Enspire UPS ENG_Booklet_R1 En Spire Series User's Manual Minuteman EN400 600 Users

User Manual: EnSpire Series UPS User's Manual MinuteMan UPS Systems - s

Open the PDF directly: View PDF PDF.
Page Count: 23

DownloadEnspire UPS ENG_Booklet_R1 En Spire Series User's Manual Minuteman-EN400-600-Enspire-Users-Manual
Open PDF In BrowserView PDF
Enspire
Series UPS
User's Manual

English

1.

Introduction

2

2.

Controls and Indicators

6

3.

Installation

7

4.

Operation

10

5.

Troubleshooting

12

6.

Replacing the Battery

13

7.

Obtaining Service

16

8.

Specifications

17

9.

Limited Product Warranty

18

A1.

Declaration of Conformity

19

© Copyright 2006
1

English

Thank you for purchasing this power protection product. It has been designed
and manufactured to provide many years of trouble free service.

IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !

Please read this manual before installing your Enspire Series UPS, models
EN400, EN600 as it provides important information that should be followed
during installation and maintenance of the UPS and batteries allowing you to
correctly set up your system for the maximum safety and performance. Included is information on customer support and factory service if it is required. If
you experience a problem with the UPS please refer to the Troubleshooting
guide in this manual to correct the problem or collect enough information so
that the Technical Support Department can rapidly assist you.

This symbol indicates "ATTENTION"

This symbol indicates "Risk of Electrical Shock"

This symbol indicates "Alternating Current Supply Phase"

This symbol indicates "Alternating Current Supply"
2

This symbol indicates "Equipment Grounding Conductor"

CAUTION! Connect the UPS to a two pole, three wire grounding
AC wall outlet. The receptacle must be connected to the appropriate
branch protection (circuit breaker or fuse). Connection to any other
type of receptacle may result in a shock hazard and violate local
electrical codes. Do not use extension cords, adapter plugs, or surge
strips.

CAUTION! To reduce the risk of fire, connect only to a circuit
provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA
70.

CAUTION! To reduce the risk of electrical shock with the installation of this UPS equipment and the connected equipment, the user
must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.

CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect
the UPS from the AC wall outlet before installing a computer interface
cable. Reconnect the power cord only after all signaling connections
are made.

WARNING: This Uninterruptible Power Supply contains potentially
hazardous voltages. Do not attempt to disassemble the UPS beyond
the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed
by QUALIFIED SERVICE PERSONNEL ONLY.

WARNING: Risk of Electrical Shock. Hazardous live parts inside
these power supplies are energized from the battery even when the
AC input is disconnected.

CAUTION! To de-energize the outputs of the UPS:
1. If the UPS is on press and release the On/Off Button.
2. Disconnect the UPS from the AC wall outlet.
3. To de-energize the UPS completely, disconnect the battery.
3

English

This symbol indicates "Direct Current Supply"

English

NOTICE: This equipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions
from digital apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable
protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly,
that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
„ Re-orient the receiving antenna.
„ Relocate the computer with respect to the receiver.
„ Move the computer away from the receiver.
„ Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
„ Shielded communications interface cables must be used with this product.

WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's
authority to operate the equipment.

Receiving Inspection
After removing your UPS from its carton, it should be inspected for damage that
may have occurred in shipping. Immediately notify the carrier and place of
purchase if any damage is found. Warranty claims for damage caused by the
carrier will not be honored. The packing materials that your UPS was shipped
in are carefully designed to minimize any shipping damage. In the unlikely
case that the UPS needs to be returned to the manufacturer, please use the
original packing material. Since the manufacturer is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS!

NOTE: These UPSs are shipped with the batteries disconnected. The batteries must be connected before putting these UPSs into service. Refer to Section 3 "Installation" for connecting the batteries.
4

As a general policy, we do not recommend the use of any of our products in life
support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect
its safety or effectiveness. We do not recommend the use of any of our products in direct patient care. We will not knowingly sell our products for use in
such applications unless it receives in writing assurances satisfactory to us
that (a) the risks of injury or damage have been minimized, (b) the customer
assumes all such risks, and (c) our liability is adequately protected under the
circumstances.
Examples of devices considered to be life support devices are neonatal oxygen
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis
systems, neonatal ventilator incubators, ventilators for both adults and infants,
anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options
on many of our UPS systems. We do not claim that units with this modification
are certified or listed as Hospital Grade by us or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.

