D914572 D 3000 WATT VLT12

User Manual: 3000 WATT

Open the PDF directly: View PDF PDF.
Page Count: 18

DownloadD914572-D 3000 WATT VLT12-3000
Open PDF In BrowserView PDF
VANNER Incorporated

Owner’s Manual

VLT Series
2000/3000 Watt
True Sine Wave Inverter

PURE SINE WAVE
INVERTER
ON

I

OFF

0
REMO.

INPUT
LEVEL
LOAD
LEVEL
STATUS
FREQ.
PWR.
SAV.

S4
S3
S2
S1

O

I

AC OUTPUT

Models
VLT12-2000
VLT12-2000-LV
VLT12-3000
VLT12-3000-LV

VLT Series

2000/3000 Watt True Sine Wave Inverter

VLT24-2000
VLT24-2000-LV
VLT24-3000
VLT24-3000-LV

Owner's Manual

Page 1

VANNER Incorporated

Owner’s Manual

Table of Contents
1 Introduction ............................................................................................................................................................. 3
2 Important Safety Instructions .................................................................................................................................. 3
2.1 General Safety Precautions .......................................................................................................................... 3
2.2 Precautions When Working With Batteries ................................................................................................... 4
3 Specifications and Features .................................................................................................................................... 5
3.1 Specifications ................................................................................................................................................ 5
3.2 Measurements .............................................................................................................................................. 6
4 Front Panel Area: .................................................................................................................................................... 7
4.1 ON / OFF/ REMOTE (Main) Rocker Switch: ................................................................................................ 7
4.2 DC Input Voltage Display .............................................................................................................................. 8
4.3 AC Load Display (Watts) .............................................................................................................................. 8
4.4 AC Output Wiring Methods: .......................................................................................................................... 8
4.5 AC Output GFCI Duplex Receptacle ............................................................................................................ 8
4.6 AC Frequency Selection ............................................................................................................................... 9
4.7 AC Voltage Selection .................................................................................................................................... 9
4.8 Load Demand (Power Saving Mode)............................................................................................................ 9
5 Protection Features and Set Points: ..................................................................................................................... 10
6 Rear Panel Area: ................................................................................................................................................... 11
6.1 Remote Port ................................................................................................................................................ 11
6.2 Remote Control Connector ......................................................................................................................... 11
6.3 Cooling Fans and Ventilation ...................................................................................................................... 12
6.4 DC Input Terminals ..................................................................................................................................... 12
6.5 Chassis Ground Lug ................................................................................................................................... 12
7 Installation ............................................................................................................................................................. 13
7.1 Inverter Installation Considerations ............................................................................................................ 13
7.2 DC Wiring Considerations .......................................................................................................................... 13
7.3 DC Wire and Fuse Sizes: ........................................................................................................................... 14
7.4 DC WIRING DRAWING .............................................................................................................................. 15
8 AC Wiring Considerations ..................................................................................................................................... 16
8.1 AC Neutral Bonding .................................................................................................................................... 16
8.2 GFCI Receptacles....................................................................................................................................... 16
9 Troubleshooting .................................................................................................................................................... 16
9.1 Status: Display Power & Fault Status ......................................................................................................... 17
10 Maintenance ........................................................................................................................................................ 18

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 2

VANNER Incorporated

Owner’s Manual

1 Introduction
Thank you for purchasing a Vanner VLT SERIES Inverter. We are confident that you will be satisfied with the
inverter’s performance and its many features. With proper installation and care, you can look forward to years of
service from this high performance product.
This document will describe the operation, technical specifications and installation procedures.

2 Important Safety Instructions
Electrocution hazard exists

Fire hazard exists

A potentially dangerous condition

Explosive hazard exists

Corrosive hazard exists

To get the most out of the power inverter, it must be installed and used properly.
instructions in this manual before installation. Keep this manual for future reference.

