Ready Guard R Installation Manual
User Manual: ReadyGuard-R Installation Manual AlarmHow.net Library
Open the PDF directly: View PDF
.
Page Count: 64
| Download | |
| Open PDF In Browser | View PDF |
5HDG\*XDUG56HULHV
6HFXULW\6\VWHPV
OFF
AWAY
STAY
AUX
,QVWDOODWLRQDQG6HWXS*XLGHIRU5HDG\*XDUG5DQG
5HDG\*XDUG5(1
K5963-1 9/01
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage
for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the
National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of
the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping
area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke
detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining
room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed.
Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the
door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or
humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could
prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
KITCHEN
BEDROOM
DINING
BEDROOM
TV ROOM
KITCHEN
DINING
LIVING ROOM
BEDROOM
LIVING ROOM
BEDROOM
BEDROOM
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
BEDROOM
BEDROOM
BEDROOM
KTCHN
LIVING
ROOM
.
CLOSED
DOOR
GARAGE
TO
BEDROOM
BASEMENT
01000-002-V0
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would
include any skylights that may be present, and the upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be sent to
the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the
phone lines, if connected to an alarm monitoring station).
–2–
Table of Contents
SYSTEM FEATURES....................................................................................................................... 4
MOUNTING THE CONTROL ......................................................................................................... 5
WIRING CONNECTIONS................................................................................................................ 6
AC POWER AND BACKUP BATTERY ......................................................................................... 9
INSTALLING WIRELESS ZONES................................................................................................ 11
MECHANICS OF PROGRAMMING............................................................................................. 14
ZONE RESPONSE TYPE DEFINITIONS...................................................................................... 15
DATA FIELD DESCRIPTIONS ..................................................................................................... 17
*56 ENHANCED ZONE PROGRAMMING MODE ..................................................................... 24
*80 DEVICE PROGRAMMING MENU MODE ........................................................................... 28
*81 ZONE LIST MENU MODE ..................................................................................................... 31
*83 ENHANCED SEQUENTIAL MODE ...................................................................................... 32
*84 ASSIGN ZONE VOICE DESCRIPTORS ................................................................................ 35
*85 RECORD CUSTOM VOICE DESCRIPTORS ........................................................................ 37
REMOTE PROGRAMMING/CONTROL (DOWNLOADING) .................................................... 38
SYSTEM OPERATION .................................................................................................................. 40
TESTING THE SYSTEM................................................................................................................ 45
SYSTEM COMMUNICATION ...................................................................................................... 46
TROUBLESHOOTING GUIDE...................................................................................................... 48
CONTACTING TECHNICAL SUPPORT...................................................................................... 50
REGULATORY AGENCY STATEMENTS .................................................................................. 51
SPECIFICATIONS .......................................................................................................................... 52
READYGUARD-R PROGRAMMING DEFAULT TABLES........................................................ 53
READYGUARD-REN PROGRAMMING DEFAULT TABLES .................................................. 54
INDEX ............................................................................................................................................. 57
LIMITATIONS OF THIS SYSTEM STATEMENT....................................................................... 59
WARRANTY................................................................................................................................... 60
SUMMARY OF CONNECTIONS DIAGRAM .............................................................................. 61
–3–
System Features
8/
ReadyGuard-R and ReadyGuard-REN are not intended for UL985 Household Fire applications unless a
24-hour backup battery (P/N LYNXRCHKIT-HC) is installed.
Powerline Carrier Devices are not UL Listed for fire or burglary functions and are intended for home
automation.
The ReadyGuard-R Series controls are self-contained, rechargeable wireless control/communicators that feature easy
installation and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of each
zone (ReadyGuard-REN if programmed). The following illustration highlights the main features of this system.
ZONES and DEVICES
• 1 hardwire zone
• Up to 24 wireless zones
(5800 Series Transmitters)
• Up to 16 wireless button zones
• Up to 8 Powerline Carrier Devices
• Supports wireless keypads
•
•
•
•
•
•
•
•
•
•
FEATURES
SYSTEM POWER
Real-time Clock display and Fixed-Word display
Message Center (for user recorded messages)
Voice announcement of system and zone status
Voice chime
Alarm Clock
Reminder
X-10 Scheduling
Latch Key Reports
Automatic Stay Arming
Remote Phone Control
• Primary Power: Ademco
1332/1332X10 Plug-in Transformer,
110VAC to 9VAC, 15VA output
(1332CN in Canada)
• Backup battery: Six 1.2V
rechargeable nickel-metal hydride
batteries.
8 USER CODES
• Installer code
• Master code
• 5 Secondary codes
• Duress code
• 3 Panic functions
OFF
AWAY
STAY
AUX
ALARM OUTPUT
• Built-in sounder
• Piezo output
(30mA max.)
• Bell output
(120mA max.)
• Steady output for
burglary/panic
• Temporal pulse
output for fire alarms
• Long Range
Radio/Alarm audio
Verification
COMMUNICATION
• Ademco Low Speed
• Sescoa/Radionics
• Ademco Express
• Ademco Contact ID
• Paging feature
01100-002-V0
OTHER FEATURES
PROGRAMMING
• Options stored in EEROM
• Can be uploaded, downloaded or
controlled via IBM-compatible
computer using Compass downloader
software and specified HAYES
modem
• Exit error feature (detects difference between
an actual alarm and exit alarm caused by
leaving a door open after the exit delay
expires)
• Event log stores up to 84 events
• Macro/ 1-button paging
• RF Jam Detection
• Remote phone control
–4–
SPECIAL FEATURES
ReadyGuard-REN
• Two-way voice
communication
• Speaker phone
operation
Mounting the Control
Wall Mounting
The illustration below shows the front assembly separated from the back plate.
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from
the front assembly board.
Certain features differ between the ReadyGuard-R and the ReadyGuard-REN models. Verify the
specific model being installed prior to programming the system.
LOCKING TABS
2. Carefully disconnect the ribbon cable
from the front assembly, leaving the
ribbon cable connected to the
terminal block PC board. The back
plate contains the terminal block for
making wiring connections.
PC BOARD
PART NUMBER
LOCATION
16
1
M XX
X
K51 X
08
1. Separate the front assembly from the
back plate by pressing on the two
locking tabs at the top of the unit.
3. Mount the back plate to a sturdy wall,
feeding the field wiring through the
appropriate openings in the back plate.
RED WIRE
MARKING
4. After wiring connections are made,
carefully reconnect the ribbon cable to
the front assembly PC board connector
(properly aligning the red wire).
5. Before closing the assembly, verify
which ReadyGuard-R model is being
installed by checking the model number
printed on the PC Boards. (Example:
SALYNXREN indicates the unit being
installed is a ReadyGuard-REN.)
DISCONNECT
THIS END ONLY!
PC BOARD
PART NUMBER
LOCATION
6. Snap the front assembly to the back
plate so it is held by the locking tabs.
01009-003-V0
Desktop Mounting
If desired, an optional mounting base (model LYNX-DM, purchased separately) allows the ReadyGuard-R Series controls to
be used on a desktop.
1. Slide the control panel onto the
mounting base locking tabs.
2. Bring all wiring through the bottom of
the mounting base, using one of the
three wire entry locations, before
making connections to the control
panel.
OFF
AWAY
STAY
AUX
3. Use tie-wraps to secure the wiring to
the built-in wire loops as needed.
Use the two supplied screws to secure
the control panel to the mounting base.
01100-003-V0
–5–
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of
Connections diagram on the inside back cover when making connections.
HARDWIRE ZONE
Supports 1 EOLR supervised zone using either closed circuit
or open circuit sensors.
LONG RANGE RADIO
Compatible with ALARMNET 7845C and 7720
Devices.
POWERLINE CARRIER DEVICES
Supports up to 8 Powerline Carrier
Devices for turning on/off lights and
appliances. Requires the use of an
ADEMCO 1332X10 transformer.
TWO-WAY VOICE
The ReadyGuard-REN supports the
two-way voice feature/Alarm Audio
Verification.
The
ReadyGuard-R
requires the installation of the
MXX
X
K51 X
08
PHONE LINES
Use either the plug-in jacks or the
screw terminals.
AC TRANSFORMER
Use the supplied ADEMCO
1332X10 9VAC, 15VA
Plug-in Transformer
(1332CN in Canada).
01009-005-V0
EARTH GROUND
See Earth Ground paragraph.
LOCAL SOUNDER DISABLE JUMPER
Remove the shorting jumper (shunt) to disable local sounder,
leaving only the external sounder active.
UL NOTE: Do not remove the shorting jumper (the shunt) for
UL installations.
SOUNDERS
The system includes a built-in sounder in the master keypad. If
desired, an external bell or piezo sounder can be connected.
Bell: Use a 6-14V bell with maximum current drain of 120mA.
Piezo: Use a 6-14V piezo sounder with maximum current drain of
30mA.
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following: 3
pulses – pause – 3 pulses – pause – 3 pulses. . .
Wiring Connections
1.
a.
Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth
grounds available at most installations:
Metal Cold Water Pipe - Secure a noncorrosive metal strap (copper is recommended) to the pipe that is electrically
connected and secured to which the ground lead.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or
equivalent, available at most electrical supply stores.
Connect terminal 1 to a good earth ground.
–6–
Wiring Connections
Wiring Connections
INCOMING
PHONE LINE
RING
TIP
RED
4
GREEN
5
3
6
TO
PREMISES PHONES
RJ31X
7
8
2
1
GREY
RING
TIP
BROWN
DIRECT
CONNECT
CORD
TIP
RING
TIP
GREY
RED
BROWN
OR
RING
8-POSITION
JACK
}
}
Make Phone Line Connections - For local or full line
seizure proceed to the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either the
8-position jack or terminals 2 (TIP) and 3 (RING).
b. Connect the handset phone lines to either the RJ11
jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The control must be placed in series
with the incoming phone line. Plugging the Direct
Connect Cord directly into the RJ31X jack, allows the
control to seize the phone line when an alarm occurs
and normal phone line usage by the premises phones if
the plug needs to be removed.
a. Cut the incoming RING and TIP phone lines
(typically red and green, respectively) and connect
them to RJ31X terminals 4 (red) and 5 (green).
b. Connect the premises end of the cut RING and TIP
wires to RJ31X terminals 1 (grey) and 8 (brown)
respectively.
c. Wire the flying leads of a Direct Connect Cord to the
control’s phone terminals as shown in the diagram
or plug into the 8-position jack.
d. Plug the Direct Connect Cord into the RJ31X jack.
GREEN
2.
INCOMING
PHONE LINE
TO
PREMISES
PHONES
01000-008-V0
Full Line Seizure Connections
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly
supervised, and the system may not respond to an open circuit on the zone.
3.
Make Hardwired Zone Connections - Zone 1 is an EOLR supervised zone that supports both open circuit and closed
circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a.
b.
c.
4.
Connect sensors/contacts to the hardwired zone terminals 6 (+) and 7 (–). Refer to the Summary of Connections
diagram.
Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in
series with the devices, following the last device.
Connect open circuit devices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop
at the last device.
Make External Sounder Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) or
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX).
a. Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by
removing the shorting jumper (shunt) on the terminal board. If disabled, however, no sounding
will occur upon AC loss, since the external sounder does not operate when AC power is lost.
8/
Do not remove shorting jumper (the shunt) for UL installations.
5.
Disable Local Sounder Option - If required the Master Keypad’s built-in piezo sounder can be disabled.
a. Remove the shorting jumper (shunt) on the terminal board.
6.
Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using
these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the SUMMARY OF
CONNECTIONS diagram.
a. Connect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.
Note: If not using the supplied Ademco connection cable, you may need to reverse the black and yellow wire connections. Refer
to the *80 Device Programming Menu Mode section for details on programming Powerline Carrier Devices.
–7–
Wiring Connections
ALL OUTPUT CIRCUITS ARE POWER LIMITED.
WARNING:
TO PREVENT RISK OF SHOCK
DISCONNECT TELEPHONE LINE
AT TELECOM JACK BEFORE
SERVICING THIS UNIT.
EARTH
GROUND
8
POS
JACK
ZONE
PHONE
2
1
3
4
5
6
TIP RING TIP RING (+)
SOUNDERS
8
7
( )
9
10
11
12
( )
(+)
( )
(+)
HARD
WIRED
ZONE
TO
INCOMING
HANDSET PHONE
PHONE
LINE
LINE
LOCAL SOUNDER
DISABLE SHUNT
REMOVE TO
DISABLE
PREMISES
TELEPHONE
14
15
16
DATA SYNC
OUT IN
PIEZO
BELL
6-14VDC
30mA max.
2k OHMS
EOLR
THE READYGUARD-R SERIES
CONTROLS ARE EQUIPPED WITH
AN INTEGRAL RECHARGEABLE
BATTERY PACK
P/N LYNXRCHKIT-SC.
13
AC
TRIGGER
SIGNAL
(NEG)
INCOMING
TELEPHONE
LINE
EARTH
GROUND
PLCD
POWERLINE
CARRIER DEVICES
RJ11
AAV / LRR
TRIGGER
(READYGUARD-R)
LRR
TRIGGER
(READYGUARD-REN)
6-14VDC
120mA max.
(e.g. WAVE2EX)
WEEKLY TESTING IS
REQUIRED TO ENSURE
PROPER OPERATION
OF THIS SYSTEM
FOR UL985 APPLICATIONS INSTALL
P/N LYNXRCHKIT-HC
AC
AC
SYNC
COM
DATA
NOTE
USE ONLY 1332/1332X10 OR 1332CN
TRANSFORMERS PROVIDED
REPLACE EVERY FOUR YEARS
1332/
1332X10/
1332CN
PLUG-IN
TRANSFORMER
9VAC, 15VA
1332X10
ONLY
CONNECTIONS
01100-004-V1
ReadyGuard-R Series Terminal Block
–8–
AC Power and Backup Battery
The system is powered by a 9VAC, 15VA Plug-in Transformer, ADEMCO 1332/1332X10 (1332CN in Canada). Refer to
the wiring table below for wire gauge and length.
Use only the provided ADEMCO
1332/1332X10 or 1332CN Transformer
Distance from Transformer
to Control
Wire Gauge
Up to 75 feet
#20
75 to 150 feet
#18
150 to 300 feet
#16
Wiring to the AC Transformer must not exceed 300 feet using 16-gauge wire. The voltage reading between
terminals 15 and 16 of the control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery. In the event of an AC power loss, the system is supported by a long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a “low battery”
message is displayed and a report is sent to the central station. In addition, the system will beep once every 45 seconds to
audibly indicate a low battery condition (press any key to stop the beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
RETAINER
NOTE
LYNXRCHKIT-HC
BATTERY PACK SHOWN
1. Connect wires from the 1332/1332X10 (1332CN in
Canada) AC Transformer to terminals 15 and 16
as shown in the wiring diagram.
2. Remove battery retainer.
BATTERY
PACK
3. Peel the backing from tape on the back plate.
4. Insert battery pack into back plate.
5. Install battery retainer.
TAPE
receptacle
on
7. After all wiring connections have been made, snap
the front assembly to the back plate and plug the
transformer into a 24-hour, 110VAC unswitched
outlet.
1
16
MXX
X
K51 X
08
6. Connect battery connector to
terminal block PC board.
8. Rechargeable batteries may take up to 48-hours to
fully charge. The “LOW BAT” message should
clear within four hours or by entering Test Mode.
BATTERY
RECEPTACLE
WIRING
TERMINALS
01009-007-V0
Ensure the cover is snapped closed prior to applying AC power.
–9–
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The ReadyGuard-R Series is equipped with an integral, replaceable, rechargeable battery pack composed of six (6)
rechargeable 1.2-volt nickel-metal hydride batteries. Select the appropriate battery pack, based on the installation’s
requirement, and install the battery pack.
Model/Part Number
LYNXRCHKIT-SC
Battery StandbyTime
4-hours (minimum)
Low Battery Notification
Approximately 1-hour before battery depletion
LYNXRCHKIT-HC
24-hours (minimum)
At least 1-hour before battery depletion
Replacing the Rechargeable Battery
1. When battery replacement is required, unplug
the transformer from the wall outlet, and open
the control panel cover.
2. Remove the battery retainer and disconnect the
battery pack connector from the receptacle on
the terminal block PC board.
LYNXRCHKIT-HC
OR
LYNXRCHKIT-SC
RETAINER
BATTERY
PACK
3. Remove the battery pack from the back plate.
4. If required, replace the tape that secures the
battery pack.
5. Install a replacement battery pack (P/N
LYNXRCHKIT-SC or LYNXRCHKIT-HC) into the
back plate.
BATTERY
CONNECTOR
TAPE
6. Install the battery retainer.
MXX
X
K51 X
08
7. Connect the battery connector to the receptacle
on the terminal block PC board.
8. After the wiring connection has been made, snap
the front assembly to the back plate.
9. Plug the transformer into a 24-hour, 110VAC
unswitched outlet.
BATTERY
RECEPTACLE
01009-006-V0
10. Rechargeable batteries may take up to 48-hours
to fully charge. The “LOW BAT” message should
clear within four hours or by entering Test Mode.
Ensure the control panel assembly is snapped closed prior to applying AC power.
–10–
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless buttons.
Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.
Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the system using the
*56 or *83 interactive mode, or input to the control via the downloader. 5800 Series transmitters (except the 5800RL
and 5827, described separately) do not have DIP switches. Each transmitter's zone number is programmed into the
system in *56 mode. Some transmitters, such as the 5816 and 5817, can support more than one "zone" (referred to as
loops or inputs). On the 5816, for example, the wire connection terminal block is loop 1, the reed contact is loop 2.
Each loop must be assigned a different zone number.
8/
The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring. Therefore, for
UL Household Burglary installations, the loop wiring may not exceed 3 feet.
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP,
5819, 5819S(WHS & BRS), and 5850(GBD) transmitters are not intended for any UL installations.
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone number to each
individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or input
number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV, or 5827 Wireless Keypad with the
system, you must program a House ID Code (01–31) in field *24 to establish
proper communication, and the keypad must be set to the same ID. House ID
00 disables all wireless keypads. An RF House ID is not necessary for other
5800 Series transmitters; the entry should be left at “00” (default) in those
cases. The 5827 reports low battery status as zone “00”.
7
2
5
8
*
0
3
6
9
#
••
•
••
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises
(5804, 5804BD, 5804BDV, 5804E, 5804WATCH, and 5827), each
transmitter is supervised by a check-in signal that is sent to the receiver at
70–90 minute intervals. If at least one check-in is not received from each
supervised transmitter within a 12-hour period, the "missing" transmitter
number(s) and "FAULT" will be displayed. The supervision for a particular
transmitter in the system that may also be carried off the premises (5801,
5802MN) may be turned off by entering it as a "UR" (unsupervised RF) type,
as described in the *56 Enhanced Zone Programming Mode section.
5800 Series transmitters have built-in tamper protection and will annunciate
as a fault condition if covers are removed.
1
4
•
•• •••
••• • •
• ••
5804BD/5804BDV
5816
5806/5807/5808
5827
5890 / 5890PI
01009-010-V1
Transmitter Input Types
All of the transmitters described have one or more unique factory-assigned input (loop) ID codes. Each of the inputs
requires its own programming zone (e.g., a 5804's four inputs require four button zones).
Transmitters can be entered as one of the following types (see transmitter’s instructions for appropriate input type):
Type
"RF" (Supervised RF)
Description
Sends periodic check-in signals, as well as fault, restore, and low battery signals.
The transmitter must remain within the receiver's range.
Sends all the signals that the "RF" type does, but the control does not supervise
"UR" (Unsupervised RF)
the check-in signals. The transmitter may therefore be carried off-premises.
"BR" (Unsupervised Button RF) These only send fault signals. They do not send low battery signals until they are
activated. The transmitter may be carried off-premises.
–11–
Installing Wireless Zones
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years,
depending on the environment, usage, and the specific wireless device
being used. Factors such as humidity, high or low temperatures, as
well as large swings in temperature may all reduce the actual battery
life in a given installation. The wireless system can identify a true low
battery situation, thus allowing the dealer or user of the system time to
arrange a change of battery and maintain protection for that point
within the system.
• Button-type transmitters should be periodically tested for battery life.
The 5801, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E,
and 5804WATCH button transmitters have replaceable batteries.
Using the Transmitter Sniffer Mode
Use this mode after all transmitters have been entered to check that all
transmitters have been properly programmed.
1. Enter Installer code (4112) + [#] + 3.
Note: If the communicator is in the process of sending a report to the central
station, the system will not go into the Sniffer mode. If so, wait a few
minutes and try again.
