BALANCE REPORT
DSF#: 06A3T

PROJECT:

ADMINISTRATION BLDG. HVAC/CEILING REPLACEMENT
UNIVERSITY OF WISCONSIN-STOUT
MENOMONIE, WISCONSIN

ARCHITECT:
ENGINEER:
CONTRACTOR:

LIEN & PETERSON ARCHITECTS, INC.
EAU CLAIRE, WISCONSIN
APEX ENGINEERING
EAU CLAIRE, WISCONSIN
CERTIFIED, INC.
ALTOONA, WISCONSIN

CERTIFICATION OF REPORT
THIS IS TO CERTIFY THAT THE ATTACHED REPORT IS A TRUE AND ACCURATE
REPRESENTATION OF THE FINAL OPERATING CONDITIONS OF EQUIPMENT AND AIR
DISTRIBUTION SYSTEMS, IN ACCORDANCE WITH PLANS DATED
11-15-06

BY:
DATE:

Douglas J. Hermans, P.E.
November 15, 2007

T&B Services, Ltd.
110B E. Grand Ave. Eau Claire, WI 54701
Eau Claire: (715) 835-7813
Madison:
(608) 251-2461
FAX:
(715) 723-4529
Email: tbservicesltd@charter.net

•Testing & Balancing
•System Analysis
•Air • Hydronics
•Sound • Vibration

Administration Building HVAC/Ceiling Replacement
UW Stout
Menomonie, Wisconsin
DSF #: 06A3T
Summary
Design

Actual

AHU-1:

26,000 cfm

26,064 cfm

RF-1:

24,250 cfm

22,965 cfm

EF-1:

1,500 cfm

904 cfm

CW Coil AHU-1:

54.75 gpm

53.0 gpm

54.75 gpm

55.8 gpm

26.0 gpm

26.2 gpm

CW Coil AHU-2:

Difiencencies
AHU-1:

System incorporates a separate minimum outside air and minimum relief opening/damper.
The supply fan is being controlled off of system static with the return fan tracking off of a
differential flow set point. The minimum outside air damper is controlled to open and close
to maintain a minimum outside air set point. The relief damper is currently set up to track
the minimum outside damper and with the system at minimum outside air, the outside
air damper is being driven to 100% open but is short on air. This is being caused by the
fact that when at minimum outside air the discharge of the retrun fan is under a negative
pressure and air is being drawn in from the minimum relief opening/damper. Total outside
will be at design (differential flow set point) but the minimum outside air AMD will be reading
a flow that is short on air.

EF-1:

Fan is existing and is currently at 60% of design with the motor fully loaded.

1

Sheet

T&B Services, Ltd.

37

of

By
8/3/07
11/14/07

Date

DA
DA

FAN EQUIPMENT TEST REPORT

PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

3rd Floor Mech.

EQUIPMENT LOCATION

FAN MANUFACTURER
MODEL OR SERIAL NO.

McQuay
CAH053GDDM

TOTAL CFM
MIN O.A.
RETURN CFM
FAN SUCTION PRESSURE (TP)
FAN DISCHARGE PRESSURE (SP)
FAN STATIC PRESSURE
FAN RPM
FAN PULLY - SIZE, TYPE
MFGR.
BELT QUANTITY / SIZE
C-C
FILTER SIZE & QUANTITY
MTR MANUFACTURER
MODEL OR SERIAL NO.

DESIGN
26000
1750
24250

3.8

ACTUAL
26064
1120 *
24944
-1.79"
+1.99"
3.78"
1072 @ 56.8 Hz

2B5V136 B2 3/16
Browning
(2) 5VX1320
48.5"
(8) 20x24x2 (8) 24x20x4
(12) 20x20x2 (12) 20x20x4

VFD @ 56.8 Hz
Static Set Point: 1.1"
Reading @ 56.8 Hz: 1.08"
(On 100% outside air, VFD
increases to 60.0 Hz and
system static decreases
to 0.99")
Min O.A.:
32x18=4.0
@ 280 fpm/1120 cfm
AMD: 1100 cfm

Baldor
EM2539T-8
RATED

MOTOR H.P.
BHP
OPERATING AMPERAGE, L1-L2-L3
VOLTAGE
RPM
MOTOR SHEAVE - SIZE, TYPE
MFGR.
O.L. HEATERS
SF
FRAME
PF / EFF

ACTUAL

40
30.0
107
200
1775
2B5V86 B 2 1/8
Browning
VFD
1.15
34T
85.0/94.5

40.0
31.9
82.4
208
1693 @ 56.8 Hz

* Differential
volume set point
is @ 1750 cfm.
Min O.A.damper is
wide open. Min
relief damper which
is also wide open
due to tracking min
O.A.damper is
drawing air in due
to negative
pressure in plenum.

