DTC2000 controllers (Max. 7) Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK Input sensors Platinum RTD: Pt100, JPt100 Linear DC input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mV Sampling rate Analog input: 0.15 sec. Thermocouple or platinum RTD: 0.4 sec. Control method PID , programmable PID, Manual, ON/OFF Relay: SPST, Max. load 250VAC, 3A resistive load Voltage pulse: 12VDC, Max. output current: 40mA Output types Current: DC 4 ~ 20mA (Load resistance: < 500Ω) Analog voltage: 0 ~ 10V (Load resistance: > 1,000Ω) Control output, alarm output, proportional output Output function Proportional output is available only when output 1 is linear voltage/current output. Alarm 12 alarm modes Communication RS-485 digital communication, 2,400bps ~ 38,400bps Communication protocol Modbus protocol, ASCII/RTU format Internal connection Internal terminals available to transmit 24V power supply and communication signals Vibration resistance 10 ~ 55Hz, 10m/s2 for 10mins, each in X, Y and Z direction Shock resistance Max. 300m/s2, 3 times in each 3 axes, 6 directions Ambient temperature 0 ~ 50°C Storage temperature -20 ~ +65°C Altitude < 2,000m Ambient humidity 35% ~ 85% RH (non-condensing) Pollution degree 2 13 9 3 4.0 3.4 60.0 3.0 3 25.2 Model Name Explanation 90.0 2 DANGER! Caution! Electric Shock! DTC1000/2000 series is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur. WARNING! Prevent dust or metallic debris from falling into the controller that will cause malfunction. DO NOT modify or disassemble the controller. DO NO use extra terminals. Do not install and/or use the controller in places subject to: dust or corrosive gases and liquid high humidity and high radiation vibration and shock Switch off the power when wiring or changing input sensors. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires. Shorten the wire when wiring a platinum resistance thermometer (RTD) to the controller, and separate power cable from load wires to prevent interference and conductive influence. Make sure the power cable and signals device are installed correctly before switching on the power of DTC1000/2000; otherwise serious damage may occur. DO NOT touch the terminals or repair the controller when the power is on to prevent electric shock. Wait at least one minute after the power is off to allow the capacitor to discharge. DO NOT touch any internal circuit within this period. DO NOT touch the internal terminals no matter the power is on or off. DO NOT place other heating source (e.g. power supply) in parallel with DTC1000/2000 during the installation. Please keep proper space in between. 12 10 3.0 Caution 11 8 DTC2000R/V/C/L 1 2 3 4 5 6 7 8 9 10 5 3 4 6 10 7 9 1 8 2 2 25.2 3.4 60.0 RUN/STOP switch Wiring and Model name DIN rail clip I/O terminals LED indicators Mounting hole Specification label Extension port Extension clip DIN rail RS-485 communication port Extension clip DC power input 90.0 Thank you very much for purchasing DELTA DTC1000/2000 Series Temperature Controller. Please read this instruction sheet before using your DTC1000/2000 series to ensure proper operation, and please keep this instruction sheet handy for quick reference. 