Smart-UPS® VT

10-30 kVA
208/220 V

Site Preparation and
Installation Manual

Smart-UPS® VT 10-30 kVA 208/220 V
Site Preparation and Installation Manual

IMPORTANT SAFETY INSTRUCTIONS –
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the SUVT series that should be
followed during installation and maintenance of the UPS and Batteries

Smart-UPS® VT 10-30kVA, 208V, Site Preparation and Installation – 990-1598A

1

Contents
Safety .....................................................................1
General Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Environmental symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Introduction ............................................................3
UPS Family Range and Components . . . . . . . . . . . . . . . . . . . . . 4
13.85 in/352 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
20.59 in/523 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Type label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connection Interface (rear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Foot print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
APC Network Management Card AP9619 (installed in UPS)
and APC Humidity Sensor (Optional) . . . . . . . . . . . . . . . . . . . . . 9

Site Preparation .....................................................10
Installation Space Requirements . . . . . . . . . . . . . . . . . . . . . . . 10
Clearance for 20.59 in/523 mm Enclosures . . . . . . . . . . . . . . . 10
Clearance for stand-alone 13.85 in/352 mm Enclosures . . . . . . 11

Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heat dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Audible noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Recommended current protection . . . . . . . . . . . . . . . . . . . . . . 13
Minimum breaker settings for 10 kVA UPS . . . . . . . . . . . . . . . . 13
Minimum breaker settings for 15 kVA UPS . . . . . . . . . . . . . . . . 14
Minimum breaker settings for 20 kVA UPS . . . . . . . . . . . . . . . . 14
Minimum setting of breakers for 30 kVA UPS . . . . . . . . . . . . . . 14
Recommended phase-conductor sizes [AWG] for a 86°F
(30°C) temperature environment . . . . . . . . . . . . . . . . . . . . . . . 15
EPO switch wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

i

Basic Wiring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Site Preparation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Mechanical assembly ............................................ 18
Stabilizing Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Leveling Feet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Floor Anchoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Drilling floor holes for floor anchoring . . . . . . . . . . . . . . . . . . . 20
Hole positions for floor anchors (stand-alone Enclosures) . . . . . 20
Floor anchoring of stand-alone systems . . . . . . . . . . . . . . . . . . 21

Electrical Installation ............................................ 22
System-Electrical Information . . . . . . . . . . . . . . . . . . . . . . . . . 22
Source connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA,
208V, 3 phase, single mains . . . . . . . . . . . . . . . . . . . . . . . . . . 25
One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA,
220V, 3 phase, single mains . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Input/Output Wiring – Single Mains (default) . . . . . . . . . . . . . 28
Input/Output Wiring – Dual Mains . . . . . . . . . . . . . . . . . . . . . 30
External Battery Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Wiring to battery bank or battery racks . . . . . . . . . . . . . . . . . . 32

Communication Wiring to EPO and Optional Equipment . . . . 33
Pin connections J106 (XR Enclosure) and J108 (EPO) . . . . . . . . 34
Pin connections J106 (UPS) to J200 (XR Enclosure - option) . . . 34
XR Enclosure, APC Maintenance Bypass Panel, and Generator
Control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Pin connections J108 (for EPO wiring options) . . . . . . . . . . . . 36

Connection of APC Humidity Sensor . . . . . . . . . . . . . . . . . . . . 37
Front panel removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Wiring Verification Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 40
Installation Site Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

ii

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Safety
General Safety Instructions
This guide contains important instructions that should be followed when handling the UPS, Battery
Enclosures, and batteries.

Symbols used in this guide
WARNING!
Risk of electric shock.
CAUTION!
Read this information to avoid equipment damage.

Indicates important information.
Note

Indicates that more information is available on this subject in a different section of this
manual.

Indicates that more information is available on the same subject in a different manual.

Environmental symbols

Temperature

990-1598B

Ventilation
requirements

Humidity

Dust/Fumes

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

Altitude

1

Safety – General Safety Instructions

General safety
WARNING!
All electrical power and control wiring must be installed by a qualified electrician and
comply with local and national codes.
WARNING!
When connected, the UPS contains energy from both AC and DC sources. If the UPS
has dual mains supply, be aware of the two AC supply sources. Risk of electric shock parts inside the UPS are energized from the battery supply even the AC power is
disconnected.
WARNING!
Servicing of batteries should be performed or supervised by personnel knowledgeable
of batteries and the required precautions. Keep unauthorized personnel away from
batteries.
WARNING!
Batteries do not contain serviceable parts. Only APC authorized personnel may open
batteries.
WARNING!
Do not dispose of battery or batteries in a fire. The battery may explode. Do not open or
mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
WARNING!
Risk of Energy Hazard, 96 V, 7.2 Ampere-hour battery. Before replacing batteries,
remove watches, rings, or other metal objects. High energy through conductive
materials could cause severe burns.
WARNING!
When handling batteries, wear rubber gloves and boots. Do not lay tools or metal
objects on top of batteries.
WARNING!
When replacing a Battery Unit, replace with the same number of the APC SYBT1
(always replace a whole Battery Module (4 Battery Units) at a time).
WARNING!
Only trained personnel familiar with the construction and operation of the equipment
and the electrical and mechanical hazards involved, may install and remove system
components.
For configurations including customer-supplied external batteries, refer to
manufacturer’s battery installation and maintenance instructions.

2

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Introduction
Welcome to the Site Preparation and Installation Manual for the Smart-UPS® VT. This manual
contains information on how to prepare your site for the installation of the UPS and optional APC
equipment (also available at www.apc.com) and instructions on how to carry out the electrical/
mechanical installation. Separate manuals are available on:
• Receiving and Unpacking - part no. 990-1747
• Operation - part no. 990-1599
Keep the UPS free from loose objects to prevent obstruction of the airflow.
Note

For more information on APC products and services, visit us at www.apc.com
Note

Note

990-1598B

Most illustrations show 20.59 in / 523 mm Enclosures but apply to both Enclosure sizes
(13.85 in / 352 mm and 20.59 in / 523 mm). Any differences between the two Enclosure
sizes will be addressed in the manual.

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

3

UPS Family Range and Components
13.85 in/352 mm Enclosures

!

