4120XM PROGRAMMING FORM Program Sheet

User Manual: 4120XM Program Sheet AlarmHow.net Library

Open the PDF directly: View PDF PDF.
Page Count: 4

~ADHVICOJ 4120XM PROGRAMMING FORM
SUMMARY OF PROGRAMMING COMMANDS
,To enter program mode, enter installer code +[8] +[0] +[0]. Enter first field address to begin programming.
ITo set standard defaults, press 97
ITo set communication defaulta, press *94 +one of the following: 80=Iow speed; “81 =Ademco Express; “82=Ademco High Speed;
83=Ademco’s Contact ID
~To change to 2nd page of program fields, press 94
.To return to 1st page of fields, press 99
To erase account &phone number field entries, press ~] +field number +~]
DTo assign zone descriptors, press “93 +zone number
.To add custom words, press 93 +00+ word number (1-20)
.To enter Installer’s Message, press 93 +00 +00
.To exit program mode, press 99 OR 98: 99 allows re-access to programming mode by installer code. 98 prevents re-access to
programming mode by installer code.
oDefault values are shown in brackets [1: otherwise default= O
*OO INSTALLER CODE ill J
Enter 4digits, o-9 [4120]
*O1 MASTER SECURITY CODE Ill
Enter 4digits, O-9 [1234] Sss1 ’54 for 6-digit enable
ASSIGN RESPONSE TYPE FOR ZONES
(Enter 00-10; see Response Types fable below)
Hard-Wire zones =1-8; Wireless zones= 1-83 plus
RF Receiver zones 88-91
(1+*)
(3+ #)
(*+ #)
00= Assign for unused zones 06= 24-HOUR SILENT
01 =ENTRYKXIT #1 07= 24-HOUR AUDIBLE
02= ENTRYEXIT #2 06= 24-HOUR AUXILIARY
03= PERIMETER
04= INTERIOR, FOUOWER 09= FIRE
10= INTERIOR, DEfAY
05= DAY/NIGHT
O9
*lo
11
12
13
*I4
15
16
17
18
’19
21
;Fd.., . .. . . . . . . . . . . .
..,..-.:Q&Nqmg~Em&
ENTRY DELAY #1 [02] (IX-IS times 15 seconds) El
EXIT DELAY #1 [W (00-15 times Is seconds) I_JJ
ENTRY DELAY %?[061(rxH5 tiMSS 15 sSCW@S) El
EXIT DELAY #2 [061(00-15 LfMeS 15 seconds) III
ALARM SOUNDER DURATION ml
01- I5times 2minutes [04]. Minimum 4minutes for UL.
ZONE 8FAST/SLOW RESPONSE [Oaslow];l=fast
KEYSWITCH ENABLE [O=disable~ l=enatie •1
(ALSO SEE ADDRESS 1*57, TRIGGER MODE)
CONFIRMATION OF ARMING DING •1
1-enable:[O-disable]
AC POWER LOSS SOUNDING l-yew [t)=flo] •1
AC POWER LOSS ALARM 1.YSS:[c-m] •1
AC RANDOMIZE I.randomize 10-40 min.; [&no] •1
DISABLE FIRE TIME-OUT I-no rimeouc [0.firs timeout]
*23 MULTIPLE ALARMS [t.yes]; c==no u
25
*26
*27
28
29
*3O
31
32
33
:;2w.N:aEjusEuiNM.
BURG. lRIGGER FOR ZONE RESPONSE TYPE
O-disable [l=ensble]
INTELLIGENT TEST REPORTING Set‘o” for UL
1-yes, (no report sent if any other report was recently sent); [O=no]
TEST REPORT INTERVAL w
Enter intend in hours, 001-199; 000=no report [024]: Max. 024 for UL.
POWER UP IN PREVIOUS STATE
[l=yes~O=nQ“1”forUL.
