ElectricalParticipant Toaster 4 Electrical Safety Participant Guide
User Manual: Toaster
Open the PDF directly: View PDF .
Page Count: 26
Download | |
Open PDF In Browser | View PDF |
FOCUS 4 CONSTRUCTION SAFETY & HEALTH Electrical Safety Participant Guide This material was produced under grant number SH-16586-07-06-F-36 from the Occupational Safety and Health Administration, U.S. Department of Labor. It does not necessarily reflect the views or policies of the U.S. Department of Labor, nor does mention of trade names, commercial products, or organizations imply endorsement by the U.S. Government. SECTION #4 Curriculum on Electrical Safety mGOALm To provide a basic understanding of how electricity works and how to protect ourselves from common electrical hazards, both on and off the job. INTRODUCTION Electrocution is the fourth leading cause of work-related death for construction workers. On average, one worker is electrocuted on the job every day in the United States. SCOPE AND LIMITATIONS This training curriculum is primarily designed for workers without any formal training on electricity, although electricians may also benefit from a review. The document focuses on some of the fundamentals of electricity, electrical wiring, electric tools, protective methods and devices, and related work methods and safe practices in the construction industry. The material is presented using an interactive training method. The curriculum focuses on common AC wiring, as found in homes and on construction sites. It also includes information on power line safety. This curriculum is not all-inclusive. It does not cover every electrical hazard nor does it describe every applicable OSHA electrical standard. ACKNOWLEDGMENTS We have drawn extensively from several sources in preparing this material. These include: ● Electrical Safety for Non-Electricians, by CSEA/Local 1,000 AFSCME ● Electrical Safety: Safety and Health for Electrical Trades, by NIOSH ● Thanks to the Construction Safety Council for permission to use their information on power line safety. ● Various training materials found on OSHA and NIOSH websites. SECTION #4 | Participant Guide 1 Electrical Safety mELECTRICAL SAFETYm mACTIVITY 1 – GROUNDINGm In your small group, read fact sheets A and B, and the following scenario. Then answer the questions below. SCENARIO: You encounter a co-worker on a residential remodeling job. She has an older drill with a steel housing and a 3-prong plug. The wiring in the building has only two-slot receptacles – with no “equipment ground” slot. She is just about to break off the grounding prong on the tool’s plug with a pair of pliers when you ask her to stop. 1. What do you say to your co-worker about this problem? Safe Work: GROUNDED tool with 3-prong POLARIZED plug, GROUNDED receptacle. 2. What can you do to correct this problem? 3. What is the best way to deal with this? SECTION #4 | Participant Guide 2 Electrical Safety mACTIVITY 1 – GROUNDINGm Factsheet A – Two Ways to Wire an Electric Tool OSHA CONSTRUCTION INDUSTRY STANDARDS SAY: 1926.302 (a) Electric power-operated tools. 1926.302 (a) (1) Electric power operated tools shall either be of the approved double-insulated type or grounded in accordance with Subpart K of this part. WHAT DOES THAT MEAN? There are two different ways of wiring an electrical tool: double insulation or the use of equipment grounding. First of all, the individual wires in the tool and cord are insulated and the cord itself is also insulated. These are the first level of insulation. With the double insulation method, the manufacturer provides a second level of insulation inside the tool, to reduce the risk of a damaged “hot” wire within the tool (generally at 120 volts AC) from coming in contact with any exposed metal on the tool. Double insulation protects you by providing another insulation barrier, preventing a wiring defect that could allow an energized conductor to touch any metal on the tool that you can touch. A double insulated tool will be marked on its handle or on a data label with the words “Double Insulated” or with a symbol: a square box within a box. With the equipment grounding method, a third wire is added to the tool’s wiring and connected to a round pin on the tool’s plug. The other end of this grounding wire is connected to the metal frame of the tool. The 3-conductor plug on the tool must be plugged into a grounded outlet. The equipment ground connection on the outlet must be connected to a grounding connection at the electrical panel. The steel electrical panel is then connected to the earth. This is generally done via clamping a system ground wire to a METAL cold water pipe or to ground rods driven into the earth. Equipment grounding only works when there is a permanent and continuous electrical connection between the metal shell of a tool and