Emerson Millennium II Multi Channel Transmitter M22 FGD MAN M21 Transmitters

User Manual: Emerson Millennium II Multi-Channel Transmitter M22

Open the PDF directly: View PDF PDF.
Page Count: 56

Reference Manual
Part Number: MAN-0076, rev. 09
Release: June 2016
Millennium II Multi-Channel Transmitter
Important Instructions
Net Safety Monitoring, Inc (Net Safety) designs, manufactures and tests products to function within
specific conditions. Because these products are sophisticated technical instruments, it is important
that the owner and operation personnel must strictly adhere both to the information printed on the
product nameplate and to all instructions provided in this manual prior to installation, operation, and
maintenance.
Installing, operating or maintaining a Net Safety Product improperly could lead to serious injury or
death from explosion or exposure to dangerous substances. Comply with all information on the
product, in this manual, and in any local and national codes that apply to the product. Do not allow
untrained personnel to work with this product. Use Net Safety parts and work procedures specified in
this manual.
Notice
The contents of this publication are presented for informational purposes only, and while every effort
has been made to ensure their accuracy, they are not to be construed as warranties or guarantees,
expressed or implied, regarding the products or services described herein or their use or applicability.
All sales are governed by Net Safety’s terms and conditions, which are available upon request. We
reserve the right to modify or improve the designs or specifications of such products at any time.
Net Safety does not assume responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use and maintenance of any Net Safety products remains solely with
the purchaser and end-user.
To the best of Net Safety’s knowledge the information herein is complete and accurate. Net Safety
makes no warranties, expressed or implied, including implied warranties of merchantability and fitness
for a particular purpose with respect to this manual and, in no event, shall Net Safety be liable for any
incidental, punitive, special or consequential damages including, but not limited to, loss of production,
loss of profits, loss of revenue or use and costs incurred including without limitation for capital, fuel and
power, and claims of third parties.
Product names used herein are for manufacturer or supplier identification only and may be
trademarks/registered trademarks of these companies.
Net Safety and the Net Safety logo are registered trademarks of Net Safety Monitoring, Inc. The
Emerson logo is a trademark and service mark of the Emerson Electric Company.
Copyright © 2016 by Rosemount, Shakopee, MN.
All rights reserved. No part of this work may be reproduced or copied in any form or by any means - graphic,
electronic, or mechanical without first receiving written permission of Rosemount, Shakopee, MN.
Warranty
1.
Limited Warranty
. Subject to the limitations contained in Section 10 (Limitation of Remedy
and Liability) herein, Seller warrants that (a) the licensed firmware embodied in the Goods will
execute the programming instructions provided by Seller; (b) that the Goods manufactured by
Seller will be free from defects in materials or workmanship under normal use and care; and (c)
Services will be performed by trained personnel using proper equipment and instrumentation
for the particular Service provided. The foregoing warranties will apply until the expiration of
the applicable warranty period. Sensors and detectors are warranted against defective parts
and workmanship for 24 months from the date of purchase and other electronic assemblies for
36 months from the date of purchase. Products purchased by Seller from a third party for
resale to Buyer (
Resale Products
) shall carry only the warranty extended by the original
manufacturer. Buyer agrees that Seller has no liability for Resale Products beyond making a
reasonable commercial effort to arrange for procurement and shipping of the Resale Products.
If Buyer discovers any warranty defects and notifies Seller thereof in writing during the
applicable warranty period, Seller shall, at its option, (i) correct any errors that are found by
Seller in the firmware or Services; (ii) repair or replace FOB point of manufacture that portion of
the Goods found by Seller to be defective; or (iii) refund the purchase price of the defective
portion of the Goods/Services. All replacements or repairs necessitated by inadequate
maintenance; normal wear and usage; unsuitable power sources or environmental conditions;
accident; misuse; improper installation; modification; repair; use of unauthorized replacement
parts; storage or handling; or any other cause not the fault of Seller, are not covered by this
limited warranty and shall be replaced or repaired at Buyer’s sole expense and Seller shall not
be obligated to pay any costs or charges incurred by Buyer or any other party except as may be
agreed upon in writing in advance by Seller. All costs of dismantling, reinstallation, freight and
the time and expenses of Seller’s personnel and representatives for site travel and diagnosis
under this limited warranty clause shall be borne by Buyer unless accepted in writing by Seller.
Goods repaired and parts replaced by Seller during the warranty period shall be in warranty for
the remainder of the original warranty period or 90 days, whichever is longer. This limited
warranty is the only warranty made by Seller and can be amended only in a writing signed by an
authorized representative of Seller. The limited warranty herein ceases to be effective if Buyer
fails to operate and use the Goods sold hereunder in a safe and reasonable manner and in
accordance with any written instructions from the manufacturers. THE WARRANTIES AND
REMEDIES SET FORTH ABOVE ARE EXCLUSIVE. THERE ARE NO REPRESENTATIONS OR
WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR
PARTICULAR PURPOSE OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE GOODS OR
SERVICES.
2.
Limitation of Remedy and Liability
. SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY
DELAY IN PERFORMANCE. THE REMEDIES OF BUYER SET FORTH IN THE AGREEMENT ARE
EXCLUSIVE. IN NO EVENT, REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTION
(WHETHER BASED IN CONTRACT, INFRINGEMENT, NEGLIGENCE, STRICT LIABILITY, OTHER
TORT OR OTHERWISE), SHALL SELLER’S LIABILITY TO BUYER AND/OR BUYER’S CUSTOMERS
EXCEED THE PRICE TO BUYER OF THE SPECIFIC GOODS MANUFACTURED OR SERVICES
PROVIDED BY SELLER GIVING RISE TO THE CLAIM OR CAUSE OF ACTION. BUYER AGREES THAT
IN NO EVENT SHALL SELLER’S LIABILITY TO BUYER AND/OR BUYER’S CUSTOMERS EXTEND TO
INCLUDE INCIDENTAL, CONSEQUENTIAL OR PUNITIVE DAMAGES. THE TERM
“CONSEQUENTIAL DAMAGES” SHALL INCLUDE, BUT NOT BE LIMITED TO, LOSS OF
ANTICIPATED PROFITS, REVENUE OR USE AND COSTS INCURRED INCLUDING WITHOUT
LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS OF BUYER’S CUSTOMERS.
Reference Manual Table of Contents
MAN-0076 Revision 09 June 2016
Table of Contents I
Contents
Section 1 : Introduction .................................................................. 1
1.1 Models covered ............................................................................................................ 1
1.2 Service support ............................................................................................................. 1
1.3 Return of material......................................................................................................... 1
1.4 Product recycling/disposal ............................................................................................ 1
Section 2 : Installation .................................................................... 2
2.1 Unpacking and inspection ............................................................................................ 2
2.2 Dimensions .................................................................................................................. 2
2.3 Mounting ..................................................................................................................... 2
2.3.1 Transmitter orientation options ...................................................................... 2
2.3.2 Faceplate rotation .......................................................................................... 3
2.4 Wiring .......................................................................................................................... 4
2.4.1 General requirements ..................................................................................... 4
2.4.2 Terminal connection ....................................................................................... 5
2.4.3 Cable choice and guidelines ............................................................................ 5
2.4.4 Important wiring guidelines ............................................................................ 5
2.4.5 Internal ground screw ..................................................................................... 6
2.4.6 External ground .............................................................................................. 6
2.4.7 Seals ............................................................................................................... 6
2.4.8 Analog output, isolated supply, non-isolated supply and jumper configuration7
2.4.9 Remotely mounted sensors jumper configuration .......................................... 8
2.4.10 Sensor and transmitter terminals .................................................................... 8
2.4.11 Remote reset .................................................................................................. 9
2.5 Sensor separation/remote mounting of sensor ........................................................... 10
2.5.1 Wiring diagrams ........................................................................................... 11
2.6 Installation checklist ................................................................................................... 12
Section 3 : Operation .................................................................... 13
3.1 Transmitter and faceplate description ........................................................................ 13
3.1.1 Display.......................................................................................................... 13
3.1.2 Status LED .................................................................................................... 13
3.1.3 Current loop measurement (test jacks) ......................................................... 14
3.1.4 Menu buttons and access .............................................................................. 14
3.1.4.1 Intrusive access ............................................................................................. 14
3.1.4.2 Non-Intrusive Access/Magnetic Reed switch Access ...................................... 14
3.2 Transmitter power up ................................................................................................. 14
Section 4 : Programming .............................................................. 15
4.1 Menu options ............................................................................................................. 15
4.2 Navigating main menu ............................................................................................... 15
4.3 Calibrate sensor .......................................................................................................... 17
4.4 Enable/Disable channels ............................................................................................. 17
4.5 Set alarm level ............................................................................................................ 17
4.6 Set relay option .......................................................................................................... 18
4.7 Relay assignment ....................................................................................................... 18
4.8 Alarm mode setting .................................................................................................... 20
4.9 Select display language .............................................................................................. 20
4.10 Modbus Setup ............................................................................................................ 20
4.11 Setup current date ...................................................................................................... 21
4.12 Setup current time ..................................................................................................... 21
4.13 View events log .......................................................................................................... 21
Table of Contents Reference Manual
June 2016 MAN-0076, Revision 09
Table of Contents II
4.14 Manual reset ............................................................................................................... 22
4.15 Self-test relay.............................................................................................................. 22
4.16 Sensor upper limit (range) .......................................................................................... 23
4.17 Select gas type ........................................................................................................... 23
4.18 Calibration gas value................................................................................................... 24
4.19 Serial number and firmware version ............................................................................ 24
4.20 Exit ............................................................................................................................. 24
Section 5 : Calibration procedure .................................................. 25
5.1 Full calibration procedure ........................................................................................... 25
5.2 Status conditions during calibration............................................................................ 28
Section 6 : Monitoring and outputs ............................................... 29
6.1 Analog 4-20mA .......................................................................................................... 29
6.2 HART Communication (Optional) ............................................................................... 29
6.3 Relays (Optional) ........................................................................................................ 30
6.3.1 Alarm relay(s) ............................................................................................... 30
6.3.2 Fault relay ..................................................................................................... 30
6.4 RS-485 Modbus RTU (Optional) .................................................................................. 31
6.4.1 Modbus registers .......................................................................................... 32
6.5 Transmitter output operation ..................................................................................... 33
6.6 Fault monitoring ......................................................................................................... 33
6.7 Fault conditions .......................................................................................................... 34
6.7.1 Transmitter fault conditions .......................................................................... 34
6.7.2 Sensor fault conditions ................................................................................. 35
Section 7 : Maintenance ................................................................ 36
7.1 Periodic response check ............................................................................................. 36
7.2 Troubleshooting ......................................................................................................... 36
7.3 Storage ...................................................................................................................... 36
7.4 Spare parts and accessories ........................................................................................ 37
Section 8 : Electrostatic sensitive device ....................................... 39
Section 9 : Wire resistance table ................................................... 40
Section 10 : Specifications ............................................................ 41
10.1 Electrical ..................................................................................................................... 41
10.1.1 Operating voltage range ............................................................................... 41
10.1.2 Power consumption ...................................................................................... 41
10.1.3 EMC compliance ........................................................................................... 41
10.2 Environmental ............................................................................................................ 41
10.2.1 Operating temperature ................................................................................ 41
10.2.2 Relative humidity .......................................................................................... 41
10.2.3 Ingress protection......................................................................................... 41
10.3 Mechanical ................................................................................................................. 41
10.3.1 Enclosure material ........................................................................................ 41
10.3.2 Conduit opening ........................................................................................... 41
10.3.3 Weight ......................................................................................................... 42
10.4 Warranty .................................................................................................................... 42
Section 11 : Certifications ............................................................. 43
11.1 North American .......................................................................................................... 43
11.2 IECEx .......................................................................................................................... 43
Reference Manual Table of Contents
MAN-0076 Revision 09 June 2016
Table of Contents III
11.3 FC Models ................................................................................................................... 43
11.3.1 North American ............................................................................................ 43
11.3.2 IECEx (aluminum) ......................................................................................... 43
11.3.3 IECEx (stainless) ............................................................................................ 43
Section 12 : Ordering information ................................................ 44
12.1 M21 single channel transmitter .................................................................................. 44
12.2 M22 dual channel transmitter ..................................................................................... 45
Reference Manual Introduction
MAN-0076, Revision 09 June 2016
Introduction 1
Section 1: Introduction
1.1 Models covered
A Millennium II gas detection system is composed of a field mounted transmitter and Millennium II
series sensors which may be integrally mounted to the transmitter or remotely mounted.