Please read the

2.1 General Safety Precautions
Do not expose the inverter to rain, snow, spray, or dust. To reduce risk of hazard, do not obstruct the
ventilation openings. Do not install the inverter in a zero-clearance compartment. Overheating may result.

To avoid a risk of fire and electric shock, make sure the wiring is in good electrical condition and is
proper gauge. Do not operate the inverter with damaged or substandard wiring.

This equipment contains components that can produce arc or sparks. To prevent fire or explosion,
do not install in compartments containing batteries or flammable materials or in locations which require ignition
protected equipment This includes any space containing gasoline-powered machinery, fuel tanks, or joints,
fittings, or other connection between components of the fuel system

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 3

VANNER Incorporated

Owner’s Manual

2.2 Precautions When Working With Batteries
If battery acid contacts skin or clothing, wash immediately with soap and water.
If acid enters eye,
immediately flood eye with running cold water for at least 20 minutes and get medical attention immediately.

Never smoke or allow a spark or flame in vicinity of battery or Engine.

Do not drop a metal tool onto the battery. The resulting spark or short-circuit on the battery or other
electrical part may cause an explosion.

Remove personal metal items such as rings, necklaces, and watches when working with a lead-acid
battery. A lead-acid battery can produces a short-circuit current high enough to weld a ring or the like to metal,
causing severe burns.
1

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 4

VANNER Incorporated

Owner’s Manual

3 Specifications and Features
3.1 Specifications
Specifications
Item

Model Number
VLT12-2000

VLT12-2000-LV

VLT24-2000

VLT24-2000-LV

VLT12-3000 VLT12-3000-LV

VLT24-3000

Continuous Output Power

2000W

3000W

Maximum Output Power
(3Min.)

2000W

3000W

Surge Rating

4000W

6000W

Nominal Input voltage

12V

24V

12V

VLT24-3000-LV

24V

120VAC (factory setting) +/- 5%
Output Voltage

100/110/115 selectable via internal front panel dip switches

Output Frequency

60Hz (factory setting) +/- 0.05%
50Hz selectable via front panel dip switch

Output Waveform

True Sine Wave ( THD < 3% )

Efficiency (full load) MAX

89.0%

92.0%

88.0%

91.0%

No Load Current Draw

2.8A

1.5A

3.0A

1.6A

Stand-By Current Draw

0.60A

0.30A

0.55A

0.35A

Input Voltage Range (VDC)

11.5-16

10.5-15.0

23-32

21.0-30.0

11.5-16

10.5-15.0

23-32

Input Level Indicator

Red / Orange / Green LED

Load Level Indicator

Red / Orange / Green LED

Failure Indicator

Red LED

Protection

Overload, Short Circuit, Reverse Polarity (Fuse), Over / Under Input Voltage, Over temperature.

Safety Certification

Meets UL458

EMC

FCC Class A

Operating Temperature
Range

-25°F to 104°F ( -31°C to 40°C)

Storage Temperature Range

-30°F to 160°F ( -34°C to 70°C)

Cooling

Thermostatically controlled cooling fan

Dimensions

17.8 L x 8.2 W x 6.5 H

Weight

22 lbs

21.0-30.0

Note: Specifications are subject to change without notice.

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 5

VANNER Incorporated

Owner’s Manual

3.2 Measurements

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 6

VANNER Incorporated

Owner’s Manual

4 Front Panel Area:

PURE SINE WAVE
INVERTER
ON

I

OFF

0
REMO.

INPUT
LEVEL
LOAD
LEVEL
STATUS
FREQ.
PWR.
SAV.

