EconoAir 2011 A3 Econo Air Gas Fired Heaters A4 X EAIR0411

User Manual: EconoAir Gas Fired Air Heaters-2011 A4-X EAIR0411

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadEconoAir-2011 A3 Econo Air Gas Fired Heaters-2011 A4-X EAIR0411
Open PDF In BrowserView PDF
EAIR 0411

ECONO-AIR
STOKVIS INDUSTRIAL BOILERS
(INTERNATIONAL) LIMITED
96R Walton Road East Molesey Surrey KT8 0DL
TELEPHONE 020 8783 3050 • FACSIMILE 020 8783 3051
Email: info@stokvisboilers.com • Website: http://www.stokvisboilers.com

Direct/Indirect Gas Fired
Heating and Ventilation Systems

SDF and SIDF SERIES
Introduction
The Stokvis comprehensive range of gas fired air heaters
provides high efficiency combined heating and ventilation
solutions across a broad spectrum of industrial and
commercial applications. Combined heating and ventilation
units ensure precise control, excellent indoor air quality and
optimum energy efficiency.
The units are available as either direct fired (SDF) or indirect
fired (SIDF) to give complete flexibility for optimum design
capability. Both the direct fired and indirect fired range of units
are fully CE approved and a comprehensive range of optional
equipment can be added to the standard models to allow
systems to be tailored to meet the requirements for factories,
warehouses and other types of large open space buildings.
Where applicable the units are currently Energy Technology
Listed by the Carbon Trust to allow qualifying users to claim
100% Enhanced Capital Allowances.

DIRECT FIRED TECHNICAL DATA
MODEL

System Types
The units are designed to provide the primary heat source
across a wide range of applications including:
• Ductless air distribution
• Air Induction systems
• Tempered input ventilation
• Industrial make up air
• Industrial air displacement ventilation
• Pressure ventilation systems

Controls
To maximise the efficiency of operation Stokvis supply a range
of fully integrated control packages to suit each application.
Units are supplied fully wired and complete with all starters
and contactors etc, plus time and temperature control via an
integral Trend controller.
Optimised start and stop is included as standard and controls
are password protected to prevent unauthorised adjustment.

1
2
3
4

For large open areas the units are available with a wide
range of optional air distribution heads to provide ductless air
distribution. This is achieved by slightly pressuring the building
to ensure very even air distribution both laterally and vertically,
thereby eliminating the requirement for extensive distribution
duct work and high level de-stratification fan units.

and outdoor installation

•

Model Range and Options

• Indirect gas fired units 15kW-900kW
• Direct gas fired units 30kW-1200kW
• Airflow range 0.5m³/s to 25m³/s
• External static pressures up to 2000 pascals depending
•
•
•
•
•
•
•
•
•
•

on airflow
Horizontal units
Vertical units
Indoor or fully weather proofed outdoor units
Variable supply air volume with inverter drives
Panel and/or bag filters
Mixing box complete with dampers and optional actuators
Integral silencer section
Optional evaporative cooling module
Heat recovery
Air distribution heads

Maximum air flow
m3/s

MUA

VAV

26

0.51

0.86

SDF2

MUA

VAV

53

66

1.03

1.41

SDF3

MUA

VAV

66

132

1.79

2.82

SDF4

MUA

VAV

REC

92

198

2.57

4.00

SDF5

MUA

VAV

REC

132

264

3.85

5.13

SDF7

MUA

VAV

REC

198

330

5.13

7.00

SDF9

MUA

VAV

REC

264

462

6.42

9.00

SDF11

MUA

VAV

REC

264

594

8.98

11.55

SDF14

MUA

VAV

REC

396

660

10.27

1400

SDF18

MUA

VAV

REC

462

924

14.12

18.18

SDF25

MUA

VAV

REC

594

1056

17.96

25.71

SDF-MUA are fixed volume fresh air units for Make Up Air applications, SDF-VAV models are full fresh air units complete with inverter drive to supply variable air volumes
to suit demand. SDF-REC models are complete with patented air recirculation to provide full fresh air or up to 80% recirculation air in variable proportions.
Each unit is available with a range of airflows and different burner sizes to give required temperature rise through the units up to a maximum of 42°C ΔT.
Maximum airflow for SDF25 REC is 22.5m3/s.
Units may be specified to suit alternative airflows and a range of external static pressure requirements up to 400 pascals (dependent on options fitted).
For higher static pressures please consult Stokvis.

SDF1

• Fully CE approved units for both indoor

•
•
•

Minimum air flow
m3/s

SDF1

MODEL

Features and Benefits

facilitate use of renewable solar energy
Units are supplied fully wired and complete with controls
Close temperature control
Fully modulating direct gas fired burner control with 20:1
turn down ratio
Indirect fired units with turn down ratio of up to 12:1

Std burner size
maximum kW
output

DIRECT FIRED MUA & VAV APPROXIMATE DIMENSIONS

Where duct work is required the units can be supplied with
either forward or backward curved fans to allow for duct work
resistance up to 2000 pascals thereby making them eminently
suitable for use with air induction systems.

