Delta Electronics Dtc1000 Series Users Manual 5011635004 DCE4

Delta-Dtc1000-Series-Users-Manual-245024 delta-dtc1000-series-users-manual-245024

DTC1000 Series to the manual ddc5a879-79f5-43c6-a36d-d2b952b7521b

2015-01-24

: Delta-Electronics Delta-Electronics-Dtc1000-Series-Users-Manual-339138 delta-electronics-dtc1000-series-users-manual-339138 delta-electronics pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadDelta-Electronics Delta-Electronics-Dtc1000-Series-Users-Manual 5011635004-DCE4
Open PDF In BrowserView PDF
  Product Profile & Outline

Output

3.0

DTC1000R/V/C/L
http://www.delta.com.tw/industrialautomation/

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

DTC 1
Series name
1

Controller position

2

Auxiliary output
groups

3

5

4

Optional

Main output type

2

3

4

5

DTC: Delta C series temperature controller
1: First controller
2: Controller connected in parallel
0: standard, 2 outputs, no auxiliary output
1: 1 auxiliary output. Not available now.
2: 2 auxiliary outputs. Not available now.
00: Standard
01: CT input. Not available now.
02: EVENT input. Not available now.
R: Relay output SPST, 250VAC, 3A
V: Voltage pulse output 12V +10% ~ -20%
C: Current output 4 ~ 20mA
L: Linear voltage output 0 ~ 10V

Enclosed functions: DC24V input, 2 outputs, relay output for output 2, RS-485 communication.

  Function & Specification
Power supply
Voltage range
Power consumption

DC24V. Isolated switching power
Rated voltage: 90% ~ 110%
Rated 24 VDC, Max. 24 W combined, 3W + 3W x number of DTC2000 controllers (Max. 7)
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Input sensors
Platinum RTD: Pt100, JPt100
Linear DC input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mV
Sampling rate
Analog input: 0.15 sec. Thermocouple or platinum RTD: 0.4 sec.
Control method
PID , programmable PID, Manual, ON/OFF
Relay: SPST, Max. load 250VAC, 3A resistive load
Voltage pulse: 12VDC, Max. output current: 40mA
Output types
Current: DC 4 ~ 20mA (Load resistance: < 500Ω)
Analog voltage: 0 ~ 10V (Load resistance: > 1,000Ω)
Control output, alarm output, proportional output
Output function
Proportional output is available only when output 1 is linear voltage/current output.
Alarm
12 alarm modes
Communication
RS-485 digital communication, 2,400bps ~ 38,400bps
Communication protocol Modbus protocol, ASCII/RTU format
Internal connection
Internal terminals available to transmit 24V power supply and communication signals
Vibration resistance
10 ~ 55Hz, 10m/s2 for 10mins, each in X, Y and Z direction
Shock resistance
Max. 300m/s2, 3 times in each 3 axes, 6 directions
Ambient temperature
0 ~ 50°C
Storage temperature
-20 ~ +65°C
Altitude
< 2,000m
Ambient humidity
35% ~ 85% RH (non-condensing)
Pollution degree
2

13

9
3

4.0

3.4

60.0

3.0

3

25.2

  Model Name Explanation

90.0

2

DANGER! Caution! Electric Shock!
DTC1000/2000 series is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne
dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may
occur.
WARNING!
Prevent dust or metallic debris from falling into the controller that will cause malfunction. DO NOT modify or
disassemble the controller. DO NO use extra terminals.
Do not install and/or use the controller in places subject to:
ƒ dust or corrosive gases and liquid ƒ high humidity and high radiation ƒ vibration and shock
Switch off the power when wiring or changing input sensors.
Be sure to use compensating wires that match the thermocouple types when extending or connecting the
thermocouple wires.
Shorten the wire when wiring a platinum resistance thermometer (RTD) to the controller, and separate power cable
from load wires to prevent interference and conductive influence.
Make sure the power cable and signals device are installed correctly before switching on the power of
DTC1000/2000; otherwise serious damage may occur.
DO NOT touch the terminals or repair the controller when the power is on to prevent electric shock.
Wait at least one minute after the power is off to allow the capacitor to discharge. DO NOT touch any internal circuit
within this period.
DO NOT touch the internal terminals no matter the power is on or off.
DO NOT place other heating source (e.g. power supply) in parallel with DTC1000/2000 during the installation.
Please keep proper space in between.

