Wylex2006 2

User Manual: Wylex2006-2

Open the PDF directly: View PDF PDF.
Page Count: 48

2006
circuit protection
http://waterheatertimer.org/How-to-wire-Whole-house-surge-protector.html
NH INSULATED CONSUMER UNITS 2
NH METAL CONSUMER UNITS 6
CONSUMER UNIT MCBs RCBOs & FUSES 9
CONTROL MODULES 9
NH DISTRIBUTION BOARDS 10
DISTRIBUTION BOARD INCOMERS 13
DISTRIBUTION BOARD MCBs & RCBOs 14
NH MCCB PANEL BOARDS 16
PANELBOARD NHG MCCBs 19
NH FUSE SWITCH COMBINATION UNITS 20
NH ISOLATORS 21
STANDARD RANGE 22
LIFELINE RCDs & ENCLOSURES 26
SWITCH DISCONNECTORS & ISOLATORS 30
TECHNICAL DATA & DIMENSIONS 32
NUMERIC INDEX 44
Founded in 1897, Wylex introduced the
first ‘consumer unit’ to the
electrical
industry, this original design was the
forerunner to the
‘Standard Range’,
which is still in wide use today.
From its base at
Wythenshawe, through
a policy of continuous design
improvement,
Wylex has developed a
comprehensive range of Domestic,
Commercial
and Industrial circuit
protection devices based on quality and
close attention to the practical
requirements of the contractor including
the fundamental requirements of
electrical safety embodied in the
relevant
British and International Standards
including IEE Wiring
Regulations.
Left
Electrium’s purpose built Commercial Centre in
Cannock, Staffordshire
THE NH RANGE
CUSTOM BUILT
To meet the ever changing requirements and designs
of the modern electrical installation, Wylex offers a
service where the standard range of products can be
modified to specific customer needs.
Our technical services and engineering teams
can assess the feasability of a product
requirement whilst our modern manufacturing
facilities
will produce a high quality competitive solution.
The NH range of consumer units provides
contemporary styling with particular attention
to installation features including:
Generous cable preparation room with neutral and
earth bars mounted on the top of the enclosure
Supplied complete with incoming devices and fixed
busbar system for speedy installation
Insulated versions with side entry cut outs profiled
to accept mini trunking and large segmented rear
cable entries to allow trimming to the
precise cable entry size
Raised interior for maximum wiring space
Circuit identification labels providing clear
understanding of outgoing ways
MAIN SWITCH
CAT REF MS RATING MCB WAYS DIN MODULES
NH204/40 40A 2
NH204/63 63A 2
NH504 100A 5
NH804 100A 8
NH1104 100A 11
NH1404 100A 14
NH1904 100A 19
NH504+3 100A 5 3
NH804+3 100A 8 3
NH804+6 100A 8 6
NH1104+3 100A 11 3
RCD INCOMER
CAT REF RCD RATING MCB WAYS DIN MODULES
NHRS204/40 40A 30mA 2
NHRS204/63 63A 30mA 2
NHRS504 100A 30mA 5
NHRS804 100A 30mA 8
NHRS1104 100A 30mA 11
NHRS1404 100A 30mA 14
NHRS1904 100A 30mA 19
NHRM204/40 40A 100mA 2
NHRM204/63 63A 100mA 2
NHRM504 100A 100mA 5
NHRM804 100A 100mA 8
NHRM1104 100A 100mA 11
NHRM1404 100A 100mA 14
NHRM1904 100A 100mA 19
NHRS504+3 100A 30mA 5 3
NHRS804+3 100A 30mA 8 3
NHRS804+6 100A 30mA 8 6
NHRS1104+3 100A 30mA 11 3
NHRM504+3 100A 100mA 5 3
NHRM804+3 100A 100mA 8 3
NHRM804+6 100A 100mA 8 6
NHRM1104+3 100A 100mA 11 3
NHTM504
100A 100mA TD*
5
NHTM804
100A 100mA TD*
8
NHTM1104
100A 100mA TD*
11
NHTM1404
100A 100mA TD*
14
NHTM1904
100A 100mA TD*
19
* Time Delay RCD
DUAL TARIFF 100A MAIN SWITCH AND 100A MAIN SWITCH
CAT REF MS RATING MCB WAYS MS RATING MCB WAYS
NHIIX2404 100A 4 63A 2
NHIIX3304 100A 3 100A 3
NHIIX5404 100A 4 100A 5
NHIIX4504 100A 5 100A 4
NHIIX3904 100A 9 100A 3
NHIIX4804 100A 8 100A 4
NHIIX7504 100A 5 100A 7
NHIIX6604 100A 6 100A 6
NHIIX5704 100A 7 100A 5
NHIIX9804 100A 8 100A 9
NHIIX8904 100A 9 100A 8
NHIIX11604 100A 6 100A 11
NHIIX51204 100A 12 100A 5
DUAL TARIFF 100A MAIN SWITCH AND 100A 30mA RCD MAIN SWITCH
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS
NHRSX5704 100A 7 100A 30mA 5
NHRSX6604 100A 6 100A 30mA 6
NHRSX7504 100A 5 100A 30mA 7
NHRSX8904 100A 9 100A 30mA 8
NHRSX9804 100A 8 100A 30mA 9
4
NH Insulated Range
NH804
NH804+3
NHRS504
NHIIX6604
With DIN
Accessory
Section
With DIN
Accessory
Section
SPLIT LOAD WITH TIME DELAY RCD INCOMER
CAT REF TD RCD MCB WAYS RCD RATING MCB WAYS
NHSTM3604 100A 100mA 6 80A 30mA 3
NHSTM4504 100A 100mA 5 80A 30mA 4
NHSTM5404 100A 100mA 4 80A 30mA 5
NHSTM6304 100A 100mA 3 80A 30mA 6
NHSTM3904 100A 100mA 9 80A 30mA 3
NHSTM4804 100A 100mA 8 80A 30mA 4
NHSTM5704 100A 100mA 7 80A 30mA 5
NHSTM6604 100A 100mA 6 80A 30mA 6
NHSTM7504 100A 100mA 5 80A 30mA 7
NHSTM8404 100A 100mA 4 80A 30mA 8
NHSTM9304 100A 100mA 3 80A 30mA 9
NHSTM12504 100A 100mA 5 80A 30mA 12
NHSTM11604 100A 100mA 6 80A 30mA 11
NHSTM8904 100A 100mA 9 80A 30mA 8
NHSTM9804 100A 100mA 8 80A 30mA 9
NHSTM10704 100A 100mA 7 80A 30mA 10
NHSTM71004 100A 100mA 10 80A 30mA 7
NHSTM61104 100A 100mA 11 80A 30mA 6
NHSTM51204 100A 100mA 12 80A 30mA 5
A range of matching DIN enclosures is also available, see page 29.