5

English

Life Support Policy

English

1. The Battery Backup and Surge output power receptacles.
2. The Low Battery/Overload/Fault (Red) LED. The Low Battery/Overload/
Fault (Red) LED illuminates in a steady state when the UPS has an internal fault and the audible alarm will be continously beeping. The Low Battery/Overload/Fault (Red) LED blinks when the UPS is Overloaded and the
audible alarm will sound one beep every half second. The Low Battery/
Overload/Fault (Red) LED blinks when the UPS reaches a Low Battery
Warning and the audible alarm will sound two beeps every five seconds.
The Low Battery/Overload/Fault (Red) LED blinks when the battery is weak
or needs to be replaced and the audible alarm sounds three beeps
every thirty seconds.
3. The input circuit breaker will trip in the event the output load exceeds the
UPS’s power rating.
4. On/Off Button.
5. The input power cord.
6. The On Utility/On Battery (Green) LED. The On Utility/On Battery (green)
LED illuminates in a steady state when the UPS is on and operating in the
AC normal mode. The On Utility/On Battery LED blinks when the UPS is
operating in the Battery mode and the audible alarm will sound one beep
every five seconds.
7. The Surge Only output power receptacles.
8. The RJ11/45 modular connectors are used for single line phone/fax/modem
protection.
9. The RJ45 connector is for the USB communications port for UPS monitoring
and control.

6

Model #

Input Power Plug

Output Power Receptacles

EN400
EN600

NEMA 5-15P W/6 ft cord

3-NEMA 5-15R Surge Only
3-NEMA 5-15R Battery Backup & Surge

English

INSTALLATION PLACEMENT

This UPS series is intended to be install in a temperature controlled environment
that is free of conductive contaminants. Select a location which will provide good air
circulation for the UPS at all times. Avoid locations near heating devices, water or
excessive humidity, or where the UPS is exposed to direct sunlight. Route power
cords so they cannot be walked on or damaged.

ENVIRONMENTAL
Operating Temperature:
Operating Elevation:

0 to 40 degrees C (+32 to +104 degrees F) at
0 to 1,500m (0 to +5,000 ft)

Operating Temperature:
Operating Elevation:

0 to 35 degrees C (+32 to +95 degrees F) at
1501 to 3,000m (0 to +10,000 ft)

Storage Temperature:
Operating/Storage Humidity:
Storage Elevation:
Audible Noise at 1 m (3 ft.):

-15 to +45°C (+5 to +113°F)
95% Non-Condensing
0 to 15,000m (0 to +50,000 ft)
<45 dBA

INSTALLATION
Be sure to read the installation placement and all the cautions before installing the
UPS. Place the UPS in the final desired location and complete the rest of the
installation procedure. These UPSs are shipped with the internal batteries disconnected. The batteries must be connected before putting these UPSs into service.
See the Connecting The Batteries procedure to connect the batteries.
WALLMOUNTING
The wallmount configuration allows the user to mount the UPS on the wall. The
UPS's back panel has keyed mounting holes for attaching the UPS to the wall.
1. Once the location and position of the UPS has been determined, use the template to mark the screw hole position on the wall. CAUTION, you should always
were protective gear for your hands and eyes when operating power tools.
2. Attach the two retaining screws (provided) to the wall and make sure that the
retaining screws are screwed into structural material. Then clean the area of any
loose material. Do not tighten the retaining screws all the way in, leave approximately 3/16" of the retaining screws sticking out.
3. Position the UPS, so that the keyed mounting holes line up with the two retaining
screws. Slide the UPS down until it is resting securely on the retaining screws.
4. The Wallmount Configuration is complete. See Connecting your Equipment.
7