• High thermal efficiency for reduced operating costs
• Currently ECA listed models
• SFP compliant with current Building regulations
• Fully compatible for use with transpired solar panels to

Std burner size
minimum kW
output

For smaller systems a SmartCom control panel may be used
instead of the Trend control to provide simple user-friendly
control with a comprehensive range of features.
The units are also fully compatible with BMS systems and
alternative BMS Controls maybe integrated within the control
strategy.

MUA & VAV HORIZONTAL UNITS
Width mm

Length
mm

Length
C/W
filters mm

Depth
mm

Depth
C/W
filters mm

Width
mm

Height
mm

800

860

1800

2420

700

1390

860

2854

• Aircraft hangars
• Arenas and exhibition halls
• Factory heating and ventilation
• Localised air replacement for booths and extract booths
• Make-up air for buildings with mechanical exhaust
• Sports halls
• Swimming pool hall heating and condensation control
• Warehouse and distribution centre heating
1
2
3
4
5

Outlet size
std fan
mm2

Air inlet
size h x w
mm

Aprox
weight
exc.
filters kg

229

600 X 760

225

SDF2

800

860

1800

2420

700

1390

860

2854

322

600 X 760

250

SDF3

1100

1100

2000

2640

1000

1690

1100

3554

453

900 X 1000

300

SDF4

1350

1250

2600

3240

1250

1940

1250

3954

507

1150 X 1150

400

SDF5

1800

1500

2900

3540

1650

2340

1500

4604

638

1550 X 1500

500

SDF7

1800

1500

2900

3540

1650

2340

1500

4604

715

1550 X 1500

515

SDF9

2050

2000

3200

3840

1900

2590

2000

5354

801

1800 X 1900

900

SDF11

2050

2000

3200

3840

1900

2590

2000

5354

898

1800 X 1900

925

SDF14

2350

2200

3500

4140

2200

2930

2200

5854

1007

2100 X 2100

1200

SDF18

2500

2600

3500

4140

2350

3080

2600

6404

1130

2250 X 2500

1400

SDF25

2500

2600

3500

4140

2350

3080

2600

6404

1267

2250 X 2500

1600

MODEL

Applications

MUA & VAV VETICAL UNITS

Height
mm

REC HORIZONTAL UNITS

REC VERTICAL UNITS

SDF4

1800

1500

3540

4180

1650

2340

1500

4700

507

1550 X 1400

700

SDF5

1800

1500

3540

4180

1650

2340

1500

4700

638

1550 X 1400

800

SDF7

1800

1500

3850

4490

1650

2340

1500

4700

715

1550 X 1400

900

SDF9

2050

2000

4200

4840

1900

2590

2000

5050

801

1800 X 1900

1100

SDF11

2350

2200

4280

4920

2200

2930

2200

5520

898

2060 X 2060

1350

SDF14

2350

2200

4540

5180

2200

2930

2200

5720

1007

2060 X 2060

1450

SDF18

2500

2600

4640

5280

2350

3080

2600

6020

1130

2210 X 2460

1650

SDF25

2750

2600

4880

5520

2600

3330

2600

6445

1267

2460 X 2460

1800

All dimensions and weights are approximate and should be confirmed with Stokvis.
All details are for internal units, please contact Stokvis for external unit information.
Filter dimensions include side access panel and/or bag filters.
Units will be delivered in sections to suit individual project.
External static pressures of up to 2000 Pa are available contact Stokvis for details of non standard units.

Direct Fired Units

Indirect Fired Units

The Principle of Direct Firing – Make-Up Air

Indirect Gas Fired Heat Exchanger

Where air is extracted from a building either for process or
environmental reasons a supply of heated replacement air
is required to balance the system and maintain comfort. If
make up air is not provided the extract system will perform
inefficiently at reduced capacity and a negative pressure will
be created. This results in cold air being drawn in around
the perimeter of the building and causing cold spots and
unpleasant draughts.

Stokvis gas fired air heaters incorporate a high efficiency gas
fired heating coil with a minimum thermal efficiency of 91%
based on NCV, currently qualifying for Enhanced Capital
Allowances.

For new installations the supply of heated make up air can
often provide the required ventilation without the need to
install additional extract units. Where matching extract is
required this can be integrated in the same unit to supply
both input and exhaust with the option of heat recovery from
the extract air. Direct gas firing provides a highly efficient
method of providing heated replacement air with thermal
efficiencies of 100% (based on NCV) and fully modulating
burner control withup to 20:1 turndown ratio.