7 1 3.0 Instruction Sheet 4 5 4.0 Temperature Controller 6 1 2 3 4 5 6 7 8 9 10 11 12 13 Output 100% 100% Cooling Heating 0 0 PV Figure 2: PID Control, Cooling) Control Figure 3: PID Control, Heating Control y Dual Output Control Deadband Heating hysteresis Cooling hysteresis ON Heating Wiring and Model name DIN rail clip I/O terminals LED indicators Mounting hole Specification label Extension port Extension clip DIN rail Extension port Cooling OFF PV Set Point Figure 4: ON/OFF Control Deadband: Dead Bandwidth: Positive Output Heating Input Deadband: Dead Bandwidth: Negative Output Cooling Cooling Heating PV 0 PV 0 Set Point DTC1000/2000 series supports the following input sensors: Input Sensor Set Point Figure 5: PID control Register Value PV Set Point Set Point Available Range Figure 6: PID Control 0 ~ 50mV linear voltage input 17 0 ~ 50mV y Programmable PID Control & Parameters Setting 4 ~ 20mA linear current input 16 4 ~ 20mA 0 ~ 20mA linear current input 15 0 ~ 20mA The programmable PID control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0 ~ 7) and parameters: “link pattern”, “cycle” and “the number of steps”. 0 ~ 10V linear voltage input 14 0 ~ 10V 0 ~ 5V linear voltage input 13 0 ~ 5V Platinum RTD (Pt100) 12 -200 ~ 600°C (-328 ~ 1,112°F) Platinum RTD (JPt100) 11 -20 ~ 400°C (-4 ~ 752°F) Thermocouple TXK type 10 -200 ~ 800°C (-328 ~ 1,472°F) Thermocouple U type 9 -200 ~ 500°C (-328 ~ 932°F) Thermocouple L type 8 -200 ~ 850oC (-328 ~ 1562°F) ° Start Pattern: The user can set up which pattern is the start pattern for the programmable control. ° Thermocouple B type 7 100 ~ 1,800 C (212 ~ 3,272 F) Thermocouple S type 6 0 ~ 1,700°C (32 ~ 3,092°F) Thermocouple R type 5 0 ~ 1,700°C (32 ~ 3,092°F) Thermocouple N type 4 -200 ~ 1,300°C (-328 ~ 2,372°F) Thermocouple E type 3 0 ~ 600°C (32 ~1,112°F) Thermocouple T type 2 -200 ~ 400°C (-328 ~ 752°F) Thermocouple J type 1 -100 ~ 1,200°C (-148 ~ 2,192°F) Thermocouple K type 0 -200 ~ 1,300°C (-328 ~ 2,372°F) Note 1: The current input is built-in with 249Ω precision resistor. See “How To Set up Current Input” section. Note 2: Default setting: Pt100 input. The range of linear input and feedback value is adjustable. Range of input feedback: -999 ~ 9,999. Take 0 ~ 20mA input as example, -999 refers to 0mA input, and 9,999 refers to 20mA input. If we change the range to 0 ~ 2,000, 0 will refer to 0mA input, and 2,000 will refer to 20mA input. 1 display scale = 0.01mA. Output There are several output types available from DTC1000/2000 series: Control Output (heating/cooling), Alarm Output and Proportional Output. Steps: Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV) has to rise to temperature X after the period of execution time T. If the result of the set point X is the same as that of the previous setting, the process is called “Soak”; otherwise, it is called “Ramp”. Therefore, the programmable control is also known as Ramp/Soak control. The default setting of the first step is Soak control. The temperature will first rise to the set point X and remain at X. The total execution time is T. Link Pattern: The pattern to be executed following the current pattern. If the setting is not 0 ~ 7, the set point will remain at the last pattern. Cycle: The additional number of cycles for a pattern. For example, if the parameter is set to 2, it refers to the pattern has to execute additional twice, totaling the execution to 3 times including the original one. The Number of Steps: The number of steps in each pattern (range: 0 ~ 7). For example, if the parameter is set to 2, it refers to the pattern will execute Step 0 ~ Step 2, and other steps will not be executed. The Execution: Available settings include “run”, “program hold”, “program stop” or “stop”. 1. When this parameter is set to “run”, the program will start its execution from step 0 of the start pattern. 2. When this parameter is set to “program hold”, the program will stop and the temperature will stop at the SV before the program stops. If the user sets to “run” again, the program will resume the step before the program stops and execute by the remaining time. 3. When this parameter is set to “program stop”, the program will stop and the temperature will stop at the SV before the program stops. If the user sets to “run” again, the program will execute again from Step 0 of the start pattern. 