the earth. If a wiring defect in the tool allows an energized wire to touch the tool’s metal shell, grounding provides a low resistance path to earth for the resulting current. This will generally allow enough current to flow so that a fuse will blow or a circuit breaker is tripped, thus turning off the electricity in that circuit. If this grounding path is broken at any point, the tool is NOT GROUNDED and the operator is at risk of shock or electrocution. All electrical tools and equipment must be maintained in safe condition and checked regularly for defects. They must be taken out of service if a defect is found. SECTION #4 | Participant Guide 3 Electrical Safety mACTIVITY 1 – GROUNDINGm Factsheet B – Install a Grounded Outlet Occasionally you will encounter a building with older wiring, having receptacles with only two slots (called “hot” and “neutral”). These older receptacles don’t contain a round slot for the “equipment ground.” If you have a tool with a 3-prong plug, this is a problem. The best solution is to have a licensed electrician install one or more grounded outlets. Of course, this will take some time and money. Is there anything else you can do instead? Here are three possibilities: In the United States (but not in Canada) you can buy a 3-prong adaptor. This is not a good idea unless you’re sure of what you’re doing. These adaptors generally come with either a small metal tab (to be attached to the screw securing a receptacle to its box cover) or with a short wire (often with green insulation and a thin, bare lug at the end of the wire). In theory, you can attach the metal tab or the grounding wire to a grounded screw in a grounded receptacle, thereby getting your equipment ground connection. If you don’t know what you’re doing, such as, if there’s no proper ground at the receptacle, there is no equipment ground, therefore, no protection from electrical shock. Another possible alternative is to get your power from a grounded generator supplying a 120 volts AC grounded outlet. (Of course, your generator must be outdoors so hazardous engine exhaust can’t enter your work area, and you’ll need a grounded extension cord.) Finally, you could do your work with cordless tools, operating at a relatively low DC voltage with re-chargeable batteries. This method would eliminate the 120 volts AC electrical hazard you’d otherwise encounter. NEVER break off a grounding prong from a 3-conductor plug. Your tools will still work, but you will have NO PROTECTION from a dangerous electrical shock in the event of an electrical defect in the tool! SECTION #4 | Participant Guide 4 Electrical Safety mELECTRICAL SAFETYm mACTIVITY 2 – IMPROPER WIRING / REVERSED POLARITYm In your small group, read fact sheets C and D, and the following scenario. Then answer the questions below. SCENARIO: You are a supervisor in a small construction company. A worker passing you in a hallway mentions that he thought he just felt a “tingle” after he plugged in an old floor lamp. He had touched a metal shell, the outside housing around a socket for the light bulb. You ask him to take you to the lamp. You unplug it and notice a two-prong plug, with both prongs the same size. You tell the worker, “I think I know what happened. We’ll get this fixed. Let me explain it to you.” 1. What is your explanation to the worker? Possibly Unsafe: 2-prong NONPOLARIZED plug – could be plugged-in “backwards” and result in electric shock if lamp is defective (see text). 2. What are some steps to deal with this issue? 3. What is the best way to correct the problem? SECTION #4 | Participant Guide 5 Electrical Safety mACTIVITY 2 – IMPROPER WIRING / REVERSED POLARITYm Factsheet C – Conductors, Connections and Polarity It takes a minimum of two wires to have an electrical circuit. Electric current involves the flow of electrons. Current is measured in amperes (amps for short). It travels from a source, through the device it operates, called the load, and then back to the source. In AC wiring, present in buildings, there is voltage present on the “hot” wire (generally at about 120 volts AC). Voltage provides the force that allows electrons to flow in a circuit. Switches on electrical devices are supposed to be wired only on the hot or live side of the circuit. The return conductor, known as the neutral, is at zero volts because it is deliberately grounded at the electrical panel. [See Activity 1 for more about electrical grounding.] The amount of current that flows in a circuit depends on its electrical resistance, or opposition to current flow, measured in ohms. In an electrical shock, the amount of electrical current, in amps, that flows through your body goes up when resistance in ohms goes down. The Current in Amps = Voltage in Volts DIVIDED BY Resistance in Ohms. HIGHER VOLTAGE = more current (if resistance remains