Tork Catalog

User Manual: Tork-Catalog

Open the PDF directly: View PDF PDF.
Page Count: 80

DownloadTork-Catalog
Open PDF In BrowserView PDF
PRODUCT CATALOG
2011

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com
responsible

energy

A DIVISION OF

NSi INDUSTRIES, LLC

NSi Industries LLC

About Us
Since 1975, NSi’s strength is in the unique products that we bring to
the market, combined with our exceptional ability to provide quality
TORK® brand products manufactured in the company’s Mount Vernon
facility. TORK® is NSi Industries largest brand, covering the categories of
Electromechanical and Digital Time Switches, Signaling and Alert Devices,
Pool and Spa Controls, Residential Timers, Photocontrols and Occupancy
Sensors.
For over 85 years, TORK brand recognition and reputation for quality and
design make it the most specified brand in the industry. The TORK brand
has a rich history beginning in the 1920s when the company introduced
the first electromechanical time switch to the marketplace. Currently, TORK’s
time switches maintain energy efficiency through lighting control in such
high profile places as the Empire State Building, Washington DC Parks and
Recreation, The Triborough Bridge, The Met Life Building and many more
institutions across the country. As the most specified brand of time switches in the
industry, TORK enjoys the hearty respect of engineers and project planners
across all channels of distribution.
In the past several years, we’ve introduced a number of TORK time
switches, in-wall and plug-in timers to meet increasingly specific needs in
the marketplace. We’ve also added a line of installer-friendly pool and
spa panels and time switches, and are proud to offer essential pool safety
products that meet and exceed federal requirements for safe pools. We
look forward to designing and engineering more of our Responsible Energy
products, helping save money and the environment through responsible and
minimal use of energy.

TABLE OF CONTENTS

TABLE OF CONTENTS

ENERGY CODE REFERENCE GUIDE  .  .  .  .  .  .  .  .  .  .  .  .  . 7
PHOTOCONTROLS

QUICK LOOK FEATURES & COMMON FEATURES .  .  .
2100 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
2110 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
2000 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
2001 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
2020 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
3000 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
5000M SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
2005A, 2007A, 2008A SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
5200 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
5400 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
5737 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
PHOTOCONTROL ACCESSORIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

11
13
14
15
16
17
18
19
20
21
22
23
24

ELECTROMECHANICAL

QUICK LOOK FEATURES & COMMON FEATURES .  .  . 27
TU40 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 29
1100 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31
7000 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33
7000Z SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35
8000 SERIES, DUTY CYCLE .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37
8000 SERIES, REPEATING VARIABLE CYCLE .  .  .  .  .  . 39
WH2  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 40
1800 SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 41
W SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43
T900 SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 45
TW SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 47
TZ SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 49
ELECTROMECHANICAL ENCLOSURES
& DIMENSIONS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 153
DIGITAL

QUICK LOOK FEATURES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 53
DTU40  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 55

DTWH40 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 55
E SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 57
E-PB SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 57
EW SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59
EWZ SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61
DG100 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 63
DZS SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65
DTS SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 67
DW SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 69
DZM SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 71
ELC SERIES, 1 & 2 ZONE  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 73
ELC SERIES, 4, 8 &12 ZONE .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 75
LC200 SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 77
DGU SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79
DGLC SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79
DLC400BP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 81
LD SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 83
DGS SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 85
EJWT & E500T SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 87
DIN SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 89
SMC  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 91
5401 SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 92
HPS STARTER .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 93
TRP SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94
DIGITAL ENCLOSURES & DIMENSIONS .  .  .  .  .  .  .  .  . 153
IN-WALL TIMERS

QUICK LOOK FEATURES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 97
SS720A SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 98
SS700Z SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 99
SS721Z SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 99
701A SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 101
711A SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 101
SSA SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 102
SS SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 103

D SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 104
A SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105
C SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106
OCCUPANCY SENSORS

SENSOR TECHNOLOGY & PLACEMENT GUIDE .  .  .  . 109
OSWS SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 110
OSC15PLS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 111
OSC12PL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 112
OSC5PL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 112
OSC20UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
OSC SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 114
ELS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 115
TRP-U .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 116
PLUG-IN TIMERS

400A SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
400D SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
600A SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
600D SERIES .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
800 SERIES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

119
120
121
122
123

TORK ALERT

MECHANICAL STROBE HORNS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
MECHANICAL HORNS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
MULTI-TONE ELECTRONIC HORNS .  .  .  .  .  .  .  .  .  .  .  .
HEAVY DUTY BELLS  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
BELLS & BUZZERS  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
CHIMES & CHIME KITS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
WEATHERPROOF MOTOR DRIVEN SIREN  .  .  .  .  .  .  .
MANUAL FIRE ALARM  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
TELEPHONE STROBE .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
TELEPHONE HORN .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
TELEPHONE RELAY .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
WALL CLOCKS  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
ELECTRIC DOOR OPENERS  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
PUSH-BUTTONS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

127
127
128
128
129
129
130
130
131
131
132
132
133
134

WARNING LIGHTS, INDUSTRIAL .  .  .  .  .  .  .  .  .  .  .  .  . 135
WARNING LIGHTS, VEHICULAR .  .  .  .  .  .  .  .  .  .  .  .  .  . 136
POWER SUPPLY UNITS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137
TRANSFORMERS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137
ACCESSORIES/REPLACEMENT PARTS/DIMENSIONS 138
POOL & SPA

PP PANEL SERIES TIMERS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141
PFP PANEL SERIES TIMERS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143
1100 SERIES TIMERS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144
DW200B TIMER .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 145
P1100 SERIES, 24 HOUR
ELECTROMECHANICAL MECHANISMS .  .  .  .  .  .  .  .  .  . 147
P1100 SERIES, 7 DAY DIGITAL MECHANISMS  .  .  . 148
JUNCTION BOXES  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148
STINGL SR-500 & SR-500PS, SVRS  .  .  .  .  .  .  .  .  .  . 149
LAYERS OF PROTECTION .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 150
ANTI-ENTRAPMENT DRAIN COVERS .  .  .  .  .  .  .  .  .  .  . 151
MAGNALATCH SELF-LATCHING GATE CLOSURES .  . 152
TRUCLOSE SELF-CLOSING GATE HINGES . . . . . . . .152
POOL&SPA SAFETY ACCESSORIES  .  .  .  .  .  .  .  .  .  .  .  . 152
ENCLOSURE DIMENSIONS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 153
ALPHANUMERIC INDEX  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 155

LA
N
AR
CH
ITE
CT
U

energy
saving
solutions

Each of these marked products have features that decrease
energy consumption and/or damage to the environment by one
or more of the following:
• Timed control, Photocontrol and/or Astronomic control of on
responsible
energy and off functions of lighting, fans, pumps and appliances 
• Timed control of systems or multiple zones of lighting
• Photo or occupancy sensing control of lighting
• Supercapacitor backup, no batteries to replace or dispose.
• Helps meet CA Title 24, ASHRAE , IECC and other
standards for responsible building products

Small Space, Meeting Rooms, Restrooms, Storage Spaces: Occupancy Sensors, Interval Timers
The first zone includes small spaces such as offices, restrooms and storage areas places where people may not occupy the space continuously. Individual wall switch
replacement provides low cost installation, with occupancy sensors and interval timers
as the best solution. In the event that wall switches provide proper coverage for the
occupancy sensor, ceiling mounted options are available.

FIC
ES

energy

< Use the Quick Reference Energy
Code Guide for approved products.

responsible

energy

RE
CE
P

TIO

N

responsible

ZONE 1: SMALL SPACE

Responsible Energy

OF

< Responsible Energy is the mark
of TORK’s commitment to developing
and manufacturing energy saving,
environmentally friendly products.

FIC
ES

solutions

The first way to save energy begins with eliminating lighting when it isn't needed.
As with exterior lighting, an efficient design matches controls to the typical use of the
area.

OF

energy
saving

INTERIOR LIGHTING ZONES

RA
L&

ENERGY CODE
REFERENCE GUIDE

ZONE 2: LARGE SPACE
Small Space, Meeting Rooms, Restrooms, Storage Spaces: Time of Day with Override,
Occupancy Sensors

CALIFORNIA Title 24

LO

T

The first zone includes small spaces such as offices, restrooms and storage areas places where people may not occupy the space continuously. Individual wall switch
replacement provides low cost installation, with occupancy sensors and interval
timers as the best solution. In the event that wall switches provide proper coverage
for the occupancy sensor, ceiling mounted options are available.

ZONE 3: HARVESTING LIGHT

CE

ON

T

RO

EXTERIOR LIGHTING ZONES

EN

When ambient light levels drop at dusk, lighting is needed to provide safety and
security. BUT: Does all lighting need to be on all night long? The proper selection
of lighting controls is essential to ensuring that energy is only used when needed.
An efficient lighting control design creates zones of light levels that can be varied
by time at night.

Large of Small Spaces with Natural Light: Light Sensors, Light Sensors with Occupancy,
Astronomic Timers.
A third zone that uses daylighting control can be added to wither of the first two
zones. light sensors can shut off a portion of the lighting when windows or skylights
contribute sufficient natural light to the area. This "harvesting" of light is an
excellent, green way to conserve energy. (NOTE: Energy codes vary on the stated
maximum time, but shorter times can give more energy savings).

E

FIC
FIC

The first zone gives a minimum light level where security is the primary
need. Determine what lighting is necessary, such as building-mounted
wallpacks and a portion of the parking lot lighting. These should be on
from dusk to dawn, and are best controlled by a photosensor device.

OF

ST

RE

Security Lighting (all night): Photocontrols, Photosensor controls

OF

WA
R

EH

OU

SE

ZONE 1: MINIMUM LIGHT LEVEL / DUSK TO DAWN

E

RO

O

M

OF

RE

FIC

E

ST

RO

O

M

CO

NF

ER

FR

B
RO REA
OM K

OM

PA
R

KIN

G

ASHRAE 90.1

ZONE 2: HIGHER LIGHT LEVEL / DUSK TO TIME OFF

FRONT PARKING LOT

Safety & Architectural Lighting (not necessary all night): Photosensor/Timebased controls, Astronomic controls
The second zone provides a higher light level for safety, when people
are normally present. Maximum levels for the parking lot and all walkway lighting are needed. These lights are best controlled by a combination photosensor and time-based device to allow shut-off during
the night. The astronomic-calculated sunset/time control can also be
useful.

ZONE 3: ARCHITECTURAL / TIMED DUSK TO TIMED OFF

ARCHITECTURAL & LANDSCAPING
DOCKS & BACK
PARKING
LOT

CONFERENCE ROOM

RECEPTION
OFFICES

WAREHOUSE

OFFICES
RESTROOM

RESTROOM

Building Facade, Landscape and Signage: Astronomic controls
The third zone covers architectural lighting for building facade or landscape and signs. These are best controlled with an astronomic-calculated
sunset/time control.

TORK 7

OFFICE
OFFICE
OFFICE

BREAK
ROOM

TORK 8

PHOTOCONTROLS

FEATURES
QUICK LOOK

COMMON FEATURES
CHOICE OF PHOTOCELLS
Cadmium sulphide, epoxysealed cells. Available in 1⁄2”
and 1".

2100
SERIES

2110
SERIES

2000
SERIES

2001
SERIES

2020
SERIES

3000
SERIES

5000M
SERIES

2005A
SERIES

5200
SERIES

5737
SERIES

Page

13

14

15

16

17

18

19

20

21

23

Mounting

Conduit

Conduit

Conduit

Conduit

Conduit

Flush

Turn-Lock

Turn-Lock

Turn-Lock

Turn-Lock

Yes

Yes

Adjustable Swivel
Housing

Die Cast
Die Cast Zinc Aluminum

UV Stabilized UV Stabilized UV Stabilized
Plastic
Plastic
Plastic

UV Stabilized
Plastic

Lexan®

Lexan®

Lexan®

Lexan®

1 - 5 fc

1 - 5 fc

1 to 3 fc

1 to 3 fc

1.5 fc

5 fc

Turn ON Light Level

1 - 5 fc

1 - 5 fc

1 - 5 fc

1 - 5 fc

Adjustable light level
adjustment

Yes

Yes

Yes

Yes

Turn OFF Ratio

3:1

3:1

3:1

3:1

3:1

3:1

5:1

3:1

1.5:1

1.5:1

Time Delay ON

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Instant

Instant

Instant

Time Delay OFF

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Light Sensor

CdS

CdS

CdS

CdS

CdS

CdS

CdS

CdS

Silicon Diode

Silicon Diode

CFL Compatible

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Surge Protection
Photo Timer

TOUGH ENCLOSURES
All conduit and flush mounted
models utilize die-cast zinc,
die cast aluminum, or genuine
Lexan® materials. All turn-lock
models utilize high impact UV
stabilized polypropylene, ABS,
PBT or Lexan® materials.

CHOICE OF MOUNTING
ORIENTATION
Models are available in fixed
position or 180° swivel.

DEPENDABLE performance
Built-in time delay prevents false
switching due to light from passing
highway vehicles, lightning, etc.
Instant response is available in
turn-lock models (5200 Series).

TURN-LOCKS MEET ANSI C136.10

Yes

All models meet the current ANSI
requirements for locking-type
prongs and color coded voltage
designations. Locking prongs are
solid brass.

TORK® Photocontrols are
designed and manufactured with
components which adhere to
the highest industry standards.
Trained personnel and in-process
quality procedures ensure that
every unit meets our strictest
quality standards.

TORK 11

Color-Coded Dome
Grey
105-130VAC
Maroon 208-277VAC
Blue
105-285VAC
Yellow
480VAC
Green
347VAC

TORK 12

2100 SERIES

SPECIFICATIONS

SPECIFICATION GRADE
1/2" CONDUIT MOUNTING
DIE CAST ZINC
PHOTOCONTROL

ON/OFF: Turn ON is 1 to 5fc, Turn OFF is 3
to 15fc, without the slide in position. ON/OFF
adjustment is easily made by moving a slide
cover. No tools required.

APPLICATIONS

SPECIFICATIONS

SPECIFICATION GRADE
1/2" CONDUIT MOUNTING
DIE CAST ALUMINUM
PHOTOCONTROL

ON/OFF: Turn ON is 1 to 5fc, Turn OFF is 3
to 15fc, without the slide in position. ON/OFF
adjustment is easily made by moving a slide
cover. No tools required.

TIME DELAY: ON and OFF.

TIME DELAY: ON and OFF.

CELL: Cadmium sulphide, epoxy-coated, 1"
diameter.

CELL: Cadmium sulphide, epoxy-coated, 1⁄2”
diameter. Model 2117 is 1" cell.

CONTACTS: Remain closed between dusk and
dawn. (The unit fails in the ON position).

Parking lot lighting
Building perimeter lighting
Outdoor signage

2110 SERIES

LEAD WIRES: Three color coded, minimum
6” wire leads, #16AWG, rated for 105˚C.

APPLICATIONS

CONTACTS: Remain closed between dusk and
dawn (the unit fails in the ON position).

2117

Parking lot lighting
Building perimeter lighting
Outdoor signage

LEAD WIRES: Three color coded, minimum
6” wire leads, #16AWG, rated for 105˚C. (2117
#10AWG red and black).

2115 & 2116

POWER CONSUMPTION:
Averages under 1 watt.

POWER CONSUMPTION:
Averages under 1 watt.

TEMPERATURE RANGE:
-40˚ to +140˚F (-40˚ to +60˚C).

TEMPERATURE RANGE:
-40˚ to +140˚F (-40˚ to +60˚C).

FAIL MODE: ON.

FAIL MODE: ON.

WARRANTY: 5 years.

WARRANTY: 5 years.

CONTACT RATINGS

CONTACT RATINGS

RATING
CATALOG
SWITCH
WIRING
DIAGRAMS
NO.
TUNGSTEN
BALLAST

FEATURES
OPERATION: Delay of up to two minutes
to prevent false switching due to light from
passing vehicles, lightning, etc.

2101

SPST

2000W

1800VA

2104

SPST

2000W

1800VA

2107

SPST

2000W

1800W

2000 SERIES

HOUSING: Heavy Duty die cast zinc
housing and base. Gasketed for maximum
weather protection.

WIRING DIAGRAMS

VOLTAGE
50-60Hz

2101

60012

120VAC

2104

60013

208-277VAC

2107

60031

120/277VAC

73866

62020

Mounting Bracket

2100
SERIESDie case aluminum housing
HOUSING:

and base. Gasketed for weather protection.
2000 SERIES

SWITCH

2115

RATING
TUNGSTEN

BALLAST

SPST

2000W

1800VA

2116

SPST

3470-4620W

2080-2770VA

2117*

SPST

3000W

3000VA

2100 WIRING
SERIES

DIAGRAMS

ORDERING INFO

ORDERING INFO
UPC
CODE

OPERATION: Delay of up to two minutes
to prevent false switching due to light from
passing vehicles, lightning, etc.

ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

CATALOG
NO.

FEATURES

CATALOG
NO.

CATALOG
NO.

UPC
CODE

VOLTAGE
50-60Hz

2115

60032

120VAC

2116

60033

208-277VAC

2117*

60037

120VAC

73866

62020

Mounting Bracket

*Not UL or CSA rated.

PHOTOCONTROLS
TORK 13

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 14

2000 SERIES

SPECIFICATIONS

1/2" CONDUIT MOUNTING
FIXED POSITION, LEXAN® HOUSING
WITH WEATHERPROOF SEALANT
PHOTOCONTROL

ON/OFF: Turn ON is 1 to 5fc. Turn OFF is 3
to 15fc, without the slide in position. ON/OFF
adjustment is easily made by moving a slide
cover. No tools required.

2001 SERIES

SPECIFICATIONS

1/2" CONDUIT MOUNTING
180° SWIVEL, LEXAN® HOUSING
PHOTOCONTROL

ON/OFF: Turn ON is 1 to 5fc. Turn OFF is 3
to 15fc, without the slide in position. ON/OFF
adjustment is easily made by moving a slide
cover. No tools required.

TIME DELAY: ON and OFF.

TIME DELAY: ON and OFF.

Cadmium sulphide, epoxy-coated, 1⁄2”

CELL:
diameter.

APPLICATIONS

CONTACTS: Remain closed between dusk and
dawn. (The unit fails in the ON position).

Flood lamp
Patio lamp
Decorative lighting

LEAD WIRES: Three color coded, minimum
6” wire leads, #16AWG, rated for 105˚C.

CELL: Cadmium sulphide, epoxy-coated, 1⁄2”
diameter.

APPLICATIONS

CONTACTS: Remain closed between dusk and
dawn. (The unit fails in the ON position).

Flood lamp
Patio lamp
Decorative lighting

LEAD WIRES: Three color coded, minimum
6” wire leads, #16AWG, rated for 105˚C.

POWER CONSUMPTION:
Averages under 1 watt.

POWER CONSUMPTION:
Averages under 1 watt.

TEMPERATURE RANGE:
-40˚ to +140˚F (-40˚ to +60˚C).

TEMPERATURE RANGE:
-40˚ to +140˚F (-40˚ to +60˚C).

FAIL MODE: ON.

FAIL MODE: ON.

WARRANTY: 5 years.

WARRANTY: 5 years.

CONTACT RATINGS
RATING
CATALOG
WIRING DIAGRAMS
SWITCH
NO.
TUNGSTEN
BALLAST

FEATURES
OPERATION: Delay up to two minutes to
prevent false switching due to light from
passing vehicles, lightning, etc.

2000

SPST

2000W

1800VA

2000-2

SPST

3470-4620W

2080-2770VA

2000-7*

SPST

2000W

1800VA

HOUSING: All Lexan® enclosures are
impact and vandal resistant. Translucent
Lexan® Dome prolongs cell life by further
screening out ultraviolet rays. Dome
and base are ultrasonically welded for
maximum strength.

WIRING DIAGRAMS
2000 SERIES

ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

CONTACT RATINGS
FEATURES
OPERATION: Delay up to two minutes to
prevent false switching due to light from
passing vehicles, lightning, etc.

CATALOG
NO.

SWITCH

2001
2002

RATING
TUNGSTEN

BALLAST

SPST

2000W

1800VA

SPST

3470-4620W

2080-2770VA

HOUSING: All Lexan® enclosures are
impact and vandal resistant. Translucent
Lexan® Dome prolongs cell life by further
2100 SERIES
screening out ultraviolet rays. Dome
and base are ultrasonically welded for
maximum strength.

WIRING DIAGRAMS

Move Slide for Earlier
or Later Turn ON

ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

ORDERING INFO

ORDERING INFO

CATALOG
NO.

UPC
CODE

VOLTAGE
50-60Hz

CATALOG
NO.

UPC
CODE

VOLTAGE
50-60Hz

2000

60017

120

2001

60015

120

2000-2

60018

208-277

2002

60016

208-277

2000-7*

62023

120/277

73866

62020

Mounting Bracket

73866

62020

Mounting Bracket

•
•

Red

Lamp

•

Move Slide for Earlier
or Later Turn ON

•240V
L2 •
L1

*Model 2000-7 has a cadmium sulphide, 1” epoxy cell. Also
UL listed and CSA certified.

Black Line
White Neutral

(Black) Line
(White)

(Red)

•

Lamp

For 277VAC:
L1 - Line
L2 - Neutral

PHOTOCONTROLS
TORK 15

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 16

2020 SERIES

SPECIFICATIONS

1/2" CONDUIT MOUNTING
180° SWIVEL, LEXAN® HOUSING
PHOTOCONTROL

ON/OFF: Turn ON is 1 to 5fc. Turn OFF is
3 to 15fc.

ON/OFF: Turn ON is 1 to 5fc. Turn OFF is
3 to 15fc.

CELL: Cadmium sulphide, epoxy-coated,
1⁄2” diameter.

CELL: Cadmium sulphide, epoxy-coated,
1⁄2” diameter.

POWER CONSUMPTION:
Averages under 1 watt.

Ideal for applications where it
is essential to aim the photocell
in an exact direction to sense
natural light but avoid artificial
light.

FLUSH MOUNTING
LEXAN® HOUSING
PHOTOCONTROL

TIME DELAY: ON and OFF.

LEAD WIRES: Three color coded,
minimum 6” wire leads, #16AWG, rated
for 105˚C.

Flood and patio lamps
Decorative lighting

SPECIFICATIONS

TIME DELAY: ON and OFF.

CONTACTS: Normally closed (the unit
fails in the ON position).

APPLICATIONS

3000 SERIES

CONTACTS: Normally closed (the unit
fails in the ON position).

APPLICATIONS
Flush Mounting
Model 3010

Pole lanterns
Lawn lighting
Walkways

LEAD WIRES: Three color coded,
minimum 6” wire leads, #16AWG, rated
for 105˚C.
POWER CONSUMPTION:
Averages under 1 watt.

TEMPERATURE RANGE:
-40˚ to +140˚F (-40˚ to +60˚C).

TEMPERATURE RANGE:
-40˚ to +140˚F (-40˚ to +60˚C).

FAIL MODE: ON.

FAIL MODE: ON.

WARRANTY: 5 years.

WARRANTY: 5 years.

CONTACT RATINGS
RATING

CATALOG

SWITCH
NO.
WIRING
DIAGRAMS
TUNGSTEN

CONTACT RATINGS
FEATURES

CATALOG
NO.

OPERATION: Delay up to two minutes to
prevent false switching due to light from
passing vehicles, lightning, etc.

SWITCH

UPC
CODE

VOLTAGE
50-60Hz

2021

60024

120

2022

60025

208-277

73866

62020

Mounting Bracket

BALLAST

SPST

2000W

1800VA

2022

SPST

3470-4620W

2080-2770VA

WIRING DIAGRAMS
120V
MODELS

ORDERING INFO
CATALOG
NO.

TUNGSTEN

2021

HOUSING: All Lexan® enclosures are
impact and vandal resistant, cover and base
are ultrasonically welded for maximum
strength.
ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

FEATURES

RATING

Line

•Neutral
•

(Black)
(White)

(Red)

Lamp

L2

HOUSING & MOUNTING: Control housing
is weather-resistant molded Lexan® with
ultrasonically welded seams.
MODEL 3000: Flush mounting through .6875”
hole in post lantern or lighting fixture, 3⁄8” NPT,
stem 3⁄4” long. Gasket and nut supplied.
MODEL 3010: flush mounting into standard,
raintight junction box. Includes plate and gasket
to fit FS type outdoor junction box.
ENERGY SAVINGS: Works with screw base
CFLs and LED lamps.

•

3000

SPST

2000W

1800VA

3002

SPST

3470-4620W

2080-2770VA

3006*

SPST

1500W

1200VA

3010

SPST

2000W

1800VA

WIRING DIAGRAMS
120V
MODEL

LAMP
LINE BLK
120V

RED

NEUT. WHITE

ORDERING INFO

208-277V
MODELS

L1

OPERATION: Delay up to two minutes to
prevent false switching due to light from passing
vehicles, lightning, etc.

BALLAST

Line

•

(Black)

•

(White)

240V
Neutral

(Red)

•

For 277VAC
L1 - Line
L2 - Neutral

Lamp

CATALOG
NO.

UPC
CODE

VOLTAGE
50-60Hz

3000

60020

120

3002

60019

208-277

3006*

60026

347

3010

60021

120

208-277V
MODEL
For 277VAC:
L1 - Line
L2 - Neutral
LINE BLK

LAMP
RED

240V
WHITE

*CSA certified only.

PHOTOCONTROLS
TORK 17

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 18

5000M SERIES

SPECIFICATIONS

DELAYED RESPONSE UTILITY GRADE
MOV SURGE ARRESTOR
PHOTOCONTROL

ON/OFF: Turn-ON is 1 to 3 fc. Turn-OFF to Turn-ON
ratio is 5 max.
TIME DELAY: ON and OFF.
CELL: Cadmium sulphide photocell responds to the
light spectrum near to that of a human eye. Resists
effects of moisture and airborne contaminants.

APPLICATIONS

RELAY: Bi-metal provides positive snap action
switching, reducing bounce and prolonging contact life.

For use on streets, highways and
other luminaries equipped with
locking type receptacles, where
most stringent surge protection
is needed.

SURGE ARRESTOR: 380 joule MOV (metal oxide
varistor) exceeds ANSI and NEMA requirements.
LOCKING PRONGS: Solid brass for maximum
corrosion resistance and electrical conductivity.
TEMPERATURE RANGE:
-40˚ to +140˚F (-40˚ to +60˚C).

OPERATION: Delayed response prevents false
switching due to light from vehicles or lighting, etc.
STANDARDS: Meets ANSI C136.10 including color
designations. Also meets EEI NEMA standards.

ON/OFF: Turn-ON is 1 to 3 fc. Turn-OFF to TurnON is 3 average.

QUICK RESPONSE
TURN-LOCK MOUNTING
PHOTOCONTROL

TIME DELAY: Instant ON/3-5 seconds OFF.
CELL: Cadmium sulphide photocell responds to the
light spectrum near to that of a human eye. Resists
effects of moisture and airborne contaminants.

APPLICATIONS

CONTACTS: Solid brass prongs for maximum
corrosion resistance and electrical conductivity.

For use on streets, highways and
other luminaries equipped with
locking type receptacles, where
instant response is required.

SURGE ARRESTOR: 360 joules MOV exceeds
NEMA and ANSI requirements.
RELAY: Positive snap action switching, reducing
bounce and prolonging contact life.

Complies with ANSI C136.10 and
EEI NEMA standards.

TEMPERATURE RANGE:
-40˚ to +158˚F (-40˚ to +70˚C).

FAIL MODE: ON.

FAIL MODE: ON.

WARRANTY: 3 years.

WARRANTY: 3 years.

CATALOG
NO.

LIGHT SENSOR

5001M

RATING
TUNGSTEN

BALLAST

1"

1200W

1800VA

5004M

1"

3470-4620W

2080-2770VA

5007M

1⁄2"

2000W
3470-4620W

1800VA
2080-2770VA

HOUSING: Lexan® UV Stabilized, permanent color
with UV resistant clear acrylic window. Models 5026M
and 5008M with polypropylene dome. Provides high
impact, flammability resistance and electrically safe
operation.

5008M*

1"

1000W

1800VA

5021M

1⁄2"

2000W

1800VA

ENERGY SAVINGS: Works with screw base CFLs
and LED lamps.

5024M

1⁄2"

3470-4620W

2080-2770VA

5026M**

1⁄2"

1000W

1800VA

ORDERING INFO
CATALOG
NO.

UPC
CODE

VOLTAGE
50-60Hz

COLOR

5001M

61012

105-130

Grey

5004M

61013

208-277

Maroon

5007M

61014

105-130/208-285

Blue

5008M*

61017

480

Yellow

5021M

61015

105-130

Grey

5024M

61016

208-277

Maroon

61045

SPECIFICATIONS

CONTACT RATINGS

FEATURES

5026M**

2005A, 2007A
& 2008A

347

WIRING DIAGRAMS

2"

2 3/16"

Green

*Not UL listed or CSA certified.
**CSA certified only.

Receptacle Surface

2 3/16"

FEATURES
STANDARDS: Meets ANSI C136.10
including color designations. Also meets
EEI NEMA standards.

CONTACT RATINGS

HOUSING: Polypropylene, UV
Stabilized, permanent color with UV
resistant clear acrylic window. Provides
high impact, flammability resistance and
electrically safe operation.
ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

RATING

CATALOG
NO.

TUNGSTEN

BALLAST

2005A

1000W

1800VA

2007A

1000W

1800VA

2008A*

1000W

1800VA

WIRING DIAGRAMS

ORDERING INFO
CATALOG
NO.

UPC
CODE

VOLTAGE
50-60Hz

COLOR

2005A

62012

105-130

Grey

2007A

62013

105-285

Blue

2008A*

62014

400-550

Yellow

2"

2 3/16"
Receptacle Surface

3 3/16"

*Not UL or CSA listed.

N

L1
Line
(Black)

N

Load (Red)
Neutral
(White)

Load

105 to 285 volt
single phase grounded
supplies and loads

L1
Line
(Black)

Load (Red)
Neutral
(White)

Load

105 to 285 volt
single phase grounded
supplies and loads

PHOTOCONTROLS
TORK 19

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 20

5200 SERIES

5400 SERIES

SPECIFICATIONS

UTILITY GRADE ELECTRONIC
WITH FAIL ON MODE
PHOTOCONTROL

SPECIFICATIONS

6000 WATT CONTACTORS
WITH TURN-LOCK
PHOTOCONTROL

ON/OFF: Turn ON is 1.5 foot candle +/- 0.2 OFF/ON
ratio is 1.5:1 average*.

RECEPTACLE: 3-prong turn-lock meets the
requirements of EEI NEMA.
POWER CONSUMPTION: Maximum 3 watts
during daylight.

TIME DELAY: Instant ON/3-5 second OFF*.
CELL: Silicon photosensor assures drift-free operation,
turning on and off at the same light level consistently
throughout the life of the unit.

APPLICATIONS

APPLICATIONS

CONTACTS: DC relay has positive snap action switching,
reducing bounce and prolonging contact life. Fail ON for
safety.

For use where the extreme
accuracy and reliability of
an electronic photocontrol is
required and in the event of
failure, light should stay ON for
safety reasons.

CONTACT RATINGS
For street lighting. Controls all
lighting loads in excess of the
capacity of the photoelectric
control contacts.

SURGE ARRESTOR: 920 joule MOV (metal oxide
varistor) exceeds ANSI and NEMA requirements.
LOCKING PRONGS: Solid brass for maximum corrosion
resistance and electrical conductivity.
POWER CONSUMPTION: 1.0 watt average @ 120V.
TEMPERATURE RANGE:
-40˚ to +158˚F (-40˚ to +70˚C).

CATALOG
NO.

SWITCH

CONTACT RATING
PER POLE

5403

DPST

3000W

5404

DPST

3000W

5404-3

DPST

3000W

5420

SPDT

3000W

FAIL MODE: ON.

WIRING DIAGRAMS

WARRANTY: 5 years.
*Consult factory for other ratios and time delays.

120 VOLT CIRCUIT
MODEL
WHT
5403

WHT

LOAD

STANDARDS: Meets ANSI C136.10
including color designations. Also meets EEI
NEMA standards.
HOUSING: UV stabilized, ANSI colorcoded, high impact polypropylene dome.
Cross-linked polypropylene gasket. High
impact ABS base. High impact, UV stabilized
acrylic window.

CONTACT RATINGS
CATALOG
NO.

LIGHT SENSOR

5231
5237

TUNGSTEN

BALLAST

Silicon Photosensor

1000W

1800VA

Silicon Photosensor

1000W

1800VA

2"

ORDERING INFO

WHT

78885

105-130VAC

5237

78886

105-305VAC

Line
(Black)

Load (Red)
Neutral
(White)

Load

105-305 VAC
single phase grounded supplies and loads

3 1/8"

120V
N

120 VOLT CIRCUIT
MODEL
5420

105 to 285 volt
single phase grounded
supplies and loads

CAS
DIMENS

RED LOAD 1
BLUE LOAD 2

WHT
H 120V

CATALOG
NO.

UPC
CODE

PHOTOCONTROL
INCLUDED

VOLTAGE
50-60Hz

5403

60009

5021M

105-130VAC

5404

60010

120 VOLT CIRCUIT
MODEL
WHT
5403

5024M

5404-3

60011

5024M

5420

60014

5021M

BLK

LOAD 1 CLOSES AT DUSK, OPENS AT DAWN
LOAD 2 CLOSES AT DAWN, OPENS AT DUSK

277 VOLT CIRCUIT
MODEL
5404-3

208-240VAC
BLK RED

WHT

BLK RED

WHT

WHT

BLK RED

BLK RED

208 or 240 VOLT
CIRCUIT
MODEL 5404

277VAC
LOAD

WHT

LOAD

LOAD

105-130VAC

LOAD

LOAD

LOAD

LOAD

WHT

WHT

WHT

H

H

120V
N

120V
N

H

H 120V

277V
N

120V/240V 3-WIRE SYSTEM

H
H

277V/480V 4-WIRE SYSTEM

CASE
DIMENSIONS

WHT
RED

208V or 240V

208V/240V 4-WIRE SYSTEM

Add photoelectric control dimensions
2" high x 3" diameter

BLK

BLUE LOAD 2

N

Load

277V/48

BLK

RED LOAD 1

Neutral
(White)

277V
N

120V/240V 3-WIRE SYSTEM

WHT
RED

N

L1
Load (Red)

H

H 120V

120 VOLT CIRCUIT
MODEL
5420
Line
(Black)

LOAD

WHT

H

120V
N

120V 2-WIRE SYSTEM

120V 2-WIRE SYSTEM

N

LOAD

WHT

H

ORDERING INFO

L1

Receptacle Surface

VOLTAGE
50-60Hz

5231

N

LOAD

WHT

ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

WIRING DIAGRAMS

2 3/16"

UPC
CODE

HOUSING: Outdoor NEMA Type 3R. Beige
enamel finish. Two 1⁄2”– 3⁄4” combination
KO in bottom.

RATING

ENERGY SAVINGS: Works with screw
base CFLs and LED lamps.

CATALOG
NO.

BLK RED

FEATURES

WHT
H 120V
BLK

4-1/2"
(114mm)

7-1/4"
(184mm)

FEATURES

BLK RED

3-13/32"
(87mm)

LOAD 1 CLOSES AT DUSK, OPENS AT DAWN
LOAD 2 CLOSES AT DAWN, OPENS AT DUSK

PHOTOCONTROLS
TORK 21

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 22

5737 SERIES

TORK 5737 T Z PHOTO-TIMER
®

SPECIFICATIONS

ON AT DUSK, OFF AT MIDNIGHT
ON EARLY MORNING,
OFF AT DAWN
PHOTO-TIMERS

ON/OFF: Turn ON at dusk is 5.0 foot candle +/- 0.5 OFF/
ON ratio is 1.5:1 average.

THE MOST FLEXIBLE PHOTO-TIMER FOR MAXIMUM
ENERGY SAVINGS AND ALL ON/OFF NEEDS!

TIME DELAY: Instant ON/3-5 seconds OFF.
CELL: Silicon photosensor
Midnight OFF: Allows user to adjust OFF time during the
night. OFF time can be set for up to two hours before (for
extra energy savings) or up to two hours after midnight.
Use to stagger groups of lights to go OFF at different times
during the night.
Early Morning ON (537TZ only): Allows user to set number
of hours after midnight (from 2-10 hours) that lights
should turn back ON.

APPLICATIONS
Offices
Restaurant signage
Billboards
Landscape and yard lighting

No programming is required, the microprocessor tracks dusk and dawn
times and automatically determines midnight, and corrects for Daylight
Savings Time. It even re-learns and resets itself after a power outage, so that
no maintenance is ever needed.

CONTACTS: DC Relay, normally closed. Provides chatter
free operation. Solid brass Prongs for maximum corrosion
resistance and electrical conductivity.

Ideal for situations when visible
traffic is reduced – lights ON at
dusk and OFF at 11pm or later,
then on again for early morning
illumination.

TEMPERATURE RANGE:
-40˚ to +158˚F (-40˚ to +70˚C).
FAIL MODE: ON.
WARRANTY: 3 years.

PHOTOCONTROL
ACCESSORIES

FEATURES

FOR TURN-LOCK CONTROLS

OPERATION: Microprocessor tracks the
dusk and dawn times with the seasons and
automatically determines midnight, NO
PROGRAMMING REQUIRED. Automatically
"re-learns" and resets after power outage,
eliminating costly maintenance. DST correction
built in.

CONTACT RATINGS
CATALOG
NO.

SWITCH

5737TZ
5737TM

TUNGSTEN

BALLAST

SPST

1000W

1800VA

SPST

1000W

1800VA

2"

ORDERING INFO
VOLTAGE
50-60Hz

5737TZ

62010

105-305VAC

62009

DEVICE

CATALOG
NO.

5500

5500-OC
2 3/16"

UPC
CODE

5500 replaces photocontrol to change light fixture to always ON. 5500-OC
replaces photocontrol to change light fixture to always OFF. Durable materials
and gasket provide longevity and weatherproof protection.

WIRING DIAGRAMS

ENERGY SAVINGS: Works with screw base
CFLs and LED lamps.

CATALOG
NO.

REPLACEMENT CAPS

RATING

HOUSING: UV stabilized, ANSI color-coded
polypropylene dome. UV stabilized, clear acrylic
window. ABS base. Cross-linked, polypropylene
gasket.

5737TM

DUSK
MIDNIGHTON
OFF
EARLY MO
RNING ON
DAWN OFF

The TORK Photo-timer Plus is the most flexible photocontrol ever,
operating like a photocontrol AND a time switch! Ideal for retrofit without
expensive rewiring. The unit turns the load ON at sunset and can be preset
to turn the load OFF up to two hours before or two hours after midnight.
It can also be set to turn the load back ON from two to ten hours after
midnight and OFF at dawn.

2"
Receptacle Surface

3 1/8"

N

Load (Red)
Load

61132

DEVICE

Shorting cap
480VAC max
1800 Tungsten
1800VA Ballast
Open cap
480VAC max
(Black housing)

CATALOG
NO.

UPC
CODE

DESCRIPTION

2223

61025

Receptacle with Neoprene
gasket

RECEPTACLE

RECEPTACLE

120-480V receptacle with color-coded #14 leads, mounting bracket and one
mounting screw.
DEVICE

120 or
277V
2 3/16"

Line
(Black)

105-305 VAC
single phase grounded supplies and loads

3 1/8"

61130

DESCRIPTION

L1

Neutral
(White)

Receptacle Surface

105-305VAC

N

UPC
CODE

RECEPTACLE

120-480V receptacle with color-coded #14 leads, neoprene gasket and two
mounting screws.

CATALOG
NO.

UPC
CODE

DESCRIPTION

2224

61026

Receptacle and mounting
bracket

120-480V receptacle with color-coded #14 leads, plastic housing, lock nut (with
1⁄2" NPT) and a mounting bracket.
DEVICE

CATALOG
NO.

UPC
CODE

DESCRIPTION

2421

61021

Receptacle with plastic
housing and bracket

L1
Line
(Black)

Load (Red)
Neutral
(White)

Load

105-305 VAC
single phase grounded supplies and loads

FOR 240V, N=L2, L1=L1

PHOTOCONTROLS
TORK 23

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 24

ELECTROMECHANICAL
TIME SWITCHES

FEATURES
QUICK LOOK
SERIES

PAGE
NO.

CLOCK
DIAL

MINIMUM
SETTINGS
(MINUTES)
ON

OFF

SKIP
A
DAY

MANUAL SUNRISE/
OVERRIDE SUNSET

COMMON FEATURES
EASY TO SET DIAL ASSEMBLY
Tork’s 24 hour dial assembly allows the user
to set the time switch more accurately, easily
moving it by hand in small increments. Dial
can provide up to 12 ON/OFFs per day with
cycles as short as 20 minutes. AM and PM
settings are easy to see by the light and dark
areas of the dial.

MAX ON
& OFF
EVENTS
PER DAY

RATINGS RESERVE
(AMPS) POWER

SWITCH TYPES

29

24 Hour

15

15

Permanent

48

SPST

DPST

1100

31

24 Hour

20

75

Yes

12

SPST

DPST

7000

33

24 Hour

20

75

Yes

Yes

12

SPST

DPST

SPDT

DPDT

3PST

40

Available

7000Z

35

24 Hour

20 or 40
Minute Offset

Yes

Yes

Astronomic

1

SPST

DPST

SPDT

DPDT

3PST

40

Available

TZ

49

24 Hour

20 or 40
Minute Offset

Yes

Permanent
by circuit

Astronomic

1

DPDT

3PST

20

Standard

W

43

7 Day

60

120

Yes

Yes

2

DPDT

3PST
4PST

40

Available

TW

47

7 Day

60

120

Yes

Permanent
by circuit

2

DPDT

3PST

20

Standard

T900

45

7 Day

60

120

Yes

Permanent
by circuit

2 SPDT
3 SPDT

20

Standard

1847A

41

24 Hour

20

75

Yes

1847AZ

41

24 Hour

1847AW

41

7 Day

20 or 40
Minute Offset
60

120

8000

37

24 Hour

15

8000

39

6, 12, 30
& 60 Min.

Varies by dial
6 sec. to 1 min.

WH2

40

24 Hour

20

TORK 27

15

75

Yes

Yes

Yes

Yes

Available

Yes

Photo
Control

Astronomic

DPST

DPDT

For applications requiring many ON/OFF
cycles per day, captive tabs on this dial tilt
in and out just using your fingertip!

TU40

SPST

SPDT

CAPTIVE TABS – DUTY CYCLE DIAL

40

SPRING WOUND RESERVE

40

SPDT

2

12

SPDT, Momentary Contact

10

Available

1

SPDT, Momentary Contact

10

Available

2

SPDT, Momentary Contact

10

Available

48

SPDT

20

30/dial

SPDT

20

12

DPST

40

Available

FIELD UPGRADEABLE
ASTRONOMIC DIALS
All Tork 24 Hour Time Switches can
be upgraded in the field to astronomic
operation.

During power outages, precision spring
mechanism takes over instantly and
automatically. Keeps the mechanism on
time up to 16 hours on 24 hour models
and up to 24 hours on 7 day models.
No resetting is needed after power
resumes, and field installation is easy!

ENCLOSED MOTOR
Time switch motors are enclosed to
protect from dust and damage.

REMOVABLE DOOR
Tork time switches feature removable
doors to provide easy access for
installation and wiring.
TORK® Electromechanical
Controls are designed and
manufactured with components
which adhere to the highest
industry standards. Trained
personnel and in-process quality
procedures ensure that every
unit meets our strictest quality
standards.