4. When this parameter is set to “stop”, the program will stop, and the control output will be disabled. Proportional Output: If Output 1 of this DTC1000/2000 series is linear voltage or current, the user can set it to “Proportional Output”. Proportional output refers to the output varies with the input. For example, if the input range is set to 0 ~ 1,000, and when the input value is 0, the output will be 0mA or 0V. When the input value is 1,000, the output will be 20mA or 10V. Output y Control Output 10V or 20mA 10V or 20mA DTC1000/2000 series offers 2 outputs for heating or cooling control. If you require dual loop output, the 2 outputs should be set to different actions (heating or cooling). If you require the 2 outputs are set to the same control action, only the control cycle of output 1 will be valid, and the 2 outputs will act at the same time. PV PV Low y Single Output Control Cooling hysteresis Positive output slope Negative output slope 0V or 4mA The control methods include: PID control, ON/OFF control, Manual control and programmable PID control. Heating hysteresis Output 0V or 4mA PV High PV PV Low PV High Figure 7: Proportional Output y Alarm Output ON Heating DTC1000/2000 series offers 12 alarm modes. When the PV exceeds or falls below SV, the alarm output will be enabled. See the table below for the 12 modes. Cooling PV OFF Set Point Set Point Figure1: ON/OFF Control Mode 0 1 Alarm Type No alarm Alarm output will be enabled when the temperature reaches upper and lower limits. y Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV – AL-L. Alarm Output Operation OFF ON OFF AL-L SV AL-H Mode Alarm Type 2 Alarm output will be enabled when the temperature reaches the upper limit. y Alarm will be enabled when the PV exceeds SV + AL-H. Alarm Output Operation 4 SV AL-L 8 AL-H ON OFF AL-L AL-H ON OFF Present temperature value (PV) AL-H 1001H 0 1002H Explanation Unit: 0.1 degree. Analog input: 1EU. The read values below indicate the occurrence of errors: 8002H: Temperature not acquired yet 8003H: Temperature sensor not connected 8004H: Incorrect sensor type 8006H: Unable to acquire temperature, ADC input error 8007H: Unable to read/write the memory ’:’ ‘0’ Machine address 1 ‘0’ ‘0’ Machine address 1 ‘0’ ‘0’ Machine address 0 ‘1’ ‘1’ Machine address 0 ‘1’ ‘1’ Machine address 0 ‘1’ ‘1’ Machine address 0 ‘1’ ‘1’ Command 1 ‘0’ ‘0’ Command 1 ‘0’ ‘0’ Command 1 ‘0’ ‘0’ Command 1 ‘0’ ‘0’ Command 0 ‘3’ ‘1’ Command 0 ‘3’ ‘1’ Command 0 ‘6’ ‘5’ Command 0 ‘6’ ‘5’ ‘1’ ‘0’ Length of response data ‘0’ (byte) ‘4’ Read staring address of ‘0’ ‘8’ data/bit ‘0’ ‘1’ ‘0’ ‘0’ ‘1’ ‘0’ ‘1’ ‘0’ ‘2’ ‘0’ ‘8’ ‘0’ ‘8’ ‘0’ ‘1’ ‘0’ ‘1’ ‘0’ 1004H 12 Input sensor type See the table in “Input” section. 1005H 0 Control method 0: PID, 1: ON/OFF, 2: Manual, 3: programmable PID 1007H 4 Control cycle of Output 1 0 ~ 99, 0: 0.5sec ‘0’ ‘0’ 1008H 4 Control cycle of Output 2 0 ~ 99, 0: 0.5sec (Invalid when the 2 outputs are the same control.) ‘0’ ‘0’ OFF Start word ’:’ ’:’ Start word ’:’ ’:’ Data content in 1000H/081xH ‘0’ ‘1’ ‘F’ ‘0’ ‘0’ ‘F’ ‘0’ ‘F’ ‘1’ ‘3’ ‘F’ ‘E’ ‘0’ ‘4’ ‘0’ ‘E’ ‘D’ Td value 0 ~ 9,999 0 Default integration value 0 ~ 1,000, Unit: 0.1% LRC1 check 100DH 0 Offset compensation value for proportional control (when Ti=0)) 0 ~ 1,000, Unit: 0.1% LRC0 check ‘A’ ‘D’ 100EH 100 COEF setting when in dual control output 1 ~ 9,999, Unit: 0.01 End word 1 CR CR LRC1 check 100FH 0 Deadband setting when in dual control output -999 ~ 9,999, Unit: 0.1° or 1EU End word 0 LF LF 1010H 0 Hysteresis of Output 1 0 ~ 9,999, Unit: 0.1° or 1EU ‘2’ ‘9’ Data content in 1001H Write data address ‘1’ ‘0’ ‘0’ 41 Write data address ‘7’ ‘0’ ‘0’ 100BH ‘1’ ‘1’ Read length