Chapter 1 Fundamental And Basic Concept DDC Wiring

User Manual: DDC

Open the PDF directly: View PDF PDF.
Page Count: 36

 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-1
Chapter-7 Direct Digital Controllers (DDC) Wiring
Direct Digital Controller (DDC)  input  output terminal   wing 
 
. Fan Coil Unit  control   DDC Controller (Model: UFC0882L)
 - FCU Control(with valve)
.. Description
DDC Controller(Model: UFC0882L)   Fan Coil Unit(FCU) control 
LONMARK® Functional Object type 8020  
 controller  Cooling Only Application  configure 
FCU capacity  control 
HVAC Control and Building Automation Systems 
7-2
On/Off type actuator   valve  (open)  FCU
capacity  control 
 -() Valve Open Control
 -() Valve Close Control
.. DDC Terminal Block Assignment UFC0882L
Terminal Block () TB1  TB6   TB8 terminals  TB3  TB
8  
Terminal
Block No
Label
Description
TB1
AC24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB2
TO4
On/Off Valve control(DO)
TO6
FCU Start/Stop control(DO)
TB4
UI1
FCU On/Off status(DI)
COM
Com for UI1 & UI2
UI2
FCU Mode status(DI)
UI3
FCU Trip status(DI)
COM
Com for UI3 & UI4
UI4
FCU Water leakage status(DI)
TB5
UI5
FCU Valve status(DI)
COM
Com for UI5 & UI6
UI6
Return Air Temperature(AI)
TB6
N+
Network wire from previous DDC
N-
Network wire from previous DDC
N+
Network wire to next DDC
N-
Network wire to next DDC
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-3
.. DDC Layout & Wiring Diagram
NOTE:
1) # RETURN AIR SENSOR(AI) & VALVE CONTROL(DO) ONLY APPLICABLE FOR TYPE 1 FCU
2) EACH COM TERMINAL TO BE SHARED BY 2 UI TERMINALS
3) ALL DIGITAL OUTPUTS ARE 24 Vac TRIAC OUTPUTS
 -
. Fan Controller DDC(Model U6F2484L)
DX/FCU Control
S/S = Start/Stop control
ST = On/Off status
TA = Trip Alarm  -
A/M= Auto/Manual status
HVAC Control and Building Automation Systems 
7-4
.. Description
DDC  fan ()  control     Fan
 control  LONMARK® 
 controller  DX unit  FCU  control   monitor  configure
 Fan Controller  DX unit  FCU  control 
.. DDC Terminal Block Assignment(UGM2484L)
Terminal
Block No
Label
Description
Remark
TB0
+24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB1
AO1
Analog Output 1
AO channels to be
commanded via binding
COM
Com terminal for AO1 & AO2
AO2
Analog Output 2
AO3
Analog Output 3
COM
Com terminal for AO3 & AO4
AO4
Analog Output 4
TB2
UI1 UI4
Universal Inputs 1-4
COM
2 COM Terminals for UI 1-4
Each com shared by 2 UI
TB3
UI5 UI8
Universal Inputs 5-8
COM
2 COM Terminals for UI 5-8
Each com shared by 2 UI
TB4
UI9 UI12
Universal Inputs 9-12
COM
2 COM Terminals for UI 9-12
Each com shared by 2 UI
TB5
UI13 UI16
Universal Inputs 13-16
COM
2 COM Terminals for UI 13-16
Each com shared by 2 UI
TB6
UI17 UI20
Universal Inputs 17-20
COM
2 COM Terminals for UI 17-20
Each com shared by 2 UI
TB7
UI21 UI24
Universal Inputs 21-24
COM
2 COM Terminals for UI 21-24
Each com shared by 2 UI
TB8
P3
High/Low frequency Pulse Input 1
COM
Com terminal for P3 & P4
P4
High/Low frequency Pulse Input 2
TB9
TO1-TO8
Digital Output 1 - 8
DO channels to be
commanded via binding
TB10
N+
Network wire from previous DDC
N-
Network wire from previous DDC
N+
Network wire to next DDC
N-
Network wire to next DDC
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-5
.. DDC Layout & Wiring Diagram
 -
. FAN CONTROL DDC U8F2484L
 - Type 1. M/V Fan Control
HVAC Control and Building Automation Systems 
7-6
.. Description
DDC  fan  control  LONMARK® 
  Mechanical Ventilation Fan  control   configure