the same). LOWER RESISTANCE = more current (if voltage remains the same). Newer electric plugs have blades that are polarized, so the hot wire on the device is connected to the hot side of the electrical receptacle, and the neutral wire is connected to the neutral side. This is done by making the neutral blade on the plug wider than the hot blade. If you look at a grounded outlet, you’ll see that the hot slot is shorter than the neutral slot. Older plugs may not be polarized, and both blades are the same size. It’s best to have an electrician re-wire the device using a polarized plug. The electrician should also ensure that the receptacle is properly wired. Electricians install grounded circuits. They follow OSHA’s Lockout/Tagout standard when working on them. Circuits are de-energized and isolated. Stored energy is released and conductors are grounded. De-activated controls are then locked out, and tags are placed at their “off” position. SECTION #4 | Participant Guide 6 Electrical Safety mACTIVITY 2 – IMPROPER WIRING / REVERSED POLARITYm Factsheet D – Reversed Polarity Can Kill! What can happen if a neutral wire of a device is connected to the hot side of a circuit? This condition is known as reversed polarity. In a worst case scenario, the result can be death. However, your electrical device will still work! (It just wants voltage across its load, nothing more.) There are inexpensive devices known as circuit testers, or polarity testers. Plug in this 3-prong device and you’ll know at a glance if there’s a wiring problem in the receptacle, just by looking at which lights are lit on the device. The two most dangerous conditions are: hot and ground reversed, and hot and neutral reversed. In 1990, a Maryland worker was killed by reversed polarity on a defective toaster oven with a twoblade, non-polarized plug. His hand touched its energized (120 volts AC) metal shell, while his leg touched the grounded housing of an air conditioner.1 See the following diagram. 1 NIOSH FACE Report 90-37, http://www.cdc.gov/niosh/face/In-house/full9037.html SECTION #4 | Participant Guide 7 Electrical Safety mELECTRICAL SAFETYm mACTIVITY 3 – WET CONDITIONS / GROUND FAULT CIRCUIT INTERRUPTERSm In your small group, read fact sheets E and F, and the following scenario. Then answer the questions below. SCENARIO: You’re an experienced worker in building maintenance, helping a new worker to learn the job. The task involves cleaning up a flooded basement. The new employee has started setting up electrical cords and tools for the job. You tell her, “Hold on a minute, let’s check out the wiring first.” Then you say, “No, we can’t do this without GFCI protection. I’ll tell you why.” 1. What would you tell the new employee? Safe Work: GROUNDED tool, 3prong POLARIZED plug, GFCI receptacle. 2. What can you do to correct this problem for now? 3. What is the best way to deal with this in the future? SECTION #4 | Participant Guide 8 Electrical Safety mACTIVITY 3 – WET CONDITIONS / GROUND FAULT CIRCUIT INTERRUPTERSm Factsheet E – Using Electrical Equipment in Wet Locations Using electrical tools or equipment in wet areas can be a hazard. If your skin is dry, it has quite a lot of resistance (measured in ohms or Ω). However, if your skin is wet for any reason (rain, sweat, standing in a puddle of water), the skin’s electrical resistance drops dramatically. The amount of electrical current, in amps, that flows through your body goes up when resistance in ohms goes down. Amps = Volts/Ohms. The Current in Amps = Voltage in Volts DIVIDED BY Resistance in Ohms. HIGHER VOLTAGE = more current (if resistance remains the same). LOWER RESISTANCE = more current (if voltage remains the same). HOW MUCH CURRENT DOES IT TAKE TO KILL ME? It doesn’t take much, especially if it passes through your heart. Currents above about 75 milliamps (mA) can cause a condition called ventricular fibrillation. (A milliamp is 1/1,000 of 1 amp.) If your heart goes into fibrillation, it beats very rapidly – but it doesn’t pump any blood – because it’s not beating in its normal rhythm. If your blood can’t carry oxygen to your brain, you’ll experience brain death in 3 to 4 minutes. The way to get you back involves another electric shock, from a defibrillator. If your skin is wet and you get your body across 120 volts of electricity, it’s very likely that you’ll have a current of 100 mA or more flowing through your heart. Currents ABOVE 10 MA can cause muscle paralysis. You may not be able to let go of energized tools or equipment. Shocks that are longer in duration are more severe. Electrical systems must be wired with either fuses or circuit breakers. These devices are known as overcurrent protection and they are rated in amps. Most common household circuits are wired for 15 amps or 20 amps. Overcurrent protection devices protect wiring and