12

10

3.0

  Caution

11

8

DTC2000R/V/C/L
1
2
3
4
5
6
7
8
9
10

5

3
4

6

10

7
9
1

8
2

2

25.2

3.4

60.0

RUN/STOP switch
Wiring and Model name
DIN rail clip
I/O terminals
LED indicators
Mounting hole
Specification label
Extension port
Extension clip
DIN rail
RS-485 communication port
Extension clip
DC power input

90.0

Thank you very much for purchasing DELTA DTC1000/2000 Series Temperature Controller. Please read this
instruction sheet before using your DTC1000/2000 series to ensure proper operation, and please keep this instruction
sheet handy for quick reference.

7

1

3.0

Instruction Sheet

4
5

4.0

Temperature Controller

6

1
2
3
4
5
6
7
8
9
10
11
12
13

Output

100%

100%
Cooling

Heating

0

0

PV

Figure 2: PID Control, Cooling) Control

Figure 3: PID Control, Heating Control

y Dual Output Control
Deadband
Heating hysteresis

Cooling hysteresis

ON
Heating

Wiring and Model name
DIN rail clip
I/O terminals
LED indicators
Mounting hole
Specification label
Extension port
Extension clip
DIN rail
Extension port

Cooling

OFF

PV
Set Point
Figure 4: ON/OFF Control

Deadband: Dead
Bandwidth: Positive

Output

Heating

  Input

Deadband: Dead
Bandwidth: Negative

Output

Cooling

Cooling

Heating
PV

0

PV

0

Set Point

DTC1000/2000 series supports the following input sensors:
Input Sensor

Set Point

Figure 5: PID control

Register Value

PV

Set Point

Set Point

Available Range

Figure 6: PID Control

0 ~ 50mV linear voltage input

17

0 ~ 50mV

y Programmable PID Control & Parameters Setting

4 ~ 20mA linear current input

16

4 ~ 20mA

0 ~ 20mA linear current input

15

0 ~ 20mA

The programmable PID control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0 ~ 7) and
parameters: “link pattern”, “cycle” and “the number of steps”.

0 ~ 10V linear voltage input

14

0 ~ 10V

0 ~ 5V linear voltage input

13

0 ~ 5V

Platinum RTD (Pt100)

12

-200 ~ 600°C (-328 ~ 1,112°F)

Platinum RTD (JPt100)

11

-20 ~ 400°C (-4 ~ 752°F)

Thermocouple TXK type

10

-200 ~ 800°C (-328 ~ 1,472°F)

Thermocouple U type

9

-200 ~ 500°C (-328 ~ 932°F)

Thermocouple L type

8

-200 ~ 850oC (-328 ~ 1562°F)
°

Start Pattern: The user can set up which pattern is the start pattern for the programmable control.

°

Thermocouple B type

7

100 ~ 1,800 C (212 ~ 3,272 F)

Thermocouple S type

6

0 ~ 1,700°C (32 ~ 3,092°F)

Thermocouple R type

5

0 ~ 1,700°C (32 ~ 3,092°F)

Thermocouple N type

4

-200 ~ 1,300°C (-328 ~ 2,372°F)

Thermocouple E type

3

0 ~ 600°C (32 ~1,112°F)

Thermocouple T type

2

-200 ~ 400°C (-328 ~ 752°F)

Thermocouple J type

1

-100 ~ 1,200°C (-148 ~ 2,192°F)

Thermocouple K type
0
-200 ~ 1,300°C (-328 ~ 2,372°F)
Note 1: The current input is built-in with 249Ω precision resistor. See “How To Set up Current Input” section.
Note 2: Default setting: Pt100 input.
The range of linear input and feedback value is adjustable. Range of input feedback: -999 ~ 9,999. Take 0 ~ 20mA input
as example, -999 refers to 0mA input, and 9,999 refers to 20mA input. If we change the range to 0 ~ 2,000, 0 will refer to
0mA input, and 2,000 will refer to 20mA input. 1 display scale = 0.01mA.