 - M/V Fan Control & General Digital Input monitoring
.. DDC Terminal Block Assignment(U8F2484L)
Terminal
Block No
Label
Description
Remark
TB0
+24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB2
UI1 UI4
Digital Inputs 1-4(DI)
COM
2 COM Terminals for DI 1-4
Each com shared by 2 DI
TB3
UI5 UI8
Digital Inputs 5-8(DI)
COM
2 COM Terminals for DI 5-8
Each com shared by 2 DI
TB4
UI9 UI12
Digital Inputs 9-12(DI)
COM
2 COM Terminals for DI 9-12
Each com shared by 2 DI
TB5
UI13 UI16
Digital Inputs 13-16(DI)
COM
2 COM Terminals for DI 13-16
Each com shared by 2 DI
TB6
UI17 UI20
Digital Inputs 17-20(DI)
COM
2 COM Terminals for DI 17-20
Each com shared by 2 DI
TB7
UI21 UI24
Digital Inputs 21-24(DI)
COM
2 COM Terminals for DI 21-24
Each com shared by 2 DI
TB9
TO1
Digital Output 1(Fan 1)
TO2
Digital Output 2(Fan 2)
TO3
Digital Output 3(Fan 3)
TO4
Digital Output 4(Fan 4)
TO5
Digital Output 5(Fan 5)
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-7
TO6
Digital Output 6(Fan 6)
TO7
Digital Output 7(Fan 7)
TO8
Digital Output 8(Fan 8)
TB10
N+
Network wire from previous DDC
N-
Network wire from previous DDC
N+
Network wire to next DDC
N-
Network wire to next DDC
.. DDC Layout & Wiring Diagram
NOTE: ALL DIGITAL OUTPUTS ARE 24 Vac TRIAC OUTPUTS
 -
HVAC Control and Building Automation Systems 
7-8
. Constant Air Volume(CAV) AHU Controller(UAH1464L)
 -
.. Description
Constant Air Volume(CAV) AHU  DDC controller( control 
Inputs
UAH1464L model controller  Universal input ()  a Digital inputs ()  
(connect) 
UAH1464L   sensor 
() Digital Inputs(Dry contacts)
Selector mode status
Smoke detector status
On/Off status
General dry contacts
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-9
Trip status
() Universal Inputs (0-5 Vdc/4-20mA/ NTC 10K temperature/Dry contacts)
Temperature sensors
Chilled water flow rate
Valve position
Universal inputs
Analog Input monitoring  abnormal sensor reading   First order Low Pass
Filter method  
    
Where, Vnew = New reading to be updated in DDC
Vold = Old reading updated in DDC
Vin = Sensor reading,
C = constant (0.0~ 1.0)
 - AHU CONTROLLER DDC UAH1464L
Outputs
UAH1464L controller  Digital Outputs(24 Vac Triac)  Analog Outputs(0-10 Vdc or 4-
20mA)   output signal 
(1) Digital Output
Digital output channels () channel  1 DO control  2 DO control 
configure 
AHU Start/Stop (Individual schedule or manual control)
DO 1 Start/Stop(Individual schedule manual control)
DO 2 Start/Stop(Individual schedule manual control)
HVAC Control and Building Automation Systems 
7-10
Fresh air damper Open/Close control/Floating control
Re-heater On/Off control
(2) Analog Output
2 nos. of Analog output channels, these are
AHU Variable Speed drive control
AHU Chilled water valve control (cooling )
AHU Heated water valve control (heating )
.. DDC Terminal Block Assignment(UAH1464L)
Terminal Blocks   TB1  TB6  TB8 terminals 
Terminal
Block No
Label
Description
Remark
TB8
+24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB3
TO1-TO6
Digital Output 1 - 6
Only TO1 is used.
TB4
AO1
Analog Output 1
Only AO2 is used.
COM
Com terminal for AO1 & AO2
AO2
Analog Output 2
AO3
Analog Output 3
COM
Com terminal for AO3 & AO4
AO4
Analog Output 4
TB1
N+
Network wire from previous DDC
N-
Network wire from previous DDC
N+
Network wire to next DDC
N-
Network wire to next DDC
TB6
UI1
Universal Input 1
COM
COM Terminal for UI 1-2
UI2
Universal Input 2
UI3
Universal Input 3
COM
COM Terminal for UI 3-4
UI4
Universal Input 4
UI5
Universal Input 5
COM
COM Terminal for UI 5-6
UI6
Universal Input 6
UI7
Universal Input 7
COM
COM Terminal for UI 7-8
UI8
Universal Input 8
TB5
UI9
Universal Input 9
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-11
COM
COM Terminal for UI 9-10
UI10
Universal Input 10
UI11
Universal Input 11
COM
COM Terminal for UI 11
TB2
DI1
Digital Input 1
COM
Com terminal for DI 1& DI 2
DI2
Digital Input 2
DI3
Digital Input 3
COM
Com terminal for DI 3
.. DDC Layout & Wiring Diagram CAV AHU
 -
HVAC Control and Building Automation Systems 
7-12
Valve Interlock with AHU status
 -
.. CAV AHU Typical Sensor Termination
TYPICAL SENSOR TERMINATION
 -
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-13
. VAV AHU  Controller  Control Logic
 - Building Automation System(BAS)  AHU graphic 
Building Automation System   AHU graphic   
 AHU  Direct Digital Controller(DDC) Control logic  
  Building Automation System 

