(GE) AK Breakers Vol 2 Of
2018-02-16
: (Ge)-Ak Breakers Vol 2 Of 2 (GE)-AK_Breakers_Vol_2_of_2 QP_ing manuals pub
Open the PDF directly: View PDF .
Page Count: 382
Download | |
Open PDF In Browser | View PDF |
F-P Index FEDERAL PACIFIC- Breakers TAB#! CAT SECTION i 1 and Switchgear DESCFUPnON CONTENTS 1 Manual #3-407 Selection &Application F-P Air Circuit Breakers SP-LV-CB-2 Specific Procedures LV Air Circuit Breaker Calibration Test I.L 12-957 Instruction Leaflet Selenium Rectifiers for Breakers 21456 Installation Sheet DMB-15and DMB-25-1 IN-302 instruction Book DMB-25and DMB-SO IN-810.1 Renewal Parts & Maint Instr. DMB-15T IN-810.2 Renewal Parts & Maint Instr. DMB-25-1T iN-810.3 Renewal Parts & Maint Instr. DMB-50-T 3 IN-820.11 Instruction Manual DST-2(5&15kV) 4 Class 6045 Installation Instructions DST-5(5&15kV) 5 IN-810.6 Instruction Manual FP Power & FM Fusematic IN-810.9 Instruction Manual FP25-600. FM25-600. FP50-1600. FM50-1600 IN-810.4 Instruction & Renewal Parts FP50-800. FM50-800 Retrofit Instructions FP-SO 1100B6403 Time-Current Curve FP25 & FP50 Motor Starting 1100B6402 Time-Current Curve FP25 & FP50 Dual Magnetic TD1 1100B6406 Time-Current Curve FP25 & FP50 TD-2 Timing Device 1100B6406 Time-Current Curve FP75 Dual Magnetic TD-1 Timing Device C-3-413 Instruction Book Type H - LV. Breakers C-3-230 Swgr Catalogue Type H2 - LV. Breakers C-3-222 Technical Data Type H-3 & HL-3 Breakers C-3-222-1 Instruction Book Type H-3 & HL-3 Breakers C-3-218 Swgr Catalogue USD Solid State Relay IN-820.4B & 4A Instruction Book Metal-Clad & LV. Switchgear IN-820-3 instruction Book Metal-Clad & LV. Switchgear 1 2 6 7 Miscellaneous Switchear Components 8 Page 1 •v;': Vi K iC a ?|0 t' ia • V-" ''"r^'X . v'^. ' • I; • ' • .. iV : .\>(Vf v. -tV I i '.;Vt''''.'-';''-,-'v v.':."' V .•;,; • • •;',:5'.'' • ''V' • 'r.i • '" ' ' • /'M , Vv.i'^V'v ' ..• i 'I ' . • .jr: - r.v -.-< ;A' kMyMi ti, , •p'lT': '•: t '. V^r'.-;:ri:•• a' stei i t •• = I , .- iiJtt^tn— r—• B6»iriTmririJ.iui^nnatttfaaias^'A': •'• -J*2.V-.;'• ' i»~'11'TBirragIt» " '•' ••: • ••.••• '" '. '! <,'•'••• •:.l.' •>•!. •• •' ' ' • •' • .; yy '-'y:0:';^icortwjiiptf • !• '.j • '• ->is!v;;: ; page Subject General Selection Factors . . . . Interrupting Ratings . . .... Short-Time Ratings . . . Operating Mechanisms. . . . .• . Control Circuit Power , . . ; . Tripping Devices . . . . .. . . 1.2 . « ♦ • Time Current Characteristic Curves . . Continuous Ci,..' it Ratings .' . Definition of Terms . . . . « r .•;? . Scries Overcurrent Tripping Device . . . • * . Determination of Shdrt-Circuit Currents • « 2.3 t • • • • • • • • • • I • f I -IP* 7-io . ;, . • 3.4 . Tripping Characteristics Produced . • • • « 10- . f"' •i'-K' » « • • I • • * P :• : 9 • • , PJ' • ''V .r> . ''r ,10.11 The Selective System . ' . The Cascade System . . National Electtical Code . Accessories for Federal Pacific Air,Circuit Breakers Application Tables ; . . . . , . . . . • • '9 • . ^ •': r-: • . . » 1. 15' IP -.-I"P1«-1S> - -P • PPiiPp^K;- / "^ tt* Li '^rj 7.7n ^:.• '' 'i . V . V* ^ Li^:J;- •I w • 'v^-i..v ^^ .'/U/' ni ^ iU CM •• , * Mii aj 4c« LJ ^ ^ C•* Li L>#<. R? L. ^^ / a • iT- »- .., ,/ • <• Wa. -l'- -.iwal /-'..-A.L>LW. J-Vjairfti ii-iil»iik^ki*Li4ii.i5ilijliL-i«ltKWj^iaUrt'»V.r."; I Lia,Ua^:.*' /*.'1 j,.aLi -'...y/'' y , -f;, SEL2OT0^3 , y :• or D.C. amperes which they will carry continuously without excccdmg the limi of: ohsemble temperatm'e . The probletn of selectuig aircircuit breakers for the" protection of low voltage circuits is similar to the problsnt of selecting other types of equipment such as motors or relays. As in the application of motors and relays, the circuit breaker should be compatible with the power system with which it is to be associated; it should be able to withstand .the conditions imposed during operation in the field. Most of these require ments will be obvious upon'inspection of the power system and the field conditions, and should be evalu ated with reference to the text of this manual. The maximum short circuit current: available at the point of application will not be so seifrevident; it is usually necessary to .calculate this value. The avaOable short or exceed &e nominal voltage of the circuit to which it is to be applied. Table No. T, page 16, lists the , greatly increased interrupting ra^gs available at Voltages lower than 600v. ;;" :y ; y 3. Available Shdit-Circuit Current and interrupt, is imique with the power system and the point of application of the circuit breaker. This publication is intendedfor use in the selection and application of general purpose low voltage air The avaOable short-bireuit cureent at a given point in a power system ii &e maximum current which the power system, when operating yiyith rtiaiximum generrating capacity and cotmected deliver to zero unpedanceshort (Circuits dmriltaneously applied from all phases or polarities to gfbund. For a-c sys Standards for Large Air Circuit Breakem. tems the rms value of themaximum asymmetric^ cur The factors which will affect the selection of air circuit breakers are as follows: 1. Circuit load current. 2. Circuit voltage. 3. Available short oirciiit current at the point of application. 4. System frequency. . 5. Local electrical codes., . 6. Limits 01 observable tempt-ature rise. .. 7. Unusual service conditions. the particular, sections deling with thein in this manual-''' rent avaOable must be less than the interrupting rating and short time ratmg of the circuit breaker. For d-c systems the maximum steady state current should be less thau the interrupting rating of the circuit.breaker. For f\ulher discussion of the selection of air circuit . breakers with respect to their interrupting capacity, reference should be madeto the tables on pages 18 and 19 on intenupting capacity and the discussion on calr cuiaJon ofavailable !^c^-clrcitit currient bn page 10, .4. System Frequency These factors and conditions should!be .referred to 'X.V 2. Circuit Voltage The voltage rating of the circuit breaker should equal circuit current, which the circuit breakers must carry circuit breakers and the trip devices associated with these circuit breakers; as recommended by the NEMA r:\ rise. After a fault current intetruption .the current carrying ability of a circuit breaker may be materially reduced. Table No. 2, page 16, shows the continuous current ratings of . Federal iPacific large air circuit breakers and series trip cdil ratings. . "'x'''• 1, Circuit toad CuiTont y ; Tlic rated continuous current of Federal Pacific circuit breakers is die designated limit in rms amperes The frequent^ :;SS(P' W.' q£ circuit breaker shoidd a^ee with the nominirf ffeqU^y.of the ppwjr system:, Federal Pacific circuit breakers are rated:iorfrcquen- •i' vies of 60^25 cycles oi .d-c, For frequencies, other ' ' than frequencies available as standard or for circuits ' on which higher order harmonics ,are present; special ; recommendations shoidd^b© requested from the Fed- ' i-x" Rt-f.^l'rTiirrTfi'^'"'" u w L ^ Vi^ w <•/ -Jt' i' -i eral Pacific Electric Company (hereafter called the "Company). 5. Locaf Electrical Codes Federal Pacific breakers are designed to comply with the National Electrical Code. Where City or State Codes are more restrietive than the National Elec trical Code, the Company should be consulted for its recommendations. Unless such recommendations art- obtained in advance of placing orders, the Company will notassume responsibility for compliance with such codes. :( 6. Limits of Observable Temperature Rise Federal Pacific air circuit breakers are designed in accordance with "the NEMA Standards SG3-3.04 on Limits of ObservableTemperature Rise above the Am bient Temperature, the latter defined in the NEMA Standard SG3-3.IS. 7. Unusual Service Conditions When unusual environmental conditions or unusual duty conditions are encountered, it is recommended that these conditions be nullified at the site of the in stallation. Unusual conditions referred to are those considered by NEMA under SG3-2.02. When such action is not possible and standard equipment adaotable to the condition is not listed, recommendations for special features necesshry to adapt standard equip ment to the conditions should be obtained from the Company in advance of placing the order. If^TEKRUPTING. RATEM.GS The interrupting rating of a circuit breaker is the highest current (rms ifalternating current) at a speci-. fied operating voltage which the breaker is required to interrupt under the operating duty specified and with a normal frequency recover voltage equal to the specified operaiing voltage. ^ . Interrupting ratings of Federal Pacific air circuit breakers arc based on test prWediirci applicable op erating duty (dutycycle),^rtormance, and conditions given in paragraphs SG3-3.07, SG3J.OS and SG3-3.19 01 the NEMA Standard for large air -ircui* brtaVc.7i Tnese paragraphs read essentially as.follpws:—, Short-Ciircult Interrupting Tests The ,iesi procedure and;characteristics of the. test -:z.m circuit to be used for verifying the ability of the cir cuit breaker to interrupt the lotaLamperes (rms if al-. ternating current) given by the interrtipting rating for the applicable operating duty shall be as follows; A. RMS Total Amporos \i The rms total amperes shall be determined by ?} measuring the current flow in the test circuit dsi) follows: . ^ The circuit breaker shall be short circuited W. omitted. . • In alternating-current circuits, the current mea-' • sured shall be the rms total current including if any, the direct-current component. It shall be measured at an instant one-half cycle after the short circuit occurs and shall be calculated in accordance with American Standard Methods for Determining the Rms Value of Sinusoidal Current Wave a.nd a . Normal-frequency Recovery Voltage. (For « i- phase test circuit the rms total current 'sHcdl be'the} average of ihe currents in ail3 phases. For asingle-;:^ phase test circuit, 3 successive tests shall be made to determine the average current in that circuit.) The circuit constants for the test circuit, with the ? required current flowing, shall be such that the i'• X/R ratio is at least 11.72, In direct-current circuits, the current measured i shall be the maximum value. The transient characteristicsof the testingcircuit for a circuit breaker with delayed tripping in the fault current range shall be such thai the 3-phase average current at the end of 30 cycles (based on a 60-cycle frequency) shall be not less than 75 per cent of the average rms total current at the end of the first half cycle. ' . •: " B. Performance < At the end of any performance at or within its interrupting rating, the circuit breaker shall be the.foUowirig condition: ^ • • • A"••• 1, Mechanical—The circuit breaker shall be in substantially t',mechanical conditioii }C[^^ :,' as at the beginnings - / 2. Electrical—The circuit breaker shall.be co- -"'. .. pable of w///iy/anrf% rated •jvjvSj • isb^u-'K^ii-uue ^c:iL/;q£> : open positionand of carryingrated current at 2. Circuit breakers having a continuous current rating above 2000 amperes— ' . a. 12 times the rated continuous cidttr^ntof the 'v•,, rated voltage for c limited time but not nec essarily without exceeding the rated tempera- . circuit breaker, or ture rise. After performance at of near its interrupting rating, it is not to be inferredthat the circuit breaker can again meet its interritpting fating without being . inspected and, if necessary, repaired, whichever is lowest. ; Ta , • Direct-Acting Delayed Overcurrent Trip Devices for Fault Currents The conditions which are assumed in assigrung . SHORT-TIME RATINGS • • The rated short-time current of a circuit breaker is the highest rms current, including the d-c component, which it will be required to carry for specifiejd shorttime intervals. Short-time rating of Federal Pacific air circuit breakers is based on test procedure^ operating duty The operating duty for determining the inter rupting rating of circuit breakers with instantaneous overcurrent trip devices for fault currents shall con sist of an opening operation, followed after a 15- (duty cycle), performance, and" conditioni giyen in paragraphs SG3-3.10 and SG3-3.16.. The paragraphs read essentially as follows:-— second interval by. a close-open operation. Short-time current tests are made io.deterntlne'[ ff'.0i^^:-..^ the ability of a circuit breaker 0 carry ^ wiferf rupting rating of circuit breakers with delayed overcurrent trip devices for fault currents shall consist short-time current without infury. of an opening operation, followed after a iS-second. interval by a close-open operation, the,tripping be ing delayed by the associated tripping devices. A. RMS Total Amperes Determined same as for interrupting rating. " if,ft' At the end of any performance ot or within it's short-time rating, the circuit breaker shall be'capa^^trif/:f^^r-- Currents 1. Circuit breakers having a continuous current rating of 2000 amperes and below —15 times the rated continuous current of the circuit . ..'X' ' B. Performance B. Interrupting Ratings for Circuit Breakers with ,u!!:wi..g ^.'icU cause instantaneous ope. ation: • fr -i: Short-Time Current Tests The operating duty for determining the. inter rent trip devices, current values in excess of the ' Interrupting ratings of Federal Pacificvak circuit breakers are shown in Table No. 1, page 16, ;J Rating {Duty Cycle) For circuit breakers with 'direct*acting overcur - bands associated with selective trip device's, A. Operating Duty for Determining the interrupting The interrupting ratings given in 8(13-3.05, are based on direct-acting overcurrent tripping. .y.. The interrupting ratings are based on the maxi- r instcn'rr.suus Overcurrent Trip Devices for Fault ' mum, intermediate and minimum short-Ume delay- Determination of Interrupting Rating breaker. ^ \ 7' ' ' C. Inlerrupling Ratings for Circuit Breakers With an interrupting rating to a circuit breaker include the stored electrostatic arid tnagnetic energy of the system, the re-establishment of an arc under tran sient voltage conditions, the decrement of the systems, and other variable conditions. These condi-' tions are considered as not differing widely in aver age systems and are to be taken into account in the -. factor of safety employed hi the rating, of (he circuit •^n ' b. 75 per cent of the interrupting rating, or c. the short-time rating, C. Conditions breakers. J.V— •• - ble of carrying rmed continuous current wiiiwut^^i-^rik exceeding tne rated temperature ribe OpUs 'yariOu^ X^Mff^f^^ parts and shall be capable of meeting its irtierrupt<^• ing rating. Short-Time Duly Cych ' The short-time duty cycle shall consist of rnalri-. taining rated short-time current for two periods of- - :• -t', one-half second each, with d 15-secorid interval of zero current between the one-half secondi perfods,'. 'rT Short time ratings of Federal Pacific air circuit breakers are shown in Table No. 3, page 17. Applic.%tion of bre.akers and series trip devices, where trip ping is delayed to provide selective tripping, is further discussed on pages 11 and 12. MSCHAWSSMS When the breaker is closed full contact should be established quickly and positively. This is required since hesitation or slowness oil closing, particularly when closing the circuit breaker against' a short cir cuit, causes excessive arcing, consequently burning of the contacts, and other danjage to. the breaker. When closing manually, the operator may hesitate or be un certain m his efforts to close the breaker, giving rise to the conditions described. To insure greater safety, as well as ease of opera tion, the following limitation recognized by the AIEE and NEMA applies to manually operated breakers: •rating shall be electrically operated from a remote position only, to provide protection for the operator when closing against fault current. 1. Direct Monual-Oporatins Mechanism Direct manual-operating mechanisms arc inte^al with the breaker, structure in DMB15, DMB25fl, .'•'I DMB50 circuit breakers. The operating handle of '^e . mechanism protrudes through the dead front panels' or the doors of the metal encldised drawout switchgear units, depending on the enclosure. 2. Electrica! Operuvlr.g Mechanisms Electrical Closing of DMB 15, 25-1 and 50 circuit breakers is accomplished by a solenoid actuated mechanism. The solenoid is controlled by. closing the control lelay provided for this purpose.' COS^TKOL CLRCUJ7 POWER The control circuit must have a reliable source of Manually operated circuit breakers shall be limited to applications where the interruptingrequirements do ot exceed 50000 amperes and where tripping is in stantaneous for current above 15000 amperes for dead-front and enclosed breakers or where interrupt ing requirements do not exceed .10000 amperes for power for successful operation of the control .cdmpo-nents. The control circuit power source ^oiiild be independeni to the degree that the voltage is main tained constant, particularly when fault conditions are encountered, and should never be allowed to fall be live-front breakers and rated cpntinupus current idoes low the minimum value required for successful opera tion of the components. not exceed 1600 amperes. For selective tripping, man ually operated circuit breakers shall limited to ap plication in which delayed tripping requirements do The following table lists rated control voltages and minimum and maximum ranges. These voltages are not exceed 150*00 amperes. Allcircuit breakers sub to be measured at the terminals of the various control jected to fault currents in excess of their interrupting mechanisms with full operating current flowing. FEDERAL PACIFIC AIR CIRCUIT BREAKERS Rated Control Voltages and Ranges ' Ralod Control :• ' • closing Voltage Range, Volts If TrippingVoltdgo Voftogo, Volti Control Devices voUt' Solenoid DIRECT CURRENT* 24t • ' • i;14-30$ 125 90-130 250 . 180;.260 . \ 115 , . • 95-125$ / 230 190-250$ • • 28-60 .'v- •• V 70-140 • ; - 90-130 . , • l40-280-;,y;;; 180-260 alternating current .460 . • • • 380-500$ • 380-500 '95-125.- '• •i96.2'5ov;.'^":-^''.': •- 190.250 " 380-5(10 • ; ; . 124-voU tripping is not rtfcommcnded. i Lncludes heater circiiits. "• Control'iroih'exciter circuits is not recotatr.endcd. 4 ' • ..... •• " fr. f hr'l ; r.*-* '>? i;. »cry- .•^•^ / '•^ •' 9 \'' t 'W Ww , • i;.. :, <\.<,:::yyti!.'r -\ ./ hMii ifj THIPPS^iG DHV5CES Tripping ''evices in DMB breakers have two dis tinct functions: a. To perform the normal siyitching operations either manually or from a remdted source. b. To protect the circuit when abnormal conditions, exist. The normal switching tripping o^w ^I'w-i is .-erformed by a shunt trip which is energized by a con stant potential source. Automatic protective trip is of three types; undervoltagc trip, shunt trip, and overcurrent trip. .t 1. The undervoltage device is a spring mechanism retained by a shunt holding coil. Upon a re duction in voltage, the mechanism is released to trip the breaker. 2. The shunt trip .device is energized from a con trol source thpugh an auxiliary sv/itch which is closed when the breaker is closed. The con trol source may be from a current transformer in the main circuit. 3. The .series over'^^ritu: trip device is in serjes with the power cucuit and is actuated by the main circuit. A more detailed description of various methods and their associated systems follows. J4c-'das . .. .:.'>^n;vi*.-- r; •.•• v-kcs^ ... • •. - tMS /-\ • •- V' T. • • .iS • ~-'^i"- |l h-4ar" ^^ 'C • •• SnilSE-3 OVE.^.Cb"E2.«l£?^5T TRIPPING :^lte DEViCS 5=OR prv^215, DMB25-1. DJyIBBO The .series bvcrcurrcnt tripping device consists of a current to the time indicated by the curve of tlie band series coil and a magnetic circuit with two armatures; specified at 600% of the pickup current. The linkage between the armature and the timer isa heavy factorysetspring (E). Depending on thesetting of this spring, one activating a long tinie delay, escapement mecha nism and the other ,a short-time delay ^escapement mechanism. These armatures, though inthe same mag netic circuit, act indopehdently at selected currents to trip the circuit breaker. Instantaneous tripping may be used in conjurictLi. with either long ime-delay or short-time-dcliiy. The long~iime' changeable from one interruptiiig rating to another,.; Table No. 3 shows permissible interrupting rating'''! range of various series, trip coils. O The long-tirae.^elay curves am shown .as the sum-; Sir v mation of the tripping device timing plufthe brisker clearing time. The broken line below the operating" / 3. insiantaneous: curve indicates the reset tiihe, i.e., the maximum time for which the overcurrent can be maintained through; . Alone or in combination wiUi the shon-tiine-delay and/or the long-time-delay. Available from 8-15 times the continuous current rating of the trip coil or in special .settings, but not exceeding 90% of the inter-: ruptiiig rating of the breaker. Unless otherwise speci fied, the standard setting of 10 times the trip coil rat ing will be supplied. the series trip device without ultimately tripping ,tlie breaker. If the current i? instantaneously r^uccd tO; and maintauied at 80% of the Jong time delay pickup current, ai or below this broken line, the tripping' device will automatically reset. The short-time^elay curves are also shown as the TABLE Typo of Broofcer TifflO Characteristic DMB-IS, 2S-t,S0 Inter. Max. } V»' ; '' Time-Current Characteristic Curves r V . A Lowor limit of bond ti Pickup Toloronco « 600% of Pickup Seftiho* M!n. 5 seconds • 15 seconds • ' . . 30 seconds • Field adjustable from 80 to 160% of trip coil rating. TABLE'-B Typo of Breokar DMB.15, 25-1,50 Time Choracterislic Pickup Toleranco ..Mox, ±10% tpler. i 10% MIn. ± 10% . ; • "•'Field adjustable 5, 7'/i. and 10 times the trip coil rating. t Th- • : lower liliiii of Kfrnd p!: ;. 'V .250% of Pickup Sotlinoy^'.. . • , '21 cyclos . ••••••, , 14 cycles • .7 cycles" ".v.;-,. !• , 'cr limit of the band is the time for which the overcurrent may persist at the given value and thea drop til BO percfcht of ,, .•kc long time delay pickup current without tripping the'circuit breaker. (See Curyesi, pj&;>s j «->rt . i. t The lower limit of the band is the time for which tlic overcurrent may persist and then drop' to 20 per cent of the short time delay: pickup current without tripping;the circuit breaker. Bunds are factory set. (Sdc Curves, pages 8 and 9).' . V -T. rr-T-^r... i .M: •••', ' ::'jO -Uii ••• «M£ KESSTfASU OEIAY- L. NOTE:— Soric« overcurrant trip eoili. hove . INSTANTANEOUS SEHtNCS F20M 3X TO 15X TRIP COtl HATING odiuttoble foclory cdlibrolod lol- tiiiEIs oi from 80% to l60Va of coil rating for long- ' time doloy • pick-up ond from 5 limet to 10 llmai coil Votitig for »hor! time Qoioy picK-up* INST, TRIP SKOV/N AT lOX TRIP COIl RATING - /fii- NOTES— l.ong.time-doloy arid initontoneout tripping (hown ore nofmolly supptiod In oil DM& Air Clreto Dreokeri. For lalocfiva tripping appllcotiont, the chorl-time-deloy shown it supplied oioner or in combination with Ibhg-limo.delayi or In. combinotion with inttontoncouj tripping) or in combinotion SHORT TIME RESETT. OEUY with long-time-delay ohd instanto- neoiit tripping. Type, of tripping jk •ym' CURRENT IN ..Mis nATiivw Cr li.iiiwS TRIPPING DEVICE Typical Dual Selective Overcurrent Tripping Curve 'W^.yakmm ':'; , i^;.V(:r'• vv;..-,, ~•'iyfrfl:i.ir}^ j // i: i.'jV • • : f'-.-r"- •'( ••..•«! • * . •[, •• V*Xi Time Delay Curves '.: * • Nema Standard SG3-3.25A • "• .^..• * _ -i";-. •• • / I CUKVf AXIMUM NOTEi THE PJCK-Uf CURRENT SETTING FOP. EACH BAND IS ADJUSTABIE TO 5, ^Vj, and 10 TIMES THE RATING OF THE SERIES OVERCURRENT TRIPPING DEVICE, f- Shorf-Time belay Curves Nema Standard SG3-3.2Sa ^->' •v'V r^X'i ^ ^ ^ -jp- tf«Tj ^e^fionr^soc^ e>? ijoitlw suiTJ-nation of the timing of the tripping device plus device, resulting in the subsequent tripping of the circuit breaker with which the trip device is associated. the breaker clearing time. The broken line below the operating curve indicates the reset time, i.e., the time Cajibravion: • for which an overload may persistthrough the device • . Circuit breakers with adjustable overcurrent trip without ultimately tripping the breaker. the current is instantaneously reduced to and maintained at 20% shall be calibrated at 80, 100, 120, 140, and 160 per cent of their continuous current rating. The toleiaiicc of the shoft-time-delay pickup current at or below this line, the device will automatically reset. shall be plus or minus 10%. Overcurrent trip coils shali be selected so as to Both the long-time-deiay curves and the short-time- vide the minimum trip'setting required. v- delay curves are average curves pnd include the varia tions between individual units, the manufacturing tol erances, and the differences between single phase and Short Time Delay Pickup:' * Shall be set at 5, 7'/z, and 10 times the ampere three phase tripping. ' rating of the overcurrent trip coil. .- Where palibratipn adjustment has been set so as Series Overcurrent Tripping: Trip coil in series with main circuit! to-co-ordinate devices properly in a selective system, the calibration-should not be disnirbed for. proper operation of the system. ' " ; trip coils, in amperes, is iishovm. in Table. No. 2,, ' DEFINSTI0N OF TERMS Functions above a predetermined value orcurreni:!fepC • without any purposelydelayed action. . shall remain closed and continue to carry the remaining ic^ly reset when tlie current is reduced within a pre- r-V ' - scribed time to a value within the rated continuous current. breakers nearest the source of power shall have inteirupting ratings equal to, or Inexcess of, theobtainable . fault current and where one or more breakers further Dual Selective Overcurrent Trip: removed from the power source have interrupting rat ings less than obtainable fault -it the point of a selective overciinent trip. " - i i Combines the function of adelayed overcurrent trip • ;' ; : •t • ' DETERMINATION OF SHbRT-CSRCUST • CURRENTS: A qualifying terra indicating that no delay is pur- ; .: '''V;- Low-yoltagc air circuit brcakcrs'are toapplied posely introduced in the action of the device. Pickup Currem: ' •with which it is associated, and which will automat- v .- The application of air circuit breakers in which the • ' the rated interrupting current of the circuit breaker load current. Cascading: _ Vrf'!* Selective Overcurrent Trip: • Functions with a purposely delayed action at ali ' : ' values of current between a predetermined value and current conditions and the breakers nearest the source Irtsfanfaneous: ^ Dual Overcurrent Trip:, Combines the function of a delayed and an instantaneous overcurreni trip. breaker nearest the fault operates to remove the over- application. . i Functions above a predetermined value of » current with a purposely delayed action. The operation of circuit breakers in series so that, of the breakers carrying the fault current, only the .!. :,: : • Delayed Overcurrent Trip: SelecHve Qvercurrent Tripping: ,• " Instantaneous Overcurrent Trip: CONMUOyS CURRENT RATSNGS Continuous current of circuit breakers and series page 16. , to circuits in the usual manner by ob.sexvihg that the, "• ratings defined as stand* id a'u noi exceeded. The in- ' • tcrrupling nitings, given ji.s the .st.nntlard, as.sufhc litai "Pickup current" as applied to an ovcrcurrcnt trip ping device (for a given calibration setting) is the min the maximum .shqri-circuil current available at li.e ; point ofapplication of the circuit breaker is calculated according io the following outline. • ' imum current which will cause operation of the tripping 10" ' '' ' ' i ?: current component, i.s dcicrmined by multiplying -dz symmetrical current as obtained from the preceding (a) For d-z circuits, the current calculaicd shall be the maximum value, taking into account all resistance up to thc 'source side of the circuit breaker but not method by a factor to account for the increase in the including any of its own resistance. average three-ph.nsc current caused by the presence of the direct-current component. While this factor de pends on the X/R ratio of the total impedance to the point of fault, a good approximation is obtained by For d-c faults of 100,000 amperes and above, conr sideratioh should be given to the rate of ri.se' of the A <' current as compared with the interrupting speed and rating of the circuit breakers. the use of a multiplying factor of 1.25. The use of (b) For three-phase a-c circuits, the current cal culated shall be the average value of the three phases of the total current, including the d-c component, at an instant one-half cycle after the short circuit occurs. X/R ratio for each low voltage circuit breaker appli cation, is generally accepted practice. This factor of ^ This value is computed by.first determining the total symmetrical current from all sources, including syn 1.25 corresponds to a ratio of 11.72. (c) For single-phase a-c circuits, the current is cal chronous motors and induction motors. .Then this, total symmetrical current is multiplied by a factor to determine the average three-phase current at an in-. culated in the s.Tmc manner as that used for three- phase circuits, as tiic maximum asymmetrical current in a single-phase circuit is identical with the current '•f-G in the highest phase of a three-phase circuit. (Sec American Standard on Low Voltage Ail' Circuit stant one-half cycle after.&e short circuit occurs. Determination of Symmetrical Current. The £y.mmetrical current consists of the sum of system and motor contributions, calculated in the following .mari ner: F , ,#• this approximate factor, in preference to the determi nation of the exact factor obtained for the specific Breakers C3 7.13) THH SELECtSVS" SYSTEM*" FV; '• 1. System contribution is determined for all sources .When service to a number of circuits'is to be and all impedances up to the source side of the circuit breaker, but. not including any of the circuit breaker impedance. At 600 volts and below, even small im and protection to all circuits must be provided, the maintained, despite a faiult in any one of the circuits selective system is applicable. In Figure .1 the main pedances should be taken into account as they may breaker A, the tie breakers B, and the feeder breakers greatly affect the result. 2. Induction and synchronous motors connected to C are between the source and the loads. In the selec tive system, a fault at any load will trip the feeder breaker C which is bettveen the load and the circuit , the bus act as generators, and at one-half cycle after the short circuit occurs, cphtributc current which may tie. breaker B, The remaining loads, however, will still be calculated from the subtransient reactance of the^ GGGG: /IF"' ..A motor. Where the reactances of the motors are not known, values are assumed for induction motors of 3.6 SOURCE times motor full-load current, and for synchronous - motors of 4.8 times motor full-load current. A -A-y'U' •; I" •v-v- vf When the motor load of the installation is not known, assumptions may be bPsed oh system voltages. 1 For system voltage of 120.and 120/208 volts, it is usual to assume that the connected load is 50 percent lighting and 'JO pcicent motor load. This corresponds to an equivaich.. »y».«.»»;a'ic£lcontiibution of twice the • , ,F.t" full connected load. • G 'v- Gc For system voltage of 240 to 600 volts, it is usual to assume that the load is 100 percent motor iPad and, in the absence of exact information, that the motors ai'e 75 pcrcnt sy??chronoust ahd,75 percent ind\irti/>n. This corre.sponds to an equivalent symificiricul con- :>c >0 'i: i. LOAbS LOADS tiilhidoh of four times tlic full connected load. >C FICU&E t Determination of the /Symmetrical Current. The asymmetrical or total rms current,^including the direct- '* Selective trip and short time delay app'dcaticns limited to ' 'V ,i -. inlcrruptins current ratines shown in table No. 3,. Page 17.^^ . ; • -j; .11 'V. , , /•""'V ' ."i '•• , • , .: '"n . » V y- , ,• .i Ui< be fed even though the faulted circuit is cleared. This element. is accomplished by "delaying the tripping time of the Note: Attention is directed to the fact' that opera tion of selective tripping requires coordination with tie breaker B to the extent that the feeder breaker C therest of the system. Asan example, the low-vokage side of a transformer bank requires that, in the appli- serving the faulted circuit, will clear the circuit before B trips. Correspondingly, the tripping time of the calion of relays or fuses on the higli-voltagc" side, main breaker A is still further delayed so that in the event that any tie breaker B clehrs the circuit as the result of an overload between it and the load, the re maining tie circuit is being fed. All the breakers in the system are timed so as to protect their associated circuits and to trip in suihcient time to protect the breakers themselves within their respective interrupt ing capacities. The following arc requirements for breakers in a selective arrangement, as outlined in the American Standard on Low Voltage Air Circuit (• ! proper coordinating steps should be taken. Examples of application of Federal Pacific air cir CASCADk system* jf • • • Although the selective system is the best recom Requirements for Circuit Breakers in Selective mendation in all cases, there are applications where it is not feasible, economically, to use feeder breakers with full interrupting, capacity at all loads. Iii such cases the cascade system may be employed. This Trip Arrangement means that only the breakers nearest the source of power must have interrupting ratings equal to the Properly selected air circtiit .breakers may be ap plied to low voltage circuits to obtain selecUve trip ping. The following requirements shall be observed: average total calculated rms current, &d stated for breakers between the source and the load.. Breakers further from the source may have lower interrupting ratings. The following are requirements for breakers, in cascade as outlined by the American Standard on (a) Each air circuit breaker must have an in- terrupting rating equal to or greater than the available fault current at the point of application. • /'V • ' • Low Voltage Air Circuit Breakers:— . (b) Except for the one farthest removed from source of power, each air circuit breaker must have a short-time rating equal to or greater than the available current at the point of application. Requirements for CircuR Breakers in Cascade Arrangement Circuit breakers are considered lb be ..in cascade (c) The iime-current characteristic of each air circuit breaker, at all valu^ of avaflable overcurent, shall be such as to insure that-the circuit when a plurality of low voltage air circuit breakers are connected in series in a distribution system, and the circuit breakers beyond those nearest to the source are applied in the following correlated manner. breaker nearest the fault shall function to remove the bvercurrent conditions. Hiose nearer the source In this cascade arrangement, circuit breakers toward shall remain closed and continue to carry the ro- thesource arc provided with instantaneous tripping de vices for current values which may occur for faults beyond otlicr circuit breakers hearer the load. Hence, mainmg load current. (d) To insure that each circuit breaker shall function to meet these requirements, the time- circuit breakers in the series other than the circuit currcn} characteristics of associated circuit breakers breaker closest to a fault may trip and interrapl loads on other than the faulty circuit. SaCL< hijraagements are used only where, the consequent jpossiblc sacrince. in service continuity is acceptable.. must no* tvviJap. The pickup settings and time de. .* cuit breakers on typical selective trip systems are given in Table No. 4, page 18. f . Breakers:— O -'0%. Jay bands of ooth tbe long-time and short-time delay. elements must be properly selected. (e) Manually-operated circuit breakers shall be (a) ""Cascading shall be limited to two. or some limited to applications La which delayed tripping times three steps of interrupting rating. requirements do not exceed 15,000 amperes or 15 fees vvip-f.-i>i; mting, whichever is gre' ici, • 1. The, interrupting rating of a circuit breaker or. breakers nearest the source of powershall bo cqual to (f) The time-current characteristic: of circuit at least 100 percent of the short-circuit current as calr". culatcd in accordance \vith preceding paragraphs of breakers in a selective system shall be such that four circuit breakers may be operated selectively in scries when required., One of these shall be a load ;v... this guide. The circuit breaker or breakers in this Cascading at 240v. and 4S0v. maximum intcmipling ratings circuit breaker equipped with an instantaneous trip is limited to two steps of .intcmipting' ratinj. t •? . ii'i.'i - . I." •; • >7* « ® •. 13 ^'.-•'\y~'* " i «• U Wft '"-7 »' •..' /!'••/"• i!" I.* k ' • • ♦ ' to voltage, current, and interrupting rating, previously, step shall be equipped with instantaneous trips set to trip at a value of current that will give back-up pro cited herein. tection whenever the circuit breaker in the next lower Ser\'ice Ci.cuifs (Sections 2351, 2354, 2356, step carries current greater thaix 80" percent of iis in terrupting rating. ' . " 2357, 1953 Code) 2. The circuit breaker or breakers in the second step shall be selected so that the calculated short- circuited iurre.nt through the first step", plus motor con The NEC Rules require that "each set of serviceentrance conductors shall be provided with a readily accessible means of disconnecting all conductors from the source of supply." Air circuit breakers approved for this application are specified-as "manually opeiS able, .... equipped with a handle or lever for me chanical operation by the hand." A push-button type of electrical remote control ihay be used in addition tribution in the-second step, wUl not exceed 200vpercent of their interrupting ratitig. For the second step of a 2-step cascade, the circuit breakers shall have an instantaneous trip set above the starting inrush- current of the load. For the second step of a 3-step cascade, the circuit breakers shall be equipped with instantaneous trips set to' trip at a value of current .that will give back-up protection whenever the circiiit .breaker in the next lower step carries current greater thait SO percent of its interrupt ing rating. • , . • . 3. The circuit breaker or breakers in the feird step electrically operated breakers is permitted if the breaker can be operated manually, in case of an emer gency, by means of an. operating lever. Such a lever is available with Federal Pacific electrically operated breakers. An enclosed breaker must be "externally operable," or capable of being operated without ex shall be selected so that the. calculated short-circuit posing the operator to contact wltii live pafis. The current through the.first'Step,.plUs ntotor contribution ofthe second and third step/"will not exceed 300 per cent of their-interrupting rating. They shall have in-., stantaneous trips set above the starting inrush current of the circuit. - ,• » oi,.' (b) All circuit breakers.subjected to fault currents • in excess of their interrupting rating shall be electri cally operated from a remote position only, to provide" protection for the operator when closing against fault current. *♦ (c) Where cascading is proposedi recommenda tions shall be obtained from the Gompany in order to insure proper coordination be^een circuit breakers. Molded case circuit breakers not recommended for use in cascade. (d) The operation of circuil^breakers in excess of their interrupting rating is liniited; to one interruption, after which inspection or f^iacemeni may be re•'quired.'.,' ' ; . " ' • • Examples of application of Federal Pacific air cir cuit breakers in typical 2-stcp cascade systems are given in Table No. 4, page 18. (i: -. MATSOIvJAL EISCTRSCAL CODE 1953 The iT'er of the National Electrical Code cited here are those which apply specincidly to air circuit' breakers and air circuit breaker application. These rules refer to the number of pOics per breaker, the to the manual handle. This means that,the use of Code recommends that a service circuit breaker shall have a rating xiot less than 50 airiperes. ;. The requirement that ,each conductor be discon nected means that the breaker should lie supplied with as many poles as there are conductors-;- Jt further specifies that "each ungrounded service-entrance con ductor shall have overcurrent protection." This means that for a three-phase, three-wire entnmce circuit, a three-pole breaker—each pole having an overcurrent trip device—^will be required. The code also requires that "not mprc than six cir cuit breakers may serve" for the service-entrance pro tection, when these breakers are "in a common en- closure, or in a group of separate enclosures, located at a readily accessible point nearest to the entrance. of the conductors, either inside or;outride••the btiild- ing Wall." This means that if there kre notimorc thah,; ••'x feeder circultf the fceder-cir^rit bjeaker in babh' circuit will also serve as the service brcake^i'.: Ifi iMcTt case, each breaker must be considered as an incom ing-line breaker, and must be provided with an over-; current device in each ungrounded conductor". If there are more than six feeder circuits, there must be a separate or main seivit . >r.-.aVe<'. . . The object of the limitation is to provide, under the condition of a common "available space,";not more calibrnliuii of overciirrciU devices and the location of than .six circuit breakers, which Would have .to be breakers, etc. Ucfcrcntcs to the Natiohal Electrical operated to cut oil the entire system served fespecially a residence or oilier building). , , Code arc not a modification of the rules, with regard • 'I '.V • "T*. r». ^ '/T'^» ip^ L-V'-! • i - ' .... •"••—' *• - .- • np -! *'; •••> /t-r :?r. fftfh .r»n \\ ->, % 'iiO /^i.'.'- r'a /^.rr> *1 "that where the overcun-ent protection' specified in the table isnot sufficient for the starting current of the . Feeder Circuits (Sections 2403 and 2405, 1953 Code) motor, it may be increased, but shall in no case ex- The general requirements' for circuit breakers and feeder circuits are that each ungrounded conductor be disconnected when the breaker opens, and that therating of the overciirrent trip device be as follows: Adjustable-trip circuit breakers of the time-delay, magnetic-trip tj'pe, or of the instantaneous-lrip type, shall have a setting of not more than 150 per cent of the allowable carrying capacity of the conductors. Motor circuits are exceptions to these requirements. For motor-feeders, (Section 4362, 1953 Code) the circuit breaker setting "shall not be greater than the ; ^ largest rating or setting of the branch-circuit protcc- ! v ! live device, for any motor of the group (based on ; Tables 26 &27, Chapter 10), plus the sum of the full-load currents of the other motors of the group. '^i; "If two or more motors of equal horsepower rating are the largest in the group, one of the motors should be considered as the largest for the above calculations. . "If two or more motors of a group must be started Motor circuits are classified as "motor feeders" and simultaneously, it may be necessary to install larger ' feeder conductors and correspondingly larger ratings or settings of feeder overcurrent protectibh." Power and light loads. If a feeder supplies a motor i "motor-branch circuits." A motor-branch circuit may serve only one motor or it may serve two or more motors. For an individual motor, "the motorrbranch-circuit overcurrent device" (that is, circuit breaker) (Section load, and, in addition, a lifting or a lighting and appliance load, the feeder circuit breaker should have ; 4342, 1953 Code) "shall be capable of carrying the a rating or a setting sufficient to meet therequirements; f starting current of the.motor. Overcurrent protection shall be considered as being obtained when this over-. of. the motors [a sin^ motor (Section 4342) br: ai group of motors (Section. 4362)], plus the normal load current of the lighting and other loads. (Section 4363, 1953 Code) current device has a rating or setting not exceeding the values" given below: Single-phase "Code Letter A" (where the. Motor controllers. From the Code "the term 'con locked rotor current is not in excess of troller'-includes any switch or device normally used to start or stop the motor." (This.refers to devices con 3.14 times the normal current)... 150% Single-phase "Code Letters B to E" (where the locked rotor current exceeds 3.14, but nected in the main circuit.) is not more than 4.99 times normal cur • "A branch^;ircuit type circuit breaker may be used 200% as a controller. When this circuit breaker is also used Single-phase—all other ; ; 250% Polyphase squirrel-cage and synchronous motors wito full-volmge, resistor or re for overcurrent protection, it shall conform to the appropriate provisions ... governing overcurrent pro tection." (Section 4383d, 1953 Code) actor starting: Section 4331 (1953)—^ RATING OF PROTEO^ "Code Letter A" (locked rotor current not exceeding 3,14 times normal cur rent) TIVE DEVICE. Motor-running ovefcuhrent de- •' 150% vices other'toan fuses shall have a rating of at Vleast 115 per cent.of toe full-load cuncni rating 200% 250% Section 4347 '1953) —RATING OF CDUiJCJrr- ^ "Code Letters B to E" (ioclm(l rotor of the motor. current exceeds 3.14, but not more, than 4.99 times normd current) All others v cccd 400 percent of the motor full load current." Motor Circuits (Section 430, 1953 Code) rent) •>. ^ BREAKER. Circuit-breakers for motor-branch- Polyphase squirrel-cage and synchronousmotors with auto-tiansformeis starting ' circuit protection shall have a continouous cur-} ^ rent rating of not less than, 115 per cent; of the: "Code I.etter A" (locked rotor current not more than 3.14 times normal) ....150% All/others j 200% Wound-rotor motors ; 150% ifuil-load current ratings of. the motors. ^ Section 4403 (1953)—CARRYING CAPACITY ' ; AND INTE^-PTTNG f. • a. The disconnecting means shall have" a carry ingcapacity of at lca:>t 115 per dcrlt ol the namc- Direct-current motors 150% An exception to the settings specified above is plate current rating of the motoi*;: •. 14 .T, ''iX /V. I* :•* * 1 ' - (; •. • V • ^11= i-i-'iCia'siC. :A - ' "-J; b.) i- - L2ALc:ii!^s:. . .. The following tables show standard and Optional A large number of accessories arc available for use with both manually and. electrically operated Federal Pacific DMB breakers.-^These-accesories are factoryinstalled in the'breaker; aid .wired and tested to per form correctly their function within their rated ciperating.range. Rated control voltages and ranges are tabulated on page 4. accessories available with the various sizes of DMB ^ breakers. These accc.ssories are available-with draw- '' out type or fixed mounted (stationary-type); breakers used in metal enclosed switchgear and also witli indi-' vidual, wall mounted DMB circuit breakers. I STANDARD ACCESSORIES 1. FEDERAL PACIFIC CIRCUIT BREAKEKS . Operating Mcchanltms DMB IS DMB 25-t Eloc. Man, Man. Man. ' Elec. D.Ma 75 DMS'tOO DMB 50 Elecincoi Elac. . Duol-mognetic time over>currenl .;v" Irlp dcvicoi—one per polo Manual Trip Poiition lndi(alor .....i.....,...™., Tsrminol Conneclori ' : .. . motntalned contact control Padlocking ProvUlon ' .y . Shunt trip device 4 circuit : X X X X X X X X X . Attached Monvol Cloiing Hoiidle Electricat Clodng' Mochaniict Qoiing relay willi cut ott, teol-ln and anii.pump (eoluret for X X X — • X X X X X X X X X • — X . X X X X X • X X X X X , X - ,x X X X • — X _.A-.. • X •' .. X X ; X,-::; -• :.x; ' X ' Auxilloty Switch ' X —- ^— . X ' ;x V' X )<^9>ptional accessories —-y ' Auxiliary Switch 4 or 8 Circuit! ...... Undervollage device—Initantoneoui • X or time deloy OvorcurrepI bell alarm—band reset Key Inlerlocfc X X X X X X Shunt Trip Device—4 circuit ouxil.iory switch X OvercurrenI lockout device—lio.nd reset ™..... — Eleclricoi lockout device Key lock .... •" Closing Swi^h (mounted or unmounted) ...... • • ' Field discharge contact Copacilor trip ' X X X X Xr X - ~ , x •' •' ..k . „ - X X • x~ X - X • X X ^ _ !. X X X X - __ — • • • • . X •X ' X • X JJ — X X X X X •' ^X-:X X X ' X - 'X X - X' . (, X •• X X ^ c-;.5- - 1 OOT • X; •" X X X ... • X X X X • X - 'x _ X X X •'X:?" '. X, • "X"' • X . X SERIES OVERCURRENI TRIP DEViCES • b- • long lime deloy ond in'slantcineous (standard) long lime deloy. only toptionol) long time delay and X X X . * • k Any combination of long time delay, - X f X A short lime delay, ond inslan- loneovs tripping or ony one . • ..... X X '- X - • .-•"-ixm x';,: , ( .X X k , •' 'X X X • '-'-i ' X' •• ' X X r X. i short time deloy (opt'onol) pt these alone (optional)- ' ' X r.- ; ^-;X j- ' '. .• r- X ,, NUMBER OF CONTROL CIRCUIT COMTACts AVA«."i3LE Vi.. r.--J /y Qrvokort OMB ^i^wijiory Swilch .... CoftJocU; tS 4 12 ftr 8 • 24 • 0MB 35-1 4 or 8 J2 or 24 . 15 DMB 50 4 DMB 75 or 8 12 or 24- U OMi t oo; to 10 o 26 , AOOO^A16 Or.'32 • .. ... 7 ; • •, •;• ; ,r -"••• • • V. :p. r. .INTcJJSUPTiMG RATUMGS OV • ;.V •. ;-ACi?iC AIR CISCUIY ni;jsAKe2is These Currents Calculated in Accordance witli AIHE and NEMA Standards. INTERRUPTING RAVINGS OF FEDERAL PACSrlC D.V.3 AlR CIRCUIT BREAKERS f • .• •, .• -• t , SEIECTIVH SYSTEM • CASCADE SYSTEM .Ciicuit Srookcr Vollage R 481.400 25,000 40- 400 90,COu ,481.400 90,000 200.1400 100,000 79,000 3000-3000 100,OCO 4000 - 0MB 90 . DMB79 4at. 250 300 350 400 300 400 800 X ' i - i . •' • [X 1,200 Lf22 - •• , 1,000 .... •; • .i;V4 yyy 2,000 2,500 . a.coa , 4.000 . vv tiliilii TV-,'"; . Tho values undorltned ore continuous ratings of circuit breokore oxciutive of serins trie coils. .: • :• •Id 4-r 4'7 4'-4''i'7^4V7;5;7'.-. i, •^V>'i''Vi; i» }*V.. ',»a u SHOi^T TIME AND SclKCriVE TRiP RATi:-viGS O? ?-:DlRAL ?ACmc CiuCUlT B^lEAKI^;;.: These Currents Calculated in Accordance with AIEE and NEMA Standards. Froquency—60 cytlat Maxiffluffl Design Vai'n£|n~~^26 Volts Dlotoctric Wilhiland Tost Voltage—2200 Volts Conlinuous Current Ratings, Amperes Fodoral FaelUc Air Circuit Breakers Rating 3 Phase, Amps Shorltlrao Rating, Amps ' Coil Ratings Applied if V-^pping is Delayed to Provido Soloelivo Tripping® Mox. Current Series Trip Ratng Coil Rating' Minimum Time Band Intermediate Maximum Time Bond Titno Bond DMB 15 15000 15000 225 1510 225 100 to 225 125 to 225 DMB 25-1 25000 25000 600 40 to 600 175 to 600 200 to 600 DMB 50 50000 50000 1600 DMB 75 75000 75000 3000 100000 100000 4000 DMB 100 V Interrupting . 200 to 1600 350 to 1600 400 to 1600 2000 to 3000 2000 to 3000 2000 to 3000 4000 4000 4000 - . ' 150 to 225 . 250 to 600 500 to 1600 : . .'••• 2000.1ft 2000' • 4000 .. 1. If ttripping instantaneous above 1500% coilrating for DMB 15, DMB 25-1 and DMB 50; 1200% for DMB 75 and DMB 100. 2. On currents above 1500% of coD rating for DMB 15, DMB25-1 and DMB 50; 1200% for DMB75 and DMB 100. •, ' .! •ii: V; • • If • •• , ''' i\ • • • v.. •.5- • - •- C- "'Wk )7 • >>y - 'V;. . . .y, ' *1 ' ' •L. 4. ( ' p, -l.i- rrvfv^ . » <9 . . 's** 6r"i x' f. '< . c; ^CUIT CUSSi2!NST AP?LICA.TJOM[ SHORl BrsSAKES TABLE nVV:-'' • Tiemfftint) ,'• .. •. ' tfliifiBS-pfe KVi^ciuf « f*rt$nl Shert^ircult C'J<'6r.l MoK-Stmrt. 1N«'me CrcvliKVA l»ed Tdia) PlMS A/v^e'et {Averaj^a 9*^hD» Acnp. UATlU SYiyjM Sr»>«m hn«i«ui CvrrvAt Arnp* . fdrmtr 'Alen# SXXXi Molo l90& IMOM 16690 «% 2^0000 194 200CO jOOOCO Unlim'ted wooo MetA Ctt^nd* Fe«d»p Bf«al.er Feeder 21700 OMS DMB DMB 221CO 50 15 50 2190 29990 30500 2080V 22400 22600 33400 s% 2i£000 93900 36600 50OCKJO 34000 37600 UAllraTti j 34600 38100 $l/a% 250000 3500 37100 50CO00 5C400 35000 DM6 36C90 M COO Fi"! -i-r D«S 15 ,(30.225} ?n 50 . 0M8 DMB . 25-1 50 DMB 75 15 (30.728) DMB » (690.1600) DMB 50 1693.1600) .53390 604M eM.6 63300 25 i$OOQQ 250000 50700 6sm 9COCOO 609CC 67900 7000 63290 70200 61100 71690 74300 105OO 65200 15 0MB DMB'25-1 (150 600) 59400 DMB 50 DMB (30.225) .DMB 25.1 (150-600) '46309 500000 DMB 25-1 5GCC0 60190 ; Se'eet.'r* 50 75 52300 4160 Fv(ly*BA'rd Main [ . 5 DMB DMB 35-1 (150-6W) DMB :S-1 (1W.6C0) 1000 lOOOOO licocc 250CO0 . IS 0MB 51300 5OCO0 DMB 44m 56300 F a DMB 48500 461C0 9TW M (39225) . (150.909) 47900 1««>00 'rc' SfLCUIVt STST(M • C 4^:e90 SVi'A ISOO SVa% (30-225I 42300 41600 43390 Por4r>t))e^:t ( 1 • '' ' DMB 227CO 32500 2DI0 M w)(h90) (tX.aOO) DM6 » DM,3 X DMS 59 DMB SO (600.1(99) DMB 75 DMB 50 (633.) 403) DMB 7.* DMB 50 DMB 75 DM& 25.1 (150.600) DMB DMB 25*1 050.600) DMB 25.1 0M.6C0) DM6 25') (IX'600) 75 OmB DMB » * 76 (690.1690) 0M3 ?S 1 OX.dX) Ma MoU Availebl* 6^500 . DMB » (609.1 £09) 90600 94500 DMB 35.1 DMB 25.1 OMR 25-) OMi 2M DMB . 75 0MB 13 (30 235) 84600 93700 100900 (1S0.6CO) DMB X r6X.1&X) DMB 75 (2000.3000) Na M.^in B'toSter DMA 75 170X 3003) ArnUelile DMB75 (TOGO-aCCO) CvKbdj Tie' No MoSn Eiteohat 0M8 76 '' DMB SO (690.)(>C0) Breaker DMB 75 (JCOO.OOCO) DMB 190 Avallbble 0M5 7S (2009.:irW) DMB75 (2iKV3'3900) DMB 100 OMB 100' PrAiible !>«• No Mr«iA Avietebie DMB 73 (2030.3000) DMB 199 (4990) DMB 75 (2W0.10CD) DMB lOO (40C9) DMB 100 No B* r. Av.-iSr - ifiali. • /"' 50900 16100 IC0005 20600 OfAB DMB DMB S% 150000 17400 21000 50 18 » 250000 174C0 21200 1 TTi 17000 590000 « UaI •'Ailed 5CC90 21500 21790 1209 27300 DMB DMB 0MB 26200 34200 80 25.1 50 28700 34700 35500 Un>JfT)ii«d 30100 36190 50000 02300 190000 1604 361C0 SViV, 48000 DMB.3S.1 (1!0.6C<1) 49090 5X00 41100 50100 DMB 25.1 050.6^9) DMB 50 (6O9.16D0) 40290 S32W 46300 2405 >2099 69300 Iftiooo' 48100 60890 250000 5*000 63000 'snoo 64&X 54700 66700 500000 50000 53200 (OOOOd ?"• *C • 0MB 25.1 (150 600) DM9 25.1 (160.6001 DMB 25-1 (150.600} 37090 4/Al«(nit«d ISOO DMB 75 24 vsA. 100000 1000 45109 46600 5W>» 50000 sya<& . (150.6001 41390 7900 07600 OfttlfAllFU I*..25CCOO 5COOOO .'• DMB 75 » - •- v -^r DMB 75 DMB M DMB DMB 3$..l (IX*6C0) • DMB « 75 DUS 75.1 <15^.'^) OMB X i)M& \S i 30.235) -"S.* f)y> iOO; OmV X r-'l i, \ 060.600) D/4A SO DMB SO (600')<;00) DMB 7S PMft DmB 25.1 (VM.rWi •DM8 .'75 :. OMB X - 75 (600.1600) . DMB 50 (600-16M; :w 74000 VJ«0 0MB 75 (;iVy50XO, . 77790 75KiO DMB 76 DMB 75 (2909.30W; DMB 75 : 0M6 M DMB OMI 73 120O3.3f<») - • DMa 25.1 rtX'603) 0M8 75 (20W.3090) ' i- '•'W- DM3 2M DMB 2S.) OSO./rOO) 18' •' SO (.150 600) <30-225; I60V.1600) I - 15 lor 109003 Dkiii, DMB " 25.1 DMB25^1 050.600) DMB DMB 62939 SO DMB 15 00.225) DMB 71200 18990 DMB (5 75 075- { ,11.1 OMB 25 1' 15 00.2251 DM.B DHB C9S00 64590 Dii^B 50 (90225) 025X 1 960? DMB IS (30.225) 33390 27500 150»0 t».:2S) DMB 31709 6000 2500C0 500000 750 1 *7600 IBIOO 150000 sv. - 3500 25100 100000 SCO « 17700 904 DMB 25.1 DMB . 100 DM6 ibo Om8 75 UvrOsiiyrfJ: . UMB 75 (JV'J. (IX. 600] ' /I rrVJ' Mi7 T.i Trr-..! nr.. *•"-> \ii-i • lr;A6 ; frwe / i yn ^ ) fwllyKoud 0M3 20600 150000 8teek«« C M M Ma»A tfo(i»nlb»th( ). SEUCTIVC 8YSTIM CASCADE SYSTEM PUtLY'RATCD SYSTCM 17500 2CQC0 10C0CO 1500 3000 20500 100000 1000 SVi% . 1*. J nCOMMEKDED ffoe?!.'! ?AC[f|( A!S CircUiT EimKtil —feeder Trip KongoU Mtown wilMn iq:co I06C0 10700 10300 13100 20103 23300 50000 fi!; •, 10590 16100 16000 18800 10209 m :1'•• y. 9900 0700 $% Corn* blovd eioo COO SELECTIVE SYSTEM CASCADE SYSTEM fully-rated system rr-^rr •.»_ F f. 12000 45700 51400 56100 47700 50700 59700 62700 54700 66700 OMft 75 .DM8 30 OMO 73 (400.1600) DM3 15 DMB 14 0M6 14 PMt 14 DMB 14 {20-225) {73 2231 CO 225) (20224) C9 723) DMB 73 ' DMB 50 OMB 50 DMB . 50 DMB 50 (400.1600) DM8 53 OMB 50 DMB 75 0^3 25-) nOO 600) 0M3 73 DM8 59 <400.1600} DM8 50 (400.1600) DMB 50 (400.1600/ DM? 50 (400.1600) DMB 73 0M8 73 tCCiM^SOOO) DM? 73 (»yi.30»1 DMB 14 129-324) DMB 23.1 (lOO-fiCOj DMB 25-1 (1CO-630) DMB 25-1 (100-6001 DMB 35-1 ,'100-6{>0| DM8 75-1 (100 403; DMB 73 DMB 50 (400-1600) DMB 50 (400.l6Ou) DMB 39 (400.1600) DMB50 (400-1609)' DMB 73 (2000.3000) DMB 73 (330O.50CO'; DMB 50 DMB 73 OMB 73 DMB 73 DMB 73 OMB73 ' v. 50000 100000 ♦i ' 300 150000 5% 250000 500000 . " *•^• 500 5% • - 7900 6450 2i7 6350 6950 1450 7050 : 100000 ISOOOO 2SOCOO 5GOCOO -. 461- 7250 8700 10000 12400 13400 13700 11000 11300 . 2400 11800 12000 1CCC00 750 5Va% 12906 14500 722 250000 200000 ; • UAiimiivti -.OoOOO • |SCKW>6 •• 1000 5'/*% : y62 • : t;- 243C0 50000a -21100 259C0 21900 26700 . 2130O .-25900 28400 1444 SOOOOO 32WO 1 ! . 5Vj% 331C0 35100 36900 38400 40100 25000 31609 35000 ?>3C0J .37560 ;• 47100 5O0CO0 40500 45300 20)00 1W4 Un.'.nKlsd 25.1 23-1 DMB DMB 13 15 (13.235) {)5.225) DMft OMO 25.1 15 23.1 0M8 30 DMB 23.1 DMB 13 PMO DMB 25.1 50 . DMS OMB IS 30 ' DMB , IS 13 om4* DMB 35.1 (40 609) (15.225) (40.600) DMO"*^--.. (13*:^ . • (13-223) (13.225) • - • 0M& 30 ' DM8 50 9600 41200 44900 43400 DM& 23.1 (40-60v) DMd2S.1 {49.6C9) DMB 23*1 (40-6001 0M6 50 (200-1603) DMB 50 (200.1600; OMO 50 (200*1600) DMB 50 DM6 • 73 . DMB 50 40 19 OMO 50 15 1 DM8 DM6 40 (200.1600) DMB 50 (200.1600) OMO 50COC UOC) OMS 50 (200-16005 DMB 74 t20CC :-3Cr0' DM& 73 (25CC jOCO) DMB (13.223) (200-1600) 349C<3 150000 * ''M 7200 27900 29700 " 31200 SOOOO / 23300 25300 150000 250000^ OMB DMB 15 0M8 OMft 20900 4800 20500 tooooo': 15 19600 3C0C0 .19500 20000 sya% 18500 165C0 taioo 10700 19200 '250000 . - 1S00 15600 16000 14O0 I61C0 50.^1 "• 3609 15100 150000 DM0- 03.223) I40C9 14200 14400 116C0 50000 DM8 23.1 8609 : 7150 50000 0300 B400 6500 75 DM8 15 DMB 35.1 DM8 34-1 DMB 24-1 DM8 38-1 DMB 75-1 (14-323) OMB 24-1 DMA 24-1 Da;&?4.1 OMB 25-1 |43 630) (43.600) (40-600) (49 6O0) (40-600) (43.600} (40 600} (40.6001 (40 600/ DM& !0 COO.I&CO) DM3 40 {200-16091 DMB 30 . OMS 25.1 (40.600: . DMB 75-1 DMB 25-1 (40.693) ; DI.^9 34-1 ' DMB 25-1 DMP 0-600; DMB srOMb 50 (7tfr-l600l DMB SO DMB 50 (200-1600) DM3 50 DMB 40 (300-1600) OMB 30 DMB 40. (300.)6W). OMB 50 (200-1660) D'AO 73 0M& 50 DMB 4C DMB 50 DMO 74 OMB 75 (W0.1690i (209-1600) (20O.)6OC« (200O-)0CO) (2000.2X0} DMB so •' DMB 50 DMA 50 • DMB 50 Dr^8 73 Dvo 73 V". P R O P O 5=^ A SPECIFIC PROCEDURES LOW VOLTAGE POWER AIR CIRCUIT BREAKERS (DRAWOQT TYPE) Drawout air circuit breakers shall be tripped open and withdrawn from cell, Fixed mounted circuit breakers shall be inspected in place, completely de-energized, unless repairs warrant removal. Arc chutes and interphase barriers are removed and inspected for burning, cracking, chipping and misalignment. Adetailed listing will be ' compiled of any interrupting components which have sustained damage or wear i.e. accumulation of scale on ceramic plates sufficient to render their respective efficiency questionable. All contacts (Main, Arcing, Auxiliary, etc.) are inspected for burning and pitting and will be cleaned, dressed, adjusted for wipe, travel, pressure as required. Operating mechanism and linkages are cleaned, lubricated and adjusted for proper operation, clearance, pressiires and tensions. All retaining rings, pins, springs, screws and bolts-are checked to be certain thev are in place and tight. Control coils, closing coils, shunt trip coils, charging motors, integral control relays and auxiliary switches and relays are cleaned, lubri cated, adjusted and inspected to be in proper working order. Contacts are burnished or replaced as requij?ed. The primary disconnect stabs on drawout circuit breakers are inspected for wear, pitting or burning and cleaned and adjusted. The circuit breaker frame, insulators, and main copper details are cleaned of all extraneous foreign material (dust, dirt, carbon, moisture, etc.). * Insulating material is tested for adequate dielectric strength from phase to phase and phase to ground with a megger type insulation tester. When a recalibration of the circuit breaker is also specified, in ad^tion to cleaning, inspecting, adjusting and minor repairing, the pole is tested by applying necessary current to cause the ciMuit breaker to trip open. The time to trip is compared to the characteristic curves and, if required, adjustments are made to insure operation within specified limits. This quotation includes current vs. time calibration on all low voltage drawout air circuit breakers. SC:SP-LV-CB-2 11-17 f3ACII=IC ELECTRIC COMPyANY n I P R O P OSA C PROPOSAL SPECIFIC PROCEEDURES: LOW VOLTAGE POWER AIR CIRCUIT BREAKERS (PRftWOUT TIPE) In general, the list of major points that are Included in a calibration test are as follows: 1. Long Time Delay Pick-up. 2. Long Time Delay Resetable Point. 3. Instantaneous Pick-up. U. Long Time Delay Time to Trip Check. 5. Short Time Delay Pick-up. 6. Short Time Delay Time to Trip Check. SC:SP-LV-CB-3 11-17 -2- FEDER/VL. RACIFIO ELECTRIC COMRANY • .ijISjtfl*^'.'.', .. ., • • • 'I'k . INSTRUCTIOIJ LEAFLET 12-957 ' •V.:A""-r.'-•? • "• ''i'"r ,.••••.•)'--v, .••.:;•• ' • •: • c -.'••• • *- f. ; l.-, . , ' , ' . •'i'.' '::'.f^C' .'fc •"' *• , ' •• I I ' '' . ' SELENIUM RECTIFIER'S FOR CIRCUIT EHEAKER OPERATION, wMm"- INTERtJiTTSJT DUTY A-C IKTEHRUPTED TIPE <(A ''K*.' . . c' . ••'I * " "'-A. ' 'i I i' ' ' •; ::V- -• . •" • w" .-v.-,-'.'I .•V •' •.' . . • ..' ^ v.l.j'' I• 'vc jj*'« «-\ • ' '' • , • • '* • •., •I'ji ••' •' ' • i •' • 4 n^;< I '.. • 'V • ' ' t' ('' •' ''y- <• . If • '•C':S.-i't'-R : ,• -a: " ' .'• . l!''-' '*•*'. • ; * . •« FEDERAL PACIFIC ELECTRIC Ca-lPAi'a' SCR/C!TCN, FiaaiSXLVANIA ' R • •-• fV--- ;c.Li,riiUM R^:.c?iri .U3 ?c::i circuit BRriARiR r "iRvTRa^IITJsT GU'IX 'U,' I, •g-RV^vG^ncral ' This rectifier is designed to deliver direct-current at • "•' • •' '• .fipi^rciadjBat©iy 120 volts at- any commercial -frequency^ The D-C voltage :- • \ will depend on the A-C voltage which can be anyid'ore from 20S to 2A0j •- ' -and also on the D-C load of the circuit; breaker solenoid, •;•, ; ' The compl ete unit consists of a full-v.--av'-: rect5 iVir.g element • ' i n ' t h e A-C line, . RIvO is positive-, BLACK, is negativ-r.j and YCii.C is a-^1. The rectiiier units should not be immersed in oil. ; AyR •U-U ; Disassembly • Selenium rectifier st'a.cks cannot be considered a simple components. Disassembly or reassembly of R;V : f v.'selenium rectifier s-oacks will almost certainly result in permanent : •.damage: or-'total failua?e.' The assembly-huj^S .should'not;, " • or loosened under any; circumstances. . :' • • ^ - ' y I • Expbsvtrfe to r-iercury Vapors : Selenium rectifiers should hot .be Used or stored 'where mercury , If: A , j j c e s e h t i Deterioration of rectifying properties and •ultimate burnva.ll hesultv. Special protective msasiires can 'be talcen where Hg vapors ® occur, ' Our engineering staff should-ybe consulted'inv such cases. Soldering :• Cairo is,necessary iia solderingyfleads to rectifier terminals, •'The rectifier should be shielded from hot drops of solderwhich may, • fall between the cells. Hot s'olde-ring irons should be handled carefully to avoid touching the selenium cells. - . , Refinishing . No finish-shovfLd be applied over the factory .finishes already i-.fe'-ri.ift' present' on the selenium r.ectifier^ because such c.Ocd..'n^gs can per-.'-auently • damage the. rectifier. Paints,/iaco.uersydnd varnishes'' may have solvent , or chemical effects on the finish'or may damage the rectifier directly> and the additional coatings may decrease •tho ability of the cells to -'dissipate'he^,"'I 'I..'Ri . 'R:'!-. . ^ R -R. fuf-j ,'vR;.V<; •".I-'tBHU.-i HEC?iFIEi^ FO;^ GI:^CUi?- ^j-ica ^ . lUTEKi^mXT^TY . •• Hanaiinp; ,!: ^ ' ' Selenium rectifiers should be handled and transported vath careo Dropping the rectifier or scratching ius protective coating is^""^c be avoided" • cells are bent, damage may be done to the rectif*Ang ^face, 'icroasing the forward current capacity or even shoi^iiing the cell, Dxist .Reaov?-l • ' • . , • Compressrd air can be used to clean rectifiers vihich have accurulated oust betv;t?n the cells. Dust interferes v.iih the circulation of cooling air, iixperience shcv;s that, other than checking for dust at fairiy long intervals, once a selenium, rectifier is installed, i^ requires no further care or attention. '. .• •'I.',' • ,Da-forming , , , i<-:i •! , _, ; • i : ' ' ^ t'i'V. -li " • Upon storage or disuse for a long period of time, selenium rectifiers may de-forni' to a cert^h extent. The effect is-opposite to' that of the forming' process during fabrication, and is manifested by a _ larger than normal momentarj'" reverse current when AC is. initially app^.edt. :. ... • V/itiiin seconds, the rectifier re-forms and permanently reestablishes its normal rectif'/ing characteristics. This phenoraenon rarely has any.sign ificance in practical applications. For applications v^ere de-forming •would be objectionablo, special nranufacturi.rig techniques can be used to . greatly reduce the de-formirig effect, :Operation " . The rectifier is desired for intermit'tent operation only, and must not be used to su 'ply loads other thari the breaker solenoid. The A-C voltage must not bo applied to the rectifier fon ••longer than 1 second nor for more than 10 operations within a 5 minute period. • The rectifier rating must not be exceeded, as for instance by the operation of 2 solenoids at once. Overloads v. . •;• •- /• / • The criterion for overloads is that overheating of the cells •must bve prevented. The id'S voltage rating of the rectifier should-not normalls" be exceeded. ' Reverse losses increase very iMpidly as voltage is increased aViove the normal rating due te ^ne' non-linear reverse re- siti'.v-ce characteristic, • Ovexn'oltage must be lirriit.. i to -•'•er^vr short durations and sm-all excesses, cthc;-vdse ovei-heauing and Xjossibie iall ure will result, 'r:- , 2 , " i-: SELSJIUH Ri;CTvpi:.:nS ?.:?i ClKCUI? BKiiy-m UPHtaTIOK INTii;F^!XTTS5T VJTl , Overloads (Cdhu'd.) ••: ' Current overloads can be borne much bsttere seleniujn rectifiers than voltage overloads, since the forward resistance de-r creases as the curi'ent increases. Current overloads *of several.- tbr.cs the normal rating can be handled by selenium rectifiers for short ;durations without causing overheating of the cells» ; Maintenance .and Adjustment . a«. •I ' .' Fuses • : Use current limitins fuses having rating of approximately 1/^ :dZ the inaxium d-c load current dram by the breaker solenoid. ! •I'.V- 'iii* Fuses, of this rating aro used in order •to protect the rectifying unit in case load should retrain : : i; connected, to the.; outfit for longer th^ the permissible ;• /bime,,;;. bo. • Sectifier .0: > " ' , /X X- ' - v vihen the rectifier is shipped from;.the-'^fict^ it is set i • . . to give proper breaker operating speed at r a~c. line -Voltage. Upon'installation, the bteaker clpsi'ng-time • \ • should be ohecked to see that coirect operation .is .obtainedj isincerline voltage conditions:, may .be f^fferent from tbpee •,.\- " '' at tHe factory. .This should be.done by-means of.a cycle • ' counter after all mechanical and dashpot adjustments have . been checked. . t'lf closing time is incorrect, the A-C ypltage must be changed, • To obtain quicker breaker operation, raise the A-C .voltage,. To obtain slower.brealcer. bperation, .iower the A-C voltage. t; Note •. •Approximately 30 day.s i. '^ter the unit has been installedj.' the breaker closing .time should be again chocked under the same conditions of supply volta.ge as existed during installation. Ad justmant to take care of tuiy change dviring the first 30 days ia made by adjusting the, A-C vb3.tage-. FoUovang this: adjustment no flirther .attention should-b»s necessciry except at. normal, .periods of brc-lcrr r.air.tenAr":e, say e;y«ery 6 months. 3-' .. . SoiiiKIU}'! •R;:CTj:FIiaS FCR CIRCUIT BRI U. vR OPiCH^VTIO; »•* ! »';'r ., ' Maintenance -sj^d Ad.iustoenfc - Cont'-d. • ''• . Curr.ent and Voltage Measurdnients ' i" ' 'r; Considerable care is necessary in mal ; proceed'ds 'follows ••k. ,;ijai :iCheck the a-c supply sobrcb'to^ see that ade^udte voltage lislavraiiablQ when the I^ilrlo^ ds. being drawas k^ k k Check the rectiiier-fuses to see that they are ;not blown-. c. d'. Inspect all ocnnectlons to see'.that none are open. • 'If .all of the above appear to be satisfactory then probably .a rectifier, unit .has failed k^less. the breaker -mechani'sm is.,.out of adjustmenlfi,. • ' • S.:' v ..- A. The failed vinit ma.y be detected as foHows; •' a. Disconnect the rectifier from ths a—c and d~c. circuits. bo Appier 110. volts a~c if/ith, a 3.00 v;att lamp in seri.es to the a-" temiinals of the rectifier for not .'more than one second^ •C» If ;the -lamp lights, one or more of .the individu^ stacks .have failed. ' _ '-i . . atteript to disassemble the,.'stack, aiad install new cel3.s, ' Supply a complete nevr stack, • k ." - 4 ??SW|S5j<5? •••'•" •SEISKIUM RFCTXFiiSn;: ' . .. .: .'•. .w"' • • •' • •• ; •.' ^-••V -V CIRCUIT DRE;U(ZR OBIIiATlGU :. ,. — - -G V ' . ^ G-••• ••- ."'iv.lL'iv,'. '/if If the insi^l^liion consists .of severail stacks connected .by vdres;. i • as ih; a.: bridge circuit; , . .• '• ••• • •• , .. . '..'-• •••• • ' . .. , "• vii.- • 'el» .Disconnect all-the stacks from, each other, ; • • ' ' 'bo Apply to"the a~c, teminals oif sich stack in turn the iiO;voit a-c, mth the 100 vfatt lanp in . series as before;, •• • ';.V. .* ' -vv:. • ' ; c, - r ' 'r:- :. v'' ^ .rifev'-N;.•. . AI3. iinits v;hich light up the lainp..should be rem~/oa. ^ V• v.-;. -yy li/-' K A?:: .• K'V'T • ' '' •.'••-• T /- ..-.Av'-TT': •SI "• :.. ;••• '' :A:r •g. • • '''• : . - •f\ .iV^o:--l::A."T • :>•. i 'r'TA..'' >'•: ;• -."v .•;. .•.=• ' -g'-' .: Jj., . . ; , . '''•.'••i'V-' A; ''\Ta K-'f •: . - •'» ••/[•:'y'.}'/•'] ,. ... ;; . ;.:-l • y:}' y4f':Mc0M 1 •: A; ;ATs .T'TV:'' ' *•: - -•V-vfc'V .T'G-TT .-' •yyyy.y •• 'v_ • - •GTS'.' ' V T. yf. ,• nV:'' •; . :* .V, 'At:-.- •;. ViGTiT - •' 9 AA "'V t'at •••• • .1 •.: ^ I- .. " T "• • -n . ;fe- • Aa.tA.G a: AyT'" ::,.'';,Ta..T:;A . . . .! • . .'..A. •-' •'•, "A, •• .>.,..>A"i.ATTT; . •' ". '• 'A.A A:V'.-—. :••' "• . uT r' • ..'r*'' ,VT •' " . . -... 7 'AS' ••/ •. •" • y-yytmyy . • ..'aTT: ..A'-':'.-j, ..^T -• ••-•- VX' ;.: ;K;., vA.. . ...-; ... -•.Av' /G. • • '.A. ..• 'tV'. TAG.'. G. ! • T-♦ - "5 - • '• • ••*••-": >-'. ; •^ ''ArTr'AT,;! - •INST.^ATION, SHEET ^ ••ci n«IB-15 and DI-S-25-1 AIR CIRCUIT BREAKEaS , r - ' •, Before inserting breaker in cubicle or cabinet; ^ f ^L Inspect- contact - v, ' • ' io Rcaaove screws'in arc chuteSo 2, Pull arc-chute fon'^ard and oxit of'breaker, thus: exposing f• contacts for inspection. Check op-eraticn of breaker, slovdy rotating the rcanual operating handle,, and observing the operation, of all' parts'. If electrically operated, • :W'ork the closing relay, the solenoid,'shunt trip, '^.dervoltage device> . bell-alar^ switch. Kirk interlock,'.etc. by haiid .to laak© siu-.e .that; the .• " >.V ^lit." !•' V I «I -I - %7'V i#r.' ;. Replace s^Crchute and breaker is ready for'ihstallation. . ' ,• ' Make sure that all connection-copper, cables and controL wiidng do- • '.energised xmldil breaker installation" is;-coiKpleted;V' :'f ^ , ..Installe.tioh - Fixed ,. - M v.: bolted into position it iray be .Necessary center the face plate in the cutout in the door^ ;• ;; ; 1« Loosen screvjs at top and bottom of face plateV.' 2» Close door and line-up face plate "with cutoutt-in door, ^ 5o'•-iTighteh -tbp^'and' bottbm screvbH&-fbce'platei.)^^ .^,f • v" . Installation - Drav/oirt \ C 3, .V/hen faceplate is lined-up, move breaker hah(ii.e ..to the ri^t, . . ; . • ^ exposing,^small .Allen-Head setrscrevj, .• . i v.' '':Tighten --sbfc-screw,^''raiease bailee .rsnd open booro • :,••,• . ; • • , . Insert breaker jrn. cubicle or cabinet,-.first "'test'position then • I'bpsrating" position-as-fdllov/sr / 'v . ..V Push breaker iritp cubicle, until it'sxops and rabi'buttpn on, lower , . ielt-hand side of breaker pops up.'f Breaker id "test" position'. PraJnary discorniecting contacts are not engagedy but secondary dis-• .: connecting contacts are in contact with similar .contacts in cubicle <, Press dovsi on read ^ut+on end punh breaker in t5.ii .•' !•• Release red button the moment breaker, starts to move in, resistance. .Insert 5/6" i'ack3..ng-in handle-bar in right-hand side of levering-ix*. '''.urretat bottom of carrj.age voider the breaker face pj-atei .. P\ish handle-bar to < ''o • •' . •- , C «-•- C ' -na •; '\ i* "'' "*:.^ evic; •cii oi'.; - V:.ori will i;. w^nCvS ':..o'..' '^n^/S'^ec liocked end o:? handle-bar into turrebo Remove breaker from cubicle or cabinet: To move breaker from "operating" position, inserf; handle-bar in turret^ press do^vn momentarily on red button, and push handle bar to the right as far &S .u Vvdll go," Remove handle-bar and pull brealcer forward gently until red button pops upo .-Breaker is no\'; in "test" positiono To remove breaker from cubicle, press red buttpii down, ,and pull breaker forward and out 'of the cubicle.. ^ ^ Wbte that pressing down on the red button always: trips the bres.!-ev'; It is impossible to move from ."test" to "operating", or from "op-nrating" to "test" vjithout first tripping the breaker. After the above test operations, the face plate should be: adjusted in the same manner as described under installation Fixed. The breaker should nov7 be pushed into "test" position, and secondary circuits checked. If it is a manual breaker vJith:,shunt-trip, or under- voltage, or bell-alarm, the'control circuits can:~be energized and the,' above accessories checked: If it is an electricallyvoperated breaker^" the Control circuits can be energized, and the breaker operated several, time-s to make sure that it functions correctly-.t .fc •series : " V-: ' . can be checked at the same time.,', ; Rack the ;break'w^ complete. ' acces-- S "operating" position, and installation. is '' • IX'lB-15 and lIiB-25-1 Instruction Book For description and maintenance see: For details and characteristic curves of Manual 3-266 (.Selection and Application:.' overcurrent devices refer to; v:>» ^11 • 'of Federal Pacific Air Circuit Breal<:ers) .y, l .• i.iiii)Miu..iiiwii -'i;, V : : < • J teEAL PACIFIC ^CTRlC COM?^ -f • f- Eastern Switcbgear: hivisioh ' vr. • • • •Meith Keyser Ayenua) P.; 0. Box 1510 • . Scranton, Permsylvatiia •.'i':."-••V-.. •; rfido.'cii IiiociT'i. VN'V Compcny. i'fj;.J.': i '' ' •••'•{ y-. h- :' '.T • .} •-C." - '. '\V ' • • il^STRUCYIOM^ . ^ vrV i ' • ^.T-' • • for • INSTAltAtiON, OPiEitAIEidNI, AMM MA!NViiMAHCt : Vj; '• MMwM ••; cf . :i;, .: ,:iR.,. Fi0oa«-PAS6FIC ASa CiSCUIT BtSSAKSaf TYPSS BMB-25 ' anA ' 0^3-^' •; V ElATSMGS: 600 Voi ts A-C . '•••: •y -y -m. 250 Vol ts D-C Type DMIJ-25' Type bMB-50 25, 600 amp -.50; 000 dmp .. Interrupting Roting; .-' r { .. Continuous Rating; 35, 50, 70, 90, 100 1.00, 125, 150, 175 Determined by series 125, 150, 175, 200 h'ip coil selection 225, 250," 300, 350 (amperes) from list 350, 400, .060, 600 400, 500, 600 QiTtp 800, 1000, 1200, at righi '.200, 225> 250, 300 •'SffitM . ; '•."•N r-.-" . 1600 amp • t .^.. .;'i' • • V- -y Mi •tf-i-y'yi , -V! .. '•y ; •• FEDERAi ElgS;Tft1C' PAGDUCTS exDcupyE crffcEi: so >AHfs it. ntA-Asx s. h. j ' :'r' •A': Y: Y -' ••t.-',- •' -- ; :. ..iipi.i •.: si • • • • . ♦-.I-.-'. •: ; Fociera! Electric Prcni.'c'' Aar;:;i9F4 CONTENTS Certain general instructions given herein contain extrocjs from Petit 7 of Standards for Lorge Ciicuit Oreekers, Pub. No.SG3~ 1951 of National Electrical Manufacturers Association. , . ' • . • , Page. General Description Standard Equipment 5 ^ 5 Optional Accessory Equipment ..y... 6 Shipment, Receiving, and Storing 7 Installation and Operating inspection 7 Inspection of Manual Operation 8 Connections 9 Drawout Mounting Phase-isolating Batriers Electrical-Operation Inspection 9 10 10 * N' Method of Operation IOSIng .. *« ^........... 12 12 Opening by Release of Trip Larch . Manual Opening, Handle-Shaft Assembly, Locking 13 13 Dual Overcunent Trip Device Closing Control Relay Auxiliary Switch, Shunr Trip Bell Alarm, Undervoltage Trip Key Lock and Other A.ccessorlei 15 15 16 17 18 Maintenance and Adjustmeiit '-I \ vU -i -.V, . ' J ^ 18 Contact Mechanism 19 Handle-Shaft Assembly 19 Closing Solenoid 20 Overcurrent Trip Device Control Re lay ^. ...v...... Auxi Ilory Svritch Shunt Trip Accessory .....'...............a*.....,......'........ Bell Alarm, Undervoltage Device, Key Interlock/ and C^i her Accessorloc 20 ,20, 21 21 ' ..................................... f '»•, j ,*a: , INSTRUCTION SKETCHES A-9031, A-9032, ,a-9033. A-9034, A-9035, Rev. Rev. Rev. Rev. Rev. 0 — Figs. 3, 4, and 5 0 — Figs. 6, 7, and 8 0 — Figs. 9 to 13, incl. 0--Figs. 14 to 21, incl. 0 — Figs. 22 to 25, incl. and Diagrams of Connections r:' '•• - ,; i 1*'f.N . 0, •!r ' I •'•'1 • • ^ • :- y / y«u-'yi u -01 .•-A*'.- •. /•i« r:;" :V f- Federal-Pacific Type DMB-25 Air Circuit Breaker with drowout mounting, ds viewed when ready for contact inspection. - v . J; j- • ii • ^ - 00 ^ " . y| ^ : . Two arc chutes have been removed, and the •^hiici is in its "up" position. >, -iy'-iL ^ ' , • ••'yy' • i Rev, I IN^302/.y •V-" ' ii!) ^ i'WS'vv^f A/ Aprils Fode.-al Electric P.-oc'ecls Compony •»* 1>-....- , .'V •; • <'. ,''f;" .• i'i ;* iiVi c~f> 77 ' 1 •':'7 "": '."•*.i'.'> j-" '777;§§^ iL;' '" •••. 7v7 • •;• ; 'if';' v" l-L-f-'l-n' •'7 * -• 7"'i; • ' . • •' s ' - •*! ' •\ •,-7., ; . - 'i t "" '' y - ,' 7^ i -• V* 7. ;.!• r* •%•. ' ! ' ' '•. -j . f.* ' r' •'•"7'/'7> i " *• •' .iy ''^ir •V.M' •/ A • i "d- ^ i /T '?• •I •V" .'.• '. •= y fil .1 c; • " n • •-' ,. jkS '• j 'if "•"'I bF •'hf {•>. "t -:v .Si-: H'y f' •••s ,;l ...' V-.- t '.r • ^ • M iteCv'j f'-y-»;." ^ -N.! . =v"^ '^5 • • •*• '* -s \V. • ••:'-,i":'t"" I'SV'l '! Fig. 1 (at left) •;: Federal-Pacific Aype PMB-5Q. }',' • ft.\ v;. ,-/. 'T »•>.' If .-. aA (iv.,' i? I' h, •}. 5 * Fig, 2 (above) •[•'li-'.-'X ; j.;; ''••• •• : • -u.' • -ff-a {• ?;• tv. Vj:.- Circuit Breaker, with 8-stage ;:-vf auxiIiary switcK -f- Xmmouhted.' 7' r.v, ;-:ii v';-" •:.'.;;i«^-v - \<' '• {i«»•.;:!»«, )l'} ]t • . .. I- J-iiiv in 7:" \r. 7?- S.f !•M =i-v A f ^ . I -J li • i;v. r\' .% : iA <4, i •> ; >5i. r • • V'-:-'• • 7'.?« "ilAAV/i - • •r7- -. i '.7\' '• i i;, .•••' 7' .7 ^ ,, "*/•' " i"' V .as A Federal-Pacific Metni-Fhclosed :v7."'> Switchgeor Uniii One Type DMB-25 and two Type DMBr^ ;; 50's are shown with phoseisolating barriers in place.. uvrtx. ;i '•; ";iS.: •• p. ,; tit'- •\ Ray. 0, ;iN-302- .'•'iiifV;.' .'.*• ''•'.•"^f^'•^.*. ^ . ' Apr!;, l'vA.4 ' '^s ' ' Po'defQl Electric Products Cofi-.pony • Pbce S • FEDERAL-PACIFIC TYPES DMB-25 AND DMB-50 AIR CIRCUIT BREAKERS GENERAL DESCRIPTION These circuit breakers are of exceptionally sturdy design, built for long service of frequent load switching and automatic interruption of overcurrents within rating. They embody features thathave been field tested formany years In thousands of circuit breakers of this design. The circuit breakers ore electrically and mechanically trip free in . any position of the closing stroke, end they will olso latch closed in the case of either electrical or manual operation when they are closed against a sustained fault the current of which does not exceed interrupting rating one-half cycle after contacts moke, Tho. . ' interrupting rating of the breaker is not affected by the selected standard.continuous rating; that is,'the interrupting rating of rhe Type DMB-50, for example, is..50,000 amp even though the overcurrent coils hove any of the standard continuous ratings from 100 to 1600 amp. ' . ^ : , A: STANDARD EQUIPMENT" The following operating features are regularly supplied with all circuit breakers orranged for electrical control: ^ ^ ^^^ 1. Dual-magnetic time overcurrent tripping — one device per pole—provides inverse time-delay tripping throughout the lower range of overcurrents and instantaneous '' tripping at the larger overcurrents. The percent of continuous current rating at which : . the device changes from time-delay to instantaneous tripping is qdjustoble. The usuar-^j pickup and timirig ad|ustments are also included. '^ 2. Manual tripping and closing from the operating handle, with provisioh for padlocking in open position. This padlocking prevents manual closing and it also maintoins the breaker in trip-free condition so electrical closing cannot be completed. If the-. ' 'A ,- . breaker is mounted in a cell, the door cannot be opened when handle is padlocked. 3. Flec''r'''.al closing from solenoid. The control circuit energizes the operating coil of a relay, the main contacts of which estoblish the circuit through tlit olenoid. Seal-in and anti-pump features are provided for maintained contact control. 