English

CONNECTING THE BATTERIES
(QUALIFIED SERVICE PERSONNEL ONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to connect the batteries.
1. Remove the UPS from the shipping box and set on the floor or a bench top.
2. Place the UPS receptacle side down.
3. Remove the battery compartment retaining screws. (FIG. 1)
4. Remove the battery compartment cover. (FIG. 2)
5. Verify proper polarity. Connect the battery positive (Red) wire to the battery
positive (Red) terminal. (FIG. 3)
NOTE: Some sparking might occur, this is normal.
6. Re-install the battery compartment cover onto the UPS.
WARNING: DO NOT pinch the battery wires with battery compartment cover.
7. Re-install the battery compartment retaining screws.
8. Continue with the rest of the Installation.
FIG. 1

FIG. 2

FIG. 3

8

CAUTION! DO NOT connect a laser printer to the output receptacles on the
UPS.

CONNECTING THE UPS TO AN AC SOURCE
CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20
amperes maximum branch circuit over-current protection in accordance with
the National Electric Code, ANSI/NFPA 70. Plug the UPS into a two pole, three
wire, grounded receptacle only. Do not use extension cords, adapter plugs, or
surge strips.
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
an AC source and there is an acceptable AC voltage present (100 - 140VAC). It
is recommended that the UPS's batteries be charged for a minimum of 4 hours
before use. The UPS may be used immediately, however, the “On Battery”
runtime maybe less than normally expected. NOTE: If the UPS is going to be
out of service or stored for a prolonged period of time, the batteries must be
recharged for at least twenty-four hours every ninety days.
RJ45 USB COMMUNICATIONS PORT CONNECTION (OPTIONAL)
The Power Monitoring Software can be used with the UPS. Use only the interface cable that comes with the UPS. Connect the USB cable (RJ45 end) to the
RJ45 USB communications port on the side of the UPS. Connect the other end
of the USB cable to the device that will be monitoring/controlling the UPS.
NOTE: Connecting to the communications port is optional. The UPS works
properly without this connection.
PHONE/FAX/MODEM PROTECTION CONNECTION (OPTIONAL)
Connect a single line phone, fax or modem line to the RJ-11/45 modular connectors on the side of the UPS. This connection will require another length of
telephone cable (provided). The cable coming from the telephone service is
connected to the port marked “IN”. The equipment to be protected is connected to the port marked "OUT". NOTE: Connecting to the phone/fax/modem
modular connectors is optional. The UPS works properly without this connection.

9

English

CONNECTING YOUR EQUIPMENT
Plug the critical equipment into the Battery Backup & Surge output receptacles
on the UPS. Plug the non-critical equipment into the Surge Only output receptacles on the UPS. Do not use extension cords, adapter plugs or surge strips
on the output of the UPS. Ensure that you do not exceed the maximum output
rating of the UPS (refer to the information label or the electrical specifications in
this manual).

English

SYSTEM OVERVIEW
This UPS protects computers, internetworking, security, and telecommunications equipment from blackouts, brownouts, overvoltages, and surges. During
normal AC operation, the UPS will quietly and confidently protect your system
from power anomalies.
The UPS will charge the batteries with the UPS in the on or off position when
the UPS is plugged into the wall outlet and there is an acceptable AC voltage
present (100 - 140VAC). When a blackout, brownout, or an overvoltage condition occurs; the UPS will transfer to the battery mode, the On Battery indicator
will illuminate and the audible alarm will sound once every five seconds indicating that the commercial power is lost or unacceptable. When the commercial
power returns or is at an acceptable level, the UPS will automatically transfer
back to the AC normal mode and start recharging the batteries. During an
extended outage when there is approximately two minutes of backup time remaining the audible alarm will sound twice every five seconds. This Low Battery Warning is letting the user know that they should save all open files and
turn off their computer. When the batteries reach the predetermined level the
UPS will automatically shutdown protecting the batteries from over discharging. Once the commercial power returns the UPS will automatically restart,
providing safe usable power to the connected equipment and start recharging
the batteries.

