151051 2224 Installation Manual

User Manual: 2224 Installation Manual AlarmHow.net Library

Open the PDF directly: View PDF PDF.
Page Count: 52

Download151051 2224 Installation Manual
Open PDF In BrowserView PDF
Content
Section 1
Overview
1.1
1.2

...................................................................................................................................................... 1-1

SK-2224 Description ................................................................................................................................ 1-1
How to Contact Silent Knight .................................................................................................................. 1-1

Section 2
Agency Requirements
2.1
2.2

............................................................................................................... 2-1

FCC Warning ........................................................................................................................................... 2-1
Underwriters Laboratories (UL) .............................................................................................................. 2-1
2.2.1
Requirements for All Installations ................................................................................................ 2-1
2.2.2
Requirements for Local Protected Fire Alarm Systems ................................................................ 2-1

Section 3
Before You Begin Installing
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9

............................................................................................... 3-1

What's in the Box? ................................................................................................................................... 3-1
Optional Accessories ................................................................................................................................ 3-2
SK-2224 Board Layout ............................................................................................................................ 3-3
Electrical Specifications ........................................................................................................................... 3-4
Environmental Specifications .................................................................................................................. 3-4
Mounting the SK-2224 ............................................................................................................................. 3-5
Assembly .................................................................................................................................................. 3-6
Wiring Specifications ............................................................................................................................... 3-7
Calculating Current Draw and Standby Battery ...................................................................................... 3-8
3.9.1
Worksheet Requirements .............................................................................................................. 3-8
Filling in the Current Draw Worksheet, Table 3-6 (Section 3.9.3) ............................................... 3-8
3.9.2
Maximum Battery Standby Load .................................................................................................. 3-8
3.9.3
Current Draw Worksheet .............................................................................................................. 3-9

Section 4
Hardware Installation

.................................................................................................................. 4-1

4.1
4.2
4.3

AC Power ................................................................................................................................................. 4-1
Battery Connection .................................................................................................................................. 4-2
Initiation Circuit Installation .................................................................................................................... 4-3
4.3.1
Contact Wiring .............................................................................................................................. 4-3
4.3.2
Two-Wire Smoke Detector Wiring ............................................................................................... 4-3
4.3.3
Four-Wire Smoke Detector ........................................................................................................... 4-4
4.3.4
Notification Circuit Installation .................................................................................................... 4-5
4.4 Alarm and Trouble Relays ....................................................................................................................... 4-5
4.5 Auxiliary Power Circuit ........................................................................................................................... 4-5
4.6 Door Release Wiring ................................................................................................................................ 4-6

151051

i

Model SK-2224 Fire Control Panel Installation/Operation Manual

4.7

Optional Accessories Installation ............................................................................................................. 4-7
4.7.1
Installing the Serial Driver Board (Model SK-2884) .................................................................... 4-7
Wiring the SK-2884 to an Expansion Device ............................................................................... 4-8
4.7.2
SK-2865 LED Annunciator Installation ........................................................................................ 4-8
SK-2865 Electrical Specification .................................................................................................. 4-8
Wiring the SK-2865 to the SK-2884 ............................................................................................. 4-8
Setting the SK-2865’s address .................................................................................................... 4-10
Mounting the SK-2865 ................................................................................................................ 4-10

Section 5
System Configuration
Section 6
System Operation
6.1
6.2

................................................................................................................ 5-1

............................................................................................................................ 6-1

Meaning of LEDs ..................................................................................................................................... 6-1
Operation Keys (Switches) ...................................................................................................................... 6-3

Appendix A
Compatible Devices

..................................................................................................................... A-1

A.1

Smoke Detectors ..................................................................................................................................... A-1
A.1.1 Enhanced Mode ............................................................................................................................ A-1
A.1.2 Two-Wire Smoke Detectors ......................................................................................................... A-2
A.1.3 Four-Wire Smoke Detectors ......................................................................................................... A-4
A.2 Notification Appliances .......................................................................................................................... A-5
General Terms and Conditions ..........................................................................................................1
Repair and RA Procedure ..................................................................................................................1
Advanced Replacement Policy ..........................................................................................................1
Limited Warranty ..............................................................................................................................2

ii

151051

Section 1
Overview
1.1

SK-2224 Description

The Model SK-2224 is a two zone, 24-volt fire control panel having the following features:
•

Two Class B zones

•

Two notification circuits rated at 1.25 amp each

•

2.5 amp power supply

•

Dedicated alarm and trouble relays

•

Auxiliary power output (.5 amp max.) for powering special applications, such as door
holders.

•

Enhanced Verification Mode, a built-in feature that distinguishes two-wire smoke detectors from pull stations.

•

Housed in a 12-13/16"W x 15-1/8"H x 3-3/8"D metal cabinet

•

Cabinet supports two 7.0 AH backup batteries

1.2

How to Contact Silent Knight

If you have a question or encounter a problem not covered in this manual, contact Silent
Knight Technical Support at 800-328-0103 (or 612-493-6455). To order parts, contact Silent
Knight Sales at 800-446-6444 (or 612-493-6435).

151051

1-1

Model SK-2224 Fire Control Panel Installation/Operation Manual

1-2

151051

Section 2
Agency Requirements
2.1

FCC Warning

This device has been verified to comply with FCC Rules Part 15. Operation is subject to the
two following conditions: (1) This device may not cause radio interference, and (2) This
device must accept any interference received, including interference that may cause undesired
operation.

2.2

Underwriters Laboratories (UL)

The SK-2224 is UL listed as a control unit for use in NFPA 72 systems. If the SK-2224 and
its accessories are to be used as part of a UL installation, carefully read the UL requirements
in this section. For more information on NFPA 72 standards, refer to the NFPA National Fire
Alarm Code, 1996 Edition.

2.2.1

Requirements for All Installations

General requirements are described in this section. When installing an individual device,
refer to the specific section of the manual for additional requirements.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use UL listed smoke detectors and notification appliances compatible with the SK-2224
from those specified in the Appendix to this manual.
3. If you are using the smoke verification feature:
•

Do not use smoke detectors with built-in alarm verification.

•

Select "Enhanced Mode" if the installation includes pull stations or water flow
switches.

4. A full system checkout must be performed any time the panel is programmed.
5. UL installations require use of Model 7628 EOL resistor assembly.

2.2.2

Requirements for Local Protected Fire Alarm
Systems

At least one UL listed supervised notification appliance must be used.

151051

2-1

Model SK-2224 Fire Control Panel Installation/Operation Manual

2-2

151051

Section 3
Before You Begin Installing
3.1

What's in the Box?

The Model SK-2224 ships with the following hardware:
Table 3-1: Contents of Shipping Box
Containing
Main Part
Part

Quantity/Item

1 Cabinet

Model
Number
122509

Panel Bag

1 Control Board

202224

1 Installation/
Operation Manual

151051

2 #8 Screws

119152

2 #8 Nuts

119538

3 Self-tapping Screws

119296

1 Earth Ground Wire

140668

1 Battery Wire Harness

130420

1 battery Jumper

140694

Hardware Bag

120 Vrms @ 60Hz
1 Transformer

115061
or a

230 Vrms at 50Hz

115031

1 Viewing Bezel

122508

4 End-of-line Resistors

111682

Note: See Section 3.7 for assembly instructions.

151051

3-1

Model SK-2224 Fire Control Panel Installation/Operation Manual

3.2

Optional Accessories

Table 3-2 is a list of optional accessories that can be used with the Model SK-2224 Fire
Control Panel.
Table 3-2: Option Accessories for the SK-2224
Model
Number

*

3-2

Name

Description

SK-2884

Serial Driver Board

Used to interface all SK-2224 expansion device to the SK2224 panel. Supports 1 Dialer (Model SK-2104) and any
combination of 4 LED Annunciators (Model SK-2865) or I/O
Modules (Model SK-2880).

*SK-2880

Input/Output (I/O) Module

Used to drive customized annunciators and interface devices.

*SK-2865

LED Annunciator

Remote LED annunciator with Silence and Reset keyswitch
inputs.