REMARKS
Unit Total:
1)
2)
3)
4)

38x8=2.11
36x8=2.00
52x14=5.06
60x14=5.83

@
@
@
@

2069
1941
1644
1629

fpm/4366
fpm/3882
fpm/8319
fpm/9497

cfm
cfm
cfm
cfm

Total: 26064 cfm
AMD:
26573 cfm
100% O.A.:
Min O.A.:

-0.64"
-0.75"

+0.94"
-0.01"

-1.48"
-0.27"

-1.72"
-0.46"

-2.10" -2.61"
-0.82" -1.36"

-3.14"
-1.79"

+1.57"
+1.99"

T&B Services, Ltd.

Sheet

2

of

37

Date

8/3/07

By

DA

TERMINAL UNIT TEST REPORT
PROJECT
SYSTEM

UW Stout-Administration Bldg.
AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-1

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

10

.550

FINAL

CFM

950

TEST
1

TEST

K
factor/
COEF.

2.287

285
VAV-2

10

.550

950

0.922

285
VAV-3

10

.550

1120

1.780

340
VAV-4

8

.350

560

2.073

170
VAV-5

4

.090

135

0.956

45
VAV-6

4

.090

75

0.770

25
VAV-7

5

.140

345

1.386

105
VAV-8

4

.090

180

0.849

55
VAV-9

4

.090

180

0.970

55
VAV-10

4

.090

1st Floor

190
60

0.933

CFM

COMPUTER
READING

933

941

311

280

1000

985

287

277

1109

1117

325

318

561

558

177

172

139

138

43

42

77

74

28

25

361

362

105

104

179

180

57

54

181

185

53

51

186

187

57

53

T&B Services, Ltd.

Sheet

3

of

37

Date

8/3/07

By

DA

TERMINAL UNIT TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-11

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

4

.090

CFM

110

FINAL
TEST
1

TEST

K
factor/
COEF.

0.925

35
VAV-12

5

.140

240

1.197

75
VAV-13

4

.090

130

0.997

40
VAV-14

4

.090

165

0.817

50
VAV-15

4

.090

90

0.628

30
VAV-16

4

.090

110

0.821

35
VAV-17

4

.090

205

0.978

65
VAV-18

10

.550

1100

1.780

330
VAV-19

6

.200

385

2.208

120
VAV-20

4

.090

205
65

1st Floor

0.949

CFM

COMPUTER
READING

105

103

38

35

248

254

85

73

132

127

43

37

164

163

55

47

85

87

32

28

115

112

36

35

217

210

69

63

1110

1105

334

330

377

378

127

122

202

207

71

62

Sheet

T&B Services, Ltd.

4
8/10/07

Date

of

37

By

DA

TERMINAL UNIT TEST REPORT
PROJECT
SYSTEM

UW Stout-Administration Bldg.
AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-21

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

5

.140

CFM

235

FINAL
TEST
1

TEST

K
factor/
COEF.

1.363

75
VAV-22

5

.140

260

1.307

80
VAV-23

4

.140

215

1.185

65
VAV-24

4

.090

200

0.949

60
VAV-25

4

.090

200

0.897

60
VAV-26

4

.090

200

1.095

60
VAV-27

4

.090

180

0.931

55
VAV-28

8

.350

560
170

1st Floor

1.870

CFM

COMPUTER
READING

235

236

75

73

265

263

78

74

209

212

74

63

197

196

59

59

205

200

68

62

210

206

63

57

182

181

56

52

563

562

190

173

5

Sheet

T&B Services, Ltd.

8/10/07

Date

of

37

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

SYSTEM

LOCATION

UW Stout-Administration Bldg.

AHU-1

NO.

SIZE

1st Floor

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-1)
101

1

350

320

347

101

2

200

191

194

101

3

200

183

200

101

4

200

165

192

101

1

350

430

361

101

2

200

248

215

101

3

200

195

209

101

4

200

192

215

103

1

280

305

270

103

2

280

241

281

103

3

280

301

285

103

4

280

295

273

103B

1

280

261

281

103B

2

280

278

280

1

135

163

139

(VAV-2)

(VAV-3)

(VAV-4)

(VAV-5)
103C

REMARKS

T&B Services, Ltd.

Sheet

6

of

Date

8/10/07

By

37
DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

SIZE

1st Floor

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-6)
1

75

99

77

1

345

366

361

1

180

221

179

1

180

212

181

1

190

230

186

1

110

132

105

103L

1

80

115

86

103M

2

80

121

87

103N

3

80

30

81

1

130

151

132

103D
(VAV-7)
103E
(VAV-8)
103F
(VAV-9)
103G
(VAV-10)
103H
(VAV-11)
103K
(VAV-12)

(VAV-13)
103P

REMARKS

T&B Services, Ltd.

Sheet

7

of

37

Date

8/10/07

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

SYSTEM

LOCATION

UW Stout-Administration Bldg.

AHU-1

NO.

SIZE

1st Floor

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-14)
103S

1

55

69

54

103R

2

55

74

56

103Q

3

55

64

54

103U

1

45

64

43

103T

2

45

65

42

103W

1

70

79

75

103V

2

40

58

40

1

205

235

217

125

1

275

250

266

125

2

275

338

277

125

3

275

290

281

125

4

275

260

286

125B

1

192

170

185

125B

2

192

148

192

(VAV-15)

(VAV-16)

(VAV-17)
103Z
(VAV-18)

(VAV-19)

REMARKS

8

Sheet

T&B Services, Ltd.