Output

Pwr
Zone
Probe
10/100Base-T

Reset

AP9619

10/100
Network
Management
Card EM

Serial:
Model:

BATTER
Y UNIT

Serial:
Model:

BATTER
Y UNIT

Serial:
Model:

BATTER
Y UNIT

Serial:
Model:

BATTER
Y UNIT

Serial:
Model:

BATTER
Y UNIT

Serial:
Model:

BATTER
Y UNIT

Unit

Serial

No

Hotline
in
Hotline US/Canada/LA
in EMEA:
Worldwide
M: +1
Support+353 91 70 800 800 4APC
numbers: 2000
APC

SKU

www.apcc.co
m/support/se

Model

rvice/geomap

SUVTF10KB2F
SUVT10KF1B2S
APC
SUVT10KF2B2S

Battery
Smart-UPS

w/1 Batt.
VT 10kVA
Module
208V
Exp.
Smart-UPS
to 2
w/2 Batt. VT 10kVA
208V
Smart-UPS Modules
w/1 Batt.
VT 10kVA
Module
208V
APC
Exp.
Smart-UPS
to 4
w/2 Batt.
VT
Modules10kVA 208V
APC
Smart-UPS
Exp.
to 4
w/3 Batt.
VT
Modules10kVA 208V
APC
Smart-UPS
Exp.
to 4
w/4 Batt. VT 10kVA
Modules 208V
APC
Smart-UPS
w/2 Batt. VT 15kVA
Modules 208V
APC
Smart-UPS
w/2 Batt.
VT
Modules15kVA 208V
APC
Smart-UPS
Exp.
to 4
w/3 Batt.
VT
Modules15kVA 208V
APC
Smart-UPS
Exp.
to 4
w/4 Batt. VT 15kVA
Modules 208V
APC
Smart-UPS
w/2 Batt.
VT
Modules20kVA 208V
APC
Smart-UPS
Exp.
to 4
w/3 Batt.
VT
Modules20kVA 208V
APC
Smart-UPS
Exp.
to 4
w/4 Batt. VT 20kVA
Modules 208V
APC
Smart-UPS
w/3 Batt.
VT
Modules30kVA 208V
APC
Smart-UPS
Exp.
to 4
w/4 Batt. VT 30kVA
208V
Modules
Types

Capacity

@– 192V

APC

SUVT10KF1B4S
SUVTF10KB4F

APC

SUVT10KF2B4S
SUVT10KF3B4S
SUVT10KF4B4S
SUVTF15KB2F
SUVT15KF2B2S

SUVTF15KB4F

SUVT15KF2B4S
SUVT15KF3B4S
SUVT15KF4B4S

SUVTF20KB4F

SUVT20KF2B4S
SUVT20KF3B4S
SUVT20KF4B4S

SUVTF30KB4F
SUVT30KF3B4S
SUVT30KF4B4S
Voltage
AC Input

& Connection

208Y/120V
4W+GND
60Hz

DC

DC Input

4W+GND
60Hz

+/- 192V

Date
installed

Apparent/
Rated
Power

Input

BATTER
Y UNIT

Current
Rated

Output

Current
Battery

Serial:
Model:

Current

BATTER
Y UNIT

7.2Ah
14.4Ah

10kVA/8kW
27.1A
208V

21.6Ah

27.8A
208V

28.8Ah

28.9A
14.4Ah

14.4Ah
21.6Ah

15kVA/12kW
40.6A
208V

28.8Ah

41.6A
208V

14.4Ah

43.3A

21.6Ah
28.8Ah

20kVA/16kW
54.2A
208V

21.6Ah
28.8Ah

AC Output
208Y/120V

Serial:
Model:

_world.dfm

Active
7.2Ah
14.4Ah

30kVA/24kW

57.7A
81.3A
208V

Batteries
Date
for 1.
Replacement

55.5A
208V

83.3A
208V
Date
for 2.
Replacement

SEE

86.6A

INSTALLAT
BEFORE
ION INSTRUCTIO
CONNECTIN
SUPPLY
NS
G TO
THE
THIS
REAR
COVER
PLACED
ON UPS MUST BE
885-2321C_rev0
4

Front

Rear

Front without front panel
10-15 kVA

20.59 in/523 mm Enclosures

!

Output
Pwr
Zone
Probe
10/100Base-

Reset

T

AP9619

10/100
Network
Managemen
t Card

EM

!

Output
Pwr
Zone
Probe
10/100Base-

Reset

T

AP9619

10/100
Network
Managemen
t Card

Blind plates
cover
empty
battery bays

EM

Serial:
Model:

BATTE
RY UNIT
Serial:
Model:

BATTE
RY UNIT
Serial:
Model:

BATTE
RY UNIT
Serial:
Model:

BATTE
RY UNIT

Serial:
Model:

Serial:
Model:

BATTE

BATTE

RY UNIT

RY UNIT

Serial:
Model:

Serial:
Model:

BATTE

BATTE

RY UNIT

RY UNIT

Serial:
Model:

Serial:
Model:

BATTE

BATTE
RY UNIT

RY UNIT
Serial:
Model:

Serial:
Model:

BATTE

BATTE

RY UNIT

Unit

Serial

No

APC

SKU

www.apcc.
Model

2F

B2S

B4S

SUVTF15KB
2F
SUVT15KF2

B2S
SUVT15KF2
B4S

4F
SUVT15KF3

B4S
SUVT15KF4
B4S
SUVT20KF2
B4S

4F
SUVT20KF3

B4S
SUVT20KF4
B4S

SUVTF30KB
4F

SUVT30KF3
B4S
SUVT30KF4
B4S
Voltage
& Connection

AC Input
4W+GND
60Hz

rld.dfm

Capacity
@– 192V
DC

Apparent/
Active

7.2Ah

Power

Rated

Input

Serial:
Model:

Current
Rated

Output

14.4Ah

Current

14.4Ah

BATTE

RY UNIT

Current

RY UNIT
Serial:
Model:

10kVA/8kW

21.6Ah

Serial:
Model:

BATTE

Battery
7.2Ah

27.1A
208V

28.8Ah

Serial:
Model:

BATTE

27.8A
208V

BATTE

RY UNIT

RY UNIT

28.9A

APC

208Y/120V

eomap_wo

Battery

APC

w/1 Batt.
VT
Module 10kVA 208V
APC
Smart-UPS
Exp.
to 4
w/2 Batt.
VT
Modules 10kVA 208V
APC
Smart-UPS
Exp.
to 4
w/3 Batt.
VT
Modules 10kVA 208V
APC
Smart-UPS
Exp.
to
w/4 Batt. VT 10kVA 4
Modules 208V
APC
Smart-UPS
w/2 Batt. VT 15kVA
Modules 208V

B4S
B4S

SUVTF20KB

rt/service/g

APC
Smart-UPS
w/1 Batt.
VT
Module 10kVA 208V
APC
Exp.
Smart-UPS
to 2
w/2 Batt. VT 10kVA
Smart-UPS Modules 208V

B2S
B4S
SUVT10KF2
SUVT10KF3
SUVT10KF4

SUVTF15KB

com/suppo

SUVT10KF1
SUVT10KF2
SUVT10KF1

4F

RY UNIT

Hotline
Hotline in US/Canada
in EMEA:
/LAM:
Worldwide
+1 800
Support+353 91
70 2000 800 4APC
numbers:

SUVTF10KB

SUVTF10KB

Smart-UPS
w/2 Batt.
VT
APC
Modules 15kVA 208V
Smart-UPS
Exp.
to 4
w/3 Batt.
VT
Modules 15kVA 208V
APC
Smart-UPS
Exp.
to
w/4 Batt. VT 15kVA 4
APC
208V
Smart-UPS Modules
w/2 Batt.
VT
APC
Modules 20kVA 208V
Smart-UPS
Exp.
to 4
w/3 Batt.
VT
Modules 20kVA 208V
APC
Smart-UPS
Exp.
to
w/4 Batt. VT 20kVA 4
Modules 208V
APC
Smart-UPS
w/3 Batt.
VT
Modules 30kVA 208V
APC
Smart-UPS
Exp.
to
VT 30kVA 4
Types w/4 Batt.
Modules 208V