equipment from overheating and fires. They may – or may not – protect you from electrical shock. If the current isn’t high enough, the fuse won’t blow or the circuit breaker won’t trip. You could be shocked or killed without ever blowing a fuse or tripping a circuit breaker. SECTION #4 | Participant Guide 9 Electrical Safety mACTIVITY 3 – WET CONDITIONS / GROUND FAULT CIRCUIT INTERRUPTERSm Factsheet F – GFCIs to the Rescue A great breakthrough in electrical safety came with the invention of the ground fault circuit interrupter (GFCI). A ground fault occurs when electrical current flows on a path where it’s not supposed to be. Under normal conditions, current flows in a circuit, traveling from the source, through the device it operates, called the load, and then back to the source. [See Activity 2 for more about wiring of electrical circuits.] Current (amps) flows out to the load from the “hot” side (which is generally at 120 volts AC) and returns on the “neutral” side (which is at zero volts). Under normal conditions, these two currents (hot and neutral) are equal. If they are not equal, because of current leakage (current returning on a different path than the neutral conductor), we get a ground fault. This can occur if current flows through your body and returns to the source through a path to ground. Electricity will take ANY available path to return to its source. We want it to return only on the neutral. The ground fault circuit interrupter (GFCI) works by using the above principles. It measures total current on the hot side and total current on the neutral side of the circuit. They are supposed to be equal. If these two currents differ from each other by more than 5 milliamps (plus or minus 1 mA), the GFCI acts as a fast-acting circuit breaker and shuts off the electricity within 1/40 of 1 second. You can still feel this small amount of current, but it will quickly shut off. GFCIs are manufactured in many forms. The most common one is the GFCI outlet. However, there are also GFCI circuit breakers, plug-in GFCI outlets and GFCI extension cords, as well as GFCIs hard-wired into devices such as hair dryers. All types have “Test” and “Reset” functions. The GFCI must trip when you press the “Test” button. It must also energize the circuit when you press “Reset.” If either test fails, you must replace the GFCI in order to be protected! SECTION #4 | Participant Guide 10 Electrical Safety mELECTRICAL SAFETYm mACTIVITY 4 – EXTENSION CORDS, COPPER AND CURRENTm In your small group, read fact sheets G and H, and the following scenario. Then answer the questions below. SCENARIO: You’re at work one day and a co-worker starts screaming: It looks like his saw is smoking, it smells like it’s burning and his extension cord is getting hot enough to burn his hand. You walk over, take one look at the scene and start shaking your head. “Well, I know what your problem is, and I’ll explain if you stop shouting,” you tell him. 1. What is your explanation to the worker? Safe Work: UL approved, 3-conductor, GROUNDED extension cord, #12 wires. 2. What are some steps to deal with this issue? 3. What is the best way to correct the problem? SECTION #4 | Participant Guide 11 Electrical Safety mACTIVITY 4 – EXTENSION CORDS, COPPER AND CURRENTm Factsheet G – Wire Size and Ampacity In terms of conducting electrical current, size matters: the size of the electrical conductor. Take a look at the following table regarding ampacity, the current carrying capacity of a conductor in amps. You’ll notice two things: the amount of current a wire can safely carry increases as the diameter (and area) of the wire increases and as the number of the wire size decreases. Welcome to the American Wire Gauge (AWG). AWG Copper Wire Table Copper Wire size (AWG) Diameter (mils) Area (Circular mils) Ampacity in free air Ampacity as part of 3-conductor cable 14 AWG 64.1 4109 20 Amps 15 Amps 12 AWG 80.8 6529 25 Amps 20 Amps 10 AWG 101.9 10,384 40 Amps 30 Amps 8 AWG 128.5 16,512 70 Amps 50 Amps BUT I DON’T WANT TO BE AN ENGINEER... Hey, neither do I, but this stuff is important. Notice that a #8 wire is twice the diameter, but four times the area of a #14 wire. There are a couple of practical applications here. For one thing, the gauge of the wire determines the rating of a fuse or circuit breaker in amps. A circuit wired with #14 copper will get a 15 amp circuit breaker. A circuit with #12 copper can get a 20 amp breaker; #10 copper can be 30 amps, and so on. The second thing to consider is that it’s possible to create a fire hazard by overloading an extension cord. This occurs when too much current is flowing in a conductor that’s not heavy enough for the electrical load in amps. The circuit can be properly wired and its circuit breaker correctly rated, but if too much current flows through an extension cord whose wires