The transmitter is certified for use in hazardous locations and is available as a single or dual sensor
system. All operator controls including configuration and calibration can be accessed without opening
the enclosure by using other communication devices and the attached magnet to actuate magnetic
Reed switches. Available outputs are: conventional 4 to 20 mA analog, Analog/HART,
electromechanical relays, or Modbus RTU digital.
1.2 Service support
Technical support for this product can be provided by contacting your local Emerson Process
Management representative or by contacting the Technical Support department at +1 866 347 3427
(toll free) or Safety.CSC@Emerson.com.
1.3 Return of material
To expedite the return of this product, proper communication between the customer and the factory is
important. Before returning a product, call +1 866 347 3427 (toll free) or e-mail
Safety.CSC@Emerson.com for a Return Material Authorization (RMA) number.
On the return of the equipment, include the following information:
1. RMA number provided to you by Rosemount
2. Company name and contact information
3. Ship all equipment, prepaid to:
Rosemount
6021 Innovation Boulevard
Shakopee, MN 55379
4. Mark all packages with the
RMA number
and type of return (e.g. return for evaluation
)
Pack items to protect them from damage and use anti-static bags or aluminum-backed cardboard as
protection from electrostatic damage.
All equipment must be shipped prepaid. Collect shipments will not be accepted.
1.4 Product recycling/disposal
Recycling of equipment and packaging should be taken into consideration and disposed of in
accordance with local and national legislations/regulations.
Installation Reference Manual
June 2016 MAN-0076, Revision 09
2 Installation
Section 2: Installation
2.1 Unpacking and inspection
Carefully remove all of the components from the packaging and verify them against the enclosed
packing list. Inspect all components for any obvious damage such as broken or loose parts. If you find
any components missing or damaged, notify your local Net Safety representative or the factory
immediately.
2.2 Dimensions
The Millennium II transmitter enclosure is available in aluminum (A359) and stainless steel (SS316).
Dimensions are provided in inches and [millimeters].
Figure 2-1 - Dimensions
*M20, 1/2” NPT, and 1/2” BSP threads also available
2.3 Mounting
Ensure transmitter and sensor are securely mounted as per local regulations. The transmitter has
mounting holes to allow mounting to a wall or pole as desired. Mounting kit hardware is required when
mounting the transmitter a pole. Contact your local Net Safety representative for detailed information
on the pole mounting kits. The transmitter should be mounted at eye-level and be easily accessible for
monitoring and maintenance purposes.
2.3.1 Transmitter orientation options
Depending on the installation and mounting requirements, the transmitter enclosure (housing) may be
mounted in different orientations as seen in Figure 2-2. To accommodate the different mounting
orientations, the electronics module can be rotated inside the transmitter enclosure.
Reference Manual Installation
MAN-0076, Revision 09 June 2016
Installation 3
Ensure the orientation allows proper wiring and adequate wire length inside the transmitter enclosure.
When determining suitable enclosure
orientation for specific applications, installers should observe all
local regulations and guidelines for mounting enclosures.
Figure 2-2 Different enclosure orientations
2.3.2 Faceplate rotation
Before wiring or rotating electronics, ensure that the power to transmitter is switched off. Do not open
the transmitter enclosure in a classified area.
Avoid touching electronic components, as they are susceptible to electrostatic discharge (ESD). Refer
to Section 8 for more information.
When the transmitter enclosure is mounted in different orientations (B, C, and D) as outlined in Figure
2-2, the electronics module will need to be rotated to ensure the display can be easily read. The
electronics module consists of the relay board, faceplate (Display/CPU assembly), and main terminal
board. To rotate the electronics module, follow these instructions:
1. Turn off power to transmitter and ensure area is de-classified
2. Remove the enclosure cover
3. Unscrew both the locking knobs and free from two metal standoffs
4. Lift transmitter faceplate from enclosure
5. Disconnect existing wiring
6. Unscrew the two metal standoffs using a ¼”hex tool
7. Carefully remove the electronics module
8. Rotate the electronics module to desired position
9. Align metal standoffs with the mounting holes of the electronics module and enclosure base
Installation Reference Manual
June 2016 MAN-0076, Revision 09
4 Installation
10. Insert metal standoffs in the appropriate mounting holes
11. Tighten metal standoffs with ¼” hex tool to secure electronics module
12. Reconnect wiring
13. Replace faceplate, then fit and hand tighten locking knobs to metal standoffs by turning
clockwise
14. Replace enclosure cover.
Figure 2-3 Rotating electronics module
2.4 Wiring
2.4.1 General requirements
Failure to follow these installation guidelines could result in death or serious injury. Ensure that only
qualified personnel perform the installation.
Electrical shock could cause death or serious injury. Use extreme caution when making contact with
the leads and terminals.
Do not open the transmitter, sensor, or junction box enclosure when in a classified area or when an
explosive atmosphere may be present unless the power to the transmitter has been removed.
Reference Manual Installation
MAN-0076, Revision 09 June 2016
Installation 5
Wiring codes and regulations may vary. Wiring must comply with all applicable regulations relating to
the installation of electrical equipment in a hazardous area and
is the responsibility of the installer. If in
doubt, consult a qualified official before wiring the system.
When separating the sensor from the transmitter, the use of shielded cable is highly recommended
to
meet electromagnetic compatibility (EMC) requi
rements and
to protect against interference caused by
extraneous electrical or electromagnetic noise
. In applications where the wiring is installed in conduit,
the conduit must not be used for wiring to other equipment.
If the 4-20 mA signal is not used, connect a jumper between the 4 20 mA terminal and the common
terminal to allow analog current levels to be monitored at the test jacks on the faceplate.
In applications where wiring is installed in conduit, conduit must not be used for wiring to any other
electrical equipment.
For effective communication, Net Safety limits sensor separation to 2000 feet (600 meters) using 16
AWG wires.
Modbus RS-485 connection 2-wire mode, multipoint serial line available. Up to 247 addresses allowed.
When developing a RS-485 chain of devices, the last device in the chain requires an end of line
termination resistor (120 Ohms).
2.4.2 Terminal connection
When connecting cable wires, use a small screwdriver to gently press down and hold the spring
connector open. Insert the appropriate wire into the open connector hole, releasing the screwdriver to
secure the wire as shown in Figure 2-4.
The connector will accommodate wire sizes between 14 and 20 AWG.
Figure 2-4 Terminal connection
2.4.3 Cable choice and guidelines
Radio frequency interference (RFI) can be caused by nearby electrical devices (e.g. transformers or high
voltage equipment) as well as handheld communication devices/radios, which when activated, may
impede the proper functioning of the transmitter and sensor. Selecting the right instrumentation cable
and making proper grounding connections within the junction box will reduce or eliminate
interference. Visible symptoms of RFI include inconsistent, incorrect, and erratic LEL and ppm readings.
2.4.4 Important wiring guidelines
Gas detection instruments are an important part of a safety alarm and shutdown system. The system is
composed of:
Installation Reference Manual
June 2016 MAN-0076, Revision 09
6 Installation
Detection instruments
Customer connected equipment
Wiring
Net Safety designs and manufactures its detection equipment under rigid quality control management
systems and makes every effort to design for the harshest of industrial environments. The other
components of the system the customer-connected equipment and wiring are also important
contributors to the overall quality and performance of the safety system.
It is important to implement wiring that ensures the reliability and integrity of the safety system. Field
wiring practices and the choice of cable type specified vary from project to project. Poor practices and
choices are often found to be the source of unwanted system disruptions. RFI and electromagnetic
interference (EMI) are usually very powerful disruptive forces in industrial facilities and these forces act
upon the system through the wiring.