14.4Ah

Serial:
Model:

14.4Ah

Serial:
Model:

BATTE

21.6Ah

BATTE
RY UNIT

RY UNIT

15kVA/12kW

28.8Ah

40.6A
208V

14.4Ah

Serial:
Model:
41.6A
208V

21.6Ah

54.2A
208V

Serial:
Model:

BATTE

43.3A

BATTE

RY UNIT

20kVA/16kW

28.8Ah

21.6Ah
28.8Ah

AC Output

RY UNIT

55.5A
208V

30kVA/24kW
57.7A

208Y/120V

DC Input

4W+GND
60Hz

+/- 192V

Date
installed

81.3A
208V

Batteries
Date
for 1.
Replacemen
t

83.3A
208V

Date
for 2.
Replacemen
t

SEE
86.6A
INSTALLA
BEFORE
TION
INSTRUC
SUPPLY CONNEC
TIONS
TING
TO THE
THIS
REAR
COVER
PLACED
ON UPS MUST
BE

Serial:
Model:

BATTE

885-2321C_r

RY UNIT

ev04

Serial:
Model:

BATTE
RY UNIT
Serial:
Model:

BATTE
RY UNIT
Serial:
Model:

BATTE
RY UNIT

Front

Rear

Front without
front panel 10-15 kVA
Front without
front panel 20-30 kVA

4

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Introduction – UPS Family Range and Components

Serial number
The serial number is available on the type label on the rear side of the UPS.

Type label
Hotline in US/Canada/LAM: +1 800 800 4APC
Hotline in EMEA: +353 91 70 2000
Worldwide Support numbers: www.apcc.com/support/service/geomap_world.dfm
Model

APC SKU

Unit Serial No

7.2Ah

SUVT10KF2B2S

APC Smart-UPS VT 10kVA 208/220V
w/2 Batt. Modules

14.4Ah

SUVT10KF1B4S

APC Smart-UPS VT 10kVA 208/220V
w/1 Batt. Module Exp. to 4

7.2Ah

SUVT10KF2B4S

APC Smart-UPS VT 10kVA 208/220V
w/2 Batt. Modules Exp. to 4

14.4Ah

SUVT10KF3B4S

APC Smart-UPS VT 10kVA 208/220V
w/3 Batt. Modules Exp. to 4

21.6Ah

SUVT10KF4B4S

APC Smart-UPS VT 10kVA 208/220V
w/4 Batt. Modules

28.8Ah

SUVT15KF2B2S

APC Smart-UPS VT 15kVA 208/220V
w/2 Batt. Modules

14.4Ah

APC Smart-UPS VT 15kVA 208/220V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 15kVA 208/220V
w/3 Batt. Modules Exp. to 4

14.4Ah

APC Smart-UPS VT 15kVA 208/220V
w/4 Batt. Modules

28.8Ah
14.4Ah

SUVT20KF3B4S

APC Smart-UPS VT 20kVA 208/220V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 20kVA 208/220V
w/3 Batt. Modules Exp. to 4

SUVT20KF4B4S

APC Smart-UPS VT 20kVA 208/220V
w/4 Batt. Modules

28.8Ah

SUVT30KF3B4S

APC Smart-UPS VT 30kVA 208/220V
w/3 Batt. Modules Exp. to 4

21.6Ah

SUVT30KF4B4S

APC Smart-UPS VT 30kVA 208/220V
w/4 Batt. Modules

28.8Ah

SUVT15KF2B4S
SUVT15KF3B4S
SUVT15KF4B4S

SUVT20KF2B4S
SUVTF20KB4F

SUVTF30KB4F

27.8/26.2A
208/220V

28.9A

15kVA/12kW

40.6/38.4A
208/220V

41.6/39.4A
208/220V

43.3A

20kVA/16kW

54.2/51.2A
208/220V

30kVA/24kW

81.3/76.7A
208/220V

21.6Ah

21.6Ah

AC Input

AC Output

DC Input

208Y/120V 4W+GND 60Hz
220Y/127V 4W+GND 60Hz

208Y/120V 4W+GND 60Hz
220Y/127V 4W+GND 60Hz

± 192V

Date
installed

Date for 1.
Replacement

Rated Input Current Rated Output Current Battery Current

27.1/25.5A
208/220V

10kVA/8kW

55.5/52.5A
208/220V

57.7A

83.3/78.7A
208/220V

86.6A

SEE INSTALLATION INSTRUCTIONS

Batteries

Voltage & Connection Types

990-1598B

Active Power

APC Smart-UPS VT 10kVA 208/220V
w/1 Batt. Module Exp. to 2

SUVTF10KB4F

SUVTF15KB4F

Apparent/

@± 192V DC

SUVT10KF1B2S
SUVTF10KB2F

SUVTF15KB2F

Battery Capacity

Date for 2.
Replacement

BEFORE CONNECTING TO THE
SUPPLY
THIS REAR COVER MUST BE
PLACED ON UPS

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

885-2321D_rev05

5

Introduction – UPS Family Range and Components

User interface






!

Output

Pwr



Zone
Probe

10/100Base-T

Reset

10/100
AP9619 Network
Management Card

EM



Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT



 Display: user-control interface used to configure the functionality, monitor the system, set alarm
thresholds, and to provide audible and visual alarms.
 Network Management Card with Environmental Monitor (AP9619): used for remote system
control and monitoring, e-mail notifications etc.
 Computer-interface port for the connection of computers with APC Powerchute® software.
 Mechanical Bypass Lever: used to bypass the upstream mains power around the UPS to support
the load directly = internal mechanical bypass operation.
 Service port (for APC maintenance personnel only).

6

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Introduction – UPS Family Range and Components

 Display port for the connection of display communication cable.
 Documentation storage.
 Inlet for communication cables.

Connection Interface (rear)











 Upper Cover Plate rear.
 Upper part of Conduit Box.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

7

Introduction – UPS Family Range and Components

 Lower part of Conduit Box.
 Power connection.
 Communication wiring connection (EPO signalling, Battery Temperature Sensor).
 Protective earth.

Foot print
Rear

Rear













36.45 in/
926 mm





20.59 in/523 mm

13.85 in/352 mm

 Conduit Box.
 Levelling feet.
 Castors.
 Communication cable inlets.

8

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Introduction – UPS Family Range and Components

APC Network Management Card AP9619 (installed in UPS) and APC Humidity Sensor
(Optional)
Humidity Sensor
!

