• • • • T&B Services, Ltd. 110B E. Grand Ave. Eau Claire, WI 54701 Eau Claire: (715) 835-7813 Madison: (608) 251-2461 FAX: (715) 723-4529 Email: tbservicesltd@charter.net Testing & Balancing System Analysis Air • Hydronics Sound • Vibration BALANCE REPORT DSF#: 06A3T PROJECT: ADMINISTRATION BLDG. HVAC/CEILING REPLACEMENT UNIVERSITY OF WISCONSIN-STOUT MENOMONIE, WISCONSIN ARCHITECT: ENGINEER: CONTRACTOR: LIEN & PETERSON ARCHITECTS, INC. EAU CLAIRE, WISCONSIN APEX ENGINEERING EAU CLAIRE, WISCONSIN CERTIFIED, INC. ALTOONA, WISCONSIN CERTIFICATION OF REPORT THIS IS TO CERTIFY THAT THE ATTACHED REPORT IS A TRUE AND ACCURATE REPRESENTATION OF THE FINAL OPERATING CONDITIONS OF EQUIPMENT AND AIR DISTRIBUTION SYSTEMS, IN ACCORDANCE WITH PLANS DATED 11-15-06 BY: DATE: Douglas J. Hermans, P.E. November 15, 2007 T&B Services, Ltd. 110B E. Grand Ave. Eau Claire, WI 54701 Eau Claire: (715) 835-7813 Madison: (608) 251-2461 FAX: (715) 723-4529 Email: tbservicesltd@charter.net •Testing & Balancing •System Analysis •Air • Hydronics •Sound • Vibration Administration Building HVAC/Ceiling Replacement UW Stout Menomonie, Wisconsin DSF #: 06A3T Summary Design Actual AHU-1: 26,000 cfm 26,064 cfm RF-1: 24,250 cfm 22,965 cfm EF-1: 1,500 cfm 904 cfm CW Coil AHU-1: 54.75 gpm 53.0 gpm 54.75 gpm 55.8 gpm 26.0 gpm 26.2 gpm CW Coil AHU-2: Difiencencies AHU-1: System incorporates a separate minimum outside air and minimum relief opening/damper. The supply fan is being controlled off of system static with the return fan tracking off of a differential flow set point. The minimum outside air damper is controlled to open and close to maintain a minimum outside air set point. The relief damper is currently set up to track the minimum outside damper and with the system at minimum outside air, the outside air damper is being driven to 100% open but is short on air. This is being caused by the fact that when at minimum outside air the discharge of the retrun fan is under a negative pressure and air is being drawn in from the minimum relief opening/damper. Total outside will be at design (differential flow set point) but the minimum outside air AMD will be reading a flow that is short on air. EF-1: Fan is existing and is currently at 60% of design with the motor fully loaded. 1 Sheet T&B Services, Ltd. 37 of By 8/3/07 11/14/07 Date DA DA FAN EQUIPMENT TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 3rd Floor Mech. EQUIPMENT LOCATION FAN MANUFACTURER MODEL OR SERIAL NO. McQuay CAH053GDDM TOTAL CFM MIN O.A. RETURN CFM FAN SUCTION PRESSURE (TP) FAN DISCHARGE PRESSURE (SP) FAN STATIC PRESSURE FAN RPM FAN PULLY - SIZE, TYPE MFGR. BELT QUANTITY / SIZE C-C FILTER SIZE & QUANTITY MTR MANUFACTURER MODEL OR SERIAL NO. DESIGN 26000 1750 24250 3.8 ACTUAL 26064 1120 * 24944 -1.79" +1.99" 3.78" 1072 @ 56.8 Hz 2B5V136 B2 3/16 Browning (2) 5VX1320 48.5" (8) 20x24x2 (8) 24x20x4 (12) 20x20x2 (12) 20x20x4 VFD @ 56.8 Hz Static Set Point: 1.1" Reading @ 56.8 Hz: 1.08" (On 100% outside air, VFD increases to 60.0 Hz and system static decreases to 0.99") Min O.A.: 32x18=4.0 @ 280 fpm/1120 cfm AMD: 1100 cfm Baldor EM2539T-8 RATED MOTOR H.P. BHP OPERATING AMPERAGE, L1-L2-L3 VOLTAGE RPM MOTOR SHEAVE - SIZE, TYPE MFGR. O.L. HEATERS SF FRAME PF / EFF