are too small, the cord will heat up. Sometimes there is also a voltage drop over a longer extension cord, which could damage your tools. SECTION #4 | Participant Guide 12 Electrical Safety mACTIVITY 4 – EXTENSION CORDS, COPPER AND CURRENTm Factsheet H – Extension Cord Facts With the wide use of power tools on construction sites, flexible extension cords often are necessary. Because they are exposed, flexible, and unsecured, they are more susceptible to damage than is fi xed wiring. Hazards are created when cords, cord connectors, receptacles, and cord- and plugconnected equipment are improperly used and maintained. Here are some factors on extension cord safety noted by OSHA. STRAIN RELIEF ● To reduce hazards, flexible cords must connect to devices and to fittings in ways that prevent tension at joints and terminal screws. Flexible cords are finely stranded for flexibility, so straining a cord can cause the strands of one conductor to loosen from under terminal screws and touch another conductor. CORD DAMAGE ● A flexible cord may be damaged by door or window edges, by staples and fastenings, by abrasion from adjacent materials, or simply by aging. If the electrical conductors become exposed, there is a danger of shocks, burns, or fire. Replace frayed or damaged cords. Avoid running cords over sharp corners and edges. DURABILITY ● The OSHA construction standard requires flexible cords to be rated for hard or extra-hard usage. These ratings are derived from the National Electrical Code, and are required to be indelibly marked approximately every foot along the length of the cord. Examples of these codes are: S, ST, SO, and STO for hard service, and SJ, SJO, SJT, and SJTO for junior hard service. GROUNDING ● Extension cords must be 3-wire type so they may be grounded, and to permit grounding of any tools or equipment connected to them. WET CONDITIONS ● When a cord connector is wet, electric current can leak to the equipment grounding conductor, and to humans who pick up that connector if they provide a path to ground. Such leakage can occur not just on the face of the connector, but at any wetted portion. Limit exposure of connectors and tools to excessive moisture by using watertight or sealable connectors. NOTE: This page is adapted from OSHA eTool: Construction, Electrical Hazards, Flexible cords. SECTION #4 | Participant Guide 13 Electrical Safety mELECTRICAL SAFETYm mACTIVITY 5 – “IT’S ONLY 120 VOLTS”m In your small group, read fact sheet I, and the following scenario. Then answer the questions below. SCENARIO: You are on a construction site in the morning after it rained all night, and there is some standing water on the ground. A co-worker is setting up his job, running an extension cord he built himself. He has used a 3-prong replacement plug, a length of 3-conductor Type NM non-metallic cable and a 3-conductor receptacle mounted in steel utility box. You see this and say, “Hey, you really need to be using a UL approved, factory made, grounded extension cord out here.” He replies, “I’ve used this set-up for years and never had any trouble. It’s not that dangerous, it’s only 120 volts. Anyway, it’s the current that kills you, not the voltage.” Safe Work: TEST A GFCI OUTLET – every time you use it – to be sure it works! 1. What would you say to this worker? 2. What can you do to correct this problem for now? 3. What is the best way to deal with this in the future? SECTION #4 | Participant Guide 14 Electrical Safety mACTIVITY 5 – “IT’S ONLY 120 VOLTS”m Factsheet I – 120 Volts Can Kill! Ordinary, household, 120 volts AC electricity is dangerous and it can kill. Voltage is the force that allows electricity to flow in a circuit. Electrical current involves the flow of electrons and it’s measured in amps. The third factor involved in current flow is resistance, the opposition to current flow, measured in ohms. We can use a simple formula to calculate the current: Current in Amps = Voltage in Volts DIVIDED BY Resistance in Ohms. Using electrical tools or equipment in wet areas can be a hazard. If your skin is dry, it has quite a lot of resistance (measured in ohms or Ω). However, if your skin is wet for any reason (rain, sweat, standing in a puddle of water), the skin’s electrical resistance drops dramatically. The amount of electrical current, in amps, that flows through your body goes up when resistance in ohms goes down. Amps = Volts/Ohms. If your skin is wet and you get your body across 120 volts of electricity – possibly from an electrical defect in a homemade extension cord – it’s very likely that you’ll have a current of 100 milliamps (mA) or more flowing through your heart. (1 mA is 1/1,000 of 1 amp.) At 100 mA, you may not be able to let go of an energized tool or piece of equipment. Currents above 75 milliamps (mA) can lead to a condition called ventricular