The gas fired heating coils have a number of advantages
compared to traditional heat exchangers and enable the
heat exchanger section to be closely matched with the filter
sizes etc. to minimise the airflow resistance and reduce the
specific fan power required. The heating coils also provide
an excellent turn down ratio for close temperature control.
Units are fully CE approved and are supplied with all
necessary safety and monitoring controls. Each coil is fitted
with a power flue venter and a differential pressure switch
which automatically shuts down the burner in the event of a
blocked flue or combustion air inlet.
Features and Benefits

Variable air volume or air recirculation units allow systems
to be matched to constantly changing extract rates or to
provide full space heating in applications where reduced
winter ventilation rates are required.
Combined Heating and Ventilation

•
•
•

In heating mode Stokvis units provide controlled amounts
of fresh air to slightly pressurise the building and the supply
air temperature is constantly monitored and adjusted via a
fully modulating burner control to optimise the heat input to
match the precise building requirements.
Close control of the air discharge temperature virtually
eliminates heat stratification whilst slight building
pressurisation ensures very even distribution both laterally
and vertically over large areas, eliminating the requirement
for extensive ductwork distribution.

•

The amount of fresh air automatically adjusts to meet the
ventilation requirements of the space.

•

The units provide the ideal solution to large areas with
variable occupancy or industrial heating applications where
ventilation rates may change throughout the day.

•
•

In summer mode the units provide 100% fresh air with the
large primary air volumes providing improved air change
rates for optimum ’free cooling’. Optional evaporative cooling
modules may also be added.
Features and Benefits

•
•
•
•
•
•
•
•
•
•

High efficiency for reduced operating costs
Fully modulating burner with high turn down
ratio (up to 20:1)
Close control with rapid response to
temperature changes
Low maintenance costs
Improved indoor air quality
Summer fresh air for “free cooling”
Alternative model options allows systems to
be tailored to suit a wide range of applications
Horizontal or vertical units
Indoor or fully weather proofed outdoor units
Optional evaporative cooling can be added

•
•

Extended heat transfer area for high
efficiency and reduced operating costs
Reduced operating temperature for
enhanced life expectancy
Standard coils manufactured from heat
resisting stainless steel tube
Optional aluminised steel tube heating coils
available at reduced cost for units operating
on full air recirculation
Modular coils utilised on higher output units
to avoid the possibility of a complete plant
shut down in the event of a burner lockout
Enhanced reliability: each burner is fitted
with a multi-try ignition system which allows
for five ignition attempts with a pre- and post
purge on each ignition sequence
Pressure switch automatically shuts down
the burner in the event of a blocked flue or
combustion air inlet
Alternative wall or roof flue terminations
Simple wall flue outlet reduces installation
costs, eliminating roof penetrations and
potential roof leaks

Model Range and Options

•
•
•
•
•
•
•
•
•
•
•

Heat outputs 15kW-900kW
Airflow range 1m³/s to 22m³/s
External static pressures up to 2000 pascals
depending on airflow
Horizontal units
Vertical units
Indoor or fully weather proofed outdoor units
Panel and/or bag filters
Mixing box complete with dampers and
optional actuators
Integral silencer section
Heat recovery
Air distribution heads

SDF/MUA

SDF/VAV

100%
Fresh air

Constant volume direct fired make up
air (MUA) heaters to provide a fixed rate
of heated fresh air to the space.
The units are ideal for supplying heating
and make up air to large areas or to
individual spray booths etc, where
constant extract rates are used.
Generally units are sized to introduce
slightly more make up air into the space
than the extract air volume.
A balanced amount of make up air can
provide a slight positive pressure to
distribute the air uniformly throughout
the building and eliminate random
air infiltration.
For special applications such as kitchen
make up air and certain industrial
processes where the transfer of odours
or dust etc to surrounding areas
needs to be avoided, the volume of
make up air supplied is lower than the
extract rate.

SDF/REC

Variable
volume
fresh air

The variable air volume (VAV) models
allow the volume of heated make
up air to vary to suit the changing
requirements of the building orchanging
exhaust rates.
The units are fitted with a special box
burner system complete with integral
fan(s) to ensure optimum combustion
throughout the range of varying volume
main air supply.
The units supply 100% fresh air at all
times but the volume of fresh air is
automatically adjusted either by the
application of a building pressure sensor
or temperature sensors.
The building pressure sensor can be
set to maintain either a slight positive or
negative pressure inside the building to
suit the requirements of the application.
When used for space heating,
temperature sensors adjust both the
air discharge temperature and the
supply air volume to provide a rapid
warm up and maintain minimal
stratification levels.