4. Shunt trip device for remote electrical tripping. A; ^ ^ 5, Fo'.'r-circuit auxiliary switch of which one ciiccit is required for switch oper ation; the balance are available purchaser's use. Suitable interlocking of operating and control functions ds de^crited herein, ore provided to protect the breaker from the effects of mlsoperotion. •; •l&ryV* i; -/- « t>i CTj* Po:ip i- Fcderd ElccHc Prodoct; Corr!j;u-.-ry " • April, l'?5'' , j;/ . OPTIONAL ACCESSORY EQUIPMENT Depending on the conditions of application, some or all of the following listed features are supplied as optional accessories. Most of thera are described in detail else-r". where in this Instruction. ... , • . 1. Eight-circuit auxiliary switch, instead of the four-circuit switch^as reguIurly V . supplied, • . . . , . • . M . 2. Undervoltage device — instantaneous or tlme-qeioy type — mechanical reset. • 3. Overcurrent bell alarm device—electrical and hand reset. Operates only when. tripping is the result of overcurrent. If required, provision is also made so thatelectrical • or manual closing is prevented until the bell alarm device has been reset. ?• . 4. Key interlock locks breakei in operj position and also opens the solenoid control circuit so electrical closing cannot be initiated. The breaker must be'in open position before the key can be removed. • : „ :" • .;; 5. Reverse current trip device—direct current. ' 6. Mounted closing momentary button at the breaker. 7. Mounting Interlocks and drawout platform — for drawout-mounted breakers. Comprise mechanical interlocks that prevent breaker movement in the cell unless breaker • is in open position. An auxiliary interlock also must be released before breaker may be withdrawn completely. If mounting is within cells provided by Federal-Pacific,a special levering-in device is included for ease of fixing final position. " • 8. Drawout terminal sets—comprising high-pressure main terminals and moderatepressure ground and control terminals of number specified. Supplied with the latter are . the matching stationary terminals that permit withdrawal to test position without disengagement. The stationary main terminals that match the main terminals on the breaker' and their insulated housings are supplied as a cell accessory; not as a circuit-breaker .".v •• . .=* : ' J- accessory. 9. Dead front, back box, and other met,!iuriicGl features that have to do with housing the breaker ore considered a part of the breaker mounting, and are supplied as specified. ' : ;• * 10, Special overcurrent tripping devices. See Special Instruction or.referto factory for description of these devices ^ Iiicii •• wi'ls- .'criety is available. ... -• " . 11.. " Rectifier for use when alternating current is used for solenoid supply. Note; if specified, a-c supply can be used for the shunt trip device without need of a rectifier. ^ :' ^0^':- sag (:»!«. ¥ F&deral Electric Prcducti Compony • ' V-;; . Pcci-: SHIPMENT, RECEIVING, AND STORING Each circuit breaker before leaving the factory i^ carefully inspected, tested, and packed. • It Is shipped in a wood crate. Hooks should not be used when handling. Ap proximate net weights are as follows (with regular accessories). Add iO % for breakers mounted on drawout platforms. Type DMB-25 2~pole Manual Electric 130 lbs. 155 lbs. Type DM3-50 3-pole 150 lbs. • . 170 lbs. 2-pole " - 280 lbs. 320 lbs. 3-pole • 310 lbs. 350 lbs. ^ ' Upon receipt examine all equipment carefully for.indication of damage sustained v-ij. • . v;. '- in transit. If damage is found call for inspection by the delivering carrier at once, and file claim with carrier. For assistance in filing claim it is odvisable that information os to the extent of the damage be sent immediately to Traffic Manager, Federal Electric Products Company, 50 Paris St., Newark 5, N. J., giving description of the damage, identification of the breaker damaged, the delivering carrier's name, and if shipped by .Vr'^ manufaclurer to be of help in filing the claims \ ' S;! rail, the car number, waybill reference, and any other information that will enable the '..-M- When unpacking the circuit breakei, the crating or boxing must be removed care- ^ ' '^v fully. Check all parts with packing list Avoid bending, breaking, or injuring any parts. Do not leave screws, bolts, nuts, etc., in the packing material, Clean all. parts befbf^ assembling them; use compressed air, if possible. See that instruction books, drawings, and tags are kept with the breakers, ^ When the circuit breaker can be Installed immediatel^y in its permanent location, it is advisable TO do so even though it will not be placed in service for some time. When set up in buildings under construction, it should be protected from dust/ dirt, and molsture. ^ - . •l.'^-v.- 'v'. V' • .'t ' If the circuit breaker cannot be installed in its permanent location irrimediately and it IS necessary, to store it, it should be kep'- .r. u ciean, dry place. It must not be exposed to dirt, to the action of corrosive gases, ur lo ^ussiblc .mechanical injury. Special care should be taken to prevent injury to the apparatus through shocks or jars due to rough handling. It is recommended that stored breakers be covered with paper instead of by materiols-that may absorb or retain moisture. Do not lubricate the breaker. .Sufficient lubricant was applied at the factory; additional amounts only attract d.irt, INSTALLATION AND OPERATING INSPECTION , Indoor .circuit, breakers should be placed iri a clean, dry location, which is free from .thedestructiveaction of acids, alkoiies, or gasesy and v/here good ventilation can;be: secured. Open-type circuit breake'-s should be rr.eu!-.icd high eribugh tb -prsvent.injury-' \,,V.••.<>'v'/jv. , •' ' __ •;; „ • •••^^••" " , Fedorcl Elecrric Products Corr.p'any •• •- •-, • '' .• April, 1934 > to the operator clue to arcing or parrs movement during cutoniotic opening. Spoce must be provided for cleaning and inspection and for protection of adjacent apparatus from flashover. Enclosed breakers should be placed in, cells or housings hoving minimum clearances as per Figs. 5 and 8, ; • V": - inspection OF MANUAL OPEKATION: ; ^ The breaker should be inspected for manual operation before it is connected to the main and control circuits. /• - V' 1. Check for removal of oil tie v/ires^ blocking, etcl See that breaker is in open position. Mechanism should be as in View A, Fig. 9; not as in View D» ' 2. Raise and lower the overcurrent trip shoft 52 (Figs. 12 and 13) to be sure it moves freely. 3. Turn handle slowly in a clockwise direciloii to move the contacts tov/ord closed position. Note that all ports move freely except for spring resistance. Note that con tacts touch approximately simultaneously toward end of closing stroke. Continue closing until completion of stroke. There should be o distinct drop-off of force required to turn the handle as end of stroke is approached. This Is on Indication that the linkage has properly moved "over toggle" so it is self-holding, sometimes referred to as "latched closed". Return handle to neutral position. Are clearances Mand N (\/iew B, Fig. 9) as specified? Is trip trigger 37 well clear of pin on end of trip lever 21 (Fig. 9) so normal vibration will not be likely to cause unexpected tripping? Check jam nuts on spring studs to see they ore tight (part 22, Fig. 9A), for example. Visually check but dc not measure clearance P(F:g. 98). This clearance assures adequate pressure on lower : • • t \: - ' main contacts 13 in case of normal expected wear of contacts. Check cll compression springs 10 and 11 (Fig. 9). None should have coils solid. • . 1 •. 4. Rotate handle counterclocky/ise until breaker trips. The mechanism assumes the. position of View D, Fig. .9, for an instant, and then it returns to position of View A becouse of pull of opening reset Spring 23, Return handle to neutral position. Did ports move freely? Check cotters, and all accessible screws, nuts, etc., for tightness. It is suggested that the section on Manual Operation on page,13be studied for explanation of whot happens during the preceding closing and opening. / : i;. Vi"^ 'y 5. So for as it rriay be done without electrical connections, check the action of the electrical devices and accessories. This will old in assuring proper operation of the linkage to \ ich they ore ttoched whe; electrical operotion can be effected. The explanation of how these ports normally operote os given in lover pages Will indicate what should be done. For exomple, after again closing the breaker move'overcurrent trip shaft 52 (Figs. 12 arid 13) in the tripping.direction to see if tripping occurs. Simliariy try the action of the shunt trip and overvoitage release if used, etc. In these cases trip trigger 37 moves clockwise sufflnlently to engage pin of trip.lever 21 so as to " " / . 1?: release the trip latch.nThe larch should always reset ouromaticoily so the tinal position of the mechonism should be as in View A, Fig. 9. ' . , • •• ' ;• —• 4 • \ • ' ' ,, , • : " ^ . ., • ,A4 4 •• . ' 4.. , ... 4 • ' , , .^-4'."-^' ' ;'4':-4cvi •Fcflorq! Elecfric Prcciucts Cor-pcr.y Pago CONNECTIONS; - Before making electrical connections every precowtion must be taken to see that all leads that are to be connected to the circuit breaker are de-energized and will remain so throughout the work. For ncn-drav/out connections be sure that all joints ore clean, bright, and free from dents or burrs and that fostenings of the connection studs are tight.. All nuts on a current-carrying stud should turn freely; they should never be forced down with a wrench. If they cannot be turned freely by hand, tap them lightly on the outer surface with a hammer and turn by hand at the same .time, A nut that cannot be worked down in this manner will ruin the thread if an ortempt is mode to force it. ff the joints are not correctly made, dangerous heotlng of the circuit breaker may result. •M• Cables and connections should be properly supported so that the clrcuit breaker is not subjected to unnecessary strains. Any strain v/hich at first has no apparent effect on the stud alignment may. In time, force the studs to take up a new alignment due to vibration during opening and closing of the circuit breaker, and poor contact may result. To ovoid overheating of the circuit breaker, the connecting leads must hove a current-carrying capacity at least equal to that of the current-carrying parts of the circuit breaker. Control wiring should be so installed that trouble on one circuit breaker cannot be communicated to the control wiring of another breaker. The control voltages and currents listed on the next page are a guide for determin ing conductor sizes for the control circuits; |n the case of drowout mountings, it is important that the non-movable parts of the main and control terminals be located cccjrately in order that the contact springs of the terminals will apply proper pressure. Even a slight variation of location rnay couse a large variation of contact pressure. Do not use the approximate dimensions as shown in Figs. 5 and 8 herein. Use only such dimensions as are shown on prints certified as correct for construction applying to the particular circuit.breaker being installed. • This Ifistructiori Manual shows several typical connection diagrams but hot all vari ations ore included. In all caises, a certified print of the applicable diagram should be used. DRAWCIT MOUNTING. ^ : ^ ^ Figs. 3, 4, 5, and 8 show the circuit breaker mounted on drawout platform with to the lower^part of the deft si.de frame (Fig.. 16 shoves one form- —slightly modified on some models). Cell^ Interlock, lover 58 shotilrl ho kept pushed down so the'- interlock rod will not interfere with entry otthe circuit oreoker Into the ceii or cause it to be stopped support and side-guide rollers for use in the cell. Adrowoul locking device is attached in test position. When lever 58 Is pushed dov/n, trip trigger 27 moves to such posiflon that the breaker will be tripped if it is not already in open position. Ease of movement complete to full-in position aga.inst the resistance of the springs of the termihdT contacts •s assured by the leyerihg-in device (see the "turret" at front of platform in FlgdCS) that;- r. • ' • • - •'7> recl'^rai , Apni, i'/54 Peociuds Coiv.... is used on circuit brrokers in cases where Federal-Pacific supplies the enclosures. Insert a rod in the turret and turn it clockwise (looking down on tne turret) for the final move ment to full-in position. If the platform is equipped with cell-catch lever 61, the end of the lever will be seen to move inwards slightly as a stop pin in bottom of cell is passed. When withdrav/ing breaker from the cell it is necc^-u. y tc p-ish lever 61 irward near the end of the withdrawal to release a catch before ct viute v/ithdrowal con be accomplished. Some models have on equivalent device that is part of the side-frame Interlock assembly. VOLTAGES AND CURRENTS FOR CONTROL AND SOLENOID CIRCUITS Type DMB-50 Type DMB-25 Normal Control Minimum Volts Current In Amp Voltage at Coil Terminals at Normal Voltage Close Trip Close Trip Minimum Volts at Coil Terminals Close Trip 24v d-c 14 10 14 48v d-c 125v d-c 250v d-c 28 5 28 115v a-c 230v o-c 460V o-c 90. 180 70 140 MM 95 190 380 190 380 50 25 M M 50* 25* 2 1 3.5 1.7 -.8 90 180 Current in Amp at Normal Voltage Close trip 60 36 10 5 2 1 70 140 7 • 3.5 95 190 190 60* 380 380 36* 1.7 .8 By use of dry-metallic rectifier PHASE-ISOLATING BARRIERS: As on aid for assuring complete isolating of phases and as an added precaution under some conditions of installation, a barrier assembly, if supplied, is used to supplement the effectiveness of the ore chutes (see breaker insrallotipii of Fig. 2).-- if a barrier u supplied it is important that it be installed on the circuit breaker when it is ready for use. ELECTRICAL-OPERATION INSPECTION; After it is certain that the wiring connections have been tested fcr possible grounds or short circuits and that the circuits are correct in accordance v/ith the certified print, the circuit breaker should be tested for electrical operation, but with the main leads opened at the disconnecting switches or by having the breaker in "test position" in its cell. This provides a complete check of the electrical control of the breaker. 1. Repeat the manual operation tests described on page 8 but without checking clearances, etc.. Check to see that ports move freely and have not become affected by :th6 installation work of connecting. Leave.breaker in closed position* •77u:K'#r' • 7": • „ ^ f • '7 Fycv.tral Rlscfric Products Cciiupony . . • Fo -j- -* ' 2. Momentarily close the shunt trip circuit. The breaker should open and the latch should automatically reset. If the lotch did not resetmove handle to latch-reset position (see Figs. 5 and 8) and make a note to check the reoson why it failed to reset (see oaae 19). . . 3. Momentarily close the closing-control circuit. The breaker should close from operation of the solenoid. Check to see that clearance between trip trigger 37 (Fig, 9B) and the pin on trip.lever 21 is the same as when the breaker is closed manually (tr^y.all manual closing and compare the clearances). 4. Repeat shunt trip and electrical closing severe! times to make sure thatoperation Is normal. Check clearance betv/een contact kickoff 64 of control relay and top of collar 63 on stem 62 (see Fig. 17).to see if it is as specified. Place the mechanism in trip-free condition by holding trip trigger 37 so it engages pin of trip lever. 21; mean while move handle to closing position. The handle and shaft action should befree with out evidence of binding. The handle parts will move tov/ard closed position but the shaft parts will move only slightly. 5. Check of accessories should then be made. • Bell Alarm; With breaker closed, move overcurrent trip shaft 52 (Figs. 12 and 13) in tripping direction. Breaker should open and alarm ring. Move handle to tripping position; the alarm should stop. Again close breaker and trip by turning shaft 52. Close shunt-trip circuit; the alarm should stop. This assumes that an auxiliary-switch contact momentarily completes the circuit through the shunt trip coil even though the breaker .is in open position. This description applies : to the usual normally open bell-alarm switch installation (see Figs. 20 and 21). Also trip by shunt trip and again ky manual trip. In neither case should the alarm ring. - Kirk Key Interlock; The electrical feature of this device is that the closingcontro! relay circuit is opened when the breaker is key locked in the open position. Lock the breaker in open position by the Kirk key lock and close the closing-control circuit. There should be no operation of the control relay. Undervoltoge Device; If facilities permit, arrange for applying-reduced voltage to the coil of the device end note the voits at.which the breaker.is tripped. Did. the mechanical reset rod extending from arm on main shaft (see Figs. .10.and. 11) p^ooeriy reset the device? If the d<=yii_e is of the time-delay type, allow about one minute for reseiting. Other Accessoi ies; Perform such operotions as required to check the effectiveness of any other accessories that embody electrical features. With the breaker in open poi.lic.,., vicsu ihe disconnecting swii -h in the main leads or move the breaket to full-in position if it is in c cell. Apply some load end repeat manual and electrical closing and opening as a test of normal switching. Remove the breaker from its cell and completely check connections,, bolts, and linkage to see that nothing has become loosened or displaced during the test operotions. ;• Reicistb!!- circuit breaker; it is now ready for service;. . • " • ' • • Art-' f r :» /> <,r> •• -;••/:• •i,.h •'<^:'• '• . - Fecferal Electric Prob'ucii CoTipc •< - ""/.rr.'i, i9c '/ METHOD OF OPERATION! Complete Information as to how the circuit breaker operates is of help v/hen tr/Ing to locate the cause of improper operation. It oiso serves as a guide for understanding the reasons for the adjustments and checks made during installation or maintenance in spections, CLOSING: V Fig, 9A shows the position of the principal ports when the circuit breaker Is open. To close the breaker^ main shaft i Is rotated clockwise by the closing solenoid or by the, handle until the parts are ds shown in Fig. 9B. During this operation trip link 5arid, strut 6move as one piece because they are latched iogerher by the trip latch (in trip' link 5). Because links 7approach toggle position" as closed position is reached, a lorge force is applied to turning square shaft 8. Contact springs 10 and_ 11 are thereby com pressed to assure high pressure at main contacts 12 and 13, and moderate pressure at the auxiliary arcing contocts 15-16. Ajumper 14 shunts contacts 13 and electrically con nects qii moving contacts to the lower main terminal as is necessary during arcing when opening. Contact 16 does not touch arcing horn 17 when in closed position. The arcing horn is electrically connected to the upper terminal through a magnetic blowout coil (^hown diagramatlcolly). On the Type DMB-50, jumper 36 shunts the main arc to ener gize the blowout coil, but.there is on auxiliary air gap in the blowout-coil circuit (in the arc chute) that opens the blowout-cpi! circuit when the main arc is extinguished. It is not necessary to apply closing force after the breaker is fully closed because in the final stage of closing, link 6, trip link 5, and main crank 48 are in a straight line; in fact, they are "over center" so the mechanism is positively held in closed position by' the force of springs 10 and 11. Such action is sometimes referred to as'"latching closed", although there is no closing latch in the usual sense. The Type DMB-25 circuit breaker has one complete moving-contact structure per pole (see Fig. 3). Type DMB-50 has two such complete structures per pole and eocb structure also includes a shorter structure that comprises only an d^embly of main con tacts 12 and 13 and associated contact springs 10. Thus there are four spring-applied - •• r • moving contact structures in parallel per pole in the larger circuit breaker (see Fig. 1)," '--r " • Note fr'-ot neither electrical nor mon'.'s! closing can tqke.place unless trip link 5 , oiid strut 6move rigidly as one piece. Theretore ir tor any reason the trip latch is re leased, or it did not^reset properly during the previous opening, the straight-line reld-: tionship of the ports is no longer maintained and closing cannot occur. The breaker thus _ cannot be closed if the shunt trip coil is energized, the low-voltage release operates, or the breaker is not in its eel1at least as far as test posi; ion.' Also when closing against ° ''"c sul^f'cient to cause ii ifjpip.g , the breakerW.If trip as soon as the circuit is established even before the breaker "iatci-cs cioaod" provided the over- current acts instontaneously. closing hov/ever, Isvrge to CQUaedevice The breaker to latch closedTheoven whenfcrces, the fauii currentareissuffibiently as lorgeosrated interruplmg current, provided the overcurrent device permits sufficient time, deldy for complete closing to occur. 1- •• • • ' • ;j ^ ,v! '--v. • r:;,.: ': ... L Ir ' .p"?;, 1954' •;;;a Fcdorc! Eloc^r'c r'.'od^crc Co- "ur.v i- - ■♦•'' ^Gce i : OPENING BY RELEASE OF TRIP LATCH: ;; Current above pickup amount through the series trip coil In each main lead causes, either time-delay or instantaneous tripping according to the type and setting.of the overcurrent device (see Figs. 12 and 13 for tripping oction). Trip trigger 37 (Fig. 9B) moves clockwise to move trip, lever 21 to release trip latch 38 (Fig. 9D), thereby col lapsing the linkage and causing" the mechanism to move to the position of Fig. 9D as a result of the force of contact springs 10, The upper main contacts 12 separate somewhat before the parting of arcing contacts 15-16 (see Fig. 9C). The mechanism is then rapid ly brought to the position shovyn In Fig.:9A by action of reset spring 23 which turns mqitt. shaft 1 counterclockwise. The trip latch resets during this movement," thereby joining link 5 and strut 6 so they act as one piece. Opening by release of.the triplotch; as described, takes place in all cases of overcurrent tripping as well as when tripping is the result of the action of the shunt trip" device, no-voltage release, reverse-current device (d-c only), the drawout locking device, or by any action that moves trip trigger 37 so it engages "pin on lever 21. Trip ping takes place at any point of the closing stroke because trip trigger 37 extends Vfertically alongside the path ofvertical travel of trip link 5, so engagement will occur when ever trip trigger 37 is moved clockwise regardless of the position of trip link 5. ':;r MANUAL OPENING: The trip latch is not released during manual opening. Instead, the opening comes about from handle movement which causes main shaft 1 to rptate counterclockwise (viewed as in pig, 98) sufficiently to collapse the "over center" condition, of main crank 48, trip link 5, and strut 6. The force exerted by springs 10 and 11, supplemented by the pull of spring 23 and other springs, completes the opening. The parts move directly to their position as shown in Fig. 9A without need of going through the intermediate step shown in Fig. 9D. HANDLE-SHAFT ASSEMBLY: The Operation of this assembly on the Type DMB-25 circuit breaker is exploined by reference to Fig. 10. The parts and their connection to each other ate as follows: Handle shaft— extends from handle 3 to alarm cam 72. Coupling crank 44 -- turns loosely on shaft 40. Clutch jews extend from the left hub of the crank. Also pin 82 extends from the left flcnge as shown. This pin has a flat surface that can be engaged by the clutch [aw of sliding-cqm clutch 42. Only a pert of this shown in Fig. 10 becouse it is icgc:/ surrounded by siidir.j cc clutch 42, Jew projections extend from the right of. main dutch 43, ' " Main clutch 43 — fixed to shaft 40, Sliding cam clutch 42 —concentric with and loosely turns on main clutch 42,. Avetti. .; col pin .(not shown in Fig., 10) extends through .shaft 40 and mQ'h clutch 43, into q, ^Ibt.'n cam clutcK 42, This pin sei'ves to control pen t ofthe motion of slid.in9 i 'c (••1''? Fcclorcl tiocfiic r'i-oducts Cornpony • • April, 193-1 clutch 42 hccai:e the slot-cut thrcrj.;!'. h: bvi&n -.-d i-},© pin permit the cam to move lengthwise along shaft 40 by a limited amount, ond also assures that cam •/=. clutch 42 will rotate along with shaft 40 and main clutch 43. • •. is a groove com recess•in its outer.surface, The essential feature ofcam clutch 42 ^ .S- — Fixed pin 50 extending from the frame into this groove cam holds cam clutch 42 without any movement lengthv/ise ofth" shui'r during ai) normal closing and .ripping •^ ^ ,' movements of handle 3. . However, if handle 3 is moved to latch reset position (see . --^iv Fig. 5), then cam clutch 42 moves to the front because of the curve in its recessed • groove cam. " • • f. ', '';'nl' Alarm cam 72 —attached to left end ofshaft 40,is bell-alarm accessory, if specified. Position spring 41 and arm 83 and associated pins return handle assembly to neutral position atend of either on opening or closing stroke. Coupling crank 44-f however, will remain in either open or closed position. , V. ;v? • *' "r The operation ofthese parts is OS follows: ; ; ilf Normal Manual Closing; Fig. 10 shows ports in normal open position of the circuit breaker, Shortly after start of turning handle 3 clockwise main clutch 43 engages i the clutch portion of coupling crank 44 so it also rotates clockwise with the result . that main crank 48 of main shaft 1 moves in a direction to. close the breaker. After handle is released, return spring 41 moves the. parts to neutral position, except that • s:"' coupling crank 44 remains in ."up" or closed position. Normal Manual Tripping: Shortly after turning handle 3 counterclockwise, main clutch 34 engages the clutch of coupling crank 44 so it rotates counterclockwise with the result that main crank 48 moves beyond to^le position ond the breaker opens. Coupling crank 44 rapidly moves during this opening because the contact springs of the breaker move it regardless of handle-shaft movement, Monudl Control of Latch Reset; If for any reason during normal manual tripping (or even, during electrical tripping), the trip latch in trip link 5 becomes released and the pull of reset spring 23 (Fig. 9A) does not reset the latch, then movemenf of handle 3 to reset position (Fig. 5) will produce positive movement of main crank 48 some- ^ ' • what beyond normal open position, thereby forcing the trip latch to reset. The ; action is as follows: Movement of handle 3counterclockwise.to reset position (Fig.; 5) causes com clutch 42 to rotate so for that fixed pin 50 and the curved groove \ cam move com clutch 42 toward the front so its clutch engages pin 82 on coupling crank 44. This produces sTmildr movement to that of normal manual'tripping,' but" the motion is carried farther, thereby assuring latch resetting unless there is condition in the latch assembly that prevents it. The descriptiori of hdndle-shaft operation OS given In the preceding opplying 'to Vhe^ ^ Type DMB-25 circuit breaker also applies to, the Type DMB-50 circuit breaker except \ that ^in the latter breaker the general arrangement of the parts is reversed: The coupUng ^ crank is in back of the main clutch, and the sliding cam clutch moves toward theVear/of the breaker when if engages fbr resetting of the trip latch. The alarm.com is located its ^ -i!, 1954 Federal Eiecfric ?fodi-ats Comrony •'090 V3 an Intermediate position instead of being on the end of the shcft. Also instead of there being a pin attached to a flange of the coupling crank, the crank is of the two-arm type, only one of which is engaged through a long pin by the sliding com clutch. Fig. n identifies the parts with numbers that generally correspond to those of similar parts as shown in Fig. 10. HANDLE LOCKS; Neutral Handle Lock: When handle is down, a pin enrerSrthe.framejSo it is neces sary to retract it by applying the thumb to the metal eye at top of handle before the handle can be turned. Padlocking at this point prevents withdrawal of the pin, thereby locking handle so it c-not be turned. The lock does not prevent electrical operation, so it is useful principally to prevent handle movement by unauthorized persoris, Complete Open-Position Handle Lock; When handle is in pddlock-open. position (see Figs, S and 8), padlocking of the handle eye prevents manual or electrical closing because main clutch 43 engages and holds coupling crank 44 (Figs, 10 and 11) in the open position. The cabinet do<«rof enclosed breakers cannot be opened when the hand|e • is locked in this manner. There is no closed-position lock because the breaker must al ways be free to trip. v';. DUAL MECHANICAL OVERCURRENT TRIP DEVICE: Figs, 22, 23, and 24 show the overcurrent trip device, comprising a coll in the main lead, atii armature moved by the magnetic force in the coil when current exceeds pickup amount., an escapement-type mechanical time-delay device that deloys move ment of the overcurrent trip shaft 52 (Figs, 12 and 13), and an. instantaneous magneti cally operated element that moves the trip shaft immediately if current exceeds a sched uled percent of pickup amount. As ordinarily supplied, an external knob is provided for adjustment of the current at which.the device "picks up" and starts the time-delay'device. The indicator for'this adjustment is calib'ated at 80, 100, 120, 140, and 160 percent of continuous current rating of the trip coil (tolerance plus or mirius 10 percent). An internal setting provides for adjustment ofthe time after pickup at which tripping will occur, and another internal setting provides adjustment of the percent of pickup current at which the instantaneous element becornes effective. . ; Modificoilwris of this basic device to meet various condiiioiv^ of service are avail able, Information concerning them accompanies circuit breakers with which they are supplied, or It is available on application to the factory. Ci CLOSING-CCNTROL RELAY: . '" order to relieve the electric closing contact of carrying the large current re- quired^for the closing solenoid, the closing control circuit only energizes the operating ^ andcontacts the connection diagrams)/ The clp^hg'? so enoid circuit is energized when the double of the control relay close because 4i '>« * Fcdsrol Eloct/ic ?rcduc(s Company . April,,!'•?" • of force exerted b/ the relay operating coll. Asea I-in of the" operating coil is provided through a resistor connected between the two main contacts (see connection diagram). •' IP- As soon as the circuit breaker closes, the double main converts of the control relay pre opened mechanically by upward movement of stem 62 (Fig. 17), which also de- energizes the seal-in circuit of the operating coil. Blowout coils aid in extinguishing the arc of interruption of the inductive current of the closing coil. Should the breaker trip before the operator's finger is removed from the closing control contact, the breaker will not reclose because the main contacts of the control relay do not recouple to the armature of the relay operating coil after breaker opening unless the coil is de-energized. This prevents "pumping" (successive open and close) if the closing-control circuit remains energized under overcurrent conditions. AUXILIARY SWITCH: This switch is directly connected to the circuit-breaker mechanism so the switch position, open or closed, corresponds to the breaker position. The auxiliary-switch contacts thus provide a means of controlling circuits that are to be responsive to circuitbreaker position. Each switch unit has four stages, and one or two such switch units are mounted on the breaker depending on its specification. Each 4-stage unit normally has two "a" contacts (closed when the breaker is closed) and two "b" contacts (clpsed when the breaker is open). However, the contacts ore convertible from one type to the other by removal of shaft assembly and changing contacts as required. ' f-l'- One "a" contact is required for use with shunt trip and one "b" contact If bell alarm is used, so with such devices it is often the practice to have two 4-stageauxiliary-switch units on the circuit breaker. No auxiliary-switch contact should be used in the circuit of on undervoltage device. The contacts carry 15 amp continuously or 250 amp for three seconds. The inter rupting rating of the auxiliary-switch contacts is as follows: Interrupting Amp Volts ' , 125v d-c 250v d-c ' Inductive n 6.25 1.75 2 115v o-c ioOv a-p 450v d-c Non—inductive i' ' ^ 75 35 15 8 • 25 5 . The drive shaft of the auxiliary switch is extended and connected to" the ON-OrF circuit breaker. G.eeii ond red signal lamps, if required, are supplied through auxiliary-switch contacts. . •SHUNT.TRIP;'\ ;• - 0. ^ : •••A. The oction.of this device requires no explanation. • rv , • • n• • ,'! ^ 'v. ^.prii,'1954 '" Fodero! Becfric Products Company Page 17 BELL ALARM: The usual orrangentent provides a normally open switch so connected mechonicolly that it closes when the overcurrent device opens the circuit breaker. An alternate arrangement sometimes used provides a normally closed switch connected in thfe some way; in this case the switch opens when the overcurrent device opens the breaker . The latter arrangernenr Is useful when ft is desired to block associated control circuits ds d parjt of ageneral protective scheme/ which may or may not include an alarm. ' I \- In either case/ the iswitch is operated by mechanical means. as shown in Pigs. 20 and 21/ according to type of circuit breaker". Drive rod 73 always moves when the breaker is opened by any method. However/ if trippingjis manual or from on electrical accessory (shunt trip/ etc.) drive bar 81 is moved aside mechanically so it connot engage switch plunger 76. In the case of manual trip, a cam on handle shaft actuates the rod or lever that deflects drive bar 81; and in the case of accessory trip, it is a similar rod or lever, as illustrated. UNDERVOLTAGE TRIP; / ;• ••-.••• y ^ The essential external features of the undervoltage trip device with mechanical immediate reset Ore shown in Fig. 25 in their position when the breaker is closed. When the coil is subject to line voltage above that for which the device is set, reset level 85 ' • ' .'niT and trip lever 84 are in the solid-line positions. The slot in the end of reset bar 57. is also positioned so that main shaft 1 con move between open and closed positions without - 1:" lengthwise movement of bor 57. When voltage is reduced so far as to cause the undervoltage device to operate, re set lever 85 moves down end trip lever 84 moves up to the dotted-line positions shown. Reset bar 57 is thereby caused to move to the left so its slotted opening will no.longer permit free movement of the arm on'main shaft 1 when breaker opens without movement of reset bar 57. . •; By the means previously described, the upward movement of trip lever 84 causes the circuit breaker to open with the result that the arm on main shaft 1 moves to the dottedline position which" again moves reset lever ,85 to its solid-line position. The undervoltage device is thusreset ond trip lever 84 will remain down provided the voltage is above that for which the device is ser. If the voltage is still too low, tr ip lever 84 will remain up and the breaker will be trip free so it cannot be closed as long os thn und'?'- • voltoge condition continues. The time-delay, attachment to the undervoltage device, if supplied, Comprises rheans for slowing down rhovement of the solenoid core pneumatically through on adjustable needle-valve opening. The device does "not reset immediately, so one minute should plr>n<«» before the breaker can be restored to service" after the undervoltape condition no longer exists. Connection to the. dndervoitage device should be.to the line side of the bredker if ] -!•' .. . I . .1 I . I' « f I .1*1 « •"t imrnediate reset is used,' and to the lood side if time-delay reset. Is usedM-'' . '".•AAs' the uridenyoltage device is" connected to the main leads, its coil must be suitable for the; ohd kiiid of current interrupted by the circuit" brsoker (a-c or d-c, as the case may^be). 1 ".v,. '''J.'J.i"'"''.' • "v ; ,i; ,rT\ /.-1\ ••••^ ; :,Vl ,• • '•• ' • ' -i « • ' ' i" ' • " . '" • FoH&rol fclectric Products Company KIRK KEY interlocks" - .. Af.ril, K;' • . ' The opplication is as shown in Fig». 18 and 19. The lock plunger causes locking latch 69 to enter a slot in lower shaft 39 (Fig. 10) of Type DMB-25 circuit breaker or to" & • • -:;-iYV . v' • . enter handle shaft 40 (Fig. 11) of Type DMB-50, in either co.se locking them in the open position of the breaker. At the same time linkage opens an electricaf contact in the closing-control relay circuit. The device embodies mechanical means for preventing completion of locking when the breaker is in closed position. . •.::;W To lock; With breaker in open position/ handle neutral, key in place, turn key counterclockwise 180® to lock breaker in open position—after which key can be removed. The breaker is locked in open position. To unlock; Insert key (unless already in place) and turn clockwise-to unlock. The key connot be removed. The closing-control-relay interlocked contact will/ be closed. So closing of the breaker may proceed either electrically or manually. ':H'; OTHER ACCESSORIES: Instructions relating to accessories other than those described herein ore supplied with all circuit breakers using such devices. ' MAINTENANCE AND ADJUSTMENT The safety and successful operation of connected apparatus depends on the proper action of the circuit breaker. Therefore the circuit breaker must have systematic care and inspection. The following points require special attention: K Be sure that the circuit breaker is in test position in its cell for all inspections in which it is necessary to have control current available, or disconnect the main leads if the breaker is not in on enclosure. Adjustments that can be rriade when the control circuits are energized may be performed when the breaker is in the test position, but if there is any doubt remove the breaker entirely from the cell —or disconnect control leads if the breaker is not mounted in an enclosure. 2. Inspect the operating mechanism periodically and keep it clean. 3. Examine the-contacts frequently. See that they are aligned and that contact " surfaces bear with r firm, uniform pressure. Replace badly pitted Or burned contacts • before tl.'-y are burned away so far as to prevent full contact or are likely to ^uuse damage to other parts of the circuit breaker. All main and control leads should be dis- ;..v connected wheri working on the contacts-. 4. All contact members, both main and control, must be kept clean and bright to insure maximum operating^ efficiency. If has been found by experience that operatina ^ / liiui upcrurmg ".'i. . i. v/ill •!< reduce < . rhe circui.t oreaker several times at intervals of not* over two. weeks the '" effects.or oxidation and materially prolong the effective life of the circuit breaker. It -"• 15 recommended that this practice be followed excppt vhct a circuit breaker which is f the regulorly operated every few days will not require such oitention. -lie 18, Rev. 1, fN-302 V '' /A&r;i,'954 - i-ec'cralE!ocfric Products Company .. .. ' Pp.g<-' 5. See that bolts, nuts,- washers, cotter pins and all terminal connections are in place and tight. . 6. Clean the circuit breaker at more frequent intervals than usual where abnormal conditions prevail, such as when near salt spray, cement dust, or acid fumes —to ovoid flashovers as a result of the accumulation of foreign substances on the surfaces of the circuit breaker. Special Instructions relating to maintenance and adjustment of various units of the circuit breakers are given in the following: , • • ' V : . ---l. CONTACT MECHANISM: Perform steps 2, 3, and 4 of the Inspection for Manual Operation (see page 8 ) including check of clearances M, N, and P(Fig. 9B) and adjust if required. When the ;• s-,. circuit breaker is in closed position, the pressure of the contact springs should be main tained at 50 lbs for the upper main.contacts 12 (Fig. 9) and at 32 lbs for arcing contacts 9. Pressure should be measured by fish scale and pull-away sling attached to straddle the contact surface so the pull will represent average pressure at center of contact. The scale should be read just as the contacts part.. The contact surfaces should be dressed with a fine file or sandpaper^ Each contact assembly is removable after disconnecting jumperand releasing the springs by unsdrewing holding nuts. The lower end of the assembly has only a pin-in-slot connection* The amount of effective toggle when handle moves to closed position is adjusted by the jam nut on the right-^and link of toggle links 7(Fig. 9), but as this is carefully adr justed ot the factory, it is unlikely that further adjustment will be required. • Failure of Trip Latch to Reset: If there is frequent failure of the trip latch to reset so it is found necessary to move handle to reset position to reset the latch more i often than occasional intervals, the ports and linkage that produce "tripping through movement of trip trigger 37(Fig. 9) should be examined in detail. Check all clearances betw.-en parts where there should be clearance. Check fastenings for "tight ^ # ' • • • I fx \m • i I & . I •: -i-: ness, Check any condition m the mounting of the circuit breaker that would be .. '«•* likely to cause abnormal vibration during opening. Particularly see that trip trigger 37 is well clear of pin on trip lever 21 at all points of the stroke. Check condition of reset spring 23 (Fig. 9) and its fastenings. If nothing can be found that would cause the latch failures, check th"^ condition of the latch itself by inspecting the latching surfaces of trip latch 38 and latch prop 86(Fig. 9). If the surfaces are worn or indicate the possibility of not holding firmly when reset, replace trip link 5 entirely; it includes the latch assembly. The re iffi* moved trip link may then be repaired if practicable. " handle-SHAFT ASSEMBLY: _ , . . . F • • . • • • • ' . . ' '• . • • . See that sliding cam clutch 42 rides freeiy on main clutch 43 (Figs. 10 and 11) and thatdutch engaging surfaces are not broken or blunted at edges. 1 „ , •. V- " • ' -••y•-:•s•J'y-•v . v> • . • '.'F- ' . .-0 ... l-o.Jorci cif'clvic Prodycts Corripa,-'^ . Ap-d- i?54 CLOSING SOLENOID; The solenoid is designed for intermittent duty. To remove the Solenoid: Hove breaker in open position. Disconnect leads to control relay and to terminal block. Re move pin in link that connects to the core.. On Type DM3-50 remove three hex head cap screws at bock of coil/ and pull out horizontally. On Type"DMB-25 remove four bolts underneath the coil. The disassembly of the device after removal from the circuit breaker is obvious. However, o list should be kept of the parts and of the order of re moval so replacement may be made in the correct opposite manner., OVERCURRENT TRIPPING DEVICE;- " ^ v Each device is removable after withdrawing six bolts from bock frome of the circuit, breaker. The series coil and the overcurrent-device assembly are withdrawn as a unit. Do not remove the tripping unit from the coil. ifi There are several forms of ovet current devices available, and suitable instructions accompany any that differ from Form A (see Figs. 22 and 24) to which the foilowirig In structions apply: • • -i--- a"-'". Pickup Adjustment: The percent of coil rating at which pickup takes ploce (the current at which timer starts its operation) is altered by turning the exposed knob. A pointer on a calibrated dial controls this adjustment, •f:A "AA, : Time-Delay Adjustment: Remove molded cose, to expose the escapement timer at bottom of assembly. On the opposite side from that shown in Fig. 24 is a circular disk that has thin metal projections which can be altered by rotation so they may be brought near to or moved owoy from adjacent thick bosses. To increase the time of pickup', move the • thin metal projections "toward the thick bosses; to decrease the time, move them away from the thick bosses. ' . Instantaneous Adjustment; Refer to Fig. 24. Place spring end in slot No. 4 for greatest, percent of coir rating at which the device changes from time-delay to instantarieous: operation. Place spring in slot No. 1 for the smallest pertent of coil rating at'which • AfcH the instantaneous eieme/.t becorhes effettive, CONTROL RELAY; ;• . With oil control circuits and main leads open, remove cover from relay'housing/ dress contacts, clean the interior, end check all connections for tightness. Reconnect the control leads. With the circuit breaker in test position in the cell, or with main leads otherwise disconnected, momentarily energize the closing-control circuit. The-breaker should close. Trip the breaker. Again energize the closing-control circuit, but this time keep it continually energized during both tbe closing ofthe breokerand a following trip. The breaker should ^not close after the tripping, thereby showing that the anti-pump,feature * of the reloy is in operating condition. It v/iil also show that the resistor which ifupplibs the seol-in contact is intact. ' • • -A •* /,p,-ll,/l' 54 • ^ ;> '44 Federol ElecJ/ic Prodych Compony • • Pogo 21 • Remove cover from front of control relay. Disconnect leads from the relay contacts that go to the closing solenoid and the terminal block. Energize the relay operating coil and close breaker slowly by handle. Note the point in the closing srroks at v/hich the relay contacts are opened because of engagement of coMar 63 with kickoff bar 64 (Fig. 17) • The contacts should not open until it Is no longer necessary to apply strong force to move the handle. The breaker is then {ust beyond the "sncp-^over" point very near the end of its stroke. If the condition is incorrect/ adjust at jam nuts dt top of stem 62 until it is correct. HoweveV/ be careful to see that the contacts will open each time aff®'" several closings are made, because it is very important that enough leeway be left *: . t . : r\ : • H so there will never be an instance in which the contacts fail to open at the end of the a'asing stroke of the breaker, yet it must also be certain that the solenoid willremain ®nergized as long as any force is required from it for breaker closing; After being sure that the preceding adjustment is correct, trip the Isreakerand again energize the relay operating coil and keep it energized throughout a manual closing followed by manual tripping. With the operating coil still energized, check to see that coupling link that connects the operating coil plunger to the relay contacts remains uncoupled. De-energize the operating coil and note that the link now couples the plunger to the contact frame. Again energize the operating coil, which should result in closing of the relay contacts. • If an incorrect condition is found make such adjustment as is necessary.. AUXILIARY SWITCH; Remove front cover and inspect contacts. Dress or replace as required-. The switch is designed so that contacts close somewhat before the end of the stroke. This insures complete engagement even if there is some rebound of contocts.of the circuit breaker during opening. The auxiliary-switch contacts should be so arranged on the shaft that they are squarely and firmly applied to the contact fingers ofthe switch when the circuit breaker is fully closed or open, as the case may be. SHUNT TRIP ACCESSORY: . . With breaker open, move the core of the coil against the trip frame assembly and slowly try tp close the breaker manually. The breaker should not close because of being trip free. When the shunt trip is not energized there should be 1/32" minirnum clear ance between the small trip lever that extends from the bottom of the shunt trip assembly and the frome thot it engages during tripping. " BELLALARM,.UNDERVpLTAQEr.D?VICE, KEY INTERLOCK, AND OTHER ACCESSORIES: The inspection of these accessories is made by performing the work described in the oDnlicobie pr-agraphs of the section, F'ectrlcal-Operotlon Inspection (page 10), after •s\-: - • ^ which remove covers of the devic.is, dress contacts, clean "all ports, check for loose connections. The undervoltage trip lever 84 (Fig. 25) should have clearance at" least 1/32" from the tripping frame that It engages. Ameasured undervoltage source should be available to make certain that the undervoltage device operates when the voltage is reduced to the omquht at which the device is supposed to operate. / 4. . '/ ;. . • .. imcrlock Switch NO. 63 P^ey Lock 67 Celt interlock Rod 59"' Adjusting Screw 60 Locking Latch 69 ( engoges slot in cottar on tower shaft Futt-tn 39 if breaker is open Position Hole Fig. 18-KEY INTERLOCK on TYPE DMB-25 Test rPosi tion Hole - Showing Ports in Lock Position / Fig.20-BELL ALARM h ' . Fig. 16-FORM A CELL INTERLOCK r Drive Rod for Alarm Switch 73 ASSEMBLY-TYPE' . DMB-25 Fig.i9-KEY INTERLOCK on Shown reody for tripping •Drive Bar at TYPE DMB-50 Showing Ports in Lock Position • • Cam for Alarm Switch 72 •• n Key Lock 68, and Switch On reoij . Handle Shaft 40"^^ ^Plunger 76 C t^Januat Trip © Lockout Rod 77 H I l9(® Beit Crank 75 Aidrm Switch 74 Locking Ljotch 69 —^ Pin 78 J U Accessory y Trip Frame 55 1' ' iciiDj •i I f, I . dosed'pr^iti: • . . i Handle Shott 40 Locking Piote 70 block 7! in suplh d.i'^< thaf-ldc^^:; cpn^fibe^^: brddHer0W Drive Rod for Alarm Switch r. Alarm Sv/itch 74 cl6sed}pcish^ 'V Plunger 76 — \-Manual-Trip Lockout Lever 80 . ! t ActuOl Cli uy 21- Bel] ALARVi ASSEMBLY Drive Bar 81 Shown reody for tripping .Cam on Hondto Shaft for LAan- TYPE DMB-50 ual Lockout Accessory-Trip Lockout Rod 79 Fija.j7;^><# • KICKOFPfc TACTS : END of'.Cki. Type 0MB,!4 • sV' : >•. • .t' *>i - *?f • Closing Solenoid 4 - • 'y-fdis Bar omitted on Type Dt^B-ZS, \^;:land Trigger 37 moved by direct contoc; I ; of Wifbdroival Trip Lug 53 ( see Fig. tZ ) 1 • Cell Catch Lever 6t 1 •• :.VV. O El) O (lli) — — —Main Shaft I 7 —Cell Interlock Lever 58 Normal Open Position Doffed-lines-shaw maximum trove! opening Reset Spring Z3 • TYPE DM B during closing Rg. [4- DETAIL of SOLENOID ond LINKAGE . -.-J TYPE DMB-25 AWWWmWWTO! stem 6Z - ' Relay Contact > Top Shelf Closing Solenoid 4 Collar 63 Kickoff 64 Spring 65 Clearance R Vis"' minimum Plunger 66 Lower Shaft of Type DMB-Z5 twain Shaft I Position immsj.' ^ely after dosing y —'' opening Reset Spring Z3 Position after Trip Latch Resets Kickoff bever 46. Note: The action is simlliar S^KE. in Type DMB-50 except for method of upward movement, for which see Fig. It Rg. 15-DETAIL of CLOSING SOLENOID"and LINKAGE:' . TY^ DMB-50 In normal open posifiori ' ' f ..]• ••• • ' •" sii® FEDERAL ELECTRIC PRODUCTS CO. M PARIS STlIEET. NCVrARK. N, J.. U. S' *. ' TYPES DMB and DS CIRCUIT BREAKERS^-:; CLOSING COi'L ar:d hVTcPLOCKtNC ClETAltS-'. DATE im yj.» ' • FixocJ R'-'/orr. Srnng -'i! jiarm m 72 Pin 50 Coupling Crank r\<7 .» Blowout Cr,tl 2'i- j ( Schematic '} —- OilUe Bearing -v. Positioning Arm 63 Arcing Horn 17-:" Han ait 3 Oilife Bearing Auxilioiy Contact 15 : I ' II Sliding Cam Clutch 42 Pin 82 Main Clutch 43 Uppei Main Contacts 12 -r 1- Hondic From Closing Solenoid Shaft 40 Load Contact Main Shaft I Assembly 18' Oitite Oilite Bearing Bearing Lower Main / y' Coritacts 13^ y • Main Crank 48 \ Bevel Gears ^9 J t 1 For Resetof Undervoltage Release Lower Shot, 39 . . . Relay Kicnoff Lever tC f^ / Jumper 14 / Strut 6 Trip Link 5 — in- MANUAL DRIVE for TYPE 0MB-25 - - 'CF- 'h—- . Latch Prop Main Crank 4is • ft:- Handle Shaft 40. Fig. 9A^BplAKgR Fixed Pin 50 Coupling Crank 44 (loose on. shaft) Handle Return Spring 4! ^ • * • . •• -3 vi;^. Fia. 12-TRIGGER TRIPRti>.G- LlNKA%:j^y^ Oilite Bearing — Sliding Cam Clulcti 42 " . ''N.-,,,*- • W:.m of TYPF DMB-25 Main autch.43 & Belt Alarm Cam 72 Handle To Handle Shaft ^ ^ Oilite Bearing Jo Reset Main Shaft I — Spring To Trip-^l.atch Assembly ' and Contact Shaft (see Fig. 9) Overcurrcnt Trio Shaft. 52 To Solenoid Bronzb Ci':tc P'"-"rg3 Trigger Spring 56 •--:v ''iF';. —To Hickoff of Relay Contaas KicHpff Spindle 51 h- Main "^Bronze Oilite CranK 48 Bearing For Reset ot Unaet • voltage Release '-HlC i- •'r U~ manual drive TYRE DMB-50 ; / .V -1 • Trip Frame 54 Wilddrawa! Trip;Lr^^^^^ Ciecrance N- '/iq ' .'''CjCt l€. •J'Brj.'.'-O'j! Coil, supplied ^ l^Arcino Contact Spring ft i Arcing Contact Stop Nut 22 E-K Y^Contact lY Spring to h\ \ •yJ Clearance M - 'Tnrp'\. (tO-^ Tnp txrtch 33 Square j , K Shafts Fig. 9C ( above ) I .' ^^Toggle Links 7 ARCING CONTACT ASSEMBLY Clearance [ :^~'7'r/p i ; Trigger 37, tt . min r ,0 otter start of Opening •y^J\ V '> Trip Lever 2! 5.EUUENCE s^Main Shaft I OPERATIONS •H Fig'.9B-BREAKER CLOSED Fig. 9D-BREAKER OPEN, ^uf Lotch Not Reset Overcurrent Trip Shaft 52 (insulated) Fig.l3-TRIGGER TRIPPING LINKAGE of:TYPE DMB-SO —Overcurrenr Device 20 Overcurrent Device 20 —Trip Trigger 37 . \ -Trip Trigger 37 Ta Shunt Trip, Undervoitage Device, •^Ta Bell Alarm Lockout •\ ana Bell Alarm Lockout ier~ ^ftage Device Trip Frame 54 £) FEDERAL ELECTRIC PRODUCTS CO y 50 PAHIS STREET RfWAHK h J USA ~iTp Shunt Ttip TYPE DMB CIRCUIT BREAKERS. \ ' • err DATE - •> . . _ S- : hi-'-"-'.! OPERATING and TRIPPING DETAILS - •' • '.* ,T. -I L '• CHUTE-S ; !• • -^.Tr PLACE ;:=1 :: L , ;• • : • vt li.r! —SVg •.|•r;jl4 ' ^4S7 \ 1, - N •'PI ?r • IV; i .='•• j 1 » » . L— -1-^ -T—:—I— ij ",y-—' V t 'Jxfcv For Co// 25" Min, C. td y ^1-' rir r-f — — y;'L Extra Aux. Sw., if Supplied ^ i'vi^ )'f-' \ Auxiliary Swirch n 1 1 n 1 1 •1 n 1 1 1 1 •1 30 Ceil Alarm Switch, if Supplied —— HO" to Close 1^ I Shunt Trip —H ; Vr tr. ) -.Pi , .. f'V,. r. .V *n* j . I - uh I—I :':i.' ' '•• '•^(x P • -^-AS-V • . • Underuoltoge Device, if • o:;- , -,s,..,, • P"."plied •-; * ' !>•/ • .ti • (• • ••""'7 • - ^ •"''W -"^'irl iii Fig.7-WITH ARC CHUTES of TWO POLES REMOVED }. ',i FR0N1 ELEVATi^f^ -f'®if^ •-^ /1-. q./.( •, • •- r'lq.o 1"' . • ^ V?. V - : i^^-RONT VIEV/ on DRAV/QUT MOUNTING. Two Arc Chutes removed; ,e the third moved up for contact irtspection. A W'i >vt.4 Wy rW-:^ t' . •f /• i r-i- • •r- A M Far Cell IB •<• ir, •-•'• -••'•• I'=' : Vi , .| j. '..y .•'•• ••ly -"ll'-,, =•-/ • ' - 1^-Ua !'•' • • .4 J.Iv- . !•' / n i rrv ,>i ^"" .•.•i'.:4.•••;s"! •r?u !•• • .. • ' ,« • HT ' • -.. "' . •• '-in ; 4j'-.--v' ••: f T _ • -M ?;•'• •'Sa'-i" '-•>- •f: ii' f :• I'ffl 1 - I I/O" to Close Control Relay £X-;;h •• ^ '• •-" 'j.. f •••ii:\ X, -.-i'V.': '"hi' 4' Shunt Trip^. ttsTt-y. >-^.'i ' ' •• • •-! • Jiis Undervoltage KTfF^*' ^ •> / i ,-••• • - -^-f ' 'f~.. •.•? s t. » %«-i,v,' , •"•y z%\ Device, if Supplied • .r'Nfr '•| r ! ,-.<"--'.a * •' • 'n; Fig. '4 •BEAR-ViEW ^ DRAWOti MCL'N"; .NG iw- Note: The control terrolnois •- •'-• y ore in the "alternote" 'Jj locotion ( see Fig. 5 ) .. •' , 1' ^•c i<- 3 ->i OPENING In DEAD-FRONT DOOR .. /O?—— I yip .A'ot for Construction S--Z8-5'' u:..' DOOR OPENINGS € Handle Shaft - ' ^6 "^»a for i Kay ipck^ 'i 'if Supplied Cell and Door Nor hicludtd In Breaker Style Number 1.. H Cell Depth 20" MIn. C.to C. Yy Bonier Assembly, If Supplied ^^•'Barrier Assembly, if Supplied 1 Control Terminals ifti Cell Door-—>-J| i II II 1 ~r^ • '/q /« Min. Auxiliary I / /c. Switch Extra C.T.'s, if Supplied " 237/q to bottom of 4 7/.gJi / »1 Matching Contact y 11 "v/y '! 5" ,CK OP eO I—^ Hari.dle 3/4— dio Alternate Location of Control Term inals, if Supplied •Extra Aux. Sw. IV; ./:t» »ii- if Supplied Electrical Solenoid Lockout, if Supplied Mi —Alarm Switch, if Supplied Overcurrent Key Interlock, if Supplied to. Trip v Vj •i" ;^".. ilf,'j m::3 •Grounding Terminal y ATI ON t: rviiioN j ^.5 Dimensions.in inches IW" J federal ELECTRIC PRODUCTS CO. so PARIS STRErr. NE»VARK. N. J.. U.S.A. TYPE •-I DMB-25 CIRCUIT BREAKER . Apprcx. Dimensions-Not for Construciioh " DATE BvOsSSj m. SKunt "rij^ Source • I TYPl CAi- COiW'ECTION DI AG RA" FOR DRAWOUr MOUNTING o iiJ U"" , -jiJ Conirol > Grnd Source qOHTROL terminal (£r- nn t4 t4 assembly ---I •••'if terminal BLOCK auxiliary RES 400A: SWi'YCH CONTROL OVERCURRENT SERIES COILS RELAY Key Interlock N-C Contact in this lead, if CONTROL used. CONNECTIONS POWER SCHEfwATIC To line side it OV is immcd'Qie reseT", but to lood Shunt side it time deloy voltoge 250 V ^ 11 CONTROL LEGENO Beil alarm conlar>. Closes onfy when breohTr *ripped (rom I'vercurrent Undervoiioge du.i.u BA ^ Contact closed -nei. urealcer it open c< de- r.e is de-energized |"b" switch) ^ UV Contact open when breohcr is open or device CTO CS • OPERATIOt4 Is de-energized ("o" switch) Conloct closed when CS is operative o) b) e) d) e) 0- Elecn-ic control switch (stolion) R Red Icmp, indicatus closed G Green lomp, Indlcotcs open Electric control trip eonfoct Electric control closing eontoct Trip coil . Closing coil (solenoid). Control reloy Xj. and xj Responsive to X ADDlTlf^^f/. SCHEMATIC Control twitch CS/C cloicd. Contro! relay Xcloses xj.ord xj which teolt-in Xthrough xj and resistcnce. Closing coll CC closes which cfosEt the brcoher. During closing the brcolccr mcchnnicoliy opens xj end X2 so Xdrops outi ^ eokrY Is in closed position, x^ end xj orr incc J front coil of X. When brcoker is tripped, xj cr.d xj recouplc to Xpr.,vided Xisnot energized, -.•iViS-i-o;..''. ''.'AV'-''?-:,: thereby assuring no pumping, ' NOTE: These connection drogroms ere rypicol ond for information only. Actuol instollotions rr.oy cii'fer ronsideioisly'according to' specificotion. ALWAYS USE THE CcRTiFlfO PRINT rCH .VtAKING CONNECTIO.NS. .• c - V-*-: R2.?2-F0RMA DUALOVERCUR- ,J I RENT TRIP DEVICE -f: E25 omp O O O. O O .<• .--• — K,. '0 900000 Note: When bell ola'm is used omit fP-m lead from 3 of auxiliary Switch to drowoul tei minol 9 and odd new ieods 05 shown. SELL ALARM CONNECTIONS for ELECTRICAL RESET from Shurl Trip circuit ond rnechotiicol reset from handle. I- • ••'•I :i ' This scheme for d-c shuni trip. ' It requires modtficotioi) for o-c. BELL ALARM *«! •' ''i '' '' " *"*' * P- -"v"''I•? ••-V.v'''Y- Fig.23-F0RM S (.ieffj.-i DUALOVERCURRENT I.I 20 19 ID 17 16 IS 14 TRIP DEVICE- 600 crfip aOTTOM • 4'' TERMINAL assembly Y4.4,. I'.'! »• • BOTTOM AUXILIARY •4 ' r.ef SWITCH t 'i 1-i-.P 0'- AUXILIARY SWITCH orid TERMINALS JNOEftVOLTAGE DEVICE 2—1 Fig. 24-FORM A (right) dualOVERCURRENt ofOropout VoUoge ^Device Normal raise dropout ' vice rsrso) . »''• .•.'.-/.•a. TRIP DEViCF-600 omp -Reset Lever 85 •v Wit/] Cover removed, showing ^''^•••1 i-lI instanraneous pickup adjustment Oevits / Peleoseti Jr^ ' ' Open . -f fc". I .. .-rt Positfon tte%teosed Trip Lever 64 1 Undervolioge Device 31 . y 'VOtTAGF orvirr ArronQement for Trip ond Reset, ^—T— Solid lines of De^rice shQw Reset Position • federal electric PRODUCTS CO SD PARIS STHEET wewxan HI USA... TYPE DMB CIRCUIT BREAKER DATE "t' ; ''?,'£s -ao\'tjrc'ioN niAGRAMs SrJt.-S', W'- Rt^EWAL PART^'&ATALoe APJD M'AINTENANCE INSTRUCTiONS Federal Pacific TYPE DM3 15-T Air Circuit Breakers January I960 -I -• "'If li'- t. U-yrl: .rQ-- '"T7T. /V i „• Hi- - - '-..-I* '1 if. " ^ 9-^: RENEWAL PARTS DAtA •v-'f:> Renewal F^rts Data wi ll provide you witli the proper Wentificatiphrof those Ren^^ ..•. ^•V;..'',v >' may require in the maititif^ance of your Federal Pacific eQuipmE^t ' . i . . which you ., • 't 'S desirable to forecast as accurately as possible yoUr requirema^ts for Renewal Parts to -^s-ur-^ fhrt ^ ' • SiSSs'S.S'S"' - oniricManS The recommendations .or stock are tiic minimum quantities that should be.a^liabie for servici'io thi' equipm^L f^el Lrot you are in a better position tlian v/e to decide how much you wish b inv^s! Renewal Par.s. ine importance of minimizing shut-dovro Urnedue to possible break-down^ no -/t (ogefiier. with uw- dislarice from source of supply and transportation facriities; should bo c^ot .d.n'ed Ion, n . ed by' i^s-.co.-i.,.i...ied i you when orcienng renewai parts. WiraUis anftik ,, u.ia„ 'nrjine 1. Obtain the complete'namepla'te feadirig of the r' , apparahis for whfch the part is deslrea. jSh'/yo"-'} 2. Turn to tiie Apparatus index and with the name-'plate reading find the page' humbe'r. of the -. • .1^, • Renewal Parts Data sheet, SiMil ' ' 3. ' '* y.*> '*• •• •. where tlie desired part is d^cribed and IdcnL'fied. y^t •:S^y ordering INSTRUCTIONS ilEifJwS, ;;Fl^'iJiS " t" ,nd adrnt tho p,,,. Oivi it. cmolct, ddmcpte, ll lu apparafus. '' ''-i''"; W""'F«' -.d.=d,L Scvu. llL ,= ••-' '•'I "a„, C.d c„„.p,,d..c,, Sdi l„, p,p. ,, ,p. (iKt your - •v^i i i - ' • r'-'yi' '-' • • :.> • • i- " ' \ •' ("• l~ O :.-i /-I Tcsf • , •' \ . '• ' ••(2) '':.• • R'v . *o'i2ge to be .applied'to'breaker as indicated; IIMS ^J!' "S''^ , , r- •• • lo be 1680 vofts, 60 cycle (field test) . •/ •- I !\ J ... r;Ij.-;i: CiReUiT BRliiAKERi i v'l ' • ;. .' circuits and grpuna/ahtf;nwSinirtil^W^ conbcts Manoa! Opsrafion '' •. • .^ ; •i, ; •. • %r.; '^ "• S'^ces. sr...cHa,i • . Alarm,.seeBreak^ item ll. shoul(? ° Trip-Free Oporafion- ^• • S 1!'^ -IS; •; • : : •' ' . trip• V • • ^. <.' *.• "*; ., ''''' pushed upward breaker should not close ' ^ " ••''•'I'A ^ .-HC • . i= ^p.ssudjc breaker shuuS trip frs^ beibra brp V-^^ • ,,• 1 breaker w trip-|e\i^nioving ifveor genfe^ ^ W) Electrical Operation ' * iV/ '-*.'•"iV^iV-:"., Rated Control Voltage . ; Control Devices ^'endidjJ^' 14-30 '48 volt DC • 250 volt DC 115 volt AC 230 volt AC 460 volt.AC UndervoltogO trip 24 volt DC 125 volt DC ; • I 'V.;A'A:v.28^(id:v;g 90-130 180-260 95-125 .190-250 380-500 •v.. '. -_','u> • Less than •90-130 , •; : 70-140 • 180-260 ' 140-260 •A . Reset • 95-125 ' - . 190-250• • . , 380-500 37,-5-75 100 75-150 34.5-69- • 200 , 92 • , 69-138h : .184 - • a 1-- •• .;«u'- .l inve delay 3 to4 -• -Cl) .CD .lime to 4 seconds. ^tikerii dosed! , ; . ./. A .Xe) If Bell Alarm is supplied refer to'I ten 11. ' • V^: —. • •;V-. v '• ;: ,oA switch 3or 4;tio-r^ 'while', '"• "- '• '(M '-0 'fuii r.?-;ai-;;,ui rinc^ "'rCna-.iC^r.or eiecfrk faiiuro. Special aUenii: ,j v:> ,i(. one end and cotter pins"are bpenfi°"' •lit- are in place, springs are net .. . W) Trip roo insulation shouifinotsiip . ": :.. • (e) Insulation on shafts should not be scratched. '. • i-'. ;.?>• (6) ' ConJocv Prossuro •' ' ,...:y .j|)v?&ip:brpakerWitivb»e^u„^ ... •y:i-.'V,sk .,'u • .•-•.; .••••"•.' •^ci! \; A-"i ..I.. .'rv'-'.V..;" :\-s' .1-^ . . J TABLc 1 ^ • " V-Gi) HntinQ 100 125 ^;,i5Q •' 9v:.y i :ci:up r^;o Trip i ;ip V(i:-ii in Ti.ioe (3) Mihcftcs SpST^'icItup Coil Rating. T.-ip '.I'ijiuf; No Trip Tnreo (3) Minutes 88 132..:. •• • .,:198 :>=• • •• V. WiV, ;*•'.• v-i-J: » • •C- .:• V•}, '[J-yr-:-: .;;.*v. .' .yi.' \ •- '\l ;• [y-'Ai - Vi": • i' •: -i,/. •S. -•'* • " •*••'* '• ,••;: * -.' *' r. . •"-. '"v Dm j5T~T:y.y COivTACf -V,••:.:• i;}-: .• •; . r-'.- t: . . - " •" r' - iRgore 1) >•'; ••'•••VVv : ••-. ",l.'--:v"VVi'v. ., V -,». -.- --rj^.-^v' ^^J.,... .g-.r. ' ' .•^•.... ...•«• ' . _•- .*.'«* .„.; .*:• • • . ..• -*2 . i .v'- 'i '•V. .•-; ^ • '» ': > . I • ' i, ' • • -> LJ t:y, E: 1• 1:^- 2C 2B. » r"r\-A .2--2/r^ 'r X Iq • I I '"/st-" •• V ... , fi^ V:. e«— . -.vnm '^w--isi Jj ur / 9 YI 9 ^ ^ !l • fl tl ' I {] ' Ix 0 u .m, la i. ' ? '; t" A • r - ' .t.. 'M •>" ^ aa • - •• [' -. 1 ••••: •' a «•' '1' '< '< ' I -a /' •••"^!::i$' • lO . ^:s"£?sat " iA •••• J'f ' • .M'l ':12^' 'fr '•fMlfri'r . - r'^; ^ ''i /lO 'E • E''i J '' X •;V0-; ISA '"^y •' \ " •^ r ' ^ vt'*—«- '-^ V,;.B V • •",-!• ,. • .-•t' ••- . •:- ",1V "(Flcure 2V ;. •.•••'.';•••-t^li.;.. • , t." i"^rr C'f; ; • ' -i.U •••<-. V . . ..^,v:-i-: o, ,v . .rj,.. v , j • : on vhis (is? VnoScr .:! Mcni.:- c-JvI; ♦ Ciccii^ tERS Those Parts Ai'e fllostrorted/See Figure 2 I Solenoid Assembly 125V DC . • •;,*.VjV r. •: :.•-; : Solenoid Assembly 250V DC • VIA - Solenoid Coil 125V DC . • Solenoid Cor! 250V DC Vv-v&VV 2 . *• - Top Auxiliary Switch . -/•, \ . ^ • ;; • • •- ^ V . rV; l/ v ; • 'l''' i." A'-, '. i;.' ;• Undervoltags Device 250V DC Instantaneous #"V *• ' .V . '^7 V • .. .- '• d'; 1151-0952'. • V--V^-1152-0952^v:V;:j •i'*> "i f* . VV "'V-'A.'';.- • , • . ; • 1153-0952bV yy$y'§§. ' • 1- -• •- • • . " V-1154-0952;: ;d ; .I151-b693;y. j il6ld54iA ?: ; Il54d757 . . Shunt Irip Assembly 250V DC or ^uGVAC Vy, - ;iV'" . 15 - Shunt-Trip Assemblv 48V DC or 115V AG ' • ' . Shunt Jrip Assernbly 125V DC or 230V AC ' •. ' 1151-0688;:.: f vd" V• 1151-0631 • ''"'j'-'i ' ' V' .tr- 1151-0775 . •^d-d -' . . 2751-0068 ISA - Time Delay Assembly used with Undervoltage .peyic^V,' • 14 - Handle 099-007 039-004 .. y . • . .1 t|ndervoltage.OeVicf 125V D^ *d'. ' *•';/ ' 1155-0757 •: •- / .1156-0757; ; .v V,:;:- .;-V V16- - Control Relay Assembly 125V DC Continuous Duty : . C o n i r o l Relay Assembly 250V DC Continuous Duly Conifo .Relay Ass-eniily 115V;AC Continuous Duty-V • Control Relay Assembly 220V AC Coiitinuous Duly • 'Cori -oi Kelay Assembly 440V Ad Continuous Duty 16A-dontrol Relay Cpver; • • d .aAY y'!i. 039-003. • • - V • . d:-' 1152-1106 . 13 ; - Undervoltage Device 115V AC Instantaneous • "d' • 1101-0589 . ;-Av-'; ; "---iV-r • 10 - Arcing Tip (Movable) 11 - Arcitig.Tip (Stat.) 12 —4-Point Secondary Contacts (breaker) • •V-;V, - 024-012 099-004- y 9- -Jj-Point Secondary Confacts.(cell) . ' 1101-0499 Bell Alarni Switch (N.C.) ' v-V. " ydKy-y-y' '1159-0581 : U51-0973 y =; ; 2701-Glll' dV^vv y; B4-()01 A • ' 5 —Breaker. Grounding Contact .6 . —5;0hm Resistor 7. —400 Ohrri Reisisfdr *•; d- 1152-0951 4 , —Basket Assernbly 225 Anip. (4 fingers) —Bell Alarm Switch (N.O.) ' 1151-0968 ' U58-0581 : —Arc Cl'iute Cover ,8 • d^;:,. - 1152-0968 • 'VV'~ Auxiliary Sv/itch Assembly /j:V 2B - Auxiliary Switch Front Cover • ";-?Ar';'V ^ 20 —Auxiliary Switch Rear Cover ^ —Arc Chute Assembly •VV;'. •• • / • . 1158-0791: ':VA,;'7.y;y:d •" 1159-079T' •; :'A.;rA;V; • v , :ii&6-0791 V •. V/ - 1167.0793. " •T.* d"' 1168-0791 d;. Vd::,;|A:d'V ' X •V;.'''dvF ,'vA^A:y;ddlpl;.o59^y;•;: •IV VJ.riSld: • •''."-'".'-''-v V : - " '.-A.';/''.''' y.. O" I' r;*;^ j./ *.«• > .* . ,•< .*$ FOR 'Di>,- r% -.[101:1: ' or'ic :: :."r-.-no'vai 'ptj.-ts civs type ''V V.'e-1.!;,- -wr.a sc-rini r.l'ov.T, on nopcplcte of brooker. • • Hansie • Closing Plate , 2 ' I-''' '.s '" • '. "4 1101-1186. •li:51rl3T2 .IIOI7IO43 ,. Indicalbf Wameplate. Assembly 7 Coil Spring V •••••. =r ^ mWl74 Negator Spring • Connacttng Strap • ••-. 14 1101-1188 .110V0S24. r.:: . y; 1102-1033 1101-1038 Connc'ctino Strap Moldecl Faceplate , . Auxiliary Shaft Support Shaft Auxiliary, • Clutch Tubing •!; 12 V -vr :•.: ••^ Ind'oa'or Pvelainer • F::Rf9i:::F%o- 1101-0960 vrr'--r,W Intllcalor Pivot Shaft. 10 11 ' - 6 9 . •, ;• : . t •:; ? M-.-; 1101-0836 vr-i;-,;' 1101-0487 ••„Spacer. K.. .18, '.'i i t - r ' - V,'." •: • •-. • . > f , - ; " 23 Rod Sprmg 25 Link 26 • , Lihk'^ 27 ( Pin 28 • •Bod Link ... . •.'i V;-^, ;v,-; ••;,• • « •••;'., • \ . .5' .;•'• • •*»% • •••;>^:e • : >/..-iV;, ..v.- • - •../•»-I' •{•V • •:. ;::77O9iOnR0''''- . • • ^ •;v' ' . ^ . : 065-006 .. •'•. . '; l-i51-0'698 HV • ••• lioi.l?:23 • ' •« , • 33; 34^ ••'•': Reset Coupling Tube 35 Pin (9/16 dia.) 36 Drawback Spring Xi' • W' 1101-0544 '' • • • ' - ' ' ; ••• ,: ••• •• • • Pin .-e'e; "-; ,' •; pin , , E -i'" _• 32 ,37;" ••,>;•. ;'-I'i'i• • •?- J;,..: . .. Mark "Q" Assembly (completei. ;• •31. •.i' K'i-v-iV . ?• v- • s" f Crank Assembly^ " •-••• •,V v:fc.v • Bell Crank Assembly 24 "• 30 .. ' ' '•] ••• • Ramp Assembly *'a'v 2?.^. • 'i- '- V-'- -• ;• • - cji' : . :.. a: .: •.;r'>f-i;: •I-?''!' 22 - • • '••i^66i;i^rrh;:... ... Ass'emb ............ , Coup!ing Lever ly 20 •21 '':v: ! ; ;;Link Rod • •:• ^- v ^ 1? V:tr " :"V - 1101-0311 ^/Cam Welded.:A^^mb1y:.• •• .' ', i . PART NUMBER Retainer 5 • • V-'V.w. '• V / 'Moiried Escutchecn 3 :;"• ,^;., . DESCRIPTION JTEM " . . , i -.'.' ®?R«coiiH.iGn<:iL"d'Spore Ports,'See Page 7-,. 'MiRy 1101-0335 1102^0335: .W .; , •• :; • , ... y'm. ;! • ?•' 1101^137. . . V/asher . *.•• •38, " , •• ;' im :]T0i-bi71 H1SM328';,S;:3' • . : '•' •. ' . . 1" ' > •;>; r. ' ••-%'J' ^ A>.;' Vr'.;;; :• • 8I'vv'; V" ' V r ./.• iP'; . ''..'iF/l: -- .-I -r ?.n?.C:viPT10.-; 39 Bearinci Cover 40 Handle Spacer Coil Spacer Lever Assembly 41 •n- 42 ':-rl;':: -:>,. • • HUhlgtR 1101^0337.,- ^Mi10M433 -il51-066Q Lever Weld Assembly Angle and Stud Assembly 43 . 44 45 Mechanism Stop 46 Spnng • • . ' ,/•• 1 . '^• 48 , Lower Shaft . .. • • 1101-0543 1101-0338 '. • 1101^336 Sleeve 52 ;• :.Mlameplate 55 56. ,1101-0157 •li()l-0334 57 ViAuxijlary ShaftSupport: ~: 58' ,,>in;> •-• 1101:0474 •./ • • " . c-./1101:0340:: • , . •V;V. 59: Hair Pin Cotter 60. Conbct & Ffexifale Connector 61 Square Shaft Assembly Compression Spring . >'• • f-' • t!-: ' vl 64 66 • Clip";. - 67 Contact Arm K Frame 68 69 ' Leading Insulator , Arcing Contact Assembly •'• 70 Upper Terminal 71 Lower Terminal Block ,i ., 73 fe'/; -r-' • •• . 110i:p445;, llQl-0332^ ' 110]>0595.;:r '. ii iistboss • : i v:^101-0422 ' ^ . Trip Bar • ;• 1101-.0423 : 1101-0539 ' ' Trip Bar Irisulation Plato . ii01-05"40 • . • Trip Lever 76;' 10 - 32 X1/2 Ig. rd, hd; nyfon screw : 10 —32 X1-1/8 ig. rd. hd. nyibnscrew '.V . p:;.; TTrip Lever Assembly '• .'ijii-Rod 80" Pin li01-03Qi . 75-: 79; 79- •>:• 110t4}^2:., 'VCiisiMo' 1151^741:; 1101-0431 65 72 .iiowm3^ • :ilbl-0432 "'• Cup K Frame Clamp K Frame ' 63 . 1101-0327- ! ' 1 11510662 1101:0326 11010369 • • - lU.r - :r . yy,. ; 1 • ''1101-0478 •. .Eccentric Stop 62 .v. .1101-0564 "Piypt Pin ^TPiri' 54 77,. •.'•s-.Vf'-'K • »* * .' ..4i > . Adjustable Stop 53 78' • .;ii0l-0316' C Scrfew 51 74 "rry 110Ir0314i; - Stop Ring 50 r- ;••:• • 1101:0315 •49 P«.!V- •• 1151^0678 iioirosn 'V v' • 1151-0677: ' 47 ' "'V: y •1,101-0496 • s.* • :r,. wmimM •T yyytlS: . yyy® yli V. -•iiSCRiPTIOM ni^ • •'i., 81 ., 82 ; • • •-• V!?v .••• •• •".. -•;.•• ;'. . • /../rXA > Steel Screw 84 Steei.Ser.ew 85 Rea r Ro j.ler V/eI Ass embly' Guide Roller V/elded Assembly V •;••' • . Lever Base Assembly 'Retaining Ring ; Lever Base Spring 89 90 Carriage Lever 91 Washer •V ' . 83. 88 XxMxX1WL0589' ^ / 1' A.'^^iT'Xli01-b343 ':;Ax' - yX-Xi'ifT'XX 'V •.••»• XT"- •-. ..Iipi;;034.4 ,v •>'. .-V- • X X .1151-0612 •.; •1151-0613 , , . A .. -1101-0018 ( . : • ' ' 95 . • :' '- '"•'washer 99 Spring. 100 rnSmSfi -••y^p Pin 102 Pin 107 .: *n09 . . '• • •' iibLte \tt:|XXa . 1101-1023 ••;-.XtA.;-. Ii5i4qp8v,-.XTXXTXXA vxX,3|f id2-ob6:' .•'•'X-^ ' X. ' iidLKspXXiA'XL^ 'x', ^ llpl-0192V XA X- r •.XxT:'''Xv, Xuis^imXx'T -x • • '-'XT;AX'; •.n-'r. v rr-T15MC^' .toi-iuj/ ^•' . X • • ^ •., -.XXA ^ni3' • "A ^ V-. X'L' AX ''i'Ax: • • .-..'•x AhxP'-At- -.'x-xv •a: vX'-;-. •Xv;«aat-:A. . ' •A.x.X: X .'T-'-'L -X • X'A XXXxX:Xxx-x-:,x' • . .,Xx--a;x':x,.xx ^ ./AT;; ' • -A':,.. .... -• . , 'i ,• . .. • • •--^•:XASXX..AAXX---X.;T.:X^i X.--'--'XAT'..XX,...X.' ? .X-.'' * : • XX •' .A--'-' •:-'••• A-. ."A-- \ • XX^'X•'X-.'-AXAX;- y -• -••X.'; • -X'. ' •iXXXyA^i .. uX' i-;'' .XX.0Xy xXxfxxxxnA'' '."x. /-vv- -- ry;v- . .'^XXi- :x ,at:A:a ^ -• x,^a::::;ax XX AXA" -x:- ' X.' «X -.a' / • • X. ,. ,: ••• T.'X' X :«h:& •• 1101^0173 •XO.r - ••••;.. vX'. X--.X.:.,. .' XX-'X'XAX.. U01X1029AX-X--;XX:X Trip Trigger. Secondary Contact Support Weld;. Assembly : • . 1151-0756 ' X tii^oVabfe.Contact Assembly AX;XA X; • ..X ^ • jlsLos^L ' ^ IIZ V1 V ilOirto •X::3X AX-X-' .••••XXr S' Basket Assembly .X-X Brass Tubing •i' 111 •. • ••. .• 1101-1022 • v • ... , v.,A. • .-T-iXT' ' 1101-102.5 X . . X' yShdulder Screw ' ' Spring^ '•••"xT,X 1101rl0.il • ;; ^rip Rod-V/eld Asisembly ^ 108 6 't .* '. V'i • ' •"• . 115i-0918 X > -,4¥S xXX' yyL Spring Support -'• -i- ' 105 Spring \'- r;:' 106 • • • Basket Washer -110 • .'.J-X'.';- .. r 104 . ;; V•. :',y •i/;T-llOl-0504 XXXf X • ' . .1101-1111- . • V, ; Locking Pin • .. .•. • 101 103 ' :v::/ 1101-0499. • • • v'"' •; Release Rod 98 1101-0881 "' ' . Trip Rod Gutder -K;-:-•. . " '•* ,. ., ' rS/Vx • 1101-0465 X Can-iage Plate V/elded Assembly 96 1101-0,021 . •x- Clip-. • • 94 :*. T---:xm X"X X110L0019 • , .• iv'ain Stab • .• ;.;T - ^ •-•XyXX« •I'l ».*-. i . vvLv;- X; Guide Rail 93 X-Vt':vAA . -i- Arc Chute Cover 86 >•": n Arc Chute. PART • A ;V • ; . -'.L" . •'/. 'r X'- ' • • . • .'xfexXxXxxXgxA;'# ..X'X. ..xAX-X. ..x:x::''a;X:xx'xx A'. -•-A'T;-A ;'. .x'.vXA' :XxpXx:AAiiiii^lli| -.'•^••X^AXXX IxFIX • XiAXxAAi » ;V' Lorig Island City, NewYork .Los Angeles, Califorhia , Atlanta, Georgia Boston, Massnchusotts Chicago, Illinois Newark, New Jersey Clcvoland, Onio Pittsburgh, Pennsylvania ^ Oaiias, Texas St Louis,'Missouri. Santa Clara, California 'Scrantbh, Pennsylvania : : •. * l- ,1 Seattle,-Washington • Toronto, Ontario, Canada . Vancouver, 8. C., Canada Granby, Quebec,iQanada FUSLiJ OFFiiC Akron, Ohio Hafrisburg. Ponnsylvariia Albiiqusrque.'Nev; Me^Jco l-!artford, Connecticut Philadelphiai Pennsylvania Phoeriix, Arizona Armdale, Halifax. Nova Sco' ia Havana, Cuba •,/Mf A'Jr'r.ia, Georgia Houston, Texas Pittsburgh, Pennsylvania Baltimore, Maryland Indianapolis, Indiana- Portland, Oregon Birmirigh'am, Alabama Kansas City, Missouri ' Knoxvilie, Tennessee; ; -. Readirtgi Pennsylvania . Boca Raton, Florida, Rich.mpnd, Virginia. . Boise, Idaho' Little .Rock. Arkansas v. • . i c ,Rocherfer,"Newj^Yor^ Buffalo, New York Long island City, New, York ^Saginaw, Wlchi^n;: Longmeadow, Massachusetts St. Louisvii^issourj' ••jf Calgary, Alberta. Canada Los Angeles, California Charlotte, North Carolina Lo.uisviUe, Kentucky - ' , . : Chicago, lillnois Lubbock, Texas Cincinnati. .Ohio Cleveland, Ohio Memphis, Tennessee-V''; Mexico City, O.F., ;Mexico Columbia, South Carolina . Miami, Florida Columbus. Ohio Milwaukee, Wisconsin^ Corpus ChfistI, Texas . Minneapolis,. Minnesota' Dallas, Texas Montreal, Q-ucbec, Canada ,'. Shreveport, Louisiana . Boston, Massachusetts , ;St. pkersburg,'Flbri'da . ' SaitLake City, Utah . , , •;' Santui^cai Puerto Rjcd Gcrantoii,, Perinsylvania' , Seattle,: V/ashingtoh Nashville, Tennessee ' v ,' ., Spokane, Washington Mov/ark, New Jersey • • Sy.-acuse, New York ' Detroit, Michigan New Orleans, Loulsiaria Toronto, Ontario, Canada • Edmonton. Alheaa, Canada Griand Rapids. Michigan Tuisa, Okiahonia : r' :, New Yorki New York ,' Norfolk,.Virginia • • ' Vancouver, B. C., Cariada ;;. Oklahortia; City, Oklahorria..' .Washipgton, Dv C.v', ..'' Omaiia. Nebraska • •Wichitai^Kansas• Ormond Beach. Florida..' !''..Winnipeg, .Manitoba; C'anadi Greensboro, North Carolina Pcnsacola, Florida 1 'F : port Vo'th, Texas f San Francisco, California :.- :Santiagoi!Chiie' Dayton, Ohio El Paso, Texas •* ;San Antonio, Texas- ' Denver, Coiorario Eltharh, London, England •v -'si ' ' Peoria, lllitiols,.': . v.. i E='/\i©,ii F=i O' G e N E R A L -O-r I C.E S : S CJ PARIS E^is.ECT'ft S T R-E E T, , ®OsVE N e!w A R K 1, ' N E f;: U E R E E V 'h • .Vf:VO' ; i. RATINiCS. DIMENSIONS, PACKAGING—STANDARD SIZES [ p- - - 2M VOITS Oversil ] Unglh CfiO MO votrs r.JftWl I Clamttr Olwsntmn'. L6S. Quanlll)' Hamber. • • ECS.i ECN.l ECN.IS ECN.2 ECN.3 10 , , 5 r'p Cartcii .'W." 10 ( UhmcW Qoa'r.tTto •' ECSJ.. 4- ECS.3 ECS.« - '£CS.». • 6CS-6" ECN.S ECN.e , 2* E^N.a , 10 • ,. "s-"' I -'V- I w Efis-'e •: '• ECNI'.O ECSl.O ECN'.tZS ECS1;I2V : ECSl.23"^ "EfNlVr' ECM • Ef":; 'i K.- 10 ' I ECSl.S ECS! S 'S costs f-CSg.D ECM.3 KN?^ ECS2,2S CCS2.5 - ECNZ.2S eCS2-5 «.• ECM2.8 ECS3.9 1 »• , 5 ECS2.3 %- • » ECS3.0.. 6CS3.2- EeK3.2, ECN3.5 ECS3.S ECh4.0 ECS4.0 •" 2-. ECNtf.S 10 ECS<.5'":. BCS5.0' • ; . S ECNS'.O. ecus.6 . 2''". 1 ECNU tCHIO 10 •tCS5.6 • - ECNS.2S ECN7 ECNa -Hi' L-.i'ii'"':. s,; • :6«B.25 ECS? ^ ECSS ECSS ECSIO . ECSI2 ECSIS ECNU ECNLS ECN17.S w to , •Kt" 10 . ECSn.S s. 10 6CS20 ECN20ECN2S , CCS25 • CCS3Q ,, ECH30 . ECN3S ECMO Ecms Cmxin ECS.lS- . tCN.« FERRULE TYPE "oiJiritrr" T Catalog , prrlCU ECS3S' . ECS40 y - 'Ki- I 10 [ u-- EC$4S life' 10 ECS50 . ECN50 ECNSO ECS6Q BLUE ecssD . «•. 8 ecs90 30 30 • ' WIOTK I ECS7G CCS200 .14" I S Hi". I ,-1 Ecsno ECS125 Hi" • I 60 9K-;V-( ECSISO Ecsns ECS2D0 EC$225 IK- I ECS2S0 ECS300 170 no UK- ;f- IK* 13«- • 2- I I eCS350 Ecs«oa. - ECSSSO r 290 ' ' ESS500 ECSEOO MIDGET FUSES—Dimensions! Overall length, 1Vi"j Cap diameter 13/32". I AmfM/to 32 V'lLTJ Caiflicj Wu.Tiber 240 VOITS 240 VOLTS MEN.l .VEN.15 1.25 I.« MEN.2 1.0, MEN.3 MCN.« 1.8 2.0 Wff!2.0 MEK.S 2,25 M"tH2.25 MEN.S' MEN.8 MFNl.O V;N:.;25 2,5 2.8 3-2 8.5 &C ' O O IV! Y FU s e . MEm.2S 1 Carton quantity; 10 I I ^ ^ r c.' Ameoffs J I 3\i. 21<0 VOLTS -j .-,v MEftl.t MENl.O MEM.B MEN2.S ' . .'MEN2.8 • MEK3.2 , UCH3.S ME: ..ME. ' _ . MFI Mf •«£! •«E ME. ME; RATINGS, DIMENSIONS, PACKAGINO—STANDARD SIZES I i jsBVom eitnin^sns Catalog Nutnber 6yetiVr~| Lcngift , Cap Oiamsto? PtlBbWlBUS I | Carton 'iuantity lbs. TiJtiwll ', j it' lOO. i£Nl,125 u.vi.zs" lISSO.U/i LtSUO LES12S LESISQ US175 CES20fl IES235 US2SQ LES300 US35I3 LESiOO LES/.W I.ESjCfl - 13«t LESSSO SSWSEH^.-.V: ? yv.]: '^.-CONO^ .(• "•»: : = ••i'.. r • it I , • • can length : • Blapctcr :: i: o'.m P%h .'.:••,••• Cartbb t he Ciuinlliy oai 100 Uw '5: - -••• V;.- ^ x : x x x ' •• • ;X X#-X:X X'. -/xv-x.^ :.ev-.^'ivl'rxXX-TxXX -:eX ''' V.v-.-'.r;.- X •' •- " y.:--'.' \. ,; - • V- •.. l-zy:. , •xr-.:x.f:- .'1". :-- '- • • . X;-.xx-ti-e;?VeX^y. .-•-•-X?:X-X'-~ -IX- ^,x-^xx-™:.•:• mmm'mVemmtmgisMf> •,i-•«•: v^Sr: Sho -•, 9 . :-r " ;;.: (>y '- O, /• -1 fl) O 0 c, L ^ - ,J i !. > \ 'X ¥ '¥ • • .♦ * -:-X -••:-• m •Z :x 'M •• - ;••;,•, h 3. Turn to the indicated Renewa!;Parts Data Sheet -i: where" the desired part is described and identified. . ; • ic V . . ' ORDERING INSTRUCTIONS . Give the Pnrf // or other iricntifyin^ itcrrnxrp end name-tlio port. Givo'the complefc numcplatc redding 6f:the cipparotus. State wh'^ i'T shiprnent is dosircH l;y f-eicjhl, cxprc?ir», or by pcrce! post. For mainrenoncc Service contact your noorest Fi £ oalcs Office to whorn you should iicnd all orders and correspondence:- See last pogc of hook for addresser, of FPE Solos Office- : • b' - • ',f". • ;• r . * v :"V-,' «/ ' \. V . '• •w.S', .• i'Qlx iViM-> .•,.1 - ! ; Avl'>' aLIJi i i"i'iM::.f:,A:~f<':> , ;> (i) Piolocfric Test • •^ •^ • , (3)1 Voltage to be 1650 volts, 60 cycle (field test). • • • • • • • , Voltages wi ll .be applied for one(1) minute without arcing.. .'• Voltage in be applied to breaker as indicated; V ' .If. • 1). coniacis ciosea voltage 10 be appjied between phase and ground and between phases. '• y-.y.. 2- with contacts open voltage to be applied between line and load termihWls,ahd:^^^ ; • and load terminafs and ground. C.' ' ; ^ YYYy line - 3 - voltage to be applied between controrcircuits and ground, and line.tenainals Ay^^^ .-./closed. V/,;" ,••//' •'. . •' • V-t'j;'.' ''frf •- (2) Manuel Opuration * ' •' ;' ' • "• • ' ' (a) -Bre?.!.?.: will be msnually closed and opened no less than iv/snty-five (25) b'lties,- BrGa!- r b'tnri, .•landle sho'i'ri .'eiurii to pcsiticn. (b) I'V-lts btsake-f is supplleci wiln a Bell Aiar.-.i, see item 11. lY. • not •' (c) 1rip breaker by ninnijally activating shunt trip. Breaker should trip before plunger reaches end of its travel. (a) V/itiV trip bar pushed upward breaker should not close. ;; t , /V y ;, (b); ,lf drawout breaker carriage locking handle is depressed the breaker should trip ffee;-before%e; /:r';«!;'Pln'-releas.es' tj^.ker-.jfrdm.cell. . : f-p, Ccl.' Tnp breaker wJth' tfip lever, movirrg itVery gentlyhr . r ' sYY/ y:-.' . ,(4) ElectircaI Operation • • • Yi; •' -''ypY ' • . i', • . Y\'' Electrical accessorieswill operate satisfactony for at ledst five (5) operations with maximum and minimum voltages as given in following chart. = /-f , , • v' ;/ tb) Items to be checked are solenoid control relay, shunt trip and underydltage trip.whlth should • ; operate satisfaclpry in the rangedf voltages shown. Control Devices • - .;iShprit ^Trlp ' Solenoid '' - Undorv oltogc -Voliago- '. V'Reset'//./ • "v'c I'f .r/A',-^s^voit'bc- / •\ " 125 volt DC /; 90-130 180-260 250 voltDG . ., • 115 volt AC i • 230 volt AC •• • thsn jiBiss than .'28-60';: 90-130 180-260 : TO-W^ 100 P: " • 0/ 140-260: •f 95-125 • • f 95-125 , . 190-250 190-250 ; •••• 380-500 .380r500 . 200 346^69: ;A;-:69-i38 /•:; 92' 184 (c) Undervoltage frip shall operate between 30-60/O of voltage rating dnd'mechanjcally.reset uridf^rvoltage trips ihall seal in at SOS of rated voiLiC t.fsee table 4b)f•/•i//' ' v W** t, , (1)'.Tinie delay 3..tO:4:.second3. • pP':pp'::'Y.-P'. ' / /"i : .