fibrillation, which can be fatal. [See Activity 4 for more information on extension cord hazards.] A major safety precaution when working under wet conditions is using an electrical device called a Ground Fault Circuit Interrupter (GFCI). A properly wired and tested GFCI can save your life. It will trip and turn off the electricity when it detects current leakage as low as 5 mA. You should consider bringing and using your own plug-in GFCI receptacle or GFCI extension cord, especially if there is any question about the condition of electrical wiring at your site. It’s important to test your GFCI every time you use it, so you know it will protect you. [See Activity 3, more about wet conditions, electrical hazards and GFCIs.] SECTION #4 | Participant Guide 15 Electrical Safety mELECTRICAL SAFETYm mACTIVITY 6 – POWER LINE HAZARDSm In your small group, read fact sheet J (pages 17-20), and read the following scenario. Then answer the questions below. SCENARIO: You are the “competent person”2 at a company that constructs and dismantles scaffolds, and you are reviewing an upcoming job with your crew. You mention that this job will require extra care because the scaffold will need to be close to a nearby power line and you will need to take necessary precautions. One of your crew says, “We shouldn’t even take on a job like that. There are lots of cases where people on scaffolds have been electrocuted. Why should we take chances with our lives?” You reply, “Yes, it can be dangerous, but there are ways to remove or control the hazard. I’ll explain it to you guys.” 1. What would you say to your crew? Safe Work: Scaffold must be AT LEAST 10 FEET from the power line. 2. What can you do to protect yourselves from power line hazards? 3. In your opinion, what is the best way to deal with power line hazards, the second best, and so on? 2 A “competent person” (required by certain OSHA standards) must be able to recognize existing and predictable hazards, and must be authorized by the employer to take action to correct unsafe conditions. SECTION #4 | Participant Guide 16 Electrical Safety mACTIVITY 6 – POWER LINE HAZARDSm Factsheet J – Power Lines Kill Workers Most people know that power lines can kill, yet a surprising number of power line deaths occur on a regular basis. Electricity is generated and transmitted at high voltages for a good reason: it limits power loss as the electricity travels long distances from power plant to point of use. Power lines can be at tens of thousands of volts, even at hundreds of thousands of volts: the higher the voltage, the greater the potential danger. Problems occur when people or equipment get too close to energized lines. Some of the most common situations that occur are: ● Contacting lines with cranes and other construction equipment ● Hitting a line when erecting or moving a scaffold ● Getting too close with a ladder or a tool, especially a conductive one, such as aluminum or wood. There are three major ways to control power line hazards: 1. Maintaining a safe distance from lines. 2. Having the power company de-energize and ground the power line(s). Have a power company rep at the site! 3. Having the power company install insulated sleeves (also known as “eels”) over power lines. (See the above item.) NOTE: Only the electric power utility can determine the clearance distance for this method of insulating lines. SECTION #4 | Participant Guide 17 Electrical Safety Factsheet J continued... NOTE: The information on pages 18 and 19 was adapted from material developed by the Construction Safety Council. Staying away from power lines is the best option. The following illustration shows the safe power line clearance distance, as well as the working clearance distance. The table shows clearance distances from power lines for various line voltages. NOTE: The term kV = 1,000 volts. For example, 50 kV = 50,000 volts. Power Line Clearance Distances Voltages Distances from Power Lines < 50kV 10 feet 200 kV 15 feet 350 kV 20 feet 500 kV 25 feet 650 kV 30 feet 800 kV 35 feet The best and easiest way, is to follow this rule: • Up to 50 kV – Stay at least 10 feet away • Over 50 kV – Stay at least 35 feet away SECTION #4 | Participant Guide 18 Electrical Safety Factsheet J continued... PREVENTIVE MEASURES GENERAL ● Move equipment/activity to the safe working distance from power lines. ● Have utility de-energize and visibly ground power lines. ● Have utility move power lines to the safe working distance. ● Have utility install insulated sleeves on power lines.* ● Install flagged warning lines to mark horizontal and vertical power line clearance distances. ● Use nonconductive tools and materials. CRANES AND OTHER HIGH REACHING EQUIPMENT ● Use an observer.* ● Use an insulated link, if applicable.* ● Use a boom cage guard, if applicable.* ● Use a proximity device, if applicable.