Eastron SDM630 Energy Meter_manual 20161221 Meter Manual
User Manual: Energy-Meter_manual-20161221
Open the PDF directly: View PDF
.
Page Count: 22
| Download | |
| Open PDF In Browser | View PDF |
SDM630-MODBUS Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2016 V2.0 Important Safety Information is contained in the Maintenance section. Familiarize yourself with this information before attempting installation or other procedures. Symbols used in this document: Risk of Danger: These instructions contain important safety information: Read them before starting installation or servicing of the equipment Caution: Risk of Electric Shock 1 Introduction The SDM630-Modbus measures and displays the characteristics of single phase two wires (1p2w), three phase three wires (3p3w,) and three phase four wires(3p4w) supplies, including voltage, frequency, current, power ,active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60 minutes. In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product. SDM630-Modbus supports max. 100A direct connection, saves the cost and avoid the trouble to connect external CTs, giving the unit a cost-effective and easy operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is password protected. 1.1 Unit Characteristics The Unit can measure and display: Line voltage and THD% (total harmonic distortion) of all phases Line Frequency Currents, Current demands and current THD% of all phases Power, maximum power demand and power factor Active energy imported and exported Reactive energy imported and exported The unit has password-protected set-up screens for: Changing password Supply system selection 1p2w, 3p3w,3p4w Demand Interval Time(DIT) Reset for demand measurements Pulse output duration Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer. 1.2 RS485 Serial – Modbus RTU This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the Unit Set-up screens are provided for setting up the RS485 port. 1.3 Pulse output This provides two pulse outputs that clock up measured active and reactive energy. The constant of pulse output 2 for active energy is 400imp/kWh (unconfigurable), its width is fixed at 100ms. The default constant of configurable pulse output 1 is 400imp/kWh, default pulse width is 100ms.The configurable pulse output 1 can be set from the set-up menu. -1- 2. Start-up Screens 3. 1 The first screen lights up all display segments and can be used as a display check 2 The second screen indicates the firmware installed in the unit and its build number. 3 The interface performs a self-test and indicates the result if the test passes. After a short delay, the screen will display active energy measurements. 3. Measurements The buttons operate as follows: 1 Selects the Voltage and Current display screens In Set-up Mode, this is the “Left” or “Back” button. 2 Select the Frequency and Power factor display screens In Set-up Mode, this is the “Up” button 3 Select the Power display screens In Set-up Mode, this is the “Down” button 4 Select the Energy display screens In Set-up mode, this is the “Enter” or “Right” button -2- 3.1 Voltage and Current Each successive pressing of the button selects a new range: 1-1 Phase to neutral voltages(3p4w) 1-2 Phase to neutral voltages(3p3w) 2 Current on each phase 3-1 Phase to neutral voltage THD%(3p4w) 3-2 Phase to neutral voltage THD%(3p3w) -3- 4 Current THD% for each phase 3.2 Frequency and Power factor and Demand Each successive pressing of the button selects a new range: 1 Frequency and Power Factor (total) 2 Power Factor of each phase 3 Maximum Power Demand 4 Maximum Current Demand -4- 3.3 Power Each successive pressing of the button select a new range: 1 Instantaneous Active Power in kW 2 Instantaneous Reactive Power in kVAr 3 Instantaneous Volt-amps in KVA 4 Total kW, kVArh, kVA -5- Energy Measurements Each successive pressing of the button selects a new range: 1-1 Imported active energy in kWh 1-2 Exported active energy in kWh 2-1 Imported reactive energy in kVArh 2-2 Exported reactive energy in kVArh 3-1 Total active energy in kWh -6- 3-2 Total reactive energy in kVArh 4. Set-up To enter set-up mode, pressing the appears. button for 3 seconds, until the password screen Setting up is password-protected so you must enter the correct password (default ‘1000’) before processing. If an incorrect password is entered, the display will show: Err To exit setting-up mode, press repeatedly until the measurement screen is restored. 4.1 Set-up Entry Methods Some menu items, such as password, require a four-digit number entry while others, such as supply system, require selection from a number of menu options. 4.1.1 Menu Option Selection 1) Use the and buttons to select the required item from the menu. Selection does not roll over between bottom and top of list 2) Press to confirm your selection 3) If an item flashes, then it can be adjusted by the maybe a further layer. and buttons. If not, there -7- 4) Having selected an option from the current layer, press The SET indicator will appear. 