TURNING THE UNIT ON/OFF
On / Off Button
Press and hold the On/Off Button for one beep then release the On/Off Button
to turn the UPS on and supply power to the load. The load is immediately
powered while the UPS runs a five second self test. Press the On/Off Button
for at least one second then release the On/Off Button to turn the UPS off. The
UPS will continue to charge the batteries whenever it is plugged into a wall
outlet and there is an acceptable AC voltage present.

10

POWER MONITORING SOFTWARE
The UPS comes with power monitoring software. See the software CD for the
installation of the power monitoring software.

ALARMS
ON BATTERY
When the UPS is operating on the batteries, the On Battery LED will illuminate
and the audible alarm will sound once every five seconds. The alarm will stop
once the UPS returns to the AC normal mode.
LOW BATTERY WARNING
The UPS will sound two beeps every five seconds when the battery reserve runs
low. This condition will continue until AC returns or the UPS shuts down from
battery exhaustion.
WEAK/BAD BATTERY
The UPS automatically tests the battery’s condition and will illuminate the Low
Battery/Overload/Fault LED and sound the alarm. This alarm will be repeated
until the batteries pass a self test. If the battery is weak, bad or disconnected,
the Low Battery/Overload/Fault LED will illuminate and the alarm will beep three
times every thirty seconds until the battery is reconnected or replaced. It is
recommended that the UPS be allowed to charge overnight before performing a
battery test to confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the
Low Battery/Overload/Fault LED will illuminate and the UPS will sound 1 beep
every half second (AC and Battery modes). This alarm will remain on until the
excess load is removed or the UPS’s self protection circuit shuts the UPS
down.
UPS FAULT
When the UPS detects a hardware fault, the Low Battery/Overload/Fault LED
will illuminate and the UPS will sound a constant alarm. The fault condition, in
some instances, may be reset by turning the UPS off and then on.

11

English

RJ-45 USB COMMUNICATIONS PORT
The USB communications protocol is HID. The HID USB driver comes standard in the Windows OS. Simply plug the USB cable into the UPS and the
computer then follow the prompts on the screen.

English

Symptom

Possible Cause

What To Do

UPS will not turn on On/Off/ button not pressed Press and release the On/Off
button to start UPS
UPS operates in Input AC circuit breaker is Reset circuit breaker by
pressing the plunger back in.
battery mode only, tripped
If the AC circuit breaker trips
even though there
after UPS starts up, reduce
is normal AC
the load on the UPS
present
Fault LED is
UPS has detected an
Call for service
illuminated
internal fault
Disconnect the computer
The On Utility LED The UPS is being
cable from the UPS and press
is illuminated, but controlled via its
the On button. If UPS works
there is no output communications port
normally, the software has
control of the UPS
The batteries may be weak Charge the batteries for 8UPS does not
provide expected or at the end of useful hours and retest. If the runtime
is still less than expected, the
service life
runtime
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated
Low Battery LED is Loose connections at the Check battery connections,
batteries, Weak batteries, charge the batteries for 8illuminated
Bad batteries
hours, replace the batteries
Overload LED is The load has exceeded the Check the specifications (see
UPS's capacity
section 8). Remove part of
illuminated
the load

12

English

REPLACING THE BATTERY
(QUALIFIED SERVICE PERSONNEL ONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to service
the batteries.

WARNING! This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement
procedure. This UPS contains no user serviceable parts. Repairs and battery replacement must be performed by QUALIFIED
SERVICE PERSONNEL ONLY.

CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful
to the skin and eyes and may be toxic.

CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batteries properly. The batteries contain lead and pose a hazard to the
environment and human health if not disposed of properly. Refer
to local codes for proper disposal requirements or return the
battery to the supplier.

CAUTION: Although the battery system voltage is only 12VDC the battery
system can still present a risk of electrical shock. These batteries produce sufficient current to burn wire or tools very rapidly,
producing molten metal. Observe these precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the battery is, remove the source of the grounding. Contact with any
part of a grounded battery can result in an electrical shock.
The likelihood of such shock will be reduced, if such grounds
are removed during installation and maintenance.
13

English

CAUTION: Replace batteries with the same number and type as originally
installed in the UPS. These batteries have pressure operated vents.
These UPSs contain sealed non-spillable maintenance-free lead
acid batteries.
Model #
Battery
Qty/Rating
Ritar Power
Part #
CSB
Part #

EN400

EN600

1-12V4.5Ah

1-12V5.0Ah

RT1245

RT1250

GP1245

HR1221W

Typical Recharge Time: 8-hours from total discharge.
Typical Battery Life: 2-5 years, depending on discharge cycles and ambient
temperature.