5
NH Insulated Range
SPLIT LOAD
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS
NHRS2404 100A 4 80A 30mA 2
NHRS3304 100A 3 80A 30mA 3
NHRS4204 100A 2 80A 30mA 4
NHRS5404 100A 4 80A 30mA 5
NHRS4504 100A 5 80A 30mA 4
NHRS3604 100A 6 80A 30mA 3
NHRS6304 100A 3 80A 30mA 6
NHRS3904 100A 9 80A 30mA 3
NHRS4804 100A 8 80A 30mA 4
NHRS6604 100A 6 80A 30mA 6
NHRS5704 100A 7 80A 30mA 5
NHRS7504 100A 5 80A 30mA 7
NHRS8404 100A 4 80A 30mA 8
NHRS9304 100A 3 80A 30mA 9
NHRS12504 100A 5 80A 30mA 12
NHRS11604 100A 6 80A 30mA 11
NHRS10704 100A 7 80A 30mA 10
NHRS61104 100A 11 80A 30mA 6
NHRS71004 100A 10 80A 30mA 7
NHRS9804 100A 8 80A 30mA 9
NHRS8904 100A 9 80A 30mA 8
NHRS51204 100A 12 80A 30mA 5
FLEXIBLE SPLIT LOAD CONSUMER UNITS
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS MCB WAYS
MIN MAX MIN MAX TOTAL
NHRS9SL 100A 3 6 80A 30mA 3 6 9
NHRS12SL 100A 3 9 80A 30mA 3 9 12
NHRS17SL 100A 5 12 80A 30mA 5 12 17
TIME DELAY FLEXIBLE SPLIT LOAD CONSUMER UNITS
CAT REF TD RCD MCB WAYS RCD RATING MCB WAYS MCB WAYS
MIN MAX MIN MAX TOTAL
NHSTM9SL 100A 100mA 3 6 80A 30mA 3 6 9
NHSTM12SL 100A 100mA 3 9 80A 30mA 3 9 12
NHSTM17SL 100A 100mA 5 12 80A 30mA 5 12 17
Flexible consumer units utilise a full DIN rail and accept modular DIN devices
such as a Bell Transformer or Timer.
SPLIT LOAD WITH DIN RAIL ACCESSORY SECTION
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS NO OF
MODULES
NHRS6504+6 100A 5 80A 30mA 6 6
NHRS5604+6 100A 6 80A 30mA 5 6
NHRS7704+3 100A 7 80A 30mA 7 3
NHRS8604+3 100A 6 80A 30mA 8 3
NHRS6804+3 100A 8 80A 30mA 6 3
NHRS4504
NHRS12SL
NHSTM4504
6
NH Metal Cased Range
MAIN SWITCH
CAT REF MS RATING MCB WAYS
NH206/40 40A 2
NH206/63 63A 2
NH506 100A 5
NH806 100A 8
NH1106 100A 11
NH1406 100A 14
NH1906 100A 19
RCD INCOMER
CAT REF RCD RATING MCB WAYS
NHRS206/40 40A 30mA 2
NHRS206/63 63A 30mA 2
NHRS506 100A 30mA 5
NHRS806 100A 30mA 8
NHRS1106 100A 30mA 11
NHRS1406 100A 30mA 14
NHRS1906 100A 30mA 19
NHRM206/40 40A 100mA 2
NHRM206/63 63A 100mA 2
NHRM506 100A 100mA 5
NHRM806 100A 100mA 8
NHRM1106 100A 100mA 11
NHRM1406 100A 100mA 14
NHRM1906 100A 100mA 19
NHTM506
100A 100mA time delay
5
NHTM806
100A 100mA time delay
8
NHTM1106
100A 100mA time delay
11
NHTM1406
100A 100mA time delay
14
NHTM1906
100A 100mA time delay
19
SPLIT LOAD
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS
NHRS2406 100A 4 80A 30mA 2
NHRS3306 100A 3 80A 30mA 3
NHRS4206 100A 2 80A 30mA 4
NHRS5406 100A 4 80A 30mA 5
NHRS4506 100A 5 80A 30mA 4
NHRS3606 100A 6 80A 30mA 3
NHRS6306 100A 3 80A 30mA 6
NHRS3906 100A 9 80A 30mA 3
NHRS4806 100A 8 80A 30mA 4
NHRS6606 100A 6 80A 30mA 6
NHRS5706 100A 7 80A 30mA 5
NHRS7506 100A 5 80A 30mA 7
NHRS8406 100A 4 80A 30mA 8
NHRS9306 100A 3 80A 30mA 9
NHRS12506 100A 5 80A 30mA 12
NHRS11606 100A 6 80A 30mA 11
NHRS10706 100A 7 80A 30mA 10
NHRS61106 100A 11 80A 30mA 6
NHRS71006 100A 10 80A 30mA 7
NHRS9806 100A 8 80A 30mA 9
NHRS8906 100A 9 80A 30mA 8
NHRS51206 100A 12 80A 30mA 5
For Dual RCD insulated consumer units see page 8
NH806
NHRS1106
NHRS4506
NHRS6606 Flush mounting consumer units available to order.