S4
S3
S2
S1

O

I

AC OUTPUT

4.1 ON / OFF/ REMOTE (Main) Rocker Switch:
Before installing the inverter, be sure the main rocker switch is set to “OFF”.
Use the ON/OFF/REMOTE main rocker switch on the front panel to turn the inverter ON.
Set the rocker switch to the ON position to turn the inverter ON. Notice the beeps and the activity of the indicator
light display. The Status led should be green indicating the inverter is ready to deliver AC power to the loads. If
multiple AC loads will be operated at the same time it may be necessary to turn the loads ON one-at-a-time to
prevent inverter overload due to the initial surge required to start the loads.
Set the rocker switch to the OFF position to turn the inverter OFF.
Set the rocker switch to the REMOTE position if a customer-supplied remote control switch is used with the
Remote Control Connector, located on the inverter back panel. (See section 3-8-2.)

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 7

VANNER Incorporated

Owner’s Manual

4.2 DC Input Voltage Display
MODEL

VLT12-2000

VLT12-2000-LV

VLT24-2000

VLT24-2000-LV

VLT12-3000

VLT12-3000-LV

VLT24-3000

VLT24-3000-LV

LED Status

DC 12V

DC 24V

RED Slow Blink

11.3~11.7

10.3~10.6

22.5~23.2

20.5~21.2

RED

11.7~12

10.6~11.0

23.2~24

21.2~21.8

ORANGE

12~13.1

11.0~12.1

24~26.2

21.8~24.1

GREEN

13.1~15.2

12.1~14.2

26.2~30.5

24.1~28.6

ORANGE Blink

15.2~16

14.2~15.0

30.5~32

28.6~30.0

OVER RED Blink

Above
16

Above 15.0

Above
32

Above 30.0

4.3 AC Load Display (Watts)
Unit
Power

DARK

GREEN

ORANGE

RED

RED BLINK

2000W

0 ~ 160W

160 ~ 660W

660 ~ 1500W

1500 ~ 1920W

Over 2000W

3000W

0 ~ 240W

240 ~ 990W

990 ~ 2250W

2250 ~ 2880W

Over 3000W

4.4 AC Output Wiring Methods:
Three AC output wiring methods are provided.
• GFCI Protected Receptacle
• GFCI Protected Hardwired Output ( LOAD terminals on GFCI Receptacle )
• Non-GFCI Hardwired output via terminal strip inside receptacle compartment.

4.5 AC Output GFCI Duplex Receptacle
The AC output neutral conductor is connected to AC ground and inverter chassis ground inside the inverter. This
conforms to National Electrical Code requirements that separately derived AC sources (such as inverter and
generators) have their neutral conductors tied to ground in the same way that the neutral conductor from the utility
is tied to ground at the AC breaker panel.

Do not connect AC neutral to AC ground downstream of the GFCI. This would cause the GFCI to trip.

Never connect the inverter output to another AC power source such as a generator or utility power. The
inverter would be destroyed.
VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 8

VANNER Incorporated

Owner’s Manual

4.6 AC Frequency Selection
AC output frequency is selected by Dip Switch “S4”.

Important Note: 60Hz AC loads may be damaged if 50Hz is selected.
The unit must be turned OFF/ON to accept new dip switch settings.
Frequency

S4

50 HZ

OFF (left)

60 HZ

ON (right)

4.7 AC Voltage Selection
Only qualified persons should change the AC output voltage setting. The AC output voltage is selected by a twoposition dip switch located inside the inverter behind the ON/OFF/Remote switch. To access the internal 2position dip switch, remove the top cover by removing the front four and rear four screws.
The unit must be turned OFF/ON to accept new dip switch settings.
Display Panel internal 2-position DIP Switch Setting
AC Output Voltage
Switch 1
Switch 2
120 VAC
ON (up)
ON (up)
115 VAC

ON (up)

OFF (down)

110 VAC

OFF (down)

ON (up)

100 VAC

OFF (down)

OFF (down)