Output

Pwr

Zone
Probe

10/100Base-T

Reset

10/100
AP9619 Network

Management Card

EM

For installing Humidity Sensor see “Connection of APC Humidity Sensor” on page 40.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

9

Site Preparation
Installation Space Requirements
Clearance for 20.59 in/523 mm Enclosures

(A)
(B)

UPS
Conduit Box
(F)

(C)

(D)

(G)
(E)

Space requirements

in

mm

Minimum clearance above Enclosure (A)

20.00

508

Enclosure depth (B)

32.99

838

Enclosure width (C)

20.59

523

Minimum rear service clearance* (compliant with NEC 110.26 for
North America) (D)

36.00

914

Minimum front clearance (E)

40.00

1,000

Conduit Box, depth (F)

3.46

88

No side clearance required (add width of Stabilizing Brackets for
floor anchoring if applicable)

0

0

Stabilizing Bracket width

3.34

85

Total installation depth, inclusive of Front Panel, Conduit Box and
minimum front and rear clearances (G)

112.45

2,840

*) Minimum free rear space for ventilation 4 in/100 mm.

10

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Site Preparation – Installation Space Requirements

Clearance for stand-alone 13.85 in/352 mm Enclosures

(A)
(B)

UPS
Conduit Box (F)
(C)
(D)
Stabilizing Bracket,
left and right

(G)
(E)

Space requirements

in

mm

Minimum clearance above UPS (A)

20.00

508

UPS depth (B)

32.99

854

UPS width

13.85

352

Minimum rear service clearance* (compliant with NEC 110.26
for North America) (D)

36.00

914

Minimum front clearance (E)

40.00

1,000

Conduit Box, depth (F)

3.46

88

No side clearance required (add width of Stabilizing Bracket for
floor anchoring if applicable)

0

0

Stabilizing Bracket width

3.34

85

Total installation depth, inclusive of Front Panel, Conduit Box
and minimum front and rear clearances (G)

112.45

2.840

*) Minimum free rear space for ventilation 4 in/100 mm.
For the stability of 13.85 in/352 mm stand-alone Enclosures, the Stabilizing Brackets
must always be mounted on both sides of the UPS. See Stabilizing Brackets.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

11

Operating Environment
Operating conditions
Install the UPS in an indoor, temperature-controlled area, free of conductive
contaminants.
Note

Temperature
Range:
32° to 104°F /
0° to 40°C

Keep Ventilated
Front-to-Rear
Airflow (see
space
considerations)

Relative
Humidity: <95%
Non-condensing

No Conductive
Dust or
Corrosive
Fumes

Altitude derating table:
3,000 ft/914 m: 100% load
4,500 ft/1371 m: 95% load
6,000 ft/1828 m: 91% load
8,000 ft/2438 m: 86% load
10,000 ft/3048 m: 82% load

Heat dissipation

UPS size

BTU/hr at fully
charged batteries

UPS size

BTU/hr at fully
charged batteries

10 kVA

1,774

20 kVA

3,624

15 kVA

2,866

30 kVA

5,486

Audible noise

12

UPS Sizes

Audible noise at 100% load
(1.09 yard/1 m from the UPS)

Audible noise at <70% load
(1.09 yard/1 m from the UPS)

10-15 kVA

54 dBA

45.4 dBA

20-30 kVA

58 dBA

48.5 dBA

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Site Preparation – Operating Environment

Recommended current protection
AC output over-current protection and AC output disconnect must be provided by the
customer.
Note

Dual/single
mains
configuration

Connection

10 kVA

15 kVA

20 kVA

30 kVA

Notes

Single

Mains/bypass
input

35 A
breaker (30
kAIC)

60 A
breaker (30
kAIC)

80 A breaker
(30 kAIC)

125 A breaker
(30 kAIC)

Dual

Mains input

35 A
breaker
(30 kAIC)

60 A
breaker
(30 kAIC)

80 A breaker
(30 kAIC)

125 A breaker
(30 kAIC)

1, 2

Dual

Bypass input

35 A
breaker
(30 kAIC)

60 A
breaker
(30 kAIC)

80 A breaker
(30 kAIC)

125 A breaker
(30 kAIC)

1, 2

Any

Output

35 A fastacting class
J fuse

60 A fastacting class
J fuse

80 A fastacting class
J fuse

125 A fastacting class
J fuse

3, 4

Note 1: If the available fault current of the installation is below 30 kA, a lower kAIC-rated breaker can be
used.
Note 2: For breaker settings, refer to below table listing available overload currents.
Note 3: If the available fault current of the installation is less than 1200 A for the 10 kVA and 15 kVA UPS
sizes, and below 2300 A for the 20 kVA and 30 kVA UPS sizes, a breaker (of the same value as for the
bypass input) can be used.
Note 4: Recommended maximum rating of a single-fuse configuration if the internal bypass is to be protected
during a load short-circuit.

Minimum breaker settings for 10 kVA UPS
Overload Event

Mains input

Bypass input

Output

Duration

Notes

Internal fault

2 kA

1.7 kA

14 kA

<10 ms

1

800% overload bypass
operation

–

223 A

223 A

500 ms

150% overload normal/
battery operation

–

–

42 A

30 s

125% overload normal/
battery operation

–

–

35 A

60 s

Continuously

34 A

31 A

31 A

∞

Note 1: For the output value, the short-circuit-level is indicated.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

13

Site Preparation – Operating Environment

Minimum breaker settings for 15 kVA UPS
Overload Event

Mains input

Bypass input

Output

Duration

Notes

Internal fault

2.5 kA

2.1 kA

14 kA

<10 ms

1

800% overload bypass
operation

–

333 A

333 A

500 ms

150% overload normal/
battery operation

–

–

63 A

30 s

125% overload normal/
battery operation

–

–

52 A

60 s

Continuously

51 A

46 A

46 A

∞

Note 1: For the output value, the short-circuit-level is indicated

Minimum breaker settings for 20 kVA UPS
Overload Event

Mains input

Bypass input

Output

Duration

Notes

Internal fault

4 kA

3.4 kA

14 kA

<10 ms

1

800% overload bypass
operation

–

444 A

444 A

500 ms

150% overload normal/
battery operation

–

–

84 A

30 s

125% overload normal/
battery operation

–

–

70 A

60 s

Continuously

68 A

62 A

62 A

∞

Note 1: For the output value, the short-circuit-level is indicated.

Minimum setting of breakers for 30 kVA UPS
Overload Event

Mains input

Bypass input

Output

Duration

Notes

Internal fault

5 kA

4.2 kA

14 kA

<10 ms

1

800% overload bypass
operation

–

667 A

667 A

500 ms

150% overload normal/battery
operation

–

–

125 A

30 s

125% overload normal/battery
operation

–

–

105 A

60 s

Continuously

102 A

92 A

92 A

∞

Note 1: For the output value, the short-circuit level is indicated.

