35600 FHI DD

User Manual: 35600

Open the PDF directly: View PDF PDF.
Page Count: 4

TRIANGLE ENGINEERING
of Arkansas, Inc.
SOUND FIGHTER FANS
12
Panel Fan Direct Drive
as standard. (Open motors are not
recommended.)
All available motor configurations
(chemical type, 50 cy, etc.) are available
as an option.
Formed motor mounting plate to minimize
vibration.
Split Tapered Standard Drive Hubs permit
easy removal of the fan from the shaft for
maintenance purposes
Standard finish: Coated with a polyester
powder coat paint system for long life and
superior corrosion resistance.
Accessory Equipment
RAIN LOUVERS supplied in heavy duty
galvanized steel to protect against rain on
supply units.
WALL BOXES for mounting to wall
openings and/or for mounting screens or
shutters. (Can also be used to convert wall
fan into semi-portable spot or man cooler.)
SHUTTERS are available in air, manual
and electric motor operated types.
DISCHARGE SCREENS are constructed
of heavy gauge wire and of a mesh
suitable for most industrial applications.
Series FHI
NON-OVERLOADING AIRFOIL Cast
Aluminum Fan Blades are a special feature
to insure high operating efficiencies.
Conventional flat blades cause excessive air
turbulence which results in motor overloads
and poor acoustic performance.
Standard Features
Heavy duty cast aluminum propeller with
Airfoil blades for quiet, efficient operation.
Standard construction is 4-bladed propeller
through 36" and 6-bladed propeller through
60". Other duties and arrangements are
available. Consult factory.
Deep spun venturi-type orifice for quieter,
more efficient operation.
Rugged all-welded structural frame for
added support and lower vibration.
Taper-lock bushing between propeller and
shaft for ease of removal, should it become
necessary.
Motors are totally enclosed, fan cooled
TRIANGLE ENGINEERING
of Arkansas, Inc.
SOUND FIGHTER FANS
13
Direct Drive
Series FHI
FAN MOTOR PROPELLER DIMENSIONS
MODEL HP RPM DIA. A B C D
FHI-24-DD 1/2 1150 24 30 16-1/2 9-1/2 3
FHI-24-DD 3/4 1150 24 30 16-1/2 9-1/2 3
FHI-24-DD 1 1150 24 30 16-1/2 9-1/2 3
FHI-24-DD 1-1/2 1750 24 30 16-1/2 9-1/2 3
FHI-30-DD 1/2 860 30 36 17-1/2 10-1/2 3
FHI-30-DD 3/4 860 30 36 17-1/2 10-1/2 3
FHI-30-DD 1 1150 30 36 17-1/2 10-1/2 3
FHI-30-DD 2 1150 30 36 17-1/2 10-1/2 3
FHI-30-DD 3 1750 30 36 17-1/2 10-1/2 3
FHI-36-DD 3/4 860 36 42 17-1/2 10-1/2 3
FHI-36-DD 1 860 36 42 17-1/2 10-1/2 3
FHI-36-DD 2 1150 36 42 17-1/2 10-1/2 3
FHI-36-DD 3 1150 36 42 20 13 3
FHI-36-DD 5 1150 36 42 20 13 3
FHI-36-DD 7-1/2 1150 36 42 20 13 3
FHI-42-DD 2 860 42 48 22 15 3
FHI-42-DD 5 860 42 48 22 15 3
FHI-42-DD 5 1150 42 48 22 15 3
FHI-42-DD 7-1/2 1150 42 48 22 15 3
FHI-42-DD 10 1150 42 48 22 15 3
FHI-48-DD 3 860 48 54 22 13 3
FHI-48-DD 5 860 48 54 22 15 3
FHI-48-DD 7-1/2 860 48 54 22 15 3
FHI-48-DD 7-1/2 1150 48 54 22 15 3
FHI-48-DD 10 1150 48 54 23-1/2 16-1/2 3
FHI-48-DD 15 1150 48 54 23-1/2 16-1/2 3
FHI-54-DD 5 860 54 60 22 15 3
FHI-54-DD 7-1/2 860 54 60 22 15 3
FHI-54-DD 10 860 54 60 23-1/2 16-1/2 3
FHI-60-DD 5 860 60 66 22 15 4
FHI-60-DD 7-1/2 860 60 66 23-1/2 16-1/2 4
FHI-60-DD 10 860 60 66 23-3/4 15-1/2 4
ALL ANGLE OPERATION:
Fan can be mounted vertically
in a wall, horizontally in a roof
with appropriate hood cover, or
at any intermediate angle.