The cable used should be a very high quality instrument grade, certified for the application conditions,
consisting of a rugged protective outer jacket, an overall electrical shield of fine braided copper or
metallic foil, and internal pairs or triads of foil shielded copper wire of suitable gauge for the power
conducted over the specified length.
The shields must be electrically continuous from the instrument junction box through other junction
boxes and finally to the connected equipment. The shield must be connected to a suitable ground sink
as specified in the instrument manual in order to protect the system from electrical disturbances.
In general, communication cables and power cables should not run in parallel for any significant length,
and should not be carried in the same cable tray. Through inductance, high currents in power cables
can induce significant ‘noise’ in communication cables running parallel alongside power cables.
2.4.5 Internal ground screw
To access enclosure grounding screw, remove the electronics module by following steps 1 through 7 in
Section 2.3.2.
2.4.6 External ground
In order to ensure proper operation of the sensor, an external earth ground is recommended. Net
Safety recommends that the external ground be connected to the grounding point on the enclosure.
2.4.7 Seals
The use of seals is recommended to further protect the system against water ingression, and
equipment should be installed according to applicable local electrical codes. Seals are especially
recommended for installations that use high-pressure or steam cleaning devices in proximity to the
transmitter.
Waterproof and explosionproof conduit seals are recommended to prevent water accumulation
within the enclosure
Seals should be located as close to the device as possible and not more than18 inches (46 cm) away
Explosionproof installations may require an additional seal where conduit enters a non-hazardous
area; ensure conformity with local wiring codes
When pouring a seal, use a fiber dam to ensure proper formation of the seal. Seals should never be
poured at temperatures below freezing
Reference Manual Installation
MAN-0076, Revision 09 June 2016
Installation 7
The jacket and shielding of the cable should be stripped back to permit the seal to form around the
individual wires. This will prevent air particles and water leakage through the inside of the shield
and into the enclosure
It is recommended that explosionproof drains and conduit breathers be used. In some applications,
changes in temperature and barometric pressure can cause breathing which allows moist air to
enter and circulate inside the conduit. Joints in the conduit system are seldom tight enough to
prevent this breathing
2.4.8 Analog output, isolated supply, non-isolated supply and jumper
configuration
The analog output may be powered from the main instrument power supply or a separate,
independent power supply in which case an isolated wiring configuration is necessary.
To set a Non-isolated or Isolated current output, simply move the Jumpers/shorting jacks (JP3 and JP4)
to either the non-isolated or isolated current position. For non-isolated current output, ensure pins 3 &
2 at JP3 & JP4 location on the main terminal board are jumped (shorted). Factory standard models ship
with jumpers at JP3 & JP4 in the non-isolated current output position.
For Isolated current output, pins 1 & 2 at JP3 & JP4 should be jumped (shorted). Note that JP3 is for
configuring channel 1 and JP4 is for configuring channel 2. Jumpers and pins are located next to the
power and 4-20 output terminals on the main terminal board. See Figure 2-5 for reference.
Figure 2-5 Non-isolated and isolated current jumpers
Installation Reference Manual
June 2016 MAN-0076, Revision 09
8 Installation
Always ensure that JP3 and JP4 jumpers are in the correct position
depending on the current output
configuration chosen
2.4.9 Remotely mounted sensors jumper configuration
Sensor separation from the transmitter may extend up to 2000 feet (600 meters) in which case a
junction box is required.
When mounting sensor remotely (separating sensor from transmitter), Jumpers JP1 and JP2 should be
installed over the pins. Jumpers and pins are located on the main terminal board near the sensor
terminals. JP1 is for channel 1 and JP2 is for channel 2. Refer to Figure 2-6.
Figure 2-6 Separation jumper positions
When separating sensor and transmitter,
install JP1 and JP2 over pins.
2.4.10 Sensor and transmitter terminals
Before wiring, ensure power to the unit is switched off. Connect the sensor wires to the sensor
terminals of the transmitter and connect the transmitter’s power and output terminals to the wiring
leading to the power source/panel. Refer to the configuration tables below for sensor as well as
transmitter power and output terminal designations.
Reference Manual Installation
MAN-0076, Revision 09 June 2016
Installation 9
Transmitter power terminals
Sensor wires
Transmitter sensor board terminal
designation
Transmitter terminal
designation
Function
White
+Vdc (from transmitter)
RST
Remote Reset
Red
SigA
+Vdc (10.5-32Vdc)
Power (+)
Blue
SigB
COM
Power (-)
Black
Com
4-20 (CH1)
Channel #1 current loop output
Green
Earth ground
ISO (CH1)
+Vdc isolated 4-20mA power,
channel #1
4-20 (CH2)
Current loop output channel #2
ISO (CH2)
+Vdc isolated 4-20mA power,
channel #2
Figure 2-7 Sensor wiring and terminal connections
2.4.11 Remote reset
If the alarm relays are configured for latching operation it may be desirable to reset latched alarms from
a remote location. In this case a normally open, momentary pushbutton switch may be connected
across terminals RST and COM.
Installation Reference Manual
June 2016 MAN-0076, Revision 09
10 Installation
Figure 2-8 Remote reset wiring
2.5 Sensor separation/remote mounting of sensor
When it is necessary to mount the sensor remotely (separated from transmitter), by way of junction
box and conduit, it is important that the installer follow the necessary requirements and guidelines
relating to sensor separation and cable selection. See Figure 2-9 for typical remote mounting of sensor.
Also refer to 2.4 for information on wiring guidelines.
When sensors are being mounted remotely, consult the multi-purpose junction box manual
(MAN-0081) for wiring instructions. Always ensure that the transmitter is supplying 10.5 - 32 VDC
across the sensor power terminals (VDC + and COM) of Net Safety junction box (JB-MPD-A/S).
The maximum distance between the sensor and transmitter is limited by the resistance of the
connecting wiring, which is a function of the gauge of the wire being used. For effective
communication, Net Safety limits the separation distance between sensor and transmitter to 2000 feet
(600 meters) using 16 AWG wire. See Section 9 for information on typical wire gauge and resistance.
Figure 2-9 Sensor separation/remote mounting of sensor
Reference Manual Installation
MAN-0076, Revision 09 June 2016
Installation 11
2.5.1 Wiring diagrams
Wiring drawings show general ways in wiring the system for analog signal output. Consult qualified
personnel on specific wiring requirements.
Figure 2-10 Non-isolated terminal connection
Installation Reference Manual
June 2016 MAN-0076, Revision 09
12 Installation
Figure 2-11 Isolated terminal connection
2.6 Installation checklist
Review the following checklist prior to turning the power on to the transmitter after installation has
been completed:
Ensure that the transmitter and sensor are properly and firmly mounted.
Ensure that stopping plugs are securely tightened on any unused conduit entries.
Ensure that the transmitter and sensor are not obstructed; transmitter and sensor are accessible
and target gas is not inhibited from reaching the sensor.
Ensure adherence to applicable local guidelines and requirements on wiring and sealing of
equipment in hazardous and non-hazardous areas.
Ensure that proper shielding and grounding practices are adhered to and local codes are being
followed.
Check system operational voltage and conditions; ensuring that they are within the applicable
specifications of the transmitter and sensor.
Verify wiring at all termination and junction points (transmitter, junction box, and power supply).
Ensure that the transmitter housing cover and sensor cap are secured tightly.
Reference Manual Operation
MAN-0076, Revision 09 June 2016
Operation 13
Section 3: Operation
3.1 Transmitter and faceplate description
Figure 3-1 Faceplate description
3.1.1 Display
The Millennium II is equipped with an Organic LED (OLED) display. It allows the user to see the
concentration of gas present for each individual channel and the various options offered. The display
has a wide temperature rating and will operate well in lowly lit conditions. In order to extend the life of
the display, a screen saver is enabled if the menu is not in use. To exit the screen saver mode, move the
magnet close to any of the three Reed switch locations (8 o’clock, 6 o’clock or 4 o’clock position).
3.1.2 Status LED
The Status LED can be solid red or green, or flashing red or green to indicate various states of the
transmitter and sensor.
Operation Reference Manual
June 2016 MAN-0076, Revision 09
14 Operation
3.1.3 Current loop measurement (test jacks)
Do not open the transmitter, sensor, or junction box enclosure when in a classified area or when an
explosive atmosphere may be present unless the power to the transmitter has been removed.
For convenience, a pair of test jacks for each analog output is provided on the front face of the display
module. Attach ammeter probes to these jacks to check loop current without opening the circuit to
insert the meter.
3.1.4 Menu buttons and access
The main menu can be accessed in two ways: Intrusive (opening the enclosure and pressing menu
buttons) and non-intrusive (keeping the enclosure closed and using the magnet and reed switches).
3.1.4.1 Intrusive access
The menu buttons provide access to the Millennium II’s Main Menu options allowing the user to review
and configure existing options under sub menus and perform calibration. There are three visible main
menu buttons that are located directly under the display screen. They are designated ‘1’, ‘2’ and ‘3’.
3.1.4.2 Non-Intrusive Access/Magnetic Reed switch Access
Accessing the main menu and making a selection can also be done via an attached magnet and Reed
switches.
The Reed switches are located in the 8 o’ clock, 6 o’ clock and 4 o’ clock positions on the face plate and
indicated by horse shoe shape print magnets. To select a Reed switch, place and hold the magnet close
to the transmitter enclosure at 8, 6 or 4 o’clock position.
Menu buttons and reed switches provide the same functions. The term ‘switch’ is used throughout to
represent menu buttons and reed sw
itches.
3.2 Transmitter power up
After power is applied to the transmitter, a warm-up routine will begin, the duration of which depends
on the sensor type. The display will indicate the sensor warming up and the Status LED will flash slow
red and the current output will be 3.0 mA. After the warm-up period, the transmitter will enter normal
operation and the screen will display: “Channel 1 00 %LEL (or ppm), Channel 2 00 %LEL (or ppm).” For
dual channel models either channel can be disabled if not in use. If a channel is disabled, the screen will
display “Disabled” for that particular channel. The enabled channel analog output will be to 4.0 mA
during normal operation.