(e) If 3,d(l.;^lafnris'5up|^^ hefefito 11^.'11. . ' • ' y ' r .• :i' Anti-pump feature of breaker shall be checked by operating cloSihgfswrtpiii/S orJl'times^^ breaker is.ciosedf. ,-'/ ' ' y • - a, ; ' • •> ' ' • . (5) Yrsui! Inspoctioa r ffv.; •yy'Yp, (a) •Breaker will 'ill be inspected for signs of mechanical or electrical fa Iipira. Special dttenli on should be ;ee that retaining rings and E-rings on contncls/.etc., are in place,, sprin^/ere not- ' ; :-..given, to see . ' . v/.-> '».» oi; .. •••:•.•. .;.v! ..; It. r-1 •'..•!'i..-iol ".cf-.i? -ifcing tip cr» .-••ijfi'flr v.hi-r. r-rcina vjr-vnrcj. . . . - (c) Adjustshle lints (maie) shoulcj not bind on crank on main shaft, v .- (d) Trip rod insulation should not slip. ;. Insulation.on shafts.should not be scratched. • } h:'''''':i / ( 6) Contact Pressure . i'/,*' I i»•.* (a) Toleranceon pressure to be + or -.10%. ( 7)' Contact Sequence . • ' ' f'M,' I .. (a) DiM8 25-lT contact sequence. V^v; ;\ • , (1) Arcing, contacts touch. Gap between main contacts should be,appro^irnately.*i/8 incli - it is important to'keep.gap at mis partof closing as great as pQSsfble;^!:^:^ • " 12) f/iain contacts close. (3) When main cor.iacts arc- completely closed arcing contacts should be open no more Uian 1/16 inch. { $) Contact Spoc.ing,& Angles ' (a) DMB 25-lT (f^efer to Figure #1.) ,, (1) Breaker open.. •. •' • ' r; , (a) 1-1/8 betweei center line ofmovable main contact and stationary contact; . (2)..-Breaker closed ' . "(a) 1/32--3/32 between arcing tips. • ':Wy% x..--. .Wv •' (-9) ;Cfiec!;'af'CoJibrotton;6f .Coilrofter Assembly in Circuit Breaker .• / ' v'-tl;-v'.! v' "i. fa)'Long Unie delay . •>: . . .. v.- : ;v;:=; l.-.Set;indicator to 80i% an(f pass 110% pick-up current indicated in ,table-mrough each cpiL ..r^^^ '^rrentshoiiid not be allowed to drop off. Trippihg'wiH occur^n tJifeeT3). minuiesv:_ ; W; ; • 2ASet.current at;90% pick-up current indicated in;tab)e.-Gear:in. trip unit sh6Uld,hpl;rndve; -: : ';,:v;t^^^ X. ' 3;>;Reset calibration position of overCurrent trip unit to currentivaiue G^re^^ndihigf to'br^ •; -^reiting unlesis otherwisespecified, betbre turning breaker over.for shipmeht.^;iv4^W;k"^^ br-?•' .••1 ,y. I i . , -VCib) Kirk Key. Interlock ' ' • ' ': ; XXK (a) V/hen lock-is. installed on breaker check for followmg; / 'X' - operated operated hfeaker, switch switch should should be opened. opened. . 2 - \Vith breaker closed key cannot be renidved. •.•.r-iW'- • -VV .1—With breaker,open turn key and remove.. Key should not stick in loCk^jf electrically • (11) Bclj Alarm (a) Trip breakef:;matiu'ally. Bell alarm should not operate. . ' "X (b) Trip breaker witJvsliunt trip or undervoltnge, if supplied on breaker. Bell aflarm shouidi. • , nr»f operate. nnorafo " not ' * ^ • r . . X:'. |;«C' (c) Trip breaker v/i th;o^ereurrent trip lever. Beii a.arm^.wilTop'eraie. vX';.' • :x. it'n- '••c •'• • "'• •'• - • .- ; . •, iV- . -V.'.i Coil RoHr.j 100 • 125 150 "rip V/jThin Three (3) Minutes >J/a Pickup No Trip •^ 110 200 108 126 144 132 154 176 ' "225 172 198 175 ..V25fr'„., ; /; :30b:^ 88 72 • 90 • 50 Pickup No Trip Coil Rating • 400:: ^ 500 600 . Tnrea {^} f.iinutes 180 220 216 264 308 352 •.•::252 ;,350.-;/ 1• I: , 1'••in ••':V.';l):. , 288:. • : , v36o:; ViO :..432't; 528 - V: r/G. • •'•7 '\VDM3 K 25-IT WITH arcing tips TOUGHING, A ^ • ••V?' WpW^'t --i \^:••:'• •- •• . . * ' /•ritftili# •v;A; J'T, HHB- .•:- H'v:;.* • */ •'• = . ' v ' V, • •-, ' •'• • •At:. j1 ••''•' ' =<• • iv'., x0§i -W;: ,- -i': .>J .v^-.V.' .,'••• -. ^ \\ M > w. \ DMB J 25-IT CONTACT DATAVi'- 'h • "-• • fV •• •M • • •-• • vV . • : •' • • • •. s 3 •: •A'. T-k '-vT^; • -T'-'y • • •'"- rY'Yli;' ••:?•>- J. (Figure 1) -3-: .•:;"/• •>.- . ,'. .V-{;•;••'/ .'• v .-''jIV I J*-":". IVV^V. 't. • , r.. .u ;QfV ," . r j 'i • ' • • • .4 » I 1 i .•". -•ii \ f • I-- . :.1.••v.H I - • i.: - i •• V; « t 'v-- ^ (•' .' 4r/r..: r -V i- . ^ .:ii y' '• 2B 2C '. 5. - •,••4 ". ; ) ;-:1 •4 4' ^ "' •-• •? 2 .1 - V •.ij.' i - T.? «•• ivl ?.4 4^-; ./ '. / '•• •« u 4- '••;4v:'4y 4^* ^v-!i.. 5 fi 6 • • ;4"7 I ; .!."* V". •> ..• /.; . .•" • -yc . r , %':•• 4 .-. 8 V> • V' - V. ' -•• •^: - O ••^ fy.r".' •' " ' 'r?!!^^•••''E. ••'-v ' 'I 9 ••• 4 •'"Svi 44^ 1 '. V ;•; • •.•..'r':;, I i-4p'444 • •'.; •Y/yiil*'- I'i.' 'r''-'' .1::.. 'y •,; -:. •ry.y4: , ••' ; .tu n '4:* .f •.... y ''.i* .• ••. •44144. ;• -..4- - 44;-:• •; t . ". . • •••Ur:-,';, A <^4 •4- • . •;. /•"! ?r *' '' "^4 'j C*i, "" ..vcrv.- ••.-V-..'»^: .• :• .• • • V" r-V-TV^^.;;-. -iwl • !t.?£i5AJ -,' .'r-.'."<—» ••••,.;v.')4<; .•4 4^^ -.-yVA r 4-44:!--4^i, ' ;• .-"y •. • • *" ' . J." .•• V*'' r^riH'-' •i^l'-?vf;-'.»S \U. • • t-'f -.y-^v y'y.y^:4.,i,-r; ( Figure 2) , ', • ' . -J'.V - '' •A ti. i"i .:^: ••• ;^(: '-•M* :5';}r ' -. . • ... ......^ . RECOMMENDED SPARE PARTS FOR DMB 25-lT BREAKERS • •Those ports are illustrctod. See Figure 2 -; ^ r 1 • - So lenp.id Assembly 125V DC Solenb.id i^sembly 250V DC lA - Solenoid.Coil 125V DC . v:7?'7'.x:r"\. • ' 7 • i 'vc;; - • r ;o'jr ' • ^^•1151-0968 ,1152-0968 ;• .1158-0581 Solenoid Coil 250V DC • • ^ 2 —Bottom Auxiliary Switch Assembly 2A 2B 2G 3 -Top Auxilian,/Sv/itch —Auxiliary Switch Front Cover —Auxiliary Switch Rear Co'ver —Arc Chute Assembly •1159-0581 ; /"727P1-0111'; • : - Basket assembly 600 Amp. (6 fingers) .5 Break^ Grounding Contact • 6 "r 5 Ohth'-Resistor• ' v. • \'-V • V 7 ',134-001:; 3A —Arc Chute Cover .4 1152-0951 1151-0973 : 024-012 , H0'l.0589 -77.:. ..•1151-li0& -1101-049^7;. -7 • H'. A," 7 v —.406 Ghm Resist^^^ 8. ' -"Bell Alarm Switch (N.O.)^F Bell Aiaftri Svvitch (N.C.) ' 9 -4-Point Secondary Contacts'(cell) - '• : . - • . ••. .i'-: . •' •^ • " . "f,. i- 12 :, - 4-Point Secondary Contacts (breaker) • •.• • • •• V : • ' 115il-d952 • undsrvoitage.DeVice230V AC Instantaneous • undervoitage Device 125V DC Instantaneous 1152-0952 1153-0952 • ^ DC Continuous butv^ . j-vonlrol Relay Assembly 250V DC CDriijnuous Dut\' .Rsiay. Assembly 115V AC Contimious Duly • Contro Relay Assembly 220V, AC C^.nfihuous Duty ' : Control Relay Assembly 440V AC Continuous Duty 16A - {Control Relay Cover • s- .. '-1 • ;••• * '•••.,* •7Sf:'7siliS cV-:.; ,^'1101^0580 • •115^57. 15 - Shunt-Trip Assembly /fSV DC or li5V AC . 3hunt Trip Assembly 250V DC or'460V AC • ' ;4>JV;,''"v V-.,i • .- • .v; : ,U54-0952 13A - Time.Delay Assembly used v/ith Undervol.tagp, pevicd —Handle mm 1151-0670 Undervoitage Device 250V DC Instantaneous 14 ""-Bk • r ' • • 13 - Undervoltage Device 115V AC Instantaneous • 77' 2751-0068:'::'•: 10 —ArdngTip (Movable) : , •llv_-;Arcing-tip7stat) •;'•.= ^-* 'f\K " ,039-003:.' 'c,;-: 7 •:v.;. 7-. 1156-0757 1158-0791 • • •1159:-0791 1166-0791 • • 'i'/t ' 1167-07"! • 1168-0791 , 1101-0592 • ik 7'./; .B-B. ' • v.: ,-.• ••..• • • - V'-v'v". •-. T-'i . 7 ^ - ••"-•-v.-,-7'77:77 •-7".^'.77 77 ::7;:'7.7--f7, i •'-'-••A. v.A'--''..--- y'-.'-" •• >. • •"••'^ x:; ' ; ..• • r, f • H fU-' ;;i type c.; • i>.;,.>i• '-r bsx-nker. ••• n; r.-.X'ji siitiwi; -.-j undXorioI *' Re=c Lover Case Spring Carriage Lever , :;..-^d;'c^l5I-06n-V . •1151-0613' : 1151-0697 1101-0018 1101-0019 ' .1101-0021 Washer .1101-0465 ' Guide Rail 1101-0499 Clip nOl-0504' Carriage Plate Y/elded Assembly ,1151-0918 • '••••'iionni' RfilcDse Rod Trio Rod Guide • gg '.•^:,'.^r 100 • .101 ;• • - • , • • ' .,; •' '•• ''"iJ'-; .'.•'••••.•r.i; '•'••• • '• • 1101-1011 Washer .• • ddv. Pin 103 104 Trip Rod V/eld Ass.embly SpringSup[x)rl 105 Spring 106 Basket Washer 107' Shoulder Screw Spring . ' , :• 1101-1023 . '1151-1008 . • •"' 1101-1029 '. d' ••'-•ii/-:; no in 112'. Secondary Contact Support V/eld, Assembly •: 102-006 .•••; 1101-0173 • -.v.: ;.1101-1280; . d. • 1101-1021 •. -V••; 1101-0063 . • Basket Assembly . , Brass Tubing Trip Trigger **113 .,:lici-1022 ',1101-1025 Spring Locking Pin Stop Pin 102 108 **109 1101-0881 rL-in Stab d; •1101-0192\' , 1152-1106 • 2705-0339 1151-1037, ; Movable Contact Assembly ,n51-0756 •/. ji-. ; ..... , 1151-0631 • I? ' • i«, ,*C^ •"ulnnia, Georgia Long Island City, NewYork Boslon, Massachusetts Los Angeles, California Santa Clara; California .;Scrant6n,'Pfennsylvanla Chicago, IllinoisClcveJancl, Ohio Nev/ark, New Jersey Pittsburgh, Pennsylvania Dallas, Toxas St Louis, Missouri ,, battle/ Vfashingtori ," iTdrohtO; Ontario, Canada .Vancouver;;S. C,,;Oanad[a Granby, Quebec', Canada 1:. FgB:E.„D OFFIGiHS - < Akron, Ohio .Harrisburg, Pennsylvania Peoria, Illinois Albuquerque, New Mexico Hartford, Connecticut Armdale, Halifax, Nova Scotia Havana, Cuba ^ l' 'i '• - •)' ., •}'.••-^r ; ••••• •• , .- . • 31# ' 1 '• ' • ... • 9 i "• • fm" ' ;• V-' • Atlanta, Georgia Houston, Texas Baltimore, Maryland Biriifilngham; Alabdnia' Indianapolis, Indiana. Kansas City, Missouri Philadeiphla^lrPennsylvatrfa Phoenix, Ariipna ' ;; Pittsburgh,'Pennsyfvariia ' •Portland; Ore^ri ;'; .. ,; •r/ fiteadingrlpanns^lv^ " Boca Raton," Florida • Knoxyille, Tennessee' Boise, Idaho Boston, Massachusetts Little Rock, Arkansas v./' :Roche^e,r,'N^"Yp^^^ ' Long Island'City, New York Sagfr)aW,|Mr6higanN: :•; Buffalo, New York Lorigmeadow, Massachusetts St. Lp.uis,.Missouri • Calgary, Alberta, Canada Los Angeles. California ' .LouisvjilB, Kentucky Cincinnati, Ohio Memphis, Tennessee jBian Frapcisco^.Califbi^ Mexico, "city, D.F.,'Mexico': Jsyntiago|5lCtii|e • Santurde, Puert^^^ ir' . Coiiimbia, South Caroiina Miami, Florida • Columbus. Ohio Milwaukee, Wisconsin Corpus Christi, Texas Minneapolis, Minnesota • Montreal, Quebec,,Canada Dallas, Texas '> • 1 .V-iCl?: Scrantdri. jPennsyivanid, : :• •'.vv. / ss-:-1, •Shrevepiart, t'ouisian^^ •' Spokane^ Woshihgtoh Nev/ark. New Jersey Syracuse, NewiYork - New Orleans, Louisiana .Torohtb, bhtarip, Canada Edmonton. Alberta. Canada New York, New York Tulsa, Oklahoma : . , • : Vancouver, B. C., 'Canadii' . y/ashington. ;Wichira',.KUneas-^^; ;• . • Norfolk, Virginia Elfham, London. England Oklahoma City, Oklahorna Fort Worth, Texas :,: - Omaha, Neb'- -ka ' Ormond Beach. Florida Pcnsacola, Florida . h'r Seattlei'washlh^btif • : ' Nashville, Tennessee' Grand Rapids, Michigan . Greensboro, North Carolina * San Antohioi Texas. • Dayton, Ohio Denver, Co'orado . Detroit, Michigan El Paso,-Texas . -'i; * • Salt Lake City, Utah Lubbock, Texas ., • • St, •Petersburg.. Florida. • Charlotte, North Carolina Chicago, Illinois Clevelahcl, Ohio t -rSmk ' • . : ; •' •' •v'^y Wihnlpeg;:'jf,iariitpbei'^ '•Ak. C. 'V-'" • igj e E.N ERAL OFFI,C ES: S O PA,R 1S :s T'R EET, ,N, EV"/A RK:,. i",. "N;^ W, J E R. ,'E y ••t.'-- -xv-'r-.V ; <••'* . ' F^riNDA/TXL PARTS'C/IS^^LOS AMD Z.ZJ MAiMTEMANCE INSfRUCTlOMS : S' • •• I • •' •M' •': •:;•• ?.• Federal Pacific TYPE DMB 50-T Air Circuit Breakers January 19©0 ;VA--M "•• ,• -. •, i;, li • - *' .* .• . '•• 'S: : -• • r • ' , ^ xx-xXx •-M : 1 •i. / ? . \:.' "T; ^ roT ••s • •^ : • •' r'• • K. i :• •••:.• •' " • • A '-1. ,'. . '• r . i • • . ixSX<.^ • •s -rKy.''-: RENEWAL PARTS DATA This Renewal Parts Data will provide you with the proper identirication of those Renev^al Parts wnich vou may require in the maintenance of your Federal Pacific equipment. ' .i. It Is desirable to forecast as accurately as possible your requirements for Renev/al Parts to assure that the necessary parts and materials will be available when needed to keep your equipment in efficient and continuous operating condition. The recommendations for stock are the minimum quantities that should be available for servicing this equipment We feel that you are in a better position than we to decide how much you wish to invest in Renewal Parts. The importance of miniini^iiig shut-dGv\n time due to possible break-downs in operation together witli the distance from source of supply and transportation facilities, should be considered by' you when ordering renewal parts. Maintain the maximum operating characteristics of your appaialus and its dependability by using genuine Federal Pacific Renewal Parts. The services of FPE engineers and Customer Service Ceniets areavaiiabie to help with your main tenance problems. ••• PROCEDURE FOR IDENTIFYING RENEWAL PARTS . 1. Obtain liie complete nameplate reading of the -v- .''"'V "'-' apparatus for which the part is desired. •'•'V • '- C: 2. Turn to the Apparatus index and with the nameplate reading find the page numbei of the Renewal Parts Data Sheet ..-;p 3. Turn to tne indicated Renewal Parts Data Sheet' where the desired part is described and •. .r- identified. ORDERING INSTRUCTIONS Give the Port » ot other identifying number ond nome rhe port. Give the eomplcre namcploro reading ofthe oppoiorua. toto vvhether shipment is desired by freight, express, or by parcel post. For mointononce Service contoct your neoreat • • ; Sales Office to whom you should send all orders end correspondence. Sec lost page of book foroddress uf FPE Solos Office. ' , •• .;y * -r-y-'- '..1 SUGGESTED MAlNTHMAHeE PROCEDURE FOR DMB 50-T AiR CIRCUIT BREAKERS (1) Dicloctric Test (a) Voltage to be 1550 volts, 60 cycle (field test).. (b) Voltages will be applied fot one (1) minute without arcing. (c) Voltage to be applied to breaker as intiicated; ,. 1-wilh contacts closed voltage to be applied between phase and ground and between phases. 2-with contacts open voltage to be applied between line and load terminals and between line and load terminals and grcund. 3-voltage to be applied-betv/een control circuits and ground, and. line terminals with contacts closed, ' X' (2) Manual Operation (a) Breaker will be manually closed and opened no (ess than twenty-five (25) times. Breaker shall not bind, handle should return to normal position. (b) If the breaker is supplied with a Bell Alarm, see item 11. (c) Trip breaker,by manually activating shunt trip. Breaker should trip before plunger reaches end of its travel. (3) Trip Free Operation (a) With trip bar pushed upward breaker should not close. (b) If drawout breaker carriage locking handle is depressed the breaker should trip free, before the pin releases breaker frorti cell. (c) Trip breaker with triplever, moving it very gently. (4) ElectricoS Operation . ' (a) Electrical eccessories v/ill operate satisfactory for at least five (5) operations with maximum and minimum voltage as gjven in following chart. (b) Items to be checked are solenoid control relay, shunt trip and undervoltage trip which should operate satisfactory in the range of voltage shown. Rated Control Control Devices Solenoid Shunt Trip Voltage 24 48 125 250 115 230 460 volt volt volt volt volt volt volt DC DC DC DC AC AC AC Undervoltage Trip 90-130 180-260 90-130 180-260 95-125 190-250 380-500 14-30 28-60 70-140 140-260 95-125 190-250 380-500 Reset Less than 37.5-75 75-150 100 200 34.5-69 92 184 69-138 (c) Undervoltage trip shall operate betwee.n 30-60% of voltage rating aiid mechanically resetunder voltage trips shall seal in at 80% of rated voltage (see table 4 b). (1) T'r.c delay 3 to 4 seconds. (d) Anti-pump feature of breaker shall be checked by operating closing sv/itch 3 or 4 times while breaker is closed. • •. (e) If Bell Alarm is supplied refer to item 11. r;;' , -r':' Vir.:JoI inspection . . , (a) Breaker will be inspected for signs of incchanical or electricai Special attention shoulfl be given to see that retaining rings and £-,rings on cqnLacls, etc., are in place, springs are not •unhooked on one end and colter pins are opened. ' .' • • * .n' - DMB 50-T CONTACT DATA •' 'T/jL' • '.,.r." '.Mi (Figure 1) , '.vV* •nlSr '• • ..:.r "7 - ''iV; •, ,, ?' ,•;! V / ' •; / I t I .- SN f • ?:• J 5r . -* t ., ..^ .' ..• .i\ . -/•:• ^ 'it Ui... * kw- • -v, 1 • V •~v: / ^• "SX^' :\ • rr-it i \. • \ 'A 3^ ,'/ 'V •'i 3C J 3B f •» *-- t A rrrn'fii . • • m" i' ' ::3 : I 9 8 10 U , j ; ^ : 1 si 'V ^ l.^ Ud tj ..; f«i ! 1101-0059 •T-' ""V- H'.Pw'";-.', ••• • r's t •/i'-rjAf' RENEWAL. PARTS- FOR .DMB -50-T (Con-nnired)• '•jm JTEM 129 •DO -V. "Bl DESCRiPTIOM PART NUMBER tock Pin .Spring ...a... . _ 1101-0062. Lock Pin 1101-0063 • 132 Pin Support fot Spring. 1101-0065 133 Spring 1101-0093 Basket Assembly 1151-0632 *«134 D5 • 136 137 '' ;.y;- 1101-0061 . 1101-0173, Basket Washer •Shouldered Screv/ 1101-0193 Spring ilOi-0192 -I'mi " • V^:v:.- v- ii'. • •. '•••' •; f. V'* * *•' '• ' -r"'- v'- • • i • SI;- . ' OA--. ' ' » • • •' .* ' j.'''•" ' -FL.AWTS Atianta, Gcoigia Long Island City, N«.w VorK Santa Clara, California Boston, Massachusetts l.ns Angeles, California Scranton, Pennsylvania Chicago, lllirois.. - ... . Newark, New Jersey •. Seattle, Washincton Cleveland, Ohio Pittsburgh, Pennsylvania Toronto, Ontario, Canada Dallas, Texjs St. Louis, Missouri Vancouver, B. C., Canada Granby, Quetjec, Canada FIELD OFFICES Akron, Ohio Harrisburg. Pennsjlraniu Albuquerque, New Mexico Hartiord, Conueciiicut Armdale, Halifax, Nova Scotiaa Havana, Cuba Atlanta, Georgia Houston, Texas Baltimore. Ma.'yisnd Indianapolis, lndiai><, Birmingham, Alabama Kansas City, Missouri Boca Raton, Florida Knoxvllle, Tennessee Phoenix, Arizona Pittsburgh, Pennsylvania Portland, Oregon Reading, Pennsylvania Richmond, Virginia Boise. Idaho Little Rock; Arkansas Rcchsster, New York Boston, Massachusetts Long island City, New York Ssginaw, Michigan ' Buffalo, New York Calgary, Alberta, Canada Lcngnioadov/, Massacnusctts 'St. Louis, Missouri Los Angeles. California St. Petersburg, Florida Charlotte, North Carolina Lx)uisviUe, Kentucky Salt Lake City, Utah Chicago. Illinois LubbocK. Texas San Antonio. Tex.as Cincinnati, Ofiic Memphis, "en.-.esseu San Francisco, California Cleveland, Ohio Mexico City, D.F., Mexico Santiago, Chile Columbia, South Carolina Miami, Florida Sanlurce, Puerto Rico Columbus, Ohio Milwaukee, Wisconsin Scranton, Pennsylvania Corpus Chrlsti, Texas Minneapolis, Minnesota Seattle. Washington Dallas, Texas Montreal, Quebec, Canada Shreveport. Louisiana Dayton, Ohio ^ Dp.nvBr, Colorado. 1 Peorla, Illinois Philadelphia, Pennsylvania Nashville, Tennessee ., Newark,. New.Jersey Spokane, V/ashlngton . Syracuse, New. Yqrk Detroit, Michigan New Orleans, Louisiana Toronto, Ontario, Canada Edmonton, Alberta, Canada El Paso, Texas New York, New York Tulsa, Oklahoma Norfolk, Virginia Vancouver, B, C.. Canada Eltham, London, England i Oklahoma City, Oklahoma V^asliington. D, C. •^ort Worth, Texas i Omaha. N^hrosK^ Wicnita, Kansas Grand Rapids, Michigan (Ormoncj Beacn, rTunua V/innipeg, Manitoba, Canada Greensboro. Nortr: Carolina 1Pensacola, Florida . Lv' » s. ELHCTR8C .jjQENERAL OFPICES: oO PARIS STREET. NEWARK 1, NEW JERSEY INSTRUCTION MANUAL TYPE DST-2 SKV & 15KV MAGNETIC AIR CIRCUIT BREAKER IN-820.11 DATED APRIL, 1972 ;ral. pacific electric company 150 AVENUE L,NEWARK, NEW JERSEY 07101 PRINTED IN U,8.A. TABLE OF CONTENTS PART I- GENERAL INFORMATION 1. Introduction 1.1 Foreword 1.2 General Description 1.3 Construction 1.4 3 3 4 4 Features 4 2. Shipping 3. Inspection 4. Storage Prior to Installation 4 5 5 5. Installation O 5 5.1 5.2 5.3 Preliminary Operations Safety Precautions Mechanical Checking 5 5 5 5.4 Installation S 5.4.1 5.4.2 5.5 5.6 5.7 Lifting Arc-chute Fitting Racking Operations Manual Checking of Operating Mechanism Electrical Checking of Operating Mechanism 5 5 6 7 7 PART II - GENERAL MAINTENANCE 6.1 6.1.1 6.1.2 6.1.3 6.1.4 6.1.5 62 Periodical Inspection Arc-chute Inspection Arcing Contact Inspection Replacement and Adjustmentof Arcing Contacts Main Contact Inspection Main Contact Replacement Operating Mechanism Maintenance 7 7 7 7 8 8 8 PART III - DETAILED MAINTENANCE PROCEDURES 7. Operating Mechanism 7.1 Characteristics 72 Principles of Operation 7.2.1 Breaker Open-ClosingSprings Discharged 7.2.2 Breaker Open-Closing Springs Charged 7.2.3 Breaker Closed with Closing Springs Discharged 7.2.4 Breaker Closedwith Springs Charged 7.3 Troubleshooting 7.3.1 The Breaker Cannot be Closed 7.3.2 7.3.3 7.4 7.4.1 Problem with the Spring Charging Motor or inthe Chain The BreakerCannot be Opened Electrically Checksand Adjustments Adjustmentof the Closing SpringMechanical Lock 7.4.2 7.4.3 Checkingthe Trip Bar for Breaker Opening Checking the Closing Release for Closing the Breaker 7.4.4 9 8 8-11 9 8 11 11 11 11 11 11-12 12 12 12 12 Adjustment of the Clearance between the Ratchet Pawl and the Sprocket Wheel to Prevent Overstressing the Pitch Chain 12 PART IV - APPENDIX 7.5 7.6 7.7 7.8 Fitting, Replacement and Adjustment of the Trip Latch Replacement of the Closing Spring Hydrauiic Shock Absorber Fitting the Operating Mechanism to the Breaker 13 13 13 14 8. Schedule of Maintenance 14 9. Operating Time & Contact Velocities 10. Control Power Requirements 11. Wiring Diagrams: ACclose;DCclose IS IS 16 12. Accessories 17-19 13. Spare Parts 19-23 Refer to IN-820.4A for metal-clad switchgear installation, operation and maintenance instructions. \ o PART I — General Information 1 INTRODUCTION 1.1 FOREWORD Metal Clad Switchgeaf, and othertype Electrical Apparatus Federal Pacific Electric Company apparatus is built to the highest standard of quality to insure continuous reliable are as follows; (a) Cleaning of cells with low pressure air or vacuum. (b) Inspection of cell bushings, cable connections and service with a minimum of maintenance. Some routine preventative maintenance is, however, required on semi bus joint connections. annual or annual basis in accordance with the various uses (c) General inspection of control wiring, and of the product It is suggested that, due to the precision craftsmanship involved in the construction of this appa components. ratus, no attempts (with the exception of few minor adjustments) should be made by the customer to fix or adjust clearances. (d) 2500 Volt DC M^erTests and DC Hi-pot Tests for, Should the need occur, the Field Service Department of the Time Delay. (f) 5KV and I5KV circuit breaker electrical and mech Insulation Reliability. (e) Protective Relay Calibration Tests for Response and Power Equipment Systems Division of Federal Pacific Electric Company is equipped to assist you with any maintenance or repair which may be required throughout the anticipated longlifeof this equipment. FPE "On-Site Test Facilities" are available to you. This service includes engineering inspection and testing of elec trical equipment planned to supplement yourregular main tenance program, to improve equipment reliability and to protect your investment. Such services, for MetalEnclosed, anical operating checks coordinated with relay response. (g) Transformer oil or askarel dielectric Hi-pot Tests (also on minimum oil breakers and tank typo oil breakers). For further information regarding service, please contact the Manager of Field Service Department at Newark, New Jersey. SkV 75,150 and 250IMVA CIRCUIT BREAKER Figure 1 1.2 GENERAU DESCRIPTION (Figure 1) The DST-2 Magnetic Air Circuit Breaker is electrically . operated, horizontal drawout for use in indoor and outdoor 1.4 DST-2 FEATURES (Ffe JirntessorAcnvisenofet/; It is designed for international application and service; therefore, the dimensional daU isgiven in both the metric and English systems. The hardware is based on the metric All breakers are equipped with the following parts and It is composed of three separate poles supported by a welded steel frame (1) and provided with wheels (2j so it can be easily moved in and out of its cell. Each pole consists of two separate parts: (a) Arc-chute (4) - isa chamber filled with ceramic baffles. provisions. (1) Arc-chutes (4) (2) Barrier (1, Fig.2) (3) 5 Unit auxiliary switch with 2"a" and 2"b" extra contacts (1, Fig. 5). Other types available upon request. (4) Lockout switch. (Blocks closing and motor circuits) (17) It has a magnetic structure that forces thearc intoconstric tions provided by the baffling. The magnetic field is (5) Latch check switch (2,Fig. 5) quick extinction of the arc. (7) "Y" relay (5, Fig. 5) (b) Contact unit - is made upof the main contacts, fixed (6) and moving (9) and the arcing contacts, fixed (7) and (9) Charging motor (4, Fig. 5) generated by coils (5) within the arc chute. Cooling and elongation of the arc within the baffle structure forces moving (10). Themain contacts, of silver plated copper, carry the normal service current. They are not affected by the interruption since they open before the arcingcontacts separate. (6) Mechanical operation counter (counts trip operations) (18) (8) TC trip solenoid and 52X close solenoid (3,Fig. 5) (10) Mechanical indication of"Charged" and "Discharged" (11) Mechanical indication of "Open" and "Closed" (20) (12) Mechanical indication of"Charged" and "Discharged" (19) The fixed and moving arcing contacts are made with (13) Mechanical drawout interlock (prevents movement of interrupting high short circuit current without damage. The puffer nozzles (8) arelocated under the fixed contacts. The moving contact group is operated by the shaft 1), through insulated links (12). The metal frame is grounded (14) Mechanical interlock discharges closing spring when tungsten-copper arc resistant inlays and are capable of - personnel. metal-clad switchgear. ^stem. ' breaker, covers the live parts providing protection to through the groundcontacts(16). A welded sheet steel front barrier is grounded thus assuring "•safety to operating peisoimel. The contact structures are separated by insulated interphase barriers. Tlie breaker can be either manually operatedby means of a knob(13) or remotely operated. The motor charged spring closing mechanism (3) is espe breakerin or out of cell with contactsclosed) (14) inserting or removing breaker from celL (15) Padlock provision. (Lock breaker tripped with pedal down or lock to prevent raddng in or out with pedal up-(14) (16) Provision for manual charging ofsprings (21) (17) Manual trip —dose control knob (13) (18) Automatic Secondary contacts in "Cormected" posi tion (22) (19) Manually operated secondary contacts in 'Test" position. cially designed for medium volt^e circuit breakers. It is completely enclosed for safety and dirtexclusioiL (20) Meehanism is medianically and electrically trip free. 1.3 CONSTRUCTION 2 SHIPPING The DST-2 is a drawout type breaker. It is built to allow <>a«» of ntaintenance and operation. The breaker isavailable complete with cell or for insertion intoa metal-dad breaker All circuit breakers are assembled and tested for optimum cell.The breaker can be positioned as follows: one crate. The 5kV 350 MVA and 15kV circuit brewers are shipped in two crates. The basic circuit breaker on its truck 1."Connected" position —where primary andsecondary disconnects are automatically connected. 2. "Test" position("Isolated" position) - whereprimary disconnects are disconnected and secondary discon nects can be manuallyconnectedor disconnected. 3. Removed from the cell by operating the "racking in" lever. It is provided with a pedal operated interloddng device(14). The circuit breaker is fitted with springloaded, self aligning primary disconnects which ei^ge the stationary studs mounted in insulating bushings in the cell (15). ¥nien the breaker is in 'Test Position" or drawn out of the cell, the cell shutter, operated by racking action of the performance in the factory before shipment. The 5kV 250 MVA circuit breaker is shipped completely assembled in with interphase barrier is in one crate. The three arc chutes arepacked in a second crate. The serial nutiiber of each drcuit breaker is on its nameplate. It is also stenciled on both breaker frame and operating medianism frame as indicated in(24, Fig. 1). The cratesare markedwith the factory order number. A copy of the packing list, endosed in a waterproof envelope is nailed on the outside of the drcuit breaker crate. Only onq envelope is furnished with orders for more than one circuit breaker shippedto a single destination. Each circuit breaker, in its crate, is enclosed in a polyethyelene dust-and-moisture-proof bag. 3 INSPECTION UPON RECEIPT OF SHIPMENT When a shipment of circuit breakers is received, each crate should be examined before it is removed from the railroad car or truck. If any damage or indication of rough handling is evident, a description of the condition should be written on the frei^t bill, a claimshould be filed against the carrier immediately, and notice of the extent of damage sent without delay to Federal Pacific ElectricCo. at the address from which shipment was made, givingserial number of the breaker, the carrier's name, and the car number if shipped by raiL This information enables the company to supply needed information to assist the purchaser in support of the daim. (See 6.1.1) 4 STORAGE PRIOR TO INSTALLATION A breaker can be safely stored provided that the following instructions are observed: (a) Handle the breaker with the utmost care, lift circuit breaker less arc diutes using a hoist or amilar means and attach the sling hooks to the holes on the sides of the breaker. The S and ISkV circuit breakers witti arc chutes are lifted by fitting the sling under the wheel channels and securing top to prevent tipping. (b) Upon receipt of the breaker an inspection should be made. The circuit breaker should be stored, (a) Check the alignment between the ground contact (16, Fig. 1) and the grounding blade located on the cell floor. (b) Insure that the arc chutes are properly connected. (c) Check the main and secondary electrical connections. (d) Never rack the breaker into the "Operate" position without the arc chutes and interphase barriers prop erly installed. 5.3 MECHANICAL CHECKING Each drcuit breaker is carefully inspected and operated at the plant before sliipment; yet it is advisable to carry out some closing and opening operations before putting a breaker into service. For detailed inspection remove arc chutes and interpliase barriers and follow the instructions for "Manual Checking of Operating Mechanism" (Section 5.6). 5.4 INSTALLATION 5.4.1 Lifting Lifting is to be done as described in Section 4 (a). Handle the breaker with the utmost care, lift it using a hoist or similar means. Inspectfor breakage. (See6.1.1) 5.4.2 Arc chute Fitting (Fig. 2) 5kV 350 and 15lcV Arc Chute Mounting Arc chutes are shipped separately from circuit breaker and must be mounted before installation. Arc chute return connection and arc chute must be positioned as follows: "Opened" and "Discharged", in its original shipping container. The ISkV and SkV 350 arc routes should be stored in the original shipping crate. (c) Keep the breakers in a dry place, protected against dust and chemical agents, preferably in cells with cell or auxiliary heaters energized. 5 INSTALLATION 5.1 PRELIMINARY OPERATIONS Before setting a breaker into operation, the following operations should be carried out: (a) Carefully clean all parts of the breaker with a dry cloth. (b) Check the condition of contacts and terminals. The main contacts are coated with a thin layer of contact lubricant. If the main contacts are dirty they should be cleaned with acetone and sparingly relubricated with FPE #1551 A 5853 contact grease. The terminals and arcing contacts should be cleaned with acetone. The three moving arcing contacts must dose and open simultaneously. See section 6.13, Page 7 for adjustment specification. Tighten all the parts listed in Appendix 8 under "Maintenance to be carried out." 5.2 SAFETY PRECAUTIONS The following checks should be made before putting a breaker into service. SkV 75, ISO AND 250 MVA Figum2a It is imperative that arc chute return connection is securely against arc chute support plate. Check that both nuts are tight affording a good electrical connection. Before fitting the arc chutes on the ISkV circuit breaker or 5kV 350, make sure there is no foreign matter inside them. It is imperative that the arc chute return connection is securely against arc chute support bracket. Checkthat both nuts are tight affording a good electrical connection. 5.5 RACKING OPERATIONS (Fig. 3a, 3b, 3c) o (a) Roll the breaker on the rails using handling dolly Then: (a) Remove screws (2) and remove the interphase bar rier (1). (b) Lift arc chute with liftingyoke (Page 18) and fit the conductor pin (3) into saddles (4). Arc chute lifting station is provided in aisle units. (c) Rotate the arc chute downwards until plates (6) are fitted to stud (7). (d) Fix the arc chute by means of nuts on studs (7), making sure that the connector (8) is assembled outside of the plates (6). See Fig. 2b and 2c. ArtChtitt ©support plates X and check that it moves freely. (b) Move the breaker to the "Test" poation using the raddng lever,as shownin Figure3a. Shift leverback and forth until you hear the clicking sound of the lock engaging the interlock rail. Lockout switch, (3), must be reset if operating circuit breaker in "Test" position is desired. (c) To continue racking, repeat the preceding oper ations after releasing the interlock bar (1) by press ing the pedal (2). Trip the circuit brealmr before pressing the intertock pedaL Reset the lockout switch each time after pressing interlock pedal to peimit electrical operation. (d) To rack the breaker out; place the lever as diown in Fig. 3b and perform the same operations as above. VWastier Wadwr Front Are Chute Support Nuts adjustod to width of support plates. Are Chute Figure 2b connection o return 5kV, 75,150 and 250 Arc Chute Mounting Arc chutes are shipped already assembled to circuit breaker. In the event of arc chute removal, the arc chute return connection and arc chute must be positioned as follows: Figure 3a Figure 3b Are Chute support braeket Front Arc Arc Chute Chute support Figure 2e return connection Figure 3c dTiriiiiT'iit-inVi' 5.6 MANUAL CHECKING OF OPERATING MECHANISM (Circuit Breaker Out of Cell) Giarge the closing springs by means of manual charging handle, then close and trip the breaker manually. Check mechanical operation of the mechanism. The breaker diould operate smoothly and freely without any indication of binding. Check that the control voltage agrees with the breaker nameplate and is within the limits specified in Appendix 10. It is suggested that several mechanical closing and opening operations be performed. 5.7 CHECKING ELECTRICAL OPERATION OF MECHANISM The circuit breaker may be electrically operated safely in the cell in the "Test" position. Move the breaker in the cell until the interlock bar drops into the first notch. This is tlte Test" position. The shutter should remain down isolating the breaker from the hi^ voltage bus. The secondary circuit is completed by manually pushing the secondary contact operating handle (right side of breaker frame) all the way in (22, Fig. 1). Reset the lockout switch (17, Fig. 1) by lifting the toggle handle. Close and trip the breaker several times from the control switch. After each closing operation the motor will recharge the closingsprings. PART II — General Maintenance 6.1 PERIODIC INSPECTION A schedule for maintenance of a breaker in service is included in Appendix No. 8. In addition to the listed operation it is recommended to carefully clean the breaker at least every six months. The contacts and arc chutes should be frequently and carefully inspected, as instructed in 6.1.1 — 6.1.5, if the breaker has been subjected to frequent operations on shortcircuits or overload. Appendix No. 8 indicates the maximum number of oper ations the breaker should be expected to perform without replacement of the contacts. 6.1.3 Replacement anil Adjusting of Arcing Contact (Figure 4} Draw the breaker out, remove the interphase barrier and arc chutes (Fig. 2). Replace the arcing contacts as followsr (a) Open the breaker and discharge the closing springs. The breaker, and in particular the operating mechanism, (b) 5kV 250, 350 and 15kV 750 MVA - Remove nut should be ^quently inspected if the breaker has been from contact pivot pin and remove pin. Remove spring pin retainer and spring pin. Remove 2 shunt subjected to dust or corrosive industrial atmospheres. 6.1.1 Arc Chute Inspection (Figure!) Draw the breaker out, remove the safety barrier (1) as instructed in 5.4.2, loosen the nuts of studs (7), rotate the arc chutes approximately 45° backward one at a time by rotating aroimd pins (3) then check the conditions of the arc chute plates. If any breakages or flaws on arc chutes or ceramicplatesor burning on blow-out coils are found, it is advisable to replace the arc chute. Replacement arc chutes may be ordered direct from the factory, by contacting Switchgear Marketing, Newark, New Jersey. screws and remove moving arcing contact. Install new contact in reverse procedure. ISkV 500 - Remove 3 studs securing moving arcing contact to the blades. Install new contact making certain that nuts are securely tightened. (c) Remove stationary arcing contact springs (5) (Fig. 4b and 4c) by removing adjusting nuts and stud. Remove upper shunt screw. Remove arcing contact assembly, remount shunt onto new arcing contacts and install in reverse procedure. (d) Adjust the moving arcing contact, makingsure that all 3 poles close simultaneously and fixed to moving main contact gap as arcing contacts touch: 5kV 250 = 8 ± I'mm (.32 ± .04 in.); 5kV 350 = 4 ± 1mm 6.1.2 Arcing Contact Inspection Draw the breaker out, remove the interphase barrier and arc diutes. The arcing contacts should be reasonably clean, without pits and deformations. Small pits can be filed without modifying the shape of the contacts. In normal use, when cunents of approximately the rated value are being inter rupted, the arcing contacts might be slightly worn; replace ment, however, is uimecessary. In more severeservice when appreciable wear is noticed, the arcing contacts should be replaced as described in 6.13. (.160 ± .04 in.); 15 kV = 11 if mm (.44 in.). Contacts may be slowly closed using the mainte nance bar (23, Fig. 1) for the 5kV breaker, and "Maintenance Close De^" (Page 19) for the 15kV breaker. ' (e) Close the breaker (Fig. 4c) and adjust the length of springs (5) to 11mm (.44 inch) for 15kV 500 and 14.5mm (37 inch) for other ratings. (f) Open and close the breaker several times to check mechaiucal operation. (g) Remount the arc chutes and the interphase barrier as instructed in 5.4.2. o © aoHd" Portion Optn Position 6kV 75,150,250 AND 350, AND 15kV TCO Fq|ura4b Rguro4a 6.1.4 Main Contact Inspection Draw the breaker out, remove the interphase barrier, and tilt the arc chute back approximately 45° one at a time. Inspect the main contacts making sure they are in good condition and see that the face of the contact is coated lightly with FPE #1551 A 5853 Contact Lubricant. Use only minute quantity. Since these contacts do not break any current they diould not be pitted or burnt. (See Appendix 8 for the number of operations the main contact ican withstand before replacement is necessary.) 15kV500MVA >•11 lOAnm 6.1.5 Main Contact Replacing Drawthe breaker out, remove the interphasebarrier and arc diutes. Replace the main contacts asfollows: (Fig. 4d) (a) Open the breaker and disdiatge the closing springs. (b) Remove the spring by mi^wing the lockout and removing the adjusting screw.Remove main contact. Irtstall new contacts in reverse procedure. NOTE: New self lockingnut should be used. (c) Adjust the main contact qrrings sothat the length is 10 1.2mm (.40 ±.008 in.) when the contacts are closed. Atl other ratings: (A3t.02in.) jmci 14.5±0L5mm MINIMUM CLEARANCE WITH Loefcnut CONTACTS ENQAGEO - (S7±.020in.) MINIMUM CLEARANCE WITH CONTACTS ENGAGED - .25inin (.01 in.) ARCING CONTACTS Figure 4c .25(nm (.01 in.) lOiOAnm (A0i.020iii.) MAIN CONTACTS Figure 4d To check contact alignment, use maintenance close handles (see Accessories Section). 6.2 OPERATING MECHANISM MAINTENANCE (Figure 9a and 9b) The operating mechanism is suppliedthoroughly lubricated and does not need any special care during its lifetime. It is, however, advisable to clean it carefully after every 2000 Primary Disconnect inspection Check primary disconnect Angers to assure that they are positioned in a circle, not bent, and clean of residue. operations or once a year, whichever comes Arst. The cleaning should be done by means of a paint brush Secondary Disconnect Inspection drenched with acetone or other similar solvent with the Check molded contact assembly and moving carriage assem breaker "Open" and springs "Discharged". The links, levers, pins and chain drive mechanismshould be lubricated with good quality light greaseSAE Grade I. bly to assure they they are not damaged and that the contact pins are not bent. / SPRING CHARGING MOTOR (4) LATCH SWITCH (2) AUXILIARY SWITCH (11 (TO SHUNT TRIP OR (52X1'CLOSE ASSEMBLY (3) y RELAY ASSEMBLY (5) FIguraS Maintenance Procedure PART III 7 OPERATING MECHANISM (TYPE "AEM") 7.2 PRINCIPLES OF OPERATION The operating positionsof the mechanism are described and diown in the following pages. 7.2.1 Breaker Open-Closing Springs (1) Distdiarged 7.1 CHARACTERISTICS The dosing springs of the operating mechanism are charged by the motor. The spring charging time is approximately 10 seconds. The medianism performs the following cycles: (a) Starting with the breaker open and springs charged: CO O TC — CO TC — CO Where: CO is a "C^ose-Open" operation TC is the Spring charging time (b) Starting with the breaker closed and springs charged: (Figure 6a) The breaker is in this posiAon after eadi "Close-Open" ^cle before recharging.This is a transient position. 7.2.2 Breaker Opoi - ClosingSprings (1) Charged (Figure 6b) This is the usual operating position of the open breaker. The sprii^ can be charged as follows: (Fig. 6a). (a) Manual Charging. Turn the shaft (3) half a turn clockwise usingthe crank (2). This corresponds to complete charging of the springs. When the shaft (3) isrotated,it drives the shaft Where: O is an "Open" operation (S) by means of the ctmin (4). The shaft, being con nected to lever (6) through connecting rod and t is the reset time crank,(8) causes, in its turn, the duuging of the springs. 0 •t —CO^—TC — C O BREAKER OPEN: CLOSING SPRINGS DISCHARGED 0000Q ©000 © • / 0 z © FigunSa BREAKER CLOSED: CLOSING SPRINGS CHARGED BREAKER OPEN: CLOSING a>RINGS CHARGED © © FIguraSd FIguraSb 10 BREAKER CLOSED: CLOSING SPRINGS DISCHARGED 0 3 0© 0.5mm —.00mm ("•-«£) ® 0© © / (0 to .04 in.! Figum? nguraOe At the end of this motion the trip latch assumes the latch position. When fully chaiged, the primaiy closing latch (13) is held rixed by the secondary closing latch (IS) on shaft (16) by means of bearing (14) assuring the springs aie kept charged. The sprocket wheel(17) is then free from ratchet (18) and idles. The breaker will not close if springs(1) are not completely charged. Although the ^ring charging can be done manually as described above, the usual procedure is to perform this operation by means of a motor. 7.2.4 Breaker Closed with Springs Charged (Figure6d) This is the usual operating position of the dosed breaker. The trip operation can be performed as follows: (a) Manually, by rotating knob (23). (b) Remote, through the shunt trip. 7.3 TROUBLE SHOOTING 7.3.1 When the Breaker Cannot be Closed This may be due to the following: (a) Looseness of the eccentric (6, Fig. 7) - adjust as (b) Motor Charging. When motor (19) is energized, it rotates camshaft (20) through the reduction gear (21); the clutches (22) are actiuted in sudi a way as to charge the springs in the same way it is done manually (see 6a). If during the operation, the voltage supply fails, the motor is always in a position to continue charging once the power is restored. Charging can of course be instructed in 7.4.1. (b)Warpage of the trip rod (8, Fig. 7) — check as instructed in 7.42. (c) Wear of lever (7, Fig. 7, Page 10). —This trouble is very uncommon and may occur after a number of operations much greater than that recommended. The lever (7) is to be replaced at our plant or by an continued manually, if necessary. 7.2.3 Breaker Closed with Discharged (Figfare6c) FPE Field Service Engineer. Closing (d) Clearance between the ratdiet pawl (3, Fig. 8) and the sprocket wheel (4, Fig, 8) is different from the prescribed dearance. —See 7.4.4 for adjustment. Springs This is a transient state for the breaker. It occurs whenever the breaker is closed and before the springs are recharged. The breaker mechanism is changed to this position as 7.3.2 Problem with the Spring Cherging Motor or in the Chain (16) (Figures) This happens if the clearance between the ratchet pawl (3) follows: The shaft (16) is rotated either by the electrical close operation or manuaUy with knob (23). and the sprodcet wheel is incorrect. See 7.4.4 for adjustment. The latch(13) is released and springs (1) rotate the lever (6) counter-clockwise. This drives the shaft (25) 7.3.3 The Breaker Cannot be Opened Electrically This may be due to the auxiliary circuit not being dosed. dockwise through lever(11) and trip link and doses the breaker. 11 Verify the circuits and their connection to the switchgear 7.4.3 Checking the Closing Release (7) for Closing termina] blocks. the Breaker (Figure 8J With breaker open and sprinp discharged: (a) Check for free movement of closing release bar (7) and make sure that when it is in the stop position, 7.4 CHECKS AND ADJUSTMENT O the right end of lever (6) is stopped by the slot (9) 7.4.1 Adjustment of the Closing Spring Mechani cal Lock (Figure 7) Since this adjustment is to be made with the breaker closed, the eccentric (6, Fig. 7) should first be locked by tightening screw (I) in such a way as to position the lobe opposite the pin (7); then, with the breaker closed and springs in the dividing plate. (b) Roller (5) should engage lever (6) with a minimum overlap of l.Smm (.06 inch). 7.4.4 Adjustment of the Clearance between the Ratchet Pawl (3) and the Sprocket Wheel (4) to prevent undue stresses to the Chain or to the Spring Charging Motor (Figure8) discharged, perform the following operations: (a) Loosen screw (1) slightly. (b) Turn knob (2) counter-clockwise until the clearance between the lever (3) and the pin (4) of trip bar (S) is between 0 and .04 inch (0 and .1 mm). (c) Rotate the eccentric (6) until it is touching pin (7) of knob (2); lock it in this position by tightening the screw (t). Starting horn spring "Discharged" (1) position, rotate the diaft (2) half a turn clockwise, whii^ corresponds to the full closiiig spring charging. The ratchet, pawl (3) must clear the sprocket wheel (4) at the instant when ^e bearing (5) presses against the upper part of lever (6) of closing release bar (7), thus assuring the spriitg"Charged" position. If the ratchet pawl (3) clears the sprodcet wheel (4) before the bearing (5) presseson the lever (6), the closing springs (1) are not completely charged and the breaker carmot be 7.4.2 Checking the Trip Bar (8) for Opening the Breaker (Figure 7) When the breaker is closed, the clearance between the pin (9) of the trip lever (10) and the trip rod (8) actuated by the knob (2) is to be 3 to 4mm (.12 to .16 in.). Should thh dosed. If, on the other hand, the ratchet pawl (3) clears the ^rocket vdieel (4) after the bearing (S) has pressedon the lever (6), the pitch chain (16) would be subjected to undue ^^clearance be less, the pin (9) would hit the trip bar (8) thus tripping the breaker. stresses and the motor would be excessively overloaded. Therefore, it is necessary to check that: Therefore, with the springs in "Charged" position, the dearance between the ratchet pawl (3) and the sprodcet' vdieel (4) must be 4 ±.Smm(.16 ±.02 inch). This is set by (a) The trip bar (8) is not warped and is not held upward by foreign matter. (b)That the pins (11) are provided with washers and adjusti^ the eccentric (8) fixed tothe base plate toget the dearance required. The mwual diarge crank will override if an operator continues to charge after the mechariism is fiiUy vg 9w •nay .3lf«¥ fw75^7*e5i#ii» snon .'3 ^4"" « t v w «aM«» jOJBUf 9/«4 --J 9tO n f/9 ^9«7i9 ArfMf 0f>^>W7aMt 9U 'J« wtfvA/ry OMOOV g^o0'9'00^\ iw<«< MOrfftvO 3UVU3ftX ZJSO l>co«rg '9K9fim*m'i ^9MmfU^^9CT JOmMS ywffit/WP •r nTfir^T xarM4»-^^r ortf M> MUfM 00 •»« Itayg^'ai^gy *0 90 e»9 vtd '>19 o: Mf VM* • 'wewwuw 1 t#f 'jiwa'amia'jy^ (•II til iiagw»»^m»w '"T !••♦ Xm i ^ ;iff 0/W < . u sf^»mm •JMW w a w *9 w umnwufy ww .mil wa»»t "OW <--S«!SV«S5^ a/wiryytr •SSTfiiaS ps/XM^Hsr 90 St079 U**nNf X Atiefr*^ . ^•099 ;«99 *^9lt^/99999 '---7 0Mr A» ,J, ArafJWa^M*^ a««M AYtMr 2w%*«0»#0 M 0I0>09^J^ 0/ 09^7 Qf^9997 # I I I A, *^\ *»-«»' «^; ^'j" '.»,' rf. 0/^ '!» %09IOt*^ •*» .•>0/0A' ravu9via ONiuim o w II XIQNSddV APPENDIX 12 Standard and Optional Accessories SPRING CHARGING CRANK DWG. NO. 1551 A 5539 (Standard) 2. Rotate until ratcheting ceases. The closing springs arc then charged. 1. Attach crank to square shaft at front,left of mechanism. (2) CRANK RACKING HANDLE, DWG. NO. 2251 B 5412 (Standard) RACK OUT RACK IN 2. If circuit breaker is in either test or operating position, 1. With circuit breaker on rails of cell, attach racking handle depress pedal (14, Fig. 1) and rack. Rackingfrom other positions does not require depressing of the pedaL in accordance with above diagram. HANDLING DOLLY DWG. NO. 2254 C 4327 (Optional) LEVER 1. Position dolly against left side of rackinghandle engage ment block and with lifting angle under frame. 2. Rotate lever by pressing on r^t side until circuit breaker front wheels are off the ground. HANDLING DOLLY ORCUIT BREAKER FRONT CHANNEL 3. Circuit breaker couldnowbe pushed in any direction. ORCUIT BREAKER 4. Disengi^e by pressing on left side and then allowing lever WHEELS to rotate upw^. 17 TRANSFER TRUCK ^.^or outdoor non-walk-in Sand ISkV switchgear. 5kV 6" High Base 1314" 15kV High Base SkV ISkV 2251D4689 2251 D4690 o 2251 D4691 2251D4692 HANDLING DOLLY owe. NO. 2251 C 4842 (Standard) HANOUNQ DOLLY 1. Position wheel below circuit breaker racking block with dolly handle up. 2. Lower handle to approximate position as shown. 3. Circuit breaker' could now be pushed in any direction by turning handle. ENQAGEMENT^IN CIRCUIT BREAKER FRONT WHEEL 5kV ARC CHUTE LIFTING YOKE, DWG. NO. 1552 B 5597 ^kV ARC CHUTE LIFTING YOKE, DWG. NO. 1551 B5597 "A** A 1 0 o o © -^ — arc CHUTE LIFTING YOKE LIFTING POINT (Standard) 1. Attach arc chute lifting yoke and tighten damping €-50R1SkV ARCCHUTE screws securely. 2. Lift by means of lifting hook or sling at point "A"; arc chute will swing at proper angle for removing or assembling on to circuit breaker. FRONT REAR 5kV MAINTENANCE CLOSE HANDLE DWG. NO. 1551 B 5628 (Standard) MAIN SHAFT 1. Attach handle to main shaft as shown. 2. Rotate downwards until contacts touch and inspect ROTATE TO CLOSE CONTACTS contact sequence. REAR OF FRAME 18 ISkV MAINTENANCE CLOSE, DWG. NO. 1551 C 5820 (Standaitl) TEST jumper; DWG. NO. 2251 C 4509 (Optional) ACCELERATING SPRING jmijm CIRCUIT BREAKER TERMINAL COMPRESS LJ CELL TERMINAL 1. With circuit breaker near the ceil, insert one end of the 1. Attach handle to extension of accelerating spring as jumper to the circuit breaker secondary disconnect shown. terminal. 2. Compress accelerating springby turning handle COW. 3. Rotate contact blades by hand and inspect contact 2. Insert the other end to the cell secondary disconnect terminal. The circuit breaker could now be tested sequence. electrically from switch on instrument door. TEST CABINET ASS'Y DWG. NO. 2251 D 4340 (Optional) 1. With the circuit breaker removed from the cell and moved near the test cabinet, insert one end of the test jumper to the circuit breaker. 2. Cormect the other end to the Test Cabinet secondary w disconnect terminal. The circuit breaker can now be tested electrically from the test cabinet. APPENDIX 13 TABLE OF SPARE PARTS FOR BREAKER SERIES OST-2 Typical part numbers shown. Breaker Serial Numbers must be givenwhen ordering replacement parts. Sketch Quantity for Description 1 Breaker Part No. 1551D5464 Type of Breaker 5kV 250 MVA 1551 D6006 5kV350MVA 1552 D 5484 15kV 500 MVA 1553 D 5484 15kV750MVA Arc Chute 1565 D 5641 Fixed Arcing 5kV350MVA 15ky750MVA 3 Pairs Contact 1551 D5641 19 5kV250MVA 15kV500 TABLE OF SPARE PARTS FOR BREAKER SERIES OST-2 Sketch No. Quantity for Description 1 Breaker Part No. Type of Br^er ( 15S2DS641 5kV 250MVA&350MVA Moving Arcing 3 3 Contact 9^ Moving Arcing 4 1569 D 5641 15kV750MVA 3 1553 D 5641 15kV 500 MVA 24 48 1571D5641 1571D 5641 15kV500MVA1200A 15kV750MVA 1200A 48 1555 D 5641 5kV 250 and 350 MVA 48 1554 D 5641 48 1570 D 5641 Contact 5 / 1200A Main Fixed Contact lSkV500&750MVA 2000Aand3000A 5kV250MVA.2000A 5kV350M^A 2000A&3000A 1568 D 5641 5kV250MVA2DOOA 5kV35DMVA 1200 & 2000A 15kV 750 MVA 2000A 6 Leading Finger for Moving Contact 6 1556D5641 1557D5641 7 Fixed Aidng 5kv250MVA 1200A 5kV350MVA3000A 15kV750MVA 1200 & 3000A 15kV 500 MVA 6 Contact 5kV Spring 1558 D 5641 250 MVA, 350 MVA. andl5kV750MVA 20 TABIE OF SPARE PARTS FOR BREAKER SERIES DST-2 No. Sketch Quantity for Description 1 Breaker Part No. Applied Voltage 5kV Rotating Moving 1559 D 5641 Arcing Contact Spring 250MVA,350MVA, andl5kV750MVA Main Fixed Contact 24 1560 D 5641 All 5 and 15kV Spring 1551B6044 1552 B 6044 10 (5> © Type AEM 12 5kV350,1200, 2000& 3000A 15kV,750-3000A Mechanism 1553 B 6044 15kV 750-1200 2000A 1556 A 5575 24VDC 1551 A 5575 11 5kV 250,1200 &2000A 15kVS00,1200 & 2000A Shunt Close Assembly Y Relay 48VDC& 115VAC 1552 A 5575 125VDC 1553 A 5575 250VDC 1555 A 5575 230VAC 1551B 5758 48VDC 1552 B 5758 125VDC 1553 B 5758 250VDC 1554 B 5758 115VAC 1555 B 5758 230VAC 1556 B 5758 24VDC Assembly U 21 1ABLE OF SPARE PARTS FOR BREAKER SERIES OST-2 No. © 13 Quantity for Description Sketch 1 Breaker Part No. Applied Voltage 1551C5584 24VDC 1552C5584 48VDC 1553 C 5584 125VDC O Shunt Trip Assembly 115/230VAC CAP. TRIP. Spring ChargingMotor 14 1554C5584 250VDC 1551B5585 48VDC 1553 B 5585 250VDC 1554 B 5585 115 VAC & 125VDC 1555 B 5585 230 VAC AuxiUaty Switch Basicbreaker is equipped with 5 unit aux. switch which provides "2a"and"2b*' spare contacts. It is not necessary to spediy this c*rV ' ^t 1551D5557 All 1552D5557 AU 1553 D 5557 All switch on breaker orders. 7 Unit aux. switch with 15 Sa & Sb spare contacts. 0 ^ Convertible contact bl3-bl4 is adjustable with infinite resolution. 8 unit aux. switch with 6a & 6b spare contacts. Lockout Switch Basicbreaker is equipped with 2 pole lodcout switch used for internal control. AC Charging 1501 A 5592 It is not necessary to 16 Motor Applications specify this switi^ on breaker order. DC Charging Lockout switch with one L additional spare contact. 22 1502 A 5592 Motor Applications O 1ABLE OF SPARE PARTS FOR RREAKER SERIES OST-2 No. 17 Part No. Applied Vofttage IS64DS641 All ISSI BS369 24 Pins 16 Contact Blodc if req'd. 1S02 A S418 16 Pins Primaiy 1553 A 5533 1200A 1551 B 5675 2000A 1572 D 5641 5kV350 3000A &15kV500 or 750 3000A Description Sketch ai • * 9 H\ Latch Switch Quantity for 1 Breaker bS^ "-S-JL Secondary Disconnect 18 Contact Assembly with 24 contacts 19 Discormect Contact Assembly Primary 20 Discormect Contact Assembly o 23 7 t r> ^ INSTRUCTIONS FOR INSTALLATION >ERAI- PACIFIC Type DST 5&15 KV Magnetic Air Circuit Breakers IN. DST November 1959 ' •». -• m bottom comer. (b) Adjust by varying spacers in latch. 2. Adjust prop to roller. position of the roller is altered, it breaks the connection between these parts, and the main shaft is then free to move to the open position. (a) Tangent point 1/8". Same as closing-lever. (b) Adjust by castle-nut on prop spring guide." ' The roller is held in its fixed relationship to the moving pans by the latch assembly. 3. Adjust solenoid travel. (a) Close breaker manually. Depressing ihe magnet armature releases the latch, allowing the two internal toggles to collapse (b) Push solenoid plunger until it hits lightly against closing lever and frip-frae roller. (c) Gap between brass washers and solenoid and thus release the roller from its relatively fixed position. back plate 3/32"-1/8". (over-travel) (d) Adjust by changing shims inside plunger. During a normal closing operation this latch linkage remains firm, allowing the solenoid and closing lever to rotate the main shaft all the way to its closed position. At this point a prop snaps into place engaging the latch roller and holding the main shaft in the closed position. Simultane ously, the solenoid cut-off switch operates to deenergize the solenoid, and, after the necessary decay of current, the solenoid and closing lever return to their initial position leaving the operating shaft in the closed position as held by the roller and the prop. 4. Over-travel stop adjustment. Adjust so that: (a) Mechanism cannot go over dead center. (b) Puffer piston does not hit rear spacer tubes. (c) Auxiliary switch linkage does not go over dead center. (d) Gap between stop and main shaft should be at least 1/8" minimum when breaker is closed. CautionI A check should be then made (manu ally) to insure that this adjustment does not allow the mechanism to lock on dead center. 5. Solenoid back-travel check. 4 - Mechanism Adjustments (a) Space between closing lever and roller, when circuit breaker is open, should be 1/16" to 1/8". (b) SKV only - Projection of solenoid plunger The most important adjustment of the mechanism is that of the roller. The tangent point between the roller and the flat surface it rests against should be approximately 1/8" from the lower cor beyond breaker frame 1-1/4" maximum, ner of the flat surface. There are two such flat 14 ' Latch Adjustment 4. Piston should not hit tubular spaces in back. 1. Latch armature engagement with segment, Shock Absorber (a) 1/16"to 5/64". 1. Should be lubricated inside with Lubriplate or 2. Gap between armature and segment when latch is unloaded 1/16" to 3/32 ". equivalent. 2. Orifice size selected will permit 10% bounce or normal opening. Trip-free opening will have more bounce (approximately 25%). 3. Adjust magnet frame to allow 1/32" to 1/16 " over- travel of armature after latch trips. (a) Gap between armature rivets and magnet pole face approximately 3/8" when latch is set. 3. Plston-rlng gaps should be 180" opposite from each other. 4. Force to trip breaker approximately 4 lbs. 5. Latch should break freely Auxiliary Switch when armature Is depressed when latch reset spring is overcome 1. Linkage should not go over dead center on closing. by hand. 2. "A'' switches make just before arc contacts touch. 6. Latch engaging surfaces on armature and segment should be free of paint or foreign matter. 3. Trip coil "A" switch makes 1" or sooner before arc trips make. 7. Magnet pole face should be lined up with armature face. 4. Mechanism Check Points contacts make after of the breaker Contacts 1. Latch must reset under all conditions (mechanical and electrical). 1. 2. With latch armature depressed, breaker should trip free before contacts way closed. "B" opening stroke. Main Contacts (a) 1/8" il/32" deflection at top of bars on all have traveled half 3 poles. (b) Make certain the two bolts at each end of 3. Latch must have at least 1/32" clearance. the Insulating support are tight. 4. At least 1/8" clearance between closing lever Note: The vertical insulating piece that supports and trip free roller. the lower bushing from the breaker frame must be tight before these adjustments are made. Any loosening of the bolts holding this support will allow an upward move ment of the lower bushing when the breaker is being closed, thus reducing contact 5. Cut-off switch operates simultaneously when prop engages roller. 6. Over-travel stop is not hit before the closing armature has touched the solenoid backplate and deflection. will not let breaker lock on dead center. (c) Clean and bright. Solenoid Cut-Off Switch Adjustment (d) 50% of line to line when checked with carbon paper and thin tissue on manual closing. 1. The solenoid cut-off switch is adjusted so that it closes its contact as prop snaps into position. (e) 3/8"gap ± 1/16"when arcing contacts touch. 2. When the mechanism settles back onto the prop, the cut-off switch contacts must remain closed. 2. Adjustment of Arcing Contact Puffer (a) To adjust arcing* contact, close breaker manually until the main upper contacts are 1. Should be free of any binding. separated by 3/8 ?. At or near this point, the 2. Should be air-tight enough to restrict opening of merely adjust the nut at the end of arcing arcing contacts just touch. To adjust this, breaker when nozzles are closed. contact spring rod. (b) With the individual phase thus adjusted, fine adjustment may then be made .to effect simul- 3. Should not be lubricated. 15 taneously making of the three arcing contacts 6. Periodically test tightness of bolts. Fig. 20-F; 1/16" of each other. Fig. 21-B. 7. Adjust main contact deflection by rotating pushrod on threaded clevis, 1/2 turn 1/32" on main 3. Cluster Contacts (a) Inside diameter of fingers. (Without tension). 1200 amp. 2000 amp. upper contact. Fig. 21-A. 8. Main pivot axis. Fig. 21-C. 1-1/8" - 1-1/4" 1-5/8" - 1-3/4" 9. Interlock, Fig. 19-B, should trip the breaker before crank can be inserted into hole. Fig. 19-A. (b) aiould be free to align to stud that is 3/18" off center in any direction without reducing contact pressure. Interlocking must be adjusted to insure tripping of the breaker before the racking-in handle can be inserted. Pig. 19-A. This is done by adjustment of the eccentric cam on the interlock. Fig. 19-B. 1. Main contacts should be open 3/8" when arcing contacts touch. Fig. 20-A. 2. Arcing contact adjusting nut. Fig. 2D-B. 3. Main contact bridging member. Fig. 20-C. 4. Pull pin to adjust push-rod. Fig. 20-D. 5. Shunt carries full current only during a portion of the interrupting time. Fig. 20-E. b o o c: o O O L i,„J lA. FIGURE 20 m. t Pi? ^ tit FIGURE 21 FIGURE 19 16 0 0 ML Vtr® FIGURE 22 FIGURE 24 FIGURE 23 FIGURE 25 17 Fig. 22 15KV DST Mechanism Adjustments in and will remain energized until contact cs/c opens. 1. Over-travel stop, Fig. 22-A, keeps main shaft from going dead centm*, but should not contact main shaft during electrical operation. The normally closed 52/y contact in the control relay (52/x) circuit opens, thereby de-energizing 52/x which in turn breaks its seal-in contact and de-energizes the breaker closing coil. 2. Adjustment, Fig. 22-B. should be 3/32" approxi mately. This gives enough travel to insure prop Should the operator close the control switch when the breaker is already closed, the closing circuit will not snapping into place. again be energized - the 52/y coil will be energized through the cs/c and 52/aa contacts thus keeping the control relay (52/x) circuit open. 3. Fig. 22-C is de-energized position of solenoidplunger when breaker is in either open or closed position. 4. Manual closing lever. Fig. 23-A. Anti-pump Feature: 5. Neoprene pad to reduce shock. Fig. 23-B. If the operator closes the control switch, and holds the switch in that position when there is a short circuit on the load 'side of the circuit breaker, the 6. Exhaust orifice of shock absorber. Fig. 23-C. overcurrent relays will function and energize the shunt trip coil, which will trip the breaker open. 7. Fig. 24-A - Latch rotates and permits toggle to collapse when armature is depressed. Reclosure (pumping) of the circuit breaker is prevented because at that instant the 52/y coil is energized and its 52/y contact in the circuit of the 52/x coil is 8. Main opening springs. Fig. 23-D. 9. Varying number of spacers will adjust position open. Therefore, the control relay 52/x cannot be of latch-roller to closing lever. Pig. 24-B. energized and thus attempt to close the breaker again. 10. Solenoid cut-off switch should operate only after Suppressor Rectifier: prop snaps into position shown (breaker is closed). Pig. 25-A. This rectifier is shown across the solenoid closing 11. Tangent point of rolle- on surface to be 1/B" approximately from lower comer of surface. coil 52/cc. Its function is to limit the inductive kick when the circuit is opened and thus reduces the arc across the 52/x contacts in series with the 52/cc coil._ Pig. 25-B. 12. Adjust roller to closing-lever by moving latch- It is used only when the control circuit is direct assembly. Fig. 25-C. current. 13. Nut to adjust prop to roller. Fig. 25-D. Opening: 14. 3/8" or enough gap to insure b-ipping. Fig. 24-C. Assuming breaker is in the closed position, energizing the trip coil from control switch or relays opens the circuit breaker by mechanical action of its operating METHOD OF OPERATION SEE SCHEMATIC DIAGRAM • Figure 26 mechanism. Closing: Special Note: Assuming breaker is in the open position with voltage on the control bus, close control switch contact cs/c. Control relay 52/x is energized through a normally closed 52/y contact. Two (2) circuits are made simul This instruction covers the circuit breaker as manufactured in standard form. It is necessary to refer to the actual diagrams supplied with the cimuit breaker, because the diagram shown is typical, and taneously when control relay 52/x contacts close. there are many variations for meeting job reauirements. a. Seal-in circuit: Control relay 52/x is sealed SOURCES OF CONTROL in through its own contact which parallels cs/c contact. Federal Pacific Type DST Air Circuit Breakers are operated by d-c solenoids and shunt trip coils. The b. Closing coil circuit: Control relay 52/x energizes the breaker closing coil 52/cc following methods of operating are available. which closes the breaker. Station Battery Closing and Tripping. The recommended method of operation of the DST air circuit breaker is by means of 125 volt d-c station batteiy-the most reliable source of power because it is essentially Cut-off switch 52/aa closes just prior to the breaker main contacts, energizing the anti-pump relay, 52/y, through the 52/x seal-in contact. 52/y seals itself 18 .JUMPEtl. (+) • « P.O. FUSE BLOCK 30 A. I2SV. C.UF. J_CS U CO O -I U u u (£ 3 O CO o o 30 A. I2SV.C.L. P.O. FUSE BLOCK (-)• »> 2^ P.O. JUMPER SCHEMATIC DIAGRAM LEGEND 7 CONTROL SWITCH CLOSE CONTACT OPEN WHEN DEVICE CONTROL SWITCH TRIP IS DE-ENERGIZED. CONTACT CLOSED WHEN DEVICE IS DE-ENERGIZED. ® CONTACT. T CONTACT. ®REO INDICATINB LIGHT Y (CLOSED) X GREEN INDICATING LIGHT AUXILIARY RELAY Y AUXILIARY RELAY CC CLOSING COIL TC TRIP COIL (OPEN) O DRAWOUT DISCONNECT OPERATING COIL OF DEVICE P.O. PULL OUT aUF. CURRENT LIMITING FUSE RECT SUPPRESSOR RECTIFIER FOR D.C. CONTROL ONLY. FIGURE 26 independent of t)ie a-c system conditions, and is available at all times. recommended that a d-c tripping battery be supplied. A constant, reliable source of tripping power is essential for a well-designed, dependable substation. Rectified AC Closing. This type of operation finds its greatest application in outdoor installations or small isolated indoor installations where the housing and maintenance of a 125 volt station battery creates Capacitor Trip. In applications where it is impractical to supply a source of d-c control, a 240 volt a-c capacitor trip may be used. This requires that a poten tial transformer be connected to the incoming line ahead of the circuit breakers so that the capacitor trip device is energized before the breaker is closed. a major problem. A single phase operating transformer is used to supply 240 volt a-c to a rectifier, which furnishes 125 volt d-c to operate the breaker. Tripping Battery. If a breaker is a-c closed, it is A 125 volt d-c shunt trip coil is used. 19 RATED CONTROL VOLTAGES AND THEIR RANGE and power supply of operating mechanisms of breakers, when measured the terminals of the mechanisms are; Rated control voltages and their ranges for control CLOSING COILS Source Voltage Coil Voltage Symbol Ami! 125 DC 125 DC 1551-1672 100 90-130 250 DC 250 DC 1552-1672 50 180-260 230 AC (Note jKl) 230 AC (Note §2) 125 DC 1551-1672 100 190-250 125 DC 1553-1672 84 190-250 TRIP Voltage Ronge COILS 24 DC 24 DC 1551-0409 25.6 14-30 48 DC 48 DC 1554-0409 12.3 28-60 125 DC 125 DC 1551-1003 250 DC 250 DC Capacitor 5 70-140 180-260 2.5 125 DC 190-250 1551-1003 Reactor WIRING DIAGRAMS Symbol With Latch Check and Lockout Scheme Without Latch Check DC close and trip AC close DC trip AC close capacitor trip 1501-0395 1501-1955 1501-0394 1501-1956 1501-0396 1501-1957 Nomeplate Marking DST 5-75, 150, 250 DST 15-150, 250, 500 Rated KV 4.16 13.8 Max. Des. KV 4.76 15.0 BIL KV 60 95 Rated freq. 60 60 Closing and trip volts are coil voltages not source voltages. NOTE #1 - For use with DST 5-250, 15-500, 1200A and an.2000A breakers. NOTE jSR - For use with DST 5-75, 5-150, 15-150 and 15-250, 1200A breakers only. FIGURE 27 20 chutes, arc-contacts, many contacts etc. allow a complete inspection in a minimum of time. Coil Data Closing coil Closing time approximately 5 cycles after coll is energized. Particular attention should be paid toNEMA SG4-5.07, paragraphs A & K, and a maintenance schedule put in effect based on the frequency of operation or six month intervals, whichever comes first. Shunt trip coil This coil is also used when capacitor trip device is specified. Breakers installed under ideal operating conditions naturally should require less maintenance than tiiose operating under more adverse conditions. Tripping time approximately 3.5 cycles from the time the coil is energized until the arc is broken. A convenient air circuit breaker log sheet is provided Test Data for each breaker. 50 Micro-ohm resistance top to bottom of main contact. NEMA - Standard for Power Circuit Breakers Insulation test SG4-5.07 repetitive duty and normal maintenance 10,000 megohms to ground Power operated breakers, when operating under usual service conditions, shall be capable of operating the required number of times given in the table on Page 34. The operating conditions and the permissible effect upon the breakers are given in the following paragraphs. For each column, all paragraphs listed must be given Dielectric test - DST-5 air circuit breaker 19 KV, 60 cycle, one minute dielectric withstand. (Test should be made with arc-chutes and interphase barriers in position, and from phase-to-phase and phase-to-ground). consideration. Dielectric test - DST-15 air circuit breaker 36 KV, 60 cycle, one minute dielectric withstand. (Test should be made with arc-chutes and interphase barriers in position, and from phase-to-phase and phase-to-ground). Note: Conditions of switching of arc-fumaces or capacitors may require special consid eration. All parts of a breaker that function during a normal operation shall be included. Other parts such as over Secondary control wiring load coils, that function only during infrequent ab normal circuit conditions shall be excluded. 1500 volt, 60 cycle one minute dielectric with stand. Servicing Milli-Voit Drop Tests Servicing shall consist of adjusting, cleaning, lubricating, tightening, etc., as recommended by the Subject to Modification Upper Flange Stud to Stud Stud to Stud Without Clusters With Clusters manufacturer. The operations listed are on the basis of servicing at intervals of six months or less. to Lower Flange Note: Federal Breakers 5KV 1200 2000 are Electric designed as Air Circuit follows in accordance with NEMA SG4-2.13. 40 25 DST 15KV 1200 2000 Pacific DST 50 DST 35 AIR CIRCUIT BREAKER MAINTENANCE DST DST DST DST Federal Pacific Electric Company high voltage air DST DST 5-75 5-150 5-150 5-250 5-250 15-150 15-250 15-250 15-500 1200 amp Line 1200 amp Line 1 4 2000 amp Line 5 1200 amp Line 6 2000 amp Line 7 1200 amp Line 13 1200 amp Line 14 1200 amp Line 16 2000 amp Line 17 circuit breakers are designed, tested and manufactured Visual Inspection in accordance with NEMA Standards for power circuit breakers. Pub. No. SQ4-1954 and as amended. Arc-Chutes: Tip the arc-chute back on the hinge pin and check the condition of the blow-out coils, Aperiodic maintenance schedule should be established in accordance with NEMA Standards to insure years of trouble-fi'ee operation. The easily accessible arc- interrupting chamber and arc-runners. (Small pieces or flakes of the ceramic arc plates may 21 chip off. If large pieces are broken a more thorough examination should be made to determine the extent of the damage.) ably clean and free of grease. (A small amount of petrolatum may be used on the two large guide pins and the small Interlock pin.) Crocus cloth may be used to dress the male connectors. The Interrupter chamber will become discolored with faultcurrent Interruption, (yellow, blue-green, Primary Disconnects: The primary disconnects should be clean and ftee of pitting. All the springs should or brown color but Is operable unless mechanical damage Is done to the arc-chamber or arc plates. be tight and the entire assembly should rotate freely on the stud. Loose springs will cause pit ting of the contact areas and heating of the cell bushings as well as the breaker. Primary discon nects should be replaced as an assembly. Arc-Contacts: The arc-contacts should be reasonably clean and free of pits, voids, and Irregularities. A fine file may be used to dress the arc contacts. Minor pitting, etc., Is to be expected under service conditions and will not necessitate replacement. Severe fault conditions will understandably cause more damage and may require replacement. Lubrication Hip Mechanism: A good grade of silicon grease or other lubricant that does not become stiff In cold Arc-Contact Alignment: Hie arc-contacts should make before the main contacts and break after the main contacts. The' stationary arcing contact is not adjustable, but the moving arc-contacts are indi vidually adjustable, and should make within weather should be used to lubricate the trip mech anism. The trip trigger should be kept fl-ee of corrosion at all times. All of the pins, bearing, etc., are a combination of non-ferrous metals and no corrosion or settling should result if lightly 1/16" of each other. (Close the breaker slowly lubricated. with maintenance closing bar and observe three pole operation fhim the side of the breaker.) Closing Mechanism: A good grade of silicon grease or other lulHlcant that does not become stiff In cold weather should be used to lubricate the Main Contacts: The main contacts should be reason closing mechanism. All of the pins, bearings, ably clean and fl-ee of irregularities. Each contact Is spring loaded, and In the open position the etc., are a combination of non-ferrous metals contact surfaces may not seat parallel. No current and no corrosion seizing should result If lightly is interrupted by the main contacts and little or lubricated. no pitting should be expected. Racklng-in Mechanism: Any good grade of heavy Main Contact Alignment: The lower set of main contacts should make before the upper set. Nei ther the upper or lower main contacts are ad grease may be used to lubricate the bearings, justable, but are rather spring loaded. The lower and upper contacts should deflect 1/8". The upper main contacts should be 5/16" apart when the arcing contacts touch. (Close the breaker slowly with the maintenance closing bar and observe three pole operation fix)m the side of the breaker.) A positive check on contact alignment Is as follows: Insert a. piece of white paper Primary Disconnects: The leading edges should be lightly greased with petrolatum to provide less friction when racklng-ln. Caution: excessive pet rolatum will melt off at high temperatures and es tablish a potential track path In the cell bushing. wormgear, etc. Operational Inspection Manual Close: Close the breaker slowly with the maintenance closing bar (arc chutes should be down and breaker completely operable except interphase barrier should be off). The breaker should close smoothly and easily. against the fixed main contacts with a piece of carbon paper between the white paper and moving contacts. Close the breaker slowly with the main tenance closing bar until it is latched closed. Hip the breaker manually and observe the contact line Imprints on the white paper. A line contact of 50 " per cent per contact Is acceptable. A small amount of tremor should be experienced after the breaker latches In. CAUTION: Do not close breaker in operate position with maintenance Auxiliary Switch: The "b" contacts should make in the open position and the "a" contacts in the closed position. The fingers of the auxiliary closing bar or without interphase barrier. Manual Trip: Hip the breaker by lifting the interlock trip bar. The breaker should trip easily with a switches contacts can be dressed with crocus cloth If pitted. Severe pitting should be investi gated circuit-wise and the auxiliary switch re minimum of lifting effort. placed. Electrical Close: Close the breaker by means of the test cabinet or in the test position in the cell. Secondary Disconnects: The male prongs of the secondary disconnect should be clean and free Low Voltage Hip: Hip the breaker electrically with of pitting. The molded housing should be reason 22 ^ the trip voltage adjusted to the minimum voltage indicated. Minimum Rated 24V DC 14V DC 48V DC 28V DC 125V DC 250V DC 70V DC 180V DC 230V AC (CAP.) 190V AC Note: The trip voltage should be measured across the trip coil, not at the source. The arma ture may be blocked up to prevent tripping to get a steady voltage reading. Puffer and Arc Chutes: Place a piece of thin paper pv Ir StE : • Ifvl over each arc chute and trip the breaker. The air blast from the puffer will raise the papers if the puffer is functioning properly and the arc-chute is free of obstructions. When corresponding with the Pactory, the following information should be given: VOLTAGE CLASS FIGURE 28 , CONTINUOUS CURRENT Remove these bolts and lift out the entire shunt INTERRUPTING RATING trip device. The shunt-trip coil can be replaced in a few CLOSING VOLTAGE CLOSING VOLTAGE RANGE TRIP VOLTAGE minutes. REPLACING SOLENOID COIL DST 15-500 Remove circuit breaker from cell and tip forward as shown in Figure 28. Disconnect the two coil-leads TRIP VOLTAGE R.INGE for the terminal block. Polarity is unimportant. DATE INSTALLED Remove circular plunger plate, etc., by removing the two 1-1/4" socket-head cap-screws that fasten it to OPERATION COUNTER WHEN RECEIVED OPERATION COUNTER WHEN INSTALLED. SERIAL NUMBER the plunger shaft. Be careful to save the brass shims under the plunger-plate, also the two screws. Remove end-plate, thus exposing coil. Lift out coil (approximately 80 lbs.) noting that leads emerge from coil on right hand side of solenoid frame (as seen from rear of breaker). REPLACEMENT OF COILS Insert new coil, have leads emerge in proper direction. Shunt-trip coil Reassemble carefully in reverse order. Remove circuit breaker from cell. Disconnect shunt-trip leads from terminal block. REPLACING SOLENOID MECHANISM AND COIL Two hex head bolts support the shunt-trip device. DST 5-250 Remove circuit breaker from cell and tip forward as shown in Figure 28. Disconnect the two coil-leads from the terminal block. Polarity is unimportant. Remove circular plunger-plate, etc., by removing the two 1-1/4" socket-head cap-screws that fasten it to the plunger shaft. Be careful to save the brass shims •mder the plunger plate, also the two screws. Attach crane or hoist to the plunger shaft as shown in figure. 3 Arcing contact, stationary Dwg. 1551-1182 3 Arcing contact, movable Dwg. 1551-1080 3 Main contact, upper stationary Dwg. 1551-1073 3 Main contact, lower stationary Dwg. 1551-1075 3 Main contact, movable Dwg. 1551-1081 3 Arc chutes Dwg. 1551-1590 6 Clusters (10 fingers each) Dwg. 1551-0284 3 Pull-rod assembly Dwg. 1551-1270 1 Solenoid coil, 250 volts DC Dwg. 1552-1672 1 Solenoid coil, 125 volts DC (230 V AC source) Dwg. 1553-1672 Loosen puffer device. Remove the nuts from the three holding bolts on the bottom of the solenoid frame. Lift complete solenoid out and set it down on floor or bench. 1 Solenoid coil, 125 volts DC Dwg. 1551-1672 Remove end-plate, thus exposing coil. 1 Shunt trip coil, 24 volts DC Dwg. 1551-0409 1 Shunt trip coil, 48 volts DC Dwg. 1551-1002 1 Shunt trip coil, 125 volts DC Dwg. 1551-1003 1 Eight circuit auxiliary switch Dwg. 1551-1665 4 One stage only of auxiliary switch Dwg. Lift out coil (approximately 80 lbs.) noting that leads emerge from coil on right hand side of solenoid frame (as seen from rear of breaker). Insert new coil, have leads emerge in proper direction. 