Suffix Catalogue Reference with /FLU eg: NHRS6606/FLU
7
NH Metal Cased Range
DUAL TARIFF 100A MAIN SWITCH & 100A MAIN SWITCH
CAT REF MS RATING MCB WAYS MS RATING MCB WAYS
NHIIX2406 100A 4 63A 2
NHIIX3306 100A 3 100A 3
NHIIX4506 100A 5 100A 4
NHIIX5406 100A 4 100A 5
NHIIX7506 100A 5 100A 7
NHIIX6606 100A 6 100A 6
NHIIX5706 100A 7 100A 5
NHIIX9806 100A 8 100A 9
NHIIX8906 100A 9 100A 8
NHIIX51206 100A 12 100A 5
NHIIX11606 100A 6 100A 11
DUAL TARIFF 100A MAIN SWITCH & 100A 30mA RCD SWITCH
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS
NHRSX5706 100A 7 100A 30mA 5
NHRSX6606 100A 6 100A 30mA 5
NHRSX7506 100A 5 100A 30mA 7
NHRSX8906 100A 9 100A 30mA 8
NHRSX9806 100A 8 100A 30mA 9
100mA available to order
NHIIX4506
SPLIT LOAD WITH TIME DELAY RCD INCOMER
CAT REF TD RCD RATING MCB WAYS RCD RATING MCB WAYS
NHSTM3606 100A 100mA 6 80A 30mA 3
NHSTM4506 100A 100mA 5 80A 30mA 4
NHSTM5406 100A 100mA 4 80A 30mA 5
NHSTM6306 100A 100mA 3 80A 30mA 6
NHSTM3906 100A 100mA 9 80A 30mA 3
NHSTM4806 100A 100mA 8 80A 30mA 4
NHSTM5706 100A 100mA 7 80A 30mA 5
NHSTM6606 100A 100mA 6 80A 30mA 6
NHSTM7506 100A 100mA 5 80A 30mA 7
NHSTM8406 100A 100mA 4 80A 30mA 8
NHSTM9306 100A 100mA 3 80A 30mA 9
NHSTM12506 100A 100mA 5 80A 30mA 12
NHSTM11606 100A 100mA 6 80A 30mA 11
NHSTM8906 100A 100mA 9 80A 30mA 8
NHSTM9806 100A 100mA 8 80A 30mA 9
NHSTM10706 100A 100mA 7 80A 30mA 10
NHSTM71006 100A 100mA 10 80A 30mA 7
NHSTM61106 100A 100mA 11 80A 30mA 6
NHSTM51206 100A 100mA 12 80A 30mA 5
NHSTM6606
FLEXIBLE SPLIT LOAD CONSUMER UNITS
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS MCB WAYS
MIN MAX MIN MAX TOTAL
NHRS9SLM 100A 3 6 80A 30mA 3 6 9
NHRS12SLM 100A 3 9 80A 30mA 3 9 12
NHRS17SLM 100A 5 12 80A 30mA 5 12 17
Flexible consumer units utilise a full DIN rail and accept modular DIN devices such
as Bell Transformer or Timer.
MAIN SWITCH ISOLATOR WITH DIN RAIL ACCESSORY SECTION
CAT REF MS RATING MCB WAYS NO of MODULE WAYS
NH506+3 100A 5 3
NH806+3 100A 8 3
NH806+6 100A 8 6
NH1106+3 100A 11 3
RCD MAIN ISOLATOR WITH DIN RAIL ACCESSORY SECTION
CAT REF RCD RATING MCB WAYS No of MODULE WAYS
NHRS506+3 100A 30mA 5 3
NHRS806+3 100A 30mA 8 3
NHRS806+6 100A 30mA 8 6
NHRS1106+3 100A 30mA 11 3
SPLIT LOAD WITH DIN RAIL ACCESSORY SECTION
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS No of MODULE WAYS
NHRS5606+6 100A 5 80A 30mA 6 6
NHRS7706+3 100A 7 80A 30mA 7 3
100mA available to order
NHRS12SLM
NH806+3
8
NH Duplex Units & Skeleton Units
METAL – SPLIT LOAD DUPLEX
TOP BANK BOTTOM BANK
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS
NHDIS88 100A 8 80A 30mA 8
NHDIS1111 100A 11 80A 30mA 11
NHDIS1414 100A 14 80A 30mA 14
NHDIS1919 100A 19 80A 30mA 19
NHDTMS88 100A 100mA TD 8 80A 30mA 8
NHDTMS1111 100A 100mA TD 11 80A 30mA 11
NHDTMS1414 100A 100mA TD 14 80A 30mA 14
NHDTMS1919 100A 100mA TD 19 80A 30mA 19
METAL – DUAL TARIFF DUPLEX
TOP BANK BOTTOM BANK
CAT REF MS RATING MCB WAYS RCD RATING MCB WAYS
NHDIIX88 100A 8 100A 8
NHDIIX1111 100A 11 100A 11
NHDIIX1414 100A 14 100A 14
NHDIIX1919 100A 19 100A 19
NHDISX88 100A 8 100A 30mA 8
NHDISX1111 100A 11 100A 30mA 11
NHDISX1414 100A 14 100A 30mA 14
NHDISX1919 100A 19 100A 30mA 19
NHDSSX88 100A 30mA 8 100A 30mA 8
NHDSSX1111 100A 30mA 11 100A 30mA 11
NHDSSX1414 100A 30mA 14 100A 30mA 14
NHDSSX1919 100A 30mA 19 100A 30mA 19
INSULATED – DUAL SPLIT LOAD RCD
ISOLATOR TOTAL No of A B
CAT REF RATING MCB WAYS RCD RATING MCB WAYS MS RATING MCB WAYS
NHISS5504 100A 10 80A 30mA 5 80A 30mA 5
NHISS8704 100A 15 80A 30mA 7 80A 30mA 8
100mA RCD available in either ‘A’ or ‘B’ section to order
METAL – DUAL SPLIT LOAD RCD
ISOLATOR TOTAL No of A B
CAT REF RATING MCB WAYS RCD RATING MCB WAYS MS RATING MCB WAYS
NHISS3406 100A 7 80A 30mA 4 80A 30mA 3
NHISS4606 100A 10 80A 30mA 6 80A 30mA 4
NHISS5506 100A 10 80A 30mA 5 80A 30mA 5
NHISS7806 100A 15 80A 30mA 8 80A 30mA 7
NHISS8706 100A 15 80A 30mA 7 80A 30mA 8
SKELETON UNITS
CAT REF DESCRIPTION
FALNH706 7 way with main switch
FALNH1106 11 way with main switch
FALNHRS706 7 way with main RCD
FALNHRS1106 11 way with main RCD
FALNH10SL* 10 way flexible split load 100A main switch 80A 30mA RCD
FALNH15SL* 15 way flexible split load 100A main switch 80A 30mA RCD
FALNHIIX10SL 10 way flexible dual tariff 2x 100A main switch
* Supplied with both metal and plastic covers
NHDIS1414
NHISS5504
FALNH10SL
NOTE
ADDITIONAL CONFIGURATIONS ARE AVAILABLE.
FOR FURTHER INFORMATION, PLEASE CONTACT OUR
TECHNICAL SERVICES DEPARTMENT.