8/10/07

Date

of
By

37
DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

1st Floor

AREA SERVED

SIZE

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-20)
1

205

244

202

1

235

252

235

1

260

285

265

1

215

348

209

1

200

234

197

1

200

245

205

1

200

220

210

1

180

213

182

125M

1

200

181

199

125M

2

180

186

179

125M

3

180

205

185

125C
(VAV-21)
125D
(VAV-22)
125E
(VAV-23)
125F
(VAV-24)
125G
(VAV-25)
125H
(VAV-26)
125J
(VAV-27)
125K
(VAV-28)

REMARKS

T&B Services, Ltd.

Sheet

9

of

37

Date

8/2/07

By

DA

TERMINAL UNIT TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-29

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

5

.140

CFM

240

FINAL
TEST
1

TEST

K
factor/
COEF.

1.391

75
VAV-30

5

.140

275

1.237

85
VAV-31

4

.090

85

0.718

30
VAV-32

4

.090

180

0.862

55
VAV-33

6

.200

480

1.548

145
VAV-34

6

.200

390

2.320

120
VAV-35

6

.200

390

2.062

120
VAV-36

6

.200

390

2.272

120
VAV-37

6

.200

390

2.305

120
VAV-38

6

.200

400
120

2nd Floor

1.416

CFM

COMPUTER
READING

237

240

77

73

287

282

89

80

90

87

36

34

186

180

56

53

493

486

155

147

387

385

116

114

381

385

118

122

392

285

112

114

382

380

117

115

406

401

124

113

T&B Services, Ltd.

Sheet

10

of

37

Date

8/3/07

By

DA

TERMINAL UNIT TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-39

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

5

.140

CFM

315

FINAL
TEST
1

TEST

K
factor/
COEF.

CFM

COMPUTER
READING

1.290

315

316

86

89

299

302

105

86

110

109

39

34

664

674

199

202

385

389

121

121

391

382

111

115

195

202

58

56

268

275

82

82

520

515

160

153

273

267

81

76

95
VAV-40

5

.140

300

1.119

90
VAV-41

4

.090

110

0.897

35
VAV-42

8

.350

680

1.870

205
VAV-43

6

.200

390

2.365

120
VAV-44

6

.200

390

2.208

120
VAV-45

4

.090

195

0.898

60
VAV-46

5

.140

275

1.208

85
VAV-47

8

.350

510

1.87

155
VAV-48

5

.140

265
80

2nd Floor

1.294

T&B Services, Ltd.

Sheet

11

of

37

Date

8/3/07

By

DA

TERMINAL UNIT TEST REPORT
PROJECT
SYSTEM

UW Stout-Administration Bldg.
AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-49

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

4

.090

FINAL

CFM

215

TEST
1

TEST

K
factor/
COEF.

1.054

65
VAV-50

8

.350

670

1.751

205
VAV-51

5

.140

255

1.165

80
VAV-52

8

.350

2nd Floor

510
155

1.87

CFM

COMPUTER
READING

225

221

70

64

688

682

198

195

257

260

79

76

519

511

146

142

T&B Services, Ltd.

Sheet

12

of

37

Date

8/2/07

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

2nd Floor

AREA SERVED

SIZE

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-29)
1

240

-

237

203

1

100

108

101

203

2

175

201

186

1

85

115

90

1

180

223

186

1

480

549

493

1

390

364

387

1

390

385

381

1

390

368

392

1

390

365

382

201
(VAV-30)

(VAV-31)
203A
(VAV-32)
203B
(VAV-33)
203C
(VAV-34)
203D
(VAV-35)
203E
(VAV-36)
203F
(VAV-37)
203M

REMARKS

13

Sheet

T&B Services, Ltd.

8/3/07

Date

of

37

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

SIZE

2nd Floor

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-38)
1

400

476

406

1

315

340

315

203J

1

220

250

214

203L

2

80

100

85

1

110

132

110

210

1

340

320

335

210

2

340

365

329

1

390

356

385

1

390

-

391

1

195

235

195

1

275

314

268

203G
(VAV-39)
203H
(VAV-40)

(VAV-41)
203K
(VAV-42)

(VAV-43)
210A
(VAV-44)
210B
(VAV-45)
210C
(VAV-46)
210D

REMARKS

T&B Services, Ltd.

Sheet

14

of

37

Date

8/2/07

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

2nd Floor

AREA SERVED

SIZE

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-47)
210E

1

255

266

266

210E

2

255

254

254

210G

1

132

153

139

210G

2

132

138

134

1

215

241

225

225

1

223

273

232

225

2

223

254

219

225

3

223

174

237

1

255

293

257

225B

1

255

-

254

225B

2

255

-

265

(VAV-48)

(VAV-49)
210H
(VAV-50)

(VAV-51)
225A
(VAV-52)

REMARKS

T&B Services, Ltd.

Sheet

15

of

Date

8/2/07
8/3/07

By

37
DA
DA

TERMINAL UNIT TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-53

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

5

.140

CFM

340

FINAL
TEST
1

TEST

K
factor/
COEF.