ACTUAL 40 30.0 107 200 1775 2B5V86 B 2 1/8 Browning VFD 1.15 34T 85.0/94.5 40.0 31.9 82.4 208 1693 @ 56.8 Hz * Differential volume set point is @ 1750 cfm. Min O.A.damper is wide open. Min relief damper which is also wide open due to tracking min O.A.damper is drawing air in due to negative pressure in plenum. REMARKS Unit Total: 1) 2) 3) 4) 38x8=2.11 36x8=2.00 52x14=5.06 60x14=5.83 @ @ @ @ 2069 1941 1644 1629 fpm/4366 fpm/3882 fpm/8319 fpm/9497 cfm cfm cfm cfm Total: 26064 cfm AMD: 26573 cfm 100% O.A.: Min O.A.: -0.64" -0.75" +0.94" -0.01" -1.48" -0.27" -1.72" -0.46" -2.10" -2.61" -0.82" -1.36" -3.14" -1.79" +1.57" +1.99" T&B Services, Ltd. Sheet 2 of 37 Date 8/3/07 By DA TERMINAL UNIT TEST REPORT PROJECT SYSTEM UW Stout-Administration Bldg. AHU-1 AREA SERVED DESIGN LOCATION VAV-1 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 10 .550 FINAL CFM 950 TEST 1 TEST K factor/ COEF. 2.287 285 VAV-2 10 .550 950 0.922 285 VAV-3 10 .550 1120 1.780 340 VAV-4 8 .350 560 2.073 170 VAV-5 4 .090 135 0.956 45 VAV-6 4 .090 75 0.770 25 VAV-7 5 .140 345 1.386 105 VAV-8 4 .090 180 0.849 55 VAV-9 4 .090 180 0.970 55 VAV-10 4 .090 1st Floor 190 60 0.933 CFM COMPUTER READING 933 941 311 280 1000 985 287 277 1109 1117 325 318 561 558 177 172 139 138 43 42 77 74 28 25 361 362 105 104 179 180 57 54 181 185 53 51 186 187 57 53 T&B Services, Ltd. Sheet 3 of 37 Date 8/3/07 By DA TERMINAL UNIT TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 AREA SERVED DESIGN LOCATION VAV-11 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 4 .090 CFM 110 FINAL TEST 1 TEST K factor/ COEF. 0.925 35 VAV-12 5 .140 240 1.197 75 VAV-13 4 .090 130 0.997 40 VAV-14 4 .090 165 0.817 50 VAV-15 4 .090 90 0.628 30 VAV-16 4 .090 110 0.821 35 VAV-17 4 .090 205 0.978 65 VAV-18 10 .550 1100 1.780 330 VAV-19 6 .200 385 2.208 120 VAV-20 4 .090 205 65 1st Floor 0.949 CFM COMPUTER READING 105 103 38 35 248 254 85 73 132 127 43 37 164 163 55 47 85 87 32 28 115 112 36 35 217 210 69 63 1110 1105 334 330 377 378 127 122 202 207 71 62 Sheet T&B Services, Ltd. 4 8/10/07 Date of 37 By DA TERMINAL UNIT TEST REPORT PROJECT SYSTEM UW Stout-Administration Bldg. AHU-1 AREA SERVED DESIGN LOCATION VAV-21 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 5 .140 CFM 235 FINAL TEST 1 TEST K factor/ COEF. 1.363 75 VAV-22 5 .140 260 1.307 80 VAV-23 4 .140 215 1.185 65 VAV-24 4 .090 200 0.949 60 VAV-25 4 .090 200 0.897 60 VAV-26 4 .090 200 1.095 60 VAV-27 4 .090 180 0.931 55 VAV-28 8 .350 560 170 1st Floor 1.870 CFM COMPUTER READING 235 236 75 73 265 263 78 74 209 212 74 63 197 196 59 59 205 200 68 62 210 206 63 57 182 181 56 52 563 562 190 173 5 Sheet T&B Services, Ltd. 8/10/07 Date of 37 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT SYSTEM LOCATION UW Stout-Administration Bldg. AHU-1 NO. SIZE 1st Floor AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-1) 101 1 350 320 347 101 2 200 191 194 101 3 200 183 200 101 4 200 165 192 101 1 350 430 361 101 2 200 248 215 101 3 200 195 209 101 4 200 192 215 103 1 280 305 270 103 2 280 241 281 103 3 280 301 285 103 4 280 295 273 103B 1 280 261 281 103B 2 280 278 280 1 135 163 139 (VAV-2) (VAV-3) (VAV-4) (VAV-5) 103C REMARKS T&B Services, Ltd. Sheet 6 of Date 8/10/07 By 37 DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. SIZE 1st Floor AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-6) 1 75 99 77 1 345 366 361 1 180 221 179 1 180 212 181 1 190 230 186 1 110 132 105 103L 1 80 115 86 103M 2 80 121 87 103N 3 80 30 81 1 130 151 132 103D (VAV-7) 103E (VAV-8) 103F (VAV-9) 103G (VAV-10) 103H (VAV-11) 103K (VAV-12) (VAV-13) 103P REMARKS T&B Services, Ltd. Sheet 7 of 37 Date 8/10/07 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT SYSTEM LOCATION UW Stout-Administration Bldg. AHU-1 NO. SIZE 1st Floor AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-14) 103S 1 55 69 54 103R 2 55 74 56 103Q 3 55 64 54 103U 1 45 64 43 103T 2 45 65 42 103W 1 70 79 75 103V 2 40 58 40 1 205 235 217 125 1 275 250 266 125 2 275 338 277 125 3 275 290 281 125 4 275 260 286 125B 1 192 170 185 125B 2 192 148 192 (VAV-15) (VAV-16) (VAV-17) 103Z (VAV-18) (VAV-19) REMARKS 8 Sheet T&B Services, Ltd. 8/10/07 Date of By 37 DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. 1st Floor AREA SERVED SIZE AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-20) 1 205 244 202 1 235 252 235 1 260 285 265 1 215 348 209 1 200 234 197 1 200 245 205 1 200 220 210 1 180 213 182 125M 1 200 181 199 125M 2 180 186 179 125M 3 180 205 185 125C (VAV-21) 125D (VAV-22) 125E (VAV-23) 125F (VAV-24) 125G (VAV-25) 125H (VAV-26) 125J (VAV-27) 125K (VAV-28) REMARKS T&B Services, Ltd. Sheet 9 of 37 Date 8/2/07 By DA TERMINAL UNIT TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 AREA SERVED DESIGN LOCATION VAV-29 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 5 .140 CFM 240 FINAL TEST 1 TEST K factor/ COEF. 1.391 75 VAV-30 5 .140 275 1.237 85 VAV-31 4 .090 85 0.718 30 VAV-32 4 .090 180 0.862 55 VAV-33 6 .200 480 1.548 145 VAV-34 6 .200 390 2.320 120 VAV-35 6 .200 390 2.062 120 VAV-36 6 .200 390 2.272 120 VAV-37 6 .200 390 2.305 120 VAV-38 6 .200 400 120 2nd Floor 1.416 CFM COMPUTER READING 237 240 77 73 287 282 89 80 90 87 36 34 186 180 56 53 493 486 155 147 387 385 116 114 381 385 118 122 392 285 112 114 382 380 117 115 406 401 124 113 T&B Services, Ltd. Sheet 10 of 37 Date 8/3/07 By DA TERMINAL UNIT TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 AREA SERVED DESIGN LOCATION VAV-39 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 5 .140 CFM 315 FINAL TEST 1 TEST K factor/ COEF. CFM COMPUTER READING 1.290 315 316 86 89 299 302 105 86 110 109 39 34 664 674 199 202 385 389 121 121 391 382 111 115 195 202 58 56 268 275 82 82 520 515 160 153 273 267 81 76 95 VAV-40 5 .140 300 1.119 90 VAV-41 4 .090 110 0.897 35 VAV-42 8 .350 680 1.870 205 VAV-43 6 .200 390 2.365 120 VAV-44 6 .200 390 2.208 120 VAV-45 4 .090 195 0.898 60 VAV-46 5 .140 275 1.208 85 VAV-47 8 .350 510 1.87 155 VAV-48 5 .140 265 80 2nd Floor 1.294 T&B Services, Ltd. Sheet 11 of 37 Date 8/3/07 By DA TERMINAL UNIT TEST REPORT PROJECT SYSTEM UW Stout-Administration Bldg. AHU-1 AREA SERVED DESIGN LOCATION VAV-49 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 4 .090 FINAL CFM 215 TEST 1 TEST K factor/ COEF. 1.054 65 VAV-50 8 .350 670 1.751 205 VAV-51 5 .140 255 1.165 80 VAV-52 8 .350 2nd Floor 510 155 1.87 CFM COMPUTER READING 225 221 70 64 688 682 198 195 257 260 79 76 519 511 146 142 T&B Services, Ltd. Sheet 12 of 37 Date 8/2/07 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. 