INSULATED DUPLEX CONSUMER UNITS AVAILABLE DURING 2006
DIN RAIL MODULAR DEVICES FOR USE IN + UNITS & FLEXIBLE UNITS
CAT REF PRODUCT MODULE
ME232-230 Staircase timer 1
MDT2
Digital time clock 1 channel 1xNO/NC contact 16A
1
MSTT-111 Digital time clock
1 channel 1xNO contact 16A
2
MSTT-227 Digital time clock
2 channel
2
MESB-20NO 20A 2 pole contactor 1
MESB-24NO 24A 4 pole contactor 2
MESB-40NO 40A 4 pole contactor 3
MESB-63NO 63A 4 pole contactor 3
MTS8 Bell transformer 2
MSTU6011S Disc type time clock
1 channel 1xNC contact 16A
3
MSTU8011S Disc type time clock
1 channel 1xNC contact 16A
3
MAT1 Disc type time clock
1 channel 1xNO contact 16A
1
When wiring in NH Consumer Units contact Wylex technical services department
NH ACCESSORIES
CAT REF PRODUCT
NHB1PP Blanking plate for busbar & cover
NH00PP Blanking plate twist fit for cover
NH00 Blanking plate push fit for cover
MCBLDX MCB locking device
EIU Cable gland kit
DLDX Isolator locking device
WPL Padlock for DLDX & HLDX
9
NH Consumer Unit Outgoing Devices & Control Modules
NSB MINIATURE CIRCUIT BREAKERS (6KA)
CAT REF RATING POLES MODULE
NSB06 6A 1 1
NSB10 10A 1 1
NSB16 16A 1 1
NSB20 20A 1 1
NSB32 32A 1 1
NSB40 40A 1 1
NSB50 50A 1 1
NSC MODULAR CARTRIDGE FUSE HOLDERS WITH FUSE
CAT REF RATING POLES MODULE
NSC05 5A 1 1
NSC10 10A 1 1
NSC15 15A 1 1
NSC20 20A 1 1
NSC30 30A 1 1
NSC35 35A 1 2
NSC40 40A 1 2
NSC45 45A 1 2
SPARE FUSES
CAT REF RATING
CFL05 5A
CFL10 10A
CFL15 15A
CFL20 20A
CFL30 30A
CFL35 35A
CFL40 40A
CFL45 45A
NSBS COMBINED MCB/RCD UNITS (C CURVE)
CAT REF CURRENT RATING RCD RATING POLES MODULES
NSBS6/2 6A 30mA 2P 2
NSBS10/2 10A 30mA 2P 2
NSBS16/2 16A 30mA 2P 2
NSBS20/2 20A 30mA 2P 2
NSBS32/2 32A 30mA 2P 2
NSBS40/2 40A 30mA 2P 2
NSBS6/1* 6A 30mA SP 1
NSBS10/1* 10A 30mA SP 1
NSBS16/1* 16A 30mA SP 1
NSBS20/1* 20A 30mA SP 1
NSBS32/1* 32A 30mA SP 1
NSBS40/1* 40A 30mA SP 1
*NH Insulated units only
NSB06 NSB10 NSB16 NSB20 NSB32 NSB40 NSB50
NSC05 NSC10 NSC20 NSC30 NSC45
NSBS32/1 NSBS32/2
MDT2 MAT1
NH00 NH00PP NHB1PP
The Wylex range of NH distribution Boards is designed to cater for a
variety of industrial and commercial applications.
The range of boards is complemented by a wide variety of incoming
options including direct connection, switch disconnector and RCD,
outgoing devices include a broad selection of MCBs and RCBOs
rated 6kA or 10kA.
This comprehensive collection of circuit protection and distribution
products allows the contractor to select the most economical
and electrically appropriate solutions.
All metal enclosures for both A Boards and B Boards
Two frame sizes 125A and 200A B Boards
Choice of incoming devices including Switch Disconnector, RCDs,
MCCBs or Direct Connection
B Boards accept four pole incomers
Over 250 different boards available from standard catalogue items
Removable pan assembly and gland plates for easy fixing and
cable entry
Split neutral bars help make full use of interior space and
keep all terminals accessible
Range of 10kA and 6kA MCBs and RCBOs
Single pole 18mm wide RCBOs
NH DISTRIBUTION BOARDS
TYPE ‘A’ SP & N DISTRIBUTION BOARD
CAT REF SWITCH RATING NO. OF SP WAYS
NHSN51 125A 5
NHSN81 125A 8
NHSN111 125A 11
NHSN141 125A 14
NHSN161 125A 16
NHSN191 125A 19
A Boards excluding incomers available to order. Range of incoming devices shown opposite.
TP & N TYPE ‘B’ DISTRIBUTION BOARDS (Excluding Incomer)
CAT REF DESCRIPTION NO. OF TP WAYS
NHTN4 125A Distribution board Excluding incomer 4
NHTN6 125A Distribution board Excluding incomer 6
NHTN8 125A Distribution board Excluding incomer 8
NHTN12 125A Distribution board Excluding incomer 12
NHTN16 125A Distribution board Excluding incomer 16
NHTN20 125A Distribution board Excluding incomer 20
NHTN24 125A Distribution board Excluding incomer 24
Suitable for use with switch disconnector, RCD or direct connection incomer arrangement
IP66 TP &N MCB Distribution boards are available up to 16 TP ways
TP & N TYPE ‘B’ DISTRIBUTION BOARDS (Excluding Incomer)
CAT REF DESCRIPTION NO. OF TP WAYS
NHTN40 200A Distribution board Excluding incomer 4
NHTN60 200A Distribution board Excluding incomer 6
NHTN80 200A Distribution board Excluding incomer 8
NHTN120 200A Distribution board Excluding incomer 12
NHTN160 200A Distribution board Excluding incomer 16
NHTN200 200A Distribution board Excluding incomer 20
NHTN240 200A Distribution board Excluding incomer 24
Suitable for switch disconnector, or direct connection incomer arrangement
Flush mounting boards also available add suffix /FLU to Catalogue Reference
eg: NHTN4/FLU
NHSN81
NHTN4
NHTN40
12
NH Distribution Boards
New 250A
version
2006
13
NH Distribution Board Incoming Units & Accessories
NH A BOARD INCOMERS
CAT REF DESCRIPTION RATING
WS602 2 Pole 2 module switch 63A
WS102 2 Pole 2 module switch 100A
WS122 2 Pole 2 module switch 125A
WRS63/2 Double Pole RCD 63A 30mA
WRS80/2 Double Pole RCD 80A 30mA
WRS100/2 Double Pole RCD 100A 30mA
WRM63/2 Double Pole RCD 63A 100mA