TORK 28

TU40 SERIES

UNIVERSAL MULTI-VOLTAGE
SAME ON/OFF TIMES EACH DAY
24 HOUR TIME SWITCH

NEW!

MORE WIRING
SPACE!

CONTACT RATINGS

SPECIFICATIONS
INPUT VOLTAGE: 120/208-240/277VAC,
60Hz (auto detection).
TIMING ACCURACY: Line frequency.

VOLTAGE

NO

NC

General Purpose

120-277VAC

40A

30A

Inductive

120-277VAC

30A

15A

Ballast

120VAC
277VAC

30A
20A

10A
10A

Tungsten

120VAC

15A

120VAC
240VAC
120VAC
240VAC

1HP, 30FLA, 90LRA
2HP, 20FLA, 60LRA
720VA
720VA

Resistive

28VDC

20A

Max above 104°F

120-277VAC

30A

TERMINAL RANGE: #8 - #18 AWG.
OPERATING TEMPERATURE:
-31°F to 116°F (-35°C to +47°C).

APPLICATIONS

POWER CONSUMPTION: 6 watts maximum.

Lighting
Pumps
Signs
Air conditioning
Water heaters
Fans

RATING

TYPE

ENCLOSURE: Polycarbonate Indoor/Outdoor
NEMA 3R or -Y suffix metal indoor NEMA 1
enclosure. Both with lockable hasp standard (see
page 153 for enclosure dimensions).

Motor Load
Pilot Duty

¼HP, 12FLA, 30LRA
½HP, 12FLA, 33LRA
290VA
360VA

WIRING DIAGRAMS

DTU40
ORDERING INFO
FEATURES
MULTI-VOLTAGE: Automatic input voltage
detection.
EASY SET: Real time clock face and day/night
markings for setting trippers.

Typical
Wiring
Diagram,
Application
Typical
Wiring
Diagram,
120120/277VAC
VAC Application

CATALOG
NO.

UPC
CODE

TIMER SUPPLY
(VAC) 60Hz

DRY CONTACTS
(UNPOWERED)

TU40

24000

120/208-240/277

DPDT

TU40-Y

24001

120/208-240/277

DPDT

ENCLOSURE
TYPE

Plastic Indoor/Outdoor
NEMA 3R
Metal Indoor
NEMA 1

TIMER
SUPPLY
H

N

NC

NO

C

NC

LOAD
L

N

N

NO

C

LOAD
L

N

L

Typical Wiring Diagram, 208-240 VAC Application

SCHEDULING: Minimum ON is setting 15
minutes. Dial has 96 captive trippers.

TIMER
SUPPLY
H

4 in 1 CONTACTS: DPDT can also wire as SPST,
SPDT, & DPST.

N

NC

NO

C

NC

NO

C

LOAD

BYPASS SWITCH: Sets timer to permanent
ON, OFF or timer operation.

L1

L2

L1

VACATION MODE: Set timer OFF with no
change of tripper settings.

L2

DTWH40

INDICATING LIGHTS: Power ON green and
load ON red and LED indicators.

Typical
Wiring120
Diagram,
120VAC
Typical
Wiring
Diagram,
120/277VAC
Application
Typical
Wiring
Diagram,
VAC Application

TIMER

SPECIFICATION WRITER’S GUIDE
SUPPLY
		 Furnish and install, where shown, a TORK time switch with
24 hour dial. The Time switch input shall be multi-voltage input 120/208/240/277VAC. Time Switch
H N
NC NO C
NC NO C
contacts shall be capable of switching 40 amperes per pole continuously up to 277 volts, and shall be DPDT, covering SPST, SPDT and DPST applications as
LOAD96 trippers permits
LOAD
required. Captive ON/OFF trippers shall accomplish 1-48 operation per day.
15 minutes switching changes. Enclosure shall be Heavy duty
lockable plastic Indoor/Outdoor NEMA 3R surface type, finished in beige, with combination 1⁄2”, 3⁄4” knockouts on bottom sides and back. Provisions shall be
N
L shall be TORK Model TU40_.
made for positive padlocking. Terminal shall be capableL of receiving
#8-#18N AWGL wire. The TimeN Switch
Typical Wiring
208-240
VAC Application
Typical Diagram,
Wiring Diagram,
240VAC
TIMER
SUPPLY
H

ELECTROMECHANICAL
CONTROLS
TORK 29

N

NC

NO

C

NC

NO

C

LOAD

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

L1

L2

L1

L2
TORK 30

1100 SERIES

SAME DAY ON/OFF
TIMES EACH DAY
24 HOUR TIME SWITCH

SPECIFICATIONS

CONTACT RATINGS

INPUT VOLTAGE: 120 or 208-277 VAC
60 Hz, varies by model.

TYPE

APPLICATIONS
Lighting
Pumps
Signs
Air conditioning
Water heaters
Fans
Automatic ON/OFF control
when operation is required at
the same time every day.

FEATURES
SCHEDULING: Minimum ON is setting 20
minutes with a minimum OFF setting of 75
minutes. Dial accommodates up to 12 pairs of
trippers. One pair included.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF automatic
operation then resumes.

ELECTROMECHANICAL
CONTROLS
TORK 31

ENCLOSURE
TYPE

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

OUTPUT
CONTACTS

1101

10011

120

SPST

1101-N

10040

120

SPST

1101-NC

10053

120

SPST

1101-O

10015

120

SPST

Metal Indoor
NEMA 1
Noryl® Indoor/Outdoor
NEMA 3R
Noryl® Indoor/Outdoor
w/ clear Lexan® cover
Metal Indoor/Outdoor
NEMA 3

1101-M

10022

120

SPST

Mechanism

1101-M-IAP

10052

120

SPST

1101-7

10033

347

SPST

1102

10012

208-277

SPST

1102-N

10045

208-277

SPST

1102-O

10046

208-277

SPST

Mechanism and
mounting plate
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Noryl® Indoor/Outdoor
NEMA 3R
Metal Indoor/Outdoor
NEMA 3

1102-M

10035

208-277

SPST

Mechanism

1103

10013

120

DPST

1103-N

10041

120

DPST

1103-NC

10054

120

DPST

1103-O

10016

120

DPST

Metal Indoor
NEMA 1
Noryl® Indoor/Outdoor
NEMA 3R
Noryl® Indoor/Outdoor
w/ clear Lexan® cover
Metal Indoor/Outdoor
NEMA 3

1103-M

10023

120

DPST

Mechanism

1104

10014

208-277

DPST

1104-N

10042

208-277

DPST

1104-NC

10055

208-277

DPST

1104-O

10017

208-277

DPST

Metal Indoor
NEMA 1
Noryl® Indoor/Outdoor
NEMA 3R
Noryl® Indoor/Outdoor
w/ clear Lexan® cover
Metal Indoor/Outdoor
NEMA 3

1104-M

10014

208-277

DPST

Mechanism

1104-M-IAP

10051

208-277

DPST

Mechanism
and mounting plate

Replacement
Trippers

Order #P47 for a pair of ON/OFF trippers

Replacement
Motor

#101 (120V) & #201 (208-277V)
For Astronomic Conversion: Order #Z KIT

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

40A

TERMINAL RANGE: #8 - #14 AWG.

Resistive

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

Tungsten

120VAC

40A

Inductive

120, 277VAC
single phase

20A

Pilot Duty

120 -277VAC

1000VA

Motor

120VAC
240VAC

2HP
5HP

POWER CONSUMPTION:
3 watts maximum.

ORDERING INFO

120 -277VAC
single phase
120 -277VAC
single phase

General Purpose

TIMING ACCURACY: Line frequency.

CONTACT
RATING

VOLTAGE

ENCLOSURE: Lockable hasp. Type varies
by model (see page 153 for enclosure
dimensions).

40A

Model 1101-7 is 30 AMP inductive at 347 volts and CSA only.

OTHER MOUNTINGS:
Intermatic® Adaptor Plate model #IAP allows
any 1100 series to fit into an Intermatic case.

WIRING DIAGRAMS
1101 & 1102 (SPST)

1103 (DPST)

M

Removable
Bridge

M

L
L

1

H

2

X

LOAD

N
For separate motor terminals
remove bridge from terminals 1 & L.

M

L
H
H
TYPICAL FOR
240V SUPPLY

1

H
N
H

LOADS

M

1104 (DPST) (Both)

2

X
LOAD

2

X

1

Must be
same phase
H

L

H

1

X

2

LOAD

LOAD

N
TYPICAL FOR
277V SUPPLY

Typical for double pole
Cut motor lead at 1

SPECIFICATION WRITER’S GUIDE
		 Furnish and install, where shown, a TORK time switch with 24 hour dial. The time switch shall be powered by a self-starting synchronous motor. Time switch
contacts shall be capable of switching 40 amperes per pole continuously at 277 volts and shall be SPST (DPST as required). Removable ON/OFF trippers shall
make possible automatic operation with a minimum ON period of 20 minutes and a minimum of 75 minutes between one OFF period and the next. Enclosure
shall be NEMA 1 surface type, finished in beige enamel, with combination 1⁄2”, 3⁄4” knockouts on bottom, both sides and back. Provision shall be made for
positive padlocking. Terminals shall be capable of receiving #8AWG wire. Time switch shall be TORK Model 11_ _ (11_ _–_, etc, to fit requirement).

TORK 32

7000 SERIES

CONTACT RATINGS

SPECIFICATIONS

WITH SKIP-A-DAY FEATURE
RESERVE POWER OPTIONAL
24 HOUR TIME SWITCH

TYPE

INPUT VOLTAGE: 120 or 208-277 VAC
60 Hz varies by model.
TERMINAL RANGE: #8 - #14 AWG.

Resistive

120 -277VAC
single phase
120 -277VAC
single phase

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

Tungsten

120VAC

40A

Inductive

120, 277VAC
single phase

20A

Pilot Duty

120 -277VAC

1000VA

Motor

120VAC
240VAC

2HP
5HP

General Purpose

TIMING ACCURACY: Line frequency.

CALIFORNIA Title 24

APPLICATIONS

ASHRAE 90.1

POWER CONSUMPTION: 3 watts,
5 watts for “L” models maximum.

Lighting
Heating
Pumps
Air conditioning
Signs

ENCLOSURE: Lockable hasp. Type varies
by model (see page 153 for enclosure
dimensions).

NEW!

FEATURES
NEW!

SCHEDULING: Minimum ON setting is
20 minutes with minimum OFF setting at
75 minutes. Dial accommodates up to 12
pairs of trippers. One pair included.
SKIP-A-DAY: Omit operations on any
day with a 7-spoke wheel marked with
days of week. 3 omitting screws included.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
OPTIONAL RESERVE POWER: “L”
models keep dial on time up to 16 hours
during power outage.

ELECTROMECHANICAL
CONTROLS
TORK 33

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

OUTPUT
CONTACTS

7100

10001

120

SPST

7102

10002

208-277

SPST

7200

11001

120

DPST

7200-O

10512

120

DPST

7202

11002

208-277

DPST

7202-O

10509

208-277

DPST

7300
7302

12001
12002

120
208-277

3PST
3PST

7120

13001

120

SPDT

7122

13002

208-277

SPDT

7220

14001

120

DPDT

7222

14002

208-277

DPDT

ENCLOSURE
TYPE

Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor/Outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor/Outdoor
NEMA 3
Metal Indoor/Outdoor
NEMA 3
Metal Indoor/Outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1

Metal Indoor
NEMA 1
Metal
Indoor
7202L
19004
208-277
DPST
NEMA 1
Metal Indoor/Outdoor
7300L
19005
120
3PST
NEMA 3
Metal
Indoor/Outdoor
7302L
19006
208-277
3PST
NEMA 3
Metal
Indoor
7120L
19007
120
SPDT
NEMA 1
Metal Indoor
7220L
19009
120
DPDT
NEMA 1
Metal
Indoor
7222L
19011
208-277
DPDT
NEMA 1
Replacement Order #P49 for a pair of ON/OFF per dial. Additional ON/OFF trippers per
Trippers
dial order #P47. 3 omitting screws #53005 supplied.
Replacement
#101 (120V) & #201 (208-277V). For "L" models #36 (120V) & #46
(208-277V). For Astronomic Conversion: Order #Z KIT for 7000 Series.
Motor
19003

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

120

40A

WIRING DIAGRAMS
7100 SPST

7200 DPST

7100 SPST

M

M

M

7300 3PST

7200 DPST

L

L

L

2
L

H

H

N

X
L

1

2

LOAD

H
N
H

7120 SPDT

2

X

M
X

1

L

LOAD

LOAD

H
N
H

2
L

3

L

L

L

5
L

6

L

DPST

H

1

LOAD

X
L
H

A

N

LOAD

B

N

2
1

L
H

LOAD

X

LOAD

A

B

N

2H
H
N
H

1

L
N

3
LOAD

N

5
LOAD

6
LOAD
LOAD

LOAD

7302 3PST

7120Z (SPDT)
M

M

X

L

H

H

4

LOAD

L

1

3

M

M
M

L

2

N

7220
DPDT (DPST)
7200Z
7220 DPDT

M

X

1

4

L LOAD

N

7120 SPDT

M

2

LOAD

LOAD

LOAD

N

1

7300 3PST

M

M

WITH RESERVE POWER
7200L

40A

OTHER MOUNTINGS:
Intermatic® Adaptor Plate model #IAP
allows any 7100 and 7200 series (except
“L” models) to fit into an Intermatic case.

ORDERING INFO

Automatic ON/OFF control
when operation is required at
the same time every day, with
optional versatility of one to six
days omission.

CONTACT
RATING

VOLTAGE

5
N

2

2

X

LOAD

L

4

H
X

1LOAD
LOAD

LOAD

3

LOAD
LOAD

2

L

N
5
H

LOAD

N

L

1

3H

2

L

4

H

L

6
LOAD

LOAD

N

1

X

2

H

LOAD

5
N

4

X

LOAD

LOAD

LOAD
A

LOAD
B

N

H

FOR USE WITH 3 PHASE 4-WIRE
N
120/208V
SYSTEMS.

SPECIFICATION WRITER’S GUIDE
		 Furnish and install, where shown, a TORK time switch with 24 hour dial and day-omitting device. The time switch shall be powered by a self-starting synchronous
motor. Time switch contacts shall be capable of switching 40 amperes per pole continuously at 277 volts and shall be SPST (DPST, 3PST, DPST, SPDT, as required).
Removable ON/OFF trippers shall make possible automatic operation with a minimum ON period of 20 minutes and a minimum of 75 minutes between one OFF
period and the next. Enclosure shall be NEMA 1 surface type, finished in beige enamel, with combination 1⁄2”, 3⁄4” knockouts on bottom, both sides and back.
Provision shall be made for positive padlocking. Terminals shall be capable of receiving #8AWG wire. Time Switch shall be TORK Model 7_ _ _ (to fit requirement).
FOR RESERVE POWER (MODELS WITH SUFFIX “L”): Spring-driven reserve shall be provided sufficient to operate the time switch contacts at least 16 hours after
power failure. On restoration of power, time switch shall transfer to synchronous motor drive and automatically rewind reserve power unit.

TORK 34

7000Z SERIES

ADJUSTS TO DAILY CHANGES
IN SUNSET TIMES!

WITH SKIP-A-DAY FEATURE
RESERVE POWER OPTIONAL
ASTRONOMIC TIME SWITCH

CONTACT RATINGS

SPECIFICATIONS

TYPE

INPUT VOLTAGE: 120 or 208-277 VAC
60 Hz, varies by model.
TERMINAL RANGE: #8 - #14 AWG.

Resistive

120 -277VAC
single phase
120 -277VAC
single phase

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

Tungsten

120VAC

40A

Inductive

120, 277VAC
single phase

20A

Pilot Duty

120 -277VAC

1000VA

Motor

120VAC
240VAC

2HP
5HP

General Purpose

TIMING ACCURACY: Line frequency.

CALIFORNIA Title 24

APPLICATIONS

ASHRAE 90.1

POWER CONSUMPTION: 3 watts,
5 watts for “L” models maximum.

Parking lots
Walkways
Outdoor signage
Window displays
Canopy lighting
Landscape lighting

ENCLOSURE: Lockable hasp. Type varies
by model (see page 153 for enclosure
dimensions).

Automatic ON at dusk, OFF
at dawn. Control of outdoor
lighting.

42°

ORDERING INFO

SKIP-A-DAY: Omit operations on any
day with a 7 spoke wheel marked with
days of the week. 3 omitting screws
included.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
OPTIONAL RESERVE POWER: “L”
models keep dial on time up to 16 hours
during power outage.

CATALOG
NO.

7200Z–*
7202Z–*
7300Z–*
7302Z–*
7120Z–*

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

**
**

120
208-277

**
**

120
208-277

**

120

OUTPUT
CONTACTS

DPST
DPST
3PST
3PST
SPDT

ENCLOSURE
TYPE

Noryl® Indoor/Outdoor
NEMA 3R
Noryl® Indoor/Outdoor
NEMA 3R
Metal Indoor/Outdoor
NEMA 3
Metal Indoor/Outdoor
NEMA 3
Noryl® Indoor/Outdoor
NEMA 3R

WITH RESERVE POWER
7200ZL–*

**

120

DPST

7202ZL–*

**

208-277

DPST

7300ZL–*

**

120

3PST

7302ZL–*

**

208-277

3PST

7120ZL–*

**

120

SPDT

7122ZL–*

**

208-277

SPDT

Replacement
Motor

Noryl® Indoor/Outdoor
NEMA 3R
Noryl® Indoor/Outdoor
NEMA 3R
Metal Indoor/Outdoor
NEMA 3
Metal Indoor/Outdoor
NEMA 3
Noryl® Indoor/Outdoor
NEMA 3R
Noryl® Indoor/Outdoor
NEMA 3R

#101 (120V) & #201 (208-277V).
For "L" models #36 (120V) & #46 (208-277V)

*Add degrees latitude to complete number (18, 30, 34, 38, 40, 42, or 45).
**Consult factory for UPC number.

ELECTROMECHANICAL
CONTROLS
TORK 35

40A

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

40°
H
N
H

38°

WASHINGTON

OREGON

L

7120Z (SPDT)

M

M

45°

ASTRONOMIC SCHEDULING: Turn
ON at sunset and OFF at sunrise daily.
OFF time can be set from 8:30PM to
2:30AM. Can be individually offset +/- 20
or 40 minutes from both sunset and OFF
times. Available from 18° - 45° northern
latitudes.

40A

WIRING DIAGRAMS
ASTRONOMIC LATITUDE
ZONES
7200Z (DPST)
7302
3PST

FEATURES

CONTACT
RATING

VOLTAGE

X

2

UTAH

LOAD

WISCONSIN

KANSAS

L
L

3

ILLINOIS

ARIZONA

L

NEW MEXICO

IND

MISSOURI

ARKANSAS

N

L

RHODE ISLAND

H

DELAWARE
MARYLAND

VIRGINIA

6

LOAD

LOAD
B

1

N

H
N
H

7302 3PST

FLORIDA

18° HAWAII

LOAD
A

N

LOAD

L

2

X

2

LOAD

LOAD

GEORGIA

LOUISIANA

30°

X

H

FOR USE WITH 3 PHASE 4-WIRE
7200Z
(DPST)
120/208V SYSTEMS.

MEXICO

1

CONNECTICUT
NEW JERSEY

NORTH CAROLINA
SOUTH
LOAD
CAROLINA

ALABAMA

MASS

PENNSYLVANIA

4

OHIO

KENTUCKY

TENNESSEE

MISS
TEXAS

NH

WEST
VIRGINIA

5
OKLAHOMA

VT

2
NEW YORK

CALIFORNIA

34°

X

1

M

MAINE

IOWA

COLORADO

LOAD

M

MICHIGAN

L

WYOMING
NEBRASKA

NEVADA

MINN

SOUTH DAKOTA

IDAHO

1

NORTH DAKOTA

MONTANA

7200Z (DPST)

18° PUERTO

M

7120Z (SPDT)

M

M

RICO

L

L

1

X

L

H
N
H

LOAD

1

X

2

2

LOAD

3

L

4

5

6
LOAD

X

LOAD
A

LOAD
B

2
H

H

L
L

1

LOAD

LOAD

N

N

N

FOR USE WITH 3 PHASE 4-WIRE
120/208V SYSTEMS.

SPECIFICATION WRITER’S GUIDE
		 Furnish and install, where shown, a TORK time switch with Astronomic dial and day-omitting device powered by a self-starting synchronous motor. Time switch
contacts shall be capable of switching 40 amperes per pole continuously at 277 volts and shall be (DPST, 3PST or SPDT) as required. ON operation shall occur
automatically at sunset (in city of use). OFF operation shall be adjustable from 8:30 P.M. to 2:30 A.M. in one-half hour increments or at sunrise. Both ON and
OFF shall have a range of adjustability of 20-40 minutes before or after sunset and sunrise. Enclosure shall be: DPST or SPDT is NEMA 3R indoor/outdoor –
Noryl® – 3PST is NEMA 3 metal indoor/outdoor. Terminals shall be of the pressure type, capable of receiving #8 AWG wire. Time switch shall be TORK Model
7_ _ _Z (to fit requirement).
		 FOR RESERVE POWER (Add Suffix L): Spring driven reserve shall be provided sufficient to operate the time switch contacts for at least 16 hours after power
failure. On restoration of power, time switch shall transfer to synchronous motor drive and automatically rewind reserve power unit.

TORK 36

8000 SERIES

CONTACT RATINGS

SPECIFICATIONS

MANY DAILY ON/OFF
OPERATIONS PER DAY
DUTY CYCLE
24 HOUR TIME SWITCH

INPUT VOLTAGE: 120, 208-277VAC or
480VAC, 60Hz, varies by model.
TIMING ACCURACY: Line frequency.
TERMINAL RANGE: #8 - #14AWG.

ORDERING INFO
ENCLOSURE
TYPE

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

OUTPUT
CONTACTS

8001

70001

120

SPDT

8001-N

70025

120

SPDT

8001-NC

70009

120

SPDT

Metal Indoor
NEMA 1
Noryl® Indoor/Outdoor
NEMA 3R
Noryl® Indoor/Outdoor NEMA
3R w/ clear Lexan® cover

8001-LC/WB

70010

120

SPDT

Mechanism and bracket

8001-O

70029

120

SPDT

8004

70002

208-277

SPDT

8001U

70003

480/120 Trans.

SPDT

NEW!

8001U-N

70014

480/120 Trans.

SPDT

NEW!

8001U-O

70011

480/120 Trans.

SPDT

Metal Indoor/Outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Noryl® Indoor/Outdoor
NEMA 3R
Metal Indoor/Outdoor
NEMA 3

DUTY CYCLE: Adjustable from 1⁄2, 1, 2,
3, 4, 6, 12, and 24 hours.

24 HOUR WITH 7 DAY OMIT
70005

120

SPDT

8007-O

70012

120

SPDT

8008

70006

208-277

SPDT

NEW!

8007U

70008

480/120 Trans.

SPDT

NEW!

8007U-0

70028

480/120 Trans.

SPDT

Metal Indoor
NEMA 1
Metal Indoor/Outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor/Outdoor
NEMA 3

24 HOUR WITH 7 DAY OMIT & RESERVE POWER
8007L

70015

120

SPDT

8008L

70016

208-277

SPDT

Metal Indoor
NEMA 1
Metal Indoor
NEMA 1

24 HOUR WITH 14 DAY OMIT
8007V

70007

120

SPDT

Metal Indoor
NEMA 1

SPDT

Metal Indoor
NEMA 1

24 HOUR WITH 14 DAY OMIT & RESERVE POWER
8007VL
Replacement
Motor

TORK 37

120 or 240VAC
480VAC

20A
20A

Motor

120VAC

3/4 HP

OTHER MOUNTINGS: Intermatic®
Adaptor Plate model #IAP allows 8001 &
8004 to fit into an Intermatic case.

WIRING DIAGRAMS

70017

120

M

ALL SPDT
MODELS

C
L

H

8007

SKIP-A-DAY: Some models include 7
day or 14 day wheel to omit selected days
of the week.

ELECTROMECHANICAL
CONTROLS

Resistive

ENCLOSURE: Lockable hasp. Type varies
by model (see page 153 for enclosure
dimensions).

8001-N

FEATURES

OPTIONAL RESERVE POWER: “L”
models keep dial on time up to 16 hours
during power outage.

CONTACT
RATING

POWER CONSUMPTION: 3 watts,
5 watts for “L” models maximum.

For one or multiple daily
ON/OFF operations.

SCHEDULING: Minimum ON setting is
15 minutes with minimum OFF setting at
15 minutes. Dial accommodates up to 96
captive tabs.

VOLTAGE

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

APPLICATIONS
Duty cycling
Ventilating fans
Pumping
Irrigation
Process control
Laboratory experiments

TYPE

120VAC
N

NC

NO
2

LOAD 2
CLOSED WITH
TAB OUTWARD

LOAD 1
CLOSED WITH
TAB INWARD

SPECIFICATION WRITER’S GUIDE
		 The time switches shall be of duty cycle type, capable of programming at 15 minute intervals of the day. Scheduled tabs shall be captive on the dial, and shall
be easily set by hand without tools to obtain or to change the desired schedule. The switching condition shall be maintained when adjacent tabs are set alike.
The unit shall be powered by a self-starting enclosed 120 (or 208-277) volt synchronous motor capable of continuous accurate operation. The switch mechanism
shall be a self-contained unit rated at not less than 20 amps, 120 volts, single pole, double throw, and shall be readily replaceable in the field. FOR 8001 ADD:
The time switch shall be similar and equal to Tork Model 8001. FOR 8007 AND 8007V ADD: An omitting device shall be furnished as an integral part of the
time switch, to enable the switching operation to be skipped for any preselected day or days of the week. The time switch shall be similar and equal to Tork
Model 8007 or (8007V.) FOR 8007L ADD: (Same description as for 8007). The unit shall incorporate an integral electrically wound spring reserve power unit,
which shall power the clock mechanism for up to 16 hours on a power failure. The time switch shall be similar and equal to Tork Model 8007L. FOR 8001U: The
unit shall be furnished with built-in 480-120V transformer to operate timing motor in parallel with 480 volt load. The time switch shall be Tork Model 8001U.

#101(120V) & #201 (208-277V).
For “L” models #36 (120V) & #46 (208-277V)

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 38

8000 SERIES

SPECIFICATIONS

MULTIPLE ON/OFF CYCLES PER DAY
REPEATING VARIABLE CYCLE
TIME SWITCH

INPUT VOLTAGE: 120VAC, 60Hz.

APPLICATIONS

24 HOUR WATER HEATER
TIME SWITCH

INPUT VOLTAGE: 208 – 250V 60 Hz.
TIMING ACCURACY: Line frequency.

TERMINAL RANGE: #8 - #14AWG.

TERMINAL RANGE: #8 - #14AWG.

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

REPLACEMENT TRIPPERS: #P49 for a
pair with one ON and one OFF per dial for
additional ON/OFF trippers per dial order
#P47. 3 omitting screws #53005 supplied.
ENCLOSURE: Indoor NEMA 1 Metal with
lockable hasp (see page 153 for enclosure
dimensions).

For one or many daily ON/OFF
operations.

SPECIFICATIONS

TIMING ACCURACY: Line frequency.

POWER CONSUMPTION:
3 watts maximum.

Duty cycling
Ventilating fans
Pumping
Irrigation
Process control
Laboratory experiments

WH2

APPLICATIONS

SAVE
ENERGY!

POWER CONSUMPTION:
3 watts maximum.

Avoid utility peak rates
Turn off when not needed

Automatic ON/OFF control of
electric water heaters. Schedules
the water heater to turn ON only
when needed, avoiding energy
waste when hot water is not
needed.

ENCLOSURE: Indoor NEMA 1 Metal with
lockable hasp (see page 153 for enclosure
dimensions).

CONTACT RATINGS
CONTACT RATINGS

FEATURES
SCHEDULING: 60 captive tabs per dial
with minimum ON/OFF settings:
– 60 minute dial with 1 minute tabs.
– 30 minute dial with 30 second tabs.
– 12 minute dial with 12 second tabs.
– 6 minute dial with 6 second tabs.

TYPE

VOLTAGE

CONTACT
RATING

Resistive

120 or 240VAC
480VAC

20A
20A

Motor

120VAC

3/4 HP

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

OUTPUT
CONTACTS

TYPE

8601

70034

120

SPDT

60 Minute

8301

70033

120

SPDT

30 Minute

8121

70032

120

SPDT

12 Minute

C
L

H

120

SPDT

6 Minute

120VAC
N

Replacement
For 8601 #102, for 8301 #108, for 8121 #107, and for 8061 #105.
Motor
Replacement #P49 for a pair with one ON and one OFF per dial for additional ON/OFF
Trippers
trippers per dial order #P47. 3 omitting screws #53005 supplied.

ELECTROMECHANICAL
PHOTOCONTROLS
CONTROLS
TORK 39

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

NC

TYPE

VOLTAGE

CONTACT
RATING

Resistive

208-277VAC

40 A, 10,000W

Replacement Motor

#201 (208-277V)

Replacement Trippers

Order #P47 for a pair of ON/OFF trippers

EXTERNAL MANUAL OVERRIDE: Until the
next regularly scheduled ON or OFF automatic
operation then resumes.

M

ALL SPDT
MODELS

ORDERING INFO

70031

SCHEDULING: Minimum ON is setting 20 minutes
with a minimum OFF setting of 75 minutes. Dial
accommodates up to 12 pairs. 3 pairs of trippers
supplied.

WIRING DIAGRAMS

DUTY CYCLE: Settings of 1⁄60 th of dial
speed.

8061

FEATURES

WIRING DIAGRAMS
TYPICAL FOR 240
VOLT SUPPLY

ORDERING INFO

NO
2

LOAD 2
CLOSED WITH
TAB OUTWARD

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

OUTPUT
CONTACTS

ENCLOSURE
TYPE

WH2

70042

208-250

DPST

Metal Indoor
NEMA 1

M

H
H

L

1

2

X
LOAD

LOAD 1
CLOSED WITH
TAB INWARD

TORK 40
40
TORK

1800 SERIES

CONTACT RATINGS

SPECIFICATIONS

FOR MECHANICALLY HELD CONTRACTORS
AND LOW VOLTAGE REMOTE CONTROL
MOMENTARY CONTACT
TIME SWITCH

INPUT VOLTAGE: 120VAC or 208-277VAC, 60Hz,
varies by model.
TIMING ACCURACY: Line frequency.

TYPE

VOLTAGE

CONTACT
RATING

General Purpose

24-277VAC

10A

Pilot Duty

24-277VAC

360VA

TERMINAL RANGE: #12 - #22AWG.
OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

APPLICATIONS

CALIFORNIA Title 24

Mechanically-held contactors
3-wire momentary
lighting systems
Remote station switching

POWER CONSUMPTION: 3 watts, 5 watts for
“L” models maximum.

ASHRAE 90.1

ENCLOSURE: NEMA 1 Metal with lockable hasp
(see page 153 for enclosure dimensions).

WIRING DIAGRAMS

ORDERING INFO
WASHINGTON

FEATURES

CATALOG
NO.

SCHEDULING: Choice of three types.

1847A

24 HOUR SKIP-A-DAY: Minimum ON setting
is 20 minutes with minimum OFF setting at 75
minutes. Dial accommodates up to 12 pairs of
trippers. Omit operations on any day with a 7
spoke wheel marked with days of week.

1848A

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

52001
52014

120
208-277

7 DAY SCHEDULING: Minimum ON setting is
1 hour with a minimum OFF setting of 2 hours.
Minimum 8 hours between 2 OFF settings. 7 day
calendar dial will accomodate up to 2 pairs on ON/
OFF trippers per day - 7 pairs are supplied.
MANUAL OVERRIDE: Until the next regularly
scheduled ON or OFF, automatic operation then
resumes.

TORK 41

SPDT
SPDT

TYPE

42°

24 Hour

OREGON

NORTH DAKOTA

MONTANA

MINN

MICHIGAN

WYOMING

**

120

SPDT

Astronomic

1847AW

52005

120

SPDT

7 Day

WITH RESERVE POWER
1847AL

52006

120

SPDT

24 Hour

1847AZL*

**

120

SPDT

Astronomic

1847AWL

52010

120

SPDT

7 Day

Replacement
Trippers

For 24 hour models order #P49 for a pair ON/OFF per dial. Additional ON/OFF
trippers per dial order #P47. 3 omitting screws #53005 supplied.
7 day models order #P69 for 7 pairs of ON/OFF trippers.

Replacement
Motor

#101(120V) & #201 (208-277V). For “L” models #36 (120V)

*Add degrees latitude to complete number (18, 30, 34, or 42).
**Consult factory for UPC number.

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

MAINE

WISCONSIN

SOUTH DAKOTA

IDAHO

UTAH

IOWA

NEW YORK

KANSAS

34°

IND

COLORADO

PENNSYLVANIA

OHIO

KENTUCKY
OKLAHOMA
ARIZONA

NEW MEXICO

ARKANSAS

TIMING MOTOR

120VAC, 60HZ

L

TENNESSEE

MASS
RHODE ISLAND
CONNECTICUT

DELAWARE
MARYLAND

VIRGINIA

CLOSE
COMMON

N

NEW JERSEY

WEST
VIRGINIA

MISSOURI

CALIFORNIA

ON

VT
NH

ILLINOIS
NEVADA

C

MECHANICALLY-HELD
CONTACTOR

NEBRASKA

24 Hour

1847AZ*

OPTIONAL RESERVE POWER: “L” models keep
dial on time up to 16 hours during power outage.

ELECTROMECHANICAL
CONTROLS

OUTPUT
CONTACTS

ON

OPEN

NORTH CAROLINA
SOUTH
CAROLINA

MISS
ALABAMA

TEXAS

ASTRONOMIC SCHEDULING: Turn ON at sunset
and OFF at sunrise daily. OFF time can be set from
8:30PM to 2:30AM. Can be individually offset +/20 or 40 minutes from both sunset and OFF times.

OFF

ASTRONOMIC LATITUDE ZONES

OFF

GEORGIA

LOUISIANA

MOMENTARY PUSH BUTTON

MEXICO

30°

FLORIDA

18° HAWAII

18° PUERTO
RICO

SPECIFICATION WRITER’S GUIDE
		 Furnish and install, where shown, a Momentary Contact time switch. Time switch shall have dial of the (24 hour with day omitting device) (Astronomic with day
omitting device) (7 day calendar) type, which shall be suitable to operate mechanically-held contactor of maximum size. Terminal board shall enable fast and
correct installation using screw terminals for up to #12AWG wire. Timing motor terminals shall be completely independent from momentary switching circuit.
Spring driven reserve mechanism shall be provided sufficient to operate time switch controls at least 16 hours after power failure. On restoration of power, time
switch shall transfer to synchronous motor drive and automatically rewind reserve. Time switch shall include solid state circuit to provide a switch closure not
in excess of two seconds on both ON and OFF contactor coil terminals at such times as are set on dial: these settings to be made with removable trippers which
can be added and removed without tools (except the astronomic dial). Contactor coil circuits shall be suitable for 10 Amp @ 24-277 VAC, 360 VA. Enclosures
shall be NEMA 1 surface (or see other mountings), with provision for positive padlocking. Time switch shall be TORK Model 1847AL, 1848A, (AZL), (AWL).

TORK 42

W SERIES

CONTACT RATINGS

SPECIFICATIONS

DIFFERENT SCHEDULES EACH DAY
7 DAY TIME SWITCH

TYPE

INPUT VOLTAGE: 120 or 208-277VAC, 60Hz,
varies by model.

Resistive

TERMINAL RANGE: #8 - #14AWG.
OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

CALIFORNIA Title 24

APPLICATIONS

ASHRAE 90.1

Heating
Air conditioning
Display lighting
Ventilating systems
Lighted signage
Storefront lighting

POWER CONSUMPTION: 3 watts, 5 watts for
“L” models maximum.

40A

120VAC

40A

Inductive

120, 277VAC
single phase

20A

Pilot Duty

120 -277VAC

1000VA

Motor

120VAC
240 VAC

2HP
5HP

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

OUTPUT
CONTACTS

W100

30001

120

SPST

33001

120

ENCLOSURE
TYPE

WIRING DIAGRAMS

W100 (SPST)

W100 (SPST)

SPDT

M

W200
W202

FEATURES

31001
31011

120
208-277

SCHEDULING: Minimum ON setting is 1 hour
with a minimum OFF setting of 2 hours. Minimum
8 hours between 2 OFF settings. Models W400A
and W402A offer minimum ON/OFF settings of
31⁄2 hours. 7 day calendar dial accommodates up
to 2 pairs of ON/OFF trippers per day – 7 pairs are
supplied.
SKIP-A-DAY: Omit operations on any day.
MANUAL OVERRIDE: Until the next regularly
scheduled ON or OFF automatic operation then
resumes.
OPTIONAL RESERVE POWER: “L” models keep
dial on time up to 24 hours during power outage.

W222
W300
W300-O
W302

34001
34011
32001
32003
32002

120
208-277
120
120
208-277

L

Metal Indoor
NEMA 1

L

L

L

L
XH
N
H

LOAD
1

N

2

LOAD

H
N
H

LOAD

2

X

1

2

H
L

N

DPDT

1

LOAD

2

L

5

L

4

5

L

N

H

3PST
3PST

35001

120

4PST

W402A

35002

208-277

4PST

Equipment (4PST)
W400A
Ground

Equipment
Ground

LOAD

LOAD

Clock Motor
Supply

3
5

6

7

L

X

1

2

H

2

H

B

X

LOAD

1

LOAD

N

N H

N

L

LOAD

B

N

N

2

3

5

LOAD

LOAD

N

4

L

H 3
LOAD

N

5

4

LOAD

LOAD

H
N

W202 (DPST)

1

2

3

4

4

MOTOR

MOTOR

MOTOR
L

7

8

8

B

H

1

L

6

H

LOAD

H

5

LOAD

L
LOAD

A

2

W202MOTOR
(DPST)
A

2

X

X

M

M
A Motor1
Clock
Supply

LOAD

A

LOAD

1

L

H

H

Metal Indoor
NEMA 1

1

LOAD

1

H

H

6

W400A (4PST)

Metal Indoor/Outdoor
NEMA 3

L

LOAD

N

3PST

M

4

L

6
LOAD

2

3

L

LOAD

3

L

LOAD

2

X

M

W220 (DPDT)

M

M

L
X

1

W220 (DPDT)

W120 (SPDT)

W120 (SPDT)

DPDT

W400A

H

L

Typical for 208-240VAC

1

X

LOAD

LOAD
1

X

LOAD

H

2

LOAD

2

LOAD

Typical for 277VAC

H

Typical for 208-240VAC

Typical for 277VAC

B

WITH RESERVE POWER
W220L

39009

120

DPDT

W222L

39010

208-277

DPDT

W300L

39005

120

3PST

W302L

39006

208-277

3PST

W400AL

39007

120

4PST

Supply
Supply

Metal Indoor
NEMA 1

Replacement
Trippers

Order #P69 for 7 pairs of ON/OFF trippers
except W400 series use #P69i.

Replacement
Motor

#101 (120V) & #201 (208-277V). For W400 series units order #101i
(120V) & #201i (208-277V). For “L” models order #36 (120V)
and #46 (208-277V), except W400 series consult factory.

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

M

M

H

W220

W300 (3PST)

W300 (3PST)

M

M

DPST
DPST

W200 (DPST)

W200 (DPST)

M

TORK 43

40A

Tungsten

ENCLOSURE: Indoor NEMA 1 Metal with lockable
hasp. Other enclosures include metal Indoor/
Outdoor NEMA 3 with suffix "O" (see page 153 for
enclosure dimensions).

W120

ELECTROMECHANICAL
CONTROLS

120 -277VAC
single phase
120 -277VAC
single phase

General Purpose

TIMING ACCURACY: Line frequency.

CONTACT
RATING

VOLTAGE

To Load(s)
To Load(s)

SPECIFICATION WRITER’S GUIDE
		 Furnish and install, where shown, TORK time switch of the 7 day type, powered by a self-starting synchronous motor, capable of being set for different ON/
OFF times each day of the week, to an operating accuracy of plus or minus 15 minutes of the desired time. Time switch contacts shall be capable of switching
40 amperes per pole continuously at 277 volts and shall be SPST (DPST, 3PST, DPDT, SPDT, 4PST as required). Removable ON/OFF trippers shall make possible
automatic operation with a minimum ON period of one hour and a minimum of 2 hours between one OFF operation and the next ON. Models W400 and W402
offer minimum ON and OFF settings of 3.5 hours. Enclosure shall be NEMA 1 surface, finished in baked beige enamel, with combination 1⁄2” - 3⁄4” knock-outs
on bottom and both sides. Provision shall be made for positive padlocking. Terminals shall be capable of receiving #8AWG wire. Time switch shall be TORK
Model W_ _ _ (to fit requirement). FOR RESERVE POWER (Add suffix L): Spring-driven reserve shall be provided sufficient to operate the Time Switch contacts
at least 24 hours after power failure (16 hour reserve power on 4PST models). On restoration of power, time switch shall transfer to synchronous motor driven
and automatically rewind reserve power unit.

TORK 44

LOAD

T900 SERIES

INPUT VOLTAGE: 120 or 208-277VAC, 60 Hz,
varies by model.
TIMING ACCURACY: Line frequency.
TERMINAL RANGE: #8 - #14AWG.

APPLICATIONS

TYPE

VOLTAGE

CONTACT
RATING

General Purpose

120/277VAC

20A

Motor

120VAC
240VAC

1HP
2HP

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

CALIFORNIA Title 24
ASHRAE 90.1

Parking lot lighting
HVAC
Display lighting
Security lighting
Lighted signage
Storefront lighting

CONTACT RATINGS

SPECIFICATIONS

PHOTOELECTRIC & 7 DAY CONTROL COMBO
DIFFERENT SCHEDULES EACH DAY
RESERVE POWER STANDARD
2 & 3 CIRCUIT LIGHTING
CONTROL CENTERS

POWER CONSUMPTION: 5 watts maximum.
ENCLOSURE: Indoor NEMA 1 Metal with
lockable hasp. Other enclosures include cover
for access to by-pass switches with suffix "E" or
Indoor/Outdoor NEMA 3 metal with suffix "O"
(see page 153 for enclosure dimensions).

Optional "E" cover

Model 2101
supplied with unit.

WIRING DIAGRAMS
T930L
T930L

T920L
T920L

ONLYCIRCUITS
CIRCUITS1 1AND
AND2 2ARE
AREINCLUDED
INCLUDEDININT920L
T920L
ONLY

ORDERING INFO
FEATURES

CATALOG
NO.

SCHEDULING:
CIRCUIT 1: ON automatically at dusk, OFF at
individual preset times each day, including
skipping days when desired. Unit can be set to
turn ON before dawn for early morning lighting.
CIRCUIT 2: ON at dusk, OFF at dawn
automatically, daily.
CIRCUIT 3: Individual daily ON and OFF settings
at desired times, including skipping any desired
day or days Minimum ON is setting 1 hour with
a minimum OFF setting of 2 hours. Minimum 8
hours between 2 OFF settings. 7 day calendar dial
will accommodate up to 2 pairs of ON-OFF trippers
per day – 7 pairs are supplied.
SKIP-A-DAY: Omit operations on any day.