2nd Floor AREA SERVED SIZE AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-29) 1 240 - 237 203 1 100 108 101 203 2 175 201 186 1 85 115 90 1 180 223 186 1 480 549 493 1 390 364 387 1 390 385 381 1 390 368 392 1 390 365 382 201 (VAV-30) (VAV-31) 203A (VAV-32) 203B (VAV-33) 203C (VAV-34) 203D (VAV-35) 203E (VAV-36) 203F (VAV-37) 203M REMARKS 13 Sheet T&B Services, Ltd. 8/3/07 Date of 37 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. SIZE 2nd Floor AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-38) 1 400 476 406 1 315 340 315 203J 1 220 250 214 203L 2 80 100 85 1 110 132 110 210 1 340 320 335 210 2 340 365 329 1 390 356 385 1 390 - 391 1 195 235 195 1 275 314 268 203G (VAV-39) 203H (VAV-40) (VAV-41) 203K (VAV-42) (VAV-43) 210A (VAV-44) 210B (VAV-45) 210C (VAV-46) 210D REMARKS T&B Services, Ltd. Sheet 14 of 37 Date 8/2/07 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. 2nd Floor AREA SERVED SIZE AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-47) 210E 1 255 266 266 210E 2 255 254 254 210G 1 132 153 139 210G 2 132 138 134 1 215 241 225 225 1 223 273 232 225 2 223 254 219 225 3 223 174 237 1 255 293 257 225B 1 255 - 254 225B 2 255 - 265 (VAV-48) (VAV-49) 210H (VAV-50) (VAV-51) 225A (VAV-52) REMARKS T&B Services, Ltd. Sheet 15 of Date 8/2/07 8/3/07 By 37 DA DA TERMINAL UNIT TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 AREA SERVED DESIGN LOCATION VAV-53 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 5 .140 CFM 340 FINAL TEST 1 TEST K factor/ COEF. 1.225 105 VAV-54 6 .200 370 1.970 115 VAV-55 8 .350 690 2.192 210 VAV-56 8 .350 660 1.970 200 VAV-57 6 .200 475 1.467 145 VAV-58 6 .200 475 1.875 145 VAV-59 6 .200 475 1.508 145 VAV-60 6 .200 355 2.064 110 VAV-61 6 .200 485 1.303 150 VAV-62 10 .550 1100 330 3rd Floor 1.755 CFM COMPUTER READING 313 315 116 105 369 385 119 113 700 703 222 215 657 658 197 192 489 482 151 148 482 480 157 148 487 491 135 135 349 349 114 104 496 491 154 148 1104 1091 327 320 T&B Services, Ltd. Sheet 16 of 37 Date 8/3/07 By DA TERMINAL UNIT TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 AREA SERVED DESIGN LOCATION VAV-63 DESIGN ACTUAL INLET SIZE SIZE VEL PRESS 10 .550 FINAL CFM 910 TEST 1 TEST K factor/ COEF. 1.970 275 VAV-64 5 .140 315 1.388 95 VAV-65 4 .090 200 0.969 60 VAV-66 10 .550 1200 1.875 360 VAV-67 4 .080 3rd Floor 175 55 0.820 CFM COMPUTER READING 903 887 250 255 317 314 92 90 203 202 62 56 1211 1206 377 368 185 183 56 52 17 Sheet T&B Services, Ltd. 8/3/07 Date of 37 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. SIZE 3rd Floor AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-53) 301 1 170 159 159 301 2 170 154 154 303A 1 185 195 195 303B 2 185 174 174 303C 1 345 293 352 303C 2 345 346 348 303D 1 330 375 330 303D 2 330 411 327 1 475 420 489 1 475 490 482 1 475 541 487 1 355 - 349 (VAV-54) (VAV-55) (VAV-56) (VAV-57) 303E (VAV-58) 303F (VAV-59) 303G (VAV-60) 303H REMARKS 18 Sheet T&B Services, Ltd. 8/3/07 Date of 37 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. 