* MOBILE HEAVY EQUIPMENT ● Install rider posts or goal posts under power lines. ● Install warning signs at driver's eye level. * These options DO NOT allow the operator to work closer than the line clearance distance. LADDERS ● Use nonconductive ladders. ● Don't carry or move extension ladders fully extended. Retract before moving. ● Get help moving ladders to maintain control. MATERIAL STORAGE ● Don't store any materials under power lines. ● Use caution tape and signs to cordon off area under power lines. EXCAVATIONS ● Call 811 to contact your local one-call service several days before you dig to locate all underground cables. ● Hand dig within three feet of cable location. ● Be aware that more than one underground cable may be buried in area of locator markings. Remember: The Only safe power lines are the ones that don’t exist. CALL 811 BEFORE YOU DIG! SECTION #4 | Participant Guide 19 Electrical Safety Factsheet J continued... POWER LINE PHOTOS: UNPROTECTED AND PROTECTED There is a hazard of shock or electrocution: scaffold and platform are less than 10 feet away from these power lines. This scaffold has been protected from electrical hazards: three power lines at the top have been de-energized, jumpered together and then electrically grounded by the power company. This power company worker is placing insulated sleeves (“eels”) over the power line in this photo. SECTION #4 | Participant Guide 20 Electrical Safety mELECTRICAL SAFETY SUMMARYm 1. CORD AND PLUG OPERATED electric tools with exposed metal parts must have a three-prong grounding plug – AND be grounded – or else be double-insulated. 2. EQUIPMENT GROUNDING only works when there is a permanent and continuous electrical connection between the metal shell of a tool and the earth. 3. PROPER POLARITY IN ELECTRICAL WIRING IS IMPORTANT: hot to hot, neutral to neutral, equipment ground to equipment ground. Polarized plugs have a wider neutral blade to maintain correct polarity. Reversed polarity can kill. 4. CIRCUITS MUST BE EQUIPPED WITH FUSES OR CIRCUIT BREAKERS to protect against dangerous overloads. Fuses melt, while circuit breakers trip to turn off current like a switch. Overcurrent protection devices protect wiring and equipment from overheating and fires. They may, or may not, protect you. 5. MOST 120 VOLT CIRCUITS are wired to deliver up to 15 or 20 amps of current. Currents of 50100 milliamperes can kill you. (1 mA = 1/1,000 of 1 Amp.) 6. WET CONDITIONS LOWER SKIN RESISTANCE, allowing more current to flow through your body. Currents above 75 milliamps can cause ventricular fibrillation, which may be fatal. Severity of a shock depends on: path of current, amount of current, duration of current, voltage level, moisture and your general health. 7. A GROUND FAULT CIRCUIT INTERRUPTER (GFCI) protects from a ground-fault, the most common electrical hazard. GFCIs detect differences in current flow between hot and neutral. They trip when there is current leakage – such as through a person – of about 5 milliamperes and they act within 1/40 of a second. Test a GFCI every time you use it. It must “Trip” and it must “Reset.” 8. EXTENSION CORD WIRES MUST BE HEAVY ENOUGH for the amount of current they will carry. For construction, they must be UL approved, have strain relief and a 3-prong grounding plug, be durable, and be rated for hard or extra-hard usage. 9. OVERHEAD POWER LINES CAN KILL. The three major methods of protection are: maintaining a safe distance, de-energizing AND grounding lines, having the power company install insulating sleeves. Have a power company rep on the site. 10. UNDERGROUND POWER LINES CAN KILL. Call before you dig to locate all underground cables. Hand dig within three feet of cable location! SECTION #4 | Participant Guide 21 Electrical Safety APPENDIX A Condensed Electrical Glossary AMPERE OR AMP: The unit of electrical current (flow of electrons). ● One milliamp (mA) = 1/1,000 of 1 Amp. CONDUCTORS: Materials, such as metals, in which electrical current can flow. ELECTRICAL HAZARDS can result in various effects on the body, including: ● SHOCK – The physical effects caused by electric current flowing in the body. ● ELECTROCUTION – Electrical shock or related electrical effects resulting in death. ● BURNS – Often occurring on the hands, thermal damage to tissue can be caused by the flow of current in the body, by overheating of improper or damaged electrical components, or by an arc flash. ● FALLS – A common effect, sometimes caused by the body’s reaction to an electrical current. A non-fatal shock may sometimes result in a fatal fall when a person is working on an elevated surface. EXPOSED LIVE PARTS: Energized electrical components not properly enclosed in a box or otherwise isolated, such that workers can touch them and be shocked or killed. Some of the common hazards include: missing knockouts, unused openings in cabinets and missing covers. Covers must not be removed from wiring or breaker boxes. Any missing covers must be replaced with approved covers. INSULATORS: Materials with high electrical resistance, so electrical current can’t flow. LOCKOUT/TAGOUT: The common name for an OSHA standard, “The control of hazardous energy (lockout /tagout).” Lockout is a means of controlling energy during repairs and maintenance of equipment, whereby energy sources are de-energized, isolated, and then locked out to prevent unsafe start-up of equipment which would endanger workers. Lockout includes – but is not limited to – the control of electrical energy. Tagout means the placing of warning tags to alert other workers to the presence of equipment that has been locked out. Tags alone DO NOT LOCK OUT equipment. Tagout is most effective when done in addition to lockout. OHM or Ω: The unit of electrical resistance (opposition to current flow). OHM’S LAW: A mathematical expression of the relationship among voltage (volts), current (amps) and resistance (ohms). This is often expressed as: E = I x R. In this case, E = volts, I = amps and R = ohms. (The equation, Amps = Volts/Ohms, as used in this curriculum, is one form of Ohm’s Law.) VOLT: The unit of electromotive force (emf) caused by a difference in electrical charge or electrical potential between one point and another point. The presence of voltage is necessary before current can flow in a circuit (in which current flows from a source to a load – the equipment using the electricity – and then back to its source). WET CONDITIONS: Rain, sweat, standing in a puddle – all will decrease the skin’s electrical resistance and increase current flow through the body in the event of a shock. Have a qualified electrician inspect any electrical equipment that has gotten wet before energizing it. SECTION #4 | Participant Guide 22 Electrical Safety APPENDIX B General Rules for Construction Electrical Safety MAJOR PROTECTIVE METHODS FROM ELECTRICAL HAZARDS Protection from electrical hazards generally includes the following methods: 1. DISTANCE: Commonly used with regard to power lines. 2. ISOLATION AND GUARDING: Restricting access, commonly used with high voltage power distribution equipment. 3. ENCLOSURE OF ELECTRICAL PARTS: A major concept of electrical wiring in general, e.g., all connections are made in a box. 4. GROUNDING: Required for all non-current carrying exposed metal parts, unless isolated or guarded as above. (However, corded tools may be either grounded OR be double-insulated.) [See Activity 1 for more about electrical grounding.] 5. INSULATION: Intact insulation allows safe handling of everyday electrical equipment, including corded tools. Category also includes insulated mats and sleeves. 6. DE-ENERGIZING AND GROUNDING: Protective method used by electrical utilities and also in conjunction with electrical lockout/tagout. 7. PERSONAL PROTECTIVE EQUIPMENT (PPE): Using insulated gloves and other apparel to work on energized equipment, limited to qualified and trained personnel working under very limited circumstances. GENERAL RULES FOR ELECTRICAL WORK ● Non-conductive PPE is essential for electricians. NO METAL PPE! Class B hard hats provide the highest level of protection against electrical hazards, with high-voltage shock and burn protection (up to 20,000 volts). Electrical hazard, safety-toe shoes are nonconductive and will prevent the wearers’ feet from completing an electrical circuit to the ground. ● Be alert to electrical hazards, especially when working with ladders, scaffolds and other platforms. ● Never bypass electrical protective systems or devices. ● Disconnect cord tools when not in use and when changing blades, bits or other accessories. ● Inspect all tools before use. ● Use only grounded extension cords. ● Remove damaged tools and damaged extension cords from use. ● Keep working spaces and walkways clear of electrical cords. RULES FOR TEMPORARY WIRING AND LIGHTING ● Use Ground Fault Circuit Interrupters (GFCIs) on all 15-Amp and 20-Amp temporary wiring circuits. ● Protect temporary lights from contact and damage. ● Don’t suspend temporary lights by cords, unless the temporary light is so designed. SECTION #4 | Participant Guide 23 Electrical Safety NOTES SECTION #4 | Participant Guide 24 Electrical Safety
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:08:23 Create Date : 2008:10:20 09:43:07-04:00 Modify Date : 2008:10:20 09:43:07-04:00 Creator Tool : Adobe InDesign CS2 (4.0.5) Producer : Acrobat Distiller 8.1.0 (Macintosh) Format : application/pdf Creator : margarita Title : ElectricalParticipant.indd Document ID : uuid:bcbeda4e-c2f9-492e-be87-c3af61b1bc25 Instance ID : uuid:d4acacf0-023f-4046-bdeb-241bd0485673 Page Count : 26 Author : margaritaEXIF Metadata provided by EXIF.tools