*SK-2104

Digital Dialer

Used to communicate alarms, trouble and supervisories to
central station. Offers 5 different reporting formats 3/1, 4/2,
BFSK, SIA, and Contact ID.

7628

UL listed End-of-line
(EOL) Resistor.

EOL resistor required for UL installations.

Requires a SK-2884 to operate with the SK-2224 control panel.

151051

Before You Begin Installing

3.3

SK-2224 Board Layout

Figure 3-1 shows the SK-2224 circuit board including location of terminals, connectors, dip
switches, and LEDs.
Programming
DIP Switches

Annunciator

SK-2884
Serial
Interface
Connector

AC Power
Connector

On-Board
Piezo Sounder

Backup
Battery
Connector

Zone 2 Notification
Inputs Appliance
Circuits

Trouble &
Auxiliary
Alarm Relays Power
Output

Figure 3-1 Model SK-2224 Layout

151051

3-3

Model SK-2224 Fire Control Panel Installation/Operation Manual

3.4

Electrical Specifications
Table 3-3: Electrical Specifications
Circuit

Rating

Primary AC

*120 Vrms at 60 Hz, or 230 Vrms at 50 Hz

Total External DC Load

2.5A @ 24 VDC

+24V Auxiliary Power

19.8 V to 28.0 V, 0.5 A max.

Trouble & Alarm Relays

2.5 A @ 30 VDC resistive

Notification Appliance Power

19.8 V to 28.0 V, 1.25 A max. each

Smoke Detector Power

19.8 V to 28.0 V, 1.0 A max.

Battery Charging Voltage

27.0 - 27.6 V

Maximum Battery Charging Current

750 mA

Minimum Low Battery Detect

20.4 V

Minimum Low AC Detect

100 Vrms at 60 Hz, full load

Note: * When ordering, specify your voltage requirements.

3.5

Environmental Specifications
Table 3-4: Environmental Specifications
Storage Temperature:

-4° - 167° F (-20 - 75 ° C)

Operating Temperature:

32° - 120° F (0° - 49 ° C)

Humidity:

10 - 85% non-condensing

It is important to protect the SK-2224 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when mounting the units:

3-4

•

Do not mount directly on exterior walls, especially masonry walls (condensation)

•

Do not mount directly on exterior walls below grade (condensation)

•

Protect from plumbing leaks

•

Protect from splash caused by sprinkler system inspection ports

•

Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)

151051

Before You Begin Installing

3.6

Mounting the SK-2224

Read the environmental specifications in Section 3.5 before mounting the cabinet.
The panel should be accessible to main drop wiring runs. It should be mounted as close to the
center of the building as possible and located within a secured area, but should be accessible
for testing and service. End-users responsible for maintaining the panel should be able to hear
alarms and troubles. When selecting a location, keep in mind that the panel itself is the main
source of alarm and trouble annunciation.
Mount the cabinet so it is firmly secured to the wall surface. When mounting the cabinet on
concrete, especially when moisture is expected, attach a piece of 3/4-inch plywood to the
concrete surface and then attach the cabinet to the plywood. Also mount any other modules to
the plywood.
Follow these steps to mount the control panel cabinet:
1. Place the cabinet on the mounting surface, level the cabinet and mark the top two
mounting holes.
2. Screw the top two mount screws about 3/4 of the way into the mounting surface.
3. Hang the control panel cabinet on the top mounting screws through the top mounting
screw keyholes.
12-1/2”
11”

Top Mounting
Screw Keyholes

15”

Bottom
Mounting Holes

Figure 3-2 Cabinet Mounting Holes

4. Insert the bottom two mounting screws into the cabinet’s bottom mounting holes.
5. Tighten all four mounting screws until the cabinet is properly secured.
6. Insert all cabinet components. See Section 3.7.
151051

3-5

Model SK-2224 Fire Control Panel Installation/Operation Manual

3.7

Assembly

The components listed in Table 3-1 are all packed within the cabinet and require some
assembly. Follow these steps to assemble the components inside the cabinet:
1. Remove keys from small manila envelope taped to the top of the cabinet.
2. Unlock the cabinet door.
3. Remove the packing material and the SK-2224 components.
4. Snap the bezel into the opening in the front of the cabinet. See Figure 3-3.
Note: The bezel will fit in only one way.

Transformer
Installation

Side View of
Slotted Stand-Off

Bezel Insertion

CPU Mounting
Screws

Figure 3-3 The SK-2224 Assembly Diagram

5. With the two #8 screws and the two #8 nuts (with built in washers), mount the transformer
in the holes in the upper left hand corner of the cabinet. See Figure 3-3.
6. With the three self-trapping screws mount the control board on the cabinet stand-offs.
Note: See Section 4 for transformer connections and battery connections.

3-6

151051

Before You Begin Installing

3.8

Wiring Specifications

Induced noise (transfer of electrical energy from one wire to another) can cause false alarms
or interfere with control panel operation in other ways.
To avoid induced noise, follow these guidelines:
•

Isolate input wiring from high current output and power wiring. Do not pull one multiconductor cable for the entire panel. Instead, separate the wiring as follows:
High current input/output:

AC power, speaker, and notification device wiring

Low current input/output:

Annunciator and zone loop wiring

Audio input/output:

Telephone wiring

•

Do not pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield
to circuit ground at the panel. You must route high and low voltages separately.

•

Route the wiring within the cabinet around the perimeter of the cabinet. It should not cross
the printed circuit board where it could induce noise into the sensitive microelectronics or
pick up unwanted RF noise from the high speed circuits. See Figure 3-4 for an example.

•

High frequency noise, such as that produced by the inductive reactance of a speaker or
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it
around a ferrite toroid.

Figure 3-4 Wire Routing Example

151051

3-7

Model SK-2224 Fire Control Panel Installation/Operation Manual

3.9

Calculating Current Draw and Standby Battery

This section is for helping you determine the current draw and standby battery needs for your
installation.

3.9.1

Worksheet Requirements

The following steps must be taken when determining SK-2224 current draw and standby
battery requirements.
Filling in the Current Draw Worksheet, Table 3-6 (Section 3.9.3)
1. For the SK-2224, the worst case current draw is listed for the panel and is recorded in the
table at Line A.
2. Add up the current draw for all smoke detectors and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. Any additional devices should be recorded at Line D.
5. Make sure that the alarm current without the panel (Lines B-D) does not exceed 2.5 A.
The total alarm current (including the panel, Lines A-D) should not exceed 2.75 A.
6. Complete the remaining instructions in Table 3-6 for determining battery size requirements.

3.9.2

Maximum Battery Standby Load

Table 3-5 shows the maximum battery standby load for the SK-2224 based on 24 hours of
standby. The standby load calculations of line D in the Current Draw Calculation Worksheet
(Table 3-6) must be less than the number shown in Table 3-5 for the battery size used and
standby hours required.
Table 3-5: Maximum Battery Standby Load

3-8

Rechargeable Battery Size

Max. Load for 24 hrs.
Standby, 5 mins. Alarm

7 AH

270 mA

151051

Before You Begin Installing

3.9.3

Current Draw Worksheet

Use this worksheet to determine current requirements during alarm/battery standby operation.
(Copy this page if additional space is required.)
Table 3-6: Current Draw Calculations
Device
For each device, use this formula:
SK-2224 Panel
A
Smoke Detectors

B
Notification Devices

Number of
Devices

Current per Device

Standby
Current

Alarm
Current

This Column X

This column
=
Current per number of devices
Standby:
100 mA
100 mA
1
Alarm:
250 mA
250 mA
Current Subtotals:
100 mA
250 mA
Refer to device manual for current ratings. See Appendix to this manual for
max. # per loop.
Standby:
mA
mA
Alarm:
mA
mA
Standby:
mA
mA
Alarm:
mA
mA
Standby:
mA
mA
Alarm:
mA
mA
Current Subtotals:
mA
mA
Refer to device manual for number of devices and current ratings.
Standby:
Alarm:
Standby:
Alarm:

C

mA
mA
mA
mA
Current Subtotals:

mA
mA
mA
mA

mA
mA

Accessory Devices
SK-2884
SK-2865

Standby:
Alarm:
Standby:
Alarm:

D

10 mA
10 mA
35 mA
75 mA
Current Subtotals:

mA
mA
mA
mA

mA
mA

*Additional Devices
Standby:
Alarm:
Standby:
Alarm:
E
Total current rating of all devices in system (add A through E):
F Total current ratings converted to amperes (x .001):

mA
mA
mA
mA
Current Subtotals:

mA
mA
mA
mA
mA
A

mA
mA
mA
A

*Note:If you are using door holders, you do not need to consider door holder current for alarm/battery standby,
because power is removed during that time. However, during normal operation, door holders draw current
and must be included in the total current that can be drawn from the panel.