QUICK ARM [l=ySS~&=f10 •1
TOUCH-TONE OR ROTARY DIAL •1
I=TouchTorr& [O~tary] See field 1%3 for Touch-Tone w/Rotary backup
pAf3x ACCiSS tiDE IT ml ~\ ~]
00-0%8-F (11-15)
PRIM. SBSCRBRACCT# IT ~ ~ ml
Enter &O% B-F(ll-15) [15 1515 la
PRIMARY PHONE NUMBER
lclclclclclclclclc lclm
Enter O-9 for each digit
34 SECONDARY PHONE NUMBER
lnclclclnclclclnc lcl
Enter O-9 for eachdigit
’35 DOWNLOAD PHONE No. nnnmnr]
Enter o-9 for each digit ICICIUCID
36 DOWNLOAD ID No. ml ml ~ml
EHIHIIEI
Enrer OO-@A-F(10-15) [1515151615151515]
*37 DOWNLOAD COMMAND ENABLES [l-enable]; ~isable
See field 1“53 for Callback disable option. For UL installations, Upload&
Download must be enabled. All othecs must be disabled.
UDmler shutdown
system Shutdown
III Not Used
Remote Bypass
uRemote Disarm
•1 RemoteArm
Upload Program
•1 Download Program
-A- 4120XM-PR 9/92 (See Instructions N6493)
38
*39
4O
41
*42
’43
44
*45
INHIBIT BYPASS OF AZONE m
01-31; [00 if all zones (except Fire zones) can be bypassed]
*47
*48
*49
SECONDARY FORMAT u
[O-LOWx; l-Contact ID; 2=Ademco High Spe@ 3-Adernco EKXSSS
LOW SPEED FORMAT (See.) •1
fo=Ademco Low Soeedl: I=Sesma/Radionics
OPEN/CLOSE REPORTS FOR ZONES 1-8 l-yes; o=no
00000000
OPEN/CLOSE REPORTS FOR ZONES 9-16 l.yes: o=rw
O; L&LA;;
CHECKSUM tiERI’iCATION n
1ye% [&no] Primary Scndry
SESCOM3ADIONICS t-seems; [o= R.sdionica] •1
DUAL REPORmNG •1
1=yeq [0.=no] If used witi Spilt Reporting “1” option (1%4), alarms go
to both primary i? semnday numbers, while all orfter reports go to
secondary only. If used with Split Reporting Z? option, open/dose and
test messages go to both lines, while all other reports go to primary.
STANDARDEXPANDED REPORT FOR PRIMARY
’50
910 11 12 13 14
EOLR DISABLE (Zones 2-8) b
[I =N.C.lWps]; O=EOLR supervkion; Must be “O” for UL.
DIAL TONE PAUSE [o-5 scsj; 1-11 SC%2-30S=; V’fOr UL •1
DIAL TON EDETECT [1-wsit tor dial tone]; o-pause, then dial
’51
’52
53
Jclclclclcl
Alarm Rstr Bypass Trbl OprVCls Low Bat
[O&andard]; 1=expanded; Note Expanded overrides 4+2 format.
STANDARDIEXPANDED REPORT FOR SECONDARY
cloclucl
RING DETECTION COUNT 1--1
01-14: 15=answering machine; [OO=no detection]
PRIMARY FORMAT r-l
~
[O-LOW Speed]; I=Ccoract ID; 2=Ademm High Speed: 3.Ademm Express
46 LOW SPEED FORMAT (Primary) •1 Alarm Rstr Bypass Trbl OprVCls Low Bat
[O=standard]; I=expanded: Note: Expended overrides 4+2 format.
[O=Ademm Low Speed]; 1=SesmdRadionics
ALARM REPORT CODE &ID DIGITS
[All cctdes default to 00]
FOR ZONES 1-32 &SUPERVISORY &RESTORE CODES
54 CODE 55 ID *56 CODE *57 ID *58 *59 CODE *6O [D
f-ii
[---I--I
{Tl
m
l-i-l
m
61 CODE 62 ID 63
El
ml
ml
i---l-l
ml
ml
I [ IAksrmRst.
ml Trouble
II]Trble Rs,
~1 BYPSSS
[~{ ByPseRst
ml
ml
-B-
1*26
1*27
1’28
1*29
1’30
1*31
FIRST RF RECEIVER SELECT I=Yes;[o=no]
SECOND RF RECEIVER SELECT I.yes; [o.no]
RF TF!ANSMlllER LOW BATTERY ANNUN.