80 – 100%
Recirculating air

20 – 100%
Fresh air

Variable air recirculation (REC) models
are fully CE approved and patented.
They provide a constant air volume with
up to 80% recirculation air.
The variable air recirculation option
combines a constant supply of 20%
fresh air which passes over the burner
with the remaining air volume being
either fresh air, recirculation air or a
mixture of fresh and recirculated air.
The variable percentage of fresh air and
recirculation air is accurately controlled
via a fully modulating face and bypass
damper with fresh air introduced using
the burner section and recirculation air
via an integral bypass.
The fully modulating burner and damper
control functions are integrated via a
microprocessor control to co-ordinate
the heating and ventilation functions.
The system can provide variable
make-up air, full building heating or
a combination of both, controlled
via building pressure sensors and
temperature sensors to respond
automatically to building pressure and
temperature requirements.

SDF / SIDF Series
GAS FIRED COMBINED HEATING AND VENTILATION
Specification
Typical Indirect Fired Unit Heater

Anodised aluminium framework with optional infill panels.
Option 1

Mineral wool insulation (0.03w/mk), panel weight 16kg/m2.

Option 2

Eco panels with enhanced insulation (0.024w/mk). Patented hydrotec water formulated polyurethane foam provides
enhanced insulation and reduced weight of 8kg/m2. The injection process guarantees continuity of thickness and
adhesion to provide excellent panel rigidity, whilst integral double edge sealing provides improved air tightness.

Indirect gas fired sections
comprise of CE certified
coils. The gas fired coils
provide high efficiency
with high turndown ratio.

Direct gas fired sections are fully CE certified
and provide 100% efficiency (NCV) and a turn
down ratio of up to 20:1.
Direct fired units provide the ideal energy
efficient solution for applications requiring
permanent ventilation or for buildings with
higher air infiltration rates.

All service panels are hinged for ease of access, with fan and burner compartment sections coming complete with locks.

Wide choice of both
panel and bag filters.

Galvanised base frame complete with
lifting access points and levelling bolts.

Standard units are supplied complete
with all wiring and controls.
Fans and motors are mounted on a separate
base frame complete with anti-vibration
mounts and flexible connections.

Aluminium aerofoil section
dampers complete with edge
seals for precise control of
fresh air and recirculation air.
A comprehensive range of
damper actuators may be
factory fitted and wired to
provide occupancy ventilation
or fresh air free cooling

SDF / SIDF Series
GAS FIRED COMBINED HEATING AND VENTILATION
Specification
Typical Indirect Fired Unit Heater

Anodised aluminium framework with optional infill panels.
Option 1

Mineral wool insulation (0.03w/mk), panel weight 16kg/m2.

Option 2

Eco panels with enhanced insulation (0.024w/mk). Patented hydrotec water formulated polyurethane foam provides
enhanced insulation and reduced weight of 8kg/m2. The injection process guarantees continuity of thickness and
adhesion to provide excellent panel rigidity, whilst integral double edge sealing provides improved air tightness.

Indirect gas fired sections
comprise of CE certified
coils. The gas fired coils
provide high efficiency
with high turndown ratio.

Direct gas fired sections are fully CE certified
and provide 100% efficiency (NCV) and a turn
down ratio of up to 20:1.
Direct fired units provide the ideal energy
efficient solution for applications requiring
permanent ventilation or for buildings with
higher air infiltration rates.

All service panels are hinged for ease of access, with fan and burner compartment sections coming complete with locks.

Wide choice of both
panel and bag filters.

Galvanised base frame complete with
lifting access points and levelling bolts.

Standard units are supplied complete
with all wiring and controls.
Fans and motors are mounted on a separate
base frame complete with anti-vibration
mounts and flexible connections.

Aluminium aerofoil section
dampers complete with edge
seals for precise control of
fresh air and recirculation air.
A comprehensive range of
damper actuators may be
factory fitted and wired to
provide occupancy ventilation
or fresh air free cooling

Direct Fired Units

Indirect Fired Units

The Principle of Direct Firing – Make-Up Air

Indirect Gas Fired Heat Exchanger

Where air is extracted from a building either for process or
environmental reasons a supply of heated replacement air
is required to balance the system and maintain comfort. If
make up air is not provided the extract system will perform
inefficiently at reduced capacity and a negative pressure will
be created. This results in cold air being drawn in around
the perimeter of the building and causing cold spots and
unpleasant draughts.

Stokvis gas fired air heaters incorporate a high efficiency gas
fired heating coil with a minimum thermal efficiency of 91%
based on NCV, currently qualifying for Enhanced Capital
Allowances.

For new installations the supply of heated make up air can
often provide the required ventilation without the need to
install additional extract units. Where matching extract is
required this can be integrated in the same unit to supply
both input and exhaust with the option of heat recovery from
the extract air. Direct gas firing provides a highly efficient
method of providing heated replacement air with thermal
efficiencies of 100% (based on NCV) and fully modulating
burner control withup to 20:1 turndown ratio.

