832 2007 Bid Opportunity Electric Steam Humidifiers Addendum 1 NMS Format Specifications Mechanical Equipment Schedules

User Manual: Electric Steam Humidifiers

Open the PDF directly: View PDF PDF.
Page Count: 40

Download832-2007 Bid Opportunity Electric Steam Humidifiers Addendum 1-NMS Format Specifications Mechanical Equipment Schedules
Open PDF In BrowserView PDF
Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

MECHANICAL SPECIFICATIONS
APPROVED SUBSTITUTES
SCHEDULE

PAGE #: 1 OF 6
SCHEDULE A

GENERAL

1.1

GENERAL REQUIREMENTS
.1

Comply with the requirements of Section 210501, Mechanical General Provisions.

.2

Comply with the requirements of Section 210504, Basic Materials and Methods.

.3

Comply with the requirements of Clause B6.

1.2

APPROVED 'SUBSTITUTES' AND 'ALTERNATES'
.1

Where a Manufacturer's name, make, model, and/or size is specified, it is for the purpose of
setting a standard of quality, performance, capacity, appearance and/or serviceability, and is
acceptable without qualification. Manufacturers listed as acceptable 'Substitutes' have been
deemed by the The Contract Administrator as capable of producing equipment and/or material of
comparable quality, performance and approximate dimensions, and can be used in the
preparation of the Bid. Where no substitutes are indicated, provide the exact make specified.

.2

'Substitute' equipment and material is deemed to be interchangeable with that specified, with little
or no revisions required to the design intent and/or other items, equipment or connections.

.3

'Alternate' equipment and material is deemed to be an acceptable 'Substitute' which will require
major revisions to the design intent and/or other items, equipment or connections.

.4

Requests for approval of additional 'Substitutes' or 'Alternates' must be submitted not less than
seven days prior to closing date of the Bid, and submissions must bear proof of acceptance by
the The Contract Administrator if used in the Bid. Requests shall include all performance,
capacity, appearance, weight, connections, power and wiring requirements, etc required for the
The Contract Administrator to make a complete evaluation.

.5

Assume full responsibility for ensuring that, when providing accepted 'Substitutes' and
'Alternates', all space, weight, connections, power and wiring requirements, etc. are considered
and adjusted costs are included in the Bid. The Mechanical systems have been designed based
on the equipment/materials of the specified manufacturer(s). The onus shall be on the
Subcontractor (along with his sub-sub-contractor and the supplier) to ensure that 'Substitute' or
'Alternate' equipment/materials will meet the required performance and electrical characteristics,
as well as fit properly into the allotted space, including allowance for required access and
servicing. Any additional costs incurred as a result of modifications to the system(s) or the room
layout, or modifications required by other trades, shall be borne by the Subcontractor (along with
his sub-sub-contractor and the supplier) and shall be deemed to be included in the Bid price.

.6

Bidders must base their price on specified manufacturers or approved 'Substitutes'. 'Alternates',
when allowed, must be listed separately, with the amount to be added or subtracted for each
substitution. If in the preparation of the Bid, this Subcontractor neglects to name the
manufacturer of an accepted 'Alternate', it will be understood that specified or 'Substitute'
equipment will be provided.

.7

If, in the opinion of the The Contract Administrator, 'Substitute' equipment/material submitted for
review as Shop Drawings is not satisfactory, satisfactory equipment/material of the specified or
an accepted 'Substitute' manufacturer must be re-submitted.

.8

If, in the opinion of the The Contract Administrator, 'Alternate' equipment/material submitted for
review as Shop Drawings is not satisfactory, satisfactory equipment/material of the specified or
an accepted 'Substitute' manufacturer must be re-submitted.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
1.3

MECHANICAL SPECIFICATIONS
APPROVED SUBSTITUTES
SCHEDULE

PAGE #: 2 OF 6
SCHEDULE A

APPROVED 'SUBSTITUTES''
.1

The following is the list of pre-approved 'Substitutes':
.1

Access Doors:

.2

Actuators for Valves and Dampers:

.3

Air Compressors
and Accessories:

.4

Air Cooled
Condensing Units:

Bauco;
Belimo

Comairco;
Airtek;

Sullair;
Hankinson;
Gardner Denver;

Keeprite;
McQuay;

Carrier;
York;

Lennox;
Engineered Air;

.5

Air Curtains (Air Doors):

King;

Cook;

Mars;

.6

Air Filters:

Farr;

AAF;

Continental;

.7

Air Handling Units:

Trane:
Haakon;

Carrier:
McQuay;

Engineered Air;
Scott-Springfield;

.8

Air Vents:

Armstrong;
Maid-O-Mist;

Braukman; Bell and Gossett;
Dole;
Hamlet and Garneau;

.9

Back Flow Preventors:

Conbraco;
Kunkle;
Fisher;
Boylston;

Beeco;
Taylor;
Singer;
Lonergan;

Febco;
Watts;
Consolidated;
Crosby-Ashton;
Masoneilan;Wilkins

.10

Boilers (Copper Tube):

Raypak;
Rendamax;

PK Thermific;
Lochinvar;

Ajax;
RBI;

York;

Superhot;

.11

Boilers (Steel Tube):

Burnham;
Superhot;

Unilux;
Universal;

Cleaver Brooks;
Bryan;

.12

Boilers (Cast Iron):

Burnham;
Smith;

Viessman;
Slant-fin;

Hydrotherm;
DeDeitrich;

.13

Boilers (Condensing):

Aerco;

Viessman;

Fulton;

.14

Chemical Treatment:

Bird Archer;
Dearborne;

Calgon;
Mogul;

Drew Chemical;

Ajax;

.15

Chillers:

Carrier;

McQuay;

Trane;

York;

.16

Chimneys:

Metal-Fab;

Ampco;

Cleaver Brooks;

.17

Cleanouts:

Ancon;

Smith;

Zurn;

Mifab;

.18

Computer Room AC Units: Hiross;

Liebert;

Airflow;

Canatel;

.19

Controls :

.20

Landis and Steafa (Siemens); Johnson; Honeywell;
Mikkelson Coward (Andover); Barber Coleman (Siebbe);
Cooling Towers:
Evapco;
BAC;

.21

Dehumidifiers:

BryAir;

PoolPak;

Engineered Air;

CSE/Delta;

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
.22

.23

MECHANICAL SPECIFICATIONS
APPROVED SUBSTITUTES
SCHEDULE

Domestic Water Heaters
(Tank type):

PAGE #: 3 OF 6
SCHEDULE A

Ruud/Rheem;
John Woods;

AO Smith;
Jetglass/BradfordWhite;

Domestic Water Heaters:
(Tankless):

CEC;

.24

Duct-free Split AC Units:

Carrier;

Freidrich;

.25

Electric Duct Coils;

Nailor Hart;

PM Wright;

.26

Expansion Tanks:

Amtrol;
Wessels;

Hamlet and Garneau;
Armstrong;

.27

Fabric Duct Diffusers:

FOF;

.28

Fan Coil Units:

McQuay;
York;

First Fan Coil;
Engineered Air;

.29

Fans
(Centrifugal and Axial):

Greenheck;
Twin City;
Woods;

Penn;
Delhi;
Cook;

New York Blower;
Barry Blower;
Northern Blower;

Fans
(Downdraft/Ceiling):

Pleasantaire;

Banvil;

Canarm;

Fans
(Fume Exhaust Systems):

Plymovent;

Belnor;

Greenheck;
Broan;

Penn;
Delhi;

Reversomatic;
Cook;

Trane
York;

Reznor;
McQuay;

Engineered Air;
Rosemex;

.30
.31
.32

Fans
(Washroom and Cabinet):

.33

Filter Gauges:

.34

Force Flow
Entrance Heaters:

Mr. Slim;

Trane;

Dwyer;

.35

Fume Detection Systems:

ACME;

CET;

.36

Furnaces:

Lennox;

Engineered Air;

.37

Gas Meters:

Equimeter;

.38

Glycol Feed Systems:

Axiom;

Hamlet and Garneau;

.39

Grilles and Diffusers:

Carnes;
Titus;

Kreuger;
Nailor Hart;

.40

Heat Exchangers
(Plate Type):

Armstrong;

Bell and Gossett;

Heat Exchangers
(Shell and Tube):

Armstrong;

Bell and Gossett;

Carrier;
Lennox;

McQuay;
Keeprite;

.41
.42

Heat Pumps:

EH Price;
Hart and Cooley;

Mammoth;
Trane;

York;
AAF;

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

MECHANICAL SPECIFICATIONS
APPROVED SUBSTITUTES
SCHEDULE

PAGE #: 4 OF 6
SCHEDULE A

.43

Heat Recovery Ventilators: Greenheck;
Lifebreath;

Carrier;
Keeprite;

.44

Humidifiers:

DriSteem;
Armstrong;

Carnes;
Nortec;

.45

Hydronic Coils:

Carrier;
Trane;

Heatcraft;
McQuay;

Broan;
Z-duct;
Rosemex;
Herrmidifier;

Hydronic System Accessories: Bell and Gosset;

Taco;

.47

Insulation (General):

Fibreglas;

Knauf;

.48

Insulation (Traps):

TrapWrap (Brocar);

.49

Level and Flow Switches:

Magnetrol;

.50

Louvres:

Westvent;
Greenheck;

Airolite;
Penn;

.51

Make-up Air Units:

Carrier:

Engineered Air;

.52

Mechanical Grooved Pipe Joints:

.53

Packaged Terminal
Air Conditioners and
Heat Pumps:

.54

Pitless Units:

Baker;

.55

Plumbing Fixtures, Drains and Brass:

Spirax/Sarco;

LavGuard (TrueBro);

Gruv-Lok;

Friedrich;
Trane;

Vapac;
Pure;

Engineered Air;

.46

Manson;

NEP;
York;

Carnes;
Ruskin;

Ventex;
I.C.E.;

Victaulic

McQuay;
Mammoth;

Mr Slim;

Monitor;

.1

Acid Dilution Tanks:

Watts;

.2

Drinking Fountains:

Oasis;

Haws;

Halsey Taylor;

Crane;

.3

Electronic Faucets:

Chicago;
Zurn;

Kohler;
Sloan;

DMP Electronics;
Cambridge;

Delta;

.4

Emergency Showers
and Eyewashes:

Guardian;

Floor Drains,
Grease Traps
and Fixture Carriers:

Ancon;

Smith;

.6

Mixing Valves:

Leonard;

Powers/Crane;

.7

Plumbing Brass:

.8

.5

.9

Haws;

Bradley

Zurn;

Mifab;

Delta;
Emco;
Smith;

Waltec;
Sloan;
Moen;

Symmons;
PricePfister;
Cambridge;

Crane;
Leonard;
Powers;

Plumbing Fixtures
(General):

Crane;

Kohler;

American Standard;

Plumbing Fixtures
(Specialty):

Fiat;

Bradley;

Metcraft;

Zurn;
Mifab;

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

MECHANICAL SPECIFICATIONS
APPROVED SUBSTITUTES
SCHEDULE

PAGE #: 5 OF 6
SCHEDULE A

.10

Showers and Tubs: Hytec;

.11

Stainless Steel Sinks:

.12

Toilet Seats;

Fiat;

Steel Queen;
KIL/Aristaline;
Architectural Metals;

Olsonite;

.56

Pressure Gauges:

.57

Pressure Relief Valves,
Pressure Regulating Valves:

Venco/Structural Glass;

Centoco;

Taylor;
Ashcroft;
Trerice;

Bemis;

Weiss;
Duro;
Ametek;

Marshalltown;
Lunkenheimer;
Marsh;
Winters;

Conbraco;
Kunkle;
Fisher;
Boylston;

Beeco;
Taylor;
Singer;
Lonergan;

Febco;
Watts;
Consolidated;
Crosby-Ashton;
Masoneilan;Wilkins

.58

Pumps (Circulating):

Armstrong;
Darling;

Grundfos;
Taco;

Bell and Gossett;

.59

Pumps (Domestic):

Armstrong;

Grundfos;

Bell and Gossett;

.60

Pumps (Domestic Booster):

Armstrong;

Bell and Gossett;

.61

Pumps (Sump and Sewage):

Armstrong;
Grinder;

Grundfos;
Myers;

.62

Pumps (Vertical Turbine):

Armstrong;

.63

Pumps (Fire):

Armstrong;

.64

Pumps (Condensate):

Armstrong;

.65

Pumps (Well):

Myers;

.66

Radiant Ceiling Panels (Hydronic):

Airtex;

TWA (Frenger);

.67

Radiant Heaters (Gas Fired):

Schwank;

Reznor; Roberts Gordon

.68

Radiation (Special):

Rosemex;

Hudevaad;

.69

Radiation (Standard):

Rosemex;
Slantfin;

Modine;
Rittling;
Engineered Air;

.70

Range Hoods:

Broan;

.71

Roof Top Units:

Trane;
Keeprite;

Carrier;
Lennox;

.72

Shock Absorbers:

Smith;

Zurn;

.73

Silencers:

VAW;

Vibro-Acoustics;;

.74

Sound and Vibration
Isolation:

Sterling;
Jacuzzi

Vibron;
Airmaster;
Vibro-Acoustics;