BATTERY REPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERIES
1. Turn off the equipment that is plugged into the output receptacles of the
UPS.
2. Press the On/Off Button for at least one second then release the On/Off
Button to turn the UPS off.
3. Unplug the UPS's power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the the UPS.
6. Turn the UPS over and lay it face down.
7. Remove the battery compartment retaining screws. (FIG. 1)
8. Remove the battery compartment cover. (FIG. 2)
9. Grasp the battery and gently pull it out far enough to disconnect the battery
wires.
10. Disconnect the battery positive (Red) wire. (FIG. 3)
11. Disconnect the battery negative (Black) wire. (FIG. 3)
NOTE: DO NOT short the battery wires together.
12. Remove the battery and set aside.
NOTE: Orient the new battery in the same direction as the original battery.
13. Place the new battery close enough to connect the battery wires.
14. Connect the battery negative (Black) wire to the battery negative terminal.
15. Connect the battery positive (Red) wire to the battery positive terminal.
NOTE: Some sparking might occur, this is normal.
16. Install the new battery into the UPS.
17. Re-install the battery compartment cover onto the UPS.
WARNING: DO NOT pinch the battery wires with battery compartment cover.
14

FIG. 1

FIG. 2

FIG. 3

15

English

18. Re-install the battery compartment retaining screws.
19. Properly dispose of the old batteries at an appropriate recycling facility or
return them to the supplier in the packing material for the new batteries.
20. The UPS is now ready for normal operation.

English

IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING section to eliminate obvious causes.
2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the
most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the problem call or fax the Technical Support department at
the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011
or visit our Web site at www.minutemanups.com the "Discussion Board".
Please have the following information available BEFORE calling the Technical Support Department.
A. Your name and address.
B. Where and when the unit was purchased.
C. All of the model information about your UPS.
D. Any information on the failure, including LEDs that may be illuminated.
E. A description of the protected equipment, including model numbers if
possible.
F. A technician will ask you for the above information and, if possible, help
solve your problem over the phone. In the event that the unit requires
factory service, the technician will issue you a Return Material Authorization Number (RMA #).
G. If the UPS is under warranty, the repairs will be done at no charge. If not,
there will be a charge for repair.
4. Pack the UPS in its original packaging. If the original packaging is no longer
available, ask the Technical Support Technician about obtaining a new set.
It is important to pack the UPS properly in order to avoid damage in transit.
Never use Styrofoam beads for a packing material.
A. Include a letter with your name, address, day time phone number, RMA
number, a copy of your original sales receipt, and a brief description of the
problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMAN UPS
1455 LeMay Drive
Carrollton, TX 75007
ATTN: RMA # _______
16

English

SYSTEM SPECIFICATIONS
Model Number
Maximum Power Capacity

EN400

EN600

400VA / 200W

600VA / 300W

INPUT
Number of Phase

Single (1∅ 2W +G)
120VAC

Nominal Voltage
Acceptable Input voltage

0 - 160VAC
100 - 140VAC

Voltage Range
Frequency Limits

50 or 60 Hz, +/-5Hz, autosensing

Low Voltage Transfer Point

96V(+/-3%) resets to Utility Power at 101V(+/-3%) or higher

High Voltage Transfer Point

146V(+/-3%) resets to Utility Power at 140V(+/-3%) or lower

Surge Energy Rating

320 J
Resettable Circuit Breaker

Input Protection

OUTPUT NON-BATTERY OPERATION
Voltage Range

120VAC: 100 - 140VAC

Frequency Range

60Hz: 55 - 65Hz or 50Hz: 45 - 55Hz
>90% (Full Load)

Efficiency (Normal Mode)