2.
3.
5801
5802MN
ON
OF
F
5804 /5804E
01009-011-V0
The keypad will display all zone numbers which have a non-zero Zone Type (even if serial numbers were not
learned yet). Fault each transmitter in turn, causing each one to send a signal. As the system receives a signal
from each of the transmitters, the zone number of that transmitter will disappear from the display. The
transmitters may be checked upon installation, or in an installed system.
When all transmitters have been checked, exit the Sniffer mode by keying Installer Code (4112) + OFF.
Notes:
• Sniffer mode does not automatically expire. You must manually exit (Installer Code + OFF) Sniffer mode to return to
normal operation.
• All BR-type units must physically be activated to clear the display, since they do not automatically send check-in
signals.
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter
are cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
• Any transmitter that is not “entered” will not turn off its zone number.
Go/No Go Test Mode
The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location, and allow you to
reorient or relocate transmitters if necessary, before mounting the transmitters permanently.
This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced. This will enable
you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the
system is in the normal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitters in their desired locations and the approximate length of wire to be run to
sensors is connected to the transmitter's screw terminals (if used), fault each transmitter. Do not conduct this
test with your hand wrapped around the transmitter, as this will cause inaccurate results
Note: On button type transmitters whose buttons have been set to Arm AWAY, Arm STAY, or Disarm, pressing a
button will take the system out of the Go/No Go Test mode and cause that action.
a.
b.
4.
5.
The keypad will beep three times to indicate signal reception and display the appropriate zone number.
If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in
either direction is all that is required.
If each transmitter produces the proper keypad response when it is faulted, you can then permanently mount
each of the transmitters according to the instructions provided with them.
Exit the Go/No Go Test mode by entering: Installer Code (4112) + OFF.
–12–
Installing Wireless Zones
5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop designations.
LOOP 3
LOOP 3
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 2
LOOP
1
LOOP 1
LOOP
1
ON
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS BUTTON
LOOP 2
OFF
LOOP 1
LOOP 3
••
•
••
•
•• •
••• ••••
• ••
5800RL
SET
HOUSE ID
5801
ENROLL AS
"UR" OR "RF"
5802 MN
ENROLL AS
"UR" OR "RF"
5802 MN2
ENROLL AS
"UR" OR "RF"
LOOP 1
LOOP 1
(TERMINALS)
LOOP 1
(TERMINALS)
5816
ENROLL AS "RF"
5814
ENROLL AS "RF"
5816MN
ENROLL AS "RF"
5816TEMP
ENROLL AS "RF"
LOOP 2
5809
ENROLL AS "RF"
LOOP 2
(REED)
LOOP 3
(AUX.
RIGHT)
5817
ENROLL AS "RF"
LOOP 1
5804WATCH
LOOP 2
(AUX.
CENTER)
LOOP 1
(TEMP
SENSOR)
ALTERNATE
POSITION
FOR LOOP 2
5806/5807/5808/5808LST
ENROLL AS "RF"
LOOP 1
5 8 0 4 B D / 5 8 0 4 B DV
ENROLL AS "BR"
PROGRAM HOUSE ID
LOOP 2
(REED)
LOOP 1
1 :15
:0
1 :13 0
: 16
LOOP 3
LOOP 1
(PRIMARY)
LOOP 2
(REED)
LOOP 1
5804/5804E
ENROLL AS "BR"
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 1
LOOP 1
(TERMINALS)
LOOP 3
(TERMINALS)
5818
ENROLL AS "RF"
5819
ENROLL AS "RF"
1
LOOP 2
(REED)
4
7
2
5
8
*
0
LOOP 3
(TERMINALS)
LOOP 1
(SOUND)
9
#
LOOP 1
(INTERNAL
SHOCK
SENSOR
LOOP 1
(MOTION)
(Green)
(Red)
(Yellow)
5827
PROGRAM
HOUSE ID
5819S (WHS & BRS)
ENROLL AS "RF"
Note:
3
6
5849
ENROLL AS "RF"
5850 (GBD)
ENROLL AS "RF"
5890/5890PI
ENROLL AS "RF"
01009-012-V1
You must enroll loop 4 on the 5801, 5804, 5804BD, 5804BDV, 5804E and 5804WATCH transmitters, regardless of whether or not the loop
is used.
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(WHS &
BRS), and 5850(GBD) wireless transmitters are not intended for any UL installations.
8/
Setting DIP Switches on the 5800RL and 5827 Transmitter(s)
Set the 5800RL and 5827 Transmitters to the programmed House ID, using its DIP switches. (OFF position is indicated by ---)
Notes:
(1)
(2)
The 5827 transmitter cannot be used in conjunction with the *58 RF Jam Detection feature.
The 5800RL cannot be used in conjunction with the Auto Arm (scheduled arming) feature.
5800RL DIP SWITCH TABLE
SWITCH UP FOR "ON"
1
2
3
SW-1 ACTIVATES
MODE SETTING
4
5
House
ID
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
6
SW-6 SETS
MODE
SWITCH DOWN
FOR "OFF"
2-6 SETS HOUSE ID
SHOWN SET FOR HOUSE ID# 12
2
---------------------------------
DIP SWITCH POSITIONS
3
4
5
----------------ON
----ON
--ON
----ON
----ON
ON
--ON
ON
ON
----ON
----ON
--ON
ON
--ON
ON
ON
--ON
ON
--ON
ON
ON
ON
ON
ON
6
--ON
--ON
--ON
--ON
--ON
--ON
--ON
--ON
House
ID
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
2
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
DIP SWITCH POSITIONS
3
4
5
6
--------------ON
----ON
------ON
ON
--ON
------ON
--ON
--ON
ON
----ON
ON
ON
ON
------ON
----ON
ON
--ON
--ON
--ON
ON
ON
ON
----ON
ON
--ON
ON
ON
ON
--ON
ON
ON
ON
01000-014-V1
Setting 5800RL DIP Switches
5827 WIRELESS KEYPAD DIP SWITCH TABLE
House
SWITCH UP FOR "ON"
1
2
3
4
HOUSE ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
5
SWITCH DOWN FOR "OFF"
SHOWN SET FOR HOUSE ID# 30
01000-013-VO
DIP SWITCH POSITIONS
1
2
3
4
--------------ON
------ON
----ON
------ON
------ON
ON
----ON
ON
--ON
------ON
------ON
--ON
--ON
--ON
--ON
ON
----ON
ON
----ON
ON
ON
--ON
ON
ON
ON
-------
Setting 5827 DIP Switches
–13–
House
5
ON
--ON
--ON
--ON
--ON
--ON
--ON
--ON
---
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
1
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
DIP SWITCH POSITIONS
2
3
4
5
------ON
----ON
------ON
ON
--ON
------ON
--ON
--ON
ON
----ON
ON
ON
ON
------ON
----ON
ON
--ON
--ON
--ON
ON
ON
ON
----ON
ON
--ON
ON
ON
ON
--ON
ON
ON
ON
Mechanics of Programming
General Programming Information
Programming options are stored in nonremovable, electrically erasable, nonvolatile EEROM memory. You can program the
system at any time, even at the installer's premises prior to the actual installation. Simply apply power temporarily to the
Control and then program the unit as desired. There are two programming modes:
• Data field programming (used for setting various system options)
• Interactive menu mode programming (used for programming zone information, programming Powerline Carrier Devices,
and for entering transmitter serial numbers)
You can also program this system remotely, using an IBM Personal Computer, a modem, and Compass Downloader for
Windows. See the Remote Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear the
feedback announcements or system beeps in the Programming Mode, of the system’s built-in speaker. To adjust the volume, press
FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the system will reset the volume to the default value (mid
level).
!
Certain features differ between the ReadyGuard-R and the ReadyGuard-REN models. Verify the specific model being
installed prior to the system programming.
Entering Program Mode - Use one of the following methods:
a) Press both the [✳] and [#] keys at the same time, within 50 seconds after power is applied to the Control or from exiting
Programming mode, OR
b) After power-up, enter the Installer Code (4 1 1 2) + 8 0 0. (This method disabled if exit Program mode using *98.)
Note: If a different Installer Code is subsequently programmed, use it instead of 4112 to enter the Programming mode.
Once you have entered the Program mode, data field *20 will be displayed (this is the first data field in the system) and both
keypad LEDs will flash.
Programming a Data Field
1. Press [*] + Field No. (for example, *21), then make the required entry.
2. When you have completely programmed a data field, the keypad will “beep” three times and then automatically display
the next data field in sequence. To go to a different field, press [*] plus the desired field number.
3. If the number of digits that you need to enter in a data field is less than the maximum number of digits available (eg.
phone number field), enter the desired data, then press [*] to program the next data field.
4. If you enter a nonexistent field, the keypad will display “EE”. Simply re-enter [*] plus a valid field number.
To view a data field without making changes, press [#] + Field No. Data will be displayed for that field.
To delete an entry in a field, press [*] + Field No. + [*]. (Applies only to fields *40–*44, *88 and *94).
Interactive Mode Programming (*56, *80, *81, *83, *84, *85)
Press [*] + interactive mode No. (for example, *56). The keypad will display the first of a series of prompts.
A detailed procedure (with displays of prompts) is provided in later sections of this manual.
Interactive Mode
Used to Program
*56 Enhanced Zone Programming Mode
Zone characteristics, report codes, and serial numbers
*80 Device Programming Menu Mode
*81 Zone List Menu Mode
Powerline Carrier Devices
*83 Enhanced Sequential Mode
5800 Series transmitter serial numbers
Voice descriptors for each zone
Up to 5 custom voice descriptors for zones
*84 Assign Zone Voice Descriptors
*85 Record Custom Voice Descriptors
Zone Lists for powerline carrier activation
Loading Factory Defaults
To load the factory defaults, enter the Programming mode, press *97, then press number 1, 2, 3, or 4 to select from default
tables 1-4 at the back of this manual, or press “0” if you are not selecting a default table.
!
If loading a default table, any data that has already been programmed into the system will be changed according to
the default table selected!
*96
resets all the subscriber account numbers and CSID in preparation for an initial download.
Exiting Program Mode
*99 allows re-entry into the Program mode using Installer Code + 8 0 0.
*98 inhibits re-entry into the Programming mode using the Installer Code.
Note: After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset delay, press [#] + [0].
–14–
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system responds to
faults in that zone. Zone types are defined below.
Type 00
Zone Not Used
Type 01
Entry/Exit Burglary #1
Zone type 00 is used to program a zone that is not used.
Zone type 01 is usually assigned to sensors or contacts on primary entry and exit doors.
Zone Characteristics:
• Entry delay #1 is programmable from 0-99 seconds (field *35).
• Exit delay is independently programmable from 0-99 seconds (field *34).
• Exit and entry delays when armed in AWAY or STAY mode.
• No entry delay when armed in INSTANT or MAXIMUM mode.
• Exit delay regardless of the arming mode selected.
01000-017-V0
Type 02
Entry/Exit Burglary #2
01000-017-V0
Type 03
Perimeter Burglary
Zone type 02 is usually assigned to sensors or contacts on which secondary entry and exit
doors that might be further from the keypad (typically used for a garage, loading dock, or
basement door).
Zone Characteristics:
Entry delay #2 is programmable from 0-99 seconds (field *36).
•
Exit delay is independently programmable from 0-99 seconds (field *34).
•
Secondary entry delay, if armed in the AWAY or STAY mode.
•
No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.
•
Exit delay begins regardless of the arming mode selected.
•
Zone type 03 is usually assigned to all sensors or contacts on exterior doors and windows.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY
mode.
01000-018-V0
Type 04
Interior, Follower
5890 / 5890PI
01000-019-V1
Type 05
Trouble by Day/
Alarm by Night
Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or
hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach the
keypad. It provides an instant alarm if the entry/exit zone is not violated first, and
protects an area in the event an intruder has hidden on the premises before the system is
armed, or gains access to the premises through an unprotected area.
Zone Characteristics:
Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or 02) or
•
interior-with-delay (type 10) zone is faulted first.
Instant alarm in all other situations.
•
Active when armed in AWAY or AWAY NO DELAY mode.
•
Bypassed automatically when armed in STAY or STAY NO DELAY mode.
Zone type 05 is usually assigned to a zone, that contains foil-protected doors or windows
or covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also be used on
a sensor or contact in an area where immediate notification of an entry is desired.
Zone Characteristics:
Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY
•
(night) mode.
• Provides a latched trouble sounding from the keypad and, if desired, a central station report
during the disarmed state (day).
Type 06
24-hour
Silent Alarm
Zone type 06 is usually assigned to a zone containing an Emergency button
(silent emergency).
Zone Characteristics:
• Sends a report to the central station but provides no keypad display or sounding.
–15–
Zone Response Type Definitions
Type 07
24-hour
Audible Alarm
Zone type 07 is usually assigned to a zone containing an Emergency
button (audible emergency).
Type 08
24-hour
Auxiliary Alarm
Zone type 08 is usually assigned to a zone containing a button for use in
personal emergencies or to a zone containing monitoring devices (i.e.:
water or temperature sensors, etc.).
Zone Characteristics:
• Sends a report to the central station, and provides alarm sounds externally and
at the keypad.
Zone Characteristics:
• Sends a report to the central station and provides an alarm sound at the keypad.
(No bell output is provided and there is no keypad timeout.)
Type 09
Supervised
Fire
5806/5807/5808
01000-020-V0
Zone type 09 can be assigned to any wireless zone used as a
fire zone. This zone type is always active and cannot be
bypassed.
Zone Characteristics:
• Bell output will pulse when this zone type is alarmed.
Type 10
Interior w/Delay
Zone type 10 is bypassed when the panel is armed in the STAY or STAY
NO DELAY mode.
Zone Characteristics:
• Entry delay #1 (with programmed entry time) when armed in the AWAY
mode.
• Entry delay begins whenever sensors in this zone are violated, regardless of
whether an entry/exit delay zone was tripped first.
• No entry delay when armed in the AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
Type 20
Arm–Stay
Zone type 20 is a special-purpose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or
disarming.
Type 21
Arm–Away
Zone type 21 is a special-purpose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• System is armed in the AWAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or
disarming.
Type 22
Disarm
Zone type 22 is a special-purpose zone type used with 5800 series
wireless pushbutton.
Zone Characteristics:
• Disarms the system when the zone is activated.
Type 23
No Alarm Response
Zone type 23 can be used on a zone when a Powerline Carrier Device
(e.g., X-10) action is desired, but with no accompanying alarm (e.g., front
door light).
Type 24
Silent Burglary
Zone type 24 is usually assigned sensors or contacts on exterior doors and
windows where bells and/or sirens are NOT desired.
Zone Characteristics:
• Instant alarm, with NO audible indication when is armed in the AWAY, STAY,
STAY NO DELAY, or AWAY NO DELAY mode.
• Report sent to the central station.
Note:
Keypad beeps if the zone is faulted when system is disarmed and Chime mode is
on.
–16–
Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the
data for this installation. Note that both keypad LEDs flash while in Programming mode.
Note: Entering a number other than the one specified will give unpredictable results.
*20
*21
*22
*23
*24
*25
*26
*27
*29
*30
*31
The Installer Code is used to enter the 4-digit Master Security Code. See
"Master Code" in the System Operation section for procedure.
Installer Code
Enter 4 digits, 0-9
If enabled, security code is not required to arm the system. The user
simply presses and holds down the AWAY or STAY key to arm.
Quick Arm Enable
0 = do not allow quick arm
1 = allow quick arm
This option allows the choice of either always backlighting the keypad or
turning the backlighting off after 10 seconds of keypad inactivity.
Keypad Backlight Timeout
0 = no timeout; always backlight keys
1 = turn backlighting off after inactivity
Forced Bypass
0 = no forced bypass
1 = provide automatic bypass of all open (faulted) zones
00 = disable all wireless keypad usage
01-31 = House ID
Powerline Carrier Devices require a House ID. This field identifies this
House ID to the Control. The Powerline Carrier Devices are
programmed in field * 80.
Powerline Carrier Device (X-10) House ID
4=E
5=F
6=G
7=H
8=I
9=J
# + 10 = K
# + 11 = L
# + 12 = M
# + 13 = N
# + 14 = O
# + 15 = P
This option allows the installer to define the specific zones intended to
chime when faulted while the system is in Chime mode. If enabled, these
zones are defined in zone list 3 (see *81 Zone List Menu Mode).
Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter
zone when Chime mode is activated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime mode on)
Refer to the User’s Manual for setting the clock time and date.
Real Time Clock Display
0 = do not display the time
1 = display the time
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
Daylight Savings Time Start/End Month
0, 0 = no daylight saving time used
1-12 = start month and end month
Enter the appropriate start and end weekend of the month.
Daylight Savings Time Start/End Week
0 = disable
1 = first weekend of month
2 = second weekend
3 = third weekend
4 = fourth weekend
5 = last weekend
6 = next to last
rd
7 = 3 from last
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming period for a
given zone
ReadyGuard-R - Applies to Long Range Radio Output if “0” is
selected in field *91
ReadyGuard-REN - Applies to Long Range Radio Output if a
Long Range Radio is connected to the Trigger Single (Neg.)
terminal #8.
*32
*33
*34
Note: UL installations: must be 0 (no forced bypass)
The House ID identifies receivers and wireless keypads.
If a 5827 Wireless Keypad or 5804BD/5804BDV Transmitter is to be
used, a House ID Code MUST be entered, and the keypad should be set
to the same ID.
RF House ID Code
0=A
1=B
2=C
3=D
All zones bypassed by this function will be displayed after the bypass is
initiated.
Fire Sounder Timeout
0 = yes, fire sounder timeout after time programmed in
field *33
1 = no fire sounder timeout; continue sounding until
manually turned off
Alarm Bell Timeout
0 = No timeout
1 = 4 min
2 = 8 min
3 = 12 min
Exit Delay
00-99 = exit delay time in seconds
4 = 16 min
UL installations: must be 0 (no limit)
This field applies only to burglary zones (zone response types 1-5, 10),
and affects long range radio reporting but does not affect central station
reporting.
Note: This field applies only to the bell and does not affect keypad
sounds.
This Control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
This field determines whether the external sounder will shut off after time
allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
The system will wait the time entered before sounding an alarm if the exit
door is left open after the system has been armed.
UL installations: must be set for a maximum of 60 seconds
–17–
Data Field Descriptions
*35
00-99 = entry delay time in seconds.
The system will wait the time entered before sounding alarm upon entering
if system is not disarmed. UL installations: must be set for a maximum of 45
seconds
*36
Entry Delay 02
00-99 = entry delay time in seconds.
The system will wait the time entered before sounding alarm upon entering.
UL installations: must be set for a maximum of 45 seconds
*37
Entry Delay 01
Audible Exit Warning/Quick Exit
Exit Warning
0 = no exit warning sound
1 = provide exit warning sound
when armed AWAY
*38
*39
Quick Exit
0 = no quick exit
1 = allow quick
exit
Confirmation of Arming Ding
0 = no ding
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF button or
RF keypad only
Power Up In Previous State
0 = always power up in a disarmed state
1 = assume the system status prior to power-down
Exit Warning: Sound consists of slow continuous beeps until last 5 seconds,
when it changes to fast beeps. The warning sound will end at the
termination of exit delay.
Quick Exit: If enabled, user can restart the exit delay time after arming in
STAY mode by entering the user code and pressing the STAY key, or by
pressing the STAY key if Quick Arm is enabled. This avoids having the
user disarm then re-arm the system after allowing someone to enter or exit
Confirmation of arming is provided by a 1/2 second external sounder “ding”
that sounds when closing report is sent, or at the end of exit delay.
If Option 2 is selected the external sounder “ding” occurs immediately after
the system receives the RF transmission.
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted, and any bypassed zones will be unbypassed.
Note: If the previous state was armed AWAY or STAY, the system will not
respond to sensor changes for 1 minute, which allows time for sensors such
as PIRs to stabilize. UL installations: must be 1 (power up in previous state)
DIALER PROGRAMMING (*40–*50)
Fields *40, *41, *42: Enter up to the number of digits shown. Do not fill unused spaces. Enter 0–9, # + 11 for ‘*’; # + 12 for ‘#’; # + 13 for
a pause (2 seconds)
NOTE: Whenever AAV is used, primary (field *41) and secondary (field *42) phone numbers should be preceded with the call waiting
disable command. Otherwise, there is the possibility of connection of the third party to LYNX during AAV mode.