.75

Special Duct Cleaning: Power-Vac;

.76

Steam System Accessories:

Bell and Gossett;
Hydromatic; Goulds

Runtal;

Engineered Air;
McQuay;

Amber-Booth;
SVC Industries;

Mammoth;
York;

Kinetics;

Advance Robotic;

Watson McDaniels;

Armstrong;

Spirax/Sarco;

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

1.4

MECHANICAL SPECIFICATIONS
APPROVED SUBSTITUTES
SCHEDULE

PAGE #: 6 OF 6
SCHEDULE A

.77

Strainers:

Armstrong;
Streamflo;

Crane;
Kitz;

.78

Thermometers:

Taylor;
Ashcroft;
Trerice;

Weiss;
Duro;
Ametek;

Marshalltown;
Lunkenheimer;
Marsh;
Winters;

.79

Trap Primers:

Mifab;

Smith;

Zurn;

.80

Unit Heaters (Hydronic):

Modine;
McQuay;

Engineered Air;
Beacon-Morris;

.81

Unit Heaters (Gas Fired):

Modine;

Reznor;

Sterling;

Beacon-Morris;

.82

Vacuum Breakers:

Febco;

Watts;

Wilkins;

Spirax/Sarco;

.83

Vacuum Cleaning
Central Systems;

Broan;

.84

Vacuum Pumps:

SIHI;

.85

Valves (General):

Crane;
Nibco;

Kitz;
Toyo;

Apollo;
Jenkins;

.86

Valves (Butterfly):

Kitz;
Apollo;

Nibco;
Dezurik;

Jenkins;
Newman-Hattersley;
Keystone; Crane;

.87

Valves (Check):

Centerline;
Singer;

Hagen;
Dezurik;

Mueller;
Crane

.88

Valves (Radiation):

Griswold;
Danfoss;

Sarco;
Dahl;

Red and White;

.89

Ventilation Specialties: Nailor Hart;
Carnes;

Greenheck;
Titus;

Ruskin;
EH Price;

.90

Water Softeners:

Filter Soft;

USF;

Culligan;

Mueller;

Sarco;

Reznor;
Trane;
Rosemex;

Newman-Hattersley;
American Valve;
Anvil;

APPROVED 'ALTERNATES'
.1

The following is the list of pre-approved 'Alternates':
.1

Access Doors:

Lehage;

Milcor;

.2

Insulation (Traps):

SnapTrap (Zestron)

.3

Water Treatment Systems:

Culligan;

END OF SCHEDULE A

Toyo;

Acudor; Mifab;

Olympic;

Prairie

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

AIR HANDLING UNIT SCHEDULE

PAGE #: 1 OF 6
SCHEDULE B

SPECIFICATIONS

1 GENERAL
1.1

Air Handling Units shall be built to the level of quality as herein specified and to the description of the
Air Handling Unit Schedule.

1.2

Substitution of any product other than that specified, must assure no deviation below the stated
capacities, air flow rate, heat transfer rate, filtration efficiency and air mixing quality. Power
requirements must not be exceeded, and where specifically defined, sound power levels must not be
exceeded. Applications for "equal" or "alternate" must address these factors.

1.3

Unless stated otherwise, air handling units are to be shipped to the job in one piece, factory
assembled. All equipment shall be factory tested prior to shipment.

1.4

The Air Handling Units shall be the product of a Canadian owned firm, built in Canada, with all
components made in Canada, where possible. The air handling units and major components shall be
products of manufacturers regularly engaged in the production of such equipment and with a
minimum of fifteen continuous years of proven production experience. Manufacturer shall have a fully
implemented and auditable quality assurance program, equal to the ISO-9002 Quality Standard.

1.5

Air Handling Units shall be as manufactured by Engineered Air and be based bid. Alternate products
must show savings and clearly indicate all areas where they do not meet specified product.

2 UNIT CONSTRUCTION
2.1

Unit casing shall be of minimum 18 (1.3mm) gauge satin coat galvanized sheet metal. Galvanized
surfaces shall be cleaned with a degreasing solvent to remove oil and metal oxides and primed with a
two part acid based etching primer. Finish coat shall be an electrostatically applied enamel of KnightFighter Grey color, to all exposed surfaces. All unprotected metal and welds shall be factory coated.

2.2

All walls, roofs and floors shall be of formed construction, with at least two breaks at each joint. Joints
shall be secured by sheet metal screws or pop rivets. Wall and floor joints shall be broken in and roof
joints broken out (exposed) for rigidity. All joints shall be caulked with a water resistant sealant.

2.3

Units shall be provided with access doors to the following components: fans and motors; filters;
dampers and operators. Access doors shall be large enough for easy access. Removal of screwed
wall panels will not be acceptable. Provide hinged access doors, fully lined, with a minimum of two
Camlock fasteners.

2.4

Casings shall be supported on formed galvanized steel channel or structural channel supports,
designed and welded for low deflections. Integral lifting lugs shall be provided for hoisting.

2.5

All units shall be internally insulated with 1" (25mm) thick 1 1/2 lb./cu.ft. (24 kg./cu.m.) density,
neoprene coated fibre glass thermal insulation

3 FANS
3.1

Centrifugal fans shall be rated in accordance with AMCA Standard Test Code, Bulletin 210. Fan
manufacturer shall be a member of AMCA. All fans and fan assemblies shall be dynamically
balanced during factory test run. Fan shafts shall be selected for stable operation at least 20% below
the first critical RPM. Fan shafts shall be provided with a rust inhibiting coating.

3.2

Forward curved fans shall be equipped with greaseable pillow block bearings, supported on a rigid
structural steel frame.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

AIR HANDLING UNIT SCHEDULE

PAGE #: 2 OF 6
SCHEDULE B

3.3

Fixed drives shall be provided. All drives shall be provided with a rust inhibiting coating. The air
balancer shall provide for drive changes (if required) during the air balance procedure.

3.4

Fan-motor assemblies shall be provided with vibration isolators. Isolators shall be bolted to steel
channel welded to unit floor which is welded to the structural frame of the unit. The isolators shall be
neoprene-in-shear type. Fans shall be attached to the discharge panel by a heavy glass fabric,
neoprene impregnated, with a sealed double locking fabric to metal connection.

4 GAS HEAT SECTION (DJ) - Indirect Fired
4.1

Heating units shall have an indirect natural gas fired heating section that is C-ETL approved for both
sea level and high altitude areas.

4.2

Heat exchanger shall be a primary drum and multi-tube secondary assembly constructed of titanium
stainless steel with multi-plane turbulators, and shall be of a floating stress relieved design. Heat
exchanger shall be provided with condensate drain connection. The heat exchanger casing shall have
1” (25 mm) of insulation between the outer cabinet and inner liner. Blower assemblies close coupled
to duct furnace type heat exchangers are not acceptable.

4.3

The burner assembly shall be a blow through positive pressure type with an intermittent pilot ignition
system to provide a high seasonal efficiency. Flame surveillance shall be with a solid state
programmed flame relay c/w flame rod. The burner and gas train shall be in a cabinet enclosure.
Insulation in the burner section shall be covered by a heat reflective galvanized steel liner.
Atmospheric burners, or burners requiring power assisted venting are not acceptable.

4.4

Unit(s) incorporating discharge air control and wherever specified, shall include 15:1 turndown (HT
burner). The high turndown burner minimum input shall be capable of controlling at 6.7% of its rated
input without on-off cycling and include built in electronic linearization of fuel and combustion air.
Efficiency shall increase from hi to lo fire.

4.5

Operating natural gas pressure at unit(s) manifold shall be 7" (1750 Pa) w.c.

5 FILTERS
5.1

Filter sections shall be provided with adequately sized access doors to allow easy removal of filters.
Filter removal shall be from one side as noted on the drawings.

5.2

The filter modules shall be designed to slide out of the unit. Side removal 2" (50mm) filters shall slide
into a formed metal track, sealing against metal spacers at each end of the track.

5.3

2" (50mm) Replaceable Media Filters: Disposable glass fibre media type enclosed in permanent
galvanized metal frames with metal retainers on both sides.

5.4

Filter media shall meet U.L. Class 2 standards.

6 DAMPERS
6.1

Damper frames shall be u-shaped galvanized metal sections securely screwed or welded to the air
handling unit chassis. Pivot rods of 1/2" (13mm) aluminum, shall turn in bronze bushings, fabricated
from self- oiling bronze. Rods shall be secured to the blade by means of straps and set screws.

6.2

Blades shall be 18 gauge (1.3mm) galvanized metal with two breaks on each edge and three breaks
on centreline for rigidity. The pivot rod shall "nest" in the centreline break. Damper edges shall
interlock. Maximum length of damper between supports shall be 42 inches (1070mm).

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

AIR HANDLING UNIT SCHEDULE

PAGE #: 3 OF 6
SCHEDULE B

6.3

Damper linkage brackets shall be 16 gauge (1.6mm) cadmium plated steel with bronze bushings, and
shall be self aligning to prevent binding.

6.4

Dampers construction shall include blade ends sealed with an adhesive backed foamed polyurethane
gasketting. Outdoor air dampers also include an all weather PVC seal, fastened with a positive lock
grip and pliable overlap edge on entering air side of interlocking edges. Dampers are interlocked from
the centre.

6.5

Mixing dampers shall be parallel blade type. Belimo actuators supplied by unit manufacturer.

7 COILS
7.1

Coils shall be Superfin as manufactured by Engineered Air. Fins constructed of aluminum or copper
shall be rippled for maximum heat transfer and shall be mechanically bonded to the tubes by
mechanical expansion of the tubes. The coils shall have a galvanized steel casing. All coils shall be
factory tested with air at 300 psig (2070 kPa) while immersed in an illuminated water tank.

7.2

Coils shall be removable from the unit at the header end, unless shown otherwise on the drawings.

7.3

Refrigerant Superfin evaporator type coils shall be equipped with distributors connected to the coil by
copper tubes. Where a hot gas bypass is required, the inlet shall be at the refrigerant distributor.
Solenoid valves, expansion valves, and related accessories are to be provided and installed by the
refrigeration contractor.

7.42

Refrigerant coils with multiple compressors shall be alternate tube circuited in order to distribute the
cooling effect over the entire coil face at reduced load conditions. Provision for use of thermal
expansion valves must be included for variable air volume and/or make-up air applications.

8 PRE-WIRED EQUIPMENT AND FACTORY INSTALLED CONTROLS
8.1

Air handling units shall be factory wired and tested, and shall be certified by C.G.A., with C.S.A.
approved components.

8.2

Wiring shall be in accordance with the Canadian Electrical Code, Part 1, and pertinent sections of Part
2 of the Code pertaining to specific equipment type and purpose.

8.3

All electrical circuits shall undergo a dielectric strength test (CSA C22.2-0), and shall be factory tested
and checked as to proper function.

8.4

Pre-wired air handling units shall bear an approved bilingual label with all the necessary identification
marks, electrical data, and any necessary cautions as required by the Canadian Electrical Code, Part
2.

8.5

Provide a system of motor control, including all necessary terminal blocks, motor contactors, motor
overload protection, grounding lugs, control transformers, auxiliary contactors and terminals for the
connection of external control devices or relays. Gas fired units shall also include high limit and
combustion air flow switch.

8.6

Automatic controls shall be housed in a control panel mounted in or on the air handling unit, which will
meet the C.S.A. standard of the specific installation. Discharge air controller, DJM, shall be
manufactured by unit supplier to ensure single source responsibility (controllers manufactured by
secondary supplier NOT acceptable).

8.7

DJ Control
Electronic DJM (Modulating Fuel w/ Modulating Combustion Air)
Solid state analyzer complete with proportional and integral control and with a discharge air sensor to
maintain set point temperature and provide rapid response to incremental changes in discharge air

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

AIR HANDLING UNIT SCHEDULE

PAGE #: 4 OF 6
SCHEDULE B

temperature. Combustion air motor speed varies in response to the modulation of gas flow to provide
optimum fuel/air mixture and efficiency at all conditions. Combustion efficiency of heat exchangers
shall increase 4 – 5% from high fire to low fire on units incorporating 15:1 turndown (HT Burner). Heat
exchangers shall provide a minimum of 80% efficiency throughout the entire operating range.
Alternate manufacturers units which do not incorporate a variable speed combustion air blower shall
have a modulating gas valve and a combustion air damper with a linear linkage connected to an
actuator which has a minimum of 100 steps of control.
Controllers for heating units only shall include the following standard features:
• linear gas and combustion air flow obtained via a built in solid state linear algorithm
• -40F (-40C) minimum operating ambient temperature
• four (4) air change pre-purge on units with over 400 MBH (117 kw) input
• post purge
• interrupted pilot
• self check on start-up to make sure air proving and discharge air sensors are operating within
design tolerances
• low fire start
• controlled burner start-up and shut down
• diagnostic lights for ease of set-up and service
• blower contactor that starts fan after burner pre-purge
• damper contact that allows fan to start after damper opens, damper to close after fan stops and
damper to close on flame failure
• non-recycling auto by-pass low limit that has built-in sensor checking
• built-in alternate blower and damper functions and set back temperatures for unoccupied mode
operation using a single room thermostat
8.8

Damper Control – Provide modulating damper operator.