  Output
There are several output types available from DTC1000/2000 series: Control Output (heating/cooling), Alarm Output
and Proportional Output.

Steps: Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV)
has to rise to temperature X after the period of execution time T. If the result of the set point X is the same as that of
the previous setting, the process is called “Soak”; otherwise, it is called “Ramp”. Therefore, the programmable control
is also known as Ramp/Soak control. The default setting of the first step is Soak control. The temperature will first rise
to the set point X and remain at X. The total execution time is T.
Link Pattern: The pattern to be executed following the current pattern. If the setting is not 0 ~ 7, the set point will
remain at the last pattern.
Cycle: The additional number of cycles for a pattern. For example, if the parameter is set to 2, it refers to the pattern
has to execute additional twice, totaling the execution to 3 times including the original one.
The Number of Steps: The number of steps in each pattern (range: 0 ~ 7). For example, if the parameter is set to 2,
it refers to the pattern will execute Step 0 ~ Step 2, and other steps will not be executed.
The Execution: Available settings include “run”, “program hold”, “program stop” or “stop”.
1. When this parameter is set to “run”, the program will start its execution from step 0 of the start pattern.
2. When this parameter is set to “program hold”, the program will stop and the temperature will stop at the SV before
the program stops. If the user sets to “run” again, the program will resume the step before the program stops and
execute by the remaining time.
3. When this parameter is set to “program stop”, the program will stop and the temperature will stop at the SV before
the program stops. If the user sets to “run” again, the program will execute again from Step 0 of the start pattern.
4. When this parameter is set to “stop”, the program will stop, and the control output will be disabled.
Proportional Output:
If Output 1 of this DTC1000/2000 series is linear voltage or current, the user can set it to “Proportional Output”.
Proportional output refers to the output varies with the input. For example, if the input range is set to 0 ~ 1,000, and
when the input value is 0, the output will be 0mA or 0V. When the input value is 1,000, the output will be 20mA or 10V.
Output

y Control Output

10V or 20mA

10V or 20mA

DTC1000/2000 series offers 2 outputs for heating or cooling control. If you require dual loop output, the 2 outputs
should be set to different actions (heating or cooling). If you require the 2 outputs are set to the same control action, only
the control cycle of output 1 will be valid, and the 2 outputs will act at the same time.

PV
PV Low

y Single Output Control
Cooling hysteresis

Positive output slope

Negative
output slope

0V or 4mA

The control methods include: PID control, ON/OFF control, Manual control and programmable PID control.

Heating hysteresis

Output

0V or 4mA

PV High

PV
PV Low

PV High

Figure 7: Proportional Output

y Alarm Output

ON
Heating

DTC1000/2000 series offers 12 alarm modes. When the PV exceeds or falls below SV, the alarm output will be enabled.
See the table below for the 12 modes.

Cooling
PV

OFF
Set Point

Set Point

Figure1: ON/OFF Control

Mode
0
1

Alarm Type
No alarm
Alarm output will be enabled when the temperature reaches upper and lower
limits.
y Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV –
AL-L.

Alarm Output Operation
OFF
ON
OFF
AL-L

SV

AL-H

Mode

Alarm Type

2

Alarm output will be enabled when the temperature reaches the upper limit.
y Alarm will be enabled when the PV exceeds SV + AL-H.