OUTPUT BATTERY OPERATION
Waveform Type

Simulated Sine Wave

Nominal Voltage

120VAC

Voltage Regulation

Nominal +/-5% (until Low Battery Warning)
50/60Hz, +/-0.5Hz (unless synchronized to utility)

Frequency

6-8 ms Typical
Transfer Time
105% for 10-seconds, 115% Shutdown Immediately
Overload Capacity
Over-Current, Short-Circuit Protected and Latching Shutdown
Protection
Runtime: Half Load (minutes)
10
Runtime: Full Load (minutes)

2

PHYSICAL
Size - Net L X W X H
Weight - Net
Size - Shipping L X W X H
Weight - Shipping

11.97 x 4.84 x 3.35" (304 x 123 x 85 mm)
6.44 lbs (2.92 Kgs)

7.05 lbs (3.20 Kgs)

15.0 x 8.20 x 5.43" (380 x 208 x 138 mm)
8.0 lbs (3.6 Kgs)
8.0 lbs (3.3 Kgs)

REGULATORY COMPLIANCE
Safety Approvals, EMC

UL1778, cUL (CSA 22.2 no. 107.1), FCC Class B
17

English
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied
and operated within specified conditions, against faulty materials (excluding the
batteries) or workmanship for a period of three years from the date of purchase.
Para Systems Inc. (Para Systems) warrants the batteries for a period of two years
from the date of purchase. For equipment sites within the United States and Canada,
this warranty covers repair or replacement of defective equipment at the discretion of
Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty
parts. Para Systems products repaired or replaced pursuant to this warranty shall
be warranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is
improperly used, is subjected to an adverse operating environment, or is operated
outside the limits of its electrical specifications; (b) the equipment is repaired or
modified by anyone other than Para Systems or Para Systems approved personnel;
or (c) has been used in a manner contrary to the product’s User's Manual or other
written instructions.
Any technical advice furnished before or after delivery in regard to use or application
of Para Systems’s equipment is furnished without charge and on the basis that it
represents Para Systems’s best judgment under the circumstances, but it is used
at the recipient’s sole risk.
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of
implied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE
FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES
ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs,
such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of
software, loss of data, cost of substitutes, claims by third parties, or otherwise. The
sole and exclusive remedy for breach of any warranty, expressed or implied, concerning Para Systems’s products and the only obligation of Para Systems hereunder, shall be the repair or replacement of defective equipment, components, or
parts; or, at Para Systems’s option, refund of the purchase price or substitution with
an equivalent replacement product. This warranty gives you specific legal rights and
you may also have other rights which vary from state to state.
18

DECLARATION OF CONFORMITY
English

A1.

Application of Council Directive(s): UL 1778
Standard(s) to which Conformity is declared: FCC Class B
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS)
Manufacturer’s Address: 1455 LeMay Drive
Carrollton, Texas 75007 USA

Type of Equipment: Uninterruptible Power Supplies (UPS)
Model No: EN400, EN600

Year of Manufacture: Beginning November 1, 2006

I hereby declare that the equipment specified above conforms to the above
Directive(s).

Robert Calhoun
(Name)

Manager Engineering
(Position)

Place: Carrollton, Texas, USA

Date: November 1, 2006

19

Notes:
English
20

Para Systems, Inc.
1455 Lemay Dr.
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011
Internet: minutemanups.com
UPS Sizing: sizemyups.com

PN - 34000293 R1



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2007:12:04 11:05:38-06:00
Modify Date                     : 2007:12:04 11:20:31-06:00
Subject                         : Enspire UPS ENG_Booklet_R1
Page Count                      : 23
Creation Date                   : 2007:12:04 11:05:38-06:00
Mod Date                        : 2007:12:04 11:20:31-06:00
Producer                        : Acrobat Distiller 5.0 (Windows)
Author                          : todd
Keywords                        : 
Metadata Date                   : 2007:12:04 11:20:31-06:00
Creator                         : todd
Title                           : Enspire UPS ENG_Booklet_R1
Description                     : Enspire UPS ENG_Booklet_R1
EXIF Metadata provided by EXIF.tools

Navigation menu