151051

3-9

Model SK-2224 Fire Control Panel Installation/Operation Manual

3-10

151051

Section 4
Hardware Installation
4.1

AC Power

At installation, connect the transformer AC inputs to the AC power source as shown in Figure
4-1. It may be necessary for a professional electrician to make this connection.
The AC inputs are rated as 120 VAC, 60 Hz or 230 VAC, 50 Hz. See Table 3-1 for more
information.
Transformer

Yellow

Control Panel

White
To AC
Power

Black
Green
Earth Ground

Figure 4-1 AC Power Connection

151051

4-1

Model SK-2224 Fire Control Panel Installation/Operation Manual

4.2

Battery Connection

The SK-2224 battery charge capacity is 7.0 AH. Use two 12V batteries of the same AH rating.
Determine the correct AH rating as per your current load calculation (see Table 3-6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
Note: The SK-2224 cabinet supports two 7.0 AH batteries.

Battery jumper (P/N 140694),
shipped with the control panel.

Figure 4-2 Battery Connection

4-2

151051

Hardware Installation

4.3
4.3.1

Initiation Circuit Installation
Contact Wiring

Wire normally open contacts as shown in Figure 4-3. This is the type of wiring that would
typically be used for water flow switches, heat detectors and other normally open devices.

Figure 4-3 N.O. Contact Wiring

4.3.2

Two-Wire Smoke Detector Wiring

Figure 4-4 shows how to connect two-wire smoke detectors to the SK-2224 loops. The figure
uses Silent Knight's SLK-24F with HSB-224 base as an example. You can use any detector
that has been UL listed for compatibility with the SK-2224. Refer to the Appendix for a list of
compatible devices. Refer to Section 5 for configuration options.

Figure 4-4 Two-Wire Smoke Detector Wiring

151051

4-3

Model SK-2224 Fire Control Panel Installation/Operation Manual

4.3.3

Four-Wire Smoke Detector

Figure 4-5 shows how to connect four-wire smoke detectors to the SK-2224 loops. The figure
uses Silent Knight's SLK-24F with HSC-4R base as an example. You can use any UL listed
device listed in Appendix A. Information on selecting zone configuration options is in
Section 5.

Figure 4-5 Four-Wire Smoke Detector Wiring

4-4

151051

Hardware Installation

4.3.4

Notification Circuit Installation

Notification appliances used with the SK-2224 must be UL listed for compatibility with the
SK-2224. Refer to the list in the Appendix at the end of this manual for a list of compatible
devices.
For proper operation, you must use polarized notification appliances with a model 7628 4.7k
ohm end-of-line (EOL) resistor on each loop. Select ANSI output pattern, if desired. Output is
configured as steady (continuous sound) for the factory default. See Section 5 for information
on changing the pattern.

Figure 4-6 Notification Circuit Installation

4.4

Alarm and Trouble Relays

The SK-2224 has built-in relays for alarm and trouble. The alarm relay is energized during
any alarm condition. The trouble relay is energized during any trouble or supervisory trouble
condition. Each relay has three terminals (N.O., Common, and N.C.). Refer to Figure 3-1 for
location of these terminals.

4.5

Auxiliary Power Circuit

The SK-2224 has a power limited auxiliary power circuit which can source up to .5A. The
terminal is labeled “AUX PWR”. Refer to Figure 3-1 for location of this terminal.

151051

4-5

Model SK-2224 Fire Control Panel Installation/Operation Manual

4.6

Door Release Wiring

Figure 4-7 shows how to configure a door release using an ESL DH series door holder.

Figure 4-7 Door Release Wiring

4-6

151051

Hardware Installation

4.7

Optional Accessories Installation

This section describes how to install the optional accessories compatible with the SK-2224
control panel.

4.7.1

Installing the Serial Driver Board (Model SK-2884)

The SK-2884 is required if the installation uses any SK-2224 expansion devices such as
Model SK2865 (LED Annunciator). The SK-2884 interfaces all the expansion devices to the
SK-2224 control panel.
Follow these steps to install the SK-2884 Serial Driver Board:
1. Unplug the AC power connector from the SK-2224 control panel. See Figure 4-1.
2. Unplug the backup battery connector from the SK-2224 control panel. See Figure 4-2.
3. Plug the SK-2884 Serial board on SK-2224 control panel by aligning the 4-pin connector
and the stand-offs with their respective receptors. See Figure 4-8.

Figure 4-8 SK-2884 Connector and Stand-off alignment

4. Reconnect the AC power connector to the SK-2224 control panel. See Figure 4-1.
5. Reconnect the backup battery connector to the SK-2224 control panel. See Figure 4-2.

151051

4-7

Model SK-2224 Fire Control Panel Installation/Operation Manual

Wiring the SK-2884 to an Expansion Device
The SK-2884 uses a three wire connection to all of the SK-2224 compatible expansion
devices (see Table 3-2).
Connect all the expansion devices to the SK-2884 as follows:
Table 4-1: SK-2884 Wiring Connections

4.7.2

SK-2884
Terminals

To
SK-2224 Expansion
Device Terminal

-

-

+

+

D (Data)

D (Data)

SK-2865 LED Annunciator Installation

This section describes how to install the SK-2865 LED annunciator. The SK-2865 is a
supervised serial device used as a remote LED annunciator unit for the SK-2224.
SK-2865 Electrical Specification
Circuit

Max Loop Resistance:

Rating
Data

50Ω

-

50Ω

+

50Ω

Alarm:

75 mA

Standby:

35 mA

Max. Current:
Operating Voltage:

24 VDC

Wiring the SK-2865 to the SK-2884
Follow these steps to properly wire the SK-2865 to the SK-2884:
1. Unplug the AC power connector from the SK-2224 control panel. See Figure 4-1.
2. Unplug the backup battery connector from the SK-2224 control panel. See Figure 4-2.

4-8

151051

Hardware Installation

3. Terminate the wiring as shown in Figure 4-9. See also Table 4-2.

SK-2884

SK-2865

Supervised
Power Limited

Figure 4-9 SK-2865 Connection to the SK-2884
Table 4-2: SK-2865 Wiring Connections

151051

SK-2865
Terminals

SK-2884 Terminals

D (Data)

D (Data)

+

+

-

-

4-9

Model SK-2224 Fire Control Panel Installation/Operation Manual

Setting the SK-2865’s address
The range of valid addresses is 0-3. Each device requires a unique address. Set the dip
switches as shown in Table 4-3. See also Figure 4-9.
Table 4-3: Addresses Per Dip Switch Setting
Dip Switch

Position

Equivalent
Address

Both

Open (off)

0

One

Closed (on)

1

Two

Closed (on)

2

Both

Closed (on)

3

Mounting the SK-2865
The SK-2865 mounts into a standard 4” square electrical box.
Follow these steps to mount the SK-2865:
1. Make sure that the SK-2865 is properly wired to the control panel. See Figure 4-9.
2. Slide the printed annunciator label into place on the SK-2865. The label fits in between the
LEDs and the clear plastic plate.
3. Place the SK-2865 into the 4” square electrical box. See Figure 4-10.
Slide Printed
Annunciator
Label In

4” Square
Electrical Box

Cover Plate
Screw

SK-2865

Cover Plate

Figure 4-10 Mounting the SK-2865

4. Place the cover plate over the top of the SK-2865 and align the holes. See Figure 4-10.
5. Insert the four cover plate screws into the four screw holes on the 4” square electrical box.
6. Screw the four cover plate screws into the cover plate until the cover plate fits firmly
against the SK-2865 and the electrical box. Do not over tighten.
4-10

151051

Hardware Installation

151051

4-11

Model SK-2224 Fire Control Panel Installation/Operation Manual

4-12

151051

Section 5
System Configuration
To configure the SK-2224 system set the dipswitch that controls the option you want to
select. The following chart shows how to program the dipswitches that control system, zone,
and notification appliance operation. Refer to Figure 3-1 for location of the dipswitches.
Important!
When you change a dipswitch, be sure to perform a system reset (press [RESET]) or power
down the panel. Dipswitch changes will have no effect until after the system has been reset.
Some switches are unused and are not referred to in this chart. Leave all unused switches in
their factory-programmed OFF position.
Table 5-1: System Configuration
To Enable

For Zone 1 (DIP 1) For Zone 2 (DIP 1)

Enhanced mode (dipswitch ON). Use when both pull
stations and detectors will be used in the same zone.