of data/bit (word/bit) 100CH AL-H ON ’:’ ‘0’ The content shall not be smaller than the range. Unit: 0.1° 1 ~ 9,999, Unit: 0.1°. Analog input: 1EU AL-H Start word Machine address 1 Lower-limit of temperature range 0 ~ 9,999 Write Response Message ‘0’ ‘0’ -200 Proportional band value Write Command Machine address 1 1003H Ti value SV ’:’ The content shall not be bigger than the range. Unit: 0.1° 476 AL-L ’:’ Upper-limit of temperature range 260 OFF Read Response Message Start word 6,000 1009H AL-L Read Command Unit: 0.1 degree. Analog input: 1EU. 100AH ON y ASCII Mode Set point (SV) ON SV Lower limit standby alarm y Alarm will be enabled when the PV reaches SV and falls below SV – AL-L 10 SV ON OFF Upper limit standby alarm y Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H. 9 1000H SV ON OFF Alarm output will be enabled when the temperature reaches the absolute value of the upper and lower limits. y Alarm will be enabled when the PV exceeds AL-H or falls below AL-L. Alarm output will be enabled when the temperature reaches the absolute value of the upper limit. y Alarm will be enabled when the PV exceeds AL-H. Alarm output will be enabled when the temperature reaches the absolute value of the lower limit. y Alarm will be enabled when the PV falls below AL-L. Standby upper/lower limit alarm y Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or falls below SV – AL-L. 7 Content OFF AL-L 6 AL-H ON y Alarm will be enabled when the PV is between SV + AL-L and SV – AL-L. 5 Setting OFF Alarm output will be enabled when the temperature reaches the lower limit. y Alarm will be enabled when the PV falls below SV – AL-L. 3 Address ON To write data content ‘0’ ‘0’ LRC1 ‘0’ LRC0 ‘8’ ‘0’ ‘F’ ‘E’ ‘D’ ‘3’ Write data content ‘3’ ‘F’ ‘E’ ‘0’ ‘8’ LRC1 LRC0 ‘D’ ‘3’ ‘0’ ‘E’ End word 1 CR CR End word 1 CR CR LRC0 check ‘3’ ‘4’ End word 0 LF End word 0 LF LF End word 1 CR CR End word 0 LF LF LF 1011H 0 Hysteresis of Output 2 0 ~ 9,999, Unit: 0.1° or 1EU 1012H 0 Read/write output percentage of Output 1 Unit: 0.1%. “Write” is only applicable in manual mode. ON 1013H 0 Read/write output percentage of Output 2 Unit: 0.1%. “Write” is only applicable in manual mode. y LRC Check OFF 1014H 0 Upper-limit regulation for analog linear output 1 scale = 2.8μA = 1.3mV 1015H 0 Lower-limit regulation for analog linear output 1 scale = 2.8μA = 1.3mV LRC check sums up from “machine address” to “data content”, e.g. 01H + 03H + 10H+ 00H + 00H + 02H = 16H. Obtain 2’s complement EA. 1016H 0 Temperature offset regulation value -999 ~ +999, Unit: 0.1° or 1EU 1020H 0 Output mode for Alarm 1 See “Alarm Output” section. 1021H 0 Output mode for Alarm 2 See “Alarm Output” section. Note: AL-H and AL-L include AL1H, AL2H, AL1L and AL2L. When Output 1 is set to Alarm Output, use AL1H (1024H) and AL1L (1025H). When Output 2 is set to Alarm Output, use AL2H (1026H) and AL2L (1027H). 1022H 0 Communication flag auto-set 0: Communication banned, 1: Communication auto-set 1024H 40 Upper limit for Alarm 1 See “Alarm Output” section. LED Display 1025H 40 Lower limit for Alarm 1 See “Alarm Output” section. 1026H 40 Upper limit for Alarm 2 See “Alarm Output” section. 1027H 40 OFF AL-L Upper limit hysteresis alarm y Alarm will be enabled when the PV exceeds SV + AL-H and disabled when the PV falls below SV + AL-L. Lower limit hysteresis alarm y Alarm will be enabled when the PV falls below SV – AL-H and disabled when the PV exceeds SV – AL-L. 11 12 SV AL-L AL-H ON OFF AL-H AL-L 1. When power is normal, POWER LED will be on. 2. After DTC1000/2000 is switched on, all LED will be on. The communication protocol will be displayed in 1 second, followed by the communication address in the next second. 3. RUN LED is on when the control is executing. 