I=immediate; [O=when disarmed] Must be “1” for UL
RF TRANSMllTER LO BAT REPORT ENABLE
I=enable [o=disable] Must be “1” for UL
RF RECEIVER SUPERVISION CHECK-IN
INTERVAL OZ-I 5times zhours;
00 disables supervision [6] Max. ‘6”(12 hr) for UL
u
•1
•1
•1
RF TRANSMllTER CHECK-IN INTERVAL II
02-15 times 2hours;
00 disables transmitter supervision [12] Max. “6- (12 hr) for UL
l“3zj”y3T’~~jyj:
I33 TOUCH-TONE W/ROTARY •1
BACKUP ENABLE I=enabl% [o~lsabie]
1‘34 COMM. SPLIT REPORT SELECTION
[O=no];1=alarmsprimary,otherssecondaty;
2=open/close, test secondary, others primary; See “5I for comments.
,,,:;~~~Q~Qs,~@.
:$.*35 :.....*..
.,,%1;::39*- ,.
ARMED STAY DIALER REPORT
1*4O 1*41
First Digit Second Digit
Armed Stay ~] ~~
This report will be senr for any Low Speed formal.
If Ademco High Speed is used, anormal closing reporl will be sent.
If Camact ID is used, anew code, R441, will be sent. 685 Receivers that do not
have revision 4.5 or higher will prim an error message in place of the English
text.
1*44
1*45
1’46
1447
1*48
RF KEYPAD TAMPER DETECT l.yes; [o=no]
ENABLE CONSOLE ANNUN.
DURING EXIT DEIAY I=enable: [O=disable]
AUXILIARY OUTPUT ENABLE
O-groundstart;1=opeticlosetrigger(TERM9);2=Notused;
[%Zone IEOLR]
ENABLE CHIME ANNUN. ON EXTERNAL
ALARM SOUNDER I.enable: [o=dkable]
WIRELESS KEYPAD DISABLE
l-disable; [O-enable]
•1
1*49
1’50
1“51
1“52
DISABLE TROUBLE SOUNDER FOR RF •1
SUPERVISION [l=diaable]; ~nable. Must be ‘0- for UL.
BABYSITTER CODE l.entia [0.dkable~(userWI
4281 HOUSE ID Enter 01-31 m
CANCEL REPORT RESTRICTION n
140 restriction; [O=wilhin Bell Timeout period only]
1“53 DOWNLOAD CALLBACK
1=dlback not required: [O=callback required]; Must be “O. for UL.
I54 HIGH SECURITY MODE
l=s-digit high SeCUriM [0=4-digit normal]
1.57 75 Trigger
I
Trigger
Trigger Mode Keyswitch output 1output 2
II1KEYSWfTCH KEYSWfTCH
ARMED LED READY LED
c1
•1
Trigger
output 3
BURG LRR
TRIGGER
10FIRE LRR PANfC LRR
TRIGGER TRIGGER
It1KEYSWITCH KEYSWITCH
ARMED LED READY LED
30FIRE LRR REMOTE
1not allowed TRIGGER SOUNDER
II I n
ZONE 6
GLASS
BREAK
RESET
BURG LRR
TRIGGER
ZONE 6
GIASS
BREAK
RESET
NOTE: fi=ADDRESS 1’57 IS SET FOR2OR3,ADDRESS“15 MUST BE O.
•1
•1
•1
158 4219A FIF?STZONE NUNBER [00],09-57 L-!_l
Set to 00 if no 4219s used. it using a4219, set kJ Ist zone #which will be assigned
to zone A on 4219. Remaining 7zones on 4219 will be the next 7zme ss.
159 4219B FIRST ZONE NUMBER [00],09-57 I-i--l
Set 00 if no 2nd 4219 used. If using a2nd 4219, set to 1st zone #which will be
assigned to zone Aon2ml 4219. Remaining 7zones on 2nd 4219 will be the next
7zone #e.
HEXADECIMAL TO NUMERIC ENTRY CONVERSION
O=10 (REPORT CODES)
O=00 (SU8S ID, PABX OR DOWNLOAD ID)
1=01,2=02,3=03,4=04,5=05,6=06, 7=07,8=08,9=09,
B=ll, C=12, D=13, E=14, F=15,
A=10 (DOWNLOAD ID ONLY)
(!2u31wIc01
ADivision of Pittway Corporation
165 Eileen Way, Syosset, New York 11791
Copyright @1992 PflTWAY CORPORATION 4120XM-PR 9/92