 - () Air Handling Unit  field device  Input  Output 
HVAC Control and Building Automation Systems 
7-14
Legend
ST: On/Off status
TA: trip alarm
A/M: Auto/Manual mode
SD: Smoke detector
DPS: Differential pressure
switch
WLD: Water leakage Detector
T: Temperature
SP: Static pressure
RH: Relative Humidity
WFR: water flow rate
KWH: kilo-watt hour
S/S: Start/Stop control
VSD: variable speed drive
M: motorised actuator
O/C: Open/Close control
 - Air Handling Unit  field device  Input  Output  Legend
.. Description of DDC Inputs and Outputs
Variable Air Volume (VAV) AHU control application   Direct
Digital Controller (DDC)  model UAH2484L 
Direct Digital Controller (DDC) Input 
Direct Digital Controller(DDC) UAH24842L   Input  
(1) Digital Input(Dry contacts)
Direct Digital Controller(DDC) UAH24842L  Digital Input () (connect)

- VAV AHU  controller  Input  Output 
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-15
VAV AHU  controller  control logic 
Digital Input 
Selector mode status
On/Off status
Trip status
Smoke detector status(maximum 4 nos.) 
General dry contacts(maximum 8 nos.) 
(2) Analog Input(0-5 Vdc/4-20mA/ NTC 10K temperature)
Direct Digital Controller(DDC)UAH24842L  Analog Input () (connect)
Analog Input 
Temperature sensors(maximum 4 nos.)
Static Pressure
Chilled water flow rate
CO2 
Universal Input(maximum 5 nos.) 
Analog Input monitoring  (abnormal) sensor reading 
  