4. ERROR LED is on when errors occur in input, memory or communication. 5. When an output is executing, its corresponding output LED will be on. 6. AT LED flashes when PID parameters are being auto-tuned. 7. RX LED flashes when DTC1000/2000 receives communication signals. TX LED flashes when DTC1000/2000 sends out communication signals. TX RX 000: 2,400bps 001: 4,800bps 011: 19,200bps 100: 38,400bps O1 010: 9,600bps Parity 00: None 10: Odd O2 01: Even Err 0: ASCII 1: RTU Run 0:2 Stop bits 1:1 Stop bit Communication address display: AT (bit 6) and Run (bit 0) are combined to binary code. Password Function The default setting of the password is disabled. To enable the password function, enter the 4-character password in the specific communication address. The password is protected by 3 levels. 1. Level 1: Only LED status, SV and PV can be read. No settings can be modified. 2. Level 2: Only LED status, SV and PV can be read. Only SV can be modified. 3. Level 3: All SV can be read. Only SV and auto-tuning can be modified. 4. Level 4: No password protection. When a password is set (in 106EH ~ 1070H), the protection will enter Level 1. To enter other levels, enter the corresponding password (in 106BH ~ 106DH). After DTC1000/2000 is switched off, the protection will return to Level 1. To unlock the password protection, the user has to remove all the passwords (in 106EH ~ 1070H). The password protection level can be read in 106EH ~ 1070H: bit b0 b1 b2 b3 b4 b5 b6 Status Level 1 Level 2 Level 3 Level 1 locked Level 2 locked Level 3 locked Unlocked bit = 0 refers to no password is set. bit = 1 refers to the password has been set (b0 ~ b2). b3 ~ b6 display the current level status. Synchronous Communication Protocol & Auto ID Setup This function allows the user to set the communication protocol of DTC2000 to the same protocol as set in the first DTC1000. The station IDs of DTC1000/2000 are arranged in decreasing order. Follow the steps below. 1. Set the auto communication ID of DTC1000 to “1” (communication address: 1022H). 2. Switch off DTC1000 before connecting it to DTC2000. Switch it on again. 3. Default communication protocol: 9,600bps, 7 bits, Even, 1 stop bit, communication address 01. 4. This function will consume 3 ~ 5 seconds more when you switch on your DTC. RS-485 Communication 1. 2. 3. 4. See “Alarm Output” section. b1: ALM2, b2: °C, b3: °F, b4: ALM1, b5: O2, b6:O1, b7: AT Positive/negative proportional output 0: positive, 1: negative LED status b0: RUN, b1: ERR, b2: O2, b3: O1, b4: RX, b5:TX b6: AT Software version V1.00 is indicated as 0x100 No. of start pattern 0~7 1032H Remaining time of the executed step 1033H Remaining time of the executed step 1034H No. of currently executed step 0~7 102CH 0 102EH 102FH 1030H 0 Supports transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps; Does not support 7, N, 1 / 8, E, 2 / 8, O, 2 communication format; Communication protocol: Modbus ASCII/RTU; Function code: 03H (read Max. 8 words in register), 06H (write 1 word into register), 01H (read Max. 16 bits of data), 05H (write 1 bit into register). y RTU Mode Read Command Read Response Message Write Command 01H 01H Machine address 01H 01H Machine address 01H 01H Machine address 01H 01H Command 03H 01H Command 03H 01H Command 06H 05H Command 06H 05H Read start address of data 10H 08H 00H 10H Length of response 04H 02H data (byte) Read length of data 00H (bit/word) 02H 00H 01H 17H Data content 1 09H CRC low byte C0H BBH CRC high byte CBH A9H Data content 2 F4H 01H Write data address Write data content E2H 9FH CRC high byte E2H 9FH CRC high byte 15H 88H 0~7 y CRC Program Example 0 ~ 100% upper limit of analog output, Unit: 0.1% 1038H 0 Lower limit of proportional output 0 ~ 100% lower limit of analog output, Unit: 0.1% unsigned int reg_crc = 0xffff; i = 0; while (length--) { reg_crc ^= RTUData[i]; i ++; for (j = 0; j < 8; j++) { if (reg_crc & 0x01) reg_crc = (reg_crc >> 1) ^ 0xA001; else reg_crc = reg_crc >> 1; } } return(reg_crc); 1040H~ 1043H 7 Number of steps in a pattern 0 ~ 7 = N refers to the pattern will be executed from Step 0 to Step N. 1050H~ 1053H 0 Additional number of cycles for a pattern 0 ~ 199 refers to the pattern will be executed for 1 ~ 200 times. 