4.8 Load Demand (Power Saving Mode)
The Load Demand feature allows the inverter to "go to sleep" if the inverter is ON but no AC loads are present.
Load Demand is adjustable via Dip Switches S1, S2 and S3 on the front panel.
Example: With the Load Demand Threshold watt setting at 45W, a load greater than 45W is required to "keep the
inverter awake" to produce AC power. If the AC load falls below 45W the inverter will "go to sleep", entering Load
Demand power saving mode.
The unit must be turned OFF/ON to accept new dip switch settings.
Load Demand
S1
S2
Threshold Watts

S3

Load Demand OFF

OFF

OFF

OFF

45W

ON

OFF

OFF

85W

OFF

ON

OFF

130W

ON

ON

OFF

175W

OFF

OFF

ON

220W

ON

OFF

ON

265W

OFF

ON

ON

300W

ON

ON

ON

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 9

VANNER Incorporated

Owner’s Manual

5 Protection Features and Set Points:
DC Input (VDC)
Model

Over Voltage

Under
Voltage

ShutRestart
down

Over Temperature Protection
Under Voltage

Shut-

ShutRestart

Alarm

down

16.5

15.5

12

11.2

13.5

12 V (LV)

15.3

14.3

11.0

10.2

12.7

24V

33.0

23.0

24

22.4

27.0

24 V (LV)

30.6

28.8

22.0

20.3

25.2

2000/3000 Watt True Sine Wave Inverter

HEAT SINK
Shut-

Restart
down

12V

VLT Series

INTERIOR

70°

Restart
down

45°

Owner's Manual

90°

60°

Page 10

VANNER Incorporated

Owner’s Manual

6 Rear Panel Area:

DC INPUT

POS(+)
REMOTE
PORT

NEG(-)
WARNING:
ENB

ENB

GND

REVERSE
POLARITY
WILL DAMAGE
UNIT.

CHASSIS
GROUND

6.1 Remote Port
The modular jack labeled Remote Port is not used.

6.2 Remote Control Connector
(The Remote Control Connector is enabled when the ON/OFF/Remote main rocker switch, located on the front of
the inverter, is in the Remote position.) This three-position connector, Phoenix part number 1911868, is labeled
GND, ENBBAR, and ENB. Use this connector with a customer supplied SPST switch to provide remote ON/OFF
control of the inverter. Remote switch circuit arrangement options are +12v to ENB, or Battery Negative to
ENBBAR, or GND to ENBBAR. The most common application (+12v to ENB) uses a +12v hot-in-run from vehicle
fuse panel to turn inverter ON when vehicle is ON, and OFF when vehicle is OFF.

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 11

VANNER Incorporated

Owner’s Manual

6.3 Cooling Fans and Ventilation
Maintain at least 3" clearance all around the inverter at all times.

6.4 DC Input Terminals
Connect DC cables, battery positive (+) to inverter positive (red); battery negative (-) to inverter negative (black).
Be aware, there will be a large spark when the last DC connection is made. Be very careful to NEVER connect
DC terminals to the inverter backwards (inverter positive to battery negative). Reverse polarity connection
may cause permanent damage to the inverter.

6.5 Chassis Ground Lug
Use a # 8 AWG or larger wire to connect inverter chassis ground lug to vehicle chassis.

WARNING!
Operating the inverter without a proper ground
connection may cause an electrical hazard.

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 12

VANNER Incorporated

Owner’s Manual

7 Installation
7.1 Inverter Installation Considerations
Install the inverter in an environment that meets the following requirements:
Mounting: Locate a flat secure, dry, horizontal surface large enough to mount the inverter.
Dry – Do not allow water to drip on or to get inside the inverter.
Cool – Ambient air temperature should be between 32°F and 105°F, the cooler the better.
Safe – Do not install the inverter in a battery compartment or other areas where flammable fumes may exist, such
as fuel storage areas.
Ventilated –Maintain at least 3" clearance all around inverter.
not obstructed.