      
Where,
Vnew = New reading to be updated in DDC
Vold = Old reading updated in DDC
Vin = Sensor reading,
C = constant(0.0~ 1.0)
(3) Pulse Input
Direct Digital Controller(DDC) UAH24842L  pulse Input () (connect)
 pulse width    Accumulated counter 
(value) 0  1,999,999,999 (display)
Output 
Direct Digital Controller (DDC) UAH24842L  Digital Output(24 Vac Triac) & Analog
Output(0-10 Vdc or 4- 20mA) 
Variable Air Volume (VAV) AHU DDC Layout  Wiring Diagram
HVAC Control and Building Automation Systems 
7-16
 - Variable Air Volume (VAV) AHU DDC Layout  Wiring Diagram
(4) Digital Output
Direct Digital Controller(DDC)UAH24842L  Digital output channel ()
 Channel  Digital Output control ()  configure 
AHU /
AHU Start/Stop(Individual schedule or manual control)
/
Fan 1 Start/Stop(Individual schedule manual control)(used as By pass damper control )
/
Fan 2 Start/Stop(Individual schedule manual control)
Return air damper /
Return air damper Open/Close control(interlock with AHU operation)
Exhaust air damper /
Exhaust air damper Open/Close control(interlock with AHU operation)
Variable Air Volume (VAV) AHU Typical Sensor Termination
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-17
 - Variable Air Volume(VAV)AHU Typical Sensor Termination
(5) Analog Output
Direct Digital Controller(DDC) UAH24842L  Analog output channel  
AHU Variable Speed Drive(VSD) control 
AHU chilled water valve control 
.. DDC Terminal Block Assignment (UAH2484L)
Terminal Block ()  TB1  TB6  TB8 terminal 
Terminal
Block No
Label
Description
Remark
TB0
+24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB1
AO1
Analog Output 1
COM
Com terminal for AO1 & AO2
AO2
Analog Output 2
TB2
UI1 UI4
Universal Input 1-4
HVAC Control and Building Automation Systems 
7-18
COM
2 COM Terminals for UI 1-4
Each com shared by 2 UI
TB3
UI5 UI8
Universal Input 5-8
COM
2 COM Terminals for UI 5-8
Each com shared by 2 UI
TB4
UI9 UI12
Universal Input 9-12
COM
2 COM Terminals for UI 9-12
Each com shared by 2 UI
TB5
UI13 UI16
Universal Input 13-16
COM
2 COM Terminals for UI 13-16
Each com shared by 2 UI
TB6
UI17 UI20
Universal Input 17-20
COM
2 COM Terminals for UI 17-20
Each com shared by 2 UI
TB7
UI21 UI24
Universal Input 21-24
COM
2 COM Terminals for UI 21-24
Each com shared by 2 UI
TB8
P3
Pulse Input
Only P3 is used.
COM
Com terminal for P3 & P4
P4
Pulse Input
TB9
TO1-TO8
Digital Output 1 - 8
Only TO1,3,5,6 are used.
TO3 not used for Tower 1
TB10
N+
Network wire from previous DDC
N-
Network wire from previous DDC
N+
Network wire to next DDC
N-
Network wire to next DDC
.. AHU Control Logic
AHU  operating mode () 
()
Purge mode
()
Alarm mode
()
Normal operation mode
()
Manual control mode 
()
Bypass damper control 
() Purge mode
Purge mode   AHU   
   

Network  purge   network  purge mode  enable
 controller    
Controller   output   ) controlled device 

On/Off (type) exhaust air damper   (set to open)
On/Off (type) return air damper   (set to close)
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-19
AHU supply air fan  (run) Fan speed     set point

Modulating (type) chilled water valve   (set to 0%)
() Alarm mode
           AHU
    AHU  
Blower VSD speed 
Return air damper  (set to close)
 AHU  chilled water valve  (fully close) return air
damper  (open)  Exhaust air damper (close)
() Normal operation mode
  (start/stop) (manually) 
 schedule 
AHU  DDC   mode selection switch  selector switch
    Auto mode   Mode selection switch
 selector switch  local mode  DDC    
 
() Manual control Mode

On/Off (type) exhaust air damper   (set to close)
On/Off (type) return air damper   (set to open)
AHU supply air fan  fan speed  static pressure setpoint 
PID algorithm  output contol singal  VSD 
Modulating (type) chilled water valve  cooling set point  PID
algorithm  output contol singal  modulating actuator 

AHU 

On/Off type Exhaust air damper  (set to close)

On/Off type return air damper  (set to open)

VSD output  0 %  (set to 0 %)

Valve output  0 %  (set to 0 %)
() Bypass damper control
Bypass damper control  AHU  interlock 
 (open/close) manually 
HVAC Control and Building Automation Systems 
7-20
Chilled water valve control
 modulating type chilled water valve  control 
Actuator  0~10 Vdc control signal   
Temperature setpoint  default PID parameter 

default setpoint 

Supply air temperature  control PID loop 

Proportional band default value 
Dead band default value 
 -Modulating valve control
 -Temperature control
Integral default value  derivative constant default value  0
 ( PI control  )
Supply Fan Variable Speed Drive (VSD) control
     Variable Speed Drive(VSD)  control  Output
Signal  0~10 Vdc   
Temperature setpoint  default PID parameter 

