251 A4 SMDC 16 Installation Manual

User Manual: SMDC-16 Installation Manual AlarmHow.net Library

Open the PDF directly: View PDF PDF.
Page Count: 20

SMDC-16SMDC-16
INSTALLATION &
OPERATION MANUAL
SMDC-16 Digital Control Communicator
and
SMPC-32 Personal Control
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
2 of 20
Table of Contents
System Description 3
Hardware
Control Panel Terminal Layout Diagram 4
Wiring Data 5 - 9
RJ-31X Wiring Diagram 9
Expansion Board Data 10
Expansion Board Wiring Diagram 10
Control Panel Hardware 11
Battery Calibration 11
Battery Calculation 12
Keypads
Keypad Function Diagram 13
Keypad Wiring Diagram 14
Keypad Voltmeter 14
PGM Trigger Wiring 15
Underwrites Laboratory
Appendix A 15
Appendix B 16
UL Information Addendum 16
Communication Requirements 17
Grades of Service 17
UL Listings 17
Grade A Local Mercantile Installation Requirements 17
Current Rating Chart 17
Walk Tests 18
Fire Walk Test 18
Walk Test History 18
UL Compliance Verification Chart 19
Compatible 2 Wire Smoke Detectors 19
Compatible 4 Wire Smoke Detectors 19
Program Requirements 19
Optex Inc. Warranty 20
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
3 of 20
General System Description
SMDC
Control
Communicator
Built In
Volt
Meter
11
Outputs
512 Event
History Buffer
99 PINs
80 Zones
Individual
Schedules for each
Partition
Printer
and
Fax
Interface High Speed
Download
Software
Up to
8
Individual
Partitions
14
Different Transmission
Formats
32 Zones
Fully Supervised
Wireless
On Site
Download
W/O Modem
2 On-Board
Supervised Phone
Lines
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
4 of 20
Terminal Layout DiagramTerminal Layout Diagram
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
5 of 20
Wiring Data
Terminals Description
69 Earth Ground Connection
Supervised Earth Ground.
Always connect Earth Ground first.
You must use a minimum of 18AWG wire.
DO NOT connect the Earth Ground to an electrical, telco, or chassis ground.
Keep the Earth Ground wire run length to a minimum.
Always touch Ground before performing any work on the control panel.
1 & 2 AC Power Input
Supervised input.
16.5 VAC, 40VA (Basler Electric Model:BE116240CAA) Class 2 plug in transformer.
Use 18AWG (twisted or zip) wire minimum.
Keep the wire run as short as possible.
Test the electrical outlet to verify that it is unswitched.
17.0 to 17.5VAC across terminals 1 and 2.
For commercial Fire Applications, the transformer needs to be enclosed in UL listed enclosure and conduit
should be used between this enclosure & control panel.
The minimum dimensions for this enclosure should be W4.25” x H5.625” x D2.5”.
3 & 4 Auxiliary Power Output
Terminal 4 is positive and terminal 3 is ground.
For devices that require an interruption of power to perform a reset (Latching outputs), terminals 53 & 54
(Switched Aux. Power) should be used to supply power.
A self resetting PTC protects this output.
5 & 6 Tamper Input
The cabinet door must use a UL listed tamper switch to comply for UL certification.
This input requires a Normally Closed contact.
This input does not require an end of line resistor.
6 & 57 Ground Inputs
Terminals 6 and 57 are Ground (-) inputs and may be used as the return side for powered devices, or for any
device that requires a ground reference.
Do not connect devices to these terminals that require a negative power source that "floats" above ground; i.e., the
return side of a two wire smoke detector or bell input.
7 & 6 Keyswitch Input
Momentary output device only.
Examples of devices that may be used to arm the control panel are:
1. automation systems.
2. wireless radio receiver.
3. light controllers.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
6 of 20
Wiring Data
Terminals Description
8 & 4LED 1 Output (12vdc)
Terminal 8 is the negative and terminal 4 positive power.
The voltage on this output will be present when all zones are in a secure state.
There must be a 1K resistor wired in series with this output to prevent damage to the LED.
9 & 4LED 2 Output (12vdc)
Terminal 9 is the negative and terminal 4 positive power.