SW1

SW6

DIP Position
ON = Enhanced
OFF = Normal

Normal mode (dipswitch OFF). Use when 4-wire smoke
detectors and smoke verification are used in the same zone.
Alarm verification

SW 2

SW 7

Note: Do not use with smoke detectors that have verification built-in.

ON = Verification zone
OFF = No verification

Fire alarm

SW 3

SW8

OFF

Supervisory

SW 3

SW8

ON

No delay

SW4

SW9

OFF

Alarm delay options

SW5

SW10

OFF

Note: Alarm delay options is to be 30 second delay
used with water flow devices
only. If the device has a builtin delay time the total delay 60 second delay
time (device delay + programmed delay) can not exceed 120 seconds.
90 second delay

SW4

SW9

ON

Zone Type

To Enable
Silencing
ANSI pattern

151051

SW5

SW10

OFF

SW4

SW9

OFF

SW5

SW10

ON

SW4

SW9

ON

SW5

SW10

ON

For NAC 1 (DIP 2)

For NAC 2 (DIP 2)

SW 1

SW 3

DIP Position
ON = Can be silenced
OFF = No silence

SW 2

SW 4

ON = ANSI
Off = Steady

5-1

Model SK-2224 Fire Control Panel Installation/Operation Manual

Table 5-1: System Configuration
To Enable

For Entire Panel
(DIP 2)

SW5
Serial Accessory Devices
*SW6

DIP Position
ON = Serial Annunciator connected to the
control panel.
OFF = No Serial Annunciator connected to the
control panel.
ON = Serial Dialer connected to the control
panel
OFF = No Serial Dialer connected to the
control panel.
ON = 6 hour delay on AC loss report.
OFF = No delay on AC (for dialer testing only).

AC loss report delay

SW7

SW8

*

5-2

Note: If there is not a serial dialer connected
to the control panel this should be set to
the OFF position.
Not Used.

Digital Dialer not available at this time.

151051

Section 6
System Operation
The annunciator on the SK-2224 board is used for all system operation. It contains the
switches for enabling silencing, resetting, and so on. The LEDs that indicate system status are
also located on the annunciator.

Figure 6-1 On-Board Annunciator

6.1

Meaning of LEDs

The chart below explains the meaning of LEDs on the system board.
Table 6-1: Meaning of LEDs
LED (Color)
AC (green)

Function
ON = Good AC
OFF = Low AC trouble condition and it was
acknowledged

Comments
If flashing, press the ACK button to acknowledged
the condition.

FLASHING = Unacknowledged AC Low trouble
condition
GENERAL TROUBLE
(yellow)

ON = System trouble
OFF = System OK
FLASHING = At least one serial device is in trouble
DOUBLE FLASHING = Two types of serial devices
are in trouble.

WALK TEST (yellow)

ON = Walk test is in progress
OFF = Walk test is off

Allow approximately 47 seconds between detector
tests.

FLASHING = Walk test is on and at least one zone is In walk test, when a detector is tripped, it will
cause an alarm for two seconds, then the control
faulted or not ready
panel will drop power to the loop for seven
seconds to reset the detector. Then an additional 38
seconds is needed to restore the detector.
If verification is used, the time between detector
test will be about 1 minute and 30 seconds.

151051

6-1

Model SK-2224 Fire Control Panel Installation/Operation Manual

Table 6-1: Meaning of LEDs
LED (Color)
GND FAULT (yellow)

Function
ON = Ground fault condition exists and was
acknowledged

Comments
If flashing, press the ACK button to acknowledged
the condition.

OFF = No fault
FLASHING = A ground fault condition detected
LOW BATTERY (yellow)

ON = Battery low condition that has been
acknowledged

If flashing, press the ACK button to acknowledged
the condition.

OFF = Good battery condition
FLASHING = Battery low condition
ALARM (red)

ON = Zone in alarm which has been acknowledged
OFF = No Alarm

If flashing, press the ACK button to acknowledged
the condition.

FLASHING = Zone in alarm has not yet been
acknowledged.
SUPERVISORY
(yellow)

ON = Zone has a supervisory condition (selfrestoring condition)

If flashing, press the ACK button to acknowledged
the condition.

OFF = No supervisory condition exists.
ZONE 1
and
ZONE 2

FLASHING = supervisory trouble detected on that
zone.
TROUBLE
(yellow)

ON = Zone has a trouble condition which has been
acknowledged

If flashing, press the ACK button to acknowledged
the condition.

OFF = No zone trouble
FLASHING = Zone has a trouble condition
DOUBLE FLASHING = Zone was disabled
CLEAN ME FLASHING = Indicates that the smoke A “Clean Me Flash” is a flash with a long LED
detector needs cleaning
“on” Time and a short LED “off” time indicating
that the smoke detector needs cleaning. Applies
only to smoke detectors with the CLEAN ME
feature. The “Clean Me” flash starts after the
trouble condition has been acknowledge.
ACTIVE (yellow)

ON = NAC is active during an alarm
OFF = NAC is not active during alarm

NAC 1
and

TROUBLE
(yellow)

NAC 2

ON = NAC has a trouble condition and was
acknowledged

If flashing, press the ACK button to acknowledged
the condition.

OFF = No trouble condition
FLASHING = NAC is in trouble
DOUBLE FLASHING = Circuit was disabled

SYSTEM SILENCED
(yellow)

ON = System audio output has been silenced
OFF = Nothing silenced
FLASHING = Partially silenced

6-2

When condition that caused audio activation
clears, this condition will clear automatically.

Note: Silencing an alarm will cause a general trouble condition.

151051

System Operation

6.2

Operation Keys (Switches)

All system operations are performed from the on-board keys (switches) as described in the
chart below.
Table 6-2: Operations and Instructions
Operation
Disable notification appliance
circuit.
To re-enable the circuit, press [NAC
DISABLE] again.
Disable a zone

Keystrokes
Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and
the corresponding TROUBLE LED will Double Flash. This function is not
available during an alarm condition.

To re-enable the circuit, press
[ZONE DISABLE] again.

Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the
corresponding TROUBLE LED will Double Flash. This function is not available
during an alarm or supervisory condition.

Begin Walk Test

Press [WALK TEST]. Walk Test LED turns on.

Note: Walk test will not activate if the control panel has a trouble, alarm,
or supervisory condition.
End Walk Test

Press [WALK TEST].

(The test ends automatically after 10
minutes of no system activity.)

NOTE: The Walk Test feature is not operational during an alarm, supervisory or
any system trouble condition.

Acknowledge condition (alarm,
supervisory, trouble)

Press [ACK]. The corresponding LED will change from blinking to steady for the
duration of the condition.

Silence Panel

Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits
that have been configured as "silenceable".

Perform system reset

Press [RESET]. Resets alarms, supervisories, troubles and all LEDs.

151051

6-3

Model SK-2224 Fire Control Panel Installation/Operation Manual

6-4

151051

Appendix A
Compatible Devices
This section of the manual lists devices (smoke detectors and notification appliances) that are
compatible with the SK-2224. Contact Silent Knight if you have a question about whether a
device not listed here is compatible.