1551-1216 Control Panel for Outdoor-Indoor Metal-Clad Switchgear - Dwg. 2253-0387 or 3351-0454 Reassemble carefully in reverse order. Quantity - Total for One Circuit Breaker Lower complete solenoid into breaker frame. Adjust so that coil leads are on the right hand side. The 3 1 Rectifier, 100 Amp Dwg. 2701-0244 bolts on bottom plate will lineup with holes in breaker 1 Suppressor Rectifier Reference Dwg. 3300-0006 Dwg. 1 Capacitor Trip Device Dwg. 2753-0137 mechanism. RECOMMENDED STOCK OF RENEWAL PARTS 1 X Relay Contactor Bull. 501-U-151-CA-186-M, One set of parts for every ten (10) circuit breakers. Dwg. 039-017 Dwg. 039-016 Dwg. 039-018 Dwg. 095-002 1 Y Relay, 2 N.O. 8i 2 N.C. Contacts, 230 V, 60 Cycle Coil Resistance 180 Ohms Dwg. 095-004 1 Y Relay, 2 N.O. & 2 N.C. Contacts, 250 V DC Continuous Duty, Coil Resistance 13,000 Ohms Dwg. 095-005 Dwg. 099-013 115 V DC 1 X Relay Contactor Bull. 501-U-151-06-M, 1 Set of arcing contacts 1 Set main disconnecting contacts assembly 230 V, 60 Cycle 1 Shuht trip coil 1 Set lift or pull rods 1 Lot of fingers and 087-004 1 X Relay Contactor segments for auxiliary Bull. 501-U-151-CA-187-M, switches 250 V DC 1 Secondary disconnecting block complete 1 Y Relay, 2 N.O. & 2 N.C. Contacts, 115 V DC Continuous Duty, Coil Resistance Note: When ordering any of the items listed below the Serial Number of the breaker must be 3650 Ohms given. PEDSerial No.. RECOMMENDED SPARE PARTS 1 Fixed Resistor, 25 Watt, 1250 Ohms •DST-5, 250-1200 Amp Air Circuit Breaker 1 18 Point Contact Secondary Block Dwg. 2752-0107 General Assembly Drawing 1551-1653 1 18 Point Contact Secondary Block Dwg. 2751-0107 (Cell) ^antity - Total for one Circuit Breaker •See Renewal Parts Catalogs for other Rated Breakers 24 SUGGESTED AIR Inspection CIRCUIT 1st BREAKER 3rd 2nd Date Inspector OPERATION COUNTER OPERATIONS SINCE SERVICING VISUAL INSPECTION ARC CHUTES ARCING CONTACTS ARCING CONTACT ALIGNMENT MAIN CONTACTS MAIN CONTACT ALIGNMENT AUXILIARY SWITCH SECONDARY DISCONNECTS PRIMARY DISCONNECTS LUBRICATION TRIP MECHANISM CLOSING MECHANISM RACKING IN MECHANISM PRIMARY DISCONNECTS OPERATIONAL INSPECTION MANUAL CLOSE MANUAL TRIP ELECTRICAL CLOSE ELECTRICAL TRIP LOW VOLTAGE TRIP PUPPER AND ARC CHUTES Code: G-Good, P-Palr, X-shouId be replaced next inspection. NOTES: 25 4th LOG Sth SHEET 6th 7th Sth 9th 10th ' ' *COMPLETE INSPECTION Ga 12-4 Asm. to adjust shock absm-ber. AND OPERATING TEST PROCEDURE FOR (d) Trip armature clearance to latch (.031 - .094) ^Ga jjl3-5 4.16 KV-75/150/250 MVA, 1200 amp. 13.8 KV-150/250/500 MVA. 1200 amp. (e) Trip armature engagement with latch (75%min.) 4.16 KV-150/250/ 2000 amp. 13.8 KV-2S0/500/ 2000 amp. If less, check armature spring tension. Breaker Type DST. (f) Trip latch free of armature throughout latch -KV MVA _ -AMP. DATE. stroke after tripping If not free for complete stroke, call Serial No. Inspection Leader. Shop Ord. No. Fed. Mfg. Ord. No. (g) Itip armature clearance to pole face (3/87/16) Ga #2-3 Operating voltage range; V Close Adjust by the number of shims under TRIP V- Operating time at normal voltage: Close Trip sec. Reclose coil frame. sec. (h) Closing lever wipe on roiler (3/32-1/8) sec. Breaker nameplate agrees with bill of material Adjust by adding or removing shims under latch frame asm. (V) (i) Prop wipe on roller (3/32-1/8) 1. Check all hardware to be tight and in place (v)___ Adjust by turning adjusting nut on spring retaining screw. 2. Control wiring continuity check Wiring Diagram No. Rev. No. (j) Stop 3. Resistance of coils: Closing Coil. Trip clearance to main shaft (1/8-3/16) Ga #1-2 .ohms. nhmg (k) Closing Resistance to be ±10% of the following values: Closing Colls ohms 1551-0409 - 2.5 ohms 1552-1672 - 4.00 ohms 1551-1002 - 5.5 ohms 1553-1672 - 1.50 ohms 1551-1003 - 25 ohms overtravel ciearance to Ga #2-3 Asm. to adjust by the number of shims between plunger and armature Trip Coils 1551-1672 - 0.90 armature plate (3/32-1/8) 5. Contact adjustments before electrical operations: Main Contacts (a) Contacting surface area should be 50% min. 4. Mechanism adjustments before eiectrical oper of bar with ations: Make impression using carbon and tissue. Dress contacts, if necessary (a) Close and open breaker slowly with manual closing lever holding prop away from roiler. Check for smooth operation, binding, over- toggie, etc. ( (b) Contact penetration (top and bottom all bars) 5KV, 15KV (1/8+1/32) ). Adjust by turning clevis on bottom of (b) Depress tiip armature and manually close push rods. 0 A 0 C breaker. allowable 1" max. movement of main contacts ( Top ). left - right, left • right 0 B ieft - right, ; .. (c) Closing lever clearance to roller (1/16-1/8) (c) Contact gap between stationary and moving 26 contacts. before breaker trips Jn. 5KV (2-7/8 + 1/4-0) Ga j|l3-4 *( ). Lockout switch has overtravel with hand trip lifted ( ). 15KV (5-1/8 + 3/8-0) Ga #1-2 0A 0B 8. Lubrication 0C Check all latch, cams, rollers, bearings, etc. Adjust shock absorber for lubrication. Check alt contacts for grease. (d) Primary gap at arcing contacts make 5KV, 15KV (3/8 + 1/8-0) Ga #1-3 9. Operating Control Voltage 0B Breaker opens at 20% below minimum voltage 0C . Adjust using C.C.V.. or .sec. (At 10% below mln. for 24V and 48V), (after 10 sec. delay on capacitor trip) washers under spring guide nut. Breako^ closes at 10% below mlnimiun voltage Arcing Contacts C.C.V. (a) Contacts on the same phase make simul 10. No Load Operations taneously During operations observe veeder counter, sema phore, puffer operation and general performance (b) Contacts make within 1/16 of each other on different phases. Adjust using washers of breakers. under spring guide nut. Close and Trip 6. Auxiliary Switches Auxiliary Contacts Trip ( Free ). (b) Normally open "A" contacts make (0-1/4") before arcing contacts touch ( ), ( 10 times at normal voltage— Reclose 10 times at normal vnltngo Reclose 15 times at minimum voltage. (Reclose breakers with latch check switch only) 11. Electrical Timing (c) Normally closed "B" contacts make after arcing contacts are 60% open 15 times at minimum voltage Trip and Trip (a) Trip Coll - "A-A" contacts make (3/4-1) before arcing contacts touch 10 times at maximum voltage_____ Close and ). Maximum trip time at normal voltage (0.05 sec.) Aux. contacts are adjusted by the spline sec.. I shaft relation to cam or operating arm. Maximum closing time at normal voltage (0.25 sec.) (d) Closing coil cut-off switch should make just Maximum trip free time at normal voltage (0.06sec.) cycles sec. after prop engages roller Adjust ( cycles ). /'vr.laa Maximum by moving position of switch locaticm on mech. frame. reclosing time at normal voltage (0.33 sec.) sec cycles (Reclose breakers with latch check switch only) (e) Latch check switch should make after trip armature has reset at least 50% ( ). Adjust by turning operating screw in arm. 12. Analyzer Curves 7. Hard Trip and Lockout Switch (a) Close and trip at minimum voltage Trip cam clearance to trip armature with breaker (b) Close and trip at normal voltage closed (1/32-Mln.) Ga #5 Trip armature overtravel with hand trip lifted (c) Reclose at minimum voltage (1/32-Min.) Ga #5 Lockout switch opens simultaneously or just (d) Reclose at normal voltage 27 L- (ti) Tri^ free at normal voltage (Rebound on opening to be 10% maximum, check Orifice size.) taneously. (b) Contacts make within 1/16 of each other on dinerent phases. 13. Mechanical Check After Electricol Operations (a) Closing lever clearance to roller (1/16 - 1/8) - If any changes In above, re-adJust and Ga #2-4 recheck after trip and close 5 times at normal voltage. (b) Trip armature clearance to latch (.063 - .094) Ga #3-4 15. Contact Resistance (c) Trip armature engagement with latch (75%min.) Resistance of new clean contacts % With baskets ( (d) Trip armature clearance to poleface ) (1200A - 60 microhms or less) (3/8 • 7/16) (2000A - 40 microhms or less) Ga #2-3 Without baskets ( (e) Closing lever wipe on roller (3/32 - 1/8) ) (1200A - 30 microhms or less) (2000A • 20 microhms or less) Tn. (f) Prop wipe on roller (3/32 - 1/8) 0A. 0B. 0C .In. jnlcrohms .microhms -microhms (g) Stop clearance to main shaft (1/8 - 3/16) Ga #1-2 16. High Potential Test (h) Closing armature overtravel clearance to plate Primary Hi Pot for one minute (3/32 - 1/8) Ga #2-3 36 KV for 15 KV breakers, 19 KV for 5 KV If any changes in above, re-adJust and Ix'eakers recheck minimum operating voltage 14. Contact Check After Electric Operations Secondary Hi Pot for one minute Main Contacts ISOO volt for all breakers (a) Contact penetration 5KV. 15KV (1/8 + 1/32) 0A left - right, 0B left - right, 0C left - right 17. Test approval mark added nameplate 18. Analyzer curves and contact impression record is Top. attached to this ropnrt 19. Signatures: (b) Contact gap (5KV 2 7/8 + 1/4-0) Ga #3-4, {15KV 5-1/8 + 3/8-0), Ga #1-2, Test Inspector. 0A Date 0B 0C Factory Foreman. (c) Primary gap at arcing (3/8 + 1/8-0 5-15KV) contacts make Customer's Inspector. Date 0A 0B 0C Note: For making adjustments use gauges 1501-1742. Revisionrwtto Arcing Contacts (a) Contacts to on same phase CVipinoor make simul 28 lN-810.9 INSTRUCTION MANUAL for TYPE FP LOW VOLTAGE POWER CIRCUIT BREAKERS and FM FUSEMATIC® BREAKERS FP25-600 FP50-1600 FM25-600 FM501600 JUNE, 1971 V © FP-25-eoO FM-25-600 CIRCUIT BREAKER F6DERA1. FUSEMATIC* PACIFIC ELECTRIC POWER EQUIPMENT SYSTEMS DIVISION 150 AVENUE L, NEWARK, NEW JERSEY 07101 COMPANV INSTRUCTION MANUAL for TYPE FP LOW VOLTAGE POWER CIRCUIT BREAKERS and FM FUSEMATIC®BREAKERS Manually and Electrically Operated BREAKER FUSEMATIC® Type FP-25-600 FM-25-600 Type FP-50-1600 FM-50-1600 INDEX t \ PAGE Part 1 General Description 3 Part 2 Shipment, Receiving, Handling & Storage 3 Part 3 Inspection & Installation 3 Part 4 Maintenance 6 Part 5 Accessories 7 Parts Overcurrent Trip Devices 9 Part 7 Wiring Diagram 11 Part 8 Recommended Spare Parts 12 FEDERAl. PACIFIC ELECTRIC COMPANY POWER EQUIPMENT SYSTEMS DIVISION 150 AVENUE L. NEWARK. NEW JERSEY 07101 PART 1 GENERAL DESCRIPTION This Instruction Manual covers the FP25-600, FP50-I600, FM25-600 and FM50-I600 Fusematic breakers only. For PART 3 INSPECTION AND INSTALLATION SECTION I Inspection - Manually Operated Breakers instructions on the FP 75 series breakers refer in Instruc tion Booklet #IN810.10. The FP line of Low Voltage Power Circuit Breakers and Fusematic Breakers, which ranges from ISA through 1600A continuous current at 600 Volt ratings, are designed for simplicity of operation, reliability and easy mainten ance. TTie FP Breaker and FM Fusematic are equipped with a stored energy mechanism mechanically trip free in any position of the closing cycle, three unit pole assemblies, fuUy field adjustable timing devices, multi-range series trip coils, and telescoping roll-out rails. The three position drawout mechanism is operable with the door closed. STANDARD ACCESSORIES Maintenance closing handle 1151-9252 Cell racking in handle 1101-9251 The FP and FM breakers consist of a coordinated set of assemblies mounted on a steel frame, all carefully adjusted and locked in place for long and trouble-free operation. To assist in properly checking and inspecting breakers prior to placing into service, the following steps should be followed in the order listed: 1. Remove arc chutes and interphase barriers. 2. Chaise stored energy mechanism by rotating operating handle to a positive stop. Return handle to normal vertical position by counter-clockwise rotation. NOTE: Charging Operation: FP & FM25-600 — Rotate handle 90° counterclock wise to engage mechanism and then 180° clockwise to positive stop. (Figure I). PART 2 SHIPMENT, RECEIVING, HANDLING AND STORAGE Raise 90° to engage ctiarging > Each FP Breaker and FM Fusematic is thoroughly inspect ed and tested before leaving the factory. Breakers are shipped in individual crates or in the cell compartment. If breakers are crated, no hooks should be used in handling. Examine all equipment carefully for indication of damage sustained in transit. If damage in transit is indicated, call for an immediate inspection by the deliveringcarrier. Upon ratchet Rotate 180° clockwise to charge springs NORMAL HANDLE POSITION assessment of the damage a claim should be filed with the carrier or, depending on the nature of the damage, an in tent to file for concealed damage should be registered. For assistance in filing the claim, advise the area sales office of Federal Pacific Electric Company, giving a full description of the damage, serial number of the breaker, delivering carrier's name, and, if shipped by rail, the car number, waybill reference, and any offier iniformation that might be Figure 1 FP & FM50-I600 — Unfold collapsible handle from vertical down position to vertical up position. Rotate 180° clockwise to positive stop. Release handle slowly. (Figure 2). of help to the Company in aiding in the filing of the damage claim. When unpacking, make sure that all items are removed from the box including packing list, instruction book, main tenance parts and hardware. Report any shortage immed iately. Stc that identification tags are left on the breaker. ^Roioe to extend^ handle Lifting eyelets are furnished for handling. Do not lift or handle breaker by the front box or the operating handle. Clean breaker thoroughly. To remove dust an industrial vacuum cleaner is recommended. If the breaker can be installed in its permanent location, it is advisable to do so, even if it is not expected to be energized for some time. When breakers must be stored in buildings under construc tion, be sure they are kept in a space free of dust, moisture, dirt and in an upright position. It is recommended that the breaker not be operated prior to final inspection. Rotofo cioel(w}M.H - ISO* to chorQo Figure 2 3. Block the undervoltage trip device, when supplied, to prevent tripping. 4. Remove right and left hand accelerating springs (Fig ure 4). 6. With maintenance closing handle in position and trip bar in tripped position, proceed to close breaker. Oper ating mechanism will now be trip free and contacts should not make. 7. Remove maintenance closing handle and trip breaker by moving trip bar. 8. Replace one pull-off spring right side only. 9. Inspect each arc chute to be sure no plates are dam aged. Replace chutes and interphase barriers on break ers. Move contacts in by hand to insure contacts move in and out freely. 10. To avoid possible injury NEVER handle or touch any moveable part of the breaker when the stored enei^ mechanism is charged. Press close button on front C - lI.E, cover. Breaker will close. Depress red trip button (located in chatting handle). Breaker will open. It. Recharge stored energy mechanism and close breaker. Slowly move series trip coil magnet (armature) to fully closed position. Breaker should trip before arma ture touches pole face assembly. Repeat this procedure on all poles. 12. On a draw-out breaker, chaige stored energy mech anism. close breaker and move draw-out interlock Figure 4 plate to the left. Breaker will trip. D/0 Interlock plate must be fully reset to the right before operating breaker to prevent trip-free operations. (Figure 6). I tjjj, • • f • Rgure 5 5. Insert maintenance closing handle #1151-9252 as in Figure 5 and slowly operate until arcing contacts touch. All arcing contacts should make rimultaneously Figure 6 with a permissible variation of 1/32 max. Moveable 13. Charge stored energy mechanism and close breaker. Pull padlock lever out. Breaker should trip before pad arcing contact fingers should align with stationary arcing contacts. Refer to Part 4 for adjusting instructions if misalign ment or misadjustments are observed. Moveable arcing contacts are designed with ride clearances for better guidance inride the arc chutes. A ride to ride move ment of 1/8 is allowable. Close breaker and check overtravel on main contacts: l/8"± 1/32". lock slot is fully exposed. 14. Check retaining rings and hardware for tightness. 15. Basket and finger assembly should be secured with Nylok retainii^ screws. Contact fingers must be free of dirt and foreign particles. The secondary contacts should operate freely. SECTION II Inspection • Electrically Operated Breakers The ratchet-driven stored energy mechanism is chained by a fractional horsepower AC/DC universal motor. Identifi cation, voltage ranges and current requirements are speci fied IkIow. The stored energy mechanism chafes in approximately one second. CHARGING MOTORS FOR FP BREAKERS STORED ENERGY MECHANISM Voltage Rating FPE Part # Motor FLA. 48VA.C./48V D.C. 162-007 15058 20 n5VA.C./125VD.C. 162-004 14976 230VA.C./250V O.C. 162-006 14978 LRA. Fuse* 50 12.0 6.5 25 5.0 6.1 12 3.5 Maximum 240V, use conlrol power transformer for higher voltage 'Class 1330 Econ Dual element fuses From wiring diagram supplied with equipment, or standard diagram Part 7 of this book, locate motor terminals on Figure 7 secondary contacts and connect required power source. Motor will charge when power Is applied and shutofT auto matically when charging cycle is completed. Breaker cannot be closed with the maintenance closing handle unless stored energy mechanism is charged. On all electrically operated FP breakers the stored energy mech anism will recharge immediately following a closing opera tion ready for instant reclosure if needed. Follow infection procedure as outlined in "Inspection — Manually Operated Breakers." In addition the following steps arc recommended: 16. From wiring diagram locate terminals on secondary contacts and connect proper control power supply and controls for shunt close and shunt trip attachments. Close and open breaker five limes electrically and check for proper operation. 17. Disconnect control power supply. Close and trip tripbreaker manually. Do not leave breaker in the charged and/or closed position while in storage. 18. Move shunt close solenoid armature manually to release closing springs without control power. 9. Draw-out mechanism on breaker should be in OUT position. 10. Push breaker inside the cell until racking-in cranks engage a positive stop. This is the OUT position. 11. Close and fasten the door. The metal mask provided on outside of front box will move freely back as It comes In contact with the door. The door should close all the way with the breaker In the OUT position. 12. Push drawout interlock to left, insert drawout lever 1101-9251, (Figure 8) into the bottom hole of the drawout mechanism and, with an up-strokc, rack breaker into the TEST position. Removedrawout lever, drawout interlock plate should snap into position com pletely covering the holes. 13. Install control power fuses, enei^izing the circuit. The motor will charge the stored enei^y mechanism. The closing and tripping control circuits become eneigized in the TEST position. 14. Open door and make sure that grounding contact in cell Is In contact with the breaker. Close door and SECTION ill - Installation Before installing breaker in cell, check following points inside cell: 1. Secondary contact support when supplied -* make sure all connections are tight and adjusted to proper dimensions. 2. Ground connections should be tight. 3. Extension rails should be free to move in and out; check rail stops for tightness. 4. Rail rollers should be free and well lubricated. 5. Main contact stabs should be tight and free of dust and dirt. Lubricate with contact grease. 6. Check condition of insulating transite plate in roof of case. Screws should be tight. 7. Remove control power fuses. 8. Place breaker on fully extended moveablc rails. Make sure all four rollers engage on inside grooves (Outside grooves fit into stationary rails inside cell). (Figure 7). check breaker electrically for proper closing and opening operation. If breaker operates properly, rack breaker back to OUT position and leave there until ready to be put into service. 15. To put circuit breaker into service push drawout interlock to left, insert drawout lever in the bottom 3. Make sure all retaining rings arc in place. hole of the drawout mechanism (Figure 8) and with 4. Surfaces marked "F" should be lubricated by a thin an upward stroke rack breaker into operating position. Remove drawout lever, interlock plate should snap in portion and red IN appears. (Figure 9 and 9A). film of "Conducto-Lube #240-200" before assembly. (Figure 12). Contacts must be inspected after every known short circuit interruption and should also be inspected at regular in spection periods. If contacts arc found to be worn or ex cessively pitted they should be dressed or replaced. CAUTION: When reinstalling the arc chutes, adjust the retaining screws on the arc chute retaining bar so that the contact insulating block clears the arc chute base when the breaker is closed. CONTACT ASSEMBLY To repair or replace moveable arcing contacts, proceed as follows (Figure 11): 1. Charge stored energy mechanism. 2. Remove arc chutes and interphase barrier. 3. Remove insulating block and push fork assembly. 4. Tighten moveable arcing contact's adjusting screw until springs are solid and remove retaining pins. Figure 9 & Figure 9A PART 4 MAINTENANCE The breakers with all component parts have been exten sively tested for performance as per NEMA Standards SG 3 and ANSI 037-13 and proved to be satisfactory with a wide margin of safety. A periodic maintenance schedule should be established. An annual inspection should be made for clean, low-use applications. More frequent inspections should be made for dirty, corrosive or high-use applications. The following instructions and adjustments should be fol lowed carefully: CONTACT ADJUSTMENT — Figure 10 and 11 MAIN AND ARCING CONTACTS ADJUSTMENT FOR FP600A AND FP1600A BREAKERS "A" • Main Contact Pressure 600A 1600A 5. Remove arcing contact pivot pin and replace moveable arcing contacts. Both contacts should be replaced at one time. 6. Make sure nylon bushings on arcing contact pivot pin are in place and in a good condition, when replacing moveable arcing contact. Reassemble following the reverse sequence of operations and adjust per Figs. 10 and 11. In most cases it is not necessary to replace contacts, but occasional redressing and readjustments are recommended. To replace stationary arcing contacts (Figure 10), remove unit pole assembly, replace main stud and arcing contact assembly, part 1151-9939, for 600A breaker and 11519937 for 1600A breaker. Adjust contacts as per Figures 10, 11 & 12. 42-50 lbs., measured at point of contact 25-35 lbs., measured at point of contact "B" - Over Travel Mains "C" - Arcing Contact Press ^ ±%2 (Fig. 10) 22-25 lbs., measured at a SHOWN FULLY CLOSED point IVi below tip of contact "D"- Gap (distance) between 16 ±^2 (Fig. 11) mains when arcing contacts touch CHECK POINTS —Figure 10, II and 12 1. Stationary arcing contacts — make sure that retaining screws and contacts are tight. 2. Main contacts should be clean and free. Figure 10 PART 5 ACCESSORIES SHUNT TRIP ••I > GAPni'^i^ i; v.! '.UN Kl SHOWN AS ARC CONTACTS MAKE Figure 21 Rgure 13 The shunt trip attachment is mounted directly above the SHOWN FULLY OPEN trip shaft. It is a non-adjustable electro-magnet intended for intermittent duty only, and its circuit should be inter rupted only by an auxiliaiy contact. SHUNT CLOSE Bgure 12 STORED ENERGY MECHANISM Check latch engagement and adjust if necessary to provide a min. of .062" latch surface contact. Make sure springs are in place and in good condition. On electrically operated breakers, remove motor to make sure roller is free and weU lubricated. Reinstall motor. Make sure that all retaining rings are in place. Check mechanism to insure that ail moving parts are free and well lubricated. OPERATING MECHANISM Make sure that all retaining rings and springs are in place and that the mechanism is free. Replace nylon bumper '• -A rollers if excessive wear is evident. Make sure that the operating mechanism resets when stored energy mech anism is charged slowly and that the trip shaft is free. It should take no more than 22 ounce inches of torque to trip the breaker. GENERAL Make sure that all current carrying parts are secured and associated hardware is tight. Basket and finger assembly should be secured but free enough to compensate for mis alignment in ceil. The free up and down movement should be approximately %o. h ' ' ^ .. JH The shunt close attachment is mounted on top of the stored energy mechanism and is used to electrically discharge the stored energy mechanism and thus to close the breaker. It is a non-adjustable intermittent duty device and its circuit should be interrupted by an auxiliary contact. UNDERVOLTAGE ATTACHMENT (Figure 15) AUXILIARY SWITCH (Figure 16) A max. 6 stage, 12 contact switch is available. It is mounted on top of the stored energy mechanism on the right hand side of the breaker and is operated by the main moveable contacts. AH contacts are operated by phenolic cams and are factory adjusted to provide "a" (normally open) and "b" (normally closed) contacts. The position and the condition of all contacts can be seen and inspected through the transparent dust covers. The contacts may be changed from a to b or b to a by removing the cover and Inverting the contact bridge. INTERRUPTING CAPACITY TYPE R-4 AUXILIARY SWITCH INTERRUPTING RATING IN AMPS D.C. D.C. A.C. Non-inductive I InilucUve I Nmi-lniluctlve SINGLE CONTACT 20 I IT 10 DELAV I ADJUSTING I 7.5 -45 A.C. Inductive — — I DOUBLE CONTACT SCREW 40 20 The undervoltage attachment is a continuous duty device, which can be provided with or without a time delay, and which mechanically trips the breaker if the voltage drops to 30% to 60% of normal voltage. It is mechanically re set and hiis no auxiliary contact in its circuit. The under voltage time delay mechanism is of the pneumatic delay BELL ALARM SWITCH (Figure 17) type. The time delay is controlled by the 10-32 adjusting screw. To inspect the undervoltage attachment, hold the move- able armature by hand, close breaker and slowly release armature. Before the armature is fully opened, the spring loaded plunger will be released, strike the trip lever and trip the breaker. Chock for misring retaining rings and loose or missing screws and bolts. Check condition of coiL If undervoltage attachment is noisy while being energized, clean faces of armature and core. Figure 17 A bell alam switch attachment is mounted on the right hand side of the breaker and will function only when breaker is tripped by the ovcrcurrent trip units. It can be manually and/or electrically reset. Closing of breaker also resets the alarm switch. To check the alarm switch attachment, trip breaker with trip button, then with shunt trip. In both cases the switch Figure 16 should not be actuated. Trip breaker by moving the series trip coil magnet and the switch should operate. PART 6 OVERCURRENT TRIP DEVICES GENERAL DESCRIPTION The direct acting series coils and magnet assemblies pro vide the energy to operate the over-current time delay device and to trip the circuit breaker, interrupting sustain ed ovcrcurrents and faults, There are seven (7) different coils covering the range from 15 to 2,000 amperes. Each magnet is field adjustable and calibrated for the values list ed in Table A. Any one of the seven series coils may be used in any one of the three ratings of FP50 circuit break ers and FM Fusematic provided the maximum coil rating does not exceed the maximum continuous current rating Each of the single phase trip coils can be looked upon as a shunt trip continuously energized by the voltage drop across its fuse. Under normal conditions the "fuse drop" voltage is zero, but it immediately rises to a value of "full phase voltage — back E.M.R. (reactive load)" when the load fuse blows. This energizes the single phase trip coil, causing the common trip bar to unlatch and trip the Fusemalic Air Circuit Breaker. The coil is specifically rated at '/m line voltage to assure instantaneous operation even when the Fusematic Air Circuit Bracket is used as a motor starter. In this case, although the back E.M.F. induced in the motor winding is equal to phase voltage, because of phase angle displacement the resultant voltage drop across the fuse is sufficient to trip Fusematic Air Circuit Breakers. of the circuit breaker frame size. _ S4n«> If* t>d _ «« Aaff KlMt nm n i i i i n i i i i t*'A r ' .c: HhiIH Mi|Ml l«r ewgiae CM tibm 'M (M iUmiM* Figure 19 METHOD OF OPERATION A. Figure 18 Dual Magnetic Overcurrent Trip Device (TD-1) (Figure 18) The dual magnetic overcurrent trip device, in combination with the series coil and magnet, provides inverse long de layed tripping for all ovcrcurrents hclow the instantaneous pickup setting, and adjustable instantaneous tripping. All devices arc factory calibrated and can be field adjusted. Series Coil and Magnet The current through the series coil provides the magneto motive force to energize the magnet assembly. The clap per type armature exerts the force on the push rod which operates the trip unit and trips the circuit breaker. The current rating of the coil and magnet may be changed by moving the pole face assembly up or down. The calibrated indicator plate lines up with the pointer on the armature to indicate the proper position of the poleface for each rating. Selective Overcurrent Trip Device (TD-2) (Fig. 18) The selective overcurrent trip device, in combination with the series coil and dual armature magnet, provides inverse long delayed tripping for all ovcrcurrents below the short B. Dual Magnetic Overcurrent Trip Device (TD-1) (Long Time Delay and Instantaneous Trip) delay pickup setting', and short delayed tripping for all The long delay overcurrent trip device consists of a dash ovcrcurrents and faults above the short delay pickup set ting. All devices arc factory calibrated and can be field adjusted. pot which operates by the positive displacement of a liquid through a fixed orifice and an adjustable tension coupling spring which permits the push rod to move rapidly when the force from the magnet exceeds a predetermined value. Single Phasing Protection (Fig. 19) When fuses arc used to protect circuits feeding three phase motors or similar reactive apparatus there is always the possibility, upon the blowing of one fuse only, that the apparatus, single phased, will burn out. To eliminate this danger, Fusematic Air Circuit Breakers incorporate three single phase trip coils, one in parallel with each of the three main fuses. Each trip coil is approximately a one thousand- turn coil wound to operate down to ' in of line voltage. I'he lever ratio between the push rod and the dash pot is adjustable permitting the time delay to be varied. There arc three calibrated positions or adjustment bands. The three bands are identified as minimum, intermediate and maximum. In addition to the long delay band .adjustment there is an adjustable tension spring which prevents motion of the push rod for currents below the maximum desired continuous current. This is (he long delay pickup. It is adjustable from 80 percent to 160 percent with calibrated points at SC/r. 100%, 120%, 140%. and 160%. The tension In the coupling spring determines the current at which the dash pot will be mechanically by-passed. This is the instantaneous pickup adjustment. The high range instantaneous.element has calibrated settings at 7.5, 10 and 15 times the coil and magnet setting. The low range has calibrated settings at .8, 1.5 and 2.5 times. High range the coil retaining screws securely. This is important to pre vent overheating and possible failure. Care should be t^en not to damage the coil insulation. B. units cannot be held modified to low range units or vice versa. C. Selective Service Trip Device (TD-2) (Long Delay and Short Delay) The selective service trip device is similar to the dual mag netic trip device except that it has a rigid coupling link in place of an instantaneous pickup coupling spring and it has a mechanical escapement timing device which provides a short delay for high values of overcurrents and for faults. The long delay dash pot is identical to that used on the dual magnetic trip device. The short delay device is oper Dual Magnetic Overcuri^nt Trip Device (TD-1) (Long Delay and Instantaneous Trip) The circuit breakers are shipped with the trip devices in stalled and properly adjusted. It is only necessary to keep the devices reasonably clean. They are lubricated for the life of the circuit breaker and must not be lubricated again. It is possible to remove and replace a trip device in the held. To Remove a Trip Device The trip units which are contained in transparent plastic cases should be removed as units. Remove the two screws ated by a separate armature in the series coil and magnet which hold the plastic case to the breaker frame. These assembly. It has an adjustable pickup spring with cali brated settings at 5, 7.5 and 10 times the coil and magnet setting. In addition, the short delay has a band adjustment with calibrated points for the minimum, intermediate and screws are located in the back side of the trip unit (looking the maximum bands. MAINTENANCE & ADJUSTMENTS Remove breaker completely from cells before servicing. A. Series Coil and Magnet Assembly The series coil and magnet requires no maintenance other than cleaning periodically to remove dust and dirt which may accumulate on bearings and pivots of the magnet arm atures. All pivots and bearings are made of nylon and no lubrication is required. The current rating of the coil and magnet may be adjusted by loosening the two pole face retaining screws a few turns and sliding the pole face of the flux shunting device up or down to the desired position. The two retaining screws must be tightened securely after making the adjustment. Certain care should be exercised when adjusting the pole face assembly to avoid bending or deforming it. (1) Do not raise or lower the pole face assembly by exerting force on the indicator plate. This plate is calibrated at the factory and bending it will alter the calibration. (2) Move the two pole faces so that they remain par allel, thus preventing binding on the magnet core. The entire series coil and magnet assembly may be remov ed and replaced in the field by removing the Vs" coil retain ing screws and the Vi" magnet retaining screws at the rear of the pole insulator. When replacing coils, always tighten 10 into the front of breaker) and can be removed by reaching in from behind. The connecting rod which connects to the magnet assembly must be slipped off the pin connection at the magnet Then unscrew the plastic part of connecting rod and remove the two nuts holding the tripping pieces in place. To Install a Trip Device Insert the push rod in the proper hole in the front channel and screw the trip unit to the channel using the two Vie" hex. head cap screws provided. IMPORTANT: Use the washer and lock washer provided. Run a 10-32 nut down the push rod. Follow it with a trip finger on top of the push rod with a spacer between the wings and another 10-32 nut. (Do not tighten it yet) Install the nylon turnbuckle and adjust its length so that it is 'A2" longer than is just necessary to permit the trip device to reset the mag netic armature against its stop. Install the turn buckle on the armature pin and retain it with E-ring provided. Adjust the position of the trip finger so that the breaker does not trip when the magnet is closed with a Viz" thick shim in the air gap, and does trip with a V64" thick shim in the air gap. Tighten the linger and check this adjustment again. The trip unit must reset the magnet armature all the way until the armature is against the stop. C. Selective Service Trip Device (TD-2) (Long Delay and Short Delay) The maintenance and adjustment of the selective service trip device is the same as the dual magnetic trip device, except that the trip finger on the short delay push rod is installed under the push rod. Care should be taken to en sure that the long delay trip finger on top of its push rod docs not interfere with the short delay trip finger whjch is installed under its push rod. PART 7 DEFINITION OF SYMBOLS TC Trip coil TCI A phase fuse trip coil TC2 B phase fuse trip coil TC3 C phase fuse trip coil X Closing release coil A Y Anti pump relay B M Spring charging motor C MC/aa MC/bb NO } Motor cut off switch (Shown with NC I closing mechanism spring discharged) — 01 Control switch 01 local 01 close Bell alarm switch BA PF Power fuse UV Undervoltage device Main power circuit - A phase Main power circuit - B phase Main power circuit - C phase Auxiliary switch contact (open when breaker is open) Auxiliary switch contact (closed when breaker Is open) A * • A 1$ I7E$ I* I sa A A A 2ir% 2iF \ >B£ 1111 AUXILIARY M CONTACTS M M M g S 8 S .21 f"20 T®22 '*24 1 5A 2Z *A 9^ 2 S S ® A «> A Ti 1 - t > - 4 6 1 - 6 t • 4 • II • - to It 1) • 14 19 - 10 17 - 10 ii • io 21 • 22 2% - 14 SWITCH FUNCTIONS CAfttV CLOSE CAOtY CLOSE mo OFCM - • FP50 a MiO OPCtt CAOLV CLOSE mo OPEN MIO CLOSE EARLY OPEN MIO FM90 - - ADD FOR FPlOO a FMIOO Wtre 2S to • 06 FPMootf Fli»0 ooty. CLOSE MID OPEN EARLY CLOSE M(0 OPEN XXM-fM TYPE FP a FM ELECTRICALU OPERATED AX.8. SCHEMATIC DIAGRAM 1^ [9C|Z0E^2ZF4 24F( , , V BASIC ELECTRICAL CONTROL I |S(mNofn&43 I " 22 23 o 1(4 12 =»I5 3 18 II 24 25 32 133 , .U 1 47 ' 44 45 ^ 51 52 e 46 48 "A ^ 53 54 49 HOUSING MECHANISM ASSEMBLY ITEM 8 PART NUMBER DESCRIPTION 1151-C-9305 Housing Frame NUMBER REQUIRED PER CIRCUIT BREAKER 2000 400 000 Ado Ado Amp 1 1 1 67 66 1151-A-9758 llOl-A-9218 Trip Lever Trip LeverShaft 5133-37 Trip Lever Shaft Retaining Ring 1104-9796 Trip Lever Shim Washer As Required 1151-A-9853 llOl-A-9927 Trip Lever Rolier Trip Lever Roiier Shaft 1 1 2 on 0104-^3 Retaining Ring 1101-A-9D52 Trip Lever Reset Spring 1 1 1 2 1 1 1 2 1 PART NUMBER DESCRIPTION Amp Asp Amp TRIP FINGER ASSEMBLY 44 3D TRIP LEVER ASSEMBLY 64 59 50 Not Shown 69 68 ITEM NUMBER REQUIRED PER CIRCUIT BREAKER 800 2000 400 29 31 45 43 48 49 47 33 32 24 23 22 1I51-A-9936 1151-A-9262 1101-A-98D4 5100-12 llOl-A-9925 llOl-A-5531 D.C.-B55 llOl-A-9883 Trtp-finger Trip Finger Spring Lockwasher 1 1 Trip Finger Spring Nut 1 1 1 1 2 1 2 2 4 2 1 1 1 1 1 1 1 1 2 2 2 2 1 2 Latch Bearing Assembly Latch Bearing Pin LatchBearing PinRetaining Ring Trip Shaft Trip Shaft Spacer Trip Shaft Bearing Trip Shaft Bearing Holder Trip Shaft Bearing Holder Rivet E598-3/8Lg. 554)22-0944)562; Trip Finger Roil Pin Trip Finger Spring llOl-A-5544 Trip Finger Spring Screw S8-10 lW-8 N-8 1 1 1 2 1 2 2 4 2 1 1 1 1 1 2 1 2 2 4 2 1 1 1 1 1 MAIN SHAFT ASSEMBLY 60 65 55 37 26 34 35 36 llOl-A-9147 llOl-A-9213 1151-A-9539 llOl-A-9216 5133-50 llOl-A-9116 lW-375 N-375 Lever Arm LeverArm Bearing Main Latch Link Main Latch Shaft Main Latch Shaft RetainingRing LeverArm Stop LeverArm Stop Lock Washer Lever Arm Stop Nut 2 2 1 1 2 2 2 2 2 2 1 1 2 2 2 2 2 2 1 1 2 2 2 2 2 2 1 1 1 1 1 2 2 2 1 1 1 1 1 2 1 2 1 2 2 1 2 1 2 1 2 2 1 2 TRIP FINGER STOP 53 54 52 51 18 5 6 7 28 1101-9145 llOl-A-9152 llOl-A-9172 llOl-A-9191 llOl-A-9108 52-028-125 1101-9215 42 5133-37 61 62 20 21 56 llOl-A-9192 5133-37 llOl-A-9194 llOl-A-9196 5133-37 llOl-A-9195 57 5133-37 19 Compression Link 2 Lift Link Drive Yoke Drive Yoke Turnbuckle Drive Yoke Turnbuckle Lock Drive Yoke Turnbuckle Lock Pin 2 1 1 1 1 1 2 Trip Lever Stop Pin Trip LeverStop Pin Retaining Ring Lift Link Pin Drive Pin 1 2 1 Drive Pin Roiier 2 Drive Pin Roiier Retaining Ring Compression Link Pin Compression Link Pin Retaining Ring 2 1 2 Lift Link Pin Retaining Ring llOl-A-9543 lW-250 N-250 Trip FingerStop Pin Stop Pin Tubing Mounting Lockwasher Mounting Nut TRIP GUIDE ASSEMBLY llOl-A-9111 5133-25 1117-B-9806 OPERATING LINKAGE 58 63 llOl-A-09934 Trip Guide Latch Trip Guide Latch Retaining Ring Trip Guide Latch Spring CROSS BAR ASSEMBLY Cross Bar 4 4' 12 11 1151-9407 1151-94D8 llDl-9219 llDl-9214 10 9 15 17 14 14* 1101-9190 5100-37 llOl-A-5543 llOl-A-9946 llOl-A-5540 llOl-A-9142 1102-9116 1104-9116 13 IW-IO 25 16 Cross Bar Cross Bar Pin Cross Bar Spacer 1 1 2 2 2 2 4 2 1 6 2 2 2 4 2 1 4 2 6 Mounting Screw 4 4 4 Mounting Washer 4 4 4 Mounting Lock Washer 8 8 8 Mounting Nut 8 8 8 Cross Bar Roiier Cross Bar Roiier RetainingRing Puli-Off Spring Hook Puli-Off Spring End Pull-Off Spring Cross Bar Guide Insulation Block Mounting Screw Insulation BlockMounting Screw Insulation Block Mounting 4 2 1 4 2 4 2 6 Lockwasher MOUNTING HARDWARE Not Shown TRIP ROD ASSEMBLY 40 27 39 38 41 llOl-A-9593 Trip Rod Guide 1151-A-9942 Trip Rod 1105-B-9606 Trip Rod Spring 52-022-0494)875 Trip Rod Guide Pin WS8-6 Trip Rod Assembly fdounting Screw 1 1 1 1 2 1 1 1 1 2 Not W-250 Shown Not Shown 1W-250 Not N-250 Shown «SIMIUR TO PART SHOWN 17 • ' J&-' FP-50 FRAME ASSEMBLY MAIN ASSEMBLY PARTS 400 I SOO FIXEO MOUNTED inM PART NUMBER DESCRIPTION 17 17* 16 11 10 15 1151-9392 1151-9395 1101-9162 1101-9163 1101-9266 1101-9266 1102-9272 1101-9272 1101-9160 1101-9273 Back Plate Assembly Back Plate Assembly 23 23* 22 22* 2000 FIXED MDUNTED 400 S 000 DRAWOUT 2000 DRAWOUT 1 1 Lower Left Side Lower Right Side Upper Right Side Upper Left Side Forward Cross Member Forward Cross Member Main Cross Member Main Cross Member GROUNDING STRIP ASSEMBLY 18 19 20 21 1101-9917 lS-250-10 lW-250 N-250 Grounding Strip Grounding Strip Mounting Screw 1111 2 2 2 2 Grounding Strip Lock Washer Grounding Strip Nut 2 2 2 2 2 2 2 2 DRAW-OUT ROLLER ASSEMBLY 1101-9686 Draw-Out Roller 1101-9685 Draw-Out Roller Shaft W-500 Draw-Out Roller Washer 5133-50 W-375 lW-375 N-375 Draw-Out Roller Retaining Ring Mounting Washer Mounting Lock Washer Mounting Nut 1S-250-10 1W-250 N-250 Frame Screw Frame Lock Washer Frame Nut 4 4 4 4 4 4 4 FRAME FASTENERS 12 13 14 16 16 16 16 16 16 16 16 16 16 16 16 NAME PLATE 1101-9295 1101-9277 Name Plate Name Plate Screw «SlMIIJtR TO PART SHOWN 19 1 DRAW OUT AND INDICATOR MECHANISM ASSEMBLY MANUALLY OPERATED FIXED DRAW-OUT 2DI0 ITEM PART NUMBER DESCRIPTION & SflD StOO ELECTRICALLY OPERATED DRAW-OUT 4«0 & ZCCO SCO FIXED 400 S ZOSD FRAME ASSEMBLY 11 11* 11* 11* 1151-9710 1152-9710 1153-9710 1154-9710 Frame Assembly Frame Assembly Frame Assembly Frame Assembly 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 INDICATOR LINKS 9 10 4 5 3 12 13 16 18 15 19 20 16 1101-9944 1116-9606 SF6-40x5/32Lg. lW-6 1101-9732 1151-9735 1101-9738 5133-15 102-023 1101-9718 1151-9739 1101-9738 5133-15 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 2 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 2 1 2 1 1 1 1 2 1 2 1 1 1 1 1 1 1 1 1 O.C. Indicator Conn. Link 1 0.0. Indicator Conn. Spring 1 O.C. Indicator Conn. Screw O.C. Indicator Conn. Washer 1 1 O.C. Indicator Conn. Return Spring 1 O.C. Indicator 1 O.C. Indicator Pin 1 Indicator Pin Retaining Ring C.D. Link Spring C.D. Link Return Spring 2 1 1 C.D. Indicator C.D. Indicator Pin 1 1 Indicator Pin Retaining Ring 1 2 1 LOCAL CLOSE LINKAGE 8 8* 6 7 17 14 1151-9720 1152-9720 1101-9732 W810-4 120-001 WS6-7 Local Close Linkage Local Close Linkage Local Close ReturnSpring 1 1 1 1 1 Close Linkage Mounting Screw 2 1 2 1 2 1 2 Local Close Switch Local Close Switch Mounting Screw 2 1 2 1 2 1 2 DRAW-OUT OPERATING MECHANISM 30 33 32 31 29 27 24 25 23 26 26* 22 22* 34 21 1151-9800 19S-312-24 1101-9743 llOl-A-9744 N-312 1101-9652 1108-B-9606 llOl-A-9734 52-048-219-1750 llOl-A-9663 1102-A-9663 llOl-A-9742 1102-A-9742 1151-9671 52-032-156-1250 Front GearAssembly Front Gear Screw Front Gear Washer 1 1 Fron Gear Spacer 1 Front Gear Lock Nut Rear Gear 1 1 1 1 1 Rear Gear Index Pin Spring Rear Gear Index Pin Rear Gear Roll Pin Operating Shaft Operating Shaft Left Shaft Guide 1 1 1 1 1 1 3 3 1 1 1 Right Shaft Guide Drive Link Assembly 2 2 Drive Link Pin 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 3 1 1 1 1 1 2 1 1 1 3 3 1 2 2 1 1 1 2 2 1 1 1 1 1 1 1 8 8 1 1 1 1 1 1 1 10 10 1 2 1 1 1 TRIP LINKAGE 35 28 36 37 38 39 40 2 1 1151-B-9528 llOl-A-5512 llOl-A-9529 llOl-A-5514 52-012-062-0500 1120-B-9606 llOl-A-5581 lW-250 N-250 Trip Link Assembly Trip Link Spacer Trip Link Pivot Shaft Trip Link Washer Trip Link Pin Trip Link ReturnSpring Trip Link Return Spring Pin Mounting Lock Washer Mounting Nut 1 1 1 1 1 1 1 6 6 1 1 1 1 1 1 1 6 6 1 1 1 1 1 1 1 8 8 1 1 1 1 1 1 1 10 10 1 1 1 1 1 1 1 6 6 1 1 1 1 1 1 1 6 6 •SIMILAR TO PART SHOWN 21 I>>t ARC CHUTE MUHBER REODIRED PER POU IHM PART NUMBER DESCRIPTION 2 1101-9554 Upper Cover 4 1101-9410 De-lonization Screen 5 1101-9411 Blow-Out Magnet 6 1101-9414 Blow-Out Magnet Insulation Plate 7 1101-9558 Left Side Plate 8 1101-9558 Center Plate 9 1101-9557 Right Side Plate 10 1101-9413 Pressure Plate Insulation 11 1101-9412 Pressure Plate 13 1101-9553 Lower Cover 12 1101-9811 Guide Pin 14 1101-9824 Thrust Plate 1 RT6-148 Front Rivet 3 RT6-100 Rear Rivet AU n>-sa 23 ' -<• bP c ni SERIES COIL & MAGNET ASSEMBLY PART NUMBER ITEM ID DESCRIPTION NUMBER REQUIRED PER FOU DUAl MABNmC SELECTIVE SERVICE m 22S 400 SCO 2000 20 SO 12S 2» 409 SOD 50 20119 SERIES COIL 7 6 5 4 3 2 1 8 9 10 1101-9771 1101-9772 1151-9994 1151-9755 1151-9756 1151-9776 1101-9440 15-20Amp Coil 30-50 Amp CdII 70-125 Amp Coil 150-225 Amp Coll 250400 Amp Coil 500-800 Amp Coll 1000-2000 Amp Coil 1 1101-9967 Rear Insulation 1101-9966 1101-9986 Insulation Disc 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Insulation Tube 1 1 1 1 1 16 1 1 8 1 1 1 1 1 1 5 1 1 3 1 1 1 2 2 1 1 1 2 2 2 1 2 1 1 2 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 2 2 1 2 1 1 1 1 2 1 1 1 1 8 1 1 5 1 1 3 1 2 2 1 1 1 2 2 1 I 1 2 2 1 1 1 2 2 1 2 1 1 1 2 1 1 1 2 1 1 1 2 1 1 16 1 1 1 1 MAGNET CORE ASSEMBLY 11 12 13 14 15 16 1151-9769 1151-9763 1151-9106 Stationary MagAet Assembly Magnet CoreAssembly Mapet Core Bracket 1101-9948 1101-9099 12R5118 Center Spacer OutsideSpacer Rivet 1 1 1 1 1 2 2 1 1 1 2 2 1 1 1 1 2 2 1 1 2 2 1 1 2 POLE FACE ASSEMBLY 1151-9750 S6-30 1101-9707 1101-9747 1101-9855 1101-9856 1101-9857 1101-9858 1101-9859 1101-9860 1101-9861 RT2-8A 20 17 18 19 27 26 25 24 23 22 21 28 Pole Face Pole Face Screw Pole Face Plate 1 2 1 1 1 Pole Face Tapped Plate Pole Pole Pole Pole Pole Pole Pole Pole Face Face Face Face Face Face Face Face Indicator Plate Indicator Plate 1 2 1 1 1 2 1 1 1 2 1 1 1 1 1 Indicator Plate indicator Plate Indicator Plate Indicator Plate Indicator Plate Indicator Plate Rivet 1 1 1 1 1 1 1 1 2 2 1 1 1 2 1 1 2 2 2 2 1 2 1 2 2 2 2 2 2 2 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 2 2 1 1 1 1 1 1 2 4 1 3 3 1 1 1 2 2 1 1 1 2 2 1 1 1 2 2 1 1 1 2 2 1 1 ARMATURE ASSEMBLY 1151-9753 1151-9754 1101-9109 5133-18 1101-9784 1101-9379 Left Hand Armature 0 19S-37S-40 19S-375-48 t 19S-375-44 S h 19S-500-20 lW-375 W.375 3/8-16 Bolt 2-1/2" Lg. 3/8-16 Bolt 3" Lg3/8-16 Bolt 2-3/4" Lg. 1/2-13 Bolt 1-1/8" Lg. 33 34 31 29 32 30 1 1 1 1 1 1 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2 1 1 1 1 2 4 1 2 2 1 1 1 2 2 1 1 1 2 2 1 1 Right Hand Armature Armature Shaft Armature Shaft Retaining Ring Spacer Washer Spacer Tube MOUNTING HARDWARE N 0 VT n lW-500 W-5Q0 3/8" Lock Washer 3/8" Washer 1/2" Lock Washer 1/2" Washer 2 1 4 4 1 1 2 1 4 4 1 1 1 1 1 1 1 3 3 1 1 1 2 2 1 1 1 4 4 1 1 1 4 4 1 1 25 FP-50 SERIES TRIP UNIT ITEM 1 PART NUMBER DESCRIPTION 1151-9082 Dual Magnetic Series Trip Unit TypeTDl Long Delay & Instantaneous Trip 1151-9081 Selecting Series Trip Unit TypeTD2 NUMBER REOUIRED PER POLE 1 Long Delay &Sliort Delay Trip 1151-9879 Special Service Trip Unit TypeTD3 Long Delay, Short Delay & Instantaneous Trip 1151-9083 Special Application Trip Unit TypeTD4 Long Delay Trip MOUNTING HARDWARE TO 1 & 4 TO 2 & 3 2 2 lS-312-7 Mounting Screw 9 lW-312 Mounting Lock Washer 2 8 1101-9128 Trip Arm 2 7 N-10 Trip Arm Jam Nut 2 6 N-250 Spacer Nut 2 5 N-10 Trip Arm Nut 2 11 1101-9026 Nylon Turnbuckle 2 12 5133-18 Tumbuckle Retaining Ring 2 10 27 iz 2£ 9£g SE r s - -t _E1 o iijuujuuuuiMjuui iuuuyyuiwju^^ z\ z\ lAAAAAjuuiMjimf mummmm 1 ti t STORED ENERGY MECHANISM ITEM PART NUMBER MANUALLY OPERATED DESCRIPTION 400 100 Rear Plate Rear Plate 1 1 Upper Channel Upper Channel : 1 Lower Channel Lower Channel Front Plate 1 I 1 9 1 lECTNICAlir OPERATED SOOO 2000 FRAME ASSEMBLY 1 I151-B-9533 r 1101-9156 1151-B-9396 2 2* 32 32* 21 34 115I-B-9365 1151-8-9362 I151-B-9364 1151-B-9230 22TM-02 : 1 1 1 1 1 1 1 9 1 9 1 1 Assembly Nut 1 1 1 9 9 1 I 9 FRONT PLATE ASSEMBLY 33 29 30 31 19 20 18 17 18 16 13 27 26 25 28 14 15 23 22 24 llOl-A-9164 llOl-A-9166 1101-A-9i55 5100-25 llOl-A-9450 Ratchet Gear Ratchet Pawl Ratchet Pawl Spring Ratchet Pawl Retaining Ring Cam Stop Latch Plate llOl-A-9522 Latch Reset Piate 1105-A-979S 2701-A-0412 1103-A-9796 Shim Washer Washer lIOl-A-9521 Cam Stop Pin Cam Stop Roll Pin e quJ e d As e q u e d Rear Shim Washer 79-022-094-0375 1101-9222 1104-9764 1101-9151 Close Latch Pin Close Latch Shim Close Latch Lever 79-022-0944)525 Close Latch Level Roll Pin 1101-9248 1101-9788 1151.A-9490 Z-7756-W Cam Stop Reset Spring Support Cam Stop Reset Spring Charging Lever Assembly llOl-A-9417 As Charging lever Pawl Spring Charging Lever Return Spring INTERNAL MECHANISM 10 9 8 3 4 5 6 7 7* 11 12 12* 36 37 35 •SIMIUR 1151-9374 Cam Assembly 1 1151-9373 Thrust Brachet Assembly 1 llOl-A-9241 Spring Holder 1101-4684 Guide Pin 2 2 2 2 1 2 2 2 2 1101-9229 1101-A-9796 1102-A-9796 1151-9806 1152-9806 1101-9267 1112-9606 1111-9606 llOl-A-9165 llOI-A-9748 22M-04 Guide Pin Cam Spacer 1 Cam Shim Main Main Main Main Main Spring Guide Spring Guide Spring Guide Screw Spring Spring Tumbuchle Head Jumbuckie'Screw . Turnbuckle Screw Nut As 2 1 2 2 2 2 1 Re 2 1 1 2 2 2 2 2 2 2 1 2 1 quired 2 2 10 10 4 2 10 4 1 1 1 10 4 1 1 1 10 2 4 4 1 1 1 1 2 2 2 2 1 10 4 1 1 1 1 1 1 1 I 1 TO PART SHOWN 29 rs (> 6 5 4 7 8 1^ o 3 .1_ I 13 12 10 '1 1 14 I L 15 19 20 21 22 23 i 24 25 *29 30 31 « 32 33 34 35 36 30 . I Y-RELAY; CHARGING MOTOR - SHUNT CLOSE; SHUNT TRIP; SAFETY LOCK ITEM PART HUMBER DESCRIPTION AIL BREAKERS Y (ANTI PUMP) RELAY 1 r 1* 1* 1* 2 3 Not Shown 1151-5569 1152-5569 1153-5569 1154-5569 1155-5569 S-10-10 IW-IO Y Relay 48VAC YRelay 115VAC YRelay 230V AC YRelay 125VDC YRelay 250V DC YRelay Mounting Screw YRelay Mounting Lock Washer 1 1 1 1 1 2 2 N-10 YRelay Mounting Nut 2 SHUNT TRIP SHUNT CLOSE SHUNT TRIP & SHUNT CLOSE 6 7 8 9 15 15* 15* 15* 15* 15* 15* 15* 13 14 12 10 11 4 5 1101-9513 1101-9512 1101-9524 1101-9516 1151-9818 1152-9818 1153-9818 1154-9818 1155-9818 1156-9818 1157-9818 1158-9818 1101-9931 1101-9690 llOl-A-5583 S104 2W-10 S8-8 1W8 Magnet Frame Magnet Core Magnet Spring Magnet Armature 1 I 1 1 1 1 1 1 1 1 1 1 Coil 24V DC Coil 48V DC Coil 125V DC Coil 250V DC 1 1 1 1 1 1 1 1 Coil 230V AC Coil 48V AC Coil 115V AC Coil 230V AC Shunt Close Arm ShuntTrip Arm 1 1 1 1 1 1 1 2 2 2 2 Guide Plate Guide Plate Screw Guide Plate Loch Washer Mounting Screw Mounting Lock Washer 400 1 2 2 2 2 000 2000 1 1 1 1 1 1 1 SPRING CHARGING MOTOR 18 18* 18* 18* 18* 17 16 19 20 15058 14975 14977 14976 14978 1101-9220 5100-31 1/4-20 X1-1/2 Lg. 21 lW-250 W-250 24 25 22 23 26 27 28 IlOl-A-5543 llOl-A-5605 SF6J2-4 2W-6 lIOl-B-5604 1S8-5 2W-8 Spring Charging Motor 48V AC-DC Spring Charging Motor 115V AC • 125V DC SpringCharging Motor 230V AC - 250V DC Spring Charging Motor 115VAC - 125V DC SpringCharging Motor 230V AC - 250V DC Motor Roller Motor Motor Motor Motor Roller Retaining Ring Mounting Screw Mounting Lock Washer Mounting Washer 1 1 3 3 3 1 1 3 3 3 1 1 1 1 3 3 3 MOTOR CUT-OFF SWITCH Motor Cut-Off Switch Switch Insulation Switch Mounting Screw Switch Mounting Lock Washer Mounting Bracket Mounting Screw Mounting LockWasher 2 2 STORED ENERGY SAFETY LOCK 33 34 35 36 31 32 29 30 1151-9863 1101-9864 1113-9606 50-028-125-1250 1101-9225 WS6-2 S8-6 lW-8 Lock Frame Lock Pin Lock Pin Spring Lock Pin Roll Pin Name Plate Name Plate Screw 2 Mounting Screw Mounting Lock Washer 2 2 'SIMILAR TO PART SHOWN 31 AUXILIARY SWITCH & SECTOR ASSEMBLY MANUALLY OPERATED ELECTRICAUY OPERATED FP-50 BREAKERS FP-SO BREAKERS ITEM FART NUMBER description 11S7-9323 3 UNITS NO EXTRA CONTACTS 11SS-S923 4 UNITS 2 EXTRA CONTACTS I1S9-9923 9 UNITS 4 EXTRA CONTACTS 11E0-$923 G UNITS G EXTRA CONTACTS 3 4 1 1 1 8 2 5 1 6 1 1 1 12 2 t161-9923 3 UNITS 6 EXTRA CONTACTS AUXILIARY SWITCH 7 24 23 21 20 6 8* 8* 8* 8 8* 17* 17* 17* 17 5 4 1 3 2 25 26 18 19 C46422 1101-9914 A-356791 1102-9914 1101-9815 C45287 1101-9961 1102-9981 1103-9961 1104-9961 1105-9961 S8-38 S848 S8-58 SB-68 1151-9911 1101-9890 5133-25 1101-9501 WS64 S8-5 lW-8 lW-8 N-8 Unit Assembly Right End Mounting Bracket End insuiation Left End Mounting Bracket 1 1 Switch Cam 1 8 Terminai Jumper 2 Contact Contact Contact Contact Contact insuiation insuiation insuiation insuiation insuiation Panel Panel Panel Panel Panel 1 1 10 2 3 1 1 1 6 2 2 Switch Assembiy Screw Switch Assembiy Screw Switch Assembly Screw SwitchAssembiy Screw Operating Shaft Assembiy Drive Link Long Drive Link Retaining Ring Drive Link Short Drive Link Lock Screw Mounting Screw Mounting Lock Washer SwitchAssembiy Lock Washer Switch Assembiy Nut 2 1 1 1 2 1 2 3 3 2 2 1 2 1 2 3 3 2 2 UNIT ASSEMBLY C-46422 NUMBER REOUIREO PER UNIT ASSEMBLY 22 045276 Unit Housing 15 16 14 13 C45278 045293 C-45300 C-45299 Moving Contact Assembiy Moving Contact Support Moving Contact Spring Moving Contact Spring Retainer Lower Terminai Stud 12 C45286-1 11 C45286-1 Upper Terminai Stud 9 A-125019-1 Terminai Nut C45298 Stationary Contact 10 1 2 2 2 2 2 2 a 2 COMMON LINKAGE ASSEMBLY (Operates: C.O. Indicator Beii-Alarm, Under Voitage, Auxiiiaiy Switch) XOOOA 490 31 31 33 33* 30 29 28 27 35 35* 34 34* 32 1151-9508 Sector Assembiy 1151-9821 1101-9509 1101-9822 1101-9508 W-250 Sector Assembiy 1102-5588 1503-2639 1101-9505 1101-9823 1101-5586 1103-5586 5133-25 Sector Pivot Pin Sector Pivot Pin Sector Drive Link 1 1 1 1 1 1 As Spacer Washer Required Spacer 1 1 1 1 Drive Pin Spacer Drive Pin Spacer 1 1 Drive & Pivot Pin Retaining Ring 5 5 Cotter Pin Drive Pin Drive Pin ^SIMILAR TO PART SHOWN 33 • •M ARC-CHUTE RETAINING BAR - INTERPHASE BARRIER AUXILIARY CONTACT ASSEMBLY ITEM PART NUMBER FRAME FRAME 1 1 3 3 4 4 4 3 3 4 4 4 Spacer Block Spacer Block 1 1 Left Barrier 1 1 4 1 1 DESCRIPTION »IIOA FRAME ARC-CHUTE RETAINING BAR 1 1* 6 5 2 3 4 1101-9887 1101-9888 1101-9885 lS-250-40 lS-250-12 lW-250 N-250 Arc-Chute Retaining Bar Arc-Chute Retaining Bar Retaining Screw Holder Retaining Screw Mounting Screw Mounting LockWasher Mounting Nut 1 3 3 4 4 4 INTERPHASE BARRIER (2 Req. Per Breaker) 9 9* 8 10 7 1101-9289 1102-9289 1101-9288 1101-9288 SA8-8 Right Barrier Assembly Screw 4 1 1 1 4 SECONDARY CONTACT ASSEMBLY DRAW-OUT BREAKERS (I Req. Per Breaker) 11 12 13 14 Not Shown 17 16 15 1151-9403 1151-0831 lS-250-7 lW-250 3S10-7 lW-10 13-250-12 lW-250 N-250 Secondary Contact Bracket Secondary Contact Block Secondary Contact Mounting Screw Secondary Contact Mounting Lock Washer Wire Binding Screw Wire Binding Lock Washer Mounting Screw Mounting Lock Washer Mounting Nut 1 As Required (1 to 6) 2 Per Block (Item 12) 2 Per Block 4 Per Block 4 Per Block 4 4 4 FIXED MOUNTED 20 23 18 19 22 21 121-012 1101-5518 1S4-14 lW-8 lS-250-8 lW-250 Terminal Block Mounting Bracket Terminal Block Mounting Screw Terminal Block Mounting Lock Washer Mounting Screw Mounting Lock Washer «SiMIUR TO PART SHOWN 35 L24 \ °28 29-'-^O '35»37 NUMBER REQUIRED PER CIRCUIT BREAKER FM-50 FUSEMATIC ATTACHMENTS ITEM 6* 6 5* 5* 5* 5 5* 80IA a zcaoA SSOA FRAME J PART NUMBER DESCRIPTION P1690 P1690 P1700 P1700 P1700 P1700 P1700 FUSE Econolim Fuse "J" 201 to 400 Amp Econolim Fuse "J" 401 to 600 Amp Econolim Fuse "L" Type II 601 to 800 Amp Econolim Fuse "L" Type II 801 to 1200 Amp Econolim Fuse "L" Type II 1201 to 1600 Amp Econolim Fuse "L" Type II 1601 to 2000 Amp Econolim Fuse "L" Type II 2100 to 3000 Amp ZDOOA FRAME FRAME J L L L L L 3 3 3 3 3 3 3 FUSE MOUNTING ACCESSORIES 7 8 9 9* 10 10* 24 14 15 16 16* 16* 17 18 19 20 21 22 23 1101-8108 1101-8107 1101-8102 1101-8202 1101-8101 1101-8201 1101-8103 N-312 lW-312 19S-500-32 19S-500-24 19S-250-20 W500 1W500 N500 19S-375-15 W375 1W375 N375 Right Hand "J" Fuse Adaptor Left Hand "J" Fuse Adaptor Fuse Support Insulator, 800 only Fuse Support Insulator, 2000 only Stab Adaptor, 800 only Stab Adaptor, 2000 only Supporting Rod Supporting Rod Nut Supporting Rod Lock Washer "L" Fuse Mounting Bolt "J" Fuse Mounting Bolt "i" Fuse Mounting Bolt 401 to 600 Amp only Fuse Mounting Washer Fuse Mounting Fuse Mounting Fuse Mounting Fuse Mounting Fuse Mounting Fuse Mounting 1 3 3 1 3 3 2 8 8 2 3 3 Lock Washer Nut Bolt Washer Lock Washer Nut 12 12 12 12 8 8 12 6 18 18 18 12 1 1 3 3 2 8 8 12 1 1 3 3 2 8 8 12 1 1 3 3 2 8 8 12 3 2 8 8 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 1 1 3 3 2 8 8 1 6 6 6 6 INTERPHASE BARRIER 800A FM-SO FRAME 1601 -2000 AMP FUSE am FRAME LINE (UPPER STUD) FUSE MOUNTING 2 r 1101-8109 11018113 Not Stlmpson Shown A1730 LOAD SIDE (LOWER STUD) FUSE MOUNTING LEFT HAND BARRIER 2 1101-8109 4 1101-8104 1 1101-8110 3 SA8-8 RIGHT HAND BARRIER 1101-8109 2 1101-8114 4 1* 1101-8113 Not Shown 40 27 30 31 32 28 29 33 34 26 25 Not Shown 37 38 39 35 36 Not Shown Stlmpson A1730 Spacer 4 2 Assembly Eyelet 8 Inside Barrier Inside Barrier Outside Barrier Spacer Assembly Screw Inside Barrier Outside Barrier Spacer Assembly Eyelet 1101-9512 S12-5B lW-12 SINGLE PHASE PROTECTIVE DEVICE Mounting Plate TrippingArm Magnet Frame Magnet Coil Magnet Core Magnet Core Screw Magnet Core Lock Washer llOl-A-9524 Magnet Core Spring llOl-A-9516 llOl-A-5583 SlO-4 Armature Plate 2W10 Guide Plate Mounting Lock Washer S8-5 lW-8 N-8 S 250-10 lW-250 Magnet Assembly Mounting Screw Magnet Assembly Mounting LockWasher Magnet Assembly Mounting Nut Assembly Mounting Screw Assembly Mounting LockWasher N-250 Assembly Mounting Nut SIO 2W10 Wire Mounting Screw Wire Mounting LockWasher S-250 Wire Mounting Screw 2W-250 Wire Mounting Lock Washer llOl-B-8105 llOl-A-8106 1101-9513 1151-B-9818 Guiding Plate Guide Plate Mounting Screw SOOA a ZOOQA FRAME 1 1 3 3 3 3 3 3 3 2 2 WIRING ACCESSi 11 12 Not Shown Not Shown ^ 37 "SIMILAR TO PART SHOWN FRONT BOX ASSEMBLY inM PART NUMBER DESCRIPTION 1 2 5 6 7 8 3 13 4 1151-9695 Front Box Assembly M51-9810 Front Box Screen 1151-C-9844 1151-9998 Front Box Cover Assembly Front Box Cover Assembly Front Box Cover Assembly Front Box Cover Assembly Lock LeverSpring Front Box Cover Mounting Screw Front Box Mounting Screw 1151-9845 1151-9999 1101-9718 17S64 WS-10-6 ELECT. ELECT. MAN. DRAWOUT FIXED DRAWOUT MAN. FIXED MAN. a ELECT. DRAWOUT MAN. a ELECT. FIXED 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 3 1 4 3 1 4 3 1 1 1 4 3 1 1 4 3 1 4 3 2000 AMP MANUAL CHARGING HANDLE ASSEMBLY 9 14 15 16 17 19 20 21 10 11 12 18 Not Shown 1101-9278 1101-9279 1102-A-9215 1101-9846 5133-25 1101-9560 1101-9846 1101-9561 1101-A-9562 1102-A-9563 1101-9149 6S10-32 lW-10 ChargingHandle Hub Charging Handie Handle Pivot Pin Handle Spring Handle Pivot Pin Retaining Ring Handle Knob Handle Knob Spring Handle Knob Screw Trip Button Trip Button Pin Trip Button Plate Handle Mounting Screw Handle Mounting LockWasher FP 50-400 & -800 MANUAL CHARGING HANDLE 22 10 11* 12 18 Not Shown 1151-9807 llOl-A-9562 llOl-A-9563 1101-9149 6S10-32 Charging Handle Trip Button Trip Button Pin Trip Button Plate Handle Mounting Screw 1111 1111 3 3 3 3 1111 1111 lW-10 Handie Mounting Lock Washer 1111 CHARGING SHAFT ASSEMBLY (All Manual and Manual & Electrical FP-50 Breakers) 25 24 31 30 23 26 28 27 1151-9479 1101-9310 1115-9606 2703-A-0412 1101-9306 1101-9301 1101-9549 1101-9548 Charging Shaft Assembly Manual Charging Dog Dog Spring Dog Washer Handle Centering Spring Handle Centering Spring Spring Guide CenteringSpring Lever 29 994)28-125-1000 Centering Spring Lever Retaining Pin «SiMiUR TO PART SHOWN 39 i. 'i ' ^•3 ., 1' ,*[. . ' • .• j-'.iiVv.V' 37- 3 14 1 m I o II 12 m I iO 23 30 « 16 w 17 O M « 20 21 ^ 18 19 31" 32 33 34 35^®^^ 38 7 14 15 M/i 24 55 6 27 29 39 n ? w '' 42 43 4 4 f 45 C) 2 46 47 K ^ 48 49 — mLII55 56 57 58 59 60 61 62 I 64 65 66 67 68 52 m BELL-ALARM, UNDERVOLTAGE TRIP SHAFT EXTENSIONS ITEM PAST NUMBER OESCRIPTION 400 000 2000 ITEM PART NUMBER 33 34 35 36 37 38 39 40 53 54 41 1101-9473 1101-9472 1101-9468 1533-18 1101-9470 1101-9480 1101-9471 1101-9485 1151-9495 1101-9481 1101-9500 42 S8-8 BELL ALARM ASSEMBLY I 2 3 17 4 5 6 7 8 9 9* 10 11 12 13 14 1101-9896 1101-9899 1151-9902 1533-25 1101-5587 1123-9606 W-250 1503nA-2639 1101-9898 1101-9897 1102-9897 1101-9900 Mounting Plate Deflector Arm Operating Link Operating Link Retaining Ring Operating Pin Operating Pin Spring Operating Pin Washer Operating Pin Cotter Pin Deflection Shaft Drive Arm Deflection Shaft Deflection Shaft Deflection Shaft Return Sorinn 59-028-125-0500 Deflection Arm &Drive Arm Pin 5133-37 Deflection Shaft Retaining Ring 1204101 Bell-Alarm Switch Bell-Alarm Switch Mounting 10S6-8 1 1 1 1 1 1 1 1 1 1 1 2 2 1 2 Screw Bell-Alarm Switch Mounting 15 1W6 16 18 19 20 21 N-6 19S-25D-8 lW-250 W-250 N-250 2 Lock Washer Bell-Alarm Switch Mounting Nut Bell-Alarm Mounting Screw 2 2 2 2 Bell-Alarm Mounting Lock Washer 2 Bell-Alarm Mounting Washer 2 Bell-Alarm Mounting Nut 2 2 2 2 2 2 2 2 2 DESCRIPTION INST. TRIP DEUYED TRIP 1 1 1 2 1 1 1 1 4 1 1 1 2 1 1 1 1 1 1 1 4 4 4 4 2 2 2 1 1 2 2 2 4 2 2 2 1 1 2 2 2 Armature Pivot Pin Spacer Armature Pivot Pin Spacer Drive Pin Drive Pin Retaining Ring Main Spring Latch Pin Armature Latch Lever Dash Pot Gasket Piston Assembly Dash Pot Housing Mounting Bracket Undervoltage Unit Mounting Screw Undervoltage Unit Mounting 44 lW-8 43 45 46 47 48 49 50 51 52 N8 19S-250-8 Lock Washer lW-250 N-250 1101-9502 1101-9501 S6-4 lW-6 5133-25 Undervoltage Unit Mounting Nut Mounting Screw Mounting Lock Washer Mounting Nut Reset Link Reset Link Reset Link Screw Reset Link Lock Washer Reset Link Retaining Ring TRIP SHAFT EXTENSIONS UNDERVOLTAGE TRIP DEVICE INST. TRIP 25 1151-9493 23 23* 23* 23* 23* 23* 22 24 26 27 28 1151-9817 1152-9817 1153-9817 1154-9817 1155-9817 1156-9817 1101-9461 1508-2639 1151-9494 1101-9478 1101-9479 29 1533-15 30 31 1151-5511 1101-9469 32 5133-18 Stationary Magnet & Bracket 1 DEUYED TRIP 1 Assembly Undervoltage Undervoltage Undervoltage Undervoltage Undervoltage Undervoltage Coil 115V AC Coll 230V AC Coll 460V AC Coil 575V AC Coil 125V DC Coil 250V DC Coil Retaining Spring Coil Retaining Cotter Pin Armature Assembly Pull Off Spring Pull Off Spring Pin 1 1 1 1 1 Pull Off Spring Pin Retaining 1 1 1 2 1 2 1 2 1 2 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 Ring Tripping Ram Assembly Armature Pivot Pin Armature Pivot Pin Retaining Ring fp-so n>-so n>-50 400 800 ZOOO 55 55* 63 63* 56 57 58 59 60 61 62 68 1101-9779 1101-9781 1101-9778 1101-9782 Left Hand Shaft Extension Left Hand Shaft Extension Right Hand Shaft Extension Right Hand Shaft Extension 59-028-125-0500 Shaft Extension Coupling Pin 1101-9531 Trip Finger 1102-9531 Trip Finger 1103-9531 Trip Finger 1101-9385 Trip Finger 1101-9309 Counter Weight 59-028-1254)625 Trip Finger Roll Pin 1101-9402 67 6L1-FF 66 S8-8 65 lW-8 64 N-8 Shaft Extension Support Shaft Extension Bearing 1 1 1 1 2 2 1 1 1 6 2 2 1 1 6 1 2 1 1 2 1 1 6 2 2 2 2 4 4 4 4 4 4 4 4 4 1 1 2 1 1 2 Thomson industries Shaft Extension Support Mounting Screw Shaft Extension Support Mounting Screw LockWasher Shaft Extension Support Mounting Nut »SIMIUR TO PART SHOWN 41 IfS'D APR 211983 IN-810.4 INSTRUCTION & RENEWAL PARTS MANUAL for TYPE FP LOW VOLTAGE POWER CIRCUIT BREAKERS and FM FUSEMATIC BREAKER FEBRUARY. 1963 FP-50-800 FM-50^0 CIRCUIT BREAKER FUSEMATIC INSTRUCTION & RENEWAL PARTS MANUAL for TYPE FP LOW VOLTAGE POWER CIRCUIT BREAKERS and FM FUSEMATIC BREAKERS Manually and Electrically Operated BREAKER FUSEMATIC Type FP-50-400 Type FP-50-800 Type FP-50-2000 FM-50-800 FM-50-2000 INDEX PAGE Part 1 General Description 3 Part 2 Shipment, Receiving, Handling & Storage 3 Part 3 Inspection & Installation 3 Part 4 Maintenance 6 Part 5 Accessories 7 Part 6 Overcurrent Trip Devices 9 Part 7 Wiring Diagram 11 Part 8 Recommended Spare Parts 12 Part 9 Spare Parts List 13 FEDERAL PACIFIC ELECTRIC COMPANY 50 PARIS STREET, NEWARK 1, NEW JERSEY PART 3 INSPECTION AND INSTALLATION PART 1 GENERAL DESCRIPTION This Instruction Manual covers the FP50-400, FP50-800, FP50-2000, FM50-800 and FM50-2000 Fusematic break SECTION I Inspection • Manually Operated Breakers ers only. For instructions on the FPlOO series breakers refer in Instruction Booklet #IN810.6. The FP line of Low Voltage Power Circuit Breakers and Fusematic Breakers, which ranges from ISA through 2000A continuous current at 600 Volt ratings, are designed for simplicity of operation, reliability and easy mainten ance. The FP Breaker and FM Fusematic are equipped with a stored energy mechanism mechanically trip free in any position of the closing cycle, three unit pole assemblies, fully field adjustable timing devices, multi-range series trip coOs, and telescoping roll-out rails. The three position drawout mechanism is operable with the door closed. The FP and FM breakers consist of a coordinated set of assemblies mounted on a steel frame, all carefully adjusted and locked in place for long and trouble-free operation. To assist in properly checking and inspecting breakers prior to placing into service, the following 15 points should be followed in the order listed: 1. Remove arc chutes and interphase barriers. 2. Charge stored energy mechanism by rotating operating handle to a positive stop. Handle should return to normal vertical position. NOTE: Charging Operation: STANDARD ACCESSORIES Maintenance closing handle 1151-9252 Cell racking in handle 1101-9251 FP & FM50-400 and 50-800 — Rotate handle 90® counterclockwise to engage mechanism and then 180® clockwise to positive stop. (Figure 1). PART 2 SHIPMENT. RECEIVING. HANDLING AND STORAGE Roise 90" fo engage chorging Each FP Breaker and FM Fusematic is thoroughly inspect ed and tested before leaving the factory. Breakers are shipped in individual crates or in the cell compartment. If breakers are crated, no hooks should be used in handling. Examine all equipment carefully for indication of damage sustained in transit. If damage in transit is indicated, call for an immediate inspection by the delivering carrier. Upon assessment of the damage a claim should be filed with the carrier or, depending on the nature of the damage, an in tent to file for concealed damage should be registered. For assistance in filing the claim, advise the area sales office of Federal Pacific Electric Company, giving a full description of the damage, serial number of the breaker, delivering carrier's name, and, if shipped by rail, the car number, waybill reference! and any other information that might be ratchet ^Rotate 160* cicckwiae to ^chorge spring NORMAL HANDLE POSITION Rgure 1 FP & FM50-2000 — Unfold collapsible handle from vertical down position to vertical up position. Rotate 180® clockwise to positive stop. Release handle slowly. (Figure 2). of help to the Company in aiding in the filing of the damage claim. When unpacking, make sure that all items are removed from the box including packing list, instruction book, main tenance parts and hardware. Report any shortage immed iately. Sec that identification tags arc left on the breaker. Lifting eyelets are furnished for handling. Do not lift or handle breaker by the front box or the operating handle. Roise to extend^ hoodie \ normal handle position Clean breaker thoroughly. To remove dust an industrial vacuum cleaner is recommended. If the breaker can be installed in its permanent location, it is advisable to do so, even if it is not expected to be energized for some time. When breakers must be stored in buildings under construc tion, be sure they are kept in a space free of dust, moisture, dirt and in an upright position. It is recommended that the breaker not be operated prior to final inspection. Rdtote clockwise - I60* to chorge Figure 2 3. Lock safety discharge interlock to prevent accidental discharge of stored energy mechanism. (Figure 3). 6. With maintenance closing handle in position and trip bar in tripped position, proceed to close breaker. Oper ating mechanism will now be trip free and contacts Operate posit Ion Safe lock posit ion should not make. 7. Remove maintenance closing handle and trip breaker by moving trip bar. 8. Replace one pull-off spring right side only. 9. Inspect each arc chute to be sure no plates arc dam aged. Replace chutes and intcrphase barriers on break er. Move contacts in by hand and tighten arc chutes only after contacts move in and out freely. Figure 3 4. Remove right and left hand accelerating springs (Fig ure 4). 10. Release discharge safety interlock. (Figure 3). NOTE; To avoid possible injury NKVER handle or touch any moveable part of the breaker when the stored energy mechanism is charged, without first applying safety interlock. Press close button on front cover. Breaker will close. Depress red trip button (located in charging handle) slowly. Breaker will open before trip button reaches its extreme stop. 11. Recharge stored energy mechanism and close breaker, Slowly move scries trip coil's magnet (armature) to fully closed position. Breaker should trip before arma riA%j ture touches pole face assembly. Repeat this procedure wM. on ail poles. 12. On a draw-out breaker, charge stored energy mechan ism. close breaker and move draw-out interlock plate sideways. Breaker will trip. (Figure 6). i '• Figure 4 ^ Hgure 5 5. Insert maintenance closing handle #1151-9252 as in Figure 5 and slowly operate until arcing contacts touch. All arcing contacts should make simultaneously with a permissible variation of Wj max. Movcable arcing con tact fingers should align with stationary arcing contacts. If misalignment or misadjustments arc observed, refer to Part 4 — MAINTENANCE FOR ADJUSTING INSTRUCTIONS. Moveable arcing contacts are de signed with side clearances for better guidance inside the arc chutes. A side to side movement of '.i is allow able. Close breaker and check overlravcl on main contacts. Figure 6 13. Charge stored energy mechanism and close breaker. Pull padlock lever out. Breaker should trip before pad lock slot is fully exposed. 14. Check retaining rings and hardware for tightness. 15. Basket and finger assembly should be secured and re taining bolts tight. Contact finger must bo free of dirt and foreign particles. Secondary female contacts mounted on breaker must operate freely. SECTION II inspection • Electrically Operated "fill Breakers Electrically the stored energy mechanism is charged by a fractional horsepower ratchet type AC/DC universal mo tor. Identification, voltage ranges and currents requirements are specified below. The stored energy mechanism is charg ed electrically in approximately one second. CHARGING MOTORS FOR FP BREAKERS STORED ENERGY MECHANISM VoitaES Rating FPE Part # LRA. Fuse' 50 12.0 25 5.0 Mator FLA. 48VA-C./48V D.C. 162-007 15058 20 I15VA.C./125V0.C. 230VA.C./250V D.C. 162-004 14976 6.5 162-006 14978 6.1 12 3.5 Maximum 240V, use control power transformer for higher voltage 'Class 1330 Econ Dual element fuses From wiring diagram supplied with equipment, or standard diagram Part 7 of this book, locate motor terminals on secondary contacts and connect required power source. Motor will charge when power is applied and shutoff auto matically when charging cycle is completed. Breaker cannot be closed with the maintenance closing handle unless stored energy mechanism is charged. On all electrically operated FP breakers the stored energy mech anism will recharge immediately following a closing opera tion ready for instant rcclosure if needed. Follow inspection procedure Steps I through 15 exactly as outlined in "Inspection - Manually Operated Breakers." In addition the following steps are recommended: 16. From wiring diagram locale terminals on secondary contacts and connect proper control power supply and controls for shunt close and shunt trip attachments. Close and open breaker five times electrically and check for proper operation. 17. Disconnect control power supply. Close and trip tripbreaker manually. Do not leave breaker in the charged and/or closed position while in storage. Figure 7 9. Draw-out mechanism on breaker should be in OUT position. 10. Push breaker inside the cell until racking-in cranks engage a positive stop. This is the OUT position. 11. Close door slowly ai^d latch and make sure that the metal mask provided on outside of front box moves freely back as it comes in contact with the door. The door should close all the way with the breaker in the OUT position. 12. Push drawout interlock to left, insert drawout icver 1101-9251, (Figi^e 8) into the bottom hole of the drawout mechanism and, with an up-stroke, rack breaker into the TEST position. Remove drawout lever, drawout interlock plate should snap into position com pletely covering the holes. 13. Install control power fuses, circuit is now energized, the motor will charge the stored energy mechanism and closing and tripping control circuits become ener gized in the TEST position. 14. Open door and make sure that grounding contact in cell is now in contact with the breaker. SECTION III - Installation Before installing breaker in cell, check following points inside cell: 1. Secondary contact support — make sure all connec tions are tight and adjusted to proper dimensions. 2. Ground connections should be tight. 3. Extension rails should be free to move in and out; check rail stops for tightness. 4. Rail rollers should be free and well lubricated. 5. Main contact slabs should be tight and free of dust and dirt. 6. Check condition of insulating transite plate In roof of case. Screws should be tight. 7. Remove control power fuses. 8. Place breaker on fully extended moveable rails. Make sure all four rollers engage on inside grooves (Outside grooves fit into stationary rails inside cell). (Figure 7). Close door and check breaker electrically for proper closing and opening operation. If breaker operates properly, rack breaker back to OUT position and leave there until ready to be put into service. 15. When putting into service push drawout interlock to left, inseit drawout lever in the bottom hole of the drawout mechanism (Figure 8) and with an upward stroke rack breaker into operating position. Remove drawout lever, interlock plate should snap in position and red IN appears. 4. Make sure nylon spacer is in place. 5. Roller 1101-9231 must roll free on its pivot pin. 6. Surfaces marked "F" should be lubricated by a thin film of "Conducto-Lube #240-200" before assembly. Contacts must be inspected after every known short circuit intcrrtiption and should also be inspected at regular in spection periods. If contacts are found to be worn or ex cessively pitted they should be dressed or replaced. CAUTION: When reinstalling the arc chutes, adjust the retaining screw holder on the arc chute retaining bar so that the arcing contacts do not come in contact with the arc chute baffles. CONTACT ASSEMBLY To repair or replace moveable arcing contacts, proceed as follows (Figure 11): 1. Charge stored energy mechanism and lock discharge safely interlock (Figure 3). 2. Remove arc chutes and interphase barrier. 3. Remove arc chute retaining bar, 4. Remove insulating block and push fork assembly. 5. Tighten moveable arcing contact's adjusting screw until springs arc solid and remove retaining pins. Rgure 9 & Figure 9A PART 4 MAINTENANCE The breakers with all component part.s have been exten sively tested for performance as per NEMA Standards SO. 3-3-17 and SG. 3-3-18 and proved to be satisfactory with a wide margin of safety. In accordance with NEMA Standards SG3 • Part 6, a peri odic maintenance schedule should be established. For the convenience of the user a simple log .sheet is provided with every breaker to ensure proper maintenance and years of 6. Remove arcing contact pivot pin and replace moveable arcing contacts. Both contacts should be replaced at one lime. 7. Make sure nylon bushings arc in place and in a good condition, while replacing moveable arcing contact. Reassemble following the same sequence of operations and adjust per Figs. 10 & 11. In most cases it is not necessary to replace contacts, but occasional redrc.ssing and readjust ments are recommended. trouble-free operation. It should be kept and followed conscientiously, especially in cases where breakers are re quired to operate under more adverse conditions. To replace stationary arcing contacts (Figure 11). remove The following instructions and adjustments should be fol lowed carefully; 1151-9432 for 2000A breaker. CONTACT ADJUSTMENT — Figure 10 and II MAIN AND ARCING CONTACTS ADJUSTMENT FOR FP400/800 AND FP 2000 BREAKERS "A" - Main Contact Press 400/800A 42-50 lbs., measured at point of contact — 2000A 25-35 lbs., measured at point of contact "B""B" - Over Travel Mains % ±V.i-j "C"- Arcing Contact Press Pre.ss 22-25 lbs., measured at a point \Vi below tip of contact "D" - Gap (distance) between ±'Ac mains when arcing contacts touch CHECK POINTS — Figure 10 and i I 1. Stationary arcing contacts — make sure that retaining screws and contacts arc tight. 2. Main contacts should be clean and free. 3. Make sure all retaining ring.s are in place, unit pole .assembly, replace main stud and arcing contact assembly, part 1151-9339, for 400/800A breaker and Adjust contacts as per Figures 10, 11 & 12. PART 5 ACCESSORIES SHUNT TRIP -J I • < Rgure 11 Figure 13 The shunt trip attachment is mounted directly above the trip shaft. It is a non-adjustable electro-magnet intended for intermittent duty only, and its circuit should be inter rupted only by an auxiliary contact. SHUNT CLOSE Figure 12 STORED ENERGY MECHANISM Check latch engagement and adjust if necessary by moving safety discharge interlock (Figure 3) to proper position. Make sure springs arc in place and in good condition. On electrically operated breakers, remove motor to make sure roller is free and well lubricated. Reinstall motor. Make sure that all retaining rings are in place. Check mechanism to insure that all moving parts arc free and well lubricated. OPERATING MECHANISM Make sure that all retaining rings and springs are in place and that the mechanism is free. Replace nylon bumper rollers if excessive wear is evident. Make sure that the operating mechanism resets when stored energy mechanism is charged slowly and that the trip shaft is free, it should take no more than 20-22 ounce inches of torque to trip the breaker. GENERAL Make sure that all current 'carrying parts arc secured and associated hardware is tight. Basket and finger assembly should be secured but free enough to compensate for mis alignment in cell. The free up and down movement should be approximately •>!