The voltage on this output will be present when the control panel is in an armed state and will be pulsating should there have
been an alarm activation while the panel was in an armed state.
There must be a 1K resistor wired in series with this output to prevent damage to the LED.
10 & 3Auxiliary 1 Input
Terminal 10 and 3 (neg.) allows for the control panel partitions to be armed with a momentary type remote arming device.
11 & 3Auxiliary 2 Input
Terminal 11 and 3 (neg.) allows for the control panel partitions to be armed with a momentary type remote arming device.
12 & 4PGM 1 Output
Terminal 12 is a programmable open collector output.
This output provides a negative voltage output that sinks to ground when activated.
Use terminal 4 to provide the positive voltage that is necessary.
This output is capable of providing a maximum of 50mA of current.
Use Altronix RBSN or the Alarm Controls model 8007 relay base with an 8012 relay.
See Chart on page 21 for wiring to relays
13-14-15-16 Data, Clk, PWR, and GND (G-EX zone expander boards)
Terminals 13 OMNET Data (yellow wire)
Terminal 15 OMNET Clock (green wire)
Terminals 14 OMNET Positive voltage (red wire)
Terminal 16 OMNET Ground (black wire)
The maximum distance is 1000 ft. that the expander boards may be remoted
These terminals provide an output voltage of approximately 13.5VDC.
17-18-19-20 Keypad Data and Power
A total of eight (8) keypads can be connected to the system
The voltage available across terminals 19 and 20 is approximately 13.5VDC
A self resetting PTC protects this power output.
The data pair (terminals 17 and 18) must be minimum #22 AWG twisted pair.
The data pair must be terminated with an end-of-line resistor for RFI and EMI rejection, we suggest that keypads be wired in
a daisy chain manner. (see page 13).
150 ohm terminating resistor is installed across the data pair at the last keypad if daisy chain.
A terminating resistor must be placed across the data pair at each keypad if home run.
There is a two position dip switch (S1), located within the rear access window of the keypad.
The dip switch (S1) is used for selecting the keypads unique address.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
7 of 20
Wiring Data
Terminals Description
21 to 44 Zone Inputs 1-16
Quick connect terminal strips.
The common side of each zone floats above ground.
Normally open and/or normally closed, or a combination of both may be installed.
Each zone may be individually programmed for supervision.
2.2K ohm 1/2W (EOL) (color coding red-red-red-gold).
Each zone may also be programmed for various loop response times.
All smoke detectors, heat detectors, water flow switches, pull station must use EOL Resistors
For trouble shooting purposes, the zone input voltages for supervised zones (with EOL) are as follows:
45 & 46 Auxiliary Power
Terminal 45 is positive and terminal 46 is ground.
For devices that require the interruption of power to perform a reset (Latching outputs), terminals 53 & 54
(Switched Aux. Power) should be used to supply power.
A self resetting PTC protects this power output.
47 & 48 Bell 2 Output (Unsupervised)
This Bell output may be steady or pulsating 12VDC on an alarm condition.
A self resetting PTC protects this power output.
49 & 50 Bell 1 Output (Supervised)
This Bell output may be steady or pulsating 12VDC on an alarm condition.
This bell output is supervised and must be terminated with a 2.2k ohm, 1/2W EOL resistor.
A trouble condition will be indicated on a short or open.
A self resetting PTC protects this power output.
The following table indicates the thresholds for the bell supervision:
* This is the point where the bell circuit becomes normal if the circuit was in a trouble condition.
51 & 52 Ext. Bell Pwr Supply Input
These terminals allow for the connection of an external power source.
Power will be delivered to terminals 49 and 50 (supervised bell output) only.
The external power source maybe 12 or 24 VDC @ 5 amps maximum.
Jumper JP9 is used to select the source of bell power:
Removed - external supplied bell power selected (factory default).
Installed - panel supplied power.
Electrical State Voltage Readings
Normal State 1.7 - 3.2 VDC
Open 3.5 - 5.0 VDC
Short 0.0 - 1.5 VDC
Resistance Current Voltage Condition
0 .18 mA 0.0 VDC Normal
2.2K .17 mA 0.4 VDC Normal
29.3K .13 mA 4.0 VDC Normal*
87K .08 mA 7.4 VDC Normal
>87K <.08mA >7.4VDC Trouble
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
8 of 20
Wiring Data
Terminals Description
53 & 54 Switched Auxiliary Power Output
Connect to devices that require an interruption of power to cause the devices to reset.