*40
*41
*42
PABX Access Code
Enter up to 6 digits if PABX is needed to access an
outside line.
Primary Phone No.
Enter up to 20 digits.
Secondary Phone No.
Enter up to 24 digits.
If fewer than 6 digits need to be entered, exit by pressing [*]. To clear
entries from field, press *40*.
If fewer than 20 digits entered, exit by pressing [*]. To clear entries from
field, press *41*.
Note: Backup reporting (8 attempts are made to the secondary phone number if
no kissoff is received after 8 attempts to the primary number) is automatic
only if there is a secondary phone number (field *42).
If fewer than 24 digits entered, exit by pressing [*]. To clear entries from
field, press *42*. See backup reporting note for field *41. If using the
paging feature, enter the pager phone number here.
Fields *43 and *44:
Enter [*] as the fourth digit if a 3-digit account number (for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
account number for Nos. 0000–0999. Exit field by pressing [*] if only 3 digits are used. To clear entries from field, press *43* or *44*.
See blank Programming Form for examples of account number entries. If using the paging feature, do not enter a leading 0 in the
subscriber account number, and do not use digits A-F anywhere in the number. Some paging systems provide voice mail capability, which
is activated by a leading 0 in the message. Enter digits 0–9; # +11=B; # +12=C; # +13=D; # +14=E; or # +15=F.
Primary Subs Account No.
*43
Enter four digits .
*44
Enter four digits.
Secondary Subs Account No.
Enter the primary subscriber account number.
To clear entries from field, press *43*.
Enter the secondary subscriber account number.
To clear entries from field, press *44*.
–18–
Data Field Descriptions
*47
Phone System Select
Note: For ReadyGuard-R only options 0, 1, 2, and 3
are applicable. For ReadyGuard-REN all
options apply.
Central
Station
No
WATS
WATS
*48
*49
Pulse
0 = No
Speaker
Phone
2 = No
Speaker
Phone
Dialing Mode
Tone
Pulse
1 = No
Speaker
Phone
3 = No
Speaker
Phone
4 = With
Speaker
Phone
6 = With
Speaker
Phone
Tone
Primary
Secondary
See choices below
See choices below
0 = 3+1; 4+1 ADEMCO Low Speed Standard
1 = 3+1; 4+1 Radionics Standard
2 = 4+2 ADEMCO Low Speed Standard
3 = 4+2 Radionics Standard
6 = 4+2 ADEMCO Express
7 = ADEMCO Contact ID Reporting
8 = 3+1; 4+1 ADEMCO Low Speed Expanded
9 = 3+1; 4+1 Radionics Expanded
Split/Dual Reporting
To Primary
1=
2=
3=
4=
5=
Note: If using pulse dialing, you must enter the numbers slowly in order to
allow the pulse dialer time to operate.
5 = With
Speaker
Phone
7 = With
Speaker
Phone
Report Format for Primary/Secondary
To Secondary
0 = All reports
This option is used to enter the correct type of phone dialing (pulse or tone),
and to select the correct WATS line option for the Central Station. For
ReadyGuard-REN this option is used to activate the speaker phone option.
Alarms, Restore, Cancel
All except Open/Close, Test
Alarms, Restore, Cancel
All except Open/Close, Test
All reports
None, unless primary
fails, then all
Others
Open/Close, Test
All
All
All
To Primary
To Paging Number
6 = All reports except Open/Close Alarms, Open/Close ‡,
Troubles
7 = All reports
Alarms, Troubles
8 = All reports
Alarms, Open/Close ‡,
Troubles
9 = All reports except Open/Close Open/Close ‡
‡ Will report Users 0, 5-8, and, if using wireless button-type
devices, will report the zone number of the arm or disarm
button 26-33. All other zones and users are not reported.
Enter * as the 4th digit of *43 through *44, if 3+1 dialer reporting is to be
used. (For an explanation of these formats, see the System Communication
section of this manual.)
Notes: (1) The maximum number of alarm and alarm restore reports during
one armed period is determined by field *92.
(2) Option 7 (ADEMCO Contact ID Reporting) must be selected for
AVM.
Use options 0 - 5 when reporting to telephone receivers.
Use options 6 - 9 when reporting to a pager is desired.
Pager Report Format
Options 6-9 send reports to the primary phone number and send reports to a
pager, which has its phone number entered as the secondary phone number
in field *42.
The pager report is a 7-digit code, with optional 16-digit prefix, in the
following format:
AAAAAAAAAAAAAAAA-EEE–00NN where:
AAA = Optional 16 digits for PIN number, etc. See field *88 for full
description of these characters.
EEE = 3-digit Event Code as follows:
911 = Alarm (NN = zone number)
101 = Open, system disarmed (NN = user no.)
102 = Close, system armed (NN = user no.)
811 = Trouble (NN = zone no.)
00 =
Always displayed before 2-digit user/zone no.
NN =
2-digit user number or zone number, depending on the type of
event (EEE) that occurred. NN=00 indicates AC loss, system low
battery, or low battery in 5827.
*50
15-Second Dialer Delay (Burglary)
0 = no dialer delay
1 = provide 15-second delay of burg. alarm report
If enabled, provides communication delay to the central station and allows
the subscriber time to avoid a false alarm transmission. Delay does not
apply to zone type 6, 7, 8, and 24 alarms, which are always sent as soon as
they occur. UL installations: must be 0 (no delay)
*51
Periodic Test Report
Test report code entered in field *64 is sent.
*52
First test Report Offset
*53
Sescoa/Radionics Select
0 = no test report
1 = once every 24 hrs
2 = weekly
3 = once every 30 days
This is the time to first report from programming or downloading.
0 = 24 hrs after exit program mode or download
1 = 6 hours after exit program mode or download
2 = 12 hrs after exit program mode or download
3 = 18 hrs after exit program mode or download
Select 0 for all other formats.
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
–19–
Data Field Descriptions
*58
RFJam Detection
For Event Logging, Option 2 must be selected.
0 = no jam detection
1 = RF jam detection with event logging, but no
central station report
2 = RF jam detection with event logging and with
central station report (if trouble/restore report is
enabled in fields *60, *71)
If the control detects an RF jam condition, a “FAULT” message appears for
zone 90. The Contact ID code for RF Jam is 344.
Note: This feature cannot be used in conjunction with the 5827 wireless keypad.
SYSTEM STATUS AND RESTORE REPORT CODES PROGRAMMING (* 59 –* 76, & * 89)
Program Report Codes using the interactive *56 Enhanced Zone Programming Mode, or codes can be entered in data fields *59-*76, *89.
The following is a set of guidelines when programming report codes. The actual report code digits that you enter depend upon the
particular installation, and should be in agreement with you and the central station office receiving the signals.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter "#+10" for A (reports a “0” on some
receivers), "#+11" for B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F. Entering "0" in the first box will disable a report.
Entering "0" in the second box results in automatic advance to the next field.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, or A–F, as described above. Entering "0" in
the first box will disable a report. Entering "0" in the second box will eliminate the expanded message for that report.
With ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different digit for each zone
until you have used up available digits. If the number of zones exceeds the number of available digits, begin with digit 1 again. This is an
"enabling" code only and is not the actual code sent to the central station office. Entries in the second boxes will be ignored. For system
status (non-alarm) codes, enter a “1” in the first box for all the system conditions you want to send to the central station. A "0" in the first
box disables the report.
SYSTEM STATUS REPORT CODES (*59–*68)
Exit Error Report Code
*59
See notes above
If the system is armed and an entry/exit or interior zone is still open
after the exit delay time has expired, an alarm will sound at the
keypad and external sounder. If the system is disarmed before the
end of the entry delay that immediately follows, the alarm sounding
will stop and no message will be sent to the central station. The
keypad will display “CA (CANCELED ALARM).”
If the system is not disarmed before the end of the entry delay
mentioned above, and an entry/exit or interior zone is still open, an
“exit alarm” message will be sent to the central station if an Exit
Error report code is selected in this field. The keypad will display
“EA (EXIT ALARM),” and the alarm sounding will continue until
the system is disarmed (or timeout occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or
interior zone within 2 minutes following the end of the exit delay,
and an “Exit Alarm” message will be sent to the central station.
If Contact ID format has been programmed, the message will contain
the zone number and error code 374 (Trouble–Exit Error). If 4+2
format is used, the digit entered in this field will be sent followed by
the second digit of the programmed alarm code for that zone. If 3+1
or 4+1 format is used, only the digit entered in this field will be sent.
This message will go to the primary phone no. Under any of these
conditions, no restore message will be sent.
If “0” is entered in this field, no special message will be sent, only
the regular alarm and alarm restore code for the zone.
*60
*61
*62
Trouble Report Code (See notes above)
This will be sent if a zone goes into trouble.
Bypass Report Code (See notes above)
This will be sent when a zone is manually bypassed.
AC Loss Report Code (See notes above)
Timing of this report is random with up to a 4-hour delay. If AC
restores before the report goes out, there is no AC restore report.
*63
Low Battery Report Code (See notes above)
This will be sent when a low battery condition exists in the system’s
standby battery.
*64
Test Report Code (See notes above)
This is sent periodically to test that the communicator and phone
lines are operational (frequency of report is selected in field *51).
*65
Open Report Code (See notes above)
This is sent upon disarming of the system. 2nd digit = user number, if
expanded or 4+2 reporting is selected.
–20–
Data Field Descriptions
SYSTEM STATUS REPORT CODES (*59–*68) Continued
This option allows for independent programming of AWAY and STAY
Arm AWAY/STAY Report Code (See notes
*66
reports. 2nd digit of report is user number if expanded or 4+2 reporting is
above)
selected.
NOTE: OPEN reports are not sent if the associated closing report is not
enabled.
*67
*68
RF transmitter Low Batt. Report Code (See
notes above)
Cancel Report Code (See notes above)
RESTORE REPORT CODES (*70–*76)
Alarm Restore Report Code, 1st Digit
*70
(See notes above)
This is sent in the event that a wireless transmitter low battery condition
exists.
This is sent upon disarming of the system after an alarm condition was
reported.
Sent when the zone that caused an alarm is restored to its non-faulted
condition. 2nd digit is automatically sent as the 2nd digit of the zone alarm
report code programmed in field *56, if expanded or 4+2 reporting is
selected.
*71
Trouble Restore Report Code
(See notes above)
Sent when a trouble in a zone is restored.
*72
Bypass Restore Report Code
(See notes above)
Sent when a zone that has been bypassed is unbypassed.
*73
*74
AC Restore Report Code (See notes above)
Sent when AC power has been restored after an AC power outage.
Low Battery Restore Report Code
Sent when a system low battery condition is restored to normal.
*75
*76
*87
*88
(See notes above)
RF Transmitter Low Batt. Restore Code
(See notes above)
Sent when a transmitter that previously sent in a “low battery” message
has sent a message indicating it no longer has a low battery condition.
Test Restore Report Code (See notes above)
Sent when the test mode is exited. A restore code entered here will cause a
restore message to be sent when Test mode is exited.
AUX Function/1-Button Paging
If “0” is entered, user can define a macro function for the AUX key. See
user manual for description of the use of this key.
If “1” is entered, you must also select an option 6-9 in field *49. The
actual pager message is 999-9999. Note that the hyphen may not be
displayed, depending on the pager service.
Note: A macro cannot be run from the Test mode.
0 = Aux key performs defined function (macro)
1 = Aux key sends predefined message to pager
Pager Characters
Enter up to 16 digits that will appear in front of the 7digit pager message.
Enter [#] + [11] for “*”
Enter [#] + [12] for “#”
Enter [#] + [13] for 2-second pause
NOTES: Verify that the pager supports [*] and [#]
characters before using them. Some pagers
require an additional delay [pause] in order to
receive the entire message.
If entered, these digits will appear in front of the 7-digit pager message
sent by the control (either upon a system event or upon pressing the AUX
key [if programmed for paging]), and during latch key report (if enabled
during scheduling). These digits can consist of a PIN number, account
number, pauses or special digits needed by the pager (these types of
characters are not displayed), or any other characters the user chooses that
will be displayed (eg., using a character code to distinguish between
control panel messages and other pager messages).
You do not need to fill all 16 digits. Press [*] + next field number to exit
the field. To clear the field, press *88*.
See field *87 to select the AUX key Paging feature. See field *49, which
must have an option 6-9 selected to enable paging messages, for
description of the pager message.
*89
Event Log 80% Full Report Code
(See notes above)
If an Event Logging selection is made in field *90, a message can be sent
to the central station receiver when the log is 80% full. If the log becomes
full, a new message will overwrite the oldest message in the log.
Note: All control and readout from the log, aside from the selection made
by the installer in field *90, is accomplished via the downloader.
–21–
Data Field Descriptions
*90
Example: To select “Alarm/Alarm Restore” and “Open/Close,” enter 9 (1
+ 8); to select all events, enter #15.
Default “3” = alarm/alarm restore (1) plus trouble/trouble restore (2).
The system has the ability to record various events in a history log (84event capacity). The types of events to be logged can be selected as
indicated. At any time, the downloader operator can then upload the log
and view or print out all or selected categories of the log. The log can also
be cleared by the download operator.
The display/printout at the central station will show the date, time, event,
and description of the occurrences.
Event Logging Options
0 = No event logging
1 = log Alarm/Alarm Restore
2 = log Trouble/Trouble Restore
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of events (add value of entries)
Note:
!
*91
The features programmed in Field *91 differ between ReadyGuard-R models. Ensure you use the correct
option for the model you are installing!
ReadyGuard-R
Long Range Radio/Alarm Audio Verification
(AAV) Trigger/Remote Phone Control
0 = long range radio trigger only
1 = AAV and remote phone control
2 = long range radio trigger and remote phone control
4 = AAV only
Notes:
For UL installations alarm audio verification
cannot be used. Alarm audio verification will only
function when Contact ID is selected.
0 = none
1 = AAV and remote phone control
2 = remote phone control only
4 = AAV only
Notes: (1) For UL installations alarm audio verification
cannot be used. Alarm audio verification will
only function when Contact ID is selected.
2) AVM/Remote phone features can only be used if
the central station or remote phone supports
DTMF commands.
*93
Number of Reports In Armed Period
0 = reports limited to a total of 10
1 = unlimited number of reports
Flexible Callback
0 = no flexible callback
1 = last digit flexible
2 = last 2 digits flexible
3 = last 3 digits flexible
For ReadyGuard-R this option is used to enable the Long Range Radio,
Alarm Audio Verification and/or Remote Phone Control options. If Long
Range Radio (0) is selected, trigger output (terminal screw #8) will
generate a steady signal for burglary alarm (a single 3 to 4-second pulse
for all types of silent alarms) or a temporal signal for fire alarm. (Refer to
Long Range Radio Installation Instructions for appropriate wiring.) Alarm
Audio Verification requires the installation of the LYNX-AVM. Refer to
the LYNX-AVM Installation Instructions.
Notes: (1) If Long Range Radio is being connected, Alarm Audio
Verification cannot be used.
(2) In order to activate the remote phone control feature and defeat an
answering machine, ensure that the correct ring detection count
(“15”) has been programmed in field *95.
(3) Remote Phone Session will be terminated if a report must be sent.
(4) If Alarm Audio Verification mode is selected, the Long Range
Radio alarm trigger is not available, and the Long Range Radio
cannot be connected.
(5) Alarm Audio Verification will only function when Contact ID is
selected and cannot be used for UL installations.
(6) If an alarm will be reported to primary and secondary phone
numbers, AAV can only function via the secondary number.
(7) If an alarm will be reported to a pager (6, 7, or 8 in field *49),
AAV cannot be used.
For ReadyGuard-REN, this option is used to enable the Alarm Audio
Verification and/or the Remote Phone Control features.
ReadyGuard-REN
Alarm Audio Verification (AAV)/Remote
Phone Control
*92
System messages are logged when any non-zero selection is made.
Notes: (1) No programming is required if connecting an ALARMNET 7845C
device because the option is always enabled.
(2) In order to activate the Remote Phone Control feature and defeat
an answering machine, ensure that the correct ring detection count
(“15”) has been programmed in field *95.
(3) Remote phone session will be terminated if a report must be sent.
(4) Alarm Audio Verification will only function when Contact ID is
selected and cannot be used for UL installations.
(5) If an alarm will be reported to primary and secondary phone
numbers, AAV can only function via the secondary number.
(6) If an alarm will be reported to a pager (6, 7, or 8 in field *49),
AAV cannot be used.
This option can be used to limit the number of messages (alarm & alarm
restore reports) sent to the central station in an armed period.
UL installations: must be 1 (unlimited reports)
If enabled, the control will ignore the last 1, 2, or 3 digits of the
programmed callback number (field *94) during a single download session.
This allows the download operator to temporarily change the callback phone
number by the number of digits selected, which allows the control to call
back similar, but different numbers during a single session. For example, if
downloading to a large number of controls, the operator can command the
controls to call back phone numbers 555-1111, 555-1112, 555-1113, etc.,
thus spreading the communications among several computers.
–22–
Data Field Descriptions
DOWNLOAD INFORMATION (*94, *95)
Download Call Back Phone Number
*94
This is the phone number the control will use to call back the downloading
computer.
Do not fill unused spaces. End field by pressing *. To clear entries from
field, press *94*.
Enter up to 20 digits as follows: 0–9, # +11 for “*”, # +
12 for “#”, # + 13 for a pause.
*95
Ring Detection Count For Downloading/
Remote Phone Control
0 = disable station initiated download and remote phone
1-14 = number of rings before control picks up phone
line
15 = defeat answering machine
Enter “15” to select defeat answering machine mode. If an answering
machine is on the premises, you need to dial the premises and hang up on
the first ring. Wait at least five (5) seconds (but no more than 22 seconds)
and dial the premises phone number again. The control will pick up and
announce “SYSTEM” every three seconds.
Note: To enter a number higher than 9 you must first press the [#] key.
Other Programming Commands
*56
ENHANCED ZONE PROGRAMMING MODE
Interactive menu mode used for programming zone attributes and report codes. Refer to the *56 Enhanced Zone Programming
Mode section for procedure.
*80
DEVICE PROGRAMMING MENU MODE
Interactive menu mode for programming Powerline Carrier Devices. Refer to the *80 Device Programming Menu Mode
section for detailed procedure.
*81
ZONE LISTS FOR MENU MODE
Interactive menu mode for programming zone lists for Powerline Carrier Devices. Refer to the *81 Zone List Menu Mode
section for detailed procedure.
*83
ENHANCED SEQUENTIAL MODE
Interactive menu mode used to enter RF transmitter serial numbers. Refer to the *83 Enhanced Sequential Mode section for
detailed procedure.
*84
ASSIGN ZONE VOICE DESCRIPTORS
Interactive menu mode used to assign descriptors to each zone. These descriptors will be announced whenever the system
announces an event involving a zone.
*85
RECORD CUSTOM VOICE DESCRIPTORS
Interactive menu mode used to record custom descriptors for use with each zone.
*96
INITIALIZE DOWNLOAD ID AND SUBSCRIBER ACCT. NO. FOR DOWNLOADING
Pressing *96 initializes the system for downloading.
*97
SET ALL PROGRAM FIELDS TO 1 OF 4 SETS OF DEFAULT VALUES
See Default Tables at the end of this manual.
*98
EXITS PROGRAMMING MODE
Prevents re-entry by: Installer Code + 8 + 0 + 0; allows re-entry only by Power-up, then [ *] and [#].
*99
EXITS PROGRAMMING MODE
Allows re-entry to program mode by: Installer Code + 8 + 0 + 0; or by Power-up, then [*] and [#].
–23–
*56 Enhanced Zone Programming Mode
This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes, and to identify
the type of loop input device. This mode can also be used for entering 5800 Series transmitter serial numbers.
Note: There are two methods for entering transmitter serial numbers. The first method is by using *56 Enhanced Zone
Programming mode (described below). The second method is by using *83 Enhanced Sequential Mode. Note that the
*83 Enhanced Sequential Mode requires that all zone information first be entered using *56 Enhanced Zone
Programming mode.
You must refer to these instructions or to the Program Form while programming the system because the keypad display does
not show prompt titles. Instead, prompts are indicated by a number/letter combination.