1.225

105
VAV-54

6

.200

370

1.970

115
VAV-55

8

.350

690

2.192

210
VAV-56

8

.350

660

1.970

200
VAV-57

6

.200

475

1.467

145
VAV-58

6

.200

475

1.875

145
VAV-59

6

.200

475

1.508

145
VAV-60

6

.200

355

2.064

110
VAV-61

6

.200

485

1.303

150
VAV-62

10

.550

1100
330

3rd Floor

1.755

CFM

COMPUTER
READING

313

315

116

105

369

385

119

113

700

703

222

215

657

658

197

192

489

482

151

148

482

480

157

148

487

491

135

135

349

349

114

104

496

491

154

148

1104

1091

327

320

T&B Services, Ltd.

Sheet

16

of

37

Date

8/3/07

By

DA

TERMINAL UNIT TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

AREA SERVED
DESIGN

LOCATION
VAV-63

DESIGN ACTUAL
INLET
SIZE
SIZE
VEL PRESS

10

.550

FINAL

CFM

910

TEST
1

TEST

K
factor/
COEF.

1.970

275
VAV-64

5

.140

315

1.388

95
VAV-65

4

.090

200

0.969

60
VAV-66

10

.550

1200

1.875

360
VAV-67

4

.080

3rd Floor

175
55

0.820

CFM

COMPUTER
READING

903

887

250

255

317

314

92

90

203

202

62

56

1211

1206

377

368

185

183

56

52

17

Sheet

T&B Services, Ltd.

8/3/07

Date

of

37

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

SIZE

3rd Floor

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-53)
301

1

170

159

159

301

2

170

154

154

303A

1

185

195

195

303B

2

185

174

174

303C

1

345

293

352

303C

2

345

346

348

303D

1

330

375

330

303D

2

330

411

327

1

475

420

489

1

475

490

482

1

475

541

487

1

355

-

349

(VAV-54)

(VAV-55)

(VAV-56)

(VAV-57)
303E
(VAV-58)
303F
(VAV-59)
303G
(VAV-60)
303H

REMARKS

18

Sheet

T&B Services, Ltd.

8/3/07

Date

of

37

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

3rd Floor

AREA SERVED

SIZE

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-61)
303L

1

255

288

259

303K

2

230

257

237

325

1

275

281

279

325

2

275

275

280

325

3

275

241

265

325

4

275

314

280

325A

1

455

464

453

325A

2

455

398

450

1

315

344

317

1

200

234

203

3256G

1

300

327

301

325G

2

300

302

298

325G

3

300

268

299

325G

4

300

318

313

(VAV-62)

(VAV-63)

(VAV-64)
325C
(VAV-65)
325E
(VAV-66)

REMARKS

T&B Services, Ltd.

Sheet

19

of

Date

8/3/07

By

37
DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1

LOCATION

NO.

SIZE

3rd Floor

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(VAV-67)
325H

1

175

217

185

REMARKS

Sheet

T&B Services, Ltd.

20

of

By
8/31/07
11/14/07

Date

FAN EQUIPMENT TEST REPORT

PROJECT

SYSTEM

UW Stout-Administration Bldg.

AHU-1 (Return)

FAN MANUFACTURER
MODEL OR SERIAL NO.

EQUIPMENT LOCATION
McQuay
CAH053 GDDM

TOTAL CFM
MIN O.A.
RETURN CFM
FAN SUCTION PRESSURE (TP)
FAN DISCHARGE PRESSURE (SP)
FAN STATIC PRESSURE
FAN RPM
FAN PULLY - SIZE, TYPE
MFGR.
BELT QUANTITY / SIZE
C-C
FILTER SIZE & QUANTITY
MTR MANUFACTURER
MODEL OR SERIAL NO.

AHU-1

DESIGN
24250
-

ACTUAL
22965
-0.64"
+0.94"
1.58"
685

2B5V136 B1 15/16
Browning
(2) BX123
47.5
-

Baldor
EM25133-8
RATED

MOTOR H.P.
BHP
OPERATING AMPERAGE, L1-L2-L3
VOLTAGE
RPM
MOTOR SHEAVE - SIZE, TYPE
MFGR.
O.L. HEATERS
SF
FRAME
PF / EFF

REMARKS
Unit Total:
60x36=15.0 @ 1531 fpm/22965 cfm
AMD: 23150 cfm

15.0
11.6
40.7
200
1765
2B5V52 B1 5/8
Browning
VFD
1.15
254T
85/93

ACTUAL
15.0
13.4
35.0
208
1773

VFD @ 60 Hz

37
DA
DA

T&B Services, Ltd.

Sheet

21

of

37

Date

8/31/07

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-1 (Return)

LOCATION

NO.