A slow flash is defined as the Status LED being ‘ON’ for 50 milliseconds and ‘OFF’ for 1 second, while a
fast flash is the LED being ‘ON’ for 250 milliseconds and ‘OFF’ for 250 milliseconds and a very fast flash
is the LED ‘ON’ for 50 milliseconds and ‘OFF’ for 50 milliseconds.
Reference Manual Programming
MAN-0076, Revision 09 June 2016
Programming 15
Section 4: Programming
4.1 Menu options
The main menu provides access to various functional settings/options, as seen in the list below. Each
menu option has a submenu, where configuration is completed.
Calibrate Sensor
Enable/Disable Channels
Set Alarm Level
Set Relay Option (available on relay models)
Relay Assignment (available on relay models)
Alarm Mode setting
Select Display Language
Modbus Setup (available on Modbus models)
Setup Current Date
Setup Current Time
View Events Log
Manual Reset
Self-test Relay
Sensor Upper Limit (Range)
Select Gas Type
Cal Gas Value
Serial Number and Firmware version
Exit
4.2 Navigating main menu
Navigation through the menu options is done by activating menu button 1 or 2. The same function is
provided using the magnet to select Reed switch 1 (indicated by printed magnet in the 8’ o clock
position on the faceplate) or Reed switch 2 (indicated by printed magnet in the 6’ o clock position on
the faceplate).
1. Enter the main menu, either intrusive or non-intrusive (using the magnet), by
selecting/activating any button then select “yes” by using switch 1.
2. The message “Calibrate Sensor?” will be displayed.
3. Activate up-down buttons (switch 1) or (switch 2) to scroll/navigate through main menu options.
4. Select/activate the enter key (switch 3) to display sub menu.
5. To exit the main menu, continue using the navigation keys (up-down keys) and select “Exit” with
enter key at each menu stage (sub menu and main menu).
6. The main menu will be exited automatically if no option is selected; it takes fifty (50) seconds to
exit to each of the previous options or stage entered. If left untouched, this continues until the
main menu is fully exited.
Programming Reference Manual
June 2016 MAN-0076, Revision 09
16 Programming
Figure 4-1 Programming flowchart
Enter Main Menu?
Calibrate Sensor?
YES
NO
1
Enable/Disable
Channels?
Set Alarm Level?
Set Relay Option?
Relay Assignment?
Alarm Mode Setting
1
2
1
2
1
2
1
2
1
2
Select Display
Language?
Modbus Setup
Setup Current Date?
Setup Current Time?
View Events Log
Manual Reset?
1
2
1
2
1
2
1
2
1
2
Selftest Relay?
Sensor Upper Limit
(Range)
Select Gas Type
Cal Gas Value
Serial Number and
Firmware Version
Exit
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
Reference Manual Programming
MAN-0076, Revision 09 June 2016
Programming 17
4.3 Calibrate sensor
This menu function allows the user to perform a calibration on the connected sensor. Refer to Section
5 for the calibration procedure.
4.4 Enable/Disable channels
This option allows the Millennium II Transmitter channels to be enabled or disabled. The default value is
channel 1 (CH1) enabled for single sensor models (model M21) while channel 2 (CH2) is permanently
disabled. Both channels are enabled for two sensor models (model M22).
1. Enter the main menu by selecting/activating any key to get the “enter main menu” prompt, then
activate switch 1 to select “yes”.
2. Select the down arrow key (switch 2) with the magnet, and scroll to “Enable/Disable Channel?
3. Activate the enter key (switch 3) to enter the option. The sub menu options: ‘CH 1 Enabled’ will
be highlighted.
4. To disable a channel 1, Activate the enter key (switch 3). “CH1 disabled” will now be highlighted /
displayed.
5. To disable channel 2, highlight ‘CH2 Enabled’ use switch 2, then activate the enter key (switch 3)
to configure to ‘CH2 disabled’.
6. To exit the main menu, select “Exit” with enter key at each menu stage (sub menu and main
menu).
4.5 Set alarm level
This option enables the channel low and high alarm levels to be viewed and set-up. Alarm levels (points)
for each channel are user determined. Alarm Point 1 and Point 2 for channel 1 does not relate to Alarm
Point 1 and Point 2 for channel 2. The channel 2 selection is only available on M22 models.
1. Enter the main menu by selecting/activating any key to get the “enter main menu” prompt, then
activate switch 1 to select “yes”.
2. Activate the up key (switch 1) or the down key (switch 2) until “Set Alarm Level?” is highlighted /
displayed.
3. Activate switch 3 to enter the “Set Alarm Level” option. Sub menu options ‘Set CH1 Level’, ‘Set
CH2 Level’ and ‘Exit’ will be displayed. ‘Set CH1 Level’ being highlighted.
4. To view channel 1 alarm points, activate switch 3. ‘CH1 Point 1’ and ‘CH1 Point 2’ will be
displayed.
5. To view channel 2 alarm points use switch 2, at step 3, highlight ‘Set CH2 Level’, then activate
switch 3. ‘CH2 Point 1’ and ‘CH2 Point 2’ will be displayed.
6. To configure channel 1 alarm levels (Point 1 or Point 2), after step 4, use switch 3 to select CH 1
Point 1 (already highlighted) then proceed to step 8, or highlight CH1 Point 2 using switch 2 ,
then activate switch 3 and proceed to step 8.
7. To configure channel 2 alarm levels (Point 1 or Point 2), after step 5, use switch 3 to select CH2
Point 1 then proceed to step 8, or use switch 2 to highlight CH2 Point 2, then activate switch 3
to make a selection. Proceed to step 8.
Programming Reference Manual
June 2016 MAN-0076, Revision 09
18 Programming
8. Use switch 1 to increase the existing values representing previously set alarm levels/points and
switch 2 to highlight and scroll across values.
9. After setting desired alarm points, select “Exit” at each menu stage (sub menu and main menu).
10. Apply test gas to confirm alarm level settings.
Alarm Point 1 and Alarm Point 2 are values completely under the control of the user. If the user
chooses, Alarm Point 1 can be assigned a value corresponding to a high alarm condition and Alarm
Point 2 assigned a value corresponding to a low alarm condition. To avoid confusion however, most
users may want to assign Alarm Point 1 as the low alarm condition and Alarm point 2 as the high alarm
condition.
4.6 Set relay option
This option allows the Alarm relay coils to be configured as energized or de-energized and latching or
non-latching.
Fault relay: The Fault relay is Energized and Non-Latching. This relay is not configurable.
Alarm relays 1, 2 and 3: Factory set as De-energized and Non-Latching. These relays are
configurable.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2) until, “Set Relay Options?” is displayed.
3. Activate the enter key (switch 3) to enter the option. The sub menu options are: ‘Fault relay’,
‘Alarm relay 1’, ‘Alarm relay 2’, ‘Alarm relay 3’.
4. Activate the down key (switch 2) or up key (switch 1) to highlight configurable Alarm relays
(‘Alarm relay 1’, ‘Alarm relay 2’, ‘Alarm relay 3’).
5. Activate the enter key (switch 3) to configure the desired Alarm relay.
6. ‘Norm. Energized’ or ‘Norm.De-Energized’ will be highlighted at the top of the display screen. To
change the Energized or De-Energized setting, activate the enter key (switch 3).
7. To change the Latching or Non-Latching setting, activate the down key (switch 2) to highlight
‘Latching’ or ‘Non- Latching’, then activate the enter key (switch 3).
8. Once the desired relay settings have been made, select “Exit” at each menu stage (sub menu and
main menu).
4.7 Relay assignment
This option allows the transmitter two (2) channels (with alarm levels/points) to be configured under
the three (3) Alarm relays. When configuring under sub menu Alarm relay 1, “RL1:CH1 (Point 1, Point
2, Disabled)” and “RL1: CH2 (Point 1, Point 2, Disabled)” is displayed. Under sub menu Alarm relay 2,
“RL2:CH1 (Point 1, Point 2, Disabled)” and “RL2:CH2 (Point 1, Point 2, Disabled)” is displayed, and
under sub menu Alarm relay 3, “RL3:CH1 (Point 1, Point 2, Disabled)” and “RL3:CH2 (Point 1, Point 2,
Disabled)”is displayed.
RL1, RL2 and RL3 represents Alarm relays 1, 2 and 3. CH1 and CH2 represent channel1 and channel 2.
Point 1 and Point 2 are Alarm level 1 and Alarm level 2. Alarm levels (points) are user determined and
are unique to the specific channel.
Reference Manual Programming
MAN-0076, Revision 09 June 2016
Programming 19
Prior to assigning relays, configure the alarm levels (points). See Section ‘4.2.4 Viewing and setting
alarm levels (points)’, and then follow the steps and example below to configure the Alarm relays. Also
see Table 3, Example and Table 4.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2) until “Relay Assignment?” is displayed.
3. Activate the enter key (switch 3) to enter the option. The sub menu: ‘Alarm Relay 1’, ‘Alarm Relay
2’, ‘Alarm Relay 3’ as well as ‘Exit’ will be displayed.
4. Choose the Alarm relay (Alarm relay 1, Alarm relay 2, Alarm relay 3) for configuration, by using
the up- down arrow keys.
5. Activate the enter key (switch 3) to make the selection. The relay (RL) and channel (CH) with
alarm level setting will be highlighted. The alarm level settings available are: Point 1, Point 2, and
Disabled.
6. Under the specific relay with channel, activate the enter key (switch 3) to choose the appropriate
setting. See Table below.
Relays and assignment options
Channel and alarm
points(levels)
ALARM RELAY 1 (RL1) with
channel # and Alarm points
(levels)
ALARM RELAY 2 (RL2) with
channel # and Alarm points
(levels)
ALARM RELAY 3 (RL3) with
channel # and Alarm points
(levels)
CH1
POINT 1= Alarm level 1
POINT 2= Alarm level 2
RL1:CH1
Point 1/Point 2/Disabled
RL2:CH1
Point 1/Point 2/Disabled
RL3:CH1
Point 1/Point 2/Disabled
CH2
POINT 1= Alarm level 1
POINT 2= Alarm level 2
RL1:CH2
Point 1/ Point 2/Disabled
RL2:CH2
Point 1/ Point 2/Disabled
RL3:CH2
Point 1/Point 2/Disabled
7. Once the appropriate settings are chosen, use the up or down arrow key (switch 1) or (switch 2)
and switch 3 to exit.