Examples of latching devices - 4 wire smoke detectors, glass breaks, etc.
A self resetting PTC protects this power output.
55 & 56 2-Wire Smoke Detector Input
This zone input requires a 2.2K ohm EOL resistor placed in parallel at the last smoke detector
The maximum number of smoke detectors that may be installed is 10.
Use the following table to assist in troubleshooting the 2-wire smoke detector circuit.
When reading DC voltage you will need to place your meter probes to terminals 55 and 56.
58 PGM 2 Output
Terminal 58 is a programmable open collector output.
This output provides a negative voltage output that sinks to ground when activated.
Use terminal 68 to provide the positive voltage that is necessary.
This output is capable of providing a maximum of 50mA of current.
Use Altronix RBSN or the Alarm Controls model 8007 relay base with an 8012 relay.
See Chart on page 15 for wiring to relays.
59-60-61 Auxiliary Relay 2 Output
These terminals provide an auxiliary Form C relay output.
This output is “dry”.
The relay contacts are rated at Max 5 amp.
Terminal 59 - Common.
Terminal 60 - Normally Closed.
Terminal 61 - Normally Open.
62-63-64 Auxiliary Relay 1 Output
These terminals provide an auxiliary Form C relay output.
This output is “dry”.
The relay contacts are rated at Max 5 amp.
Terminal 62 - Common.
Terminal 63 - Normally Closed.
Terminal 64 - Normally Open.
65 Listen In Input
This terminal allows for the provision of a listen in amp. and will provide an audio path to the amplifier.
Power for the amplifier should be derived from Aux. Power terminals 3(-) and 4(+) or 45(+) and 46(-).
(Additional hardware required).
Condition Voltage Reading
Trouble 0.0 VDC to 0.62 VDC
Normal 0.62 VDC to 1.80 VDC
Alarm 1.80 VDC to 7.96 VDC
Trouble 7.96 VDC or greater
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
9 of 20
Wiring Data
Terminals Description
66 PGM 3 Output
Terminal 66 is a programmable open collector output.
This output provides a negative voltage output that sinks to ground when activated.
Use terminal 68 to provide the positive voltage that is necessary.
This output is capable of providing a maximum of 50mA of current.
Use Altronix RBSN or the Alarm Controls model 8007 relay base with an 8012 relay.
See Chart on page 15 for wiring to relays.
67 & 68 Auxiliary Power Output
Terminal 68 is the positive and terminal 67 is ground.
For devices that require the interruption of power to reset them (Latching outputs), terminals 53 & 54 (Switched
Aux. Power) should be used to supply power.
A self resetting PTC protects this power output.
70-71-72 Long Range Radio Outputs
These terminals allow for the installation of the Optex Long Range Radio Transmitter, RF-RM1 that when used
will provide a higher level of communication integrity.
Additional hardware required.
Compatible only with Optex America Inc. radio system.
73-74-75-76 Teleco 2 Input
73 (Ring) is the premise side.
74 (Tip) is the premise side.
75 (Ring) the teleco input from the phone company.
76 (Tip) the teleco input from the phone company.
These terminals are used for connecting the control panel to an RX-31X phone jack to provide full line seizure.
Fault condition sensed at 4.V.
77-78-79-80 Teleco 1 Input
77 (Ring) is the premise side.
78 (Tip) is the premise side.
79 (Ring) the teleco input from the phone company.
80 (Tip) the teleco input from the phone company.
These terminals are used for connecting the control panel to an RX-31X phone jack to provide full line seizure.
Fault condition sensed at 4.V.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
10 of 20
Expansion
The SMDC allows for the installation of up to eight (8) remote zone expansion boards.
These zone expansion boards allow for the installation of eight individual protection devices.
The maximum length of cable that maybe installed to wire these zone boards is 1000 feet of twenty two (22) gauge four (4)
conductor.
Each of the zone expansion boards have addressing jumpers that must be either removed or in place to allow the control panel to
“talk” and identify which expansion board is issuing the command.
The chart below indicates the proper addressing methods for each zone expansion board.