Default setpoint 

Minimum supply air static pressure  control PID loop 
Sensor range 

Proportional band default value 

Dead band default value 
Integral default value  derivative constant default value 
 ( PI control  )
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-21
 - VSD control
 - Static Pressure Control
. VAV Box DDC Controller(Model: UAV0520L)
.. Description
UAV0520L  Variable Air Volume(   
       controller  cooling only
application   configure  space temperature   set 
set-point  DDC controller 
Floating type damper actuator 
 cool air  space 
damper    cool air
 DDC controller  airflow rate
 control  set-point temperature
 Cooling Maximum
Flow  Cooling Minimum Flow 
VAV Box controller program 
ထည့္ေပးရန္လိုသည္။
 -
.. Control of Pressure Independent VAV Operation
 - Note:(
HVAC Control and Building Automation Systems 
7-22
 - Air Flow  Maximum Flow  Minimum Flow  
.. DDC Terminal Block Assignment(UAV0520L)
Terminal Blocks ()  TB1  TB6  NET terminals 
Terminal
Block
Label
Description
TB1
COM
24 VAC Input(N)
24V
24 VAC Input(L)
TB2
MO
Motor Open(Triac output for Damper open control)
24V
24 VAC output to damper actuator
MC
Motor Close(Triac output for Damper close control)
TB3
RV1
Not used
RV2
Not used
RV3
Not used
TB4
24V
Not used
FAN
Not used
TB5
COM
Common(Ground) for Thermostat
+5V
+5 VDC Power Supply for Thermostat
TS
Space Temperature Sensor input
T/O
Set point adjustment input from Thermostat
EXT
Not used
TB6
+5
+5 VDC Power Supply for Occupancy Detector(If connected)
OD
Occupancy Detector Input from sensor
COM
Common(Ground)
NET
N+
Network Input
N-
Network Output
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-23
N+
Network Input
N-
Network Output
.. DDC Layout and Wiring Diagram
 -
. Lighting Controller DDC(ULC0882L)
.. Description
ULC0882L  Lighting controller    Program 
LONMARK® standard  ULC0882L modle DDC controller  configured to
Lighting DB  control   DB On/Off status  monitor  
Universal inputs  () monitor  ULC0882L  connecte 
sensor 
()
Digital Inputs(Dry contacts)
()
Analog Inputs(4-20mA) 
()
Analog Inputs(0-5 Vdc)
()
Temperature sensors(NTC 10K Thermistor, -15°C to
100°C) 
 Dry contact digital input   
.. Output channels
Controller  Digital Outputs(maximum 8 nos. 24 Vac Triac)  Analog Outputs
(maximum 2 nos. 0-10 Vdc)   command 
 Digital Output(DO)  
HVAC Control and Building Automation Systems 
7-24
 - DI = Digital Input and DO = Digital Output
Terminal Blocks  ()  TB1  TB6  TB8 terminals 
.. DDC Terminal Block Assignment (ULC0882L )
Terminal
Block No
Label
Description
Remark
TB1
AC24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB2
TO1-TO8
DO Channels 1-8
TB3
AO1-AO2
AO Channels 1-2
TB4
UI1
Universal Input 1
All UI are digital inputs
COM
Com for UI1 & UI2
UI2
Universal Input 2
UI3
Universal Input 3
COM
Com for UI3 & UI4
UI4
Universal Input 4
TB5
UI5
Universal Input 5
COM
Com for UI5 & UI6
UI6
Universal Input 6
UI7
Universal Input 7
COM
Com for UI7 & UI8
UI8
Universal Input 8
TB6
N+
Network wire from previous DDC
N-
Network wire from previous DDC
N+
Network wire to next DDC
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-25
N-
Network wire to next DDC
.. DDC LAYOUT & WIRING DIAGRAM
NOTE: 1) EACH COM TERMINAL TO BE SHARED BY 2 UI TERMINALS
2) ALL DIGITAL OUTPUTS ARE 24 Vac TRIAC OUTPUTS
3) ALL ANALOG OUTPUTS ARE 0-10 Vdc
 -
HVAC Control and Building Automation Systems 
7-26
.. Typical Sensor Termination
 -
ULC0882LT7V1
DDC internal schedule   Lighting Distribution Board(  
 DDC  Lighting DB () status  Start/Stop control 
 -
ULC0882LT7V2
Male/Female toilet lighting  control 
Toilet  Occupancy detector  CAV controller(E1/E2)  (connect) 
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-27
Toilet lighting  ( Occupancy status changes
 unoccupied status  (delay) Toilet lighting 

 -
. GENERAL MONITORING DDC UGM0882L
.. Description
 Universal inputs ()  monitor

UGM0882L  (connect)  sensors 
()
Digital Inputs(Dry contacts)
()
Analog Inputs(0-5 Vdc)
()
Analog Inputs(4-20mA)
Analog Input monitoring  abnormal sensor reading  
First order Low Pass Filter method  
    