8.9

Low Limit
Provide a discharge air low limit equipped with an automatic by-pass time delay to allow for cold
weather start-up. On a heating system failure this device will shut down the fan and close the outdoor
air damper. This device shall require resetting by interrupting the electrical circuit.

8.10

Fire alarm circuits (where required) shall be powered from a relay in unit circuitry.

8.11

C-TRAC3 Controller
The controller shall automatically start in heating, economizer, or cooling mode based on continuously
monitored ambient temperature and load requirements.
The controller shall include an adjustable low limit set point for freeze protection to cease equipment
operation in the event of low discharge temperature. If the discharge air temperature falls below the
adjusted set point, the blowers will shut down and the outside air dampers shall close. ___The low
limit bypass timer shall vary automatically depending on the thermal coefficient of the style of heat
exchanger.
If the discharge air temperature approaches the low limit set point, the controller shall automatically
reduce the economizer minimum fresh air down to half of its original setting to compensate.
Dual sensors shall be used in the discharge air for precise temperature control.
As the ambient temperature falls, the C-TRAC3 controller shall automatically compensate for outside
air thermal expansion by proportionally reducing the amount of outside air.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

AIR HANDLING UNIT SCHEDULE

PAGE #: 5 OF 6
SCHEDULE B

In Occupied/Unoccupied mode (For Std AC units only) the controller shall be capable of unoccupied
heating with adjustable temperature setback with intermittent blower operation.
The heat/economizer/cool function shall be modulating discharge air with 0-10 VDC reset. Minimum
discharge air set point reverts to minimum set point if the BMS control fails.
The C-TRAC3 electronic temperature control system shall provide 3 stages of mechanical cooling
control to maintain discharge temperature. The minimum run and off time for the compressors shall
be variable based on load requirements.
When in heating mode, the C-TRAC3 shall provide a signal to the DJM2 programmed logic heating
controller for series DJ gas fired heater.
Mechanical cooling shall be disabled below an adjustable low ambient temperature set point.
The C-TRAC3 shall have indication and troubleshooting LED lights, multi-meter set point and sensor
temperature test points, and a common alarm contact in the event of equipment failure. Information
can be accessed from a PDA (personal digital assistant) or laptop computer for improved access to
control settings using Engineered Air SMC software.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

AIR HANDLING UNIT SCHEDULE

PAGE #: 6 OF 6
SCHEDULE B

AIR HANDLING UNIT SCHEDULE
AIR HANDLING UNIT TAG

AHU-1

SERVICE

Gym/Hall

FAN SECTION

LOCATION

Mezzanine Mechanical Room 204

MAKE / MANUFACTURER

DJE40/C / Engineered Air

MODEL / FAN - SIZE/TYPE

FC/15x15

TOTAL AIRFLOW RATE CFM (l/s)

4,000

(1,888)

MINIMUM FRESH AIRFLOW RATE CFM (l/s)

2,200

(1,038)

0.5

(12)

5

(4)

EXTERNAL STATIC IN. W.G. (pa)
MOTOR HP (kw)
FILTER SECTION

PLEATED 30% (MERV 7)

FILTER NO. & SIZE INCHES (mm)

2

@

20

x

25

(500

x

625)

2

@

16

x

25

(400

x

625)

HEATING
SECTION

HEATING CAPACITY KW (mbh) INPUT/OUTPUT

118/95

MEDIUM

Natural Gas

ENTERING AIR TEMP. ºF (ºC)
LEAVING AIR TEMP. ºF (ºC)

COOLING
SECTION

COOLING COIL NO. & SIZE INCHES (mm)

ACCESSORIES

(400/324)

COOLING CAPACITY TOTAL/SENS MBH (ton)

1
190

17.3

(-8.2)

92

(33.3)

@

30

(15.9)

MEDIUM

x

50
/

(750

x

1250)

123

(10.3)

R-22

ENTERING AIR TEMP. DRY/WET ºF (ºC)

81.6

(27.6)

/

68

(20)

LEAVING AIR TEMP. ºF (ºC)

53.1

(11.7)

/

52.8

(11.6)

MAX. AIR PRESSURE DROP IN. W.G. (pa)

0.6

(152)

MAX. FACE VELOCITY FPM (m/min)
UNIT WEIGHT LBS (kg)

500

(152)

2200

(998)

Vertical Configuration
Controls for heating and cooling shall be suitable for
control by the DDC system.

END OF SCHEDULE B

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg MB
PART 1

PAGE #: 1 OF 2
SCHEDULE C

SPECIFICATIONS
.1

GENERAL
.1
Unit shall be ETL and cETL approved, completely assembled for one-piece shipping and
rigging, leak pressure and functionally tested at the factory to assure a trouble-free startup after installation, covered by a 1-year limited parts warranty on the complete unit.
.2
Unit shall have a steel angle frame to provide the rigid support required for shipping,
riggin and years of dependable operation, zinc-coated steel that has been finished by a
powder paint process to provide a long-lasting quality appearance, removable panels for
easy access to all internal components during maintenance and service.
.3
The dimensions of each unit shall not exceed those specified in the plans.
.4
Each compressor shall be mounted on isolators to minimize the transmission of vibration.
.5
All condenser coils be draw thru design and constructed of copper tubes arranged in
staggered rows and mechanically expanded into aluminum fins.
.6
The condenser fan motor(s) shall be directly connected to the condenser fans, have
permanently lubricated ball bearings, have inherent overload protection and be arranged
for vertical discharge of the condenser air.

.2

OPTIONS ON YORK MODEL CMB
.1
Low Ambient Pressure Switch Kit.

.3

GYM CONDENSING UNIT
.1
GENERAL
.1
Compressors shall be hermetic type, 3600 RPM, set on resilient neoprene
mounts and complete with line voltage break internal overload protection, internal
pressure relief valve and crankcase heater.
.2
Condenser coils shall be copper tube type, mechanically expanded into
aluminium fins. Coils shall be factory tested with air at 300 psig (2070 kPa) while
immersed in an illuminated water tank. Coils shall be C.S.A. certified.
.3
Condenser fans shall be direct driven propeller type arranged for vertical draw
through air flow. Motors shall be weather resistant type, with integral overload
protection and designed for vertical shaft condenser fan applications. Fan and
motor assemblies shall be mounted on a formed orifice plate for optimum
efficiency with minimum noise level.
.2

PART 2

CONDENSING UNIT SCHEDULE

Split System Condensing Units
.1
Condensing units shall be C.S.A. approved. Condensing units shall be designed
for a minimum of 15 F (8 C) liquid sub cooling. Condensing units shall operate
down to 50 F (10 C) as standard. Multiple compressor/condenser circuits shall
be separate from each other. Suction and liquid lines shall be extended to the
outside of the cabinet. Service ports fitted with Schraeder fittings shall be
connected to the suction and discharge lines for charging or pressure gauge
readings.
.2
Controls for hermetic compressor units shall include compressor and condenser
fan motor contactors, control circuit transformer, cooling relays, recycling
pumpdown relays, ambient compressor lockout, high pressure controls and
automatic reset low pressure controls. Head pressure actuated fan cycling
control shall be provided on all dual condenser fan units.

STANDARD OF ACCEPTANCE
.1

Base Bid: As per schedule.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg MB
PART 3

CONDENSING UNIT SCHEDULE

PAGE #: 2 OF 2
SCHEDULE C

SCHEDULE

CONDENSING UNIT SCHEDULE
CAPACITY
NO.

SERVICE

MAKE

MODEL

MBH

VOLT

PHASE

MCA

MOP
Max/Min

208

1

32.7

50/35

208

1

30.3

50/30

208

1

15.1

25/15

208

1

8.9

15/10

208

1

18.3

30/20

208

1

8.9

15/10

208

1

8.9

15/10

208

1

15.1

25/15

208

1

15.1

25/15

208

1

18.3

30/20

208

1

30.3

50/30

600

3

600/3

10.53

20.1

30/30

(ton)
CU-1

FC-1

York

CMB060

CU-2

FC-2

York

CMB048

CU-3

FC-3

York

CMB030

CU-4

FC-4

York

CMB018

CU-5

FC-5

York

CMB036

CU-6

FC-6

York

CMB018

CU-7

FC-7

York

CMB018

CU-8

FC-8

York

CMB030

CU-9

FC-9

York

CMB030

CU-10

FC-10

York

CMB036

CU-11

FC-11

York

CMB048

CU-12

AHU-1

EngA

CUA173

CU-13

HRV-1

York

HA120

60
(5)
48
(4.)
30
(2.5)
18
(1.5)
36
(3.)
18
(1.5)
18
(1.5)
30
(2.5)
30
(2.5)
36
(3.)
48
(4.)
190
(15.9)
120
(10.)

END OF SCHEDULE C

REMARKS
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
c/w Low
Ambient Kit
17 Tons
3 Circuits
c/w hot gas
bypass

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

FAN COIL UNIT SCHEDULE

PAGE #: 1 OF 3
SCHEDULE D

SPECIFICATIONS
.1

.2

GENERAL
.1
Furnish and install Belt Drive Blower Coil Units where indicated on the plans and
specifications. Units shall be completely factory assembled and tested and shipped as
one piece except where noted.
.2

All units shall be capable of meeting or exceeding the scheduled capacities for cooling,
heating and air delivery. All unit dimensions for each model and size shall be considered
maximums.

.3

All units shall be of “draw-thru” design with coils, fans, motor/ drive and drain pan
completely contained within the unit cabinet.

.4

Electric heat to be in the blow-thru configuration.

.5

Units shall be cETL listed in compliance with UL/ANSI Std. 1995.

.6

All unit coils shall meet or exceed the scheduled cooling and heating capacity, selected
and rated in accordance with ARI 410.

CONSTRUCTION
.1
All units shall be fabricated of minimum 18 gauge galvanized steel with a G90 zinc
coating, able to withstand a 125 hour salt spray test per ASTM B-117. Panels shall be
die-formed “multi-bend” construction for optimum strength and rigidity. All exterior panels
shall be (single wall insulated with 1 inch, 4 pound per cubic foot skin, dual density
fiberglass insulation) (foil faced-insulated with 1" thick, 1.8 pound per cubic foot density
scrim reinforced foil faced insulation), rated for a maximum air velocity of 3600 f.p.m. In
addition to using adhesive complying with NFPA 90A, the insulation shall incorporate a
secondary mechanical fastener attached to the unit casing wall (weld pin). Adhesive as
the only method of fastening the insulation to the casing is not acceptable. Minimum
thermal conductivity shall be 0.24. Insulation must meet all requirements of UL 181 and
NFPA 90A. All units shall have minimum 1" duct collars on discharge and return.
.2

All access panels shall be fully insulated and attached with standard fasteners on at least
two opposite sides. No single access panel shall be larger than 30” x 36” for safety and
ease of handling. No coil or drain piping or electrical connections shall pass through any
access panel.

.3

Each unit shall be furnished with a one-piece heavy gauge IAQ 304 stainless steel drain
pan with welded corner construction.

.4

All units shall be provided with 9/16” diameter hanger rod holes in the top and bottom
panels for “through-bolt” type suspension installation. Spring type unit mounting vibration
isolators shall be provided by the unit manufacturer.

.3

FAN ASSEMBLY
.1
All units shall be furnished with standard selection double inlet forward curved centrifugal
blowers statically and dynamically balanced for smooth operation. All blower wheels
shall have two set screws and shall be mounted on solid steel shafting rotating in ball
bearings with a minimum design average life of 100,000 hours. All standard blower
assemblies shall have resilient mounted cartridge type permanently lubricated ball
bearings.

.4

FAN MOTOR & DRIVE ASSEMBLY
.1
All fan motors shall be standard NEMA design motors of the horsepower listed in the
equipment schedule. All motors shall be 1750 RPM, 60 hertz ODP single speed motors
rated for continuous duty. All motors shall be reversible rotation type.
.2

Three phase motors shall be “across-the-line” start type in 56 Frame size up through two
horsepower.

.3

All motors shall be mounted on an adjustable base.

.4

All motor wiring is to be terminated in a junction box, external to the unit casing.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
.5

.5

FAN COIL UNIT SCHEDULE

PAGE #: 2 OF 3
SCHEDULE D

All fan drive assemblies shall include an adjustable pitch motor pulley, a fixed pitch
blower pulley and a standard cross section “V-belt”. All fan drives shall be selected at a
minimum service factor of 1.2.

COILS
.1
All unit coils shall be rated in accordance with ARI 410.
.2

All coils shall be 1/2" O.D. seamless copper tubes with collared and corrugated aluminum
fins. All tubes shall be mechanically expanded to provide an efficient bond between tube
and fin.

.3

Direct expansion (DX) coils shall have 0.0055" thick aluminum fins and 0.016" tube wall
thickness.

.4

DX coils shall be tested to 450 PSIG pressure and factory sealed and charged with a
minimum of 5 PSIG nitrogen or refrigerated dry air. DX coils shall be provided with a
fixed orifice refrigerant distributor. A field furnished and installed thermal expansion valve
(TXV) shall be mounted directly to the refrigerant distributor.