The prompts for *56 are as follows:
A 01
Zone Number -------------------------- for entering the zone number
b
Zone Type ------------------------------ for entering zone type
C
Report Code ---------------------------- for entering the zone’s report code
d
Input Type ------------------------------ for entering the transmitter’s input type
E
Loop Number -------------------------- for entering the transmitter loop number
F
Delete Serial Number? --------------- for deleting existing serial number
1A
Enroll Mode?--------------------------- selects serial number enroll mode
1b
Serial Number-------------------------- for entering transmitter’s serial number
1C
Voice Descriptor? --------------------- selects voice descriptor mode
1d
Descriptor 1 ---------------------------- for entering first descriptor word
1E
Descriptor 2 ---------------------------- for entering second descriptor word
1F
Descriptor 3 ---------------------------- for entering third descriptor word
–24–
*56 Enhanced Zone Programming Mode
While in Program mode, press *56 to enter Zone Programming Menu Mode.
Refer to the zone assignment table for *56 on the separate programming form.
The following explains the *56 prompts in detail. The left two columns identify the prompts and list the available entries for
each. The right-most column provides a further explanation of the entries.
Notes: (1) You may find it convenient to adjust the volume setting before entering the Programming Mode. This will
allow you to clearly hear feedback announcements or system beeps.
% -
b
Enter the 2-digit zone number to be programmed and the Voice Descriptor
for the selected zone number will be announced, if it is programmed. Press
[*] to advance.
• Zone 01 = hardwire
• Zones 02-25 = RF zones (only)
• Zones 26-41 = Button zones (only)
• Zone 92 = Duress
• Zones 95, 96, 99 = Panic zones
Pressing 00 exits mode, upon which the prompt “56” blinks, indicating the
mode is inactive. Press [*] + any field number to go to that field.
Zone number
01-41, 95, 96, 99 = Zone number
[*] = continue
00 = exit Zone Programming mode
Zone type
zt
00-24 = zone type
[*] = continue
[#] = return to previous prompt
Note: If 00 is accepted as a zone type, save the 00
zone type and advance to the confirm delete
prompt (F).
'
d
Enter the report code for this zone.
[*] = continue
[#] = return to previous prompt
The report code consists of 2 hexadecimal digits, each in turn consisting of
2 numerical digits. For example, for a report code of "3C", enter [0][3] for
"3" and [1][2] for "C".
If this is Zone 1, 95, 96 or 99, the system skips to the VOICE
DESCRIPTOR prompt (1C).
Input type
Enter the input type for the transmitter assigned to this zone. Refer to the
transmitter’s instructions for input types of each transmitter.
Report code
rc
i
Each zone must be assigned to a zone type, which defines the way in
which the system responds to faults in that zone. Enter the 2-digit zone
type for this zone as follows:
00 = Not Used
08 = 24 Hr Aux
01 = Entry/Exit #1
09 = Fire without verify
02 = Entry/Exit #2
10 = Interior w/Delay
03 = Perimeter
20 = Arm–Stay
04 = Interior Follower
21 = Arm–Away
05 = Trouble Day/Alarm Night
22 = Disarm
06 = 24 Hr Silent
23 = No Alarm Response
07 = 24 Hr Audible
24 = Silent Burglary
3 = RF (supervised RF) – sends periodic checkin signals, faults, restore and low battery
signals
Note: RF type transmitters must remain within
range of the receiver, otherwise a
supervision failure signal will occur.
Note: Zones 2-25 should be assigned Input Type 3 or 4 . Zones 26-41
should be assigned Input Type 5 only.
4 = UR (unsupervised RF) – sends same as
“RF” type, but control does not supervise
the check-in signals
5 = BR (button type) – sends only fault and low
battery signals; does not send restores or
check-in signals
Note UR and BR type transmitters may be carried
off premises (out of range without causing a
supervision failure.
[*] = continue
[#] = return to previous prompt
)
l
Loop number or Loop and Serial
number (if using RF Learning)
1-4 = loop number for the zone of the
transmitter being entered.
0 + [*] = continue to DELETE ZONE
PARAMETERS CONFIRMATION
prompt (F)
[*] = continue to the ENROLL MODE prompt
(1A) if not entered, or VOICE
DESCRIPTOR prompt if already entered
[#] = return to previous prompt
–25–
This prompt can be used to enroll loop number and serial number via
RF transmission or the loop number can be enrolled manually. If
using the RF Learning Mode, there is no need to manually enter a
loop number. Proceed directly to RF Learning
Note: BR type devices cannot be enrolled by using UR or RF type. Likewise,
UR or RF type devices cannot be enrolled by using a BR type device.
There is a 52-second time-out for RF enrolling. At the end of the timeout, the system returns to the INPUT TYPE prompt (d). If enrolled, loop
number and “L” are displayed.
RF Learning - Two (2) transmissions (2 key depressions) at least 5
seconds apart will be required for BR type devices (device type 5). Two
beeps will sound after the second transmission, confirming that the loop
number and serial number have been learned.
*56 Enhanced Zone Programming Mode
For all other device types, four (4) transmissions are required (fault,
restore and fault, restore). A single beep will sound after the second
transmission confirming that the loop and serial number have been
captured. Following the fourth transmission the system will confirm that
the loop number and serial number have been learned and announce the
Voice Descriptor for the zone, if it is programmed, followed by two
beeps.
Press [*] to continue.
Manual Entry - Enter the desired loop number and press [*] to continue
(see the transmitter’s Installation Instructions for specific loop
designations).
Note: The loop number can be changed even if the zone has already been
entered. Care should be taken when using this feature as it has the
capability to make zones inoperable by creating a mismatch of a
working serial number/loop number combination. This should be reconfirmed if the loop number is changed.
“L” indicates that the zone’s serial number has already been enrolled.
*
Delete zone parameters confirmation
0 = discard the delete request
1 = confirm requested delete
Note: If 00 was entered as a zone type in prompt
(b), 00 will be retained and system will
advance to prompt (1C)
-% 0'
Enroll mode
0 = advance to the VOICE DESCRIPTOR
prompt (1C).
This function deletes either the serial number or all zone information that
is programmed for the zone.
If “00” was entered in the zone type, the confirmation of the delete
request will delete all information associated with the zone currently
being programmed.
If “0” was entered in the loop number, the confirmation of the delete
request will delete the serial number of to the zone currently being
programmed.
If “L” is displayed, the serial number for this transmitter has already been
entered. It may, however, still be viewed, confirmed (only if in listen
mode), or deleted.
Note: This will save all zone parameters.
1 = enter now and proceed to SERIAL
NUMBER prompt (1b).
Note: Not applicable if the serial number is
already present.
2 = copy the last serial number entered into
local ram.
Note: If this is the 1st zone, none will be in the
buffer and the panel will emit a long tone.
Not valid if serial number is already present.
3 = view existing serial number.
Note: Only if “L” is displayed. If “L” is not
displayed, panel will emit a long beep.
9 = advance to F; delete existing serial number.
Note: Only if “L” is displayed. If “L” is not
displayed, panel will emit a long beep.
[*] = advance to the VOICE DESCRIPTOR
prompt (1C). This will save all zone
parameters.
[#] = return to the LOOP NUMBER prompt (E).
View serial number
Enter “3”. Each digit will be redisplayed, and the keypad will beep once
for digits 1-6, and three times for the last digit.
Confirm serial number
The serial number/loop number combination can be confirmed after one
transmission from a BR type device or two transmissions (fault and
restore) from a UR or RF type device. If a transmission is received that
matches the serial number and loop number entered, the system will
confirm the reception by announcing the Voice Descriptor for the zone, if
it is programmed, followed by three beeps, and a “C” will appear on the
display indicating the received serial number and loop number have been
confirmed. No further transmissions will be received.
Delete serial number
The serial number can be deleted by entering “9”.
If “L” is not displayed, the serial number for this transmitter has not been
previously entered. You may enter the serial number manually, copy the
previous serial number, return to Prompt (E) or enter the serial number
later using the *83 Enhanced Sequential Mode.
Note: In order for all entered parameters to be
accepted, you must advance to the VOICE
DESCRIPTOR prompt (1C).
–26–
*56 Enhanced Zone Programming Mode
Manual entry
Enter "1" to advance to Serial number prompt (1b).
Copy the previous serial number
Enter “2” to copy the previous serial number entered.
Return to Prompt (E)
Enter “#” to return to Loop Number prompt (E).
Enter transmitter later
Enter “0” or “*” if you wish to enter the transmitter later, using the *83
Enhanced Sequential Mode described later in this manual.
Notes: (1) The panel will listen only when it is in the idle loop waiting for key
entry and a serial number has been entered. If a key is entered, the
function must be completed and the panel will listen again.
(2) A long beep indicates illegal entry or duplicate serial number/loop
entry
-b
Serial number
In this mode, the transmitter serial numbers can only be entered manually.
Enter the transmitter’s 7-digit serial number.
[#] = return to prompt 1A and reject any serial
numbers entries that have been made.
[*] = return to prompt 1A, (if a valid serial
number has been entered, the "L" is
displayed and the serial number will be
copied into EEROM from the last serial
entered into the buffer.)
Enter the 7-digit serial number printed on the transmitter. If an incorrect
digit is entered, press the [#] key to backup to prompt (1A) and start over.
When all 7 digits are entered, press the [*] key.
Note: This prompt can be used only to manually
enroll a serial number. RF enrollment will be
rejected and the current zone descriptor will
be announced, followed by a single long
beep and the system will return to prompt
(1A).
-'
Voice descriptor
-d
Descriptor 1
-)
-*
0 = skip to next zone (A)
1 = enter descriptor mode; existing descriptor
for this zone will be announced
vi
vi
vi
If 52 seconds passes and no entry has been made, the system returns to
prompt (1A).
Notes: (1) If the serial and loop number combination is already present the
keypad will emit a single long beep and the system will return to the
(1A) prompt and “L” will be displayed.
(2) If less than 7 digits have been entered, the keypad will emit a single
long beep and return to the (1A) prompt without displaying the “L”.
(3) If more than 7 digits have been entered, the first 6 digits will be
saved along with the last digit that was entered (entering 123456789
yields the serial number 1234569).
Each zone can have a voice descriptor of up to 3 words that will be
announced whenever the system announces status for that zone.
† see *84 Assign Zone Voice Descriptors section for vocabulary index
Enter [#] + 2-digit vocabulary index number† of
first descriptor word for this zone.
6 = accept word and advance to descriptor 2
(descriptor 2 will be announced)
8 = accept word and advance to next zone
(prompt A) – entire zone descriptor will be
announced
Press any other key to repeat the selected word.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press
[#] + desired 2-digit vocabulary index number.
If descriptor 1 is not desired, enter [#] + 99 (blank), then press [8] to return
to zone number prompt.
Descriptor 2
† see *84 Assign Zone Voice Descriptors section for vocabulary index
Enter [#] + 2-digit vocabulary index number† of
second descriptor word for this zone.
6 = accept word and advance to descriptor 3
(descriptor 3 will be announced)
8 = accept word and advance to next zone
(prompt A) – entire zone descriptor will be
announced
Press any other key to repeat the selected word.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press
[#] + desired 2-digit vocabulary index number.
If descriptor 2 is not desired, enter [#] + 99 (blank), then press [8] to return
to zone number prompt.
Descriptor 3
† see *84 Assign Zone Voice Descriptors section for vocabulary index
Enter [#] + 2-digit vocabulary index number† of
third descriptor word for this zone.
6 or 8 = accept word and advance to next zone
(prompt A) – entire zone descriptor will
be announced
Press any other key to repeat the selected word.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press
[#] + desired 2-digit vocabulary index number.
If descriptor 3 is not desired, enter [#] + 99 (blank), then press [8] to return
to zone number prompt.
–27–
*80 Device Programming Menu Mode
Powerline Carrier devices (eg., X-10 brand devices) are programmable switches that can be used to perform many different
functions. They can be used to turn lights on and off, control sounders, or for status indications. In this system, each device
must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). Each of these
is described below.
The control supports a total of 8 output devices.
The 1332X10 transformer sends signals from the control panel through the premises AC wiring to the Powerline Carrier
Devices (which are plugged into AC outlets). Devices plugged into Powerline Carrier Devices can then be made to perform
various functions in response to commands entered at the keypads in the security system.
8/
Powerline Carrier Devices are not UL Listed for fire or burglary functions and are intended
for home automation.
Programming Options Defined
The following will help you understand the programming of output devices when using *80 and *81 modes.
ACTION
The "ACTION" of the device is how the device will respond when it is activated by the "START"
programming. There are four different choices of actions:
• ACTIVATE for 2 SECONDS and then reset.
• ACTIVATE and REMAIN ACTIVATED until stopped by some other event.
• PULSE ON and OFF until stopped by some other event.
• NOT USED when the device is not used.
START
The "START" programming determines when and under what conditions the device will be activated. The
following START options are available:
Start by Event
1. Event is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone list) in
order to activate the device. These conditions apply only when a zone list is used. The different
choices for "EVENT" are listed below and in the “Programming Powerline Carrier Devices” paragraph
that follows.
• ALARM
Device activates upon any alarm in an assigned zone in the zone list.
• FAULT
Device activates upon any opening or short in an assigned zone in the zone list.
• TROUBLE Device activates upon any trouble condition in an assigned zone in the zone list.
• NOT USED Device action is not dependent upon one of the above events.
2. A zone list is a group of zones to which the “EVENT” applies in order to activate a particular device.
Note that there are a total of 3 output device-related zone lists that can be programmed in *81 menu
mode; when the selected EVENT (alarm, fault or trouble) occurs in any zone in the selected “Start”
ZONE LIST (1, 2, or 3), activation of the selected device will START.
Start by Zone Type or System Operation
If a system operation, such as “DISARMING” or “ANY FIRE ALARM,” is to activate the device, the
appropriate choice would also be entered under the “ZONE TYPE” option. “ZONE TYPE” is used
independently of the “EVENT/ZONE LIST” combination.
If a "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault will cause
the device to activate as selected in "ACTION.” If the same “ZONE TYPE” is also chosen for the STOP
programming, any zone of that type that restores will de-activate the device.
If a "SYSTEM OPERATION" is chosen (e.g., End of Exit Time), that operation will cause the device to
activate as selected in "ACTION.” The different choices for "ZONE TYPE" and "SYSTEM
OPERATION" are listed in the “Start zone type” paragraphs later in this section, and in the Programming
Form.
–28–
*80 Device Programming Menu Mode
The "STOP" programming determines when and under what conditions the device will be de-activated. The
following options are available:
STOP
Upon Restore of a Zone List
Restore Zone List: If a "ZONE LIST" is used as the “Stop” event, the device will de-activate when all the
zones in that list restore from a previous fault, trouble, or alarm condition. This will occur regardless of
what is programmed to "START" the device; therefore, a "RESTORE ZONE LIST" would normally only
be used when a "ZONE LIST" is used to start the device.
Upon a Zone Type or System Operation
Zone Type/System Operation: Instead of using a "RESTORE ZONE LIST," a specific zone (response) type
or system operation action can be selected to de-activate the device.
If a specific "ZONE TYPE" is chosen, any zone of that response type that restores from a previous alarm,
trouble, or fault condition will cause the device to de-activate.
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to de-activate.
During normal system operation, any devices may be manually started by keypad entry of: Code* + [#] + 4 + “n;” or
manually stopped by keypad entry of: Code* + [#] + 7 + “n,” where “n” = the device number to be controlled.
* Code is required for devices 7 and 8. For devices 1-6, code is not required. See User Manual for more information.
Programming Powerline Carrier Devices
While in program mode, press *80 to enter Output Device Menu Mode. This mode is used to program all output devices
used in the system. Refer to the output device table for *80 on the separate programming form when programming output
devices.
Note: The House ID of the Powerline Carrier Devices must be entered in data field *25.
The prompts for *80 are as follows:
80
Powerline Carrier Device Programming Main Menu prompt
A 01
Device Number ------------------------ for entering the device number
b
Device Action-------------------------- for defining the action the device will perform when active
C
Start Event Type----------------------- for assigning the event type to start the action
d
Start Zone List ------------------------- for assigning the zone list to start the action
E
Start Zone Type ----------------------- for assigning the zone type to start the action
F
Stop Zone List ------------------------- for assigning the zone list to stop the action
1A
Stop Zone Type------------------------ for assigning the zone type to stop the action
–29–
*80 Device Programming Menu Mode
The following explains these prompts in detail. The left two columns identify the prompts and list the available entries. The
right-most column provides a further explanation of the entries.
Note: Entering a number other than one specified will give unpredictable results.
Powerline Carrier Device programming
0 = exit mode
1 = enter mode
Entering “1” advances to the next prompt below.
Entering “0” exits mode, upon which this prompt blinks, indicating the
mode is inactive.
%
Device number
Enter device numbers as 2-digit entries.
b
-
Device action
aa
0 = No response
1 = Close for 2 seconds
2 = Close and Stay Closed
3 = Continuous Pulse on & off (1 sec ON, 1 sec
OFF)
[*] = continue
[#] = return to previous prompt
Start event type
'
et
d
zl
)
01-08 = device number to be programmed
[*] = continue
00 = exit Device Programming mode
0 = Not used
1 = Alarm
2 = Fault
3 = Trouble
[*] = continue
[#] = return to previous
prompt
Start zone list
1-3 = zone list number (to be programmed in
field *81)
0 = zone list not used for this device
[*] = continue
[#] = return to previous prompt
Start zone type
zt
01-58 = zone type to start this device action
(select only those that are applicable)
00 = zone type not used for this device
[*] = continue
[#] = return to previous prompt
Enter the 1-digit action (0-3) for the device being programmed (current
action is displayed).
NOTES:
1. If “3” is entered (pulse), only up to 3 different devices can be
pulsed if one of the devices is a siren/horn (X-10 Powerhouse
Security model SH10A). In addition, the siren/horn cannot be
manually activated using the lights on/lights off keypad commands.
2. If using an X-10 Powerhouse Security SH10A siren:
• you must use device action “3.”
• you must change the device action default to “3” if using default
table 2 or 4
Enter the 1-digit event type (0-3) to activate the device being
programmed. A zone list must be used in conjunction with an event. If a
zone type/system operation is to be used instead of an event, enter “0”.
If a zone list will be used to start the device action, enter the zone list
number at this prompt.
If a zone type or system operation will be used to start the device action,
enter the appropriate 2-digit code for the device being programmed (see
table that follows).
Choices for zone types
00 = Not Used
01 = Entry/Exit #1
02 = Entry/Exit #2
03 = Perimeter
04 = Interior Follower
08 = 24 Hr Aux
05 = Trouble Day/Alarm Night 09 = Fire
06 = 24 Hr Silent
10 = Interior w/Delay
07 = 24 Hr Audible
24 = Silent Burglary
Choices for system operation
20 = Arming–Stay
33 = Any Alarm (except zt 08)
21 = Arming–Away
36 = At Bell Timeout**
22 = Disarm. (Code + OFF) 38 = Chime
31 = End of Exit Time
39 = Any Fire Alarm
32 = Start of Entry Time
40 = Bypassing
** Or at Disarming (which ever occurs earlier)
*
-%
Stop zone list
zl
1-3 = zone list to stop this device action
0 = zone list not used
[*] = continue
[#] = return to previous prompt
Stop zone type
zt
01-58 = zone type to start this device action
(select only those that are applicable)
00 = zone type not used for this device
[*] = continue
[#] = return to previous prompt
42 = Sys. Batt. Low
43 = Comm. Failure
52 = Kissoff
58 = Duress
If a zone list will be used to STOP, or restore, the device action, enter
the zone list number 1, 2, or 3 (to be programmed in *81 mode). If not
used, enter “0”.
If a zone type or system operation will be used to STOP the device
action, enter the appropriate 2-digit code (see the "ZT" choices listed
above). If not, enter 00.
The display then returns to the DEVICE NUMBER prompt (A) so that
you can enter the next device number to be programmed, or enter [0][0]
to end device programming.
–30–
*81 Zone List Menu Mode
While in Program mode, press *81 to enter Zone List Menu Mode. This mode is used to program zone lists for output
devices (programmed in *80 menu mode) or Chime-by-Zone in Zone List 3.
NOTES:
• Any list may include any or all of the systems zone numbers.
• A zone list can be assigned to more than one Powerline Carrier Device.
The prompts for *81 are as follows:
81
Zone List Programming -------------- Main Menu prompt
A 01
Zone List Number--------------------- for entering the zone list number to be programmed
b
Zone Entry to List --------------------- for entering zones to the assigned zone list
C
Delete Entire List? -------------------- for deleting the entire zone list and its contents
d
Delete Specific Zones From List? -- Selects whether to delete zones or return to next zone list number
E
Delete Zones --------------------------- for deleting specific zones from the current zone list
The following explains these prompts in detail. The left two columns identify the prompts and list the available
entries. The right-most column provides a further explanation of the entries.
