ICM491

Single Phase Line Monitor

Reliable line voltage protection for single phase systems

SPECIFICATIONS
Input
• Line Voltage: 95-135 VAC or 190-270 VAC 		
(selectable)
• Maximum Operating Input: 142-275 VAC
• Line Frequency: 50-60 Hz

Protects against High/Low
voltage and rapid system
recycling, 95-270 VAC
operation, adjustable
anti-short cycle timer...

DESCRIPTION
The ICM491 was specifically designed
to guard equipment against damage
caused by under/over voltage conditions
and/or rapid system recycling.

FEATURES
• 5-Second Interrogation Delay... helps
prevent nuisance tripping
• LED Indication... normal run and fault
indications
• 95-270 VAC Operation... in a single
model
• Integral Anti-Short Cycle
Protection... “Delay on break” circuit
provides adjustable (.1 to 10 minutes)
lockout delay to prevent rapid system
recycling; no external ASC timers
required
• Meets IEEE 587... A&B for transient
protection

LII114-1

Output
• Type: Relay, energized upon acceptable 		
conditions
• Form: SPDT, Single Pole, Double Throw
• Ratings: 6A @ 120 VAC resistive
			 5A @ 240 VAC resistive
Response Times
• Line Dropout: .05 seconds (typical)
• Line Voltage Sag: 5 seconds (typical)
• Turn On (sec): Based on minimum time 		
selected
Lockout Delay Timer
• Dry Relay Contacts
• Time Delay: Adjusts from 6-600 seconds
(+/- 10%)
Under Voltage Protection
• Voltage Dropout: Setpoint is -12%
• Voltage Pickup: Setpoint is -8%
Over Voltage Protection
• Voltage Dropout: Setpoint +12%
• Voltage Pickup: Setpoint +8%
Environmental
• Operating Temperature: -40°F to +167°F
(-40°C to +75°C)
• Transient Protection: Meets IEEE 587
Standards for Categories A&B without false output
or degradation
– (6Kv 0.5 µs x 100 KHz Ring Wave)
– (6Kv 1.2 x 50 µs Impulse Wave)
Mechanical
• Mounting: Surface mount using (2) #8 screws
• Terminations: .25” male quick-connect 		
terminals

7313 William Barry Blvd., North Syracuse, NY 13212
(Phone) 315-233-5266 (Toll Free) 800-365-5525
(Fax) 315-233-5276
www.icmcontrols.com

MODE OF OPERATION
Upon application of power to the monitor, and provided all voltages and line conditions are acceptable,
the green load energized LED indicator will glow. This is an indication that the output contacts have
successfully transferred.
Should a High/Low voltage condition exist for longer than the 5 second interrogation delay or a loss of
power for more than 50 mS, the relay and green LED shall be de-energized. The red status LED will
rapidly flash. Re-energization is automatic upon correction of the fault condition, after the anti-short
cycle time delay is complete. Should a fault condition exist upon application of power, the relay will not
energize and the red status LED will flash rapidly, indicating power is outside specifications. A blinking
LED indicates power is good, but unit is still in ASC lockout.
Adjustment: Select the desired operating voltage. If status LED blinks once per second, voltage is within
specification and unit is awaiting the end of the ASC delay. If the red status LED rapidly flashes red,
adjusting input voltage knob higher or lower should cause a slow blink to result, but ensure input voltage
is not beyond motor operating specification. Once input voltage is properly set, adjust “ASC Time Delay”
knob to desired ASC delay.