UPC
CODE

INPUT SUPPLY
(VAC) 60Hz

41033

120

2 SPDT

T920L-E

41034

120

2 SPDT

T920L-O

41035

120

2 SPDT

T930L

41055

120

3 SPDT

T930L-E

41056

120

3 SPDT

T930L-O

41057

120

3 SPDT

Metal Indoor
NEMA 1
Metal Indoor NEMA
1 with switch access
Metal Indoor/outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor NEMA
1 with switch access
Metal Indoor/outdoor
NEMA 3

ON ON OFF OFF

ON ON OFF OFF

AUTO
AUTO

AUTO
AUTO

SWITCH
TIMETIME
SWITCH
OFF OFF ON ON

MM

C C

NOTE:
NOTE:
Contacts
7-12
Contacts
7-12
unpowered.
areare
unpowered.

RELAY
RELAY

PHOTOELECTRIC
PHOTOELECTRIC
CONTROL
CONTROL

ON ON OFF OFF

ON ON OFF OFF

ON ON OFF OFF

AUTO
AUTO

AUTO
AUTO

AUTO
AUTO

NOTE:
NOTE:
Contacts
4-12
Contacts
4-12
unpowered.
areare
unpowered.

RELAY
RELAY

C C
PHOTOELECTRIC
PHOTOELECTRIC
CONTROL
CONTROL

MM

CONTACTOR
CONTACTOR
CONTROL
CONTROL
CIRCUIT LINELINE
CIRCUIT

RED RED
WHITE
WHITE
BLACK
BLACK

L1 L1
OPEN
CLOSEOPEN LINELINE
CLOSE

1 1

CONTACTOR
CONTACTOR
CONTROL
CONTROL
CIRCUIT
CIRCUIT

1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12

1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12
H 120V
H 120V
N N
60C 60C
LINELINE

TIME
TIME
SWITCH
SWITCH

TO DAWN
SAFETY
LIGHTS
DUSKDUSK
TO DAWN
SAFETY
LIGHTS
(PHOTOCELL
- PHOTOCELL
(PHOTOCELL
ON - ON
PHOTOCELL
OFF) OFF)

NEU.NEU.
OPEN
OPEN
CLOSE
CLOSE

H 120V
H 120V
N N
60C
BLACK 60C
BLACK
LINELINE
WHITE
WHITE
RED RED

2 2

L1 L1
LINELINE
OPEN
OPEN
OPENLINELINE
OPEN
CLOSE
CLOSE
CLOSE
CLOSE

3 3

1 1

TO DAWN
SAFETY
LIGHTS
DUSKDUSK
TO DAWN
SAFETY
LIGHTS
(PHOTOCELL
- PHOTOCELL
(PHOTOCELL
ON - ON
PHOTOCELL
OFF) OFF)

2 2

NEUNEU
OPEN
OPEN
CLOSE
CLOSE

LOAD
LOAD

LOAD
LOAD

#P69 for 7 pairs of ON/OFF trippers.
#36 (120V)
#66061

RESERVE POWER: Standard feature on all
models keep dial on time up to 24 hours during
power outage.
NOTE: All models are designed to control a contactor circuit and are not recommended for direct switching of most lighting loads.

TORK 45

ENCLOSURE
TYPE

OUTPUT
CONTACTS

MANUAL BY-PASS SWITCHES: Single pole,
20 Amps – one per circuit. Factory pre-wired to
terminal strip. ON/OFF/AUTO positions for each
circuit is independent – will not disturb automatic
settings.

ELECTROMECHANICAL
CONTROLS

MANUAL
CONTROLS
MANUAL
CONTROLS

MANUAL
CONTROLS
MANUAL
CONTROLS

T920L

Replacement
Trippers
Replacement
Motor
Replacement
Bypass Switch

ALL3 3CIRCUITS
CIRCUITSARE
AREINCLUDED
INCLUDEDININT930L
T930L
ALL

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

SPECIFICATION WRITER’S GUIDE
		 T900 SERIES – Furnish and install, where shown, a TORK Photo/Time Control of the 7 Day Calendar dial type, which shall be suitable to operate mechanicallyheld contactor(s). Photo/Time Control shall be pre-wired to a central terminal block which provides connecting terminals for Photocontrol and independent
contactor control circuit(s). Time switch shall function to prevent energization of lighting for preset periods each day. Time switch dial shall permit different
ON/OFF settings for each day of the week, with provision for omitting selected days. Control shall include pre-wired manual switching for each contactor circuit
specified. Enclosure shall be NEMA 1 surface. Photocontrol to be remotely installed in appropriate outside location. It shall be fully temperature compensated
and shall provide for time delay of at least 15 seconds to prevent false switching. Photocontrol shall operate control center to energize whenever natural lighting
falls below 1.5 - 5.5 foot candles turn on. Spring driven reserve timing motor shall be provided sufficient to operate time switch controls at least 24 hours after
power failure. On restoration of power, time switch shall transfer to synchronous motor drive and automatically rewind reserve power unit. FOR DUSK-TO-DAWN
LIGHTS: Control shall provide additional contactor circuit to above specifications except that it shall be responsive to Photocontrol only. Tork Model T-920L or
equal. FOR PRESET ON/PRESET OFF: Control shall provide for additional contactor circuit to above specification except that it shall be responsive to time switch
only. Tork Model T-930L.

TORK 46

TW SERIES

INPUT VOLTAGE:
120 or 208 - 277VAC, 60Hz, varies by model.

TYPE

VOLTAGE

CONTACT
RATING

General Purpose

120/277VAC

20A

Motor

120VAC
240VAC

1HP
2HP

TIMING ACCURACY: Line frequency.
TERMINAL RANGE: #8 - #14AWG.

CALIFORNIA Title 24

OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

ASHRAE 90.1

APPLICATIONS
Heating
Air conditioning
Display lighting
Ventilating systems
Lighted signage
Storefront lighting

CONTACT RATINGS

SPECIFICATIONS

DIFFERENT SCHEDULES EACH DAY
MANUAL BYPASS SWITCHES
RESERVE POWER STANDARD
7 DAY TIME SWITCH

POWER CONSUMPTION: 5 watts maximum.

Optional "E" cover

ENCLOSURE: Indoor NEMA 1 Metal with lockable
hasp (see page 153 for enclosure dimensions).

WIRING DIAGRAMS
MANUAL CONTROLS
MANUAL
CONTROLS
ON
ON
OFF
ON

AUTO

ORDERING INFO
FEATURES

CATALOG
NO.

UPC
CODE

OUTPUT
CONTACTS

SCHEDULING: Minimum ON setting is 1
hour with a minimum OFF setting of 2 hours.
Minimum 8 hours between 2 OFF settings. 7 day
calendar dial accommodates up to 2 pairs of
ON-OFF trippers per day – 7 pairs are supplied.

TW-220L

39013

120

DPDT

TW-220L-E

39021

120

DPDT

TW-222L

39014

208-277

DPDT

SKIP-A-DAY: Omit operations on any day.

TW-300L

MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
MANUAL BY-PASS SWITCHES: Single pole,
20 Amps – one per circuit. Factory pre-wired
to terminal strip. ON/OFF/AUTO positions for
each circuit is independent – will not disturb
automatic settings.

TW-302L
Replacement
Trippers
Replacement
Motor
Replacement
Bypass Switch

39016

120

3PST

208-277

3PST

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

1

2

1

#36 (120V) & #46 (208-277V)
#66061

3

ON

5

4

5

AUTO

6
6

NOTE:
Switching contacts
NOTE:
are unpowered
Switching contacts
are unpowered

OFF

OFF
AUTO

7

9

8

7

9

8

LINE
LOAD
LINE
LINE
LOAD
LOAD
LINE

N

H
N

H

TW300L
TW300L

When single line source is
When
source is
used, single
jumperline
terminals
used,
jumper
terminals
1-5-7-9 and connect all com1-5-7-9
and
connect2all
commons to
terminals
and
3.
mons to terminals 2 and 3.

LOAD
LINE
LOAD
LINE
LOAD

MANUAL CONTROLS
MANUAL
CONTROLS
ON
OFF
ON

1

2

1

H

3

4

OFF

TW220L
TW220L

OFF
AUTO

AUTO

TIME
SWITCH
TIME
SWITCH
2
4
3

M
M

ON
ON

OFF
AUTO

AUTO

5
5

6
6

7
7

8
8

CONTACTOR
CONTROL
CONTACTOR
CIRCUIT
9
CONTROL
CIRCUIT
9

N

H

NOTE: All models are designed to control a contactor circuit and are not recommended for direct switching of most lighting loads.

TORK 47

Metal Indoor
NEMA 1
Metal Indoor NEMA
1 with switch access
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1

Order #P69 for 7 pairs of ON/OFF trippers.

RESERVE POWER: Standard feature on all
models keep dial on time up to 24 hours during
power outage.

ELECTROMECHANICAL
CONTROLS

ENCLOSURE
TYPE

M

ON

OFF

OFF
AUTO

AUTO

TIME
SWITCH
TIME
SWITCH
2
4
3

M

INPUT SUPPLY
(VAC) 60Hz

39015

ON

OFF
AUTO

N

CONTACTOR
CONTROL
CONTACTOR
CIRCUIT
CONTROL
CIRCUIT

COMMON
OPEN
COMMON
CLOSE
OPEN
CLOSE
COMMON

COMMON
OPEN
CLOSE
OPEN

Wiring shown is for mechaniWiring
shown
is for mechanically-held
contactors.
Use
cally-held
contactors.
CLOSE terminal
onlyUse
for magCLOSE
terminalcontactors
only for magnetically-held
and
netically-held
contactors
and
to control direct
loads not
toexceeding
control direct
loads
not
2000
watts.
exceeding 2000 watts.

CLOSE

SPECIFICATION WRITER’S GUIDE
Furnish and install, where shown, a TORK time switch of the 7 day type, capable of being set for different ON/OFF times each day of the week, to an operating accuracy
of plus or minus 15 minutes of the desired time. The time switch shall be powered by a self-starting synchronous motor with spring-driven reserve, which shall be
sufficient to operate the time switch contacts at least 24 hours after power outage. On restoration of power, time switch shall transfer to synchronous motor drive and
automatically rewind reserve power unit. Time switch shall provide for automatic operation with a minimum of one hour between an ON/OFF operation with minimum
of four ON/OFF operations per day. ON/OFF operations shall be accomplished by removable ON/OFF trippers on the dial. Time switch contacts shall be capable of
carrying a minimum 20 amperes per pole continuously at 277 volts and shall be DPDT or 3PST. Manual switches shall be provided as an integral part of the time switch,
one for each pole, and shall permit manual switching to maintained ON or OFF positions until manually returned to AUTOMATIC position. Terminal strip shall be capable
of receiving #10AWG wires. Enclosure shall be NEMA 1 surface type, finished in beige enamel, and with 1⁄2” - 3⁄4” combination knock-outs on bottom, both sides and
top. Provision shall be made for positive padlocking. (Specify “E” door for manual switches to be accessible when case is locked). Shall be TORK Model TW (to fit switch
requirement) or equal in general purpose NEMA 1, (general purpose metal) or (Indoor/Outdoor NEMA 3) enclosure.

TORK 48

TZ SERIES

CONTACT RATINGS

SPECIFICATIONS

MANUAL BYPASS SWITCHES
RESERVE POWER STANDARD
ASTRONOMIC TIME SWITCH

INPUT VOLTAGE:
120 or 208 - 277VAC, 60Hz, varies by model.

TYPE

VOLTAGE

CONTACT
RATING

General Purpose

120/277VAC

20A

Motor

120VAC
240VAC

1HP
2HP

TIMING ACCURACY: Line frequency.
TERMINAL RANGE: #8 - #14AWG.
OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).

CALIFORNIA Title 24

APPLICATIONS

ASHRAE 90.1

POWER CONSUMPTION: 5 watts maximum.

Schools
Industrial yards
Shop windows
Parking lots
Highway signs
Bridges

ENCLOSURE: Indoor NEMA 1 Metal with
lockable hasp and for some models enclosures
is Indoor/Outdoor NEMA 3 metal with suffix "O"
(see page 153 for enclosure dimensions).

WIRING DIAGRAMS
ASTRONOMIC LATITUDE ZONES
45°
42°

ORDERING INFO
FEATURES
SCHEDULING: Turn ON at sunset and OFF at
sunrise daily. OFF time can be set from 8:30PM
to 2:30AM. Can be individually offset +/- 20
or 40 minutes from both sunset and OFF times.
Available from 18° - 45° northern latitudes.
SKIP-A-DAY: Omit operations on any day with
a 7 spoke wheel marked with days of the week.
3 omitting screws included.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
MANUAL BYPASS SWITCHES: Single pole,
20 Amps - one per circuit. Factory pre-wired to
terminal strip. ON/OFF/AUTO positions for each
circuit is independent, will not disturb automatic
settings.

CATALOG
NO.

TZ-220L*
TZ-220L-O*

UPC
CODE

**
**

INPUT SUPPLY
(VAC) 60Hz

40°
OUTPUT
CONTACTS

120

DPDT

120

DPDT

TZ-222L*

**

208 - 277

DPDT

TZ-300L*

**

120

3PST

TZ-300L-O*
TZ-302L*
Replacement
Motor
Replacement
Bypass Switch

**
**

120

3PST

208 - 277

3PST

Metal Indoor
NEMA 1
Metal Indoor/outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor/outdoor
NEMA 3
Metal Indoor
NEMA 1

34°

NOTE:
Switching contacts
NOTE:
are unpowered
Switching contacts
are unpowered

AUTO
WASHINGTON

OREGON

NORTH DAKOTA

MONTANA

MINN

WYOMING

MAINE

WISCONSIN

SOUTH DAKOTA

IDAHO

AUTO

MICHIGAN

NH
NEW YORK

NEBRASKA
ILLINOIS
NEVADA

UTAH

IND

COLORADO
KANSAS

PENNSYLVANIA

OHIO

KENTUCKY

ARIZONA

NEW MEXICO

ARKANSAS

TENNESSEE

RHODE ISLAND
CONNECTICUT

VIRGINIA

DELAWARE
MARYLAND

M

2

1

3

5

4

5

6
6

7
7

9

8

LINE
LOAD
LINE
LINE
LOAD
LOAD
LINE
LINE
LOAD
LOAD
LINE
LOAD

9

8

N

H

N

H

NORTH CAROLINA
SOUTH
CAROLINA

MISS
ALABAMA

TEXAS

1

MASS

NEW JERSEY

WEST
VIRGINIA

MISSOURI

CALIFORNIA
OKLAHOMA

M

VT

IOWA

TIME
SWITCH
TIME
2 SWITCH
4
3

GEORGIA

LOUISIANA

30°

TZ300L
TZ300L
When single line

sourcesingle
is used,
When
line
jumperis terminals
source
used,
1, 5, 7,terminals
9 and connect
jumper
1,all5,commons
7, 9 and toconnect
allterminals
commons2 and
to 3.
terminals 2 and 3.

MEXICO
FLORIDA

18° HAWAII

MANUAL CONTROLS

18° PUERTO

MANUAL CONTROLS

RICO

M
1
1
H
H

M

TIME
SWITCH
TIME
2 SWITCH
4
3
2

3

4

5
5

6
6

7
7

8
8

9
9

N
N

CONTACTOR
CONTROL
CONTACTOR
CIRCUIT
CONTROL
CIRCUIT

CONTACTOR
CONTROL
CONTACTOR
CIRCUIT
CONTROL
CIRCUIT

COMMON
OPEN
COMMON
CLOSE
OPEN
COMMON
CLOSE

OPEN
COMMON
CLOSE
OPEN
CLOSE

TZ220L
TZ220L
Wiring shown is for

mechanically
Wiring
shown isheld
for
contactors. Use
mechanically
heldCLOSE
terminal only
contactors.
Usefor
CLOSE
magnetically
held
terminal
only for
contactors and
magnetically
heldto
control direct
contactors
and loads
to not
exceeding
control
direct2000
loadswatts.
not
exceeding 2000 watts.

#66061

*Add degrees latitude to complete number (18, 30, 34, 38, 40, 42, or 45).
**Consult factory for UPC number.

NOTE: All models are designed to control a contactor circuit and are not recommended for direct switching of most lighting loads.

TORK 49

38°

For "L" models #36 (120V) & #46 (208-277V)

RESERVE POWER: Standard feature on all
models keep dial on time up to 24 hours during
power outage.

ELECTROMECHANICAL
CONTROLS

ENCLOSURE
TYPE

MANUAL CONTROLS
MANUAL CONTROLS

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

SPECIFICATION WRITER’S GUIDE
Furnish and install, where shown, a TORK time switch with Astronomic dial and day-omitting device, and a 3-way manual switch for each circuit. The time switch shall
be powered by a self-starting synchronous motor with spring-driven reserve, which shall be sufficient to operate the time switch contacts at least 16 hours after power
failure. On restoration of power, time switch shall transfer to synchronous motor drive and automatically rewind reserve. ON operation shall occur automatically at
sunset in (city of use). OFF operation shall be adjustable from 8:30 P.M. to 2:30 A.M. in one-half hour increments or at sunrise. Both ON and OFF shall have a range of
adjustability of 20 or 40 minutes before or after sunset and sunrise. Time switch contacts shall be capable of carrying a minimum of 20 amperes per pole continuously
at 277 volts and shall be DPST (3PST). Manual switches shall be provided as an integral part of the time switch, one for each pole, and shall permit manual switching
to maintained ON or OFF positions until manually returned to AUTOMATIC position. Terminal strip shall be capable of receiving #10AWG wires. Enclosure shall be NEMA
1 surface type, finished in beige enamel, and with 1⁄2” - 3⁄4” combination knock-outs on bottom, both sides and top. Provision shall be made for positive padlocking.
(Specify “E” door for manual switches to be accessible when case is locked). Time switch shall be TORK Model TZ-___ (to fit requirement).

TORK 50

DIGITAL
TIME SWITCHES

FEATURES
QUICK LOOK
DTU40

DTWH40

E-PB

E

EW

EWZ

DG

DGM

DZS

DTS

DWZ

Page No.

55

55

57

57

59

61

63

63

65

67

69

Number of Channels

1

1

1

1 or 2

1 or 2

1 or 2

1 or 2

1

1, 2, or 4

1, 2, or 4

20 (140)

20

20

20

56

56

99

ON/OFF Set Points

7 pair (98) 7 pair (98)

DW

DZM

ELC71/72 ELC74/78/712

Page No.

69

71

73

1

Number of Channels

2

2

99

99

ON/OFF Set Points

99

99

7/365 day

7/365 day

7/365 day

LIGHTING CONTROLS

CYCLE - SIGNAL TIMER

DGU

DGUM

DGLC

DLC400

DG

DGS

DIN

75

79

79

79

81

85

85

89

1 or 2

4, 8, or 12

1

1

1 or 2

4

1 or 2

1

1 or 2

128

128

56

56

56

99

56

56

8 pair
3 pair/ch

7/365 day

7/365 day

24 Hour

7 Day

7 Day

365 Day/7 Day Scheduling

7 day

7 day

24 hour

24 hour

7 day

7 day

Automatic Daylight
Savings Adjustment

Manual

Manual

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Automatic Daylight
Savings Adjustment

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Leap Year

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

24

24

24

Individual Holiday Schedules

24

24

26

26

10

10

Yes

Yes

Yes

Yes

Leap Year

7/365 day 7/365 day

ENERGY/LIGHTING
CONTROLS

Individual Holiday Schedules
Block Holiday

9

9

Season Scheduling

Block Holiday
4

Astronomic (Sunrise/Sunset)

Yes

365 Day/7 Day Scheduling 7/365 day 7/365 day

4

Yes

Yes

Season Scheduling

4

Astronomic (Sunrise/Sunset)

Yes

7/365 day 7/365 day 7/365 day 7/365 day

24
9

9

9
4

Yes

Yes

Yes

Photosensor Input

Photosensor Input

Yes

Yes

Yes

Yes

Yes

Yes

Remote Override Input

Remote Override Input

Yes

Yes

Yes

Yes

Yes

Yes

User Defined Input

User Defined Input

Yes

Yes

Signal/Pulse Duration

Yes

Yes

Yes

Yes

Yes

Yes

Signal/Pulse Duration

Yes

Momentary for Contactors

Option

Option

Option

Yes

Yes

Momentary for Contactors

Duty Cycle

Duty Cycle

31 Day Cycle

31 Day Cycle

Yes

Yes

Yes

Manual Override

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Manual Override

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Clock Format

AM/PM

AM/PM

AM/PM

AM/PM

AM/PM

AM/PM

12/24

12/24

12/24

12/24

12/24

Clock Format

12/24

12/24

12/24

12/24

12/24

12/24

12/24

12/24

12/24

12/24

AM/PM

7 day Super
Capacitor

7 day Super
Capacitor

Power Outage Backup

Permanent

Permanent

Permanent

Schedule Retention
without power

Yes

Yes

Power Outage Backup
Schedule Retention
without power

Rechargeable Rechargeable 4 day Super 4 day Super 4 day Super 4 day Super 7 day Super 7 day Super 7 day Super
Battery
Battery
Capacitor Capacitor
Capacitor
Capacitor Capacitor Capacitor
Capacitor
Battery

Battery

Staggered Start

Permanent Permanent
Yes

Yes

Permanent
Yes

Permanent Permanent Permanent
Yes

Yes

Yes

Memory Module
Computer Programming
Software
Output Contacts: Amps
Resistive or General Purpose

Staggered Start

Yes

Memory Module

Yes

Computer Programming
Software
Output Contacts: Amps
Resistive or General Purpose
Contact Type: Dry
Unpowered

40A

40A

30A

40A

40A

40A

20A

20A

30A/20A

30A/20A

30A

Contact Type: Dry Unpowered

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Voltage Input AC

120/208240/277

120/208240/277

120

120-277

120-277

120-277

120-277

120-277

120/208240/277

120/208240/277

120/208240/277

Low Voltage Input
(select models)
TORK 53

12VDC 24VAC

Voltage Input AC
Low Voltage Input
(select models)

7 day Super 7 day Super 7 day Super
Capacitor Capacitor
Capacitor
Permanent Permanent
Yes

Yes

2 day Capacitor 7 day Super 7 day Super 7 day Super
1 year battery Capacitor
Capacitor
Capacitor

Capacitor

Battery

Permanent

Permanent

Yes

Yes

Yes

Yes

6 month
battery

7 day Super 7 day Super
Capacitor
Capacitor

Permanent Permanent Permanent
Yes

Yes

Yes

Permanent

Yes

Yes

8 year battery
Battery

Yes

Yes

Yes

Yes

30A

30A

20A

20A

20A

20A

20A

30A

20A

20A

16A

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

24/120/208
240/ 277

120-277

120-277

120-277

120/208240/277

120-277

120-277

120

12VDC
24VAC

24VAC

120/208- 120/208- 120/208-240/
240/277 240/277
277

24VAC All Models

TORK 54

DT SERIES

NEW!

AUTOMATIC VOLTAGE DETECTION
24 HOUR OR 7 DAY HOUR
TIME SWITCH

MORE WIRING
SPACE!
NEW!

INPUT VOLTAGE: 120/208-240/277
VAC, 50/60 Hz (auto detection). DTWH40 is
120/240VAC (auto detection).

TYPE

VOLTAGE

Resistive

TERMINAL RANGE: #8 - #18AWG.
OPERATING TEMPERATURE:
-31°F to 116°F (-35°C to +47°C).

APPLICATIONS
DTU40
Pumps, motors, fans
Signs and lighting
Water heaters
Heating and air conditioning

CONTACT RATINGS

SPECIFICATIONS

POWER CONSUMPTION: 6VA Max.
ENCLOSURE: DTU40 polycarbonate Indoor/
Outdoor NEMA 3R. DTWH40 polycarbonate
indoor NEMA 1 enclosure with clear cover. Both
with lockable hasp (see page 153 for enclosure
dimensions).

DTU40

DTWH40

DTWH40
Water Heaters
This timer turns OFF when rates
are high and turns OFF when no
one is home.

SAVE
ENERGY!

120-277VAC

40A

30A

Inductive

120-277VAC

30A

15A

Ballast

120VAC
277VAC

30A
20A

10A
10A

Tungsten

120VAC

15A

120VAC
240VAC
120VAC
240VAC

1HP/30FLA/90LRA
2HP/20FLA/60LRA
720VA
720VA

Resistive

28VDC

20A

Max above 104°

120-277VAC

30A

Pilot duty

1⁄4HP/12FLA/30LRA
1⁄2HP/12FLA/33LRA

290VA
260VA

Typical
Wiring
Diagram,
Application
Typical
Wiring
Diagram,
120120/277VAC
VAC Application
TIMER
SUPPLY
N

NC

CATALOG
NO.

UPC
CODE

TIMER SUPPLY
(VAC) 60Hz

NO. OF
CHANNELS

DRY CONTACTS
(UNPOWERED)

L

N

DTU40

24004

120/208-240/277

1

DPDT

DTWH40

24005

120/240

1

DPDT

H

NC

N

NO

C

LOAD
L

N

NC

NO

C

WIRING DIAGRAMS
L1

MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.

C

N

L

Typical Wiring Diagram, 208-240 VAC Application
TIMER
SUPPLY

DAYLIGHT SAVING: Manual button push for
one hour adjustment.

NO
LOAD

ORDERING INFO

SCHEDULING: 7 ON & OFF pairs of set points
for individual programs on each day of the
week. Minimum setting is 1 minute.

NC

DTU40

H

FEATURES

NO

Motor

Avoid utility peak rates
Turn off when not needed

RATING

NC

NO

C

LOAD

L2

L1

L2

DTWH40

DTU40

Typical
Wiring120
Diagram,
120VAC
Typical
Wiring
Diagram,
120/277VAC
Application
Typical
Wiring
Diagram,
VAC Application

EXTERNAL MANUAL OVERRIDE: DTWH40
only on clear door. Override without opening
case.

TIMER
SUPPLY
H

N

TIMER
SUPPLY
NC

NO

C

NC

LOAD

RANDOM MODE: Varies ON and OFF times to
create "lived-in" look when away.

L

CLOCK FORMAT: AM/PM.

Typical
Wiring
Diagram,
Application
Typical
Wiring
Diagram,
120120/277VAC
VAC Application

N

N

NO

C

H

L

N

L

TIMER
SUPPLY
H

N

NC

NO

C

L

N

N

L2

NO

C

LOAD
L

N

L

Typical Wiring Diagram, 208-240 VAC Application
TIMER
SUPPLY

NC

NO

C

NC

NO

C

H

N

NC

NO

C

LOAD
L1

NC

LOAD

Typical Wiring
208-240
VAC Application
Typical Diagram,
Wiring Diagram,
240VAC

POWER OUTAGE BACKUP: Battery retains
time and schedule.

N

LOAD

L1

NC

NO

C

LOAD
L2

L1

L2

L1

L2

DTWH40
Typical
Wiring120
Diagram,
120VAC
Typical
Wiring
Diagram,
120/277VAC
Application
Typical
Wiring
Diagram,
VAC Application

DIGITAL
CONTROLS
TORK 55

TIMER
SUPPLY
H

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

N

NC

NO

C

LOAD
L

N

N

NC

NO

C

LOAD
L

N

L

TORK 56

E & E-PB SERIES

CONTACT RATINGS

SPECIFICATIONS

BACK-UP WITHOUT BATTERY,
ECO FRIENDLY!

MULTIPURPOSE CONTROLS
1 OR 2 CHANNEL
24 HOUR TIME SWITCH

INPUT VOLTAGE:
E SERIES
120 - 277VAC, 50/60Hz (automatic detection).
E-PB
120VAC, 50/60Hz.

APPLICATIONS

TERMINAL RANGE: #8 - #16AWG.

E101B

Signs
Air conditioning
Lighting
Sump pumps
Ventilating fans

OPERATING TEMPERATURE:
-40° to +149°F (-40° to +65°C).

1

4CONSUMPTION: 6VA Max.
3
POWER

ENCLOSURE: Plastic Indoor/Outdoor NEMA 3R
is standard
with lockable hasp (see page 153 for
L
N
N
120/277VAC
enclosure dimensions).

2A

120VAC

5A

720VA

720VA

720VA

120-277VAC

470VA

1HP

1HP
11⁄2HP
2HP

1HP
11⁄2HP
2HP

120VAC
240VAC

1HP
2HP

30A

30A

28VDC

20A

30A

Inductive

120-277VAC

40A

30A

30A

Ballast

120VAC
208-277VAC

30A
20A

30A
20A

Tungsten

120VAC

15A

120-277VAC

Pilot Duty

E101B

3

2

120VAC
TIMER
5
SUPPLY
LOAD 208VAC
240-277VAC

Motor4

LOAD

LOAD

L

15A

30A

SPDT

1

10A
10A

30A
12A
30A
12A
20A
6A

40A

TIMER
SUPPLY

Resistive
N

N

N

1
28VDC

SPST
11 2HP

⁄

2HP

2

3

120/277VAC

E101PB
VOLTAGE
RATING
NO

120/240VAC
277VAC
120/240VAC
277VAC
120VAC
277VAC

120-277VAC

SPST

2

E120B
RATING
NO
NC

VOLTAGE

General Purpose

E120B

TIMER
SUPPLY

E101B, E103B, E201B
RATING
NO

TYPE

TIMING ACCURACY: Line Frequency.

4

30A

E120

TIME
SUPP
1

LOAD
L

N

N

L

120/277VAC

WIRING DIAGRAMS

E103B

DPST

TIMER
SUPPLY

E101B
1

FEATURES
SCHEDULING: 20 ON/OFF set points repeat
each day. Minimum setting 1 minute.

E101B

UPC
CODE

82401

INPUT SUPPLY
(VAC) 50/60Hz

120-277

NO. OF
CHANNELS

OUTPUT
DRY CONTACTS

1

E103B

82411

120-277

1

82406

120-277

1

LEAP YEAR: Automatic Compensation.

E201B

82466

120-277

2

E101PB

82401

120-277

L

1N

N

2

3

L

TIMER
SUPPLY

L

1

4

N

E101B

2

3

4

N
5

N

3

1
2
TIMER
SUPPLY

SPST
LOAD

1

N

120/277VAC

2
N

L

6

TIMER
SUPPLY
1
LOAD

E101PB
DPST

SPDT
TIMER
SUPPLY
1

3

2

N

L

2

LOAD

4

3

4

LOAD

5

TIMER
SUPPLY

5

6

1

2

L

N

4
N

5

N

3

4

5

120/277VAC

N

2

3

4

5

6

PULSE OFF
E201B

E201B ONLY: UNIT MUST
BE CONFIGURED FOR
TIMER
MOMENTARY
OPTION.

2

L

N

N

3
TIMER
SUPPLY
LOAD
1

3

CH 1
SP

4

3

2

LOAD

N

120VAC
N

6
TIMER
SUPPLY

PULSE ON

1

L

E201B

L

L2

208 OR 240VAC

CH 1
SPST

LOAD

LOAD

1

2

L

N

MOMENTA
C

3

4

CH 2
SPST

SUPPLY

N

L

2

SPST

120/277VAC

LOAD

N

N

L

DPST

TIMER
SUPPLY

MOMENTARY CONFIGURATION
CH 1

L1

6

N

120/277VAC

1
LOAD

N

L
N
N
N 120/277VAC

4DPST
5
LOAD

LOAD

3

L

1

120/277VAC
L

N

N

TIMER
SUPPLY

LOAD

POWER OUTAGE BACKUP: Permanent
schedule retention. Supercapacitor provides
4 days of real time backup.

5

6

E103B

4

3

LOAD

4

120/277VAC

TIMER
SUPPLY
LOAD

L2

3

2

L

N

SPDT
L1

208 OR 240VAC

SPST

1

2

E120B E103B

LOAD

E120B

SPST
SPDT

TIMER
SUPPLY

1

1

DPST

CH 2
SPST

LOAD

DPST

TIMER
SUPPLY

CH 1
SPST

LOAD

120/277VAC

SPST

L

CLOCK FORMAT: AM/PM.

4

5

6

N

L

N

120/277VAC
LOAD

PULSE O

E201B O
BE CON
MOMEN

120/277VAC

120/277VAC

DPST

TIMER
SUPPLY

1

E201B

1

2

4

3

5

6

LOAD
L

LOAD
N

N

N

L

120/277VAC
DPST

TIMER
SUPPLY

1

2

3

4

5

6

L2

208 OR 240VAC

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

LOAD

2

3

4

5

6

CH 1
CH 2
SPECIFICATION
SPST
SPST WRITER’S

MOMENTARY CONFIGURATION

TIMER
GUIDE
CH 1
SUPPLY
TIMER
E100B
only
–
1.
Furnish
and
install
a
TORK
digital
time
switch
with
(40
Amp
SPST
contacts,
model E101B,E201B) (40 Amp DPST contacts, model E103B) (30 Amp SPDT
SUPPLY
L1
L2
contacts,
model
E120B).
2.
Unit
shall
be
capable
of
20
set
points.
3.
Unit
shall
repeat
the
same
schedule
each day. 4. (Model E201B ONLY) Unit shall be capable of being
LOAD
208 OR 240VAC
1
2
3
4
5
6
4 maintained
5
1
2
6 a 1 channel momentary 5. Unit shall have automatic Daylight Savings Time and Leap Year compensation. 6. Unit shall program in AM/PM
a32 channel
or
LOAD
LOAD
format. 7. Unit shall have LCD display. 8. Unit shall have permanent schedule retention. 9. Unit real time clock shall be retained by super capacitor for 100 hours in a
power failure. 10. Unit shall be capable of manual override ON or OFFL either
to thePULSE
nextON
scheduled
event or permanently. 11. Unit shall have a NEMA 3R Indoor/Outdoor
PULSE OFF
N
N L 12. Unit
Nshall have Load Status indication. 13. Unit shall have Power Failure indication. 14. To order specify TORK Model E101B (E103B) (E120B)
L
N
plastic enclosure.
120/277VAC E201B ONLY: UNIT MUST
120/277VAC
BE CONFIGURED FOR
MOMENTARY OPTION.
(E201B).

TIMER
SUPPLY
L1

DPST

TIMER
SUPPLY

E103B

MOMENTARY OPTION: For mechanically
held contractors: Model E201B only. Configure
with simple jumper change for single-channel
momentary operation.

TORK 57

TIMER
SUPPLY

120/277VAC

E120B

DIGITAL
CONTROLS

E201B
SPST
6

5

LOAD

DAYLIGHT SAVING: Automatic adjustment
(can be omitted).
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.

4

3

2

ORDERING INFO
CATALOG
NO.

120/2

1

2

L

N

MOMENTARY CONFIGURATION
CH 1

3

4

PULSE ON

5

6

PULSE OFF

TORK 58

EW SERIES

AUTOMATIC DST - SAVES TIME
CHANGES TWICE A YEAR

MULTIPURPOSE CONTROL
1 OR 2 CHANNEL
7 DAY TIME SWITCH

SPECIFICATIONS

CONTACT RATINGS

TIMING ACCURACY: Line Frequency.

TYPE

INPUT VOLTAGE:
120 - 277VAC, 50/60Hz (automatic detection).
energy

APPLICATIONS

ASHRAE 90.1

Outdoor signs
Lighting security
Heating and air conditioning

40A

120-277 VAC

30A

30A

Inductive

120-277VAC

40A

120-277 VAC

30A

30A

Ballast

120VAC
208-277VAC

30A
20A

120VAC
208-277VAC

30A
20A

10A
10A

Tungsten

120VAC

15A

120VAC

15A

2A

Pilot Duty

120-277VAC

720VA

120-277 VAC

720VA

720VA

Motor

120VAC
208VAC
240-277VAC

SPST
1HP TIMER
120VAC
11⁄2HPSUPPLY 208VAC
2HP
240-277VAC

1HP
11⁄2HP
2HP

1HP
11⁄2HP
2HP

Resistive

28VDC

30A

30A

POWER CONSUMPTION: 6VA Max.
ENCLOSURE: Plastic Indoor/Outdoor NEMA 3R.
EW101B
Suffix -C plastic clear cover Indoor/Outdoor NEMAEW120B
TIMER
3R. Suffix SPST
-Y metal Indoor enclosure NEMA 1. All TIMER
SUPPLY
with lockable hasp (see page 153 for enclosure SUPPLY
dimensions).
1
2
3
4
1

2

L

N

SPDT

3

LOAD

4

LOAD

5

EW101B

1

2

30A

N

N

WIRING DIAGRAMS

120/277VAC

ORDERING INFO
FEATURES
SCHEDULING: 20 ON & OFF set points
for individual programs for each day of the
week. Minimum setting is 1 minute.
DAYLIGHT SAVING:
Automatic (can be omitted).
LEAP YEAR: Automatic Compensation.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
CLOCK FORMAT: AM/PM.
POWER OUTAGE BACKUP: Permanent
schedule retention. Supercapacitor provides 4
days of real time backup.

1

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 50/60Hz

NO. OF
CHANNELS

EW101B

82431

120-277

1

SPST

EW103B

82441

120-277

1

DPST

EW120B

82436

120-277

1

SPDT

EW201B

82467

120-277

2

SPST

EW103B-C

82253

120-277

1

DPST

82255

120-277

1

L

EW120B-Y
EW201B-Y

82437
82261
82299

120-277
120-277
120-277

1
1
2

EW101B
SPST

TIMER
SUPPLY

1

2

1

3

N

3

N

120/277VAC

N
L

1

CH 2
SPST

2

120/277VAC

3

4
LOAD
PULSE OFF

LOAD

N

N

CH 1

1

2

3

4

5

1

2

N

120/277VAC

PULSE ON

L
N

N

N

DPST
momentary configuration

3

EW103B
4
5
TIMER
SUPPLY

6

1

2

DPST

1

4

3

LOAD

CH 1

TIMER
SUPPLY

5

2

3

N

LOAD
N

L

N

L

4

5

6

6

120/277VAC
N

PULSE ON

PULSE OFF

EW201B ONLY: UNIT MUST BE
CONFIGURED FOR MOMENTARY OPTION

120/277VAC

N

DPST

TIMER
SUPPLY

CH 1

3

1

2

L1

L2

3

4

5

6

DPST

TIMER
SUPPLY
4

5

6

LOAD
SPECIFICATION 1WRITER’S
GUIDE
4
3
5
6
2
208 OR 240VAC
EW SERIES – 1. Furnish and
installON
a TORKPULSE
digital OFF
time switch with (40 Amp SPST contacts, model EW101B, EW210B) (40 Amp DPST contacts, model EW103B) (30 Amp
PULSE
L
N
LOAD
LOAD
SPDT contacts,
model
EW120B).
2.
Unit
shall
be
capable
of 20 set points.
3. Unit shall be capable of a different schedule each day of the week. 4. (Model EW201B ONLY)
120/277VAC EW201B ONLY: UNIT MUST BE
CONFIGURED
FOR
MOMENTARY
OPTION
Unit shall be capable of being a 2 channel maintained or a 1 channel momentary. 5. Unit shall have automatic Daylight Savings Time and Leap Year compensation. 6.
L
N
N
L
N
Unit shall program in AM/PM
format. 7. Unit shall have LCD display. 8. Unit shall have permanent schedule retention. 9. Unit real time clock shall be retained by super
120/277VAC
capacitor for 100 hours in a power failure. 10. Unit shall be capable of manual override ON or OFF either to the next scheduled event or permanently. 11. Unit shall have
DPST
TIMER
a NEMA 3R Indoor/OutdoorSUPPLY
plastic enclosure. 12. Unit shall have Load Status indication. 13. Unit shall have Power Failure indication. 14. To order specify TORK Model
EW101B (EW103B) (EW120B) (EW201B).

1

2

L1

L2

3

4

5

6

6

208 OR 240VAC
L

N

L

EW103B

TIMER
SUPPLY

CH 2
SPST

5

LOAD

momentary configuration

CH 1
SPST

N

L2

120/277VAC

EW201B

6

LOAD

208 OR 240VAC

5

EW201B ONLY: UNIT MUST BE
CONFIGURED FOR MOMENTARY OPTION

L

5
4

6

PULSE ON

CH 2
SPST

LOAD

TIMER
SUPPLY

SPST

TIMER
4
5
SUPPLY
2

4

LOAD

120/277VAC

L1

momentary configuration

TORK 59

2

3

2

120/277VAC

CH 1
SPDT

1
L

TIMER
SUPPLY

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

3

CH 1

4

N

MOMENTARY OPTION: For mechanically
held contractors: Model EW201B only. Configure
with simple jumper change for single-channel
momentary operation.

DIGITAL
CONTROLS

L

N

EW120B
EW201B

TIMER
SUPPLY

SPDT
SPST

2
1

PULSE OFF

EW201B ONLY: UNIT MUST BE

TIM
SU
1

L

CH 1
SPST

LOAD

momentary configuration

DPST
SPDT

1

EW

120

SUPPLY

4

N

N

EW201B

TIMER
TIMER
SUPPLY

120/277VAC

L

EW120B-C

3

N

SPDT
DPST

LOAD

LOAD

EW103B-Y

2

4

120/277VAC

EW120B
EW103B

SPST
CH 2
SPST

CH
1
TIMER
SPST
SUPPLY

L

N

120/277VAC

EW101B

EW201B

OUTPUT
DRY CONTACTS

N

3

28LOAD
VDC

LOAD
L

RATING
NO
NC

120-277VAC

OPERATING TEMPERATURE:
-40° to +149° (-40° to +65°C).

CALIFORNIA Title 24

EW120B
VOLTAGE

General Purpose

TERMINAL RANGE: #8 - #16AWG.
responsible

EW101B, EW103B, EW201B
RATING
VOLTAGE
NO

LOAD

TORK 60

EWZ SERIES

PREFERRED FOR
OUTDOOR LIGHTING

MULTIPURPOSE CONTROL
1 OR 2 CHANNEL, ASTRONOMIC
7 DAY TIME SWITCH

SPECIFICATIONS

CONTACT RATINGS

TIMING ACCURACY: Line Frequency.

TYPE

INPUT VOLTAGE:
120 - 277VAC, 50/60Hz (automatic detection).
energy

APPLICATIONS

ASHRAE 90.1

Outdoor signs
Lighting security
Heating and air conditioning

40A

120-277 VAC

30A

30A

Inductive

120-277VAC

40A

120-277 VAC

30A

30A

Ballast

120VAC
208-277VAC

30A
20A

120VAC
208-277VAC

30A
20A

10A
10A

POWER CONSUMPTION: 6VA Max.

Tungsten

120VAC

15A

120VAC

15A

2A

ENCLOSURE: Plastic Indoor/Outdoor NEMA 3R

Pilot Duty

120-277VAC

720VA

120-277 VAC

720VA

720VA

Motor

120VAC
208VAC
240-277VAC

1HPTIMER
SUPPLY
11⁄2HP
2HP

SPST
120VAC
208VAC
240-277VAC

1HP
11⁄2HP
2HP

1HP
11⁄2HP
2HP

Resistive

28VDC

28 VDC

30A

30A

is standard with lockable hasp (see page 153 forEWZ120
EWZ101
SPST
enclosure
dimensions).