Notes: (1) Entering a number other than one specified will give unpredictable results.
(2) Do not assign zones with zone types 20, 21 or 22 to a zone list.
%
b
-
Zone list programming
-
Zone list number
Pressing 1 advances to the next prompt below.
Pressing 0 exits mode, upon which this prompt blinks, indicating the mode
is inactive.
0 = exit mode
1 = enter mode
01-03 = zone list number to be programmed
00 = exit Zone List mode
[*] = continue
Zone entry to list
zz
01-41, 95, 96, 99 = zone numbers to add to
zone list
[*] = accept zone number and enter the next
zone number
00 = accept zone number(s) and continue to
next prompt
'
Delete entire zone list?
d
Delete zones from list?
)
Delete zones
0 = don’t delete; continue to next prompt
1 = delete the current zone list
1 = continue to delete zones prompt
0 = don’t delete; continue to next zone list
number prompt (A….01)
[#] = return to zone list number prompt (A….01)
Enter each 2-digit zone number to be deleted
from the current zone list, followed by the [*]
key.
[*] = delete zone and enter next zone to be
deleted
00 = delete zone and return to next zone list
number prompt (A….01) desired
–31–
Enter the Zone List Number 01, 02, or 03 to program (or 00 if no zone lists
are used).
Enter each zone number to add to the zone list by first entering the zone
number, then the [*] key (for example, 01* 02* 03*). The system will
announce the Voice Descriptor for the selected zone, if it is programmed.
After all desired zones are enrolled, enter “00” to advance.
To delete the zone list, enter “1”. All zones in the zone list will be deleted
automatically and programming will return to the ZONE LIST NUMBER
prompt.
To save the zone list or delete specific zones from the list, enter “0”.
To save the entire zone list, enter “0” and programming will return to the
ZONE LIST NUMBER prompt.
To delete a zone or zones in a zone list enter “1”.
When deleting a zone(s) from the zone list, if the selected zone has a Voice
Descriptor programmed, upon deletion it will be announced as a
confirmation that it has been deleted. After all zones to be deleted are
entered, enter “00” to return to the ZONE LIST NUMBER prompt so that
another list can be programmed, if desired.
*83 Enhanced Sequential Mode
By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain all other existing
data that has been programmed for that zone. Note that the *83 Enhanced Sequential mode requires that all zone information
must first be entered using the *56 Enhanced Zone Programming mode for all zones below zone number 26 (4 button key
area).
Note: Any zone which already has a serial number learned in will not be accessible in *83 Enhanced Sequential mode!
Certain button-type transmitters have more than one button (e.g., 5804). Note that each button must be assigned to a different
zone. Similarly, the 5816 Transmitter has contact terminals and a reed switch for use with a magnet. If using both, each must
also be assigned to a different zone.
This means that the procedures that follow must be repeated for each button-type zone below zone number 26 or contact on
the transmitter. Four zone button-type devices are held in zones 26 and above. They will be started on boundaries of zones
26, 30, 34, and 38. These four zone button-type devices will have the option to have all information entered in this field. One
entry will set the loop number, report code, zone type, and input device type for all 4 buttons, and a second entry will enter
one serial number into four zones.
Note: Use this mode only after all other zone information has been programmed, including transmitter loop numbers except for
button-type zones over zone number 26. The panel will stop at zones 26, 30, 34 and 38 and zone data can be entered as a
default here.
Enter Serial Number Sequential mode by pressing *83. The prompts for *83 are as follows:
A 01
Zone Number ------------------------------------ for entering the zone number to be programmed
1A
Enroll Mode-------------------------------------- Selects method of serial number or viewing
1b
Enroll Serial Number--------------------------- for entering transmitter serial numbers
F
Delete Serial Number -------------------------- for deleting existing serial numbers
The following explains these prompts in detail. The left two columns identify the prompts and list the available entries. The
right-most column provides a further explanation of the entries.
Notes: (1) Entry of a number other than one specified will give unpredictable results.
(2) In Enhanced Sequential Mode, 4 button type keys will always be enrolled simultaneously. They will be stopped at the 4
button boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zone of the key has a
serial number enrolled, the remaining keys cannot be programmed in sequential mode. In addition, if the zone has not
been set up (duplicate loop, missing zone type, etc.) only entries 0 (skip to the next zone) and 4 (copy the key template)
will be allowed.
(3) You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to
clearly hear feedback announcements or system beeps.
%
-
Zone number
Enter the 2-digit zone number.
[*] = continue; system searches for zones not
yet entered (for zones 2 through 25 a zone
type must be entered), then advances to
ENROLL SERIAL NUMBER prompt “1b”
00 = exit Sequential mode
Enter the 2-digit zone number of the first transmitter to have its serial
number entered. The system will announce the Voice Descriptor for the
selected zone number, if it is programmed.
Press [*] to continue. Starting with this zone number, the system will
search for the first transmitter that has all of the following attributes preprogrammed in *56 ENHANCED ZONE PROGRAMMING:
a) Make sure that the appropriate input type was selected in *56 (RF,
UR, or BR programmed)
b) Make sure that the appropriate loop number was selected in *56.
c) No serial number programmed
d) Zone type
If the first zone number entered does not have one or more of the above
attributes, the system will search its database for the first zone that does,
and will display it at the enroll SERIAL NUMBER prompt (1b).
Pressing 00 exits mode, upon which the prompt “83” blinks, indicating
the mode is inactive.
Note: Two exceptions to the requirement above exist for keys. Four zone
button type devices (zone numbers 26, 30, 34, and 38) will be stopped
only if there are no serial numbers enrolled in all 4 zones of the key,
regardless of the attributes that have been entered. In addition, zone
types are not required to be present. In this case, 1A, Option 4 must be
selected prior to “Learn”.
–32–
*83 Enhanced Sequential Mode
-% zz
-%
Enroll mode
0 = advance to next zone to be enrolled
1 = enter now and proceed to SERIAL NUMBER
prompt (1b).
For 4 button keys (zones 26-29, 30-33, 34-37, &
38-41) the serial number will be enrolled to all four
buttons.
If enrolling a key, the panel will emit a long beep
when entering a 1 to indicate that the present key
set up is invalid.
Notes: 1. A valid template or key has 4 existing
zones, each with a zone type, unique loop
number.
2. If the display automatically advances to
"1A" rather than "1b" the configuration of
the key is not valid. At that point copy
template, skip, or return are the only
legal entries.
2 = copy the previous serial number entry from
the buffer.
Notes: 1. Before you can copy a serial number you
must first enter a serial number. If no
serial is stored in the buffer and a copy is
attempted the panel will emit a long beep
indicating an invalid operation.
2. Not applicable for 4 button key zones 2629, 30-33, 34-37, & 38-41.
3 = view existing serial number.
Note:
Only if “L” is displayed. If the “L” is not
displayed the panel will emit a long beep.
4 = copy the 4 button key template that has been
set in zone numbers 26-29 (all zone parameters except serial numbers). (Only valid on
zones 30-33, 34-37, & 38-41 that do not have
serial numbers enrolled.)
Notes: 1. Template acceptance is indicated by two
beeps after copying.
2. A single long beep emitted when copying
a indicates the template is not valid.
9 = delete existing serial. Go to the (1A) prompt.
For 4-button key, zones 26-29, 30-33, 34-37,
& 38-41 have serial numbers. Delete all four
at one time.
Note:
Only if “L” is displayed. If the “L” is not
displayed the panel will emit a long beep.
[*] = advance to next zone to be enrolled
[#] = return to previous prompt (A)
–33–
Note: If “L” is displayed, the serial number for this transmitter has already
been entered, however, it may still be confirmed, viewed or deleted.
If the transmitter’s serial number has not been previously entered, you
may enter the enroll serial number mode (1A) by entering “1”, or copy
the last serial number that was entered by entering “2”.
If the transmitter’s serial number has been previously entered, you may,
view the present serial number by entering “3”. If view is selected each
digit will be re-displayed, and the keypad will beep once for digits 1-6,
and three times for the last digit. Once the serial number has been entered
by either selecting a “1” or a “2”, you will return to this prompt with the
“L” on the display. The serial number/loop number combination that was
entered can be confirmed by getting two transmissions (fault and restore)
from the RF or UR device or one transmission from the BR device. If a
transmission is received that matches the serial number and loop number
entered, the system will announce the Voice Descriptor for the loop
followed by three beeps, and a “C” will be displayed indicating that the
received serial number and loop number transmission has been
confirmed to match. No further transmissions will be received. When
confirming a 4 button key, only the serial number is confirmed, since it
assumed that all loops are used. Pressing any key will allow a
confirmation.
*Long beep indicates illegal entries, or duplicate serial number/loop entry*
When the last zone has been entered, the display will remain on that zone.
To exit this mode and return to data field program mode, press 00 at the
ZONE NUMBER prompt.
When all zones have been programmed, test each zone using the system’s
Test mode. Do not use the Transmitter ID Sniffer mode for this, since it
will only check for transmission of one zone on a particular transmitter,
and not the zones assigned to each additional loop.
For Zones 26-29, 30-33, 34-37, and 38-41 any loop can be used for RF
enrollment. If enrolling via RF, it will be confirmed without additional
transmissions.
*83 Enhanced Sequential Mode
-b
-b
Serial number
zz
Enter transmitter’s 7- digit serial number via RF
learning or manually.
[#] = return to (1A) prompt and reject whatever
serial number entries have been made.
[*] = return to (1A) prompt (if a valid serial
number has been enrolled, “L” is displayed
and the serial number will be copied into
EEROM and the last serial entered buffer.
Note: For zones 26, 30, 34 and 38 only BR type
devices can be used.
This prompt can be used to enroll the transmitter serial number via
RF transmission or manually. If using the RF Learning Mode there is
no need to manually enter a serial number. Proceed directly to RF
Learning. Upon entering the Serial Number mode, the Zone
Descriptors will be announced.
Note: BR type devices can be enrolled only by transmission from BR
devices. Likewise, UR and RF devices can only be enrolled by
transmission from a UR or RF device
RF Learning - Two (2) transmissions (2 key depressions) at least
five seconds apart, will be required for BR type or four (4)
transmissions (fault, restore and fault, restore) for UR or RF type. If
the learned serial number has a different loop number than that
entered in *56 the system will announce the Voice Descriptor, if it is
programmed, followed by two beeps and will return to Prompt (1A)
and “L” will be displayed.
If the loop number captured by RF transmission and that entered in
*56 mode match, the system will announce the Voice Descriptor, if it
is programmed, followed by three beeps and return to Prompt (1A)
and “LC” will be displayed. No additional transmissions are needed
for confirmation.
Manual Entry - Enter the 7-digit serial number printed on the
transmitter. If you enter an incorrect digit, press the [#] key to backup
to prompt (1A) and start over. When all 7 digits are entered, press the
[*] key. If less than 7 digits are entered, the keypad will emit a single
long beep and return to the (1A) prompt without displaying the “L”.
If more than 7 digits have been entered, the first 6 digits will be saved
along with the last digit that was entered (entering 123456789 yields
the serial number 1234569).
Note: If 52 seconds pass and no entry has been made, the system returns
to prompt (1A).
*
Delete serial number
This function deletes only the serial number.
0 = discard the delete request
1 = confirm requested delete
Entering a “9” at prompt (1A). Confirmation of the delete request will
cause deletion of the serial number pertaining to the zone being
programmed.
Note: Entering a “9” at prompt (1A) will cause the
panel to return to prompt (1A) regardless of
the confirmation answer.
Note:
In Enhanced Sequential Learn Mode, 4 button type keys will always be learned simultaneously. They will be stopped at the 4 button
boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zone of the key has a serial number learned, the
remaining keys cannot be programmed in sequential learn mode. In addition, if the zone has not been set up (duplicate loop, missing zone
type, etc.) only entries 0 (skip to the next zone) and 4 (copy the key template) will be allowed.
–34–
*84 Assign Zone Voice Descriptors
Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when the system
announces any event involving a zone number. Each descriptor can consist of up to 3 words. Press *84 while in
Programming mode.
The prompts for *84 are as follows:
84
Voice Descriptors-------------------- Main Menu prompt
A 01
Zone Number ------------------------- for entering the zone number to be programmed
b
Descriptor 1--------------------------- for assigning the first word of this zone’s descriptor
C
Descriptor 2--------------------------- for assigning the second word of this zone’s descriptor
d
Descriptor 3--------------------------- for assigning the third word of this zone’s descriptor
The following explains these prompts in detail. The left two columns identify the prompts and list the available
entries. The right-most column provides a further explanation of the entries.
Note: Entering a number other than the one specified will give unpredictable results.
%
b
'
d
Pressing 1 advances to the next prompt below.
Pressing 0 exits mode, upon which this prompt blinks, indicating the
mode is inactive.
Assign zone voice descriptors
0 = exit mode
1 = enter mode
Zone number
zz
[*] = continue to next prompt (any existing
descriptors will be announced, then
descriptor 1 will be repeated)
00 = exit voice descriptor mode
Descriptor 1
vv
Enter [#] + 2-digit vocabulary index number of
first descriptor word for this zone.
6 = accept word and advance to descriptor 2
(descriptor 2 will be announced)
8 = accept word and advance to prompt (A) for
next zone. Press any other key to repeat the
selected word.
Descriptor 2
vv
vv
Enter [#] + 2-digit vocabulary index number of
second descriptor word for this zone.
6 = accept word and advance to descriptor 3
(descriptor 3 will be announced)
8 = accept word and advance to prompt (A) for
next zone. Press any other key to repeat the
selected word.
Descriptor 3
Enter [#] + 2-digit vocabulary index number of
third descriptor word for this zone.
6 or 8 = accept word and advance to prompt
(A) for next zone. Zone descriptor will
be announced. Press any other key to
repeat the selected word.
–35–
Enter the 2-digit zone number for which this descriptor is being
assigned, then press [*]. The Voice Descriptor for the selected zone will
be announced, if it is programmed.
Enter the first word of the descriptor for the selected zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply
press [#] + desired 2-digit vocabulary index number.
If descriptor 1 is not desired, enter [#] + 99 (blank), then press [8] to
return to zone number prompt.
Enter the second word of the descriptor for the selected zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply
press [#] + desired 2-digit vocabulary index number.
If descriptor 2 is not desired, enter [#] + 99 (blank), then press [8] to
return to zone number prompt.
Enter the last word of the descriptor for the selected zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply
press [#] + desired 2-digit vocabulary index number.
If descriptor 3 is not desired, enter [#] + 99 (blank), then press [8] to
return to zone number prompt.
*84 Assign Zone Voice Descriptor
s
VOICE VOCABULARY INDEX
00 ½ second pause
A
01 ALARM
02 ATTIC
03
04
05
06
07
B
BABY
BACK
BASEMENT
BATHROOM
BEDROOM
C
08 CHECK
09
10
11
12
D
DEN
DETECTOR
DINING
DOOR
E
13 EMERGENCY
F
14 FIRE
15 FLOOR
16 FRONT
G
17 GARAGE
18 GUN
P
30 PATIO
31 POOL
45 1ST
46 2ND
47 3RD
H
19 HALL
R
32 ROOM
70
71
72
73
74
I
20 INSIDE
K
21 KITCHEN
L
22 LAUNDRY
23 LIBRARY
24 LIVING
25
26
27
28
M
MAIN
MASTER
MESSAGE
MOTION
O
29 OFFICE
33
34
35
36
37
38
39
S
SHED
SHOP
SIDE
SLIDING
SMOKE
STORAGE
SYSTEM
Custom Word #1
Custom Word #2
Custom Word #3
Custom Word #4
Custom Word #5
99 Blank (for erasing
a previously
programmed
word)
SYSTEM WORDS
AC LOSS
ARMED
AWAY
BYPASSED
CHIME
DISARMED
DISARM SYSTEM
NOW
EXIT NOW
FAULT
INSTANT
LOW BATTERY
NOT
READY TO ARM
STAY
U
40 UPSTAIRS
41 UTILITY
W
42 WINDOW
Y
43 YARD
Z
44 ZONES
Note: If button type device is used to Arm Away, Arm Stay, and disarm the system it is recommended to assign
“Check” and “Zones” voice descriptors to each of the three zones. This will allow the system to announce
“Check Zones” “Low Battery” if the button device has a low battery.
–36–
*85 Record Custom Voice Descriptors
Use this mode to record up to 5 custom voice descriptors. Press *85 while in Programming mode.
Note: Entering a number other than one specified will give unpredictable results.
%
d
0 = exit mode
1 = enter mode
Entering “1” advances to the next prompt below.
Entering “0” exits mode, upon which this prompt blinks, indicating the
mode is inactive.
Custom descriptor number
Record up to 5 custom words.
Assign custom voice descriptors
Enter 7 + d + [*] where d = 0-4, each
representing custom word 70, 71, 72, 73, or 74,
respectively. Any existing word will be
announced.
Press [#] to start recorder. Start speaking
immediately after the third beep.
Speak the desired word clearly near the
microphone. Recording stops after 1.5
seconds.
6 = accept word and ready to record next
descriptor prompt (A….7d)
[#] = re-record descriptor
00 = exit Record mode after pressing 6 to
accept word
Press any key to repeat the recorded word.
–37–
Remote Programming/Control (Downloading)
General Information
The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), a HAYES Modem, and
ADEMCO's Compass Downloader for Windows (as specified below).
8/
Downloading may only be performed if a technician is at the site.
Multiple security levels protect remote programming against compromise by attempts to defeat the system.
1. Security Code Handshake: An 8-digit download ID code must be matched between the Control and downloader.
2. Site-Initiated Remote Programming: The installer or subscriber initiates the call from the subscriber premises (by
entering Installer Code + # + 1) while disarmed. All parameters can then be downloaded via the phone lines using a
personal computer.
3. Station-Initiated Remote Programming: The operator calls the site from your office to initiate the download call. The
Control hangs up and then calls back the PC via the preprogrammed telephone number. The unit can then be uploaded,
downloaded, or controlled from your office.
4. Telco Handoff: The installer or subscriber performs a download session on the call initiated from the site or from local
laptop computer (by entering Installer or Master Code + # + 1 at the control panel).
5. Data Encryption: Data passed between the PC and the Control is encrypted for security so that it is very difficult for a
foreign device tapped into the phone line to take over communication and substitute system-compromising information.
Equipment required to download to a system at the premises
• An IBM PC compatible computer and appropriate interconnecting cables.
• Either a HAYES brand SMARTMODEM 1200 (Level 1.2 or higher external or Level 1.1 or higher [with 4 position DIP
switch] internal style), a HAYES brand Optima 336 external, a HAYES brand Optima 24 Plus FAX96, or an Ademco
CIA Modem.
• Compass Downloader for Windows (at revision level supporting ReadyGuard-REN).
Initial Download: Enter Installer Code + # + 5. This sets field *95 to 4 rings, and system to “no call-back” option. The
download computer can then call the subscriber, make connection, and download all programming data.
Flexible Callback: If enabled in field *93, the download operator can temporarily change the last 1, 2, or 3 digits (depending
on selection) of the call back number. This allows the control to call back a computer other than the one programmed, which
may be helpful at times of high computer traffic. See field *93 for a full description.
Remote Programming Information
The downloading system can perform many functions when in communication with the Control. Besides uploading and
downloading, the status of the system can be observed and various commands can be initiated, as follows:
• Arm the system in the away mode; disarm the system.
• Bypass a zone.
• Force the system to accept a new program download.
• Shut down communication (dialer) functions (for nonpayment of monitoring fees in an owned system).
• Shut down all security system functions (for nonpayment for a leased system).
• Inhibit local keypad programming (prevents account takeover).
• Command the system to upload a copy of its resident program to the office.
• Set the time
• View/Modify
• X-10/ Scheduling
• Read: arming status, AC power status, lists of faulted zones, bypassed zones, zones currently in alarm, zones currently in
trouble, and rf sensors with low battery conditions; read control’s time.
Notes: (1) After the control and the PC have established valid communication, the keypad will become inactive and will
display "CC."
(2) The keypad will become active after the download communication is terminated.
(3) The detailed operation of the download functions is covered in the installation instructions for the Compass
Downloader for Windows.
–38–
Remote Programming/Control (Downloading)
Remote Programming Advisory Notes
• Keypad entries are ignored during the time interval stated above.
• A copy of the program downloaded may be printed using the IBM PC-compatible computer’s internal report
generator, when an optional printer is connected (consult your PC manual for proper printer and connections).
• Program upload or download time is approximately one minute, fifteen seconds for a complete program.