1st Floor

1

SIZE

DESIGN
VEL

CFM

FINAL

TEST TEST TEST
1

VEL

CFM

1453/15983

1453

15983

REMARKS

*

44x36

*

AK

AREA SERVED

9475
11.0 1507

2nd Floor

2

8300

3rd Floor

3

8225

**

6982

Design grille total adds up to 26240 cfm. Design supply minus design outside air = 24250 cfm.
Proportioned air to available flow.
** No way to accurately read individual flows for 1st and 2nd floors

22

Sheet

T&B Services, Ltd.

of

By
8/31/07
11/7/07

Date

37
DA
DA

FAN EQUIPMENT TEST REPORT

PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-2

FAN MANUFACTURER
MODEL OR SERIAL NO.

EQUIPMENT LOCATION
McQuay
CAH012 GDAC

TOTAL CFM
MIN O.A.
RETURN CFM
FAN SUCTION PRESSURE (TP)
FAN DISCHARGE PRESSURE (SP)
FAN STATIC PRESSURE
FAN RPM
FAN PULLY - SIZE, TYPE
MFGR.
BELT QUANTITY / SIZE
C-C
FILTER SIZE & QUANTITY
MTR MANUFACTURER
MODEL OR SERIAL NO.

Basement Mech.

DESIGN
6860
660
6200

ACTUAL
6914
668
6246
-2.01"
+0.65"
2.66"
978
B1 15/16

2.0
2B5V90
w/
Browning
(2) B46
13.25
(3) 12x24x2 (3) 12x24x12
(2) 24x24x2 (2) 24x24x12
Baldor
EM3311T-8
RATED

MOTOR H.P.
BHP
OPERATING AMPERAGE, L1-L2-L3
VOLTAGE
RPM
MOTOR SHEAVE - SIZE, TYPE
MFGR.
O.L. HEATERS
SF
FRAME
PF / EFF

ACTUAL

5.0
3.6
22.3
15.5
200
1770
2BK55H w/ H 1 3/8
Browning
B28.0
1.15
213T
79.0/91.7

7.5
5.72
16.8
208
1772

16.8

REMARKS
Min O.A.
OA: 45.0˚F
RA: 75.0˚F
MA: 72.1˚F

=

9.67%

-0.76"

-1.33"

-1.70"

-2.01"

+0.65"

23

Sheet

T&B Services, Ltd.

of

By
8/31/07
11/14/07

Date

37
DA
DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

SYSTEM

LOCATION

UW Stout-Administration Bldg.

AHU-2

NO.

SIZE

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(HC-101)
1

225

168

203

2

225

182

205

3

225

195

206

4

225

222

211

5

225

212

221

1

160

193

170

2

160

183

175

1

200

235

212

1

245

270

243

1

125

161

130

2

125

161

125

1

145

238

155

1

145

109

156

(HC-102)

(HC-103)

(HC-104)

(HC-105)

(HC-106)

(HC-107)

REMARKS

24

Sheet

T&B Services, Ltd.

of

By
8/31/07
11/14/07

Date

37
DA
DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-2

LOCATION

NO.

AREA SERVED

SIZE

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(HC-108)
1

150

166

165

2

150

186

161

1

150

204

150

2

150

170

153

9

1

225

237

235

9

2

225

241

237

9

3

225

230

237

9

4

225

212

237

9

5

225

207

244

9

6

225

246

246

9

7

225

214

238

9

8

225

217

237

7

1

120

148

126

6A

2

200

272

212

(HC-109)

(HC-110)

(HC-112)

REMARKS

25

of

37

By
8/31/07
11/14/07

DA
DA

Sheet

T&B Services, Ltd.

Date

DIFFUSER AND GRILLE TEST REPORT
PROJECT

UW Stout-Administration Bldg.

SYSTEM

AHU-2

LOCATION

NO.

SIZE

AREA SERVED

AK

DESIGN
VEL

CFM

TEST TEST TEST
1

FINAL
VEL

CFM

(HC-113)
1

200

203

214

2

200

238

217

1

300

239

315

2

300

286

330

1

1

155

171

164

1

2

155

175

170

15

3

200

104

214

(HC-114)

(HC-118)

REMARKS

T&B Services, Ltd.

Sheet

26

of

Date

8/10/07

By

EXHAUST FAN TEST REPORT

PROJECT

UW Stout-Administration Bldg.

EXH. FAN NO.
OR LOCATION

MANUFACTURER

TYPE OR SIZE
FAN
CFM
TOTAL
STATIC
PRESS.
FAN
RPM

AMPS

DB-16
1500

ACTUAL

904

DESIGN

-

ACTUAL

-0.31"/+0.19"

DESIGN

-

ACTUAL

1410
(1) 4L38

DESIGN

-

ACTUAL

1/4

DESIGN

4.4

ACTUAL

4.3

DESIGN

115

ACTUAL

121

DESIGN

1725

ACTUAL

1731

MOTOR

1VL34 x 1/2

FAN

Inacc.

VOLTAGE
MOTOR
RPM

Trane

DESIGN

BELTS
MOTOR
HP

Existing
EF-1

SHEAVE

37
DA

T&B Services, Ltd.

Sheet

27

of

37

Date

8/10/07

By

DA

DIFFUSER AND GRILLE TEST REPORT
PROJECT

SYSTEM

UW Stout-Administration Bldg.