Alarm Output Operation

4

SV

AL-L

8

AL-H

ON
OFF
AL-L

AL-H

ON
OFF

Present temperature value (PV)

AL-H

1001H

0

1002H

Explanation
Unit: 0.1 degree. Analog input: 1EU.
The read values below indicate the occurrence of errors:
8002H: Temperature not acquired yet
8003H: Temperature sensor not connected
8004H: Incorrect sensor type
8006H: Unable to acquire temperature, ADC input error
8007H: Unable to read/write the memory

’:’

‘0’

Machine address 1

‘0’

‘0’

Machine address 1

‘0’

‘0’

Machine address 0

‘1’ ‘1’

Machine address 0

‘1’

‘1’

Machine address 0

‘1’

‘1’

Machine address 0

‘1’

‘1’

Command 1

‘0’ ‘0’

Command 1

‘0’

‘0’

Command 1

‘0’

‘0’

Command 1

‘0’

‘0’

Command 0

‘3’ ‘1’

Command 0

‘3’

‘1’

Command 0

‘6’

‘5’

Command 0

‘6’

‘5’

‘1’ ‘0’ Length of response data ‘0’
(byte)
‘4’
Read staring address of ‘0’ ‘8’
data/bit
‘0’ ‘1’
‘0’

‘0’

‘1’

‘0’

‘1’

‘0’

‘2’

‘0’

‘8’

‘0’

‘8’

‘0’

‘1’

‘0’

‘1’
‘0’

1004H

12

Input sensor type

See the table in “Input” section.

1005H

0

Control method

0: PID, 1: ON/OFF, 2: Manual, 3: programmable PID

1007H

4

Control cycle of Output 1

0 ~ 99, 0: 0.5sec

‘0’ ‘0’

1008H

4

Control cycle of Output 2

0 ~ 99, 0: 0.5sec (Invalid when the 2 outputs are the same
control.)

‘0’ ‘0’

OFF

Start word

’:’

’:’

Start word

’:’

’:’

Data content in
1000H/081xH

‘0’

‘1’

‘F’

‘0’

‘0’

‘F’

‘0’ ‘F’

‘1’

‘3’

‘F’

‘E’

‘0’

‘4’
‘0’

‘E’ ‘D’

Td value

0 ~ 9,999

0

Default integration value

0 ~ 1,000, Unit: 0.1%

LRC1 check

100DH

0

Offset compensation value for proportional
control (when Ti=0))

0 ~ 1,000, Unit: 0.1%

LRC0 check

‘A’ ‘D’

100EH

100

COEF setting when in dual control output

1 ~ 9,999, Unit: 0.01

End word 1

CR CR

LRC1 check

100FH

0

Deadband setting when in dual control
output

-999 ~ 9,999, Unit: 0.1° or 1EU

End word 0

LF LF

1010H

0

Hysteresis of Output 1

0 ~ 9,999, Unit: 0.1° or 1EU

‘2’ ‘9’

Data content in 1001H

Write data address

‘1’

‘0’ ‘0’

41

Write data address

‘7’

‘0’ ‘0’

100BH

‘1’

‘1’

Read length of data/bit
(word/bit)

100CH
AL-H

ON

’:’

‘0’

The content shall not be smaller than the range. Unit: 0.1°

1 ~ 9,999, Unit: 0.1°. Analog input: 1EU

AL-H

Start word

Machine address 1

Lower-limit of temperature range

0 ~ 9,999

Write Response Message

‘0’ ‘0’

-200

Proportional band value

Write Command

Machine address 1

1003H

Ti value

SV

’:’

The content shall not be bigger than the range. Unit: 0.1°

476

AL-L

’:’

Upper-limit of temperature range

260

OFF

Read Response Message

Start word

6,000

1009H
AL-L

Read Command

Unit: 0.1 degree. Analog input: 1EU.

100AH

ON

y ASCII Mode

Set point (SV)

ON

SV

Lower limit standby alarm
y Alarm will be enabled when the PV reaches SV and falls below SV – AL-L

10

SV

ON
OFF

Upper limit standby alarm
y Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H.

9

1000H

SV

ON
OFF

Alarm output will be enabled when the temperature reaches the absolute
value of the upper and lower limits.
y Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.
Alarm output will be enabled when the temperature reaches the absolute
value of the upper limit.
y Alarm will be enabled when the PV exceeds AL-H.
Alarm output will be enabled when the temperature reaches the absolute
value of the lower limit.
y Alarm will be enabled when the PV falls below AL-L.
Standby upper/lower limit alarm
y Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or
falls below SV – AL-L.