(). Figure 14 The shunt close attachment is mounted on top of the stored energy mechanism and is used to electrically discharge the stored energy mechanism and thus to close the breaker. It is a non-adjustable intermittent duty device and its circuit should be interrupted by an auxiliary contact. UNDERVOLTAGE ATTACHMENT (Figure 15 & 15A) AUXILIARY SWITCH (Figure 16) A 4 pole or a 10pole auxiliary switch is normally provided. m It is mounted on top of the stored energy mechanism on the right hand side of the breaker and is operated by the main moveable contacts. All contacts are operated by nylon cams and are factory adjusted to any of the following combinations: Normally Open Early Open Late Open Normally Closed Early Closed Late Closed The position and the condiloin of all contacts can be seen and inspected through a transparent dust cover. LOAD AND INTERRUPTING CAPACITY TYPE R-4 AUXILIARY SWITCH IKTERRUPTIN6 RATIN6 IN AMPS Volts D.C. Inductive B.C. Non-inductive Inductive SINGLE BREAK 15 Figure 15A Figure 15 I -45 I OOUBIi BREAK The undcrvoUagc attachment is a continuous duty device, which can be provided with or without a time delay, and which mechanically trips the breaker if the voltage drops 40 20 to 30% to 60% of normal voltage. It is mechanically reseltable with no auxiliary contact in its circuit. The undervoltage time delay mechanism is of the surface tension delay type. The time delay is controlled by the viscosity of a fluid and is factory adjusted. BELL ALARM SWITCH (Figure 17) To inspect the undervoltage attachment, hold the movcablc armature by hand, close breaker and slowly release arma ture. Before the armature is fully opened, the spring load ed plunger will be released and strike the trip lever and trip the breaker. Check for missingretainingrings and loose or missing screws and bolts. Check condition of coil. If undervoltage attachment is noisy while being energized, clean faces of both armatures. Figure 17 A bell alarm switch attachment is mounted on the right hand side of the breaker and will function only when breaker is tripped by the overcurrcnt trip units. It can be manually and/or electrically reset. Closing of breaker also resets the alarm switch. Figure 16 To check the alarm switch attachment, trip breaker with trip button, then with shunt trip. In both cases the switch should not be actuated. Trip breaker by moving the series trip coil magnet and the switch should operate. PART 6 OVERCURRENT TRIP DEVICES GENERAL DESCRIPTION The direct acting series coils and magnet assemblies pro vide the energy to operate the over-current time delay device and to trip the circuit breaker, interrupting sustain ed overcurrents and faults. There are seven (7) different coils covering the range from 15 to 1600 amperes. Each magnet is set and calibrated in the factory at the desired continuous current rating. Any one of the seven series coils may be used in any of the FP circuit breakers and FM Fusematic circuit breakers provided the current The trip coils will operate from 630 volts down to 7A volts. Each coil, when energized, releases a spring loaded plunger which trips and locks the circuit breaker in the "TRIP FREE," (Open) position. The plunger(s) which has been released indicates which fuse(s) have blown. They arc reset manually, after replacing the blown fuses, by pulling the plimger(s) out as far as they will go and releasing them. The reset plunger will remain latched in the "OUT" position. The circuit breaker should be thoroughly in spected after every "Blown Fuse" operation and returned to service only after the conditions in part 3 Section I & 11 "Inspection and Installation" have been satisfied. rating does not exceed the maximum continuous current rating of the circuit breaker frame. (IE., 600A, 1600A.] - rti, snwcmssKceo WMrmu. >• . Figure 19 METHOD OF OPERATION A. • Series Coil and Magnet Figure 18 Dual Magnetic Overcurrent Trip Device (TD-1) The current through the series coil provides the magneto pickup setting, and adjustable instantaneou.s tripping. All motive force to energize the magnet assembly. The clapper type armature exerts a force on the push rod which operates the trip unit and trips the circuit breaker. The current rating of the coil and magnet may be changed by moving the pole face assembly up or down. The trip ^stem must be recalibrated after adjusting the magnet devices are factory calibrated and can be field adjusted. pole face. (Figure 18) The dual magnetic overcurrent trip device, in combination with the series coil and magnet, provides inverse long de layed tripping for all overcurrents below the instantaneous Selective Overcurrent Trip Device (TD-2) (Fig. 18) The selective overcurrent trip device, in combination with the series coil and dual armature magnet, provides inverse long delayed tripping for all overcurrents below the short delay pickup setting, and short delayed tripping for ail B. Dual Magnetic Overcurrent Trip Device (TD-1) (Long Time Delay and Instantaneous Trip) The long delay overcurrent trip device consists of a dash overcurrents and faults above the short delay pickup set pot which operates by the positive displacement of a liquid ting. All devices are factory calibrated and can be field through a fixed orifice and an adjustable tension coupling spring which permits the push rod to move rapidly when adjusted. possibility, upon the blowing of one fuse only, that the apparatus, single phased, will burn out. To eliminate this the force from the magnet exceeds a predetermined value. The lever ratio between the push rod and the dash pot is adjustable permitting the time delay to be varied. There are three adjustment bands, identified as minimum, inter mediate and maximum. In addition to the long delay band adjustment there is an adjustable tension spring which danger, Fusematic Air Circuit Breakers incorporate three single phase trip coils, one in parallel with each of the three maximum desired continuous current. This is the long main fuses. delay pickup. It is adjustable from 80 percent to 160 The voltage drop across a blown fuse energizes the single phase trip coil in parallel with it. and 160%. Single Phasing Protection (Fig. 19) (Fusematic) When fuses arc used to protect circuits feeding three phase motors or similar reactive apparatus there is always the prevents motion of the push rod for currents below the percent with calibrated points at 80%, 10(5%, 120%, 140% The tension in the coupling spring determines the current at which the dash pot will be mechanically by-passcd. This is the instantaneous pickup adjustment. The high range instantaneous element has calibrated settings at 7.5, 10 and 15 times the coil and magnet selling. The circuit breakers are shipped with the trip devices in stalled and properly adjusted. It is only necessary to keep the devices reasonably clean. They are lubricated for the life of the circuit breaker and must not be lubricated again. It is possible to remove and replace a trip device in the field. C. Selective Service Trip Device (TD-2) (Long Delay and Short Delay) The selective service trip device is similar to the dual magnetic trip device except that it has a rigid coupling link in place of an instantaneous pickup coupling spring and it has a mechanical escapement timing device which provides a short delay for high values of overcurrents and for faults. The long delay dash pot is identical to that used on the dual magnetic trip device. The short delay device Is operated by a separate armature in the series coil and magnet assembly. It has a pickup adjustment range of 5 to To Remove a Trip Device The trip units which are contained in transparent plastic cases should be removed as units. Remove the two screws which hold the trip unit to the breaker frame. These screws are located in the back of the trip unit and can be removed by reaching in from behind. The connecting rod which connects to the magnet assembly must be slipped off the pin connection at the magnet. The plastic con nector and trip fingerare then removed from the pusii-rod. 10 times the coil and magnet setting. In addition, the short delay has an adjustable band with minimum, intermediate and maximum settinp. To Install a Trip Device Insert the push rod in the proper hole in the front channel and screw the trip unit to the channel uang the two 5/16" hex. nuts provided. Run a special "Dyna-lock" 10-32 nut down the push rod. Follow it with a trip finger on top of the push rod with a spacer between the wings and another MAINTENANCE & ADJUSTMENTS Remove breaker completely from cells before servicing. A. Series Coil and Magnet Assembly The series coil and magnet requires no maintenance other than cleaning periotiicaily to remove dust and dirt which may accumulate on bearinp and pivots of the magnet arm atures. All pivots and bearings are made of nylon and no lubrication is required. The entire series coil and magnet assembly may be remov ed and replaced in the field by removing the %" coil retain ing screws and the ^k" magnet retaining screws at the rear of the pole insulator. When replacing coils, always tighten the coil retaining screws securely. This is important to pre vent overheating and possible failure. Care should be taken not to damage the coil insulation, 10-32 nut. (Do not tighten it yet.) Install the nylon tum-buckle and adjust its length so that it is 1/32" longer than Is just necessary to permit the trip device to reset the magnetic armature against its stop. InstaU the turn buckle on the armature pin and retain it with E-ring provided. Adjust, the position of the trip finger so that the breaker does not trip when the magnet is closed with a 1/32" thick shim in the air gap, and does trip with a 1/64" thick shim in the air gap. Tighten the fingerand check this adjustment ^ain. The trip unit must reset the magnet armature all the way until the armature is against the stop. C. Selective Service Trip Device (TD-2) (Long Delay and Short Delay) The maintenance and adjustment of the selective service trip device is the same as the dual magnetic trip device, except that the trip finger on the short delay push rod is installed under the push rod. Care should be taken to en B. 10 Dual Magnetic Overcurrent Trip Device (TD-1) (Long Delay and Instantaneous Trip) sure that the long delay trip finger on top of its push rod does not interfere with the short delay trip finger which is installed under its push rod. PART 7 WIRING DIAGRAMS DEFINITION OF SYMBOLS Trip coil — 01 A phase fuse trip coil B phase fuse trip coil C phase fuse trip coil Control switch 01 local C1 close BA Bell alarm switch PF Power fuse UV Undervoitage device Closing reiease coil A Anti pump relay B Spring charging motor 0 Main power circuit • A phase Main power circuit - B phase Main power circuit • C phase NO ) Motor cut off switch (Shown with NC I closing mechanism spring discharged) Auxiliary switch contact (open when breaker is open) Auxiiiary switch contact (closed when breaker is open) 5& * TTTT 4 tn! 70 rt w ") <0 M CM CM 4 in to in AUXILIARY CONTACTS 1 — 2 3 — 4 in 11 — 12 13—14 Xa Jo ; \b ZZ 9ie S —6 7 — 8 9 — 10 15 — 16 <24 17 — 18 19-20 21 — 22 23 — 24 SWITCH FUNCTIONS a a b b a b a b a b a b CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT TYPE FP a FM ELECTRICALtV OPERATED A.C.B. SCHEMATIC DIAGRAM FP25 FP50 FM25 FM50 I2C0 140 I 8ASIC ELECTRICAL CONTROL flPt I At AflM I I EXTRA AUXILIARY CONTACTS FP BREAKER OPERATING SEQUENCE 1. Control switch 01-C closed (local close) or remote close via Terminal 1A. 2. "X" coil is energized thru "b" contact of the "Y" relay, "b" contact of the breaker auxiliary switch, and "aa" contact of the motor cut-off switch. 3. Stored energy closing spring released via "X" coil, closing breaker. 4. Closing breaker operates auxiliary switch opening "b" contacts and closing "a" contact thus energizing anti pump "Y" relay and de-energizing "X" coil. 5. "Y" relay remains energized via seal-in contact thus providing anti-pumping lockout of "X" coil if 01 is held closed. C1 6. "Y" relay is de-energized when 01 contact is opened. C1 7. Closing breaker, closes auxiliary switch "a" contacts permitting the breaker to be tripped electrically when control power is switched to auxiliary stabs 5B and 6B. 8. Motor cut-off switch contact "bb" closes when spring discharges and re-opens when spring is fuily charged. 9. Auxiliary switch "b" contact closes when the breaker is tripped. 10. Motor cut-off switch contact "aa" closes when the closing mechanism spring is fully charged. 11. The breaker will close when control switch 01 C1 is closed. 11 PART 8 RECOMMENDED SPARE PARTS No. Reg. FP-25-600 6 3 6 1151-9986 1151-9939 1151-9088 6 li52-9380 6 3 1151-9566 3 No. Reg. 6 3 12 3 FP-50-1600 1151-9986 1151-9937 1151-9354 1152-9354 1151-0632 1151-9566 Description Moving arcing contacts Upper stud assembly Main Stationary contact assembly Leading contacts Cluster assembly Arc Chutes SHUNT CLOSE Mounting Ret. Voltage Assembly No. 48V AC 48V DC nSV AC 125V DC 1151-6038 1152-6038 1153-6038 230V AC 230V OC Drawing 1100-6034 SHUNT TRIP Mounting ng IRef. Voltage Assembly No. 48V AC 48V DC 115V AC 125V DC 230V AC. 250V DC 1151-6039 1152-6039 1153-6039 DrawTflg wTfli 1100-6035 MOTORS TO CHARGE STORED ENERGY MECHANISM Mounting Ref. Voltage 48V AC Assembly No. 48V DC 115V AC 125V OC 230V AC 250V OC 1102-6013 1103-6013 Drawing 1100-6014 1104-6013 UNDER VOLTAGE TRIP DEVICE Mounting Ref. Voltage Assembly No. 115V AC 1I51C6138 115206138 1153C6138 230V AC 480V AC 12 Drawing 1100C6032 Printed in U.S.A. • • • '•v::;f I PART -i.-A -'-i: : .;;:ir GENERAL DESCRIPTION .s .r This instruction manual coveiS the PP75-3000 circuit breaker and FMIOO-3000 fuseraatic breaker. For instructions on the FP50 series breaker, refer to instruction manual IN-810.4. The FP75 line of low voltage power circuit breakers and fusematic breakers ranging from 2000a through 3000A continuous current at -MiS 600 volt ratings, is designed for simplicity of operation, reliability, and easy maintenance. The FP breaker is equipped with a stored energy mechanism whi^ch is mechanically trip-free in any position of the glosing cycle, three unit pole assei^lies, fully field—adjustable timing devices, series trip coiis, and roll-out rails. The three position drawout -V' mechanism is operable with the door closed. The FMlOO-3000 fusematic system consists of two individual drawout devices. The breaker unit is identical to a standard FP75-300G, e for addition of a Single Phasinig Protection trip device. The fuse unit consists of fuses mounted on a breaker drawout truck. Key , .interlocks are provided, which require the breaker to be in th TOST position before the fuse t^ck can be racked in or out. Secondary contacts are provided on both the breaker and fuse truck to allow connection of the Single Phasing Protection device. AA-V:'.-;; • STANDARD ACCESSORIES Maintenance closing handle, 1151-9252 (two required) Cell rackiiig-in <^ank, 1151*-5036 ;/ A Emergency charging handle, 1151-5349 -•k:% •k. . • •k'k :k;-Vv; : AvH'Ar.-.v .'A -T?l -2\ PART II- ^ •' •-: SHIPPING. RECEIVING. HANDLING. AMD STORING 5• '• Vv :• : Each FP breaker and PM fuseniatic is thoroughly inspected and tested before leaving the factory. Breakers are shipped in individual crates. No hooks should be used in handling. Examine all equipment carefully for indication of damage sustained in transit.. If damage , v.^ in transit is indicated, call for an immediate inspection by. the ' delivering carrier. Upon assessment of the damage, a claim should . be filed with the carrier or, depending on the nature of the damage, - ^ an intent to file for concealed damage should be registered. For .! assistance in filing the claim, advise the area sales office of , • Federal Pacific Electric Company, giving a full description of the damage, serial number of the breaker, delivering carrier's name, and, if shipped by rail, the car number, waybill reference, and any other information that might be of help to the Company in aiding in the filing of the dcunage claim. ^ ••• - ..-..•rr--:*?/' When unpacking, make sure that all items are removed from the box:, - . including packing, list, instruction book, maintenance parts, and hardware. Report any shortage immediately. See that identification ^ tags are left on the breaker. Lifting eyelets are furnished for handling. Do not lift or handle breaker by the front box, by the operating handle, or by the .secondary contacts. Clean breaker thoroughly^ cleaner is recommended. 4 To remove dust, an industrial vacuum If the breaker can be installed in its permanent location^ it is eidvisable to do so, even if it is not e:q>ected to be energized for some time. When breakers must be stored.-^ in buildings under construction, be sure they are kept in a spiace i Vl-'.* "J-- ' free of dust, moisture, dirt, and in an upright position. It is recommended that the breaker not be operated prior to final • ->Vr inspection. •i V 1 i .-I"'. /Iv- • " • V' v."' -3- P A R T :-V III TTJSPECTION Aiap INSTALLATION Section 1. Inspection The PP75 breaker consists of a coordinated set of assemblies# mounted on a steel frame, all carefully adjusted and locked in place for long and trouble-free operation. To assist in properly checking and inspecting breakers prior tP placing into seiwice, the following points should be followed in the; jorder. listed.: : 1. Remove arc chutes. 2. Remove covers marked, "REMOVE THIS PLATE FOR EMERGENCY CH^ING;• 5" Using emergency charging handle, 1151-5349, charge each ^ mechanism by rotating the handle clockwise 180 to positive stop*^ ^:^^ 3, Lock safety discharge interlocks to prevent accidental discharge' of stored energy mechanism (Figure 2). Miere is a safety inter].ook on each mechanism. 4. Remove right- and left-hand accelerating springs (Figure 3)•. Insert maintenance closing handles, 1151-9252, as in Figure.4, and slowly operate simultaneously until arcing contacts touch. All arcing contacts should make simultaneously with a permissible variation of 1/32 maximum. Movable arcing contact fingers should ' align with stationary arcing contacts. v.," If misalignment or misadjustments are obsei'ved, refer to part four of this manual, "MAINTENANCE," for'adjusting instructions, rMovable arcing contacts are designed'with side clearances for better guidance inside the arc chutes. A side-to-side movement of 1/8 is v allowable. Close breaker and check overtravel on main contacts. Remove maintenance closing handles and tripl breaker. ; r • •h ' f •• • •" * • ' "'Ji' 6, Replace pull-off springs, 7, Inspect each arc chute to be sure ho plates are damaged. . Replace chutes on breaker. Move contacts in, by hand, and tighten arc chhtes only after contacts move in and out ffeelyi 8. Release discharge safety interlocks (Figure 2). NOTE: To avoid, possible injury, NEVER handle or touch; any movable part of thd '7 breaker when the stored energy mechanism is" charged, without first applying safety interlocks. Operate closing release solenoid manually, with vigor, releasing both stored energy mechanisms simultaneously. Breaker will close. NOTE: T..e Glose button on escutcheon will NOT close breaker unless control power is-connected. Depress red trip lever on escutcheon to Open the breaker. 9. Recharge stored energy mechanisms and close breaker. Slowly move series trip coil magnec (armature) to fully closed positi0n. Breaker should trip before armature- touches pole iface assentblyi Repeat this procedure on all poles. 10. " Check retaining rings and hardware for tightness.. 11. . Basket and finger assembly should be secured and retaining bolts tightened. Contact finger must be free of dirt and foreign, particles. Secondary female contacts mounted on breaker must,. .operate freely. ^ . •:t'\ \ 12. Electrically, the stored energy mechanism is charged by a fractional horsepower ratchet-type A.C./D.C. universal motor. Identification, voltage ranges, and current requirements are specified below. The stored energy mechanism is charged, ^ electrically, in approximately one second. Two motors of^ r :7 identical ratings are used. CHARGING MOTORS FOR FP BREAKERS STORED ENERGY MECHANISM Voltage Ral^incr V F.P.E. Part # Motor , ,48V A.C./4SV D.O. ^ 162-007 ,115V. A.C./125V D.C. 162-004 - FLA. • LRA. 15058 20.0 ^ ;50 14976 6.5 230V A.C./250V D.C. 162-006 ; 14978 6>1 240V maxiraxMa—use control power transformer for higher voltage 25 12 1 life- - -5- Prom wiring diagram supplied with equipment, or from the standard diagram in Part VII of this manual, locate motor terminals on secondary contacts and connect required power source. . Motors will charge when power is applied and automatical!:* shut off when charging cycle is completed. Breaker cannot he closed with the maintenance closing handle unless the stored energy mechanism is charged. On all electrically operated FP breakers, the stored energy mechanism will recharge immediately following a closing operation^—ready for inistant reclosure, 13. if needed. From wiring diagram, locate terminals on secondary contacts and connect proper control power supply and controls for shunt clpse^ and shunt trip attachments. Close and open breaker five times, electrically, and-check for proper operation. 14. Disconnect control power supply. Do not leave breaker in the - charged and/br closed position while in storage. 15. When the FMlOO-SOOO is furnished, check the separate fuse truck,^^ using applicable procedures as listed above. Section 11. Installation ' • ' • • ' • •• •. Before installing breaker in cell, check the following points inside - - • - ' . - •, r' U- ' •' cell: 1. Secondary contact support—make sure all connections are tightened and adjusted to proper dimensions ^ v. • • '•I.e.,' 2. Ground Connections should be tight. 3. Removable extension rails should fit and lock properly in ceil, 4. Breaker wheels should be free and well lubricated. 5. Main contact stabs should be tight and free of dust and dirt. • • . ' . -• -• Z;. / ^ •. '''-wT'.'', '"'nm ' \ . , -• •' • ! •f -6- ;-j;) 6. Check condition of insulating transite plate in roof of *_ase. Screws should, be tight. 7. 8. . Remove control power fuses. Place breaker on installed extension rails. Make sure ^11 four wheels are in rail grooves. 9, ^ Drawout mechanism on breaker should be in OUT position. 10. While depressing trip lever, push breaker inside the cell until racking-in cfaijcs engage a positive stop. This is the OUT position. Remove rail extensions and store in cell. 11. Close door slowly and latch; make sure that the metal mask which; is provided on the-outside of front box moves freeily back as it comes in contact with the door. The door should close all the - way with the breaker in the OUT position. 12. v.''/, Depress trip lever and insert racking-in crank, il5lC5036 (Figure 5). position. Rotate crank clockwise until breaker reaches TEST At this point, interlock bar will drop into slpt on cell floor when racking-in crank is removed. This locks breaker in TEST position and releases trip interlock. 13. Install control power fuses; circuit is now energized. •V%(• The motors will charge the stored energy mechamisras, and closing and-; tripping control circuits become energized; in the TEST position 14. Open door and imake sure that grounding contact in cell is nov^ contact with the; breaker. 'V.'.f Close door and check breaker electrically for proper closing and opening operation. •iSiV .-,.a If breaker operates properly, rack breaker back to OUT positionand leave there until ready to put into service. • 15. • When" putting into service, insert racking-in handle, rotate clockwise until breaker is in OPERATE position. When properly racked in, the interlock bar will be free to drop into another slot, locking the breaker in position. The trip interlock will be released and the interlock bar will drop when the racking-in crank i s removed. , •• kimmi -7- 16. When the FMlOO-3000 is furnished, the points listed above, relative to cell, stationary contacts, contact stabs, and racking-in assembly, should also be checked on the fuse truck. Note that ai trip interlock is hot furnished-on the fuse truck* Fuse truck has two positions only--"IN" and "OUT." Positi.ve stops in the gear train determine proper location of the breaker f ^ in both the "IN" and "OUT" positions. PA R T IV MAINTENANCE The breakers and all component parts have been tested extensively for performance, per NiSMA Standards SG.3-3-17 and SG. 3-3-18, and have '. proved to be satisfactory with a wide margin of safety. ; In accordance with KEMA Standard SG.3, Part 6, a periodic maintenance^ ^^ , ^ -1 ^ j schedule should be established. .i.— j-i__ —: i For the convenience of the user, a • N . •>;! simple log sheet is provided with every breaker to ensure proper maintenance and years of trouble-free operation. It should be kejpt . r and followed conscientiously, especially in cases where breakers are required to operate under more adverse conditions; , The following instructions and adjustments should be followed . , ' i.-; ... carefully: Main and Arcing Contacts Adjustment "A" - Main contact press "B" - Overtravel mains 25-35 pounds, measured at point of contact 1/8-1/32 •r'm -8- "C" - Arcing contact press 22-25 pounds, measured at a point 1-1/4 below tip' of • •'' contact "D" - Gap (distance) between mains when arcing contacts touch '• ' v 1/8-1/32 . ' ' life"!''' . z. ; , • ' • . • ^ CHECK POINTS (Figures 6 and 7) 1. Stationary arcing contacts—make sure that retaining screws and contacts are tight. 2. Main contaqtS should be cleari and free. ; 3. Make sure all retaining rings are in place. 4. Make sure nylon spacer is in place. 5. Roller, 1101-9231, must roll free oh its pivot pin. 6. Surfaces marked "P" should be lubricated by a thin film-of; : "Conducto-Lube," No. 240-200, before assembly. Contacts must be inspected after every known short circuit interruption and also should be inspected at regular inspection periods. If contacts are. found to be worn or excessively pitted, they,. should be dressed or replaced. ' CAUTION; When reinstalling the arc chutes, adjust the retaining serw,,;^^|^ holder on the ard chute retaining bar so that the arcing cpntadts do not come in contact with the arc chute baffles. A; : TO CONTACT ASSEMBLY To repair or replace movable arcing contacts, proceed as follows (Figure 6).: 1. Charge Stored energy mechanism and lock discharge safety ^ ^ interlock (Figure 2). ' / W p. -9- -;,:''-V- 2. Remove arc chutes. 3. Remove arc chute retaining bar. , •; 4. Remove insulating block and push fork assembly. 5. Tighten movable arcing contact's adjusting screw until springs are solid, and remove retaining pins. 6. Remove arcing contact pivot pin and replace movable arcing contacts. Both contacts should be replaced at one time. i'"' 7. Make sure nylon bushings are in place and' in good condicion while r'.' replacing movable arcing contact. 'TV Reassemble, following the same sequence of operations, and adjust per Figures 6 and 7. Inmost cases, i t is not necessary to replace contacts, but occasional redressing and readjusting are recoramehded. To replace stationary arcing contacts (Figure 6), remove unit pole assembly, replace main stud and arcing contact assembly, 1151-5023. r;''; ' n Adjust contacts per Figures 6, 7, and 8. • ' STORED ENERGY MECHANISM Check latch engagements and adjust, if necessary, by moving safety discharge interlock (Figure 2) to proper position. Make sure springs are in place and in good condition. is free and well lubricated. retaining rings are in place. To check the alarm switch attachment, trip breaker With trip button, then with shunt trip. actuated. In both cases, the switchl should not be Trip brewer by moving the series trip, coil magnet; the switch should operate. . MM- 50 230 ' 60 80 115 250 30 0.45 0,5 D 0 125 50 2.0 2.5 ; 230 250 Inductive BREAK 115 125 A.C. . . .V '• • .-V>, f: • • t ; -13- P A R T V I OVERCURRENT TRIP DEVICES GENERAL DESCRIPTION The direct acting series coils and magnet assemblies provide the energy to operate the overcurrent time delay device and to trip the circuit breaker, thus, interrupting sustained overcurrents and faults., Each magnet is adjusted at the factory and calibrated for either > 2000 to 2500 ampexres, or 3000 amperes. • n!, DUAL MAGNETIC OVERCURRENT TRIP DEVICE (TD-1) (Figure 13) The dual magnetic overcurrent.trip device, in combination with the. series coil and dual armature, magnet, provides inverse, long delayed tripping for all overcurrents below the instantaneous pick-up setting and the adjustable instantaneous tripping. All devices are factory calibrated and can be adjusted in the field. SELECTIVE OVERCURRENT TRIP DEVICE (TD-2) . 0k . (Figure 13) The selective overcurrent trip device, in combination with the series coil and dual armature magnet, provides inverse, long delayed tripping , ' for all overcurrents below the short delay pick-up setting, and provides short delayed tripping for all overcurrents and faults above the short delay pick-up setting. All devices are factory calibrated and cain'be'/adjusted'dn the field.. •'.''--'-''0^^ , . , 'r- ' ' -14- SINGLE PHASING PROTECTION \ V When fuses are used-to protect circuits feeding three phase motors or similar reactive apparatus, there is always the possibility, upon the blowing of one fuse only, that the apparatus, single phased, will burn out. To eliminate this danger, fusematic air circuit breakers incorporate three single phase trip coils, one in parallel with each of the three main fuses. Each trip coil is approximately a one thousand-turn coil, wound to operate down to 1/10 Of line voltage. - Each of the single phase trip coils can be looked upon as a shunit' tri^, / ' continuously energized by the voltage drop across its fuse. Under normal conditions, the "fuse drop" voltage is zero, but it immediately , ;^ rises to a value of full phase voltage—when the load fuse blows.. This energizes the single phase trip coil, causing the common trip bar to unlatch and trip the fusematic air circuit breeker. The coil is specifically rated at 1/10 line voltage to assure instantaneous : // operation, even vAien the fusematic air circuit breaker is used as a motor starter. In this case, although the back E.M.F. induced in the motor winding is equal to phase voltage, because of phase angle :r/^; V; - displacement, the resultant voltage drop across the fuse i^Sufficient^^. to trip the fusematic air circuix. breaker. ' , = ' ".ll •' ' I METHOD OF OPERATION A. Series Magnet , .; v The current through the circuit;_breaker pole provides the magnetomotive force to energize the magnet assembly. : - The^i- clapper-type armature exerts the force on the push rod whi^ operates the trip unit and trips the circuit breaker. ' ^ "1 V '-5 ' i'' f >. -15- B. Dual Magnetic Overcurrent Trip Device (TD-1) (Long Time Delay and Instantaneous Trip) .... The long delay overcurrent trip device conLsists of a dash pot which operates by the positive displacement of a liquid through i ' / a fixed orifice, and an adjustable tension coupling^ spring whibh i^^t^^t^^r permits the push rod to move rapidly when the force from the magnet exceeds a predetermined value. The lever ratio between the' push rod and the dash pot is adjustable, permitting the time delay to be varied. bands. There are three calibrated positions or adjustment ;i ^ The three bands are identified as minimum, intermediate)^ ^ and maximum. In addition to the long delay band adjustment, there is an adjustable tension spring which prevents motion of the push^^\^^^^^ rod for currents below the maximum desired continuous currents ' v This is the long delay pick-up. It is adjustable from 80%i tb 160%, with calibrated points at 80%, 100%, 120% 140%, -and 160%, The tension in the coupling spring determines the current at > which the dash pot will be mechanically by passed. This is the instantaneous pick-up adjustment. ,The, instantaneous element has a meiximvim setting of twelve. C. Selective Service Trip Device '(TD-2) (Long Delay and Short Delay) The selective service trip device is similar to the dual magnetic trip device, except that it has a rigid coupling-link in place of an instantaneous pick-up coupling spring, and it has a mechanical escapement timing device which provides a short delay for' high, values of overcurrents and for faults. The long delay dash pot is" identical to that used on the dual magnetic trip device. The short delayjdevice is operated by a separate armature in the series magnet assen&ly. It has an adjustable pick-up spring with calibrated settings at 5, 7.5, and 10 times the boil and ihagnet setting. 'im. In addition, the short delay has a band adjustment withj calibrated points for the minimum, intermediate^ and maximimi bandb^/§>f2 ' • • •• ' -16- MAINTENANCE & ADJUSTMENTS '.t • REMOVE BREAS^R COMPLETELY FROM CELLS BEFORE SERVICING. A. Series coil and Magnet Assembly seriest magnet requires no maintenance other than cleaning; periodically, to remove dust and dirt which may accumulate on hearings and pivots of the magnet armatures. All pivots and hearings are made of nylon, and no lubrication is required. B. Dual Magnetic Overcurrent Trip Device (TD-1) Instantaneous Trip) •., I (Long Delay and The circuit hreakers are shipped with the trip devices installed and properly adjusted. It is only necessary to keep rhe devices reasonably clean. They are lubricated for thd life of the circuit. 5 >•' '•f-' breaker and must not be lubricated again. C, Selective Service Trip Device (TD-2) (Long Delay and Short Delay) The maintenance and adjustment of the selective service trip '•r : \ • device is the same as for the dual magnetic trip device. D. Series trip.units must be recalibrated, on the circuit breaker, if they are removed or replaced in the field. The factory should be contacted if the series trip units require servicittg. v' i: VY'"' r .» ' • '.wAfc''. ' • ,. V,i* *... i.'v,'*." •17^ mfST 7 ,. Trip coll TC , A phase fuse trip coll T : ^ ^ i ;I; B. phase fuse trip coll :• .r j [ TCI T02 '•} \ TC3 iVf.! .?•{ -ifirx •.1 I — 01 close Bell alarm switch 1V . •• r ^ . i ' Power fuse PF VA C phase fuse trip coll '• Closing release coil 01 local Control switch . V ; V" ' » I f'ii —Undervoltage device — ivK'. Main power circuit • A phase /.i?;,:Hk f' AntI pump relay SI•j. •^;. Spring charging motor U »u •;i.; MC/aa i DEFiMm©?^ ©F' SVaViBOLS' V }.•';/]• 01 — NO ). Motor cut off switch tSnown with NO ) closing mechanism spring discharged) i MC/bb :— 1.' Auxiliary ^Kch contact (open when breaker is open) r-a Auxlliaty ^Itdi contact (closed when breaker is open) ^;.b A A A lA^ «e$ A S S a S A 'S S % "V •• •! \ -.''Srvw • I' M9 C9$ 785 M5 '-|NS*I»< teMIRtinlllfl wi v;v\ ii'lrnrr * I IS «k M M Bk AUXILIARY CONTACTS I ,is ,» ,iT t"r& f. » ab » n M «»,. • :» ::« ;i . i SWITCH ruwcTiONt ctosi CAAI.T CI.OM • ^• • AAoorva moea.ntce. tAIItT 5>-B« ' M Vie ' 19 ' M' ' kl"< M MIS OXB nis t u i r »«lll,T BBCO -HIV' I aowt Wlro 19eaWWov ' • ra89.wlr.: JS. "'B «">»« f :• npg ppara 2Leem«Auv i IV 'I S I 9] eOLMJUKi •' i! )f; ; 'Mm OJCTRiCH eoimtoi !i tScafiovn^'Cxriu mixiuAnrcoirmcn! 3 I . • „ . .. OPCRoms ox-a scifzmnc otaeaAQ .••• i'i • Btri i aC' itot(l anVA M, •• I ne > ae< • •• **-*- * , • •;! ";\V>sJi, .; "fff.ftfW. • 1 = .»• :• caatT c t o g SE. . »t •• BIB ortn' mo OBIN I. v:- ,1 FP BREAKER OPERATINGT SEQUENCE • r.; '«*; r. • "t'^ri IT•(I't f fr.. : . ! '• i--«A. Control swItch. Ol'C closed. "X" coil Is energized thru "b" contact of the "V" relay, "b" contact of the breaker awtlliary switch, and "aa" contact of the motor ciit'Off switch. : Il\ '•-•iM '45^. :;'^ •;i -1 : .w > i.t.; 1.-. »• > ' v •• 1 '0 • jv 3- Stored energy closing spring released w'a "X" coil, closing breaker. ;:i 4. Closing breaker operates auxiliary switch opening "b" contacts and closing "a" contact i anil pump."Y" relay and de-energizing "X" coll. r t / t n u sthus . e nenergizing erf "Y'Vrelay relay remains energized via seal-In contact thus providing antl-pumping loclwut of ;; 'X'^coll'if—ls'held closed. S' ? •-'x"^oii"i - 6:'"Y" relay Is de^energized when-^contact Is opened. » spring is fully charged. 9^ Auxiliary switch "b" contact closes when the breaker is tripped V AA'- y] -i; -18- •: -f;V P A R T V.1P VIII I.'.'•«*»•••; MINIMUM RECOMMENDED SPARE PARTS FP75-3000 & FMlOO-3QqO BREAKERS Description Required P a r t No 2. • • Moving arcing, contacts Upper stud assembly Main stationary contact assembly Leading contactis ; Cluster assembly Arc chutes 12 ' 1151A9986 3 1151B5023 24 1151A9354 6 1152A9354 1151B1024 1151D9566 6* 6 t:;. /•'tsm *12 required for EMlOO-3000 breaker SHUNT CLOSE ATTACHMENTS (common for all PP breakers) - 480 volts A.C., 60 cycles 115 volts A.C., 60 cycles 230 volts A.Cw# 60 cycles 48 volts D.C. 125 volts D.C. 250 volts D.C. 1151B5359 1152B5359 115385359 1151B5359 1152B5359 115385359 SHUNT TRIP ATTACHMENTS (common for all FP breakers) . - 48 volts A.C., 60 cycles 115 volts A.C., 60 cycles 230 volts A.C., 60 cycles V. t;,- .!4 1151A5326 1152A5326 1153A5326 48 volts D.C. 1151A532S; 125 volts D.C. 1152A5326 250 volts D.C. 1153A5325 : • .I'V4 'V • • -r^W'V fe-l W-i ' !• -19-, RECOMMENDED SPARE PARTS (continued) UNDERVOLTAGE ATTACHMENT (common for all FP breakers) Description Part Numbers delayed instantaneous 115 volts A.C. 230 volts A.C. 1151-9458 1151-9456 1152-9458 1152-9456 450 volts A.C. 575 voltsA.C. 1153-9458 1153-9456 1154-9458 1154-9456 125 volts D.C. 1155-9458 1155-9456 250 volts D.C. 1156-9458 1156-9456 MOTORS TO CHARGE FP BREAKER STORED ENERGY MECHANISM (common for all PP breakers) Description Note: Part No. Motor FLA. LRA. Two motors of specified voltage required for FP75-3000 48V A.C./48V D.C. 115V A.C./125V D.C. 230V A.C./250V D.C. 162-00/ 15058 20.0 162-004 14976 6.5 162-006 14978 6.1 50 . 25 12 Maximum 240V, use control power transformer for higher voltages, P a r t No. Emergency manual charging handle Maintenance closing handle 1151-9252 Drawout crank 1151C5036 1151C5349 Subject: FP-50 Breaker - Revision of Retrofit {using E. Pgh. Actuator) The original procedure to retrofit an FP-50 was to use the Beaver Flux transfer trip. But experience has shown that the Flux transfer trip would cause the breaker to trip free. When the breaker is closing, mechanical shock would release the Flux transfer, causing the trip free condition. To eliminate this problem, an E. Pgh. actuator is used instead of the Flux trip. The bracket for the E. Pgh. actuator is shown in Figure #1. The bracket is mounted using the same three holes as the original trip unit used. The two additional holes to hold bracket in place are shown in Figure #1 drawing of mounting bracket. To trip the breaker, remove the aluminum paddle on trip bar on the right side of the breaker. Remount the tripping paddle on the trip bar to the left, approximately 1 9/16" from center of original hole, and drill a hole in tripping bar to keep paddle from moving. The hole size is equal to a §29 drill bit. The paddle is just inside bracket that holds tripping bar to the frame of breaker. When mounting this tripping paddle to trip bar, it is best to charge the stored energy mechanism to insure that the trip paddle is mounted correctly. This is done because when the stored energy mechanism is being charged the trip bar moves forward a little. If this procedure is not followed, the breaker will trip free due to the movement of trip bar (Figure #2). To reset the E. Pgh. actuator, use the indicating assembly located just behind the stored energy mechanism on the right-hand side of breaker (Figure §3). The reset arm on actuator may have to be bent to get the correct position to reset the actuator. Before mounting amptector to frame of breaker, remove the A Phase tripping paddle and the counter-weight which is right next to A Phase 2 - tripping paddle. The counter-weight is placed in a downward position so it does not interfere with amptector as shown in Picture # . The next step is to hacksaw a little piece of metal off the racking bar which is also shown in Picture # to accept amptector. If this piece of metal is not cut off, amptector will not sit in a vertical position. not harm breaker at all. This will After above procedure is completed, take a piece of Micarta to mount amptector. Place it to the piece of metal, which is bolted underneath the stored energy mechanism on the left-hand side of mechanism. Drill two holes to hold the piece of Micarta to frame. take piece of Micarta off and countersink the two holes. Then The next step is to drill three more holes in the Micarta to match the three holes on the brackets of the Beaver amptector. Mount the Micarta piece to the frame first and then mount the Beaver amptector to the Micarta piece (Figure #4). Pershing Road Breaker Lab - Chicago FP-50 RETROFIT (FIGURE Jl) Actuator Mounting ^'/yTo Center L -of Hole ^ / ^•e X d r- 5liN> SIDE VIEW h NOTE: V (FIGURE #1) Use same holes thatv mount trip unit. Use 1/6" metal FP-5Q RETROFIT Trip Paddle Mounting (FIGURE #2) vti—^ FRONT VIEW ACTUATOR' r>i TRIP PADDLE SIDE VIEW NOTE: Actuator tripping lever must be bent in a downward position. When stored energy mechanism is charged, trip bar and paddle move toward actuator. (FIGURE #2) FP-50 RETROFIT Reset Arm (FIGURE #3) INDIGATING ASSEMBLY ACTUATOR (FIGURE #3) FP-50 RETROFIT Amptector Mounting 4 (FIGURE #4) v%- <- o C' G o 7 o » G 1-^ e Ci iiy 0 0 0 vj y 0 o CSQ -<- 0 V O 0 © /1 ^ 0 L V. / ; 0 0 0 o 0 /^'Ah NOTE: (FIGURE H) Use 1/16" Micarta. \ REDERAL. PACIRIC ELECTRIC OR CANADA VANCOUVER Ff^E TYPE H AIR CIRCUIT BREAKERS MAINTENANCE INSTRUCTIONS I r FOR ^ TYPE H AIR CIRCUIT BREAKERS ^ LIST OF CONTENTS item no. DESCRIPTION PAGE NO. 1 2 Introduction Shipment 3 3 3 Storage Unpacking Location Mounting Connections 3 3 3 3 3 4 5 6 7 8 I t: Ifjr.,- 9 10 n 12 13 14 15 16 17 18 19 Inspection Closing the breaker Maintenance Removing the faceplate Stored energy mechanism Spring mechanism Spring release mechanism Motor mechanism Breaker mechanism Adjustments Overload relays Main contacts i; a * " 4 4 6 6 6 6 7 3 9 JO ]] . A- f' | 20 Hood ]] (• 21 Arc chutes ]] j 22 23 Arcing contocts Drawout circuit breakers Spare parts ]] 13 f f I5 ; 24 TYPE H AIR CIRCUIT BREAKERS INTRODUCTION FPE Type H low voltage power circuit breakers are designed to provide many years of reliable service even under severe conditions. The mecha nism design employs high throw-off toggles to ensure tripping even after long periods of inacti vity. Current carrying parts are designed for low current densities and the extremely efficient trip ping relays do not require high current density coils thus realizing a low temperature rise even when the circuit breaker is loaded to its full rating. FF^E LOCATION Unless the circuit breaker enclosure is specifi cally designed for outdoor or unusual service con-, ditions, circuit breakers should be installed in a clean dry place which is free from atmospheric contaminants and where good ventilation con be secured. Sufficient space shduld be provided to moke connections and so that the breaker is read ily accessible for operation and maintenance. Re ference should be mode to local code regulations. MOUNTING Normal maintenance and replacement of ore con trol parts can be mode without special tools or resetting factory adjustments and thus maintenance shut down periods can be very short. Circuit breakers should be enclosed in sheet steel coses in accordance with recommended dimensions SHIPMENT bolts through the base, (Frame size 2 & 3 use 'V bolts), while drowout type breakers will roll in or and in general these cases provide the mounting for the breaker. Fixed mounted breakers ore mounted with-4-3/8" Eoch circuit breaker is carefully inspected and tested before leaving the factory and then packed by workmen experienced in the proper handling ond packing of electrical equipment. Every circuit breaker should be examined immediately on receipt for any damage sustained enroute. If damage is evident or if indication of rough handling is visi ble, 0 claim should be filed immediately with the transportation company. FPE should be notified immediately if replacement parts are required. out on roils which ore fixed to the enclosure. A worm and nut assembly is used to pull the breaker either on or off the disconnecting contacts. The mounting support should be a rigid structure able to withstand the impact of breaker closing and tripping. CONNECTIONS Before making any electrical connections to the circuit breaker, every precaution must be taken to ensure that all cables which are to be connected STORAGE Air circuit breakers should be stored in their ship ping crates in the upright position in a clean dry area. Should the breaker get wet it must be thor oughly dried out using forced worm air over an extended period until "infinite" readings ore obtained using a 600 volt megger. UNPACKING Crates used for domestic shipment of air circuit breakers ore of open lattice work construction so that the breaker may be readily uncroted without damage. The breaker is bolted into the crate using its normal mounting holes so it is preferable to first remove top, front and sides of the crate. The breaker may then be unbolted and removed from the remaining crate. Do not lift the breaker by the reor connecting terminals or the operating handle. Lift on the steel channel at the front and hold the base to keep the breaker steady. The steel side plates will support the breaker but core should be taken to set the breaker on a level surface to avoid da mage to the relays or the interlock linkage on draw out type breakers. Check the breaker thoroughly to see that no ports ofthe breaker hove been damaged or forced out of alignment during shipment. to the circuit breaker are safely de-energized. Breaker terminals are silver plated for maximum joint efficiency and cable connectors should be clean and free from dents or burns and bolted se curely to the breaker terminals. Poor joints lead to breaker overheating and subsequent contact deterioration and eventual breaker failure so that considerable care should be exercised in making these primary connections. Cables or bus connections should be properly sup ported so that the circuit breaker terminals are not subjected to unnecessary weight or strain. Any strain which at first has no apparent affect, may cause poar contact alignment after prolonged peri ods of vibration or shock from normal breaker opera tions. Meter shunts, resistors and similar devices which operate at relatively high temperatures should be mounted far enough away from the circuit breaker so that they do not contribute to breaker heating. Control circuit wiring where applicable should be made in strict accordance with detailed wiring diagrams. Wiring connections are made to terminal blocks or to secondary drawout contacts and should be run in a supported and protected manner such that control wires cannot come into contact with primary connections. type h air circuit breakers CLOSING THE BREAKER ceeding with inspection. completely before pro fhoJld the breaker U'^?^®"9hly checkedwhen and itoperated to ensore trouble free operation is placed in sforedthe energy as opposed to spring assisted closing, en«qy tore the breaker con be closed. manual CLOSING The handle is rotated counter-clockwise to the up1. Make visible inspection after installotion to fS:;'"9will charging cam. then comp ensure no parts have been damaged or forced ptating the handle through 180" out of alignment. l'^ letely chorge the springs. A rochet mechanism allows severol short strokes instead of one 180° 2. peck door interlock lever (see page 5) for single stroke if preferred and also prevents any freedom of movement ond block in depressed spring fly back during the charging stroke. The position. This Will allow normal breaker opera- springs con be charged when the breaker is closed tion With the door open. 3. On drowout breakers check the drowout mecha nism to see that the breaker rolls freely on the which will alowone immediate reclosure. Pressing a mechanical push button on the face plate releases breaker®^ compression springs to close the L 1 completely ®"9oges thethe nutcon and pulls .L the breaker home on tact. There should be approximotely 1/8" clear ELECTRICAL CLOSING ance between the mole stab and the contact A universal ac/dc 120 volt '4 H.P. motor is used tinger spacer. to wind the spring closing mechanism and a shunt 4. On drowout breakers check the drowout inter- close releases the stored energy to close the break l^ock. The interlock should be free with the er. Upon supplying control power with the breaker open, the motor will automatically charge the Spring (time 2-4 seconds). Pressing a close button breaker as it moves from either position. ®' *ii then close theP'breaker. ®^® ®'' When ®remote location will the breaker is 5. peck contacts to see that they ore clean and tripped the motor will immediately rewind the mechtree of foreign material. breaker fully engaged or in the test position but should ride up on the wedge to trip the 6. peck ony control wiring to ensure it has not been damaged during installation. 7. Check overload relays. Push on armature to en sure that the relay will trip the breaker. If mo derate force is used the relay armature will move slowly because of the delay characteris tics. A heavier force will extend the instantaneous springs and should trip the breaker immediately. Note that a small amount of oil seepage may occur during shipment if the breaker has not been in the upright position but the relay de sign emplays sufficient cavities to trap ample amounts of oil for relay operation. 5. Close and trip the breaker several times to ensure correct operations. Note that interlocks should be voided or in normal released position so that the spring closing mechanism will pick up the contacts and thus avoid discharging the mechanism without its normal load. Dis- charging the spring closing mechanism without load 'niposes severe stresses on the linkage and should be avoided. onism to charge the spring ready for the next close operation. An emergency closing handle is supplied which can be used in the event of control power failure. Ihe handle is inserted into the faceplate connect ion and is used in the same manner as for manual closing to store the energy in the spring. To close the breaker insert the opposite end of the handle in the small hole to the lower right as illustrated figure 1, page5 . ' MAINTENANCE The breakers have been manufactured and tested in accordance with NEMA standards SG-3 and to ensure the safety and the successful functioning of connected apparatus which depends upon the proper operation of the circuit breaker, the circuit breaker must have regular, systematic care and inspection. The following points require special attention: 1. Be sure that the circuit breaker and its mech anism are disconnected from allelectric power, both high voltage and control circuit: also be sure that the main closing spring is discharged before being inspected or repaired. 0 - v.. TYPE H AIR CIRCUIT BREAKERS 2. Inspect the operoting mechanism periodically and keep it cleon. 3. Exomine the contocts frequently, see that they ore oMgned and that contact surfoces bear with firm uniform pressure. Replace badly pitted or burned contacts before they are burned away sufficiently to cause damage to other parts of the apporotus. 4. The contact members of all types of discon necting or interrupting devices must be kept clean ond bright to insure maximum operating efficiency, it has been found by experience that operoting the circuit breoker several times at intervals of not over two weeks will remove the effects of oxidation ond materially prolong the effective life of the circuit breaker. It is recommended that this practice be followed except that a circuit breaker which is operated every few days will not require much attention. 5. See that bolts, nuts, washer, clips and oil ter minal connections are in place and tight. 6. Clean the circuit breoker at regular intervals where obnormal conditions sucn os salt de posits, cement dust or acid fumes prevoil to avoid flashovers as a result of the accumulation of foreign substances on the surface of the circuit breaker. 7. Always check for loose nuts and bolts after any mointenonce work has bee'n completed. CIRCUIT BREAKER FACEPLATE 'M. Figure la Figure lb MANUAL 1. Front Plate 2. Frome 3. Floating Trim 4. Manual Trip 5. On-Off indicotor ELECTRICAL 6. Spring chorge indicator 7. Door Interlock lever 8. Rating plate 9. Close button 10. Emergency close handle 11. Emergency spring chorge 12. Emergency manual close 13. Local close button 14. Motor cut off switch type h air circuit breakers REMOVING THE FACEPLATE With the front plate and frame removed the complete mechanism is exposed and inspectian and lubUMhe front plote, (2)the frome and (3) the fiooting ncatian of moving ports is readily accomplished. trim end it is mounted to the cross channel of the consists of three ports: Use o very light good quality machine grease such OS lubroplateon the rochet assembly. Alight moch- mechanism bracket. To disassemble, first remove the 4 oval heod be^opplied" where grease cannot ing the front plate turn it to the left so it will slip SPRING MECHANISM over the trip lever (4). The floating trim will The spring mechanism is located in the steel cross then be free to be removed. Note that one side of channel and consists of seven parts (See fig. 2). the trim is bevelled to correspond with the hinging ot the front cover and it must be reploced correct The spring is charged by turning the crank approx screws in eoch corner of the front plote. In remov imately 180° in a clockwise direction. The rochet ly to ensure smooth action os the door closes and holding panel prevents ony flyback during the over the faceplate. The monuol handle is coptive in the front plate and moy be removed by drawing out the %" rolpin charging stroke. The spring in the charged position IS 10° over toggle and is held by a needle bearina com. " holding the clutch to the shaft (See fig. 2). SPRING RELEASE MECHANISM STORED ENERGY MECHANISM Before close inspection of the stored energy mech- The spring release mechanism is located behind onism extreme core should be taken to ensure the the frontplote and below the holding cam assembly nncc NOT dischorgeTripping the circuit breakers DOES the spring. On electrically When the spring is fully charged the needle bearing discharge the spring. spring mechanism. and consists of 5 ports (see Fig. 3). ot the holding cam assembly is stopped by the be used to prevent the motor from recharging the ground steel cam (8). When the manual close button spring automatically. If the face plate indicotor IS pressed or when the shunt close is actuated, snows CHARGED" closing the breaker will the cam is rotated which releases the charged' operated breakers the motor cut off switch must r\ 'bracket-croBs channel PLAN VIEW FRONT ELEVATION (crank and eprhg In chorged position) (monuol spring charging hondle ossembly) 13. Handle 14. Clutch 15. Rolpin (ratchet end holding powl In charged position) Figure 2 - Spring Mechanism 1. Main spring 2. Spring guide 3. Crank 4. Rochet 5. Holding pawl 6. Holding cover 7. Holding pawl spring »• FP^E TYPE H AIR CIRCUIT BREAKERS 1 m Figure 3a SPRING RELEASE MECHANISM Manual Mechonism —Sprinq " a Charqed _ Figure 3b Pl=-.. ji l • c • Discharged n- l j tiecfncal Mechonism - Spring 8. Ground steel cam 9. Two set screws 11. Shunt close (when used) 1 2. Return spring 10. Manual close button (when used) 13. Micro Limit Switch MOTOR MECHANISM The motor mechanism consists of a '4 h.p. univers al motor with a worm gear reduction. An eccentric lever is mounted on the end of the worm gear redution and drives the osci Hating lever. The driving pawl is mounted on the oscillating lever and with embly from the breoker.The eccentric driving lever is threoded onto the end of the worm gear reduction of the motor. Tap lightly in a counter clockwise eoch stroke of the lever drives the ratchet around the limit switch is actuated to cut off the motor. A spRciol greose is used in the worm gear reduct ion assembly and should not require replacement. If necessary use only Led-Plate compound 250. To remo-e the motor mechanism, remove the two The following table lists the stondard ratings of '4 - 20 Allen Head screws inside the steel cross channel (see Fig.4). Tilt the motor in to disengage motors. Note thot for a.c. applicotions 115 volt motor is used throughout ond a control tronsformer it from the oscilloting lever and remove the ass- is supplied for voltages other than 115V. one tooth at a time until the spring is charged and RATED CLOSING CONTROL VOLTAGE VOLTAGE RANGE MAXIMUM MOTOR CURRENT AMPS 48V dc 125V dc 250V dc llSVoc direction to remove the eccentric and then remove the motor mounting bolts. SHUNT CLOSE AMPS TRIPPING VOLTAGE RANGE VOLTS 28-60 90 - 130 180 - 260 95 - 70 - 140 140 - 280 125 230V Qc 460V oc 190 - 250 Inrush 12 380 - 500 Full load 6 575V QC 475 - 630 95 - 125 190 - 250 380 - 500 475 - 630 SHUNT TRIP AMPS PF^E type h air circuit breakers cross I channel ^ I I • J ®— lever plunger micro switch 1. Driving pawl 2. Oscillating lever 3. Motor assembly 4. Shunt close 5. Motor limit switch Electrically operated breakers use a motor to rotate the cronk and fully charge the spring. Figure 4— Motor Mechanism BREAKER MECHANISM The breaker mechanism is attached to the spring closing mechanism by means of a closing cronk (1) connected to on eccentric link (2) which pivots on a uni-ball (3). See figure 5(a) The breaker is closed by rotating the closing crank cam backwards which releases the latch bearing allowing the linkage to collapse. When the breaker is open and the spring charged ready for closing, the latch bearing will have a clearance of 1/64" to 1/16" above the ground steel cam. Figure 5 (b). clockwise through approximately 180°. As the crank starts to move the linkage is prevented from If there is notsufficient clearance between the cam and the latch bearing the cam cannot return to its the ground steel cam (5). As the crank continues one attempt, the vibration may assist the cam to its proper location and the breaker will then close. collapsing by the latch bearing (4) resting against to rotate the pin (6) is pushed by the closing cast ing (7)up to the stops (8) located on the mechanism side plates. See Figure 5 (o). The breaker is tripped by rotating the ground steel proper position and the breaker will not latch. After If the clearance is excessive, the lotch bearing may bounce off the ground steel cam and the break er will not close. TYPE H AIR CIRCUIT BREAKERS Ff^E ADJUSTMENTS During the course of manufacture each circuit breaker is operated up to 50 times. All adjustments are set and locked and should not require adjust ment in the field. However should the breaker fail to operate correctly the following adjustments can be made. 7/ 1. Latch Adjustment (See Fig. 6) Figure 5(o) When the breaker fails to latch the spring mech anism discharges without carrying the contact assembly to the closed position. Without the in ertia of the contact assembly to absorb the energy from the closing spring, severe stress is imposed on the closing mechanism and damage will result if this process is repeated. To adjust the latch first loosen the lock screw (9). Turn the adjusting screw (10) counter-clockwise two or three turns to ensure proper latching. Close the breaker and then turn the adjusting screw clock wise slowly until the breaker trips. Then turn the adjusting screw back counter-clockwise one and one quarter turn and lock with lockscrew (9). If the breaker is subjected to severe vibration which results in nuisance tripping more latch travel is needed and one and a half turns can be used. 2. Holding Cam If the holding cam does not reset properly it may be jarred when the closing spring is charged, the breaker will attempt to close as the closing spring is charged without pressing the close button or operating the shunt close device. Figure 5b Referring to the spring mechonism shown in Figure 3, adjustments can be made as follows and should be tried one at a time. 1. The return spring (12) may require sHghtly more pressure. Bend the toil of the spring a little to increase the pressure. 2. The motor limit switch is operated by the hold ing com and it may prevent the cam from return ing against the top stop screw. Bend the operat ing lever of the limit switch to overcome this. To adjust the holding cam itself releose the lock nut on the top screw and turn counter clockwise one quarter of a turn and relack. This increases the loading on the cam and it is important that the adjustment be made care Figure 6 fully to ensure that the resultant load will not be too heavy for the shunt close device. I TYPE H AIR CIRCUIT BREAKERS OVERLOAD RELAYS LONG DELAY CALIBRATION All type H breokers are supplied with the new type The relays ore colibrafed of the foctory at 80%, PA direct acting overcurrent relay. These relays 100% ond 160% of trip coil rating and may be ad are dual mognetic type consisting of long delay justed in the field to these calibrated marks. element ond an instantaneous element. A series coil is used on breakers below 600 amp eres while a single conductor provides sufficient mognetic flux for all ratings over 600 amperes.The very efficient magnetic design permits operation of the reloy ot very low ampere turn values ond thus the coil normally associated with air circuit breoker reloys is completely eliminated for oil ratings of 600 amperes and over. In addition, coils used on the lower rotings employ much lower current dens ities than usual for this type of device and thus will operote ot much lower temperatures. INSTANTANEOUS CALIBRATION The relays are colibroted at the facto.y at 10 times the trip coi Irating or for the range to suit the cont inuous rating of the breaker and may be adjusted in the field to these colibroted marks. STANDARD TRIP RATINGS Breaker Type Overcurrent Trip Ratings (100% Calibration) 50.70. 90, 100, 125, 150 instantaneous Trip Range (Adjustable) 175, 200. 225, 250, 300, 8-15 times 350, 400. 500. 600, 800. 1000, 1200, 1600 200, 225, 250, 300, 350, 400, 500, 600, 300, 1000. 1200 1600 20C0, 2500, 3000 Overcutrent Trip ratings 8-15 times 4-10 times 1200, 1600, 2000, 2500 3000, 3500, 4000 4-10 limes 4000.5000. 5000 4-10 times Adjustable Screv OIL FILLER HOLE The relays are shipped from the foctory filled with oil and should not require servicing. If the relays Ore disossembled they should be thoroughly cleoned with carbon tetracmoride and reassembled with care to ensure they ore completely free of dirt or lint. Refill the relay with 20 cc of the replacement silicon oil using o squirt type oil can. CHECKING RELAY OPERATION Push ori both sides of moving ormature with gentle pressure. The armature will move slowly as the delay piston retards the movement. At a point be fore the ormoture meets the yoke, the delay action ceases obruptiy and the ormoture should travel freely to meet the yoke. In so doing the insuloted pull rod connected to the armature should pull the the lever on the trip rod to trip the breoker. Adjust the screw at the trip shaft end of the pull rod if necessary to ensure the breaker trips. 1. Fixed Yoke This procedure may'be repeated with more severe pressure which will extend the instantaneous spr ings and allow the armature to touch the yoke and 2. Moving Armature 3. Loi.g delay springs 4. Instantaneous springs 5. Delay mechanism 6. Oil filler hole 7. Long delay adjustments 8. Instantaneous adjustments F igure 7 trip the breaker. Reference should be made to the time current chor- octeristic curves for proper settings to suit load conditions. TYPE H AIR CIRCUIT BREAKERS of breakers, The hood is an osbestos type material ond will break if subjected to undue shocks, there When a short deloy is required under short circuit fore, care should be used in hondling. conditions o delay device is introduced to prevent the instantaneous action of the reloy. Three colib- ARC CHUTES roted deloys or 5, 15 or 25 cycles ot 6 times the Where the hood does not have a front panel the arc instantaneous pickup are provided. chutes may be removed without removing the hood for inspection of contacts. A long handled screw A mechanicol escopement device is mounted on driver is necessary to reach the mounting screws the moving ormature of the relay to prevent its ot the back of the base. The arc chute may dis SELECTIVE TRIPPING ATTACHMENT movement under short circuit conditions. The tim ing odjustment is mode fay the amount of extension of the escapement spindle. Release the locknut on the side and odjust to one of the calibrated colour from arc interruption but will not need re placement unless heavy deposits of ore contoct material ore present or unless parts are distorted or cracked. marks. MAIN CONTACTS ARCING CONTACTS Main contacts are a silver alloy ond should be clean, bright and free from pitting. They may be gently sonded if necessory using o fine sandpaper time the circuit breaker interrupts the current and should be inspected at regular intervals if the to remove pit morks. Avoid hoving particles fall into the mechanism. If main contocts ore severely damaged careful in spection of all current corrying ports made. Supporting pins, linkage and springs should be exomined for damoge cess heat. Annealed or distorted ports Arcing contacts are subjected to burning every circuit breaker is operated frequently. They should alwoys be inspected after the breaker hos inter rupted o short circuit and should be replaced if should be especiolly due to ex they ore showing serious pitting ond burning. To remove the moving arcing contact from the should be Remove the braid connection by removing the Vt— replaced. breoker, remove the circlip and W dio. pin (3). 20-round head machine screw. Examine the braid carefully for excessive broken stronds or burned HOOD The hood is provided to restrict ionized gases portions. Replace if necessary by disconnecting from the lower main contact bor. Replace in re from direct access to the steel enclosure and in verse order. oddition carries interphose barriers. The hood is To remove the fixed arcing contact refer to Figure 8. Remove mounting bolts as indicoted and replace. held in place as illustrated for the various types Figure 8o Figure 8b (1) Fixed Arcing Contacts 25H-1 (2) Moving Arcing Contacts (5) Fixed Arcing Contact 50H—1 (6) Lower fixed orcing contoct 50H—1 (3) Pin (4) Moin contact (8) Contact sideplate. (7) Blowout coil ff^e type h air circuit breakers 50-1600 AMP. n. 2000-4000 AMP thip shaft (1) Roller (2) Folding Roil (3) (4) (5) (6) (7) ' Crank Nut Crankshaft Interlock com Shock Absorber Control tab wJ (8) Thrust bearing (9) Interlock lever tab (10) Interlock trip rod (11) Truck Stops (12) Rolpin r Top OF BP£AH£A FAAMg TAtP Sff4Pr 5000-6000 AMP f' 12 Figure 9 - Drowout Mechoni sm type h air circuit breakers DRAWOUT CIRCUIT BREAKERS FF^E engaging the main contacts. The wedge is located All drawout circuit breakers ore mounted on o three in the bottom of the enclosure and the trip lever position corrioge so thot the breoker moy be moved adjusted as shown in the diagrams above. to ony of its positions, connected, tested and with It is essential that the breaker trip after three turns of the crank when removing the breaker to ensure drawn without opening the door. On the smoller frame breokers o folding roil ass that the circuit is not broken on the drawout con tacts. embly is used while the large frame breakers re quire 0 rigid self supporting truck. These ore ill If the breaker does not latch properly after it has been moved through this interlock position, check ustrated in Figure 9. to see that the interlock has reset and the trip shofr An interlock is provided which will ensure that the hos returned to its normal position and clearances breaker is open when it is either engaging or dis are maintained os indicated. 1. Closing Link Assembly 2. Hood 3. Arc Chute 4. Base 5. Operating Handle 6. Dual Overload Relay 7. Main Moving Contact 8. Yoke 9. Trip Shaft 10. Closing Casting Link 11. Operating Eccentric Link 12. Crankshaft 13. Faceplate 14. Spring Mechanism Frame 15. Braid 16. Main Fixed Contacts 17. Moving Arcing Contact 18. Faceplate Bracket 19. Terminals SECTION VIEW25H-1 20*. Floating Trim 21. Floating Trim Springs 22. Trip Button 23. Interlock Lever 24. Fixed Arcing Contacts 25. Ground Steel Cam 26. Ratchet Wheel 27. 28. 29. 30. Spring Crank Main Spring .Holding Com Assembly Spring Charge Indicator 31. Manual Close Button 32. Provision for Padlocking Trip Button 33. Provision for Padlocking Operating Handle 34. Handle Clutch 35. 36. 37. 38. Manual Trip Rod Interlock Lever Spring Moving Arcing Contacts Fixed Arcing Contacts 39. Blowout Coil 40 Blowout Core Section View 50H-1, 75H-1 13 FRyE TYPE H AIR CIRCUIT BREAKERS Section View 100H-1 1. 2. 3. Tie Bar Hood Arc-chute 4. Base 5. 6. 7. Operating Handle Overload Relay Insuloted Couplinq . 8. Yoke 9. Tripshaft 10. Operating Lever 11. Operating Link 12. Cronkshaft 13. Faceplate 14. Spring Mechanism Frome 15. Braid 16. Main Contacts 17. Arcing Contacts 18. Faceplate Bracket 19. Terminols 20. 21. Blowout Coil Armoture 22. Trip Button 23. Interlock Lever 24. Wing Nuts 25. 26. Ground Steel Com Ratchet Wheel 27. Spring Crank 28. Main Spring 29. Holding Com Assembly 30. Spring Charge Indicator 31. Manual Close Button (55) 32. Provision for Padlocking Trip Button 33. Provision for Padlocking Operating Handle 34. Handle Clutch 35. Interlock Lever Spring 36. Floating Trim 37. Floating Trim Springs 38. 14 Moving Main Contacts # TYPE H AIR CIRCUIT BREAKERS SPARE PARTS ubreakers to promptly reploce sufficient be or corried in stock operotorsappreciated of circuit any spore worn,ports broken damaged parts.to enable If will the be reodily that a stock of parts reduces deloys in service and soves time and expense. The following spare ports are recommended as minimum requirements for a breaker instollation. Quantity •(1) DESCRIPTION ITEM NO. PART NUMBER FOR BREAKER TYPE 25H.] Moving Arcing Contact 2 49B-98 Stationary Arcing Contact Upper Stationary Arc." 3 49B-94 3A Lower 3B " " " - SOH-t 75H.1.3000A I00H.I.4OOOA TOOH-1 I600AMP 50H.1.3000A 75H.t.4000A 6000A 49B-88 498-89 49B-88 - _ 49B-9889 49B-9888 49B-89 49B-9889 49B-9889 49B-9889 49B-9888 49B-9888 49B-9888 Arc Chute 1 41A-4 41A-9880B 41A-9B80B 41A-8 41A-2-3 Main Braids 5 27A-81 27A-45A-1 27A-89 27A-45A-1 27A-58 195A-1 i95A-l 195A-1 I95A-1 195A-1 Relay Oil (60cc) - - ^hen ordering spare ports specify complete nameplote data. * (1) Quantities listed ore totol for a 3 pole breaker except lOOH—1 which uses 6 of each arcing contact and braid for a three pole breaker. -P \i> "^1 •4© 1. Arc chutes » 2. Moving arcing contacts 3. Stationary arcing contacts 3a. Upper stationary arcing contact 3b. Lower stationary arcing contact 4. Main moving contact ©4 5. Braids 6. Upper main contact 7. Lower main contact 50H-1, 75H-1, lOOH.] FOR ELECTRICALLY OPERATED BREAKERS ADD Qty. DESCRIPTION VOLTAGE RATING 48V D.C. 125V D.C 250V D.C. ~U^ A.C. | 230V A.C. UsQV A.C I 575V A.C. Motor 183A-IA-3 Closing Coil Shunt Trip Coil 46A-9922-10B 240A-4 240A-6 240A-3 240A-4 240A-5 240A-6 46A-9922-I0B 46A-9922-10C 46A-9922-10O 46A-9922-I0A 46A-9922-10B 46A-9922-10D 46A-9922-IOO 46A-7705-J 46A-77Q5-K 45A-7705-L 240A-2A 240A-2B 240A-2C 240A-2D No Volt Coil t-imit Switch(SLS) Limit Switch (CC) Auxiliary Relay 183A-1A-1 183A-1A-2 183A-1A-1 183A-1A-2 49E-8 49E-8 49E-8 49E-8 49E-8 49E-8 249E-6 249E-8 249E-6 219A-4 219A-5 2I9A-6 2i9A-7 219A-8 249E-8 Control Transformer NOTE: When ordering spore parts specify complete nameplate doto. m © © © © \ % © 1. Antl-pumping relay 2. Coil assembly for No Volt Trip 3. Shunt Close assembly 4. Control transformer 5. Spring Limit Switch (S.LS.) 6. Closing Coil Limit Switch (C.C. 7. Motor feOe^AL fAo'Fic S^4> TW/j AJ)^ JU7o^ 71^^ y^. n^y^' T S- X5~o f^ciftJ K\) ^.iL huy. Qji5t£jjj )C\J 4' 7^ / f" %*JL. .- AjAajS/A' - Ujt VACUUA\ /(jLTfoP*^. A^/c. cfor esTfdh^^cJf l2^fcJ flAU^ X67) l2>'Lp\J C>o j'/e^if-^/Ocy Co doAjTt Cu/Z'e^ F/ptlJ'O dUs'i^ C^y ^IfVDO 7f'P\/!>L^ hi'F^ (IfAyF^z-n 0OfOO5f/ r^ ]/. A- // ^sA*7i*0 C-3-222 JUNE,1983 TYPEH-3,HL-3 LOW VOLTAGE POWER AIR CIRCUIT BREAKERS • ; •V.> • . - :.;.v . • -.s' t •;:'i .i . •1:V- i : i • / E D E E D H R A ./'5. V -r..- R '-mM- PIONEER F - PIONEER L 1 M IT E D •• • ; ;,m ..T d" ^ -c; . V t^••V—1^-— - APPLICATION Type H-3and HL-3 low voltage power air circuit breakers are used in metal-enciosed switchgear and unit switchgear conform to the following standards: ANSI C37.13 — "Low-Voltage AC Power Circuit Breakers" substations lor the protection and control of low voltage power circuits up to 250 volts dc and 600 volts ac. They are a means of safelyswitching loads and automatically clearing circuits when such abnormal conditions as sustained overloads, short circuits, ground faults, or ANSI C37.16 —"Preferred Ratings, Reiated under-voltage occur. ANSI C37.17 —'Trip Devices for AC and General- Requirements, and Application Power Circuit Breakers and AC Power Circuit Protectors" RATINGS Purpose DC Low-Voltage Power 600, 800,1600,2000, 3000, 3200, 4000 and 6000 ampere Circuit Breakers" continuous current rating are available. Interrupting capacities from 30,000 to 130,000 amperes for Type H-3, and up to 200,000 amperes for Type HL-3 fused air circuit breaker are available. DRAWOUT OR FIXED MOUNTING Type K-3 and HL-3 breakers are available mounted on a drawout cradle with disconnecting primary power and secondary control contacts. Type H-3 breakers can also be ANSI C37.19 —"Low-Voltage AC Power Circuit Breakers and Switchgear Assemblies" ANSI C37.20 —"Switchgear Assemblies including metal-enclosed bus" ANSI C37.28 —"Low-Voltage AC Integrally Fused Power Circuit Breakers" ANSI C37.50 —'Test Procedures for Low-Voltage AC Power Circuit Breakers Used in provided lor fixed mounting. Enclosures". ELECTRICAL OR MANUAL OPERATION The breakers are provided with either a manually operated handle or an electric motor for charging the stored-enei^ closing mechanism. British Standard 4752, "Part 1" CSA CSA • "Canadian Electrical Code, Part 1". C22.1 (22.2 • No. 31, "Switchgear Assemblies" • "Switchgear Assemblies" • 1A "Specification for Switchgear EEMAC C8-2 USD SOLID STATE OVERCURRENT RELAY Full overcurrent protection features include USD solid- lEC 1S7-1, and Control Gear for voltages up to and including 10(X)V ac and 1200V state relays with Federal Pioneer's ZSIF^ (ZONE SELECTIVE INSTANTANEOUS PROTECTION). STANDARDS Federal Pioneer Ty^ H-3 and HL-3 circuit breakers and FEATURES low resistance long time, ground fault and characteristics ZSIP* Prevents magnetic heating areas of frame Reliability and inierchangeability Compression spring, stored energy operating mechanism Positive control of speed and force of closing, independent of the operator Ratchet-wheel stored energy mechanism Easy interchangeabilityof - "Switchgear Assemblies" Breakers" BENEFITS installed in vacant cell of different current rating. MANUAL OR ELECTRICAL Choice of local or remote OPERATION control. TYPE HL-3 FUSED AIR CIRCUIT BREAKER Up to 2(X>,(X)0 ampere rms symmetrical interrupting capacity. Blown fuse, single phase Protection of rotating protection machinery Rapid identification of faulted phase Blown fuse indicator OPTIONAL FEATURES Padlockable shutters on drawout breakers Overload lockout SAFETY flyback Mechanical Interlocks SAFETY Door Interlocks SAFETY No obsolescence No asbestos used Key interlocks SAFETY Cell Switches SAFHY Up to 48 auxiliary contacts arc chutes Silver plated main drawout - Pause anywhere in charging cycle. No handle type H-3with Federal Pioneer Type H-2 breaker Fibre reinforced poiyester NEMASC-S Rejection feature to prevent breaker being Selective protection and adjustable time current Precision assembly - "Low-Voltage Power Circuit High contact pressure and instantaneous, short time, Stainless steel in critical - FEATURES contacts USD relay with dc. Part 1, Circuit Breakers." NEMASC-3 BENEFITS Trip-free operation Proven multi-segment design double break ' Recommendations for Low-Voltage Maximum efficiencyand Flexibility in control schemes contacts low temperature rise Shunt trip and shunt close Remote operation possible Individually spring-loaded Contact pressure increases Protection from main draw-out contacts with higher current flow. Undervoliage trip undervoltage damage to designed for "blow-on" rotating machinery effect. Operations Counter DRAWOUT CONSTRUCTION Inherently dead front Three position closed-door racking Safely Interlock ensures breaker is open and spring discharged before breaker is connected or withdrawn Mortitoring of maintenance intervals SAFETY SAFETY Breaker Lifting Devices Easyhandling ^ PAGE DETAILED CONSTRUCTION SUPPORTING FRAME 2 OPERATING MECHANISM 2 MAIN CONTACTS 3 ARC CONTROL 4 DRAWOUT CONSTRUCTION 5 TYPE HL-3 FUSED AIR CIRCUIT BREAKERS 8 ACCESSORIES FOR H-3 AND HL-3 CIRCUIT BREAKERS 10 •^USD SOLID STATE OVERCURRENT RELAY AVAILABLE FEATURES 15 ZSIP® 17 LOCAL AND REMOTE INDICATION 17 USD RELAY MODELS 17 TECHNICAL DATA SUMMARY TYPE H-3 BREAKER DATA 18 TYPE HL-3 BREAKER DATA 19 SPRING CHARGING MOTOR DATA 19 COIL RATING DATA 20 USD RELAY SETTINGS 21 CURRENT SENSOR SIZES AND AMPERE TAPS 22 USD RELAY TIME-CURRENT CHARACTERISTICS 23 TYPICAL SPECIFICATION 24 TABLE OF CONTENTS SUPPORTING FRAME The type H-3 and HL-3 breakers are assembled on a moulded base of high strength polyester-glass compound using individual pole pieces carefully interlocked together and supported by a stainless steel frame. The use of stainless steel prevents magnetic heating. The mouldings are deeply ribbed to provide large creepage distances between adjacent current carrying parts. These ribs also serve as stiffeners to resist bending and distortion under conditions of DETAILED CONSTRUCTION maximum stress. The circuit breaker frame is manufactured to close tolerances and jig-assembled to ensure accurate alignment of all parts. Close control is maintained over dimensional stability to ensure complete uniformity and interchangeability of finished breakers of each frame size. OPERATING MECHANISM Two types of operating mechanisms are available on the complete range of Manually operated H-3breaker Manual Operation For manual operation the charging handle, located centrally on the breaker faceplate, is first rotated counter-clockwise and then pressed in to engage a clutch mechanism. Rotating the handle clockwise approximately 180° will fully charge the closing spring. A positive ratchet wheel mechanism allows a pause anywhere during the charging stroke without handle fly-back. The breaker type H-3 and HL-3 circuit breakers; can then be closed by pressing a direct manual for local control and electrical acting manual close button on the for both local and remote operation. A high strength compression type closing spring is employed in all operating mechanisms to give positive control of closing speed and force, independent of the operator. KJ 0 ilectric inotorcbarged operating mechanism (faceplate box removed) breaker faceplate. The closing spring can also be charged manually when the breaker is open and left in the charged position, to be released from a remote position. The manually operated mechanism includes provision for padlocking the handle. On frame sizes 1600 amperes and above, the handle has a pull-out extension for ease of operation. dedicated tripping solenoid operated by the USD overcurrent relay. An electrical trip button is provided on the faceplate and will operate in both "connected" and "test" positions. A manual trip button is also provided and operates in all breaker positions. In addition to the electrical "close" and "trip" buttons one additional electrical button can be provided on the faceplate for special purpose i" controls such as electrical reset of lockout devices. The faceplates of both operating mechanisms, include CLOSED-OPEN and CHARGED-DISCHARGED Electrical Operation For electrical operation a universal series-wound gear motor, suitable for operation on a.c. or d.c. current is provided. The motor is available in voltage ratings of 48,120, 250V d.c. and indicators and provision for key interlocks and/or operation counter. 120, 240V a.c. A toggle switch mounted on the ''aceplate permits the motor to be deenergized during maintenance or inspection. A spring limit switch stops the motor when the closing spring is fully charged. After the motor has charged the closing spring, the breaker can be closed remotely using a shunt close device. The motor operates to charge the spring immediately after the breaker opens so it is ready to close as soon as the electrical close button is pressed. A latch check switch prevents any attempted electrical close until the trip shaft is completely reset in readiness to close. As an option, the motor may be connected to charge the spring, after the breaker closes to provide one immediate reclosure after opening. The electrically operated mechanism includes provision for a manual spring charging handle for emergency use. A shunt trip for remote tripping of the breaker is provided on all electrically Sperated breakers in addition to the H-3brea<:e/mafn and arcing contacts MAIN CONTACTS Type H-3 and HL-3 breakers have silver tungsten double-break bridge type main contacts, with wedge contact surfaces. The angular configuration minimizes the "blow-off" forces produced by short circuit currents. Individual segments of the main moving contacts are fully insulated from each other and the carrying arm and are also self-aligning. Two compression springs per contact produce high contact pressures to ensure the breakdown of corrosive films and dirt. The design was optimized utilizing extensive computer studies, to control current flow through the segments while minimizingtemperature rise. ARC CONTROL arcing by a shield located below the When the breaker opens under loads or short circuits, the main contacts part stationary arcing contact. An insulating barrier, fixed in the switchgear first and the double break contacts compartment above the arc chutes, completes the arc control system. quickly establish a wide air gap. The current-flow is transferred to the arcing contacts, through a heavy copper braid. At no time are hinge pins relied on for carrying current in the Federal Pioneer H-3 and HL-3 breakers. The arcing contacts part and an arc is established and the magnetic field produced forces the arc up into the arc chute. The arc chutes are made of fibre DETAILED :ONSTRUCTION reinforced polyester and contain the steel arc chute plates and de-ionizing plates. The action of the arc-quenching and de-ionizing plates pulls the arc still further inside the arc chute, where it is cooled and broken into many small series arcs. The arc is thus extended, cooled and quickly extinguished, without arcing on the main contacts. During interruption, the main contacts are further protected from the m Arcing contacts parted .Arc extinguished CONNECTEDposition Sp^:i: DISCONNECTEDposition DRAWOUT CONSTRUCTION SeK'V.' ^4-- - ^;:' Thedrawout mechanism provides three positions for the breaker with the door closed. CONNECTED —Primary and secondary contacts energized TEST —Primary contacts isolated; secondary contacts energized DISCONNECTED — Primary and secondary contacts isolated A positive gear drive can be operated from the breaker faceplate even when the enclosure door is closed and operates a cam lever on each side of the draw-out cradle to move the breaker TESTposition through its positions. Normally, the door can be opened with the breaker in any position. An optional door interlock can be provided to trip the breaker if the door is opened. The breaker is guided accurately on grooved steel wheels fitted to the outside of the breaker frame. As the breaker is moved in from the "disconnected" position, the grounding contact is engaged first. This is a sturdy phosphor bronze to copper contact which ensures a positive ground connection to the breaker frame. The secondary or control contacts make next, as the breaker reaches the "test" position. Finallythe main contacts are made as the breaker reaches the "connected" position. A positive stop DETAILED CONSTRUCTION on the mechansim ensures that the 7jm\ \' breaker isfully connected before it can be closed. Breaker position is also clearly shown by indicators on the side .'