Example: LEL combustible sensor connected to channel 1 and H2S sensor connected to channel 2.
1. Set Alarm Levels (points): Setup alarm levels for each channel, e.g. Channel 1 point 1 = 20% LEL,
Channel 1 point 2 = 40% LEL, Channel 2 point 1 = 10 ppm, and Channel 2 point 2 = 20 ppm. Refer
to Section ‘4.2.4: Viewing and setting alarm levels (points)’ when setting alarm levels.
2. Set Relay Options: Each alarm relay can be set up for energized or de-energized and latching or
non-latching. Configure alarm relays options as desired. See ‘4.2.5 Setting Relay options’.
3. Relay Assignment: There are (3) alarm relays and (2) channels. Assign alarm relays to channels as
desired, e.g.
o Alarm relay 1 assigned to Channel 1 Point 1 (20% LEL)
o Alarm relay 2 assigned to Channel 2 Point 1 (10 ppm)
o Alarm relay 3 assigned to Channel 1 Point 2 (40% LEL)
o Alarm relay 3 assigned to Channel 2 Point 2 (20 ppm)
Programming Reference Manual
June 2016 MAN-0076, Revision 09
20 Programming
4.8 Alarm mode setting
Only used on Oxygen (ST341) sensors
This option is available for detecting oxygen levels. The user is allowed to set up two Alarm points/level
(normal oxygen level is 20.9 %) under three available Alarm Modes. These Alarm Modes are: Above-
Above, Below-Below and Below-Above. The Alarm Mode chosen by the user depends on the particular
application/operation. If surrounding air is to be used for calibration, ensure that no contaminants are
present. Refer to the Oxygen sensor manual for detailed information.
4.9 Select display language
This option allows the display language to be selected. The default language is English. There are also
options for Spanish, French, and Portuguese.
1. Enter the main menu by activating any key to get the “enter main menu” prompt then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2) until “Select Display Language?” is
displayed.
3. Activate the enter key (switch 3). The default language, ‘English’, will be displayed.
4. Locate other languages by activating the enter key (switch 3).
5. Once the desired language is displayed, select “Exit” at each menu stage (sub menu and main
menu).
4.10 Modbus Setup
This option enables the following Modbus parameters to be set:
Addressing: From 001 (default) to 247.
Baud Rate: 02400 bps, 04800 bps, 09600 bps (default), 19200 bps, and 57600 bps.
Frame Format: EVEN Parity (default), ODD Parity, NO Parity.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Select the up arrow key (switch 1) or down arrow key (switch 2) until “Modbus Setup” option is
displayed.
3. Activate the enter key (switch 3) to display ‘slave address’ (default address: 001).
4. Use the up key (switch 1) to increase the address and the down key (switch 2) to decrease the
value. The value range is 001-247.
5. Activate the enter key (switch 3) when the desired value is displayed.
6. After setting the Slave Address, exit to this sub menu option using switch 3.
7. Activate the down key (switch 2) to highlight ‘baud rate’, then activate the enter key (switch 3)
to display the current baud rate.
8. Use the up key (switch 1) to increase the baud rate and the down key (switch 2) to decrease it.
Reference Manual Programming
MAN-0076, Revision 09 June 2016
Programming 21
9. Activate the enter key (switch 3) when the desired value is displayed.
10. After setting the baud rate, exit this sub menu option using switch 3, and then activate the down
arrow key (switch 2) to highlight ‘Parity Bit’.
11. Activate switch 3, then activate the up key (switch 2), or the down key (switch 1) to choose a
value.
12. Activate the exit key (switch 3) when the desired value is displayed, then select “Exit” at each
menu stage (sub menu and main menu).
4.11 Setup current date
This option allows you to set the current date for event logging. The default date is set at the factory in
Mountain Time.
1. Enter the main menu by selecting/activating any key to get the “enter main menu” prompt, then
activate switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2) until “Setup Current Date?” option is
displayed.
3. Activate the enter key (switch 3) to display the sub menu option ‘year’, ‘month’, ‘day’.
4. Activate the up key (switch 1) to change the current year/month/day settings and switch 2 to
cycle across ‘year’, ‘month’, ‘day’ values and ‘OK’.
5. After desired setting are made, navigate to “OK?” and activate the enter key (switch 3) to
confirm. To exit main menu, select “Exit” at each menu stage (sub menu and main menu).
4.12 Setup current time
This option allows you to set the current time for event logging. The default time is in Mountain Time.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down (switch 2) until “Setup Current Time?” option is displayed.
3. Activate the enter key (switch 3) to display the sub menu: hour’, ‘minute’, ‘seconds’.
4. Activate the up arrow key (switch 1) to change the current hour/minute/second settings, then
use switch 2 to cycle across ‘hour’, ‘minute’, ‘seconds’ values and ‘OK’.
5. After desired settings are made, navigate to ‘OK’ and activate the enter key (switch 3) to confirm.
To exit main menu, select “Exit” at each menu stage (sub menu and main menu).
4.13 View events log
The Millennium II Transmitter has the ability to store up to 980 events. Events can be viewed by
navigating through this menu option. The most recent events are shown first.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Navigate through the main menu using switch1 or switch 2 until “View Event Log?” is displayed.
Programming Reference Manual
June 2016 MAN-0076, Revision 09
22 Programming
3. Activate the enter key (switch 3) to display the sub menu. The most recent event will be
displayed.
4. Select the up arrow key (switch 1) and the down arrow key (switch 2) to toggle through all past
events.
5. After viewing, select “Exit” at each menu stage (sub menu and main menu).
The on-screen Events Format/host includes:
Channel Number: CH1, CH2, or transmitter: ML2. Events that occurred under these formats will be
logged.
Event Types: There are a total of 11 events that are stored and displayed. See table below for a list
of the events, and how they are displayed on the Millennium II screen.
Date and Time: Each event is date and time stamped.
Event Types
Display on Screen
Events Format /host
Power up or Reset
Power UP / RST
ML2
Communication Fault
Communication Err
CH1 or CH2
High Level Alarm
High Alarm
CH1 or CH2
Low Level Alarm
Low Alarm
CH1 or CH2
Calibration Completed
Cal Complete
CH1 or CH2
Calibration Zero Failed
Cal Zero fail
CH1 or CH2
Calibration Span Fail
Cal Span Fail
CH1 or CH2
Calibration Aborted
Cal Abort
CH1 or CH2
Sensor Fail
Sensor Fail
CH1 or CH2
Channel Enabled
Enabled
CH1 or CH2
Channel Disabled
Disabled
CH1 or CH2
4.14 Manual reset
A Manual Reset is required after a calibration failure or to clear a latched Alarm relay. When a manual
reset is done, the transmitter will return to normal operation.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2) until “Manual Reset?” option is displayed.
3. Activate the enter key (switch 3) to display the sub menu: ‘Initiate Reset’.
4. Select “yes” using switch 1 to reset.
4.15 Self-test relay
When activating the self-test relay function, ensure all external equipment is disabled to prevent
Reference Manual Programming
MAN-0076, Revision 09 June 2016
Programming 23
unwanted alarm activation. Enable external equipment once testing is completed.
The Self-test relay option continuously turns relays on and off to ensure that they are functioning
properly. The Fault Relay is tested first, automatically followed by tests on Relay 1, 2, and 3. After the
relays have been tested, “Relay Test Complete” will be displayed. See steps to initiate relay self-test
below.
Proper functioning electromechanical relays have a clicking sound during this test.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up arrow key (switch 1) or down arrow key (switch 2) until Self-test Relay?” option
is displayed.
3. Activate the enter key (switch 3) to display the sub menu: ‘Self-Test Relay. Caution, will trip
alarm’.
4. Select “yes” using switch 1. ‘Ensure alarm response items are disconnected’ will be displayed.
5. Ensure all external alarm devices are de-activated, and then select “yes” using switch 1.
6. After test is successfully completed, select “Exit”.
4.16 Sensor upper limit (range)
This option is used to set the upper limit (range) of the gas being detected. The upper limit will vary
depending on the sensor used and may not be selectable for all sensors.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2), until “Sensor Upper Limit (Range)”option is
displayed.
3. Activate the enter key (switch 3) to display the sub menu: ‘CH1: range’, ‘CH2: range’.
4. Select the channel (sensor) to be configured and adjust the sensor’s range using the up-down
arrow keys (switch 1) or (switch 2). The specific sensor provides the upper limits/ranges.
If no selections appear when activating the up/down arrow keys at this stage, the specific sensor
only has one upper limit/range, which cannot be altered.
5. Activate the enter key (switch 3) when the desired upper limit/range is reached.
6. To exit, select “Exit” at each menu stage (sub menu and main menu).
4.17 Select gas type
“Select Gas Type” option allows the user to select a particular target gas and/or Correction (“K”) Factor
in the case of Catalytic Bead sensors (model SC310) or choose the type of LEL gas (gas curve) in the case
of IR (model SC311) sensors. See specific sensor manual in relation to this menu option.
Programming Reference Manual
June 2016 MAN-0076, Revision 09
24 Programming
4.18 Calibration gas value
This option allows the user to select the calibration gas value in the transmitter main menu. Although it
is recommended that 50% span gas should be used for calibration, for some sensors, the transmitter
will allow tolerance/flexibility in the calibration gas available; 10% to 60% span gas allowed for some
sensor types. See specific sensor manual.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2), until “Cal. Gas value” option is displayed.
3. Activate the enter key (switch 3). Channel1 and channel 2 existing calibration gas values will be
displayed in three numeric groups: ‘hundreds’, ‘tens’, and ‘ones’. For example: 0 5 0 indicates a
calibration gas value of 50% span.
4. Highlight the required channel with calibration gas value using the navigation keys (switch1) or
(switch 2), then select using switch 3. Switch 1 is used to increase /change a value in each
numeric group, while switch 2 is used to cycle across the numeric groups.