Suffix -MB without enclosure
TIMER
and includes mounting bracket.
SUPPLY

SPDT

TIMER
SUPPLY

1

2

3

4

1

2

3

LOAD

4

LOAD

5

LOAD
L

N

N

120/277VAC

L

WIRING DIAGRAMS120/277VAC

SCHEDULING: 20 ON & OFF set points
for individual programs for each day of the
week. Minimum setting is 1 minute.
ASTRONOMIC: Adjustable 10° - 60°
Northern or Southern latitudes. Can be
individually offset +/- 1-240 minutes
from both sunset and sunrise times.
DAYLIGHT SAVING: Automatic
(can be omitted).
LEAP YEAR: Automatic Compensation.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 50/60Hz

1

NO. OF
CHANNELS

82470

120-277

1

SPST

EWZ103

82473

120-277

1

DPST

EWZ120

82471

120-277

1

SPDT

EWZ201

82472

120-277

2

SPST

120-277

1

82269

120-277

1

DPST

EWZ120-MB

82275

120-277

1

SPDT

EWZ201-MB

82281

120-277

2

SPST

TIMER
SUPPLY

2

1

3

SPST

EWZ103-MB

SPST

2

1
L

N

CH 2
SPST

POWER OUTAGE BACKUP: Permanent
schedule retention. Supercapacitor provides 4 days
of real time backup.
MOMENTARY OPTION: For mechanically held
contactors: Model EWZ201 only. Configure
with simple jumper change for single-channel
momentary operation.
momentary configuration
CH 1

TIMER
SUPPLY

TORK 61

3

4
LOAD
PULSE OFF

1

N

L1

5

2

3

4

5

2

3

TIMER
SUPPLY

L

N

PULSE ON

L
N

CH 2
SPST

LOAD

N

N

DPST

EWZ103
4

5

6

4

5

L2

1

2

4

3

LOAD

CH 1

TIMER
SUPPLY

DPST

5

1

2

LOAD
L

N

3

N

N

L

4

5

6

6

120/277VAC
L

N

N

PULSE ON

PULSE OFF

EWZ201 ONLY: UNIT MUST BE
CONFIGURED FOR MOMENTARY OPTION

120/277VAC
DPST

TIMER
SUPPLY

1

2

3

4

5

6

6

L1
L2
4
3
5
6
1
2
SPECIFICATION
WRITER’S
GUIDE
LOAD
208 OR 240VAC
EWZ SERIES – 1. Furnish
and
install
TORK
digital
time
switch
with
(40
AMP
contacts,
models
EWZ101,
EWZ201)
(40 Amp DPST contacts, model EWZ103) (30 AMP
PULSE ON
PULSE OFF
LOAD
LOAD
L
N
contacts,
model
EWZ120). 2. Unit shall be capable of 20 set points. 3. Unit shall be capable of a different schedule for each day of the week. 4. Unit shall be have
120/277VAC EWZ201 ONLY: UNIT MUST BE
CONFIGURED
FOR1°MOMENTARY
OPTION
astronomic option adjustable
from
60° northern
or southern
latitudes. 5. Unit shall be have astronomic option with offset up to 4 hours and 59 minutes, before or
L
N
N
L
N
after sunrise. 6. (Model
EWZ201 ONLY) Unit shall be capable of being a 2 channel maintained or a 1 channel momentary. 7. Unit shall have automatic Daylight Savings
120/277VAC
Time and Leap Year compensation. 8. Unit shall
program in AM/PM format. 9. Display shall be of LCD type. 10. Unit shall have permanent schedule retention. 11. Unit
DPST
TIMER
real time clock shall beSUPPLY
retained by capacitor for 100 hours in a power failure. 12. Unit shall be capable of manual override ON or OFF either in the next scheduled event
or permanently. 13. Unit shall have NEMA Type 3 indoor/outdoor enclosure as standard. 14. Unit shall have Load Status indication. 15. Unit shall have Power Failure
indication. 16. To order1specify
4
3 Model EWZ101
5 (EWZ103)
6 (EWZ120) (EWZ201).
2 TORK

6
L2

PULSE OFF

EWZ201 ONLY: UNIT MUST BE
CONFIGURED FOR MOMENTARY OPTION

TI
SU
1

L

5

LOAD

DPST

208 OR 240VAC
120/277VAC

3

208 OR 240VAC

CH 1
EWZ103

L1

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

LOAD

N

TIMER
SUPPLY

1

2

6

LOAD

TIMER
SUPPLY

momentary configuration

CH 1
SPST

N

5
4

EW

120

CH 1
SPST

6

2

N

momentary configuration

CH 2
SPST

SPST

120/277VAC

EWZ201

4

LOAD
LOAD

N

1

EWZ201 ONLY: UNIT MUST BE
CONFIGURED FOR MOMENTARY OPTION

L

120/277VAC

3

TIMER
SUPPLY

SPDT
CH 1

PULSE ON

N

120/277VAC
N

CLOCK FORMAT: AM/PM.

DIGITAL
CONTROLS

3
2

L
N
120/277VAC

EWZ120
TIMER
SUPPLY
4
5

N

EWZ201

120/277VAC

EWZ201
3

L

4

LOAD

DPST
SPDT

CH 1

4
LOAD

L

2
1

L

N

momentary configuration

TIMER
SUPPLY

3

SUPPLY

1

4

N

2

120/277VAC

TIMER
TIMER
SUPPLY

120/277VAC

EWZ101

1

30A

N

LOAD
L

1

82263

3

OUTPUT
DRY CONTACTS

EWZ101

EWZ101-MB

2

EWZ101

EWZ120
EWZ103
SPST
CH 2
SPST

CH
1
TIMER
SPST
SUPPLY

ORDERING INFO

N

N

EWZ101

EWZ201

FEATURES

RATING
NO
NC

120-277VAC

OPERATING TEMPERATURE:
-40° to +149° (-40° to +65°C).

CALIFORNIA Title 24

EWZ120
VOLTAGE

General Purpose

TERMINAL RANGE: #8 - #16AWG.

responsible

EWZ101,EWZ103, EWZ201
RATING
VOLTAGE
NO

LOAD

TORK 62

DG100 SERIES
MULTIPURPOSE CONTROLS
1 OR 2 CHANNEL
365/7 DAY
TIME SWITCH

HOLIDAY PROGRAMMING
FOR MORE SAVINGS!

NEW!

SPECIFICATIONS

CONTACT RATINGS

TIMING ACCURACY: Line Frequency.

TYPE

VOLTAGE

NO

NC

Resistive

24-277VAC

20A

10A

Ballast

120 VAC
277 VAC

20A

10A

Tungsten

120VAC

15A

INPUT VOLTAGE:
120 - 277VAC, 50/60Hz (automatic detection).
TERMINAL RANGE: #12 - #18AWG.

APPLICATIONS

OPERATING TEMPERATURE:
-31° to +131°F (-35° to +55°C).

CALIFORNIA Title 24

Pilot Duty

POWER CONSUMPTION: 6VA Max.

ASHRAE 90.1

Indoor/Outdoor lighting
HVAC equipment
School warning and other
Traffic lights
Water heaters in offices,
churches and factories

Motor

ENCLOSURE: Noryl® Indoor/Outdoor NEMA
3R. Suffix -Y metal indoor enclosure NEMA 1. All
with lockable hasp (see page 153 for enclosure

Resistive

120VAC
240VAC
120VAC
240VAC
28VDC

RATING

1HP
2HP

290VA
360VA
1⁄4HP
1⁄2HP

20A

10A

720VA

dimensions).

WIRING DIAGRAMS
DGM100A

DG200A

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 50/60Hz

NO. OF
CHANNELS

OUTPUT
CONTACTS

SCHEDULING: 56 ON & OFF set points
provide individual programs for each day of
the week. Minimum setting is 1 minute.

DG100A

82201

120-277VAC

1

DPDT

DG200A

82209

120-277VAC

2

SPDT

MOMENTARY CONTACT: DGM100A has 2
second contact closures for ON & OFF control of
mechanically held contactors or latching relays.

DGM100A

82210

120-277VAC

1

DGM100A-Y

82222

120-277VAC

1

SPDT
Momentary
SPDT
Momentary

FEATURES

BLOCK HOLIDAY: 9 holiday blocks can be
set for individual days or for duration of any
number of days.

DG100A

DAYLIGHT SAVING: Automatic
adjustment (can be omitted).
LEAP YEAR: Automatic Compensation.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
CLOCK FORMAT: AM/PM or 24 Hour
format.

SPECIFICATION WRITER’S GUIDE
DG100/200A SERIES – 1. Furnish and install, where noted, a 1 (2) channel 7-day programmable digital time switch. 2. Controller shall program in AM/PM (12 hour) or
Military (24 hour) formats. 3. Unit shall be capable of switching 20 amps ballast loads at 277VAC. 4. Controller shall be capable fo 56 set points; separate scheduling for
each day of the week with one minute resolution. 5. Controller shall have 365 day holiday capabilities with 9 block holidays for individual or duration of any number of
days. 6. Controller shall be able to select USA Standard Daylight Saving, Standard time, or programmable dates. 7. Controller shall have automatic Leap Year correction.
8. Controller shall have Permanent Schedule Retention. 9. Controller shall have 7 days backup for real time with built in super capacitor; no batteries to maintain. 10.
Controller shall be capable of Manual Override ON or OFF to the next scheduled event using 1 button for each channel. 11. Unit shall have NEMA Type 3R indoor/outdoor
enclosure as standard. 12. To order specify TORK Model DG100A (DG200A). 13. To order momentary contact closure for latching contactor control specify DGM100A.

POWER OUTAGE BACKUP: Permanent
schedule retention is provided. Supercapacitor
provides 7 days of real time back up.

DIGITAL
CONTROLS
TORK 63

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 64

DZM200B

DZS SERIES

REMOVABLE MEMORY
MODULE FOR COMPUTER
PROGRAMMING!

MULTIPURPOSE CONTROLS
1, 2 OR 4 CHANNEL
365 / 7 DAY ADVANCED
TIME SWITCH

SPECIFICATIONS
N

GND NO

UPPER
BOARD

TIMER SUPPLY

C

ON

L

energy

APPLICATIONS

CALIFORNIA Title 24

HVAC equipment
Horns and bells
Interior lighting
Electric motors
Outdoor lighting
and signs

N

PULSE
ON

208-240V

INPUT VOLTAGE: 120/208-240/277VAC,
50/60Hz.
277V

N

SCHEDULING: 99 ON & OFF set points
allow individual programs for each day of
the week at a minimum 1 minute apart.

NO. OF
CHANNELS

DRY CONTACTS
(UNPOWERED)

DZS100BP

82182

120/208-240/277

1

DPDT

DZS200BP

ASTRONOMIC: Adjustable 10˚ - 60˚ Northern or
Southern latitudes can be individually offset +/-1 to
240 minutes from both sunset and sunrise times.

DZS400BP
USB-MMP

82183
82184

120/208-240/277
120/208-240/277

2

120

4
Memory Module
Programmer

82196

SPDT

82215

120/208-240/277

1

DPDT

HOLIDAYS: 1 to 24 individual dates.

DZS200BP-0

82227

120/208-240/277

2

SPDT

SIGNAL/PULSE DURATION: 2 different
settings per channel: 1-99 seconds.

DZS200BP-12

82228

12VDC

2

SPDT

DZS200BP-24

82229

24VAC

2

SPDT

DAYLIGHT SAVING: Automatic adjustment
(can be omitted).
LEAP YEAR: Automatic Compensation.

82230

120/208-240/277

4

SPDT

NC

24-277VAC

30A

30A

24-277VAC

20A

Ballast

120VAC
277VAC

30A
20A

10A
10A

120-277VAC

13A

Tungsten

120-277VAC

15A

2A

NO C

NC

L

L
LOAD

N

277V

GND NO

Motor Load

C

NC

NO

C

C

N

120 208-240

120-277VAC

Resistive

28VDC120V

N

720VA

120 208-240277

30A

L

ON

OFF

C

12-277VAC

30A

1HP

ON

PULSE
OFF

OFF

720VA 720VA

PULSE
ON

PULSE
OFF

N

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

1HP

L

PULSE
ON

208-240V

8A
CH 2

120-277VAC

720VA

20A

N

MECHANICALLY HELD CONTACTORS
OR LATCHING RELAYS

LOAD
NO
NC
N

277

CH 1
SPDT
L

208-240V

C

TIMER SUPPLY

Pilot Duty

120VAC
CH 1

1HP
2HP

277V

L

LOADNC
NO

1HP
2HP

208-277VAC

NC

CH 2
SPDT
L

WIRING DIAGRAMS
AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

CH 4
SPDT

CH 1
SPDT

C

120VAC
DZM200B

N

120V

CH 2
SPDT

L
LOAD

277V

LOAD

N

NO C

TIMER SUPPLY

LOWER
BOARD

N

NC

NO C

NC

DPDT
N

120

208-240 277

L

120V

C

208-240V
SUPPLY
AC LINE INPUT TIMER
SELECT PROPER TERMINALS
277V
AND APPLY ONLY ONE VOLTAGE

DZS100BP

120

L

LOAD
N

NO NC

C

CH 3
SPDT

LOAD
N

NO NC

208-240 277

UPPER
BOARD

120V

L

208-240V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

L
LOAD

277V

LOAD

N

CH 1
SPDT

C

TIMER SUPPLY

DZS200BP

120 208-240

C

C

NO NC

TIMER SUPPLY

LOAD

277V

MANUAL OVERRIDE: Until the next regularly
scheduled ON or OFF, automatic operation then
resumes. In signal mode, activates pulse.

LOAD

N

N

NC

N

NO C

CH 2
SPDT

NC

NO C

NC

LOWER
BOARD
120

208-240 277

L

120V

L

C

L

CH 1
SPDT

N

L

NO

LOAD

N

277

208-240V

NC

L

CH 2
SPDT

NO NC

CH 4
SPDT

LOAD

120V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

GND NO

N

DZS400BP

N

DZS400BP-0

General Purpose

PULSE
OFF

CH 2
SPDT

N

LOAD

UPPER
BOARD

Includes software

DZS100BP-0

N

CH 3
SPDT

N

SEASONS: 1 to 4 with different daily schedules
which can wrap around into the new year.

DZS400BP
RATING
VOLTAGE
NO
NC

208-240 277

208-240V

N

SPDT

PULSE
ON

NO C

TIMER SUPPLY

TIMER SUPPLY
(VAC) 50/60Hz

DZS100BP, DZS200BP
RATING
VOLTAGE
NO
NC

TYPE

MECHANICALLY HELD CONTACTORS
OR LATCHING RELAYS

ENCLOSURE: Noryl Indoor/Outdoor NEMA
3R. Suffix -0 metal Indoor/Outdoor NEMA 3. All
with lockable hasp (see page 153 for enclosure
dimensions). DZS400BP
DZS200BP

UPC
CODE

CONTACT RATINGS

LOAD

120V

®

CATALOG
NO.

NC

L

CH 1
SPDT

POWER CONSUMPTION:
5VA Max: DZS100/200BP.
6VA Max: DZS400BP.

FEATURES

OFF

LOWER
BOARD

OPERATING TEMPERATURE:
-40° to +158°F (-40° to 70°C).

ORDERING INFO

C

ON

PULSE
OFF

N

TIMER SUPPLY

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

ASHRAE 90.1

NO

C

LOADL

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

responsible

NC

L

120 208-240277

120V
DZS400BP
TIMING ACCURACY:
Line frequency.

TERMINAL RANGE:
#14-#16AWG for line input.
#12-#16AWG load outputs.

C

OFF

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

LOAD

208-240V

N

277V

L
LOAD
N

DPDT

TIMER SUPPLY

DZS100BP

CLOCK FORMAT: AM/PM or Military time.
POWER OUTAGE BACKUP: Permanent schedule
retention with memory module. Supercapacitor
provides 7 days of real time backup.

C

NO NC

C

NO NC

SPECIFICATION WRITER’S GUIDE
CH 1
CH 2
L
DZS SERIES – 1. Furnish and install, where noted, a 4L (2) (1)LOAD
channel
digital
time switch with portable Memory Module on front panel.SPDT
2. MemorySPDT
Module shall be
LOAD
capable of being programmed at any one location and inserted
into DZS100BP,
200BP, 400BP Series (with memory module socket) in any other remote location.
N
N
C
NO
C NO
NC
3. Optional programmer shall be available (Model MMP), capable of accomplishing Windows based settings on a PC for easy duplication
of NC
Memory
Modules
or
DZS200BP
individualized programs for multiple locations 4. Unit shall have copy feature: Can be configured to copy program schedules from one memory module to another
without use of the optional memory module programmer. 5. Controller shall program in AM/PM (12 hour) or Military (24 hour) formats. 6. Controller shall program in
L
one minute resolution. 7. Display shall be of LCD type. 8. Controller shall be capable of 99 set points; separate scheduling for each
day ofLOAD
theL week. LOAD
9. Controller shall
N
N
have 365 day holiday capabilities with 24 single dates and 4 seasons of unlimited duration. 10. Different daily schedules shall be programmable within
each season.
11. Controller shall have Daylight Saving or Standard time. 12. Controller shall have automatic Leap Year correction. 13. Controller shall haveDPDT
Permanent Schedule
Retention. 14. Controller shall have 7 day backup for real time with built in super capacitor. 15. Controller shall be capable of manual override ON or OFF to the next
Scheduled event using 1 button for each channel. 16. Unit shall have NEMA Type 3 indoor/outdoor enclosure as standard. 17. Controller
shall
C
NO
NC beC capable
NO NCof having
2 different pulse durations 1-99 seconds, user settable and assignable to each channel. DZS100BP
18. Controller shall be capable of having astronomic on one (or all) channels
with 1-240 minutes, plus or minus offset from Sunrise or Sunset. 19. Controller shall be capable of being configured to copy to multiple memory modules. 20. To order
L
L
specify TORK Model DZS100BP (DZS200BP) (DZS400BP).
LOAD
LOAD
N

120

208-240 277

120V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

208-240V

277V

TIMER SUPPLY

MEMORY MODULE: Removable MM can be
programmed at any one location and inserted into
another DZS series unit.

N

COPY FEATURE: Unit can be configured to copy
program schedule to multiple memory modules.
OPTION: Memory Module Programmer with
software for computer connection programming. Also
allows stand alone battery operation for portable
copy feature.

TORK 65

277

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

208-240V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

277V

TIMER SUPPLY

N

120

208-240 277

120V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

DIGITAL
CONTROLS

120 208-240

120V

208-240V

277V

N

N

TORK 66

L

DTS SERIES

MAINTAINED AND
SIGNAL TIMING

MULTIPURPOSE CONTROLS
1, 2 OR 4 CHANNEL
365 / 7 DAY ADVANCE
TIME SWITCH

DTS400B
SPECIFICATIONS

Indoor and outdoor lighting
Heating and air conditioning
Security systems
Horns and bells
Low voltage lighting
Misting and spraying
Roof cooling
Clock correction systems
Process functions

CH 2
SPDT

NO C

TIMER SUPPLY

N

120

NC

LOAD

POWER CONSUMPTION: 6VA Max.

UPPER

GND NO

ENCLOSURE: Noryl® Indoor/Outdoor NEMABOARD
3R with lockable hasp (see page 153 for enclosure
dimensions).

CH 1
SPDT

NO

L

DTS400B

N

120

13A

15A

2A

120VAC

8A

120-277VAC

Pilot Duty

120-277VAC

Motor Load

120VAC
208-277VAC

1HP
2HP

1HP
2HP

28VDC

30A

30A

C

NC

Resistive

720VA 720VA

12-277VAC

720VA 720VA

120-277VAC

1HP

1HP

L

N

NO NC

C

NO NC

CH 1
SPDT

WIRING DIAGRAMS

120-277VAC

20A

LOAD

N

C

TIMER SUPPLY

DTS200B

10A
10A

Tungsten

CH 2
SPDT

LOAD

30A
20A

120VAC
277VAC

CH 4
SPDT

NC

20A

Ballast

LOAD

C

24-277VAC

30A

N

CH 3
SPDT

30A

24-277VAC

L

N

277V

RATING
NO NC

General
NC Purpose

NO C

L

208-240V

DTS400B
VOLTAGE

VOLTAGE

208-240 277

120V

DTS100B, DTS200B
RATING
NO
NC

TYPE

TIMING ACCURACY: Line Frequency.

OPERATING TEMPERATURE:
-40° to +149° (-40° to +65°C).

ASHRAE 90.1

CONTACT RATINGS

N
CH 1
SPDT

TERMINAL RANGE:
AC LINE INPUT
#14 - #16AWG for lineSELECT
input.
PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE
#12 - #16AWG load outputs.

CALIFORNIA Title 24

LOAD

N

INPUT VOLTAGE: 120/208-277VAC,
LOWER
50/60Hz.
BOARD

APPLICATIONS

L

LOAD

CH 2
SPDT

208-240 277

120V

208-240V
TIMER SUPPLY

AC LINE INPUT
SELECT PROPER TERMINALS
LOWER
AND APPLY ONLY ONE VOLTAGE

L

NO C

BOARD

N

120

ORDERING INFO
FEATURES
SCHEDULING: 99 ON/OFF set points
allow individual programs for each day
of the week at a minimum 1 minute apart.
SEASONS: 1 to 4 with different daily
schedules which can wrap around into the new
year.

CATALOG
NO.

UPC
CODE

TIMER SUPPLY
(VAC) 50/60Hz

DTS100B
NO. OF
CHANNELS

DRY CONTACTS
(UNPOWERED)

DTS100B

82185

120/208-240/277

1

DPDT

DTS200B

82186

120/208-240/277

2

SPDT

DTS400B

82187

120/208-240/277

4

SPDT

LOAD

DPDT
L
LOAD

C

NC

L
LOAD

N

277V
TIMER SUPPLY

120

NO C
N

208-240 277

208-240V

N

NC

N

120V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

L

LOAD

277V

CH 3
SPDT

N

NO NC

C

NO NC

UPPER
BOARD

208-240 277

120V

C

TIMER SUPPLY

N

CH 1
SPDT

CH 2
SPDT

NO NC

C

120

NO

C

DTS400B

LOAD

N

N
CH 1
SPDT

NO NC

CH 2
SPDT

NO C

TIMER SUPPLY

NC

L

LOAD

N

208-240 277

120

NC

NO C

NC

208-240 277

L

120V

208-240V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

L

L
LOAD

277V

LOAD

N

N

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

L

LOAD

208-240V

LOAD

N

277V

N

DPDT

N

MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes. In signal mode,
activates pulse.

C

TIMER SUPPLY

DTS100B

LEAP YEAR: Automatic Compensation.

120

NO NC

C

NO NC

208-240 277

CH 1
SPDT

120V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

208-240V

L

L
LOAD

CH 2
SPDT

LOAD

N
N
SPECIFICATION WRITER’S GUIDE
C
NO NC C NO NC
DTS SERIES – 1. Furnish and install, where noted, a 4 (2) (1) channel digital time switch.DTS200B
2. Controller shall program in AM/PM (12 hour) or Military (24 hour) formats.
3. Controller shall program in one minute resolution. 4. Display shall be of LCD type. 5. Controller shall be capable of 99 set points; separate scheduling for each
L
day of the week. 6. Controller shall have 365 day holiday capabilities with 24 single dates and 4 seasonsACofLINEunlimited
duration. 7. Different
dailyL schedules shall be
INPUT
LOAD
LOAD
SELECT PROPER TERMINALS
programmable within each season. 8. Controller shall have Daylight Saving or Standard time.
9.APPLY
Controller
have automatic Leap Year Ncorrection.
10.
Controller shall
AND
ONLY ONEshall
VOLTAGE
N
have Permanent Schedule Retention. 11. Controller shall have 7 day backup for real time with built in super capacitor. 12. Controller shall be capable
of
manual
override
DPDT
ON to activate pulse #1 duration. 13. Unit shall have NEMA Type 3 Indoor/Outdoor enclosure as standard. 14. Controller shall be capable of having two different pulse
durations 1-99 seconds, user settable and assignable to each channel. 15. To order specify TORK Model DTS100B (200B) (400B).
277V

TIMER SUPPLY

N

CLOCK FORMAT: AM/PM or Military time.

120

208-240 277

120V

208-240V

POWER OUTAGE BACKUP: Permanent
schedule retention. Supercapacitor provides
7 days of real time back up.

277V

C

TIMER SUPPLY

DTS100B
N

TORK 67

NC

L

LOAD

N

120V

DAYLIGHT SAVING: Automatic adjustment
(can be omitted).

DIGITAL
CONTROLS

C

LOWER
BOARD
N

SIGNAL/PULSE DURATION: 2 different
settings per channel: each 1-99 seconds.

GND NO

L
LOAD

277V

DTS200B

HOLIDAYS: 1 to 24 individual dates.

L

208-240V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

CH 4
SPDT

120

NO NC

C

NO NC

208-240 277

120V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

208-240V
277V

L

L
LOAD
N

LOAD
N

TORK 68

DW SERIES

SPECIFICATION
FAVORITE!

MULTIPURPOSE CONTROLS
365 / 7 DAY ADVANCED
1 OR 2 CHANNEL TIME
SWITCHES

CONTACT RATINGS

SPECIFICATIONS

VOLTAGE

General Purpose

NC

24-277VAC

30A

30A

Ballast

120VAC
277VAC

30A
20A

10A
10A

Tungsten

120-277VAC

15A

2A

Pilot Duty

120-277VAC

720VA

720VA

Motor Load

120VAC
208-277VAC

1HP
2HP

1HP
2HP

Resistive

28VDC

30A

30A

TERMINAL RANGE:
#14 - #16AWG for line input.
#12 - #16AWG load outputs.
OPERATING TEMPERATURE:
-40° to +158°(-40° to 70°C).

1 CHANNEL
Outdoor lighting
Security lighting
Parking lot lighting
Canopy lighting

RATING
NO

TIMING ACCURACY: Line Frequency.
INPUT VOLTAGE:
120/208-240-277VAC, 50/60Hz.

APPLICATIONS

POWER CONSUMPTION: 5VA Max.
ENCLOSURE: Noryl Indoor/Outdoor
NEMA 3R. Suffix -0 metal Indoor/Outdoor NEMA
3. All with lockable hasp (see page 153 for
enclosure dimensions).
®

2 CHANNEL
HVAC equipment
Interior lighting
Electric motors
Refrigerator defrost control:
condensers, heaters.

WIRING DIAGRAMS

DWZ100B
DWZ100B
SERIES SERIES

ORDERING INFO
CATALOG
NO.

UPC
CODE

TIMER SUPPLY
(VAC) 50/60Hz

NO. OF
CHANNELS

DRY CONTACTS
(UNPOWERED)

SCHEDULING: 99 ON & OFF set points
allow individual programs for each day
of the week at a minimum 1 minute apart.

DWZ100B

82189

120/208-240/277VAC

1

SPDT

DW200B

82190

120/208-240/277VAC

2

SPDT

ASTRONOMIC (DWZ100B only):
Adjustable 10°- 60° Northern or Southern
latitudes. Can be individually offset +/- 1 to 240
minutes from both sunset and sunrise times.

DW200B-0

FEATURES

TYPE

82231

120/208-240/277VAC

2

SPDT

TIMER SUPPLY
TIMER SUPPLY

N

120

120V

N
208-240
120277
208-240

L

120V

277

SPDT

TIMER SUPPLY
TIMER SUPPLYC

N

L
N

277V

AC LINE INPUT
AC LINE INPUT
SELECT PROPER
SELECTTERMINALS
PROPER TERMINALS
AND
APPLY
ONE VOLTAGE
AND APPLY
ONLY
ONEONLY
VOLTAGE

LOAD
N

CH 1 CH 2
SPDT SPDT

CH 2
SPDT

DW200B
DW200B
SERIES SERIES

NO CNC NO NC

LOAD

208-240V208-240V
277V

C

SPDT

CH 1
SPDT

120

120V

N
208-240
120277
208-240
120V

L

208-240V208-240V
277V

277V

NO CNC NO
C NC
NO CNC NO NC

277

L
LOAD
N

L

L
LOAD LOAD
N

N

LOAD
N

AC LINE INPUT
AC LINE INPUT
SELECT PROPER
SELECTTERMINALS
PROPER TERMINALS
AND APPLY
AND
ONLY
APPLY
ONEONLY
VOLTAGE
ONE VOLTAGE

HOLIDAYS: 1 to 24 individual dates.
DAYLIGHT SAVING: Automatic adjustment
(can be omitted).

TWO SPEED
TWOPUMP
SPEEDWIRING
PUMP WIRING

LEAP YEAR: Automatic Compensation
scheduled ON or OFF, automatic operation then
resumes.

SPECIFICATION WRITER’S GUIDE
DWZ100B – 1. Furnish and install, where noted, a 1 channel digital time switch. 2. Controller shall program in AM/PM (12 hour) or Military (24 hour) formats.
3. Controller shall program in one minute resolution. 4. Display shall be of LCD type. 5. Controller shall be capable of 99 set points; separate scheduling for each day
of the week. 6. Controller shall have 365 day holiday capabilities with 24 single dates. 7. Controller shall have Daylight Saving or Standard time. 8. Controller shall have
automatic Leap Year correction. 9. Controller shall have Permanent Schedule Retention. 10. Controller shall have 7 day backup for real time with built in supercapacitor.
11. Controller shall be capable of manual override ON or OFF to the next scheduled event using 1 button. 12. Unit shall have NEMA Type 3 Indoor/Outdoor enclosure
as standard. 13. Controller shall be capable of having astronomic with 1-240 minutes, plus or minus offset from sunrise or sunset. 14. To order specify TORK Model
DWZ100B.
DW200B – 1. Furnish and install, where noted, a 2 channel digital time switch. 2. Controller shall program in AM/PM (12 hour) or Military (24 hour) formats.
3. Controller shall program in one minute resolution. 4. Display shall be of LCD type. 5. Controller shall be capable of 99 set points; separate scheduling for each day
of the week. 6. Controller shall have 365 day holiday capabilities with 24 single dates. 7. Controller shall have Daylight Saving or Standard time. 8. Controller shall have
automatic Leap Year correction. 9. Controller shall have Permanent Schedule Retention. 10. Controller shall have 7 day backup for real time with built in supercapacitor.
11. Controller shall be capable of manual override ON or OFF to the next scheduled event using 1 button. 12. Unit shall have NEMA Type 3 Indoor/Outdoor enclosure.

MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
CLOCK FORMAT: AM/PM or Military time.
POWER OUTAGE BACKUP: Permanent
schedule retention. Supercapacitor provides 7
days of real time backup.

DIGITAL
CONTROLS
TORK 69

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 70

DZM SERIES

GREAT FOR LATCHING
CONTACTORS

MOMENTARY OUTPUT
365 / 7 DAY ADVANCED
LIGHTING CONTROL TIME
SWITCH

APPLICATIONS

CALIFORNIA Title 24

Low voltage latching relays
Direct wire to mechanically
held contactors

General Purpose

120-277VAC

20A

Pilot Duty

120-277VAC

720VA

POWER CONSUMPTION: 4VA Max.
ENCLOSURE: Noryl® Indoor/Outdoor NEMA
3R. Suffix -0 metal Indoor/Outdoor NEMA 3. All
with lockable hasp (see page 153 for dimensions).

FEATURES

SEASONS: 1 to 4 with different daily
schedules which can wrap around into the new
year.

RATING

OPERATING TEMPERATURE:
-40˚ to 158˚F (-40˚ to +70˚C).

ASHRAE 90.1

ASTRONOMIC: Adjustable 10° - 60° Northern
or Southern latitudes can be individually offset
+/- 1 to 240 minutes from both sunset and
sunrise times.

VOLTAGE

TERMINAL RANGE:
#14 - #16AWG for line input.
#12 - #16AWG load outputs.

energy

WIRING DIAGRAMS

ORDERING INFO
CATALOG
NO.

UPC
CODE

TIMER SUPPLY
(VAC) 50/60Hz

NO. OF
CHANNELS

DZM200BP

82188

120/208-240/277

2

DZM200BP-0

82232

120/208-240/277

2

USB-MMP

82196

Memory Module
Programmer

DRY CONTACTS
(UNPOWERED)

SPDT
Momentary
SPDT
Momentary

TIMER SUPPLY
AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

N

120

208-240V

Includes software

277V

CH 1

DAYLIGHT SAVING: Automatic adjustment
(can be omitted).

C

ON

CH 2

OFF

C

ON

OFF

MECHANICALLY HELD CONTACTORS
OR LATCHING RELAYS

LEAP YEAR: Automatic Compensation.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.

L

L
PULSE
ON

PULSE
OFF

N

CLOCK FORMAT: AM/PM or Military time.
POWER OUTAGE BACKUP: Permanent
scheduled retention with memory module.
Supercapacitor provides 7 days of real time
backup.

PULSE
ON

PULSE
OFF

N

SPECIFICATION WRITER’S GUIDE
DZM 200BP only – 1. Furnish and install, where noted, a 2 channel digital time switch with portable Memory Module on front panel. 2. Memory Module shall be capable
of being programmed at any one location and inserted into DZM200BP (with memory module socket) in any other remote location. 3. Optional programmer shall be
available (Model MMP), capable of accomplishing Windows based settings on a PC for easy duplication of Memory Modules or individualized programs for multiple
locations 4. Unit shall have copy feature: Can be configured to copy program schedules from one memory module to another without use of the optional memory module
programmer. 5. Controller shall program in AM/PM (12 hour) or Military (24 hour) formats. 6. Controller shall program in one minute resolution. 7. Display shall be of
LCD type. 8. Controller shall be capable of 99 set points; separate scheduling for each day of the week. 9. Controller shall have 365 day holiday capabilities with 24 single
dates and 4 seasons of unlimited duration. 10. Different daily schedules shall be programmable within each season. 11. Controller shall have Daylight Saving or Standard
time. 12. Controller shall have automatic Leap Year correction. 13. Controller shall have Permanent Schedule Retention. 14. Controller shall have 7 day backup for real
time with built in super capacitor. 15. Controller shall be capable of astronomic function, adjustable from 10 – 60 degrees Northern or Southern latitude. Each zone can
additionally be offset 1 - 240 minutes for both sunset and sunrise. 16. Controller shall be capable of manual override ON or OFF to the next scheduled event using 1
button for each channel. 17. Unit shall have NEMA Type 3 indoor/outdoor enclosure as standard. 18. Controller shall be capable of 2 independent momentary outputs ON and OFF for each channel. 19. To order specify TORK Model DZM200BP.

MEMORY MODULE: Removable MM can be
programmed at any one location and inserted
into another DZM series unit.
COPY FEATURE: Unit can be configured to
copy program schedule to multiple memory
modules.
OPTION: Memory Module Programmer with
software for computer connection programming.
Also allows stand alone battery operation for
portable copy feature.

TORK 71

208-240 277

120V

HOLIDAYS: 1 to 24 individual dates.

DIGITAL
CONTROLS

DZM200BP

TYPE

TIMING ACCURACY: Line frequency.
INPUT VOLTAGE: 120/208-240/277VAC,
50/60Hz.

responsible

SCHEDULING: 99 ON & OFF set points
allow individual programs for each day
of the week at a minimum 1 minute apart.

CONTACT RATINGS

SPECIFICATIONS

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 72

ELC SERIES

ENERGY AND LIGHTING CONTROL
1 & 2 ZONE
LIGHTING CONTROL
TIME SWITCH

THE DO-IT-ALL ENERGY
& LIGHTING CONTROLLER

NEW!

FEATURES

CALIFORNIA Title 24

CATALOG
NO.

UPC
CODE

TIMER SUPPLY
(VAC) 50/60Hz

NO. OF
CHANNELS

OUTPUT
CONTACTS

ELC71PC/120

82517

120

1

DPDT

ELC71PC/208-240

82518

208-240

1

DPDT

ELC71PC/277

82519

277

1

DPDT

ELC72PC/120

82520

120

2

SPDT

ELC72PC/208-240

82521

208-240

2

SPDT

ELC72PC/277

82522

277

2

SPDT

EPC-LC

82233

LCS115M

82082

Accessory Photo
Sensor
Accessory
Momentary Switch

SENSOR EVENT: 32 sensor driven events
allow individual programs for each day of the
week.

BLOCK HOLIDAY: 10 holiday blocks can be
set for individual days or for duration of any
number of days and may use one of 3 holiday
schedules.

MOMENTARY CONTACT: May be configured
for momentary ON/OFF operation to control
latching contactors. The ELC71/72 operates as a
single-channel unit.

DIGITAL
CONTROLS
TORK 73

VOLTAGE

General Purpose

POWER CONSUMPTION: 6VA Maximum.

ORDERING INFO

HOLIDAYS: 26 holidays may be set using 10
individual dates, 10 month type (last Monday
in May), or 6 specific holidays with one of 3
independent holiday schedules.

UNIVERSAL INPUT: 2 inputs may be assigned
to any channel.
SWITCHED INPUT: Accepts input from optional
momentary or maintained switch.
PHOTOSENSOR INPUT: Accepts input from
optional sensor. EPC-LC (indoor/outdoor) has a
range from 0 to 200 foot-candles.
USER DEFINED INPUT: Accepts user supplied
4 – 20 milliamp sensor.

TYPE

OPERATING TEMPERATURE:
-20°F to +140°F (-29°C to + 60°C).

ASHRAE 90.1

SCHEDULING: 128 time based events allow
individual programs for each day of the week at
a minimum 1 minute apart. Event types include
ON, OFF, Duration, or Duty Cycle.

ASTRONOMIC: Adjustable 10° - 70°
Northern or Southern latitudes. Settings can be
offset from both sunset and sunrise times.

TIMING ACCURACY: Line frequency.

TERMINAL RANGE:
#10 - #16AWG for line/load.
#14 - #22AWG universal input.

energy

HVAC equipment
Indoor/Outdoor lighting
Meets indoor/outdoor lighting
energy code requirements

CONTACT RATINGS

INPUT VOLTAGE:
120, 208-240, 277 50/60Hz (model specific).
responsible

APPLICATIONS

SPECIFICATIONS

PULSE/TIME DURATION: 4 different ON
settings from 1 second to 23 hours, 59 minutes,
59 seconds.
DUTY CYCLE: 4 different ON and OFF patterns
from 1 second to 23 hours, 59 minutes, 59
seconds.
DAYLIGHT SAVING: Automatic adjustment
(can be omitted).
LEAP YEAR: Automatic Compensation.
REMOTE OVERRIDE: Universal input may
be programmed for timed override from a
momentary or maintained dry contact switch.

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

RATING
NO

NC

120/277VAC

20 A

10 A

Ballast

120VAC
208-277VAC

20A
10A

10A

Tungsten

120-277VAC

5A

Pilot Duty

120-240VAC

470VA

275VA

Motor

120VAC
208-277VAC

1HP
2HP

1⁄4HP
1⁄2HP

ENCLOSURE: Noryl® clear cover Indoor/
Outdoor NEMA 3R with lockable hasp (see page
153 for enclosure dimensions).

WIRING DIAGRAMS

ELC72

ELC71

SPST

MANUAL OVERRIDE: Keyboard button
control until the next regularly scheduled ON or
OFF, automatic operation then resumes.
STAGGERED START: Optional stagger up
time between channels, after a power outage;
selectable from 5 seconds, 15 seconds, 30
seconds, 1 minute, 5 minutes, 10 minutes, and
15 minutes.
CLOCK FORMAT: AM/PM or 24 hour format
POWER OUTAGE BACKUP: Capacitor
provides minimum of 1 week of real time
backup for program and time of day.
SPECIFICATION WRITER’S GUIDE
Installer shall furnish and install Tork ELC71 single-channel (or ELC72, two-channel) electronic time control. The control shall have 24 hour, 7 day, 365 day, or astronomic
capability with 128 events available. It shall also have 4 user-definable durations and duty cycle lengths plus automatic daylight savings time and leap year adjustments.
Control shall have remote override capabilities (timed, toggle or enable type.) Control shall have keyboard override until overridden again or until next event is reached.
It shall be capable of switching loads based on user-definable temperature and light levels with 32 events available. Control shall have momentary (latching relay)
capability and shall have astronomic features plus 30 definable holidays and 6 pre-programmed holidays. Controller shall have 7 day backup for real time with built in
supercapacitor. The digital time display shall be 3⁄4” in height. Clock format shall be selectable, allowing a choice of 12 hour (AM/PM) or 24 hour format. Wiring terminals
shall have the capability to accommodate #16 to #10 AWG wire. Control shall be housed in NEMA 3R enclosure with clear-view cover and shall be lockable to guard
against vandalism or tampering.

TORK 74

ELC SERIES

ENERGY AND LIGHTING CONTROL
4, 8 & 12 ZONE
LIGHTING CONTROL
TIME SWITCH

THE DO-IT-ALL ENERGY &
LIGHTING CONTROLLER

NEW!

energy

CALIFORNIA Title 24
ASHRAE 90.1

HVAC equipment
Indoor/Outdoor lighting
Meets indoor/outdoor lighting
energy code requirements

FEATURES

UPC
CODE

TIMER SUPPLY
(VAC) 50/60Hz

NO. OF
CHANNELS

OUTPUT
CONTACTS

ELC74*

82523

24/120/208-240/277

4

SPDT

ELC78

82524

24/120/208-240/277

8

SPDT

ELC712

82525

24/120/208-240/277

12

SPDT

EPC-LC

82233

Accessory Photo Sensor

LCS115M

82082

Accessory Momentary Switch

TORK 75

INPUT VOLTAGE:
24/120/208-240/277VAC, 50/60Hz.

General Purpose

RATING
NO

NC

120 - 277VAC

20A

10A

Ballast

120 VAC
208-277 VAC

20A
10A

10A
3A

Tungsten

120-277VAC

5A

Pilot Duty

120-240VAC

470VA

275VA

Motor

120VAC
208-277VAC

1HP
2HP

1⁄4HP
1⁄2HP

WIRING DIAGRAMS

SPST

*Also CSA certified.

BLOCK HOLIDAY: 10 holiday blocks can be
set for individual days or for duration of any
number of days and may use one of 3 holiday
schedules.

DIGITAL
CONTROLS

VOLTAGE

ENCLOSURE: Metal Indoor NEMA 1 with
lockable hasp (see page 153 for dimensions).

CATALOG
NO.

SENSOR EVENT: 32 sensor driven events
allow individual programs for each day of the
week.

MOMENTARY CONTACT: May be configured
for momentary ON/OFF operation to control
latching contactors. The ELC74 operates as a
two channel unit. The ELC78 operates as a four
channel unit. The ELC712 operates as a six
channel unit.

TYPE

OPERATING TEMPERATURE:
-20°F to +140°F (-29°C to + 60°C).

ORDERING INFO

HOLIDAYS: 26 holidays may be set using 10
individual dates, 10 month type (last Monday
in May), or 6 specific holidays with one of 3
independent holiday schedules.

UNIVERSAL INPUT: 8 inputs may be assigned
to any channel. ELC74 includes 4.
SWITCHED INPUT: Accepts input from optional
momentary or maintained switch.
PHOTOSENSOR INPUT: Accepts input from
optional sensor. EPC-LC (indoor/outdoor) has a
range from 0 - 200 foot-candels.
USER DEFINED INPUT: Accepts user supplied
4 – 20 milliamp sensor.

TIMING ACCURACY: Line frequency.

POWER CONSUMPTION: 10VA Maximum.

SCHEDULING: 128 time based events allow
individual programs for each day of the week at
a minimum 1 minute apart. Event types include
ON, OFF, Duration, or Duty Cycle.

ASTRONOMIC: Adjustable 10° - 70°
Northern or Southern latitudes. Settings can be
offset from both sunset and sunrise times.

CONTACT RATINGS

TERMINAL RANGE:
#10 - #16AWG for line input.
#10 - #16AWG for load output.
#14 - #22AWG universal input.

responsible

APPLICATIONS

SPECIFICATIONS

PULSE/TIME DURATION: 4 different ON
settings from 1 second to 23 hours, 59 minutes,
59 seconds.
DUTY CYCLE: 4 different ON and OFF patterns
from 1 second to 23 hours, 59 minutes, 59
seconds.
DAYLIGHT SAVING: Automatic adjustment
(can be omitted).
LEAP YEAR: Automatic Compensation.
REMOTE OVERRIDE: Universal input may
be programmed for timed override from a
momentary or maintained dry contact switch.
MANUAL OVERRIDE: Keyboard button
control until the next regularly scheduled ON or
OFF, automatic operation then resumes.