14

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Site Preparation – Operating Environment

Recommended phase-conductor sizes [AWG] for a 86°F (30°C) temperature
environment

UPS/AWG sizes

Mains input
[AWG]

AC output
[AWG]

DC input
[AWG], 75°C Wire

10 kVA

8

8

1

15 kVA

6

6

1

20 kVA

4

4

1

30 kVA

1

1

1

Use Molex lug type or equivalent, and crimp to manufacturer’s specifications.
Note

Cable Size
[AWG]

Cable Lug Type

Crimping Tool

Die

Terminal Bolt
Diameter

12

YA12CL2TC38

MD7-34R

W12CVT

0.2 in/6 mm

8

YA8CL2TC38

MD7-34R

W8CVT

0.2 in/6 mm

6

YA6CL2TC38

MD7-34R

W5CVT

0.2 in/6 mm

4

YA4CL2TC38

MD7-34R

W4CVT

0.2 in/6 mm

1

YA1CL2TC38

MD7-34R

W1CVT

0.2 in/6 mm

)

WARNING!
At 100% non-liniear load (EN50091-3 standard), the neutral shall be rated for 200%
phase current.

EPO switch wiring
The UPS must be connected to either a dry contact or a 24VDC Emergency Power Off (EPO) switch.

See “Pin connections J108 (for EPO wiring options)” on page 37

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

15

Basic Wiring Overview
Maintenance
Bypass Panel

AC input power

(Optional Equipment)

DC power
Communication Interface

EPO
EPO

AC power (output)

XR Enclosure(s)
(Optional, 4 Max.)

16

UPS

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Site Preparation Checklist
System components. Have you –



determined minimum battery run time requirement based on load (kW and kVA) and selected the
proper number of APC XR Enclosures (SUVTBXR2B6S, SUVTXR2B6S and SUVTBXR6B6S,
SUVTXR6B6S) and Battery Unit (SYBT1). Always install a whole Battery Module (4 Battery
Units) at a time.



considered Service Program or Extended Warranty plan?

Site Preparation. Have you –



verified that input voltage and current are available?



considered correct operating space, floor strength (see Installation Space Requirements), cooling,
and environment (see Operating Environment).



reviewed all electrical work to determine wiring requirements?

Arrival Preparation. Have you –



verified that space and handling equipment are available to receive the UPS/XR Enclosure?
(Including unloading the UPS/XR Enclosure from the delivery truck).



scheduled an authorized electrician to install the UPS/XR Enclosure?

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

17

Mechanical assembly
Stabilizing Brackets
Always install the Stabilizing Brackets on the 13.85 in/352 mm Enclosure (shipped with the UPS) to
enhance the stability of the Enclosure.
Attach the Stabilizing Bracket to the UPS Enclosure re-using the screws used to secure
the UPS to the pallet during shipment.
Note

!

Output

Pwr
Zone
Probe
10/100Base-T

Reset

AP9619

10/100
Network
Management
Card EM



Serial:
Model:

Serial:
Model:

Serial:
Model:

BATTE

RY UNIT

BATTE

RY UNIT

Serial:
Model:

BATTE

Serial:
Model:

RY UNIT

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT

BATTE

RY UNIT

Serial:
Model:

Serial:
Model:

BATTE

RY UNIT

Serial:
Model:

BATTE

Serial:
Model:

RY UNIT

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT



Serial:
Model:

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT



Serial:
Model:

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT

Serial:
Model:

BATTE

RY UNIT

Stabilizing
Bracket

If the Enclosure needs to be moved after Stabilizing Brackets have been attached to the Enclosure,
the Stabilizing Brackets must be pushed up into their high position.
 Loosen the two screws of both Stabilizing Brackets, and push the bracket up into the high
position.
 When the Enclosure has reached its new position, push the Bracket into its “down” position
again, and tighten the screws.
WARNING!
For stability reasons, do not remove Stabilizing Brackets from 13.85 in/352 mm
Enclosures.

18

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Leveling Feet
Verify that the installation has been electrically wired before setting the leveling feet.
Note

Setting the leveling feet
Set the leveling feet to ensure the UPS is horizontal when it is in its final operating position. Use a 13/
14-mm wrench (shipped with UPS) to adjust all 4 leveling feet from front to back, and left to right,
until the pads make solid contact with the floor. Use a bubble level to check the Enclosure is
horizontal.

13/14-mm wrench

CAUTION!
To avoid equipment damage, do not push or pull the UPS after the leveling feet have
been lowered.

When the Leveling Feet have been set, remember to reinstall the Front Panel.
See Front Panel section.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

19

Floor Anchoring

Note

If floor anchoring is required in your area, read this section. If not, proceed to
Operating Environment. However, if you install a 13.85 in/352 mm Enclosure, it must
always be equipped with the Stabilizing Bracket for enhanced stability (not necessary
to bolt the Stabilizing Bracket to the floor in non-seismic areas).

Drilling floor holes for floor anchoring

Note

If the UPS installation requires floor anchoring, the UPS installation must be anchored to
the floor, re-using the brackets that also secured the UPS to the pallets when shipped. For
easy determination of where to drill the holes, refer to the applicable drawings below
indicating hole positions and size.

Hole positions for floor anchors (stand-alone Enclosures)
Rear

Rear
5.78in/
147mm

5.11in/
130mm

Floor anchor holes:
Ø 10 mm

Floor anchor holes:
Ø 10 mm

5.11in/
130mm
5.11in/
130mm

 20.59 in/523 mm Enclosure

25in/650mm

 13.85 in/352 mm
Enclosure

5.11in/
130mm
5.11in/
130mm

0.92in/
23.5mm
26.3in/575mm

15.9in/404mm

 Refer to this drawing for floor anchor positions for 20.59 in/523 mm.
 Refer to this drawing for 13.85 in/352 mm.

20

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Mechanical assembly – Floor Anchoring

Recommended minimum number of floor bolts per Enclosure: 4 (1 in each corner).
Recommended floor bolt size: 5/16(3/8) in/8 mm.
Note

Floor anchoring of stand-alone systems
In seismic areas, it is recommended that the installation be bolted to the floor, and that the batteries be
secured in the Enclosure by the Battery Securing Brackets.
 For floor anchoring, use the 2 transport brackets that were used to secure the UPS to the pallet
during transport.
Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

Floor Anchoring
Bracket
(re-use of transport
bracket)

BATTERY UNIT

Serial:
Model:

BATTERY UNIT








 Align the 4 holes in the bottom angle of the Floor Anchoring Bracket on either side of the
Enlosures to the pre-drilled holes in the floor

Front Panel

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

21

Electrical Installation
System-Electrical Information
WARNING!
All electrical power and power control wiring must be installed by a qualified electrician,
and must comply with local and national regulations for maximum power rating.