5) Having completed a parameter setting, press to confirm your selection. to return to a higher menu level. The SET indicator will be removed and you will be able to use the and further menu selection. 6) On completion of all set-up, press restored. buttons for repeatedly until the measurement screen is 4.1.2 Number Entry Procedure When setting up the unit, some screens require the entering of a number. In particular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right. The procedure is as follows: 1) The current digit to be set flashes and is set using the 2) Press been set. and buttons to confirm each digit setting. The SET indicator appears after the last digit has 3) After setting the last digit, press will be removed. to exit the number setting routine. The SET indicator 4.2 Change password 1 Use the and choose the change password option to 2-1 Press the to enter the change password routine. The new password screen will appear with the first digit flashing -8- 2-2 Use and to set the first digit and press to confirm your selection. The next digit will flash. 2-3 Repeat the procedure for the remaining three digits 2-4 After setting the last digit, SET will show. Press removed to exit the number setting routine and return to the Set-up menu. SET will be 4.3 DIT Demand Integration Time This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement. The options are: 0, 5, 8, 10, 15, 20, 30, 60 minutes 1 From the set-up menu, use and buttons to select the DIT option. The screen will show the currently selected integration time. 2-1 Press to enter the selection routine. The current time interval will flash -9- 2-2 Use and select the time required. buttons to 2-3 Press to confirm the selection. SET indicator will appear. Press to exit the DIT selection routine and return to the menu. 4.4 Backlit setup 1 The backlit lasting time is settable Default lasting time is 60minutes For example, if it’s set as 5, the backlit will be off in 5minutes from the last time operation on the meter. 2 Press to enter the selection routine. The current time interval will flash The options can be: 0(always on),5,10,30,60,120minutes Use set-up, and buttons to select the time required. Press to confirm the 4.5 Supply System Use this section to set the type of power supply being monitored. - 10 - 1 From the Set-up menu, use and buttons to select the System option. The screen will show the currently selected power supply. 2-1 Press to enter the selection routine. The current selection will flash 2-2 Use and buttons to select the required system option: 1P2(W),3P3(W) ,3P4(W) 2-3 Press to confirm the selection. SET indicator will appear. Press to exit the system selection routine and return to the menu. SET will disappear and you will be returned to the main Set-up Menu 4.6 Pulse output This option allows you to configure the pulse output 1. The output can be set to provide a pulse for a defined amount of energy active or reactive. Use this section to set up the pulse output for: Total kWh/ Total kVArh Import kWh/Export kWh Import KVArh/Export KVArh - 11 - 1 From the Set-up menu, use and buttons to select the Pulse output option. 2-1 Press to enter the selection routine. The unit symbol will flash. 2-2 Use and choose kWh or kVArh. On completion of the entry procedure, press buttons to to confirm the setting and press to return to the main set up menu. 4.6.1 Pulse rate Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per dFt/0.01/0.1/1/10/100kWh/kVArh. (It shows 1 impulse = 10kWh/kVArh) 1 From the Set-up menu, use and buttons to select the Pulse Rate option. - 12 - 2 Press to enter the selection routine. The current setting will flash. Note: When it’s dFt, it means 2.5Wh/VArh Use and procedure, press up menu. buttons to choose pulse rate. On completion of the entry to confirm the setting and press to return to the main set 4.6.2 Pulse Duration The energy monitored can be active or reactive and the pulse width can be selected as 200, 100(default) or 60ms. (It shows pulse width of 200ms) 1-1 From the Set-up menu, use and buttons to select the Pulse width option. 1-2 Press to enter the selection routine. The current setting will flash. Use and procedure, press up menu. buttons to choose pulse width. On Completion of the entry to confirm the setting and press to return to the main set - 13 - 4.7 Communication There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus RTU, parameters are selected from Front panel. 4.7.1 RS485 Address (The range is from 001 to 247) 1 From the Set-up menu, use and buttons to select the Address ID 2-1 Press button to enter the selection routine. The current setting will be flashing. 2-2 Use and buttons to choose Modbus Address(001 to 247) On completion of the entry procedure, press button to confirm the setting and press button to return the main set-up menu. - 14 - 4.7.2 Baud Rate 1 From the Set-up menu, use and buttons to select the Baud Rate option. 