3rd Floor AREA SERVED SIZE AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-61) 303L 1 255 288 259 303K 2 230 257 237 325 1 275 281 279 325 2 275 275 280 325 3 275 241 265 325 4 275 314 280 325A 1 455 464 453 325A 2 455 398 450 1 315 344 317 1 200 234 203 3256G 1 300 327 301 325G 2 300 302 298 325G 3 300 268 299 325G 4 300 318 313 (VAV-62) (VAV-63) (VAV-64) 325C (VAV-65) 325E (VAV-66) REMARKS T&B Services, Ltd. Sheet 19 of Date 8/3/07 By 37 DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 LOCATION NO. SIZE 3rd Floor AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (VAV-67) 325H 1 175 217 185 REMARKS Sheet T&B Services, Ltd. 20 of By 8/31/07 11/14/07 Date FAN EQUIPMENT TEST REPORT PROJECT SYSTEM UW Stout-Administration Bldg. AHU-1 (Return) FAN MANUFACTURER MODEL OR SERIAL NO. EQUIPMENT LOCATION McQuay CAH053 GDDM TOTAL CFM MIN O.A. RETURN CFM FAN SUCTION PRESSURE (TP) FAN DISCHARGE PRESSURE (SP) FAN STATIC PRESSURE FAN RPM FAN PULLY - SIZE, TYPE MFGR. BELT QUANTITY / SIZE C-C FILTER SIZE & QUANTITY MTR MANUFACTURER MODEL OR SERIAL NO. AHU-1 DESIGN 24250 - ACTUAL 22965 -0.64" +0.94" 1.58" 685 2B5V136 B1 15/16 Browning (2) BX123 47.5 - Baldor EM25133-8 RATED MOTOR H.P. BHP OPERATING AMPERAGE, L1-L2-L3 VOLTAGE RPM MOTOR SHEAVE - SIZE, TYPE MFGR. O.L. HEATERS SF FRAME PF / EFF REMARKS Unit Total: 60x36=15.0 @ 1531 fpm/22965 cfm AMD: 23150 cfm 15.0 11.6 40.7 200 1765 2B5V52 B1 5/8 Browning VFD 1.15 254T 85/93 ACTUAL 15.0 13.4 35.0 208 1773 VFD @ 60 Hz 37 DA DA T&B Services, Ltd. Sheet 21 of 37 Date 8/31/07 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-1 (Return) LOCATION NO. 1st Floor 1 SIZE DESIGN VEL CFM FINAL TEST TEST TEST 1 VEL CFM 1453/15983 1453 15983 REMARKS * 44x36 * AK AREA SERVED 9475 11.0 1507 2nd Floor 2 8300 3rd Floor 3 8225 ** 6982 Design grille total adds up to 26240 cfm. Design supply minus design outside air = 24250 cfm. Proportioned air to available flow. ** No way to accurately read individual flows for 1st and 2nd floors 22 Sheet T&B Services, Ltd. of By 8/31/07 11/7/07 Date 37 DA DA FAN EQUIPMENT TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-2 FAN MANUFACTURER MODEL OR SERIAL NO. EQUIPMENT LOCATION McQuay CAH012 GDAC TOTAL CFM MIN O.A. RETURN CFM FAN SUCTION PRESSURE (TP) FAN DISCHARGE PRESSURE (SP) FAN STATIC PRESSURE FAN RPM FAN PULLY - SIZE, TYPE MFGR. BELT QUANTITY / SIZE C-C FILTER SIZE & QUANTITY MTR MANUFACTURER MODEL OR SERIAL NO. Basement Mech. DESIGN 6860 660 6200 ACTUAL 6914 668 6246 -2.01" +0.65" 2.66" 978 B1 15/16 2.0 2B5V90 w/ Browning (2) B46 13.25 (3) 12x24x2 (3) 12x24x12 (2) 24x24x2 (2) 24x24x12 Baldor EM3311T-8 RATED MOTOR H.P. BHP OPERATING AMPERAGE, L1-L2-L3 VOLTAGE RPM MOTOR SHEAVE - SIZE, TYPE MFGR. O.L. HEATERS SF FRAME PF / EFF ACTUAL 5.0 3.6 22.3 15.5 200 1770 2BK55H w/ H 1 3/8 Browning B28.0 1.15 213T 79.0/91.7 7.5 5.72 16.8 208 1772 16.8 REMARKS Min O.A. OA: 45.0˚F RA: 75.0˚F MA: 72.1˚F = 9.67% -0.76" -1.33" -1.70" -2.01" +0.65" 23 Sheet T&B Services, Ltd. of By 8/31/07 11/14/07 Date 37 DA DA DIFFUSER AND GRILLE TEST REPORT PROJECT SYSTEM LOCATION UW Stout-Administration Bldg. AHU-2 NO. SIZE AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (HC-101) 1 225 168 203 2 225 182 205 3 225 195 206 4 225 222 211 5 225 212 221 1 160 193 170 2 160 183 175 1 200 235 212 1 245 270 243 1 125 161 130 2 125 161 125 1 145 238 155 1 145 109 156 (HC-102) (HC-103) (HC-104) (HC-105) (HC-106) (HC-107) REMARKS 