Where, Vnew = New reading to be updated in DDC
Vold = Old reading updated in DDC
Vin = Sensor reading,
C = constant(0.01~ 0.99)(Refer to
SCPTdebounce
)
()
Pulse Inputs(minimum pulse width 500 ms)(0-9999 counts)
Note: Accumulated counter value is saved in battery backed up RAM in the DDC;
this value will be kept if DDC power is recycled.
()
Temperature sensors(NTC 10K Thermistor, -15°C to 100°C)
Output channels
Other controllers via binding can command Digital Outputs(maximum 8 nos. 24 Vac
Triac) & Analog Outputs(maximum 2 nos. 0-10 Vdc) of UGM0882L.
HVAC Control and Building Automation Systems 
7-28
 -
There are total 7 Terminal Blocks, TB1 to TB6 & TB8 terminals.
.. Terminal Block Assignments(UGM0882L)
Terminal
Block No
Label
Description
Remark
TB1
AC24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB2
TO1-TO8
DO Channels 1-8
DO channels to be
commanded via binding
TB3
AO1-AO2
AO Channels 1-2
AO channels to be
commanded via binding
TB4
UI1
Universal Input 1
COM
Com for UI1 & UI2
UI2
Universal Input 2
UI3
Universal Input 3
COM
Com for UI3 & UI4
UI4
Universal Input 4
TB5
UI5
Universal Input 5
COM
Com for UI5 & UI6
UI6
Universal Input 6
UI7
Universal Input 7
COM
Com for UI7 & UI8
UI8
Universal Input 8
TB6
N+
Network wire from previous DDC
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-29
N-
Network wire from previous DDC
N+
Network wire to next DDC
N-
Network wire to next DDC
.. Typical Sensor Termination
DDC LAYOUT(Controller Model UGM0882L )
NOTE: 1) EACH COM TERMINAL TO BE SHARED BY 2 UI TERMINALS
4) ALL DIGITAL OUTPUTS ARE 24 Vac TRIAC OUTPUTS
5) ALL ANALOG OUTPUTS ARE 0-10 Vdc
 -
HVAC Control and Building Automation Systems 
7-30
.. DDC LAYOUT & WIRING DIAGRAM
TYPICAL SENSOR TERMINATION
 -
. General Monitoring DDC UGM2484L
.. Description
UGM2484L is General Monitoring controller 
Maximum 24 nos. of Universal inputs  monitor  2 nos. of High frequency Pulse inputs

UGM24842L controller  (connect)  I/O point 
()
Digital Inputs (Dry contacts)
()
Analog Inputs (0-5 Vdc)
()
Analog Inputs(0-20mA)
Analog Input monitoring  abnormal sensor reading   First order
Low Pass Filter method   is used to
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-31
    