1060H~ 1063H 0 No. of the link pattern for the current pattern 0 ~ 8, 8 refers to end of the program. 0 ~ 7 refers to the next pattern No. following the current pattern. 1068H 1 Run/Stop setting 0: Stop, 1: Run, 2: Program end, 3: Program hold 1069H 0 Control selection of Output 1 0: Heating, 1: Cooling, 2: Alarm, 3: Proportional output 106AH 0 Control selection of Output 2 0: Heating, 1: Cooling, 2: Alarm 106BH 0 Unlock Level 1 password protection. Read/write allowed Shall be the same as Level 1 password (106E) 106CH 0 Unlock Level 2 password protection. Use Level 3. Shall be the same as Level 2 password (106F) Installation 0 Unlock Level 3 password protection. Use Level 2 Shall be the same as Level 3 password (1070) How to connect maximum 8 DTC1000/2000 controllers by using DIN rail. 0 Unlock Level 1 password protection/Set up password Unlock password before setting it up. 0 Unlock Level 2 password protection/Set up password Unlock password before setting it up. 1070H 0 Unlock Level 3 password protection/Set up password Unlock password before setting it up. 1071H 1 Read/write communication address 1 ~ 247 1072H 0 Read/write communication format 1: RTU, 0: ASCII 1073H 2 Read/write communication speed 0 ~ 4: 2,400 ~ 38,400 1074H 1 Read/write communication data length 0: 8 bits, 1: 7 bits 1075H 1 Read/write parity bit 0: None, 1: Even, 2: Odd 1076H 1 Read/write stop bit 0: 2 stop bits, 1: 1 stop bit 2000H~ 203FH 0 SV temperature for Pattern 0 ~ 7. SV for Pattern 0 is set in 2000H ~ 2007H Unit: 0.1° 2080H~ 20BFH 0 Execution time for Pattern 0~7. Time for Pattern 0 is set in 2080H ~ 2087H 0 ~ 900 (1 scale = 1 minute) How to Set Up Current Input For general input 0:°F, 1: °C (Default) 0813H Read/write auto-tuning status 0: End (Default), 1: Start 0814H Run/Stop setting 0: Stop, 1: Run (Default) 0815H Program hold flag 1: Program hold 0816H Program stop flag 1: Program stop 6. Communication format: Command 01: read bit, 05: write bit, 03: read word, 06: write word. 20H 00H CRC high byte Unit: minute Temperature unit display 03H FFH 20H Unit: second 0811H Write data content 01H 10H DDH 8FH BBH 77H 5. Address and content of the bit register (read bits are stored starting from LSB, and written data is FF00H, set the bit as 1. 0000H sets the bits data to “0”). 20H 00H 10H 08H CRC low byte CRC low byte 03H FFH Write data address DDH 8FH No. of currently executed pattern 106FH 01H 10H CRC low byte Upper limit of proportional output 106EH 10H 08H 03H 1,000 106DH Write Response Message Machine address 1037H 1035H Communication protocol displayed on LED after the power of DTC1000/2000 is switched on: AT Lower limit for Alarm 2 Read/write status 102AH ‘0’ ‘F’ ‘E’ For current input (4 ~ 20mA, 0 ~ 20mA) JU MP ER JP1 J UMP E R P IN HE A DE R JP1 P IN HE A DE R DE FA U LT SE TTI NG The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0.5 (Windows) Create Date : 2008:08:27 15:42:23+08:00 Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2008:08:27 15:42:23+08:00 Format : application/pdf Title : Microsoft Word - 5011635004-DCE4.doc Creator : Document ID : uuid:c72caa8b-3685-4136-a6a1-97542c918f43 Instance ID : uuid:b00b25ee-34e6-47d8-8aa4-99411b6c2b05 Page Count : 2 Author :EXIF Metadata provided by EXIF.tools