.5

Tube wall thickness shall be 0.025" on chilled water, hot water, and direct expansion
coils.

.6

FILTER RACK ASSEMBLY
.1
All units shall be furnished with a flat filter rack with hinged access on both sides
designed to accept a 2" nominal standard sized filters. All units shall be provided with
nominal 2" pleated filters factory installed. One complete set of spare pleated filters shall
be provided for each unit.

.7

DISCHARGE PLENUM SECTION
.1
Where shown on the plans, the unit manufacturer shall furnish a fully insulated discharge
plenum section complete with a double deflection supply grille (cannot be used with
discharge heating coil plenum options).

.8

ELECTRICAL CONTROL
.1
The unit fan motor shall be completely factory wired to an external electrical enclosure.
Each unit shall include fan control package with 24 volt control voltage. Each unit shall
include motor circuit fusing, contactor, control circuit transformer and terminal strip for
connection of field wiring.
.2

.9

A main incoming power fused disconnect switch shall be factory furnished and wired by
the unit manufacturer for single point power connection.

ELECTRIC HEAT SECTION
.1
Where shown on the plans and in the schedule, the unit manufacturer shall furnish an
electric resistance heating assembly with the heating capacity, voltage and stages as
shown in the schedule. The heater assembly shall be designed and rated for installation
to the blower coil unit in the blow-thru configuration without the use of duct extensions or
transitions between the unit and the heater assembly. The heater assembly shall be
factory assembled to the air handling unit and completely factory wired. The heater/unit
assembly shall be listed for zero clearance meeting all N.E.C. requirements and be cETL
listed in compliance with UL/ANSI Std. 1995.
.2

All heating elements shall be open coil design using Ni-Chrome wire mounted in ceramic
insulators and housed in an insulated heavy gauge galvanized steel housing. All
elements shall terminate in a machine staked stainless steel terminal secured with
stainless steel hardware. The element support brackets shall be spaced no greater than
3-1/2" on center. All internal wiring shall be rated for 105°C minimum.

.3

All heaters shall include over-temperature protection. All heaters shall include a nonadjustable airflow switch.

.4

An incoming line power distribution block shall be provided. The power distribution block
shall be designed to accept incoming power wiring capable of carrying 125% of the
calculated load current.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
.5

PART 2

PAGE #: 3 OF 3
SCHEDULE D

In addition to the above, electric heaters shall include the following options:
.1
Main incoming power disconnect fused.
.2
Magnetic contactors wired for disconnecting operation
.3
Fan control package with heater interlock contacts.
.4
Minimum two stages of heating control

STANDARD OF ACCEPTANCE
.1

PART 3

FAN COIL UNIT SCHEDULE

Base Bid: All selections are based on Johnson Controls Model AHI Horizontal.
SCHEDULE

FAN COIL UNIT SCHEDULE
AIR
NO.

FC-1

MultiMultiGames

(661)

(75)

(0.4)

(27 / 20)

(5.3)

(3.5)

(21.1)

(20)

150

JCI

AHI-12

1,300

0.3

1

80 / 67

56.1

37.7

70

5

(613)

(75)

(0.7)

(27 / 20)

(4.7)

(3.2)

(21.1)

(17)

102

JCI

AHI-8

AHI-8

Office
BPCC

106 &

Office

115-117

Wellness/

112 & 114

JCI

AHI-8

JCI

AHI-8

125

JCI

AHI-8

GNSC Mtg
Lab

FC-11

SENS
6

JCI

Impove
Lounge

DB
70

107-111

Home

DB/WB

41.9

GNSC

FC-10

(kw)

63.3

FC-5

Creative

(pa)

80 / 67

AHI-8

FC-9

TOTAL SENS

70ºF

3/4

JCI

Computer

MBH (tons)

0.3

103

FC-8

EAT (ºF)

1,400

Meeting

FC-7

EAT (ºF) KW (mbh)

HP

AHI-16

FC-4

FC-6

HEATING HEATING

JCI

Purpose
FC-3

COOLING

150

Purpose
FC-2

E.S.P MOTOR COOLING

SERVICE LOCATION MAKE MODEL CFM (l/s) IN. H2O

700

0.3

1/2

80 / 67

33.5

21.8

70

4

(330)

(75)

(0.3)

(27 / 20)

(2.8)

(1.9)

(21.1)

(14)

500

0.3

1/3

80 / 67

22.2

14.6

70

3

(236)

(75)

(0.2)

(27 / 20)

(1.9)

(1.3)

(21.1)

(10)

875

0.3

3/4

80 / 67

39.3

26.1

70

5

(413)

(75)

(0.4)

(27 / 20)

(3.3)

(2.2)

(21.1)

(17)

300

0.3

1/3

80 / 67

13.1

8.6

70

3

(142)

(75)

(0.2)

(27 / 20)

(1.1)

(0.8)

(21.1)

(10)

345

0.3

1/3

80 / 67

16.9

10.9

70

3

(163)

(75)

(0.2)

(27 / 20)

(1.5)

(1.0)

(21.1)

(10)

700

0.3

1/2

80 / 67

33.5

21.8

70

3

(330)

(75)

(0.3)

(27 / 20)

(2.8)

(1.9)

(21.1)

(10)

590

0.3

1/3

80 / 67

29.4

19.0

70

3
(10)

123-124

JCI

AHI-8

(278)

(75)

(0.2)

(27 / 20)

(2.5)

(1.6)

(21.1)

121-122

JCI

AHI-8

880

0.3

3/4

80 / 67

39.5

26.2

70

8

AHI-12

(415)
1,200

(75)
0.3

(0.4)
3/4

(27 / 20)
80 / 67

(3.3)
53.2

(2.2)
35.4

(21.1)
70

(27)
8

(566)

(75)

(0.6)

(27 / 20)

(4.5)

(3.0)

(21.1)

(27)

Arts

101

JCI

END OF SCHEDULE D

Total Amps
(amps)

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

PART 3

FAN SCHEDULE

PAGE #: 1 OF 1
SCHEDULE E

SPECIFICATIONS
.1

Weatherproof, seamless, heavy gauge, spun aluminum housing, easily removed for service
access

.2

Roof mounted, downflow or upflow configuration as noted

.3

Recessed base suitable for mounting on roof curb and acting as counterflashing

.4

Centrifugal, non-overloading, backward inclined, aluminum fan wheel (non-sparking construction)

.5

Heavy duty ball bearings with minimum life of 200,000 hours

.6

Belt driven with adjustable pulleys

.7

Motor to be mounted out of the airstream, with positive cooling ventilation air

.8

Electrical conduit chase to be provided through the unit, with UL safety disconnect switch, and
wiring between the switch and the motor

.9

hinged sub-base and gravity backdraft damper

.10

Aluminum birdscreen

.11

Factory fabricated roof curb or field fabricated roof curb at the Sub-contractor's option
SCHEDULE

FAN SCHEDULE
NO.

SERVICE

MAKE

MODEL

AIR

E.S.P

CFM (l/s)

IN. H2O

RPM

HP

70ºF

(pa)

(kw)

EF-1

MOTOR

VOLTS

PHASE
REMARKS

Kitchen
Cook
VCR-HP
1,600
1
1331
3/4
208
3
1
148
165VH6B
(755)
(250)
(0.6)
EF-2
Zamboni
Cook
ACE-B
800
0.5
1200
1/4
120
1
2
131
120C
(377)
(125)
(0.2)
EF-3
Electrical
Cook
ACE-B
3,000
0.5
1065
1
208
3
3
202
180C
(1415)
(125)
(0.7)
Table Notes:
1. Upblast fan. Furnish with disconnect switch, prefabricated ventilated restaurant roof curb, curb hinge kit, and
grease trough kit. Fan to be ULC listed for grease extraction and compliant with NFPA 96. Coordinate power
supply with Division 26.
2. Downblast fan. Furnish with disconnect switch, prefabricated roof curb and normally closed motorized damper
wired to open when fan "runs".
3. Downblast fan with two speed motor. Furnish with disconnect switch, prefabricated roof curb and normally
closed motorized damper wired to open when fan "runs".
END OF SCHEDULE E

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PART 1
1.1

HEAT REVOCERY UNIT SCHEDULE

PAGE #: 1 OF 2
SCHEDULE F

SPECIFICATIONS
HEAT RECOVERY VENTILATOR HRV-1
.1

Packaged Heat Recovery Ventilator

.2

Belt Driven, Centrifugal type Supply and Exhaust Blowers, each with internal vibration isolation
and sealed ball bearings.

.3

Integral Defrost and Speed Controls, including Motorized Dampers, sensors, 24V transformer,
and Integral Micro-processor circuit board with power and control interlocks and contacts.

.4

motors shall be continuous duty, permanently lubricated.

.5

Single point power supply for 208V / 3 phase

.6

Insulated motorized Outside Air Damper

.7

Insulated Gravity Backdraft Exhaust Air Damper

.8

Indoor Units:
.1

Double wall construction fully insulated with 1" high density Styrofoam. Inner wall
constructed of 24 Ga G90 galvanized steel. Outer wall constructed of 20 Ga G90
Galvanized steel and sealed access doors

.2

4 ducted connections

.3

Flat Plate Polypropylene heat recovery core.

.4

Sealed Fan Bearings

.5

Washable Foam Filters in Exhaust and Supply Air Streams

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PAGE #: 2 OF 2
SCHEDULE F

SCHEDULE

HEAT RECOVERY UNIT SCHEDULE
HRV TAG

HRV - 1

SERVICE

Building

FAN SECTION

LOCATION

Mech Room

MAKE / MANUFACTURER

Nu-Air NU2035

MODEL / FAN - SIZE/TYPE

FC, DWDI

TOTAL SUPPLY AIRFLOW RATE CFM (l/s)

3,770

(1,778)

TOTAL EXHAUST AIRFLOW RATE CFM (l/s)

2,430

(1145)

1.2

(300)

MOTOR HP/voltage/phase (kw/voltage/phase)

2.0/208/3

(1.5/208/3)

FILTER SECTION

PLEATED 30% (MERV 7)

EXTERNAL STATIC IN. W.G. (pa)

POLYPROPYLENE CORE WITH A MINIMUM OF
62% SENSIBLE EFFECTIVENESS

ACCESSORIES

PART 3

HEAT REVOCERY UNIT SCHEDULE

FACE AND BYPASS DEFROST
PAINTED EXTERIOR FINISH
DISCONNECT SWITCH

END OF SCHEDULE F

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

MAKE UP AIR UNIT SCHEDULE

PAGE #: 1 OF 2
SCHEDULE G

SPECIFICATIONS
.1

The direct fired make up air unit shall be design certified by CSA International and CAN ETL.

.2

CONSTRUCTION FEATURES
.1
Housing constructed of heavy duty G90 galvanized steel
.2
Forward curved centrifugal blower wheel
.3
Vibration isolation
.4
Adjustable drive assemblies
.5
Adjustable motor mount
.6
Ball bearing motors
.7
Heavy duty, pre-lubricated bearings rated for 200,000 hours of operation
.8
Static resistant belts
.9
Service doors on both sides
.10
down discharge
.11
Spring loaded profile plates automatically adjust for any airflow
.12
Weatherproof safety disconnect switch
.13
Fully insulated casing
.14
ETL listed

.3

BLOWER
.1
10" forward curved, centrifugal blower.
.2
Permanently lubricated ball bearings.
.3
Galvanized finish.
.4
3/4" Shaft.
.5
0-4000 CFM.
.6
2500 max. RPM.
.7
Used in heated and non-heated supply fans.

.4

TEMP CONTROL
.1
Maxitrol 14
.2
40-80°F Discharge Temp Control

.5

INTAKE
.1
Sloped Foam Filtered Intake for Size #1 Modular Heater.
.2
21.813" Wide x 44.375" Long x 23.375" High.
.3
Includes 2" Foam EZ Kleen Metal Mesh Filters.