-/.•v.,;::" ^ of the faceplate box. Whenever the breaker is moved out the reverse sequence takes place. After Rejection Feature the breaker reaches the "disconnected" Rejection Safety Feature A rejection feature is standard on all position and the enclosure door is opened, rugged folding tracks can be pulled down to roll the breaker by hand fully clear of the enclosure, exposing all the plug-in contacts for examination. Safety shutters are available as an option to cover the main plug-in contacts of the enclosure. Safety interlock The drawout mechanism is provided with a safety interlock as standard to ensure that the breaker is open and the closing spring is discharged before the breaker is either withdrawn from the cell or connected into the cell. Thedrawout mechanism operating shaft is located behind a padlockable sliding gate interlock on the breaker faceplace. Lowering the gate to insert the drawout handle trips the air circuit breaker if it is closed, and then discharges the closing spring if it is charged. As long as the handle is inserted, the breaker cannot be closed. frame sizes and prevents entry of a breaker into an enclosure intended for a different frame size. Pins on both sides of the breaker frame must match slots cut in brackets mounted on both sides of the cradle. If the cradle is a different frame size than the breaker, the breaker pins will not match the slots cut in the cradle brackets. M /ain Drawout Contacts - 1600A H-3 mm, Main Drawout Contacts Main drawout contacts utilize electro magnetic force to create a "blow-on" effect to increase contact pressu re as current flow increases. This high pressure gripping action, along with a wiping-action as contacts are first engaged, maintains low contact resistance and operating temperatu res. These contacts are pre-loaded with individual springsforeach pairof contacts to provide a reliable selfaligning connection. The 600and 800 ampere breaker contacts utilize 4 pairs Main Drawoot Contacts - 2000A H3 of segments, each 1/8"(3.18mm) thick. rows arranged in a compact box are The 1600 ampere breaker contacts use 6 pairs of segments, each 1/4" (6.35 mm) used on the4000 ampere breaker. thick. The 3000 and 3200 ampere breaker use two sets of 1600 ampere contacts. The 2000 and 4000 ampere breakers ^utilize rows of contact segments designed to give "line-contact" for maximum conductivity in minimum space; individual springs are again used. Two rows of these contacts are used on the2000 ampere breaker, and four such All main drawout contacts are silver plated formaximum efficiency and low temperature rise as a standard feature. g^^ei m » TYPEHL-3 FUSED AIR CIRCUIT BREAKERS T/pe Hi-3 f used^/f CircoU Breaker The use of HRC fuses increases the HRC Fuse Protection interrupting capacity of the fused breaker to 200,000 amperes. The air Faultcurrent damage is a result of the excessive heat energy released and the mechanical distortion produced by magnetic forces. Both these destructive elements are proportional to the square circuit breaker alone retains the interrupting rating for its frame size, which ranges from 30,000 amperes symmetrical at 600 volts with a 600 ampere frame size, to 85,000 amperes symmetrical at 600 volts with a 4000 ampere frame size. Overcurrent Protection When a short circuit occu rs the magnitude of the current and the co-ordination between the fuse and the breaker overcu rrent relay will determine whether the breaker or the fusewillclearthe fault. Co-ordination must be such that the breaker will not attempt to clear faults beyond its ratings. As breaker contacts must withstand the peak let-through of the of the short circuit current. The heat energy is also directly proportional to the time that the short circuit current flows. Since HRCfuses have the precise qualities of limiting both the current and the time through which it acts, fault damage can be considerably reduced. HRC fuses operate silently and safely without expelling any ionized gas. Selection of Ratings & Co-ordination The frame size and trip ratings for fused breakers are selected in the same manner as for a conventional air circuit fuse there is a maximum size fuse which breaker. Toachieve the best protection from the HRC fuse, the smallest rating which can co-ordinate with the relay can be supplied with each breaker should be chosen. frame size. Co-ordination between the Where fused breakers are used in breaker relay and the fuse is such that series, co-ordination between the fuses the breaker will operate to clear over must also be considered. With reference loads and faults up to its interrupting to the |2t curves for the fuses in rating and the fuse will clear faults above question, one must ensure that the total the breaker rating. clearing |2t of the load side fuse does not exceed the melting l^tof the supply side fuse. Where the HRCfuse must piotect equipment by virtue of its current •* limiting abilities, the maximum peak withstand current for the equipment to be protected must be determined. For the circuit breaker, the maximum peak withstand current is 2.3 times the symmetrical short-circuit rating. Atthe available short circuit current in RMS symmetrical amperes, the peak letthrough current of the fuse selected should not exceed the maximum peak withstand current for the equipment to be protected. For further information on breaker- fuse co-ordination contact Federal Pioneer. Fuse Truck In ratings of 2000, 3000 and 4000 am peres, a separate fuse truck is available to be used in conjunction with an H-3 breaker. Key interlocking is provided to ensure that the circuit breaker is open before the fuse unit is withdrawn. The fuse unit is equipped with a rejection feature which prevents entry ^ of the fuse unit into the breaker cell. TYPE HL-3 FUSED AIR CIRCUIT BREAKER Single Phase Protection and Blown Fuse Indicator Single Phase Protection Protection against single phasing caused by breaker fuse interruption is a standard feature on Type HL-3 fused air circuit breakers. Three solenoid coils (one per phase) are connected in parallel with the HRC fuses. They are provided with plungers which act directly on the common trip shaft. The coils are rated 1/5th line voltage so that should a fuse blow on short circuit, the coil will provide sufficient power to trip the breaker, even though the line voltage may be reduced. Blown Fuse Indicator The type HL-3 circuit breaker is available in 600 to 4000 amperes frame sizes. The HL-3 breaker is similar to a drawout Type H-3 with the addition of a provision for mounting NEMA HRCfuses. Optional An indicator is provided which is actuated by the single phase protection coils. Should one fuse blow, the These fuses are mounted on the line side on a frame extension at the rear of the breaker and are accessible for corresponding coil will trip the breaker and project an indicating bar through the faceplate. The three indicators are coloured red, yellow and blue and correspond to left, centre and right side fuses. When the fuse has been replaced the linkage can be reset by pushing in replacement when the breaker is fully the indicator. The breaker can then be withdrawn. reclosed. accessories available for the H-3 breaker are also available for the fused breaker. The following maximum fuse sizes may be used: HL-3 FRAME RELAY RATING RATING MAXIMUM FUSE RATING (AMPERES) (AMPERES) (AMPERES) 800 NEMA L 1200 NEMA L 2000 NEMA L 3000 NEMA L 4000 NEMA L 6000 NEMA L Secondary Conirol Contacts ACCESSORIES FORH-3AND HL-3 CIRCUIT BREAKERS Secondary Control Contacts Secondary control contacts are provided on drawout units to automatically connect or disconnect control circuits, as the circuit breaker moves through its positions in the cradle. The contacts are designed so that the control circuit can be energized or isolated in the test position. These connections can be altered in the field, when required, by means of jumpers between contacts of the stationary block. Supplied in multiples of 8 contacts, a total of 48 can be provided, and each contact has a continuous current rating of 30 amperes. In applications where a control supply voltage in excess of 250 V is to be used, the higher voltage contacts are double spaced (i.e. the adjoining Shunt Trip Shunt Trip The shunt trip is a solenoid device separate from the dedicated solenoid used with the USD relay. When energized it acts directly on the breaker trip shaft to trip the breaker. Coils are interchangeable with all standard control ratings available. (See rating data). A shunt trip is supplied as standard on electrically operated breakers and is available as an option on manually operated breakers. contact is unused). Contacts are formed copper, cadmium plated and mounted in a polycarbonate moulding. The moulding is designed with high barriers between contacts to provide large creepage distances. The movable secondary contact block fitted to the breaker assembly is spring mounted to ensure alignment with the stationary contacts. ni The device is energized directly, or from a control transformer, and is ^mi connected across two phases. If voltage is available on the line side terminals, the coil is energized and will compress the springs. The breaker may then be closed in the normal manner. In operation, the coil drops-out at 35% of rated voltage for 120V a.c. and 46% of rated voltage for 240V a.c. Both pull in at 80% rated voltage. Overload Lockout Device Shunt Uose Shunt Close The shunt close device is used to release the energy stored in the closing spring to close the breaker from a remote position. It is standard on electrically operated breakers and is available as an option on manually operated breakers. The overload lockout device prevents reclosing of the breaker either manually or electrically after the breaker has been tripped by the overload relay, until this device is manually reset. The direct acting shunt trip solenoid plunger mechanically holds the closing mechanism in the trip-free position, preventing closing of the main contacts. The latch check switch wired in series with the closing coil is open in this position, to block electrical operation of the closing coil. The device is reset by pushing the manual overload lockout reset button on the breaker faceplate. This reset button is spring returned to its normal position. Alarm Contacts A Single Pole Double Throw contact is supplied and operated In conjunction with the overload lockout device. Contact is reset with the overload lockout device. Where overload Undenoltage Trip with Time Delay Attachmenl Undervoltage Trip The undervoltage trip provides protection on loss of system voltage or low system voltage. It is an a.c. solenoid holding two compressed springs which will trip the breaker mechanically when the supply voltage -•\'^al!s too far below normal. (See rating '' data). Tripping action may be instantaneous or delayed up to 5 seconds when the adjustable timedelay attachment is specified. lockout is not required a momentary overload alarm contact can be supplied to operate a remote flag relay. N/r Y *4 ^ Auxiliary Sw.tch ACCESSORIES FORH-3AND HL-3 CIRCUIT BREAKERS Auxiliary Switch All H-3 and HL-3 units use a multi- section rotary switch coupled directly to the closing shaft, operated on a snap action principle which provides quick break switching. Switches with up to 20 poles are available. "i: Mechanical Interlock Mechanical Interlock Mechanical interlocks are available on all H-3 and HL-3 breakers. They are used to mechanically interlock breakers in a two or three breaker transfer scheme, in the case of a two breaker transfer scheme, mechanical interlocks ensure only one breaker is closed while the other is held in a tripfree position. Mechanical interlocks connect the closing shaft of one breaker to the trip shaft of a second breaker by means of a flexible cable and vice versa. In a three breaker transfer scheme mechanical interlocks Operations Counter Operations Counter A five digit mechanical counter can be supplied, mounted in the faceplate of the breaker. This device is mechanically driven by the "CHARGED-DISCHARCED" indicator, and operates once for each charging of the breaker closing spring. Operations counters are ensure only two breakers are closed while the third is held in a trip-free position. Drawout breakers are interlocked by cable connections between the cradles. There are no permanent connections between the breaker and matching cradle when interlocking is supplied, so the breaker can be freely withdrawn from the cell. Mechanical recommended where breakers will be interlocks are operable only when the breaker is in the connected position. subjected to frequent operations as an When withdrawn to the "test" indicator of the recommended position, breakers can be test operated maintenance intervals. in the normal manner. With the key removed the closing mechanism is completely trip-free, preventing closing of the main contacts. On electrically operated units an auxiliary switch contact is provided to operate in conjunction with the interlock isolating the closing circuit. V..- r.ot Door Interlock All H-3 and HL-3 circuit breakers may be fitted with a device which acts to trip the unit when the cell door is opened. In operation, the door lever acts internally on the mechanical trip button causing it to move in towards ^he faceplate. Cell Switches Cell Switches Cell switches mounted in the cradle can be provided to serve as position indicators or as an electrical interlock bypass. The switches are operated when the breaker is removed from the "connected" position in the enclosure. Each switch contains one normally closed and one normally open contact. A total of six switches can be supplied. These contacts are rated 10 amperes up to 300V a.c. mssBm Ke)' Interlock ^ev Interlocks /pe VF key interlocks, single or double lock, with 3/8 inch (9.5mm) projection can be provided. Provision is made for key interlocks on all frame Shutters Shutters are available for all frame sizes up to and including 3200 amperes for both line and load side main plug-in contact stabs. For the 600, 800,1600, 3000 and 3200 ampere H-3 frame sizes, shutters are of the lifting type. They have a padlock bracket in the bottom of the enclosure for locking in the down position. When the breaker moves from the "test" to the "connected" position, shutter bolts on the frame of the ACCESSORIES FOR H-3 AND HL-3 CIRCUIT BREAKERS breaker lift the shutter to expose the main plug-in contacts. For the 2000 ampere H-3 and for the 600, 800, 1600, 2000 and 3000 Lifting Device facilitates safe handling of breaker amperes HL-3, shutters are of the splitting type. When the breaker Lifting Device moves from the test to operating Federal Pioneer for all frame size position, shutter bolts on the frame of the breaker open the shutter to expose the main plug-in contacts. A separate blanking truck may be used in 4000 ampere drawout breaker breakers. The lifting device is a onepiece yoke which fits into lugs on the breaker sideplates. This permits safe enclosure drawout tracks. Lifting yokes cells. are ordered as follows. A lifting device is available from removal of the breaker from the Part Number 26G-542 for 600, 800, 1600 and 2000 ampere H-3's. Part Number 26G-151 for 3000, 3200 and 4000 ampere H-3's. Part Number 26G-601 for 600, 800, 1600 and 2000 ampere HL-3's. Part Number 26G-603 for 3000 and 4000 ampere HL-3's. Part Number 26G-150 for 6000 ampere 100H-2. v.—Ti. tTS" I^ Shutters lift automatically as breaker moves to ••CONNECTED" position AVAILABLE FEATURES BENEFIT Long time, short time instantaneous and ground fault protective functions Pick up elements work independently ZSIP® on short time and ground Selective co-ordination fault Thumbwheel programming switches with positive detents and gold plated contacts. Factory calibrated discrete for maximum service continuity Relay reliability Selectivity with minimum system damage Precision setting of protection function, without in service "drift". ^.•yaiues for pick up and time delay. Jolour keyed faceplate Ease of setting relay Local and remote indication Rapid fault location Type H-3 and HL-3 breakers are supplied with the Federal Pioneer Type USD Solid State Overcurrent Relay, as a standard feature. The USD relay protects low voltage power systems against damage caused by short circuits, overloads and ground faults. The relay may have up to four pick up elements: instantaneous, shorttime, long time and ground fault, each working independently of the others for increased reliability. Local and remote indication are availabie. In addition ZSIP® (ZONE SELECTIVE INSTANTANEOUS PROTECTION) is availabie for the short-time and ground fault elements. USD Relay - A standard feature of H-3, HL-3 breakers ^-N>; ®||j^|£ | ^H|> ^'W la " l^« J^-4jjl ^^^SSSlpi [f to ^^Pl'^^j^pj'^^en-™-—jj^^l^^jf USD SOLID STATE ERCURRENT RELAY ^ Carefully matched components of the USD trip system The Type USD Relay is mounted low on the front of the breaker frame, away from the arc-chutes. Tripping energy for the operation of the circuit breaker is obtained solely from the circuit being protected. Other power sources are only required for fault indication (if specified). The USD relay complies with ANSI Standard C37.17 "Trip Devices for AC and General-Purpose DC Low-Voltage Power Circuit Breakers". Three multiple-tap current sensors, mounted on the breaker provide power input to the USD relay from the protected circuit and current signals to the fault detection logic circuit. A fourth sensor, can also be ordered where four-wire ground fault protection is required. Sensors utilize high quality grain-oriented silicon steel alloy cores, and are encapsulated in POLESTIGLASS to provide moisture protection and mechanical strength. Sensor tap setting is shown on the breaker faceplate by an adjustable rotatable disc. Solenoid Trip Device — A dedicated direct acting solenoid provides positive activation of the trip latch on the breaker, and positive resetting after operation, completes the trip system. Pick up levels and time delay settings are factory programmed and calibrated in discrete settings for repetitive accuracy and precision. Cold plated contacts on the thumbwheel switches used for selecting settings, assure long lasting, positive electrical performance. ZSIP® LOCAL AND REMOTE INDICATION Selectivity between main and feeder breakers is conventionally obtained by using time co-ordinated trip devices, with the device furthest downstream Local indication is by long-life LED's on the relay faceplate while remote indication is facilitated through a set of dry contacts which can be connected set for minimum time delay. The to remote annunciating or alarm disadvantages of this method is that devices. 120 volt a.c. 2.5VA control fault levels increase in zones closer to the main breaker and the time to clear power is required. these faults increases. The power system must withstand these high fault current levels until the time delay on the first device upstream of the fault /""Spires. ' - With ZSIP® the trip device that senses a fault in its zone of protection trips instantaneously, minimizing system damage. The USD relay also sends a restraint signal to all upstream devices and causes them to operate according to their time co-ordinated protection mode, increasing service continuity. ZSIP® is available on the short time and ground fault elements of the USD relay. USD RELAY MODELS * i fig CHARACTERISTICS USD-3 LONG TIME • SHORT TIME «/) 1- WITHOUT ZSIP® Ul SHORT TIME % WITH ZSIP® UJ —1 UJ INSTANTANEOUS • • O USD-3IR • • • GROUND FAULT WITH ZSIP® D • • USD-6* • • • • • • LOCAL AND REMOTE INDICATION *Add the following suffixes: 6 for use with CUD 1.5 and CSD-6 sensors 8 for use with CSD-8 sensors 16 for use with CSD-16 sensors 20 for use with CSD-20 sensor 32 for use with CUD-30 and CUD-32 sensor 40 for use with CUD-40 andCUD-60 sensors 17 TYPE H-3 BREAKER DATA 30H-3 BREAKER TYPE MINIMUM ENCLOSURE WIDTH (INCH) 25 42H-3 50H-3 65H-3 50H-3 75H-3 100H-3 100H-2 25 25 25 32 32 32 32 600 600 600 600 600 600 600 600 635 635 635 635 635 635 635 635 1 minute withstand 2200 2200 2200 2200 2200 2200 2200 2200 CURRENT CONTINUOUS 600/600 1600/2000 1600/2000 3000/3200 3000/3200 4000 6000 (AMPERES) CURRENT VOLTAGE (VOLTS) Voltage Ratings Rated Maximum Voltage 600/800 INTERRUPTING TECHNICAL DATA SUMMARY CURRENT (RMS SYMMETRIC:AL) (1) WITH INSTANTANEOUS TRIP 254 V 42,000 50,000 508 V 30,000 42,000 635 V 30,000 42,000 65,000 65,000 65,000 85,000 130,000 130,000 50,000 65,000 50,000 85,000 85,000 85,000 50,000 65,000 50,000 65,000 85,000 85,000 WITH SHORT TIME DELAY (2) 254 V 30,000 42,000 508 V 30,000 42,000 635 V 30,000 42,000 MAKING CURRENT (Peak amperes) TIMES (SECONDS) 50,000 65,000 50,000 65,000 85,000 85,000 50,000 65,000 50,000 65,000 85,000 85,000 50,000 65,000 50,000 65,000 85,000 85,000 69,000 96,600 115,000 149,500 115,000 149,500 195,500 195,500 -Closing (Contact Touch) .025 .025 .025 .030 .030 .030 .030 .030 -Closing (Breaker Latched) .030 .030 .030 .035 .035 .035 .035 .035 -Contact Parting .004 .004 .004 .005 .005 .005 .005 .005 -Arcing (Max.) (3) .0085 .0085 .0085 .0085 .0085 .0085 .0085 .0085 .034 .034 .034 .034 .034 .034 .034 .034 .176 .176 .176 .176 .176 .176 .176 .176 -Total Clearing incl. USD relay operation time -Reclosing Time (No Intentional Time Delay) (4) -Motor charging time 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 TEMPERATURE RISE ON TERMINALS (40°C AMBIENT) less than 55°C (1) INTERRUPTING DUTY CYCLE consists,of an opening operation, a15 second interval, followed by a close-open operation, perANSI Std. C37.50. . . < (2) SHORT-TIME DUTY CYCLE consists of 2 —30 cycle intervals with a 15 second period of zero current between the two periods, perANSI Std. C37.50. (3) Maximum Arcing Time in critical current range (Range 175-400A) is .035 seconds. (4) Operating factor for reclosing duty is 100%. 18 i TYPE HL-3 BREAKER DATA* BREAKER TYPE FRAME SIZE AMPS INTERRUPTING RATING BREAKER CAVFUSE KASVM. 30HL-3 INTERRUPTING RATING MAXIMUM FUSE SIZE BREAKER ONLY KASYM. AMPS 24£V 600 200 42 480V 30 600V 30 800 NEMA L 30HL-3 800 200 42 30 30 1200 NEMA L 50HL-3 1600 200 65 50 50 2000 NEMA L 50HL-3 2000 200 65 50 50 3000 NEMA L 75HL-3 3000 200 85 85 65 4000 NEMA L 100HL-3 4000 200 130 85 85 6000 NEMA L Ml data for HL-3 is same as corresponding size H-3 air circuit breaker, except for increased -interrupting capacity. SPRING CHARGING MOTOR DATA NOMINAL VOLTAGE 48 VOLTS DC CURRENT REQUIRED 7 amperes (INTERMITTENT) 125 VOLTS DC 250 VOLTS DC 120 VOLTS AC 240 VOLTS AC 4 amperes 2.5 amperes 4 amperes 2.5 amperes 4.0 sec. 4.0 sec. 4.0 sec. 4.0 sec. MOTOR CHARGING TIME 4.0 sec. AUXILIARY SWITCH CONTACT RATINGS 10 amperes up to 254V a.c. 1 ampere at 250V d.c. 2 amperes at 125V d.c. SECONDARY CONTROL CONTACT RATING 30 amperes CELL SWITCH CONTACT RATING 10 amperes up to 300V a.c. COIL RATING DATA TECHNICAL DATA SUMMARY RATED MINIMUM D.C. AMPERES AMPERES CONTROL VOLTAGE OPERATING VOLTAGE OHMS INRUSH SEALED 2.45 0.34 til SHUNT 120 AC 75 30.0 TRIP 240 AC 150 312.0 1.5 0.15 6.0 8.0 0.2 TYPE A 48 DC 40 125 DC 40 50.0 2.2 0.2 250 DC 70 312.0 0.8 0.1 SHUNT 120 AC 60 13.0 1.4 TRIP 240 AC 120 50.0 1.0 MOMENTARY 48 DC 40 13.0 2.0 RATED 125 DC 40 86.0 2.5 ONLY 250 DC 70 215.0 1.25 SHUNT 120 AC 90 30.0 2.45 0.34 CLOSE 240 AC 180 312.0 1.5 0.15 48 DC 40 6.0 8.0 0.2 125 DC 60 50.0 2.2 0.2 250 DC 150 312.0 0.8 0.1 UNDERVOLTACE 120 AC 96 23.0 2.45 0.34 TRIP 240 AC 190 312.0 0.8 0.1 ANTI-SINGLE 240 AC 90 13.0 2.8 MOMENTARY PHASE 480 AC 120 50.0 1.8 RATED DEVICE 600 AC 120 50.0 2.3 ONLY TYPES NOTES: Type Ashunt trip is continuously rated and is used only when acontinuous rated coil for aseparate trip source is required. Type Bshunt trip is momentary rated. It is used as the dedicated solenoid for theUSD relay or earlier SD relay and/or when onlya separate trip coil is required. 20 USD RELAY SETTINGS ELEMENT PICK UP LEVELS IN MULTIPLES OF SENSOR TAP INSTANTANEOUS 4X, 5X, 6X, ex, 10X, 12X, OFF (1) DELAY IN SECONDS NO INTENTIONAL TIME DELAY SHORTTIME 2X, 3X,4X,6X,8X,10X .11, .25, .33, .45, Pt(2),.05 inZSIP® mode regardless of short time delay setting. LONGTIME .6X, .7X, .8X, .9X,1.0X,1.1X 2.0,4.0,6.0,8.0, 10.0,14,0,16.0,22.0, 26.0,30.0(3) GROUND FAULT Catalogue Numbers: USD-6(IR)-6 .25, .50, .75,1.0,1.5, 2.0 .08, .14, .20, .26, .32, USD-6 (IR) -8 .25, .50, .75, 1.0,1.25,1.5 .02 in ZSIP® mode regardless of ground fault time delay setting. USD-6 (IR) -16 .20, .30, .40, .50, .60, .70 USD-6 (IR) -20 .20, .25, .30, .40, .50, .60 USD-6 (IR) -32 .20, .22, .24, .28, .32, .36 USD-6 (IR) -40 .20, .22, .24, .26, .28, .30 TEMPERATURE RANGE: The USD relay is ambient temperature compensated over the range-20°C to +55°C. Tolerances apply over this range. Operation outside this range is possible. Consult Federal Pioneer. (1) DISCRIMINATOR: When the instantaneous pick-up switch is in the "OFF" position, the instantaneous element will not pick up unless the breaker closes on a fault that exceeds 13X the sensor tap setting, in wh ich case a discriminator will initiate tripping. In addition a trip will be initiated if a fault of 13Xthe sensor setting, or greater occurs while the breaker is supplying a load of less than 0.04Xthe sensor tap setting. If the breaker closes and the cu rrent is greater than 0.04X,but less than 13Xthe sensor tap setting, the discriminator monitors the current for 40ms. and if the fau It level of 13X is not exceeded during this time, the discriminator switches itself off. (2) SHORTTIME Time Delay .55 sec. @6X (3) LONG TIME Time Delays shown @ 6X TOLERANCES: ± 8% on pick up values ± 10% on time delay values RELAY RESETTIME: 30ms CURRENT SENSOR SIZES AND AMPERE TAPS TECHNICAL DATA SUMMARY SENSOR TYPE TAPS AVAILABLE IN PRIMARY TAPS BREAKER FRAME 600A 30H-3, 42H-3 CUD-1.5 100,150 SENSOR TYPE TAPS AVAILABLE IN PRIMARY TAPS BREAKER FRAME CSD-20 800,1200,2000 2000A 50H-3,65H-3 800A 30H-3, 42H-3 3000A 50H-3 1600A 50H-3, 65H-3 3000A 2000A 50H-3, 65H-3 CUD-30 600A CSD-6 250, 400, 600 30H-3,42H-3 4000A100H-3 50H-3, 65H-3 50H-3, 65H-3 6000A100H-2 2000A 800A 30H-3, 42H.3 400, 600, 800 3200A 75H.3 800A 30H-3, 42H-3 1600A CSD-8 75H.3 1200, 2000, 3000 3200A SOH-3 1600A 50H-3, 65H-3 2000A 3200A CUD-32 50H-3 1600, 2000, 3200 3200A 75H-3 4000A100H-3 50H-3, 65H-3 6000A 100H.2 1600A 50H-3, 65H-3 CSD-16 1000,1200,1600 2000A 50H-3, 65H-3 CUD-40 1600, 3000, 4000 4000A 100H-3 6000A 100H-2 CUD-60 22 5000,6000 6000A100H-2 /""o-rtrS' TYPE USD SOLID STATE OVERCURRENT RELAY TIME-CURRENT CHARACTERISTICS .4 10000 S 20 .6.7.8.91 oo r>too>o Low voltage power air circuit breakers shall be 3 pole 600 volt class with continuous current ratings and trip ratings as detailed on the plans. Interrupting ratings will be in with enclosure door closed, and shall be equipped with an interlock to ensure breaker contacts are open and closing spring is discharged when racking tool is inserted. Faceplate accordance with NEMA Standards for mounted control buttons, indicators the frame and/or their application in a fully rated system. Breakers shall have double break main contacts, a 3 phase solid state overload relay and shall be trip free in operation. A compression spring stored energy closing mechanism (either manually or electrically charged) shall be used for all ratings, with breakers being closed by means of a push button and shall have the ability to close and latch at interrupting rating at 600 volts. An emergency manual spring charging handle shall be supplied for electrically operated breakers. Breaker faceplate shall have "closed-open" indicator, spring interlocks etc. shall be accessible "charged-discharged" indicator, provision to padlock manual charging handle, provision to lock breaker in "open" position, and provision to lock drawout mechanism. Drawout circuit breakers shall be suitable for 3 position (connected, test, disconnected) racking without opening enclosure door. Electrically operated breakers must have provision for emergency manual closing by inserting a special tool through the faceplate. A control isolating switch shall be provided on the faceplate to isolate the supply to the spring charging motor. Relay pickup and time delay settings shall be selected in discrete factory calibrated values by means of detent action thumbwheel actuated switches with gold-plated contacts. When a solidly-grounded system is used, the relay shall be equipped with Zone Selective Intantaneous Protection feature on short time and ground fault elements. A direct acting dedicated solenoid shall be used for initiating breaker triping. Breakers shall be Federal Pioneer Limited Type H-3 or HL-3. r^i C-3-222-1 PIONEER FEBRUARY 1984 INSTRUCTIONS FOR THE CARE AND MAINTENANCE OF H-3 AND HL-3 CIRCUIT BREAKERS r mbi •ft' . F ' This manual applies to H-3and HL-3 breakers. For H-2and HL-2 breakers, consult the following instruction manuals: For breakers with serial numbers BH consult Instruction Manual C-3-221-1 dated September 1979. For breakers with serial numljers TH consult Instruction Manual C-3-221-1 dated March 1976. For breakers with serial numbers T consult Instruction Manual 0-3-414 dated August 1966. CONTENTS GENERAL DESCRIPTION PAGE 1 General Basic Breaker Types Breaker Description 1 RECEIVING. HANDLING AND STORAGE 1 1 BREAKER OPERATION Drawout Mounted Breakers Drawout Racking Mechanism Fixed Mounted Breakers Power Terminal Connections Secondary Control Circuits Pre-Service Inspection Manual Closing Electrical Closing BREAKER MAINTENANCE Removing the Faceplate . 5 Lubrication . 5 Close Latch Adjustment . 7 Mechanism Latchingand TripShaft Adjustment Spring Discharge Interlock . 9 Shunt Trip Unden/ollage Trip .10 Shunt Close ..12 ClosingSpring Charging Motor Motor ClosingSpring Limit Switch ..13 Latch Check Switch Contact Maintenance Main Power Contacts Contact Differenfial ..14 ..14 ..14 .10 .11 ..12 ..13 Main Moving Contact Deflection ..14 Slow Close Device ..16 Arcing Contacts ..16 Arc Chutes Overload Protection ..16 ..16 ..18 Overload Lockout Fuse Mounting ..18 Antl-Slngle Phase Deviceand Blown Fuse Indicator.. Secondary Control Contacts ..19 Auxiliary Switch Mechanical Operations Counter ..19 ...19 ..19 Mechanical Interlock Door Interlock ...20 Key Interlocks ...21 ...20 Cell Switches ...21 Shutters ...22 ...22 Rejection Features Lifting Device Spare Parts ...22 ...24 Before placing in service read this Instruction Manual completely and perform the pre-senrlce Inspection (see page 4). r GENERAL Type H-3 and HL-3 power Air Circuit Breakers are suitable for controlling and protecting low voltage power circuits up to 250 volts dc and 600 volts ac. They are a means of safely switching loads and automatically clearing circuits when abnonnal conditions occur such as undervoltage, sustained overloads, and short circuits. The proper INSTALLATION, MAINTENANCE and OPERATION of these breakers is a prime safety consideration for the protection of personnel and equipment Reference to this manual and adherence to its recommendations will enhance the perfomiance of these breakers under all conditions. This manual does not purport to cover all details or variations of equipment nor to provide for every possible contingency to be met in connection with receiving, storage, installation, maintenance or operation. Should further information be required or particular problems arise which are not covert sufficiently, please refer to Federal Pioneer Limited. RECEIVING, HANDLING AND STORAGE Receiving Immediately upon receipt of the breaker an examination should be made for damage sustained in transit. If damage has occurred or there is evidence of rough handling a claim should be filed immediately with the transportation company and Federal Pioneer Limited should be notified. Check all parts against the packing list to make sure all the correct items have been received. Handling and Storage Lift the breaker by the steel channels at the front and back. Do not lift by the connecting tenninals, arc chutes, or operating handle. Check the unit thoroughly to see that no parts were damaged or forced out of alignment during shipment. If replacement parts are required, the manufacturer should be notified promptly. The breaker should be installed in a clean di^ ventilated area, which is free from atmospheric contaminants. Each circuit breaker should be stored In its shipping crate in an upright position in a clean dry area. Should the unit get wet, it must be thoroughly dried out using forced warrn air over an extended period until "infinite" readings BASIC BREAKER TYPES Type H-3 breakers are available mounted in a drawout cradle with disconnecting primary power and secondary control contacts. Alternativelya stationary fixed mounting in a suitable enclosure can be provided. These breakers are provided with either a manually operated handleor an electric motor forcompressing the are obtained using a 600 volt megger. BREAKER OPERATION DRAWOUT MOUNTED BREAKERS Switchgear assemblies for drawout mounted breakers are provided with supporting rails, main power contacts closing spring. and secondary contacts to mate with those on the HL-3 type breakers are available in the drawout version only, either manually or electrically operated. HL-3 type Drawout Racking Mechanism breakers are similar to the H-3 type but in addition have high rupturing capacityfuses mounted on the lineside on a frame extension at the rear of the unit. BREAKER DESCRIPTION The three main functional components of a breaker are its mechanism, the conducive members and the interrupting devices. The mechanism unit is designed to receive energy, store it, and deliver it to close the breaker contacts when required. Upon activation of the trip device, the mechanism must allow the contacts to open regardless of the state of the mechanism, that is the breaker mechanism is "TRIP FREE". The conductive members are assembled on a moulded base of fiberglass reinforced polyester. Individual pole pieces carefully interlocked together and supported by a steel frame provide the mechanical support and insulat ing structure required. The conductive members com prise the main power contacts (drawout mounting) or lugs (fixed mounting), the main fixed contacts and the main moving bridge contacts. breakers when it is racked into position. An interlock is provided which will ensure thatthe unit is open and the main spring is discharged when itis either engaging or disengaging the main disconnecting con tacts. A block is provided on the racking mechanism which operates in conjunction with the gate interlock lever over the racking opening. Before withdrawing electrically operated breakers tum off the motor isolating switch on the faceplate. To withdraw the unit, move the gate over the crank opening down so as to expose the socket end of the drawout racking shaft This action will first open the unit if it is closed and then discharge the main spring if it is charged.The racking handlemay now be inserted in the racking shaft socket and by counter-clockwise rotation the unit will move outward. At the "test" position the main contacts are withdrawn but the auxiliary contacts remain engaged in the test position. Further turns of the racking handle will move the unit to the "disconnected" position. It is then free to be pulled manually forward to the end ofthe tracks. Two lifting lugs are provided on each side of the unit so that it can be lifted clear of the tracks. Lifting yokes are available from the manufacturer. (Fig. 32). Grounding continuity is established Vb inch (3.2 mm) before the secondary control contacts are energized. Itis maintained throughout breaker positioning in the enclo The interrupting devices are the fixed and moving ardng sure until the secondary control contacts have been contacts and the arc chutes. de-energized by Ve inch (3.2 mm). Grounding continuity In addition to these main functional components the breaker is available with overload protection and other accessories and interlocking devices. is established when the moving ground contact on the breaker mates with the stationary ground contact located on the frame of the breaker enclosure. Page 1 PART NUMBERS AIR CIRCUIT BREAKERS (DRAWOUT) FIGURE 1 SECTION OF K-3 BREAKER Type30H-3 Typ«50H-3 Type SOH-3 Type50atKl75H-3 Type 100H-3 600 and 600 Amp 1600 Amp 2000 Amp 3000 and 3200 Amp 4000 Amp 41A-5040 1. Arc Chute Assembly 41A-504D 41A-504D 41A-504D 41A-504D 2. Intemliase Barrier 13A-574C 13A-574C 13A-574C 13A-578C 13A-578C 13A-172A-1 13A-172A-1 3. R. H. End Barrier 13A-575C 13A-575C 13A-575C 4. L H. End Barrier 13A-576C 13A-S76C 13A-576C 13A-172A-1 13A-172A-1 5. Front Flash Shield 182A-542B 182A-542B 182A-542B 182A-40A-1 182A-40A-1 (-41A-1) (^1A-1) 6. Closed-Open Link 170A-585 170A-585 170A-585 170A-585 170A-585 54C-507 540507 7. Crank Assembly 54C-507 54C-507 54C-507 8. Crank Box 24A-15A-2 24A-15A-2 24A-15A-2 24A-15A-2 24A-15A-2 9. Crank Box Bearings 29B-514 29B-514 29B-S14 29B-514 29B-514 210A-505 210A-505 210A-505 210A-505 210A-505 35A-508 35A-508 35A-50d 35A-508 10. Holding Pawl 11. Ratchet Wheel 35A-508 12. Osciilating Lever 168B-S92 1686-592 1686-592 1686-592 168B-592 13. Clutch 45A-8 45A-8 45A-6 45A-8 45A-8 14. Charged-Dlscharged Link 15. Closed-Open Button 16. Charged-Oischarged Button 1686-580 1686-580 1686-580 1686-580 168B-580 182A-567B 182A-567B 182A-567B 182A-567B 182A-567B 182A-568B 182A-568B 182A-568B 182A-568B 182A-568B 17. Front Plate 53M-65A-3 53M-65A-3 53M-65A-3 53M-65A-3 53M-65A-3 18. Indicator Plate 53M-64A-3 53M-64A-3 63M-64A-3 53M-64A-3 53M-64A-3 19. Faceplate Box Assembly 24A-8 24A-8 24A-8 24A-8 24A-8 20. Floating Trim 21. Faceplate Assembly 267A-1 267A-1 267A-1 267A-1 267A-1 84A-10C-2 84A-10C-2 84A-10C-2 84A-10C-2 84A-10C-2 115G-500 115G-500 115G-501 115G-501 115G-501 168B-39A-3 168B-39A-3 168B-39A-3 168B-39A-3 168B-39A-3 22. Handle Assembly 23. Close Lever 24. Close Latch 35A-509 35A-509 35A-509 35A-S09 35A-509 25. Trip Rod Assembly 224B-124A-1 224B-124A-1 224B-124A-1 224B-124A-1 224B-124A-1 26. 27. 28. 29. 30. 31. 32. 33. 201B-88 201B-88 2016-88 201B-88 201B-88 168A-3 168A-3 168A-3 168A-3 168A-3 201B-72 201B-72 201B-72 201B-72 201B-72 2350-17 235D-17 235D-17 2350-17 2350-17 170A-590 170A-590 170A-590 170A-593 170A-593 242A-510 242A-511 242A-511 242A-512 242A-512 29B-512 298-512 296-512 296-512 296-512 42B-500 42B-500 426-500 42B-500 426-500 34. Breaker Frame 81A-566 81A-566 81A-566 81A-567 81A-567 35. 36. 37. 38. 39. 235B-26 2356-26 235B-26 2356-26 2356-26 168B-96 168B-96 1686-96 1686-96 1686-96 16A-9 16A-9 16A-9 16A-9 16A-9 Spring Guide Pin Closing Casting Closing Pin Tie Rod Assembly Closing Shaft Mani Spring Guide Bushkigs Clamp Assembly Trip Shaft Trip Latch Latch Bearing Ixjwer Moulding Sensor Mounting Bracket 40. Barrier 41. Sensor 182A-509D 182A-509D 182A-509D 14C-543 140543-1 26G-606 26G-606 26G-606 26G-627 26G-627 182A-24(-25) CSD-6(-8) 182A-24(-25) 182A-24(-25) 182A-24(-25) 182A-24(-25 CSD-16 CSD-20 CUD-30(-32) CUO-40 42. Jumper 147B-511 147D-503 147D-503 1470-510 1470-510 43. Centre Statlonarv Main Contact 44. Main Moving Contact (Wafer Assy) 49E-577 49E-550 49E-550 49E-550 49E-550 49E-575 49E-57S 49E-575 49E-575 49E-575 45. Upper Stationary Main Contact 49E-554 49E-548 49E-549 49E-548 49E-549 46. Closing Link Assembly 170A-589 170A-589 170A-589 170A-589 170A-589 47. Braid 27A-500 27A-500 27A-500 27A-500 27A-500 48. 49. 50. 51. 242A-521 242A-520 242A-520 242A-521 242A-521 55B-502 556-502 556-502 556-502 556-502 49E-552 49E-552 49E-552 49E-552 49E-552 Wafer Contact Spring Spring Holder Moving Arcing Ck>ntact Stationary Arcing Contact 49E-551 49E-551 49E-551 49E-551 49E-SS1 52. Load Terminal 271A-584 271A-507 271A-506 271A-507 271A-506 53. Anti-Bounce Plate 53L-545 S3L-545 53L-545 53L-S45 53L-545 54. Base Moulding 182A-548D 162A-548D 182A-548D 182A-548D 182A-5480 55. Trip Flipper 79A-517 79A-517 79A-517 79A-517 79A-517 56. Trip Coll Assembly 57. Lower Channel 240A-514 240A-514 240A-514 240A-514 240A-514 39A-530 39A-530 39A-530 39A-531 39A-531 58. Finger Spacer 26H-78 26H-503 59. Orawout Contact Assembly 49E-130 49E-519 49E-572(-573 49E-519 60. SLSCam 35A-512 35A-512 35A-512 35A-512 35A-512 61. Ground Stab 49B-274A-1 49B-274A-1 49B-274A-1 49B-274A-1 496-274A-1 62. Lower Flash Shield 13A-566B 13A-566B 13A-566B 13A-566B 13A-5666 26H-503 (FIXED) 49E-574 45. Uppsr Stdtionary Main Contact 49E-555 49E-549 49E-549 49E-549 49E-549 52. LoadTemrinal 271A-583 271A-506 271A-506 271A-506 271A-506 FIGURE 1 /j®® / & SECTION OF H-3 BREAKER Page 3 Except for the mounting the following instructions for 6. Close and open the unit several times to ensure mounted breakers. correct operation. Interlocks should be defeated or be in normal release position, if an undervoltage trip unit is FIXED MOUNTED BREAKERS mechanism will pick up the contacts, and thus avoid discharging the mechanism without its normal contact fixed mounted breakers equally apply to drawout H-3 and HL-3 circuit breakers should be mounted in sheet steel enclosures in accordance with recommended dimensions. The mounting support should be a rigid structure able to withstand the impact caused by the switching operations, without any distortion and undue vibration of the mechanism. POWER TERMINAL CONNECTIONS attached hold it down manually so the spring closing spring load. 7. Manually activate the tripping devices to estaJjIish that they are operable. These devices include manual trip Rg. 2, spring discharge lever Rg. 9, shunt trip Rg. 11 and 12, and undervoltage trip Rg. 13. 8. Check all cable connections to ensure that they are tight. 9. The electrical operation of drawout breakers shouldbe checked in the "test" position. The H-3 and HL-3 terminals are silver plated for maximum joint efficiency and cable connectors must be clean and free from dents or burrs, and bolted securely to the terminals. Poor joints lead to over-heating and subsequent contact deteriorafion, and an eventual failure. Cables or bus connections should be properly supported so as not to transfer any unnecessary mechanical or short circuit stress to the terminals. Any strain which may have no apparent effect initially may after prolonged periods of vibration and shock from normal operation, cause poor contact alignment. Manual Closing The closing mechanism compresses a mainspringwhich is held compressed until released. The handle is rotated counter-clockwise to the vertical position and pushed In to engage the clutch. Rotating the handle ISO" clockwise fully chargesthe spring and as the internal crankpasses through top-dead-centre, rotation is stopped, and held by Meter shunts, resistors, and similar devices which the close release latch. Operation of tftis latch by means of the close push button Rg. 2 in the faceplate releases the spring energy to close the breaker. A multi-tooth ratchet wheel prevents recoil and permits the spring operateat relatively high temperature should be mounted awayfrom the circuit breakerso they do not contribute to charging to be performed in sevet^ short strokes if desired. On frame sizes 1600 amperes and above, the the heating of the unit. handle is a pull-out extension typeforease of operation. Electrical Closing SECONDARY CONTROL CIRCUITS Control circuit wiring, where applicable, should be made in strict accordance with detailed wiring diagrams. Wiring connections, which are made to terminal blocks should be run in a supported and protected manner, so control wiring cannot come into contact with the primary connections. On all electrically operated units the motor charges the spring unit the close release latch engages. The close latch Is operated by a solenoid energized from the push button in the faceplate. Fig. 2 or by a remote button. The closing stroke then follows in a similar manner to that of the manual type described above. A removable handle is provided to permit manual charging of the spring. A mechanical close button similar to that on the manually operated unitis not Included. Emergency operationof the PRE-SERVICE INSPECTION close release latch is accomplished by insertion of a pin Read this instruction manual completely and inspect and through a small aperture in the faceplate. Fig. 2. A suitable pin is provided in the upper end of the manual check the unit in accordance with this manual. charging handle. The following itemsshouldbe specifically checked. BREAKER MAINTENANCE 1. Make a visual Inspection after installation to ensure that no parts have been damaged or forced out of The safe and successful operation of connected ap alignment. paratus depends uponthe proper operation of the circuit 2. Check the door interlock lever for freedom of and inspection. ITie following points require special movement, when supplied. (Fig. 27). 3. Check the main and drawout contacts to see that they are clean and free from foreign material. 4. Check all the control wiring to ensure that it has not been damaged or moved during the installation. 5. Check the single phase protection (when supplied) by breaker. Therefore, it must have regular, systematic care attention. 1. Beforeinspectingor repairing the H-3 or HL-3 be sure it is disconnected from any electric power, either high voltage or control voltage. Also check that the main spring is discharged. If the breaker is electrically operated,turnthe motor isolating switch on the faceplate to the "off" position before tripping the unit to prevent the ' manually raising each tripping plunger in turn on the threetripping coils, Rg. 24. If the unit is closed, itshould trip and the correct indicator should show on the 2. Inspect the operating mechanism periodically and faceplate. (Rg. 2). keep It clean. Page 4 motor from recharging the spring. (Fig. 2). i Y FIGURE 2(A) FACEPLATE FOR ELECTRICALLY OPERATED FIGURE 2(B) FACEPLATE FOR MANUALLY OPERATED LEGEND 1. Open-Closed indicator 2. Front Plate 3. 4. 5. 6. Floating Trim Spring Charged-Discharged indicator Mechanical Operations Counter Emergency Manual Close 9. Gate for Drawout Crank 10. Manual Trip 11. Sensor Tap Setting indication 12. Rating Plate 13. Electrical Control ButtOTis 14. Motor Cut-Off Svfltch 7. Close Button 15. Single Phase indicator and Reset 8. Key Interlock 16. Overload Lockout Reset REMOVING THE FACEPLATE (Fig. 2) MANUALLY OPERATED MECHANISM (Ref. Fig. 3). First remove the four oval head screws located at the corners of the faceplate and remove the faceplate and trim. The four mounting screws located at the base of the enclosure may now be removed and the enclosure withdrawn. When replacing the faceplate and trim it is important that the bevelled edge of the trim be positioned on the side nearest the enclosure door hinge. OIL-SAE 30 1. Alllinkage pivots within the mechanism compartment. 2. Allclosing shaft bearings. 3. Holding pawl pivot (located within the faceplate enclosure-upper left hand corner). 4. Close latch pivot (located below the main ratchet wheel). LUBRICATION Grease-Lubrlplate Lo-Temp. 1. Spring guide pin (located at the lower end of the H-3 breakers have been tested for mechanical endur ance to the prescribed numl>er of operations by ANSI closing spring). 2. Ratchet wheel teeth. standards without lubrication during the tests. No seizing of the mechanism occurred and the breakers were still ELECTRICALLY OPERATED MECHANISM operational. In service It Is possible to encounter dust, corrosive atmospheres and other adverse conditions which may Impair proper operation. Therefore, we consider It prudent to lubricate and dean breakers periodically. ANSI standards recommend lubrication and (Ref. Fig. 3). sen/icing to be carried out at the following periods. In frame sizes 600 and 800 amps this inten/al Is 1750 operations, In sizes 1600 and 2000 amps the Interval Is 500 operations, and in sizes 3000 amps and atxive, 250 operations. The following points should receive attention: Oil-SAE30 1. All linkage pivots within the mechanism compartment 2. All closing shaft bearings. 3. Holding pawl pivot (located within the faceplate enclosure-upper left hand corner). 4. Motor limit switch lever pivot (located with the front channel - left hand corner). 5. Close latch pivot (located below the main ratchet v^eel). Page 5 FIGURES ELECTRICALLY OPERATED LUBRICATION Grease-Lubriplate Lo-Temp. FIGURES MANUALLY OPERATED LUBRICATION 1. Spring guide pin (located at (he lower end of the closing spring). 2. Ratchet wheel teeth. 3. Front face of the ratchet wheel. 4. Oscillating lever - right hand end (at the motor drive cam). 5. Driving pawl pivot and springs (located on left hand end of the closing spring.) CLOSE LATCH ADJUSTMENT (Figs. 6(A) and 6(B)) The function of the close latch is to arrest or hold the ratchet wheel at a point 13 degrees past top-deadcentre. with the spring fully charged in readiness to close. The closing stroke is initiated by release of the latch, either manually by means of the mechanical push button in the faceplate or electrically by means of the close solenoid. Insuffident engagement of the latch may allow the closing stroke to occur at completion of the charging of the spring. Referring to figure 6(A), the adjusbnent procedure for the upper stopscrew is as follows. The ratchet wheel assembly (Item 1) is made up of two m ^ IL plates riveted together. The two plates are held apart by spacers located between the plates on the four rivets. Rotate the ratchet wheel until one of the spacers on a rivet is directly above the nose of the close latch (Item 2). Loosen locknut (Item 3). Turning the stopscrew (Item 4) counter-clockwise adjusts the dose latch up. Adjust the close latch height until there is approximately Vaz inch (0.8 mm) clearance between the spacer and the nose of the close latch. Tighten the locknut securely. Referring to figure 6(B). the adjustment procedure for the lower stopscrew is as follows. Be sure that the main spring is discharged and that the main contacts are open. Loosen locknut (Item 5). Manually depress the close latch (Item 2) until it stops on the lower stopscrew (Item 6). Adjust the close latch height until there is approximately Vsa inch (0.8 mm) clearance between the bottom of the teeth on the ratchet wheel and nose of the close latch. Tighten the locknut securely. LINKAGE X — Oil - SAE 30 Y — Grease - Lubripiate FIGURE 4 MANUALLY OPERATED 1. Ratchet Wheel 2. Holding Pawl 3. Close Latch 4. Auxiliary Switch 5. Spring Guide Pin 6. Solid State Overcurrent Relay m. Page 7 FIGURES ELECTRICALLY OPERATED 1. Ratchet Wheel 2. Holding Pawl 3. Oscillating Lever 4. Close Latdi 5. Shunt Close 6. Motor 7. 8. 9. 10. 11. ml Auxiliary Switch Spring Limit Sviritch Spring Guide Pin Solid State Overcurrent Relay Anti-Single Phase Device and Blown Fuse Indicator FIGURE 6(A) CLOSE LATCH ADJUSTMENT 1. Ratchet Wheel 2. Close Latch 3. Upper Lockout 4. Upper Stopscrew 5. Lower Lockout 6. Lower Stopscrew FIGURE 6(B) FIGURES MECHANISM LATCHING AND TRIP SHAFT ADJUSTMENT TRIP SHAFT ADJUSTMENT Misadjustment of latching results in failure to close, but It does not prevent the closing spring from being compres sed and discharged for closure. S There are 3 possible causes of improper latching: A) On units equipped with an overload lockout or single phase dewce, failure to manually reset the device after it has operated, will prevent latching and the discharge of the closing spring will not move the main contacts. B) Misadjustment of the main linkage will prevent latching with the same result as above. This adjustment controls the engagement of the trip roller with the trip shaft, and also the position of the toggle pin when the main contacts are in the closed position. ':4 y C) Insufficient overlap of the latch roller with the trip cam secured to the trip shaft. This condition will cause the moving contacts to pick up slightly and drop back to fully open position when the closing spring is discharged. To correct A — Push manual reset lever. (Fig. 2). To correct B — Linkage adjustment must be made.(Fig. 7). 1. Locknut This adjustment is accomplished by means of an 2. Adjusting Screw eccentric bolt accessible from the right hand side of the To proceed, isolate the breaker for servicing. Remove mechanism compartment. This eccentric moves the the arc chutes, front flash shield, interphase barriers, toggle pin (Item 5) relative to the slop in the sides of the faceplate assembly, and faceplate box assembly. Be sure the main contacts are open and the main spring Is mechanism compartment. discharged. s FIGURE? LINKAGE ECCENTRIC ADJUSTMENT \ To ensure the main spring is completely discharged, a manual charging handle must be used to remove any spring force on the holding pawl, and driving pawl in the case of electrically operated breakers. Lift the holding and driving pawl away from the ratchet wheel. Releasing the manual charging handle now allows the main spring to completely discharge, with the crank assembly going to the bottom dead centre position, and the spring guide to its lowest point of travel. Next remove the eccentric locking plate (Item 3). Rotate the eccentric bolt clockwise until the closing casting (Item /oV^ I„ I j l(o)l @ 1. Spring Guide Pin 2. Main Spring Clamp 3. Locking Plate 4. Eccentric 5. Toggle Pin 6. Connecting Link 7. Closing Casting 7) pushes the closing pin to within 1/16 inch (1.6 mm) away from the stops in the mechanism sideplates. This can be seen by viewing the mechanism sideplates from ^ove. The locking plate should now be replaced, locating it to the nearest notch. Tighten the retainer nut firmly. In this operation, two wrenches should be used — one holding the head of the bolt at the left hand side — the other tightening the nut at the right hand side. To check the adjustment, close the main contacts. The closing pin should be against the stops inthe mechanism sideplate. If it is not, proceed as follows. With the main spring discharged and the main contacts open, remove the eccentric locking plate. Rotate the eccentric bolt clockwise an amount required to locate it in the next notch of the locking plate. The locking plate should now be replaced and the retainer nut firmly tightened. Return to the checking procedure above. 8. Stop in Mechanism Sideplates To correct C-Latch roller engagement adjustment must 9. Mechanism Sideplate be made. Page 9 FIGURE 10 This adjustment, located on the left hand side of the mechanism compartment, controls the engagement of the trip shaft to the latch roller. If this engagement Is ECCENTRIC ADJUSTMENT insufficient, the roiier may release during the dosing stroke, resulting in faiiure to close. The main contacts wiii appear to move but not compiete the travel. To adjust, the following procedure should be used. With reference to Rg. 8 loosen iocknut (item 1) and turn adjusting screw (item 2) counter-clockvrtse two turns. Close the breaker and slowly turn the screw clockwise until the unit trips. Now turn Ihe screw counter-clocdcwise one and one quarter turns and tighten the iocknut. •-1/52 IN. NOTE: Whenever this adjustment is made the following should be checked if present on the breaker. (•6mm) SEE DETAtL W 1. Latch Check Switch setting on electrically operated breakers (Rg. 16). 2. Shunt Trip Type B striker rod adjustment (Fig. 12). 3. Undervoitage trip striker adjustment (Rg. 13). 4. Drawout gate interlock lever eccentric adjustment on drawout breakers (Fig. 10). 1. Lockout 2. Gap Screw 3. Eccentric SPRING DISCHARGE INTERLOCK 4. Flipper Drawout mounted breakers are fitted vrith a gate interlock to prevent the breaker being withdrawn while the unit is dosed or the main spring is charged. Depressing the gate interlock down to expose the drawout crank opening first trips the breaker then discharges the main closing spring. It should be noted that "empty" discharges of the closing spring stress the mechanism to a slightly greater extent than on normal closure. For this reason it is advisable to avoid additional intentional discharges to those which occur when the breaker is withdrawn and the spring is still charged. drawout lever acting on the close button lever. Fig. 9. SPRING DISCHARGE LEVER - - -- Adjustment of the drawout gale interlock lever is performed as follows. Be sure the trip shaft is rotated down so the left hand flipper is resting against the adjusting screw. Be sure the drawout lever is lifted to its upward position. With reference to Fig. 10 loosen Iocknut (Item 1) and alien head cap screw (Item 2). Using a wrench, rotate eccentric (item 3) until the clearance between the eccentric and right hand flipper (Item 4) on ^ flie trip shaft is approximately 1/32 inch (0.8 mm). Holding the eccentric in position with wrench, tighten alien screw securely. Tighten iocknut securely. Discharging the main spring is accomplished by the FIGURE 9 —iu . - . DETAIL 'A' - • - The lever arrangement requires no adjustment. Depres sing the drawout lever activates the closing latch which discharges the m^n spring. This action results in failure to close, but discharge of the main spring. Whenever trip shaft adjustment is perfoimed (Fig. 8), the drawout gate interlock lever adjustment should be checked. SHUNT TOIP Two types of shunt trip units are available for use on ail H-3 and HL-3 breakers each having specific performance features. The two types are described as follows;— TYPEA(Rg.ll) This unit consists of a rectangular laminated solenoid frame, mounted on the left hand side of the mechanism 1 1 and acting directly on die trip shaft. When used on typical 120 volt ac control, the coil has a continuous rating, with a holding current of only 340 miiiiamperes. This makes possible use of this trip unit without the conventional / 1. Closing Latch 2. Spring Discharge Interlock Lever Page 10 normally open auxiliary switch contact in series with the coil. When used in conjunction with a typical latchingtype ground fault relay the breaker is locked out and wiii be totally trip-free until the relay has been reset Any attempt to reclose the breaker before resetting the relay will preclude a restriking of the ground fault. No FIGURE 12 SHUNT TRIP TYPEB adjustment is required on this device and the only attention needed is that of ensuring that the plunger is \ free of any binding or friction. This unit is capable of :.f y-«4ripping at 50% of the rated voltage. TypeB(Fig.12) This is a cylindrical solenoid mounted within the mechanism compartment at the lower rear and acting directly on the trip shaft. Unlike the Type A unit, it is not continuously rated and for any application a normally open auxiliary switch contact must be used. In the 120 volt ac application the Type B uriit is equivalent in performance to the Type A device (i.e. will operate at 50% of rated voltage) but in the 125 volt do rating, tripping can be perfomied at levels as low as 25% of nominal rating. One adjustment is provided in the Type B trip unit to control the extent of free travel between the plungerand the trip shaft lever. By lifting the plungeruntil the striker rod is lightly touching the trip shaft lever a space of 1/16 inch (1.6 mm) should exist between the end of the plunger and the stop plate as shown in Figure 1. Plunger 2. Stop Plate 3. Mechanism Sideplate 4. Shunt Trip (Separate Trip Source) 12. If adjustment is required, loosen the 8-32 socket head 5. Shunt Trip (USD Relay Trip Source) screw located at the bottom end of the plunger and turn the striker rod within the plunger as required. Retighten the set screw. If trip shaft adjustment (Fig. 8) is altered at any time, this striker rod adjustment should be checked. The shunt trip is identified on the wiring diagram by the symtrol "TC". ^'''^^oth units can be installed on one breaker. With regard _ to use, the following rules are usually adhered to: 1. A Type B is used where only a separate trip coil is required. 2. With USD relay, a Type B is used between the mechanism sideplaies to operate wiUi the relay, and possibly a Type B mounted outside the left hand mechanism sideplate to be used as a separate trip coil. 3. A Type A. mounted only outside the left hand mechanism sideplate, is used only when a continuous rated coil for a separate tripsource is required. 4. Type Aand Type Bused in conjunction with the USD relaycan both be used on the same unit. UNDERVOLTAGE TRIP (Fig. 13) FIGURE 11 The Undervoltage Trip is a spring operated unitmounted SHUNT TRIP TYPE A on the left hand side of the main mechanism compart ment and acting directly on the trip shaft. In operation two springs are held in compression by a rectangular solenoid. • $ Normally supplied in the 120 volt ac rating, the solenoid has a holding currentof 340 milliamperes, with an inrush of 2.45 amperes. A mechanical escapement time delay attachment is available which provides a delay adjusta ble from 0 to 5 seconds. •mo.,- An adjustable striker (Item 1) is provided to control the engagement of the solenoid plunger to the trip shaft. With the solenoid energized and the plunger seated, adjust the striker as required to provide a gap of 5/16 inch (8 mm) between the striker and the trip shaft lever. Tighten locknut firmly. If at any time the trip shaft adjustment (Fig. 8) has been altered the undervoltage striker adjusUnent should be checked. A vernier time adjustment in the form of an eccentric is provided for fine adjustment, independent of the scale setting. If trimming is required, loosen the locknut located on the inside of the lever and turn the eccentric counter-clockwise to increase time, and clockwise to 1. Mechanism Sideplate 2. ShuntTripTypeA shorten time. The locknut must be firmly tightened each time the eccentric is moved. Page 11 No adjustment is required on this unit and the only FIGURE 13 attention needed is that of ensuring that the plunger is UNDERVOLTAGETRIP free of any binding or friction. The device is capable of operating at 75% of rated voltage. . (3 - 0 • ^ • The shunt close is identified on the wiring diagram by the symbol "CC". CLOSING SPRING CHARGING MOTOR All electrically operated units employ a series-wound gear motor, suitable for operation on alternating or direct current, '''he reduction gear compartment is sealed and ' - lubricated for life and the armature bearing similarly o. requires no maintenance lubrication. The basic motor is available in voltage ratings 48, 120,250 dc and 120, 240 ac. In all alternating current applications above 240V a step down control transformer is used in conjunction with the 120 volt motor. A toggle switch mounted in the faceplate permits the motor to be de-energized during maintenance or inspection. (Fig. 2). ' ' •• 0 1. Striker 2. Trip Shaft Lever 3. Timer 4. Vernier Time Adjustment Preferred control circuitry permits spring charging to take place after the breaker has tripped only. While a unit can be supplied to charge after close, this should be used only in applications requiring high speed reclosing. Unless otherwise specified all units are supplied to operate in the "charge after trip" sequence. The charging motor is identified on the wiring diagram by the symbol "M". FIGURE 14 In operation, the undervoltage trip has a dropout of SHUNT CLOSE 35% of rated voltage for 120 V. a.c. and 46% of rated voltage for 240 V. a.c. Both have a pull-in of 85% rated voltage and are identified on the wiring diagram by the syml5ol "27". SHUNT CLOSE (Fig. 14) This accessory is supplied on electrically operated circuit breakers and consists of a rectangular laminated solenoid frame, similar to the Type A shunt trip device. It is mounted within the front mechanism compartment, and its function is that of actuating the close latch to Im initiate the closing stroke. It may be energized by the normally open push button in the faceplate or by a remote push button. In ac ratings the coil is inherently continuously rated and in the typical 120 volt application the holding current is 340 milliamps, with an inrush of 2.45 amperes. For dc operation a holding resistor in conjunction with a plunger operated limit switch again provides a continuous rating. The shunt close unit is fitted with an independent normally closed limit switch, operated by the solenoid plunger. This switch is connected in series with the spring charging motor and serves to render the motor inoperative while the solenoid is energized. Used in conjunction with the conventional "charge after trip" motor operation, this performs the duties of an anti-pump relay. The breaker will not reclose because the spring is retained in a discharged condition. Only when the close signal is removed will the motor operate to charge the spring. Page 12 1. Shunt Close Coil 2. Independent Normally Closed Limit Switch To remove the motor, first remove the bracket assembly from the frame channel, noting the number of shims at the top and iDOttom faces of the motor bracket. The drive cam and outboard bearing should then be removed. The drive cam Is threaded to the motor output shaft and can be readily released by a light tap in the counter-clockwise direction. Remove the hex head bolt holding the front bracket to the motor. Next, remove the mounting screws at the end opposite to the drive and motor housing can be withdrawn from the rear bracket. When replacing the motor bracket assembly in the channel, replace the shims as originally installed. Do not tighten the hex head bolt holding the front bracket to the motor until the screws holding the motor brackets in the front channel have been tightened securely. FIGURE 16 LATCH CHECK SWITCH I I fb' 0 \C-'5 ® )<] MOTOR CLOSING SPRING LIMIT SWITCH (Fig. 15} fe(h® (4 All electrically operated M-3 and HL-3 units are equipped with a limit switch which stops the motor at the end of the charging stroke. The switch Is mounted In the left hand end of the front channel. The switch is coupled with a lever actuator to a cam located on the rear of the crank assembly. As the crank passes through top-dead-centre and the ratchet wheel bearing approaches the close latch, the lever actuator moves to operate the switch and de-energize the motor. The lever actuator is reset when the main spring discharges. No adjustment Is required for the motor closing spring limit switch. LATCH CHECK SWITCH (Fig. 16) The latch check switch is provided on electrically operated units to prevent any attempted electrical close until the trip shaft is completely reset and seated in readiness to close. The switch is connected in series with the shunt close solenoid and prevents operation of the solenoid until the trip shaft is fully seated. Failure of the trip shaft to be completely reset at the beginning of the close stroke will result in a trip free operation. This malfunction can occur In 1. Latch Check Switch 2. Pivot Screw 3. Lock Screw 4. Mounting Plate 5. Trip Shaft Lever With reference to Fig. 16, adjustment of the latch check switch is performed as follows: With the circuit breaker open, loosen pivot screw (Item 2) and lock screw (Item 3). By lowering mounting plate (Item 4) at the front end, engage the switch roller to trip shaft lever (Item 5) until the lever just begins to lift. From this reference point, raise the front end of the mounting plate 1/16 inch (1.6 mm) and tighten both pivot and lock screws firmly. transfer switch installations where one circuit breaker is mechanically interlocked with its companion, and a signal to close enters before the trip shaft has fully returned to its stop. A key interlock or any form of mechanical lockout presents the same set of conditions. In normal operation the latch check switch should require no readjustment, but if at any time the trip shaft adjustment (Fig. 8) is altered, the latch check switch setting should be checked as above. This device Is Identified on the wiring diagram by Uie symbol "LCS". 1. Cam 2. SLS Lever Actuator 3. Spring Limit Swritch FIGURE 15 MOTOR CLOSING SPRING LIMIT SWITCH Page 13 CONTACT MAINTENANCE Examine the main breaker contacts (and disconnecting MAIN MOVING CONTACT DEFLECTION At intervals as recommended by ANSI standards (see contacts on drawout mounting breakers) frequently to see that they are properly aligned and that the contact paragraph on Lubrication), the deflection of the main moving contacts should be checked. The deflection surfaces bear with firm uniform pressure. should be maintained between the limits of 3/64 to 4/64 The contact surfaces of all types of disconnecting or interrupting devices must be kept clean and bright to ensure maximum operating efficiency. Contact surfaces which are corroded by contaminated atmospheres will cause overheating and subsequent failure of the device. The alloy contacts of the type H-3 and HL-3 will resist contamination to a great degree but in areas where sulphur is present or other chemicals which readily combine with silver, regular maintenance is required to inches (1.2 to 1.6 mm) for 600, 800, 1600, and 2000 ampere frame sizes, and 2/64 to 3/64 inches (0.8 to 1.2 mm) for 3000, 3200, and 4000 ampere frame sizes. A gauge is available for measuring purposes which carries a scale graduated in 1/64 inch (0.4 mm) divisions. For the 1600 amp and larger frames use Gauge Number 96A-500, and for the 600 and 800 amp frame use Gauge Number 96A-501. With the circuit breaker open establish the starting or See that bolts, nuts, washers, clips and ail terminal connections are in place and tight, espedaiiy after completion of any maintenance work. "zero" point for each main moving contact assembly. Applythe gauge to the left hand side as shown in Figure 20 (A) and note the position of the pointer. To assist in positioning the gauge the pointer should be moved fonivard or "up scale" then released to allow the indicator When abnormal conditions exist, such as salt deposits, pins to locate as shown. cement dust or add fumes the breaker should be With the circuit breaker closed again apply the gauge as ensure contact efficiency. cleaned at regular intervals. This will prevent fiashovers caused by the accumulation of foreign substances. shown in Figure 20(B), and note the position of the pointer. The number of divisions the pointer has moved from "zero" position indicates the amount of main contact deflection, each division representing 1/64 inch MAIN POWER CONTACTS (0.4 mm) deflection. Main contacts are silver alloy and should be dean, bright When adjustment is required, proceed as shown in Figure 21. Using any suitable blocking device, position the moving contact members toward the closed position as shown and loosen capscrews (Item 1). Shims (Item 2) are added as required to restore deflection to within the limits stated above. After shims are added, it is important that the capscrews be finnly tightened before closing the and free from pitting. They may be gently sanded if necessary using a fine emery to remove pit marks. Avoid having particles fail into the mechanism, and wipe contacts clean with doth after sanding. If the main contacts are severely damaged make a careful inspection of ail current carrying parts. Supporting pins, linkage, and especially springs should be examined for damage due to excess heat. Annealed or distorted parts should be replaced. Before attempting this, consult unit in the normal manner. A supply of shims is included with tire gauges. the manufacturer. FIGURE 17 CONTACT DIFFERENTIAL ADJUSTMENT CONTACT DIFFERENTIAL (Fig. 17 and 18) At intervals as recommended by ANSI standards (see paragraph on Lubrication), the differential between the main and arcing contacts should be checked. The y-® (SK differential should be maintained between the limits of 0.050 to 0.065 inches (1.3 to 1.6 mm). Using the slow close device (Fig. 16 (A)) close the contacts until the moving arcing contact touches the stationary arcing contact (Fig. 16 (B)). A gap of 0.050 to 0.065 inches (1.3 to 1.6 mm) between the main moving wafer contacts and the main upper fixed contact should exist The gap is checked using a feeler gauge. If adjustment is neces sary, shims (Fig. 17, Item 4) are placed between the stationary arcing contacts and the main upper fixed contact. This is done by removing the stationary arcing contacts. Shims are available from the manufacturer (Part Number 241A-500). Note that it is not important nor necessary that the arcing contacts touch simultaneously. The differential should be measured on each pole by closing the contacts until the arcing contacts touch on the pole being measured. Contact differential should always be checked before main moving contact deflection. Page 14 V4-20XVa Inch Long Hex Bolt and Lockwasher V4-20 Hex Nut and Lockwasher V4-20 X1 inch Long Hex Boltand Lockwasher Shim V4-20 X=»/4 Inch Long Hex Boltand Lockwasher FIGURE 18(A) SLOW CLOSE DEVICE / V 1. Closing Shaft Lever 2. Slow Close Device FIGURE 18(B) SLOW CLOSE DEVICE 1. Closing Shaft Lever 2. Slow Close Device 3. Feeler Gauge SLOW CLOSE DEVICE removing the two 1/4-20 hex-head bolls on each side of A slow dose maintenance device is available which can be attached to the drcuit breaker to permit slow the chute. The chutes mate with the upper base and can be lifted clear to expose the ardng contacts. A lower flash shield mountedto the upper stationarymaincontact operation of the contacts and closing mechanism. The device is available from the manufacturer, FPE Part No. 115G-514. As shown in Rgures 18 (A) and 18 (B) the tool is attached to one of the lever arms of the dosing shaft The slow dose device requires no attaching bolts below the stationary contact can also be removed to expose the silver contact surfaces of the main contacts. This shield protects the main contacts during arc/'^S, interruption. The arc chute may discolour from arc interruption but will not need replacement unless heavy deposits of arc material are present or parts are distortedor cracked. and can be installed and removed with ease. ARCING CONTACTS (Fig. 17) Arcing contacts are subjected to pitting every time the circuit breaker interrupts currentand shouldbe inspected at regular inten/als if the unit is operated frequently. They should always be inspected after the breaker has interrupted a short circuit and should be replaced If they are showing serious pitting and loss of contact material. To remove the fixed ardng contacts from the drcuit breaker take out the two hex-head machine screws (Item 5) at the base of each fixed contact To remove the moving arcing contacts simply take out the two hex-head machine screws which hold each contact in the assembly. Note that the braid is attached to the contad by the lower hex-head screw (Item 3). Remove the nut and lockwasher (Item 2) at the rear of the assembly first before removing this lower screw. When repladng, tighten the lower screw (Item 3) firmly to attach the braid to the moving ardng contact before replacing the lockwasher and nut (Item 2) at the rear of the assembly. When repladng ardng contacts, be sure to retrieve ail hardware Items and assemble as originally installed. Whenever repladng ardng contacts inspect the braids and replace them if they are discoloured or strands are broken. ARC CHUTES The arc chutes are made of fiberglass reinforced polyestermaterial. They may be removed individually by OVERLOAD PROTECTION (Fig. 22) Type H-3 and HL-3 breakers are normally supplied with solid state overload protection. The solid state overcurrent trip system protects low voltage power systems against damage caused by overloads and faults. The types of protection offeredare overload,short drcuit and ground fault. Zone selective instantaneous protection (ZSIP) is also available. The trip unit operates to open a low voltage circuit breaker In accordance with a set of programmable time-current characteristics. Tripping energy for the operation of the circuit breaker is obtained solely from the drcuit being protected. Other power sources are not required, except for fault indication. The complete solid state overcurrent trip system consists of the primary current sensors, the overload relay, and the direct acting shunt trip solenoid. Each sensor is available with changeable tap settings to suit the rating of the breaker. Note — Sensor tap settings must not be changed while power is flowing through the breaker. When the sensor tap settings are altered, the sensor tap setting indication on the breaker faceplate (Rg. 2) should also be changed. Turning the screw to the right of the Indication rotates a dial behind the rating plate until the correct tap setting indication is given. The direct acting shunt trip solenoid Is a Type B shunt trip, mounted between the mechanism sidb- DEFLECTION GAUGE FIGURE 19 MOVING CONTACT DEFLECTION MOVING CONTACT ASS'Y B SPACER I [/ T I ©iFBicD Page 16 m ^ FIGURE 20(A) MOVING CONTACT DEFLECTION 1. Moving Contact in Open Position 2. Deflection Gauge FIGURE 20(B) MOVING CONTACT DEFLECTION 1. MovingContact in Closed Position 2. Deflection Gauge r* Page 17 OVERLOAD LOCKOUT DEVICE {Fig. 23) FIGURE 21 The overload lockout device prevents reclosing of the breaker either manually or electrically after the breaker MOVING CONTACT ADJUSTMENT has been tripped by the overload relay, unti this device Is manually reset. Two micro switches with normally open contacts are also available to act as overload alarm contacts. The direct acting shunt trip solenoid plunger mechani cally holds the closing mechanism in the trip-free position thus preventing closing of the main contacts. The latch check switch wired in series with the closing coll is open In this position, preventing any attempted electrical operation of the closing coil. O The device is reset by pushing the manual overload lockout reset button on the breaker faceplate (Fig. 2). This reset button is spring loaded and returns to its normal position. 1. ®/i6-18 X1 Inch Long Hex Bolt 2. Shim FIGURE 23 plates. One adjustment is provided to give a space of 1/16 inch (1.6 mm) between the end of the plunger and the stop plate on the trip shaft. If adjustment is required, refer to the section entitled Shunt Trip, Type B (Fig. 12). OVERLOAD LOCKOUT DEVICE Many H-3 and HL-3 type breakers have been supplied with the SO type solid state relay. This relay has been replaced in manufacturing by the USD type solid state relay. The USD relay Is an improved design incorporating many features not available on the SD relay. For complete details of the SD relay refer to instruction manual C-3-216-2. For complete details of the USD relay refer to instruction ?!! manual C-3-217-2. FIGURE 22 ^(3 D j TYPE USD SOLID STATE RELAY • ur 1. Overload Lockout Reset 2. Reset Spring 3. Shunt Trip (USD Relay Trip Source) 4. Overload Lockout Flipper 5. Overload Alarm Contacts ""It li? 01 FUSE MOUNTING — HL-3 ONLY , V. ?,.J All HL-3 circuit breakers in frame sizes up to and Including 4000 amps have provision for mounting NEMA HRC fuses, mounted on the line side on a frame extension at the rear of the unit. As an option, in ratings of 3000 and 4000 amps, a separate fuse truck is available used in conjunction with a standard circuit breaker. Key interlocking Is provided to ensure that the circuit breaker is open before the fuse unit Is withdrawn. The fuse unit is equipped with a rejector feature which ' w Page 18 prevents entry of the fuse unit into the breaker cell. In all applications the circuit breaker is equipped with anti-single phase protection. HL-3 Frame Rating (Amperes) Relay Rating (Amperes) Maximum Fuse Rating (Anperes) supply voltage in excess of 250 Is to be used, the higher voltage contacts are double spaced (I.e. the adjoining contact Is unused). 