24 Sheet T&B Services, Ltd. of By 8/31/07 11/14/07 Date 37 DA DA DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-2 LOCATION NO. AREA SERVED SIZE AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (HC-108) 1 150 166 165 2 150 186 161 1 150 204 150 2 150 170 153 9 1 225 237 235 9 2 225 241 237 9 3 225 230 237 9 4 225 212 237 9 5 225 207 244 9 6 225 246 246 9 7 225 214 238 9 8 225 217 237 7 1 120 148 126 6A 2 200 272 212 (HC-109) (HC-110) (HC-112) REMARKS 25 of 37 By 8/31/07 11/14/07 DA DA Sheet T&B Services, Ltd. Date DIFFUSER AND GRILLE TEST REPORT PROJECT UW Stout-Administration Bldg. SYSTEM AHU-2 LOCATION NO. SIZE AREA SERVED AK DESIGN VEL CFM TEST TEST TEST 1 FINAL VEL CFM (HC-113) 1 200 203 214 2 200 238 217 1 300 239 315 2 300 286 330 1 1 155 171 164 1 2 155 175 170 15 3 200 104 214 (HC-114) (HC-118) REMARKS T&B Services, Ltd. Sheet 26 of Date 8/10/07 By EXHAUST FAN TEST REPORT PROJECT UW Stout-Administration Bldg. EXH. FAN NO. OR LOCATION MANUFACTURER TYPE OR SIZE FAN CFM TOTAL STATIC PRESS. FAN RPM AMPS DB-16 1500 ACTUAL 904 DESIGN - ACTUAL -0.31"/+0.19" DESIGN - ACTUAL 1410 (1) 4L38 DESIGN - ACTUAL 1/4 DESIGN 4.4 ACTUAL 4.3 DESIGN 115 ACTUAL 121 DESIGN 1725 ACTUAL 1731 MOTOR 1VL34 x 1/2 FAN Inacc. VOLTAGE MOTOR RPM Trane DESIGN BELTS MOTOR HP Existing EF-1 SHEAVE 37 DA T&B Services, Ltd. Sheet 27 of 37 Date 8/10/07 By DA DIFFUSER AND GRILLE TEST REPORT PROJECT SYSTEM UW Stout-Administration Bldg. Existing EF-1 SIZE AK Restrooms AREA SERVED DESIGN TEST TEST TEST 1 FINAL LOCATION NO. 312A 1 210 199 89 313A 2 210 137 88 325B 3 75 36 37 212 4 210 57 88 213 5 210 65 91 215 6 - 27 48 103Y 7 75 28 49 12A 8 330 69 114 13 9 330 100 123 VEL CFM VEL CFM REMARKS Unit Total: 24x6=1.0 904 fpm/ 904 cfm Face Dampers Only No damper T&B Services, Ltd. Sheet 28 of 37 Date 8/2/07 By DA CIRCULATING WATER PUMP TEST REPORT PROJECT SYSTEM UW Stout-Administration Bldg. PUMP LOCATION OR NUMBER Existing Hot Water Pump Bell & Gossett 2AB 5 3/8 BF PUMP MANUFACTURER MODEL OR SERIAL NO. 1531 ACTUAL DESIGN PUMP GPM PUMP RPM DISCHARGE PRESSURE (Ft. H20) SUCTION PRESSURE (Ft. H20) TOTAL HEAD (F T. H 2 0) * 70 No Flow Full Flow No Flow Full Flow No Flow Full Flow 18-P5 70 1771 118.0 ft 100.0 ft 85.8 ft 73.8 ft 32.2 ft 26.2 ft 25 * TOTAL HEAD (FT H 2 0) = PUMP DIFFERENTIAL x 2.307 (If differential is in psig) MOTOR MANUFACTURER MODEL OR SERIAL NUMBER Bell & Gossett Ser: 110-8-LH RATED MOTOR HP BHP OPERATING AMPERAGE, L1-L2-L3 VOLTAGE RPM O.L.HEATERS REMARKS: ACTUAL 1 1/2 4.4-4.0/2.0 208-220/440 1750 - 3.1 2.9 208 1771 2.9 T&B Services, Ltd. Sheet 29 of 37 Date 7/11/07 By DA/JA FLOW INDICATOR DATA SHEET UW Stout-Administration Bldg. PROJECT SYSTEM Hot Water UNIT SERVED AREA SERVED INDICATOR SIZE FINAL DESIGN INDICATOR READING Basement METER READING GPM INDICATOR READING GPM IN. WATER FT. WATER HC-101 3/4S B&G 2.5 0 1.67 0.55 HC-102 3/4S B&G 0.9 44 0.87 3.6 HC-103 3/4S B&G 2.1 16 2.0 1.75 HC-104 3/4S B&G 0.8 50 0.79 5.63 HC-105 3/4S B&G 0.7 50 0.82 6.1 HC-106 3/4S B&G 0.3 50 0.82 6.05 HC-107 3/4S B&G 0.3 50 0.90 7.2 HC-108 3/4S B&G 0.6 50 0.89 7.0 HC-109 3/4S B&G 0.6 50 1.0 9.0 HC-110 3/4S B&G 4.6 0 2.4 1.11 HC-112 3/4S B&G 1.0 50 0.95 8.02 HC-113 3/4S B&G 1.6 36 1.57 5.4 HC-114 3/4S B&G 1.8 24 1.78 2.5 HC-118 