.6

FILTERS
.1
3 - EZ Kleen Non-Woven Polyester Metal Mesh Filter.
.2
20"x 25"x 2" Used for heater and supply fan intakes.
.3
23 layers of expanded aluminum and one layer of non-woven polyester.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

MAKE UP AIR UNIT SCHEDULE

PAGE #: 2 OF 2
SCHEDULE G

MAKE UP AIR UNIT SCHEDULE
MAKE UP AIR UNIT

MAU-1

FAN SECTION

SERVICE

Direct Fired Kitchen Make Up Air

LOCATION

Roof

MAKE / MANUFACTURER

CaptiveAire A1-D.250-G10

MODEL / FAN - SIZE/TYPE

10" FC

TOTAL AIRFLOW RATE CFM (l/s)

1,600

(755)

EXTERNAL STATIC IN. W.G. (pa)

1

(250)

MOTOR HP (kw)

1

(1)

FILTER SECTION

2" EZ Keen Non-Woven Polyester Metal Mesh

ACCESSORIES

HEAT
ING

FILTER NO. & SIZE INCHES (mm)
HEATING CAPACITY KW (MBH)

1

@

20

x

25

55.7

MEDIUM

(500
(190)

Gas

TEMP RISE ºF ( ºC)

110

(61)

UNIT WEIGHT LBS (kg)

552

(250)

PACKAGED C/W ALL CONTROLS

END OF SCHEDULE G

x

625)

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

GRILLE & DIFFUSER SCHEDULE

PAGE #: 1 OF 1
SCHEDULE H

GRILLE & DIFFUSER SCHEDULE
TYPE

MAKE

MODEL

SERVICE

BORDER

CORE

BLADE

FRAME

FASTEN

FINISH

REMARKS

S1

EH

SCD

SUPPLY

-

3C

-

3P

-

NOTE 1

NOTE 2

SCD

SUPPLY

-

3C

-

3P

-

NOTE 1

NOTE 2

SCD

SUPPLY

-

3C

-

3P

-

NOTE 1

NOTE 2

SDGE

SUPPLY

-

-

-

-

A

NOTE 1

NOTE 3

520

SUPPLY

F

520D

L

-

A

NOTE 1

-

520

SUPPLY

F

520D

L

-

A

NOTE 1

-

SPD

SUPPLY

-

-

-

3P

-

NOTE 1

NOTE 2

80

RETURN

CH

80

-

-

-

NOTE 1

-

90

RETURN

-

90

L

-

A

NOTE 1

-

10A

RETURN

F

10A

-

-

A

NOTE 1

-

80

EXHAUST

F

80

-

-

A

NOTE 1

-

90

EXHAUST

-

90

L

-

A

NOTE 1

-

K609

LOUVER

PRICE
S2

EH
PRICE

S3

EH
PRICE

S4

EH
PRICE

S5

EH
PRICE

S6

EH
PRICE

S7

EH
PRICE

R1

EH
PRICE

R2

EH
PRICE

R3

EH
PRICE

E1

EH
PRICE

E2

EH
PRICE

L1

AIROLITE

NOTE 1

TABLE NOTES:
NOTE 1 FINISH AS SELECTED BY THE CONTRACT ADMINISTRATOR
NOTE 2 600mm(24")x600mm(24") MODULE AND DIFFUSER FACE SIZE.
NOTE 3 COMPLETE WITH OPPOSED BLADE DAMPER.

END OF SCHEDULE H

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 1 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

WC-1
General use

TOILET - FLOOR MOUNTED EXPOSED FLUSH VALVE (DUAL FLUSH FLUSH
VALVE)
American Standard #3451.160 'MADERA ELONGATED' 'Low Consumption' Toilet,
floor mounted, vitreous china, EverClean™ antimicrobial surface which inhibits the
growth of stain and odor causing bacteria, mold and mildew, elongated syphon jet
flush action bowl, 2-1/8" (54mm) fully glazed internal trapway, 10" x 12" (254mmx
305mm) large water surface, 6L (1.6 gal.) per flush, 1-1/2" (38mm) top spud with
condensate channel and bolt caps, for use with flush valve. Provide Floor Flange,
flange bolts and gasket. Sloan #WES 111-YO 'UPPERCUT' Water Saving Dual Flush
Flushometer, C.P. low consumption, factory set flow, quiet action diaphragm type
with non-hold open feature, vacuum breaker and extended seat bumper on backcheck angle stop and anti-microbial green lever handle, down 6 LPF / up 4.2 LPF
consumption. Centoco #AM500STSCC Toilet Seat, elongated heavy duty solid
plastic with Anti-Microbial Compound (to inhibit the growth of bacteria), open front
less cover, with reinforced stainless steel check hinge, posts, washers and nuts.

WC-2
Handi cap

TOILET - FLOOR MOUNTED EXPOSED FLUSH VALVE (BARRIER FREE
DESIGN) (DUAL FLUSH FLUSH VALVE)
American Standard #3461.160 'MADERA ELONGATED 16-1/2" (419mm) HIGH' Low
Consumption Toilet, floor mounted, vitreous china, EverClean™ antimicrobial surface
which inhibits the growth of stain and odor causing bacteria, mold and mildew,
elongated syphon jet flush action bowl, 2-1/8" (54mm) fully glazed internal trapway,
10" x 12" (254mm x 305mm) large water surface, 6L (1.6 gal.) per flush, 1-1/2"
(38mm) top spud with condensate channel and bolt caps, for use with Flush Valve.
Provide Floor Flange, flange bolts and gasket. Sloan #WES 111-YG 'UPPERCUT'
Water Saving Dual Flush Flushometer, C.P. low consumption, factory set flow, quiet
action diaphragm type with non-hold open feature, vacuum breaker and extended
seat bumper on back-check angle stop and anti-microbial green lever handle, down 6
LPF / up 4.2 LPF consumption. Centoco #AM820STS Toilet Seat, elongated heavy
duty solid plastic with Anti-Microbial Compound (to inhibit the growth of bacteria),
open front with cover, reinforced stainless steel check hinge, posts, washers and
nuts.

UR-1
General Use

URINAL - WALL HUNG - EXPOSED FLUSH VALVE
American Standard #6501.010 'WASHBROOK' Low Consumption Urinal, wall hung,
vitreous china, washdown flush action 3.8L (1.0 Gal.) flush, extended sides for
privacy, integral flush spreader, outlet connection, less strainer, 3/4" (19mm) top
spud, wall hangers, open trap, for use with flush valve.American Standard #0470680070A Strainer, removable stainless steel, 2" (50mm) outlet, connecting flange with
gasket and bolts. Sloan #186-1-XL REGAL Flush Valve, C.P. low consumption, 3.8
LPF (1.0 GPF) factory set flow, quiet action diaphragm type with non hold open
feature, vacuum breaker and back-check angle stop. Jay R. Smith #SQ4-1819 Urinal
Wall Access Cleanout, with round stainless steel face and V.P. screw. Jay R. Smith
#0637 Urinal Carrier, with steel pipe legs, block base feet supports and bearing
plates.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 2 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

LAV-1
General Use

BASIN - COUNTER MOUNTED (STAINLESS STEEL)
Franke 'WASHROOM SYSTEMS' #OV1821-5-1 Basin, centre hole, 21" x 18" x 5"
(530mm x 460mm x 127mm) deep, counter mounted, grade 18-10 type 304 stainless
steel, front overflow, mirror finished rim, satin finished bowl, self-rimming.Chicago
Faucets #333-V-665-MT Metering Single Tempered Water Faucet, C.P. single hole
C.C., solid cast brass lead-free body, 'SLO-KLOSE' cartridge with vandal resistant 1
L/cycle (0.25 gpc) per push flow spray spout, easy-tip lever handle and mixing tee
with inlet check tails. McGuire #155A-X Basin Drain, C.P., cast brass 1 pc. top, open
grid with 17ga. (1.5mm), 1-1/4” (32mm) tailpiece with double gasket. McGuire
#H170BV Basin Supplies, C.P., polished brass, rigid horizontal integral copper sweat
tube nipple, 1/2" (12mm) I.D. x 5" (127mm) long, all brass 1/4 turn ball valves angle
stops with combination V.P. loose key and handle, escutcheons and flexible copper
risers. McGuire #8872C-17T 'p' Trap, C.P. brass adjustable body, 17 gauge (1.5mm),
1-1/4" (32mm) and escutcheon.

LAV-2
Handi Cap

BASIN - WALL HUNG (BARRIER FREE DESIGN) LARGE FLAT SLAB DESIGN
American Standard #9141.011 'WHEELCHAIR BASIN', 4" (102mm) centres, 27" x
20" x 3 - 7-1/2" (686mm x 508mm x 76 - 191mm) deep, wall hung, vitreous china, flat
slab, low front lip for wheelchair access, front overflow, for concealed arm
carrier.Chicago Faucets #802-V-317-XK Faucet, C.P. 4" (102mm) C.C., solid cast
brass lead-free body, 1/4 turn ceramic disc valve cartridges, with vandal resistant 7.6
LPM (2.0 GPM) flow aerator outlet and cast brass 4" (102mm) blade handles.
McGuire #155WC Basin Drain, C.P., cast brass 1pc. top, offset open grid with 17ga.
(1.5mm), 1-1/4” (32mm) tailpiece. McGuire #H165LKN3RB Basin Supplies, C.P.,
polished brass, rigid horizontal nipple 3/8" (9.5mm) x 3" (75mm) long I.P.S., heavy all
brass angle stops, with V.P. loose key, escutcheons and S.S. braided flexible risers.
McGuire #8872C 'p' Trap, C.P., polished, cast brass adjustable body, 1-1/4" (32mm)
with cleanout plug, seamless brass wall bend and escutcheon. Jay R. Smith #0700Z-27 Basin Carrier, with steel pipe legs, block base feet support, narrow sleeve and
base for extended concealed arms. McGuire #PW2000WC 'PROWRAP' Sanitary
Covering, of PVC, vandal-resistant flexible seamless construction, anti-microbial, to
exposed piping (to protect against heat/contusions) as per local codes.

LAV-3
General Use
(Wellness)

BASIN - WALL HUNG (BARRIER FREE DESIGN & GENERAL USE) FOR TIGHT
SPACE AREAS
American Standard #0954.000 'MURRO' Basin, 4" (102mm) centres, 22" x 21"x 5 - 71/2" (559mm x 533mm x 127-191mm) deep, wall hung, vitreous china, integral back
splash, self draining deck area, sloped front lip, rear overflow, for concealed arm
carrier.Chicago Faucets #802-V-665 Metering Faucet, C.P. 4" (102mm) C.C., solid
cast brass lead-free body, 'SLO-KLOSE' cartridges, with vandal resistant 1L/cycle
(0.25 GPC) per push flow spray, flow aerator outlet and cast brass push handles (5#
(2.2 kg) push faucet - check local codes for usage). McGuire #155A Basin Drain,
C.P., cast brass 1 pc. top, open grid with 17ga. (1.5mm), 1-1/4” (32mm) tailpiece.
McGuire #H165LKN3RB Basin Supplies, C.P., polished brass, rigid horizontal nipple
3/8" (9.5mm) x 3" (75mm) long I.P.S., heavy all brass angle stops, with V.P. loose
key, escutcheons and S.S. braided flexible risers. McGuire #8872C 'p' Trap, C.P.,
polished, cast brass adjustable body, 1-1/4" (32mm) with cleanout plug, seamless
brass wall bend and escutcheon. Jay R. Smith #0700-Z Basin Carrier, with steel pipe
legs, block base feet support and concealed arms. (For narrow wall installation
provide 'Z' type sleeve for arms). American Standard #0059.020 Semi-China
Pedestal, to exposed piping (to protect against heat/contusions) as per local codes.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 3 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

LAV-4
General Use
(Dressing Rooms)

BASIN - WALL HUNG (BARRIER FREE DESIGN & GENERAL USE) FOR TIGHT
SPACE AREAS
American Standard #0954.000 'MURRO' Basin, 4" (102mm) centres, 22" x 21"x 5 - 71/2" (559mm x 533mm x 127-191mm) deep, wall hung, vitreous china, integral back
splash, self draining deck area, sloped front lip, rear overflow, for concealed arm
carrier.Chicago Faucets #802-V-XK Faucet, C.P. 4" (102mm) C.C., solid cast brass
lead-free body, 1/4 turn ceramic disc valve cartridges, with vandal resistant 7.6 LPM
(2.0 GPM) flow aerator outlet and cast brass lever handles. McGuire #155A Basin
Drain, C.P., cast brass 1 pc. top, open grid with 17ga. (1.5mm), 1-1/4” (32mm)
tailpiece. McGuire #H170BVRB Basin Supplies, C.P., polished brass, rigid short
horizontal integral copper sweat tube nipples, 1/2" (12mm) I.D. x 5" (127mm) long, all
brass 1/4 turn ball valve angle stops with combination V.P. loose key and handles,
escutcheons and S.S. braided flexible risers. McGuire #8872C-17T 'p' Trap, C.P.
brass adjustable body, 17 gauge (1.5mm), 1-1/4" (32mm) and escutcheon. Jay R.
Smith #0700-Z Basin Carrier, with steel pipe legs, block base feet support and
concealed arms. (For narrow wall installation provide 'Z' type sleeve for arms).
American Standard #0059.020 Semi-China Pedestal, to exposed piping (to protect
against heat/contusions) as per local codes.

LAV-5
General Use
(Barrier Free)

BASIN - COUNTER MOUNTED (BARRIER FREE DESIGN)
American Standard #9494.001 'CADET UNIVERSAL ACCESS' Basin, 4" (102mm)
centres, 21" x 17-1/2" x 5-1/4 - 6-7/8" (533mm x 445mm x 133-175mm) deep,
counter mounted, vitreous china, rear overflow. Provide basin rim sealant.Chicago
Faucets #802-V-317-XK Faucet, C.P. 4" (102mm) C.C., solid cast brass lead-free
body, 1/4 turn ceramic disc valve cartridges, with vandal resistant 7.6 LPM (2.0 GPM)
flow aerator outlet and cast brass 4" (102mm) blade handles. McGuire #155WC
Basin Drain, C.P., cast brass 1pc. top, offset open grid with 17ga. (1.5mm), 1-1/4”
(32mm) tailpiece. McGuire #H165LKN3RB Basin Supplies, C.P., polished brass, rigid
horizontal nipple 3/8" (9.5mm) x 3" (75mm) long I.P.S., heavy all brass angle stops,
with V.P. loose key, escutcheons and S.S. braided flexible risers. McGuire #8872C 'p'
Trap, C.P., polished, cast brass adjustable body, 1-1/4" (32mm) with cleanout plug,
seamless brass wall bend and escutcheon. ATS SPEC #BF-1 'Sanitary Safti-Covers'
of PVC, vandal-resistant flexible seamless construction, anti-microbial, to exposed
piping (to protect against heat/contusions) as per local codes.