Be sure ventilation openings on front and back are

Dust free– Do not install the Inverter in dusty environments. Dust will be drawn inside and will greatly shorten the
life of the inverter.
Close to batteries but not exposed to battery fumes – Use the recommended wire lengths and sizes (see section
3-5). Avoid excessive cable lengths. Do not install the Inverter in a non-vented compartment with the batteries.
Do not mount the Inverter where it will be exposed to the gases produced by the batteries. Battery gases are very
corrosive. Prolonged exposure will damage the Inverter.

WARNING!

Shock Hazard.

Before proceeding further, verify that the Inverter is NOT
connected to batteries, and that all wiring is disconnected from any
electrical sources.
NEVER connect the inverter AC output terminals to an incoming
AC source.

7.2 DC Wiring Considerations
•

•

Do not connect the 12V model to a 24V battery. The unit will be destroyed immediately. Operation of
the inverter without a proper ground connection may result an electrical safety hazard. Damage caused by
reversed polarity will void warranty.

WARNING! Loose DC connections will overheat and could cause a fire.
Torque the DC terminal bolts to 9 -12 ft-lbs.

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 13

VANNER Incorporated

Owner’s Manual

A DC FUSE IS REQUIRED to protect the DC cables in case of a short circuit. The wiring of the inverter
installation should conform to the National Electric Code (NEC) and any other state or local codes in effect at
the time of installation. Article 551 of the NEC requires any DC cable from a battery, which measures longer
than 18 inches along its length, be protected by a fuse.

Failure to place a fuse in the inverter

positive cable will void warranty.
•

BE AWARE, as a large number of capacitors become charged upon completion of the DC circuit,
THERE WILL BE A LARGE SPARK when the last battery connection is made. The spark is normal and will
occur every time the batteries are connected. It is advisable to make the last DC connection at the inverter,
not at the battery, to reduce the risk of battery explosion.

•

To minimize electromagnetic radiation that could interfere with sensitive electronics, route the AC output
wiring and DC power wiring with as much physical separation as possible from low voltage wiring such as
audio and video signal wires. Route the DC positive and negative cables as close together as possible and
use cable ties to keep them together.

•

If passing through steel or other ferrous metal walls, the DC input cables need to pass through the same hole
to prevent causing a transformer effect. If two holes are required, cut a slot to connect the two holes to
prevent heating of the ferrous metal.

•

Proper DC cable size is critical for the performance and safe operation of the inverter system. The
DC Cable and Fuse Sizing Chart shows the minimum cable sizes recommended. These sizes allow a ½ volt
maximum voltage drop at maximum inverter capacity and will insure optimum inverter performance. DC cable
to be used with these fuse sizes should be minimum insulation temperature rating of 105°C and voltage
rating of 600V.

•

DC cables should be as short as possible.

•

Do not use the vehicle chassis as the DC negative conductor. The negative cable should be the same size as
the DC positive cable and should be connected directly to the battery negative terminal.

7.3 DC Wire and Fuse Sizes:
Use the following DC cable and inline fuse sizes. DC cables should be as short as possible (ideally less than 10
feet, never exceeding 20') and large enough to handle the required current in accordance with the electrical codes
or regulations applicable to the installation. DC cables that are too small or too long will cause DC voltage drop
which will result in deteriorated inverter performance such as poor surge capability and frequent low-input voltage
warnings and shutdowns.
Model Number

VLT12-2000
VLT12-2000-LV

VLT24-2000
VLT24-2000-LV

VLT12-3000
VLT12-3000-LV

VLT24-3000
VLT24-3000-LV

Distance from battery to inverter in feet
(Length of cable needed is 2 times the distance.)

Cable Size
1/0
2/0
3/0
4/0
250MCM

10
13
16
21
24

20
26
33
42
49

6
8
11
14
16

13
17
22
28
32

Fuse (Bussmann)
Vanner part number

AMG250
013916

AMG175
013913

AMG300
013917

AMG175
013913

Fuse Holder

VLT Series

Vanner part number 012992 (Bussmann AMG Series)

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 14

VANNER Incorporated

Owner’s Manual

7.4 DC WIRING DRAWING
Battery to inverter cable connection

DC INPUT

POS(+)
NEG(-)

WARNING:

REMOTE
PORT

REVERSE POLARITY
WILL DAMAGE UNIT
SHOCK HAZARD.
DO NOT OPEN. NO
USER SERVICEABLE
PARTS INSIDE.