A.1 Smoke Detectors
This section of the manual contains information about smoke detectors that are compatible
with the SK-2224.
SK-2224
Identifier
Voltage Range

24F
16.2 - 27.3 VDC

Note: The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur.

A.1.1 Enhanced Mode
Enhanced mode allows the installer to use pull stations on a loop that has been programmed
for Enhanced Alarm Verification. If a single detector goes into alarm it will start the alarm
verification cycle. If a pull station is activated any time during the alarm verification cycle and
after the control panel re-applies loop power (power will drop for seven seconds to restore
detector during verification), the panel will go into immediate alarm and discontinue the
verification cycle.
Warning! Do not mix different models or manufacturers of smoke detectors on the input loops.

151051

A-1

Model SK-2224 Fire Control Panel Installation/Operation Manual

A.1.2 Two-Wire Smoke Detectors
The table below lists two-wire smoke detectors that are compatible with the SK-2224. The
table is organized by manufacturer. The columns show the number of detectors per loop that
can be used.
Note: The check mark by manufacturers name indicates that this device can be used in enhanced mode.
Table A-1: Compatible Two-Wire Smoke Detectors
Manufacturer

Enhance
Mode
Compatible

Compatibility ID

Model Name or Number
(Base model name or number in
parentheses.)

# per Loop
Head

Base

55000-350 (45681-200)

55000-350

45681-200

24 / loop

55000-250 (45681-200)

55000-250

45681-200

24 / loop

DS200 (MB200-2W)

A

B

24 / loop

DS200HD (MB200-2W)

A

B

24 / loop

DS250 (MB2W or MB2WL)

B

A

18 / loop

DS250HD (MB2W or MB2WL)

B

A

18 / loop

DS250TH (MB2W or MB2WL)

B

A

18 / loop

425

S10

N/A

40 / loop

425C

S10

N/A

40 / loop

425CR

S10

N/A

40 / loop

425CRT

S10

N/A

40 / loop

425CT

S10

N/A

40 / loop

429C (S10A)

N/A

S10A

30 / loop

429CRT (S11A)

N/A

S11A

30 / loop

429CST (S11A)

N/A

S11A

30 / loop

429CT (S10A)

N/A

S10A

30 / loop

609U01-11

S10

S00

40 / loop

609U02-11

S10

S00/S03

40 / loop

611U (601U or 602U)

S10

S00/S03

40 / loop

611UD (601U or 602U)

S10

S00/S03

40 / loop

611UT (601U or 602U)

S10

S00/S03

40 / loop

612U (601U or 602U)

S10

S00/S03

40 / loop

612UD (601U or 602U)

S10

S00/S03

40 / loop

711U (701E or 701U)

N/A

S10A

25 / loop

712U (701E or 701U)

N/A

S10A

25 / loop

713-5U (702E or 701U)

N/A

S10A

25 / loop

713-6U (702E or 701U)

N/A

S10A

25 / loop

721-U (S10A)

N/A

S10A

30 / loop

721-UT (S10A)

N/A

S10A

30 / loop

Apollo

Detection Systems

ESL

ESL
(Cont.)

A-2



















151051

Table A-1: Compatible Two-Wire Smoke Detectors
Manufacturer

Enhance
Mode
Compatible










Compatibility ID

Model Name or Number
(Base model name or number in
parentheses.)

# per Loop
Head

Base

525

FDT1

N/A

17 / loop

525T

FDT1

N/A

17 / loop

SIH-24F (HS-224D or HSB-224)

HD-3

HB-5

25 / loop

SLK-24F (HS-224D)

HD-3

HB-5

25 / loop

SLK-24FH (HS-224D)

HD-3

HB-5

25 / loop

1100

A

N/A

20 / loop

1100T

A

N/A

20 / loop

1100TB

A

N/A

20 / loop

1151 (110LP)

A

A

20 / loop

1400

A

N/A

20 / loop

1451 (B401B)

A

A

20 / loop

1800

A

N/A

20 / loop

1851B (B101B)

A

N/A

20 / loop

1851DH (DH1851DC)

A

N/A

20 / loop

2100

A

N/A

20 / loop

2100T

A

N/A

20 / loop

2100TB

A

N/A

20 / loop

2151 (B110LP or B110LRP)

A

A

20 / loop

2300T

A

N/A

20 / loop

2300

A

N/A

20 / loop

2300TB

A

N/A

20 / loop

2400

A

N/A

20 / loop

2400 (DH400)

A

N/A

20 / loop

2400AIT

A

N/A

20 / loop

2400AT

A

N/A

20 / loop

2400TH

A

N/A

20 / loop

2451 (B401B)

A

N/A

20 / loop

2451DH (DH 400)

A

N/A

20 / loop

2451TH (B401B)

A

N/A

20 / loop

2800

A

N/A

20 / loop

System Sensor

2800TH

A

N/A

20 / loop

(Cont.)

2851B (B101B)

A

A

20 / loop

2851BTH (B101B)

A

A

20 / loop

2851DH

A

A

20 / loop

2851TH (B101B)

A

A

20 / loop

Falcon

Hochiki



System Sensor
















151051

A-3

Model SK-2224 Fire Control Panel Installation/Operation Manual

A.1.3 Four-Wire Smoke Detectors
Table A-2: Compatible Four-Wire Smoke Detectors
Manufacturer

A-4

Model

Silent Knight

SD-P24F with SD-B4@ base

Detection Systems

DS200/DS200HD
MB200

ESL

445 Series
449 Series

Gentex

624
824
2040-24 Power Supervision Unit

System Sensor

1851B
2851/2851BTH
DH200ADCD

151051

A.2 Notification Appliances
The chart below lists notification appliances compatible with the SK-2224.
Table A-3: Compatible Notification Devices
Manufacturer

Model

Type

Amseco

K-MB-6P

6” Bell

Amseco

K-MB-8P

8” Bell

Amseco

K-MB-10P

10” Bell

Faraday

446X 12/24VDC

Vibrating Bell

Faraday

476X 12/24VDC

Vibrating Bell

Faraday

477X 12/24VDC

Single Stroke Bell

Faraday

5303B-0-14-( )-DC

Chime (flush)

Faraday

5304B-0-14-( )-DC

Chime (surface)

Faraday

5305B-0-4-( )-DC

Chime (ceiling)

Faraday

5306B-0-14-( )-24-DC

Chime/Strobe (flush)

Faraday

5307B-0-14-( )-24-DC

Chime/Strobe (surface)

Faraday

5308B-0-4-( )-24-DC

Chime/Strobe (ceiling)

Faraday

5333B-0-14-24-DC

Multi-Tone Horn (flush)

Faraday

5334B-0-14-24-DC

Multi-Tone Horn (surface)

Faraday

5336B-( )-14-24-DC

Multi-Tone Horn/Strobe (flush)

Faraday

5337B-( )-14-24-DC

Multi-Tone Horn/Strobe (surface)

Faraday

5338B-( )-4-24-DC

Multi-Tone Horn/Strobe (ceiling)

Faraday

5343B-0-14-24-DC

Single Tone Horn/Strobe (flush)

Faraday

5344B-0-14-24-DC

Single Tone Horn/Strobe (surface)

Faraday

5345B-0-4-24-DC

Single Tone Horn/Strobe (ceiling)

Faraday

5348B-( )-4-24-DC

Single Tone Horn/Strobe (ceiling)

Faraday

5373B-0-14-24-DC

8-Tone Horn/Strobe (flush)

Faraday

5374B-0-14-24-DC

8-Tone Horn/Strobe (surface)

Faraday

5375B-0-4-24-DC

8-Tone Horn/Strobe (ceiling)

Faraday

5376B-0-14-24-DC

8-Tone Horn/Strobe (flush)

Faraday

5377B-0-14-24-DC

8-Tone Horn/Strobe (surface)

Faraday

5378B-0-4-24-DC

8-Tone Horn/Strobe (ceiling)