SH-1
General Use

SHOWER - PRESSURE BALANCING VALVE
Symmons #4-5000-X 'SAFETYMIX' Shower Valve, C.P. heavy duty pressure
balancing controller, all brass and stainless steel body design, maximum temperature
limit stop, service stops, metal escutcheon plate, heavy duty spindle with single
control metal lever handle. Symmons #4-150 'SENIOR' Institutional Head, C.P. cast
brass, one piece, with 7.6 LPM (2.0 GPM) flow and secured with vandal-resistant
screws. Bobrick #B207 Curtain Rod, S.S. 1" (25mm) dia. 20 GA. (1.0mm). Bobrick
#B204-2/B204-1 White Vinyl Curtain, 42" x 72" (1065mm x 1830mm) with S.S.
hooks. Jay R. Smith #2005A Floor Drain, with water proofing flange and nickel
bronze strainer. Provide 'p' Trap.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 4 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

SH-2
Handi Cap

SHOWER - PRESSURE BALANCING VALVE (BARRIER FREE DESIGN) (HAND
SHOWER SPRAY)
Symmons #1-250-X-FSB30-V 'SAFETYMIX' Shower Valve, C.P. heavy duty pressure
balancing controller, all brass and stainless steel body design, maximum temperature
limit stop, service stops, metal escutcheon plate, heavy duty spindle with single
control metal lever handle, with 7.6 LPM (2.0 GPM) flow adjustable hand shower
spray, 30" (762mm) offset slide bar, 59" (1500mm) flexible metal hose, supply elbow,
with flange and inline vacuum breaker. Bobrick #B207 Curtain Rod, S.S. 1" (25mm)
dia. 20 GA. (1.0mm). Bobrick #B204-3/B204-1 White Vinyl Curtain, 70" x 72"
(1778mm x 1830mm) with S.S. hooks. Symmons #QD C.P. Snap-On / Off Quick
Disconnect, for removal of hand shower and hose assembly. Jay R. Smith #2005A
Floor Drain, with water proofing flange and nickel bronze strainer. Provide 'p' Trap.

SK-1
General Use
(Office)

SINGLE BOWL SINK - STAINLESS STEEL - BACK LEDGE
Franke 'WASHROOM SYSTEMS' #LBS6808-1-4 S.S. Sink, 4 hole, 20-1/2" x 20" x 8"
(521mm x 508mm x 203mm) deep, counter mounted, back ledge, grade 18-8 type
302 stainless steel, single compartment, satin finished rim and bowl, self rimming,
with crumb cup strainer, sound deadening and mounting kit. Extra hole
(specify).Chicago Faucets #2301-V-8 'MARATHON' Faucet, C.P. 8" (203mm) C.C.,
deck mounted, solid cast brass lead-free body, washerless, ceramic drip-free disc
valve cartridge, cast brass swing spout with vandal resistant 7.6 LPM (2.0 GPM) flow
aerator outlet, removable deck plate, if required, for two hole application, hose and
spray unit, single control metal lever handle, 3/8" (10mm) supply tubes. McGuire
#H170BV-LR Sink Supplies, C.P., polished, rigid horizontal integral copper sweat
tube nipples, 1/2" (12mm) I.D. x 5" (127mm) long, all brass 1/4 turn ball valves angle
stops with combination V.P. loose key and handles, escutcheons less flexible copper
risers. McGuire #8912C 'p' Trap, C.P. polished cast brass adjustable body, 1-1/2"
(38mm) with cleanout plug, seamless brass wall bend and escutcheon.

SK-2
SINGLE BOWL SINK - STAINLESS STEEL - BACK LEDGE
General Use
Franke 'WASHROOM SYSTEMS' ALBS6805-1-3 S.S. Sink, 3 hole, 8” (203mm)
(Creative Arts/Canteen) centres, 20-9/16" x 20-1/8" x 5" (522mm x 511mm x 127mm) deep, counter mounted,
back ledge, grade 18-8 type 302 stainless steel, single compartment, satin finished
rim and bowl, self rimming, with crumb cup strainer, sound deadening and mounting
kit. Chicago Faucets #1100-V-L9-XK Faucet, C.P. 8" (203mm) C.C., deck mounted,
solid cast brass lead-free body, 1/4 turn ceramic disc valve cartridges, swing spout
with vandal-resistant 7.6 LPM (2.0 GPM) flow aerator outlet and cast brass hooded
lever handles. Provide Sink Supplies with metal angle stops, adaptors, escutcheons
and flexible metal risers. Provide 'p' Trap, cast brass 1-1/2" (38mm) with cleanout,
union and escutcheon.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 5 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

SK-3
General Use
(Creative Arts)

DOUBLE BOWL SINK - STAINLESS STEEL - BACK LEDGE
Franke 'WASHROOM SYSTEMS' ALBD6405-1-3 Sink, 3 hole, 8” (203mm) centres,
20-1/2" x 31-1/4" x 5" (521mm x 794mm x 127mm) deep, counter mounted, back
ledge, grade 18-8 type 302 stainless steel, double compartment, satin finished rim
and bowl, with spillway, self rimming, with crumb cup strainers, sound deadening and
mounting kit.Chicago Faucets #786-V-GN8A-390-XK Faucet, C.P. 8" (203mm) C.C.,
below deck mounted, cast brass lead-free body, 1/4 turn ceramic disc valve
cartridges, with vandal-resistant swivel gooseneck spout with 8” (203mm) inlet to
outlet projection, 7.6 LPM (2.0 GPM) flow aerator outlet and 2-1/2" (64mm) cast
brass lever handles. Symmons #5-210-CK 'MAXLINE' Thermostatic Mixing Valve,
extruded brass body, brass and stainless steel control components, vandal-resistant
cap, with in-line strainers and checks. Mixer installed in H & CW supplies to provide
tempered water to hot side of faucet - as per local codes. Temperature range 85º F
(30º C) to 160º F (71º C). Set valve temperature at 120º F (49ºC). (Provide tee,
adaptors and flex. copper tubing to suit.)McGuire #H165N5-LR Sink Supplies, C.P.
Polished Brass Sink Supplies, rigid horizontal nipples 3/8" (10mm) x 5" (127mm)
long, I.P.S. heavy all brass angle stops with wheel handle stops and escutcheons,
less flexible copper risers. McGuire #8912C 'p' Trap, C.P. polished cast brass
adjustable body, 1-1/2" (38mm) with cleanout plug, seamless brass wall bend and
escutcheon.

SK-4
General Use
(Janitors Room)

JANITOR MOP SINK - PRECAST TERRAZZO FLOOR MOUNTED - CRESCENT
CORNER
Stern Williams #CRS 2200 Mop Sink, 28" x 28" x 12" (711mm x 711mm x 305mm)
deep, floor mounted, corner precast terrazzo with stainless steel cast integral cap on
front drop and Integral Drain with strainer.Chicago Faucets #305VB-R-XK-Hose
Faucet, C.P. 8" (203mm) C.C., wall mounted, solid cast brass lead-free body, 1/4
turn ceramic disc valve cartridges, cast brass lever handles, body mounted vacuum
breaker, integral stops, 36" (915mm) hose and hanger. Provide 'p' Trap, 3" (75mm).
Stern Williams #T-40 S.S. Mop Hanger, triple. Stern Williams #BP S.S. Back Splash
Panels, on two sides.

SK-5

SINGLE BOWL SINK - STAINLESS STEEL - BACK LEDGE
Franke 'WASHROOM SYSTEMS' #LBS6807-1-3 S.S. Sink, 3 hole, 8" (203mm)
centres, 20-1/2" x 20" x 7" (521mm x 508mm x 178mm) deep, counter mounted,
back ledge, grade 18-8 type 302 stainless steel, single compartment, satin finished
rim and bowl, self rimming, with crumb cup strainer, sound deadening and mounting
kit.Chicago Faucets #786-FC-XK Faucet, C.P. 8" (203mm) C.C., below deck
mounted, cast brass lead-free body, 1/4 turn ceramic disc valve cartridges,
gooseneck spout with integral 7.6 LPM (2.0 GPM) flow laminar (non aerating) outlet,
plain spout end and cast brass 4" (102mm) blade handles. Symmons #5-210-CK
'MAXLINE' Thermostatic Mixing Valve, extruded brass body, brass and stainless
steel control components, vandal-resistant cap, with in-line strainers and checks.
Mixer installed in H & CW supplies to provide tempered water to hot side of faucet as per local codes. Temperature range 85º F (30º C) to 160º F (71º C). Set valve
temperature at 120º F (49ºC). (Provide tee, adaptors and flex. copper tubing to
suit.)McGuire #H165N5-LR Sink Supplies, C.P. Polished Brass Sink Supplies, rigid
horizontal nipples 3/8" (10mm) x 5" (127mm) long, I.P.S. heavy all brass angle stops
with wheel handle stops and escutcheons, less flexible copper risers. McGuire
#8912C 'p' Trap, C.P. polished cast brass adjustable body, 1-1/2" (38mm) with
cleanout plug, seamless brass wall bend and escutcheon.

SK-6

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 6 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

SK-7
DF-1
HAWS COOLER

HI-LO DUAL DRINKING FOUNTAIN - STAINLESS STEEL WALL HUNG
Haws #1011HI-LO Fountains, wall mounted, stainless steel, 18 gauge (1.2mm) with
#4 satin finish, 14" dia. (356mm) receptors, lead free, 'Soft Touch Valve' control
bubblers, self-closing, automatic volume regulators, open grid strainers.Haws
#6700.4 Mounting Plate, 36" (914mm) x 12" (305mm) x 3/16" (5mm) steel mounting
plate that is predrilled and furnished with all thread studs, nuts and washers.McGuire
#HST11BV Fountain Supplies, C.P. polished brass straight 1/4 turn all brass ball
valve stops with loose key handles. McGuire #8872C-17T 'p' Trap, C.P., 17 gauge
(1.5mm), brass adjustable body, 1-1/4" (32mm) and escutcheon (Trap is concealed
in wall - provide access to meet local codes). Jay R. Smith #0823-2 Fountain Carrier,
with plate and block base feet support.
REMOTE WATER CHILLER
Haws #HCR8 Remote Chiller, to serve remote outlets as indicated, lead-free,
capacity of 8GPH (30L/h), compressor, with 0.5 gal. (2.25L) stainless steel reserve
storage tank, louvre air cooled with fan, hermetically sealed reciprocating type, 1/5
H.P. 120 V. single phase A.C. with insulated power cable and 3-prong moulded plug.
Provide receptacle with ground fault interrupter. Housed in a galvanized steel
cabinet.

DF-2
General Use

SEMI-RECESSED DRINKING FOUNTAIN - STAINLESS STEEL WALL HUNG
Filtrine #102-STVFountain, wall mounted, semi recessed, heavy duty, stainless steel,
16 gauge, (1.6mm) with #4 satin finish seamless rounded inside corner one piece
receptor, lead-free, 'Soft Touch Valve' cast brass control bubbler, self closing valve
and automatic volume regulator and vandal resistant open grid strainer, tailpiece.
Provide Fountain Supply, C.P. with metal straight stop. Provide 'p' Trap, cast brass 11/4" (32mm) with unions (Trap is concealed in wall - provide access to meet local
codes).

EW-1
(H/C)

EMERGENCY EYE / FACE WASH S.S. RECEPTOR WALL HUNG (BARRIER
FREE DESIGN) C/W MIXING VALVE
Haws #7360BTWC Emergency Eye/face wash, wall hung, stainless steel receptor,
dual aeration spray heads with flip-top dust covers, min. 11.4 LPM (3.0 GPM) flow,
in-line brass strainer, volume regulator, S.S. push handle operating ball valve with
S.S. trim, offset open grid strainer, all factory assembled, wall hanger and emergency
sign McGuire #8872C-17T 'p' Trap, C.P., 17 gauge (1.5mm), brass adjustable body,
1-1/4" (32mm) and escutcheon. If piping length to unit is more than 50'-0" (19.7m)
provide 3/4" (19mm) CW supply to unit, 1/2" (12.7mm) connection, escutcheon.
Provide adequate support in wall for eye wash mounting.
EMERGENCY EYE / FACE WASH TEMPERED WATER MIXER (SINGLE
STATION)
Haws #9201EW Supply Fixture, thermostatic temperature control valve, all brass and
stainless steel design, with liquid filled motor, check stops, safety shut-off should cold
water supply fail, hot water failure will allow cold water flow through both the fixed
and variable by-pass, outlet temperature gauge, 1/2” (12mm) supplies. Tempered
water factory set at 80 deg. F (26C) (Model #9201EW provides up to 7 GPM (120L)
at 30psi (246kPa) drop through valve.