WRM80/2 Double Pole RCD 80A 100mA
WRM100/2 Double Pole RCD 100A 100mA
WRL63/2 Double Pole RCD 63A 300mA
WRL100/2 Double Pole RCD 100A 300mA
WRMT100/2 Double Pole Time Delay RCD 100A 100mA
NHDPDC Double Pole direct connection 100A
NH B BOARD INCOMERS
CAT REF DESCRIPTION RATING
WS603 3 Pole 3 module switch 63A
WS103 3 Pole 3 module switch 100A
WS123 3 Pole 3 module switch 125A
WS604 4 Pole 4 module switch* 63A
WS104 4 Pole 4 module switch* 100A
WS124 4 Pole 4 module switch* 125A
WRS63/4 Four Pole RCD* 63A 30mA
WRS100/4 Four Pole RCD* 100A 30mA
WRM63/4 Four Pole RCD* 63A 100mA
WRM100/4 Four Pole RCD* 100A 100mA
WRL63/4 Four Pole RCD* 63A 300mA
WRL100/4 Four Pole RCD* 100A 300mA
WRMT100/4 Four Pole Time Delay RCD* 100A 100mA
NH4PINKIT Four Pole Incomer Connection Kit* 100A
NH200TPI Triple Pole switch disconnector 200A
NHTPDC Four Pole direct connection 125A
NH200DC Four Pole direct connection 200A
NHSPAK Single phase adaptor kit 125A
* Four Pole DIN Incomers require Incomer connection Kit. REF, NH4PINKIT
EXTENSION & ACCESSORY BOXES
CAT REF DESCRIPTION DIN MODULES
NHEB Cable extension box (plain)
NHEB/DIN DIN accessory box single row (plain)
NHAB DIN accessory box single row 18
NHAB2 DIN accessory box two row 36
NHAB3 DIN accessory box three row 54
NHAB4 DIN accessory box four row 72
NHAB5 DIN accessory box five row 90
18 modules per row
ACCESSORIES
CAT REF DESCRIPTION
NHEP11 Replacement gland plate
NH00 Way blank
NHB1PP 1 Way busbar & cover blank
3TPBP 9 way busbar & MCB way blank kit
PSBL1 Way blank (single module)
PSBL3 Way blank (3 module)
MCBLDX Locking device for MCB
WPL Padlock for MCBLDX
NHPBDL MCB Board door lock
PDDPL Doorlock with padlocking device
WDH-1 Document wallet
NHCEKIT 14 terminal clean earth kit
NHCEKIT20 20 terminal clean earth kit
WS102
WS123
NHAB2
NH4PINKIT
14
NH Miniature Circuit Breakers
PSB06-B PSB32-B PSB63-B
PSB206-B PSB232-B
PSB306-B PSB332-B
SINGLE POLE MCBs
RATING POLES B CURVE C CURVE D CURVE
6A 6kA 1 NSB06-B NSB06-C NSB06-D
10A 6kA 1 NSB10-B NSB10-C NSB10-D
16A 6kA 1 NSB16-B NSB16-C NSB16-D
20A 6kA 1 NSB20-B NSB20-C NSB20-D
32A 6kA 1 NSB32-B NSB32-C NSB32-D
40A 6kA 1 NSB40-B NSB40-C NSB40-D
50A 6kA 1 NSB50-B NSB50-C NSB50-D
63A 6kA 1 NSB63-B NSB63-C NSB63-D
6A 10kA 1 PSB06-B PSB06-C PSB06-D
10A 10kA 1 PSB10-B PSB10-C PSB10-D
16A 10kA 1 PSB16-B PSB16-C PSB16-D
20A 10kA 1 PSB20-B PSB20-C PSB20-D
32A 10kA 1 PSB32-B PSB32-C PSB32-D
40A 10kA 1 PSB40-B PSB40-C PSB40-D
50A 10kA 1 PSB50-B PSB50-C PSB50-D
63A 10kA 1 PSB63-B PSB63-C PSB63-D
TWO POLE MCBs
RATING POLES B CURVE C CURVE D CURVE
6A 10kA 2 PSB206-B PSB206-C PSB206-D
10A 10kA 2 PSB210-B PSB210-C PSB210-D
16A 10kA 2 PSB216-B PSB216-C PSB216-D
20A 10kA 2 PSB220-B PSB220-C PSB220-D
32A 10kA 2 PSB232-B PSB232-C PSB232-D
40A 10kA 2 PSB240-B PSB240-C PSB240-D
50A 10kA 2 PSB250-B PSB250-C PSB250-D
63A 10kA 2 PSB263-B PSB263-C PSB263-D
TRIPLE POLE MCBs
RATING POLES B CURVE C CURVE D CURVE
6A 6kA 3 NSB306-B NSB306-C NSB306-D
10A 6kA 3 NSB310-B NSB310-C NSB310-D
16A 6kA 3 NSB316-B NSB316-C NSB316-D
20A 6kA 3 NSB320-B NSB320-C NSB320-D
32A 6kA 3 NSB332-B NSB332-C NSB332-D
40A 6kA 3 NSB340-B NSB340-C NSB340-D
50A 6kA 3 NSB350-B NSB350-C NSB350-D
63A 6kA 3 NSB363-B NSB363-C NSB363-D
6A 10kA 3 PSB306-B PSB306-C PSB306-D
10A 10kA 3 PSB310-B PSB310-C PSB310-D
16A 10kA 3 PSB316-B PSB316-C PSB316-D
20A 10kA 3 PSB320-B PSB320-C PSB320-D
32A 10kA 3 PSB332-B PSB332-C PSB332-D
40A 10kA 3 PSB340-B PSB340-C PSB340-D
50A 10kA 3 PSB350-B PSB350-C PSB350-D
63A 10kA 3 PSB363-B PSB363-C PSB363-D
For other ratings please contact Wylex technical
NSBS6/1 PSBS32/1
MCBLDX WPL NH00 NH00PP NHB1PP
PSBS40/2
MESB-40NO
15
SP & SPSN RCBOs & Modular Devices
SINGLE MODULE RCBO - FOR USE IN NH DISTRIBUTION BOARDS
RATING POLES C CURVE
6A 6kA 1 30mA NSBS6/1
10A 6kA 1 30mA NSBS10/1
16A 6kA 1 30mA NSBS16/1
20A 6kA 1 30mA NSBS20/1
32A 6kA 1 30mA NSBS32/1
40A 6kA 1 30mA NSBS40/1
6A 10kA 1 30mA PSBS6/1
10A 10kA 1 30mA PSBS10/1
16A 10kA 1 30mA PSBS16/1
20A 10kA 1 30mA PSBS20/1
32A 10kA 1 30mA PSBS32/1
40A 10kA 1 30mA PSBS40/1
50A 10kA 1 30mA PSBS50/1
ACCESSORIES
CAT REF DESCRIPTION
MCBLDX Locking device for MCB/RCBO
WPL Padlock for MCBLDX
PS00 Way Blank - (2x Half Module)
PSBL3 Way Blank - 3 Module
3TPBP Blank kit 9 modules & 9 MCB way blank
NH00 Way Blank - 1 Module
NH00PP Twist Fit 1 module blank
NHB1PP Busbar & cover blank 1 module
TWO MODULE RCBO
- NOT FOR USE IN NH DISTRIBUTION BOARDS
RATING POLES C CURVE
6A 6kA 2 30mA NSBS6/2
10A 6kA 2 30mA NSBS10/2
16A 6kA 2 30mA NSBS16/2
20A 6kA 2 30mA NSBS20/2
32A 6kA 2 30mA NSBS32/2
40A 6kA 2 30mA NSBS40/2
6A 10kA 2 30mA PSBS6/2
10A 10kA 2 30mA PSBS10/2
16A 10kA 2 30mA PSBS16/2
20A 10kA 2 30mA PSBS20/2
32A 10kA 2 30mA PSBS32/2
40A 10kA 2 30mA PSBS40/2
For use in DIN Enclosures EG: NH ED Range or + Units
DIN RAIL MODULAR DEVICES
CAT REF PRODUCT MODULE
MDT2 Digital Timeclock 1 channel 1xNO/NC Contact 16A 1
MSTT-111 Digital Timeclock 1 channel 1xNO Contact 16A 1