7

Content

OFF

AL-L

6

AL-H

ON

y Alarm will be enabled when the PV is between SV + AL-L and SV – AL-L.

5

Setting

OFF

Alarm output will be enabled when the temperature reaches the lower limit.
y Alarm will be enabled when the PV falls below SV – AL-L.

3

Address

ON

To write data content

‘0’
‘0’

LRC1

‘0’

LRC0

‘8’

‘0’

‘F’

‘E’

‘D’

‘3’

Write data content

‘3’ ‘F’
‘E’ ‘0’
‘8’

LRC1
LRC0

‘D’ ‘3’

‘0’

‘E’

End word 1

CR CR

End word 1

CR CR

LRC0 check

‘3’

‘4’

End word 0

LF

End word 0

LF LF

End word 1

CR CR

End word 0

LF LF

LF

1011H

0

Hysteresis of Output 2

0 ~ 9,999, Unit: 0.1° or 1EU

1012H

0

Read/write output percentage of Output 1

Unit: 0.1%. “Write” is only applicable in manual mode.

ON

1013H

0

Read/write output percentage of Output 2

Unit: 0.1%. “Write” is only applicable in manual mode.

y LRC Check

OFF

1014H

0

Upper-limit regulation for analog linear output

1 scale = 2.8μA = 1.3mV

1015H

0

Lower-limit regulation for analog linear output

1 scale = 2.8μA = 1.3mV

LRC check sums up from “machine address” to “data content”, e.g. 01H + 03H + 10H+ 00H + 00H + 02H = 16H. Obtain 2’s
complement EA.

1016H

0

Temperature offset regulation value

-999 ~ +999, Unit: 0.1° or 1EU

1020H

0

Output mode for Alarm 1

See “Alarm Output” section.

1021H

0

Output mode for Alarm 2

See “Alarm Output” section.

Note: AL-H and AL-L include AL1H, AL2H, AL1L and AL2L. When Output 1 is set to Alarm Output, use AL1H (1024H) and AL1L
(1025H). When Output 2 is set to Alarm Output, use AL2H (1026H) and AL2L (1027H).

1022H

0

Communication flag auto-set

0: Communication banned, 1: Communication auto-set

1024H

40

Upper limit for Alarm 1

See “Alarm Output” section.

  LED Display

1025H

40

Lower limit for Alarm 1

See “Alarm Output” section.

1026H

40

Upper limit for Alarm 2

See “Alarm Output” section.

1027H

40

OFF
AL-L

Upper limit hysteresis alarm
y Alarm will be enabled when the PV exceeds SV + AL-H and disabled when
the PV falls below SV + AL-L.
Lower limit hysteresis alarm
y Alarm will be enabled when the PV falls below SV – AL-H and disabled
when the PV exceeds SV – AL-L.

11

12

SV

AL-L

AL-H

ON
OFF
AL-H

AL-L

1. When power is normal, POWER LED will be on.
2. After DTC1000/2000 is switched on, all LED will be on. The communication protocol will be displayed in 1 second,
followed by the communication address in the next second.
3. RUN LED is on when the control is executing.
4. ERROR LED is on when errors occur in input, memory or communication.
5. When an output is executing, its corresponding output LED will be on.
6. AT LED flashes when PID parameters are being auto-tuned.
7. RX LED flashes when DTC1000/2000 receives communication signals. TX LED flashes when DTC1000/2000
sends out communication signals.
TX

RX

000: 2,400bps 001: 4,800bps
011: 19,200bps 100: 38,400bps

O1

010: 9,600bps

Parity

00: None
10: Odd

O2
01: Even

Err
0: ASCII
1: RTU

Run
0:2 Stop bits
1:1 Stop bit

Communication address display: AT (bit 6) and Run (bit 0) are combined to binary code.