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

STAGGERED START: Optional stagger up
time between channels, after a power outage;
selectable from 5 seconds, 15 seconds, 30
seconds, 1 minute, 5 minutes, 10 minutes, and
15 minutes.
CLOCK FORMAT: AM/PM or 24 hour format.
POWER OUTAGE BACKUP: The program
and time of day are maintained for a minimum
of 2 days by means of a capacitor. After two
days, a lithium battery takes over and provides
a minimum accumulated time of 1 year. The
lithium battery should provide over 10 years of
protection.
COMPUTER INTERFACE: Unit may be
programmed with a PC.
SPECIFICATION WRITER’S GUIDE
Installer shall furnish and install Tork ELC74 four channel (ELC78 eight channel or ELC712 twelve channel) electronic time control. The control shall have 24 hour, 7 day,
365 day or astronomic capability with 128 events available. It shall also have 4 (8) user-definable durations and duty cycle lengths plus automatic daylight saving time
and leap year adjustments. Control shall have remote override capabilities (timed, toggle or enable type). Control shall have keyboard override until overridden again
or until next event is reached. It shall be capable of switching loads based on user-definable temperature and light levels with 32 events available. Control shall have
momentary (latching relay) capability and shall have astronomic features plus 30 definable holidays and 6 pre-programmed holidays. Control shall provide 2 days of
power outage carry-over without a battery. Control shall provide 10 years of power outage protection with a battery. The digital time display shall be 3⁄4” in height. Clock
format shall be selectable, allowing a choice of 12 hour (AM/PM) or 24 hour format. Control shall be capable of interfacing (sending and receiving data) with a personal
computer. Control shall be housed in a NEMA 1, lockable steel enclosure, to guard against vandalism or tampering.

TORK 76

CONTACT RATINGS

Resistive

TERMINAL RANGE: Relay #12AWG; input
power terminals #14 - #22AWG; TOD/sensor
terminals accept #18 - #22AWG.
responsible

energy

APPLICATIONS

ASHRAE 90.1

Pilot Duty

POWER CONSUMPTION: 5VA Maximum.

NO

NC

120/240VAC
277VAC
120VAC
240/277VAC

20A
12A
20A
6A

10A

120/240/277VAC

5A

120/240VAC
277VAC

10A
3A
3A

LIGHT LEVEL

STAGE 1

470VA
690VA

4

5

6

STAGE 2

3

8

2

9
1

275VA
4

7

POWER

1

10

OTHER MOUNTINGS:
LC200M mechanism only.

For 120 VAC
Operation

NEUT 120V240V 277V

LINE INPUT

N
H

WIRING DIAGRAMS

STAGE 1

C

NO NC

5

6

7

3

8

2

SET

ENCLOSURE: LC200 includes metal Indoor
NEMA 1 with lockable hasp (see page 153 for
dimensions).

EPC1 sensor
supplied with unit.

Use to control two different
outdoor lighting circuits utilizing
one photocell. Sign lighting can
turn ON at one ambient light
level while parking lot lighting
turns ON at a different light
level.

9
10

RUN

STAGE 2

C

NO NC

OUTPUT 1 OUTPUT 2

WHITE
BLACK

LOAD 1
TOD1
C
TOD2

LOAD 2

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 50/60Hz

NO. OF
ZONES

OUTPUT
CONTACTS

PHOTOSENSOR INPUT: EPC1 included.

LC200

82111

120/240/277VAC

2

SPDT

DUAL OUTPUTS: with independent turn-ON
adjustment for Stage1 and Stage 2.

LC200M

120/240/277VAC

2

5

6

STAGE 2

4

7

5

6

8

3

8

9

2

9
1

10

SET

LINE INPUT

10

RUN

H
H

C

NO NC

C

NO NC

OUTPUT 1 OUTPUT 2

RED
BLACK

LOAD 1
STAGE 1

STAGE 2

LOAD 2

SPDT
For 277 VAC
Operation
NEUT 120V240V 277V

LINE INPUT

N
H

C

NO NC

C

OUTPUT 1 OUTPUT 2

WHITE
BLACK

NEUT 120V240V 277V

LINE INPUT

H
H

LINE INPUT

N
H

C

NO NC

C

NO NC

OUTPUT 1 OUTPUT 2

WHITE
ORANGE

LOAD 1
LOAD 2

LOAD 2

For 240 VAC
Operation

NEUT 120V240V 277V

NO NC

LOAD 1

SWITCHED INPUT: Can be used with a time
switch for photocell ON of two different lighting
circuits at different ambient light levels, then
time-of-day OFF.

NEUT 120V240V 277V

7

3
2
1

For 120 VAC
Operation

LIGHT LEVEL ACTIVATION: Turn ON is user
settable from 2 to 100 footcandle; Independent
light level adjustment for each zone. Turn OFF
is a maximum of 2 times turn ON level. Built-in
delay ON of 30 seconds to avoid reaction to
lightning or headlights.

STAGE 1
4

POWER

82113

For 240 VAC
Operation

LIGHT LEVEL

EPC

EPC1

ORDERING INFO
FEATURES

Tungsten

OPERATING TEMPERATURE:
-40°F to +140°F (-40°C to + 60°C).

TOD1
C
TOD2

24 hour convenience stores
Open wall parking structures
Large canopies
Building perimeters
Atriums

Ballast

RATING

VOLTAGE

EPC

TYPE

INPUT VOLTAGE:
120/240/277VAC, 50/60Hz.

TOD1
C
TOD2

SPECIFICATIONS

TOD1
C
TOD2

STAGE LIGHTING
TURN ON LEVEL

LIGHT LEVEL / TIME OF DAY OPTION
2 ZONES LIGHTING CONTROL
TIME SWITCH

EPC1

LC200 SERIES

C

NO NC

C

NO NC

OUTPUT 1 OUTPUT 2

RED
BLACK

LOAD 1

SPECIFICATION WRITER’S
GUIDE
LOAD
2
Furnish and install an electronic light sensor and control with dual outputs for two lighting zones. Each output shall be capable of a different user settable turn
ON light level set For
points277
fromVAC
2 to 100 footcandles. Turn ON to turn OFF ratio shall be 1:2. Controller shall also offer two digital inputs, which can accept a contact
Operation
closure from an independent time switch
or EMS system,
thereby allowing for independent time of day control.
LINE INPUT
OUTPUT 1 OUTPUT 2
NEUT 120V240V 277V

N
H

C

NO NC

C

NO NC

WHITE
ORANGE

LOAD 1
LOAD 2

DIGITAL
CONTROLS
TORK 77

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 78

DGU &
DGLC SERIES

CODE SOLUTION FOR
SMALL PROJECTS

NEW!

LIGHTING CONTROL WITH PHOTO
OR OVERRIDE INPUT, 7 DAY
7 DAY LIGHTING
CONTROL TIME SWITCH

TERMINAL RANGE:
#12 - #18AWG for line/load.
#18 - #26AWG sensor/switch input.

responsible

energy

APPLICATIONS

EXTERIOR LIGHTING
Signage and store windows
Security
Parking lots

FEATURES

ASHRAE 90.1

Model EPC-A supplied
with DGLC-A unit.

CATALOG
NO.
With optional
Timed Override

82211

120-277VAC

1

DPDT

DGUM100A

82212

120-277VAC

1

DGUM100A-Y

82224

120-277VAC

1

SPDT
Momentary
SPDT
Momentary

DGLC100A-NC

82223

120-277VAC

1

DPDT

DGLC200A-NC

82213

120-277VAC

2

SPDT

EPC-A

82112

Accessory Photo
Sensor

SSA200R-24

14015

24VAC/24VDC

TRP-U

82030

120/277VAC

PHOTOSENSOR INPUT: Unique push
button set-up assures accurate operation
with automatic calibration that adjusts for
wire size and distance. EPC-A photo sensor is
included with the DGLC-A and may be ordered
as an option for use with model DGU100A &
DGUM100A.

MOMENTARY CONTACT - DGUM100A:
2 second contact closure ON & OFF to control
mechanically held contactors or latching relays.

DIGITAL
CONTROLS
TORK 79

OUTPUT
CONTACTS

VOLTAGE

Resistive

ENCLOSURE: Noryl® Indoor/Outdoor NEMA
3R . Suffix -NC Noryl® Indoor/Outdoor NEMA
3R with clear Lexan® cover. Suffix -Y metal
Indoor enclosure NEMA 1. All with lockable
hasp (see page 153 for dimensions).

RATING
NO

NC

24-277VAC

20A

10A

Ballast

120VAC
277VAC

20A

10A

Tungsten

120VAC

15A

Motor

POWER CONSUMPTION: 6VA Maximum.

INPUT SUPPLY
NO. OF
(VAC) 50/60 Hz CHANNELS

DGU100A-Y

MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.

REMOTE OVERRIDE ON: Each channel has
independent input for a maintained dry-contact
closure. May use TORK model SSA200R-24
and TRP-U for timed override. May use with
occupancy sensor as override.

UPC
CODE

TYPE

Pilot Duty

OPERATING TEMPERATURE:
-31°F to +131°F (-35°C to + 55°C).

ORDERING INFO

SCHEDULING: 56 ON & OFF set points
provide individual programs for each day
of the week. Minimum setting is 1 minute.

LIGHT LEVEL ACTIVATION: Turn ON is user
settable from 1 to 100 footcandle; Turn OFF
is a maximum of 2 times turn ON level. Each
channel has an independent setting. Includes a
user settable delay before ON or OFF between
1 – 90 seconds.

TIMING ACCURACY: Line frequency.
INPUT VOLTAGE: 120-277VAC, 50/60Hz
(auto detection).

CALIFORNIA Title 24

INTERIOR LIGHTING
Open office zoning
Hallways
Meeting and sales areas
Stock rooms and warehouses

CONTACT RATINGS

SPECIFICATIONS

Resistive

120VAC
240VAC
120VAC
240VAC
28VDC

DGU100A

1HP
2HP

290VA
360VA
1⁄4HP
1⁄2HP

20A

10A

720VA

DGUM100A

DGU100A

WIRING DIAGRAMS
DGU100A

DGLC100A

DGUM100A

SPDT
Transformer
Power Pack

SPST

DGUM100A

DGLC100A

DGLC200A

BLOCK HOLIDAY: 9 holiday blocks can be
set for individual days or for duration of any
number of days.
DAYLIGHT SAVING: Automatic adjustment
(can be omitted).
LEAP YEAR: Automatic Compensation.
CLOCK FORMAT: AM/PM or 24 Hour
format.
POWER OUTAGE BACKUP: Permanent
schedule retention. Supercapacitor provides 7
days of real time backup.

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

DGLC100A

DGLC200A

SPECIFICATION WRITER’S GUIDE
DGU and DGLC SERIES - 1. Furnish and install, where noted, a 1 (2) channel 7 day programmable digital time switch. 2. Controller shall program in AM/PM (12
hour) or Military (24 hour) formats. 3. Unit shall be capable of switching 20 amps ballast load at 277VAC. 4. Controller shall be capable of 56 set points; separate
scheduling for each day of the week with one minute resolution. 5. Controller shall have photo sensor input user adjustable per circuit between 1 and 100 footcandle
turn ON level. 6. Each channel shall have and switched input to override circuit ON. 7. Controller shall have 365 day holiday capabilities with 9 block holidays
for individual or duration of any number of days. 8. Controller shall be able to select USA Standard Daylight Saving, Standard time, or programmable dates. 9.
Controller shall have automatic Leap Year correction. 10. Controller shall have Permanent Schedule Retention. 11. Controller shall have 7 days backup for real time
with built in super capacitor; no batteries to maintain. 12. Controller shall be capable of Manual Override ON and OFF to the next scheduled event using 1 button
for each channel. 13. Unit shall have NEMA type 3R indoor/outdoor enclosure standard. 14. To order specify TORK Model DGU100A. (Alt 14. To order 1 channel
momentary contact closure for latching contactor control specify DGUM100A). (Alt 14. To order controller with EPC-A photo sensor included in package specify TORK
Model DGLC100A-NC (DGLC200A) with clear cover.

TORK 80

DLC400BP

FLEXIBLE INDOOR/
OUTDOOR LIGHTING
CONTROLLER

4 ZONE LIGHTING CONTROL
TIME SWITCH

responsible

energy

APPLICATIONS
INTERIOR LIGHTING
Open office zoning
Hallways
Meeting and sales areas
Stock rooms and warehouses
EXTERIOR LIGHTING
Signage and store windows
Security
Parking lots

FEATURES
CONFIGURABLE ZONES: Simple three
position slide switch sets logic for each zone:
Time ON/Time OFF, Photo ON/Photo OFF, or
Photo ON/ Time OFF.
SCHEDULING: 99 ON & OFF set points allow
individual programs for each day of the week.
Minimum 1 minute apart.
ASTRONOMIC: 1. Adjustable 10° - 60°
Northern or Southern latitudes. 2. Can be
individually offset +/-1-240 minutes from both
sunset and sunrise times.
PHOTOSENSOR INPUT: EPC2 photo sensor
included.
LIGHT LEVEL ACTIVATION: Turn ON
and OFF level is user settable from 1 to 100
footcandle. Each channel has an independent
setting.
REMOTE OVERRIDE: Maintained dry contact
closure or use TORK Model SSA200R-24 for
timed override with flash warning before OFF.
May use with occupancy sensor as override.

DIGITAL
CONTROLS
TORK 81

CALIFORNIA Title 24

SPECIFICATIONS
TIMING ACCURACY: Line frequency.
INPUT VOLTAGE:
120/208 - 240/277VAC, 50/60Hz.

CONTACT RATINGS
TYPE

VOLTAGE

General Purpose 24-277VAC, 30VDC

RATING
NO

NC

30A

30A
10A

TERMINAL RANGE: #10 - #14AWG.

Ballast

120-277VAC

20A

OPERATING TEMPERATURE:
-40°F to +158°F (-40°C to + 55°C).

Tungsten

120VAC

10A

Pilot Duty

120-277VAC

720VA

720VA

POWER CONSUMPTION: 30VA Maximum.

ASHRAE 90.1

ENCLOSURE: Metal Indoor/Outdoor NEMA 3 with
lockable hasp (see page 153 for dimensions).

Model EPC2
supplied with unit.
Memory Module
Programmer optional

WIRING DIAGRAMS

With optional
Timed Override

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT SUPPLY (VAC)
50/60 Hz

NO. OF
CHANNELS

OUTPUT
CONTACTS

DLC400BP

82191

120/208-240/277

4

SPDT

USB-MMP

82196

Memory Module
Programmer

SSA200R-24

14015

24VAC/24VDC

Includes Software
SPDT

MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
SEASONS: 1 to 4 with different daily schedules
which can wrap around into the new year.
HOLIDAYS: 1 to 24 individual dates.
DAYLIGHT SAVING: Automatic adjustment
(can be omitted).
LEAP YEAR: Automatic Compensation.
POWER OUTAGE BACKUP: Permanent
schedule retention with memory module.
Battery provides real time backup for 6 months
cumulative.
MEMORY MODULE: Removable MM can be
programmed at any one location and inserted
into another DZS series unit.
OPTION: Memory Module Programmer with
software for computer connection programming.
Also allows stand alone battery operation for
portable copy feature.

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

SPECIFICATION WRITER’S GUIDE

DLC400BP – 1. Furnish and install, where noted, a 4 zone lighting controller with photosensor input (TORK model EPC2 photosensor to be supplied with controller). 2. Memory Module shall be capable of being
programmed at any one location and inserted into DLC400BP (with memory module socket) in any other remote location. 3. Optional programmer shall be available (Model MMP), capable of accomplishing Windows
based settings on a PC for easy duplication of Memory Modules or individualized programs for multiple locations 4. Each zone shall be capable of independent, user settable turn ON and turn OFF light level set
points ranging from 1 to 100 footcandles. 5. Three position slide switches shall be provided for each of the 4 zones allowing for user settings based on a) time of day or b) combination time of day and light level or
c) light level. 6. Controller shall provide 30 Amp General Purpose isolated contacts (unpowered) for each zone as well as a 500 ma, 24VDC output. 7. Controller shall have 1 digital input per channel for: a) remote
contact closure which can be used to turn corresponding outputs ON/OFF outside of the normal control time or b) remote timed override which can be accomplished for the corresponding outputs with the use of TORK
model SSA200R-24. 8. Enclosure shall provide separate wiring compartments for power connections and auxiliary connections. 9. Controller shall be capable of local override ON or OFF to the next scheduled event
using the keypad for each zone. 10. Each zone shall be capable of astronomic function, adjustable from 10 – 60 degrees Northern or Southern latitude. Each zone can additionally be offset +/- 1–299 minutes for
both sunset and sunrise. 11. Controller shall provide automatic daylight saving time (which can be omitted). Leap year adjustment shall be compensated for automatically. 12. Controller shall have 365 day holiday
capability with 24 single dates and 4 seasons of unlimited duration. 13. Controller shall be capable of 99 set points with separate scheduling for each day of the week. 14. Controller shall have back-up capability: a)
Schedule shall be retained for 40 years without power, b) real time shall be retained for 6 months using a field replaceable 9V lithium battery. 15. Unit shall have a NEMA type 3, metal indoor/outdoor enclosure.

TORK 82

LD SERIES

ADD A WARNING BLINK
TO ANY CONTROL

EXTENDED LIGHTING CONTROL
LIGHTING DELAY
TIME SWITCH

INPUT VOLTAGE:
120/208/240/277VAC, 50/60Hz.
TERMINAL RANGE: #10 - #16AWG.
OPERATING TEMPERATURE:
-22° to 150°F (-30° to +65°C).

ASHRAE 90.1

APPLICATIONS

CONTACT RATINGS

SPECIFICATIONS

POWER CONSUMPTION: 5VA Maximum.

®

®

ENCLOSURE: Metal Indoor NEMA 1 with
lockable hasp (see page 153 for dimensions).

®

®

Open offices
Gymnasiums
Warehouses
Outdoor recreation courts
User-activated lights
with time limits
Match with photocontrol and
timer to limit hours of use

RATING

TYPE

VOLTAGE

General
Purpose
Ballast

24/240VAC
277VAC
120VAC
208-277VAC

Tungsten

120-277VAC

5A

3A

Pilot Duty

120-240VAC
27VAC

470VA
690VA

275VA

Resistive

28VDC

20A

10A

NO

NC

20A
20A
20A
10A

10A
3A
10A
3A

WIRING DIAGRAMS
LDSH WIRING

LDS WIRING

TORK TIME SWITCH

TORK TIME SWITCH

OUTPUT TERMINALS

OUTPUT TERMINALS
OFF

NO

C

OFF

NC

MOMENTARY
PUSH-BUTTON SWITCH

C ON OFF
DO NOT APPLY
VOLTAGE

N

TIME SWITCH
INPUT

120

208
240

H

REMOTE
INPUT

277
VAC

H
C ON OFF
DO NOT APPLY

INPUT POWER

VOLTAGE

NO

N

N

C

277
VAC

INPUT POWER

AUX. OUTPUT
TERMINALS
NC

208
240

120

TIME SWITCH
INPUT

MAIN LOAD OUTPUT
TERMINALS
NC

120 VAC

ON

ON

N

NC

N

N

H

C

MOMENTARY
PUSH-BUTTON
SWITCH

H

REMOTE
INPUT

NO

MAIN LOAD OUTPUT
TERMINALS

NO

C

NC

NO

C

H

H

H

AUX
LOAD

ORDERING INFO

FEATURES
MAINTAINED INPUT WITH LOAD WARNING BLINK:
LDS Series controls output load contacts based on power applied
to the time switch input contact. At removal of power from
the time switch input, LDS Series provides 1 second blink then
keeps load contacts closed for an extra 1 or 5 minutes (user
selectable) before turn off.
MAINTAINED INPUT WITH AUXILARY WARNING:
LDSH Series controls output load contacts based on power
applied to the time switch input contact. At removal of power
from the time switch input, LDSH Series closes a second set of
contacts for a user supplied audible or visual warning device.
The warning circuit closes for a selected time of 4 seconds (best
for audible device or continuous, then keeps load contacts closed
for an extra 1 or 5 minutes (user selectable) before turn OFF.

CATALOG
NO.

LDS-A
LDS
LDSH-A
LDSH

UPC
CODE

81026
81025
81031
81028

INPUT SUPPLY (VAC)
50/60 Hz

120/208-240/277
120/208-240/277
120/208-240/277
120/208-240/277

MOMENTARY INPUT: Provides timed override when time
switch input contact is unpowered (timer OFF). When activated
during the warning period, load contacts are kept closed and
timing starts. Both series can accept momentary input contact
closure for ON to start the timing and OFF to end the timing.
TIMED OVERRIDE SETTINGS: User may select override
times of 1⁄2, 1, 11⁄2, 2, 6, 9, or 12 hours. Warning before OFF is
always active after override time.

LOAD

OUTPUT
CONTACTS

ENCLOSURE
TYPE

SPDT

Metal Indoor
NEMA 1

SPDT
SPDT
SPDT

Mechanism
Metal Indoor
NEMA 1
Mechanism

N

TORK TIME SWITCH

TORK TIME SWITCH

OUTPUT TERMINALS

OUTPUT TERMINALS
OFF

NO

C

OFF

NC

MOMENTARY
PUSH-BUTTON SWITCH

VOLTAGE

N

TIME SWITCH
INPUT

N

120

208
240

H
120 VAC

REMOTE
INPUT

277
VAC

H
C ON OFF
DO NOT APPLY

INPUT POWER

VOLTAGE

NO

N

N

C

NO

277
VAC

INPUT POWER

AUX. OUTPUT
TERMINALS
NC

208
240

120

TIME SWITCH
INPUT

MAIN LOAD OUTPUT
TERMINALS
NC

NC

ON

ON

H

C

N

N

C ON OFF
DO NOT APPLY

NO

MOMENTARY
PUSH-BUTTON
SWITCH

H

REMOTE
INPUT

N

LOAD

N

MAIN LOAD OUTPUT
TERMINALS
C

NC

NO

C

H

H

H
ON
OFF
COMMON

AUX
LOAD
MECHANICALLY HELD
CONTACTOR WITH
COIL CLEARING
CONTACTS

ON

N

MECHANICALLY HELD
CONTACTOR WITH
COIL CLEARING
CONTACTS

OFF
COMMON

PHOTOCONTROL

N

N

TORK TIME SWITCH
OUTPUT TERMINALS

APPLICATION EXAMPLE

Lighting for a high school’s tennis courts
turns on during normal class hours
when natural light diminishes using a
7 day time switch and photocell. After
3pm, staff members sometimes use the
courts (the time switch is then off). A
momentary pushbutton activates the
LDSH for timed override of HID lighting.
Five minutes before the lights go out, an
auxiliary contact flashes an incandescent
warning beacon (HID lighting can not
be made to blink). Additional timed
override can be arranged for via the
momentary pushbutton.

APPLICATION WIRING

NO

C

NC

FLASHING LIGHT

H

120V

N

C

ON

H

OFF

N

N

120 208/240277

REMOTE INPUT TIME SWITCH INPUT

MOMENTARY
PUSHBUTTON
SWITCH

AUXILLARY
OUTPUT
NO
C

LDSH

NC

INPUT POWER
N

MAIN LOAD
OUTPUT
NO
C

NC

120V

OFF
N
ON

H
120V
N
OFF

SWITCHED CIRCUIT
TO TENNIS COURT
LIGHTS

ON

N

MECHANICALLY-HELD
4 POLE LIGHTING
CONTACTOR

SWITCHED CIRCUIT
TO TENNIS COURT LIGHTS

480V CIRCUITS FROM PANEL

DIGITAL
CONTROLS
TORK 83

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 84

DGS SERIES

SIGNALING AND DUTY CYCLE
24 HOUR OR 7 DAY
TIME SWITCH

31 DAY CYCLE TIME:
AN INDUSTRY FIRST!

NEW!

SPECIFICATIONS
TIMING ACCURACY: Line frequency.
INPUT VOLTAGE:
120 - 277 VAC, 50/60 Hz (auto detection).
TERMINAL RANGE: #12 - #18AWG.
OPERATING TEMPERATURE:
-31°F to +131°F (-35°C to + 55°C).

APPLICATIONS

POWER CONSUMPTION: 6VA Maximum.

Signaling
Duty cycle

ENCLOSURE: Noryl Indoor/Outdoor NEMA
3R with lockable hasp (see page 153 for
enclosure dimensions).
®

CONTACT RATINGS
TYPE

VOLTAGE

Resistive

RATING
NO

NC

24-277VAC

20A

10A

Ballast

120VAC
277VAC

20A

10A

Tungsten

120 VAC

15 A

Motor

120 VAC
240VAC
120VAC
240VAC

Resistive

28VDC

Pilot Duty

720VA
1HP
2HP
20A

290VA
360VA
1⁄4HP
1⁄2HP
DGS100A

FOR 120V/277VAC
10A

WIRING DIAGRAMS
DGS100A
FOR 208-240VAC
DGS100A
FOR 120V/277VAC

DG180A
FOR 120V/277VAC

ORDERING INFO

FEATURES
DG180A & DG280A: 56 ON & OFF set points provide
individual daily programs. Minimum setting is 1 minute.
DGS100A: 56 ON & OFF set points provide individual programs
for each day of the week. Minimum setting is 1 minute.
DUTY CYCLE: Two different ON/OFF patterns or signal
durations may be programmed. The durations can be up to 23
hours, 59 minutes and 59 seconds in length.
SKIP FUNCTION (24 HOUR UNITS ONLY): Each channel
can be set for ACTIVE/SKIP operations that alternate from 1 - 31
days. This becomes an effective way to cycle loads on varying
days within the month. Using the two-circuit DG280A, two loads
can be set to operate on alternate days in a simple manner.

CATALOG
NO.

UPC
CODE

INPUT SUPPLY (VAC)
50/60 Hz

NO. OF
CHANNELS

OUTPUT
CONTACTS

24 HOUR MODELS
DG180A

82206

120-277VAC

1

DPDT

DG280A

82207

120-277VAC

2

SPDT

DG280A-24

82220

24VAC

2

SPDT

120-277VAC

1

DPDT

DGS100A-12 82218

12VDC

1

DPDT

DGS100A-24 82219

24VAC

1

DPDT

DGS100A
FOR 208-240VAC

DG180A
FOR 208-240VAC

DG280A

7 DAY MODELS
DGS100A

82205

DAYLIGHT SAVING: Automatic adjustment (can be omitted).

DG280A

LEAP YEAR: Automatic Compensation.
MANUAL OVERRIDE: Until the next regularly scheduled ON
or OFF, automatic operation then resumes.
CLOCK FORMAT: AM/PM or 24 hour.
POWER OUTAGE BACKUP: Permanent schedule retention.
Supercapacitor provides 7 days of real time backup.

DIGITAL
CONTROLS
TORK 85

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

SPECIFICATION WRITER’S GUIDE
DGS100A SERIES –1. Furnish and install, where noted, a 1 channel 7 day programmable digital time switch. (Alt 1 DG180 Series 1. Furnish and install, where noted,
a 1 (2) channel 24 hour programmable digital time switch. 2. Controller shall program in AM/PM (12 hour) or Military (24 hour) formats. 3. Unit shall be capable of
switching 20 amps ballast load at 277VAC. 4. Controller shall be capable of 56 set points; separate scheduling for each day of the week with one minute resolution. 5.
unit shall be capable of two duty cycle or signal durations from 1 second to 23 hours, 59 minutes and 59 seconds. 6. Controller shall be able to select USA Standard
Daylight Saving, Standard time or programmable dates. 7. Controller shall have automatic Leap Year correction. 8. Controller shall have Permanent Schedule Retention.
9. Controller shall have 7 days backup for real time with built in super capacitor; no batteries to maintain. 10. Controller shall be capable of Manual Override ON and OFF
to the next scheduled event using 1 button for each channel. 11. Unit shall have NEMA type 3R indoor/outdoor enclosure as standard. 12. To order specify TORK Model
DGS100A (Alt 12. Controller shall have a 31 day cycle to alternate days that programs are active or to be omitted. 13. To order specify TORK Model DG180A [DG280A]).

TORK 86

EJWT & E500T
SERIES

NEW!

PERFECT FOR
PROCESS CONTROL

DELAY, INTERVAL &
PERCENTAGE TIME CYCLE
TIME SWITCHES

SPECIFICATIONS

CONTACT RATINGS

TIMING ACCURACY: 1% of timing range.

TYPE

VOLTAGE

General Purpose
Resistive

INPUT VOLTAGE: 120/240VAC, 60Hz.
TERMINAL RANGE: #12 - #18AWG.
OPERATING TEMPERATURE:
32°F to +122°F (0°C to + 50°C).

APPLICATIONS

POWER CONSUMPTION: 16VA Maximum.

EJWT

RATING
NO

NC

120-240VAC

20A

10A

120-240VAC

20A

10A

Motor

120VAC
208-240VAC

1HP
2HP

1⁄4HP

Pilot Duty

120/240VAC

470VA

275VA

1⁄2HP

ENCLOSURE: Indoor NEMA 4X is standard (see
page 153 for enclosure dimensions).

Poultry and livestock
Agriculture or greenhouse
Oil well pumping
Ventilation
Process control

E502T

E501T

EJWT

ORDERING INFO
FEATURES
EJWT – PERCENTAGE TIMER
• 960 time combinations with two dials.
• Cycle Time Dial sets 32 repeating cycles from
15 seconds to 24 hours.
• Percentage ON Dial has 32 steps from 0%
to 100%.
• Repeats cycle as long as power is applied.

CATALOG
NO.

UPC
CODE

INPUT SUPPLY (VAC)
60 Hz

OUTPUT
CONTACT

EJWT

82513

120-240VAC

SPDT

E500T

82514

120-240VAC

SPDT

E501T

82515

120-240VAC

SPDT

E502T

82516

120-240VAC

SPDT

E500T – ON DELAY TIMER
• Dial sets 32 time delay durations from
5 seconds to 3 hours.
• External switch activated starts delay to ON.
• Runs until external switch turns OFF.

WIRING DIAGRAMS

EJWT

E500T / E501T / E502T

E501T – AUTO OFF INTERVAL TIMER
• Dial sets 32 time durations from 10 seconds
to 12 hours.
• Start/Stop button or External switch starts
interval ON.
• Automatically turns OFF at end of preset time.
• START/STOP or External switch turns OFF.
E502T – OFF DELAY TIME
• Dial sets 32 time durations from 5 seconds
to 3 hours.
• External switch starts interval ON.
• Automatically turns OFF at end of preset time.
• External switch turns OFF.

DIGITAL
CONTROLS
TORK 87

E500T / E501T / E502T

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 88

DIN SERIES

1 OR 2 CHANNEL
7 DAY TIME SWITCH

ASHRAE 90.1

CONTACT RATINGS

SPECIFICATIONS

PANEL BUILDERS
CHOICE

CALIFORNIA Title 24

NEW!

OPERATING TEMPERATURE:
DIN100B: 14°- 131°F (-10°- +55°C).
DIN200B: 14°- 113°F (-10°- +45°C).

Panel builders
Indoor/Outdoor lighting
Security systems
HVAC equipment

CALIFORNIA Title 24

DIN100B

VOLTAGE

Resistive

POWER CONSUMPTION: 4VA Maximum.

ASHRAE 90.1

RATING
NO

NC

120VAC

16A

16A

General Purpose

120VAC

8A

8A

Motor
(DIN100 only)

120VAC

1⁄2HP

TERMINAL RANGE: #12 - #18AWG.

APPLICATIONS

TYPE

INPUT VOLTAGE: 120VAC, 50/60Hz.

MOUNTING: DIN rail #50022 (35mm) or
flat surface using supplied adapter.

DIN200B

WIRING DIAGRAMS

DIN200B
DIN200B

DIN100B

DIN100B

ORDERING INFO
UPC
CODE

DRY
CONTACTS

CLOCK INPUT
50/60 Hz

NO. OF
CHANNELS

NUMBER OF
ON/OFF

DIN100B

82193

SPDT

120VAC

1

8

2

4 Channel A
3 Channel B

DIN200B

82192

SPDT

120VAC

35.80

Channel B (C2)
Output

55.00

52.5

NC

14

8

7

6

1

2

3

DIN100B
35.80

46.00
60.00

5

6

1

2

NC

NO

2

3

4

5

Input

D

Channel B (C2)

NO

3

1

Channel A (C1)

14

8

7

6

1

2

3

85

85.00

45.00

7

6

60

Channel B (C2)

8

7

35.2

Channel A (C1)
Output

52.5

NC

8

Channel A (C1)

Channel B (C2)
Output

55.00

4

NC

NO
DIN200B

CLOCK FORMAT: AM/PM.

Channel B (C2)

NO
85

MANUAL OVERRIDE: Until the next regular
scheduled ON or OFF, automatic operation then
resumes.
POWER OUTAGE BACKUP: Battery retains
time and schedule.

60

Channel B (C2)
85.00

SCHEDULING: 8 ON and OFF pairs of set
points for DIN100B. 4 ON and OFF (CH A) and
3 ON and OFF (CH B) pairs of set points for
DIN200B. Individual programs on each day of
the week. Minimum setting is 1 minute.

CATALOG
NO.

45.00

FEATURES

4

35.2

5

4

5

Channel A (C1)

Channel A (C1)
46.00
60.00

DIGITAL
CONTROLS
TORK 89

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

Channel A (C1)
Output

Input

TORK 90

SMC SERIES

5401 SERIES

SPECIFICATIONS

MOMENTARY
CONTACT ADAPTER

INCREASED AMPERAGE
& VOLTAGE SWITCHING
40 AMP CONTACTORS

INPUT VOLTAGE: 120VAC, 50/60Hz.
TERMINAL RANGE: #12 - #18AWG.
OPERATING TEMPERATURE:
-31°F to +131°F (-35°C to + 55°C).
POWER CONSUMPTION: 6VA max.

APPLICATIONS

ENCLOSURE: Noryl® Indoor/Outdoor
NEMA 3R with lockable hasp (see page
153 for dimensions).

Converts maintained contacts for
pulse switching
Timer to latching contactor control
Photocell to latching contactor control
Signaling

CONTACT RATINGS

5401

Lighting loads
Exhaust fans
Electric and hot water heaters
Refrigeration and defrosting

5441

TYPE

VOLTAGE

RATING

Resistive

120-600VAC

50A

FLA

120-600VAC

40A

Motor

120VAC
240VAC
480VAC
600VAC

3HP
7.5HP
20HP
25HP

ORDERING INFO
UPC
CODE

INPUT SUPPLY
(VAC) 50/60Hz

OUTPUT
CONTACTS

SMC3D

52011

120

SPDT
Momentary

CONTACT RATINGS
NC

Resistive

120VAC

10A

10A

General Purpose

120VAC

10A

10A

Motor

120VAC

1⁄4HP

NC

SMC 3D
ON RELAY
NC NO C

5401

H
120VAC
N

INPUT
120
VAC
OFF RELAY

BLACK

NC NO C

WHITE

Control circuit
from Time Switch

ON PULSE

120VAC

NEUTRAL

N

L

C

NO

AUX

LOAD

DIGITAL
CONTROLS
TORK 91

LOAD

N

LOAD

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

NC
H

CONTACT

277VAC
480VAC

81021
81022

120VAC
208VAC
277VAC
480VAC

Wire
B, C
the sa

NO. AOF
CONTACTORS

120

1

120

4

OUTPUT
CONTACTS
N

B

3PST

120VAC
208VAC
277VAC
480VAC

Control circuit from Time Switch

24VAC
Wire other circuits B, C and D respectively

120 to 480VAC

{

A

N

C

D

C

D

A

Keep low voltage wires
inside this compartment.

120VAC
208VAC
277VAC
480VAC

B

Wire contactors
B, C and D
the same as A.

D

B

120VAC
208VAC
277VAC
480VAC

Wire other c

3PST

C

A

24VAC

5441

120 to 480VAC

Control circu

B

Control circuit from Time Switch

120VAC

C

D

Keep low voltage wires
inside this compartment.

Wire other circuits B, C and D respectively

120VAC

120
VAC

SMC 3D
ON RELAY

OFF RELAY

NC NO C

NC NO C

PUSH
ON

{

N

120VAC

COIL
VOLTS

{

TORK DIGITAL CONTROL
TERMINAL BLOCK

MAINTAINED CONTACT INPUT

L

5401

{

UPC
120VAC
CODE
208VAC

120VAC
208VAC
277VAC
480VAC

Control circuit
from Time Switch

Wire contactors
B, C and D
the same as A.

H

REALAY CONTACTOR

L

CATALOG
NO.

5441

PUSH OFF

OFF PULSE

120VAC
208VAC
277VAC
480VAC

5

120VAC
208VAC
277VAC
480VAC

120VAC
208VAC
277VAC
480VAC

ORDERING
5440INFO

N

PUSH ON

LOW VOLTAGE
LATCHING RELAY
OR MECHANICALLY
HELD CONTACTOR

WHITE

ENCLOSURE: 5401 - Metal NEMA 3
enclosure. 5441 - Metal NEMA 1 Indoor
enclosure (see page 153 for enclosure
dimensions).

TORK DIGITAL CONTROL
TERMINAL BLOCK
MAINTAINED CONTACT INPUT

NO

BLACK

EASY WIRING: Includes 120 volt control
wiring compartment. 5441 has terminal strip
pre-mounted for quick connection.

SMC 3D
120VAC,
240VAC
Input – Sustained voltage 120VAC
WIRING
DIAGRAMS
277VAC, 30VDC
Momentary Contacts (unpowered)
30 Amps inrush

C

5401

CONTACT RATINGS: Can switch up to 40
AMPS per pole from 120VAC to 600VAC, one
to three circuits simultaneously.

{

NO

{

MOMENTARY OUTPUT: SMC3D provides
two dry output contacts. The ON contact
provides a 2 second contact closure (pulse)
when power is applied to the input contacts.
The OFF contact provides a 2 second pulse
when power is removed from the input
contacts.

RATING

VOLTAGE

WIRING DIAGRAMS

FEATURES

{

TYPE

MAINTAINED INPUT: SMC3D accepts
maintained input power from any 120 volt
control. When power is applied or removed a
short contact closure (pulse) is created on the
dry output contacts.

Coil Data: 120VAC @ 60Hz
6VA Holding/seal; 60VA inrush

{

FEATURES

CATALOG
NO.

{

APPLICATIONS

TORK 92

HPS STARTER

SPECIFICATIONS

FOR HIGH PRESSURE SODIUM LAMPS
STARTING AID

LINE VOLTAGE: 105 - 347VAC.
LAMP VOLTAGE: 55 or 100VAC.

TRP SERIES

SPECIFICATIONS

LOW VOLTAGE SWITCHING
TRANSFORMER RELAY
POWER PACKS

CONTACTS: SPST contacts.
CONTACT RATING:
20 Amps Ballast @ 120 or 277VAC.
15 Amps Tungsten @ 120VAC.
1.0 Horsepower @ 120VAC.

LAMP WATTAGE: 35 to 400 watts.
OPERATING TEMPERATURE:
-40°F to +221°F (-40°C to + 105°C).

APPLICATIONS

LEAD LENGTH: 9 inches.
ENCLOSURE: Durable, high temperature

Designed to operate as a starting aid, for all
H.P.S. ballasts from 35 to 400 watts, with lamp
voltage of 55 or 100 volts.

Lexan® housing.

APPLICATIONS

TEMPERATURE RANGE:
0° to 150°F (–18° to 66°C).
Pre-wired in metal enclosure.

Low voltage switching of line voltage
lighting circuits up to 20 Amp ballasts or
15 amp tungsten loads. Also up to 1.0 HP
motors for ventilating and exhaust fans.
Low voltage switching by digital or
mechanical controls for higher amperage
loads including those of two different
voltages.

ORDERING INFO
FEATURES
SMART VOLTAGE: Delivers appropriate
trigger spikes for lamp ignition, then reduces
voltage to good lamps. Continues to feed
voltage spikes to old or poorly working
lamps.

CATALOG
NO.

UPC
CODE

DESCRIPTION

HPS30

81030

High Pressure Sodium Starter

BALLAST

design, color coded for ease of installation.

BLACK
RED
TAP

H.P.S.
STARTER
WHITE

LINE

TORK 93

ORDERING INFO
CATALOG
NO.

UPC
CODE

TRP-1**

82032

TRP-2**

82033

TRP400*

82132

TRP402*

82133

TRP800*

82135

TRP802*

82136

DESCRIPTION

Single Transformer
Relay Powerpack
Single Transformer
Relay Powerpack
Four Transformer
Relay Powerpack
Four Transformer
Relay Powerpack
Eight Transformer
Relay Powerpack
Eight Transformer
Relay Powerpack

INPUT
VOLTAGE

120VAC
277VAC
120VAC
277VAC
120VAC
277VAC

SURGE SUPPRESSOR
FOR HIGH ELECTRICAL NOISE

EASY INSTALLATION: Universal 3 wire

DIGITAL
CONTROLS

ENCLOSURE: Metal NEMA 1 Indoor
enclosure (see page 153 for enclosure
dimensions).

*Not for use with occupancy sensors.
**For replacement parts only. For newer style Transformer Relay Power Pack, see
TRP-U on page 116.

WIRING DIAGRAMS

HIGH GRADE MATERIAL: All components
are sealed with high grade die-electric
material to protect against contaminants and
other adverse environmental conditions.

WEIGHT: 7 oz.

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

COMMON

CENTER
CONTACT
LAMP
SHELL

APPLICATIONS
For high electrical noise
interference, recommended
for all digital controls.

ORDERING INFO
CATALOG
NO.

UPC
CODE

DESCRIPTION

90058-1

81024

Surge Suppressor

TORK 94

IN-WALL TIMERS

FEATURES
QUICK LOOK

SS720A SERIES

SPECIFICATIONS

24 HOUR OR 7 DAY
DIGITAL IN-WALL
TIME SWITCH

TIMING ACCURACY: Line frequency.
INPUT VOLTAGE: 125VAC, 60Hz.
WIRE SIZE: #14AWG.
OPERATING TEMPERATURE:
32°F to +104°F (0°C to +40°C).

APPLICATIONS

SS700Z

SS721Z

SS720A

701A

SSA

SSA-R24

SS

D1060
D212

A

C

Page No.

99

99

98

101

102

102

103

104

105

106

Timer Type

7 Day
Digital

7 Day
Digital

7 Day
Digital

24 Hour
Mechanical

Auto OFF
Digital

Auto OFF
Digital

Auto OFF
Electronic

Auto OFF
Electronic

Auto OFF
Mechanical

Auto OFF
Mechanical

Voltage

120/277

120/277

120

120

120/277

24

24/120/
208-240/277

120

ON

1 min.

1 min.

1 min.

30 min.

OFF

1 min.

1 min.

1 min.

30 min.

Minimum
Settings

5 min-12 hr 5 min-12 hr
10-60 min.
1 min-18 hr
10 min-8 hr 10 min-8 hr
2-12 hr

Outdoor security lighting
Interior lights for lived-in look
Fans and motors
Appliances

125/250/277 125/250/277
Various
2 min-12 hr

Various
2 min-12 hr

ORDERING INFO
Manual Override

Yes

Yes

Sunrise/Sunset

Yes

Yes

ON/OFF Set Points

10 Pair

10 Pair

Yes

Yes

SCHEDULING: 7 ON and OFF pairs of set
points for individual programs on each day of
the week. Minimum setting is 1 minute.
7 Pair

24

Flash Warning

TORK 97

Capacitor

Capacitor

Battery

Switch Type

SPST

SPST

SPST

Resistive Ratings

16A

16A

15A

SPST

NEW!