INSTALLATION
1. Determine operating voltage,
95-135 VAC or 190-270 VAC.
2. Disconnect power.
3. Connect the ICM491’s power connections
(L1 & L2) to power supply lines L1 & L2 (or
N). Ensure there is only one “L2” terminal
connected at any time:

OM L1 L2

L2

For
95-135 VAC Operation

OM L1 L2

L2

For
190-270 VAC Operation

4. Find a convenient location in control circuit
where the ICM491’s on-board relay contacts
can make or break the control circuit. The
“COM” terminal connects to the “NO” contact
when power is within specification, “COM”
connects to “NC” when power is outside
specification.
5a. With control power off, cut control circuit and
terminate control wires with 1/4” female spade
connections. Connect one terminated line to
“COM” terminal, the other terminated line to
“NO” terminal.
5b. For new installations, where the control circuit
voltage is the same as the voltage being
monitored, it may be easier to connect “COM”
terminal to “L1” terminal with a jumper wire
as shown in ladder diagram. Then, connect
control circuit to terminal “NO.”
6. Set the “input voltage” knob to the actual line
voltage, or to the motor’s nameplate voltage.
7. Turn the “ASC Time Delay” knob to its
minimum position (counter-clockwise).

8. Apply power. Observe “Load Energized” and
“Status” LEDs. If incoming power is within
specification, unit will energize load in 6
seconds. The following is a table showing what
LED indicators correspond to:
LED
Load Energized
Load Energized
Status
Status
Status

STATE
Off
On
Off
Blink
Rapid Flash

INDICATION
Internal relay is de-energized
Internal relay is energized
Voltage is within range
Voltage is good, unit is in ASC
Voltage is out of range

Note: Both LEDs off indicates no power to
unit.
9. Set the “ASC Time Delay” to the desired antishort cycle lockout time.

WIRING DIAGRAM
Typical wiring diagram for 115 VAC system
L1

Fuse

L2/N

NC NO COM L1

L2

L2

115
230

ICM491

115 VAC Contactor

Motor



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.2.2-c063 53.352624, 2008/07/30-18:05:41
Create Date                     : 2009:08:06 09:17:51-04:00
Metadata Date                   : 2009:08:06 09:17:51-04:00
Modify Date                     : 2009:08:06 09:17:51-04:00
Creator Tool                    : Adobe InDesign CS4 (6.0.3)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 5565 bytes, use -b option to extract)
Instance ID                     : uuid:4eadc06c-f4dc-594a-8176-2343616b61ea
Document ID                     : xmp.did:04801174072068119457DA2249762A6F
Original Document ID            : xmp.did:04801174072068119457DA2249762A6F
Rendition Class                 : proof:pdf
History Action                  : created, saved, saved, saved, saved, saved, saved
History Instance ID             : xmp.iid:04801174072068119457DA2249762A6F, xmp.iid:05801174072068119457DA2249762A6F, xmp.iid:06801174072068119457DA2249762A6F, xmp.iid:07801174072068119457DA2249762A6F, xmp.iid:09801174072068119457DA2249762A6F, xmp.iid:0A801174072068119457DA2249762A6F, xmp.iid:0AB8DECE102068119457DA2249762A6F
History When                    : 2009:08:06 08:11:39-04:00, 2009:08:06 08:15:36-04:00, 2009:08:06 08:15:36-04:00, 2009:08:06 08:19:25-04:00, 2009:08:06 08:49:17-04:00, 2009:08:06 08:49:21-04:00, 2009:08:06 09:10:15-04:00
History Software Agent          : Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0
History Changed                 : /, /metadata, /, /, /, /
Manifest Link Form              : ReferenceStream
Manifest Placed X Resolution    : 72.00
Manifest Placed Y Resolution    : 72.00
Manifest Placed Resolution Unit : Inches
Manifest Reference Instance ID  : uuid:ea42eb63-a458-11da-b47a-a98b2e7b0186
Manifest Reference Document ID  : adobe:docid:photoshop:28fedadb-a442-11da-a0cb-bdbc79903fde
Doc Change Count                : 22
Format                          : application/pdf
Producer                        : Adobe PDF Library 9.0
Trapped                         : False
Page Count                      : 2
Creator                         : Adobe InDesign CS4 (6.0.3)
EXIF Metadata provided by EXIF.tools

Navigation menu