Existing EF-1

SIZE

AK

Restrooms

AREA SERVED
DESIGN

TEST TEST TEST
1

FINAL

LOCATION

NO.

312A

1

210

199

89

313A

2

210

137

88

325B

3

75

36

37

212

4

210

57

88

213

5

210

65

91

215

6

-

27

48

103Y

7

75

28

49

12A

8

330

69

114

13

9

330

100

123

VEL

CFM

VEL

CFM

REMARKS
Unit Total:
24x6=1.0
904 fpm/ 904 cfm

Face Dampers Only

No damper

T&B Services, Ltd.

Sheet

28

of

37

Date

8/2/07

By

DA

CIRCULATING WATER PUMP TEST REPORT
PROJECT

SYSTEM

UW Stout-Administration Bldg.
PUMP LOCATION
OR NUMBER

Existing Hot Water Pump

Bell & Gossett
2AB 5 3/8 BF

PUMP MANUFACTURER
MODEL OR SERIAL NO.

1531

ACTUAL

DESIGN

PUMP GPM
PUMP RPM
DISCHARGE PRESSURE
(Ft. H20)
SUCTION PRESSURE
(Ft. H20)
TOTAL HEAD
(F T. H 2 0) *

70
No Flow
Full Flow
No Flow
Full Flow
No Flow
Full Flow

18-P5

70
1771
118.0 ft
100.0 ft
85.8 ft
73.8 ft
32.2 ft
26.2 ft

25

* TOTAL HEAD (FT H 2 0) = PUMP DIFFERENTIAL x 2.307
(If differential is in psig)
MOTOR MANUFACTURER
MODEL OR SERIAL NUMBER

Bell & Gossett
Ser: 110-8-LH
RATED

MOTOR HP
BHP
OPERATING AMPERAGE, L1-L2-L3
VOLTAGE
RPM
O.L.HEATERS

REMARKS:

ACTUAL

1 1/2
4.4-4.0/2.0
208-220/440
1750
-

3.1

2.9
208
1771

2.9

T&B Services, Ltd.

Sheet

29

of

37

Date

7/11/07

By

DA/JA

FLOW INDICATOR DATA SHEET

UW Stout-Administration Bldg.

PROJECT

SYSTEM

Hot Water

UNIT
SERVED

AREA SERVED

INDICATOR
SIZE

FINAL

DESIGN
INDICATOR
READING

Basement

METER READING

GPM

INDICATOR
READING

GPM

IN. WATER

FT. WATER

HC-101

3/4S B&G

2.5

0

1.67

0.55

HC-102

3/4S B&G

0.9

44

0.87

3.6

HC-103

3/4S B&G

2.1

16

2.0

1.75

HC-104

3/4S B&G

0.8

50

0.79

5.63

HC-105

3/4S B&G

0.7

50

0.82

6.1

HC-106

3/4S B&G

0.3

50

0.82

6.05

HC-107

3/4S B&G

0.3

50

0.90

7.2

HC-108

3/4S B&G

0.6

50

0.89

7.0

HC-109

3/4S B&G

0.6

50

1.0

9.0

HC-110

3/4S B&G

4.6

0

2.4

1.11

HC-112

3/4S B&G

1.0

50

0.95

8.02

HC-113

3/4S B&G

1.6

36

1.57

5.4

HC-114

3/4S B&G

1.8

24

1.78

2.5

HC-118

3/4S B&G

1.5

0

1.48

0.43

REMARKS:

T&B Services, Ltd.

Sheet

30

of

37

Date

7/11/07

By

DA/JA

FLOW INDICATOR DATA SHEET

PROJECT

SYSTEM

UW Stout-Administration Bldg.

Hot Water

UNIT
SERVED

INDICATOR
SIZE

DC-2

AREA SERVED
FINAL

DESIGN

1st Floor

METER READING

INDICATOR
READING

GPM

INDICATOR
READING

GPM

IN. WATER

3/4 Taco

9.0

1.8

0

1.3

4.7

DC-28

1/2 Taco

1.42

0.4

40

0.37

1.2

DC-27

1/2 Taco

3.2

0.6

30

0.57

2.9

DC-26

1/2 Taco

3.2

0.6

35

0.60

3.2

DC-25

1/2 Taco

3.2

0.6

25

0.57

2.9

DC-24

1/2 Taco

3.2

0.6

15

0.59

3.1

DC-23

1/2 Taco

4.4

0.7

0

0.66

3.8

DC-22

1/2 Taco

3.2

0.6

0

0.59

3.1

DC-21

1/2 Taco

3.2

0.6

0

0.58

3.0

DC-18

1/2 Taco

4.4

0.7

15

0.69

4.3

DC-19

1/2 Taco

0.8

0.3

45

0.30

0.8 *

DC-20

1/2 Taco

0.36

0.2

55

0.24

0.5 *

DC-14

1/2 Taco

0.36

0.2

45

0.24

0.5 *

DC-15

1/2 Taco

0.09

0.1

57

0.24

0.5 *

DC-16

1/2 Taco

0.09

0.1

40

0.18

0.3

FT. WATER

*

REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable

T&B Services, Ltd.