10 kVA
8 kW

15 kVA
12 kW

20kVA
16 kW

30 kVA
24 kW

Input voltage / Bypass voltage (V)

3-phase
208Y/
120 V

3-phase
208Y/
120 V

3phase
208Y/
120 V

3-phase
208Y/
120 V

Input current (nominal, per phase) (A)

24.3

36.5

48.2

72.9

Maximum input current per phase (continuous, at
minimum mains voltage)

26.7

40.2

53.0

80.1

Input current protection for mains source or single
mains supply (external to UPS, not supplied) (A)

3x35

3x60

3x80

3x125

Input current protection for bypass source in dual mains
configuration (external to UPS, not supplied) (A)

35

60

80

125

Input frequency (Hz) range

40-70

40-70

40-70

40-70

Output voltage (on line). (V)
Minimum and maximum values (+/- 1%)

120/208

120/208

120/208

120/208

Output current (nominal, per phase) (A)

27.8

41.6

55.5

83.3

Maximum output current
(in bypass only at 110% overload per phase)

30.5

45.8

61.1

91.6

Neutral output current (with 100% switch mode load)
(A)

48.1

72.1

96.2

144.2

Output current protection (external to UPS, not
supplied) (A)

40

60

80

120

Output frequency range (Hz)

50/60

50/60

50/60

50/60

DC overcurrent protection and disconnect switch for
external safety:
DC voltage rating of the battery supply
Maximum available short-circuit current

27.8

41.8

55.7

83.5

+/- 192
10 kA

+/- 192
10 kA

+/- 192
10 kA

+/- 192
10 kA

UPS ratings 208 V

22

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Electrical Installation – System-Electrical Information

10 kVA
8 kW

15 kVA
12 kW

20kVA
16 kW

30 kVA
24 kW

Input voltage / Bypass voltage (V)

3-phase
220Y/
127 V

3-phase
220Y/
127 V

3-phase
220Y/
127 V

3-phase
220Y/
127 V

Input current (nominal, per phase) (A)

22.9

34.6

46.5

68.9

Maximum input current per phase (continuous, at
minimum mains voltage)

25.2

38.0

50.1

75.8

Input current protection for mains source or single
mains supply (external to UPS, not supplied) (A)

3x35

3x60

3x80

3x125

Input current protection for bypass source in dual mains
configuration (external to UPS, not supplied) (A)

35

60

80

125

Input frequency (Hz) range

40-70

40-70

40-70

40-70

Output voltage (on line). (V)
Minimum and maximum values (+/- 1%)

127/220

127/220

127/220

127/220

Output current (nominal, per phase) (A)

26.2

39.4

52.5

78.7

Maximum output current
(in bypass only at 110% overload per phase)

28.9

43.3

57.7

86.6

Neutral output current (with 100% switch mode load)
(A)

45.5

68.2

90.9

136.4

Output current protection (external to UPS, not
supplied) (A)

40

60

80

120

Output frequency range (Hz)

50/60

50/60

50/60

50/60

DC overcurrent protection and disconnect switch for
external safety:
DC voltage rating of the battery supply
Maximum available short-circuit current

26.4

39.6

52.7

78.9

+/- 192
10 kA

+/- 192
10 kA

+/- 192
10 kA

+/- 192
10 kA

UPS ratings 220 V

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

23

Electrical Installation – System-Electrical Information

Source connections
WARNING!
The UPS must be supplied from a 208Y/120 V or 220Y/127 V 4W + GND 60Hz
source.
CAUTION!
Verify clockwise phase-rotation (L1, L2, L3) and make sure a neutral connection is
present.
For recommended “Recommended current protection” , see The Site Preparation
section.
CAUTION!
The installation must comply with all local and national codes.

Refer to NEC Articles 310-15, 310-16 for further information.

8

24

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Electrical Installation – System-Electrical Information

One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA, 208V, 3 phase, single mains
Utility source
(provided by others)
3PH 208Y/120V
4 wire + ground

1
MIB
10kVA, 35A.T.
15kVA, 60A.T.
20kVA, 80A.T.
30kVA, 125A.T.

10kVA, 27.8A
15kVA, 41.7A
20kVA, 55.6A
30kVA, 83.3A

2

Maintenance
Bypass
Panel

10kVA, 27.8A
15kVA, 41.7A
20kVA, 55.6A
30kVA, 83.3A

Q1(UIS)
3P

10kVA, 27.8A
15kVA, 41.7A
20kVA, 55.6A
30kVA, 83.3A

XR Battery Cabinet 8
DC Input
Breaker

10kVA, 22.2A
15kVA, 33.3A
20kVA, 44.4A
30kVA, 66.6A
2

2

UPS
10kVA, 27.8A
15kVA, 41.7A
20kVA, 55.6A
30kVA, 83.3A

5

MBS
3P

Notes:
1. Must be 4 wire + ground WYE source provided by others.
2. Dashed lines between units (- - -) represent AC/DC cabling
provided by others.

10kVA, 27.8A
15kVA, 41.7A
20kVA, 55.6A
30kVA, 83.3A

2

Q2/UOS)
4P

Q3(BPS)
4P

3. Input overcurrent protection is based on 80% rating – any
deviation please contact APC.

F1, 3P

4. AC Power cabling is 4 wire + ground at 208VAC 3-phase.
5. Separate conduits, 2 wire + ground
6. UPS input and output cables must be in separate conduits.
7. Power wiring and control wiring must be in separate
conduits
8. XR Battery Enclosure can be bayed to UPS. Baying kit has
to be purchased as an option.
XR Battery Enclosure is available without breaker with DC
fuses only. Up to 4 XR Battery Enclosures can be connected
to UPS to extend backup time.

2

UPS System Output 10kVA, 15lVA,
20kVA and 30kVA
208V 3ph – 4 wire + ground or
120V 1ph – 2 wire + ground

9. Single mains installation is a default.
Dual Mains option requires custom entineering. Please refer
to APC Custom Engineering group and drawing# CEGSUVT10kF-SD for details.
10. Installation must comply with all applicable national and
local codes.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

25

Electrical Installation – System-Electrical Information

One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA, 220V, 3 phase, single mains
Utility source
(provided by others)
3PH 220Y/127V
4 wire + ground

1
MIB
10kVA, 35A.T.
15kVA, 60A.T.
20kVA, 80A.T.
30kVA, 125A.T.

10kVA, 26.2A
15kVA, 39.4A
20kVA, 52.5A
30kVA, 78.7A

2

Maintenance
Bypass
Panel

10kVA, 26.2A
15kVA, 39.4A
20kVA, 52.5A
30kVA, 78.7A

Q1(UIS)
3P

10kVA, 26.2A
15kVA, 39.4A
20kVA, 52.5A
30kVA, 78.7A

XR Battery Cabinet

8

DC Input
Breaker

10kVA, 22.2A
15kVA, 33.3A
20kVA, 44.4A
30kVA, 66.6A
2

2

UPS
10kVA, 26.2A
15kVA, 39.4A
20kVA, 52.5A
30kVA, 78.7A

5
MBS
3P

Notes:
1. Must be 4 wire + ground WYE source provided by others.
2. Dashed lines between units (- - -) represent AC/DC cabling
provided by others.
3. Input overcurrent protection is based on 80% rating – any
deviation please contact APC.

10kVA, 26.2A
15kVA, 39.4A
20kVA, 52.5A
30kVA, 78.7A

2

Q2/UOS)
4P

Q3(BPS)
4P
F1, 3P

4. AC Power cabling is 4 wire + ground at 208VAC 3-phase.
5. Separate conduits, 2 wire + ground
6. UPS input and output cables must be in separate conduits.
7. Power wiring and control wiring must be in separate
conduits
8. XR Battery Enclosure can be bayed to UPS. Baying kit has
to be purchased as an option.
XR Battery Enclosure is available without breaker with DC
fuses only. Up to 4 XR Battery Enclosures can be connected
to UPS to extend backup time.