Installation program location 2.6 must have the correct number of expander boards enabled.
G-EX Expander Board Jumper Setting
G-EX Zone # J1 J2 J3
Board 1 = Zones 17-24 Off Off Off
Board 2 = Zones 25-32 Off Off On
Board 3 = Zones 33-40 Off On Off
Board 4 = Zones 41-48 Off On On
Board 5 = Zones 49-56 On Off Off
Board 6 = Zones 57-64 On Off On
Board 7 = Zones 65-72 On On Off
Board 8 = Zones 73-80 On On On
Expansion Diagram
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
11 of 20
Control Panel Hardware
Location Description
P1 Battery Connection
Use only a 12VDC lead acid. Use of any other battery type may cause damage.
SMDC provides a continuous 13.6VDC to the panel under normal conditions.
11.45VDC, a low battery signal will be transmitted to the central station if programmed.
11.85VDC, the panel will transmit a battery restore code to the central station, if programmed.
The panel will disconnect the battery 9.0 Vdc after loss of AC power
The control panel will revert to the same operating condition once the AC power has returned.
The SMDC control panel is protected by a self-resting PTC.
The PTC will remain open until the polarity has been corrected and then automatically reset.
P2 Keypad Connector
This input allows for a SMPC keypad to be easily attached to the control panel via Optex part number 5090-0194
cable assembly to program the control panel or to perform any task that would be simplified by having the keypad
attached directly to the control panel.
Relays
K6 Relay used for auxiliary Relay 2. Contacts rated @ 5 amp.
K7 Relay used for auxiliary Relay 1. Contacts rated @ 5 amp.
K1 Relay used for telephone line seizure on phone line number one and two.
K3 Relay used for telephone line switching between phone line number one and two.
K8 Fire bell relay.
K4 Dialer relay.
K2 Radio output relay.
Battery Calibration
Should there been damaged caused to the control panel EEprom this may cause a need to re-calibrate to SMDC control panel to
accommodate your battery. You should always check the battery charging circuit with a load before the final turnover to insure proper
operation. The following steps are used for the calibration process
1. Enter your company PIN.
2. Press Enter.
3. The keypad will now be placed in the Volt Meter mode.
4. Press Program.
5. The keypad will display: “Disconnect Battery”
“Press Enter”
6. Disconnect battery & Press ENTER.
7. Wait 2 seconds.
8. Re-connect battery.
9. Press Scan until the battery current is displayed.
10. Disconnect AC.
11. Keypad should display a negative current.
12. Restore AC.
13. Press Clear.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
12 of 20
Battery Calculations
Example 72 Hour Standby Plus 4 Minutes Bell Ringing
Equipment (Non Alarm) Current (ea.) X# of Hours X# of Units =Total Ah
SMDC-16 .113 A_ X 72 X1 =8.136
SMPC-32 D .070 A_ X 72 X1 =5.04
SMPC-32 DL .095 A_ X 72 X1 =6.840
GEX .029 A_ X 72 X2 =4.176
2 wire smoke detectors _______ X X =
Switched Aux Power ________ X X =
Aux. Power ________ X X =
(1) ttl 24.192
Equipment (In Alarm) Current (ea) X# of Hours X# of Units =Total Ah
SMDC-16 .290 A__ X 4 min ÷ 60 X1 =0.019
SMPC-32 D .111 A X 4 min ÷ 60 X1 =0.007
SMPC-32 DL .140 A X 4 min ÷ 60 X1 =0.009
G-EX .029 A X ________ X =0.004
2 wire smoke detector ________ X ________ X =_______
Switched Aux. Power ________ X ________ X =_______
Aux. Power ________ X ________ X =_______
Indicating Device (bells, etc) .500A X 4 min ÷ 60 X1 =0.033
(2) ttl =0.072
(1+2) ttl =24.264
multiply by derating factor of 1.2 total =29.117
A suitable battery for 72 hour standby is 12vdc 33 amp hour
Work Sheet 72 Hour Standby Plus 4 Minutes Bell Ringing
Equipment (Non Alarm) Current (ea) X# of Hours X# of Units =Total Ah
SMDC-16 .113 A_ X 72 X =
SMPC-32 D .070 A_ X 72 X =
SMPC-32 DL .095 A_ X 72 X =
GEX .029 A_ X 72 X =
2 wire smoke detectors ________ X 72 X =
Switched Aux Power ________ X 72 X =
Aux. Power ________ X 72 X =
(1) ttl
Equipment (In Alarm) Current (ea) X# of Hours X# of Units =Total Ah
SMDC-16 .290 A__ X 4 min ÷ 60 X =
SMPC-32 D .111 A X 4 min ÷ 60 X =
SMPC-32 DL .140 A X 4 min ÷ 60 X =
GEX .029 A X 4 min ÷ 60 X =
2 wire smoke detector ________ X 4 min ÷ 60 X =
Switched Aux. Power ________ X 4 min ÷ 60 X =
Aux. Power ________ X 4 min ÷ 60 X =
Indicating Device (bells, etc) .500A X 4 min ÷ 60 X =
(2) ttl =
(1+2) ttl =
multiply by derating factor of 1.2 total
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
13 of 20
Keypad Functions
Keypad Wiring
The following diagrams show the two methods available for the wiring of keypads, the termination resistor placement for both
methods and the keypad addressing.
