MULTIPLE-ENTRY POWER CONNECTION WITH JUNCTION BOX
SUBMITTAL SHEET WSC-0705
WARMUP INC.
USA: us@warmup.com
Tel.: 1-888-927-6333
www.warmup.com
CANADA: ca@warmup.com
Tel.: 1-888-592-7687
www.warmup.ca
DESCRIPTION
As standard, robust and corrosion resistant polyamide enclosures are
supplied for use in safe (non-hazardous) or hazardous (Class1,Div.2) areas.
When used in hazardous areas, the enclosures provide type EExe
protection (increased safety) in “Electrical Apparatus for Potentially
Explosive Atmospheres”.
SPECIFICATION
OPERATING TEMPERATURES -40°F to +212°F / -40°C to +50°C
EARTH CONTINUITY PLATE Available as extra
APPROX VOLUME 635cm3
MATERIAL Glass reinforced Polyester, Fire Retardant
DIMENSIONS
The enclosure has a uniquely designed hinged cover that allows the unit
to remain ‘as one’ during installation.
SPECIAL FEATURE
147mm
76.5 mm external
The w
orld’s best-selling electric floor heating brand
WARMUP INC.
USA: us@warmup.com
Tel.: 1-888-927-6333
www.warmup.com
CANADA: ca@warmup.com
Tel.: 1-888-592-7687
www.warmup.ca
The world’s best-selling electric floor heating brand
MULTIPLE-ENTRY POWER CONNECTION WITH JUNCTION BOX
SUBMITTAL SHEET WSC-0705
INSTALLATION INSTRUCTIONS
The w
orld’s best-selling electric floor heating brand
WARMUP INC.
USA: us@warmup.com
Tel.: 1-888-927-6333
www.warmup.com
CANADA: ca@warmup.com
Tel.: 1-888-592-7687
www.warmup.ca
The world’s best-selling electric floor heating brand
MULTIPLE-ENTRY POWER CONNECTION WITH JUNCTION BOX
SUBMITTAL SHEET WSC-0705
MULTIPLE-ENTRY POWER CONNECTION WITH JUNCTION BOX
SUBMITTAL SHEET WSC-0705
14.For heating cables with an outer jacket, slide parts in place
as shown below.
Figure 14-1
Figure 14-2
15.power wire:Cut inner jacket of cable back 3.9”(100mmm)
CutConductor wire 0.5”(12mm)
Figure 15
Figure 16-1
Figure 16-2
Figure 16-3
16.Connect the power conductors to the cable leads.
Connect the incoming supply ground to the cable braid and
to the green ground wire. The wire nuts, included, are not for
use with aluminum feed wires. The junction box needs to be
grounded.
The w
orld’s best-selling electric floor heating brand
WARMUP INC.
USA: us@warmup.com
Tel.: 1-888-927-6333
www.warmup.com
CANADA: ca@warmup.com
Tel.: 1-888-592-7687
www.warmup.ca
The world’s best-selling electric floor heating brand
MULTIPLE-ENTRY POWER CONNECTION WITH JUNCTION BOX
SUBMITTAL SHEET WSC-0705
MULTIPLE-ENTRY POWER CONNECTION WITH JUNCTION BOX
SUBMITTAL SHEET WSC-0705
TECHNICAL SUPPORT
Warmup is available 24/7/365 at (888) 927-6333.
For quotes, layouts and specific technical information, contact us at:
Warmup USA
52 Federal Rd #1F, Danbury, CT 06810
(888) 927-6333
us@warmup.com
Warmup CANADA
374 Wellington St W, Toronto, ON M5V 1E3
(905) 990-2075
ca@warmup.com
RELATED PRODUCTS
NAMSR CABLE FOR ROOF & GUTTER APPLICATIONS - see WSC-0929
NAMSR CABLE FOR PIPE FREEZE PROTECTION - see WSC-0930
SPEEDFIT SPLICE - see WSC-2804
SPEEDFIT-TEE - see WSC-0105
SPEEDFIT-END KIT - see WSC-3004

Navigation menu