2

UPS System Output 10kVA, 15kVA,
20kVA and 30kVA
220V 3ph – 4 wire + ground or
127V 1ph – 2 wire + ground

9. Single mains installation is a default.
Dual Mains option requires custom entineering. Please refer
to APC Custom Engineering group and drawing# CEGSUVT10kF-SD for details.
10. Installation must comply with all applicable national and
local codes.

26

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Electrical Installation – Wiring

Wiring
Make sure the UPS is in its location of use before wiring begins.
Note

CAUTION!
Verify clockwise phase-rotation (L1, L2, L3) and make sure a neutral connection is
present.
Power terminal lug diameter: minimum 0.2 in/6 mm.
Torque value: 45 lbf-in/7Nm.
Note

If floor anchoring is required, attach the Floor Anchoring Brackets to the UPS now.
Follow step 1 under Floor Anchoring (Option).
Note

Please leave a copy of your wiring diagram with the customer to facilitate maintenance
and troubleshooting.
Note

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

27

Input/Output Wiring – Single Mains (default)
The UPS is designed for both single (default) and dual mains installations. Follow the below steps to
install the UPS in a single-mains installation.
The illustrations show a 20.59 in/523 mm Enclosure, but installation procedures are
identical for 13.85 in/352 mm Enclosures).
Note

Wiring procedure – single mains


N

N






Conduit box
(top part)







EPO
Conduit

Input

Output

Conduit box
(bottom part)

MBP
Conduit

 Loosen the (6) M4 screws from the cover of the cable termination area on the rear, and remove.
 Loosen the (2) M4 screws (1 each side) from the top part of the Conduit Box. Loosen the M4
screws attaching it to the bottom part (2 screws in a 13.8 5in/352 mm Enclosure, 3 screws in a
20.59 in/523 mm Enclosure), and remove.

28

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

 Loosen the (4) M4 screws (2 each side) from the bottom part of the Conduit Box and remove.
 Punch 2 holes in the marked areas of the Conduit Box bottom to fit the size of the conduit pipes,
and reattach the Conduit Box bottom to the Enclosure, re-using the (4) M4 screws.
 Install conduit pipes in the Conduit Box.
 Run cables through the conduit pipes and the bottom of the Conduit Box, pull behind the bar
and up into the input/output area.
 Reinstall the top part of the Conduit Box to the Enclosure, following reverse installation
procedures.



Mains
input
cables
Neutral





L1
L2

L3

Neutral

N
N

L1
L2
L3



 Output
 cables


 Ground
cables

 Attach input cable lugs to L1, L2 and L3 input busbars (left side in the UPS – on the front of the
busbar), using the provided M6 torx screws. Attach output cable lugs to L1, L2 and L3 output
busbars, using the provided M6 torx screws. Attach N x 2 where shown, using the provided torx
screws.
 Attach Ground x 2 where shown, using the provided torx screws.
 Fasten cables with cable ties.
 Reinstall rear cover.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

29

Input/Output Wiring – Dual Mains
The UPS is designed for single mains installation as default. Follow the below instructions to install
the UPS in a dual-mains installation
The illustrations show 20.59 in/523 mm Enclosures, but the installation procedures are
identical for 13.85 in/352 mm Enclosures).
Note

Wiring procedure – dual mains



C



N







N

A






Conduit box
(bottom part)

Bypass

Input

EPO Conduit

Output

Conduit box
(top part)

B

MBP Conduit

 Loosen the (6) M4 screws from the cover of the cable termination area, and remove.
 Loosen the (2) M4 screws (1 each side) from the top part of the Conduit Box. Loosen the M4
screws attaching it to the bottom part (2 screws in a 13.8 5in/352 mm Enclosure, 3 screws in a
20.59 in/523 mm Enclosure), and remove.
 Loosen the (4) M4 screws (2 each side) from the bottom part of the Conduit Box and remove.

30

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Electrical Installation – Input/Output Wiring – Dual Mains

 Punch 3 holes in the Conduit Box bottom to fit the size of the conduit pipes, and reattach the
Conduit Box bottom to the Enclosure, re-using the (4) M4 screws.
 Install conduit pipes in the Conduit Box bottom.
 Run cables through the conduit pipes and the bottom of the Conduit Box. Guide the cables
behind the bar and up into the input/output area.
 Reinstall the top part of the Conduit Box to the Enclosure, following reverse deinstallation
procedures (described in a previous step).
 Remove the (2) M6 screws from Brackets A, B, and C and remove all 3 brackets.



Utility
input
cables





L1
L2

Neutral

Neutral

L3
N
L1
L2

N
L3
L1
L2
L3
N










Bypass
input
cables
Output
cables
Neutral

 Ground
cables

 Attach input cable lugs to L1, L2 and L3 input busbars (left side in the UPS – on the front of the
busbar), using the provided M6 torx screws. Attach bypass cable lugs to L1, L2, L3 bypass
busbars, using the provided torx screws. Attach output cable lugs to L1, L2, L3 output busbars,
using the provided torx screws.
Attach N x 3 where shown., using the provided torx screws.
 Attach Ground x 3 where shown.
 Fasten all cables with cable ties.
 Reinstall rear cover.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

31

External Battery Wiring
Wiring to battery bank or battery racks

L1
L2

L3
N
L1
L2

N
L3
L1
L2


Bat+

L3
N

N

N

Bat-

 Attach DC cables to upper part of busbars as shown.

For configurations including customer-supplied external batteries, refer to manufacturer’s
battery installation and maintenance instructions.

32

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Communication Wiring to EPO and
Optional Equipment

EPO switch must be connected to a NEC Class 2 wiring.
Note

Note

Use only 28-16AWG copper wire for the connection of the Emergency Power Off (EPO)
and other optional equipment. Keep all other wiring and uninsulated live parts separate of
other NEC Class 2 circuits.
Do not connect any circuits to the EPO terminal block unless it can be confirmed that the
circuit is a NEC Class 2 circuit.

Note

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

33

Electrical Installation – Communication Wiring to EPO and Optional Equipment

Pin connections J106 (XR Enclosure) and J108 (EPO)

L1
L2

L3
N
N
L1
L2
L3

J106 Pin Connections:
8

Ext. charging control return

7

External control of charging

6

Q3 active return

J108 Pin Connections:

5

Q3 active

1

Normally open EPO

4

Battery measurement supply*

2

Normally open EPO return

3

Battery unit quantity*

3

Normally closed EPO

2

Max. battery temperature*

4

Normally closed EPO return

1

Battery measurement return*

5

+24V SELV supply

6

SELV ground

* Should be used with APC XR
Enclosures only

Pin connections J106 (UPS) to J200 (XR Enclosure - option)
Pins 1 through 4 are for battery measurement (only applicable to APC XR Enclosures).
Pins 5 & 6 are for external maintenance bypass Q3. When Q3 is closed, signals are fed back to the
UPS controller.
Pins 7 & 8 are for external charge control. When 7 & 8 are closed, the UPS charges batteries with a
pre-defined percentage (0-100%) of the maximum charging power. To be used in generator
applications, or if special codes requires control of charging.