–39–
System Operation
Security Codes
Installer Code
The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer
Code is 4-1-1-2, but may be changed in field *20.
The Installer Code is the only code that can enter Programming mode and also, in normal operation mode, is used to enter the
Master Code, which allows access to the normal functions of the system.
Master Code
In normal operation mode, the Installer Code is used to enter the 4-digit Master Security Code.
To enter/change the Master code by installer, using the keypad enter:
Installer Code + [CODE key] + [02] + desired 4-digit Master Code
To change the Master code by master, using the keypad enter:
Current Master Code + [CODE key] + [02] + new Master Code + new Master Code again
Secondary User Codes
In normal operation mode, the Master Security Code can be used to assign up to 6 secondary 4-digit security codes, including
a Babysitter Code and a Duress Code. The Master Code can also be used to remove secondary codes from the system
(individually).
To assign (or change) a secondary security code, using the keypad enter:
Master Code + [CODE key] + User # (03–08) + desired Secondary Code
The system will emit a single beep when each secondary code has been successfully entered.
To delete a secondary security code, using the keypad enter:
Master Code + [CODE key] + User # (03–08)
•
•
•
•
•
•
Security Code Notes
The Master and Secondary security codes permit access to the system for arming, disarming, etc.
The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer Code cannot disarm the
system if it was armed by pressing and holding a Quick-Arm button.
The Babysitter Code (User Code No. 7) can disarm the system only if it was used to arm it. In addition, the Babysitter
Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
Duress code (User Code No. 8) sends a special code to the monitoring station when used to perform any system
operation.. Instruct users to be careful not to use this code for normal usage.
If a secondary code is inadvertently repeated for different users, the lower user number will take priority.
Opening/closing reports are sent for the Installer Code as No. 01, with the appropriate subscriber number. Master Code
and set of secondary user codes are sent as Nos. 02 and 03–08, respectively, in Contact ID® format (with the appropriate
user number); in 4+2, it is 1–8. Quick arming (and open/close executed by downloader) is reported as user 00.
Panic Keys
There are three panic key pairs that, if programmed, can be used to manually initiate alarms and send a report to the central
station.
Each can be individually programmed for 24-hour silent, audible, personal or fire emergency responses. The panic function is
activated when both keys of the appropriate key pair are pressed at the same time.
The panic functions are identified by the system as follows:
Keys
Displayed as Zone
[1] & [*]
95
[*] & [#]
99
[3] & [#]
96
Important: For the silent panic functions to
be of practical value, the system must be
connected to a central station.
–40–
System Operation
Keypad Functions
The keypad allows the user to arm and disarm the system, and perform other system functions, such as bypassing zones.
Zone and system conditions (alarm, trouble, bypass) are displayed in the display window. When an alarm occurs, keypad
sounding and external sounding will occur, and the zone(s) in alarm will be displayed on the keypad. Pressing any key will
silence the keypad sounder for 10 seconds (only once). Disarming the system will silence both keypad and external sounders.
When the system is disarmed, any zones that were in an alarm condition during the armed period will be displayed (memory
of alarm). To clear this display, simply repeat the disarm sequence (enter the security code and press the OFF key). The
keypad also features chime annunciation, and 3 panic key pairs for silent, audible, fire or personal emergency alarms. These
keys can notify the central station of an alarm condition, if that service is connected. A summary of system functions is
provided below for more detailed information refer to the User's Manual.
Security Functions (Empty boxes represent the user’s security code)
Checking system status: STATUS (high level messages); press
To arm in STAY mode:
+
STAY
STATUS
again for secondary messages
(or installer code + [3])
To restart exit delay:
(applies only if system is armed in Stay
STAY
mode)
To arm in AWAY mode:
+
AWAY
To arm with NO DELAY:
+
AWAY
To arm if Quick Arm is programmed:
AWAY
or
(or installer code + [2])
or
+
+
To turn Chime mode on or off:
BYPASS
+
FUNCTION
To play back a message:
FUNCTION
+
CHIME
NOTE
If a 5827 Wireless keypad has FUNCTION
been installed,
it cannot be used to
+ RECORD
activate message playback/recording, programming the real time clock or
scheduling remotely. In this case, you must use the master keypad on the
control panel to perform these functions.
OFF
PLAY
Volume Control
To adjust message playback/system announcement volume:
To mute system announcements:
+
FUNCTION
To set the scheduling:
+
FUNCTION
FUNCTION
To activate or deactivate X-10 devices 1-6:
FUNCTION
VOLUME
*+
+
LIGHTS ON
*+
+
TEST
To turn Test mode off:
+
OFF
To use the defined AUX function: Press and hold
To define AUX function:
+
+
+ [3] or [6]
or
LIGHTS OFF
FUNCTION
AUX
FUNCTION
CODE
AUX
LIGHTS ON
or
LIGHTS OFF
+ dev. no.
+ user number (* master code)
key 2 secs (4 beeps) +
+
AUX
+ action separated by +
AUX
To send message to pager: Press and hold
+
+ device number
+ user number + user’s code (*master code)
To delete a user code (except Master Code):
To turn Test mode on:
+ [3] or [6]
+ [64]
+
CODE
VOLUME
+ [63]
To activate or deactivate X-10 devices 7 & 8:
To add a user code:
+
OFF
+
FUNCTION
+
FUNCTION
+
VOLUME
To restore/unmute announcement & volume:
Other Functions
To set the time and date:
OFF
+ 2-digit zone number(s)
Message Center
To record a message:
To stop recording before end of 20 seconds:
NO DELAY
(hold down for at least 2 seconds)
STAY
To disarm the system and silence alarms:
To bypass a zone(s):
+
STAY
key 2 seconds (4 beeps)
–41–
AUX
terminated by +
AUX
System Operation
Speaker Phone Operation (ReadyGuard-REN Only)
To place a call or answer a call using the speaker phone: [#] +
To flash (switch between two calls using call waiting):
To hang up and exit speaker phone mode:
To enable/disable (toggle) ringer: [#] +
NOTE
The ARMED and READY LEDs blink alternately
when the Speaker Phone is active.
AUX
AUX
OFF
VOLUME
+
AUX
To return the keypad to telephone mode after disarming the system: [#] +
AUX
Remote Phone Control Feature
The remote phone control feature, which must be enabled in field *91, allows the user to access the security system from any
off-site touch-tone telephone. The control will pick up the incoming call, based on the ring count specified in field *95, and
will announce “SYTEM” every three (3) seconds for the next eight (8) seconds. During this period the panel will wait for a
valid User Code to be entered. If a valid User Code is not entered or the eight (8) second period expires a modem tone will be
generated for remote programming (Compass Downloading). If a valid User Code has been entered, the control will
announce the current system status and/or beeping sounds.
Keypad Functions
Remote Phone Control Feature
To remotely disarm system:
Quick Arm Note
The installer code and
babysitter code cannot
disarm the system if
armed by Quick Arm
method.
+ [1]
+ [2]
To remotely arm in AWAY mode:
+ [3]
To remotely arm in STAY mode:
+ [2] or [3] + [0]
To remotely arm in AWAY or STAY with no delay:
To remotely activate X-10 devices 1-6: [#] + [4] + device no.
To remotely activate X-10 devices 7 & 8:
+ [#] + [4] + device no.
To remotely deactivate X-10 devices 1-6: [#] + [7] + device no.
To remotely deactivate X-10 devices 7 & 8:
+ [#] + [7] + device no.
To remotely Bypass zones:
+ [6] + zone no.
To remotely activate Forced Bypass:
To remotely check system status: [*]
To end remote phone control session: Hang Up or
+ [6] + [#]
+ [9]
–42–
System Operation
8/
Alarm audio verification cannot be used for UL installations.
Alarm Audio Verification (Two-Way Voice Feature)
This feature allows the central station operator to listen, talk to or conduct a two-way conversation with an individual(s) at
the premises. It also assists the operator in gathering information about the nature and location of the alarm that may be
helpful in responding to police and fire departments. All ReadyGuard-R Series control panels are capable of supporting the
Two-Way Voice feature, however only the ReadyGuard-REN has this feature built in. The ReadyGuard-R requires the
installation of the Audio Verification Module (LYNX-AVM). For further information regarding the ReadyGuard-R Two
Way Voice Feature refer to the LYNX-AVM Installation and Setup Guide. The ReadyGuard-REN does not make system
announcements when the Two-Way voice feature is active.
Activation
The ReadyGuard-REN sends the "alarm message" followed by a "Listen-in-to-Follow message" (Contact ID code 606) to the
Central Station. The Listen-in-to-Follow message causes the Central Station's digital receiver to temporarily hold the phone
line for approximately 1-minute. When the ReadyGuard-REN receives the "kissoff" from the central station, indicating that
the alarm message has been received, the Two-Way Voice (AVM) feature is activated in the (default) “Listen Mode” and
sirens and keypad sounds are discontinued. The ReadyGuard-REN transmits a beep acknowledgment to the Central Station,
once per second. The beep alternates between two tones and indicates that the ReadyGuard-REN is waiting for a session
command from the Central Station operator. Once a command is issued the beep acknowledgement is discontinued,
however, if a command is not issued within two minutes the system will “time out” and the call will be terminated.
Operator Commands
The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AVM commands shown in
the table below. The session may be extended 5 minutes, without changing the operating mode, by pressing the [7] key on the
touch-tone phone. Selecting another operating mode also resets the session an additional 5 minutes. During the last minute
of the 5 minute, session, the ReadyGuard-REN generates two beeps every 30 seconds to alert the Central Station operator
that the session is about to time out. The Central Station operator may then extend the session by pressing the [7] key on the
touch-tone phone. If the session is not extended the phone line is disconnected, and the session is ended. Sessions may be
ended at any time by pressing the [9] key on the touch-tone phone. The AVM modes are described as follows:
Note: When entering AVM commands make sure the Central Station receiver has been disconnected from the phone line,
otherwise AVM commands may not go through.
Key
1
Function
Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication from the central station to the
violated premises, and allows the operator to talk communicate through the ReadyGuard-REN speaker. In this mode the
ARMED (red) and READY (green) LEDs blink alternately.
2
VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice communications between the central
station and the violated premises. In this mode the ARMED (red) and READY (green) LEDs blink alternately.
3
Listen Mode: Pressing the [3] key on the touch-tone phone, enables one-way audio from the violated premises to the central
station. The Listen Mode is the start up default mode of the voice feature and allows the operator to listen through the ReadyGuardREN microphone. This mode does not affect the existing LED pattern.
7
Extends the session 5 minutes without changing its operating mode.
9
Ends the session and disconnects the phone line.
–43–
System Operation
Powerline Carrier Devices (e.g. X-10 devices)
If Powerline Carrier Devices are used, two keypad entries available to the user are included. They can manually activate or
deactivate the device(s) for starting or stopping some action, such as turning lights on or off, etc.
These keypad entries are:
Security Code* + [#] + [4] + Device # activates (starts) that device.
Security Code* + [#] + [7] + Device # de-activates (stops) that device.
* Code is required for devices 7 and 8. Code is not required for devices 1-6.
Exit Error Alarm Displays
If programmed:
• A display of "CA" and a zone indication will appear if an exit or interior zone contained a fault during closing at the
time the exit delay ended (e.g., exit door left open), but the system was disarmed during the entry delay time. The
alarm sounder and keypad sound continuously, but stop when the system is disarmed. No message will be transmitted to
the central station.
• A display of "EA" and a zone indication will appear if an exit or interior zone contained a fault during closing at the
time the exit delay ended, but the system was NOT disarmed during the entry delay time. The alarm sounder and
keypad sound continuously until the system is disarmed (or timeout occurs). An Exit Alarm message is sent to the central
station.
• The "EA" display, etc. will also result if an alarm from an exit or interior zone occurs within two minutes after the end of
an exit delay.
In any of the above cases, use a second OFF sequence (code plus OFF key) to clear the display.
Trouble Conditions
The word "FAULT" on the keypad's display, accompanied by a rapid "beeping" at the keypad, indicates that there is a trouble
condition in the system. Pressing any key can silence the audible warning sound. Instruct users to call for service
immediately upon seeing any of the following messages.
"Fault" and "Battery" Displays
• A display of "FAULT" and one or more zone numbers indicates that a problem exists with the displayed zone(s) and
requires attention.
After correcting the problem, the display can be cleared by entering the security code plus the OFF key twice.
• The fault condition may also be caused by some change in the environment that prevents the built-in receiver from
receiving signals from a particular wireless sensor.
• A display of "LOW BAT" with no zone number indicates that the system's backup battery is weak.
• A display of "LOW BAT" with a zone number and a once-per-45 seconds "beeping" at the keypad indicates that a
low battery condition exists in the wireless sensor displayed (zone "00" indicates a wireless button/keypad). If the battery is
not replaced within 30 days, a “FAULT” display may occur.
Power Failure
• If there is no display at all, and both indicators are not lit, operating power for the system has stopped and the system is
inoperative.
• If the display is lit and the AC display is off, the system is operating on battery power only.
• During an AC power loss, the backlighting will turn off and the indicators will flicker slightly to minimize deep discharge
of the battery.
Other Displays
dI = Busy-Standby: Displayed upon power-up. After approximately 1 minute* the green “READY” LED should light. If
the “dI” remains displayed for more than 1 minute, the system is disabled.
* To bypass the 1-minute delay, press [#] + [0]. Important: Do not try to bypass 1 minute delay before “dI” is displayed!
CC = Modem Comm: The system is communicating with the central station for change of function or status verification.
FC = Comm. Failure: A communication failure has occurred. This message clears only when the system is subsequently
armed.
90 = RF Jam: The system has detected an RF jamming condition or excessive interference.
PH = Speaker Phone Mode: The system is in Speaker Phone mode.
PC = Phone Control: The remote Phone Control feature is active.
–44–
Testing the System
Test Mode
After installation is completed, the security system should be carefully tested, as follows.
1.
2.
3.
With the system in the disarmed state, check that all zones are intact. If the READY LED is not lit, press the
[*] key to display the faulted zone(s). Restore faulted zone(s) if necessary, so that READY LED lights. Fault
and restore every sensor individually to assure that it is being monitored by the system.
Enter the security code and press the TEST key. The outside sounder will sound for 1 second and all the LED
segments on the keypad display light for 3 seconds. LYNX announces the zone’s voice descriptor (if
programmed) followed by 3 beeps, each time a contact is faulted. A test report should be transmitted (if
programmed) to the central station immediately. If the backup battery is discharged or missing, the sounder
may not turn on and a LOW BATTERY report will be transmitted with a TEST report. The keypad will beep
once every 45 seconds as a reminder that the system is in the Test mode.
To turn off the Test mode enter security code and press the OFF key.
Notes: (1) Triggering a zone set to Arm AWAY, Arm STAY, or Disarm will take the system out of Test and cause that action.
(2) BR type transmitters do not display during Test mode (keypad beeps only)
(3) Macros cannot be run from the Test mode.
Armed System Test
Alarm messages will be sent to the central station during the following tests 1 and 2. Notify them in advance
that tests will be in progress.
1.
Arm the system and fault one or more zones. After 15 seconds (if optional dialer delay is selected), silence
alarm sounder(s) by entering the code and pressing OFF. Check entry/exit delay zones.
2.
Check the keypad-initiated alarms that are in the system by pressing the Panic key pairs. If the system has been
programmed for audible emergency, the keypad will emit a steady alarm sound, and “ALARM” and zone
number will be displayed. Silence the alarm by entering the security code and pressing OFF.
If the system has been programmed for silent emergency, there will be no audible alarms or displays, but a
report will be sent to the central station.
3.
If Powerline Carrier Devices have been installed, test their programmed action.
4.
Notify the central station when all tests are finished, and verify results with them.
5.
To test the wireless part of the system and the RF receiver, perform the two additional tests described in the
Installing Wireless Zones section: Sniffer mode and Go/No Go Test.
Note:
System Test mode (installer/master code + test) and Go/No Go Test (installer code + # + 8) will be
automatically terminated after 3-1/2 to 4 hours if the installer or user does not manually terminate it.
This ensures that fire and panic zones will not remain disabled. However, Sniffer mode (installer code
+ # + 3) does not automatically expire. You must manually exit (Installer/User Code + OFF)
Sniffer mode to return to normal operation.
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are
vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program
to the user as well as acquainting the user with the proper operation and limitations of the alarm system
and its component parts. Recommendations must be included for a specific program of frequent testing (at
least weekly) to ensure the system's proper operation at all times.
–45–
System Communication
This section provides an explanation of formats this system accommodates for reporting alarms and other system
conditions to the central station. The process of a successful transmission consists of both the method of
communication between the control panel and the central station receiver, and the actual way the information is sent
and displayed at the central station.
Communication Overview
When the panel calls the central station receiver, it waits to hear a “handshake” frequency from the receiver to
confirm that the receiver is on-line and ready to receive its message. Once the panel hears the handshake it is
programmed to listen for, it sends its message. The panel then waits for a “kissoff” frequency from the receiver
acknowledging that the message was received and understood.
If the handshake frequency is not given or is not understood by the panel, the panel will not send its message. Once
the handshake frequency is received and understood by the panel, the panel will send its message. If there is an
error in the transmission (the receiver does not receive a “valid” message), the kissoff frequency will not be given by
the central station receiver.
The panel will make eight attempts to the primary telephone number and eight attempts to the secondary telephone
number (if programmed) to get a valid message through. If the panel is not successful after its numerous attempts,
the keypad will display “FC.” If the secondary number is a pager, “FC” displays after the first 8 attempts to the
primary number.
The following chart defines the three sets of (handshake/kissoff) frequencies that the panel supports, and the different
formats that can be sent for each.
FORMAT
Low Speed
3+1
4+1
4+2
Sescoa/Rad
3+1
4+1
4+2
Express
4+2
Contact ID®
HANDSHAKE
1400Hz
TRANSMITS DATA
1900Hz (10PPS)
(Standard report)
KISSOFF
1400Hz
TRANSMIT TIME
Under 15 seconds
2300Hz
1900Hz (20PPS)
(Standard report)
2300Hz
Under 10 seconds
1400–2300Hz
DTMF (10 cps)
1400Hz
Under 3 seconds
1400–2300Hz
DTMF (10 cps)
1400Hz
Under 3 seconds
Report Code Formats
3+1 and 4+1 Standard Formats
3+1 and 4+1 Expanded Formats
4+2 Format
ADEMCO Contact ID®
Reporting Format
Comprise a 3- (or 4-) digit subscriber number and a single digit report
code (e.g. alarm, trouble, restore, open, close, etc).
Comprise a 3- (or 4-) digit subscriber number, and a 2-digit report code.
The first digit is displayed on the first line, followed by a second line
where the first digit is repeated 3 (or 4) times and followed by the
second digit. This is the “expanded” digit.
Comprises a 4-digit subscriber number and 2-digit report code.
Comprises a 4-digit subscriber number, 1-digit event qualifier
("new" or "restore"), 3-digit event code, and 3-digit zone number, user
number, or system status number (see the following page).
The following table shows the message formats for 3+1, 4+1 and 4+2 reports, where:
SSS or SSSS
A
Z
Tt
Bb
=
=
=
=
=
Subscriber ID
Alarm Code (1st digit)
Typically Zone Number* (2nd digit)
Trouble Code (1st & 2nd digits)
Bypass Code (1st & 2nd digits)
C
U
Gg
R
RTt
E A C = AC Loss Code (1st & 2nd digits)
L L B = Low Battery Code (1st & 2nd digits)
=
=
=
=
=
Close Code (1st Digit)
User Number (in hex)
Test Code (1st & 2nd digits)
Alarm Restore Code
Trouble Restore Code (1st & 2nd digits)
R B b = Bypass Restore Code (1st & 2nd digits)
R A A C = AC Restore Code (1st & 2nd digits)
O = Open Code (1st Digit)
R L L B = Battery Restore Code (1st & 2nd digits)
*Zone numbers for: [*] & [#], or [B] = 99; [1] + [*], or [A] = 95; [3] + [#], or [C] = 96; Duress = 92
–46–
System Communication
3+1/4+1 Expanded
SSS(S) A
AAA(A) Z
SSS(S) T
TTT(T) t
SSS(S) B
BBB(B) b
SSS(S) E
EEE(E) AC
4+2
SSSS AZ
Report
Alarm
3+1/4+1 Standard
SSS(S) A
Trouble
SSS(S) T
Bypass
SSS(S) B
AC Loss
SSS(S) E
Low Battery
SSS(S) L
SSS(S) L
LLL(L) LB
SSSS LLB
Open
SSS(S) O
SSSS OU
Close
SSS(S) C
Test
SSS(S) G
Restore Alarm
SSS(S) R
AC Restore
SSS(S) RA
SSS(S) O
OOO(O) U
SSS(S) C
CCC(C) U
SSS(S) G
GGG(G)g
SSS(S) R
RRR(R) Z
SSS(S) RA
SSSS Tt
SSSS Bb
SSSS EAC
SSSS CU
SSSS Gg
SSSS RZ
SSSSRA Ac
RARARA(RA)Ac
Low Battery Restore
SSS(S) RL
SSS(S) RL
SSSS RLLB
RLRLRL(RL)LB
Trouble Restore
SSS(S) RT
SSS(S) RT
RTRTRT (RT)t
SSSS RTt
Bypass Restore
SSS(S) RB
SSS(S) RB
RBRBRB (RB)b
SSSS RBb
ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where:
CCCC = Customer (subscriber) ID
Q=
Event qualifier, where: E = new event, and R = restore
EEE = Event code (3 hex digits) (for a complete list of event codes, refer to the central office receiver manual)
GG = Always “00”
ZZZ = Zone/Contact ID number reporting the alarm, or user number for open/close reports. System status
messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.