Where, Vnew = New reading to be updated in DDC
Vold = Old reading updated in DDC
Vin = Sensor reading,
C = constant(0.01~ 0.99)(Refer to SCPTdebounce)
()
Low Frequency Pulse Inputs(counter value 0-9999)
(minimum pulse width 500ms)
()
High Frequency Pulse Inputs(counter value 0-1,999,999,999)
(minimum pulse width 50ms) (Only for terminal P3&P4)
Note: Accumulated counter value is saved in battery backed up RAM in the DDC;
this value will be kept if DDC power is recycled.
()
Temperature sensors(NTC 10K Thermistor, -15°C to 100°C)
()
Temperature sensors(Platinum 1K RTD type)(Only for UI17-UI24)
.. Output channels
Other controllers via binding can command Digital Outputs(maximum 8 nos. 24 Vac Triac)
& Analog Outputs(maximum 4 nos. 0-10 Vdc/0-20 mA) of UGM2484L.
 -
.. DDC Terminal Block Assignment(UGM2484L)
Terminal
Block No
Label
Description
Remark
TB0
+24V
24 VAC Input(L)
COM
24 VAC Input(N)
TB1
AO1
Analog Output 1
AO channels to be commanded
via binding
COM
Com terminal for AO1 & AO2
AO2
Analog Output 2
AO3
Analog Output 3
HVAC Control and Building Automation Systems 
7-32
COM
Com terminal for AO3 & AO4
AO4
Analog Output 4
TB2
UI1 UI4
Universal Inputs 1-4
COM
2 COM Terminals for UI 1-4
Each com shared by 2 UI
TB3
UI5 UI8
Universal Inputs 5-8
COM
2 COM Terminals for UI 5-8
Each com shared by 2 UI
TB4
UI9 UI12
Universal Inputs 9-12
COM
2 COM Terminals for UI 9-12
Each com shared by 2 UI
TB5
UI13 UI16
Universal Inputs 13-16
COM
2 COM Terminals for UI 13-16
Each com shared by 2 UI
TB6
UI17 UI20
Universal Inputs 17-20
COM
2 COM Terminals for UI 17-20
Each com shared by 2 UI
TB7
UI21 UI24
Universal Inputs 21-24
COM
2 COM Terminals for UI 21-24
Each com shared by 2 UI
TB8
P3
High/Low frequency Pulse Input 1
COM
Com terminal for P3 & P4
P4
High/Low frequency Pulse Input 2
TB9
TO1-TO8
Digital Output 1 - 8
DO channels to be commanded
via binding
TB10
N+
Network wire from previous DDC
N-
Network wire from previous DDC
N+
Network wire to next DDC
N-
Network wire to next DDC
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-33
.. DDC Layout & Wiring Diagram
 -
HVAC Control and Building Automation Systems 
7-34
.. Typical Sensor Termination
 -
-End-
 Chapter-7 Direct Digital Controllers (DDC) Wiring
7-35
Contents
. Fan Coil Unit  control   DDC Controller (Model: UFC0882L) ................... 1
.. Description ........................................................................................................................................ 1
.. DDC Terminal Block Assignment UFC0882L........................................................................................ 2
.. DDC Layout & Wiring Diagram .......................................................................................................... 3
. Fan Controller DDC(Model U6F2484L) ................................................................................ 3
.. Description ........................................................................................................................................ 4
.. DDC Terminal Block Assignment(UGM2484L) ...................................................................................... 4
.. DDC Layout & Wiring Diagram .......................................................................................................... 5
. FAN CONTROL DDC U8F2484L .......................................................................................... 5
.. Description ........................................................................................................................................ 6
.. DDC Terminal Block Assignment(U8F2484L) ....................................................................................... 6
.. DDC Layout & Wiring Diagram .......................................................................................................... 7
. Constant Air Volume(CAV) AHU Controller(UAH1464L) ........................................................ 8
.. Description ........................................................................................................................................ 8
.. DDC Terminal Block Assignment(UAH1464L) ...................................................................................... 10
.. DDC Layout & Wiring Diagram CAV AHU.......................................................................................... 11
. VAV AHU  Controller  Control Logic ................................................................ 13
.. Description of DDC Inputs and Outputs ............................................................................................. 14
.. DDC Terminal Block Assignment (UAH2484L) ..................................................................................... 17
.. AHU Control Logic ............................................................................................................................ 18
. VAV Box DDC Controller(Model: UAV0520L) ..................................................................... 21
.. Description ...................................................................................................................................... 21
.. Control of Pressure Independent VAV Operation ................................................................................ 21
.. DDC Terminal Block Assignment(UAV0520L) ...................................................................................... 22
.. DDC Layout and Wiring Diagram ....................................................................................................... 23
. Lighting Controller DDC(ULC0882L) ............................................................................... 23
.. Description ...................................................................................................................................... 23
.. Output channels ............................................................................................................................... 23
.. DDC Terminal Block Assignment (ULC0882L ) .................................................................................... 24
HVAC Control and Building Automation Systems 
7-36
.. DDC LAYOUT & WIRING DIAGRAM ................................................................................................... 25
.. Typical Sensor Termination ............................................................................................................. 26
. GENERAL MONITORING DDC UGM0882L ......................................................................... 27
.. Description ..................................................................................................................................... 27
.. Terminal Block Assignments(UGM0882L) ........................................................................................... 28
.. Typical Sensor Termination ............................................................................................................. 29
.. DDC LAYOUT & WIRING DIAGRAM ................................................................................................... 30
. General Monitoring DDC UGM2484L ................................................................................ 30
.. Description ...................................................................................................................................... 30
.. Output channels ............................................................................................................................... 31
.. DDC Terminal Block Assignment(UGM2484L) ..................................................................................... 31
.. DDC Layout & Wiring Diagram ........................................................................................................ 33
.. Typical Sensor Termination ............................................................................................................... 34

Navigation menu