34

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Electrical Installation – Communication Wiring to EPO and Optional

When connecting the Q3 auxiliary signal, use gold-plated N/C auxiliary switch on Q3.
Note

XR Enclosure, APC Maintenance Bypass Panel, and Generator Control wiring
J106
8

Charging control switch

7
6

Q3
switch

5
4

4

3

3

2

2

1

1
J200 (XR Batteries)

Pins 1 through 4 are for battery measurement (only applicable to APC XR Enclosures).
Pins 5 through 6 are for external maintenance bypass Q3.
Pins 7 and 8 are for external charge control.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

35

Electrical Installation – Communication Wiring to EPO and Optional Equipment

Pin connections J108 (for EPO wiring options)
EPO switch wiring. The UPS must be connected to either a dry contact or a 24VDC Emergency

Power Off (EPO) switch.
Connect the EPO cable, using one of the following 4 wiring configurations.
1: Dry Contracts
Normally Open

J108
1
2

EPO circuit

EPO is activated when pin 1 is
connected to pins 3, and 5

3
4
5
6

2: +24V Normally Open J108
1
2

EPO circuit

3
4
5

EPO is activated when an
isolated SELV 24VDC voltage
is supplied on pin 1 with
reference to pin 2.

6

3: Dry Contacts
Normally Closed

J108
1
2
3
4

EPO circuit

5

EPO is activated when a
connection from pin 3 to pin 5
is opened

6

4: +24V Normally
Closed

J108
1
2
3
4
5
6

36

EPO circuit

EPO is activated when a SELV
24VDC voltage removed from
pin 3 with reference to pin 5

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Connection of APC Humidity Sensor
Front panel removal


!

Output

Pwr

Zone
Probe

10/100Base-T

Reset

10/100
AP9619 Network
Management Card

EM



Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT



 To remove a Front Panel, turn screw clockwise to unlocked position.
 Pull top of Front Panel free of UPS.
 Lift the Front Panel free of the two slots at the bottom of the Enclosure.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

37

Electrical Installation – Connection of APC Humidity Sensor

The Humidity Sensor is provided in a plastic bag attached to the front of the UPS.
Note

!

Output

Pwr

!

Output

Pwr

Probe



Zone
Probe

Zone

10/100Base-T

10/100Base-T

Reset

Reset

10/100
AP9619 Network
Management Card

10/100
AP9619 Network
Management Card

Serial:
Model:

Serial:
Model:

BATTERY UNIT

EM

EM

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

Serial:
Model:

Serial:
Model:

BATTERY UNIT

BATTERY UNIT

BATTERY UNIT

Serial:
Model:

Serial:
Model:

BATTERY UNIT

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

Serial:
Model:

Serial:
Model:

BATTERY UNIT

BATTERY UNIT

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT



BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

Serial:
Model:

BATTERY UNIT

BATTERY UNIT

Serial:
Model:

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT

Serial:
Model:

BATTERY UNIT
Serial:
Model:

Serial:
Model:

Serial:
Model:

BATTERY UNIT

BATTERY UNIT

BATTERY UNIT







 Remove the 2 screws from the cable inlet at the front – and remove cable-inlet plate.
 Guide the cable through the hole in the bottom plate and up through the cable inlet.
See “Foot print” on page 8 to locate the communication cable inlet.

38

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Electrical Installation – Connection of APC Humidity Sensor

 Guide the cable up alongside the side panel and insert the Humidity Sensor plug into the socket
marked “Probe”.
 Fasten the cable to the side panel with enclosed cable ties.
 Remount the cable-inlet plate.
 Place the Humidity Sensor where applicable.

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

39

Wiring Verification Procedure
Do not connect batteries in the UPS.
Note

Use following procedure to verify that the UPS has been wired properly:








1. If your installation includes an XR Enclosure, make sure that the DC breaker (if
available) is in the OFF position and that both 125A fuses are removed from the
XR Enclosure.
2. Check that the power wiring is torqued to 45 lbf.in/7Nm.
3. If your installation includes an XR Enclosure, remount the 125A fuses in the XR
Enclosure and check that the DC breaker (if available) on the XR Battery
Enclosure is in the ON position.
4. Please leave a wiring diagram on site for service / technical support personnel.
If a problem occurs, phone Customer Support at (1) (800) 800-4272 (US and Canada).
Refer to rear cover for contact numbers in other countries.

Note

If you have purchased any optional equipment, refer to product-specific manuals.
Note

Start-up must be performed by APC authorized personnel only. Call APC to scedule a
free 5x8 Start-up service.
Note

40

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Installation Site Checklist
This checklist should be completed by the electrician after the wiring has been completed:

Installed at (company name, date, contact)__________________________________________

Name and telephone number of electrician: ___________________________________________

UPS serial number: ______________________________________________________________

Input Circuit Breaker size and type: _________________________________________________

Output fuse size and type: ________________________________________________________

Location of protection devices (room):______________________________________________

Breaker ID: ___________________________________________________________________

EPO type: ____________________________________________________________________

Wire size and type: _____________________________________________________________

Ground connection method and location: ________________________________________

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

41

APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer
support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer
support information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact an APC Customer Support center by telephone or e-mail.
– Regional centers:
Direct InfraStruXure Customer Support Line

(1)(877)537-0607 (toll free)

APC headquarters U.S., Canada

(1)(800)800-4272 (toll free)

Latin America

(1)(401)789-5735 (USA)

Europe, Middle East, Africa

(353)(91)702000 (Ireland)

Japan

(0) 35434-2021

Australia, New Zealand, South Pacific area

(61) (2) 9955 9366 (Australia)

– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
Contact the APC representative or other distributor from whom you purchased your APC product for
information on how to obtain local customer support.

Entire contents copyright © 2005 American Power Conversion. All rights reserved.
Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and
Smart-UPS VT are trademarks of American Power Conversion Corporation and may be
registered in some jurisdictions. All other trademarks, product names, and corporate names
are the property of their respective owners and are used for informational purposes only.

990-1598B

*990-1598B*

06/2005



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Modify Date                     : 2005:12:12 15:17:05-05:00
Create Date                     : 2005:06:23 09:08:39Z
Creator                         : FrameMaker 6.0
Page Count                      : 48
Page Mode                       : UseOutlines
About                           : uuid:9ed8e868-e3e0-11d9-8e5e-0050e466b204
Producer                        : Acrobat Distiller 6.0.1 for Macintosh
Mod Date                        : 2005:12:12 15:17:05-05:00
Creation Date                   : 2005:06:23 09:08:39Z
Creator Tool                    : FrameMaker 6.0
Metadata Date                   : 2005:12:12 15:17:05-05:00
Document ID                     : uuid:37e48f24-e3da-11d9-8e5e-0050e466b204
Format                          : application/pdf
Title                           : untitled
Has XFA                         : No
EXIF Metadata provided by EXIF.tools

Navigation menu