Cleanout

CLEANOUTS - FLOOR CLEANOUT - HEAVY TRAFFIC FINISHED AREAS
Jay R. Smith Series 4100 'Twis-To-Floor' Floor Cleanout, duco coated cast iron body
and removable positive gasket seal closure plug and heavy duty 6" (150mm) with
extra heavy nickel bronze cover and frame, secured with stainless steel screws, C.O.
cast in cover. (For water-proofed areas provide 'FC' flange with flashing clamp).

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 7 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

FD-1
(Finished Floor)

FLOOR DRAINS - FINISHED AREAS
Jay R. Smith Series 2005AHD Floor Drain, all duco coated cast iron body, reversible
flashing clamp with seepage openings and adjustable 5" (127mm) diameter nickel
bronze 1/2" (12.5mm) thick strainer, secured with S.S. screws, 4" (100mm) throat on
strainer.

FD-2
(Mechanical Room)

FLOOR DRAINS WITH COMBINATION FUNNEL - MECHANICAL ROOMS
Jay R. Smith Series 2320-3591 Funnel Floor Drain, all duco coated cast iron body,
flashing clamp with seepage openings and adjustable 8 1/2" (216mm) diameter C.I.
grate with 4" x 9" (101.6mm x 228.6mm) oval funnel.

GT-1
(Kitchen)

INTERCEPTORS - GREASE INTERCEPTOR
Jay R. Smith Series 8450E Grease Interceptor, all duco coated inside & outside C.R.
steel enzyme type, removable baffles, gasketed cover with lock and lift ring, integral
flow control device, deep seal trap with cleanout and bottom debris trapping leg. Flow
rating of 75 GPM (285LPM) and grease capacity for 150 pounds (67.9KG). For flush
with floor installation provide extension 'E' as required to meet invert of pipe.

HB-1

HOSE BIBB - INTERIOR - WASHDOWN
Acorn Series 8121CP Hose Valve, C.P. heavy duty polished cast brass body with
integral cast flange, vandal-resistant lock shield bonnet with removable wheel handle,
3/4" (19mm) NPT female inlet and hose end vacuum breaker.

RD-1
General Use
(Control Flow)

ROOF DRAINS - FLOW CONTROL
Jay R. Smith Series 1083-CAN-ERCCID 'RAINTROL' Flow Control Roof Drain, all
duco coated 15-1/4" (387mm) diameter cast iron body, with under deck clamp, solid
extension and sump receiver, flashing clamp with seepage openings and, 11"
(280mm) diameter secured cast iron dome with 6" (150mm) high flow rate control
weir. (Solid extension height to suit roof construction).

Trap Primers

TRAP SEAL PRIMERS - MECHANICAL
SMS INC. Series PR-500 Automatic Trap Seal Primer Valve serving 1 to 4 drains,
cast brass body, serving individual or remote area drains (primer automatically
activated when there is a pressure drop in the system) with 1/2" (12.7mm) NPT
(MtoF) connections with strainer and integral back flow preventer & vacuum breaker.
(For 2, 3 or 4 drains provide primer unit with distribution unit assembly #DU-U)

Urinal Cleanouts

CLEANOUTS - URINAL CLEANOUT
Jay R. Smith Series SQ4-1819 Urinal Wall Access Cleanout, with S.S. bolt and wing
nut, complete with 4" (102mm) diameter polished S.S. access cover and secured
with V.P. screw.

Wall Cleanout

CLEANOUTS - LINE CLEANOUT
Jay R. Smith Series 4420 Line Cleanout, in cast iron ferrule with cast bronze tapered
thread plug, with full size pipe opening. Where cleanouts are concealed behind
finished walls access shall be made by Smith 4422 round stainless steel plate and
slotted flat head stainless steel screw.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 8 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:

FIXTURE/EQUIPMENT DESCRIPTION

Water Hammer

WATER HAMMER ARRESTORS
SMS INC. Series SC Series 'Water Hammer Arrestors' with brass piston in a type 'K'
copper casing size according to manufacturer's recommendations chart below to
eliminate water hammer and shock from piping system. Provide Water Hammer
Arrestors on hot and cold water supplies to all quick valves, solenoids, and plumbing
fixtures, and locate in an upright position between the last two fixtures on a line, or
horizontally at the end of line closest to supply source. On projects exceeding five
stories in height, provide water hammer arrestors on domestic water risers as follows.
Locate arrestors at the end of riser opposite supply source. Arrestor shall be two pipe
sizes larger than the riser is at the connection point, not exceeding the largest pipe
size diameter in the riser.

WH-1

NON FREEZE WALL HYDRANT - BOX - EXTERIOR
Jay R. Smith Series 5509QT Box Type Wall Hydrant, 1/4 turn non-drip, ceramic
cartridge, 3/4" (19mm) non freeze wall type with bronze face and stainless steel with
full 180 deg. cover opening box, adjustable wall-flange operating key and selfdraining integral vacuum breaker. Length to suit wall thickness.

DWH-1,2,3,4

DOMESTIC WATER HEATER
Domestic water heater shall be Bradford White model EF-100T-300E-3N(A) with a
rated storage capacity of not less than 379 liters (100 usgallons), a minimum gas
input of 300,000 BTU/hr (88 kw), a minimum recovery of 1,268 LPH (335 USGPH/) at
56°C (100°F) temperature rise, and a Thermal Efficiency Rating of 93%. It shall be
design certified by CSA International for 82°C (180°F) application, either with or
without a separate storage tank. The tank shall be lined with Vitraglas vitreous
enamel and shall have a bolted hand hole cleanout. The tank shall have four
extruded magnesium anode rods installed in separate head couplings. This water
heater shall be equipped with stainless steel cold water inlet and Hydrojet Sediment
Reduction System. The heater shall be insulated with Non-CFC foam to meet
ASHRAE 90.1b standard. This water heater shall be equipped with an electronic
ignition system, an ASME rated T&P relief valve and a premix closed combustion
system for direct venting using either 76mm (3") or 102mm (4") plastic vent pipe that
has been certified to ULC S636. The water heater shall be factory assembled and
tested. The water heater shall be approved for zero inch clearance to combustibles.
The control shall be an adjustable electronic thermostat to any temperature up to
82°C (180°F). A recycling Energy Cut Off (E.C.O.) shall shut off all gas in the event
of an overheat condition. Provide complete with Manitoba Department of Labour
approved concentric vent kit. The entire installation shall be made in compliance with
all local codes and the requirements of the Authorities Having Jurisdiction.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB

PLUMBING FIXTURE & EQUIPMENT
SCHEDULE

PAGE #: 9 OF 9
SCHEDULE I

PLUMBING FIXTURE & EQUIPMENT SCHEDULE
FIXTURE/EQUIPMENT
TAG:
ST-1

FIXTURE/EQUIPMENT DESCRIPTION
DOMESTIC HOT WATER STORAGE TANK
Domestic Hot Water Storage tank to be Bradford White Model No. NV310J-5A with a
storage capacity of 1,174 liters (310 usgallons) and overall dimensions of 2,185mm
(86") high x 1016mm (40") diameter. The tank shall be constructed to achieve hot
water delivery of 80% of tank capacity without a drop in outlet temperature utilizing
the HydroJet HC device. The tank shall have high density foam insulation, 50mm
(2") thick to meet ASHRAE 90.1b standard. The tank shall be built in accordance
with ASME construction and so labeled, with a working pressure of 861.6 kPa (125
PSIG). The tank lining shall be Vitraglas with a five year warranty against tank
failure. The tank shall have the following standard tapping sizes: 1) Hot Water
Supply 75mm (3") 2) Heater Loop 75mm (3") 3) Relief Valve Tapping 32mm (1-1/4")
4) Tank Thermostat 20mm (3/4")

END OF SCHEDULE I

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

BOILER SCHEDULE

PAGE #: 1 OF 2
SCHEDULE J

SPECIFICATIONS
.1

The boiler shall be design certified by CSA International and shall meet the requirements of ANSI
Z21.13 and CSA 4.9. The boiler shall bear the ASME "H" stamp and shall be national board
listed.

.2

COMBUSTION CHAMBER:
.1
The Stainless Steel combustion chamber shall be designed to drain condensation to the
bottom of the heat exchanger assembly. The combustion chamber shall be sealed and
completely enclosed, independent of the outer jacket assembly. A build-in trap shall allow
condensation to drain from the heat exchanger assembly.

.3

BURNER:
.1
The burner shall be a premix design and constructed of high temperature Stainless Steel
with knitted metal fiber outer covering to provide modulating firing rates. The burner shall
provide equal distribution of heat through the entire heat exchanger. A window view port
shall be provided for visual inspection of the boiler during firing.

.4

HEAT EXCHANGER:
.1
The heat exchanger shall be inspected and tested to A.S.M.E. Section IV requirements.
The A.S.M.E. Section IV seal of approval will not be provided as standard for jurisdictions
not requiring the A.S.M.E Section IV seal of approval. The heat exchanger shall be a twopass heat exchanger with maximum working pressure of 160 PSI (1100 kPa). The heat
exchanger shall be gasket-less. A suitable pressure relief shall be furnished with the
heater.

.5

CONTROLS:
.1
The control system shall have an electronic display for boiler set up, boiler status, and
boiler diagnostics. All components shall be accessible from the front of the jacket. The
boiler shall be equipped with; a temperature/pressure gauge; A flow switch shall be
provided loose.

.6

VENTING OPTIONS
.1
The boiler shall be vented as a Category IV condensing appliance using CPVC material
approved for use on condensing application under standard ULC S636 or equivalent. The
following venting options shall be utilized: 1. Horizontal & Vertical Outside Air. 2.
Through-Wall Venting. 3. Outdoor Venting. 4. Direct Venting.

.7

GAS TRAIN:
.1
The gas train shall consist of a gas valve with a pressure regulating electro-hydraulic
actuator to provide slow opening, fast closing, safety shutoff and air/gas ratio control.
Ignition Module: The ignition module shall employ a direct spark ignition with 3 tries for
ignition followed by lockout. Trial for ignition shall proceed with 15 seconds between
retrials.

.8

EXTERNAL JACKET AND FASTENERS:
.1
The external jacket shall be of stainless steel mirror finish panels and heavy gauge
painted steel assembled utilizing interference fit locks and minimal non-strip self tap
screws..

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 3

BOILER SCHEDULE

PAGE #: 2 OF 2
SCHEDULE J

SCHEDULE

BOILER SCHEDULE
TAG

MANUFACTURER
MODEL NO

B-1

CAMUS DYNAMAX
MODEL 0150

B-2

CAMUS DYNAMAX
MODEL 0150

MINIMUM
GAS INPUT
KW (MBH)
8.9 (30)

MAXIMUM
GAS INPUT
KW (MBH)
44 (150)

8.9 (30)

44 (150)

MAXIMUM REMARKS
OUTPUT
KW (MBH)
41 (140)
Natural gas fired boiler with modulating
control down to 20% of max. fire rate.
Provide complete with all trim and
appurtenances required by the local
authorities having jurisdiction.
41 (140)
Natural gas fired boiler with modulating
control down to 20% of max. fire rate.
Provide complete with all trim and
appurtenances required by the local
authorities having jurisdiction.

END OF SCHEDULE J

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

INFLOOR HEATING SYSTEM PUMP
SCHEDULE

PAGE #: 1 OF 1
SCHEDULE K

SPECIFICATIONS
.1

The following are general specifications. Refer to the Individual Pump Specifications in the
schedule for operating characteristics, specific requirements, and any deviations.
.1

Vertical In Line Centrifugal Pumps:
.1

Radially split casing

.2

Bronze fitted construction

.3

1200 kPa (175 psi) pressure rating

.4

Mechanical seal with flushing line

.5

Drip proof motor at 1800 rpm, unless noted otherwise

.6

Stainless steel shaft

.7

All Pump Motors shall be 208 V / 3 phase, unless noted otherwise

.8

All Duplex Pumps run concurrently, unless noted otherwise.

.9

Duplex Pumps running concurrently (Both pumps operating at the same time) are
sized at 50% capacity each when both pumps are running.

.10
PART 2

.1

Pumps shall be selected so that the motors are non-overloading when
only one pump is operating.

.2

Pumps shall be selected so that they are running on a usable point of
their pump curve when only one pump is operating.

Duplex Pumps running individually (one pump running, the other 100% standby)
are sized for 100% individual capacity

STANDARD OF ACCEPTANCE
.1

All selections are based on Armstrong

INFLOOR HEATING SYSTEM PUMP SCHEDULE
TAG

LOCATION &
SERVICE

IFP-1A

Infloor Heating
Duplex Pump
50% Standby
Infloor Heating
Duplex Pump
50% Standby

IFP-1B

MFG. &
MODEL &
SIZE
Armstrong
4380
1.5x1.5x8
Armstrong
4380
1.5x1.5x8

FLUID

Water
Water

FLOW
L/S
(USGPM)
1.14
(18)

HEAD
kPa
(feet)
167.2
(56)

MOTOR
KW/V/Ф
(HP/V/Ф)
1.2/208/3
(1.5/208/3)

1.14
(18)

167.2
(56)

1.2/208/3
(1.5/208/3)

END OF SCHEDULE N

NOTES

Bronze Fitted
Construction, 1800
rpm, Op Temp = 120ºF
Bronze Fitted
Construction, 1800
rpm, Op Temp = 120ºF

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

ELECTRIC HEATING COIL
SCHEDULE

PAGE #: 1 OF 2
SCHEDULE L

SPECIFICATIONS
.1

The following are general specifications. Refer to the Individual Electric Coil Specifications in the
schedule for operating characteristics, specific requirements, and any deviations.