  Password Function
The default setting of the password is disabled. To enable the password function, enter the 4-character password in the
specific communication address. The password is protected by 3 levels.
1. Level 1: Only LED status, SV and PV can be read. No settings can be modified.
2. Level 2: Only LED status, SV and PV can be read. Only SV can be modified.
3. Level 3: All SV can be read. Only SV and auto-tuning can be modified.
4. Level 4: No password protection.
When a password is set (in 106EH ~ 1070H), the protection will enter Level 1. To enter other levels, enter the
corresponding password (in 106BH ~ 106DH). After DTC1000/2000 is switched off, the protection will return to Level 1.
To unlock the password protection, the user has to remove all the passwords (in 106EH ~ 1070H).
The password protection level can be read in 106EH ~ 1070H:
bit

b0

b1

b2

b3

b4

b5

b6

Status

Level 1

Level 2

Level 3

Level 1 locked

Level 2 locked

Level 3 locked

Unlocked

bit = 0 refers to no password is set. bit = 1 refers to the password has been set (b0 ~ b2). b3 ~ b6 display the current level status.

  Synchronous Communication Protocol & Auto ID Setup
This function allows the user to set the communication protocol of DTC2000 to the same protocol as set in the first
DTC1000. The station IDs of DTC1000/2000 are arranged in decreasing order. Follow the steps below.
1. Set the auto communication ID of DTC1000 to “1” (communication address: 1022H).
2. Switch off DTC1000 before connecting it to DTC2000. Switch it on again.
3. Default communication protocol: 9,600bps, 7 bits, Even, 1 stop bit, communication address 01.
4. This function will consume 3 ~ 5 seconds more when you switch on your DTC.

  RS-485 Communication
1.
2.
3.
4.

See “Alarm Output” section.
b1: ALM2, b2: °C, b3: °F, b4: ALM1, b5: O2, b6:O1, b7: AT

Positive/negative proportional output

0: positive, 1: negative

LED status

b0: RUN, b1: ERR, b2: O2, b3: O1, b4: RX, b5:TX b6: AT

Software version

V1.00 is indicated as 0x100

No. of start pattern

0~7

1032H

Remaining time of the executed step

1033H

Remaining time of the executed step

1034H

No. of currently executed step

0~7

102CH

0

102EH
102FH
1030H

0

Supports transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps;
Does not support 7, N, 1 / 8, E, 2 / 8, O, 2 communication format;
Communication protocol: Modbus ASCII/RTU;
Function code: 03H (read Max. 8 words in register), 06H (write 1 word into register), 01H (read Max. 16 bits of
data), 05H (write 1 bit into register).

y RTU Mode
Read Command

Read Response Message

Write Command

01H

01H

Machine address

01H 01H

Machine address

01H 01H

Machine address

01H 01H

Command

03H

01H

Command

03H 01H

Command

06H 05H

Command

06H 05H

Read start address
of data

10H

08H

00H

10H

Length of response
04H 02H
data (byte)

Read length of data 00H
(bit/word)
02H

00H

01H 17H

Data content 1

09H

CRC low byte

C0H BBH

CRC high byte

CBH A9H

Data content 2

F4H 01H

Write data address

Write data content

E2H 9FH

CRC high byte

E2H 9FH

CRC high byte

15H 88H

0~7

y CRC Program Example

0 ~ 100% upper limit of analog output, Unit: 0.1%

1038H

0

Lower limit of proportional output

0 ~ 100% lower limit of analog output, Unit: 0.1%

unsigned int reg_crc = 0xffff; i = 0;
while (length--)
{
reg_crc ^= RTUData[i];
i ++;
for (j = 0; j < 8; j++)
{
if (reg_crc & 0x01)
reg_crc = (reg_crc >> 1) ^ 0xA001;
else
reg_crc = reg_crc >> 1;
}
}
return(reg_crc);

1040H~
1043H

7

Number of steps in a pattern

0 ~ 7 = N refers to the pattern will be executed from Step 0
to Step N.

1050H~
1053H

0

Additional number of cycles for a pattern

0 ~ 199 refers to the pattern will be executed for 1 ~ 200
times.