Faraday

5405B-0-14-24-DC

Sync Control Unit

151051

A-5

Model SK-2224 Fire Control Panel Installation/Operation Manual

Table A-3: Compatible Notification Devices
Manufacturer

A-6

Model

Type

Faraday

5508B-( )-14-24-DC

Single Gang Sync Strobe (flush)

Faraday

5521B-( )-14-24-DC

4” Square Sync Strobe (surface)

Faraday

5522B-( )-14-24-DC

4” Square Sync Strobe (flush)

Faraday

6126B-U-14-24 VDC

Horn/Strobe

Faraday

6223B-0-14-24-DC

Horn (flush)

Faraday

6224B-0-14-24-DC

Horn (surface)

Faraday

6225B-0-4-24-DC

Horn (ceiling)

Faraday

6226B-( )-14-24-DC

Horn/Strobe (flush)

Faraday

6227B-( )-14-24-DC

Horn/Strobe (surface)

Faraday

6228B-( )-4-24-DC

Horn/Strobe (ceiling)

Faraday

6243B-0-14-24-DC

Electron-Mechanical Horn (flush)

Faraday

6244B-0-14-24-DC

Electron-Mechanical Horn (surface)

Faraday

6245B-0-4-24-DC

Electron-Mechanical Horn (ceiling)

Faraday

6246B-( )-14-24-DC

Electron-Mechanical Horn/Strobe (flush)

Faraday

6247B-( )-14-24-DC

Electron-Mechanical Horn/Strobe (surface)

Faraday

6248B-( )-4-24-DC

Electron-Mechanical Horn/Strobe (ceiling)

Faraday

6300B-0-14-24-DC

Mini-Horn (flush)

Faraday

6301B-0-14-24-DC

Mini-Horn (surface)

Faraday

6302B-( )-4-24-DC

Mini-Horn (ceiling)

Faraday

6310B-0-14-24-DC

Mini-Horn/Strobe/Strobe (flush)

Faraday

6311B-0-14-24-DC

Mini-Horn/Strobe/Strobe (surface)

Faraday

6312B-( )-14-24-DC

Mini-Horn/Strobe/Strobe (ceiling)

Faraday

6320B-0-14-24-DC

Sync Mini Horn/Strobe (1 gang)

Faraday

6321B-0-14-24-DC

Sync Mini Horn/Strobe (1,2 gang)

Faraday

6322B-( )-14-24-DC

Mini Horn/Sync Strobe (1,2 gang, 4SQ)

Federal Signal

450

Horn

Federal Signal

VALS

Horn/Strobe

Gentex

GX90-4

Horn

Gentex

GXS-4-15-1

Strobe

Gentex

GXS-4-1575

Strobe

Gentex

GX90S-4-15

Horn

Gentex

GX90S-4-1575

Horn

151051

Table A-3: Compatible Notification Devices
Manufacturer

Model

Type

Gentex

HG124

Horn

Gentex

SHG24-1575

Horn/Strobe

Gentex

SHG24-15

Horn/Strobe

Gentex

GMH-24-X

Horn

Gentex

GMS-24-X

Horn/Strobe

Gentex

GMS-24-X

Horn/Strobe

Gentex

G0T24

Horn

Gentex

G0S24-X

Horn

Gentex

WGMS-24-X

Horn/Strobe

System Sensor

MASS241

Horn/Strobe

System Sensor

MASS24110ADA

Horn/Strobe

System Sensor

MASS2415ADA

Horn/Strobe

System Sensor

MASS2475ADA

Horn/Strobe

System Sensor

SS4110ADA

Strobe

System Sensor

SS2415ADA

Strobe

System Sensor

SS2475ADA

Strobe

System Sensor

PS2415ADA

Mini-Horn/Strobe

System Sensor

PS241575ADA

Mini-Horn/Strobe

System Sensor

PS24110ADA

Mini-Horn/Strobe

System Sensor

PS2475ADA

Mini-Horn/Strobe

Wheelock

46T-G4-24-R

Bell

Wheelock

46T-G6-24-R

Bell

Wheelock

46T-G10-24-R

Bell

Wheelock

46T-G6-24-WS-24-HF-R

Strobe/Bell

Wheelock

46T-G10-24-WS-24-HF-R

Strobe/Bell

Wheelock

46T-G6-24-WH-24-HF-R

Strobe/Bell

Wheelock

46T-G10-24-WH-24-HF-R

Strobe/Bell

Wheelock

7001T-12\24-W-FR

Strobe Horn

Wheelock

7002T-12\24-W-FR

Strobe Horn

Wheelock

AES-DL1-R

Multitone Horn

Wheelock

AES-EL1-R

Multitone Horn

Wheelock

AES-DL1-WS-24-VF-R

Multitone Horn

151051

A-7

Model SK-2224 Fire Control Panel Installation/Operation Manual

Table A-3: Compatible Notification Devices
Manufacturer

A-8

Model

Type

Wheelock

AES-EL1-WS-24-VF-R

Multitone Horn

Wheelock

AES-DL1-WH-24-VF-R

Multitone Horn

Wheelock

AES-EL1-WH-24-VF-R

Multitone Horn

Wheelock

AES-DL1-WM-24-VF-R

Multitone Horn

Wheelock

AES-EL1-WM-24-VF-R

Multitone Horn

Wheelock

AH-24-R

Horn

Wheelock

AH-24WP-R

Horn

Wheelock

AMT-12\24-R

Strobe Horn

Wheelock

AMT-24-LS-VFR

Strobe Horn

Wheelock

AMT-24-LSM-VFR

Strobe Horn

Wheelock

AMT-24-IS-VFR

Strobe Horn

Wheelock

AS2415W-FR

Audible Strobe

Wheelock

AS241575W-FR

Audible Strobe

Wheelock

AS2430W-FR

Audible Strobe

Wheelock

AS2475W-FR

Audible Strobe

Wheelock

AS24110W-FR

Audible Strobe

Wheelock

AS2415C-FW

Audible Strobe

Wheelock

AS2430C-FW

Audible Strobe

Wheelock

AS2475C-FW

Audible Strobe

Wheelock

AS24100C-FW

Audible Strobe

Wheelock

AS-2415-VFR

Strobe Horn

Wheelock

AS-241575-VFR

Strobe Horn

Wheelock

AS-2430-VFR

Strobe Horn

Wheelock

AS-2475-VFR

Strobe Horn

Wheelock

AS-24110-HFR

Strobe Horn

Wheelock

SM-12/24-R

Strobe Horn Controller

Wheelock

DSM-12/24-R

Strobe Horn Controller

Wheelock

CF-BF1

Chime

Wheelock

CF-BF1-R

Chime

Wheelock

CH70-24-R

Chime

Wheelock

CH90-24-W

Chime

Wheelock

CH70-2415W-FR

Chime Strobe

151051

Table A-3: Compatible Notification Devices
Manufacturer

Model

Type

Wheelock

CH70-241575W-FR

Chime Strobe

Wheelock

CH70-2430W-FR

Chime Strobe

Wheelock

CH70-2475W-FR

Chime Strobe

Wheelock

CH70-24110W-FR

Chime Strobe

Wheelock

CH-CF1

Chime

Wheelock

CH-CF1-R

Chime

Wheelock

CH-CF1-W

Chime

Wheelock

CH-DF1

Chime

Wheelock

CH-DF1-R

Chime

Wheelock

CH-BF1-WS-24-HF-R

Strobe Chime

Wheelock

CH-CF1-LS-24

Strobe Chime

Wheelock

CH-CF1-MS-24

Strobe Chime

Wheelock

CH-CF1-IS-24

Strobe Chime

Wheelock

CH-CF1-LS-24-CFW

Strobe Chime

Wheelock

CH-CF1-MS-24-CFW

Strobe Chime

Wheelock

CH-CF1-IS-24-CFW

Strobe Chime

Wheelock

CH-CF1-WS-24-CF-W

Strobe Chime

Wheelock

CH-DF1-LS-24

Strobe Chime

Wheelock

CH-DF1-MS-24

Strobe Chime

Wheelock

CH-DF1-IS-24

Strobe Chime

Wheelock

CH-DF1-LS-24-VFR

Strobe Chime

Wheelock

CH-DF1-LSM-24-VFR

Strobe Chime

Wheelock

CH-DF1-MS-24-VFR

Strobe Chime

Wheelock

CH-DF1-IS-24-VFR

Strobe Chime

Wheelock

CH-DF1-WM-24-VFR

Strobe Chime

Wheelock

CH-DF1-WS-24-VF-R

Strobe Chime

Wheelock

DSM-12/24

Sync Module

Wheelock

EH-DL1-R

Electronic Horn

Wheelock

EH-EL1-R Electronic Horn

Electronic Horn

Wheelock

EHS-DL1-W-VF-R

Strobe Horn (single input)