Home Run Wiring
Daisy Chain Wiring
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
14 of 20
Keypad Hardware
SMPC-32 D /DL Keypad Connections
SMPC-32 Connection Wire Color SMDC Terminal
Keypad + Red 20
Keypad - Black 19
Keypad Data Green 18
Keypad Data Yellow 17
1 keypad = 150 ohms ¼ watt
2 keypads = 300 ohms ¼ watt
3 keypads = 450 ohms ¼ watt
4 keypads = 600 ohms ¼ watt
5 keypads = 750 ohms ¼ watt
6 keypads = 900 ohms ¼ watt
7 keypads = 1050 ohms ¼ watt
8 keypads = 1240 ohms ¼ watt
Keypad Address Switch (S1) Settings Keypad Rear Access Window
SWITCH (S1) A B
1st Keypad Off Off
2nd Keypad On Off
3rd Keypad Off On
4th Keypad On On
Expanded Address Keypads
5st Keypad Off Off
6nd Keypad On Off
7rd Keypad Off On
8th Keypad On On
Keypad Voltmeter
The SMDC control panel allows for the installer to check the control panel system voltages with the information to be displayed
on the LCD. The voltage voltages and currents that will be displayed when the installers PIN and ENTER is depressed is:
Bell Sense voltage.
Battery current.
Battery voltage.
Switched auxiliary voltage
2 Wire smoke detector voltage.
Buss voltage.
Ground fault voltage.
Telephone line status.
When a negative battery current reading is displayed and the AC is removed, this is the total current draw on the panel.
When positive battery current reading is displayed and the AC power is applied this is the charging circuit for the battery.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
15 of 20
PGM Trigger Wiring
Relay Module Wiring Diagram PGM Used For Ground Start Wiring Diagram
PGM outputs are low current transistor outputs that are held above ground. Once these outputs are triggered they sink to ground and
supply a 50 mA output maximum.
Warning: pulling an excess of 50mA runs the risk of damaging these outputs.
Appendix A
For Installation Instructions, see Installation Manual, Part No. 3440-0251.
Use a UL Listed End of the Line Relay for 4 wire smoke detectors.
This control unit should be checked by a qualified technician at least every 3 years.
This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm code ANSI/NFPA 72-1993 (National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed information describing proper installation,
operation, testing, maintenance, evacuation planning and repair service is to be provided with this equipment.
Maximum Battery Charging Current is 700 mA.
Type of Service: Automatic Fire Alarm, Manual Fire Alarm, Water Flow Alarm, Sprinkler Supervisory.
Type of Signaling: Digital Alarm Communicator Transmitter. (RF using Optex-Morse Model RF-RM1 transmitter).
The SMDC-WX (wireless features) have not been investigated for use in UL Listed Fire Applications or UL Listed Burglar
Applications.
The SMDC-INT-P/F (fax and printer options) are not for Commercial Fire Applications.
The SMDC-INT Board connections are limited to same room.
This unit includes verification feature that will result in a delay of the system alarm signal from the indicated circuits. The total delay
(Control Unit plus smoke detectors) shall not exceed 60 seconds. No other smoke detector shall be connected to these circuits unless
approved by the Local Authority Having Jurisdiction.