1060H~
1063H

0

No. of the link pattern for the current
pattern

0 ~ 8, 8 refers to end of the program. 0 ~ 7 refers to the
next pattern No. following the current pattern.

1068H

1

Run/Stop setting

0: Stop, 1: Run, 2: Program end, 3: Program hold

1069H

0

Control selection of Output 1

0: Heating, 1: Cooling, 2: Alarm, 3: Proportional output

106AH

0

Control selection of Output 2

0: Heating, 1: Cooling, 2: Alarm

106BH

0

Unlock Level 1 password protection.
Read/write allowed

Shall be the same as Level 1 password (106E)

106CH

0

Unlock Level 2 password protection. Use
Level 3.

Shall be the same as Level 2 password (106F)

  Installation

0

Unlock Level 3 password protection. Use
Level 2

Shall be the same as Level 3 password (1070)

How to connect maximum 8 DTC1000/2000 controllers by using DIN rail.

0

Unlock Level 1 password protection/Set up
password

Unlock password before setting it up.

0

Unlock Level 2 password protection/Set up
password

Unlock password before setting it up.

1070H

0

Unlock Level 3 password protection/Set up
password

Unlock password before setting it up.

1071H

1

Read/write communication address

1 ~ 247

1072H

0

Read/write communication format

1: RTU, 0: ASCII

1073H

2

Read/write communication speed

0 ~ 4: 2,400 ~ 38,400

1074H

1

Read/write communication data length

0: 8 bits, 1: 7 bits

1075H

1

Read/write parity bit

0: None, 1: Even, 2: Odd

1076H

1

Read/write stop bit

0: 2 stop bits, 1: 1 stop bit

2000H~
203FH

0

SV temperature for Pattern 0 ~ 7.
SV for Pattern 0 is set in 2000H ~ 2007H

Unit: 0.1°

2080H~
20BFH

0

Execution time for Pattern 0~7.
Time for Pattern 0 is set in 2080H ~ 2087H

0 ~ 900 (1 scale = 1 minute)

How to Set Up Current Input

For general input

0:°F, 1: °C (Default)

0813H

Read/write auto-tuning status

0: End (Default), 1: Start

0814H

Run/Stop setting

0: Stop, 1: Run (Default)

0815H

Program hold flag

1: Program hold

0816H

Program stop flag

1: Program stop

6. Communication format: Command 01: read bit, 05: write bit, 03: read word, 06: write word.

20H 00H

CRC high byte

Unit: minute

Temperature unit display

03H FFH

20H

Unit: second

0811H

Write data content

01H 10H

DDH 8FH

BBH 77H

5. Address and content of the bit register (read bits are stored starting from LSB, and written data is FF00H, set the
bit as 1. 0000H sets the bits data to “0”).

20H 00H

10H 08H

CRC low byte

CRC low byte

 

03H FFH

Write data address

DDH 8FH

No. of currently executed pattern

106FH

01H 10H

CRC low byte

Upper limit of proportional output

106EH

10H 08H

03H

1,000

106DH

Write Response Message

Machine address

1037H

1035H

Communication protocol displayed on LED after the power of DTC1000/2000 is switched on:
AT

Lower limit for Alarm 2
Read/write status

102AH

‘0’

‘F’ ‘E’

For current input (4 ~ 20mA, 0 ~ 20mA)
JU MP ER

JP1

J UMP E R

P IN HE A DE R

JP1

P IN HE A DE R

DE FA U LT SE TTI NG

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Create Date                     : 2008:08:27 15:42:23+08:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2008:08:27 15:42:23+08:00
Format                          : application/pdf
Title                           : Microsoft Word - 5011635004-DCE4.doc
Creator                         : 
Document ID                     : uuid:c72caa8b-3685-4136-a6a1-97542c918f43
Instance ID                     : uuid:b00b25ee-34e6-47d8-8aa4-99411b6c2b05
Page Count                      : 2
Author                          : 
EXIF Metadata provided by EXIF.tools

Navigation menu