Sheet

31

of

37

Date

7/11/07

By

DA/JA

FLOW INDICATOR DATA SHEET

PROJECT

UW Stout-Administration Bldg.

SYSTEM

Hot Water

UNIT
SERVED

INDICATOR
SIZE

DC-13

AREA SERVED
FINAL

DESIGN

1st Floor

METER READING

INDICATOR
READING

GPM

INDICATOR
READING

GPM

1/2 Taco

1.42

0.4

35

0.38

1.25

DC-12

1/2 Taco

3.2

0.6

12

0.57

2.9

DC-11

1/2 Taco

0.8

0.3

35

0.30

0.8

DC-10

1/2 Taco

4.4

0.7

15

0.65

3.8

DC-9

1/2 Taco

3.2

0.6

20

0.58

3.0

DC-8

1/2 Taco

3.2

0.6

20

0.60

3.2

DC-3

1/2 Taco

5.64

0.8

0

0.78

5.3

DC-7

1/2 Taco

4.4

0.7

20

0.70

4.4

DC-5

1/2 Taco

0.09

0.1

45

0.24

0.5 *

DC-6

1/2 Taco

0.09

0.1

45

0.27

0.6

DC-4

1/2 Taco

10.76

1.1

0

0.98

8.5

DC-1

3/4 Taco

9.0

1.8

0

1.26

4.4

DC-17

1/2 Taco

0.36

0.2

48

0.21

0.4

IN. WATER

FT. WATER

*

*

REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable

T&B Services, Ltd.

Sheet

32

of

37

Date

7/11/07

By

DA

FLOW INDICATOR DATA SHEET

PROJECT

UW Stout-Administration Bldg.

SYSTEM

Hot Water

2nd Floor

UNIT
SERVED

INDICATOR
SIZE

225A

AREA SERVED

1st Floor Serving 2nd

FINAL

DESIGN

METER READING

INDICATOR
READING

GPM

INDICATOR
READING

GPM

IN. WATER

1/2 Taco

1.15

0.36

52

0.37

1.2

225B

1/2 Taco

2.05

0.48

45

0.47

2.0

210A

1/2 Taco

2.05

0.48

45

0.49

2.1

210B

1/2 Taco

2.05

0.48

35

0.47

2.0

210E

1/2 Taco

2.05

0.48

35

0.47

2.0

210D

1/2 Taco

2.05

0.48

30

0.49

2.1

203G

1/2 Taco

6.27

0.84

10

0.83

6.1

203F

1/2 Taco

2.05

0.48

30

0.47

2.0

203E

1/2 Taco

2.05

0.48

35

0.47

2.0

203M

1/2 Taco

2.05

0.48

38

0.47

2.0

203D

1/2 Taco

2.05

0.48

37

0.47

2.0

203C

1/2 Taco

2.05

0.48

40

0.47

2.0

REMARKS:

FT. WATER

T&B Services, Ltd.

Sheet

33

of

Date

8/1/07

By

37
DA

FLOW INDICATOR DATA SHEET

UW Stout-Administration Bldg.

PROJECT

SYSTEM

Hot Water

UNIT
SERVED

AREA SERVED

INDICATOR
SIZE

FINAL

DESIGN
INDICATOR
READING

GPM

2nd Floor

METER READING

INDICATOR
READING

GPM

IN. WATER

DC-51

1/2 Taco

2.22

0.5

33

0.49

2.1

DC-52

1/2 Taco

2.22

0.5

32

0.51

2.3

DC-50

1/2 Taco

3.2

0.6

15

0.59

3.1

DC-43

1/2 Taco

1.42

0.4

40

0.37

1.2

DC-44

1/2 Taco

1.42

0.4

37

0.37

1.2

DC-47

1/2 Taco

2.22

0.5

23

0.50

2.2

DC-46

1/2 Taco

2.22

0.5

0

0.47

2.0

DC-45

1/2 Taco

1.42

0.4

30

0.38

1.3

DC-48

1/2 Taco

0.36

0.2

33

0.24

0.5

DC-49

1/2 Taco

0.36

0.2

40

0.21

0.4

DC-42

1/2 Taco

1.42

0.4

36

0.37

1.2

DC-39

1/2 Taco

0.36

0.2

35

0.24

0.5

DC-38

1/2 Taco

1.42

0.4

0

0.37

1.2

FT. WATER

*
*

*

REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable

T&B Services, Ltd.

Sheet

34

of

37

Date

8/1/07

By

DA

FLOW INDICATOR DATA SHEET

PROJECT

UW Stout-Administration Bldg.