Circuit (Zone) Control unit delay, seconds Smoke detector
Model Delay, seconds
a. Include detector data or the following or equivalent statement. “The delay (power-up) (start-up) time marked on the installation
wiring diagram of the smoke detector or on the installed smoke detector(s) is to be used.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
16 of 20
Appendix B
Zone Type Description
1. Entry / Exit 1) Away mode - this zone is always delayed (entry / exit).
2) Stay mode - this zone is always delayed (entry / exit).
3) Instant mode - this zone is always delayed exit and always instant alarm on entry.
2. Perimeter
Instant
1) Away mode - this zone is always an instant alarm.
2) Stay mode - this zone is always an instant alarm.
3) Instant mode - this zone is always an instant alarm.
3. Interior 1 1) Away mode - this zone responds as a follower.*
2) Stay mode - this zone responds as a follower. *
3) Instant mode - this zone responds as an instant alarm if activated.
4. Interior 2 1) Away mode - this zone responds as a follower. *
2) Stay mode - this zone is always bypassed.
3) Instant mode - this zone is always bypassed.
5. Interior 3 1) Away mode - this zone is always delayed.
2) Stay mode - this zone is always delayed.
3) Instant mode - this zone is always bypassed
6. 24 Hour 1) This zone type is used for devices that will create an alarm regardless of the armed state of the SMDC.
7. Fire 1) This type of zone may also be enable for Fire Supervisory after the YES has been programmed.
2) If YES is selected for Fire Supervisory, the keypad(s) will emit a steady tone on an alarm condition and display
the zone in alarm.
8. Day Zone 1) Disarmed - an activation creates an trouble condition.
2) Armed - an activation creates an instant alarm condition.
9. Garage Door 1) This zone type allows the zone to be open when arming the SMDC.
2) When the zone restores, it is returned as an active entry delay zone.
3) The zone must restore to a secure condition prior to exit delay time expiring.
4) Should the zone fail to secure, an exit error code will be transmitted if so programmed.
5) An alarm will be generated if the zone is left open.
* Note: The term follower is defined as the zone will be delayed on entry if the Exit door is sensed by the control panel first, should the follower zone be
sensed first by the control panel, the follower zone will create an alarm instantly.
UL Information Addendum
Equipment
The following equipment has been listed by Underwriters Laboratories:
Control Panel Model SMDC-16.
Expansion Board, Model G-EX.
Keypad, Model SMPC-32 D/ SMPC-32 DL.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
17 of 20
Communication
This unit has been tested with:
Varitech Model V-300, Receiver Using 3/1, 4/1, 4/2 Pulsed communication formats and Varitech 4-2 FSK Communication format
and found to be compatible.
This unit has been tested with Sur-Gard Model SG-DRL2A, Receiver using 4-1 pulsed communication format, 4-2 pulsed
communication format, SIA LEVEL 1 communication format and Contact ID communication format and found to be compatible.
Grades Of Service
The unit is suitable for Police Station connect, GRADE A, Mercantile Premises and Mercantile Safe and Vault, service if used in
conjunction with Model MDC-16CCS attack proof enclosure and a Listed GRADE A, local sounding device.
The unit is suitable for Local, GRADE A, Mercantile Premises and Mercantile Safe and Vault, service if used in conjunction with
Model MDC-16CCS attack proof enclosure and a listed, GRADE A, local sounding device.
The unit is suitable for Central Station, GRADE C, service if used in conjunction with Model MDC-16CCS attack proof enclosure.
The unit is suitable for Central Station, Grade B, service if used in conjunction with Model MDC-16CCS attack proof enclosure
and a Listed, Grade A, local sounding device.
UL Listings
UL 1023 - Household Burglar-Alarm System Units.
UL 985 - Household Fire Warning System Units.
UL 1610 - Central-Station Burglary-Alarm Units.
UL 1635 - Digital Alarm Communicator System Units.
UL 365 - Police Station Connected Burglar Alarm Units And Systems.
UL 609 - Local Burglar Alarm Units And Systems.
UL864 - Control Units for Fire-Protective Signaling Systems.