5. To exit, select “Exit” at each menu stage (sub menu and main menu).
4.19 Serial number and firmware version
This option is used when the serial number or firmware version of the Millennium II Transmitter is
required.
1. Enter the main menu by activating any key to get the “enter main menu” prompt, then activate
switch 1 to select “yes”.
2. Activate the up key (switch 1) or down key (switch 2), until “Serial Number and Firmware
Version” option is displayed.
3. Activate the enter key (switch 3). The firmware version and serial number will be displayed.
4. To exit, select “Exit” at each menu stage (sub menu and main menu).
4.20 Exit
This option allows the user to exit the menu system and return to the normal operation mode.
Reference Manual Calibration procedure
MAN-0076, Revision 09 June 2016
Calibration procedure 25
Section 5: Calibration procedure
5.1 Full calibration procedure
Prior to attempting calibration read and understand the calibration procedure below. Also see Figure
5-1 for additional reference.
The following calibration procedure should be followed to ensure an accurate correlation between the
output signal and the gas concentration. For accurate performance, the Millennium II is calibrated
using 50% span gas. The transmitter will however, allow some flexibility in the use of calibration gas
with some sensors; calibration gas outside of 50 % span (10% - 60% span gas) will be allowed on specific
sensor models (see specific sensor manual for details). The calibration gas value can be chosen by
selecting it under “cal. gas value” in the main menu. A full calibration will take approximately 5 minutes
to complete.
Air movement, drafts and wind can cause dilution of calibration gas flow which can cause an erroneous
calibration and inaccurate performance. To avoid this, use a Calibration Cup attached to the bottom of
the sensor. The cup doesn’t have to be removed for normal operation. When the cup is in place, inject
calibration gas at a rate of 0.5 1.0 liter per minute.
Ensure the transmitter is functioning properly as indicated by the status LED and current output.
1. Enter the main menu by selecting/activating any key to get the “enter main menu” prompt, then
activate switch 1 to select “yes”.
2. When “Calibrate Sensor?” is displayed, activate the enter key (switch 3).
3. When “Calibrate Sensor #1?” is highlighted, activate the enter key (switch 3) if this is the sensor
to be calibrated.
4. If sensor #2 is to be calibrated, select the down arrow key (switch 2) to scroll to “Calibrate Sensor
#2?”
5. Select the desired sensor to be calibrated (1 or 2) by activating the enter key (switch 3).
6. Select “YES” with switch 1 to confirm the selection, and then apply clean air (zero gas) from
canister when “Apply Clean Air” is displayed. Ensure no contaminant gases are around if
ambient air is being used.
7. Select “Z & Span” using switch 1 for normal (full) calibration. “Setting zero” will be displayed as
the sensor is being zeroed.
8. Apply 50% calibration gas (* or % cal. gas value chosen) when prompted.
9. The display will show “Spanning” with the gas value (%LEL or PPM depending on the sensor) as
the gas is detected.
10. Remove the calibration gas when “Remove Cal Gas” is displayed.
11. “Cal Complete” will be displayed when calibration is complete.
12. Apply zero gas (clean air) to purge system. This is particularly important when using long tubing.
Calibration procedure Reference Manual
June 2016 MAN-0076, Revision 09
26 Calibration procedure
The “Zero” calibration option is selected if the sensor is only being zeroed (this not a complete
calibration)
It does not require the application of span gas, as only the sensor’s zero point is adjusted. Ensure that
no
contaminants are present, if the surrounding air is to be used for Zeroing. If Zero calibration is
needed, at step 7 above, select ‘Zero’ using switch 3).
Reference Manual Calibration procedure
MAN-0076, Revision 09 June 2016
Calibration procedure 27
Figure 5-1 Calibration flowchart
Calibrate Sensor?
Enter Main Menu?
YES
NO
1
Calibrate Sensor #1
Calibrate Sensor #2
Exit
Calibrate Sensor #1?
Apply Clean Air
3
3
3
1
3
Remove air canister (if
used) - Zero calibration
complete, full calibration
continue to next block
CH 1: Apply 50% span gas
CH 1 Spanning
LEL/ppm reading
Remove Calibration Gas
Calibration Complete
Note: Some sensor types can
be calibrated with 10% to
60% span calibration gas,
refer to the applicable sensor
manual
Span Failed
Perform a manual reset
and repeat calibration
procedure
Purge calibration lines
with clean air from
canister, then remove air
canister
YES
No
Z&SPAN Zero
Full
Calibration
Zero
Calibration
Zero
Successful?
Zero Failed
Perform a manual reset
and repeat calibration
procedure
No
Yes
Span
Successful
?
Yes
No
Note: Calibration process is
identical for Channel #2
Calibration procedure Reference Manual
June 2016 MAN-0076, Revision 09
28 Calibration procedure
5.2 Status conditions during calibration
Condition
Current output
LED indication
Red
Green
Relay outputs
Fault
Alarm
Sensor is zeroing itself
3 mA
Off
Solid
Normal state
Normal state
Sensor is waiting until it detects application
of calibration gas
3.3 mA
Very fast
Off
Normal state
Normal state
Sensor waits until gas level stabilizes, then
begins spanning
3.3 mA
Very fast
Off
Normal state
Normal state
Spanning is complete, user asked to remove
calibration gas
3.6 mA
Off
Solid
Normal state
Normal state
Displayed for four (4) seconds once gas
concentration drops to 3% full-scale after
user asked to remove calibration gas
3.6 mA
Off
Solid
Normal state
Normal state
Signal was too unstable to acquire an
accurate zero after ninety (90) seconds
3.0/3.3
Solid
Solid
Fault state
Normal state
Displayed for four (4) seconds if the
calibration gas was remove prematurely or if
a ninety (90) second time limit has elapsed
and the signal was too unstable to acquire
accurate data
3.0/3.3
Solid
Solid
Fault state
Normal state
Reference Manual Monitoring and outputs
MAN-0076, Revision 09 June 2016
Monitoring and outputs 29
Section 6: Monitoring and outputs
6.1 Analog 4-20mA
A 4-20 mA current output is used to transmit the transmitter and sensor status and fault codes to other
devices. This output can be wired for isolated or non-isolated operation. A 4.0 mA output indicates
normal operation; the transmitter’s output current range is 4.0 - 20.0 mA. For a full list of output
current values and what they indicate, see 6.5.
The Millennium II transmitters offer a variable 4-20 mA analog output. This output will provide gas
concentration through the 4-20 mA range, where 4 mA equals zero gas concentration and 20 mA
equals the high range of the sensor (e.g. 100% LEL or 100 ppm). Other conditions such as faults and
calibration notifications (e.g. apply gas) are indicated in the 0-3.9 mA range. Faults are indicated at
either 0 mA or 2.5 mA.
To differentiate between conditions resulting in 2.5 mA, view the Event Log. See Event Log
menu
option.
6.2 HART Communication (Optional)
The HART protocol is a powerful communication technology enabling users to exploit the full
functionality of the Millennium II Transmitter. The HART communication option is only available with
the single channel version of the Millennium II Transmitter. The Millennium II Transmitter is a generic
device that will work with other universal communication devices.
The HART Communicator may be connected to the single channel Analog/HART model Millennium II
Transmitter via the HART Port connector (HPT-001) which provides the necessary interface for
communication. The HART Port connector is fitted to one of the ¾” NPT conduit entries and its
communication wires fitted to the HART Pins located at J5 near the ribbon cable on the underside of the
display/CPU assembly. The HART Communicator probe wires (leads) are then connected to HART Port
connector contact points. HART Communication may also be done remotely using a designated Net
Safety Multipurpose Junction box (JB-MPH-A/S). See the HART Port connector manual (MAN-0083) for
more details. When remote HART Communication is being done, ensure the HART jumper is connected
across pins at J5 near ribbon cable on display/CPU assembly. By default the jumper is connected across
pins. The HART Communicator can be connected directly in the 4-20 mA signal wiring across a 250 -
600 Ohm resistor. Do not install resistor within transmitter. See Figure 6-1.
Monitoring and outputs Reference Manual
June 2016 MAN-0076, Revision 09
30 Monitoring and outputs
Figure 6-1 Analog/HART wiring
6.3 Relays (Optional)
Optional electromechanical relays have Form-C SPDT contacts rated 5 Amps at 30 VDC/ 250 VAC.
There are four physical relays; one Fault and three Alarm relays. These relays have Normally Open and
Normally Closed contacts at the output terminals.
6.3.1 Alarm relay(s)
The Millennium II transmitters can be ordered with three (3) programmable alarm relays. These relays
will change state from their non-alarm state to an alarm state when gas concentrations, as read by the
sensor, reach the programmed alarm points set in the transmitter.
The alarm relays can be programmed to change states on alarm point #1 or alarm point #2 for either
channel. They can also be programmed to be energized or de-energized under normal conditions, and
then either latching or non-latching.
6.3.2 Fault relay
Millennium II transmitters and sensors complete continual checks for situations that may prevent the
transmitter and sensor from providing an expected response to ambient conditions and records these
as a fault condition in the message log and the output(s) of the transmitter. When a system fault is
detected, the Red Status LED will flash fast (250 milliseconds on, 250 milliseconds off), the analog
output will output a 2.5 mA signal, and the fault relay will change states (de-energize to provide a fault
condition).
Reference Manual Monitoring and outputs
MAN-0076, Revision 09 June 2016
Monitoring and outputs 31
The fault relay is normally energized when no fault conditions are present and is set up for non-latching.
The operation of the fault relay is not configurable.
The Millennium II transmitter provides various fault conditions to indicate that the transmitter or
connected sensor(s) are not operating as expected. These fault conditions will override any alarm
conditions because the sensor may be unable to detect a gas exposure reliably. Examples of fault
conditions can range from no detection due to memory or communication errors and sensor failure.
Other faults can provide unreliable detection due to sensor drift or sensor nearing the end of its life.
When a Millennium II transmitter is in fault mode, immediate action should be taken to determine the
source and correct the fault condition.
The fault relay output is not commonly used to imitate an automatic shutdown. The fault output
indicates a potential problem with the transmitter not an alarm condition.