Wheelock

EHS-EL1-W-VF-R

Strobe Horn (single input)

Wheelock

EH-DL1-WS-24-VF-R

Strobe Horn (dual input)

151051

A-9

Model SK-2224 Fire Control Panel Installation/Operation Manual

Table A-3: Compatible Notification Devices
Manufacturer

A-10

Model

Type

Wheelock

EH-EL1-WS-24-VF-R

Strobe Horn (dual input)

Wheelock

EH-DL1-WH-24-VF-R

Strobe Horn (dual input)

Wheelock

EH-EL1-WH-24-VF-R

Strobe Horn (dual input)

Wheelock

EH-DL1-WM-24-VF-R

Strobe Horn (dual input)

Wheelock

EH-EL1-WM-24-VF-R

Strobe Horn (dual input)

Wheelock

HSW-24-HFR

Remote Strobe

Wheelock

HS2W-24-HFR

Remote Strobe

Wheelock

HSPW-24-HFR

Remote Strobe

Wheelock

IS-24-VFR

Remote Strobe

Wheelock

IS1-24-VFR

Remote Strobe

Wheelock

IS3-24-VFR

Remote Strobe

Wheelock

ISP-24-HFR

Remote Strobe

Wheelock

LS-24-VFR

Remote Strobe

Wheelock

LS1-24-VFR

Remote Strobe

Wheelock

LS3-24-VFR

Remote Strobe

Wheelock

LSP-24-HFR

Remote Strobe

Wheelock

LSM-24-VFR

Remote Strobe

Wheelock

LS1M-24-VFR

Remote Strobe

Wheelock

LS3M-24-VFR

Remote Strobe

Wheelock

LSPM-24-VFR

Remote Strobe

Wheelock

MS-24-VFR

Remote Strobe

Wheelock

MS1-24-VFR

Remote Strobe

Wheelock

MS3-24-VFR

Remote Strobe

Wheelock

MSP-24-HFR

Remote Strobe

Wheelock

MB-G6-24-R

Motor Bell

Wheelock

MB-G10-24-R

Motor Bell

Wheelock

MBS-G6-24-W-HF-R

Motor Bell with Strobe

Wheelock

MBS-G10-24-W-HF-R

Motor Bell with Strobe

Wheelock

MIZ-24-R

Mini-Horn

Wheelock

MIZ-24-W

Mini-Horn

Wheelock

MIZ-24-LS-VFR

Mini-Horn/Strobe

Wheelock

MIZ-24-LSM-VFR

Mini-Horn/Strobe

151051

Table A-3: Compatible Notification Devices
Manufacturer

Model

Type

Wheelock

MIZ-24-MS-VFR

Mini-Horn/Strobe

Wheelock

MIZ-24-HSW-HFR

Mini-Horn/Strobe

Wheelock

MIZ-24-IS-VFR

Mini-Horn/Strobe

Wheelock

MIZ-24-WS-VF-R

Mini-Horn/Strobe

Wheelock

MIZ-24-WS-VF-W

Mini-Horn/Strobe

Wheelock

MIZ-24-WH-VF-W

Mini-Horn/Strobe

Wheelock

MIZ-24-WM-VF-W

Mini-Horn/Strobe

Wheelock

MT-12/24-R

Strobe Horn

Wheelock

MT4-12/24-R

Multitone Appliance

Wheelock

MT4-115-R

Multitone Appliance

Wheelock

MT-24-LS-VFR

Strobe Horn

Wheelock

MT-24-LSM-VFR

Strobe Horn

Wheelock

MT-24-MS-VFR

Strobe Horn

Wheelock

MT-24-IS-VFR

Strobe Horn

Wheelock

MT-24-SL-VFR

Strobe Horn

Wheelock

MT-24-SLM-VFR

Synch. Multitone Strobe

Wheelock

MT-24-WM

Strobe

Wheelock

MT-24-WM-VF-R

Horn

Wheelock

MT-24-WM-VFR

Strobe Horn

Wheelock

NH-12/24-R

Horn

Wheelock

NS-2415W-FR

Strobe Horn

Wheelock

NS-241575W-FR

Strobe Horn

Wheelock

NS-2430W-FR

Strobe Horn

Wheelock

NS-2475W-FR

Strobe Horn

Wheelock

NS-24110W-FR

Strobe Horn

Wheelock

NS4-2415W-FR

Strobe Horn

Wheelock

NS4-241575W-FR

Strobe Horn

Wheelock

NS4-2430W-FR

Strobe Horn

Wheelock

NS4-2475W-FR

Strobe Horn

Wheelock

NS4-24110W-FR

Strobe Horn

Wheelock

RS-2415W-FR

Strobe

Wheelock

RS-2415W-FR

Strobe

151051

A-11

Model SK-2224 Fire Control Panel Installation/Operation Manual

Table A-3: Compatible Notification Devices
Manufacturer

A-12

Model

Type

Wheelock

RS-241575W-FR

Strobe

Wheelock

RS-2415-HFR

Strobe

Wheelock

RSP-2415-VFR

Strobe

Wheelock

RS-241575-VFR

Strobe

Wheelock

RSP-241575-VFR

Strobe

Wheelock

RS-2430-VFR

Strobe

Wheelock

RS-2430-HFR

Strobe

Wheelock

RS-2475-VFR

Strobe

Wheelock

RSP-2475-HFR

Strobe

Wheelock

RS-24110-HFR

Strobe

Wheelock

RSP-24110-HFR

Strobe

Wheelock

RSS-2415W-FR

Strobe

Wheelock

RSS-241575W-FR

Strobe

Wheelock

RSS-2430W-FR

Strobe

Wheelock

RSS-2475W-FR

Strobe

Wheelock

RSS-24110W-FR

Strobe

Wheelock

RSS-2415C-FW

Strobe

Wheelock

RSS-2430C-FW

Strobe

Wheelock

RSS-2475C-FW

Strobe

Wheelock

RSS-24100C-FW

Strobe

Wheelock

RSSP-2415W-FR

Strobe

Wheelock

RSSP-241575-FR

Strobe

Wheelock

RSSP-2430W-FR

Strobe

Wheelock

RSSP-2475W-FR

Strobe

Wheelock

RSSP-24110W-FR

Strobe

Wheelock

SL-24-VFR

Synchronized Remote Strobe

Wheelock

SL1-24-VFR

Synchronized Remote Strobe

Wheelock

SL3-24-VFR

Synchronized Remote Strobe

Wheelock

SLP-24-VFR

Synchronized Remote Strobe

Wheelock

SLM-24-VFR

Synchronized Remote Strobe

Wheelock

SL1M-24-VFR

Synchronized Remote Strobe

Wheelock

SL3M-24-VFR

Synchronized Remote Strobe

151051

Table A-3: Compatible Notification Devices
Manufacturer

Model

Type

Wheelock

SLPM-24-VFR

Synchronized Remote Strobe

Wheelock

SHW-24-VFR

Synchronized Remote Strobe

Wheelock

SH2W-24-VFR

Synchronized Remote Strobe

Wheelock

SHPW-24-VFR

Synchronized Remote Strobe

Wheelock

SCM-24-R

Controller for Synchronized Strobes

Wheelock

SM-12/24-R

Sync Module

Wheelock

SR-2415-VFR

Sync Strobe

Wheelock

SRP-2415-HFR

Sync Strobe

Wheelock

SR-241575-VFR

Sync Strobe

Wheelock

SRP-241575-VFR

Sync Strobe

Wheelock

SR-2475-VFR

Sync Strobe

Wheelock

SR-2475-HFR

Sync Strobe

Wheelock

SR-24110-HFR

Sync Strobe

Wheelock

SRP-24110-HFR

Sync Strobe

Wheelock

V7001T-12\24-W-FR

Strobe Horn

Wheelock

WM3T-24-FR

Remote Strobe

Wheelock

WM3T-24-VFR

Remote Strobe

Wheelock

WS1T-24-FR

Strobe

Wheelock

WS3T-24-FR

Strobe

Wheelock

WST-24-FR

Strobe

151051

A-13

Model SK-2224 Fire Control Panel Installation/Operation Manual

A-14

151051

Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
•

All new fire products manufactured by Silent Knight after September 1, 1997 have a
limited warranty period of 18 months from the date of manufacture against defects in
materials and workmanship. See limited warranty statement for details.