2-1 Press to enter the selection routine. The current setting will flash. 2-2 Use and buttons to choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k, 38.4k On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu. 4.7.3 Parity 1 From the Set-up menu, use and buttons to select the Parity option. 2-1 Press to enter the selection routine. The current setting will flash. - 15 - 2-2 Use and buttons to choose Parity (EVEN / ODD / NONE) On Completion of the entry procedure, press to confirm the setting and press to return to the main set up menu. 4.7.4 Stop bits 1 From the Set-up menu, use and buttons to select the Stop Bit option. 2-1 Press to enter the selection routine. The current setting will flash. 2-2 Use and choose Stop Bit (2 or 1) On completion of the entry procedure, press buttons to to confirm the setting and press to return to the main set up menu. Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2. - 16 - 4.8 CLR The meter provides a function to reset the maximum demand value of current and power. 1 From the Set-up menu, use and buttons to select the reset option. 2 Press to enter the selection routine. The MD will flash. Press to confirm the setting and press to return to the main set up menu. 5 Specifications 5.1 Measured Parameters The unit can monitor and display the following parameters of a single phase two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) supply. 5.1.1 Voltage and Current Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies) Voltages between phases 173 to 500V a.c. (3p supplies only) Basic current (Ib): 10A Max current : 100A Min. Current: 5% of Ib Starting current: 0.4% of Ib Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies) Percentage voltage THD% between phases (three phase supplies only) Current THD% for each phase 5.1.2 Power factor and Frequency and Max. Demand Frequency in Hz Instantaneous power: Power 0 to 99999 W Reactive Power 0 to 99999 VAr Volt-amps 0 to 99999 VA Maximum demanded power since last Demand reset Power factor - 17 - Maximum neutral demand current, since the last Demand reset (for 3p4w supply only) 5.1.3 Energy Measurements Imported active energy 0 to 999999.99 kWh Exported active energy 0 to 999999.99 kWh Imported reactive energy 0 to 999999.99 kVArh Exported reactive energy 0 to 999999.99 kVArh Total active energy 0 to 999999.99 kWh Total reactive energy 0 to 999999.99 kVArh 5.2 Measured Inputs Voltage inputs through 4-way fixed connector with 25mm² stranded wire capacity. single phase two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) unbalanced. Line frequency measured from L1 voltage or L3 voltage. 5.3 Accuracy Voltage Current Frequency Power factor Active power (W) Reactive power (VAr) Apparent power (VA) Active energy (Wh) Reactive energy (VARh) Total harmonic distortion Temperature co-efficient Response time to step input 0·5% of range maximum 0·5% of nominal 0·2% of mid-frequency 1% of unity (0.01) ±1% of range maximum ±1% of range maximum ±1% of range maximum Class 1 IEC 62053-21 ±1% of range maximum 1% up to 31st harmonic Voltage and current = 0.013%/°C typical Active energy = 0·018%/°C, typical 1s, typical, to >99% of final reading, at 50 Hz. 5.4 Interfaces for External Monitoring Three interfaces are provided: an RS485 communication channel that can be programmed for Modbus RTU protocol an Pulse output(Pulse 1) indicating real-time measured energy.(configurable) an Pulse output(Pulse 2) 400imp/kWh The Modbus configuration (Baud rate etc.) and the pulse output assignments (kW/kVArh, import/export etc.) are configured through the Set-up screens. 5.4.1 Pulse Output The unit provides two pulse outputs. Both pulse outputs are passive type. Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export kWh or kVarh. The pulse constant can be set to generate 1 pulse per: dFt = 2.5 Wh/VArh 0.01 = 10 Wh/VArh - 18 - 0.1 = 100 Wh/VArh 1 = 1 kWh/kVArh 10 = 10 kWh/kVArh 100 = 100 kWh/kVArh Pulse width: 200/100/60ms Pulse output 2 is non-configurable. It is fixed up with active kWh. The constant is 400imp/kWh. 5.4.2 RS485 Output for Modbus RTU For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu: Baud rate 2400, 4800, 9600, 19200, 38400 Parity none (default)/odd/even Stop bits 1 or 2 RS485 network address nnn – 3-digit number, 001 to 247 Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from the set-up menu. 5.5 Reference Conditions of Influence Quantities Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified tolerance) of these conditions. Ambient temperature 23°C ±1°C Input frequency 50 or 60Hz ±2% Input waveform Sinusoidal (distortion factor < 0·005) Magnetic field of external origin Terrestrial flux 5.6 Environment Operating temperature Storage temperature Relative humidity Altitude Warm up time Vibration -25°C to +55°C* -40°C to +70°C* 0 to 90%, non-condensing Up to 2000m 1 minute 10Hz to 50Hz, IEC 60068-2-6, 2g 5.7 Mechanics - 19 - 6 Wiring diagram - 20 -