SYSTEM

Hot Water

UNIT
SERVED

INDICATOR
SIZE

AREA SERVED
FINAL

DESIGN
INDICATOR
READING

GPM

INDICATOR
READING

2nd Floor

METER READING
GPM

IN. WATER

DC-40

1/2 Taco

0.36

0.2

25

0.21

0.4

DC-36

1/2 Taco

1.42

0.4

32

0.37

1.2

DC-41

1/2 Taco

0.09

0.1

0

0.24

0.5

DC-35

1/2 Taco

1.42

0.4

33

0.37

1.2

DC-37

1/2 Taco

1.42

0.4

25

0.38

1.3

DC-30

1/2 Taco

0.36

0.2

42

0.24

0.5

DC-34

1/2 Taco

1.42

0.4

30

0.37

1.2

DC-33

1/2 Taco

2.22

0.5

22

0.50

2.2

DC-31

1/2 Taco

0.09

0.1

40

0.24

0.5

DC-32

1/2 Taco

0.36

0.2

45

0.26

0.6

DC-29

1/2 Taco

0.36

0.2

60

0.24

0.5

FT. WATER

*

*

*

*
*
*

REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable

35

Sheet

T&B Services, Ltd.

Date

8/1/07

of

37

By

DA

FLOW INDICATOR DATA SHEET

PROJECT

UW Stout-Administration Bldg.

SYSTEM

Hot Water

AREA SERVED
FINAL

DESIGN

UNIT
SERVED

INDICATOR
SIZE

325C

1/2 Taco

1.15

325

1/2 Taco

325A

INDICATOR
READING

2nd Floor serving 3rd

METER READING

INDICATOR
READING

GPM

IN. WATER

0.36

38

0.37

1.2

2.05

0.48

35

0.49

2.1

1/2 Taco

8.19

0.96

15

0.94

7.9

325G

1/2 Taco

8.19

0.96

0

0.95

8.1

303H

1/2 Taco

2.05

0.48

32

0.47

2.0

303G

1/2 Taco

1.15

0.36

40

0.35

1.1

303F

1/2 Taco

3.2

0.60

38

0.61

3.3

303E

1/2 Taco

0.51

0.24

60

0.28

0.7

303D

1/2 Taco

2.05

0.48

30

0.49

2.1

303C

1/2 Taco

2.05

0.48

33

0.47

2.0

GPM

FT. WATER

*

REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable

T&B Services, Ltd.

Sheet

36

of

37

Date

8/1/07

By

DA

FLOW INDICATOR DATA SHEET

UW Stout-Administration Bldg.

PROJECT

Hot Water

SYSTEM

UNIT
SERVED

INDICATOR
SIZE

AREA SERVED
FINAL

DESIGN
INDICATOR
READING

GPM

INDICATOR
READING

3rd Floor

METER READING
GPM

IN. WATER

DC-64

1/2" Taco

3.2

0.6

50

0.56

2.8

DC-62

1/2" Taco

7.2

0.9

35

0.89

7.0

DC-65

1/2" Taco

0.36

0.2

53

0.24

0.5

DC-63

1/2" Taco

7.2

0.9

32

0.87

6.7

DC-66

1/2" Taco

22.76

1.6

0

1.53

20.9

DC-67

1/2" Taco

0.09

0.1

55

0.21

0.4

DC-60

1/2" Taco

1.42

0.4

60

0.37

1.2

DC-59

1/2" Taco

2.22

0.5

55

0.52

2.4

DC-61

1/2" Taco

1.42

0.4

60

0.37

1.2

DC-58

1/2" Taco

2.22

0.5

60

0.50

2.2

DC-57

1/2" Taco

2.22

0.5

52

0.51

2.3

DC-54

1/2" Taco

0.8

0.3

53

0.30

0.8

DC-53

1/2" Taco

2.22

0.5

50

0.49

2.1

DC-55

1/2" Taco

7.2

0.9

35

0.92

7.6

DC-56

1/2" Taco

3.2

0.6

47

0.57

2.9

FT. WATER

*

*

*

REMARKS: * Approximate readings. Accuracy of differential pressure readings this low is questionable

T&B Services, Ltd.

Sheet

37

of

Date

9/19/07

By

37
DA

FLOW INDICATOR DATA SHEET

PROJECT

SYSTEM

UW Stout-Administration Bldg.

Chilled Water

UNIT
SERVED

INDICATOR
SIZE

AREA SERVED
FINAL

DESIGN
INDICATOR
READING

GPM

INDICATOR
READING

METER READING
GPM

0.9

AHU-1 / Top

4" Taco

0.96

54.75

0

AHU-1 / Bottom

4" Taco

0.96

54.75

0

55.8

1.0

AHU-2

2" Taco

8.0

26.0

45

26.2

8.1

REMARKS: * Main Bldg FMD: 117 gpm

53.0m
53.0 ,

IN. WATER

FT. WATER



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 39
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:d3beefbe-9893-11dc-b954-000a95cfc0d2
Modify Date                     : 2007:11:21 18:42:39-06:00
Create Date                     : 2007:11:21 18:29:11-06:00
Metadata Date                   : 2007:11:21 18:42:39-06:00
Document ID                     : uuid:a1d902c0-9891-11dc-9aa4-000a95cfc0d2
Format                          : application/pdf
Creator                         : MacDraw I: LaserWriter 8 8.7.3
Producer                        : Acrobat Distiller 6.0 for Macintosh
EXIF Metadata provided by EXIF.tools

Navigation menu