Code
110
121
122
123
131
132
134
135
146
150
301
302
344
373
374
380
381
383
Definition
CONTACT ID® EVENT CODES
Code
Fire Alarm
Duress
Alarm, 24-hour Silent
Alarm, 24-hour Audible
Alarm, Perimeter
Alarm, Interior
Alarm, Entry/Exit
Alarm, Day/Night
Silent Burglary
Alarm, 24-Hour Auxiliary
AC Power
Low System Battery/Battery Test Fail
RF Jam Detected
Fire Loop Trouble
Exit Error Alarm
Global Trouble, Trouble Day/Night
RF Supervision Trouble
RF Sensor Tamper
384
401
403
406
407
408
441
570
602
606
607
623
Definition
RF Sensor Low Battery
Disarmed, Armed AWAY (NO DELAY),
Armed AWAY
Scheduled Auto Arm
Cancel by User
Remote Arm/Disarm (Downloading)
Quick Arm AWAY/NO DELAY
Disarmed/Armed STAY/NO DELAY, Quick Arm
STAY/NO DELAY
Bypass
Periodic Test
AAV to follow
System Test
Event Log 80% Full
NOTE: The following codes are logged in the event log upon
occurrence, but are not reported:
305 = System Reset
627 = Keypad Program Mode Entry
–47–
Troubleshooting Guide
SYSTEM (including Wireless)
SYMPTOM
1.
2.
Transmitter signal not
received at control.
Transmitter zone number
appears during
Transmitter Sniffer mode,
but does not clear.
POSSIBLE CAUSE
1a.
Transmitter not properly powered.
REMEDY
1a
Check or change transmitter's battery.
1b. If Transmitter is 5827, House Code not set in
field *24, or transmitter is not set to same
House Code set in that field.
1b. Check code switches inside transmitter. Must
match with RF House Code programmed.
1c.
1c.
Transmitter is located too far from RF receiver.
Move transmitter or RF receiver.
1d. There is metal shielding between transmitter
and RF receiver.
1d. Check for large metal obstructions, then
relocate transmitter if necessary.
1e.
Transmitter is malfunctioning.
1e.
1f.
Transmitter No. (zone) is not programmed.
2a.
Transmitter zone type (ZT) is set to 00 (Not
Used).
Verify by activating control with another,
similar transmitter. If O.K. now, return
defective transmitter.
1f.
Verify programming.
2a.
Set ZT to a valid active zone type in field *56.
2b. Transmitter battery not installed.
2b. Install proper battery.
2c.
5800 System transmitter not "entered" in
system.
2c.
"Enter" unit in field *56 or *83.
Low battery message on
keypad.
3a. "Low Bat" (no zone Nos.)
3a.
System battery is low or missing.
3a.
Replace system battery.
3b. "Low Bat" + "00".
3b. Remote RF keypad/button battery is low.
3b. Replace battery in the RF keypad.
3c.
"Low Bat" + "nn".
3c.
Transmitter for zone “nn” has a low battery.
3c.
Replace the battery in the displayed
transmitter.
4.
Periodic beep(s) from
keypad.
4a.
System is in Test mode.
4a.
Enter Code + OFF to exit Test mode.
3.
4b. A transmitter low battery has occurred and is
displayed.
4b. Enter Code + OFF and replace the battery.
4c.
4c.
A supervision fault has occurred.
4d. System low battery
Check the transmitter indicated. Restore
communication to the receiver to cancel the
condition.
4d. Replace system battery
5.
6.
7.
With 5800 System, there is
no response to a
transmitter in normal
operation, although zone
number clears during
Transmitter Sniffer mode.
Nuisance or phantom
alarm.
Intrusion alarm for no
apparent reason.
Put control in Test mode. If zone does not respond,
try operating the tamper switch or another input to
the transmitter.
5a.
If another input causes the zone to be displayed,
the wrong input was "entered" when
programming.
5a.
Delete input's serial number (not the zone),
and enter the proper input (see field *56).
5b. If no response at all from this transmitter, this
physical transmitter has not been entered by the
system. Transmitter Sniffer display is being
cleared by another unit programmed for this
zone.
5b. Determine which transmitter is programmed
for this zone and reprogram as necessary.
6a.
6a.
Sensors not properly installed, wired, or
monitored.
Check installation to see if in accordance with
established procedure.
6b. Universal transmitter (5817) programmed
wrong.
6b. Check programming switches on transmitter.
7a.
7a.
Protected door or window opened while system
armed.
Check with all occupants of protected home.
7b. Improper user operation of exit/entry delays.
7b. Check setting of entry and exit delays.
7c.
7c.
Magnets located too far from switches, and/or
doors and windows not properly aligned.
–48–
Check all openings for proper switch and
magnet orientation.
Troubleshooting Guide
CONTROL
SYMPTOM
1.
2.
POSSIBLE CAUSE
1a.
The word “AC” is not
displayed.
Digital communicator message
not being received.
REMEDY
Interrupted AC power supply.
1a.
Check transformer connection and
powerline circuit breaker.
2a. Remove from Test mode.
2b. Check all connections.
2c. Check with a different CONTROL
PANEL.
2d. Program prefix or access code into the
CONTROL PANEL.
2e. System cannot work in this situation.
2a. System in Test mode.
2b. Telephone connection not secure.
2c. Digital communicator malfunctioning.
2d. Telephone number in program needs prefix
or access code.
2e. Telephone call to central monitoring station
requires operator assistance.
3.
Does not arm properly.
READY light not on.
4.
Open or faulted zone(s)
Check for faulted zones and make intact, or use
Bypass arming, if desired.
System is in communication with
downloader at central station.
4a.
System doesn't respond to
keystrokes on keypad.
4a.
4a.
"CC" displayed.
4b. System has just been powered and is in its
one minute initialization.
4b. "d1" displayed.
Wait until download session is finished.
4b. Wait for initialization to finish, or bypass
this time by pressing '#' + '0.'
SMOKE DETECTOR
SYMPTOM
1. Detector alarms, no apparent
reason.
POSSIBLE CAUSE
1a.
Dust, dirt in sensing chamber.
1b. Improper location.
2.
Detector's siren sounds.
1c.
Unit malfunctioning.
2a.
Unit not receiving required power.
2b. Unit malfunctioning.
–49–
REMEDY
1a.
Clean unit's sensing chamber
with vacuum cleaner per
unit's instructions.
1b. See unit's instructions for
locations to avoid. Relocate
as necessary.
1c. Replace detector.
2a. Check for proper installation
of battery. Try new battery.
2b. Replace detector.
Contacting Technical Support
PLEASE, before you call Technical Support, be sure you:
• READ THE INSTRUCTIONS!
• Check all wiring connections.
• Determine that the power supply and/or backup battery are supplying proper voltages.
• Verify your programming information where applicable.
• Note the proper model number of this product, and the version level (if known) along with any documentation
that came with the product.
• Note your First Alert Professional customer number and/or company name.
Having this information handy will make it easier for us to serve you quickly and effectively.
You may contact Technical Support via Toll Free Fax. Please include your return fax number. You will receive a reply within
24 hours. You may also contact Technical Support via modem to ATLIS-BBS, Tech Support's Electronic Bulletin Board
System. Replies are posted within 24 hours.
Technical Support: .............................................................................................................1-800-538-5585 (8 a.m.-8 p.m. E.S.T.)
Technical Support Fax Number: .........................................................................................1-800-447-5086
ATLIS-BB Electronic Bulletin Board System: .....................................................................1-516-496-3980
(1200 - 9600 Baud, 8 Data Bits, 1 Start/Stop Bit, No Parity)
ATLIS-FAX FAXBACK Automated Fax Retrieval System:...................................................1-800-573-0153 or 1-516-921-6704 / ext. 1667
World Wide Web Address: ...................................................................................................http:// firstalertpro.com
–50–
Regulatory Agency Statements
UL NOTICE: This is a "Grade A" residential system.
FCC ID: CFS8DLLYNXREN
RADIO FREQUENCY EMISSIONS
Federal Communications Commission (FCC) Part 15
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Industry Canada
This Class B digital apparatus complies with Canadian ICES-003.
Cet Appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
TELEPHONE/MODEM INTERFACE
Federal Communications Commission (FCC) Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration number
and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This
equipment is hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications
network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements
document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications
company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with
the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user
to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water
pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or
electrician, as appropriate.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed
to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the
requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
–51–
Specifications
ReadyGuard-R Series
Security
Controls
1. Physical: 10-3/8” W x 7-1/8” H x 1-3/4” D
2. Electrical:
VOLTAGE INPUT: 9VAC from plug-in 15VA transformer.
RECHARGEABLE BACKUP BATTERY: Six 1.2-volt/cell nickel-metal hydride rated at
1100 mA.
ALARM SOUNDER: Piezo = 6-14VDC, 30mA max/ Bell = 6-14VDC, 120mA max (e.g.,
ADEMCO’s WAVE2EX).
LONG RANGE RADIO: Rated 12mA@12-volt nominal (negative trigger signal).
3. Communication:
FORMATS SUPPORTED:
ADEMCO Express, 10 characters/sec, DTMF (TouchTone) Data Tones, 1400/2300Hz
ACK, 1400Hz KISSOFF.
ADEMCO Contact ID® Reporting, 10 characters/sec., DTMF (TouchTone) Data Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
ADEMCO Low Speed, 10 pulses/sec, 1900Hz Data Tone,
1400Hz ACK/KISSOFF.
Radionics/SESCOA, 20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF. Can
report 0–9, B–F.
Line Seize: Double Pole
Ringer Equivalence: 0.6B
FCC Registration No.: 5GBUSA-25623-AL-E
4. Maximum Zone 1 Resistance: 300 ohms, excluding 2k ohm EOLR
–52–
ReadyGuard-R PROGRAMMING DEFAULT TABLES
Function
(boldface indicates defaults that differ between tables)
Table 1
Table 3
Table 4
Table 2
*20
Installer code
*21
Quick arm enable
*22
Keypad backlight timeout
*23
Forced bypass
*24
RF house ID code
*25
Powerline carrier device house code
*26
Chime-by-zone
*27
Real-time clock display
*29
Daylight saving time start/end month
*30 Daylight saving time start/end weekend
*31 Single alarm sounding per zone
*32
Fire sounder timeout
*33
Alarm bell timeout
*34
Exit delay
*35
Entry delay 1 (zone type 01)
*36
Entry delay 2 (zone type 02)
*37
Audible exit warning/quick exit
*38
Confirmation of arming ding
*39
Power up in previous state
*40
PABX access code
*41
Primary phone number
*42
Secondary phone number
*43
Primary subscriber account number
*44
Secondary subscriber account number
*47
Phone system select
*48
Report format
*49
Split/dual reporting
*50
15 second dialer delay (burglary)
*51
Periodic test report
*52
First test report offset
*53
Sescoa/radionics select
*56
Enhanced Zone programming
*58
RF jam detection
*59
Exit error report code
*60
Trouble report code
*61
Bypass report code
*62
AC loss report code
*63
Low battery Report code
*64
Test report code
*65
Open report code
*66
Arm away/stay report code
*67
RF transmitter low battery report code
*68
Cancel report code
*70
Alarm restore codes
*71
Trouble restore report code
*72
Bypass restore report code
*73
AC restore report code
*74
Low battery restore report code
*75
RF transmitter low battery restore report code
*76
Test restore report code
*80
Powerline Carrier Devices
*81
Zone lists for devices
*84
Assign zone voice descriptors
*87
Auxiliary Function/ 1-button paging
*88
Pager characters
*89
Event log 80% full report code
*90
Event logging
*91
LRR/AAV Trigger/Remote Phone Control
*92
Number of reports in armed period
*93
Flexible call back
*94
Download phone number
*95
Ring detect count for downloading/remote phone control
Default Master Code
Default Duress Code
By activating *96, Field 43, and 44 will be changed to 15, 15, 15, 15.
4112
1
0
0
0,0
0
0
1
4,10
1,5
0
0
1
7,0
3,0
6,0
1,1
0
1
------15,15,15,15
--1
7,0
0
0
0
2
0
See *56 table
0
1
1,0
0,0
0,0
1,0
1,0
0
0,0
1,0
1,0
1
1,0
0,0
0,0
1,0
1,0
0,0
See *80 table
See *81 table
– 53 –
4112
1
0
0
0,0
0
0
1
4,10
1,5
0
0
1
7,0
3,0
6,0
1,1
0
1
------15,15,15,15
--1
7,0
0
0
0
2
0
See *56 table
0
1
1,0
0,0
0,0
1,0
1,0
0
0,0
1,0
1,0
1
1,0
0,0
0,0
1,0
1,0
0,0
See *80 table
See *81 table
Programming
0
--0,0
4112
1
0
0
0,0
0
0
1
4,10
1,5
0
0
1
7,0
3,0
6,0
1,1
0
1
------15,15,15,15
--1
7,7
9
0
0
2
0
See *56 table
0
1
1,0
0,0
0,0
1,0
1,0
0
0,0
1,0
1,0
1
1,0
0,0
0,0
1,0
1,0
0,0
See *80 table
See *81 table
0
--0,0
6321
1
0
0
0,0
0
0
1
4,10
1,5
0
0
1
6,0
4,5
6,0
0,1
0
1
------15,15,15,15
--1
7,7
0
1
3
2
0
See *56 table
0
0
1,0
0,0
0,0
1,0
1,0
0
0,0
1,0
1,0
1
1,0
0,0
0,0
1,0
1,0
1,0
See *80 table
See *81 table
Refer to *84
1
--0,0
3
15
3
3
2
0
0
--15
1,2,3,4
---
2
0
0
--15
1,2,3,4
2,5,8,0
2
0
0
--15
1,2,3,4
---
2
0
0
--15
1,2,3,4
---
1
--0,0
ReadyGuard-REN PROGRAMMING DEFAULT TABLES
(boldface indicates defaults that differ between tables)
Function
Table 1
*20
Installer code
*21
Quick arm enable
*22
Keypad backlight timeout
*23
Forced bypass
*24
RF house ID code
*25
Powerline carrier device house code
*26
Chime-by-zone
*27
Real-time clock display
*29
Daylight saving time start/end month
*30 Daylight saving time start/end weekend
*31 Single alarm sounding per zone
*32
Fire sounder timeout
*33
Alarm bell timeout
*34
Exit delay
*35
Entry delay 1 (zone type 01)
*36
Entry delay 2 (zone type 02)
*37
Audible exit warning/quick exit
*38
Confirmation of arming ding
*39
Power up in previous state
*40
PABX access code
*41
Primary phone number
*42
Secondary phone number
*43
Primary subscriber account number
*44
Secondary subscriber account number
*47
Phone system select
*48
Report format
*49
Split/dual reporting
*50
15 second dialer delay (burglary)
*51
Periodic test report
*52
First test report offset
*53
Sescoa/radionics select
*56
Enhanced Zone programming
*58
RF jam detection
*59
Exit error report code
*60
Trouble report code
*61
Bypass report code
*62
AC loss report code
*63
Low battery Report code
*64
Test report code
*65
Open report code
*66
Arm away/stay report code
*67
RF transmitter low battery report code
*68
Cancel report code
*70
Alarm restore codes
*71
Trouble restore report code
*72
Bypass restore report code
*73
AC restore report code
*74
Low battery restore report code
*75
RF transmitter low battery restore report code
*76
Test restore report code
*80
Powerline Carrier Devices
*81
Zone lists for devices
*84
Assign zone voice descriptors
*87
Auxiliary Function/ 1-button paging
*88
Pager characters
*89
Event log 80% full report code
*90
Event logging
*91
Alarm audio verification/remote phone control
*92
Number of reports in armed period
*93
Flexible call back
*94
Download phone number
*95
Ring detect count for downloading/remote phone control
Default Master Code
Default Duress Code
By activating *96, Field 43, and 44 will be changed to 15, 15, 15, 15.
4112
1
0
0
0,0
0
0
1
4,10
1,5
0
0
1
7,0
3,0
6,0
1,1
0
1
------15,15,15,15
--5
7,0
0
0
0
2
0
See *56 table
0
1
1,0
0,0
0,0
1,0
1,0
0
0,0
1,0
1,0
1
1,0
0,0
0,0
1,0
1,0
0,0
See *80 table
See *81 table
– 54 –
0
--0,0
Table 2
Table 3
6321
4112
1
1
0
0
0
0
0,0
0,0
0
0
0
0
1
1
4,10
4,10
1,5
1,5
0
0
0
0
1
1
6,0
7,0
4,5
3,0
6,0
6,0
0,1
1,1
0
0
1
1
------------15,15,15,15
15,15,15,15
----5
5
7,7
7,0
0
0
1
0
3
0
2
2
0
0
See *56 table See *56 table
0
0
0
1
1,0
1,0
0,0
0,0
0,0
0,0
1,0
1,0
1,0
1,0
0
0
0,0
0,0
1,0
1,0
1,0
1,0
1
1
1,0
1,0
0,0
0,0
0,0
0,0
1,0
1,0
1,0
1,0
1,0
0,0
See *80 table
--See *81 table See *81 table
Refer to *84 Programming
1
0
----0,0
0,0
Table 4
4112
1
0
0
0,0
0
0
1
4,10
1,5
0
0
1
7,0
3,0
6,0
1,1
0
1
------15,15,15,15
--5
7,7
9
0
0
2
0
See *56 table
0
1
1,0
0,0
0,0
1,0
1,0
0
0,0
1,0
1,0
1
1,0
0,0
0,0
1,0
1,0
0,0
See *80 table
See *81 table
1
--0,0
3
15
3
3
2
0
0
--15
1,2,3,4
---
2
0
0
--15
1,2,3,4
2,5,8,0
2
0
0
--15
1,2,3,4
---
2
0
0
--15
1,2,3,4
---
*56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLE 1
Zone No. Zone Type Alarm Code
Input Type
Loop Number
Zone Descriptor
1
0
0,0
----2
1
1,0
3 (RF)
2
16,12 (FRONT DOOR)
3
1
1,0
3 (RF)
2
04,12 (BACK DOOR)
4
3
1,0
3 (RF)
2
42 (WINDOW)
5
10
1,0
3 (RF)
1
28,10 (MOTION DETECTOR)
26
21
1,0
5 (BR)
3
27
22
1,0
5 (BR)
2
28
20
1,0
5 (BR)
4
29
23
0,0
5 (BR)
1
30
21
1,0
5 (BR)
3
31
22
1,0
5 (BR)
2
32
20
1,0
5 (BR)
4
33
23
0,0
5 (BR)
1
92
--1,0
----99
6
1,0
----NOTE: Zone 1 is a hardwire zone; Zone 2 to 41 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic
*56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLE 2
Zone No.
Zone Type
Alarm Code
Input Type
Loop Number
1
2
3
4
5
6
26
27
28
29
30
31
32
33
92
95
96
99
0
1
1
1
04
9
21
22
20
23
21
22
20
23
--08
09
07
0,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
0,0
1,0
1,0
1,0
0,0
1,0
1,0
1,0
1,0
--3 (RF)
3 (RF)
3 (RF)
3 (RF)
3 (RF)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
---------
--2
2
2
1
1
3
2
4
1
3
2
4
1
---------
Zone Descriptor
16,12 (FRONT DOOR)
04,12 (BACK DOOR)
17, 12 (GARAGE DOOR))
28,10 (MOTION DETECTOR)
37,10 (SMOKE DETECTOR)
NOTE: Zone 1 is a hardwire zone; Zone 2 to 41 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic
*56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLES 3 & 4
Zone No.