MSTT-227 Digital Timeclock 2 channel 2
MESB-20NO 20A DP Contactor 1
MESB-24NO 24A 4 Pole Contactor 2
MESB-40NO 40A 4 Pole Contactor 3
MESB-63NO 63A 4 Pole Contactor 3
For use in DIN Enclosures EG: NH ED Range or + Units
NH MCCB Panel Boards offer 250A
or 400A fault rated, fully shrouded
busbar systems in a modular
enclosure system.
The 630mm wide enclosure system
combined with MCCBs and a range
of accessories, provides a competent
flexible main or sub-main distribution
board.
MCCBs with 25kA fault breaking
capacity
25A-125A ratings
70mm2cable clamp terminals or
10mm flat bar
Full Range of accessories including
sealable terminal covers
Fully shrouded bus bars
Excellent access to N/E bars for
cabling
Full or partial lockable doors
Fully conforms with BSEN 60943-1
form 2
NH125 MCCB PANELBOARDS
17
NH125 Panelboards
250A SWITCH DISCONNECTOR INCOMER
OUTGOING MODULAR HEIGHT
WAYS HEIGHT (mm) CAT REF
250A 6 17 902 NHPB6SW250
8 17 902 NHPB8SW250
12 20 1060 NHPB12SW250
BSEN 60439
250A Busbars
Busbar fault rated 25kA–1 sec
IP31 (41 with door) Ingress Protection
Earth and neutral terminals for each SP way
630mm wide x 165mm deep
120 mm24 Core Max on Incoming Terminals
70 mm24 Core Max on Outgoing Terminals
Fully assembled
Complete with incomer
Also available excluding incomer for direct connection applications
200A MCCB INCOMER
OUTGOING MODULAR HEIGHT
WAYS HEIGHT (mm) CAT REF
200A 6 17 902 NHPB6CB200
8 17 902 NHPB8CB200
12 20 1060 NHPB12CB200
BSEN 60439
250A Busbars
Busbar fault rated 25kA–1 sec
IP31 (41 with door) Ingress Protection
Earth and neutral terminals for each SP way
630mm wide x 165mm deep
120 mm24 Core Max on Incoming Terminals
70 mm24 Core Max on Outgoing Terminals
Fully assembled
Complete with incomer
DOOR KITS
PANELBOARD MODULAR
HEIGHT CAT REF
6/8 way 17 NHFHDK17
12 way 20 NHFHDK20
Door lock NHPBDL
ACCESSORY BOXES
PANELBOARD MODULAR HEIGHT
HEIGHT (mm) CAT REF
Cable Spreader Box 4 210 NHCSB
DIN Accessory Box NHGAB
A Board 13 way NHG13DB
NHPB6SW250
NHPB6CB200
NHFDK17
All NH Panelboard enclosures are 630mm wide x 165mm deep x modular height
1 Module = 52.5mm. Colour finish RAL 7035
400A SWITCH DISCONNECTOR INCOMER
OUTGOING MODULAR HEIGHT
WAYS HEIGHT (mm) CAT REF
400A 6 20 1060 NHPB6SW400
8 20 1060 NHPB8SW400
12 23 1217 NHPB12SW400
16 26 1375 NHPB16SW400
BSEN 60439
400A Busbars
Busbar fault rated 25kA–1 sec
IP31 (41 with door) Ingress Protection
Earth and neutral terminals for each SP way
630mm wide x 165mm deep
240 mm24 Core Max on Incoming Terminals
70 mm24 Core Max on Outgoing Terminals
Fully assembled
Complete with incomer
Also available excluding incomer for direct connection applications
400A MCCB INCOMER
OUTGOING MODULAR HEIGHT
WAYS HEIGHT (mm) CAT REF
400A 6 20 1060 NHPB6CB400
8 20 1060 NHPB8CB400
12 23 1217 NHPB12CB400
16 26 1375 NHPB16CB400
Conforms to BSEN 60439
400A Busbars
Busbar fault rated 25kA–1 sec
IP31 (41 with door) Ingress Protection
Earth and neutral terminals for each SP way
630mm wide x 165mm deep
240 mm24 Core Max on Incoming Terminals
70 mm24 Core Max on Outgoing Terminals
Fully assembled
Complete with incomer
DOOR KITS
PANELBOARD MODULAR
HEIGHT CAT REF
6/8 way 20 NHFHDK20
12 way 23 NHCBDK12
NHCBDK11
16 way 26 NHCBDK15
NHCBDK11
Door lock NHPBDL
EXTENSION BOXES
PANELBOARD MODULAR HEIGHT
HEIGHT (mm) CAT REF
Cable Spreader Box 4 210 NHCSB
DIN Accessory Box NHGAB
A Board 13 way NHG13DB
18
NH125 Panelboards
NHPB6SW400
NHPB6CB400
NHFHDK20
}
}
19
NH125 Panelboard Circuit Breakers
NHGPCB1001
NHGPCB633
NHCB1TS NHCB3TS
NH SINGLE POLE MCCBS
Conforms to BSEN 60947-2
16kA Icu at 240V ac
Fixed magnetic
Fixed thermal
Double insulated
Terminal Capacity 70mm2
RATING CAT REF
25A NHGPCB251
32A NHGPCB321
40A NHGPCB401
50A NHGPCB501
63A NHGPCB631
80A NHGPCB801
100A NHGPCB1001
125A NHGPCB1251
NH THREE POLE MCCBS
Conforms to BSEN 60947-2
25kA Icu at 415V ac
Fixed magnetic
Fixed thermal
Double insulated
Large range of accessories
Terminal Capacity 70mm2
RATING CAT REF
25A NHGPCB253
32A NHGPCB323
40A NHGPCB403
50A NHGPCB503
63A NHGPCB633
80A NHGPCB803
100A NHGPCB1003
125A NHGPCB1253
NH MCCBs ACCESSORIES
DESCRIPTION CAT REF
70mm Terminal adaptor (2x25 to 1x70mm) NHPBN25/70
Dolly and padlocking facility NHPCBLDX
Padlock to fit NHPCBPL
1P Terminal Shroud NHPCB1TS
3P Terminal Shroud NHPCB3TS
AUXILIARY EQUIPMENT
Auxiliary Contacts
1 x n.o./n.c. Volt Free NHPCBAU1
2 x n.o./n.c. Volt Free NHPCBAU2
MCB Blanking kit 3x TP Ways 3TPBP
Robust steel enclosures with cable glanding
plate supplied top and bottom
Removable door opens through 180º for
ease of access
Easy access fuse link fixings
Fully rated neutral
Fully shrouded terminals
Handle padlocking facility locks switch &
door in off position
Large cable terminal capacity
Ingress protection to IP4X
Positive indication of On and Off
NH Fuse combination units are designed
with features that ensure full compliance with
EN60947 while also providing an economical
and high quality range of industrial
switchgear products.