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 60 Hz

COLOR

SS720A

14017

120

White

SS720AA

14018

120

Light Almond

RANDOM MODE: Varies ON and OFF
times to create "lived in" look when away.
Yes

Audible Warning

Power Outage Backup

FEATURES

Yes

Yes

Yes

Capacitor

Capacitor

SPST

15 & 20A 800W/1200W

Yes

DAYLIGHT SAVING: Manual button push
for one hour adjustment.

Yes

MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.

CONTACT RATINGS
TYPE

VOLTAGE

RATING

General Purpose

120VAC

15A

WIRING: Requires a neutral.

Resistive

120VAC

15A

CLOCK FORMAT: AM/PM.

Tungsten

120VAC

15A

Motor

120VAC

1HP

Electronic Ballast

120VAC

500VA

SPDT

SPST or SPDT

SPST

SPST

SPST or DPST

POWER OUTAGE BACKUP: Rechargeable
Ni-MI battery retains time and schedule.

1A

4A or 7.5A

15

20/10/10A

20/10/10A

WALL PLATE: Supplied with standard single
gang decorator wall plate.

TORK 98

SS700Z & SS721Z
SERIES

BACKUP WITHOUT
BATTERY, ECO FRIENDLY!

NEW!

SUNSET / SUNRISE, ASTRONOMIC
7 DAY IN-WALL TIMER

SS700Z SERIES

TIMING ACCURACY: Line frequency.

energy

RATING

INPUT VOLTAGE: 120/277VAC, 50/60Hz.

Resistive

16A

120/277VAC

16A

WIRE SIZE: #12AWG input/output - #16AWG
3-way (remote).

Ballast

10A

120/277VAC

13A

Tungsten

8A

120VAC

8A

Pilot Duty

360VA

120VAC

720VA

Motor

1⁄2HP

120VAC

1HP

CALIFORNIA Title 24
ASHRAE 90.1

Outdoor security lighting
Interior lights for lived-in look
Fans and motors
Appliances

SS721Z SERIES

VOLTAGE

TYPE

OPERATING TEMPERATURE:
32°F to +104°F (0°C to + 40°C).

responsible

APPLICATIONS

CONTACT RATINGS

SPECIFICATIONS

With wall plate
(not included)

RATING

WIRING DIAGRAMS

ORDERING INFO

CONTACT RATINGS

CATALOG
NO.

UPC
CODE

INPUT SUPPLY
(VAC) 50/60 Hz

SWITCH
TYPE

COLOR

SS700Z

14019

120/277

SPST

White

SS700ZA

14020

120/277

SPST

Light Almond

SS721Z

14027

120/277

SPST

White

SS721ZA

14028

120/277

SPST

Light Almond

FEATURES
SCHEDULING: 10 ON and OFF pairs of
set points for individual programs on each
day of the week. 11 day groups speed
programming. Minimum setting is 1 minute.
ASTRONOMIC: Sunset and sunrise times
are adjustable from 10°- 60° Northern
or Southern latitudes. Can be individually
offset +/- 1-240 minutes for earlier or later
operation.
RANDOM MODE: Varies ON and OFF
times to create lived in look when away.
DAYLIGHT SAVING: Automatic
adjustment (can be omitted).
LEAP YEAR: Automatic Compensation.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.

MANUAL MODE: Does not run programs
until set to AUTO (automatic) mode.
VACATION MODE: No operation when
away.

WIRING DIAGRAM: INSTALLATION SS721Z

EASY WIRING:
SS700Z does not require a neutral, can be
used as a 3-way switch.
SS721Z Requires a neutral, can be used as
a 3-way switch.

H

COMMERCIAL GRADE SPECS: Control
lighting contactors and 277VAC loads.
Compatible with CFL lamps.

Blue

Red

Black

Load
White

CLOCK FORMAT: AM/PM.
POWER OUTAGE BACKUP: Permanent
schedule retention. Supercapacitor provides 2
days of real time backup.

Black

N

N

Ground

WIRING DIAGRAM: THREE-WAY INSTALLATION SS721Z
Connect a wire inside the gang-box between Traveler A and Hot.

ORDERING INFO
Green
Black

Blue

Black

Traveler A

H

Black
Red
Traveler B

Load
White

N

N

Ground

Green

IN-WALL TIMERS
TORK 99

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 100

701A & 711A SERIES

SPECIFICATIONS
SPECIFICATIONS

24 HOUR
IN-WALL TIME SWITCH

INPUT VOLTAGE: 125VAC, 60Hz.
WIRE SIZE: #14AWG.

SSA SERIES

SPECIFICATIONS

DIGITAL AUTO OFF
IN-WALL
TIME SWITCH

TIMING ACCURACY: .002%.
INPUT VOLTAGE:
120/277 VAC, 50/60Hz.

OPERATING TEMPERATURE:
32°F to +104°F (0°C to +40°C).

APPLICATIONS

WIRE SIZE: #18AWG.

APPLICATIONS
Offices, meeting rooms, library aisles
Stock and equipment rooms
Exhaust fans – work areas, utility
rooms, bathrooms
Hot tub heaters and circulating pumps
Timed override lighting and HVAC for
after hours and for loads controlled
by electromechanical or digital time
switches.

Porch or patio
Doorway
Pool
Outdoor security lighting

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT SUPPLY

SSA100

14010

120/277 VAC

SSA200

14011

120/277 VAC

SSA100R-24

14014

24VAC/24VDC

SSA200R-24

14015

24VAC/24VDC

LCS115M

82082

OPERATING TEMPERATURE:
0°F to +100°F (-17°C to +37°C).
TIME
SETTINGS

OUTPUT
CONTACTS

Minutes: 5, 15, 30
Hours: 1, 3, 6, 9, 12
Minutes: 10, 20, 40
Hours: 1, 11⁄2, 2, 4, 8
Minutes: 5, 15, 30
Hours: 1, 3, 6, 9, 12
Minutes: 10, 20, 40
Hours: 1, 11⁄2, 2, 4, 8
Momentary Switch
for Override (white)

SPST
SPST
SPDT
SPDT
SPST

CONTACT RATINGS

CLOCK FORMAT: AM/PM marked on
dial.
WALL PLATE: Supplied with single gang
wallplate.

INPUT SUPPLY
(VAC) 60 Hz

8-IN-1 TIMING: Choose from 8 preset ON
intervals.

COLOR

701A

10113

125

White

701AA

10118

125

Light Almond

711A

10114

125

White

MANUAL SCROLL-UP: Option allows
adjustment in 10 minute intervals.
FLASH WARNING: Optional flicker feature
turns load off for 1 second, 2 minutes before
end of timed cycle and again 1 minute before
end of timed cycle.

CONTACT RATINGS
TYPE

VOLTAGE

General Purpose

800W
800W
1200W
1⁄6HP

Pilot Duty
30V
1V min.

120VAC
30V
1V min.

240VA
1A
100µA

RATING
701A SERIES

711A SERIES

125 VAC

20A

15A

Resistive

125 VAC

20A

15A

Tungsten

125 VAC

1500W

1250W

Motor

125 VAC

1 HP

1⁄2HP

Ballast

SSA100/200

SSA100/200R-24

WIRING DIAGRAMS
SSA100/200

AUDIBLE WARNING: Optional beep will
sound every 12 seconds during the last 2
minutes of timed cycle.

BLACK

HOT

GREEN

120V GROUND

GREEN /YELLOW

277V GROUND

RED

TAMPER RESISTANT: Time ON interval
preset hidden behind wall plate.

RED

EASY SET: Dip switches provide quick set-up
of timing and options.
EASY WIRING: No neutral needed, great
for retrofit.
BACKLIT DISPLAY: Numerical read-out of
time remaining includes graphic bar showing
time remaining in 10% increments. Stands out
strongly in lighted and dark areas.

BLACK
ORANGE
BLUE
GREY

REMOTE
OVERRIDE

(+) 24VAC
or
(–)
VDC

NC
C
NO

YELLOW
YELLOW

SSA200R-24
USING TRP TRANSFORMER RELAY POWERPACK
BLACK
ORANGE
BLUE
GREY

REMOTE
OVERRIDE

NC
C
NO

YELLOW
YELLOW

LOW
VOLTAGE

20 AMP
LOAD

L

RED

WALL PLATE: Supplied with white standard
single gang decorator wall plate.
SSA-R24: Offers low voltage control with
SPDT output and includes momentary input.

NEUTRAL

LOAD

RED

WIRING: Requires a neutral.

Motor

120VAC
120VAC
277VAC
120VAC

RED
BLACK
BLUE

N

BLACK

VACATION MODE: Set timer OFF with
no change of tripper settings.

Tungsten

RED

BYPASS SWITCH: Slide switch for ON,
OFF, or TIMER (automatic) operation.

NEW!

UPC
CODE

RATING

TORK
TRP

SCHEDULING: Minimum ON setting is
30 minutes. Dial has 48 captive trippers.

CATALOG
NO.

VOLTAGE

WHITE

ORDERING INFO
FEATURES

TYPE

FEATURES

L

IN-WALL TIMERS
TORK 101

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 102

SS SERIES

SPECIFICATIONS

AUTO OFF
IN-WALL TIME SWITCH

TIMING ACCURACY:
±5% @ 60° to 80°F.

D SERIES

SPECIFICATIONS
SPECIFICATIONS

NEW!

ELECTRONIC AUTO OFF
IN-WALL TIME SWITCH

TIMING ACCURACY: Line voltage.
INPUT VOLTAGE: 120VAC, 60Hz.

INPUT VOLTAGE:
24/120/208-240/277VAC, 50/60Hz.

WIRE SIZE: #14AWG.
OPERATING TEMPERATURE:
32°F to 122°F (0°C to 50°C).

WIRE SIZE: #18AWG.
OPERATING TEMPERATURE:
0°F to +100°F (-17°C to +37°C).

APPLICATIONS

APPLICATIONS
Whole house fans
Indoor/Outdoor lighting
Bathroom fans and lights
Self storage

Bathroom fans and lights
Indoor/Outdoor lighting
Storage areas
Hospitality areas

ORDERING INFO

ORDERING INFO
FEATURES
VARIABLE TIMING: Choose from 1 minute
to 18 hours.
FLASH WARNING: “F” suffix models with
flicker feature turns load off for 1⁄2 second, 2
minutes before end of timed cycle and again 1
minute before end of timed cycle.
AUDIBLE WARNING: “B" suffix model will
buzz that every 12 seconds during the last 2
minutes of timed cycle.
TAMPER RESISITANT: Time ON interval
preset is hidden behind wall plate.
EASY SET: Small screw driver adjustment
provides quick set-up of timing.
EASY WIRING: No neutral needed, great
for retrofit.

CATALOG
NO.

INPUT SUPPLY
(VAC) 50/60Hz

WARNING BEFORE
TIME OUT

SWITCH
TYPE

SS20

14005 24/120/208-240/277

None

Single pole

SS20F

14008 24/120/208-240/277

*Flicker

Single pole

SS13F

14007 24/120/208-240/277

*Flicker

3-way

SS13B

14006 24/120/208-240/277

**Beep

3-way

*Flicker feature turns load OFF for ½ second, 2 minutes before end of timed cycle and again 1 minute
before end of timed cycle.
**Beep feature will begin a ½ second audible warning every 12 seconds during the last 2 minutes of
timed cycle.

CONTACT RATINGS
TYPE

SS13F &
SS13B

3-WAY: SS13 SERIES replaces standard
3-way switch with no re-wiring.
COLOR: White.

UPC
CODE

SS20 &
SS20F

FEATURES
VARIABLE TIMING:
Button push changes time ON setting.
D1060M: 10, 20, 30, 60 minute.
D212H: 2, 4, 8, 12 hour.
LED DISPLAY: Indicator moves to new range
as timer counts down.
TAMPER RESISTANT: Time ON interval preset.
EASY SET: No adjustments, just wire and go!
WIRING: Requires a neutral.
THREE COLORS: Ivory, Light Almond, White.

MINIMUM LOAD

CONTACT
RATINGS

VOLTS

WATTS

.25-4.0A Resistive
.25-4.0A Ballast*
.25-4.0A Tungsten
1⁄8HP @ 120VAC
1⁄3HP @ 240VAC
.50-7.25A Resistive
.50-7.25A Ballast*
.50-4.0A Tungsten
1⁄6HP @ 120VAC
1⁄2HP @ 204VAC

24
120
208
240
277
24
120
208
240
277

6
30
50
60
70
12
60
105
120
150

CATALOG
NO.

UPC
CODE

INPUT
SUPPLY
(VAC) 60Hz

TIME
SETTINGS

OUTPUT
CONTACTS

D212H

14021

120

Ivory

2, 4, 8, 12 HOURS

D212HA

14022

120

Light Almond

2, 4, 8, 12 HOURS

D212HW

14023

120

White

2, 4, 8, 12 HOURS

D1060M

14025

120

Ivory

10, 20, 30, 60 MINUTES

D1060LA

14024

120

Light Almond

10, 20, 30, 60 MINUTES

D1060MW

14025

120

White

10, 20, 30, 60 MINUTES

CONTACT RATINGS
TYPE

VOLTAGE

RATING

General Purpose

120VAC

15A

Resistive

120VAC

1000W

Tungsten

120VAC

1000W

Motor

120VAC

1⁄4HP

*Not compatible with compact fluorescent lamps (CFL) and electronic fluorescent ballasts.

IN-WALL TIMERS
TORK 103

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 104

A SERIES

SPECIFICATIONS

SPRINGWOUND AUTO OFF
IN-WALL TIME SWITCH

INPUT VOLTAGE:
125/250/277VAC, 50/60Hz.
TERMINAL SIZE: #12AWG.

C SERIES

SPECIFICATIONS

COMMERCIAL STYLE
SRINGWOUND AUTO OFF
IN-WALL TIME SWITCH

INPUT VOLTAGE:
125/250/277VAC, 50/60Hz.
TERMINAL SIZE: #12AWG.

OPERATING TEMPERATURE:
32°F to 122°F (0°C to 50°C).

OPERATING TEMPERATURE:
32°F to 122°F (0°C to 50°C).

ORDERING INFO

APPLICATIONS
Whole house fans
Indoor/Outdoor lighting
Bathroom fans and lights
Self storage

CATALOG
UPC
NO.
CODE
15 MINUTE MAX.

Wallplate not
included

A515MH

15020

A515MHW

15120

A515M

15013

A515MW

15113

A515MA

15127

HOLD
FEATURE

With Hold

APPLICATIONS
COLOR

Ivory
White
Ivory

No Hold

Wallplate
included

Ventilating fans
HVAC
Whirlpools
Self storage
Motors and pumps

White
Light Almond

30 MINUTE MAX.

A530MH

15021

A530MHW

15121

A530M

15014

A530MW

15114

CONTACT RATINGS
FEATURES

TYPE

VARIABLE TIMING: Twist knob for time
ON setting. Time ON lengths from 15 minutes
to 12 hour vary by model.

VOLTAGE

RATING

125VAC
250VAC
277VAC
125VAC
250VAC
277VAC

20A
10A
10A
20A
10A
10A

125VAC

7A

Resistive
Inductive

HOLD FEATURE: Some models have position
for constant ON.

Tungsten

EASY SET: No adjustments. Just wire and go!
EASY WIRING: No neutral required. Great
for retrofit! Use as single or in multi-gang box
with no de-rating.

125VAC
250VAC

Motor

1HP
2HP

A530MA

15022

A560MHW

15122

A560M

15015

A560MW

15115

A502HHW

15123

A502H

15016

A502HW

15116

3

9

6

0

0

12

12

3

9

6

9

A506HHW

15125

A506H

15018

9

A506HW

15118

With Hold

No Hold

Ivory
White

With Hold
No Hold

With Hold
No Hold

FEATURES
VARIABLE TIMING: Twist knob for time
ON setting. Time ON lengths from 15 minutes
to 12 hour vary by model.

Ivory

HOLD FEATURE: Some models have position
for constant ON.

White

EASY SET: No adjustments. Just wire and go!

White

EASY WIRING: No neutral required. Great
for retrofit!

Ivory

SWITCH TYPE: SPST, except C460M and
C412H – DPST

White

COLOR: Metal-brushed aluminum.

White

WALL PLATE: Includes real metal wall plate
with screw mounting, to add extra security for
commercial applications.

Ivory

TYPE

VOLTAGE

RATING

125VAC
250VAC
277VAC
125VAC
250VAC
277VAC

20A
10A
10A
20A
10A
10A

Tungsten

125VAC

7A

Motor

125VAC
250VAC

1HP
2HP

Resistive
Inductive

3

A512HH

15026

A512HHW

15126

A512H

15019

A512HW

15119

9

0
3

21

CAUTION: This timer is not to be used in precision timing applications where
inaccurate timing could have dangerous consequences (i.e. sun lamp, sauna, etc.).
6

15501

HOLD
FEATURE

No Hold

30 MINUTE MAX.

C530M

15503

No Hold

60 MINUTE MAX.

NEW!

C560M

15505

No Hold

C560MH

15506

With Hold

C460M*

15011

No Hold

2 HOUR MAX.

C502H

15507

No Hold

6 HOUR MAX.

C506H

15511

No Hold

12 HOUR MAX.

21

T OR K

1

C515M

White

With Hold

Ivory
NEW!

White

C512H

15513

No Hold

C512HH

15514

With Hold

C412H*

15010

No Hold

*DPST switch type.

1

2

CATALOG
UPC
NO.
CODE
15 MINUTE MAX.

12 HOUR MAX.

0
1

6

2

Light Almond

ORDERING INFO

CONTACT RATINGS

1

T OR K

2

White

6 HOUR MAX.

POT

2

0
12

No Hold

2 HOUR MAX.

POT

0

White
Ivory

15128

A560MH

COLOR: Ivory, Light Almond, White.

12

Ivory

60 MINUTE MAX.

SWITCH TYPE: SPST.
WALL PLATE: Fits standard or decorator
style wall plates, see below (not included).

With Hold

9

No Hold

Ivory
White

CAUTION: This timer is not to be used in precision timing applications where
inaccurate timing could have dangerous consequences (i.e. sun lamp, sauna, etc.).

All A Series timers have SPST switch type.

IN-WALL TIMERS
TORK 105

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 106

OCCUPANCY SENSORS

OSWS SERIES

SENSOR TECHNOLOGY
& PLACEMENT GUIDE
TECHNOLOGY
PIR AND ULTRASONIC

A Passive Infrared Sensor (PIR sensor), is a device that measures infrared
radiation (IR), or heat, from objects in its field of view. Because it only receives
information, it is considered passive. The IR sensor views a human body as an
IR generating object. The lens of the occupancy sensor breaks up the field of
view into IR sensitive bands. The occupancy sensor is designed to only react
when heat is sensed moving from band to band. For PIR occupancy sensors to
work object must have direct “line of sight” to the PIR sensor.

PLACEMENT GUIDELINES

PIR SENSOR, DECORATOR STYLE
IN-WALL
OCCUPANCY SENSOR

• Designed for ceiling mounting at a height of 8-10 feet (mounting
sensor at greater heights decreases the sensitivity to motion, while
lower mounting height will decrease range).
• The sensor needs a visually unobstructed view of the normally
occupied workspace and entry door(s).
• Avoid sensor placement with a direct view out a doorway. Placing the
sensor offset from the center and away from the door is
recommended.
Both technologies show higher sensitivity closer to the sensor to allow small
•
If the occupant cannot see a PIR sensor from their normal work
movements to be noticed. Sensitivity reduces further away from the sensor and
position,
the sensor will not be able to detect their presence.
may require a walking step to activate the sensor.
• File cabinets, partitions, or walls are typical types of obstructions. If
there are other obstructions between the sensor and the occupant, an
ultra-sonic or dual technology ceiling sensor is recommended.
• When the light level feature is used, mount within 15 feet of the
widows or skylight and avoid mounting the sensor close to lighting
WALL SENSOR
fixtures.
A Wall Switch Sensor provides a 180° coverage pattern, extending outward
•
Place
the sensor no closer than 5 feet to an HVAC airCEILING
duct whenAND
usingWALL OCC SENSOR SENSING PATTERNS
CEILING AND WALL OCC SENSOR SENSING PATTERNS
from the sensor. This will allow for instant turn ON when an occupant enters the
dual technology sensors.
space. Total area covered will be over 400 square feet.
• Open office designs encourage placement of the sensors to allow
overlapping coverage of small motion range and a clear view into
• Proper placement gives the sensor a clear line of sight to the entry door
each cubicle. Walking step motion may cover the entry to the space.
without viewing the hallway.
Dual technology units provide added sensitivity to small motion.
• The occupant must be able to see the sensor from their normal work position
otherwise the sensor will not be able to detect their presence.
• For offices where there are other obstructions between the sensor and the
occupant or the entry door, a ceiling sensor is required.
An Ultrasonic Sensors (US sensor) is a technology that works on a principle
similar to radar or sonar. It is an active technology that sends and receives. It
emits an inaudible high-frequency sound wave and evaluates the echo which
is received back after bouncing around in the room. This allows the sensor to
evaluate the whole room and can “look” over walls and obstructions to identify
movement.

PLACEMENT GUIDELINES

CEILING AND WALL OCC SENSOR SENSING PATTERNS

CONTACT RATINGS:
OSWS9P-120: 1000W Ballast, 800W
Incandescent, 1⁄6HP at 120VAC.
OSWS9P-277: 1800W Ballast at 277VAC.
OSWS9PD & OSWS9PDM: 1000W Ballast, 800W
Incandescent, 1⁄6HP at 120VAC, 1800W Ballast
at 277VAC.

responsible

energy

CALIFORNIA Title 24

CEILING SENSOR

A Ceiling Sensor provides a 360° coverage pattern of up to 1200
square feet when using passive infrared only. When using dual
technology the coverage pattern extends to over 2000 square feet.
Barriers within the space that block line-of-sight to sensor detection will
decrease coverage area when using passive infrared by itself, ultrasonic
dual technology will allow the sensor to get around the obstructions.

SPECIFICATIONS

ASHRAE 90.1

APPLICATIONS

ADJUSTABLE TIME DELAY:
30 seconds - 30 minutes.

Offices and hotels
Classrooms
Conference rooms
Lavatories
Hallways

OPERATING TEMPERATURE:
32° to 131°F (0° to 55°C).
MOUNTING: Box mount.

FEATURES
OSWS9P-120, OSWS9P-277 & OSWS9PD:
OPERATION: Automatic ON and automatic OFF
based on occupancy detection.
OFF DELAY: Selectable from 30 seconds to 30
minutes.
MANUAL OVERRIDE: Includes ON and OFF
switch.
EASY WIRING: No neutral required. Great for
retrofit.
OSWS9PD ALSO INCLUDES:
SENSITIVITY ADJUSTMENT: For PIR range.
DAYLIGHTING MODE: Adjustable level to
keep lights OFF even when occupancy is sensed if
adequate light exists in the room from windows or
skylights.

ORDERING INFO
CATALOG
NO.

UPC
CODE

DESCRIPTION

OUTPUT
CONTACTS

OSWS9P-120

82077

PIR in-line wall switch

120VAC

OSWS9P-277

82078

PIR in-line wall switch

277VAC

OSWS9PD

82079

120/277VAC

OSWS9PDM

82080

PIR in-line wall switch
with ambient light sensor
PIR in-line wall switch
manually activated

WIRING & COVERAGE DIAGRAMS
Wall Mounting Box

OSWS9PDM - VACANCY SENSOR:
OPERATION: Manual push button on and then
automatic OFF.

LINE
(Black)

OFF DELAY: Selectable from 30 seconds to 30
minutes.

LOAD
(Red)

SENSITIVITY ADJUSTMENT: For PIR range.
DAYLIGHTING MODE: Adjustable level to
keep lights OFF even when occupancy is sensed if
adequate light exists in the room from windows or
skylights.
MANUAL OVERRIDE: Includes ON and OFF
switch.

120/277VAC

GND
(Green)

Top and Side Coverage Pattern Diagrams

EASY WIRING: No neutral required.

35'

16'
180° Coverage
15°

4.0'
15°
35'

TORK 109

TORK 110

OSC15PLS

SPECIFICATIONS

PIR SENSOR, WITH AMBIENT LIGHT
OVERRIDE, MULTI-VOLTAGE
INTEGRAL POWERPACK,
CELING MOUNTED
OCCUPANCY SENSOR

VOLTAGE: 120 - 347VAC.
ADJUSTABLE LIGHT LEVEL: 5FC - 200FC.

responsible

energy

CALIFORNIA Title 24
ASHRAE 90.1

ADJUSTABLE TIME DELAY: 30 seconds 30 minutes (DIP switch).
TEST MODE: 5 seconds, upon initial power-up
or DIP switch reset.

APPLICATIONS

PIR COVERAGE: 1200 sq. ft.

Offices and hotels
Classrooms
Conference rooms
Lavatories
Hallways

sensitivity adjustment:
Full or 50% low (DIP switch).
operating temperature:
32° to 131°F (0° to 55°C).
mounting: Ceiling or box mount.
contacts: SPST dry contacts.

FEATURES

contact ratings: 800W Incandescent,
1000W ballast at 120VAC. 1800W Ballast at
277VAC. 2200W Ballast at 347VAC.

OPERATION: Automatic ON and automatic
OFF based on occupancy detection.

OSC12PL
& OSC5PL

SPECIFICATIONS
VOLTAGE: 24VDC.

PIR SENSOR
CELING MOUNTING
OCCUPANCY SENSORS

UPC
CODE

INPUT
SUPPLY

COVERAGE
(FEET)

DESCRIPTION

OSC15PLS

82076

120-347VAC

1200

WHITE

WIRING & COVERAGE DIAGRAMS

OSC15PLS
SENSOR

N

LOAD

WHITE (NEUTRAL)
BLACK (LINE)

RED

RED

ADJUSTABLE LIGHT LEVEL:
10FC - 150FC.

Offices
Classrooms
Conference rooms
Lavatories
Hallways

ADJUSTABLE TIME DELAY:
5 seconds - 30 minutes (DIP switch).
TEST MODE: 5 seconds, upon initial
power-up or DIP switch reset.
PIR COVERAGE: 1200 sq. ft.

OSC5PL / OCCUPANCY SENSOR
ASSORTED
SENSING
PATTERNS
OSC5PL
/ OCCUPANCY
SENSOR
ASSORTED SENSING PATTERNS

FEATURES

18ft

SENSITIVITY ADJUSTMENT:
Full or 50% low (DIP switch).

18ft

MOUNTING: Ceiling or box mount.

OPERATION: Automatic ON and automatic OFF
based on occupancy detection.

DAYLIGHTING MODE: Selectable to
keeps lights off when occupancy is sensed
if adequate light exists in the room from
windows or skylights.

CATALOG
NO.

POWER SUPPLY: TRP-U Power Pack
(up to 6 units).

CALIFORNIA Title 24

APPLICATIONS

OFF DELAY: Selectable from 30 seconds to 30
minutes.

POWER SWITCHING: Built-in power pack
for direct line voltage control.

energy

ASHRAE 90.1

OFF DELAY: Selectable from 30 seconds to
30 minutes.

ORDERING INFO

CURRENT CONSUMPTION: 9mA.

responsible

OPERATING TEMPERATURE:
32° to 131°F (0° to 55°C).

ORDERING INFO

12ft
COVERAGE
(FEET)

12ft

ECOSETTING: Learns typical use patterns and
adjusts the OFF delay for the most efficient time.

CATALOG
NO.

UPC
CODE

INPUT
SUPPLY

WALK-THROUGH MODE: Selectable to turn
lights OFF after only 3 minutes. If no activity is
detected after 30 seconds of occupancy detection,
lights turn OFF.

OSC5PL

82083

24VDC

500

White

OSC12PL

82081

24VDC

1200

White

TRP-U

82030

120/277VAC

DAYLIGHTING MODE: Selectable to keep lights
OFF when occupancy is sensed if adequate light
exists in the room from windows or skylights.

LCS115M

82082

DESCRIPTION

Power Pack
Momentary Switch

COVERAGE DIAGRAMS

PRESENTATION MODE: Optional MANUAL OFF
by an accessory wall switch (LCS115M). Sensor
will keep lights OFF while movement in room is
detected, then return to automatic ON after 5
minutes.

DIP SWITCH
Sensitivity

Time Delay

1

50%

VACANCY MODE: Optional MANUAL ON by
an accessory wall switch (LCS115M) and then
automatic OFF.

100%
Walk Through

3

Audible Alert

4

Enabled
Visible Alert

Vacancy

6

Disabled
Enabled

WARNING BEFORE OFF: Optional visual flash
warning and/or audible beep warning one minute
before turn OFF.

Enabled

20 Minutes
25 Minutes

Hold ON

30 Minutes

Disabled

OFF

ON

8

Disabled

15 Minutes

Enabled

7

Disabled

30 Seconds
5 Minutes
10 Minutes

5

Disabled

MANUAL OVERRIDE: Optional manual control
by an accessory wall switch (LCS115M) for ON and
OFF.

2

5 Sec/EcoSet

Factory Setting

9

Enabled

OSC5PL

OSC12PL

PLUG TERMINAL: Quick disconnect for sensor.
POWER SWITCHING: Transformer relay power
pack (TRP-U) required to power sensor and provides
line voltage switching. (see page 116 for product
information).

OCCUPANCY
SENSORS
TORK 111

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

22
6.7

11

7

3

3

7

11

TORK 112

OSC2OUP

DUAL TECHNOLOGY
CELING MOUNTED
PIR/ULTRASONIC
OCCUPANCY SENSOR

SPECIFICATIONS
VOLTAGE: 24VDC.
energy

CALIFORNIA Title 24
ASHRAE 90.1

APPLICATIONS

PIR COVERAGE: 1500 sq. ft. (adjustable).
SENSITIVITY ADJUSTMENT: Individual setting
range for ultrasonic of 50% and PIR of 75%.
ULTRASONIC OUTPUT: 32Hz
MOUNTING: Ceiling or box mount.

OPERATION: Automatic ON and automatic
OFF based on occupancy detection.
OFF DELAY: Selectable from 8 to 40
minutes.
ECOSETTING: Learns typical use patterns
and adjusts the OFF delay for the most
efficient time.

POWER SWITCHING: Transformer relay
power pack (TRP-U) is required to power
sensor and provide line voltage switching
(see page 116 for product information).

ADJUSTABLE TIME DELAY:
8 - 40 minutes.

US COVERAGE: 2000 sq. ft. (adjustable).

FEATURES

TORK 113

VOLTAGE: 24VDC.
responsible

energy

CALIFORNIA Title 24
ASHRAE 90.1

APPLICATIONS

HUMIDITY: 0 to 95% R.H. non-condensing for
indoor use only.

OFF DELAY: Selectable from 8 to 40
minutes.

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT
SUPPLY

COVERAGE
(FEET)

DESCRIPTION

OSCS20UP

82075

24VDC

2000 ft US
1500 ft PIR

White

TRP-U

82030

120/277VAC

Power Pack

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

POWER SWITCHING: Transformer relay
power pack (TRP-U) is required to power
sensor and provide line voltage switching
(see page 116 for product information).

ADJUSTABLE TIME DELAY:
8 - 40 minutes.

SENSITIVITY ADJUSTMENT: Manual
setting range of 50%.
ULTRASONIC OUTPUT:
OSC5U: 40kHz
OSC10U/OSC20U: 32kHz
MOUNTING: Ceiling or box mount.
OPERATING TEMPERATURE:
32° to 104°F (0° to 40°C).
HUMIDITY: 0 to 95% R.H. non-condensing
for indoor use only.

ECOSETTING: Learns typical use patterns
and adjusts the OFF delay for the most
efficient time.
MOTION INDICATION: Green for
ultrasonic motion. Indicator may be disabled.

POWER SUPPLY: TRP-U Power Pack
(up to 4 units).

US COVERAGE: 2000 sq. ft. (adjustable).

FEATURES
OPERATION: Automatic ON and automatic
OFF based on occupancy detection.

CURRENT CONSUMPTION: 33mA.

TEST MODE: 8 seconds, upon initial
power-up for 1 hour.

Offices and hotels
Classrooms
Conference rooms
Lavatories
Hallways

OPERATING TEMPERATURE:
32° to 131°F (0° to 55°C).

COVERAGE DIAGRAMS

OCCUPANCY
SENSORS

SPECIFICATIONS

ULTRASONIC, CEILING MOUNTING
OCCUPANCY SENSORS

POWER SUPPLY: TRP-U Power Pack
(up to 3 units).

TEST MODE: 8 seconds, upon initial
power-up for 1 hour.

Offices and hotels
Classrooms
Conference rooms
Lavatories
Hallways

MOTION INDICATION: Red for infrared
motion, Green for ultrasonic motion.
Indicators may be disabled.

CURRENT CONSUMPTION: 33mA.

responsible

OSC SERIES

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT
SUPPLY

COVERAGE
(FEET)

DESCRIPTION

OSC5U

82072

24VDC

500 SQ FT

White

OSC10U

82073

24VDC

1000 SQ FT

White

OSC20U

82074

24VDC

2000 SQ FT

White

TRP-U

82030

120/277VAC

Power Pack

COVERAGE DIAGRAMS

TORK 114

ELS

TRP-U

SPECIFICATIONS

INDOOR LIGHT LEVEL
ELECTRONIC
CCUPANCY
SENSOR

responsible

energy

VOLTAGE: 24VDC.

ASHRAE 90.1

LOAD REQUIREMENTS:
Ballast 20amp @120/277VAC.
Incandescent 20amp@120VAC.
Motor 1HP @120/240VAC.
Output 150mA @24VDC (with relay connected).

POWER SUPPLY: TRP-U Power Pack (up
to 4 units).
operating temperature:
50° to 104°F (10° to 40°C).

APPLICATIONS

mounting: Ceiling or box mount.

Offices
Classrooms
Conference rooms
Hallways

LOW VOLTAGE INPUT:
Control ON: 12 - 24VDC
Hold ON: 12 - 24VDC
Hold OFF: 12 - 24VDC

Power and switching
for occupancy sensors
Power and switching
for SSA R-24 series
BAS input compatible
Demand shedding applications
Device override to hold on
Momentary switched override
Low voltage 3-way wiring

FEATURES
DAYLIGHTING CONTROL: Turns OFF
when sufficient daylight present.
ADJUSTABLE LIGHT LEVEL:
10FC - 250FC (DIP switch).

FEATURES

EASY MOUNTING: Low voltage Class 2
wiring allows recommended mounting about
3 feet from daylight sources.

OPERATION: Switches line voltage loads ON/OFF
based on a contact closure from an occupancy sensor,
AUTO OFF switch, or relay.

PRESET ON DELAY: 30 seconds prevents
false triggering.

VOLTAGE: 120/230/277VAC, 50/60Hz.

CURRENT CONSUMPTION: 9mA.

CALIFORNIA Title 24

APPLICATIONS

ADJUSTABLE OFF DELAY:
Set from 3 to 15 minutes.

SPECIFICATIONS

INTELLEGENT
POWER PACK

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT
SUPPLY

DESCRIPTION

ELS-1

82049

24VDC

Indoor Daylight Sensor

TRP-U

82030

120/277VAC

Power Pack

operating temperature:
32° to 131°F (0° to 55°C).

ORDERING INFO

INTELLEGENT INPUT: Three additional input wires:
1. Hold OFF for demand shed control.
2. Hold ON override of local devices such as sensors.
3. Momentary switch input for remote override.

CATALOG
NO.

UPC
CODE

INPUT
SUPPLY

DESCRIPTION

TRP-U

82030

120/277VAC

Power Pack

MULTI-VOLTAGE: Tri-voltage input for flexibility.

LCS115M

82082

QUICK MOUNTING: Snaps into 1⁄2" box KO.

WIRING DIAGRAMS

MOUNTING: Box mount to 1⁄2" KO.

Momentary Switch

WIRING DIAGRAMS

ON
1 2 3 4 5 6 7

Power Pack 277V
Model TRP2
or Power Pack 120V
Model TRP1

New
Extension
Box

Existing
Junction
Box

TRP-U
LOW VOLTAGE WIRING

New Cover With
1/2 K.O. Provision
PHOTO SENSOR
ORIENTATION ARROW
UNDER IVORY COVER

PROGRAMMABLE 7-SECTION SLIDE SWITCH FOOT CANDLE SELECTION*
+

1 2 3 4 56
FOR7

SLIDE

FOOT CANDLE

#1

10FC

Warehouse

#2

25FC

#3

50FC

#4

75FC

Corridors
Machine equipment display showroom (such as
automobile and farm equipment) LOBBY (such as
airport waiting area).
Classrooms, common office areas

#5

100FC

Drafting rooms

#6

150FC

Retail display areas

250FC

High critical areas, product sorting and grading,
paint quality control.

#7

Bend Tabs After
Inserting in K.O.
Hole
New Extension Box
Only Used When
Low Voltage Wiring
Has to be Enclosed

*Slide only one switch to ON for selection, all other switches remain OFF.

OCCUPANCY
SENSORS
TORK 115

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 116

PLUG-IN TIMERS

400A SERIES

400D SERIES

INDOOR GENERAL PURPOSE 1875W
MECHANICAL MULTIPLE
ON/OFF TIMERS

INDOOR GENERAL
PURPOSE 1800W
DIGITAL PROGRAMMABLE
ON/OFF TIMERS

NEW!
responsible

energy

CALIFORNIA Title 24
ASHRAE 90.1

401A

APPLICATIONS

460D

APPLICATIONS
405A

Lamps, radios, televisions
Appliances
Automatically turn ON/OFF items
in the home, gives the home a
"lived in" look while away.

Lamps, radios, televisions
Appliances
NEW!

455D

Automatically turn ON/OFF items in
the home, gives the home a "lived
in" look while away.

402A

FEATURES

454D

NEW!

422A

FEATURES

457Z

REPEAT SCHEDULE: Daily.

REPEAT SCHEDULE: 7 day programming.

VARIABLE TIMING: Multiple ON/OFF times.

VARIABLE TIMING:
460D, 454D, 455D: Manual Daylight Savings
adjustment. Random mode for lived-in look. Manual
Override ON/OFF.

ON/OFF: Manual ON/TIMER switch.
ENERGY SAVINGS: Works with CFLs and LED lamps.

403A

457Z: Turns ON at Sunset; turns OFF at Sunrise or
other times; automatic DST adjustment; Random Mode
for lived-in look; Manual Override ON/OFF.
BACKUP: Battery back-up.
ENERGY SAVINGS: Works with CFLs and LED lamps.
ACCURACY: Digital accuracy to 1 minute.

ORDERING INFO
CATALOG
NO.

UPC
CODE

401A

16001

402A

16002

403A

16013

405A

16014

422A

16019

ORDERING INFO

RATINGS

125 VAC, 15A, 1875W Resistive
125VAC, 10A, 1250W Tungsten
125VAC, 1⁄3HP

125VAC 15A, 1875W Resistive
125VAC 500W Tungsten
125VAC TV-4

NO. OF
OUTLETS
( )

TYPE OF
PLUG

DESCRIPTION

VARIABLE TIMING
SEGMENTS

CATALOG
NO.

UPC
CODE

1

Polarized

Multiple ON/OFF Lighting Timer

15 minute

460D

16017

1

Grounded

Heavy Duty 24 hour Timer

15 minute

454D

16009

1

Polarized

Powerful & Compact Automatic Timer

30 minute

455D

16015

2

Grounded

Heavy Duty 15 AMP Automatic Timer

15 minute

1

Grounded

Heavy Duty 24 hour 15AMP Timer

30 minute

NOTE: " " = Indicates outlet location.

457Z

16016

RATINGS

120VAC, 15A, 1800W General Purpose
120VAC, 15A, 1800W Resistive
120VAC, 1000W Tungsten
120VAC, 1⁄3HP, TV-5
120VAC, 15A, 1800W General Purpose
120VAC, 15A, 1800W Resistive
120VAC, 960W Tungsten
120VAC, 1⁄3HP TV-5

NO. OF
OUTLETS
( )

TYPE OF
PLUG

DESCRIPTION

1

Polarized

Daily Programmable Digital Timer

24 ON/OFFs

VARIABLE TIMING
SEGMENTS

1

Grounded

Daily Programmable Digital Timer

Different schedule for
each day of the week.

2

Grounded

Daily Programmable Digital Timer

Multiple ON/OFFs
20 ON/OFFs

2

Grounded

Ultimate Plug-In 2-Outlet Timer

Different schedule for
each day of the week.
ON at Sunset
OFF at Sunrise

NOTE: " " = Indicates outlet location.

PLUG-IN TIMERS
TORK 119

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 120

600D SERIES

600A SERIES

OUTDOOR
NEW!
GENERAL PURPOSE 1875W
7 DAY DIGITIAL WITH
PHOTOCELL, 7 DAY DIGITAL
OUTDOOR TIMERS

OUTDOOR GENERAL PURPOSE 1875W
MECHANICAL PLUG-IN
PHOTOCELL COUNTDOWN
TIMERS

APPLICATIONS

responsible

energy

CALIFORNIA Title 24
ASHRAE 90.1

Photocell

APPLICATIONS

Landscape or Christmas lighting
Controls small pumps, fountains, motors

Landscape and Christmas lighting
Control small pumps, fountains,
motors, etc.
Energy saving

601A
602A

621D & 631D

(621D without photocell)

611A

611D

FEATURES

FEATURES

REPEAT SCHEDULE: Daily.

REPEAT SCHEDULE: 7 day programming.

VARIABLE TIMING: Multiple ON/OFFs, Manual ON/
TIMER switch.

VARIABLE TIMING: Manual Daylight Savings
adjustment. Random mode for lived-in look.
Manual ON/TIMER switch. Multiple ON/OFF for
each day of the week.

PHOTO TIMER: Two styles
652A - Dial setting. ON at dusk and OFF 2, 4, 6, or 8 hours
later. 654A - Digital setting. ON dusk and OFF 1 to 9 hours
later or at random times.

652A

BACKUP: Battery back-up.
ACCURACY: Digital accuracy to 1 minute.

ENERGY SAVINGS: Works with CFLs and LED lamps.

654A

ORDERING INFO
CATALOG
NO.

UPC
CODE

601A

16020

602A

16021

611A*

16022

652A

16026

654A

16025

RATINGS

125 VAC, 15A, 1875W General Purpose
125VAC, 15A, 1875W Resistive
125VAC, 10A, 1250W Tungsten
125VAC, 1⁄2HP
125VAC, 15A, 1875W General Purpose
125VAC, 15A, 1875W Resistive
125VAc, 650W Tungsten
125VAC, 1⁄3HP, TV-5

NO. OF
OUTLETS
( )

TYPE OF
PLUG

DESCRIPTION

1

Grounded Mechanical Outdoor Timer, with18" cord

2

Grounded Mechanical Outdoor Timer, with18" cord

1

Wall Mountable
Grounded Mechanical Outdoor
Timer, with 24" cord

2

Grounded

Photocell Outdoor Timer with 6.5" cord

2

Grounded

Photocell Outdoor Timer with 6.5" cord

VARIABLE TIMING
SEGMENTS

15 minutes
Multiple ON/OFFs
15 minutes
Multiple ON/OFFs
15 minutes
Multiple ON/OFFs
Photo ON
Dawn or timed OFF
Photo ON
Dawn or timed OFF

*611A: 1⁄3HP

PHOTOCELL: 611D and 631D have built-in
photocell to always turn ON at dusk and OFF at
dawn. Add a time OFF schedule

655D

655D
Remote

WIRELESS REMOTE: 655D receives ON/OFF
signal up to 80 feet away.