•

This limited warranty does not apply to those products that are damaged due to misuse,
abuse, negligence, or have been modified in any manner whatsoever.

Repair and RA Procedure
•

All products that are returned to Silent Knight for credit or repair require a RA (Return
Authorization) number. Call Silent Knight Customer Service at 800-446-6444 or 612-4936435 between 8:00 A.M. and 5:00 P.M. CST, Monday through Friday to obtain a return
authorization number. Silent Knight Technical Support is available at 800-328-0103
between 8:00 A.M. and 7:00 P.M. CST, Monday through Friday.

•

RA number must be prominently displayed on the outside of the shipping box. See return
address example under Advanced Replacement Policy.

•

All products returned to Silent Knight must be sent freight pre-paid. After product is
processed, Silent Knight will pay for shipping product back to customer.

•

Return the Silent Knight product circuit board only. Products that are returned in cabinets
will be charged an additional $20 to cover the extra shipping and handling costs over
board only returns. Do not return batteries. Silent Knight has the authority to determine if
a product is repairable. Products that are deemed un-repairable will be returned to the
customer.

•

Product that is returned that has a board date code more than 18 months from date of
manufacture will be repaired and the customer will be assessed the standard Silent Knight
repair charge for that model.

•

A detailed description of the problem should be included with each return.

Advanced Replacement Policy
•

Silent Knight offers an option of advance replacement for fire product printed circuit
boards that fail during the 18 month warranty period.

•

For advance replacement of a defective board call Silent Knight at 800-446-6444 or
612-493-6435 to obtain a RA (Return Authorization) number and request advanced
replacement.

•

Customers must use a MasterCard or Visa credit card to get an advance replacement.

151051

Model SK-2224 Fire Control Panel Installation/Operation Manual

•

A new or refurbished board will be shipped to the customer. The customer will initially be
billed for the replacement board but a credit will be issued after the repairable board is
received at Silent Knight.

•

The defective board must be returned within 30 days of shipment of replacement board for
customer to receive credit. No credit will be issued if the returned board was damaged due
to misuse or abuse.

•

Repairs and returns should be sent to:
Silent Knight
Attn: Repair Department
7550 Meridian Circle
Maple Grove, MN 55369-4927
RA Number:___________________

Limited Warranty
Silent Knight warrants that the products of its manufacture shall be free from defects in materials or
workmanship for 18 months from the manufacturing date code on the printed circuit board, if such
goods have been properly installed, are subject to normal proper use, and have not been modified in
any manner whatsoever. Upon return of the defective product to the nearest Silent Knight, Silent
Knight will, at its sole discretion, either repair or replace, at no cost, such goods as may be of defective
material or workmanship. Customers outside the United States are to return products to their
distributor for repair.
SILENT KNIGHT SHALL NOT UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY
INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING FROM LOSS OF PROPERTY OR
OTHER DAMAGE OR LOSSES OWING TO THE FAILURE OF SILENT KNIGHT SECURITY
SYSTEMS PRODUCTS BEYOND THE COST OF REPAIR OR REPLACEMENT OF ANY
DEFECTIVE PRODUCTS.
SILENT KNIGHT MAKES NO WARRANTY OF FITNESS OR MERCHANTABILITY AND NO
OTHER WARRANTY, ORAL OR WRITTEN, EXPRESS OR IMPLIED, BEYOND THE 18
MONTH WARRANTY EXPRESSLY SPECIFIED HEREIN.

151051

SK-2224 Basic Operating Instructions P/N 151055
These instructions must be framed and displayed next to the SK-2224 panel in accordance
with NFPA 72 fire code for Local Fire Alarm System.

Cut Along the Dotted Line

LED (Color)

Function

AC (green)

ON = Good AC
OFF = Low AC trouble condition and it was acknowledged
FLASHING = Unacknowledged AC Low trouble condition

GENERAL TROUBLE
(yellow)

ON = System trouble
OFF = System OK
FLASHING = At least one serial device is in trouble
DOUBLE FLASHING = Two types of serial devices are in trouble.

WALK TEST (yellow)

ON = Walk test is in progress
OFF = Walk test is off.
FLASHING = Walk test is on and at least one zone is not ready

GND FAULT (yellow)

ON = Ground fault condition exists and was acknowledged
OFF = No fault
FLASHING = A ground fault condition detected

LOW BATTERY (yellow)

ON = Battery low condition that has been acknowledged
OFF = Good battery condition
FLASHING = Battery low condition

ZONE 1 ALARM (red)
and
ZONE 2

ON = Zone in alarm which has been acknowledged
OFF = No Alarm
FLASHING = Zone in alarm has not yet been acknowledged.

SUPERVISORY
(yellow)

ON = Zone has a supervisory condition (self-restoring condition)
OFF = No supervisory condition exists.
FLASHING = supervisory trouble detected on that zone.

TROUBLE
(yellow)

ON = Zone has a trouble condition which has been acknowledged
OFF = No zone trouble
FLASHING = Zone has a trouble condition
DOUBLE FLASHING = Zone was disabled
CLEAN ME FLASHING = Indicates that the smoke detector needs cleaning (LED is on long and

Off for a short time period)
NAC 1
and
NAC 2

ACTIVE (yellow) ON = NAC is active during an alarm
OFF = NAC is not active during alarm
TROUBLE
(yellow)

SYSTEM SILENCED
(yellow)

ON = NAC has a trouble condition and was acknowledged
OFF = No trouble condition
FLASHING = NAC is in trouble
DOUBLE FLASHING = Circuit was disabled
ON = System audio output has been silenced
OFF = Nothing silenced
FLASHING = Partially silenced

Operation

Keystrokes

Disable notification appliance circuit.
To re-enable the circuit, press [NAC
DISABLE] again.

Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding
TROUBLE LED will Double Flash. This function is not available during an alarm condition.

Disable a zone
To re-enable the circuit, press [ZONE
DISABLE] again.

Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the corresponding TROUBLE
LED will Double Flash. This function is not available during an alarm or supervisory condition.

Begin Walk Test

Press [WALK TEST]. Walk Test LED turns on.
Note:
Walk test will not activate if the control panel has a trouble, alarm, or supervisory condition.

End Walk Test

Press [WALK TEST].
NOTE: The Walk Test feature is not operational during an alarm, supervisory or any system trouble
condition.The test ends automatically after 10 minutes of no system activity.

Acknowledge condition (alarm, supervisory,
trouble)

Press [ACK]. The corresponding LED will change from blinking to steady for the duration of the condition.

Silence Panel

Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits that have been configured as
"silenceable".

Perform system reset

Press [RESET]. Resets alarms, supervisories, troubles and all LEDs.
For Service Contact:

Cut Along the Dotted Line



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : Yes
Create Date                     : 1998:07:08 17:02:24
Producer                        : Acrobat Distiller 3.0 for Windows
Creator                         : PSCRIPT.DRV Version 4.0
Title                           : 151051.book
Modify Date                     : 2000:05:10 09:39:50
Page Count                      : 52
Page Mode                       : UseThumbs
EXIF Metadata provided by EXIF.tools

Navigation menu