The CI-SITE/MC-0 Site Monitor and Controller is a low current, high reliability site monitor capable of
operating at extreme temperatures in remote locations. The Site Monitor and Controller has eight analog
inputs for monitoring various voltage levels, eight digital inputs for monitoring logic levels, and eight
“open drain” outputs for activating relays or alarms. The Site Monitor and Controller can be set up in a
limited configuration as a stand-alone unit at a repeater site and can be used to send alarms tones over
the air. The Site Monitor and Controller can also be configured as a Gateway-Slave configuration where
the Gateway is located at a base station and is connected to a computer running the Site VIEW application software (CI-SITE/MC-9). The Gateway communicates with the Slave units located at the remote
repeater sites using FFSK format over the RF links (the Site Monitor and Controller has an FFSK modem
built in). This also allows the Slave units to be remotely reprogrammed, controlled, and monitored from
the Gateway location.
The Site Monitor and Controller can also be used in a Hot / Cold Standby System. The Site Monitor and
Controller can monitor alarm and voltage inputs on the Primary system and switch over radio communications to the Secondary system automatically on any alarm or low voltage condition.
The Site Monitor and Controller provides the following features:
19” rack mountable chasis
- chasis is capable of holding two Site Monitor and Controllers in 1 RU
Built-in FFSK Modem
- capable of 1200/2400 baud over a Daniels radio link with pre/de-emphasis or flat audio
Low current consumption
- average current draw of 65 mA when active,
- average current draw of 15 mA when in standby
Eight analog inputs
- individual analog inputs can be configured as contact closures, switches, open collector or
variable voltage inputs
- individual channel hold timers
Eight digital inputs
- individual digital inputs can be configured with 0 - 2.56 V, 0 - 5.0 V, 0 - 25 V and 4 - 20 mA
user defined ranges up to 100 V.
- individual channel low and channel high set point triggers with individual hold timers
- 10 bit A/D
Eight outputs
- “open drain” FET outputs, voltage switching up to 50 Vdc @ 150 mA current sink
- programmable pulse or latching outputs
Optional temperature sensors
- span of -55 °C to +125 °C (-67 °F to +257 °F)

43 Erie Street
Victoria, B.C.
Canada V8V 1P8

TN860 Rev 3-0-0 Jan 07

Toll Free
Phone:
Fax:

Canada & U.S.A.
1-800-664-4066
1-877-750-0004

International
Phone: 250-382-8268
Fax: 250-382-6139

© Copyright 2007 Daniels Electronics Ltd. All rights reserved.

e-mail:
web:

Internet
sales@danelec.com
www.danelec.com

Page 1 of 2

T h i s p r o d u c t h a s b e e n d i s c o n t i n u e d a n d i s n o l o n g e r m a n u f a c t u r e d b y D a n i e l s E l e c t r o n i c s L td .

TN860 CI-SITE/MC-0 Site Monitor and Controller

DANIELS

TECHNICAL NOTES

TM

MT-3 Radio Systems

ELECTRONICS LTD.

Examples of Site Monitor and Controller Capabilities:
Input Monitoring
Outside and Inside Temperatures
High VSWR Alarms
AC Power Fail Alarms

Transmitter Forward and Reverse Power
Solar Panel, Battery and Regulated Voltages
Door Alarms

Output Control
Redundant System Enable
Light Activation

Generator Start
Directional Antenna Control

Installation:
Connect the Daniels Electronics subrack with A-PNL-AUX96-3 auxiliary connector to the Site Monitor
and Controller as shown in the diagram below. The diagram below shows a Site Monitor and Controller
connected to a Daniels Repeater with an AC-3E audio control card.
CI-SITE/MC-0
SITE MONITOR
AND CONTROLLER

P1 (A-PNL-AUX96-3 CONTROL CONNECTOR)
DANIELS RADIO EQUIPMENT

(SPARE 5)AUX_1_AUDIO O/P1
(SPARE 6)AUX_1_AUDIO 0/P2
(SPARE 1) AUX_1_AUDIO I/P1
(SPARE 2) AUX_1_AUDIO I/P2
(ALARM 6) AUX PTTA I/P
GROUND
(ALARM 2) COR A
GROUND

13.8V
9.5V
RXA SIG STRENGTH
REVERSE ALARM OUTPUT
FORWARD ALARM OUTPUT

13.8V
GROUND

J3-5

RX+

J3-6

RX-

J3-1

TX+

J3-2

TX-

J3-14

PTT OUTPUT

J4-2

GROUND

J3-10

COR INPUT A

J4-3

COR INPUT B

J4-6

ANALOG INPUT 1

J4-7

ANALOG INPUT 2

J5-7

ANALOG INPUT 3

J5-3

DIGITAL INPUT 1

J5-2

DIGITAL INPUT 2

J4-5

+13.8V INPUT

J4-1

GROUND
Jumpers Required:
AC-3E: JU48A, Remove JU51

43 Erie Street
Victoria, B.C.
Canada V8V 1P8

Page 2 of 2

Toll Free
Phone:
Fax:

Canada & U.S.A.
1-800-664-4066
1-877-750-0004

International
Phone: 250-382-8268
Fax: 250-382-6139

© Copyright 2007 Daniels Electronics Ltd. All rights reserved.

e-mail:
web:

Internet
sales@danelec.com
www.danelec.com

TN860 Rev 3-0-0 Jan 07

T h i s p r o d u c t h a s b e e n d i s c o n t i n u e d a n d i s n o l o n g e r m a n u f a c t u r e d b y D a n i e l s E l e c t r o n i c s L td .

TN860 CI-SITE/MC-0 Site Monitor and Controller



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2006:12:27 15:21:47-08:00
Modify Date                     : 2006:12:27 15:21:47-08:00
Page Count                      : 2
Creation Date                   : 2006:12:27 23:21:47Z
Mod Date                        : 2006:12:27 23:21:47Z
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Author                          : plunness
Metadata Date                   : 2006:12:27 23:21:47Z
Creator                         : plunness
Title                           : Disc TN860-3 Site Monitor.qxd
EXIF Metadata provided by EXIF.tools

Navigation menu