Zone Type
Alarm Code
Input Type
Loop Number
1
2
3
4
5
6
7
8
9
26
27
28
29
30
31
32
33
92
99
0
1
1
3
3
3
3
10
9
21
22
23
23
21
22
23
23
--6
0,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
0,0
0,0
1,0
1,0
0,0
0,0
1,0
1,0
--3 (RF)
3 (RF)
3 (RF)
3 (RF)
3 (RF)
3 (RF)
3 (RF)
3 (RF)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
5 (BR)
-----
--2
2
2
2
2
2
1
1
3
2
4
1
3
2
4
1
-----
Zone Descriptor
16,12 (FRONT DOOR)
04,12 (BACK DOOR)
42 (WINDOW)
42 (WINDOW)
42 (WINDOW)
42 (WINDOW)
28,10 (MOTION DETECTOR)
37,10 (SMOKE DETECTOR)
NOTE: Zone 1 is a hardwire zone; Zone 2 to 41 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic
– 55 –
*80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 4 (devices 2-7 have no default values)
Start
Device Number
Action
Event
Zone List
1
8**
2
2
2
1
Stop
Zone Type
System Operation
Restore of
Zone List
Zone type
System operation
2
33
36
** NOTE: If using an X-10 Powerhouse Security SH10A siren as device 8, you must change the device action default to “3” if using default table 4.
*80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 1 and 2 (devices 2-7 have no default values)
Start
Device Number
Action
8**
2
Event
Zone List
Stop
Zone Type
System Operation
Restore of
Zone List
33
*81 ZONE LIST FOR OUTPUT DEVICES DEFAULT TABLE: Applies To Default Table 1 - 4.
Zone List 1 28, 32
Zone List 2 29, 33
Zone List 3 2, 3
– 56 –
Zone type
System operation
36
– Index –
*56 Enhanced Zone Programming Mode
...................... 11, 14, 20, 23, 24, 25, 26
*80 Device Programming Menu Mode
........................................23, 28, 29, 30
*81 Zone List Menu Mode ............... 23, 31
*83 Enhanced Sequential Mode
................ 14, 23, 24, 26, 27, 32, 33, 34
*84 Assign Zone Voice Descriptors . 23, 27,
35, 36
*85 Record Custom Voice Descriptors ........
................................................... 23, 37
*96 Initialize Download ID and Subscriber
Acct. No. for Downloading ................ 23
*97 Set All Program Fields to 1 of 4 Sets of
Default Values .................................. 23
*98 Exits Programming Mode ................ 23
*99 Exits Programming Mode ................ 23
1332 Transformer .................................... 9
15 Second Dialer Delay ...............19, 53, 54
24-Hour Audible Alarm ......................... 16
24-Hour Auxiliary Alarm ....................... 16
24-Hour Silent Alarm ....................... 15, 40
5800 Series Transmitters ........................ 11
5800RL ........................................... 11, 13
5801 ...................................................... 11
5802CP ................................................. 11
5802MN .......................................... 11, 12
5802MN2 .............................................. 12
5804 ...........................................11, 12, 32
5804BD......................................11, 12, 17
5804BDV ...................................11, 12, 17
5804E.............................................. 11, 12
5804WATCH .................................. 11, 12
5816 ...................................................... 32
5827 ...........................................11, 13, 17
A
AC Loss Report Code .................20, 53, 54
AC Power .......................................... 9, 10
AC Restore Report Code .............21, 53, 54
AC, Power Loss ....................................... 9
ADEMCO Contact ID Reporting ............ 19
ADEMCO Express .......................... 19, 52
ADEMCO Low Speed ..................... 19, 52
Alarm Audio Verification (Two-Way Voice
Feature) ............................................ 43
Alarm Audio Verification Trigger/Remote
Phone Control ................................... 22
Alarm Bell Timeout ....................17, 53, 54
Alarm Output........................................... 4
Alarm Restore Codes ....................... 53, 54
Alarm Restore Report Code .................... 21
Alarm Sounder ...................................... 52
Arm Away/Stay Report Code ........... 53, 54
Arm–Away ............................................ 16
Arm–Stay .............................................. 16
Assign Custom Voice Descriptors ........... 37
Assign Zone Voice Descriptors...................
........................................14, 35, 53, 54
B
Babysitter Code ......................................40
Back Plate ................................................5
Backlighting ...........................................17
Backup Battery ...................................9, 10
Backup Reporting ...................................18
Battery Life ............................................12
Battery, Low ..........................................44
Bell ....................................................6, 52
BR ...................................................11, 25
Burglary Zones .......................................17
Busy-Standby .........................................44
Button Transmitters ..........................11, 12
Button Type ...........................................25
Button Zones ..........................................25
Bypass Report Code ...................20, 53, 54
Bypass Restore Report Code .......21, 53, 54
C
CA .........................................................44
Callback Number....................................22
Cancel Report Code .........................53, 54
Canceled Alarm ......................................20
CC .........................................................44
Chime Mode ....................................17, 41
Chime-by-Zone ................................53, 54
Closing Report .......................................18
Comm. Failure .......................................44
Communication ........................................4
Compass Downloader .............................38
Confirmation of Arming Ding ...........53, 54
Contact ID..............................................46
Contact ID Event Codes ..........................47
Contact ID Format ............................20, 40
Contact ID Reporting ........................47, 52
Custom Descriptor Number .....................37
Custom Voice Descriptors.................23, 37
D
Data Field ..............................................14
Daylight Savings Time Start/End.17, 53, 54
Default Master Code .........................53, 54
Default Tables ..................................53, 54
Delete Zone Parameters Confirmation .....34
Delete Zones ..........................................31
Descriptor 1 .....................................27, 35
Descriptor 2 .....................................27, 35
Descriptor 3 .....................................27, 35
Desktop Mounting ....................................5
Device Action ........................................30
Device Number ......................................30
Device Programming ..............................14
dI Display ..............................................44
Disarm .............................................16, 41
Download Call Back Phone Number........23
Download Phone Number .................53, 54
Download, Initial ....................................38
Downloader................................21, 38, 39
Duress Code .....................................40, 55
Audible Exit Warning/Quick Exit 18, 53, 54
AUX Function ....................................... 41
AUX Function/1-Button Paging...21, 53, 54
AUX Key .............................................. 21
Away Mode ........................................... 41
E
EA......................................................... 44
Earth Ground ........................................... 6
Enroll Mode ..................................... 26, 33
Entry Delay ............................... 18, 53, 54
Entry/Exit Burglary ................................ 15
Error Code 374 ...................................... 20
Event Log ................................................ 4
Event Log 80% Full Report Code 21, 53, 54
Event Logging ..................... 21, 22, 53, 54
Exit Alarm ............................................. 20
Exit Delay...................... 17, 18, 41, 53, 54
Exit Door ............................................... 17
Exit Error Alarm Displays ...................... 44
Exit Error Feature..................................... 4
Exit Error Report Code ............... 20, 53, 54
Exit Warning ......................................... 18
Express .................................................. 46
External sounder .................................... 17
F
Factory Defaults ..................................... 14
Fault ...................................................... 44
FC ................................................... 44, 46
Fire Sounder Timeout ................. 17, 53, 54
First Test Report Offset .............. 19, 53, 54
Flexible Callback ................. 22, 38, 53, 54
Forced Bypass...................... 17, 42, 53, 54
Front Assembly Board ........................ 5, 14
G
Go/No Go Test Mode ............................. 12
H
Handshake Frequency............................. 46
Hardwired Zone ....................... 4, 6, 25, 55
Hayes .................................................... 38
House ID ................................... 13, 17, 29
I
Input Type ................................. 11, 25, 55
Installer Code............................. 40, 53, 54
Interactive Mode .................................... 14
Interior W/Delay .................................... 16
Interior, Follower ................................... 15
K
Keypad Backlight Timeout ......... 17, 53, 54
Keypad Functions ............................ 41, 42
Keys ...................................................... 11
Kissoff Frequency .................................. 46
L
Local Sounder Disable.............................. 7
Local Sounder Disable Jumper .................. 6
Long Range Radio/Alarm Audio
Verification TriggerRemote Phone
Control.............................................. 22
Loop Number................................... 25, 55
LOW BAT ............................................. 44
Low Battery Report Code ................. 53, 54
Low Battery Restore Report Code
............................................. 21, 53, 54
Low Speed ............................................. 46
LYNX-DM .............................................. 5
– 57 –
M
Macro Function ......................................21
Master Code ...........................................40
Master Security Code..............................17
Memory of Alarm ...................................41
Message Center ......................................41
Modem Comm .......................................44
Mounting Base .........................................5
Mute System Announcements .................41
O
Open Report Code ............................53, 54
Optima 24 Plus FAX96 Modem. .............38
R
Radionics............................................... 19
Radionics/SESCOA ............................... 52
Range .................................................... 11
Real-Time Clock Display ....... 4, 17, 53, 54
Record A Message ................................. 41
Record Custom Voice Descriptors........... 14
Recording .............................................. 37
Remote Phone Control...................... 23, 42
Remote Programming/Control .......... 38, 39
Report Code ..................................... 20, 25
Report Code Formats.............................. 46
Report Format ............................ 19, 53, 54
Response Time......................................... 6
Restart Exit Delay ............................ 18, 41
RF ......................................................... 25
RF (Supervised RF) ................................ 11
RF House ID Code ..................... 17, 53, 54
RF Transmitter Low Battery Report Code
T
Technical Support .................................. 50
Temporal Pulse ...................................... 17
Test Mode ............................41, 45, 48, 49
Test Report Code ............................. 53, 54
Test Restore Report Code ............21, 53, 54
Testing The System................................ 45
Time And Date ...................................... 41
Transmitter Loop Numbers..................... 13
Trouble by Day/ ..................................... 15
Trouble Conditions ................................ 44
Trouble Report Code ...................20, 53, 54
Trouble Restore Report Code ......21, 53, 54
Troubleshooting Guide ..................... 48, 49
Unsupervised Button Rf ......................... 11
Unsupervised Rf .................................... 11
Ur (Unsupervised Rf) ....................... 11, 25
User Codes ........................................ 4, 41
P
................................................... 53, 54
RF Transmitter Low Battery Restore ...........
V
Voice Descriptor .........................25, 27, 35
Voice Vocabulary Index ......................... 36
Voltage Input ......................................... 52
Volume Control ..................................... 41
N
No Alarm Response ................................16
No Delay................................................41
Number Of Reports in Armed Period ...........
.............................................22, 53, 54
PABX Access Code ....................18, 53, 54
Pager .....................................................19
Pager Characters.........................21, 53, 54
Pager Function .......................................41
Pager Message........................................21
Pager Report Format ...............................19
Paging Feature........................................21
Panic Keys .............................................40
Perimeter Burglary .................................15
Periodic Test Report ...................19, 53, 54
Phone Lines .............................................6
Phone System Select ...................19, 53, 54
Piezo ..................................................6, 52
Play Back a Message ..............................41
Plug-In Transformer .............................6, 9
Power Failure .........................................44
Power Up in Previous State .........18, 53, 54
Powerline Carrier Device ... 4, 6, 17, 28, 29,
44, 53, 54
Powerline Carrier Device House Code ....53,
54
Powerline Carrier Device Programming ...30
Powerline Interface Module ......................6
Primary Phone Number...............18, 53, 54
Primary Subscriber Account Number...........
.............................................18, 53, 54
Program Mode, Entering .........................14
Programming Mode ................................17
Q
Quick Arm .............................................41
Quick Arm Enable ......................17, 53, 54
Quick Exit ..............................................18
............................................. 21, 53, 54
RF Jam .................................................. 20
Ring Detect Count For Downloading...........
............................................. 23, 53, 54
S
Scheduling ....................................... 38, 41
Secondary Phone Number........... 18, 53, 54
Secondary Subscriber Account Number .......
............................................. 18, 53, 54
Secondary User Codes ............................ 40
Security Codes ................................. 17, 40
Security Functions.................................. 41
Serial Number .......... 23, 24, 26, 27, 32, 34
Sescoa/Rad ............................................ 46
Sescoa/Radionics Select ....... 19, 20, 53, 54
SH10A .................................................. 30
Signal Strength....................................... 12
Silent Burglary ....................................... 16
Single Alarm Sounding Per Zone 17, 53, 54
Siren/Horn ............................................. 30
Site-Initiated Remote Programming ........ 38
SMARTMODEM 1200 .......................... 38
Smoke Detectors ................................ 2, 49
Sniffer Mode.............................. 12, 45, 48
Sounders .................................................. 6
Speaker Phone Operation ........................ 42
Specifications......................................... 52
Split/Dual Reporting................... 19, 53, 54
Start By Event ........................................ 28
Start By Zone Type ................................ 28
Start Event Type .................................... 30
Start Zone List ....................................... 30
Start Zone Type ..................................... 30
Station-Initiated Remote Programming .... 38
STAY Mode .......................................... 41
Stop Recording ...................................... 41
Stop Zone List........................................ 30
Stop Zone Type ...................................... 30
Supervised Fire ...................................... 16
Supervised RF.................................. 11, 25
System Battery ....................................... 48
System Communication .................... 46, 47
System Features ....................................... 4
System Operation .......................................
................28, 29, 40, 41, 42, 43, 44, 56
System Words ........................................ 36
– 58 –
W
Wall Mounting ........................................ 5
WAVE2EX ........................................... 52
Wireless Button Zone ............................... 4
Wireless Buttons .................................... 11
Wireless Transmitter .............................. 21
Wireless Zones ...................................... 11
Wiring Connections ............................. 6, 7
World Wide Web Address ...................... 50
X
X-10...........................................28, 38, 44
Z
Zone 1 Resistance .................................. 52
Zone Bypass .......................................... 41
Zone Descriptor ..................................... 55
Zone Entry To List ................................. 31
Zone List ..............................23, 53, 54, 56
Zone List Number .................................. 31
Zone List Programming.................... 14, 31
Zone Number..............................25, 32, 35
Zone Programming .......................... 53, 54
Zone Response Type ........................ 15, 16
Zone Type ....................................... 25, 30
Zones and Devices ................................... 4
WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency.
Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example:
•
Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work without power.
Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices
powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
•
Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path
has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
•
A user may not be able to reach a panic or emergency button quickly enough.
•
While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide
early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency
Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are as follows.
Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke
cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not
sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor or basement
fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general,
detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping
gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending on
the nature of the fire and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient
warning to allow all occupants to escape in time to prevent injury or death.
•
Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual.
Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can
only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls,
ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any
material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense
changes in temperature; however, as the ambient temperature of the protected area approaches the temperature range of 90° to 105°F
(32° to 40°C), the detection performance can decrease.
•
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of
closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less
likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by
noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may
not warn hearing-impaired people.
•
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily
out of service. Telephone lines are also subject to compromise by sophisticated intruders.
•
Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves from
the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
•
This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long
as 20 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system
should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be
tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of
batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External
factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given
installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to
maintain protection for that given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for insurance.
Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and
property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn
about these developments.
– 59 –
ONE YEAR LIMITED WARRANTY
Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its
security equipment (the "product") to be free from defects in materials and workmanship for one year from date of original purchase, under
normal use and service. Seller's obligation is limited to repairing or replacing, at its option, free of charge for parts, labor, or transportation,
any product proven to be defective in materials or workmanship under normal use and service. Seller shall have no obligation under this
warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than the Seller. In case of defect, contact
the security professional who installed and maintains your security equipment or the Seller for product repair.
This one year Limited Warranty is in lieu of all other express warranties, obligations or liabilities. THERE ARE NO EXPRESS
WARRANTIES, WHICH EXTEND BEYOND THE FACE HEREOF. ANY IMPLIED WARRANTIES, OBLIGATIONS OR
LIABILITIES MADE BY SELLER IN CONNECTION WITH THIS PRODUCT, INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A
PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE. ANY ACTION FOR BREACH OF ANY WARRANTY, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY, MUST BE BROUGHT WITHIN 12
MONTHS FROM DATE OF ORIGINAL PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY
CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY
THE SELLER'S OWN NEGLIGENCE OR FAULT. Some states do not allow limitation on how long an implied warranty lasts or the
exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
Seller does not represent that the product may not be compromised or circumvented; that the product will prevent any personal injury or
property loss by burglary, robbery, fire or otherwise; or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm may only reduce the risk of a burglary, robbery, fire or other events occurring
without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property
loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE
OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY
OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE
EXCEED THE PURCHASE PRICE OF THE PRODUCT, WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY
AGAINST SELLER. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. No
increase or alteration, written or verbal, to this warranty is authorized.
– 60 –
RJ11
8
POSITION
JACK
2
1
ZONE
PHONE
3
4
5
6
TIP RING TIP RING (+)
TO HANDSET
PHONE
LINE
SOUNDERS
7
( )
HARD
WIRED
ZONE
INCOMING
PHONE
LINE
PLCD
8
9
10
11
12
( )
(+)
( )
(+)
13
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE
HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING
INTERFERENCE THAT MAY CAUSE UNDESIRED
OPERATION.
THE READYGUARD-R SERIES CONTROLS ARE
EQUIPPED WITH AN INTEGRAL RECHARGEABLE
BATTERY PACK P/N LYNXRCHKIT-SC.
16
NOTE
USE ONLY
1332/1332X10
OR 1332CN
TRANSFORMERS
PROVIDED
INCOMING
TELEPHONE
LINE
EARTH
GROUND
15
DATA SYNC
OUT
IN
LOCAL SOUNDER
DISABLE SHUNT
REMOVE TO DISABLE
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE PROTECTION
ASSOCIATION'S STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOC., BATTERYMARCH PARK,
QUINICY, MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
14
AC
POWERLINE
CARRIER DEVICES
ALL OUTPUT
CIRCUITS
ARE POWER
LIMITED.
EARTH
GROUND
TRIGGER SIGNAL (NEG)
NOTE: Connection of the fire alarm signal to a fire alarm headquarters or a central station shall be permitted
with the approval of the local authority having jurisdiction. The burglar alarm signal shall not be
connected to a police emergency number.
– 61 –
The System must be checked by a qualified technician once every three years.
WARNING:
TO PREVENT
RISK OF
SHOCK
DISCONNECT
TELEPHONE
LINE AT TELECOM
JACK BEFORE
SERVICING
THIS UNIT.
AAV / LRR
TRIGGER
(READYGUARD-R)
LRR
TRIGGER
(READYGUARD-REN)
PREMISES
TELEPHONE
PIEZO
BELL
2k OHMS
EOLR
6-14VDC
30mA max.
WEEKLY TESTING IS
REQUIRED TO ENSURE
PROPER OPERATION
OF THIS SYSTEM
6-14VDC
120mA max.
(e.g. WAVE2EX)
TO 24HR 110VAC
UNSWITCHED
OUTLET
AC
AC
SYNC
COM
DATA
FCC ID: CFS8 DLLYNX (LYNXR/LYNXR24) AND
CFS8DLLYNXREN (LYNXR-EN) COMPLIES WITH
FCC RULES, PART 68 FCC REGISTRATION
No. 5GBUSA-25623-AL-E RINGER EQUIVALENCE: 0.6B
1332/1332X10/1332CN
CONNECTIONS
1332X10 ONLY
CONNECTIONS
PLUG-IN
TRANSFORMER
9VAC, 15VA
FOR UL985 APPLICATIONS INSTALL
P/N LYNXRCHKIT-HC
REPLACE EVERY FOUR YEARS
01100-005-V1
-NOTES-
– 62 –
-NOTES-
– 63 –
i.l
K5963-1 9/01
175 Eileen Way, Syosset, New York 11791
http://firstalertpro.com
Copyright © 2000 PITTWAY CORPORATION
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Page Mode : UseThumbs XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Create Date : 2002:01:18 05:13:41Z Modify Date : 2008:10:01 12:21:55-05:00 Metadata Date : 2008:10:01 12:21:55-05:00 Producer : Acrobat Distiller 4.0 for Windows Format : application/pdf Document ID : uuid:14e18fa6-1bf2-4f9e-9173-bdc34ef2aac7 Instance ID : uuid:a2ac15de-16c5-4ae3-ad18-4d08b06969a2 Page Count : 64 Page Layout : SinglePageEXIF Metadata provided by EXIF.tools