For Grade A Local Mercantile Installations
The minimum requirements to form a listed Grade A local System includes:
1. Low Battery Alarm condition (Unless dialer used to transmit a low battery message).
Current Rating Chart
Control SMDC-16 =113 MA
Keypad SMPC-32D =70 MA
Keypad SMPC-32 DL =95 MA
Expansion Board G-EX =29 MA
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
18 of 20
Walk Test
It is imperative to perform a Walk Test after the initial installation of the system. The Walk Test allows you to test all burglary type
zones. Zone option for Walk Test (menu 2.1.7.7.) must be selected for each of these zones.
To initiate the Walk Test mode:
The Central Station and subscriber must be notified of this test as the communicator will also be tested by transmitting alarm
signals as well as the audible devices on all 24 Hour and Day zones.
Press the WALK key.
Enter your installer PIN.
Press 1 button on keypad to select WALK TEST.
Once the Walk Test is initiated, all zones programmed for Walk Test will scroll on the keypad.
Each time a zone is activated the keypad will emit an audible tone send a signal (if it is a 24 hour type zone programmed for
reporting), tripped the audibles (if it is a 24 hour type zone programmed to activate voltages, relays, etc.) eliminate that zone from
scroll list and return to scrolling the remainder of zones that need to be tested.
After all zones have been tested, the keypad will display “WALK TEST DONE” on the keypad display.
Press CLEAR key to exit Walk Test Mode.
Fire Test Mode
It is imperative to perform a Fire Walk Test after the initial installation of the system. The Fire Walk Test allows you to test all zones
that have been programmed as a Fire zone in the installers program (menu 2.1.1.). Zone option for Walk Test (menu 2.1.7.7.) must be
selected for each of these zones.
To initiate the Fire Walk Test mode:
The Central Station and subscriber must be notified of this test as the communicator will also be tested by transmitting alarm
signals as well as the audible devices will also be tested.
Press WALK button.
Enter your installers PIN.
Press 2 button on keypad to select FIRE WALK TEST.
Once the Fire Walk Test is initiated, all fire zones programmed for Walk Test will scroll on the keypad.
Each time a zone is activated, the keypad will emit an audible tone, send a signal (if programmed for reporting), tripped the audibles
(if programmed to activate voltages, relays, etc.) eliminate that zone from scroll list and return to scrolling the remainder of zones
that need to be tested.
The control panel will automatically reset the power for both the 2-wire smoke detector circuit and the switched auxiliary power
allowing for the activation of subsequent devices with out the need to return to a keypad and performing a power reset
After all zones have been tested, keypad will display “WALK TEST DONE” message on keypad.
Press CLEAR key to exit Walk Test
Walk Test History
Walk Test history allows the installation company to view the activation’s of both the Burglary and the Fire Walk test history in the
same sequence of activation’s that have occurred. To view the walk test history:
Press the WALK key.
The display will ask for a PIN number.
Enter your Installer Pin Number.
Display will scroll three choices.
Press 3 key on keypad to select WALK TEST HISTORY.
The first zone that tripped will be on the display, to view subsequent activation’s press the SCAN button.
After the last zone that was activated is scanned, the keypad will revert back to the Walk Test options.
The Walk test history will be retained in the memory until another walk test is performed regardless of the arming and disarming of
the control panel.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
19 of 20
UL Compliance Verification Chart
Compatible Bell/Horn/Strobe
MFG MODEL # DEVICE TYPE MFG MODEL # DEVICE TYPE
Wheelock MB-G6-12-R Motor Bell Wheelock MB-G10-12-R Motor Bell
Wheelock MBS-G6-12-W-HF-R Motor Bell With Strobe Wheelock MBS-G10-12-W-HF-R Motor Bell With Strobe
Wheelock MIZ-12-R Mini- Horn Wheelock MIZ-12-W Mini-Horn
Wheelock MIZ-12-WS-VF-R Mini Horn/Strobe Wheelock V7001T-W-FR Strobe Horn
Wheelock WST-12-FR Strobe Wheelock WS1T-12-FR Strobe
Wheelock WS3T-12-FR Strobe Wheelock 46T-G10-12-R Bell
Amseco MSB-10B-PV4-12 Motor Bell
Compatible 2-Wire Smoke Detectors
Mfg Model #
Detection Systems DS250/DS250TH Detector Identifier = A
System Sensor 2400 /2400 TH Detector Identifier = A
Sentrol 429 C/429 CT Detector Identifier = S10A
System Sensor 2300 T Detector Identifier = A
Compatible 4-Wire Smoke Detectors
The operating voltage range for 4-wire smoke detector is 9.7 - 13.7 Volts
Mfg Model #
System Sensor 1112, 2112, 2112T, 2112TSRB
ESL 449 AT/ 449 CT, 741 U/ 741 UT
Detection Systems DS 250 /250 TH used with MB4W base
Program Requirements
When programming the SMDC-16, the following programs must be maintained to meet minimum UL requirements for Household
Burglar Systems and/or Commercial Burglar Alarm Systems and Police Connect.