With ratings from 20A to 200A and a choice
of single pole or three pole configurations,
NH fuse combination units have a utilisation
category of AC23A, and fused short circuit
capacity of 80kA.
NH FUSE-COMBINATION UNITS
NH FUSE COMBINATION UNIT 20A-32A
20A SP&N NHSPSF20
TP&N NHTPSF20
32A SP&N NHSPSF32
TP&N NHTPSF32
NH FUSE COMBINATION UNIT 63A-125A
63A SP&N NHSPSF63
TP&N NHTPSF63
100A SP&N NHSPSF100
TP&N NHTPSF100
125A TP&N NHTPSF125
Accessories
63A Copper Isolator Link NHCIL2
100A & 125A Copper Isolator Link NHCIL3
63A 100A & 125A Cable Spreader Box NHCSB2
NH FUSE COMBINATION UNIT 160A-400A
160A TP&N NHTPSF160
200A TP&N NHTPSF200
315A TP&N NHTPSF315
400A TP&N NHTPSF400
Accessories
160A & 200A Copper Isolator Links NHCIL3
160A & 200A Cable Spreader Box NHCSB3
315A & 400A Copper Isolator Links NHCIL4
315A & 400A Cable Spreader Box NHCSB4
Fuse Combination Units Technical Specification
EN 60947-3 IEC 947-3
80kA RMS Fused Short Circuit Capacity
AC23A Utilisation Category
415V ac Rated Voltage Full Uninterrupted Duty
NH ISOLATOR SWITCHES STEEL ENCLOSURE
RATING BOX SIZE TP&N/SP&N
20A 1 NHSW320
32A 1 NHSW332
40A 1 NHSW340
63A 1 NHSW363
63A 2 NHSW363X
100A 2 NHSW3100
125A 2 NHSW3125
21
NH Fuse Combination Units & Isolator Switches
supplied with
20A fuses
supplied with
32A fuses
supplied with
63A fuses
supplied with
100A fuses
supplied with
125A fuses
no fuses
supplied
no fuses
supplied
no fuses
supplied
no fuses
supplied
NHSPSF32
NHTPSF63
NHTPSF160
NHSW63X
Spreading Room is allowed for at one end only. To fit a 4 core cable at both ends an additional Cable spreader box will be required.
Above 22mmV cable lugs terminal interphase barriers are required. 1 Module=52.5mm. Contact Wylex Technical Services department for details.
24
Standard Range
INSULATED-SWITCH FUSE
CAT REF CURRENT RATING NO. OF WAYS
104 45A 1
108 60A 1
160C 60A 1
‘C’ models supplied with cartridge fuse
INSULATED-MAIN SWITCH ISOLATOR
CAT REF ISOLATOR RATING NO. OF WAYS
204 45A 2
304 60A 3
404 60A 4
604 100A 6
804 100A 8
METAL-SWITCH FUSE
CAT REF CURRENT RATING NO. OF WAYS
106 45A 1
106RED 45A 1
108M 60A 1
160CM* 60A 1
110M/63* 63A 1
110M/80* 80A 1
110M* 100A 1
*Supplied complete with cartridge fuse
METAL-MAIN SWITCH ISOLATOR
CAT REF ISOLATOR RATING NO. OF WAYS
206 45A 2
306 45A 3
406 60A 4
606 100A 6
104
204
160CM 110M
106 206
25
Standard Range Outgoing Devices & Accessories
MCBs
CAT REF CURRENT RATING CONTACT SHIELD COLOUR
B6 6A WHITE
B10 10A GREY
B16 16A BLUE
B20 20A YELLOW
B32 32A RED
B40 40A ORANGE
CARTRIDGE FUSES (Including contact shield)
CAT REF CURRENT RATING CONTACT SHIELD COLOUR
C5 5A WHITE
C15 15A BLUE
C20 20A YELLOW
C30 30A RED
C35 35A ORANGE
C40 40A ORANGE
C45 45A GREEN
CAT REF CURRENT RATING
L45 45A
L60 60A
CARTRIDGE FUSE LINKS
CAT REF CURRENT RATING CONTACT SHIELD COLOUR
CFL5 5A WHITE
CFL10 10A BLUE
CFL15 15A BLUE
CFL20 20A YELLOW
CFL30 30A RED
CFL35 35A ORANGE
CFL40 40A ORANGE
CFL45 45A GREEN
REWIRABLE FUSES
CAT REF CURRENT RATING CONTACT SHIELD COLOUR
R5 5A WHITE
R15 15A BLUE
R20 20A YELLOW
R30 30A RED
CARTRIDGE FUSE LINKS
CAT REF CURRENT RATING
LFL45 45A
LFL60 60A
LFL63 63A
LFL80 80A
LFL100 100A
ACCESSORIES
CAT REF DESCRIPTION
FC Spare cartridge fuse container
FWC Fusewire card 1m 5A, 15A, 30A
M10 Blank shield for unused ways
B6 B10 B16 B20 B32 B40
C5 C15 C20 C30 C35 C40 C45
R5 R15 R20 R30
M10
}
}
}
for use with 108, 145 & 160
type switch fuses
for use with 108 or 108M
for use with 110M
units only
The Lifeline range of residual
current devices, rcd’s provides
valuable additional protection to
almost any type of installation by
detecting earth fault current below
the level sensed by traditional
overcurrent devices such as fuses of
miniature circuit breakers.