ORDERING INFO
CATALOG
NO.

UPC
CODE

611D

16018

621D

16056

631D
655D*

RATINGS

NO. OF
OUTLETS
( )

TYPE OF
PLUG

1

Grounded

2

Grounded

16027

125 VAC, 15A, 1875W General Purpose
125VAC, 15A, 1875W Resistive
125VAC, 1000W Tungsten
125VAC, 8A Ballast
125VAC, 1⁄2HP

2

Grounded

16042

125VAC, 5A, 625W Resistive
125VAC, 600W Tungsten

2

Grounded

DESCRIPTION

Wall Mountable Photocell & 7 Day
Digital 2-in-1 Timer, with 24" cord
Wall Mountable, 7 Day
Digital Timer, with 18" cord
Wall Mountable Photocell & 7 Day
Digital 2-in-1 Timer, with 18" cord
Remote control
indoor/outdoor receiver

VARIABLE TIMING
SEGMENTS

Photo ON
Dawn or timed OFF
Multiple ON/OFFs for
each day of the week
Photo ON
Dawn or timed OFF
Handheld remote ON/OFF

* ETL listed for U.S. and Canada.

NOTE: " " = Indicates outlet location.

NOTE: " " = Indicates outlet location.

PLUG-IN TIMERS
TORK 121

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 122

800 SERIES

NEW!
OUTDOOR GENERAL
PURPOSE 1875W
MECHANICAL & DIGITAL
STAKE TIMERS

APPLICATIONS
Landscape and Christmas lighting
Other outdoor lighting
Energy saving
803B
806B

FEATURES
REPEAT SCHEDULE: Mechanical timer 24 hours. Digital
timer 7 day programming.
806D

MECHANICAL TIMING: Multiple ON/OFFs, Manual ON/
TIMER switch.
DIGITAL TIMING: Manual ON/TIMER switch. Multiple
ON/OFF for each day of the week.
PHOTOCELL: 806D has optional built-in photocell to
always turn ON at dusk and OFF at dawn or 1 to 12 hours
later.
ENERGY SAVINGS: Works with CFLs and LED lamps.

ORDERING INFO
CATALOG
NO.

UPC
CODE

803B

16057

806B

16037

806D

16038

RATINGS

125VAC, 15A, 1875W Resistive
125VAC, 10A, 1250W Tungsten

125VAC, 15A, 1875W Resistive

NO. OF
OUTLETS
( )

TYPE OF
PLUG

3

Grounded

6

Grounded

6

Grounded

DESCRIPTION

VARIABLE TIMING
SEGMENTS

Mechanical Outdoor Stake Timer,
with 2' cord
Mechanical Outdoor Stake Timer,
with 2' cord. 3 timed outlets and 3 untimed.

15 minutes
Multiple ON/OFFs
15 minutes
Multiple ON/OFFs
Multiple ON/OFFs for each
Digital Outdoor Stake Timer, with 6' cord. 3 day of the week or Photo
timed outlets and 3 untimed.
ON and Dawn or 1-12
hours OFF.

NOTE: " " = Indicates outlet location.

PLUG-IN TIMERS
TORK 123

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 124

TORKALERT

™

MECHANICAL
STROBE HORNS

ALARM SOUNDS

MULTI-TONE
ELECTRONIC
HORNS

ALARM
TONE

BELL
HI-LO
CHIME
SINGLE STROKE BELL
HORN
3 BEEPS, PAUSE
SIREN
SLOW WHOOP

24VDC &115VAC

APPLICATIONS

APPLICATIONS

TA880-N5

High performance for industrial
signaling applications. Offers high
sound output, low current draw and
dependable operation. Strobes use
xenon flashtube, ideal for maximum
efficiency and reliability.

TA5508H-G1

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT
VOLTAGE

INPUT
CURRENT
(AMPS)

dB
@10 FEET

CANDELA

TA880-N5

96015

120VAC

0.115

96

15

ALARM: Penetrating mechanical sound.

TA5508H-G1

96071

24VDC

.059

strobe only

15/75

WIRING: Low current draw.

NOTE: TA880-N5 For outdoor use, unit must be mounted in a TA-WBBF outdoor backbox. See page 138
for ordering. TA5508H-G1 for indoor mounting only.

FEATURES

MOUNTING: 4" square surface mounting.

TA875-1G1

For indoor and outdoor use.
Superior sound penetration for
various room conditions. Screw
terminals accept #12AWG.

MECHANICAL
HORNS

FEATURES
OPERATING TEMPERATURE:
TA-MTS: -31˚F to +150˚F (-35˚C to +66˚C).
DIMENSIONS AND MOUNTING:
TA-MTS: 41⁄18”H x 41⁄8”W x 317⁄32”D
Can be mounted on celing or wall.
TA875-1G1: 43⁄4”H x 43⁄4”W x 13⁄8”D
1 gang, 2 gang or 4" square backbox.

TA875-1G1 24VDC HORN
CURRENT
(AMPS)

TA-MTS

ALARM
TONE

HORN
BELL
HORN 2
CODE 3 HORN
CODE 3 TONE
SLOW WHOOP
SIREN
HI-LO

TYPICAL dB
@10 FEET

0.020
0.025
0.028
0.026
0.023
0.023
0.040
0.040

91
96
93
93
97
97
95
96

TA-MTS 115VAC HORN
AMPS @ 120VAC
TYPICAL dB @10 FEET
HIGH
STANDARD
HIGH
STANDARD
OUTPUT
OUTPUT

0.050
0.041
0.050
0.050
0.042
0.050
0.045
0.042

0.042
0.039
0.040
0.042
0.040
0.042
0.041
0.039

85
82
85
82
79
85
85
82

82
75
79
75
75
82
82
79

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT
VOLTAGE

DESCRIPTION

TA875-1G1

97641

20-31VDC,
24VDC

Multi-tone Electric Horn

TA-MTS

97674

115 VAC

Multi-tone Electric Horn

HEAVY DUTY
BELLS

4", 6", 10" DIAMETERS
AC VIBRATING BELLS

ORDERING INFO

APPLICATIONS

CATALOG
NO.

Loud tone with typical decibel
output of 103 dB. Low frequency
resonation for strong penetration
of noisy areas like boiler rooms,
water pumping stations, elevators
and air compressor rooms.

UPC
CODE

INPUT
VOLTAGE

INPUT CURRENT
(AMPS)

APPLICATIONS

SURFACE TYPE

TA874-N5

96023

120VAC, 60Hz

0.070

TA874-N5R
(Red)

97613

120VAC, 60Hz

0.070

TA875-G1

97687

24VDC

0.035

For indoor or outdoor applications.
High sound output, durable and
dependable performance. Ideal for
schools and hopsitals.

ORDERING INFO
INPUT
VOLTAGE CURRENT
(AMPS)

dB
@ 10
FEET

CATALOG
NO.

UPC
CODE

SHELL
SIZE

TA340-4G5

96001

4”

24VAC

0.320

81-90 Dawn Mist

TA340-4N5

96002

4”

120VAC

0.065

81-90 Dawn Mist

TA340-6G5

96003

6”

24VAC

0.320

81-95 Dawn Mist

TA340-6N5

96004

6”

120VAC

0.065

81-95 Dawn Mist

COLOR

WITH WEATHERPROOF BACKBOX TA-WBBF UL LISTED FOR OUTDOOR USE

FEATURES

TA876-N5

INPUT VOLTAGE: Wide input voltage
ratings for compatibility with unregulated
power supplies.

HOUSING: Steel, painted Dawn Mist.
Resonant grill design for high sound
output.

WIRING: Screw terminals for convenient
IN/OUT wiring. Low current draw for
minimizing power supply and wiring cost.

MOUNTING: To indoor box TA-BBSF
or outdoor box TA-WBBF, see accessories
page 13*.

NOTE: Use TORK signal timers for 24 hour or 7 day scheduling, see page 85.

96026

120VAC, 60Hz

0.070

FEATURES
TERMINAL SIZE: #12 - 22 AWG.

TA340-10G5

96005

10”

24VAC

0.320

84-98 Dawn Mist

WIRING: Screw terminals permit fast IN/OUT
field wiring.

TA434-4N5

98005

4"

120VAC

0.065

81-95

Red

HOUSING: Steel gong and cast aluminum. See
page 138 for dimensional drawings.

TA434-6N5

97521

6”

120VAC

0.065

81-95

Red

TA434-10N5

96522

10”

120VAC

0.065

84-98

Red

NOTE: Use TORK signal timers for 24 hour or 7 day scheduling, see page 85.

TORK ALERT ™
TORK 127

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 128

LIGHT DUTY AND
GENERAL PURPOSE
BELLS & BUZZER

WEATHERPROOF
MOTOR DRIVEN
SIREN

DIMENSIONS
FRONT VIEW

8-1/4"

Power
wires
2 feet
long

APPLICATIONS

APPLICATIONS
Designed to operate on either bell
ringing transformers or batteries.
Non-adjustable sound.

TA725

(2) 9/32"
mounting
holes

Mount siren (hardware not included)
15-3/8"

FRONT VIEW

For industrial and outdoor
use. Ideal for evacuation and
warning systems.

TA740

6-7/8"

7-1/2" dia.
(2) nuts,
loosen to
adjust siren
direction.
8-1/4"

FEATURES
ALARM: Bell ringing, non-adjustable sound.
DIMENSIONS FOR TA725:
3" H x 21⁄2" W x 1" D.
MOUNTING: Fully enclosed sturdy steel bases
and covers. Base and cover snap together, no
screws required.

ORDERING INFO

FEATURES

CATALOG
NO.

UPC
CODE

SWITCH

VAC

VDC

AMPS

dB

TA740

96228

21⁄2” Gong

8-16

3-6

1

76 @ 10'

TA744

96230

4" Gong

8-16

3-6

1

78 @ 10'

TA725

96226

Buzzer

8-16

3-6

1

88 @ 3'

ORDERING INFO

MOUNTING: Fully enclosed sturdy steel bases.

Junction box &
(2) wire nuts (not furnished)

ORDERING INFO
CATALOG
NO.

UPC
CODE

INPUT
VOLTAGE

dB
@10 FEET

AMPS

VA

TA315-1N5

96599

120VAC/DC

117

2.5

300

APPLICATIONS

Powerful and loud, pleasant sounding
push-button chimes. Ideal for homes,
apartments and offices.

ALARM: Chime.

HOUSING: Red enamel paint over heavy
gauge aluminum housing. Fully enclosed
motor. 180° swivel and adjustable
direction.

Siren power wires

(2) 9/32"
mounting
holes

PULL-DOWN STATION

APPLICATIONS

INPUT: 16V, 10VA, 120VAC.

1/2" conduit (not furnished)
6-7/8"

MANUAL FIRE
ALARM

CHIMES &
CHIME KITS

FEATURES

Power
wires
2 feet
long

INPUT VOLTAGE: 120AC & DC, 60Hz.
ALARM: Loud, distinctive tone. Designed
to be effective over standard horns or bells.

8-1/2" dia.

1/2" conduit
connector

CATALOG
NO.

UPC
CODE

TAC212WS

96064

TAC212WL

96054

TAC210W

96052

DESCRIPTION

16VAC Chime + Push Button
clip for Stucco + 10VA
Transformer
16VAC Chime +
2 Push-buttons +
10VA Transformer
16VAC Chime

DIMENSIONS

73⁄16”L x 4”W x 2”D
71⁄4”L x 43⁄4”W x 21⁄2”D
71⁄4”L x 43⁄4”W x 21⁄2”D

Designed for indoor use.
Ideal for schools, hospitals,
industrial plants, warehouses
and retail stores. Key
required to close and reset
device. Meets requirements,
BSA, MEA, CA and UL.
FEATURES
ALARM: Loud, distinctive tone. Designed to be
compatible with any control panel to initiate local
alarm signals, trip municipal fire alarm box and start
fire pumps.

ORDERING INFO
CATALOG
NO.

UPC
CODE

SWITCH

VOLTS

AMPS

TA270A

96521

SPST, NO

30V AC/DC

1

MOUNTING: Sturdy metal construction, mounts to
a standard single gang electrical box.

TORK ALERT ™
TORK 129

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 130

TELEPHONE
RELAY

TELEPHONE
STROBE

APPLICATIONS

APPLICATIONS
For single-line analog phone
lines. Emits a high intesity
flashing light when the telephone
rings. Ideal for alerting the
hearing impaired, high ambient
noise environments and quiet
zones. ADA compliant.

This device activates appliances
when a telephone ring voltage is
detected. For indoor and outdoor
use with horns, bells or strobes.
Recommended use where
ambient noise levels are high.
FCC approved.

ORDERING INFO

FEATURES
PLUG:
RJ-11C connection.
TA-B-KHD-120VAC, includes 120VAC
power cord.

RINGER
PEAK
EQUIVALENCE CANDLEPOWER

CATALOG
NO.

UPC
CODE

INPUT TELEPHONE
RING VOLTAGE

POWER

TA-B-KHD-120VAC

97101

45-130V, 20-30Hz

120VAC

0.4

50-130V, 20-30Hz

Analog line
ring voltage

1.5

TA-B-KHD-1000-PP

97102

ORDERING INFO

FEATURES

CATALOG
NO.

UPC
CODE

INPUT TELEPHONE
RING VOLTAGE

AC INPUT
VOLTAGE

RINGER
EQUIVALENCE

PEAK
CANDLEPOWER

70,000

INPUT: Accepts RJ-11C phone plug.

TA-B-8332

97100

39-150V/20-30Hz

WIRING: Hard wire connections,
for analog phone lines.

Up to
115VDC-500MA

0.6

8,000

115VAC-5A,
230VAC-2A

MOUNTING: Easily mounts to interior
surfaces, for indoor use.

MOUNTING: Weatherproof, indoor and
outdoor, includes mounting bracket.

TELEPHONE
HORN

WALL CLOCKS
QUARTZ & ELECTRIC

ORDERING INFO
QUARTZ CLOCK

APPLICATIONS

APPLICATIONS
High quality compact signaling
device. For indoor use. Easily
connects to phone systems and
enables locations with moderate
to high ambient noise to have
a loud telephone alert. FCC
approved.

Each model meets United States
Government Specifications. All
Clocks provide second hand for
accurate timing.
ORDERING INFO

FEATURES
ALARM: Adjustable tone and volume.

FEATURES

CATALOG
NO.

UPC
CODE

INPUT TELEPHONE
RING VOLTAGE

dB
@3 FEET

RINGER
EQUIVALENCE

TA-B-KHS-1000-PP

97103

50-130V, 20-30Hz

90

0.8

PLUG: RJ-11C modular connection.
MOUNTING: Grey enclosure. For indoor use, surface
mountable.

QUARTZ
Accurate to one minute per year. Low power
consumption for long battery life.
Uses AA battery (not supplied).
ELECTRIC
110VAC, 60 Hz synchronous motor. 66 inch line
cord and plug. Does not require grounding.
MOUNTING: Concealed mounting brackets allow
for simple, neat placement on walls.

CATALOG
NO.

UPC
CODE

TYPE

SIZE

FRAME
COLOR

TA1886 G

96156

QUARTZ

8”

Grey

TA1886 B

96155

QUARTZ

8”

Brown

TA1887 G

96159

QUARTZ

12”

Grey

TA1887 B

96157

QUARTZ

12”

Brown

TA1887 BK

96158

QUARTZ

12”

Black

ELECTRIC CLOCK
CATALOG
NO.

UPC
CODE

TYPE

SIZE

FRAME
COLOR

TA1880 G

96152

ELECTRIC

8”

Grey

TA1880 B

96151

ELECTRIC

8”

Brown

TA1882 G

96154

ELECTRIC

12”

Grey

TA1882 B

96153

ELECTRIC

12”

Brown

TORK ALERT ™
TORK 131

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 132

PUSH-BUTTONS
ILLUMINATED,
NON-ILLUMINATED &
WEATHERPROOF

ELECTRIC DOOR
OPENERS
REMOTE CONTROL
& CONTACT DEVICES

DIMENSIONS
TA1786B Only
1 3/8"
(34mm)

2-3/8" DIA.

1-13/16"
BETWEEN
CL

2 13/32"
(61mm)

MOUNTING HOLES
ON MODEL TA1786B and TA1786CB

MODEL TA1786CB

For unlocking or locking metal or
wooden doors using low voltage
wiring. For AC, use TA591 or
TA592 transformer.

MORTISE TYPE REMOTE OPENER

Reversible for right or left hand door. Use with mortise entrance locks having a latch
bolt with up to 1⁄2" width and throw. Dimensional drawings available on page 138.
DEVICE

CATALOG
NO.

UPC
CODE

VOLTS

AMPS

For outdoor use to activate low
voltage bells, buzzers, horns or any
other audible signal. Ideal for factory
doors, receiving departments, small
office buildings, limited access retail
stores and private homes.

BUTTON

For activating a variety of signals, ideal for limiting space applications. Self-insulating and can be
mounted in any direction. All units include companion magnet. Dimensions: 23⁄16”L x 1⁄2”W x 1⁄2”D
UPC
CODE

DESCRIPTION

TA60

96975

Circuit closed with
magnet engaged

TA61

96976

Make & break
NO and NC

TA62

96977

Circuit open with
magnet engaged

VOLTS

24VAC
12VDC

TA09

96960

8-16VAC
3-6VDC

.95-1.75
1.25-1.80

AMPS
MAX.

TA154

.5

96962

16VAC
3-6VDC

BUTTON

Signals automatically with the opening and closing of doors, windows and transoms. Operates from
pressure in any direction. Non-tilt, non-jamming design. Fits 3⁄4" hole; no need to mortise.
DEVICE

CATALOG
NO.

UPC
CODE

DESCRIPTION

TA44

96995

Normally closed
Push to open

TA45

96996

Normally open
Push to close

TA46

Momentary contact
96997 Push
to make & break

VOLTS

AMPS
MAX.

CATALOG
NO.

Reversible for right or left hand door. Standard surface type used with lock latches with
up to 5⁄8" width and throw. 6" wire leads. Dimensional drawings available on page 138.
CATALOG
NO.

UPC
CODE

TA603L

2

ELECTRIC DOOR SWITCH

TA152

96961

UPC
CODE

DESCRIPTION

INPUT
VOLTAGE

TA1786B

96090

Without conduit
backplate

TA1786CB

96091

With conduit
backplate

Momentary Contacts
4 amps AC/DC @ 12V
4 amps AC, 2 amps DC @ 24V
2 amps AC
1 amp DC @48V

NON-ILLUMINATED PUSH-BUTTONS, UP TO 24VAC

COLOR

96035

Gold

CATALOG
NO.

UPC
CODE

COLOR

SIZE

TA600

96041

Polished
Brass

21⁄4”
(diameter)

TA603

96044

Polished
Brass

13⁄4”
(diameter)

TA631

96088

White

23⁄4 x 7⁄8"

TA635

96047

Ivory, black bar

23⁄4 x 7⁄8"

TA666BK

96048

Black, ivory bar

23⁄4 x 23⁄4

TA602

96043

Polished Brass

13⁄8 x 51⁄4 ”

TA601

96042

Sprayed Brass

2 x 29⁄16 ”

5⁄8"

TA620*

96045

Chrome

5⁄8”
(diameter)

5⁄8"

TA620B*

96046

Brass

5⁄8”
(diameter)

SIZE

13⁄4"

(diameter)

VOLTS

TA631L
12-24V
AC/DC

UPC
CODE

RIM TYPE REMOTE OPENER

DEVICE

CATALOG
NO.

.95-1.75
1.25-1.80

ILLUMINATED PUSH-BUTTONS, UP TO 16VAC

DOOR/WINDOW CONTACTS, ROLLING BALL TYPE

MODEL TA1786B

WEATHERPROOF PUSH-BUTTONS / SOLID CAST BRASS

MAGNETIC SWITCH CONTACTS
CATALOG
NO.

2 13/32"
(61mm)

APPLICATIONS

APPLICATIONS

DEVICE

1 3/16"
(30mm)

96089

White

23⁄4 x 7⁄8"

8-16VAC, 3-6VDC

DOOR TRIP SWITCH

TA656B

96039

Gold

TA215LB

96031

Brass

TA620L*

96037

Chrome

TA620LB*

96038

Brass

15⁄16

x 23⁄4”

BUTTON

For turning lights/signals on or off when doors are opened or closed. Ideal for closets, dark rooms, Signals automatically as door is openend. Commonly used on store doors to announce
storage areas of walk-in refrigeration. Rust resistant steel case with 4 knockouts, antique brass plate. entrance of customers. Mounts on top of door frame. Solid cast brass. Size: 3 x 15⁄8“
Box dimensions: 11⁄4"W x 3 7⁄8"H x 2”D. Plate dimensions: 11⁄4”W
DEVICE

CATALOG
NO.

UPC
CODE

DESCRIPTION

VOLTS

AMPS
MAX.

TA502

96964

Light ON when
door is open

125VAC
250VAC

6
3

DEVICE

CATALOG
NO.

TA236
TA503

96965

Light OFF when
door is open

125VAC
250VAC

6
3

UPC
CODE

96963

VOLTS

12-24VAC

AMPS
MAX.

2

11⁄4 x 2”

(diameter)
(diameter)

*Stainless steel plate to fit TA620 models: Order TA 147-1

TORK ALERT ™
TORK 133

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 134

WARNING LIGHTS
INDUSTRIAL UNITS

WARNING LIGHTS
VEHICULAR UNITS

ORDERING INFO

APPLICATIONS

COLOR

LETTER TO
REPLACE "*"

Red
Amber
Clear
Blue

R
A
C
B

conduit mounting. Full
selection of dome colors,
see "Ordering Info". For
outdoor use. All units must be
mounted vertically with base
at bottom.

DESCRIPTION

TA52*N5 – COMPACT ROTATING BEACON
DEVICE

117VAC
117VAC

TA53*E1 – ROTATING BEACON

Light intensifying reflector rotates arounf a low current 25 watt bulb. Bayonet socket for
easy lamp replacement. Ideal for restricted or dangerous areas.

VOLTS AMPS

90 FPM
Corrosion resistant/Outdoor use
Glass filled polypropylene housing
Acrylic dome
TA47AN5 96161
Tamper resistant dome clamps
Nominal current draw
TA47AR5 96162
91⁄2"H x 81⁄2” diameter

TA47RN5 96061

CATALOG UPC
NO.
CODE

TA52RN5 96063
.9

TA52AN5 96163

240VAC,
60Hz

TA52BN5 96263

DESCRIPTION

VOLTS AMPS

DEVICE

CATALOG UPC
NO.
CODE

TA53RE1 96083

80-90 FPM
360˚ rotation
Dependable belt & turntable design
117VAC .21
Acrylic dome
Nominal current draw
61⁄2”H x 55⁄8” diameter

TA53AE1 96183
TA53AF1 96185

Solid state circuitry in a low profile design. No moving parts means less Maintenance!

TA93-2AN5 97623
TA93-2CN5 96968
TA93-2BN5 97624

Single point shock-mounting. Ideal for use on security or service vehicles.

DESCRIPTION

VOLTS

90-100 FPM
Dependable belt & turntable design
25 watt lamp
Acrylic Dome
Nominal current draw
71⁄2”H x 6” diameter

12VDC

DEVICE

CATALOG UPC
NO.
CODE

DESCRIPTION

VOLTS

75 FPM, 12 watt lamp
12VDC
Quiet belt-drive motor.
Teardrop design fits under windshields.
Includes glare shield, velcro tape
TA54RE1 96087
41⁄2”H x 71⁄2” diameter

TA54AE1 96187

36VDC
24VDC

TA371L*N5 – ROTATING SEALED TWIN BEAMS

TA93-2*N5 – MIDI-STROBE

TA93-2RN5 99622

R
A

TA54*E1 – PORTABLE, MAGNETIC, ROTATING BEACON

Single point shock-mounting. Ideal for use on security or service vehicles.

TA53AG1 96184

DEVICE

Red
Amber

conduit mounting. Full
selection of dome colors,
see "Ordering Info". For
outdoor use. All units must be
mounted vertically with base
at bottom.

TA47*N5 / TA47*R5 – ALL PURPOSE 360° BEACON

CATALOG UPC
NO.
CODE

LETTER TO
REPLACE "*"

1⁄2"

Large parabolic reflector rotates around a 100 wall bulb. Long range beam. Use to indicate
equipment malfunctions, security intrusion, etc.
CATALOG UPC
NO.
CODE

COLOR

APPLICATIONS

1⁄2"

DEVICE

ORDERING INFO

DESCRIPTION

Heavy Duty, double sealed beam, revolving light with 30 watt lamps. Each 35,000 CP bulb
provides long range visibility.

VOLTS AMPS

70-80 FPM
Solid state electronic circuitry
High output 3-4 watt, 3.6 joules
Vertically mounted flash tube
117VAC .04
Snap out socket base for
360˚ Fresnel dome optics
Nominal current draw
6 1⁄2”H x 5 1⁄8” diameter

DEVICE

CATALOG UPC
NO.
CODE

TA371LRN5 96500

DESCRIPTION

TA131D*N5 / TA131D*U1 – DOUBLE FLASH SUPER STROBE

VOLTS AMPS

80-90 FPM
117 VAC
Lexan® dome
Quiet belt drive motor
Anodized aluminum housing with polished
aluminum, non-tarnishing base
Snap lock retaining ring
for quick & economical changeout
91⁄2”H x 8 1⁄2” diameter

.8

Ideal for industrial applications requiring extremely high visibility. One model
covers all popular mounting methods: 1⁄2" pipe, surface, flange, electrical box.
DEVICE

CATALOG UPC
NO.
CODE

TA131DRN5 96510
TA131DAN5 96610
TA131DRU1 96511
TA131DAU1 97611

TA94*N5 – ELECTRONIC STROBE

DESCRIPTION

VOLTS AMPS

120VAC
60 FPM, 7.5 JPF
High intensity 85,000 peak CP
Flashtube Rated at 7000-8000 hrs.
Durable Lexan® housing
10.55”H x 71⁄4” diameter

.2

TA879 – VEHICULAR BACKUP ALARM

Solid state electronic unit. Helps to comply with OSHA and State regulations. Makes
distinctive noise, ideal for extreme variations in background noise
DEVICE

CATALOG UPC
NO.
CODE

TA879

96102

DESCRIPTION

VOLTS

2 sound levels
97 or 87 dB +/- dB at 4ft
Multi-voltage
Water-resistant housing

12 to
48VDC

31.0VDC

High intensity strobe tube with inner fluted lens for maximum brilliance. No moving parts makes
it immune to shock and vibration. Ideal for security alert.
DEVICE

CATALOG UPC
NO.
CODE

DESCRIPTION

VOLTS AMPS

70-80 FPM
Solid state electronic circuitry High
output 3-4 watt, 3.6 joules
Acrylic dome
TA94AN5 97627
117VAC .04
Glass filled polypropylene housing
Suitable for outdoor use
TA94BN5 97628
91⁄2”H x 81⁄2” diameter
TA94RN5 97626

NOTE: "FPM" = Flashes per minute
"JPF" = Joules per flash
For replacement parts and accessories, see page 138.

TORK ALERT ™
TORK 135

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 136

ACCESSORIES,
REPLACEMENT
PARTS
& DIMENSIONS

POWER SUPPLY
UNITS
24 VDC UNITS

TA640
TA606

Red
Amber
Clear
Blue
Green
White

Units provide power to
multiple signaling devices
depending on requirements.

TA606
Regulated and filtered 24VDC up to 600mA. Easy to
use screw terminals, accepts #16-24AWG. No conduit is
required for installation.

RIPPLE
OUTPUT
CURRENT REGULATION VOLTAGE

CATALOG
NO.

UPC
CODE

INPUT
VOLTAGE

OUTPUT
VOLTAGE

TA606

96109

117VAC

24VDC

600mA

TA640

96110

115VAC

24VDC

4A

+/-5%

10mVRMS

TA640
Dual output unit, each providing 2 Amps fo current. If
connected in parallel, will provide up to 4Amps. Circuit
breaker provides input protection.

TRANSFORMERS

UNIT

ORDERING INFO
UPC
CODE

TYPE

TA590

96104

Bell

TA591

96105

Chime

VOLTS-AMPS PRIMARY SECONDARY
(VA)
VOLTAGE
VOLTAGE

5
10

120
120

10
16

Hz

60
60

TA592

96106

Tri-Volt

10-10-20

120

8-16-24

50/60

TA598

96602

Tri-Volt

20-30-30

120

8-16-24

60

TA599
TA1245Y-50
TA1245Y-75

96108
96166
96167

Heavy Duty
Heavy Duty
Heavy Duty

96971

Acrylic Dome – Amber

TA-M1

96138

12VDC Motor

TA53, TA54

TA-B1

96114

Small Drive Belts

TA53, TA54

TA-B2

96115

Large Drive Belts

TA371L

TA-B3

96116

Drive Belts

TA53, TA54

TA-L3

96129

12VDC Bulb

TA53

TA-L4

96130

24VDC Bulb

TA93-2

TA-L6-2

96982

110VAC Xenon Flash Tube

TA52

TA-L8

96134

110VAC Bulb

TA47

TA-L9

96135

110VAC Bulb

TA-L10

96136

110VAC Xenon Flash Tube

TA-L10-1 96981

110VAC Xenon Flash Tube

40
50VA
75VA

120
120/208/240
120/208/240

24
24
24

60
60
60

TA-L12

97625

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

WIRING DIAGRAMS

1/2"

2-7/8"

1-13/16"

TA874 Series

TA-BBSF 97694

TA874 Series

TA-WBBF 97692

Backbox – 4" painted Dawn Mist
Weatherproof Backbox – .5" KOs
4" painted Dawn Mist
Semi-Flush plate – Dawn Mist

3"

3-1/2"

TA-ADR

96111

Acrylic Dome – Red

TA47, TA94

TA-ADA

96311

Acrylic Dome – Amber

TA47, TA94

TA-ADB

96411

Acrylic Dome – Blue

TA52, TA53

TA-D5B

96419

Acrylic Dome – Blue

WIRE
LEADS
11/16"

3/32"
1-3/8"

TA-D6A

96320

Dome – Amber

TA54

TA-D6C

96422

Dome – Clear

TA93, TA94

TA-D7R

96121

Fresnal Dome – Red

TA93, TA94

TA-D7A

96321

Fresnal Dome – Amber

TA-D7B

96421

Fresnal Dome – Blue

TA131D

TA-D8R

96970

4-1/16"

15/16"
3/16" 7/16"

HEAVY DUTY BELLS
6”
10" DIA.

10”

6"
4-1/16" 3-3/8"

3-3/8"

10" DIA.

4-1/16"

3-3/8"
3-3/8"
4-1/16"

3-3/8"

3-1/4"
.173 DIA. CSK 80 ° TO 82°
TO 11/32" DIA. – 4 PLACES

3-3/8"
4-1/16"

3-3/8"

.173 DIA. CSK 80 ° TO 82°
TO 11/32" DIA. – 4 PLACES

4 1/16”
3-3/8"

3-3/8"

3-1/4"

4-1/16"

.173 DIA. CSK 80 ° TO 82°
TO 11/32" DIA. – 4 PLACES

.173 DIA. CSK 80 ° TO 82°
6" 11/32" DIA. – 4 PLACES
TO

4-1/16" 3-3/8"

Acrylic Dome – Red

.173 DIA. CSK 80 ° TO 82°
TO 11/32" DIA. – 4 PLACES
3-1/4"

3-3/8"4-1/16"

3-1/4"

3-1/4"

3-1/4"

.173 DIA. CSK 80 ° TO 82°
TO 11/32" DIA. – 4 PLACES

4”
3-3/8"

10" DIA.

6"

4-1/16"

4-1/16" 3-3/8"

4-1/16"

Fresnal Dome – Clear

TA93, TA94

5/8"

27/32" 23/32"

Dome – Red

TA54

CL

1-9/16"

No. 6 FLAT HEAD
WOOD SCREW

Semi-Flush plate – Red

TA47, TA94

3/32"

7/16"

CL

TA154

1/4"
15/16"

7/32"

1/8"

5/8"
1-1/4"

Replacement switcH

96621

1-1/4"

110VAC Bulb

4-1/16"

TORK 137

NO. 8 FLAT HEAD
WOOD SCREW

TA503SW 96969

TA-D7C

1"

CL

TA503

TA93, TA94

5/8"
1-3/4"

5-7/8"

Replacement switch

96120

1-9/16"

3-5/8"

TA502SW 96966

TA-D6R

3/4"

5-3/8"

TA502

TA54

3/8"

1-3/8"

Backbox

TA-BBSF, TA-WBBF TA-SFPFR 97697

11/32"

2-3/4"

3/32"

TA502-BX 96967

97707

1/8"

1/16"

TA09

TA502

TA-BBSF, TA-WBBF TA-SFPF

1/16"

9/16"

DESCRIPTION

3-3/8"

TORK ALERT ™

11/16"

No. 6 MOUNTING
SCREWS (3)

1/2"

CL

TA-D8A

TA94

APPLICATIONS

CATALOG UPC
NO.
CODE

WIRE
LEADS

CL 1-3/8"

2-1/8"

< Full selection of dome colors.
To designate color, place desired
letter in place of " * "

TA53

TA-94

CATALOG
NO.

3-5/16"

1-3/16"

TA131D

TA371L

Engineered to ensure long
use on bells, buzzers and
chimes.

9/16"

TA152

ORDERING INFO

ORDERING INFO
FEATURES

REMOTE CONTROL DOOR OPENERS

15/16"

APPLICATIONS

LETTER TO
REPLACE "*"
R
A
C
B
G
W

COLOR

DIMENSIONS

4-1/16"

2-7/8"

.173 DIA. CSK 80 ° TO 82°
TO 11/32" DIA. – 4 PLACES

TORK 138

POOL&SPA CONTROLS

PP PANEL SERIES
POOL AND SPA PANELS
WITH TIME SWTICHES

APPLICATIONS
Pumps
Swimming pools
Fountains
Ponds

LISTED
POOL/SPA
CONTROL PANEL
3NZM

PP-100R-P4

ORDERING INFO

PP-20R-2P4

CONTROL
INPUT

CONTROL #2

120VAC

N/A

Rated for 15A, 1⁄2HP @ 120VAC

53011

Mechanical
24 hour timer
Digital
7 day timer

120VAC

N/A

Rated for 15A, 1⁄2HP @ 120VAC

PP-20R

94015

N/A

120/240VAC

N/A

Panel only. Add controls from
page 147 and 148.

PP-20R-P1

53000

P1101-M

120VAC

N/A

PP-20R-P4

53001

P1104-M

240VAC

N/A

DEVICE MOUNTING: Provision for
mounting one or two devices in any
combination accepts toggle, GFCI, X-10 and
UPB type devices in, PP-100R and PP-125R
enclosures.

PP-20R-2P1

53002

P1101-2M

120VAC

PP-20R-2P4

53003

P1104-2M

240 VAC

Included with control
#1 mechanism
Included with control
#1 mechanism

PP-100R

94016

N/A

120/240VAC

TRANSFORMER: Select panels include 120V
input: 100 watt with output 12V/13V or 300
watt with output 12V/13V/14V.

PP-100R-P4

53004

P1104-M

240VAC

PP-100R-P4P1

53005

P1104-M

240VAC

P1101-M

120VAC

PP-100R-2P4

53006

P1104-M

240VAC

P1104-M

240VAC

PP-100R-P4P4FM

53009

P1104-M

240VAC

P1104FM-M

240VAC

PP-125R

94017

N/A

120/240VAC

PP-125R-P4

53007

P1104-M

240VAC

PP-125-2P4

53008

P1104-M

240VAC

P1104-M

240VAC

PP-125R-P4-100X

94018

P1104-M

240VAC

PP-125R-P4-300X

94019

P1104-M

240VAC

PP-10R-M-GFCI

FEATURES
COMBINATION PANEL: The PP panel
series provides a flexible platform to create a
custom pool and spa control at an off the shelf
price. Start with a blank panel and addtimers,
freeze controls, circuit breakers, switches and
outlets for a custom installation. Or select a
pre-assembled timer/panel available in many
popular combinations.
PP-10R: 15 amp timed GFCI protected outlet
with additional GFCI outlet.
PP-20R: 20 amp load center 120-240V, 1/2
circuit breaker base.
PP-100R: 100 amp load center 120-240V,
5/10 circuit breaker base.
PP-125R: 125 amp load center 120-240V,
8/16 circuit breaker base.
CONTROLS: Freeze protection or mechanical
and digital timers are all available with unique
features not found elsewhere in the industry.
Find specification details on pages 147 and 148.
BREAKERS: Listed for Cutler Hammer (BR),
GE (THQL), Murray/Siemens (MP) and Square D
(HOM) (not included).

REVERSIBLE DOOR: Easy-Hinge patented
removable and reversible door. Change from
left to right opening. Solves installation issues
in the field.
WHILE-IN-USE COMPARTMENT: Inside
mounting for two devices with cord exit.

COMPACT 2-IN-1: PP-20R-2P1 and
PP-20R-2P4 includes two timers in a compact
housing. Interlock switch allows second timer
to turn ON only if first timer is in operation.
ENCLOSURE: Metal NEMA 3R with lockable
hasp. See page 153 for dimensions.

NOTE: " " = Indicates freeze protection.

POOL & SPA
CONTROLS
TORK 141

PP-125R-P4-100X

PP-125R-P4

PP-20R-P4

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

CATALOG
NO.

UPC
CODE

PP-10R-M-GFCI

53010

PP-10R-E-GFCI

CONTROL #1

CONTROL
INPUT

ADDITIONAL
INFORMATION

120VAC

Two timers design 50A panel

240VAC

Two timers design 60A panel
Panel only. Add controls from
page 147 and 148.
Add another control
from page 147 and 148.

Timer 2 includes
Fireman Switch
Panel only. Add controls
from page 147 and 148.
Add another control from
page 147 and 148.

Includes 100 watt
Low Voltage Transformer
Includes 300 watt
Low Voltage Transformer

TORK 142

PFP SERIES

1100 SERIES

POOL FREEZE PROTECTION
SWIMMING POOL
TIME SWITCHES

SPECIFICATIONS

SAME ON/OFF TIMES EACH DAY
SWIMMING POOL
TIME SWITCHES

INPUT VOLTAGE: 120 or 208-277VAC,
60Hz (varies by model).
TIMING ACCURACY: Line frequency.
TERMINAL RANGE: #8 - #14AWG.
OPERATING TEMPERATURE:
-40° to 165°F (-40° to +74°C).

APPLICATIONS

APPLICATIONS

POWER CONSUMPTION: 3 watt max.

Pool pumps
Heaters
Lighting

Pumps
Swimming pools
Fountains
Ponds

ENCLOSURE: Lockable hasp. Type varies
by model. See page 153 for dimensions and
additional enclosure information.

FEATURES
SCHEDULING: Minimum ON setting is 20 minutes with a
minimum OFF setting of 75 minutes. Dial accommodates up to
12 pairs of trippers. One pair included.
MANUAL OVERRIDE: Until the next regularly scheduled
ON or OFF automatic operation then resumes.

FEATURES
FREEZE PROTECTION ONLY: Sensor turns on
load when outdoor air temperature drops to user
settable level between 33°F to 42°F. Moving
water prevents costly freeze damage.
TIMERS WITH FREEZE PROTECTION:
Control loads with mechanical or digital timer
with regular on and off schedule. Built-in
temperature sensor forces load on if outdoor air
temperature drops to user settable level between
33°F to 42°F.
COMBINATION PANEL
Combination of timers, freeze protection,
breaker base, and device mountings.
PP-20R: 20 amp load center 120-240V, 1⁄2
circuit breaker base.
PP-100R: 100 amp load center 120-240V, 5⁄10
circuit breaker base.

ORDERING INFO
CATALOG
NO.

UPC
CODE

CONTROL

CONTROL
INPUT

NOTES

CATALOG
NO.

UPC
CODE

PFP2

94035

PFP2-M

240VAC

Freeze protection only

1101

10011

PFP3

94036

PFP3-M

120/240
w/neutral

Freeze protection only

1101-M-IAP

10052

PFP1102

94037

PFP1102-M

240VAC

1104

10014

PFP1103

94038

PFP1103-M

120/240
w/neutral

1104-N

10042

PFPEW1102

94039

PFPEW1102-M

240VAC

1104-O

10017

PFPEW1103

94040

PFPEW1103-M

120/240
w/neutral

1104-M-IAP

10051

PP-20R-F2

94033

PFP1102-M

240VAC

1101FM-N

10043

94034

PFP1102-M &
P1104FM-M

240VAC

Freeze protection
with timer
Freeze protection
with timer
Freeze protection
with Digital timer
Freeze protection
with Digital timer
Freeze protection
with timer
Timer 2 includes
Fireman Switch

1104FM-N

10044

120/240VAC

Thermostat accessory

1101FM-M

10043

1104FM-M

10044

1101D

10028

1104D

10029

1104DF

10032

PP-100R-F2F4FM
PFPT

94028

BEAKERS: Listed for Cutler Hammer (BR), GE
(THQL), Murray/Siemens (MP) and Square D
(HOM) (not included).
WHILE-IN-USE COMPARTMENT: Inside
mounting for two devices with cord exit.

Replacement Trippers

DEVICE MOUNTING: Provision for mounting
one or two devices in any combination accepts
toggle, GFCI, X-10 and UPB type devices.

POOL & SPA
CONTROLS
TORK 143

NOTE: "

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

CONTACT RATINGS

ORDERING INFO

" = Indicates Freeze Protection.

Replacement Motor

INPUT SUPPLY
(VAC) 60Hz

OUTPUT
CONTACTS

ENCLOSURE
TYPE

Metal Indoor
NEMA 1
Mechanism
and
120
SPST
mounting plate
Metal Indoor
208-277
DPST
NEMA 1
®
Indoor/Outdoor
Noryl
208-277
DPST
NEMA 3R
Metal Indoor/Outdoor
208-277
DPST
NEMA 3
Mechanism
and
240
DPST
mounting plate
Noryl® Indoor/Outdoor NEMA
120
SPST
3R with fireman switch
®
Indoor/Outdoor NEMA
Noryl
208-277
DPST
3R with fireman switch
Mechanism with fireman
120
SPST
switch
Mechanism
with fireman
208-277
DPST
switch
Two 1101
Metal Indoor/Outdoor
120
SPST each
NEMA 3R
Two
1104
Metal
Indoor/Outdoor
208-277
DPST each
NEMA 3R
One
1104
Metal
Indoor/Outdoor
NEMA
208-277
One 1104FM
3R
Order #P47 for a pair of ON/OFF trippers
Order #PF48 for a pair of ON/OFF trippers for 1100FM series
120

SPST

TYPE

VOLTAGE

CONTACT
RATING

40A

Resistive

120-277VAC
single phase
120-277VAC
single phase

Tungsten

120VAC

40A

Inductive

120, 277VAC
single phase

20A

Pilot Duty

120-277VAC

1000VA

Motor

120VAC
240VAC

2HP
5HP

General Purpose

40A

#101 (120V) & #201 (208-277V)

TORK 144

DW200B TIMER

CONTACT RATINGS

SPECIFICATIONS

TWO SPEED PUMP CONTROL
TIME SWITCH

TYPE

TIMING ACCURACY: Line Frequency.
INPUT VOLTAGE:
120/208-240/277VAC, 50/60Hz.

Two speed pumps
SVRS device

30A

30A

Ballast

OPERATING TEMPERATURE:
-40°F to 158°F (-40°C to +70°C).