The gas fired heating coils have a number of advantages
compared to traditional heat exchangers and enable the
heat exchanger section to be closely matched with the filter
sizes etc. to minimise the airflow resistance and reduce the
specific fan power required. The heating coils also provide
an excellent turn down ratio for close temperature control.
Units are fully CE approved and are supplied with all
necessary safety and monitoring controls. Each coil is fitted
with a power flue venter and a differential pressure switch
which automatically shuts down the burner in the event of a
blocked flue or combustion air inlet.
Features and Benefits

Variable air volume or air recirculation units allow systems
to be matched to constantly changing extract rates or to
provide full space heating in applications where reduced
winter ventilation rates are required.
Combined Heating and Ventilation

•
•
•

In heating mode Stokvis units provide controlled amounts
of fresh air to slightly pressurise the building and the supply
air temperature is constantly monitored and adjusted via a
fully modulating burner control to optimise the heat input to
match the precise building requirements.
Close control of the air discharge temperature virtually
eliminates heat stratification whilst slight building
pressurisation ensures very even distribution both laterally
and vertically over large areas, eliminating the requirement
for extensive ductwork distribution.

•

The amount of fresh air automatically adjusts to meet the
ventilation requirements of the space.

•

The units provide the ideal solution to large areas with
variable occupancy or industrial heating applications where
ventilation rates may change throughout the day.

•
•

In summer mode the units provide 100% fresh air with the
large primary air volumes providing improved air change
rates for optimum ’free cooling’. Optional evaporative cooling
modules may also be added.
Features and Benefits

•
•
•
•
•
•
•
•
•
•

High efficiency for reduced operating costs
Fully modulating burner with high turn down
ratio (up to 20:1)
Close control with rapid response to
temperature changes
Low maintenance costs
Improved indoor air quality
Summer fresh air for “free cooling”
Alternative model options allows systems to
be tailored to suit a wide range of applications
Horizontal or vertical units
Indoor or fully weather proofed outdoor units
Optional evaporative cooling can be added

•
•

Extended heat transfer area for high
efficiency and reduced operating costs
Reduced operating temperature for
enhanced life expectancy
Standard coils manufactured from heat
resisting stainless steel tube
Optional aluminised steel tube heating coils
available at reduced cost for units operating
on full air recirculation
Modular coils utilised on higher output units
to avoid the possibility of a complete plant
shut down in the event of a burner lockout
Enhanced reliability: each burner is fitted
with a multi-try ignition system which allows
for five ignition attempts with a pre- and post
purge on each ignition sequence
Pressure switch automatically shuts down
the burner in the event of a blocked flue or
combustion air inlet
Alternative wall or roof flue terminations
Simple wall flue outlet reduces installation
costs, eliminating roof penetrations and
potential roof leaks

Model Range and Options

•
•
•
•
•
•
•
•
•
•
•

Heat outputs 15kW-900kW
Airflow range 1m³/s to 22m³/s
External static pressures up to 2000 pascals
depending on airflow
Horizontal units
Vertical units
Indoor or fully weather proofed outdoor units
Panel and/or bag filters
Mixing box complete with dampers and
optional actuators
Integral silencer section
Heat recovery
Air distribution heads

SDF/MUA

SDF/VAV

100%
Fresh air

Constant volume direct fired make up
air (MUA) heaters to provide a fixed rate
of heated fresh air to the space.
The units are ideal for supplying heating
and make up air to large areas or to
individual spray booths etc, where
constant extract rates are used.
Generally units are sized to introduce
slightly more make up air into the space
than the extract air volume.
A balanced amount of make up air can
provide a slight positive pressure to
distribute the air uniformly throughout
the building and eliminate random
air infiltration.
For special applications such as kitchen
make up air and certain industrial
processes where the transfer of odours
or dust etc to surrounding areas
needs to be avoided, the volume of
make up air supplied is lower than the
extract rate.

SDF/REC

Variable
volume
fresh air

The variable air volume (VAV) models
allow the volume of heated make
up air to vary to suit the changing
requirements of the building orchanging
exhaust rates.
The units are fitted with a special box
burner system complete with integral
fan(s) to ensure optimum combustion
throughout the range of varying volume
main air supply.
The units supply 100% fresh air at all
times but the volume of fresh air is
automatically adjusted either by the
application of a building pressure sensor
or temperature sensors.
The building pressure sensor can be
set to maintain either a slight positive or
negative pressure inside the building to
suit the requirements of the application.
When used for space heating,
temperature sensors adjust both the
air discharge temperature and the
supply air volume to provide a rapid
warm up and maintain minimal
stratification levels.

80 – 100%
Recirculating air

20 – 100%
Fresh air

Variable air recirculation (REC) models
are fully CE approved and patented.
They provide a constant air volume with
up to 80% recirculation air.
The variable air recirculation option
combines a constant supply of 20%
fresh air which passes over the burner
with the remaining air volume being
either fresh air, recirculation air or a
mixture of fresh and recirculated air.
The variable percentage of fresh air and
recirculation air is accurately controlled
via a fully modulating face and bypass
damper with fresh air introduced using
the burner section and recirculation air
via an integral bypass.
The fully modulating burner and damper
control functions are integrated via a
microprocessor control to co-ordinate
the heating and ventilation functions.
The system can provide variable
make-up air, full building heating or
a combination of both, controlled
via building pressure sensors and
temperature sensors to respond
automatically to building pressure and
temperature requirements.