6.4 RS-485 Modbus RTU (Optional)
Optional RS-485 Modbus RTU protocol is available. The tables on the following pages give the detailed
Modbus registers and the bit values for the transmitter register.
The Millennium II Transmitter utilizes 2- wire Modbus RS-485 multi serial mode. This Modbus solution
implements a 2-wire electrical interface in accordance with the EIA/TIA-485 standards. For this
MODBUS configuration, it is important that a third wire be used for connecting all the ‘Common
(COM) in the chain. Also a 120 Ohm line termination is required for the last device in the line. See Figure
6-2. The Instrument Engineer is responsible for calculating line length and adhering to Modbus
protocols.
Figure 6-2 Two-wire Modbus configuration
Monitoring and outputs Reference Manual
June 2016 MAN-0076, Revision 09
32 Monitoring and outputs
6.4.1 Modbus registers
Reg#
Meaning
Readable
Writeable
40001
Concentration value as calculated by sensor (RTUsensor_out), Channel 1
X
40002
Sensor status (RTUsensor_stat), Channel 1
X
40003
Temperature of sensor element housing in Kelvin (RTU temperature), Channel 1
X
40004
RFU, Channel 1, always read as 0x0000
X
40005
RFU, Channel 1, always read as 0x0000
X
40006
Concentration value as calculated by sensor (RTUsensor_out), Channel 2
X
40007
Sensor status (RTUsensor_stat), Channel 2
X
40008
Temperature of sensor element housing in Kelvin (RTU temperature), Channel 2
X
40009
RFU, Channel 2, always read as 0x0000
X
40010
RFU, Channel 2, always read as 0x0000
X
**40021
Transmitter Status
X
40091
Initialize Quick calibration, channel 1 to 2
X
X
40092
Initialize Normal Calibration, channel 1 to 2
X
X
NOTE: Alarm points can be set up through Modbus registers 40093 to 40096
40093
Channel 1 high alarm limit
X
X
40094
Channel 1 low alarm limit
X
X
40095
Channel 2 high alarm limit
X
X
40096
Channel 2 low alarm limit
X
X
40101
Reset latch relays
X
RFU Reserved for future use
** The transmitter Status register (Register 40021) is a bit flag register. The following table shows the detailed meaning
of each bit in the register.
Bit
Meaning
0x0000
Normal Sensor operation no fault or alarm has happened
0x0001
Channel 1 sensor fault status tripped. Communication Fault, Calibration Fault, etc
0x0002
Channel 1 Low Alarm tripped
0x0004
Channel 1 High Alarm tripped
0x0008
Channel 2 sensor fault status tripped. Communication Fault, Calibration Fault, etc
0x0010
Channel 2 Low Alarm tripped
0x0020
Channel 2 High Alarm tripped
0x0040
Channel 1 needs Calibration
0x0080
Channel 2 needs Calibration
Reference Manual Monitoring and outputs
MAN-0076, Revision 09 June 2016
Monitoring and outputs 33
6.5 Transmitter output operation
The following table outlines the operation of the outputs of the Millennium II transmitter under
different conditions. These outputs include the analog output, LED indications, and the relay outputs.
For the outputs’ status, refer to the descriptions below the table.
Condition
Current output
LED indication
Red
Green
Relay outputs
Fault
Alarm
No gas present
4 mA
Off
Slow
Normal state
Normal state
Gas present, concentration below alarm
points
4-20 mA depending
on gas concentration
Slow
Off
Normal state
Normal state
Gas present, concentration at or above
alarm points
4-20 mA depending
on gas concentration
Slow
Off
Normal state
Alarm state
Fault condition present, no gas present
2.5 mA
Very fast
Off
Fault state
Normal state
Fault condition present, gas present
2.5 mA
Very fast
Off
Fault state
Normal state
Fault condition present, gas above alarm
points
2.5 mA
Very fast
Off
Fault state
Normal state
Electrochemical XChem sensors only:
Sensor end of life condition present, gas
above or below alarm points
2.5 mA for 10
seconds, 4-20 mA for
50 seconds
Very fast
Off
Fault state for 5
seconds,
normal state for
55 seconds
Normal state
Fault relay:
Fault state means that the relay is in the de-energized state. Normal state means that the
relay is in the energized state.
LED indications:
Flash rates are outlined in the following table:
Flash description
On
Off
Slow
50 milliseconds
1 second
Fast
250 milliseconds
250 milliseconds
Very fast
50 milliseconds
50 milliseconds
Alarm relay(s):
Alarm state means that if the relay is programmed for normally de-energized, the relay
will energize to alarm; if the relay is programmed for normally energized, the relay will de-energize to
alarm. Normal state is what state that the relay is programmed for (e.g. normally energized or normally
de-energized).
6.6 Fault monitoring
Self-testing circuitry continuously checks for problems that could prevent proper response. When
power is applied to the Millennium II Transmitter, a microcontroller automatically tests the system to
ensure that it is functioning properly. During normal operation, it continuously monitors the signal
from the internal sensor source. In addition, a “watchdog” timer is maintained to ensure the program is
running correctly. When a system fault is detected, the Status LED will have a Red fast flash and the
fault signal will output a 2.5 mA signal. The transmitter’s event log may be viewed in order to
distinguish the fault condition. Refer to the Event Log menu option.
Monitoring and outputs Reference Manual
June 2016 MAN-0076, Revision 09
34 Monitoring and outputs
The fault detection circuitry does not monitor the operation of external response equipment or
external wiring to the transmitter. It is important that external equipment and wiring be checked
periodically to ensure they are operational.
6.7 Fault conditions
Fault conditions will override any alarm conditions because the sensor may be unable to detect a gas
exposure reliably, as such, the alarm relay will not provide an output.
Fault conditions provided by an instrumentation device are critical indicators that the device is not
operating as expected; therefore, when a fault condition is present, immediate attention to that fault
condition is required.
Net Safety strongly recommends that the 2.5
mA analog fault condition and fault relay (if used) be
monitored in conjunction with alarm levels on the analog output and the alarm relay, if used.
6.7.1 Transmitter fault conditions
Fault conditions that the transmitter detects are as follows:
Fault condition
M21
M22
Input voltage less than 8 VDC
P
P
Input voltage more than 33 VDC
P P
Critical memory fault
P
P
Onboard power supply fault
P
P
Reference Manual Monitoring and outputs
MAN-0076, Revision 09 June 2016
Monitoring and outputs 35
6.7.2 Sensor fault conditions
Fault conditions that the various Millennium II sensors detect are as follows:
Fault condition
SC310
SC311
ST322
ST332
ST340
ST320
ST330
ST341
ST360
Zero calibration failure
P
P
P
P
P
Span calibration failure
P
P
P
P
P
P
P
P
P
Low temperature
P
P
P
P
High temperature
P P P P
Low power
P P P P P
High power
P P P P P
Replace sensor
P P P P P P P P P
Zero drift
P
P
P
P
P
Signal invalid
P
Over-range
P
P
P
P
P
Memory fault
P
P
P
P
P
P
P
P
P
Power supply fault
P
P
P
P
P
Sensor end of life
P
P
P
P
P
P
Sensor weak signal
P P P P
Sensor thermistor fault
P
Maintenance Reference Manual
June 2016 MAN-0076, Revision 09
36 Maintenance
Section 7: Maintenance
7.1 Periodic response check
Net Safety Monitoring recommends that a bump test be performed every 90 days to ensure continued
functionality and accuracy of the detection system. Full calibration is recommended when the sensor
fails to meet acceptable accuracy standards. This involves the application of calibration gas to the
sensor, then the observation of the response LEDs, analog output, and external monitoring equipment.
Be sure to prevent unwanted response of external monitoring devices and equipment during this
procedure. If the Millennium II’s response to calibration gas is within the specified accuracy then it is
not necessary to perform a calibration.
Example: When 50% of full scale is applied, the response is expected to be between 11.5 mA (47% of full
scale) and 12.5 mA (53% of full scale). An additional consideration is the accuracy tolerance of the
calibration gas which may be + or - a few percent. If the calibration gas is + or - 10% of full scale then the
reading may be from 10.7 mA (42% of full scale) to 13.3 mA (58% of full scale).
7.2 Troubleshooting
Response to the input should be checked and, if necessary, calibration should be performed whenever
the accuracy of this check is not satisfactory. The system should also be checked when sensor or
transmitter is added or removed. If problems should develop, first check for faulty wiring, confirm
proper voltage to transmitter and attempt a calibration. If problems persist, please contact Net
Safety’s Service Department first by phone to try and resolve any issues. If issues cannot be resolved,
please follow the procedure on ‘how to return equipment’.
7.3 Storage
The transmitter and its electronic components/parts should be stored in locations free from dust and
moisture. The storage temperature should be well within the limits of the certified temperatures of the
equipment. See Section 10 for storage temperatures.