3/4S B&G 1.5 0 1.48 0.43 REMARKS: T&B Services, Ltd. Sheet 30 of 37 Date 7/11/07 By DA/JA FLOW INDICATOR DATA SHEET PROJECT SYSTEM UW Stout-Administration Bldg. Hot Water UNIT SERVED INDICATOR SIZE DC-2 AREA SERVED FINAL DESIGN 1st Floor METER READING INDICATOR READING GPM INDICATOR READING GPM IN. WATER 3/4 Taco 9.0 1.8 0 1.3 4.7 DC-28 1/2 Taco 1.42 0.4 40 0.37 1.2 DC-27 1/2 Taco 3.2 0.6 30 0.57 2.9 DC-26 1/2 Taco 3.2 0.6 35 0.60 3.2 DC-25 1/2 Taco 3.2 0.6 25 0.57 2.9 DC-24 1/2 Taco 3.2 0.6 15 0.59 3.1 DC-23 1/2 Taco 4.4 0.7 0 0.66 3.8 DC-22 1/2 Taco 3.2 0.6 0 0.59 3.1 DC-21 1/2 Taco 3.2 0.6 0 0.58 3.0 DC-18 1/2 Taco 4.4 0.7 15 0.69 4.3 DC-19 1/2 Taco 0.8 0.3 45 0.30 0.8 * DC-20 1/2 Taco 0.36 0.2 55 0.24 0.5 * DC-14 1/2 Taco 0.36 0.2 45 0.24 0.5 * DC-15 1/2 Taco 0.09 0.1 57 0.24 0.5 * DC-16 1/2 Taco 0.09 0.1 40 0.18 0.3 FT. WATER * REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable T&B Services, Ltd. Sheet 31 of 37 Date 7/11/07 By DA/JA FLOW INDICATOR DATA SHEET PROJECT UW Stout-Administration Bldg. SYSTEM Hot Water UNIT SERVED INDICATOR SIZE DC-13 AREA SERVED FINAL DESIGN 1st Floor METER READING INDICATOR READING GPM INDICATOR READING GPM 1/2 Taco 1.42 0.4 35 0.38 1.25 DC-12 1/2 Taco 3.2 0.6 12 0.57 2.9 DC-11 1/2 Taco 0.8 0.3 35 0.30 0.8 DC-10 1/2 Taco 4.4 0.7 15 0.65 3.8 DC-9 1/2 Taco 3.2 0.6 20 0.58 3.0 DC-8 1/2 Taco 3.2 0.6 20 0.60 3.2 DC-3 1/2 Taco 5.64 0.8 0 0.78 5.3 DC-7 1/2 Taco 4.4 0.7 20 0.70 4.4 DC-5 1/2 Taco 0.09 0.1 45 0.24 0.5 * DC-6 1/2 Taco 0.09 0.1 45 0.27 0.6 DC-4 1/2 Taco 10.76 1.1 0 0.98 8.5 DC-1 3/4 Taco 9.0 1.8 0 1.26 4.4 DC-17 1/2 Taco 0.36 0.2 48 0.21 0.4 IN. WATER FT. WATER * * REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable T&B Services, Ltd. Sheet 32 of 37 Date 7/11/07 By DA FLOW INDICATOR DATA SHEET PROJECT UW Stout-Administration Bldg. SYSTEM Hot Water 2nd Floor UNIT SERVED INDICATOR SIZE 225A AREA SERVED 1st Floor Serving 2nd FINAL DESIGN METER READING INDICATOR READING GPM INDICATOR READING GPM IN. WATER 1/2 Taco 1.15 0.36 52 0.37 1.2 225B 1/2 Taco 2.05 0.48 45 0.47 2.0 210A 1/2 Taco 2.05 0.48 45 0.49 2.1 210B 1/2 Taco 2.05 0.48 35 0.47 2.0 210E 1/2 Taco 2.05 0.48 35 0.47 2.0 210D 1/2 Taco 2.05 0.48 30 0.49 2.1 203G 1/2 Taco 6.27 0.84 10 0.83 6.1 203F 1/2 Taco 2.05 0.48 30 0.47 2.0 203E 1/2 Taco 2.05 0.48 35 0.47 2.0 203M 1/2 Taco 2.05 0.48 38 0.47 2.0 203D 1/2 Taco 2.05 0.48 37 0.47 2.0 203C 1/2 Taco 2.05 0.48 40 0.47 2.0 REMARKS: FT. WATER T&B Services, Ltd. Sheet 33 of Date 8/1/07 By 37 DA FLOW INDICATOR DATA SHEET UW Stout-Administration Bldg. PROJECT SYSTEM Hot Water UNIT SERVED AREA SERVED INDICATOR SIZE FINAL DESIGN INDICATOR READING GPM 2nd Floor METER READING INDICATOR READING GPM IN. WATER DC-51 1/2 Taco 2.22 0.5 33 0.49 2.1 DC-52 1/2 Taco 2.22 0.5 32 0.51 2.3 DC-50 1/2 Taco 3.2 0.6 15 0.59 3.1 DC-43 1/2 Taco 1.42 0.4 40 0.37 1.2 DC-44 1/2 Taco 1.42 0.4 37 0.37 1.2 DC-47 1/2 Taco 2.22 0.5 23 0.50 2.2 DC-46 1/2 Taco 2.22 0.5 0 0.47 2.0 DC-45 1/2 Taco 1.42 0.4 30 0.38 1.3 DC-48 1/2 Taco 0.36 0.2 33 0.24 0.5 DC-49 1/2 Taco 0.36 0.2 40 0.21 0.4 DC-42 1/2 Taco 1.42 0.4 36 0.37 1.2 DC-39 1/2 Taco 0.36 0.2 35 0.24 0.5 DC-38 1/2 Taco 1.42 0.4 0 0.37 1.2 FT. WATER * * * REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable T&B