.2

Frame shall be galvanized steel with either flanged duct connections or suitable for insertion into
the side or bottom of a duct, as scheduled. Mounting flanges shall be independent of the terminal
box so as to allow installation without opening the box or drilling into it.

.3

Resistance heating elements shall be of high grade nickel-chrome alloy and shall be insulated by
floating ceramic bushings from the galvanized steel frame. Coil terminal pins shall be stainless
steel insulated by means of non-rotating ceramic bushings.

.4

Duct heaters shall be non-sensitive to air flow direction and interchangeable for horizontal or
vertical ducts. Heater shall be CSA approved for zero clearance in horizontal ducts.

.5

Refer to the Individual Electric Coil Specifications in the schedule for heating outputs and staging.
In general, heating and reheat coils up to 5 kw shall be single stage on/off, heating and reheat
coils 5 kw and over shall be two stage on/off, and pre-heat coils shall be single stage with SCR
control.

.6

Physical size shall conform to the duct size, but shall not result in air velocity less than 140 m/min
(450 fpm) nor a watt density higher than 4.5 watts/cm² (30 watts/in²).

.7

Heater shall be c/w an integral control cabinet with a hinged door, to enclose the required
terminal strips, lugs, and control components. All controls shall be pre-wired.

.8

Standard power and control components shall include:
.1
Single point power supply
.2
Control transformer as required, c/w individual fuse or breaker
.3
Power and control terminals
.4
Magnetic contactors
.5
Automatic reset over heat protection
.6
Manual reset over heat protection
.7
Air pressure differential switch for auto-shut-off on low air flow

.9

Optional power and control components to be included, shall include:
.1
Disconnect switch
.2
SCR (modulating) controller
.3
Integral discharge temperature sensor/controller

.10

Maximum Air Pressure Drop: 56 kPa (0.25” H2O)

PART 2

STANDARD OF ACCEPTANCE
.1

Products as manufactured by Caloritec, Thermolec and Chromalox are acceptable.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 3

ELECTRIC HEATING COIL
SCHEDULE

PAGE #: 2 OF 2
SCHEDULE L

SCHEDULE

ELECTRIC HEATING COIL SCHEDULE: (BASED ON THERMOLEC)
TAG

LOCATION

SERVING

EHCHRV--1

MECH. MEZZ.
RM 203

HRV-1

TYPE

OPEN
COIL

DUCT SIZE POWER
mm
KW
(V/PH)
(INCHES)

AIR
FLOW
L/S
(CFM)

TEMP
RISE
(F)

800x400
(32"x16")

1415
(3000)

105

100

575/3

OPTIONS

1-2-3

NOTES:

STANDARD BUILT-IN CONTROLS: ALL DUCT HEATERS SHALL BE COMPLETE WITH THE
FOLLOWING BUILT-IN CONTROLS: HIGH LIMIT CUT-OUTS, MAGNETIC CONTACTORS AS
REQUIRED, CONTROL TRANSFORMER, AND AIR FLOW SENSOR. ALL HEATER
CONTROL PANELS SHALL BE CAPABLE OF BEING INSTALLED IN A HORIZONTAL PLAIN.
REFER TO ELECTRICAL DRAWING FOR VOLTAGE AND PHASE INFORMATION.

OPTIONS:

1) BUILT-IN DISCONNECT SWITCH.
2) SCR PROPORTIONAL CONTROLLER
3) SCREENS BOTH SIDES

END OF SCHEDULE L

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

GAS FIRED UNIT HEATER
SCHEDULE

PAGE #: 1 OF 2
SCHEDULE M

SPECIFICATIONS
.1

GAS-FIRED, SEPARATED COMBUSTION UNIT HEATERS
.1
Provide CSA certified 82%-83% high-efficiency, separated-combustion, power vented,
gas-fired unit heaters. The unit shall be designed for use in a building with negative
pressures up to 0.15" W.C.

.2

FUEL
.1

Unit heater shall be equipped for use with natural gas. Gas connection shall be external
to the cabinet.

.3

HEAT EXCHANGER
.1
The heater shall be equipped with a multi-cell, 4 pass serpentine style steel heat
exchanger. Heat exchanger tubes shall be press fabricated of titanium stabilized,
corrosion resistant aluminized steel. All heat exchangers shall be fabricated with no
welding or brazing, only tool pressed mechanical joints. All heat exchanger cells shall be
designed with an aerodynamic cross section to provide maximum airflow.

.4

BURNER
.1
The units shall incorporate a single, one piece burner assembly with a single orifice. The
burner shall have a continuous wound close pressed stainless steel ribbon separating the
flame from the burner interior. All units shall have a single venturi tube and orifice
supplying fuel to a one-piece burner housing. Each heat exchanger cell shall use
balanced draft induction to maintain optimum flame control.

.5

CONTROLS
.1
Controls shall include a two-stage gas valve; direct spark multi-try ignition with electronic
flame supervision with 100% lockout integrally controlled via a printed circuit control
board. The control board shall also incorporate diagnostic lights, DIP switches for fan
overrun settings, and a relay for fan only operation. All units shall be equipped with a
safety limit switch.
.2

.6

.7

All controls shall be enclosed in the sealed control compartment to protect them from
accidental damage, dust, and atmospheric corrosion.

COMBUSTION AIR AND VENTING
.1
The unit shall have a factory-installed power venter device to draw combustion air from
outside of the building. The outside air shall enter the unit through a factory-installed
round inlet air terminal on the rear of the heater. The control compartment shall be sealed
and the access door shall be gasketed to prevent dirt, lint, dust, or other contaminants
present in the heated space from entering the unit. The control compartment door shall
be equipped with a safety interlock switch to prevent operation when the door is open.
.2

The combustion air supply pipe and flue exhaust pipe shall be run in parallel from the
heater to a factory supplied concentric adapter assembly, which allows for a single wall or
roof penetration, to the vertical air inlet and vent terminal.

.3

The combustion air/venting system shall include a vibration isolated power venter motor
and wheel assembly and a combustion air pressure switch and a flame rollout switch.

ELECTRICAL
.1
Operation shall be controlled by an integrated circuit board that includes LED diagnostic
indicator lights. Supply voltage connections shall be made in a sealed junction box. 24volt control connections shall be made on an externally mounted terminal strip with
connections (W1, W2, R, and G). All internal wiring, both line and control voltages, shall
be terminated by insulated terminal connectors to minimize shock hazard during service.

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
.8

PART 3

GAS FIRED UNIT HEATER
SCHEDULE

PAGE #: 2 OF 2
SCHEDULE M

CABINET
.1
Each unit shall be equipped for use with 115/1 volt power supply.
.2

All units will be equipped with a built-in disconnect switch.

.3

The cabinet shall be low profile with a pre-coat or powdercoat RAL 1001 white paint
finish. Finish shall be a minimum 80 gloss on G30 galvanized steel.

.4

The unit shall be designed for ceiling suspension.

.5

The cabinet shall be equipped with RAL 3005 burgundy painted, roll-formed horizontal
louvers with Downturn nozzle.

.6

The cabinet shall be equipped with a full safety fan guard. The enclosed motor and fan
assembly shall be resiliently mounted to the cabinet to reduce vibration and noise.

.7

The unit shall be designed with a full opening service access panel complete with screw
closure attachment and lifting handle for removal. Service panel shall be fully gasketed
and equipped with a safety interlock switch. All components in the gas train, all standard
electrical controls, and the power venter shall be within the sealed service compartment.

SCHEDULE

GAS FIRED UNIT HEATER SCHEDULE
TAG

MAKE MODEL

AIR
CFM
(l/s)

GUH-1 Reznor UDAS 100 1345
(635)

INPUT OUTPUT MOTOR REMARKS
MBH MBH
HP
(kw)
(kw)
(kw)
105.0 87.2
(30.8) (25.5)

0.25
(0.2)

Two stage separated combustion air unit
heater with vertical concentric combustion
air/vent roof termination kit, TEFC motor, two
stage thermostat, thermostat guard, and
adjustable downturn nozzle

END OF SCHEDULE M

Bid Opportunity No. 832-2007
Bronx Park Community Centre
Good Neighbours Senior Centre
Winnipeg, MB
PART 1

COOLING COIL SCHEDULE

PAGE #: 1 OF 1
SCHEDULE N

SPECIFICATIONS
.1
.2
.3

.4

.5

.6

.7

.8
.9

PART 2

GENERAL
.1
Contractor shall furnish and install Direct Expansion coils, manufactured by York to meet
the peformance requirments set forth in the schedule. Coils shall be available for R-22.
CERTIFICATION
.1
All coils shall have performance certified in accordance with ARI Standard 410.
TUBES
.1
All coils shall have 5/8” OD seamless copper tube arranged in a staggered pattern
perpendicular to the air flow. The copper tubes shall be firmly bonded to the fins by
mechanical expansion.
HEADER AND DISTRIBUTORS
.1
All headers shall be of heavy seamless copper tubing or brass, as dictated by the
schedule, and shall be silver brazed to the tubes. The refrigerant distributor shall be of
the venturi type for even distribution of refrigerant and low-pressure drop, sized for the
required duty and silver brazed to the distributor tubes. All piping connections shall be of
¼” or 5/16” round seamless copper sized for the required duty and of equal length for
maximum distributor efficiency.
FINS
.1
Aluminum fins shall be available in either 0.010” thickness and copper fins shall be
available in 0.006” thickness. All shall have a die-formed corrugation with guide channels
to create a turbulent wiping action behind the tubes and minimize moisture carry-over.
Fins shall have fully drawn collars for accurate spacing and to maximize fin tube contact.
Fins shall be firmly bonded by mechanical expansion to increase heat transfer and
ensure reliable. Fins shall be continuous across entire width of the coil up to 48-1/4”.
CASING
.1
The casing shall be a full channel, die formed, mill galvanized steel and provide ample
shipping and stacking support for the fin bundle. Tube sheets shall have extruded collars
for tube support and to prevent damage due to expansion and contraction of the fin
bundle. Intermediate coil casing channel supports shall be provided on coils with a fin
length greater than 62”; two supports above 100”. Casing channels shall be free
draining, without depressions to prevent moisture and contaminants collection.
FACE SPLITS
.1
Face splits shall be available when single coil total MBH excceds 500 MBH or for multiple
compressors appications. The minimum split section shall never be less than 6 tubes
high. Coil face splits should be of equal number of tubes to provide equal refrigerant load
splits.
ROW CONTROL
.1
Row control shall be available by selecting two or more coils positioned in series.
TESTING AND WORKING PRESSURE
.1
All coils, including headers, return bends, and distributors, shall be designed to conform
to the ANSI B9.1 (Saftey Code for Mechanical Refrigeration) when operating with a
refrigerant pressure not exceeding 325 PSIG and shall be tested with 325 PSIG
compressed air under water.
STANDARD OF ACCEPTANCE

.1

Base Bid: All selections are based on York Cooling Coils.

CONDENSING UNIT SCHEDULE
NO.

SERVICE

MAKE

MODEL

EAT (F)
DB/WB

TOTAL CAP
(MBH)
TOTAL/SENS

DX-HRV-1
HRV
York
DX Coil
90 / 73
130 / 83
Table Notes:
1. Stainless steel drain pan supplied and installed by contractor.
END OF SCHEDULE N

COIL
SIZE
(IN)
HXW
32 X 34

AIR
FLOW
(CFM)

REF.

REMARKS

3,770

R-22

1



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V2.3 (128-bit)
User Access                     : Print, Copy, Extract, Print high-res
XMP Toolkit                     : 3.1-702
Creation Date--Text             : 17/1/2008 16:29:1
Keywords                        : CONSTRUCTION OF BRONX PARK COMMUNITY CENTRE – HOME OF GOOD NEIGHBOURS SENIOR CENTRE – 131 CHELSEA PLACE, WINNIPEG MANITOBA
Producer                        : Amyuni Document Converter
Format                          : application/pdf
Creator                         : .
Title                           : 832-2007 Bid Opportunity
Description                     : 
Subject                         : CONSTRUCTION OF BRONX PARK COMMUNITY CENTRE – HOME OF GOOD NEIGHBOURS SENIOR CENTRE – 131 CHELSEA PLACE, WINNIPEG MANITOBA
Version                         : Version 2.10h - Licensed to Marcel Neron
Creator Tool                    : 
Modify Date                     : 2008:02:01 11:29:46-06:00
Metadata Date                   : 2008:02:01 11:29:46-06:00
Create Date                     : 2008:02:01 11:29:46-06:00
Document ID                     : uuid:451998c7-a6b3-485f-afaf-0e43940a2862
Instance ID                     : uuid:9b8e27f8-9a80-4677-9d5e-df313618c29c
Has XFA                         : No
Page Count                      : 40
EXIF Metadata provided by EXIF.tools

Navigation menu