SDF and SIDF SERIES
Introduction
The Stokvis comprehensive range of gas fired air heaters
provides high efficiency combined heating and ventilation
solutions across a broad spectrum of industrial and
commercial applications. Combined heating and ventilation
units ensure precise control, excellent indoor air quality and
optimum energy efficiency.
The units are available as either direct fired (SDF) or indirect
fired (SIDF) to give complete flexibility for optimum design
capability. Both the direct fired and indirect fired range of units
are fully CE approved and a comprehensive range of optional
equipment can be added to the standard models to allow
systems to be tailored to meet the requirements for factories,
warehouses and other types of large open space buildings.
Where applicable the units are currently Energy Technology
Listed by the Carbon Trust to allow qualifying users to claim
100% Enhanced Capital Allowances.

DIRECT FIRED TECHNICAL DATA
MODEL

System Types
The units are designed to provide the primary heat source
across a wide range of applications including:
• Ductless air distribution
• Air Induction systems
• Tempered input ventilation
• Industrial make up air
• Industrial air displacement ventilation
• Pressure ventilation systems

Controls
To maximise the efficiency of operation Stokvis supply a range
of fully integrated control packages to suit each application.
Units are supplied fully wired and complete with all starters
and contactors etc, plus time and temperature control via an
integral Trend controller.
Optimised start and stop is included as standard and controls
are password protected to prevent unauthorised adjustment.

1
2
3
4

For large open areas the units are available with a wide
range of optional air distribution heads to provide ductless air
distribution. This is achieved by slightly pressuring the building
to ensure very even air distribution both laterally and vertically,
thereby eliminating the requirement for extensive distribution
duct work and high level de-stratification fan units.

and outdoor installation

•

Model Range and Options

• Indirect gas fired units 15kW-900kW
• Direct gas fired units 30kW-1200kW
• Airflow range 0.5m³/s to 25m³/s
• External static pressures up to 2000 pascals depending
•
•
•
•
•
•
•
•
•
•

on airflow
Horizontal units
Vertical units
Indoor or fully weather proofed outdoor units
Variable supply air volume with inverter drives
Panel and/or bag filters
Mixing box complete with dampers and optional actuators
Integral silencer section
Optional evaporative cooling module
Heat recovery
Air distribution heads

Maximum air flow
m3/s

MUA

VAV

26

0.51

0.86

SDF2

MUA

VAV

53

66

1.03

1.41

SDF3

MUA

VAV

66

132

1.79

2.82

SDF4

MUA

VAV

REC

92

198

2.57

4.00

SDF5

MUA

VAV

REC

132

264

3.85

5.13

SDF7

MUA

VAV

REC

198

330

5.13

7.00

SDF9

MUA

VAV

REC

264

462

6.42

9.00

SDF11

MUA

VAV

REC

264

594

8.98

11.55

SDF14

MUA

VAV

REC

396

660

10.27

1400

SDF18

MUA

VAV

REC

462

924

14.12

18.18

SDF25

MUA

VAV

REC

594

1056

17.96

25.71

SDF-MUA are fixed volume fresh air units for Make Up Air applications, SDF-VAV models are full fresh air units complete with inverter drive to supply variable air volumes
to suit demand. SDF-REC models are complete with patented air recirculation to provide full fresh air or up to 80% recirculation air in variable proportions.
Each unit is available with a range of airflows and different burner sizes to give required temperature rise through the units up to a maximum of 42°C ΔT.
Maximum airflow for SDF25 REC is 22.5m3/s.
Units may be specified to suit alternative airflows and a range of external static pressure requirements up to 400 pascals (dependent on options fitted).
For higher static pressures please consult Stokvis.

SDF1

• Fully CE approved units for both indoor

•
•
•

Minimum air flow
m3/s

SDF1

MODEL

Features and Benefits

facilitate use of renewable solar energy
Units are supplied fully wired and complete with controls
Close temperature control
Fully modulating direct gas fired burner control with 20:1
turn down ratio
Indirect fired units with turn down ratio of up to 12:1

Std burner size
maximum kW
output

DIRECT FIRED MUA & VAV APPROXIMATE DIMENSIONS

Where duct work is required the units can be supplied with
either forward or backward curved fans to allow for duct work
resistance up to 2000 pascals thereby making them eminently
suitable for use with air induction systems.