TRIANGLE ENGINEERING
of Arkansas, Inc.
SOUND FIGHTER FANS
14
Direct Drive
Series FHI
MODel MTr. TiP PeaK CFM
nO. HP rPM SPeeD BHP .00"SP .10"SP .125"SP .25"SP .375"SP .50"SP .75"SP 1.00"SP
FHI-24-DD 1/2 1150 7159 .48 5400 5120 5070 4600 3860 3050
FHI-24-DD 3/4 1150 7159 .72 6830 6410 6290 5670 4428 3341
FHI-24-DD 1 1150 7159 1.00 7396 6874 6744 6091 4935 3779 2494
FHI-24-DD 1-1/2 1750 10990 1.15 8320 8140 8100 7790 7450 6762 5710 4499
FHI-30-DD 1/2 860 6751 .48 7770 7180 6950 5720 4170 1870
FHI-30-DD 3/4 860 6751 .71 9340 8650 8420 7210 5810 4090
FHI-30-DD 1 1150 8949 1.10 10400 10110 9950 9120 8210 7200 4670
FHI-30-DD 2 1150 8949 1.73 12500 12080 11920 11080 10190 9220 6683 3210
FHI-30-DD 3 1750 13737 2.98 13920 13560 13440 12980 12520 12040 10860 9597
FHI-36-DD 3/4 860 8110 .70 12003 11404 11217 9946 8436 6790 3253
FHI-36-DD 1 860 8110 1.17 15046 14246 14059 12937 11674 10208 5369
FHI-36-DD 2 1150 10845 1.68 16050 15500 15300 14200 12850 11300 7850 4350
FHI-36-DD 3 1150 10845 2.85 20120 19370 19100 18020 16920 15600 12450 7185
FHI-36-DD 5 1150 10845 4.87 21370 20920 20800 20150 19450 18680 16700 13960
FHI-36-DD 7-1/2 1150 10845 7.06 24650 24150 24000 23180 22300 21400 19300 16050
MODel MTr. TiP PeaK CFM
MODel nO. HP rPM SPeeD BHP .00"SP .10"SP .125"SP .25"SP .375"SP .50"SP .75"SP 1.00"SP
FHI-42-DD 2 860 9460 2.23 20051 19391 19165 18281 17361 16292 13753 10081
FHI-42-DD 5 860 9460 5.49 29021 28342 28013 27072 25929 24727 22156 15046
FHI-42-DD 5 1150 12650 5.21 26812 26127 26076 25089 24120 23142 21054 18354
FHI-42-DD 10 1150 12650 9.89 32709 32054 31910 30820 29907 28970 26860 24397
FHI-48-DD 3 860 10810 2.90 25900 24701 24402 22930 21305 19419 13672
FHI-48-DD 5 860 10810 5.39 33439 31982 31624 29915 28091 26220 21545
FHI-48-DD 7-1/2 860 10810 7.11 37980 36565 36213 34320 32303 30238 25550
FHI-48-DD 10 1150 14456 9.70 40598 39602 39306 38200 36904 35600 33096 30202
FHI-48-DD 15 1150 14456 14.14 48820 47700 47402 46099 44795 43297 40403 37396
FHI-54-DD 5 860 12160 4.99 36755 35208 34824 33021 30992 28802 23650
FHI-54-DD 7-1/2 860 12160 7.34 45662 44360 43854 41438 38668 36165 31356 24622
FHI-54-DD 10 860 12160 10.40 50262 48678 48282 46142 43934 41632 36260
FHI-60-DD 5 860 13510 4.57 38745 36993 36341 34348 31930 29515 24074
FHI-60-DD 7-1/2 860 13510 7.50 47730 46065 45663 43630 41323 38797 33103
FHI-60-DD 10 860 13510 10.21 57483 55349 54580 49652 44905 41085 33906 18585
4 Blades6 Blades
TRIANGLE ENGINEERING
of Arkansas, Inc.