Exit time should not exceed 60 seconds.
Entrance time should not exceed 45 seconds including pre-alarm delay.
Loop response not to exceed 1 second.
Bell and/or Siren - 4 minutes minimum to meet UL Residential Burglar & Fire.
Bell and/or Siren - 15 minutes minimum to meet UL Commercial Burglar Alarm and Police Connect.
For the Fire Bell to ring in Temporal Pattern the following settings must be entered:
1. Zone Type must be set to Fire Zone (menu 2.1.1).
2. Bell 1 must be set to YES (menu 2.8.1).
3. Bell 1 Pulse must be set to YES (menu 2.8.2).
4. Temporal Fire must be set to YES (menu 4.9).
Burglar Alarm Loops must alarm in open or shorted conditions.
Low Battery must be programmed to report.
Two separate phone numbers (rcvr 1 & rcvr 2) must be programmed to meet Commercial Fire Applications.
Close Ringback must be program YES.
Abnormal Self Test code must be programmed.
Installation and Operation Manual
Optex Inc. - 1845 W. 205th St. - Torrance, Ca. 90501 - 800-966-78393440-0251 A4
20 of 20
Warranty
1 Optex equipment is warranted to be free from defects in workmanship or materials for a period of one (1) year from
date of shipment to the original purchaser. No equipment may be returned without express written approval of after a
determination by that such equipment is defective because of poor workmanship or defective materials. Optex shall
replace or repair, at its sole and exclusive option, such defective materials or parts thereof at its own expense, except
that Purchaser shall pay all shipping, insurance, and similar charges incurred in connection with the replacement of the
defective equipment or parts thereof. This warranty is void in case of abuse, abnormal usage, faulty installation or
repair by unauthorized persons, acts of God, or if for any other reason Optex determines that such equipment is not
operating properly as a result of causes other than poor workmanship or defective materials.
2Equipment not manufactured by Optex is subject solely to the terms and conditions of the manufacturer’s warranty, if
any, applicable to such equipment.
3THE AFORESAID WARRANTIES ARE EXPRESSLY MADE IN LIEU OF ANY OTHER WARRANTIES,
EXPRESS OR IMPLIED, IT BEING UNDERSTOOD THAT ALL SUCH OTHER WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR
PURPOSE OR HEREBY EXPRESSLY EXCLUDED. IN NO EVENT SHALL OPTEX BE LIABLE TO THE
PURCHASER FOR ANY DIRECT, COLLATERAL, INCIDENTAL OR CONSEQUENTIAL DAMAGE IN
CONNECTION WITH PURCHASER’S USE OF THE EQUIPMENT, OR FOR ANY OTHER CAUSE
WHATSOEVER RELATING TO THE EQUIPMENT.
WAIVER AND MODIFICATIONS:
No waiver or modifications of any of the foregoing terms and conditions of sale or limited warranty policy shall be
effective unless such waiver or modification is in writing and signed by an authorized representative of Optex.
TERMS AND CONDITIONS TO PREVAIL:
The foregoing Terms and Conditions shall prevail notwithstanding any variance with any Purchase Order or other
document submitted by the Purchaser for the equipment and regardless of whether or not the equipment was delivered
to the Purchaser thereunder.
Any shipment made by Optex shall be in reliance upon Purchaser’s acceptance of Optex Terms and Conditions as
aforesaid and may not be interpreted as an acceptance or an offer to contract on the basis of any Purchaser’s Terms
and Conditions.