120VAC
277VAC

30A
20A

10A
10A

Tungsten

120-277VAC

15A

2A

POWER CONSUMPTION: 5VA max.

Pilot Duty

120-277VAC

720VA

720VA

ENCLOSURE: Noryl® Indoor/Outdoor NEMA 3R
is standard with lockable hasp. See page 153 for
enclosure dimensions and accessories.

Motor Load

120VAC
208-277VAC

1HP
2HP

1HP
2HP

Resistive

28VDC

30A

30A

CH 1
SPDT

SPDT

DWZ100B SERIES

TWO CHANNEL: Two programmable contacts
for independent control of pool equipment and
SVR or coordinated control for two speed pumps.
SCHEDULING: 99 ON & OFF set points allow
individual programs for each day of the week at
a minimum 1 minute apart.

ORDERING INFO
CATALOG
NO.

DW200B
DW200B-0

UPC
CODE

82190
82231

TIMER SUPPLY
(VAC) 60Hz

120/208-240/277VAC
120/208-240/277VAC

SPDT
C

TIMER SUPPLY

NO. OF
CHANNELS

2
2

DRY CONTACTS
(UNPOWERED)

DWZ100B SERIES
TIMER SUPPLY

N

SPDT
SPDT

120

208-240 277

120V
N

120

208-240 277

208-240V

120V

C

NO NC

TIMER SUPPLY

N

L
N

L

277V

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

TIMER SUPPLY

LOAD
N

CH 1
SPDT

DW200B SERIES

NO NC

AC LINE INPUT
SELECT277V
PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

DAYLIGHT SAVING: Automatic adjustment
(can be omitted) for year-round pools.

DW200B SERIES

LOAD

208-240V

HOLIDAYS: 1 to 24 individual dates for
preprogrammed longer run times for heavy use
times.

NC

24-277VAC

WIRING DIAGRAMS

FEATURES

NO

General Purpose

TERMINAL RANGE: #12 - #16AWG.

APPLICATIONS

CONTACT
RATING

VOLTAGE

120

120V
N

120

C

208-240 277

208-240 277

CH 2
SPDT

C

NO NC

NO NC

C

277V L

208-240V

LOAD
AC LINE INPUT
N
SELECT
PROPER
TERMINALS
277V
AND APPLY ONLY ONE VOLTAGE

C

NO NC

NO NC

L

208-240V

120V

CH 2
SPDT

L
LOAD
L N

LOAD
N

LOAD
N

AC LINE INPUT
SELECT PROPER TERMINALS
AND APPLY ONLY ONE VOLTAGE

TWO SPEED PUMP WIRING

MANUAL OVERRIDE: Until the next regularly
scheduled ON or OFF, automatic operation then
resumes.

TWO SPEED PUMP WIRING

CLOCK FORMAT: AM/PM or Military time
POWER OUTAGE BACKUP: Permanent
schedule retention when timer is powered
down at the end of the season. Super capacitor
provides 7 days of real time backup.

POOL & SPA
CONTROLS
TORK 145

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

TORK 146

P1100 SERIES

QUICK INSTALL/RELEASE LEVER: For easy installation
and removal when installing into pool panels.

SWIMMING POOL TIMERS, 24 HOUR
ELECTROMECHANICAL
CONTROL

LOAD INDICATOR LAMP

P1100 SERIES

QUICK INSTALL/RELEASE LEVER: For easy installation
and removal when installing into pool panels.

SWIMMING POOL TIMERS, 7 DAY
DIGITAL CONTROL

LOAD INDICATOR LAMP
LARGE LCD DISPLAY

CONVENIENT EXTERNAL ROCKER SWITCH: 3 position
switch: OFF/ON/AUTO. Use switch to turn OFF pump at the
end of pool season.

LARGE "MANUAL" BUTTON: 3 operating modes
available: OFF/ON/AUTO. Using the OFF mode, the pool can
be closed down without disrupting the time settings.

REAL TIME SWITCH FACE: Easy to set and check time.

POWER OUTAGE BACKUP: Battery retains time and
schedule.

CAPTIVE TRIPPERS: 15 minute intervals, no lost trippers.
HEATER CONTACTS: FM suffix includes "Fireman Switch"
to turn off pool heater 20-30 minutes before timer turns OFF.
Contact rates SPST, 15A @120V.

7 DAY PROGRAMMING ONE MINUTE INTERVAL:
Allows for the control of various electrical equipment on a 7
day schedule. 15 schedule weekly programs.

THERMOSTAT: PFP models include built in Freeze
Protection. No extra wiring. Thermostat turns on load at
user settable level between 33°F and 42°F. Moving water
prevents costly freeze damage.
ACCESSORY CONTACT: PF models include extra contact to
accept PFPT Freeze Protection Accessory. Thermostat turns ON
load at user settable level between 33°F adn 42°F. Moving
water prevents costly freeze damage.
TIMER INTERLOCK: Makes one second timer dependant
on operation of another timer.

ORDERING INFO
CATALOG
NO.

RESISTIVE/
UPC INPUT SUPPLY
CODE (VAC) 60Hz CONTACTS INDUCTIVE
RATINGS

HP RATING

PFP2-M

94026

240

DPST

40A

7.5HP @ 240V

PFP3-M

94027

120/240
w/neutral

DPST

40A

3 HP @ 120V
7.5HP @ 240V

P1101-M

10056

120

DPST

40A

3 HP @ 120V

P1101FM-M

10060

120

DPST

40A

3 HP @ 120V

PF1101-M

94020

120

DPST

40A

3 HP @ 120V

PF1101FM-M

94024

120

DPST

40A

3 HP @ 120V

PFP1102-M

94022

240

DPST

40A

7.5HP @ 240V

PFP1103-M

94023

120/240
w/neutral

DPST

40A

3 HP @ 120V
7.5HP @ 240V

P1104-M

10057

240

DPST

40A

7.5HP @ 240V

P1104FM-M

10061

240

DPST

40A

7.5HP @ 240V

PF1104-M

94021

240

DPST

40A

7.5HP @ 240V

PF1104FM-M

94025

240

DPST

40A

7.5HP @ 240V

P1101-2M

10058

120

DPST

40A

2HP @ 120V

P1104-2M

10059

240

DPST

40A

5HP @ 240V

POOL & SPA
CONTROLS
TORK 147

NOTES

Thermostat
only
Thermostat
only

Fireman
Switch
Accepts PFPT
thermostat input
Fireman Switch & Accepts
PFPT thermostat input
Freeze Protection
included
Freeze Protection
included

Fireman
Switch
Accepts PFPT
thermostat input
Fireman Switch & Accepts
PFPT thermostat input
Replacement for
PP-20R-2P1
Replacement for
PP-20R-2P4

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

THERMOSTAT: PFPEW models include built in Freeze
Protection. No extra wiring. Thermostat turns on load at
user settable level between 33°F and 42°F. Moving water
prevents costly freeze damage.
ACCESSORY CONTACT: PFEW models include extra
contact to accept PFPT Freeze Protection Accessory.
Thermostat turns ON load at user settable level between 33°F
and 42°F. Moving water prevents costly freeze damage.

ORDERING INFO
CATALOG
NO.

RESISTIVE/
UPC INPUT SUPPLY
CODE (VAC) 60Hz CONTACTS INDUCTIVE
RATINGS

HP RATING

PEW101-M

82432

120

DPST

40A

3 HP @ 120

PFEW101-M

94029

120

DPST

40A

PFPEW1102-M

94031

240

DPST

40A

PFPEW1103-M

94032

120/240
w/neutral

DPST

40A

Accepts PFPT
thermostat input
protection
7.5HP @ 240V Freeze
included
3 HP @ 120V Freeze protection
7.5HP @ 240V
included

PEW104-M

82442

240

DPST

40A

7.5HP @ 240V

PFEW104-M

94030

240

DPST

40A

Accepts PFPT
7.5HP @ 240V thermostat
input

NOTES

TIMER INTERLOCK: Makes one timer dependant on
operation of another timer.

3 HP @ 120

NOTE: "

" = Indicates Freeze Protection.

WIRING DIAGRAMS

POOL & SPA
JUNCTION BOXES

A

B

C

APPLICATIONS
For installation of underwater pool
lights or low voltage connections.
Solid brass with grounded post and
3 ground terminals for use with
metallic or PVC conduit.
NOTE: "

" = Indicates Freeze Protection.

ORDERING INFO
CATALOG
NO.

UPC
CODE

NPF CONDUIT HUB PIPE INPUT
A/B/C
SIZE

PB-50

94041

1⁄2"

/ 1⁄2" / 1⁄2"

1⁄2"

PB-75

94042

3⁄4"

/ 3⁄4" / 3⁄4"

.3⁄4"

PB-100

94043

3⁄4"

/ 1"/ 3⁄4"

3⁄4"

& 1"

TORK 148

SR-500 & SR-500PS

NEW!

SAFETY VACUUM
RELEASE SYSTEMS

2
1
Of all the protections you can put
between your family and the risk of
entrapment, the best protection is

APPLICATIONS

AT THE SOURCE.

®

A Safety Vacuum Release System (SVRS)
works by monitoring the vacuum on the
suction side of the pool or spa pump. When a
blockage occurs in the main drain or skimmer,
a sudden rise in vacuum will cause the SR-500
and SR-500PS to shut down and activate an
audible alarm. The pump will remain off with
the alarm sounding until manually reset.

Make Your Pool & Spa Safer, Update your

LAYERS OF PROTECTION
Door alarms on doors leading to the pool or spa area
help to alert parents or staff to anyone entering the
pool from the house or building.

Commercial & Residential
Swimming pools and spas
Fountains
Ponds
Any pump size

WARNING ALARM: Multiple audible alarm
capabilities – allows for quicker alert to harmful
situations.
AUXILARY CONTACTS: Accessible extra dry
contact – auxiliary equipment can be added.
EQUIPMENT PROTECTION: Low vacuum
sensing - (prevents cavitations or running the
pump dry, eliminating costly equipment failure).
SCHEDULING: Programmable 24 hour timer,
or as stand-alone SVRS working in conjunction
with existing pool controller.

POOL & SPA
CONTROLS
TORK 149

Remote alarms linked to the Safety Vacuum Release
System (SVRS) alert parents or attendants when the
SVRS is activated, indicating that someone in the pool
may need help.

ORDERING INFO

FEATURES
PROTECTION:
• Provides an important layer of protection,
reducing entrapment risk.
• Turns off pump in milliseconds upon detecting
sudden vacuum change.
• Vacuum monitored 128 times per second,
rapid response and accurate readings.
• Power monitored 50/60 times per second,
insures continuous power detection.
• Newest state-of-art NEC microprocessor
technology-- guaranteed reliability and
performance.

OUTSIDE
THE POOL AREA
Keep children from
accessing the pool
or spa when
unattended

DOOR ALARMS

1

POWER OUTAGE BACKUP: Insures
settings and reading will be saved, 30 minute
rapid recharge.

INPUT SUPPLY DRY CONTACTS
(VAC) 60Hz
(UNPOWERED)

CATALOG
NO.

UPC
CODE

SR-500

95425

120/240

DPST

SR-500PS

95426

120/240

DPST

MAINTENANCE OVERRIDE: 30 minute
maintenance override - (for pool or spa
service).
BUILT-IN DIAGNOSTICS: Displays
error codes, prevents guessing during
troubleshooting.
EASY RETROFIT: Integrates with common
existing timer box Trouble free installation, no
pipes to cut or glue.
COMPLIANCE: ASME/ANSI 112.19.17 as
required by the International Building Codes
(IBC) and the International residential Codes
(IRC). Meets all current codes and standards
for
SVRSs on new and existing pools and spas.
ENCLOSURE: Plastic Indoor/Outdoor NEMA
3R with lockable hasp. See page 153 for
dimensions and additional information.

2

Restrict access to a pool or spa by surrounding the
area with fencing that is equipt with a self-closing,
self-latching gate closure. Utilize gate latches that
are adjustable, magnetically operated as well as key
lockable.

CONTACT RATINGS
TYPE

General Purpose
Motor

VOLTAGE

120VAC
240VAC
120VAC
240VAC

FENCE & GATE

3

An emergency STOP button allows parents or attendants in the
area to immediately and easily shut down the pump system in
the event of entrapment.

INSIDE
THE POOL AREA
Minimize the
risk of entrapment
injuries or drowning

CONTACT
RATING

20A
3HP

EMERGENCY STOP

4

SVRS

The SVRS automatically shuts down the vacuum pump when
sensing a rise in vacuum pressure – in some cases, reacting to
potential entrapment conditions in LESS THAN ONE SECOND!
Audible alarms linked to the SVRS alert those nearby to a
potential entrapment.
SVRS should meet or exceed ASME/ANSI A112.19.17 standards
in order to comply with IRC and IBC codes.

5

3

DRAIN COVERS

Minimize potential entrapments or “Differential Hold Down
Forces,” thereby minimizing the potential for a swimmer to
be entrapped.

4

5

Anti-entrapment drain covers should meet or exceed ASME
and ANSI A112.19.8 2007 and 2007 Federal Pool & Spa
Safety Act and have a Certified Safe Flow Rating. Many
compliant drain covers are easily retrofitted to existing drains.

ALL ITEMS AVAILABLE FROM NSi/TORK!

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

More details available in our Safety Products catalog and Layers of
Protection brochure, ask your sales representative for more information.

ANTI-ENTRAPMENT
DRAIN COVERS

SELF-LATCHING
GATE CLOSURES
& SELF-CLOSING
GATE HINGES

NEW!

NEW!

640-475XV
TCA1-MK2
DS360M

TCHD1ARP-MK2
AV20X20 & AV26X26

FEATURES
DS360M DRAINSAFE
• Designed for use with suction outlet sumps up
to 8" in size, will retrofit smaller 5” sumps using
additional knockouts.
• Certified Safe flow of 123 GPM.
• ASME/ANSI A112.19.8 2007 Standard Compliant.
DS12X12P DRAINSAFE
• Designed to retrofit Pentair style frames, and
functions on dual drain as well as single suction
outlets.
• Certified Safe flow of 250 GPM @ 1.5 FPS.
• ASME/ANSI A112.19.8 2007 Standard Compliant.
DS12X12H DRAINSAFE
• Designed to retrofit Hayward style frames, and
functions on dual drain as well as single suction
outlets.
• Certified Safe flow of 250 GPM @ 1.5 FPS.
• ASME/ANSI A112.19.8 2007 Standard Compliant.

FEATURES

DS12X12P

DS12X12H

ORDERING INFO
CATALOG
NO.

UPC
CODE

DESCRIPTION

SURFACE AREA
(SQ.IN)

RETROFIT
FRAME

DS360M

95431

Drainsafe Anti-Entrapment
Type Suction Outlet Cover

27

N/A

DS12X12P

95429

53

Pentair

DS12X12H

95430

53

Hayward

640-475XV

95432

159.6

18 x 18

AV20X20

95433

AV26X26

95434

Drainsafe 12 x 12" Anti-Entrapment
Type Suction Outlet Cover
Drainsafe 12 x 12" Anti-Entrapment
Type Suction Outlet Cover
Waterway 18 x 18"
Anti-Entrapment Drain Cover
Eureka 20 x 20"
Anti-Entrapment Drain Cover
Eureka 26 x 26"
Anti-Entrapment Drain Cover

640-475XV WATERWAY
• Designed for single and multiple drain use, the
640-475XV works on dual drain as well as single
suction outlets.
• Minimizes “Differential Hold Down Forces” of
dual drain systems.
• Certified Safe flow rate of 540 GPM @ 1.09 FPS.

73.6
108.9

12 x 12
(9 x 9 minimum)
18 x 18
(12 x 12 minimum)

MAGNA•LATCH GATE CLOSURES
MagnaLatch quality latches are self-latching with
permanent magnets which never lose power, for
safer, child-resistant security for your swimming
pool gate. The Top Pull model can be mounted so
the release knob reaches the minimum code height,
typically 54", on a shorter gate. It's adjustable for
when the gate gets out of alignment. The Vertical
Pull model is designed for gates and fences that
are 60” or more in height.
TRU•CLOSE GATE HINGES
TruClose® hinges are designed so the residential
homeowner can quickly and easily adjust tension to
support a 375lbs gate load and self-closes up to a
55lb gate, for the ultimate safety around pools and
other areas requiring self-closing gates. Hinges
are rust-free and are self-lubricating. Regular duty
and heavy duty models available.

FENCE
MATERIAL

PACKAGING
AVAILABLE

CATALOG
NO.

UPC
CODE

DESCRIPTION

MLTPS2BGA

95439

MagnaLatch Top Pull Gate Latch

MLTPRP

95445

MLVPS2BGA

95440

MLVPRP

95444

MLS2RPAKA

95446

Round Post Adapter Kit

Wholesale

MLSPACER

95447

MagnaLatch Gap Spacer

Retail

Wholesale

MagnaLatch Top Pull Gate Latch, 2" Gap

Retail

Spacer included

Wholesale

MagnaLatch Vertical Pull Gate Latch
MagnaLatch Vertical Pull Gate Latch, 2"

Retail

Gap Spacer included

REGULAR DUTY MODELS
TCA1RP-MK2

98018

TruClose® Regular Range Gate Hinge

Metal

Retail

TCA1-MK2

98026

TruClose® Regular Range Gate Hinge

Metal

Wholesale

TCA3RP-MK2

98019

TruClose® Regular Range Gate Hinge

Vinyl, Wood

Retail

TCA3-MK2

98027

TruClose® Regular Range Gate Hinge

Vinyl, Wood

Wholesale

TCAMA2RND

98024

TruClose® Regular Range Gate Hinge,
Round frames
adjustable gap

Wholesale

HEAVY DUTY MODELS

DS-MR

DS-AA

TORK 151

MLTPS2BGA

POOL & SPA SAFETY
ACCESSORIES

AV20X20 & AV26X26 EUREKA
• Eureka drain covers unique grating system is
designed for new construction and retrofit, to add
protection from entrapment.
• ASME/ANSI A112.19.8 2007 Standard Compliant.
• Certified Safe flow rate of 223 GPM (20x20),
495 GPM (26x26).

POOL & SPA
CONTROLS

ORDERING INFO

TCHD1ARP-MK2

98020

TruClose® Heavy Duty

Metal

Retail

TCHD1AL2-MK2

98021

TruClose® Heavy Duty, with 2 legs

Metal

Wholesale

TCHD2RP-MK2

98022

TruClose® Heavy Duty

Vinyl, Wood

Retail

TCHD2L2-MK2

98023

TruClose® Heavy Duty, with 2 legs

Vinyl, Wood

Wholesale

SAFETY ACCESSORIES

SR-RA

SR-ESB

SR-RA

95437

Remote Alarm

SR-ESB

95438

Emergency Stop Button

DS-AA

95435

Drainsafe Masonry Anchor Kit - for
DS360M

DS-MR

95436

Drainsafe Mud Rings, Universal Fit

ALL ITEMS AVAILABLE FROM NSi/TORK!

A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com

More details available in our Safety Products catalog and Layers of
Protection brochure, ask your sales representative for more information.

TORK 152

ENCLOSURES

ENCLOSURES
STANDARD
FOR MODELS

METAL INDOOR NEMA 1
ENCLOSURE #68229

STANDARD
FOR MODELS

METAL INDOOR/OUTDOOR NEMA 3
MODEL #9006

STANDARD
FOR MODELS

METAL INDOOR NEMA 1
ENCLOSURE #63016-1

MECHANISM &
MOUNTING BRACKET #62153-1

MODELS

1101

7120

TZ220L-0

TZ300L-0

TZ220L

TW220L

Use Bracket #64039

1102

7122

TZ300L-0

T920L-0

TZ300L

TW300L

W100

W120
W220

3-5/8 "

W222

3-1/16"

1103

8001

W300

T920L

W200

1104

8004

W302

T930L

W202

1101FM

8061

W300L

TW222L

1104FM

8121

W302L

TW302L

7100

8301

#62158 "E" DOOR

7102

8601

T920L-E

7200

8602

TW220L-E

T930L-0

7202

TU40-Y

1101-7

EW201-Y

TRP400

7220

1847AZL LDS-A

7222

8007

7200L

8007L

7202L

8007V

7120L

8150

1847A

8150U

1848A

8007U

1849A

8007VL

1847AZ

8008

1847AL

8008L

STANDARD
FOR MODELS

2-1/2"

ELC72PC/120
ELC72PC/208-240

11-1/2"

12"

W302

DLC400BP

LDSH-A

STANDARD
FOR MODELS

DLC400BP

12-1/4"

T930L-E

MECHANISM
ONLY

MECHANISM
MECHANISM
WITH BRACKET WITH BRACKET
#62153-1
#64039

4"

1101NC DGLC100A-NC

1101-M-IAP

7200

1103NC DGLC200A-NC

1104-M-IAP

7202

1104NC

1102

7120

8001-NC

1103

7122

METAL INDOOR NEMA 1
ENCLOSURE #70100

DG SERIES

W200

W222L

E101PB

1103-N

W202

1847AW

E Series

W120

TU40

7-5/8"

1847AWL

DTU40

EW Series

11-7/8"

W220

DG Series DZS Series

TERMINAL BLOCK

MECHANISM ONLY
GROUND
4-9/16 "
SCREW

MECHANISM & BRACKET

CLEARANCE HOLE
FOR GROUND SCREW

4-9/16 "

MODELS
5441

6-5/8 "

5-1/16"
4-9/16 "

7-5/8"

BRACKET

4-9/16 "

MECHANISM ONLY
4-9/16 "

3-5/8 "

TERMINAL BLOCK

MECHANISM & BRACKET

EWZ101-MB
2-3/32 "

E, EWZ, EH
SERIES

EWZ103-MB

11-1/2"

BRACKET

SMC-3D

4-9/16MECHANISM
"
3-5/8
"
&
BRACKET

6-5/8 "

EWZ201-MB

6-5/8 "

MECHANISM & BRACKET
3-3/8"

MECHANISM
ONLY

EWZ120-MB
8-5/16"

3-1/16 "

2-1/2"

1-15/16 "

14-1/8"

12-3/4"

3-1/2"

TERMINAL BLOCK

MECHANISM & BRACKET
DG SERIES

WIRING COMPARTMENT
10-1/8"

WITH MOUNTING
BRACKET
#64039

STINGL

3/4" or 1" KO

7-5/8"

6-5/8 "

3-5/8 "

1/2" or 3/4" KO

3-1/16"

Note: Indoor Enclosure Only

11-1/2"

TERMINAL BLOCK

TERMINAL BLOCK

9000PC
3-1/16"

1-15/16 "

DZS, DTS,
DZM, DW,
DWZ
SERIES

3-1/4"

STANDARD
FOR MODELS

W400A

1101D

1101DF

W402A

1114D

1114DF

W400AL

1104D

1104DF

METAL DUPLEX INDOOR/OUTDOOR
NEMA 3 MODEL #9004L

4-9/16 "

4-9/16 "

6-5/8 "

EW103B-C EW120B-C

TERMINAL BLOCK

3-1/16 "

DZM, DW,
DWZ BRACKET
SERIES

6-5/8 "

TERMINAL BLOCK

1-15/16 "

MECHANISM & BRACKET
DZS, DTS,

MECHANISM ONLY

PLASTIC INDOOR/OUTDOOR
NEMA 3R WITH CLEAR WINDOW

MODELS

4-9/16 "

TERMINAL BLOCK

1-15/16 "

MECHANISM & BRACKET

8-5/16"

STANDARD FOR MODELS

SMC-3D

3-1/16 "

MECHANISM & BRACKET
E, EWZ,
3-3/8"

EH

SERIES

MECHANISM
ONLY

LC200M

MODELS

TERMINAL BLOCK

4-17/32 "

1102-M

1103-M

1104-M
SMC-3D
8001-LC/WB

DTWH40

8601

8121

8602

8061

5-1/2"

3.4000"

EJWT
E500T

MECHANISM & BRACKET
3-13/32 "

E501T

7 1/2” 7 1/ ”
2

1-13/16 "

9-3/8"

7-1/2"

PP-20RPP-20R
PP-20R-P1
PP-20R-P1
PP20R-P4
PP20R-P4
PP-20R-2P1
PP-20R-2P1
PP-20R-2P4
PP-20R-2P4

MECHANISMS/BRACKETS

5-37/64 "
3-1/16 "

STANDARD
FOR MODELS

STANDARD
FOR MODELS
1101-O

1104-O

7302, L, Z, ZL 8001U-0

1102-0

7200-O

1103-0

7202-O

8007-0

POOL PANEL SERIES

4"

MECHANISM
ONLY

METAL INDOOR/OUTDOOR NEMA 3
MODEL 9000B – SUFFIX "O"

LC200M MOUNTING
WITH BRACKET

MODELS

4-11/16"

MECHANISM
WITH BRACKET

LC200M

LC200M

MECHANISM & BRACKET
4-17/32 "

3-9/32 "

LDS
LDSH

MECHANISM & BRACKET
LC200M
3-13/32 "

LDS SERIES MOUNTING
WITH BRACKET

MODELS

3.4000"

MECHANISM & BRACKET

LDS

1-13/16 "

2-1/8 "

4-17/32 "

LDSH

3-9/32 "

3.4000"

LDS
LDSH

MECHANISM & BRACKET
3-13/32 "

13 3/8” 13 3/ ”
8

PP-100R
PP-100R
PP-100R-P4
PP-100R-P4
PP-100R-P1P4
PP-100R-P1P4
PP-100R-2P4
PP-100R-2P4
PP-100R-P4P4FM
PP-100R-P4P4FM

17 3/4” 17 3/ ”
4

SHOWN WITH
SNAP TRACK

3-3/8"

4 5/8” 4 5/ ”
8

4 1/4” 4 1/ ”
4

4"

7 1/2”

7300, L, Z, ZL 8001-0
8007U-0

4-11/16"

11”

3-3/4"

MECHANISM & BRACKET

8301
3-1/16"

11”

E502T

#64039/62153-1/65447

5-13/16 "

TERMINAL BLOCK

EWJT & E500T SERIES
ENCLOSURE

SR-500PS

3-1/2"

4-9/16"

1-15/16 "
7000 Series
1847A, Z

1848A

3-9/32 "

STINGL SVRS
ENCLOSURE

WITH MOUNTING
BRACKET
#62153-1

2-1/8 "

1101-M

MECHANISM & BRACKET

LDS
LDSH

MECHANISM & BRACKET

MECHANISM & MOUNTING
BRACKET #65446

6-5/8 "

4"

MODELS

SR-500

BRACKET

6-5/8 "

TERMINAL BLOCK

3-1/16 "

ADAPTER
MECHANISM & BRACKET
PLATE
4-9/16 "

MECHANISM ONLY

5-1/16"

NEMA 1 ENCLOSUREE, EWZ, EH
SERIES

METAL INDOOR/OUTDOOR
NEMA 3
MODEL 9000A – SUFFIX "0"

ELC712

1/2" or 3/4" KO
3/4" or 1" KO

2-3/32 "

6-5/8 "

ELC78

4-3/16"

8-3/4"

1/4"
MOUNTING
HOLE

W222

METAL INDOOR NEMA 1
ENCLOSURE FOR W400 SERIES

ELC78 & ELC712
ENCLOSURE

5401 ENCLOSURE

BRACKET

4-11/16"

DWZ Series

4"

12"

3-1/16 "

1-15/16 "

EWZ SERIES

MECHANISM ONLY

EWZ Series

DZM Series

STANDARD
FOR MODELS

TERMINAL BLOCK

9000P

1102-N

SMC-3D

EW Series

PLASTIC INDOOR/OUTDOOR
NEMA 3R #9000P

MODELS

7120Z, ZL

DW Series

E Series

7102

10"

5441 and 5440 REMOTE CONTACTORS

7202Z, ZL

DTS Series

7100

6-5/8 "

1104-N

18"

6-5/8 "

3-3/8"

W220L

BRACKET

3-5/8 "

4"

70100

W100

8001-N

4-9/16 "

12"

DWZ
SERIES

1101-N

8001U-N

MECHANISM & BRACKET

2-3/32 "

ELC74
ENCLOSURE

ELC74

9/32"
MOUNTING HOLES

TRP800

6-5/8 "

DZS, DTS,

7200Z, ZL

7122Z, ZL

4-9/16 "

4"

12"

TRP800

TRP 800 (GROUP OF 8)

9/32"
MOUNTING HOLES

IAP
BRACKET
MECHANISM ONLY
DG SERIES
INTERMATIC ADAPTER PLATE

EWZ SeriesDZM, DW,

STANDARD
FOR MODELS

10"

TRP800

NORYL® & LEXAN®
INDOOR/OUTDOOR
NEMA 3R MODEL #9000NC

14-1/4"

NORYL® INDOOR/OUTDOOR
NEMA 3R MODEL #9000N

ELC72PC/277
18"

STANDARD
FOR MODELS

DLC400BP

9/32"
MOUNTING HOLES

ELC71PC/277

EW130B-Y EW120B-Y

METAL INDOOR NEMA 1
ENCLOSURE #63100

ELC71 & ELC72 SERIES
ENCLOSURE

ELC71PC/120
ELC71PC/208-240

3-1/2"

TRP 400 (GROUP OF 4)

STANDARD
FOR MODELS

TRP 800 (GROUP OF 8)

9/32"
MOUNTING HOLES

TRP402

7-5/8"

Use Bracket #62153-1
W300

TRP400

TRP 400 (GROUP OF 4)

PP-20R
PP-20R-P1
PP20R-P4
PP-20R-2P1
PP-20R-2P4

7 1/2”

PP-20R
PP-20R-P1
PP20R-P4
PP-20R-2P1
PP-20R-2P4

1-13/16 "

11”

13 3/8”

13 3/8”

6 1/8” 6 1/ ”
8

12 3/4” 12 3/ ”
4

11”

PP-100R
PP-100R
PP-100R-P4
PP-100R-P4
PP-100R-P1P4 PP-100R-P1P4
PP-100R-2P4 PP-100R-2P4
PP-100R-P4P4FM
PP-100R-P4P4FM

PP-125R
PP-125R
PP-125R-P4
PP-125R-P4
PP-125R-2P4
PP-125R-2P4
PP-125R-P4-100X
PP-125R-P4-100X
PP-125R-P4-300X
PP-125R-P4-300X
17 3/ ”
17 3/ ”
4

4

PP-10R-M-GFCI
PP-10R-M-GFCI
PP-10R-E-GRCI
PP-10R-E-GRCI

20 3/4” 20 3/ ”
4

9 3/4” 9 3/ ”
4

2-1/8 "

DZS100BP-0 DZS200BP-0
DZS200BP DW200B-0
DZM200BP-0

5-13/16 "

5-37/64 "

5-13/16 "

5-37/64 "

5401

4 1/4”

SHOWN WITH
SNAP TRACK

4 5/8”

4 1/4”

4 5/8”

4 5/8” 4 5/ ”
8

4 1/2” 4 1/ ”
2

SHOWN WITH
SNAP TRACK
12 3/4”

12 3/4”

PP-125R

PP-125R

6 1/8”

6 1/8”

TORK 153
PP-10R-M-GFCI PP-10R-M-GFCI

TORK 154

ALPHANUMERIC INDEX

ALPHANUMERIC INDEX

1101 . . . . . . . . . . . . . . . . . . . . . . . . . 31, 144

2104 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

652A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

8001U-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C512HH  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZS100BP-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

1101-7 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

2107 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

654A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

8004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

C515M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZS200BP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

1101D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

2115 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

655D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 122

8007 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

C530M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZS200BP-12 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

1101FM-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

2116 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

701A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

8007L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C560M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZS200BP-24 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

1101FM-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

2117 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

701AA  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 101

8007-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C560MH .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZS200BP-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

1101-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

2223 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

711A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

8007U  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

D1060LA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 104

DZS400BP  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

1101-M-IAP  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31, 144

2224 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

7100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8007U-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

D1060M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 104

DZS400BP-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

1101-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

2421 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

7102 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8007V .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

D1060MW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 104

E101B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 57

1101-NC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

7120 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8007VL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

D212H .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 104

E101PB .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 57

1101-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

3002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

7120L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

8008 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

D212HA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 104

E103B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 57

1102 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

3006 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

7120Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

8008L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

D212HW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 104

E120B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 57

1102-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

3010 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

7120ZL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

8061 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

DG100A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 63

E201B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 57

1102-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

401A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

7122 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8121 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

DG100A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 63

E500T .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 87

1102-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

402A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

7122ZL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

8301 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

DG180A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 85

E501T .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 87

1103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

403A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

7200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8601 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

DG200A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 63

E502T .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 87

1103-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

405A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

7200L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

90058-1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94

DG280A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 85

EJWT .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 87

1103-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

422A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

7200-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

A502H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DG280A-24 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 85

ELC712 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 75

1103-NC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

454D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 120

7200Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A502HHW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGLC100A-NC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79

ELC71PC/120 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 73

1103-O  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

455D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 120

7200ZL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A502HW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGLC200A-NC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79

ELC71PC/208-240 . . . . . . . . . . . . . . . . . . . 73

1104 . . . . . . . . . . . . . . . . . . . . . . . . . 31, 144

457Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 120

7202 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

A506H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGM100A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 63

ELC71PC/277 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 73

1104D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

460D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 120

7202L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

A506HHW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGM100A-Y  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 63

ELC72PC/120 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 73

1104DF .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

5001M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

7202-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

A506HW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGS100A  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 85

ELC72PC/208-240 . . . . . . . . . . . . . . . . . . . 73

1104FM-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

5004M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

7202Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A512H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGS100A-12 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 85

ELC72PC/277 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 73

1104FM-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

5007M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

7202ZL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A512HH .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGS100A-24 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 85

ELC74 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 75

1104-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

5008M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

7220 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

A512HHW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGU100A-Y .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79

ELC78 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 75

1104-M-IAP  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31, 144

5021M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

7220L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

A512HW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGUM100A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79

ELS-1  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 115

1104-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 144

5024M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

7222 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

A515M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DGUM100A-Y .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79

EPC1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 77

1104-NC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

5026M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

7222L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

A515MA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DIN100B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 89

EPC2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 81

1104-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31, 144

5231 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

A515MH .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DIN200B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 89

EPC-A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79

1847A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

5237 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7300L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

A515MHW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DLC400BP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 81

EPC-LC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 73, 75

1847AL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 41

5401 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

7300Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A515MW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DS12X12H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 151

1847AW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 41

5403 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

7300ZL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A530M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DS12X12P .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 151

EW101B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59
EW103B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

1847AWL  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 41

5404 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

7302 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

A530MA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DS360M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 151

EW103B-C .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

1847AZ .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 41

5404-3 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 22

7302L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33

A530MH .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DS-AA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

EW103B-Y .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

1847AZL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 41

5420 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

7302Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A530MHW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DS-MR .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

EW120B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

1848A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

5441 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

7302ZL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35

A530MW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DTS100B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 67

EW120B-C .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

5500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

73866 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

A560M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DTS200B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 67

EW120B-Y .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

2000-2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 15

803B  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 123

A560MH .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DTS400B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 67

EW201B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

2000-7 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 15

5500-OC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 24
5737TM  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 23

806B  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 123

A560MHW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DTU40  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 55

EW201B-Y .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 59

2001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

5737TZ .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 23

806D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 123

A560MW .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 105

DTWH40 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 55

EWZ101 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

601A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

8001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

AV20X20  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 151

DW200B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 145

EWZ101-MB  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

2005A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

602A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

8001-LC/WB .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

AV26X26 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 151

DW200B-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 145

EWZ103 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

2007A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

611A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

8001-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C412H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DTWH40 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 55

EWZ103-MB  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

2008A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

611D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 122

8001-NC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C460M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DWZ100B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 69

EWZ120 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

2021 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

621D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 122

8001-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C502H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZM200BP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 71

EWZ120-MB  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

2022 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

631D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 122

8001U  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C506H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZM200BP-O  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 71

EWZ201 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

2101 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

640-475XV .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 151

8001U-N .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 37

C512H  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 106

DZS100BP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

EWZ201-MB  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 61

TORK 155

TORK 156

ALPHANUMERIC INDEX

ALPHANUMERIC INDEX

HPS30 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 93

PFP2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

T920L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 45

TA503 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA93-2RN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TCHD1ARP-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

LC200 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 77

PFP2-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

T920L-E  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 45

TA503SW . . . . . . . . . . . . . . . . . . . . . . . . . 138

TA94AN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TCHD2L2-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

LC200M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 77

PFP3 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

T920L-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 45

TA52AN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TA94BN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TCHD2RP-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

LCS115M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 75, 112

PFP3-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

T930L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 45

TA52BN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TA94RN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TRP-1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94

LDS  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 83

PFPEW1102  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

T930L-E  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 45

TA52RN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TA-ADA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TRP-2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94

LDS-A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 83

PFPEW1102-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

T930L-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 45

TA53AE1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 136

TA-ADB .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TRP400 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94

LDSH .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 83

PFPEW1103  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

TA09 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA53AF1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 136

TA-ADR .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TRP402 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94

LDSH-A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 83

PFPEW1103-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

TA1245Y-50  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TA53AG .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 136

TA-B1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TRP800 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94

MLS2RPAKA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PFPT .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

TA1245Y-75  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TA53RE1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 136

TA-B2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TRP802 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 94

MLSPACER .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PP-100R .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA131DAN5 . . . . . . . . . . . . . . . . . . . . . . . 136

TA54AE1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 136

TA-B3 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TRP-U .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 79, 112, 116

MLTPRP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PP-100R-2P4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA131DAU . . . . . . . . . . . . . . . . . . . . . . . . 136

TA54RE1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 136

TA-B-8332 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TU40 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 29

MLTPS2BGA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PP-100R-F2F4FM .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

TA131DRN5 . . . . . . . . . . . . . . . . . . . . . . . 136

TA5508H-G1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 127

TA-BBSF  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TU40-Y .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 29

MLVPRP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PP-100R-P4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA131DRU1 . . . . . . . . . . . . . . . . . . . . . . . 136

TA590 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TA-B-KHD-1000-PP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 131

TW-220L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 47

MLVPS2BGA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PP-100R-P4P1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA152 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA591 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TA-B-KHD-120VAC  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 131

TW-220L-E  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 47

OSC10U  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 114

PP-100R-P4P4FM  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA154 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA592 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TA-B-KHS-1000-PP  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 131

TW-222L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 47

OSC12PL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 112

PP-10R-E-GFCI .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1786B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA598 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TAC210W  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 129

TW-300L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 47

OSC15PLS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 111

PP-10R-M-GFCI .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1786CB .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA599 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TAC212WL  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 129

TW-302L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 47

OSC20U  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 114

PP-125-2P4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1880 B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA60 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TAC212WS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 129

TZ-220L  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 49

OSC5PL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 112

PP-125R .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1880 G .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA600 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-D5B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TZ220L-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 49

OSC5U  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 114

PP-125R-P4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1882 B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA601 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-D6A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TZ-222L  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 49

OSCS20UP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 113

PP-125R-P4-100X .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1882 G .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA602 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-D6C .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TZ-300L  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 49

OSWS9P-120 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 110

PP-125R-P4-300X .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1886 B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA603L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-D6R .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TZ-300L-O .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 49

OSWS9P-277 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 110

PP-20R .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1886 G .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA606 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TA-D7A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TZ-302L  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 49

OSWS9PD .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 110

PP-20R-2P1  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1887 B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA61 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA-D7B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

USB-MMP .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 65

OSWS9PDM .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 110

PP-20R-2P4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA1887 BK .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA62 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA-D7C .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W100 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

P1101-2M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

PP-20R-F2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

TA1887 G .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 132

TA620 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-D7R .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W120 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

P1101FM-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

PP-20R-P1  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA215LB .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA620B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-D8A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W200 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

P1101-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

PP-20R-P4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 141

TA236 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA620L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-D8R .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W202 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

P1104-2M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SMC3D .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 91

TA270A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 130

TA620LB .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-L10  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W220 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

P1104FM-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SR-500 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 149

TA315-1N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 130

TA631L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-L10-1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W220L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

P1104FM-M 240VAC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

SR-500PS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 149

TA340-10G5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA635 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-L12  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

P1104-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SR-ESB  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

TA340-4G5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA640 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 137

TA-L3  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W222 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43
W222L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PB-100 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

SR-RA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

TA340-4N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA656B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-L4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W300 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PB-50 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

SS13B .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 103

TA340-6G5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA666BK .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 134

TA-L6-2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W300L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PB-75 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

SS13F .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 103

TA340-6N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA725 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 129

TA-L8  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W300-O  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PEW101-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

SS20 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 103

TA371LRN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TA740 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 129

TA-L9  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W302 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PEW104-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

SS20F .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 103

TA434-10N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA744 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 129

TA-M1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W302L .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PF1101FM-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

TA434-6N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA874-N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 127

TA-MTS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

W400A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PF1101-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SS700Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 99
SS700ZA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 99

TA44 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA874-N5R .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 127

TA-SFPF .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W400AL .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PF1104FM-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SS720A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 98

TA45 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA875-1G1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 128

TA-SFPFR .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

W402A .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

PF1104-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SS720AA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 98

TA46 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA875-G1 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 127

TA-WBBF .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

PFEW101-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

SS721Z .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 99

TA47AN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TA876-N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 127

TCA1-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PFEW104-M  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 148

SS721ZA .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 99

TA47AR5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TA879 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 136

TCA1RP-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PFP1102 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

SSA100 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 102

TA47RN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TA880-N5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 127

TCA3-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PFP1102-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SSA100R-24 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 102

TA502 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 133

TA93-2AN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TCA3RP-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PFP1103 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 143

SSA200 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 102

TA502-BX .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 138

TA93-2BN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TCAMA2RND .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

PFP1103-M .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 147

SSA200R-24 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 102

TA502SW . . . . . . . . . . . . . . . . . . . . . . . . . 138

TA93-2CN5 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 135

TCHD1AL2-MK2 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 152

TORK 157

TORK 158

NOTES

TERMS OF SALE

TORK VENDOR NUMBER: 662381
1. Prices are F.O.B. our plant.
2. Prices do not include any sales tax.
3. Freight charges will be prepaid on all orders $100.00
and over shipping ­within continental USA using standard
shipping methods and service.
4. Minimum order – $100.00.
5. Claims for shortage, erroneous charges or price corrections
shall be deemed waived unless made in writing, delivered
to NSi within 30 days of invoice.
6. Terms of payment – 2% 10th prox. net 25th following.
7. Warranties – We strive to produce the highest quality
products on the market today. NSi guarantees all products
to be free of defects in material and workmanship for
a period of 90 days from date of sale. Any claims for
defective material must be agreed to in writing by NSi.
Defective material will be replaced on an F.O.B., our
factory basis. NSi disclaims the implied warranty of fitness
for a particular application.

OTHER PRODUCTS AVAILABLE

ADDRESS
9730 Northcross Center Court
Huntersville, North Carolina
28078 USA
PHONE
office 800.321.5847
technical support 888.500.4598
FAX
800.841.5566

EMAIL
nsi@nsiindustries.com

WEB
www.nsiindustries.com

NSi can provide many other products for special applications
which are not ­listed in this catalog. If you require an item which
you do not find listed, please contact us. We would be pleased
to provide a quotation upon receipt of a ­drawing or a sample.

GUARANTEE

It is our goal to provide extraordinary
products and services on a daily basis. If our
products or service do not meet with your
satisfaction, please let us know ­immediately
and we promise to make every reasonable
effort to remedy the ­situation.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : No
Page Count                      : 80
Create Date                     : 2017:08:23 05:39:18
Creator                         : PDFium
Producer                        : PDFium
EXIF Metadata provided by EXIF.tools

Navigation menu