1600NEMAL 1600 NEMAL 3000NEMAL 3000 NEMAL 4000 NEMAL 6000 NEMAL ANTI-SINGLE PHASE DEVICE AND BLOWN FUSE AUXILIARY SWITCH (Fig. 5) On all H-3 and HL-3 units a multi-section rotary switch Is used. It is coupled directly to (he closing shaft and operates on a snap-action principle which provides quick break switching. No adjustment is required and the switch is available in the following contact arrangements. INDICATOR — HL-3 BREAKER ONLY (Fig. 24) 4-pole, providing 2 normally open and The anti-single phase device is supplied on all frame sizes. The unit consists of three trip solenoids each acSng upon an independent slide, which in turn acts directly onto the trip mechanism. When activated by the 6-pole, t2-pole, 16-pole, 20-pole, solenoid, Uie slide moves forward and latches in this The following contact ratings apply. position, thus locking the breaker in a trip-free state. Each solenoid coil is connected In parallel across the corresponding power fuse and in normal operation the trip coil Is, in effect, shorted out. The slides are colour coded, red, yellow and blue and when tripped they protrude through an aperture in the faceplate (Ret. Fig. 2), thus providing a blown fuse indicator. Red indicates the left hand phase, yellow centre and blue right hand. To reset, the slide is lifted and pushed in at the faceplate opening. The breaker cannot be redosed until the anti-single phase device and blown fuse indicator is reset. Two coil voltage ratings are available, one for system voltages 240 or less, and one for systems 480 to 600 volts. The coils are identified by colour coded leads — the 240 volt carries blue leads, the 600 volt rating is fitted providing 4 providing 6 provldng 8 providing 10 normally normally normally normally open open open open 2 normally dosed. and 4 normally closed. and 6 normally closed. and 8 normally closed. and 10 normally closed. 10 amperes up to 254 V.a.c. 1 ampere at 250 V.d.c. 2 amperes at 125 V.d.c. FIGURE 24 ANTI-SINGLE PHASE DEVICE |P> ^ I '1 vs with red leads. A simple mechanical check of the unit can be made by raising each plunger by hand to observe movement of the corresponding slide and rotation of the trip shaft. The plunger must be raised firmly against the intemal stop to ensure that full travel Is achieved. An electrical test may be performed by means of a single phase variable ac source. 250 va or larger. The test signal is applied directly to the trip coil terminals after first disconnecting one of the connecting leads. This is necessary to isolate the trip coil from the power fuse. TTie 240 volt coil should operate at approximately 50 volts and the 600 volt rating at approximately 100 volts. In this test It should be noted 1. Solenoid 2. Slide that these coils are short-time rated and In normal 3. Trip Shaft operation are de-energized the Instant the breaker 4. Blown Fuse Indicator opens. A preset voltage and a momentary on-off switching action is recommended. Do not sustain the test power after the coil has operated. , •T SECONDARY CONTROL CONTACTS (Fig. 34) MECHANICAL OPERATIONS COUNTER (Rg. 25) Secondary control contacts are provided on drawout units to automatically connect or disconnect control circuits, as the circuit breaker moves through its positions In the cradle. The contacts are designed such that the control circuit can be energized or isolated in the test position. These connections can be altered In the field, when required, by means of jumpers between contacts of A five digit mechanical counter can be supplied. It is mounted in the faceplate of the breaker (Fig. 2). the stationary block. This device is mechanically driven by the "charged- discharged" indicator. The counter operates once for each charging of the breaker main spring. No adjustment or maintenance is required for successful counter operation. Supplied In multiples of 8 contacts, a total of 48 can be provided, and each contact has a continuous current Operations counters are recommended where breakers rating of 30 amperes, in applications where a control the recommended maintenance intervals. will be subjected to frequent operations as an indicator of Page 19 FIGURE 26(A) MECHANICAL INTERLOCK FIGURE 25 MECHANICAL OPERATIONS COUNTER I* ^ DrSCHARGEDl 3l» CLOSE I Qm\H I DU V9IU' LC OISJOSCUU^ 1. Breaker Frame 2. Upper Plunger (Connected to ClosingShaft) 3. Lower Plunger (Connected to Trip Shaft) MECHANICAL INTERLOCK (Fig. 26) FIGURE 26(B) Mechanical interlocks are available on all H-3 and HL-3 MECHANICAL INTERLOCK breaker frame sizes. They are used to mechanically interlock breakers in a two or three breaker transfer scheme. In the case of a two breaker transfer scheme, mechanical interlocks ensure only one breaker is closed while the other is held in a trip free position. In a three breaker transfer scheme, mechanical interlocks ensure only two breakers are closed while the third is held In a J trip free position. Jl) Mechanical Interlocks connect with flexible cable the pi closing shaft of one breaker to the trip shaft of a second breaker, and vice versa. If one breaker is closed, the other breaker Is held in a trip free position. Drawout breakers are interiocked by cable connections between the two cradles. There are no permanent connections between the breaker and matching cradle when interlock ^ ing is supplied, so the breaker can be freely withdrawn t « from the cell. Mechanical interlocks are operable only .J when the breaker is in the connected position. When withdrawn to the test position, breakers are not interlocked and can be test operated in the normal manner. Mechanical interlocks are preset at the factory and require no adjustment. The plungers at the rear of the breaker should be checked for freedom of movement at intervals as recommended by ANSI standards (see paragraph on Lubrication). With the breaker removed from the cell, manually close the main contacts using the slow close device (Fig. 18). With reference to figure 26 (a), the top plunger at the rear 1. Breaker Frame 2. Cradle Frame 3. Upper Flipper 4. Lower Flipper 5. Cable Connections to Lower Cradle DOOR INTERLOCK (Fig. 27) All H-3 and HL-3 circuit breakers may be fitted with a device which acts to trip the unit when the cell door is of the breaker connected by cable to the closing shaft should move freely with movement of the closing shaft. Next, charge the main spring and close the breaker. Pushinginon the lowerplunger at the rear of the breaker should open the main contacts. If the plungers do not move freely, the cable must be removed from the sheath opened. In operation, the door lever acts internally on the mechanical trip button causing it to move in towards the faceplate. This interlock may be defeated by arresting the movement of the trip button. A screwdriver blade or and cleaned to restore free movement. breaker. Page 20 similar tool inserted through the slot in the trip button will allow the door to be opened without tripping the circuit CELL SWITCHES (Fig. 29) FIGURE 27 DOOR INTERLOCK Cell switches mounted in the cradle can be provided when required to serve as position indicators or external electrical interlocks. The switches are operated when the breaker is moved from the test to operating position in the enclosure. Each switch contains one normally closed and one normally open contact. A total of six switches can be supplied. These contacts are rated 10 amperes up to 300 V.a.c. FIGURE 29(A) CELL SWITCHES (600, 800, 1600 & 2000 AMP) m KEY INTERLOCKS (Fig. 28) Type VP key interlocks single or double lock with 3/8 Inch (9.5 mm) projection can be provided. They mount with 3/8-16 screws behind the breaker faceplate. Key interlocks can be installed in the factory. Provision is made for key interlocks on all frame sizes. The lock plunger engages the tapered section of the manual trip button when the key Is removed. With the key removed the dosing mechanism Is completely trip free thus preventing ciosing of the main contacts. For electrically operated units an auxiliary switch contact is provided to operate in conjunction with the Interlock to Isolate the closing circuit. 1. Breaker Frame 2. Cradle Frame 3. Operating Bracket 4. Cell Switches FIGURE 28 KEY INTERLOCK FIGURE 29(B) CELL SWITCHES (3000, 3200 & 4000 AMP) FEDERAL P ONEE POLES VOltS 'R. SIZE RELAY NT.CAP. CONtAai.C CONTROL FREO. 1. Cell Switches 2. Cradle Bus Pan 3. Ground Stab 4. Shutter (In Open Position) Page 21 For the 2000 ampere H-3 and for the 600, 800,1600 and SHUTTERS (Fig. 30) Shutters are available for all frame sizes up to and including 3200 amperes for both line and load side main plug-in contact stabs. For the 600, 800, 1600, 3000, and 3200 ampere H-3 frame sizes, shutters are of the lifting type shown In figure 30 (A). They have a padlock bracket In the bottom of the enclosure for locking In the down position. When the breaker moves from the test to operating position, shutter bolts on the frame of the breaker lift the shutter to expose the main plug-In contacts. 2000 ampere HL-3 shutters are of the splitting type shown In figure 30 (B). When the breaker moves from the test to operating position, shutter bolts on the frame of the breaker open the shutter to expose the main plug-In contacts. The shutters do not require field maintenance. REJECTION FEATURES (Fig. 31) Rejection features are provided on all frame sizes. The rejection feature prevents entry of a breaker into an enclosure of a different frame size. Pins on both sides of the breaker frame match slots cut in brackets mounted FIGURE 30(A) SHUTTERS on both sides of the cradle. asi atf (T) If the cradle is a different frame size than the breaker, the breaker pins will not match the slots cut In the cradle brackets. Entry of the breaker Into the wrong frame size enclosure Is then prevented. FIGURE 31 REJECTION FEATURES 1. Cell Switches 2. Secondary Control Contacts 3. Ground Stab 4. Shutter Mechanism 5. Padlock Bracket FIGURE 30(B) SHUTTERS 1. Breaker Frame 2. Rejection Pin 3. Rejection Bracket 4. Cradle Sideplate LIFTING DEVICE (Fig. 32) uunjvaiM'M'Jir D A lifting device is available from the manufacturer for all frame size breakers. The lifting device is a one-piece yoke which fits Into lugs on the breaker sideplates. This permits safe removal of the breaker from the enclosure drawout tracks. Lifting yokes are ordered as follows; Part Number 26G-542 for 600,800,1600 and 2000 ampere H-3"s. Part Number 26G-151 for 3000,3200 and 4000 ampere H-3's. 1. Cell Switches 2. Secondary Control Contacts Part Number 26G-601 for 600,800,1600 and 2000 ampere HL-3's. 3. Ground Stab 4. Shutter Mechanism 5. Shutter Page 22 Part Number 26G-603 for 3000 and 4000 ampere HL-3's. < FIGURE 32 LIFTING DEVICE lU'' f l«. FIGURE 33 COIL DATA Rated Control Voltage Shunt Trip Type A Minimum Operating Voltage 120 AC 240 AC 48 DC 125 DC 250 DC 120 AC Shunt Trip TypeB 240 AC 48 DC 125 DC 250 DC 120 AC 240 AC 48 DC 125 DC 250 DC Unden/oltage Trip Anti-Single Phase Device 120 AC 240 AC 240 AC 480 AC 600 AC 120 AC Charging Motor 240 48 125 250 AC DC DC DC Page 23 SPARE PARTS (Fig. 34) By the nature of its application and its switching capability spare parts for the circuit breaker should nomn^iy not be required. If Uie unit is going to be used for frequent load switching, then the parts shown on the recommended spare parts list shouid be carried in stock. When ordering spare parts, the compiete natiepiate data, especially the breaker serial number, shouid be provided to ensure that the correct parts are supplied. FIGURE 34 SPARE PARTS MAIN DRAWOUT CONTACT ASSEMBLY MAIN DRAWOUT CONTACT ASSEMBLY (4000 Amp) (600 & SOD Amp) MAIN DRAWOUT CONTACT ASSEMBLY (1600. 3000 & 3200 Amp) MAIN DRAWOUT CONTACT ASSEMBLY (2000 Amp) I STATIONARY ARCING CONTACT ASSEMBLY Page 24 \ -U.- MOVING ARCING CONTACT ASSEMBLY ARC CHUTE ASSEMBLY MAIN MOVING CONTACT (WAFER ASSEMBLY) SPACER FOR WAFER ASSEMBLY (OUTER) ARC CHUTE LOWER FLASH SHIELD SPACER FOR WAFER ASSEMBLY (INNER) MAIN MOVING CONTACT SPRING MAIN BRAIDS CHARGING MOTOR MAIN MOVING CONTACT SPRING GUIDE nci -:::i SOLENOID COIL SHUNT TRIP TYPE A UNDERVOLTAGETRIP SHUNT CLOSE SOLENOID COIL SHUNT TRIP TYPE B ANTI-SINGLE PHASE DEVICE LIMIT SWITCH SECONDARY CONTROL CONTACTS CENTRE STATIONARY MAIN CONTACT (1600, 2000, 3000, 3200 & 4000 AMP) i.'•o "i UPPER STATIONARY MAIN CONTACT (1600, 3000 & 3200 AMP DRAWOUT) UPPER STATIONARY MAIN CONTACT CENTRE STATIONARY MAIN CONTACT (1600, 3000 & 3200 AMP FIXED, (600 & 800 AMP) ALL 2000 & 4000 AMP) UPPER STATIONARY MAIN CONTACT UPPER STATIONARY MAIN CONTACT (600 & 800 AMP DRAWOUT) (600 & 800 AMP FIXED) FEDERAL PIONEER LIMITED Offices in principal cities across Canada ••;.V-—•••- :——i-. •-r. jr;,j,.ir^. • :i, .r FEDERAL • '. • '. •:: •' • IP I O N E E R K'^SISIvF .t^-iii-ilr-'^-'ai:--;-- •r. » > :!• • .! 'tj USD Solid State Relay The USD relay provides full overcurrent protection for modern electrical installations. introduction The USD solid state overcurrent relay is Federal Pioneer's latest generation of solid state protective relays. The USD is a self powered device which obtains its energy from the current through the breaker being controlled. No auxiliary power supply is required for tripping. The relay protects low voltage power systems against damage through the operation of JO*e otftHcuaHtw Btiiv .1 'ilK- • • its overload, short circuit and fjls " Sr . • ground fault circuitry. Zone Selective Instantaneous Protection (ZSIP) is also available as a standard feature on USD relays equipped with ground fault elements. The Federal Pioneer type H-3 and HL-3 air circuit breakers are supplied with the USD relay as a standard feature. Description The USD overcurrent protection package is comprised of a 3 phase USD relay, current sensors and a high input energy direct acting solenoid type shunt trip. In the case of a 3 phase 3 wire system 3 sensors are mounted in the breaker. On a 3 phase 4 wire solidly grounded system a fourth sensor is required for ground fault protection. Available Relay Models There are two basic types of USD relays, the USD-3 and the USD-6. The features of these relays are listed below. Reiay USD-3 Features Long Time, Short Time and Instantaneous. USD-3IR As USD-3 -r local indication and contacts for remote indication. USD-6 Long Time, Short Time with ZSIP, Instantaneous and Ground Fault with ZSIP. USD-6IR As USO-6-f local Indication and contacts for remote indication. ZSIP® Selectivity between main and feeder breakers is conventionally obtained by using time co-ordinated trip devices, with the device furthest downstream set for minimum time delay. The disadvantages of this method are that fault levels increase in zones closer to the main breaker and the time to clear these faults increases. The power system must withstand these high fault current levels until the time delay on the first device upstream of the fault expires. With ZSIP® the trip device that senses a fault in its zone of protection trips instantaneously, minimizing system damage. The USD relay also sends a restraint signal to all upstream devices and causes them to operate according to their time co-ordinated protection mode, increasing service continuity. ZSIP® is available on the short time and ground fault elements of the USD relay. Local and Remote Indication Local indication is by long-life LED's on the relay faceplate while remote indication is facilitated through a set of dry contacts which can be connected to remote annunciating or alarm devices. 120 volt a.c. 2.5VA control power is required. USD Solid State Relay Figure 2 — Remote Indication and ZSIP Connections for USD-6IR USD Relay Models s <0 S 6 O Q (A CO CO 3 3 3 n n Q CO Characteristics 3 LongTime , • USD RELAY OPENING ON LEFT HAND SfOE OF RELAY • • • Elements CONNECTOR HARNESS Short Time Elements CATALOGUE NO. USO«((U4 • • COLOUR CODED IS OA. WIRES 1 TYPE TEW. 600V INSUt IDS CU AU WIRES ARE LOOSE ANO without ZSIP* 7S CNCMESLONG. Short Time Elements • • • • • • with ZSIP* Instantaneous 0 , • Elements PROMT VUW Ground Fault Elements with ZSIP* piNNa Local and Remote Indication coioua OfWKtt • • CONTROL POWER IJOVSOHtZSVA *Add the following sufTixes: — 6 for use with CUD 1.5 and CSD^ sensors — INST./S.T. — 8 for use with CSD-8 sensors CONTACT RATING 4 AMP 120 VAC 4AMP24VDC B—0 16 for use vwth CSD-16 sensors El—0 B—H - 20 for use with CSD-20 sensor — 32 for use with CUD-30 and CUD-32 sensors RESTRAINT CN RESTRAINT OUT ZSIP RESTRAINT SIGNALS RESTRAINT COM — 40 for use with CUD-40 and CUD-60 sensors Figure 1 — USD-6IR Faceplate Layout 30*.COVeBCU»BewTRUjyTy>EUSO «csn •mli.T 4 Relay Operation The USD relay Is comprised of current matching transformers, a power supply, logic circuitry, The relay has 4 elements which operate independently and perform the various protection functions. They are: Short Time, thumbwheel switches, and the Long Time, Instantaneous and Ground Fault The pickup settings output pulse generator. These components are housed in a single LT. and/or time bands are field SI metal enclosure. Interconnection of selectable by means of thumbwheel switches located on 5:6 the USD relay with the primary current sensors and the shunt trip solenoid is accomplished through OlGOCaiE? 4 4 Mutrwicsor 4 MC unvNTsiucnoH T. 0 T, 0 G 0 N 0 a labelled terminal block mounted on the faceplate of the relay. Connections for the control power local indication, remote indication and the Zone Selective C 0 Instantaneous Protection (ZSIP) is 0 0 A 0 accomplished by means of a colour coded wiring harness. The harness is attached to a 10 pin connector that plugs and locks into the left hand side of the relay enclosure. This connection is shown in Figure 2. the relay faceplate. The pickup and time delay settings are factory programmed and calibrated in • discrete settings for repetitive accuracy and precision. Gold plated contacts are used on the thumbwheel switches for selecting settings, assuring long lasting positive electrical performance. 3 I USD Solid State Relay Selecting Settings Figure 3 — USD Relay Functional Block Diagram Thumbwheel switches for selection of current pickup levels and time delays are provided on the relay faceplate, grouped in a vertical column, and paired according to tWST. PtCK.UP O.F.TRtP CONTROL the characteristic controlled. CURRENT Adjacent to each knurled thumbwheel switch is a setting table which correlates the setting LONG TIME PtCK-UP LONG TIME delay SHORT number on the switch face (0-9) TIME delay with the actual setting. CURREPIT The use of thumbwheel switches provides positive factory calibrated settings, which are immune to "drifting" in service. SHORT TIME PtCK'UP BYPASS DLY IF NO RESTRAINT LOGIC POWER SUPPLY MONTTOR t Long Time C.F. PtCMJP BYPASS OLY The pickup setting is adjustable IF NO RESTRAINT from 0.6 to 1.1 times the current sensor tap setting with calibration points at 0.6,0.7,0.8,0.9,1.0 and 1.1 times. Pickup tolerance is ±8%. Time delay is adjustable from 2 seconds to 30 seconds with 10 zsv ZSIP SICNAL ENCODER StONAl DECODER restraint OUT RESTRAINT tN calibration points at 2,4,6,8,10, 14,16,22,26 and 30 seconds. The The definite time delay The tolerance is ±10% of the sensor tap setting with calibration points at 4, 5,6,8,10 and 12 times. There is also an "off" position on time shown. the selector switch. With this current level is adjustable from 0.08 to 0.32 seconds with Short Time setting the instantaneous element will not pickup unless the breaker The pickup setting is adjustable closes on a fault that exceeds 13 0.20, 0.26 and 0.32 seconds. When from 2 to 10 times the current times the sensor tap setting, in sensor tap setting with calibration points at 2,3,4,6,8 and 10 times. Pickup tolerance is ±8%. The Short Time delay characteristics are which case a discriminator will operated in the ZSIP mode tripping will be instantaneous (.02 sec.) unless the relay is operating in the back up TCP (Time Coordinated time intervals shown are at 6 times the current sensor tap setting. initiate the tripping. Pickup tolerance is ±8%. has an inverse time characteristic. characteristic at the 10 times calibration points at 0.08, 0.14, Protection) mode. The tolerance is adjustable from 0.11 to 0.45 Ground Fault seconds with calibration points at There are 6 models of USD-6 (IR) 0.11, 0.25, 0.33 and 0.45 seconds. The band width is ±10% of the ±10% of the times shown. Figure 4 feature on all relay types. When relay which have varying ground fault pick-up levels. This allows you to match the relay and sensors in order to comply with the 1200 amp max. rating specified by electrical short time ZSIP is selected and the codes. The various models are fault is within the relay's zone the relay trips instantaneously shown in Figure 4. USD-6(IR)-16 .20. .30. .40, .50. .60, .70 (0.05 seconds). The ground fault element has a definite time delay characteristic USD-6(IR}-20 .20. .25, .30, .40, .50, .60 USD-6(IR)-32 .20. .22. .24, .28, .32, .36 USD-6(IRM0 .20, .22, .24, .26, .28, .30 times shown. In addition an Pt function is available as a standard instantaneous for fault currents in excess of 10 The pickup setting is adjustable times the sensor tap setting. For from 4 to 12 times the current fault currents below this value it Catalogua Pick-Up Number LavoIs USD-6(IR)-6 .25, .50, .75,1.0,1.5,2.0 USD-6(IR)-8 .25. .50, .75.1.0.1.25,1.5 ^ USD Solid State Relay ZSIP Mode Selection Figure 5 — Characteristics of Current Sensors A faceplate mounted rotary switch allows selection of ground fault 7 9 4 9 •91919 10 M 40 90001 isag B a§S§g§8§ §ll§§i and short time operating modes. Local and Remote Indication When a fault of sufficient magnitude occurs on a circuit the USD relay will trip its associated circuit breaker. Identification of the fault is very important due to the different procedures which should be followed, (before the breaker can be reclosed), if the breaker trips on overload, short circuit or ground fault Normally in the case of an overload tripping, the breaker can be reclosed safely, but with short circuit and ground fauit tripping, investigation is required to locate and repair the fault before reciosing the circuit breaker. CU0-1.S CSD4 \i CSM CSO>t9 y»pcal indication is provided by ' frtoo 199 .119 CrlSO 190 .230 C9S0 0499 0900 10 90 lie J911 0400 99 .113 0600 180 .199 OtfiO ue 2X7 01009 199 01309 339 01M9 919 M MS 430 .199 t«0 .830 O1390 8M 09000 199 .130 JB30 01200 840 200 oooo CStMO ng life LED's located on the relay .110 faceplate. These LED's require 120V A.C. control power and they indicate which element of the relay has been operated. Indication LED's are considered superior to CUfrSO "pop-out" mechanical indicators as they provide high visibility indication and positive reset. •THE SECeWOMtToTuiSewlORS 1$ RATIO• AMWtSFORAa 1*9 03909 499 519 09009 600 181 c>ifieQ &3COO c-noe &taoo €•9000 C-woo C4000 snrucGs 9 4 9 « 19910 >0 so IT 40 «,«saas g I |_s! The LED's will stay on until the relay is reset or control power is interrupted. Sensors For remote indication, 3 sets of dry contacts which can be connected special application 5 amp output to a remote annunciator or alarm secondary units which mount on device are provided. There are also the primary conductors of the air separate contacts for remote circuit breaker. These sensors then indication of overload, short circuit supply the fault detection logic circuitry of the USD relay with a current signal, through matching transformers provided in the relay. This signal is also supplied to a regulator in order to provide a power source to the USD relay's and ground fault. The contact is rated 4 amps, 120V AC and 4 amps, 24V DC and is terminated at the socket on the left hand side of the relay. - ^ The Federal Pioneer sensors are electronic circuitry. The core of the current sensor is manufactured with a high quality grain oriented siiicon steel alloy. The core is tape wound and then encapsulated with polestigiass to provide moisture protection. The sensors have two or three tap settings (according to the rating). The same relay can be used for each selectable tap, thereby, the trip rating of the breaker can easily be changed by simply changing the sensor taps. 5 I USD Solid State Relay CUD current sensors have field adjustable tap settings which allow simple alteration of the breakers trip rating. Shunt Trip . - , , The high input energy direct acting shunt trip is a cylindrica! solenoid which is mounted in the circuit breaker in such a way that the plunger is held in the reset position by gravity. The USD relay, while operating in the trip level, provides a pulse with an initial voltage of 140V. When this trip pulse is supplied to the solenoid, the plunger travels free striking the trip lever of the air circuit breaker. ipi Relay Testing The USD Relay has a test plug mounted on the faceplate which is used to connect a (type DDT-USD) Test Set or a metering device in order to run a complete operational test on the relay. This unit also checks the output tripping energy provided by the relay to the shunt trip. The Test Set is plugged into a convenient test plug Figure 6 — Current Sensor Size and Ampere Taps provided on the faceplate of the Sensor Taps Type Available Federal Pioneer Breaker Frame relay. The pinout of this test plug is as follows: CUD-1.5 CSD-6 CSD-8 CSD-16 100.150 250,400. 600 400. 600,800 1000.1200, 1600 CSD-20 800. 1200.2000 CUD-30 1200, 2000. 3000 600A 30H-3. 62H-3 800A 1600A 2000A 30H-3, 42H-3 50H-3, 65H-3 50H-3, 6SH-3 30H-3. 42H-3 1600A 30H-3. 42H-3 SOH-3. 65H-3 2000A 50H-3, 65H-3 Ground Fault Positive Input 800A 1600A 2000A 30H-3. 42H-3 Overcurrent Positive input 50H-3. 65H-3 50H-3, 65H-3 50H-3. 65H-3 CUD-6D 1600,3000,4000 5000. 6000 Long Time Pickup/Inhibit 8 Ground Fault Pickup/Inhibit Overcurrent Trip Inhibit 50K-3 4000A 6000A 100H-2 3200A SOH-3 75H-3 100H-3 100H-2 6000A IOOH.3 100H-2 6000A 100H-2 4000A Short Time Pickup/inhibit 75H-3 50H-3 75H-3 100H-3 4000A 6000A Instantaneous Pickup/Inhibit 50H-3, 65H.3 1600A 3000A 3000A Ground Fault Signal 60H-3. 65H-3 2000A 3200A CUD-40 Overcurrent Signal 600A 3200A 1600,2000.3200 Signal 800A 3200A CUD-32 Pin 10 Logic Common 11 Ground Fault Trip Signal (Delay) 12 Overcurrent Trip SignaUDeiay) USD Solid State Relay The DDT-USD test set allows on-site testing of USD relay characteristics. Special Applications The USD relay can be modified to suit custom applications. For further details consult Federal Pioneer. The following special application models are available without custom engineering. tia25m:.=ii. amt ^ttttrrnn If Marine Version The USD relay is available for marine applications under the following catalog numbers, iiifarifiiii ' "^V'''* yrf-nViTtf- rl| .if? P' I I ».^. I USDM-21, USDM-3, USDM-3IR. These models are specially constructed to withstand the rigours of marine duty. In addition the short time and long time responses have been modified to suit marine applications. Ground fault pick-up is not available in the USDM series. Instantaneous pick-up in the USDM series is identical to that of the regular USD ,4glay. The short time pick-up is lodified to provide tripping at 2.0, 2.25, 2.5, 2.75, 3.0 and 4.0 times the sensor tap. The USDM-21 relay does not have a long time pick-up while the USDM-3 and USDM-3IR have the same long time pick-up settings as the USD-3. Time delays in all cases are the same as the regular USD relay. Long Time Version The USD relay is available with only long time pick-up under the catalogue number USD-LT. The long time pick-up levels and time delays are the same as those on the regular USD relay. This relay will not provide any instantaneous or short time protection. It is also SD 3 phase overcurrent relay. The Test Set is completely The relay accumulates energy on a trip capacitor after a fault condition has been determined and dumps it into the shunt trip device. To assure overall operation of the relay, it is necessary to check that self-contained, including a storage this TRIP circuit does accumulate compartment for test leads and a the required amount of energy when given the signal to do so by any of the four elements. The test USD Test Set The Federal Pioneer type DDT-USD Test Set is a portable instrument used for field testing of the USD or carrying handle, and is capable of checking all facets of the relays' operations. The Test Set contains a current source and the logic circuitry which performs the test functions. The digital readout display selection switches and all controls are mounted on a fully labelled front panel. The Test set operates by delivering a momentary 70 amp (14 per unit) secondary injection current to the available with local and remote relay, thereby allowing the indication under the catalogue complete testing of the number USD-LT-IR. instantaneous element To allow accurate calibration testing of the pickup settings on all elements, the current source of the Test Set is controlled to provide three output ranges with metering from 0.2 per unit to 14 per unit. set has a built-in feature to monitor the trip capacitor voltage and give indication of a LOW TRIP during the Overall Time Delay Test. USD Solid State Relay Figure 7 — Time-Current Characteristics g g s ssgsii cutvcs lOMC 1IMI SHORT TtMT INfTANIAKfOlJS CROUNO UUIZ CUtVfS RAMO ON NOMINAl VAtUU INHN SiNUiOtfMi CUttlNt. nooucviON louRANCts ano AkOlfNT TfaintAtUtC CmCTS fCOM >9*C TO •»SS*C WtlL CMIM MAXVHUM 10% VAtMTtON ON TttU OUAV AND sovONoiCKur lONCTIMI CURVfS MMC i.iNoiCAnovAiuu The USD relay is the brains of the H'3 UKC breaker. U SIC RlnUUNTTlMTDtUV ATOTlMlSSfNSORTAP 3. PtC«UPATeiA,0.9.«4. ».t.l.e.*UT{MtS SfNSOtTAP I. MSSICtfPUSINTS TIME DEUT AT « TIMES SENSOR TAP. 2. PtCKUPAT2.3.4,«,0. RIOTIMIS SENSOR TAP SHOWN AT 3 TCMa I SENSOR TAP ClOCNO fAUlT CURVES PKKUP SNO%VN AT OJ TtMfi SENSOR TAP. ncxup AT 4.S. A, 1.10 A 12 TIMES SENSOR TAP. SHOWN AT 4 TIMES SENSOR TAP. t A POOIfl 20 M 40 SOgRSr o CURRENT IN TIMESSENSOR TAP Federal Pioneer Limited F EDS R P 1 O N E A1. 1 e r| initQxajiuKsit Parts Information Type H-3/HL^3 Circuit Breakers lecommended Spare Parts le H-3 Circuit Breakers 50H-3 (1600/2000A) 30H-3,42H-S(800A) DESCRIPTION PART NUMBER Arc Chute Assembly Stationary Arcing Contact Upper Stationary Main Contact (Rxed) Upper Stationary Main Contact (Drawout) 41A-504D 13A-566B 182A-S42B 4gE-552 49E-551 49E-555 49E-554 3 3 Center Stationary Main Contact Main Drawout Contact Assembly 49E-577 49E-130 3 6 Arc Chute Lower Flash Shield Front Flash Shield Moving Arcing Contact QUANTITY PER BRKR 3 3 1 3 3 PART NUMBER 41A-504D 13A-S66B 182A-542B 49E-552 49E-6S1 49E-649 49E-S7S 241B-532 241B-533 242A-S20 3 3 1 3 3 3 3 3 3 6 3 9 18 3 18 36 55B-502 13A-S74C 13A-67SC 13A-576C 27A-500 6 2 1 1 3 49E-S48 (1600A) 49E-549 (2000A) 49E-650 49E-519 (1600A) 49E-572and 49E-S73 (2000A) Main Moving Contact (Wafer Assembly) Spacer for Wafer Assembly (Outer) Spacer for Wafer Assembly (Inner) Main Moving Contact Spring Main Moving Contact Spring Holder 49E-575 241B^32 241B-633 242A-520 (42H-3) 242A-S21 (30H-3) interphase Barrier S5B^02 13A-574C R.H. End Barrier LH. End Barrier Main Braid 13A-S75C 13A-576C 27A-500 12 3 12 24 24 6 2 1 1 3 ouANxmr PER BRKR 6SH-3(1600/2000A) DESCRIPTION PART NUMBER Arc Chute Assembly 41A-504D 13A-666B 182A-40A-1 182A-41A-1 49E-652 49E^1 Arc Chute Lower Flash Shield R.H. Front Flash Shield LH. Front Flash Shield Moving Arcing Contact Stationary Arcing Contact Upper Stationary Main Contact (Fixed) Upper Stationary Main Contact (Drawout) Center Stationary Main Contact Main Drawout Contact Assembly Main Moving Contact (Wafer Assembly) Spacer for Wafer Assemby (Outer) Spacer for Wafer Assembly (Inner) Main Moving Contact Spring Main Moving Contact Spring Holder Interphase Barrier End Barrier Main Braid 49E-5SS 49E-S54 4gE-656 49E-130 49E-575 241B-532 241B-633 242A-520 S5B-S02 13A-678C 13A-172A-1 27A-500 QUANTITY PER BRKR 6 6 1 1 6 6 6 6 6 12 24 6 24 48 12 2 2 6 NOTE ADDITIONAL SPARE PARTS FOR BREAKERS ELECTRICALLY OPERATED ARE LISTED ON PAGE 2 FPE circuit breakers are subject to continuous product improvement which may result in minor part changes. To ensure that the correct parts are supplied, it is essential that complete nameplate data be provided, especially the serial number, when spare parts ate ordered. 2/86 NEW ISSUE FEDERAL PACIFIC RELIANCE ELECTRIC ULASS 0O125P Parts Information lype H-3/HI^3 Circuit Breakers Recommended Spare Pai lype H-3 Circuit Break^ 100H-3(4000A) 7SH-3 (3200A) DESCRIPTION Arc Chute Assembly Arc Chute Lower Flash Shield R.H. Front Flash Shield LH. Front Flash Shield Moving Arcing Contact Stationary Arcing Contact Upper Stationary Main Contact (Hxed) Upper Stationary Main Contact (Orawout) Center Stationary Main Contact Main Orawout Contact Assembly Main Moving Contact (Wafer Assembly) Spacer for Wafer Assembly (Outer) Spacer for Wafer Assembly (Inner) Main Moving Contact Spring Main Moving Contact Spring Hoider Interphase Barrier End Barrier Main Braid QUANTinf PART NUMBER PER BRKR 6 6 41A-504D 13A-S66B 182A-40A-1 182A-41A-1 49E-552 49E-551 49E^9 49E-548 49E-5S0 49E-519 49E-575 241B-532 241B-533 242A-520 55B^2 1 1 6 6 6 6 6 12 36 6 38 72 6 2 13A-578C 13A-172A-1 27A-500 2 6 PART NUMBER 41A-504D 13A-S12 182A-40A-1 182A-41A-1 49E-SS2 49E-651 4gE-623 49E^23 49E-624 49E-S03C 49E-S75 241B^32 241B-633 242A-S20 SSB^ (Inner) 55B^ (Outer) 13A-S78C 13A-172A-1 27A-600 QUANTITY PER BRKR 6 6 1 1 6 6 6 6 6 12 36 6 36 72 6 12 2 2 6 ADDITIONAL PARTS FOR ELECTRICALLY OPERATED BREAKERS H-3 & HL-3 DESCRIPTION MOTOR: 120V AC, DC PART NUMBER QUANTITY PER BRKR 183A-513 1 183A-517 1 183A-620 1 Shunt Close Coll Type A Undervoltage Coil Type A 46A-500-C") 1 Shunt Trip Coil Type B (SSD Trip Dewce) 46A-508 1 Shunt Trip Coil Type B (Separate Source) Single Phase Trip Coil Type B 46A-5012,5,6,7(—) 1 Limit Switch DC Control 249E-a 249E-9 1 1 182A-15A-1 49E-536-1 49E-536-2 1 1 1 249A-S09B 249A-S10B 249A-511B 249A-512B 249A-513B 1 1 1 1 1- 48V DC 240V AC, DC Limit Switch AC Control (**)Secondary Control Contact Block (Fixed) ("isecondary Control Contact Block (Moving) ("iSecondary Control Contact Block For 600V Line Voltage Input Only Auxiliary Switch - 4 Pole (2NO/2NC) Auxiliary Switch - 8 Pole (4NO/4NC) Auxiliary Switch -12 Pole (6NO/6NC) Auxiliary Switch -16 Pole (8NO/8NC) Auxiliary Switch - 20 Pole (10NO/10NC) (**)8 Contact Per Block Specify Number of Blocks (•**)Specify Type and Voltage FPE circuit breakers are subject tocontinuous product improvement which may result in minor part changes. To ensure that^ecorrect parts are supplied, itisessent'el that complete nameplate data be provided, especially the serial number, when spare parts are ordered. FFiE FEDERAL RAOFIG RELIANCE ELECTRIC 2/6< NEW ISSU e 1985 Federal l^cilic Electri PRINTED UN US CLASS 602SP Parts Information '(elUXSl fVpe H-3/Hi^3 Circuit Breakers Re^mmended Spare Parts Circuit Breakers SOHL-3 (1600/2000A) 30HL-3 (800A) QUANTITY PART QUANTITY NUMBER PER BRKR description NUMBER PER BRKR Arc Chute Assembly 41A-S04D 13A-566B 3 3 182A-542B 49E-S52 1 Arc Chute LowerFlash Shield Front Flash Shield Moving Arcing Contact Stationary ArcingContact Upper Stationary Main Contact Center Stationary Main Contact Main DrawoutContact Assembly Main Moving Contact (Wafer Assembly) Spacer for Wafer Assembly (Outer) Spacer for Wafer Assembly (Inner) Main Moving Contact Spring Main Moving ContactSpringHolder Interphase Barrier R.H. End Barrier I M PnrI Barrier 49E^52 49E-551 49E-668 49E-650 49E-573 49E-575 3 3 3 3 49E-551 4gE-567 49E-577 49E-130 49E-575 6 12 3 12 24 6 2 Z41B-532 241B-533 242A-521 55B-502 13A-574C 13A-575C 13A-576C 241B-532 241B-533 242A-520 558-502 13A-574C 13A-675C 13A-576C 27A-500 1 1 a DESCRIPTION Arc Chute Assembly Arc Chute Lower Flash Shield R.H. Front Flash Shield LH. Front Flash Shield Moving Arcing Contact Stationary Arcing Contact L.H. Upper Stationary Main Contact R.H. Upper Stationary Main Contact Center Stationary MainContact Main Drawout Contact Assembly Main Moving Contact (Wafer Assembly) Spacer for Wafer Assembly (Outer) Spacer for Wafer Assembly (Inner) MainMoving Contact Spring Main Moving ContactSpring Holder Interphase Barrier End Barrier Main Braid 41A-504D 13A-566B 182A-40A-1 182A-41A-1 49E-552 49E-551 49E-569-1 49E-569-2 49E-550 49E-519 49E-575 241B-532 241B-533 242A-520 55B-502 13A-578C 13A-172A-1 27A-500 1 1 3 100HL-3 (40C0A) 75HL-3 (3000A) PART NUMBER 3 3 1 3 3 3 3 12 18 3 18 36 6 2 41A-504D 13A-566B 182A-542B QUANTITY PER BRKR 6 6 1 1 6 6 6 6 6 12 36 6 36 72 6 2 2 6 QUANTITY PER BRKR PART NUMBER 6 41A-504D 13A-612 6 1 182A-40A-1 182A-41A-1 49E-5S2 1 49E-551 70.12J013B.1 70.12X)13B5 49E-624 49E-509C 49E-575 241B-532 241B-S33 242A-520 55B-504 (Inner) S5B-S05 (Outer) 13A-578C 13A-172A-1 27A-500 6 6 6 6 6 12 36 6 36 72 6 12 2 2 6 notes: and ampere rating offuses installed. ADOmONALSPARE PASTS FOR BREAKERS SLECmiCAU-TOPEBATEO ABE LISTED ON PAGES 2/86 NEW ISSUE FEDERAL FACFIC1 RELIANCE ELECTRIC m f-iryAUjiyfe.!!, Parts Information type H-3/H1^3 Circuit Breakers' Part IdentificatiM Type H-3 Circuit Breai"' 2000 AMP M i SECTION OF H-3 BREAKER 4000 AMP Arc Chute Asscably Interphese Barrier 22. Handle Atseably 23. Close Lever ft.H. End Barrier L.H. End Barrier 24. Close Latch 25. 2i. 27. 28. Trip Rod Atseably Spring Guide Pin Closing Casting Closing Pin Front Flash Shield Closed-Open Link Crank Asseibly Braid Closing Link Asseably 48. Wafer Contact Spring 49. 50. 51. Spring Holder Hoving Arcing Contact Stationary Arcing Contact Tie Rod Atseably Closing Shalt Hain Spring 52. Load Terainal Ratchet Wheel 32. Guide Bushings 53. Anti-Bounce Plate Oscillating Lever • 33. Claap Asseably 54. Base Houlding Clutch 34. Breaker Fraae 55. Trip Flipper Charged-Oischarged Button Indicator Plate Faceplate Bo> Atseably Floating Trie Faceplate Atseably not 47. 29. Front Plate • Hain Hoving Contact (Wafer Assyi Upper Stationary Ham Contact 30. 31. Bos Charged-Oischarged Link Closed-Open Button 21 Centre Stationary Main Contact 44. 45. 46. Crank Bos Bearings Holding Panl Crank 20 43. 35. Trip Shaft 56. Trip Coil Asseably 36. 37. Trip Latch Latch Bearing 57. Loaer Channel 58. Finger Spacer 38. 39. Leaer Houlding Sensor Hounting Bracket 59. Drauout Contact Asseably 40. 41. Barrier Sensor 60 61. SLS Caa Ground Stab 62. Loner Flash Shield 42. Juaper shonn 2/ FRjE FEDERAL REOFIC RELIANCE ELECTRIC NEW ISS os.Maiof ov^eof lrTO(aMSS£ Parts Information Type H-3/HLp3 Circuit Breakers tart Identification lf^HL-3 Circuit Breakers 1600 a 2000 AMP 14X16 1 0.] -a Tcrria 4000 AMP SECTION OF HU-S BREAKER 1. 2. Arc Chute Actiably Interphise Berritr 24. Close Latch 46. 25. Trip Rod Assenbly 47. Closing Link Assenbly Braid 3. 4. 5. R.H. End Barrier L.N. End Barrier Front Flash Shield 26. 27. Spring Guide Pin Closing Casting 48. 49. Haler Contact Spring Spring Holder 28. Closing Pin 6. Closed-Open Link 29. Tie Rod Assenbly 50. 51. Moving Arcing Contact Stationary Arcing Contact Load Terninal 7. Crank Assenbly 30. Closing Shalt 52. S. Crank Boi 53. Anti-Bounce Plate 4. Crank Bos Bearings Main Spring Guide Bushings Clanp Assenbly 54. 55. 56. Base Houlding Trip Flipper Trip Coil Assenbly 10. Holding Paul 31. 32. 33. 11. Ratchet Wheel 34. Breaker 12. Oscillating Lever • 13. Clutch 35. 36. Trip Shalt Trip Latch 14. Charged-Oischarged Link 37. 15. Closed-Open Button 16. Charged-Discharged Button 17. IB. Frane 57. Louer Channel Latch Bearing 58. 59. Finger Spacer Orauout Contact Assenbly 38. 39. Louer Houlding Sensor Mounting Bracket 60 61. SLS Can Ground Stab Front Plate 40. Barn.ier 62. Louer Flash Shield Indicator Plate 41. Sensor If. 20. Faceplate Bos Assenbly Floating Trin 42. 43. Junper Centre Stationary Hain Contact 63. 64. Line Side Bar Line Side Terninal 65. Fuse 21. 22. Faceplate Assenbly Handle Assenbly 44. Main Moving Contact (Haler Assy) 45. Upper Stationary Hain Contact 66. 67. Interphase Barrier R.H.6 L.K. Orauout Wheel Assy 23. Close Lever * not shoun FEDERAL mClFIC RELIANCE ELECTRIC Parts Information Type H-3/HL-3 Circuit Breakers Recommended Spare Part^ •Y V-' MAIN DRAWOUT CONTACT ASSEMBLY (800 Amp) MAIN DRAWOUT CONTACT ASSEMBLY (4000 Amp) MAIN DRAWOUT CONTACT ASSEMBLY -f. (1600, 3000 & 3200 Amp) •V ,V' MAIN DRAWOUT CONTACT ASSEMBLY (2000 Amp) ftM •. -r. STATIONARY ARCING CONTACT ASSEMBLY FEDERAL PACIFIC f f RELIANCE ELECTRIC mB MOVING ARCING CONTACT ASSEMSJv Parts Information Type H-3/H1^3 Circuit Breakers Recommended Spare Parts ARC CHUTE ASSEMBLY MAIN MOVING CONTACT (WAFER ASSEMBLY) SPACER FOR WAFER ASSEMBLY (OUTER) ARC CHUTE LOWER FLASH SHIELD SPACER FOR WAFER ASSEMBLY (INNER) MAIN MOVING CONTACT SPRING MAIN CHARGING MOTOR BRAIDS MAIN MOVING CONTACT SPRING GUIDE 'W 62cr SOLENOID COIL jp-^T TRIP TYPE A K (VOLTAGE TRIP SHUNT CLOSE 2/86 NEVV ISSUE SOLENOID COIL SHUNT TRIP TYPES ANTI-SINGLE PHASE DEVICE LIMIT SWITCH FEDERAL PACIFIC HeUANCE ELECTniC CLASS 602SP pro(sj Parts Information ©aitii Type H-3/HL-3 Circuit Breaker Recommended Spare Pa SECONDARY CONTROL CONTACTS CENTER STATIONARY MAIN CONTACT (1600, 2000, 3000, 3200, & 4000 AMP) UPPER STATIONARY MAIN CONTACT (1600, 3000 &3200 AMP DRAWOUT) UPPER STATIONARY MAIN CONTACT (1600, 3000 & 3200 AMP FIXED, ALL 2000 & 4000 AMP) UPPER STATIONARY MAIN CONTACT (600 AMP DRAWOUT) LiSrw-y CENTER STATIONARY MAIN CONTACT (800 AMP) UPPER STATIONARY MAIN CONTACT (800 AMP FIXED) Federal Pacific / 2500 Blue Ridge Road / Raleigh. North Carolina / 919-783-100( FEDERAL PACIFIC f* RELIANCE ELECTRIC MM !N-820.4A INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FEDERAL PACIRC METAL-CUD SWITCHGUR JANUARY 1972 , ' S'. ' r-»' . ^.1 -"5! fex.. ,... •0: •A •^:- INDEX Part r\ Page I. General Features Shipment Inspection Moving and Lifting Storage 4 Foundation 4 Part 11. installation Housing Inspection Assembly A—Protected Work Aisle Assembly B—Center Aisle Assembly C—Non-Walk-in Tightening Connections 5 5 5 6 6 6 Bus Duct 6 Additions to Existing Equipment 6 Equipment Batteries I Wiring Grounding 1 I Fuses I Dummy Breaker I Insulation Taped Connections 12 Ground Fault CT Terminations .12 Part III. Pre^nerEization Tests r\ Preparation 14 Dielectric Tests 14 Operational Tests 14 Part IV. Maintenance Benefits : Inspection Program IS IS IS Part V. Safety Requirements for Power Switchgear Assemblies Unqualified Person—General Public Qualified Person 17 17 General Instructions to Qualified Persons 17 Part VI. Switchgear Accessories Standard 18 Indicating Lamps 18 Miscellaneous 18 List of Illustrations Figure 1—Lifting Gear—21 feet and Under (Dwg. 2200C0I66) Figure 2—Lifting Gear—Over 21 feet (Dwg. 220OC0I67) Figure 3—Installation of Floor Channels—Indoor 2 3 4 Figure 4—Installation of Floor Channels—Outdoor 4 Figure S—Table A—Recommended Torque Values Figure 6—Base Assembly (Dwg. 220OC0I68) 6 7 Figure 7—Outdoor Protected Work Aisle Construction (Dwg. 2200DOI69) Figure 8—Outdoor Center-Aisle Construction (Dwg. 22C0DOI70) Figure 9—Base Connections and Cell Bolting (Dwg. 2200C0I7I) 8 9 10 Figure 10—Additions to Existing Units (Dwg. 2200C0172) 10 Figure 11—Boot Installation 12 Figure 12—Taping Instructions ; 13 Figure 13—Table B—Dielectric Test Values 14 This manual for job orders shipped beginning March, 1971. PART I - GENERAL sections. 1. Switchgear Housings and DST-2 Air Circuit Breakers are jig constructed in alignment flxtures to assure REMOVAL FROM CARRIER AND INSPECTION FOR DAMAGE interchangeability of breakers. Compartmentalized construction segregates the circuit breaker, main bus, current transformers, potential transformers, and control power transformers. 2. Complete interlocking between tha cell and circuit breaker provides safety to personnel and equipment by prevention of incorrect operating procedure; 3. Equipment is-designed to reduce installation time, and to comply with ANSI Standards C37.20. OUTDOOR: 4. Equipment is constructed so that additional sections may be readily added in the fleld. 5. Protected scheduled work-aisle provides ample space for a maintenance program regardless of weather. Breakers draw out into aisle with suflicient space for interchangeability. The service area is ventUated, waterproof, and adequately lighted; service receptacles are provided. 6. The undercoated structural foundation supports are designed to be self-contained making it necessary to support foundation steel only. This design permits elevating switchgear on supporting structures and thereby reduces flood hazards. 7. Outdoor finish: Three-coat system consisting of a zinc chromate primer, an intermediate coat, and a final ASA-24 dark*gray exterior coat. SHIPMENT The switchgear is assembled, wired, adjusted and given complete tests at the factory, after which it is inspected and packed for shipment, llie air circuit breakers are not shipped in the switchgear compartments, but are Pv bly drawings and floor plans for details of shipping CONSTRUCTION FEATURES INDOOR OR OUTDOOR: packed in separate crates. Each crate is identified, and a complete list of its contents is included in the shipping papers. All instruments and relays are suitably blocked as required to prevent damage to bearings and move ments. Protected work-aisle metal-clad switchgear is shipped in completely assembled sections whenever possible to provide ease of handling and installing. See job assem Immediately upon receipt of the shipment, identify all component parts and check them against the shipping list. Make a thorough examination to detect any dam age which may have been incurred during transit If any dama^ is discovered, file a claim immediately with the carrier, and send notice of the extent of the damage to the Federal Pacific Electric Company plant from which shipment waa mader giving complete-iden tification, carrier's name, and railroad car number if the shipment was made by rail. The information will enable the company to supply necessary information in support of claim. MOVING AND LIFTING SWITCHGEAR^ 1. It is extremely important that care be taken in handling, rigging, hoisting, rolling, or moving assembled switchgear into place. Metal-clad switch- gear isdesigned to be bandit only inan upright posi tion and should never be handled in any other way without first consulting with the Switchgear Engineer ing Department. 2. Each shipping section of indoor switchgear is bolted to a heavy shipping skid which- should remain with the gear until it is moved into final location. Each section of outdoor gear is supplied with heavy lift ing lugs bolted to the switchgear base. 3. When lifting shipping units with a crane, it is prefer able to use two hooks simultaneously, one on each end. Each pair of lifting hooks should be equipped with a spanner bar to prevent excessive distortion. If only a single hook crane is available, arrange spannerfs) to lifting rig as shown on typical outdoor gear lifting drawings 2200C0166 and 2200CX)167. (Figures 1 and 2). 4. When cranes are not available, equipment can be rolled into place on shipping skids (indoor) or steel base (outdoor) provided with each shipping section. Pushingor pullingforces should beapplied to the skid or base and not the Switchgear. 5. Shippingskidscan be removed by using a foot jack in each comer of the shipping section afler the switchgear has been moved to its final location. ) ) ) WEIGHTS OF CELL SECTIONS WIDTH OF CELL AATIHG of CELL DIMENSION EQUAL 10 OR GREATERr IRAN DEPTH OFSWITCHGEAR SWITCHGEAR WHEN LIFTING-i 2.SOO LBS 2,700 LBS DST-2 5KV-2S0 1200 A 26" •D5T-2 5KV-2S0 2000A DST-2 SKV-3S0 DST-2 'SKV-3S0 1200 A 2000A 2626" . 26' 2,900 UBS DST-2 3000A 36" 3,600 LBS. I200A 2000A 36* 36* 3^0 LBS A300 LBS SKV-3M DST-2 ISKV-MO OST-2 ISKV-SOO INSERT WOODEN BLOCKS TO.PROTECT APPROX NCT WEIGHT 2.800 LBS DST-2 ISKV-7S0 I200A 36" 3,100 DST-2 ISKV-750 2000A 36" 3,400 LBS DST-2 OST-2 ISKV-SOO ISKV-TSO 3000A 3000A 36" 36" 3,600 LBS NOTE LBS 4,000 LBS WEIGHT DOES NOT INCLUDE BREAKER To TYPICAL OUTDOOR NON-WALK-IN CONSTRUCTION SHOWN RECOMMENDED METHOD OF LIFTING CELLS(2l'-0' LG MAXJ AND ALL WORK AISLE SECTIONS FPE DWG.NO. 2200C0I66 FIGURE 1 o o o x> NOTE:FOR CELL WEIGHTS REFER TO DWG. 2200C0I66 -INSERTWOODEN BLOCKS TO PROTECT DIMENSION EQUAL TO OR GREATER THAN DEPTH OF SWITCHGEAR TYPICAL OUTDOOR NON-WALK-IN CONSTRUCTION SHOWN recommended method of LIFTING CELLS(2|-0. LG. AND OVER) AND ALL WORK A|SLE SECTIONS FIGURE? FPE DWG. NO. 2200C0I67 ^ STORAGE BEFORE INSTALUTiON Protection against loss of equipment is an important precaution. Trouble and delay will be avoided by hav ing good storage facilities arranged so that the appa ratus will be accessible only to authorized persons and so that it can be quickly located when required in the erection program. Switchgear equipment, regardless of whether it is to be installed immediately or stored for a while before being erected, should be kept in a dry, clean place. Conditions such as dampness caused by rain or change in tempera ture, cement dust, etc., should be carefully gturded against. Covering the equipment with a temporary shelter or tarpaulin is frequently necessary both during storage and erection. The longer the period of storage, the greater must be the care taken for protection of the equipment. If dampness or condensation may be en countered in the storage location, heaters should be placed inside the units to prevent moisture damage. Approximately 600 watts of heaters per unit will be re quired. Remove all cartons and other miscellaneous material packed inside the units before energizing any heaters. If the equipment has been subjected to mois ture it should be tested with a lOOOV or 2500V megger after heaters have been turned on for approximately one week. A reading of at least 100 megohms should be obtained. - Batteries should be uncrated and put on trickle charge .immediately on receipt. Relay covers should never be left off since the relays are %delicate devices and future malfunctions because of mois ture arid dust oould prevent proper tripping of circuit breakers. Breakers should be prepared for storage separately. Refer to appropriate breaker instruction book. FOUNDATION Federal Pacific Metal-Clad Switchgear is accurately built on true and level betlplates. This care and accuracy insures ease of operation and interchangeability. Equal care during installation should be used. True and level supports for this equipment are ofutmost importance. Little more than ordinary care in laying out arid preparing the foundation will be repaid in reaction of cost and labor of installation. The steel supporting members Used in the floor should • be held level until the concrete is set. The surface of the floor under the housing should not project above the supporting members. For indoor switchgear only, the ^rface ofthe floor should not lie below the supporting ^embers by more than 'A'. *Thefloor infrom ofthe housing should not very more then W in ony squareyardandtmsantAptosfisX.ehovt the level ofthestqiportingmembers. A smoothfloor'willmake rolling ofthe removable element easier. *Wheninstallingswitchgearwherefloors alretidyexist, it will usually be desirable to pour a newfinishedfloor above with embedded channels or cut slots for embedding and leveling the supporting channels. Encircling loops of reinforcing or building steel aroimd single phase conduaors should be avoided in the main cableentrancearea ifthese are rated 600amperes orabove. FIG. 3 or an equivalent must be used to obtain an ade quate foundation. Bolting the switchgear to the foimdation is an acceptable method. Welding to the founda tion is preferred because it does not require an accurate lining up of holes. FIG. 4 or an equivalent must be used to obtain an ade quate foundation for outdoor equipment. Welding to the foundation is the preferred method of securing. *For indoor switchgear only. SWITCHGEAR BASE HOLES OR SLOTS PROVIDED IN SWITCHGEAR BASE FOR WELDING (PREFERRED} OR BOLTING, SUGGEST 3/8" HARDWARE. SEE FLOOR PLAN FOR LOCATION. WELD HERE 1/8 MAX. 1/8 MAX. FIGURE 3 FIGURB4 PART 11 - INSTALLATION HOUSING INSPECTION 1. Before setting equipment in place, refer to switchgear drawings and, after completely uncrating equipment, check permanent location to see that equipment will properly fit on channels and foundation location. Align and bolt all shipping sections together so that a con tinuous switchgear installation is obtained. (Refer to Assemblies "A", "B", and "C below.) 2. Carefully inspect all portions of the circuit, breakers for posable damage. SkV 250 MVA-circuit breakers are shipped completely assembled with arc chutes. 15kV and SkV 350 MVA circuit breakers are shipped separate from arc chutes and may be assembled properly in the protected work aisle and center aisle outdoor houses by use of the arc chute lifting bracket attached to the aisle ceiling. After inspection, the circuit breakers should be carefully inserted and racked into the switchgear cells. 3. Remove shipping braces, inspect for damaged parts, cracked epoxy bus, primary disconnect btishings, bent secondary disconnects, cracked porcelain, in sulators, wiring insulation — check and report evi dence of abuse to equipment. 4. Inspect cells to be certain that power contacts and secondary disconnect contacts located in rear of cell ASSEMBLY "A**: OUTDOOR PROTECTED WORK AISLE CONSTRUCTION (See dwg. 2200D0169.) 1. Locate the cell sectionsaccurately on the foundation. When cell equipment is in two sections, locate the sections from the center of the foundation. 2. Check the leveling of the units; use shims where foun dation is uneven. Remove lifting lugs. 3. When cells are in two sections and the above are pro perly leveled and aligned, firmly bolt the bases, cells, and roofs together with the hardware furnished for this purpose. 4. Aisle Section: A. When aisle section is in one piece, remove ail protective lumber and bracing except wooden horizontal and center vertical braces. Remove lifting lugs. , B. When aisle section is in two pieces, remove all protective lumber and bracing from each section except wooden horizontal brace, wooden vertical comer and vertical center brace, and open end wooden frame bracing. Remove lifting lugs. WARNpiG: UNDER NO CONDITION MAY THE WOODEN HORIZONTAL ROOF SUP PORT BE REMOVED BEFORE ITEM 5 BELOW IS COMPLETED. are free ofdirt and dust. Cell floor must be clear of all dust and debris to facilitate easy handling of circuit breaker. 5. The breaker is provided with a maintenance closing device for manually closing the breaker. It cannot be used as a manual device to close in the breaker when 5. Slide aisle section(s) into place, making sure that aisle roofs overlap cells and reston top of cell roofs. Aisle side sheets must be'on outside of cell sections. in the cell. This handle should be used only when the breaker is withdrawn from the compartment. 6. When aisle section is aligned with the cell portion, 6. Refer to the circuit breaker Instruction Manual Si^e sheets together and apply cement (furnished) to lN-820.11 before inserting breakers into cells. 7. If porcelain entrance or load bushings are mounted in the roof, use flexible connections from incoming and outgoing lines to reduce the strain on the por celains. 8. Inspect all instrument doors for damage to protective relays. apply caulk (furnished) between overlapping roof and sidesheet surfaces. Firmly bolt bases, roof, and roof gasket joints. ' 7. Remove existing wooden braces. 8. Remove floor plates at ends and at base anchor ing points. 9. Fasten aisle base to cell base. (See dwg. 22(X)C0171, Figure 9). 10. Tackweld or anchor the bases to the foundation as Control-wiring underground conduit from the control building should terminate inside the switchgear at a level above any existing high-water marks (4" maximum above floor line). Heaters are furnished in front and rear of each outdoor unit. ft The followingdescriptions and drawings give the general arrangement, sequence of installation, method of fas tening the gear to the foundation, location of conduit areas, and other information for the proper location and a&sembly of the equipment: indicated on the floor plan drawing. 11. Re-install floor plates. 12. Check and adjust instniment doors for proper align ment to correa possible mishandling during shipment. 13. Complete the assembly of the main and ground buses (when required) by inserting the sections shipped loose for the shipping breaks. (Tighten the bus bar connections per Table **A" on page 6.) Assemble the PVC boots around the main bus joints and fasten together with the nylon hardware fur nished. ($ee instruction page 12.) ' G 14.Re-connect ^wiring at shipping breaks and where required per wiring diagrams furnished. NOTE: A. Customer control wiring connections must be terminated at terminal blocks only — no splicing is permitted. B. Allwiringin conduits must be in accordance with National Electrical Code. ASSEMBLY^B": OUTDOOR CENTER All joints in the bus should be assembled and insulated as described above for main buses. Adjustable joints are provided to allow for variations in building construc tion, etc. These joints should be loosened before installa tion ofthe duct, then tightened after being set in the posi tion required by the flxed points at the ends ofthe duct; Outdoor bus duct must be gasketed at the joints between shipping sections. All removable covers on outdoor bus duct except bottom coversmustbe gasketed.Do not bolt covers in place until AISLE CONSTRUCTION .1.Complete items 1, 2, 3, 10, 12, 13, and 14 per assembly "A" above. 2. Bolt aisle-end channels in place. all interior assembly work on the duct is completed and access will no longer be required. Outdoor bus duct of the 13.8 kv class are provided with heaters. Connect these heaters in accordance with the wiring diagrams furnished with the equipment before . 3. Install floor plates. energizing the bus duct. 4. Assemble end panels of the aisle section. 5. Assemble aisle roofs and seam gaskets. 6. Apply caulk (furnished) between overlapping roofand side sheet sumces. Firmly bolt roofs and side sheets together and apply cement to roof gasket joints. •7. Check and adjust instrument doors for proper alignmentrtocorrect possible mishandling dunng shipment ASSEiyiBLY'"(r:t)UTDOOR NON^WALK-IN CONSTRUCTION 1.Complete items1,2,3.10,12,13 and 14per assembly ^A" above. TIGHTENING CONNECTIONS 1. Bus splices at shipping break should be carefully in spect to becertain that good clean, uncontammated contact is obtained before bolting up tight. A torque wrench should be used. 2. It is also important to be sure that all outgoing-cable connections ^re tightened in the same manner as bus splices. ADDITIDN OF UNITS TO EXISTING EQUIPMENT Beforeadding units to existing equipment, consult and study all drawings furnished with the equipment. In addition to the usual drawingsfurnishedwith nw equip ment, specialdrawings may be furnished covering com plicated or special assembly work. Ako, checkto make sureall necessary parts are«n hand. BEFORE ANY COVERS ARE REMOVED OR ANY DOORS OPENED WHICH PERMIT ACCESS TO THE PRIMARY CIRCUITS, IT IS ESSENTIAL THAT THE CIRCUIT OR CIRCUITS BE DE-ENER GIZED AND BREAKERS BE WITHDRAWN TO A DISCONNECTED POSITION AND TAGGED. IF WORK IS TO BE DONE ON REMOTE EQUIP MENT CONNECTED TO A UNIT THE BREAKER FOR THAT UNIT SHOULD BE PLACED IN THE DISCONNECTED POSITION ANDTAGGED. ALSO THE REMOTE EQUIPMENT SHOULD BE ISO TABLE A LATED FROM ANY OTHER POWER SOURCES RECOMMENDED TORQUE (Values in Foot Pounds) CONNECTED TO FT. Type Bolt Steel* Everdur i/lb'-lS 18 15 3/8M6 31 21 l/2''-13 55 45 S/S'-Il 80 65 '••Steel hardware must be SAE 5 or stronger. FIGURES Dwg. No. 2200C0172 (Figure 10) indicates the special procedures required to add new inetal-clad units to out doorequipment with protected aisle. For indoor equip ment it is usually necessary only to remove the end cover sheets and to re-assemble them on the new units after these are located and bolted to the existing units. Otherwise, the installation procedure is the same as described in Part 11. BUS DUCT Busduct connectingbetweengroupsof metal-clad switchgear, or between metalclad switchgear and other ap paratus, should be installed as shown on the arrange mentdrawings furnished with the duct. Supports should be provided as indicated on the drawings. When the units are in place and mechanical assembly is completed, assemble the main bus and other primary connections. Secondary wiring and control bus con nections should be made in accordance with the wiring diagrams furnished with the equipment. O V J -CONTROL CONDUIT I5KW—H»KVh FRONT POOR^ ^ •D .REAR DOOR I SPECIAL CANTILEVER >1 "TT _ li! LEVEUN^HANNELOR *rBEAM ''TTI^REAR DCiOH 1J .11I I I l_l-l».E, If COHOOII tSila CONCRETE CURBS OR PADS MOUNTING 'ri u53 NON-WALK-IN INSTRUMENT pOOR REAR DOOR FRONT MNa NOTES FOR SHIPPING SECTIONS AND SPECIAL H0UNTIN6 DIMENSIONS SEE.JOB OWGS AND FLOOR PLAN AISLE FLOOR CELL FU»R AISLE BASE CULBASE ^BOLTING.CELLTO BOLTIHG,AISLE TO AISLE and cell TO CELL AISLE CHANNEL DEPTH OF SW TCHGEAR DEPTH OF AISU EXTENSION PROTECTED WORK AISLE REAR DOOR REAR OOOl N •INSTRUMENT DOOR- 1 ! ltl f rA AISLE BASE CHANNEL SUPPORT -DEPTH OF STHTCHGEAR - CENTER AISU AREA • DEPTH OF SWITCHGEAR CENTER AISLE METHOD OF MOUNTING AND INSTALLATION OF BASES FOR OUTDOOR HOUSES F|6URP§ FPE DWG. NO. 2200COI68 ) IMPORTANT NOTE; * NOTE I: ONE PIECE AISLE SHIPPING SECTION - 00 NOT REMOVE WOODEN HORIZONTAL AND CENTER VERTICAL ROOF BRACES UNTIL AISLE ROOF OVERLAPS AND RESTS ON SWITCHGEAR ROOF CAULK MOTE 2: SPLIT AISLE SHIPPING SECTION DO NOT REMOVE WOODEN HORIZONTAL.VERTICAL CORNER AND VERTICAL CENTER BRACES i AND OPEN END •WOODEN FRAME BRACING UNTIL AISLE ROOF OVERLAPS NOTE:APPLY CAULKING COMPOUND TO ALL BUTTING AND OVERLAPPING JOINTS AND RESTS ON SWITCHGEAR ROOF Vi-itx i'u.*atr t MAUM MSMII WOODEN HOnZONTAL ROOF BRACE MTU CEMtNT V«-nxru.aotrt WALHCWMn OUTDOOR ROOF GASKET MSU ROOT WOODEN VERTICAL BRACE ROOF ASSEMBLY MXMAU iOtf SWITCHGEAR SECTION X i.ztu.ieLT AISLE SECTION PROTECTED WORK AISLE COVER aATE 545I6006S RIGHT HAND. 545280066 LEFT HAND (SHOWN) METHOD OF JOINING AISLE AND SWITCHGEARSECTIONS AT INSTALLATION ' 2200D0I69 ' hoURET o 3 APPlt CCHENT ROOr CAtKfT VflAXI* iSXI'l&Mf A SEALMO WASKtR ARPLY- CAULKIHO COMPOUMO "^swItchcearroof AISLE ROOF ROOF A^EMBLY iixusiAooa N07E:AmV UULKiN& COMPOUKD TO ALL lUTTiNO AND OVCALAfRlNG JOtMTR OUTOOOA ROOT MSKET (USLC) AISLE OOOR FRAME ASSEMeUr fIDEAHCET AISLE EXTENSION UOE SHEET AISLE OOOR fLOOR PLATES SWITCHGEAR SECTION Vi*iSxi.sois,Ma - AISLE SASe CHANNEL SUPPORT CENTER AISLE SECTION r- SWITCHGEAR SECTION • CFNTER WORK AISLE METHOD OF JOINING AISLE AND SWITCHGEAR SECTIONS AT INSTALLATION 22Q0D0I70 FffiURES -|h6Xs'lg. hex hd. bolt ^-Z0X.79LG.HEX HD.60LT LOCK 4 nM WASHER LOCKWASHER A HEX NUT CELL SIDE SHEET 14 HEX NUT (WCLOCO) REAR FRAME UPRIGHT CELL— UPRIGHT •r ♦A* CELL UPRIGHTS REAR FRAME UPRIGHTS AISLE BASE- CELL BASE CELL BASE AISLE BASE TO CELL BASE SECTION A-A (TOP SECTIOtO PROTECTED WORK AISLE END OF UNIT CELL TO CELL (REAR) f •I4X rLfi.11EX HILBOLT LOCK A FLAT WASHER 16 HEX NUT(WELDED) CUT TO SUIT ROOF GASKET AT ASSEMBLY I6X I^S LG.HEX HO. BOLT LOCKWASHER.FLAT WASHER AND HEX NUT AISLE CHANNEL OUTDOOR ROOF SUPPORT ROOF FLANGES AISLE CHANNEL SUPPORT TO CELL BASE CENTER WORK AISLE Drawing2200C0171 BOLTING DETAILS FIGURES -fWSTING ROOF- IDE SKEErS.RANELS^AND DOOR UOVCO, CAULKED AND30LTE0 IN END POSITION FEND TRIM OIOYED A BOLTED to END POSITIOH) TTTTym? EXISTING UNITS (raoiOTED WORK AISU SHOWN) FUTURE UNITS (FUTURE LOT END ADDITIONS SHOWN) FIELD PROCEDURE FOR EXPANSION OF EXISTING OUTDOOR SWITCHGEAR FIGURE 10 10 Drawing 2200C0172 EQUIPMENT BATTERIES Follow batteiy manufacturer's instructions carefully when installing the battery. Be sure that ventilation is provided to carry off the fumes. If steel work seems to be affected by the fumes, apply black asphaltum paint Make sure that the battery charger is functioning, and that the charging rate is not excessive. Test for specific graviQr regularly. nection is necessary for every switchgear. installation. A poor ground may be worse than no ground since it gives a false feeling ofsafety to thoseworking aroundthe equipment. It ^buld also be of sufficient capacity to handle any abnormal condition that might occur on the system and should be independent of the grounds,used for any other apparatus. CONTROL CIRCUIT FUSES If battery is installed remote from the switchgear, have FPEECON* CLASS 1330 cables of sufncient size to keep the voltage drop at a DUAL ELEMENT CONTROL CIRCUIT FUSES 100,000 AMP RMS A.C. minimum. INTERRUPTING CAPACITY Be sure battery is charged and no abnormal loads are evident before putting switchgear in service. Ampere' Catalog #-2S0V WIRING 1 ECN-1 ECN-3.2 ECN-d.25 ECN-10 ECN-15 ECN-20 All incoming and. outgoing control connections should be made i» accordance with the switchgear sche matic and wiring diagrams. Afier wiring is completed,, all connections should, be carefully checked against the diagrams to insure that all coimections are correct and' rs ^ proper. ECN-25 The wiring diagram number of each switchgear unit is stamped on the nameplate of the control panel. The wir ing diagram number applying to each circuit breaker ECN-30 ECN-35 ECN-60 , 3.2 , 6.25 la 15 2B 2530' 35 60 isstam^ oneach breaker onthe nameplate. These fuses provide instantaneous- protection against Interconnecting wiring diagrams between the asso ciated equipment are not normally supplied with metalclad switchgear. ability within the sizes listed. short circuits plus a hi^ degree of current limiting DUMMY BREAKER GROUNDING Each switchgear assembly is provided with a ground Dununy removable elements are used as a means of isolating drcuits or bus sections where operation is.in frequent and a circuit breaker caimot be economically justified for an interim of time. The deviceconsbts of a bus extending the full length of the complete assembly. Sections of ground bus previously discoimected at shipping breaks must be reconnected when the units framework to simulate the circuit breaker removable element with a set of six studs similar to those on the are installed. « breakers. The studs are connected by shorting^ bars which are fully insulated and metal-enclosed. The sta tionary structure is the same as for a circuit breaker. When the device is racked into position, it connects the The ground bus should be connected to the station ground at both ends with as direct a connection as pos sible and should not be run in metal conduit. The grounding conductor should be capable of carrying the maximum line-to-ground current for the duration of line and load side of bus. the fault Under no conditions must the dummy element be When switchgear has center aisle construction, insure that the connecting ground bus is connected between opposite aisle sections. racked into or out of the cell when the bus or the unit is ener^zed. Key interlocks are applied to insure that all sources of power are dbconnected before the dununy element can be operated. Floor interlocks are provided to prevent insertion into specific ceUs. A reliable permanent and low resistance ground con 11 o INSULATION BOOTS ON 5 AND 15KV CLASS EQUIPMENT,BUS BAR JOINTS ARE INSULATED-WITH MOLDEDtBUS BAR BOOTS. THE BOOT IS:PULLED IN PLACE AROUND THE .BUS BAR/JOINT. AFTER FITTING, HOLES ARE PUNCHED FOR CLEARANCE OF THE NYLON HARDWARE. NOTE; CHECK BUS BOLT TORQUE BEFORE ASSEMBLING BOOTS. TAP 1:1 xz NOTE V 1 oi NOTE V r .JLl MAIN. o| MAIN THRU I 1 '— j'— j BOOT •SOOT «« RIGHT angle •BOOT THRU o =NpTE V; PUNCH 9/32 OIA. HOLES AND ATTACH WITH NYLON HARDWARE. TIGUREU faults. These transformers are normally installed in a horizontal position directly above or below the primary cable terminals, so that the primary cable or cables can pass through them. One transformer is required for each three-phase circirit. TAPED CONNECTIONS For taped connections use materials as listed in taping instructions. Fig. 12. Extreme care should be taken in taping unusual contour joints with vinyl tape. Where armored cable is used, the armor must be ter minated aad grounded bd'ore the cable passes throu^ Taping a flat or a cylindrical surface such as a bus bar or cable is a relatively simple process in which much the same technique is used whether the tape is paper, cloth, or plastic. Vinyl tape may be stretched sliehtly to help it conform to irregular contours. This is an ad< vantage if properly understood and used correctly, but . can be harmful if the tape is stretched unnecessarily to make it "conform." The pressure sensitive adhesive is not designed to withstand large sidevise (shear) forces for a long time; and if the contour is such that the tape tension can be relaxed by a side slippage, some slippage will take place. the transformer. Armor clamps are furnished for this ptupose when spedfied. When lead or other condiicting sheath cable, or cable with shielding tape or braid is used, it is recorrunended that the sheath or shield be grounded solidly to the switchgear ground bits. The ground lead should be' bonded to the sheath or shield on the side of the current transformer away from the primary terminals. In cases where the ground cannot be applied before the cable passes through the~transformer, bond the lead to the sheath or shield between the transformer and the pri mary terminals. The ground conductor must then be passed back along the side path through the current transformer before being connected to the ground bus. • Where potheads are used in units provided with ground fault current transformers, the pothead mount ings must be' insulated from groimd. ROUND FAULT CURRENT TRANSFORMERS (THROUGH-TYPE) Through-type current transformers are furnished vhere specffied for sensitive protection against ground 12 O ) D (VARNISH CAMBRIC) 9 DESCAIPTION 1 o l/jNVLPtASTIC ^lOTHK rwiDex36Y0&. tc. 1 ftCD ELECTRIC At TAPE •AT EACH STEP USE S TUIWS OF TA«. IN CASESWHERE END MUST BE BEN^_ SUFFICIENT AREA MUST BE TAPED TQ. MASHUA CORP. PREVENT VARNISH CAMBRIC FROM SUMMERVItLC« NJ. COMING LOOSE. 2 ELEaRICAL GLASS TAPE-MEDIUM WEAVE M/2*WIDE X.004THK 3G YDS* to. BURLINGTON 'hesgon a'or equal SECURE BRAIO WITH 2 LAPS TAPER AS SHOWN (PQUrETHYLENE) 3 U 310 or CAN VARNISH STERLING VARNISH TAPE (NOTE 1} 4 SEWICKLEY.PA. HALF-LAPPED GLASS TAPE I VARNISH NOTE I . , TAPER MAY BEMAOE WITH TYPE PT PENCILING TOOL > PLM PRODUCTS, 3871 WEST I50TH ST.,CUVLAHD,OHIO METHOD I NON -SHIELDED CABLE TERMINATION COVERED WRAPWITH HALF-LAPPED LAYERS OF TAPE BEGINNING AT ONE END. A REVERSE DIRECTION AND CONTINUE APPLYING HALF-LAPPED LAYERS MAKING ONE-HALF OF THE NUMBERS GIVEN IN CHART THESE LAYERS ARE APPUED WITH JUST SUFFICIENT STRETCH TO INSURE GOOD CONFORMANCE WITH NO AIR VOIDS OR WRINKLES.Af TER THESE LAYERS ARE APPLIED,REVERSE DIRECTION AND APPLY BALANCE OF LAYERS CHART'A' MAX. VOLTAGE 600 5000 LAYERS OF TAPE 2 1 13 Z3& 36000 la METHOD 2 . LAYER OF HALF-LAPPED TAPE 6 15000 TYPE 4 SPLICE (BUS OR CABLE) TO C/T OR P/T 'A* INSULATION OVERLAP UtH A DUX-SEAL fILL WITH NO STRETCH. a HALF-LAPPED VINYL TAPE SEE CHART -A" Z 4 ALSO MINIMUM EXTENSION OF BUS INSULATION THRU SUPPORT TO ALLOW SPECIFIED OVERLAP OF TAPE COVERED PAD JOINTS (BOLT HEADS PER TYPE 4 PAO JOINT AND BOLT HEADS PER TYPE 4 PAD JOINT AND BOLT HEADS PER TYPE 4 BUB SUPPORT HALF-LAPPED TAPE SECOND TYPE 3 TAPE OVER SECOND RING BUS SPLICE TYPE 7 TYPE S *T' BUS & CABl-E TP BUS TAPING INSTRUCTIONS FIGURIW BUS-FLEXIBLE CONNECTORPORCELAIN TERMINAL CABLE TO PORCELAIN TERMINAL PAItr III - PRE ENERGIZATION TESTS TABLED PREPARATION DIELECTRIC TEST VALUES BEFORiE STARTING ANY INSPECTION OR TEST ING BE SURE PRIMARY CIRCUITS ARE DEENERGIZED. 60 Cycle Rated Careful reference should be made to each component Voltage instruction leaflet before attempting to place the switchgear in servii%. If dry-type or oil askarel-fllled -power transformers are furnished as part of the switchgear equipment, consult their instruaion books or leaflets, particularly regarding absorption of moisture, and Standard Full-Wave Impulse KV Factory Test (Withstand) Tests KV 600 V 4.16 kV 7.2 kV effects of dust and sand, etc. 13.8 kV The equipmentshould be checked to be certain no tools or any other equipment have been left in the switchgear. 23 34.5 When coimections are to be made to or from an electric kV kV 1.6 14.25 .27.0 27.0 45.0 60.0 2.2 19 36 36 60 80 NA60 95 95 150 150 HGURE13 utility, public or privately-owned, consult their -repre sentatives very early in the construction period, as many of them have very strict requirements which must When the switchgear has electrically operated circuit breakers, they are operated in some installations from local battery or auxiliary control supply, and in other installations are operated from the switchgear bus, or a connection ahead of the incoming master circuit breaker. In the event the primary source of power is locked open, it will be necessary to use an auxiliary source of power to operate the circuit breakers, lamps, bell-alarm switch, undervoltage devices, rectifiers, capacitor shunt trips, etc. Check circuit breakers in "test" and "operate" positions, paying particular atten tion to good contact between movable stationary secon dary contacts in both positions. Check puffer by placing hand over arc chute and feeling puff of air during open ing operation. Check that primary disconnect penetra be met before service connections will be made. Any indication of moisture will require that equipment be dried out before placing in service. Care should be exercised in diying-out operations to be certain that the maYimiim temperature during the drying period does not exceed70 to 75° C. on switchgear. In the event it is desired to give the equipment a high potential test be_ fore placing in service, thb test should only be made after the equipment is thoroughly dry. The value of test voltage should correspond to the voltages listed • "inTable B. Note that field tests are 75% of the factory • KV Field Test 60 Cyde test values. tion is at least 14" on cell stabs. Check that breaker DIELECTRIC TESTS Dielectric tests are made at the factory to determine mechanism closing springs discharge between "test" and "removed" positions. ' i interlocks should be operated manually to make the adequacy of insulation. Devices used as part of switchgearassemblies shall be capable of meeting these sure that protection is complete. Remove spare Iceys to supervisory office. tests. Exception — There is certain apparatus such as poten Each relay and trip device or other component should be operated manually to be certain its contacts perform their required function. Removeany material that was installed at the factory to block parts or devices during shipment. Preliminary settings for test purposes should be applied to relays. The various operational functions tial transformers, auto transformers, motor starting, reactors, and motor-operated devices whose standards call for a lower test voltage than those given in Table B. When such devices are used, they must be disconnected during these tests. are indicated on the schematics and wiring diagrams of. the switchgear equipment. Altemating P.n.qoN ~ HSElffiRA^ TDBLIC I t ^ /General public "is all persons," without" exception, who'are not -'qualified in accordance with Section 2. o . .*1 ^ fV.' Gener^ public includes unqualified persons who might be authorized ,by reason of *enq>loymBnt or-conditions to havec access to the area;T ^of.Tpower switchgear. Examples are pluxnbers, janitors, owners,..etc. '"ggMjpm T^tsotr • ^. ••;r;' -• ^ > '^dporsthe' purpose:of this bulletin,:^ qualified person is oneV^xo is I :B^^5^-#s/?:i'iihoroughly trcdned, eind :understands the hazards involved in any area, his responsibility, such as constructioa,:^ ^ - rm ^ •rtpf^ya-hinn And, mai nj^finange of switChgear appeuratUS".. C InVadditiCTi, he has th following qualifications:; -2;' ; . r—• (1). Is able to de-i-energize, .clear and tag^circuits and. : equipment in accordance with established safety ' practices. ' (2) Wescrs. protective equipment such as nibber gloves, hard hat, dark glasses, flash-clothes, etc.,. in accordance • with- established safety practices, and is trained in their proper care. (3)' Is certified in rendering first aid, especially in the technique of removing- a person in contact with a JLive circuit, and-in. applying artifieal respiration. *V ; .T - tu-'m 1 - 3. GBtoftL INSTRUCTIONS TO QUALIFIED PERSCBTSr Qualified persons shall work only on equipment that is completely de-energized from all sources of electric power, including control power. A. Understand the Equipment - - Qualified persons shall leam and understand instruction infoinnation furnished. B. Clearing Equipment for Work - - Qualified persons shall consider all circuits and equipment as l i ^ at all times until .completely de-energized, tested, grounded, tagged or properly identified, jand released for work in an authorized manner. C. Cleaning of Equipment No cleaning .or similar work shall be done qualified personnel within -the reach of parts or equipment unless they have been de-energized and prepared for work in accordance with (B) above.^ D. Working Alone — - Where Permitted — - Whi^ alonf, a qualified person shall do no cleaningw^or other work inside compartments ;• • or Compartment-doors and cc«rers unless the, equipment toJse . •worked on has been de-energa^ed and prepared for work in -accordance with (B) above. Carrying Equipment and Tools - - Qualified personnel sha^ll at all times be aware of the hazards associated with carrying and placing equipment and tools such as ladders, brooms,, mops, lamp holders, tool belts,; tool boxes, keys, etc., in places., where circuits may become energized. F. Removing Tools - - Qualified personnel s^ll exercise care in not leaving tools or keys on buses, doors, panels, equipment cases or tanks, rotating machines and in or on compartments. ANO March 1966 '•'t'' 1^1 A &-t f. -rTTTTT" PART I INSTALLATION AND OPERATION Par. # Title jPflg« 1. Shipment 2. Removal from Carrier and Inspection for Damage 3. Moving and Lifting Switchgear... 4. Storage Before liibiuliation 5. Alignment of Foundation 6. 7. Equipment Insiaiiation Breaker Lifting Devices 3 3 & Batteries 3 9. 11. Outdoor Switchgear Wiring Grounding 3 3 3 12. Ground Dettctlon 3 13. Control Circuit Fuses 3 10. ••• 14. Tightening Connections 4 15. Pqlestiglas Insulation 4 16. Taped Connet,tions 4 17. Insulation Boots . T » 18. Getting Ready for Service 8 19. Dielectric Test 8 20. Operational Testing 8 PART II MAINTENANCE 1. Maintenance Benefits and Facilities 9 A. Maintenance Program B. Maintenance Records C. Maintenance Test D. Maintenance Equipmen. 2. Frequency of Inspection 9 3. Safety Practices 9 4. Maintenance Program for Switchgear A. Metal-Clad Stationary Units B. Medium Voltage Powet Circuit Breakers C. Low Voltage Power Circuit Breakers 10 5. 