Services, Ltd. Sheet 34 of 37 Date 8/1/07 By DA FLOW INDICATOR DATA SHEET PROJECT UW Stout-Administration Bldg. SYSTEM Hot Water UNIT SERVED INDICATOR SIZE AREA SERVED FINAL DESIGN INDICATOR READING GPM INDICATOR READING 2nd Floor METER READING GPM IN. WATER DC-40 1/2 Taco 0.36 0.2 25 0.21 0.4 DC-36 1/2 Taco 1.42 0.4 32 0.37 1.2 DC-41 1/2 Taco 0.09 0.1 0 0.24 0.5 DC-35 1/2 Taco 1.42 0.4 33 0.37 1.2 DC-37 1/2 Taco 1.42 0.4 25 0.38 1.3 DC-30 1/2 Taco 0.36 0.2 42 0.24 0.5 DC-34 1/2 Taco 1.42 0.4 30 0.37 1.2 DC-33 1/2 Taco 2.22 0.5 22 0.50 2.2 DC-31 1/2 Taco 0.09 0.1 40 0.24 0.5 DC-32 1/2 Taco 0.36 0.2 45 0.26 0.6 DC-29 1/2 Taco 0.36 0.2 60 0.24 0.5 FT. WATER * * * * * * REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable 35 Sheet T&B Services, Ltd. Date 8/1/07 of 37 By DA FLOW INDICATOR DATA SHEET PROJECT UW Stout-Administration Bldg. SYSTEM Hot Water AREA SERVED FINAL DESIGN UNIT SERVED INDICATOR SIZE 325C 1/2 Taco 1.15 325 1/2 Taco 325A INDICATOR READING 2nd Floor serving 3rd METER READING INDICATOR READING GPM IN. WATER 0.36 38 0.37 1.2 2.05 0.48 35 0.49 2.1 1/2 Taco 8.19 0.96 15 0.94 7.9 325G 1/2 Taco 8.19 0.96 0 0.95 8.1 303H 1/2 Taco 2.05 0.48 32 0.47 2.0 303G 1/2 Taco 1.15 0.36 40 0.35 1.1 303F 1/2 Taco 3.2 0.60 38 0.61 3.3 303E 1/2 Taco 0.51 0.24 60 0.28 0.7 303D 1/2 Taco 2.05 0.48 30 0.49 2.1 303C 1/2 Taco 2.05 0.48 33 0.47 2.0 GPM FT. WATER * REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable T&B Services, Ltd. Sheet 36 of 37 Date 8/1/07 By DA FLOW INDICATOR DATA SHEET UW Stout-Administration Bldg. PROJECT Hot Water SYSTEM UNIT SERVED INDICATOR SIZE AREA SERVED FINAL DESIGN INDICATOR READING GPM INDICATOR READING 3rd Floor METER READING GPM IN. WATER DC-64 1/2" Taco 3.2 0.6 50 0.56 2.8 DC-62 1/2" Taco 7.2 0.9 35 0.89 7.0 DC-65 1/2" Taco 0.36 0.2 53 0.24 0.5 DC-63 1/2" Taco 7.2 0.9 32 0.87 6.7 DC-66 1/2" Taco 22.76 1.6 0 1.53 20.9 DC-67 1/2" Taco 0.09 0.1 55 0.21 0.4 DC-60 1/2" Taco 1.42 0.4 60 0.37 1.2 DC-59 1/2" Taco 2.22 0.5 55 0.52 2.4 DC-61 1/2" Taco 1.42 0.4 60 0.37 1.2 DC-58 1/2" Taco 2.22 0.5 60 0.50 2.2 DC-57 1/2" Taco 2.22 0.5 52 0.51 2.3 DC-54 1/2" Taco 0.8 0.3 53 0.30 0.8 DC-53 1/2" Taco 2.22 0.5 50 0.49 2.1 DC-55 1/2" Taco 7.2 0.9 35 0.92 7.6 DC-56 1/2" Taco 3.2 0.6 47 0.57 2.9 FT. WATER * * * REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable T&B Services, Ltd. Sheet 37 of Date 9/19/07 By 37 DA FLOW INDICATOR DATA SHEET PROJECT SYSTEM UW Stout-Administration Bldg. Chilled Water UNIT SERVED INDICATOR SIZE AREA SERVED FINAL DESIGN INDICATOR READING GPM INDICATOR READING METER READING GPM 0.9 AHU-1 / Top 4" Taco 0.96 54.75 0 AHU-1 / Bottom 4" Taco 0.96 54.75 0 55.8 1.0 AHU-2 2" Taco 8.0 26.0 45 26.2 8.1 REMARKS: * Main Bldg FMD: 117 gpm 53.0m 53.0 , IN. WATER FT. WATER
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Page Count : 39 XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:d3beefbe-9893-11dc-b954-000a95cfc0d2 Modify Date : 2007:11:21 18:42:39-06:00 Create Date : 2007:11:21 18:29:11-06:00 Metadata Date : 2007:11:21 18:42:39-06:00 Document ID : uuid:a1d902c0-9891-11dc-9aa4-000a95cfc0d2 Format : application/pdf Creator : MacDraw I: LaserWriter 8 8.7.3 Producer : Acrobat Distiller 6.0 for MacintoshEXIF Metadata provided by EXIF.tools