• High thermal efficiency for reduced operating costs
• Currently ECA listed models
• SFP compliant with current Building regulations
• Fully compatible for use with transpired solar panels to

Std burner size
minimum kW
output

For smaller systems a SmartCom control panel may be used
instead of the Trend control to provide simple user-friendly
control with a comprehensive range of features.
The units are also fully compatible with BMS systems and
alternative BMS Controls maybe integrated within the control
strategy.

MUA & VAV HORIZONTAL UNITS
Width mm

Length
mm

Length
C/W
filters mm

Depth
mm

Depth
C/W
filters mm

Width
mm

Height
mm

800

860

1800

2420

700

1390

860

2854

• Aircraft hangars
• Arenas and exhibition halls
• Factory heating and ventilation
• Localised air replacement for booths and extract booths
• Make-up air for buildings with mechanical exhaust
• Sports halls
• Swimming pool hall heating and condensation control
• Warehouse and distribution centre heating
1
2
3
4
5

Outlet size
std fan
mm2

Air inlet
size h x w
mm

Aprox
weight
exc.
filters kg

229

600 X 760

225

SDF2

800

860

1800

2420

700

1390

860

2854

322

600 X 760

250

SDF3

1100

1100

2000

2640

1000

1690

1100

3554

453

900 X 1000

300

SDF4

1350

1250

2600

3240

1250

1940

1250

3954

507

1150 X 1150

400

SDF5

1800

1500

2900

3540

1650

2340

1500

4604

638

1550 X 1500

500

SDF7

1800

1500

2900

3540

1650

2340

1500

4604

715

1550 X 1500

515

SDF9

2050

2000

3200

3840

1900

2590

2000

5354

801

1800 X 1900

900

SDF11

2050

2000

3200

3840

1900

2590

2000

5354

898

1800 X 1900

925

SDF14

2350

2200

3500

4140

2200

2930

2200

5854

1007

2100 X 2100

1200

SDF18

2500

2600

3500

4140

2350

3080

2600

6404

1130

2250 X 2500

1400

SDF25

2500

2600

3500

4140

2350

3080

2600

6404

1267

2250 X 2500

1600

MODEL

Applications

MUA & VAV VETICAL UNITS

Height
mm

REC HORIZONTAL UNITS

REC VERTICAL UNITS

SDF4

1800

1500

3540

4180

1650

2340

1500

4700

507

1550 X 1400

700

SDF5

1800

1500

3540

4180

1650

2340

1500

4700

638

1550 X 1400

800

SDF7

1800

1500

3850

4490

1650

2340

1500

4700

715

1550 X 1400

900

SDF9

2050

2000

4200

4840

1900

2590

2000

5050

801

1800 X 1900

1100

SDF11

2350

2200

4280

4920

2200

2930

2200

5520

898

2060 X 2060

1350

SDF14

2350

2200

4540

5180

2200

2930

2200

5720

1007

2060 X 2060

1450

SDF18

2500

2600

4640

5280

2350

3080

2600

6020

1130

2210 X 2460

1650

SDF25

2750

2600

4880

5520

2600

3330

2600

6445

1267

2460 X 2460

1800

All dimensions and weights are approximate and should be confirmed with Stokvis.
All details are for internal units, please contact Stokvis for external unit information.
Filter dimensions include side access panel and/or bag filters.
Units will be delivered in sections to suit individual project.
External static pressures of up to 2000 Pa are available contact Stokvis for details of non standard units.

EAIR 0411

ECONO-AIR
STOKVIS INDUSTRIAL BOILERS
(INTERNATIONAL) LIMITED
96R Walton Road East Molesey Surrey KT8 0DL
TELEPHONE 020 8783 3050 • FACSIMILE 020 8783 3051
Email: info@stokvisboilers.com • Website: http://www.stokvisboilers.com