600V Metal-Enicloi^ Accessories 10 6- 2.4 and 13.2KV Metal-Clad Accessories 11 7. Miscellaneous Switchgear Accessories 8, List of Equipment Instruction Books 11 12 ;V: 5r^ ? SHIPMENT The switchgear is assembled, wired, adjusted and given complete tests at the factory, after which it is inspected and packed for shipment. The air circuit breakers are not shipped in the switchgear compartments, but are packed in separate crates. Each crate is identified, and u com pletelist of its contents is included in the shipping papers. All instruments and relays are suitably blocked to pievent damage to bearings and movements. REMOVAL FROM CARRIER & INSPECTION FOR DAMAGE Immediately upon receipt of the shipment, identify all component parts and check them against the shipping list." .Make a thorough examinationto detect any damage which may have heen incurred during transit. If any damage is discovered, file a claim immediately with the carrier, and send notice of the extent of the damage to the Federal Pacific Electric Company plant from which shipment was made, giving complete ideuiification, car rier's name and railroad car number if the shipment was made by rail. Switchgear equipment, r^ardiess of whether it is to be . installed immediately or stored for a while before being erected, should be kept in a dry, clean place. Conditions . such as dampness caused by rain or change in tempera ture, cement dust, etc.,should becarefully guarded against. ' Covering the equipment with a temporary shelter ot tar paulin is frequently necessary both during storage and . erection. The longer the period of storage, the greater must be the care taken for protection of the equipment. Il| is advisable to place electric strip heaters or lamps within enclosures to raise temperature approximately 10 degrees above outside temperature at all limes. Crated apparatus which is not to be erected immediately will store much better if left crated. It should, however, be inspected to make sure that no damage has been in- . curred during transit. When arrangements are made prior to shipment, electric strip heaters circuit can be taketi out of crate so that' heaters can be energized while switchgear equipment re mains in the crates. The information wilt enable the compan) to supply nec ALIGNMENT OF FOMNDaTION essary information in support of claim. Federal Pacific metal switchgear is accurately built on true and level bedplates. This care and accuracy insures ease of operation and interchangeability. Equal care in ' MOVING AND LIFTING SWITCHGEAR 1. The importance cannot be overstressed regarding the care in handling, rigging, hoisting, roiling or moving assembled switchgearinto place. Metal-clad switchgear is designed to be handled only in ai. upright position and should never be handled in any other way with out first consulting with switchgear headquarters de sign section. 2. Each shipping section of indoor switchgear is bolted to a heavy shipping skid which should remain with the gear until it is moved into final location. Each section of outdoor gear is supplied with heavy lifting lugs bolted to switchgcai' base. 3. When lifting shipping units with a crane, it is prefer able to use two hooks simultaneously, one on each end. Each pair of lifting hooks should be equipped with a spanner bar to prevent excessive distortion. If only a single hook crane is available, arrange spaiiner to lifting rig as shown on typical outdoor gear drawing 2200-0114. Lifting from front and rear of units permits placing shipping sections side by side for bolting without interference from lifting rig or hook. 4. When cranes are not available, equipment can be rolled into place on shipping skids provided with each shipping section. Pushing or pulling forces should be applied to the skid and not the Switchgear. 5. Shipping skids can be removed by using a foot jack installation should be used. A true and level floor for this equipmei.i is of utmost importance. Alittle more than ordinary care in laying out • and prepaiing the foundation will be repaid in reduction of cost and labor of installation. The steel supporting members used in the floor should be held lev<"l until the concrete is set. The surface of the floor under the housing should not project above the sup porting member. The floor in front of the housing shuuld not, vary more than Yti" in any square yard and must not project above the level of the supporting members. The heticr this floor is finished the easiei will be the rolling of the removable breaker unit. When installing metal-clad switchgear on existing floors ' it will usually be desirable to pour a new finish floor with embedded channels or cut slots for embedditig and level ing the supporting channels. Encircling loops of reinforcing or building steel around single phase conductor should be avoided in .the areas marked foi main cables—when these circuits are rated at 600 amperes or above. One of these methods or its equivalent must be used to obtain an adequate foundation. Fig. 2 and 3 tack welding equipment to floor channels is preferred since this method does not require accurate lining up of bolts. in each corner of the shippingsection aftei tlie switchgear has been moved to its final location. STORAGE BEFORE INSTALLATION Protection against loss of equipment is an important pre caution. Trouble and delay will be avoided by having good storage facilities arranged so that the apparatus will be accessible only to authorized persons and so that it t). HOLES PROVIDED IH SWGR. 2" HOLES ON FOR CHANNa OK PLUG WELD SW'GR. TO ..CHANNa IRON. LEVEL AND HOLD EACH UNIT WITH Ml" 0. BOLT, GROUTING THEN POUR IN CONCRETE. . can be quickly located when required in the erection program. Vj-16 TAP IN BASE FOR WELDING (PREFERRED) OR BOLTING. SUGGEST W HOWE. SEE FLOOR PUN FOR LOCATION. '/4" PUTS WELDED BETWEEN EUNGES UNDER ^ROUTING HOLES. FIG. #2 fie, >3 ) ) ) R4TIN0 OF CELl WIDTH 4FPR0XIUATE OF CELL NET WEICMT • OST-S-79 TO 5-240,1200 4. 86- 2000 OST-9-ISOTO S-2S0, 20004. 26- 5800 OST-tS-ISO TO 15-500.1200 36- 4000 AND 2000 4. NOTE *APPBO«IMATE WEIQMTS DO HOT INCLUOt BBtAKES fRONT fOOr VIEW JACKS ALTEWWATg M6TH00 SfDE View OF LIFTJWO COWOU^T OR BREAKER ORAWOJT AREA CABve SPACE ACCESS 0«>£NfA#C SfCUHING ANGLE AiVCLE SOGCeST WElOtNC BOLTING OR DETAIL V CONDUIT OR CABLE SPACE BREAKER OAAWOUT AREA r ACCeSS^OPENlNG SECURING ANGLE SUGGEST WetOING OR BOLTING REuovaBLE urTine 'j\o " ; ;.va •'V;'^e, J SECURING ANSLEy^ ^ SEE DETAIL -A DETAIL "B* WECOMMENDEO METM003 OF J>HCHQHINB CONCRETE RAO AND LEVELING CHANNELS TO BE SURAUEO ST CUSTONER UNLESS OTMERWISE SPECIFIED. RECOUUENOEO NETHODS Of ANCHORING ARE SHOWN IN DETAILS 'A' B'a' The units UAY be bolted, welded or anchored to the CH«MNfL. SUGCEST 1/1 INCH HARDWARE FOR BOLTING. (HARDWARE SUPPLIED BY CUSTOUER I PHDHWAL PACIWtC WLMTWIO CHiMVELS SHOUID BE l-EVEl. WITH EACH OTHER ANO LEVEL OVER THEIR ENTIRE LENGTH I RECOUUENDED SIZE OF CHANNEL ~~ neCCMUENOEO HETHOO-W LIFTtNe FINISHED 4-X».AiP/FTI FLOOR SHOULD NOT BE HIGHER Than LEVELING CHANNELS' an;- SHOULO ALSO HAVE SLIGHT PITCH AWAY FRON CH4KNEI.S. 2200-0114 •1.'. v; .'k- J •TTT'"?" cOUIPMENT INSTALLATION Th'- '••iring diagram number of each Switchgear unit is A. li'-fiirt veiling pquipmeni in place, refer to switch- f-l?•• ; b-<8V(J driavings and, after completely uncrating equip:n'n:, check permanent [oration to see that equipment ;r every swikiigear installation. It should he of sufficient capacity to handle any .abnormal condition that might occur on the systemand should be independent of the grounds used for any other apparatus. A- permanent low resistance ground is essential for ade quate protection. A poor ground may be worse, than no ground siiice it gives a false feeling of safety to those working around the equipment. A. For 600 volt gear it is recoinnicuctj ihut a device for lifting and lowering FP-25 and FP-50 brcakctj .u and from the breaker compartments be used. For indoor switchgear it is recommended that the purchasoi i.isiall a monorail crane over the front of the switchgch,, ci Federa! Pacific c.m supply a hydraulically operated lift-truck as an additional item of equipment. For outdooi .switchgear a special hydraulic lift-truck can be supplied (see Index (or Accessories). B. FP-75 breakers are furnished with a lifting spreader, which provides a ready method of placing the breakers in their compartments when a crane'is being used. The .simplest method for two-wire single-phase systems is to connect two clear filament lamps of the system voltage BATTERIES in series across the two wires with a ground connection between the two lamps. A ground on one side will short- Follow battery manufacturer's instructions carefully when installing the battery. Be sure that ventilation is provided to carry off the fumes. If steelwork seems to be affected by the fumes," apply black asphaltum paint. Make sure that the battery charger is functioning, and that the charging rate is not excessive, lest for specific gravity regularly. GROUND DETECTION On ungrounded low voltage systems (up to 600 volts AC) new switchgear equipment quite often does not include ground detection lamps or voltmeters. Nevertheless it i.s quite important to check for grounds in the system at intervals. circuit and darken the lamp on that side. The same gen eral scheme is used for multi-phase systems. For higher voltages, use potential transformers, or static ground detectors. CONTROL CIRCUIT FUSES If battery is installed remote from the switchgear, have cables of sufTicienl size to keep the line drop at a mini FPE ECON CLASS 1330 DUAL'ELEMENT CONTROL CIRCUIT FUSES 100,000 RMS INTERRUPTING CAPACITY mum. Catalog ii—250 V Ampere Catalog #—600 V OUTDOOR SWITCHGEAR EC\-1 1 If porcelain entrance or load bushings are mounteu in the roof, use flexible connections from incoming and out going lines to reduce the strain on the porcelains. ECS-1 ECN-3 3 ECS-3 ECN-6 ECN-10 EC.\-15 ECN-20 6 10 15 20 ECS-0 ECN-25 ECN-30 ECN.60 25 30 60 Small-wiring underground conduit from the control build ing should terminate inside the switchgear at a level above any existing high-water marks. Healers are furnished in front and rear of each unit. ECS-10 ECS-IS ECS-20 ECS.25 ECS-30 ECS-60 These Fuses provide dual proteciion. WIRING % All incoming and outgoing control connections should be made in accotdance with the switchgear schematic and wiring diagrams. After wiring is completed, all connec tions should be carefully checked against the diagrams to insure that all connections are correct and proper. 1. Time delay protection against unnecessary blowouts from high inrush currents of breakei solenoid coils and control power transformers. 2. Instantaneous protection against short circuits plus a high degree of current limiting ability within the sizes listed. cent bus work also be waxed to'prevent spill or splashing TlGHTENtNG CONNECTIONS j Sus.sp'"''^ •'1' shipping break should be.carefully in- .•ipecled lo be certain that good clean contact is ob tained liefore bolting up tight, Torque* wrench should be used. 2—It is important also to be sure that all outgoing cable connections are tigiitened in the same manner as bus splices. Recommended Torque Values 5/16" Bolt • 1« Ft. Lbs. %" •" 21 " W " 45 " casting compound from sticking to adjacent' surfaces. Care should be taken to. be certain that n-.- wax is used where adhesion is reqiiirerl. The fo-'.m mole!, when re moved from the joint, may be rcysrj j'r.jviding it is rewaxcd. it is imporlanl that all vent hob.-;- he kept rican in t/ie compound boxes or foam molds lo prevent the entrapment of air which will result in voids in themolding. The entire process for assembling the mold and mixing the Folestiglas, takes somewhat less than 15 minutes. For the resin lo become solid may lake from ouc to four hours, depending on the ambient temperature. It is ad visable. however, when using the foam removable type molds, to check with a sciew driver or a pencil, the sur " *ui>|iliiTs fur rulclirl un liux tuniii'- wrindu-:', Waldrick Kiigr. Co.. I'.O. IV.I .?y8, HuiiliriKior, >;;ulic'.i, Ni w Yoik. .\nd tin; • P. S. Slurtfvanl Comiianj. Adiiisuo. illiiniis. face of the Polestiglas to see if the material has hardened, before removing the mold. The material as supplied, will have a viscosity, such that if mixed properly will com plete its reaction, making a joint that is non-tracking, corona resistant, and non-hydroscopic. "POLESTIGLAS" INSULATION (For !5Ki'' clasx only except when otherwise specified) It is standard manufacturing practice wheie piatin al lo insulate all electrical joints except shipping breaks at trie factory before shipment. Federal Pacific Electric Co.'s In operations with other than standard compound boxes type Number 1 and Number 2, communicate with the factory for specifications. Field experience will indicate that boxes can be made in either horizonl.il or vertical planes. Folestiglas mix can be supplied as a patching exclusive Folestiglas flame relardent and non-tracking molded and cast materials arc used throughout. Where it compound or filler for small voids, etc. is impractical to use cast on insulation such as on an outgoing cable connection, flame relardent Polyvinyl tape is supplied. TAPED CONNECTIONS Instructions for assembling and compounding bus joints, transformer connection etc., with "Folestiglas" insulating compound arc— For taped connections use materials as listed on attached instruction sheet, using copper meeh and conductive tape as shown. Extremecare should be taken in taping unusual contour joints with vinyl tape. "Folestiglas" is a two part resin system. It is shipped in separate containers, so that the catalyst, which is about 19' by weight of the resin, when completely stirred and mixed can he poured directly from the large container into the compound box mold. Taping a fiat or a cylindrical surface such as a bus bar or cable is a relatively simple pinress in which much the same technique b used whether the tape is paper, cloth, film or plastic. The tape lies tnitiirally in a spiral, and Casting compound is supplied in separate containers— each container of compound and container of catalyst, when mixed, will fill one compound box. a tape with some elongation so that wrinkles are not created. This property is also u-sefui in guiding the tape to maintain the proper overlap. \ inyl tapes possess this elongation lo an exceptional degree. Combined with it is a "memoiy" in the tape which causes it to contract after application and pull down to a snug fit, mininiii:ing voids or other irregularities in the insulation. This is an ad vantage if properly understood and used coriectly, but can be harmful if the tape is stretched unnecessarily to make it "conform" to certain contours. The pressure sensitive adhesive is not designed to withstand large sidewise (shear) forces for a long time; and if the contour is such that the tape tension can he relaxed by a side slippage, some slippage will take place. The identification number of the material supplied with each joh is as follows: Field joints with compound boxes. Current Transformer^ etc 2700-5053 Patching Compound 2700-5054 Catalyst 2700-5051 Picture Number 1 - . . shows the standard assembly of a bus joint with compound box. Assemble compound box as indicated in picture 2, mix resin and catalyst in line with instructions furnished with material, and described above, and pour, as illustrated in picture 3, up to the top of the mold. This material will then set to a hard non- hydroscopic mass. The black compound box is left in there are no problems of conformance. However, when a small degree of irregularity is present, it b helpful to use Many surfaces requiring insulation-stress cones, for in stance—are of such shape that they cannot be wra|^>ed spirally without excssive stretching of the tape. Usually in such cases a taping method can be devised thai will position in this operation, and is not removed. The final make use of the "men.ory" or "regain" characteristics of the tape lo insure proper insulation. is filled with Polestiglas. If the surface is developable (capable of being covered fay a flat sheet without stretching), it is always possible to joint looks exactly as picture 3, with .the exception that it An alternate method of making compound boxes in the field is illustrated in picture 4, where a foam mold is supplied. This foam mold is supplied as a unit, and is clamped lo the joint that is to be insulated. The foam mold should be waxed inside with Johnson's paste wax before it is assembled on the joint. It is recommended that the outside surface of the compound box and adja apply the tape in such a way t.hnt there are no forces tending to make it slip sidewise. This is done by wrap ping along the geodesies of the surface (lines of shortest distance between two points.) The general principle is that of letting _the tape lay itself on tlie surface to be covered; if necessary, the tape can be cut several times for some surfaces. - < :^-- 'N — - m-'-.. • r'.kJj.-'-i.' -1 [ v^ Jt^- I:- '.A , M,' I -| •'-. -V, - J ^•a-r'-'.'-l .' 'h' "'•-. ' • ••'-*• ir-'i. " ii; , ^i ' ••;. '-:C:;:!^":'V;^ m • ' ». ,A : -;y ' , >-'?J m-A M'l ;t:>^irrV,- I .V ' Ws-Iroj,! ;, , : :,-v: \-l'' 1 •' . •- ' • /' . • ) SI TAPiNG INSTRUCTIONS (from ORAWINO Z7SI-04A2.j a ROLLS DESCRIPTION ISO- 100 VINYL PLASTIC ELECTRICAL TAPE 1 INCH WIDE X 36 YARDS LG. FLAME RETARDCNT 1 002-009 1 4 INCH WIDE KNtTTED COPPCA MESH. 15 FEEr THE FOLLOWING INSTRUCTIONS SHOULD 8E FOLLOWED IN TAPING ALL main connections as required on SWITCHGEAR. kEM PART NO. 2 1CARBON SLACK^^,0£ BIASjg SEMI-CONOUCTlVE 1 72 yards long 1/2 ROLL 3 LAYER OF HALF-LAPPED TAPE.' WRAP WITH HALF-LAPPED LAYERS OF .010 TAPE BEGINNING SEE table -A' AT ONE END. REVERSE DIRECTION AND CONTINUE APPLYING HALF.LAPPEO LAYERS MAKINO ONE-HALF OF THE NUMBERS ORDtRlNC INSTRUCTIONS GIVEN IN TABLE "A". THESE LAYERS ARE APPLIED WITH JUST sufficient STRETCH TO INSURE GOOD CONFORMANCE WITH NO AIR VOIDS OR WRINKLES. AFTER THESE LAYERS ARE APP UAT.SPCCinEOlN GRP. 51 WILL MAKE KV. AMPERAGE THE FOLLOWING AMOUNT OF CONNS. LIED. REVERSE DIRECTION AND APPLY BALANCE CFLAYERS WITH NO STRETCH. FIG. I SEftVlCC VOLTAGE LAYERS "A" OF CREEPAGE TAPE BRAID. CURRENT TRANSFORMER COVERED BUS CABL£ INSULATION HALF-LAPPCO TAPE FOR STRESS RELIEF CONES cable 2 6 15.000 13 MIN. 1 1 1/2 5 6 5 1200 2 3 5 IS 2000 1200 3 3 l'/2 l»/2 2 QTY. 600 15 2000 3000 5 BUS 1: 6 ROLLS 1 e 1 8FEET 1 J f/gROLL 1 FEET l/aROLL ISOOOV. S: REFER TO THE RECOMMENDATION OF THE OTY. 1200 AMP. QTY. UNITS 1 ! 8 ROLLS 15 FEET • 1/2 ROLL 1 UNITS f 4 ROLLSl 1 2 0 FEET 3 1/2 HOLM 1 I UNIT CCNSrcrs of material 3 COKNECTIONS r'ALSO MINIMUM exTCNSION OF BUS INSULATION THRU SUPPORT TO ALLOW ifn^S'^ECinEO OvrQtAP oF TAPE. SEE FIG CURRENT TRANSFORMER I Ifl -BUS PAD JOINT AND BOLT HEADS WITH COPPER MESH FOLLOWED BY I LAYER HALF-LAPPED CONDUCTIVE TAPE BUS .SEMI-COHOUCTIVE FIG. 5 SUPPORT ^ TAPE (ITEM -HALF-LAPPED TAPE TRANSFORMER TAPE AT EACH GTEP USE 3 TURNS OF TAPE. IN CASES WHERE END I tape (irtii II II COPPER COPPER MUST BE TAPED TO PREVENT VARNISH CAMBRIC FROM COMING LOOSE. (VARNISH CAMBRIC) I ITEM 31 TAPE I ITEM CONNECTION SEMI - CONDUCTIVE TAPE (ITEM 3) SEE FIG. 4 MUST BE BENT. SUFFICIENT AREA MESH MESH fITEM 21 rircM ei SECURE BRAID NOTE o/ TAPE OVER WITH 2 LAPS OF TAPE 150- TAPER AS SHOWN 80* LOO SECOND RING 100 -H f FIG: 7 -r I -c 1 'BUS BAR TO DISCONNECT INSULATED WIRE TO BUS CONNECT/ON {folyethylene) SWtTCH STUD CONNECTION potential transformer etc. cable TERMINATION KOTE;#l-TsMr WT to «flth •W peBtlling tel. product of Pioducti, 3871 Wort r/^ V;'•• E::;: •" "v''. : -•.V - • II COPPER MESH IITEM 2) FIG. 6 POTENTIAL TRANSrORUER CONNECTION IN BUS JOINT COMPOUND BOX 5PLrC£ ! 3) TAPE (ITEM SEMI - CONDUCTIVE FIG. 4 HEAVY DUTY 600 AMP. 0R4A •^•4-1 FIG. 3 UNITS 1 FOR COVERED QTY. 2 ROLLS oe WITH COPPER MESH FOLLOWED BY I LAYER HALF-LAPPEC CONDUCTIVE tape. MANUFAGTUfttft. A UNITS HEAVY DUTY I2O0 AMP. 1 UNIT CONSISTS OF MATERIAL FOR 3 CONNECTIONS Table 'a* PAD JOINT AND BOLT HEADS FIG. 2.CABLE CONNECTION NOTE; 750 5.000 12 —ftXULAMP. < r LIGHT AND 5000 V. »> - J ^. (MSULATION BOOTS ' On 5KV class equipmcn! electrical joints are insulated with molded bus bar hoots. The boot is pulled in place around the bus bar joint. After htting two (or three as conditions require) holes are punched for clearance of the 10-32 nylon hardware. (Insulation boots can be applied to I.IKV class when phase to phase clearance is 7" min. and phase to ground clearance is 6" min. If rodgap situation is present increase dimensions by 1 inch.) id . C "Vi!.. TYPICAL BAR CONNECTIONS TAP . Norc "A TAKE OFF BOOT DETAIL BOOT .NOTE "m- MAIN l-Mi X3 MAIN, l-VL' X3 TAP 33C0A0042 \-Vi X6 MAIN, )-Vi X3 tAP .3300A0046 I-Vj X 6 MAIN, 2-M! x 3 TAP .3300A0051 3307A3239 . 3308A3239 3309A3239 RIGHT ANGLE DETAIL BOOT I-Vj X3 MAIN, l-i/j X 3 TAP 3300A0044 3307A3239 I-Vj X 6 MAIN, I-M: X 3 TAP 33(X)A0047 • 3308A3239 1-i/S ? 6 MAIN. 2-'/j X3 TAP 3300A0053 3309A3239 l-% X 6 .MAIN, l-Vi X 6 TAP 3300.\0030 Refer to Factory . BOOT NOTE "A" .i THRU OCTAIl MAIN THRU BOOT 1-% X 3 3300,A0045 3307A3239 1-V6 X 6 3300AC049 3308A3239 2-^x3 3300A0O&4 3310A323y BOOT RIGHT ANGLE WITH DEAD END DETAIL 1-% X3 MAIN, 1-¥j X3 TAP •330OAOOte BOOT 3307A3239 1-1^ X 6 MAIN, 1-V> X 3 TAP 3300A0b48' 33iD8A3239 1-% X 6 MAIN, 2-V4 X 3 TAP 3.300A0052 3309A3239 MAIN — DEAD NOTE "A": 3 EA 10-32 x 1" LG RD HD NYLON SCREENS AND 10-32 HEX HD NYLON NUTS SUPPLIED WITH EACH BOOT •:fmhA f •• .".MG nSADY FOR SERVICE rcA rcnce should be made to each component in•iirrir.'ion I' -iilct before attempting to place the switchgear in if Irv-type or oil or askarel-filled power transforinors are furnished as part of the switchgear equip ment. consult their instruction books or leaflets, particu larly regarding absorption ofmoisture, and eflfects ofdust The equipment .should be checked to be certain no tools on any other equipment have been left in the switchgear. When connections are to be made to or from an Electric Utility, [ uhlic.or privately owned, consult their represen tatives V-TV early in the construction period, as many of them have very strict requirements which must be met before service connections will be made. and sand, etc. Any indication of moisture will require that equipment OPERATIONAL TESfiNG be dried out before placing in service. Care sliuuld be Upon completion of installation, and inspection of the cir cuit breakers and other components, together with instal lation of any incoming and outgoing control connections, it is time to start operational testing. Outgoing feeder exercised in drying-out operations to be certain that the maximum temperature during the drying period docs not exceed 70 to 75 degrees centigrade on switchgear. In the event it is desired to give the equipment a high potential test before placing in service, this test should only be made after the equipment is thoroughly dry, allowing approximately 10 days drying time. The value of test voltage should correspond to the voltages listed below. DIELECTRIC TESTS The following dielectric tests shall be made to determine the adequacy of insulation. Devices used as part of sw itchgear assemblies shall be capable of meeting the following dielectric tests. Exception—^There is certain apparatus such as pclenlial transformers, auto transformers, motor starting reactors, and motor-operated devices the standards for which call for lower test voltage than those given below. When such devices are used, they may be disconnected during these tests. Alternating-current test voltage shall have a crest value equal to 1.41 times thevalues specified. A sine wave shape is recommended. The frequency shall not be less than the rated frequency of the apparatus tested. The test voltage shall be applied for one minute. Direct-current test voltage, if used in lieu of alternaciiigcurrent test voltage, shall be 1.41 times the specified altei/^>nBting-current voltage. A. Equipment Rated 60 Volts and Below That part of assembled equipment rated 60 volts or less shall withstand an altemating-curreni voltage tesi of SCO volts. B. Equipment Rated 61 to 600 Volts Alternating-current assembled equipment and alternatingcurrent circuits of equipment of higher rated voltage rated 61 to600 volts shall withstand an alternating-current voltage test of 1000 volts plus twice rated voltage, witii a minimum of 1500 volts. Factory Test. When assembled in field and connected, test voltages should be 75% of factory test value. cables should not be connected at start of test. If it is a Power Center with Power Transformer and highvoltage di.sconnect or interrupter switch ahead of the switchgear, lock the switch in the open position in order to protect the test operator. r Similarly if it is a generating station, the generator breaker should be locked opeu. If there are low voltage manual breakers, they may be , checked in "test" and "operate" positions. Extreme care should be taken that all contacts and housing switches (if any) align properly. When the switchgear has dectrically operated circuit breakers, they are operated in some installaiiona from local battery or auxiliary control supply, and in other installations are operated from the switchgear bus, or a connection ahead of the incoming master circuit breaker. In the event the primary source of power is locked open, it will be neces-sary to use an auxiliary source of power to operate the circuit breakers, lamps, belbalarm switch, undervoltage devices, rectifiers, capacitor shunt trips, etc. Check circuit breakers in "test" and "operate" positions, paying particular attention to good contact between mov able and stationary secondary contacts in both positions. Key Interlocks should he operated manually to makesure that protection is complete. Remove spare keys to super visory office. Each relay and trip device or other component should be operated manually to be certain its contacts perform their required function. Remove any material that wasinstalled at the factory to block relay contacts during the shipment. Preliminary settings for test purposes should be applied to relays. The various operational functions are indicated on the schematic and wiring diagrams of the switchgear equipment. After completion ofall operational tests, all relays should be set. All trip indicators on the relays should be checked to see that they function properly. •- C. Equipment Rated 601 to 2399 Volts— Alternating Current Alternating-current asseunbled equipment rated 601 to Upon completion of device settings and tests, the main incoming and feeder cables should be properly phased 2399 volts shall withstand an alternating current voltage test of 20(W volts plus 2^ times rated voltage. When assembled in field and connected, test voltages should be 75% of factory value. strain off studs ofcircuit breakers and porcelain supports D. Equipment Rated 2400Volts Alternating-Current The entire switchgear structure shdud be carefully vacuum and Above DotedVeltoge KV 2.4 4.16 7.2 13.8 14.4 23 34.5 Standunl Full-Wave 60 Cytio KV Field Conn. 60 CyeloKV Facloty 11-25 14.25 27.0 27.0 37.50 45.0 60.0 15 19 36 36 50 60 80 Impuhe IWIIhtland) Tetli KV 45 60 95 95 110 150 200 out and connected to the switchgear. Incoming and out going cables should be braced so as to take mechanical of various types. cleaned (preferred) or blown out, and all rear and side plates that have been removed should be rebolted in place. All secondary and power connections should ^ tested for grounds with high potential tester or merger. Megger readings of one megohm per thousand volts is acceptable. If readings are lower equipment" should be dried out until insulation resistance vdues improve to one megohm per thousand volts." Preferable readings are Operating Voltage KV 1.2 2.5 5.0 8.66 15 Insulation Resistance 12 25 50 150 300 Megohm at 25 •Sir 11 A preventive maintenance program is outlined for me dium-voltage, metal-clad type switchgear, low voltage After the switchgear has been serviced and adjusted, its operation should be checked before it is returned metal-enclosed switchgear, and air-magnetic powei c-licuit to service. This can be best done by putting the breaker in the test position and operating it wWb breakers. The outline lists benefits to be derived, recorda, tests and facilities required, and inspection and servicing its associated control and protective devices. If it is steps. desired to lest the breaker outside its compartment, use the nine-foot test-jumper drawing #3352-0017 supplied with the switchgear. MAINTENANCE BENEFITS AND FACatTiES Basic elements are outlined for a maintenance program D. MAINTENANCE EQUIPMENT of switchgear installations. A. MAINTENANCE PROGRAM Adequate maintenance equipment ^ould include: I. Spare parts for at least those parts of the switchgear that are vital to continued operation. Manufacturer's A well executed program has these benefits; 1. Longer life of switchgear and fewer replacements. 2. Reduced time on repairs and overhauls, and the op tion of scheduling them at an opportune time. 3. Fewer failures with unexpected outages. 4. Timely detection of any imdesirable o^ratingco.iditions which require correction. 5. Improv^ plant performance and increased operating economies. B. MAINTENANCE RECORDS A file should be established and include: 1. A record of all installed switchgear and its mainte recommended list of spare parts can be used as a guide in combination with operating experience to determine variety andquantity of parts to bestocked.. 2. A well-lighted shop equipped with following; a. A test cabinet for air magnetic breakers or an inspection rack. ' b. Maintenance closing device for power breakers. c. Test jumperfor connecting breaker to control cir cuit when it is outeide its compartment. d- Relay test plugs for making tripping, timing and e. calibration tests of relays. A selection of ammeters, voltmeters and instru ment transformers. An insulation resistance tester. An overhead crane or hydraulic lifting device. nance schedule. FREQUENCY OF INSPEaiON Nameplate data of the equipment and its major com It is generally good practice to inspect equipment three and drawings. spect and maintain it every one. to three years depending on its service and operation conditions. This suggest^ ponents, instruction books, renewal parts bulletins A list of all items which have to be inspected and what adjustments are to be checked. 4. A record of past inspections and test results. to six months after it is first put in service and Aen in schedule is only a guide. Conditions that can make more frequent maintenance necessary are: 1. High humidity and ambient temperature, 2. corrosive atmosphere, 3. excessive dust and dirt, 4. high repetitive C. MAINTENANCE TESTS Maintenance tests are applicable as indicated: . Insulation resistance tests of the breakers and of the duty, 5. frequent interruption of faults, 6, older equip* ment, and 7. history on preceding inspections. . SAFETY PRACTICES readings and comparisons made. Deterioration of in sulation and the need for corrective action can be Maintenance employees must follow all recognized safety practices, such as those contained in the National Electri- > cal Safely Code and in company or other local safety regu lations during maintenance. All of the units of switchgear to be maintained must be de-energized, tested for poten^®1| pounded and tagged out before removing covers and ' sively lower after each test. the solid insulation surrounding an energued conductor High potential tests are not required and are not recommended except in special circumstances, such protection to personnel. Another example is the mainte nance closing device, which is exactly what the name switchgear bus can be useful in determining the con dition of the insulation if they are made regularly. Since definite limits cannot be given for satisfactory insulation resistance, a record must be kept of the r^gnized if the instrument readings are progres as after repairs or modifications to the equipment that included the primary circuit. When such tests are necessary, they may be made using 75% of the standard 60-cycle insulation test voltage for new equipment. barriers for acct^ to primary circuits. As is well known, . in power apparatus should not be relied upon to provide imphes and should never be used to close manually a' circuit breaker that is connected to an energized circuit: All removable devices, ^uch as the circuit breakers and rollout potential transformeis, should be removed from • the metal-clad switchgear hpqsing. , V. Clean silver-plated breaker primary disconnecting de ance program for switchgear vices. Wiether cleaned or not, lubricate devices by •—' *, nUllML ,„r, ri.nancf lllC Ilc-I" - prosram should include . f the 1 rthorough 11 • • applying a thin film of slow aging, heat resistant inspecliiin. servicing and adjustment of the totlowing components for 2.4-13.8 KV operating service. petrolatum. ' 5. Inspect breaker operating mechanism for loose hard ware and missing or broken cotter pins, retaining, A. METAL-CLAD STATIONARY UNITS rings, etc. Examine cam, latch and roller surfaces for damage or excessive wear. 1. Remove accumulated dust and dirt. Vacuum cleaning is recommended. 6. Clean and relubricate operating mechanism. Use a non-hardening grease to lubricate cams, rollers, 2. Wipe insulated buses and bus supports with a clean cloth mobtened (when necessary) with a petroleum solvent or similar cleaner. Wipe insulation dry after latches and props, and pins and bearings. We recom mend LUBRIFLATE, "AERO" grade, manufactured by Fiske Bros. Refining Company, Newark, N. J. cleaning. 7. Check breaker operating mechanism adjustments and readjust as described in the instruction book. If these adjustments cannot be made within specified toler ances, it will usually indicate excessive wear and 3. Inspect buses and connection bars for physical dam age, evidence of corona cutting or other conditions that can indicate deterioration of the insulation. 4. If taping has been damaged or needs replacing fol need for a complete overhaul. low instructions on Federal Pacific drawing page 6. 8. Check control device for frradom of operation. Re place contacts when badly worn or burned. 5. Inspect alignment and contacting of primary discon necting devices, checking for signs of abnormal wear or other damage. Note; Discoloration of the silvered surface is not usually harmful unless caused by sul phide deposits which can be removed by a solvent, 9. Inspect breaker control wiring for tightne^ of connections. 10. After the breaker has been serviced, operate it slowly with -closing device to check freedom from binding or friction and check that contacts move to the fully opened and fully closed positions. Check electrical operation either in test position or rerhoved from such as alcohol, or by silver polish. 6. Check adjustments and operation of safety shutters, interlocks, auxiliary and limit switches. 7. Inspect all relays, contactors, switches, fuses and other devices for correct operation. compartnient. 8. Check tightness of anchor bolts and structure bolts, also control connections and continuity of wiring. C. LOW VOLTAGE POWER CIRCUIT BREAKERS 600 VOLT AC 9. Check strip heaters and clean air filters at ventilation openings when these are present. The preceding information applies in nearly all details to Low Voltage Metal Enclosed (600 Volt AC) switchgear, both indoor and outdoor, the differences are only minor, and are due to physical differences in the switchgear. 10. Repair damaged paint finishes. B. MEDIUM VOLTAGE POWER CIRCUIT BREAKERS METAL-ENCLOSED SWITCHGEAR 600 VOLT (AIR MAGNETIC TYPE) 2.4 TO 13.8 KV MAXIMUM Air magnetic type circuit breakers should be maintained SWITCHGEAR ACCESSORIES on the same schedule as the metal-clad units, or ever>2500 non-fault operations, of at least every six months, Descriptipn whichever comes first. It is also recommended that when Part No. "Breaker Racking-in Handle or Crank . the normal operating duty is a combination of fault in terruptions and repetitive operations, the breaker should be inspected and serviced after a fault operation at or near its interrupting rating. Remove the breaker from its housing for inspection. FP-25 and 50 FP-75 1101 B 9251 11.51 C5036 "Breaker Maintenance Closing Handle FP-25 and 50 1151B 9252 FP:75(2Reg.) 1. Wipe insulating parts, including bushings and the Breaker Extension Rails inside of box barriers, clean of smoke and dust. . Repair moderate damage to bushing insulation by sanding smooth and refinishing with a clear insulat FP-75 (2 Req.) 1151 C 5214 "Breaker Emergency Charging Handle ing varnish. FP-75 Only 2. Inspect alignment and condition of movable and sta tionary contacts. Check their adjustment as described 1.151 B 5349 Breaker Lift Yoke or Chain (Use With Overhead Crane) FP-25 and 50 . in the instruction book. 3. Check arc chutes for evidence of damage, and re place damaged parts. When arc chutes are removed, blow out dust and loose particles. 10 4051 A 3274 FP-75 Breaker Hydraulic Lift Truck FP-25, 50 and 75 only . FP-25 and 50 only • 167-002 2651 B 0200 2652 B 0200 FP.25, 50, 75 and 100 2653 B 0200 •' ,• iViSTAL-ClAD SWITCHGEAR 2.4 TO 13.8 KV Breaker Test Caliinct—Outdoor :SWITCHGEAR ACCESSORIES © Specify circuit requirements Description Part No. Breaker Racking-In Cranks DST-5KV-15KV, 20", 30" &34" D.ST-15-.SOO DST-15-1000-.3n00A Wide Breakers Non Walk-in •Hand Closing Lever Gang Operated Di.sconnecf Switch 2252-0222 5 and 15KV (Manual ISG only) •Arc Chute Lifting Yoke DST-5-75.5-150 Walk-in (And right end cell is 17" •Breaker Maintenance Closing Lever 2251-0215 1551-2826 1551-0429 1551-1693 15521693- DST-5-350 1551-2454 1551-2124 'v-f * Standard Accessories normally supplied with switchgear. All other items included only where specified. Breaker Test Jumper Cable—9 Ft. (18 Points) (Not required when test cabinet is specified) 33K B0017 MISC. SWITCHGEAR ACCESSORIES Closing Rectifiers — 240 V 60 cycle AC (264V Max) •Breaker Test Jumper Cable—9 Ft. (30 Points) (Required only if test of hrkr. out of cell must include circuit function of the auxiliary contacts) 125 volt DC intermittent duty. AC not to be applied longer than one (1) second nor more than ten (10) times in any one minute period. 3354 B 0017 Part No. 100 Amp4-8-1 Stock, 240V AC. 125 Volt DC 2701-0244 60 Amp 4-8-1 Stock. 240V AC.125 Volt DC 2702-0244 3351-1458 . (except 5-350) 3352-1458 DST-15KV-30" Wide Breakers Arc Suppression Rectifier (DST Breaker only) 3353-1458 125 volt DC—Service 1-Stack Steel & Aluminum Bolted Cell Non-Walkin DST.17".21" Alum. House 2251 D 2851 DST 30" Alum. House 2252 D 2851 DST-17".21" Steel House DST 30" Steel House 087^^)04 Hook Stick For Disconiiecting Switches 2253 D 2851 2254 D 2851 30" Steel House 5350 & 15-1000 DST 30" Steel House 5350 & 15-1000 S-foot Stick 3751-0540 10-foot Stick 12-foot Stick 14-foot Stick 3752.8540 3753-0540 3754-0540 Cable Lugs, Cast Eyebolt—Dwg. 2701-0010 Cable Range 'Breaker Handling Dolly—Indoor DST-5-75 #10W to #2W 2C to 4/oC 1551-2825 2251-0333 DST.5-250, 5-350, 15-500, 15-1000 Breaker Test Cabinet^—Indoor (Except 15-10()0) 125VDC QoseS Trip (4101 D 0116) 2701-0010 2702-0010 250MCM to 500MCM 2703-0010 600MCM to lOOOMCM 2704-8610 1250MCM to 1500MCM 1500MCM to 2000MCM - 27a'>-0010 27064)010 3354 D 0070 230V ACClose Cap.Trip. (4101 D 0117) ; Touch Up Paint 3355 D0070 Exterior outdoor dark gray ASA-24 230V AC Qo8eBll%iiyTrip (4101 D 0115) - Interior indodr light gray ASA-61 3356 D 0070 250V DCQoseS Trip (4101 D 3987) 230V ACGose Cap. Ttlp (4101 D 0117) 230V ACGoseDCTVip (4101 D 0115) .= 'Arc Chute Maintenance Prop •Breaker Spring Charging (Stored Energy) Lever DST I 2751-0145 DST-15-500, 5-250 DST-5-350 DST-15-1000 Breaker otherwise use 2252-0222) 2253-0222* \viMJ 2251-0277 3351-1807 2251-0222 DST-5KV-17" Wide Breaker Outdoor DST-5-2S0, 5-350, 15-500 & 15-1000 3.351-0660 Cell Main Contact Wrench—15KV DST-5KV-17" Wide Breaker Indoor & •Breaker Outdoor Transfer Truck DST-5KV-20" Wide Breakers DST.5KV.30" Wide Breakers I -1-• : 48V DC Gose, Trip &Motor (4101 D 5114) Joint Compound Box Ordering information 3359 D0070 Box &Compound (1 Connection) 3360 D 0070 Joint Compound Box Ordering Information ViX 6t 3366 D 0070 Box & Compound (1 Connection) 2751-0470 V4 X 6 Conductors Kit ' 2752-()470 For Insulation Boot Ordering, .See Page7 - '• 3367 D 0070 Unit Heaters Description 120-208 Volts, Complete Assembly, 3368 D 0070 125V DC Close, Trip &12SVAC Motor (4104 D5U4) 3369 D 0070 115V AC Close, Motor &DC trip X 3, 1/4 X 3 Conductors Kit 48V DC Gose, Trip &125V aC Motor (4103 D 5114) Finl^ S-20. 3357 D 0070 125V DCClose, Trip &Motor ' (4102 D 5114) Finish S-18 • Part No. 125-375 Watts 2752 B 0569 240-277 Volts, Complete Assembly, 3370 D0070 230V AC Close, Motor &DC Trip 3371 D 0070 . 230V AC Gose, Motor &Cap. Trip . 3372 D 0070 300-375 Watts . . 2751B 0569 120-240Volt Thermostat (Close55'F, Open65°C 1604)01 277 Volt Thermostat (Close 55'F; Open 65.°.C) 11 • • Switchgeor Indicating Lamps Pataloi: No# ~ Description Catalog No. Description 1 Resistors Lamps—not including color vcps. Voltage Series Resistor OHMS AC or DC 115 125 2754-0135 27554)135 27564)135 27574)135 2758-0135 ' SERVICE VOLTAGE OHMS 24 110 2701-0116 800 2900 2702-0116 1400 3200 2703-0116 2900 115 3200 125 208 800 1400 70 . 2708-0116 . 50 2751.0135 27524)135 2753 0135 • 50 70 - 208 5800 2704-0116 230 6500 27054)116 5800 2706-0116 6500 230 2707-0116 7100 250 7100 2.50 110 24 Indicating Lamp Parts Color Caps green 2703 0117' amber v.:?; amps. Spacer 1/32" ' Receptacle asseinbly, leas Resistor, Bezel and Color 2701-0124 2751-0119 . blue 27040117 27054)117 24-E Lamp 24 V. .032-.b38 064-007 red 27014)117 2702-0117 white Cap. Spring Retainer Washer 2701-0118 Instruction Books MISC. SWITCHGEAR ACCESSORIES 600 V Air Circuit Breaker IN-810.9 IN.810.10 FP-25 and 50 FP.7S.3000 2.4 to 13.8 KV Air Circuit Breaker DST.15,250,500 DST.5, 150,250 DST.5-75. IN.820.2 IN.820.2 IN.820.5 Supplement for Stored Energy Spring Supplement for Stored Energy Hydraulic Ground and Test Device Oil Immersed Transformers Oil & Askarel Transformers Filtering &Testing Oil, Enclo.«ed Switchgear Switchgear IB 5 050 CDGV IB 5.051 Directional Overcurrent CDD IB 6260 Overvoltage and Undervoltage VDG Generator Differential IN.820.9 IN.822.0 INT.lOO IN.266 . IB 6360 be Timing IB 6400 Immediate, Single Shot Reclosing Multi.Shot Reclosing VAR 11 IB 6420 VAR 42 CAG IB 6425 Instantaneous Voltage and Current Auxiliary IN.T-7700 IN.T.103 IB 6350 DDG DDT IB 6320 VAT Instantaneous Overcurrent #32956 IB 6300 • ' Transformer Differential IB 6450 CAA VAA IB 6460 INSTRUMENTS Type JA and JD Long Scale Switchgear Instruction and Maintenance of 4.16° and 13.8 Metal •>/•">• .''G'-'Ph h..: • •V A "•/r", •?;,,, r-iKi • •;• V''t. ;':';^-'t.;-^s i-r^' e D IL-' AG-pA-i I •• • '• "• . - ",•' - *•-.' \ • • m i» • non &•-; D GfinTbrApT-i [_j- ^' S • 1K a i 1 'VyiinilWhM"-'** iiuiiiiuiilH WM 1 11 - { -. ' ; •••in i-•fe'-i ift' . -.fe*- i 1 ' m I /- • V: ! iu i y! 1A »G'v' r-i';? 5h;> ••',• fAiJi. iiixi, ii AAMf I ;• , Low Voltage Metal-EnclpsctI Switchgear with Type FP Air Circuit Breakers i •.-aaa-A'I' .Vi»-I :T'---1t--v,v-.jA - -AAaaA' FP25-600 •• Air Circuit Breaker Federal Pacific Metal-Gncloscd Switchgear is specifi- • cally designed for use in industrial plants, commercial buildings, and utility cpjppanies whore a high degree of service continuity and reliability arc required. This equipment may be anplied at 208, 240, 480, and 600 volts " a-c witH vitejryptij.g ratini^S up to 130,000 amperes synmit.k'h—.! vl'iO."?'! atnperes asymmetrical circuit brcakei's having SPiCop a^npcrcs interrupting G-" Federal Pacific Low Voltage Switchgear utili-zes the| most modern design'concepts providing maximum pro-'' tection to distrfbution equipment and complete safety to *•?--'"••"•t I-—".^nnel. With tell dooc •All Federal Pacific circuit brokers employ. K stored „ . energy mechanism. This permits safe closing on all . - ^ circuits because the fast closing, speed, of the circuit f-'. V.V'h incrcas.-'s the range ot the breaker siisc n.atcan be safely ' g^r assembly, .Federal: PaoW builds a>pe PP50 air capacity which:may be stacked foiir high. . : ..A AA:' :-'•'ih^rr^rU -/feu, circuit-.'' liieakers can be placed in either of three positions: "C ' ' • Every switchgear unit incompletelyi^^ksemb^ed.andr .:^ wired priorto shipment. Rigid testing andfquality con- /vA. : trol procedures insure cbihpliancc \rith thm £uierV rn . V quirements and applicablQ industry .stahdarids, fnduding •• ' those of ASA. NEMA, and IEEE. ' ' , '; ' .^' A; V Signif.cant design improvements—primacny.iri the air • "A" ; '" circuit breakor.'—enable Federal.Pacific to produce.rpli- AAri..;v: able metal-enclosed switehgear^arid pm'TOit 'consjd«jib}*e4A'r' ' f/^^^ sayings in their applicatioiL .-''AA-'AAAIA^'AAA AA'•: A:•• •;-A-A-AAA'::A'AAA..AAAi^^ i'x'l • .,• £' ' •••'.f-ii io u.t.4.'i -r . F£=OE;RAl- P»ACfF;Cr ^ r-iA • d' ----- El£..tJC T}- 1A1 Low Voltage [ItetarEncfosed Swltchge^r 600 Volts a-c—25,000 to 150,GOG AiTiporss 10 I Y ' *' '••i; •- • • • ::••..j: ••' '' ^ ; i:!: 1 '• • 'if.-! ; • "hk ;ife*vy.v!5l^" fe;?;''"- •' ••l* • ; t t : I •', y.-.'' •,•'•• .-- iGj'j.'riV"'' • ! i : -r -li • ;• , . , ' ' :- I ^n •; • ^$1 3') t.* f f j ' y:-,.A- «v.- -v < • .*- i } 't *1' '..'^ i •.ijs'rrr; asi' ' Kr)l :.s:••;>' '* V. -../ '}-.5.• • — TT/V. ' r* • "'' :'•. •'«, TiSSj:; —••^•" .^•y . ,, * iv' . » •£.••- •• •• 'j • • . T» . 1. •• • ; \ "i ' • I J ' ' Ceil for FP25-8dO clrcnit breakers ' If-,.. ;;ivSid fT'-vii. '7 *•• *"• Bjsigfiasas , fe-i,'. . *'•••• "i Mf-' ('• 1;:^ Iv.Mfer •<:••••.'' : r Bu^compartment , tvO '(71^ CONSTRUCTION , Federal Pacific Low Voltagre Switehgear utilizes the most modern design concepts. Circuit breaker cells 'are made of formed sheet steel and are jig-welded to insure accurate alignment for interchangeability of circuit breakers. Universal bolted frame conscruciion provides the rigid steel framework for the switcbgear exterior. Top, side, and rear bus compartments are covered by removable steel plates. Bus bars arc heavily silver Cellfor FP50-i600 circuit breakers ! v ,'5 1 - /? plated for maximum conductivity and are securely braced to withstard the shucks and. magnetic stresses caused by fnu:^ "iirrents capable of being produced by the system in which the switcbgear is installed. • . .V j!'-: .v-!- Terminal blocks for control circuits arc located a safe distancc.from the bus, and are accessible from the rear of the switchboard. . • Each breaker cell door is louvered to provide adequate ventilation ncce.ssa ry for the switcbgear to stay below lb" prp«erib»f' rpmpp'o^ure rise. Prior to paiiitiiip-. all nietal paiU are tompietely degreased and given a phos- 'ijl: •' ISbaked on to.provide a durable finish. V?v"v.rv-'.v.':--vrr.v:' - .• -lA' . I' •"• A. phaiizing treatment. This preparation is followed by .T application of a standard ASA-61 light gray paint that • .»>;• X.K''-- ' ' • ; |';y' 7,. , • . • I- G ' . Cell (orFP75-3D00 circuit breakers ! ^ . .. -t r ......... .-..-t.. . --.....j,.. ... pv SCTR5C -iCOfWPA-NV l.'i^VV'V 'V.- Low Voltage Metal-Enclosed •^QaT 600 Volts 2-0—25,009 to 15.0,000 Amperes !C Oescrir -V* Sheet r»c,- • • 3 - * <• »*i '( three position drawout Type FP Breakers cap be inovcci from •"Connecteci" 'I'. "Tost" or "DisconnocUid" position witiiout oponiriK the : • rm cell door. An operating lever is inserted into a drawout . cam, and the breaker position is chanRed by a single • W- stroke. An indicator is clearly visible on the drawout cam for Quick, positive identification of the breaker posi tion at ail times. The interlock cover plate must be moved before the drawout handle can be placed into the cam. Movement of the cover plala automaticaiiy trips the breaker insuring personnel complete safety by mak ing ifimpossible to move the breaker frdm any position with the main contacts closed. Illl... - Connected position '. • L V- -r-.v"., :;V- -'f t. ? I . '''''' Test position Disconnected position [ i (A*' T-'M..,, . TELESCOPiNQ ROLLUUT '!3 t" —i •'. -, i-it'-'.' 1' ti 1ii ^ •- Breakers can bo completely with drawn from the cell for examina tion, maintenance, or replacement. Teles-oping guide rails rigidly at^chod to the breaker cell provide a substantial support for the breaker to roli in and out A posi tive "stop" at the end of the rails prevents further travel after the breaker has completely cleared the enclosure. s. •k- ""^>^1 I: ..-V'' •% i 'S'i' ICraaait. W- *• ?• , PSSfht-fSA?- P-.Sv 'FtC -HI-^CTfTJO COMP»AnV P-r.th*., ".'i '-" 'l • Low Voitage iVIetal-EncIosad SVi-dtchgear 600 Vafts a-c—25,000 ta 150,000 Arrneres !C -i-.'iR'i-. OUTDOOR CONSTRUCTION A fuH sekction of both steei and aluminum outdoor housings is availu!)lc—with standard piMtcotod-nisle construction. Tho .basic indoor switchi^car assembly r.V'' is mounted on a steel or aluminum base. Then an outdoor enclosure is built around ,tbe switchgear. Tbe outdoor housing oonfain.s lights and reeejitacles, as well as screened ventilating louvers and heaters to prevent condensation. Accessibility to the front and rear is pro vided by doors. Outdoor steel housings are phgsuhatized followed by an epoxy undercoat and given a finish coat- . ing of ASA-2-$ dark gray paint Aluminum outdoor housings may bo natural finish or at user's tipt'on ol'odi'ed a light green color. The allodiz- ing process is aiso a preparation for paint; and either at the time of manufacturing or at a future date, a com patible paint may be applied. All outdoor switchgear is coated with an automotive type "uudcrseal" to provide protection against deterio ration to all surfaces not acceasi'ole after iiistallation. Federal Pacific outdoor enclosures have been tested in accordance with MEMA standards and were found to greatly exceed the requirements in that wat«!r whb com- 11 1. ''i: ^< 1' •i;-N 'i/ »• • pletely excluded. r-i i i' ♦" , . , \rf .1 l. '1 r>'i" . •Ibi •' .• • .^Mv ''iv-'Ss: '•I- lor-.:"' V,'... •..-•-tr-vii.'.:'.' AlURilRum Otiidoor Hotislne rrtl'fi'if." 11 te'' 'IV Lr "•.'V r'' Steel Outdoor Housini r 'V. .•••-,r^v.'.'v- V,- 'PSDKIRAl. PAC ©LASS Voitage Motal-Encbsec. / D':i;.cnr -!•••":' Shee-i SOO Volts 2-c—25,000 to 150,0'7o . .t;pares 1 ' FP Air Circuit Breakers 9Z a-iVr* •' .1.. "m' ilf '-v-ij , •1-' ; ,•*?J: ?"'^f A."* »1 FP75-3000 v4- f^;; IT;;'-?!;! g I**- "u'.V ; . FP25-600 '•'\ r . •' •«a < . '1 7' 'Nv- •, i- " -:.gT '! >• • <•' h -• "= • >• i ' 1 •.' . •. , , •*•:• «V-* ? ^ ^ 1^71 i FPlGO-4000 FP50-1600 i i. '••V-'-.-V"''•' •" -'; *^i.' '* •**'*' • t-r« r-4 ^ • tz^'fcaA' FEATURES: Dependable stored energy operation j Manual—electrical—^manual/olectrical operation Field adjustable timing device / Low-loss hinge contacts / Safe, three-position drawout FP25 Breaker is equipped with a stored energy mech INTERRUPTING RAHNGS anism and may be provided as a manual,' electrical or The breakers, though rated on a symmetrical basis, are manual/electrical breaker. tested under maxhmim asymmetrical conditions itn'fft FP.'iO Breaker is equipped with a stored energy mech.nnism and may be provided as a manual, electrical or the test eiraiit X/R ratio being not less than 6.6, which corresponds to an average asymmetry factor of 1.17. To determine the instantaneous symmetrical short cir manual/electrical breaker. The compact design of the FP50-1C00 enables it to be stacked four high in a vertical section which reduces the overall size or the assembly. FP75 and FPlOO Breakers are equipped with an electri cally operated spring charged stored energy mecha nism. These breakers have provisions for' emergency manual operation. cuit current, use the sub-transient react-sncc of the rotating apparatus (both synchronous and induction machines) and the impedance values of all interveningportions of the circuit to the point of fault Note that' for these low-voltage systems the impedance of short runs of conductors, bus runs, current transformer and intervening circuit , breakers themselves, may- become important elements in limiting the total short circuit as they usually represent a relatively high percentage FP breakers should be applied within their assigned voltage, continuous current, interrupting and "shorttime ratings and should be. selected to provide the pro tection required by the other components of the circuit. The following table shows both the asymmetrical and • symmetrical current interrupting ratings. FP breakers are equipped with a direct acting over- TABLE II interrupting ratings of the total system impedance. current trip device. Trip coils should be selected so as to provide the minimum trip setting required. Table 1 shows the standard coll ratings that are available witn each of the different FP :breakers. TABLE t ;.tandarcl current ra. qgs (amperes) FP-50, fP-25 I5X 20X 30X 40X SOX 70 SO too 125 ISO 175 200 225 250 300 350 400 500 £00 15X 225 20X" 250 300 30X 40X 2000 2500 3000 Breaker voltaje type FP-lOO • 4000 5000 6000 4Bt-80a 350 • SOX 70X 400 500 SOX lOOX 600 800 1000 1200 1000 125X 150 175 200 fP-7S : System 241-480 240 & Oelow FP.25 FP.60 FP.75 FP-ICO ahcrt-tlme measured St raring wilhcut Instant vy cycle ofter lault, amperes* cerfesfrlp asym metrical (overage 3-pl)39e : rnw) 25,000 • 50,000 75,000 60,000 rp.75' 75 rS fP-IOO 100,tSP FP-75 rp-£o, Fp./S FP-lOO 50,000 asym metrical 85,CCO • 30,000 50',c.no ;.5,cco dS.COO 1 . 42.000 lOOXlCO I 85,000 75,000 1 devlco. amperes rms 65,000 35,000 30 Cycle symmetrical 22,000 42,000 100,000 rP-25 FP-50 with tabTfl III due to their Ki withstoftdabilily. f .Interrupting rating current 65,0.*.0 153,000 1 13O,'J00 25,000 . 50,000 75,000 100,CiJO sym. .metrical . 22,000 42,000 05.000 • 85,000 • i 25.000 ??.no6"~' r-o.floo 75,000 -17,' •'0 103,000 ? 5,000 .• 25,!:i;o 50,CO!) 22,('f~ 75,000 , 100,000- 42,000 : 65,000 85.(03 ""*11'"-'"' -l 'J.s F E O K FAO? Fi C 2_r CT";';: c cc T" Am V .. '•I' r :•. , " -; "i.ow ^'oStege, fl*2tel-Er!do£.^d S-vitohsaaij-'iu Vci4s a-c—"5,0QQ to 15d,CD0 Amperes SC '"K"" : , .,.;r' .-^'awiS^'V • STORED ENERGY MECHANISM Fedursl I'acific sturfid energy device, iociited behiml tlie front plate, hns springs that are charged either manu ally or electric.iily to provide a constant quick-make of chc tree'-:":' -ts The fast closin-' speed of the breaker is i':deiien:lcv,v of the operator's netion, and it is impossible lo tense or slow-close the breaker contacts. This consistent hitrh speed increa.scs the ranfre of breaker sizes which can be aafoly operated n-.anually and reduces breaker maintenance by extending,'contact life. Control power rpquircments are virtually eliminated with .stored enercy because the charging force is sup pliedeither manually or by a fractional horsepowerelec tric motor. This stored energy oponuion reduces the : • Ktr IJ .«NT. n -/jir I t- y VV II t A K ,l^\xUtX* *> !:•' "X •Oi ' I . lii i:^AiaJXKl i 1:" •i • " ^IMT.. .' -< f, {.irw.. « 0 ' ".. ... isiBi;, :;y;yv;.'oSKORTofiAY fcSii r,-^nr'.V TD-1 Tifflliig DeylctFrontyieW. : . .TD-2 Tiinlng bovice Front View . . , c i - ,ir!3 ...., I if •-. •• •• ' Vi ; •• ••-1 'i ^ ; ' mmM IKiliC . i;-- j . t ' '^TDiT^tlhiirig Defe •;5y •.. ' : "I INTEaRUPT NO RATING ASyMMHTRlOAL .amperes , •:, is.ocQ • zs.MoV . ; . •: 480V socV; : • IS v, 22,000:•.• :.: 7o; • ?0,CC0'.. ^••; ; ; .•.••«,ooo--.150' 'CC.OOO ; ; '."50,000 • ' 5co; soo 7;-.ooq •'>:•'•: • .•.•••..•:'.';;ts,oo9...:' "v .:;. 500 •.; ^.^• V . ^OO.CM:" i•.•.,• ..•>•:, •••;-';85;cyo''. ••'2ots>y, yadoo''.' •• ..'. •MSO.OOO ••' ":-' vi30.ooo••••. y:.' r Aooo-'y . . . 4' ^ I'T/ 240V IS" 3" v2op6:' '• TRIP COIL HIH. BifiD G CYC. TRIP STMMETRICAt / WITH SHORT DElftV TRIP • wiTHilHSTANTANEOOS . .. : AHPESESv'..: vj . 24pV; •..' .-.14,000'' -'i" J V TD-2 TimihgDeviCB Side VioW' : . •• .'3 • • 250. COPV Z9 70 70 250 v. 500 . ;5oo.. •; 2000 •' •400(1 t f.-V •• •.*" /w -• 500 2000 .Max."3SHn- :• 30 CYC. 14 CYC. • 48DV 70 • INTER. BAND;' 2000' 240V 70' 150 • 2;4l 1000-1000 2000 • . 4000 . -w-. . ^ 430V.; BOOV :240V 70 : v.-w 150 . ' 150- : .70 250 loop" • 4C0V SQOV 70.• . ,' .'70 •••150 .-aso;' ! '250 • .150 : 2bo - '.lOOS; . ."1000, ' iiboo. 2bG0 ' yiooo; • .2000.: y'2obo ••4000 '"i ' 2000 • ^ -<• '^,r.':A'.. Voriisge Metal-Enclosed Swfijcffgear • ••.-•• . 300 Vfilts ?i-c—23,000 to 150,000 Ainpefa$ iC ..:h- Dvr V'"-' i.-' •. •. :•.' FP25-600 • V „ t'• • •V AIR GIRaOlT BRtAKERS' •' . •• i,'•" K- V'!' I r •' STORED ENERGY MECHAM.ISWi Manually, Electrically or Manually/ElDctrjcally ;> Operated •P '• • • f 'i; -'i .. . .* i -' t >•;,•: s."), ^ ...\ ' " rAp:' M}:.. r V .. I. •.r V ^rV-.. ' - • , i ?. DiMENSIONS! "•'• -• USti',' I"'" "• 3''p-'33.^ iilAA ::-'v •;-\v r -Fyv;'. ^= ; • 'V i''." - '-< eV. • •. ; , 0' • ••' -3333^3: •^- •? :3 3 'F*'!, ' •'•'••- -• -4v "•• •• • I ... . • • ' 3?iiS3^m-. ^\ ••3--3 '• -'i >'•'•' tf-' '.:- •-.-•.p .;' 3— -i ^BSi'Sti.S!... .w-s.-- " ••"K '.v?. iiliWiP'•••••.;— — - ^•.^ .. .1 • IMHRnUPTlKG RATIMC. CURRENT MEASBHED BREAKER TYPE ?- ' ::'-fns-m': ' .'• \3 •-ymMt.WJ' •••"^ -. A .3 .. SYMMETtliCAL y'• -• •' • • • -' - ASYMMETlliCAE •, 1 : FRAME. SIZE CP" TIHU0U3 CURE] MT BATIMr, OF CL'i! Etii "•• . ". -.- ' '." ' STWMCTHICAE . V/IIHDUT SERIES TRIPS "- y2.woy yy'V:' ••' • • •-a«Aaa' 22000 F,;;, -W 35000'j.:; ;-. • • ' •; • 130000 •' > - • 3:3-;2SOOO; yAj, •' mnnn • ' ,, 42000 ^ y ' •r-.yy '. -• 480-241 240andBijloW / 1-^—: 30 CYCtE SHOAT-TIWt flATIHC-WITHOUT . SERIES TRIPS, AMPERES CABRYIHO PARTS ASYMMETRlCAi • •• -F ' yeiMABi y.'; . ;• • AT .^ CYCU AFTER FMJLT^^ .;— 1. 'j^ono'. • •,.•• -i : •: • •22000 •" ;2,2POO • .600 • V-- - *• •• p.-- •! • "r-C-3R.AL- i>>/.'.\C.c3=5C'' Er-EO'pHEC: C ^P'; PA^^^•^• rtlo. rchj; •? iv>T7'.t.* TtEiiii 'iHnRRUPTIKC RATINQ CURRtNT MEASURED: AT Vi CYCLE AfTER FAULTS, AMPERES, .•. ASYMMETRICAl I SYMMETRICAL 30 CYCLE SPOST-TIHt RATINfi, WITHOUT ' SERIES TRirS, AMPERES ASTMMETRiCSL SYAIMfTRICAl 42000 . ' 4?M0 240 AJRI S«!ow Ssri^H'psiAi- r at*r«rU.M ;?• Lin^f \/o?tage SLAS.f- xear 600 Volts a-c—25,000 tc 150,0 Ai-n^HrCi: IC Dti3C;'ip' A'O ShftOs . L"^;; - - FP75-3000 AIR CIRCUIT BREAKER stored Energy r Mechanism Electrically Operated • M'-; • •• ii<: ; • •• •«, ' . •**•** -l-f '-f • : ^ The normal method of operating this ; ' "V i 'l — " ' a I - - •ui breaker is by an a-c/d-c electric mo « • ♦ . ,• tor charged, stored energy mecha i -i. • , nism. Provisions are made for man r ual charge for emergency closing the !. r,, !•'••• • breaker. • ' i 'M •' -i r :A . : ~\a:> n I a.3 esw • , • A LzOf^OSliSiB '-v a' :!I/ --V- y . • 28>y„" 1, •>•>11' A- • iV.iAAi-i rrJ: At- : vli; ^ ^ i ). !.l L \ A" K- :"! ; C-' •••t.-. . %>;"v • ; . . • IHTERRUPTINC RAimS CURRENT MEASURED BRtAKEa TYPE fP75-3000 480-2AI 240 snit Selov •' •< —i ;Vt^A . ; r • sesii- aV ib • , ^''inZ-i-'A .;V,|4Uj-j- • • •" Tinniniwff 'f •;"-.'i-iHj''n •» • };i; J^'-i •s.'d SREAKER TYPE FPieO-4000 IHTERRUPTIKG RATING CURRENT KEASUREO AT U CYC.LE AFTER FAULTS, AMPERES 30 CYCLE SNORT-TIME RATING WITHOUT SERIES TRIPS, AMPERES • VOLTAGE ASYMMETRICAL SYMMETRICAL ASYMMETRICAL SYMMETRICAL ^6D0-A81 100000 kWi"-- 100000 85OO0 A80-541 100000 esooo lOOOOO SSOOO 240 8.ld Below ISOOQO ' 100000 B5000. FRAME SIZE CGHTIHUOUS CURRENT RATING OF CURRENT CARRYING PARTS WITHOUT SERIES TRIPS i' ' • 130000 .' .' i ' v •' Aooo-eioo '• : / r-i=bf:(;RAL' pAo:.-?-13. BLBcrvr-,.c • ' •• •• .* . . oos^'iPAWV • I""' ?ciMv c- tion only when breakei is tripped by the overcurrcnt trip units. The bell alarm can be manually and/or elec trically reset. Rcclosing breaker also resets the alarm switch. Bell alarm switch- is available with either .nor mally open or normally closed contacts. Shunt trip: The shunt trip attachment is mounted dii-ectly above the trip shaft. It is a non-adjustable electro-magnet intended for intermittent duty only, and its circuit is interrupted only by an auxiliary contact. Shunt close: The shunt close attachment is mounted on top of the stored energy mechanism and is used to elec trically discharge the stored energy mechanism and thus to close the breaker. It is a non-adjustable inter mittent duty device and its circuit is interrupted by an auxiliary contact. FP25 FP50 A compact, easy-to-use maintenance lift truck is avail currcnt Trip Devices-— one per poto Manual Trip Button Manual Close Button Electrical Close Button X X X X X X "Closed" Mechanism Indicator X X X X• ' • X X X X X X X' • . "Sprlnss Charced" "Sprlnits Discharged" Attached Manual Closing Handle *Eleptfical Ch3rs'(^2 Mechanism IIS a-c, 125 d-c control Closing relay with cut off. X • X seal-in and anti-pump features for maintained contact control Draw-out interlock X X . * X X X X X X •X X X X X X X X X "X X X X xt ' Instantaneous X X X X Time delay X X X X X X >; X . Padlocking Provision $hunt Close device Shunt trip deviceAuxiliary $wi(cn--6 circuit — — OPTIONAL ACCESSORIES Overcurrcnt liell alarmhand reset Electrical lockout device X X X y. Key Interlock X X . X X - ' draulically foot-oper.ated, the mainton.aiice truck enables Shunt Close Device X Shunt Trip Oevirc X X _ • X X . " ::• X * \ — 1' •• SERIES OV*; 'CURRENT TRl Long delay and tn^isntaneous . (Standard) TD-1 Long delay and Short delay (Optional) TO-2 Long delay. Short delay sation with extremely fast arc extinction. .• X X — the removal and handing of the largest type Federal Pacific Circuit Bre.-iker by one man. Refer to fact- arcs. The arc is confined within tv/o low-volume, highpressure parallel arc chamber.'.. This means rapid deioni- •X X "Test", "Disconnected" Condition Indicator—"Opcn"- X iiircnupf the arc by dividing the current between two X ' Position Indicator "Connected", Manual/Electric Close Button A pa'alU-l arc-splitting system is used to effectively X X X Manual Close Button ARC CHUTES FPIOO X able for Use with Federal Pacific Switchgear. Hy- for details. fP75 TO-l Dual Magnetic Time Ovcr- ••Auxiliary Swilch—fi Circuits tindervoltdge device— CIRCUIT BREAKER MAINTENANCE TRUCK Electrteal Instantaneous (Cptlcnall TO-3 Motor Starling fOr-lional) TD-4 Long delay only rOp'lonai) HEVIGES X X X X X * Typs PA ' . X . ,X TD-5 X •,X • ^ -i. •• MSJitnum—'.J Circuit • 4S volt Dt!- p AU plastic material—not readily breakable. • ' Single Rating Lamp—For all operating voltages. AC IP'iC ELECTRIC COM1PA.N'V' . 'y.'- Auoiisfv •I'^NSEl MCEL3 • ."'I,' " " "• •to " • .- 'm .-. RE6I5T0H5 • ; •I', lage; . o-t J*. Ohini 800 140O 2900 2702-0116 2703-0116 2704-0116 V-' •^' -i 50 70 US 125 5800 . • 6500.'• 7100 , 2707-OnS «« "24 • 3200, ,- 2705-0116 2706mU6 • -0 Seivict Voltage ilO ^/9ff«ne 2701-0116 -'•!.••• _ Oesciption 208 . 230 250 ' imiBAIlHC UMP HUTS 1 .24-£ Lamp 24 V. .032-.O38 amp.' . '«a 0{> NSCES&stY SPACeRS.CAT.'Isa ;/OI'OI}4 tHICX WHEN PANEL TrOCKNESS IS LESS IHAN-b ' I • •; n HDETRA*. PAOIF'IC EUS.CTRIC OOMPANV' 11 iw T'A '.•in'- • ..; KE ' • 1 .•s.i • . --v • /.' '•''••;• '.1 • "li: '^1;;/ " tKI --4> -•A:.. - j* if TYPE VD . I TYPE VFN mm. APPLICATION Key interlocks are attached to mschantcal and electrical device? to insure a safe prtxictermined sequence of oper ations. Hie intcrlc^c':? are a simple mechanical device that a.rc pi'.titivc ir ->ction but very difficult to defeat and may bt .itlached 'n any equipmeni v;h:'re it is possible to engage irio'.'iny operators. Various acccssrries are available to extend the basic operation of tiic interlock for control circuit switching. However,,it shotildbe rcmemhcrci tliat ilie reliabflityof such arratigomeni? mus' dcpem' on tho rcliabiUty of the control source and .should "iai' safe" in the event of a power failure. INTERLOCKS - Typf- VB. VF. VFN These imerhiuk.s f^rm the basic group of mierlocks used in aH application-. Tlte choice bet'voyn locks in this group depends entirely on the •mounting arrangement preferred; Honslttgs arc of brass either machined from bar stock or cast, and carry the 5/P" diameter, bfass plunger in exactly rhc same relatioasblp to the lock. Plunger travel is 3/4' and the plunger exren'sion from the Uv;k body in the ret<-.,ctcd position may be any one of six siaiKi. .-'1 irnyi'ts. Nisii standard pmjecdons can be stippficd •I. additjonal cost. S'cindard arrangement is for the key to be renpNT the "plunger extended" position only. The opposite be supplied at no addilicnal charge when specified. TYPE VD This lock is used on removable or hinged panels a:.d supplied with vr«1(l an »dUi^ iatch iUlViJ block which VYXiiWU 19 is illVAlll'.V. moiintc ic mounted on the fArMj^xrnKfn unH once t^nia It ir Ii.' mg is removable rxairfr part and ^cmo^'ed from the latch block tlie ke\' is trapped pnd can- iTi^T •' II.X' be removed. In all other respects tltis lock asse.a'-ly is identical .o the Haste locks previously described. TYPE T the type T is a traasfcr'interlock desigilcd for .a key ;ni-.:rcliangc and usually consists of.a master IcKk and or more Tclsase locks. In operation the key to the,master lock is retjuned. ilntO - .-m all. the release keys are.'insened in the lock'.assembty,' then the master key can bc r^oved and ia.s.? doing • traps all the release keys. •' Nry combi:=ation of master and release ,s is posrir'e b'ji it should be noted there is no extc ual pluTrger.fo:- locking operation. " •. • S'. ' > V'' to &B Stationary part oi' the mechanism. The lock hdus >. rAOTr-'^'o' -eLETO-TRiC "o -•.bli.S i if MTfl, POLTt III iimm TYPE VF •m r:Ol'NTiNG 0:MFNS', ::.5 U 1r rf- Tl 1( rJ —« - -f IBBi SEMI-FLUSH MOUNTING FLAT PANEL - fr ]• URFACE^ MOUNTING FLAT OR DISHED PANEL is 1 U-, V y [• T]—- !' ' . fr .fe-'i li • -li rl vrt-j v---:-LSEMI-FLUSH MOUNTING DISHED FANEL DRIUINCi DETAIL J6 /'- 1 1 I 'Us . •- .Hi-ECTRJC i;. _ ^•'••'eET.'.NPWAR«;-N =w'JEPSEy COrV3:RANY Lo'v- ''>"^ K "ai^r^einT?;- ''-r"* "' " :."•- Im Federal Pacific Lons Scale In«lriimenU aro deslitie'l specifically for eojitri^ and distriUtion .•ivi'.chboartLs^ Th'.' iiislriimenta combin«! the case '>f reading aiTonk'Jby ;i 7 inch acale and the compa< "icss of a' 4'::-i"cb pawl size- A clearly distinguished cijlntcr, o^iatmp over a 250' fire scnie, provides fdi tinicfe iind''frcc»ra'" •15(1 w;; • readings at c'onsicieroble distances. .: • M CONSTRUCTION A sturdy meuil housing and tiYodern styifd front are ,25 standardizcfi 'ur nil ranges .aJid types in both d-c and ii-c movemruu. l>ireet Curfn' (i'lass 1^150 Ty'a= JP) instruments e • ploy a hign stren'p.h magnet moving •:>•• accurately balanced o!i steel p>\-ots m jewel hearings. . Aitdrnating Current' (Class 0155 Type JA) amroe'Lpi'a and voltmew opcr.Te on the irott icpuls'ion p.rineiple • - u 1. C. iHil' fe.. Ejfc.X •,j with nip daiiij'.pj. AsUmeters ore of ihe dynam'micter type with nuignelic damping. FEATURES Tamper Proof: Stiids permanently mounted on case ' 1 1'^"" 'Vv- ])roliibit removnl of instrument cover by unauthorized personnel. Instruments nre flush mounted on panels ,8-5 iRJjjBtnsrtt—.. .•]<,•! uptolVi''. Accurate: 1% of full scale value, Zero Adjustment*. Zero adjuster is provide '> 'C",''' • y'-l/'t-vi''',.: • ..("-1, • rtsaCinLIv tHevinr ,eiei[r.-.ri ' • . • ,v . "'Explflflw!, Visrr c( t C fiW. F.EDERAI. iPACI.FlO ei-ECTF?IC COMRANV^^ August, fSiSe: ^ •)-'"-Jl!7 'lifts : . .T .KT"'-: ' 'f-', 1:5'4.1 .ifv "•VT- W ' m. •IT''?:! I' • ' iitt'im'-i" -•• '3- '' m' f?' 30 .tT "-b-- •V • j. «n *• *cy f, V j..[o enit capacity of 50 mv. ' atid furnished with pair of i. Insert value in place of ®" ' e to suit application, and insert •D.001M.\-:5000y\'. KxternaJ re- a. re!|uired; availauie separately. vaiiie to suit priuiary of current 3/•-p secondary. Insert this value '>•1 I . -I-'X, rV • • 005AA-250AA. fspr S A. Select lull scale vofe'e: to siiit primary of potential traasformor having 150 v secondary. Insert this value.fn place of e.g. JA-150W-1500VV o. Select full sc.ale value to suit application and insert m ylace uf * Indicate product of current transfonner i-a:io and potential transformer ratio e.a JA-0011CW/.141/I2r:e"rT;tfe7r.^ -r—Wv. 1 Sl>>tlrh»;; '•' IP' ' Sy'm.AiPOsi i !ffT!T . ••-•'i PCOO | WAntB. | • " 2s,o» "!. IK'?'• 'intsmiiitlirBtiffl • • Sn" 23,009' . I ' I'lO "*C0 150 " - pf.il •'- ]»'• ; • 3, >1*8 '^1^. FU^E KIT PURCHASING DATA* . ., EJO-l-O" E30;!-a0 t Fata fypt .. sa'c- "j wST - SM-*- 1 • Cl'£-r Rni Ul Cals'ag flsBiMr SM-5, ' 2631'1«!I6 SlE-2 OA-ZOO. ytalcd ' 'V £»-l-0 E)9-l-90 E»-l^£ $M-4 SM-S SA-200. w<)A ' - .;r-nplet* Switoh«s ^ aun? to.supply l!w f<'How!iiijini;on;'r;ttf.n: •• ' , Storwi-Energy .Switch CatP.lop Noml^-r Voitsge Rating , Motor ,; ' •!, i^iiard CataloR Number d.c, _! A 'I'lT- •A-'JT:;: ONI.Y I-'RCNT C.ONNISCTED S'ATiOHES -..r, - • V :.l.e. • 'L'" ' " If Mutirr Opwatetl, Control'Velta^: .......a.c. — jp,. Rptin;/ . - i::. OptTating- Mechaniam; Manual _ AVAILABtJ! • •"•"VWAL.'i FS/\e.ii"T , Lwi--. --cia V - W*- •f \ •, \ •' V • X *** .' ' •> ". >• INSTRUCTiaNS FCR INSTA.^AiiON, OPERATION AND MAINTENANCE •T of TYPE TH" DRY-TYPE TRANSFORMERS •- — -rt _ ^ rj: •• «;• j, • FEDERAL1 '•i' ' ' 1 '' '• B.L.\= OTR!C PACIFIC , '^ COMPANY sci zncassc iViOUNTING Vror^foi'.-cri AU Federal Paeifie's Tvpu I'FH" trarisformers arc shipped niountcd on ciiiicr a sHid. or In the case of the snral.f'cr sizes, on a pallet. Adequate size and strength of the skid- or pallet insures protection during shipment and ease of handling. The Type "FH" trar..sfornK-r.s 225 KVA and below arc supplied with Korfund isohitors which .should he placed under the four, cor ners of tlie unit wh-en it is floor mounted for full isolation of vibration.frora the buiiiiing stcucfure. This isolation in adiiftion- transformer lionsing is covered with a he.'ivy laminated'paper and the complete tfansformcr is cither b.andcd to the.-pallet or to the internal isolating monnis will provide a ma.ximuni of .bolted to the skid. : suitable,.for wail hiounting art- equipped with brackets for this .. vibration isolation and sound reduction. Those transformers purpose; The heavy angle.br.-ickets mounted to.the base are Core and Coils Core and cods shipped from the Federal Pacific factory i.s designed, to carry the transformer's weight when bolted lo the building structure. The top .slide-type brackets are intended to hold the transformer in an upright position. .. .skid moiinletl .an! overcd with protcoled iv.per wrapping, and ha-.-c !i protccti-.-e box frame covering the complete'structure' Type "FH" transformers 300 KVA and'aboive are also equipi\c(i to insure that ilu itaiisformcr will not be 'l;un.e:ed with normal handling durinesh.nnnoi:.- trnnsformcrs, the vibrrition isviviors ,-uc made ineffective (•iifim: with vibration Isolators, l lbwevci-.-becaiise of the weight o'" iht-se .shipment .by the piaccmeni of r.-d -nipping bars in parailci -,vi;l: the isdlallng maieriiil. Upon insiaiiaiion f/ie hnli iloy.i: iteim; painted red and the shipping bars also painted red shnni'd he ypoEHS R12CB5PT' removed io permit the core and-coils to be eifectivciy i.solaidd. ... • • 'v.-.'I; Ail transformers leaving the Federal Pacific Fleci'ric factory arc in first-cl.iss condition. Therefore, upon arrival at destination a The bolt down items and isolation shipping bar ctin b'o stored within the transformer housing so 'as to be readily r>v.tilabie visual inspection should he m.ade pi lor to unloading, to deter-' mine any evidence of rough handling. If damage is.cvidcnt or from its installation site. for use in the event the transformer ever need be removed .. i; • •;any'indication of rough handling visible, a claim shouici be filed • •.immediately with the carrier and noilficailon of this claim If fishould be.sent to the Federal Pacific Electric salcsntan. • 1.0CATi0N For satisfactory operation transformers should be so positioned as not to restrict free air flow through the transformex louver.s. '' I . = :• : .PalJel-s and skids are constructed so.that all inmsformers may be,moved by a forkiift truck. All tra'hsformers in.iy be skidded, '. <'V., • draped or rolled into position on their shipping forms. Lifting • 1 / eyes are provided on all transformers and are of sufficient I •; ' ..strength, to permit overhead* lifts with a crane. i ... ! --.'vr. .5 ••i;OkVdv Federal Pacific trarisformer shouid'bevlhid on-its '- V-1. /'•'iside fof'any reason. All transformers arc supported on vibra"tion_.isolators underneath the core-and coll stru'cture find this ••.. isolating material could be damaged beyond repair if the trans-: . •T'fornier is.tnrncd on its side. : ' V '"fi' ;t'A .spreader bar need only Iks'us^d I'*!?' 'l'!. on the large power sized encased dry-typc trnnsformcrsi This is because the lifting arc-fastened to the base and long lifting cables or sling might ^ • possibly crush the casing unless a spreader is used. -No fixed rule applies; however, the larger tlte air: circulation louver, the farther from a wdU it should-'be piaccdt Tlte small lighting transformer need only' be placed two inches froni a . wail whereas a large power transformer should be ptaecd at' least six inches from a wall. Good air circulation is essential ' in the-area in which a dry-type transformer is installed. There shoiild be available at least one. hundred.cubic feet:of air per minute per kilowatt loss of 'thc trahsforfher. Sticli a volume of air will iestrict the ambient afr ris'e.in the rbom to less-than 10° centigrade. To determine the air requirements of a planned instalintidn, :the KVA size of-transformer to be used and its full load total watts loss,should be used -to calculate the above .' i,/',; air requirements. Transformers weighing in excess of "one thoiisand pounds should be installed close to a main, building, support to insure a minimum of vibration transmission throughout the structure. • iH STORAGB Dry-type transformers preferably should be .stored in a warm , do' location with uniform tcmpcraiiire. 'Ventilating openings should be kept covered to keep out dust. If It is necessary .to leave a transformer put of doors it should be thoroughly '.protected to prevent moisture and foreign material froth ciiteiing. Conden.salion and the alisorptihn of moi.sture can be greatly ; reduced by the insiaiiaiion of either heat lampsor space heaters. Transformers arc e.iipensive items^of electrical equipment and should be treated with reasonable care in choice of storage location. . • . COL^SiMECtSO'^S Wiring compartments are provided at the bottom .of the trans former enclosure. Knockouts arc not provided because.of the difficulty of insuring the correct size and the chrrcct location .for eachvinstallation. However, both cnds..as';wolI as Ihb: rear and bottom, of the wiring comparlnienl arc :suitabie cable en trance'areas. All'transformer terminals'are rigidly supported to insure that no damage occurs to the coils during the period the connections arc.made-to the transformer. A complete per-, mancnt connection diagram is included as: arf intcgral part of the transformer nameplate. •|':-v All COP,- and coil sliuc'iircs. aUiioiigli isolated from thi:. trans former casing by vibration isolators, have a flexible grounding connection which insures that all non-ciirrent carrying parts arc at the same potential. Standard practice of adequately grounding the ti-ansformer to the station or circuit ground should be followed. If this procedure is followed no danger a, r-- qiiir; - .-.•e moisture iron: : - •• a'l , ••• ••.•.andiTei;:ic .s .dirt upon ir.ialaiioii h.oconiL.-, r In., in .vhnion absorbs, a consicici'.ibic anionni , t moj-i'nre .iud the sui-aec i-, contaminated; It h atit isr.bie to •.spec; aiiil clean any -f ne transformer susnccted of havi'v; ireen cont.'smiiiatcd v ti' diji, and moisture, especially print lo rc-encrgizins opcaf'tS or maintenance personnel. ©PiElRATaOS^ It is advisable to drt' ;-,i' dry-type transforniei jvliea been known to have beer eXDOSttd to long |ieri'HK .To maintain safe operating conditions do not remove covers, of panels over openings in the trtinsformcr housing while the humidity-or other moisinre. Whenever mpiiiur ; vj : ..;;otr. transformer is energized. the surface.of ihc in'-.v.irnioTi. ii must be cii-i-.-.i i i- • iri. n::ir- Caution: No attempt should ever be made to change the tap connection while the transformer is energized. For all relatively clean and dry indoor inslall:itions the Type "FH" transformer will continue to operate satisfactorily under all normal conditions of energization and load. No concern need be expressed over periods of shut down as to the trans- ./ormer's ability to retain its electrical strength. However, in- gization. The applica'':-:. jf ;joi air, radian. • • . in .-rivd heat siiiTicicni to remove visiidc signs of moi.S;;. • • r.'nri.dlv air that is required. Fniiurn due to cxce.S5 inoa. n • .-c. Illover external cretpagc Siirf.iccs readily coiitan-. Ma i-,; iv. a'.'f'-.ture. Therefore, removal of this su.d'ace mois; ' t ; . dielectric integrity. , - Unfortunately insiiialion resistance of: ib- • liqtiid f-iled transformer!,'-aic of liltl,-. i.e on a .'. former. ,\ttempts htivc it.-cn made to :-.feei/y'rcs!siu:ic I-.S- DCS; sonic instances if is necessary to install Type "FH" transform- which wiirindicate, IninMormcr uryr.csr, .nal dielecliic tiieii.eib. ,ers opt of doors with the proieclibh afforded cither by rain The nature of the'-insuhiiioh ti.scd; in drynyite irwvtV.rnttTs is such thtit megger feaUinyt cannot be relied upt.T,. shields or a building shelter. Under sueh conditions of operation the greatest reliability will be obtaincci if the tra'iisfpfmer ,is continually, under load./Condensate,may form and ti'ltimaicly be absorbed in the insulation" if an outdoor triinsformer is de- .energized for .long periods of time. If such a situation arises, .the transformer should be inspected for visible signs of moisture .oil the core and coils, before rc-energizihg. If moisture is ob-:. served the transformer, shdiild bo dried as indic.aicd in the paragraph under DRYING. Type "FH" transformers may be loaded in accordance with the ASA loading giiidc for dry-type transformers. Caution: Under no conditions should Type "FH" transformers be.asked to carry more than 110% overload for a long period of time for the reason that extreme temperatures may de velop and cause transformer failure. If It is necessary under emergency conditions to exceed this value of loading, fan cooling should be added as an emergency measure. Adequate •forced air cooling will permit load increases of 33'/<% of nameplate rating. Type "FH". transformers 501 KVA and above may.be purchased with factory supplied supplemental. fan cooled rating, TVansformers/iiypc "HH" 50t kVA and above may l-r tup-' : plied with supplemenlti! fan cooling. Fan motor mtiiiMcnance consists only of. periodic iiibricalion if used froiiueidK. No maintenance is feqiiired on thc'diai-iype thcrmoipelct and al im cbmaets which coiitro! the circuit.. Since the dial-type eter is of the bourdon type, the therniometcr cither uvil.s/. accurately"or not at till. It will only fail to oper.ite .i iht bourdon tube ;is punctured and loses its liquid pressure. The. control and alarm, contacts are of the micro .switch v.iricty and suitable for many hundreds of thousands of oportitions. .SURGE pnoTtBormm For normal opcrtition on protected lines dry-type transfornii r> need no surge proicctiou. However, when these ininsfonuers are. applied to circuit.s with some exposure to lightning surges • it is advisable, to protcct with'suitable lightning avrcstors. The •Form 28 and: Typo RM arrestors. will give adcqnute protection, when properly,'chosen for thc'vqliage rating they are to protect.. A continuously energized transformer needs periodic mainte nance oniy for the purpose of removing accumulations of dust and din from the cooling ducts and conducting surfaces. Failure to remove large accumulations of dust and dirt will ultimately lead to overheating. of Ihe transformer and its ultimate failure. Frequency of such cleaning should depend on the environment of the transformer. Caution: Extreme care should be taken .to assure that the vdre enamel is never darna.ged. The. v/ire enamel is of an extrerheiy high dielectric strength, it has an exceptional high temperature normallife.; . . • .. . -I .!l •• ij if ' T- ' ;., A •; • ii' -1. iO-. .ii'v';) JV.^: a^' .i'"v < /a*.V:'Vv- . ••, l-o' - • ' i i V. *^<1*1 r i w <•••••*;•'i'lpi "'• • ' -i-HCii A: ;v. : • |iU --V • r- Q 6# •1 V ,-=>-1 I ,.-V lA :..« i S ,•., •>( i i )j IL V . f I *e' u I "f ' '1'- •MA:'''r'' ? 3 , ;•. • I .. { "r f'' i\ '• j- f-jA " i rr':'?.'^,-''^/;;'V; ••• \ ; .;: 1.. > •• • '' i ii • • - c*. -< • ; '.v-Wi '*';• 'i^ S-; jji*".' i"' io5 J> ' ' '' V ififfri 'iS.I.'- i>'«iV«vi >'• •-,' :•.' i v':- f ..•: <--L r^ii =- tw .V>-'.;-. f-» . -.te* >v- I'V. • . :..i:£L::,..,j-i:;i:yv q. - 1 i. : t •r»rf r'«-»i»*
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Create Date : 2015:05:26 10:55:41-05:00 Creator : PFU ScanSnap Organizer 5.2.10 #iX500 Modify Date : 2015:05:26 12:15:08-05:00 Has XFA : No XMP Toolkit : Adobe XMP Core 5.6-c015 81.157285, 2014/12/12-00:43:15 Metadata Date : 2015:05:26 12:15:08-05:00 Creator Tool : PFU ScanSnap Organizer 5.2.10 #iX500 Format : application/pdf Document ID : uuid:19ead5d5-98df-4002-a49f-a0095eeefe97 Instance ID : uuid:0f306848-9dce-4a50-8a79-9e2e74df98e5 Producer : Adobe PDF Scan Library 3.2 Page Count : 382EXIF Metadata provided by EXIF.tools