CHASSIS
GROUND

INLINE FUSE

SPRING WASHER

PVC WIRE

Do not place anything between
battery cable lug and terminal surface.
Assemble exactly as shown.

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 15

VANNER Incorporated

Owner’s Manual

8 AC Wiring Considerations
8.1 AC Neutral Bonding
The neutral conductor of the inverter AC output circuit is connected to ground (the bare wire) inside the inverter.
This conforms to National Electrical Code requirements that separately derived AC sources (such as inverters
and generators) must have their neutral conductors tied to ground. The AC output ground wire should go to the
grounding point for the AC loads; for example, if there is a distribution panel ground bus. Do not connect neutral
to ground in any panel, receptacle or device downstream of a GFCI as this would cause the GFCI to trip.

8.2 GFCI Receptacles
While the pure sine wave output of the Inverter is equivalent to the waveform provided by utilities, it is possible
that some GFCI's may not perform properly on inverter power. If additional GFCI receptacles are needed use
Hubbell GFR5252WA or Pass & Seymour 2091 or 2094.

9 Troubleshooting
WARNING! Do not open or disassemble the Inverter. Attempting to service the unit
yourself may result in a risk of electrical shock or fire, and will void warranty.

Problems and
Symptoms

Possible Cause

Solutions

No AC Output Power
STATUS LED is RED
a. Blinking fast

Shutdown for
High Input
Voltage.

Reduce input voltage.

b. Blinking slowly.

Shutdown for
Low Input
Voltage.

Recharge battery.
Check DC connections.
Verify correct cable size.

c. Blinking Intermittently.

Shutdown for
Over
Temperature.

Improve ventilation.
Make sure vent openings
are not obstructed.
Reduce ambient
temperature.

d. Solid ON.

Shutdown for
overload, short
circuit or wiring
error.

Reduce AC load. Check
AC wiring for short circuit.

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 16

VANNER Incorporated

Owner’s Manual

9.1 Status: Display Power & Fault Status
Green LED

LED Signal

Solid

Power OK

Slow Blink

Power Saving

Red LED

LED Signal

Status

Fast Blink

Overvoltage Shutdown

Slow Blink

Undervoltage Shutdown

Intermittent Blink

33

33

Solid

VLT Series

Status

2000/3000 Watt True Sine Wave Inverter

33

Overtemp Shutdown
Overload Shutdown

Owner's Manual

Page 17

VANNER Incorporated

Owner’s Manual

10 Maintenance
Very little maintenance is required to keep the inverter operating properly. Clean the exterior periodically
with a damp cloth to prevent accumulation of dust and dirt. Verify DC connections are all clean and tight.

Vanner Inc
4282 Reynolds Drive
Hilliard, OH 43026
800-227-6937
800-ACPOWER
email: info@vanner.com
www.vanner.com
D914572-D

VLT Series

2000/3000 Watt True Sine Wave Inverter

Owner's Manual

Page 18



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 18
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : 278c9632-d26f-11e5-0000-af78633ee321
Producer                        : Nitro PDF PrimoPDF
Modify Date                     : 2016:02:10 11:30:55+05:00
Create Date                     : 2016:02:10 11:30:55+05:00
Creator Tool                    : PrimoPDF http://www.primopdf.com
Document ID                     : 278c9632-d26f-11e5-0000-af78633ee321
Format                          : application/pdf
Title                           : Microsoft Word - D914572-D.doc
Creator                         : mikeo
Author                          : mikeo
EXIF Metadata provided by EXIF.tools

Navigation menu