Direct/Indirect Gas Fired
Heating and Ventilation Systems



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Create Date                     : 2011:04:28 16:30:19+01:00
Modify Date                     : 2011:05:16 13:34:16+01:00
Metadata Date                   : 2011:05:16 13:34:16+01:00
Creator Tool                    : Adobe InDesign CS3 (5.0)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 16555 bytes, use -b option to extract)
Version ID                      : 1
Instance ID                     : uuid:591837b8-8f0e-4254-99c8-4cf241f7e155
Document ID                     : adobe:docid:indd:90ce6dd3-6988-11e0-903e-df6408956c53
Rendition Class                 : proof:pdf
Derived From Instance ID        : 79620851-6813-11e0-8197-997d9e52079d
Derived From Document ID        : adobe:docid:indd:1c5cb7d5-6270-11e0-a9ff-dcf6d349a6d6
Derived From Version ID         : 1
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 300.00, 300.00, 300.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 343.00, 150.00, 72.00, 72.00, 72.00, 300.00, 300.00, 72.00, 300.00, 300.00, 343.00, 300.00, 300.00, 300.00
Manifest Placed Y Resolution    : 300.00, 300.00, 300.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 343.00, 150.00, 72.00, 72.00, 72.00, 300.00, 300.00, 72.00, 300.00, 300.00, 343.00, 300.00, 300.00, 300.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : xmp.iid:777FE3E69061E011B4D78ED69DA74DCC, xmp.iid:727FE3E69061E011B4D78ED69DA74DCC, xmp.iid:787FE3E69061E011B4D78ED69DA74DCC, xmp.iid:0B154F06FA64E0118E788D535E5ADDE4, xmp.iid:AA045C239362E01197D3DFFBB310DFCC, uuid:38bd4204-91b8-11d7-a776-e837ff04c337, uuid:E40D2408CE28DD119D7CE7ACEFA885B5, uuid:DEB4B441CE28DD119D7CE7ACEFA885B5, uuid:DD0D2408CE28DD119D7CE7ACEFA885B5, uuid:5AB0BC20CE28DD119D7CE7ACEFA885B5, uuid:0C094878CE28DD119D7CE7ACEFA885B5, uuid:C374836189FED911B724BDEFADA6420C, xmp.iid:A8045C239362E01197D3DFFBB310DFCC, uuid:1BE4A5D4CD28DD119D7CE7ACEFA885B5, xmp.iid:0C154F06FA64E0118E788D535E5ADDE4, uuid:437B247AA367E011AC92BC141529BAF1, uuid:5af37174-830d-4881-a8ad-44d75ae57297, uuid:fa9518b5-f13d-41b7-a9dd-14619fd5215e, uuid:a1f89ac4-c4fb-4c97-b70e-b80b74ac98c5, xmp.iid:B1FF300BA461E011B4D78ED69DA74DCC, xmp.iid:0A154F06FA64E0118E788D535E5ADDE4, uuid:20abc37c-7943-4765-a592-ad5abf37c917, xmp.iid:73BC8929EF64E0118E788D535E5ADDE4, xmp.iid:70BC8929EF64E0118E788D535E5ADDE4, xmp.iid:0C154F06FA64E0118E788D535E5ADDE4, xmp.iid:19C98B1DBB61E011B4D78ED69DA74DCC, xmp.iid:16C98B1DBB61E011B4D78ED69DA74DCC, xmp.iid:17C98B1DBB61E011B4D78ED69DA74DCC
Manifest Reference Document ID  : xmp.did:757FE3E69061E011B4D78ED69DA74DCC, xmp.did:6F7FE3E69061E011B4D78ED69DA74DCC, xmp.did:737FE3E69061E011B4D78ED69DA74DCC, uuid:6e82c9c7-2440-45b2-8033-0fee10806166, adobe:docid:indd:1c5cb7d5-6270-11e0-a9ff-dcf6d349a6d6, adobe:docid:photoshop:ec86f767-91b6-11d7-a776-e837ff04c337, adobe:docid:photoshop:578c436b-26c8-11d7-b345-d60d87dcec0e, uuid:D3CC46D8AC16DD118CF5C5656FE0A092, adobe:docid:photoshop:578c436c-26c8-11d7-b345-d60d87dcec0e, adobe:docid:photoshop:578c4367-26c8-11d7-b345-d60d87dcec0e, adobe:docid:photoshop:578c4369-26c8-11d7-b345-d60d87dcec0e, uuid:C274836189FED911B724BDEFADA6420C, adobe:docid:indd:b38ac1c9-5fac-11e0-bbb9-80365c0c0944, adobe:docid:indd:ece1b24f-06e9-11dd-8830-d560acc41b1d, xmp.did:ECDB4E4ADC64E011BD57FE2F0F99E232, uuid:40f67086-81f1-49ea-b71f-722753729d47, uuid:83E7B265A061E0119C08A6896D158B3D, uuid:81E7B265A061E0119C08A6896D158B3D, uuid:86E7B265A061E0119C08A6896D158B3D, xmp.did:ACFF300BA461E011B4D78ED69DA74DCC, uuid:6e82c9c7-2440-45b2-8033-0fee10806166, uuid:EB8A30E1AD61E011BE92E7D7C36822E3, uuid:6e82c9c7-2440-45b2-8033-0fee10806166, uuid:6e82c9c7-2440-45b2-8033-0fee10806166, xmp.did:ECDB4E4ADC64E011BD57FE2F0F99E232, xmp.did:18C98B1DBB61E011B4D78ED69DA74DCC, xmp.did:478B5022A861E011B4D78ED69DA74DCC, xmp.did:438B5022A861E011B4D78ED69DA74DCC
Manifest Reference Version ID   : 1
Format                          : application/pdf
Title                           : EconoAir-2011 A3.indd
Producer                        : Adobe PDF Library 8.0
Trapped                         : False
GTS PDFX Version                : PDF/X-4
Page Count                      : 8
Creator                         : Adobe InDesign CS3 (5.0)
EXIF Metadata provided by EXIF.tools

Navigation menu