SOUND FIGHTER FANS
19
BOX MOUNTED IN
WALL/SHUTTER
MOUNTED TO BOX
INSIDE
1-1/2”
FLANGE
B
B
AINSIDE OUTSIDE
BOX MOUNTED IN
WALL/SHUTTER
MOUNTED TO OUTSIDE
OF WALL
BOX MOUNTED THROUGH
WALL/SHUTTER
MOUNTED TO OUTSIDE
OF BOX
FHI Series
WALL BOXES
Standard sizes for use with
FHI Belt-Drive and Direct Drive Fans
NOTE: “A" DIMENSION WILL INCREASE 6" WHEN A BACKDRAFT DAMPER IS SPECIFIED TO BE MOUNTED INSIDE BOX.
WHEN INSTALLATION OF FAN REQUIRES A SHUTTER, A MINIMUM OF 6" SHOULD BE ALLOWED BETWEEN FAN BLADE AND SHUTTER.
CONSULT FACTORY FOR SPECIAL APPLICATIONS AND SIZES.
BOX MODel MOTOr HP a DiMenSiOn B DiMenSiOn HOle SiZe Flange SiZe gaUge
S-24 1/4 HP-2 HP 22-1/2" 30-3/8" O.D. 30-3/4" X 30-3/4" 1-1/2" 16
3 HP 28-1/2" 30-3/8" O.D. 30-3/4" X 30-3/4" 1-1/2" 16
S-30 1/2 HP-2 HP 22-1/2" 36-3/8" O.D. 36-3/4" X 36-3/4" 1-1/2" 16
3 HP-5 HP 28-1/2" 36-3/8" O.D. 36-3/4" X 36-3/4" 1-1/2" 16
S-36 1 HP-2 HP 22-1/2" 42-3/8" O.D. 42-3/4" X 42-3/4" 1-1/2" 16
3 HP - 7-1/2 HP 28-1/2" 42-3/8" O.D. 42-3/4" X 42-3/4" 1-1/2" 16
S-42 1-1/2 HP-2 HP 22-1/2" 48-3/8" O.D. 48-3/4" X 48-3/4" 1-1/2" 16
3 HP - 7-1/2 HP 28-1/2" 48-3/8" O.D. 48-3/4" X 48-3/4" 1-1/2" 16
10 HP 34-1/2" 48-3/8" O.D. 48-3/4" X 48-3/4" 1-1/2" 16
S-48 1-1/2 HP-5 HP 28-1/2" 54-3/8" O.D. 54-3/4" X 54-3/4" 1-1/2" 16
7-1/2 HP- 10 HP 34-1/2" 54-3/8" O.D. 54-3/4" X 54-3/4" 1-1/2" 16
S-54 2 HP-5 HP 28-1/2" 60-3/8" O.D. 60-3/4" X 60-3/4" 1-1/2" 16
7-1/2 HP- 10 HP 34-1/2" 60-3/8" O.D. 60-3/4" X 60-3/4" 1-1/2" 16
S-60 2 HP-5 HP 28-1/2" 66-3/8" O.D. 66-3/4" X 66-3/4" 1-1/2" 16
7-1/2 HP-10 HP 34-1/2" 66-3/8" O.D. 66-3/4" X 66-3/4" 1-1/2" 16
S-72 3 HP-5 HP 28-1/2" 78-3/8" O.D. 78-3/4" X 78-3/4" 1-1/2" 16
7-1/2 HP - 10 HP 34-1/2" 78-3/8" O.D. 78-3/4" X 78-3/4" 1-1/2" 16
15 HP - 20 HP 40-1/2" 78-3/8" O.D. 78-3/4" X 78-3/4" 1-1/2" 16
25 HP 46-1/2" 78-3/8" O.D. 78-3/4" X 78-3/4" 1-1/2" 16
S-84 5 HP 28-1/2" 90-3/8" O.D. 90-3/4" X 90-3/4" 1-1/2" 16
7-1/2 HP - 10 HP 34-1/2" 90-3/8" O.D. 90-3/4" X 90-3/4" 1-1/2" 16
15 HP-20 HP 40-1/2" 90-3/8" O.D. 90-3/4" X 90-3/4" 1-1/2" 16
25 HP 46" 90-3/8" O.D. 90-3/4" X 90-3/4" 1-1/2" 16

Navigation menu