Reference Manual Maintenance
MAN-0076, Revision 09 June 2016
Maintenance 37
7.4 Spare parts and accessories
Description
Part Number
3/4 NPT ATEX certified plug - Aluminum
CP-AL-002
3/4 NPT ATEX certified plug - Stainless Steel
CP-SS-001
Aluminum separation kit
JB-MPD-A
Stainless Steel separation kit
JB-MPD-S
Magnet assembly
MAGNET-1
Conduit reducer - 3/4” to M20 - Aluminum
M20R
Conduit reducer - 3/4” to M20 - Stainless Steel
M20R-SS
Sun shade kit - Requires UN-MK-1
SSK-2
1" Pipe Mounted Sun shade kit/rain guard - Includes UN-MK-31
SSK-51
2" Pipe Mounted Sun shade kit/rain guard - includes UN-MK-32
SSK-52
3" Pipe Mounted Sun shade kit/rain guard - Includes UN-MK-33
SSK-53
Single channel transmitter w/analog output
TX-M21-A
Single channel transmitter w/analog & mech. relay outputs
TX-M21-AR
Single channel transmitter w/analog &digital Modbus outputs
TX-M21-AD
Single channel transmitter w/analog , mech. relay &digital Modbus output
TX-M21-ARD
Single channel transmitter w/ analog / Hart communication output
TX-M21-AH
Single channel transmitter w/ analog / Hart communication output for
wireless capable transmitters
TX-M21-AH-FC
Single channel transmitter w/analog /Hart communication & relay output
TX-M21-AHR
Single channel transmitter w/analog /Hart communication & relay output
for wireless capable transmitters
TX-M21-AHR-FC
Dual channel transmitter w/analog output
TX-M22-A
Dual channel transmitter w/analog and mech. relay output
TX-M22-AR
Dual channel transmitter w/analog & digital Modbus output
TX-M22-AD
Dual channel transmitter w/analog, relay & digital Modbus output
TX-M22-ARD
2" Pipe Mounting kit (stainless steel)
UN-MK-1
1" Pipe Mounting kit - All Millennium II & ECO-SENSE Gas Detectors
(stainless steel)
UN-MK-31
2" Pipe Mounting kit - All Millennium II & ECO-SENSE Gas Detectors
(stainless steel)
UN-MK-32
Maintenance Reference Manual
June 2016 MAN-0076, Revision 09
38 Maintenance
Description
Part Number
3" Pipe Mounting kit - All Millennium II & ECO-SENSE Gas Detectors
(stainless steel)
UN-MK-33
Reference Manual Electrostatic sensitive device
MAN-0076, Revision 09 June 2016
Electrostatic sensitive device 39
Section 8: Electrostatic sensitive device
Definition: Electrostatic discharge (ESD) is the transfer, between bodies, of an electrostatic charge
caused by direct contact or induced by an electrostatic field.
The most common cause of ESD is physical contact. Touching an object can cause a discharge of
electrostatic energy. If the charge is sufficient and occurs near electronic components, it can damage
or destroy those components. In some cases, damage is instantaneous and an immediate malfunction
occurs. However, symptoms are not always immediateperformance may be marginal or seemingly
normal for an indefinite period of time, followed by a sudden failure.
To eliminate potential ESD damage, review the following guidelines:
Handle boards by the sides taking care not to touch electronic components.
Wear grounded wrist or foot straps, ESD shoes or heel grounders to dissipate unwanted static
energy.
Prior to handling boards, dispel any charge in your body or equipment by touching a grounded
metal surface.
Ensure all components are transported and stored in ESD safe packaging.
When returning boards, carefully package in the original carton and static protective wrapping.
Ensure ALL personnel are educated and trained in ESD Control Procedures.
In general, exercise accepted and proven precautions normally observed when handling electrostatic
sensitive devices.
Wire resistance table Reference Manual
June 2016 MAN-0076, Revision 09
40 Wire resistance table
Section 9: Wire resistance table
Distance
Feet (Meters)
AWG #20
0.5 mm2
AWG #18
0.8 mm2
AWG #16
1.0 mm2
AWG #14
2.0 mm2
100 (30.5)
1.02
0.64
0.40
0.25
200 (61)
2.03
1.28
0.80
0.51
300 (91.4)
3.05
1.92
1.20
0.76
400 (121.9)
4.06
2.55
1.61
1.01
500 (152.4)
5.08
3.20
2.01
1.26
600 (182.9)
6.09
3.83
2.41
1.52
700 (213.4)
7.11
4.47
2.81
1.77
800 (243.8)
8.12
5.11
3.21
2.02
900 (274.3)
9.14
5.75
3.61
2.27
1000 (304.8)
10.20
6.39
4.02
2.53
1250 (381)
12.70
7.99
5.03
3.16
1500 (457.2)
15.20
9.58
6.02
3.79
1750 (533.4)
17.80
11.20
7.03
4.42
2000 (609.6)
20.30
12.80
8.03
5.05
2250 (685.8)
22.80
14.40
9.03
5.68
2500 (762)
25.40
16.00
10.00
6.31
3000 (914.4)
30.50
19.20
12.00
7.58
3500 (1066.8)
35.50
22.40
14.10
8.84
4000 (1219.2)
40.60
25.50
16.10
10.00
4500 (1371.6)
45.70
28.70
18.10
11.40
5000 (1524)
50.10
32.00
20.10
12.60
5500 (1676.4)
55.80
35.10
22.10
13.91
6000 (1828.8)
61.00
38.30
24.10
15.20
6500 (1981.2)
66.00
41.50
26.10
16.40
7000 (2133.6)
71.10
44.70
28.10
17.70
7500 (2286)
76.10
47.90
30.10
19.00
8000 (2438.4)
81.20
51.10
23.10
20.20
9000 (2743.2)
91.40
57.50
36.10
22.70
10000 (3048)
102.00
63.90
40.20
25.30
Resistance shown is one way. This figure must be doubled when determining closed loop resistance.
Reference Manual Specifications
MAN-0076, Revision 09 June 2016
Specifications 41
Section 10: Specifications
10.1 Electrical
10.1.1 Operating voltage range
10.5 to 32 VDC
18 to 32 VDC (HART versions only)
10.1.2 Power consumption
2.4 W @ 24 VDC (average - varies by sensor types/quantities)
10.1.3 EMC compliance
EN 50270:2006 per EMC directive 2004/108/EC
10.2 Environmental
10.2.1 Operating temperature
-67 °F to +185 °F (-55 °C to +85 °C ) - Stainless steel
-58 °F to +185 °F (-50 °C to+85 °C ) Stainless steel North American explosion-proof certification
-40 °F to +185 °F (-40 °C to +85 °C ) - Aluminum
10.2.2 Relative humidity
0 - 95% RH non-condensing
10.2.3 Ingress protection
IP66 (Aluminum)
IP67 (Stainless Steel)
IP64 (with sensors)
Type 4X (transmitter only)
10.3 Mechanical
10.3.1 Enclosure material
Cast Aluminum (A359)
Stainless steel (SS316)
10.3.2 Conduit opening
3/4” NPT (3X)
Specifications Reference Manual
June 2016 MAN-0076, Revision 09
42 Specifications
10.3.3 Weight
Aluminum: 5.5 lbs (2.5 kg)
Stainless Steel: 7.0 lbs (3.2 kg)
10.4 Warranty
3 years
Reference Manual Certifications
MAN-0076, Revision 09 June 2016
Certifications 43
Section 11: Certifications
11.1 North American
Class I, Division 1, Groups BCD T5
Class I, Zone 1, AEX/Ex d IIB+H2 T5
-50 °C ≤ Ta + 85 °C
NEMA Type 4X/IP67
FM6320, ANSI/ISA 12.13.01, CSA 22.2 No. 152:2006
11.2 IECEx
Ex d IIB+H2 T5 Gb
IECEx DNV 12.0014 (Aluminum) IP66, controller only
IECEx FMG 12.0006X (Stainless Steel) IP 67, controller only
IEC 60079-0: 2007-10 & IEC 60079-1: 2007-04
11.3 FC Models
11.3.1 North American
Class I, Division 1, Groups BCD T5
Class I, Zone 1, AEx/Ex d IIB+ H2 T5
-50 °C ≤ Ta + 85 °C
NEMA Type 4X/IP67 (transmitter only)
CSA C22.2 No. 152:2006
11.3.2 IECEx (aluminum)
Ex d IIB+H2 T5 Gb
-40°C ≤ Ta ≤ + 85°C
IP66
IECEx DNV 12.0014
11.3.3 IECEx (stainless)
Ex d IIB+H2 T5 Gb
-55°C ≤ Ta ≤ + 85°C
IP67
IECEx FMG 12.0006X
Special conditions for safe use:
Consult the manufacturer if dimensional information on the flameproof joints is necessary.
Ordering information Reference Manual
June 2016 MAN-0076, Revision 09
44 Ordering information
Section 12: Ordering information
12.1 M21 single channel transmitter
Model
Description
M21
Millennium II Single Channel Transmitter
Output
Description
A
Analog Output
AD
Analog and Digital RS485 Modbus RTU Protocol Outputs
AH Analog and HART Protocol Outputs
AHR
Analog, HART Protocol and Relay Outputs
AR
Analog and Relay Outputs
ARD
Analog, Relay and Digital RS485 Modbus RTU Protocol Outputs
Enclosure
Description
A
Aluminum
S
Stainless Steel
Wireless
Description
_
Not Required
FC
Wireless Ready - THUM Capable (Used Only With AH or AHR
Outputs)
Reference Manual Ordering information
MAN-0076, Revision 09 June 2016
Ordering information 45
12.2 M22 dual channel transmitter
Model
Description
M22
Millennium II Dual Channel Transmitter
Output
Description
A
Analog Output
AD
Analog and Digital RS485 Modbus RTU Protocol Outputs
AR
Analog and Relay Outputs
ARD
Analog, Relay and Digital RS485 Modbus RTU Protocol Outputs
Enclosure
Description
A
Aluminum
S
Stainless Steel
MAN-0076
Revision 09
June 2016
EmersonProcess.com/FlameGasDetection
AnalyticExpert.com
twitter.com/Rosemount_News
youtube.com/user/RosemountAnalytical
facebook.com/Rosemount
Americas
Emerson Process Management
6021 Innovation Blvd.
Shakopee, MN 55379
USA
T +952 906 8888
F +952 949 7001
SAFETY.CSC@Emerson.com
Europe
Emerson Process Management AG
Neuhofstrasse 19a P.O. Box 1046
CH-6340 Baar
Switzerland
T + 41 (0) 41 768 6111
F +41 (0) 41 768 6300
SAFETY.CSC@Emerson.com
Middle East and Africa
Emerson Process Management
Emerson FZE
Jebel Ali Free Zone
Dubai, UAE
P.O. Box 17033
T +971 4 811 8100
F + 971 4 886 5465
SAFETY.CSC@Emerson.com
Asia Pacific
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T + 65 6 777 8211
F + 65 6 777 0947
SAFETY.CSC@Emerson.com
©2016 Emerson Process Management. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one
of the Emerson Process Management family of companies. All other marks are property of their
respective owners.
The contents of this publication are presented for information purposes only, and, while effort has been
made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or
implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available on request. We reserve the right to modify
or improve the designs or specifications of our products at any time without notice.

Navigation menu