One of the largest ranges available
in the UK today offers other
features which include:-
Fully shrouded terminals
Contact position indication on
the dolly handle
Both Type AC and Type A (DC
sensitive) devices available
A range of enclosures from IP20
upto IP65
Time delay versions available in
2 and 4 pole configurations
LIFELINE RANGE
28
Lifeline Range
2 POLE RCDs – TYPE AC
CAT REF RATED CURRENT SENSITIVITY
WRS16/2 16A 30mA
WRS25/2 25A 30mA
WRS32/2 32A 30mA
WRS40/2 40A 30mA
WRM40/2 40A 100mA
WRS63/2 63A 30mA
WRM63/2 63A 100mA
WRL63/2 63A 300mA
WRS80/2 80A 30mA
WRM80/2 80A 100mA
WRS100/2 100A 30mA
WRM100/2 100A 100mA
WRL100/2 100A 300mA
2 POLE RCDs DC SENSITIVE – TYPE A
CAT REF RATED CURRENT SENSITIVITY
WRDVS16/2 16A 10mA
WRDVS32/2 32A 10mA
WRDS40/2 40A 30mA
WRDM40/2 40A 100mA
WRDS63/2 63A 30mA
WRDS80/2 80A 30mA
WRDS100/2 100A 30mA
WRDM100/2 100A 100mA
4 POLE RCDs – TYPE AC
CAT REF RATED CURRENT SENSITIVITY
WRS32/4 32A 30mA
WRS40/4 40A 30mA
WRM40/4 40A 100mA
WRS63/4 63A 30mA
WRM63/4 63A 100mA
WRL63/4 63A 300mA
WRS100/4 100A 30mA
WRM100/4 100A 100mA
WRL100/4 100A 300mA
4 POLE RCDs DC SENSITIVE – TYPE A
CAT REF RATED CURRENT SENSITIVITY
WRDS40/4 40A 30mA
WRDM40/4 40A 100mA
WRDS63/4 63A 30mA
WRDM63/4 63A 100mA
WRDS100/4 100A 30mA
WRDM100/4 100A 100mA
TIME DELAY UNITS (100ms)
CAT REF DESCRIPTION RATED CURRENT SENSITIVITY
WRMT100/2 2P 100A 100mA
WRMT100/4 4P 100A 100mA
WRS32/2 WRS80/2
WRS100/2 WRM100/2
WRS63/4
WRM100/4
NH METAL DIN ENCLOSURES
CAT REF DESCRIPTION
NH4ED6 4 modules
NH7ED6 7 modules
NH10ED6 10 modules
NH13ED6 13 modules
NH16ED6 16 modules
NH21ED6 21 modules
Supplied with earth & neutral terminal bars cover and visor
IP65 DIN ENCLOSURES AND ACCESSORIES
CAT REF DESCRIPTION
WBE3 2/3 module enclosure
WBE4 4 module enclosure
WBE3/EK Earth block
WBE3/NK Neutral block
WBE4/EK Earth block
WBE3/NK Neutral block
WBE/BS Blanks
WME/FB Wall mounting plate
NH INSULATED DIN ENCLOSURES
CAT REF DESCRIPTION
NH4ED4 4 modules
NH7ED4 7 modules
NH10ED4 10 modules
NH13ED4 13 modules
NH16ED4 16 modules
NH21ED4 21 modules
Supplied with earth & neutral terminal bars cover and visor
NH10ED4
WBE4/NK installed in WBE4
29
Enclosures Range
DIN ENCLOSURES
DIN IP CAT REF CAT REF
MODULES RATING INSULATED METAL
2 IP40 ESE2 ESM6
2 IP40 ESE2L* -
2 IP54 - ESM7
4 IP20 ESE4 -
4 IP40 ESi4 ESM8
4 IP54 - ESM11
4 IP54 - ESM13**
* Supplied with earth connection link
** Larger enclosure for larger cables
ESE2 ESE4
NH13ED6
Wylex provide a range of isolators d
esigned for applications
where local isolation is required. The modular
WS range of
switches can be independently configured to provide a
variety of live and neutral arrangements up to 4 poles.
In addition Wylex offer a range of enclosed
switch disconnector isolators suitable for
commercial and industrial applications
up to 125A.
Rotary isolators can be locked in
the off position and have
facility for up to 3
padlocking devices for
added safety and
security.
SWITCH DISCONNECTORS & ISOLATORS
31
Isolators & Switch Disconnectors
921E
WS102 WS104
TRIPLE POLE & NEUTRAL 415V, 50HZ AC
CAT REF DESCRIPTION CURRENT RATING
921E With switched neutral, surface mounting
in a metal enclosure 32A
921X With switched neutral, for loose mounting
in an enclosure (Non DIN) 32A
WS RANGE OF MODULAR ISOLATORS
CAT REF DESCRIPTION CURRENT RATING
WS601 1 Pole, 1 module 63A
WS101 1 Pole, 1 module 100A
WS121 1 Pole, 1 module 125A
WS602 2 Pole, 2 module 63A
WS102 2 Pole, 2 module 100A
WS122 2 Pole, 2 module 125A
WS603 3 Pole, 3 module 63A
WS103 3 Pole, 3 module 100A
WS123 3 Pole, 3 module 125A
WS604 4 Pole, 4 module 63A
WS104 4 Pole, 4 module 100A
WS124 4 Pole, 4 module 125A
NH ISOLATOR SWITCHES STEEL ENCLOSURE
RATING BOX SIZE TP&N/SP&N
20A 1 NHSW320
32A 1 NHSW332
40A 1 NHSW340
63A 1 NHSW363
63A 2 NHSW363X
100A 2 NHSW3100
125A 2 NHSW3125
NHSW63X
SUPPLY AUTHORITY ISOLATOR ASSEMBLIES
CAT REF DESCRIPTION CURRENT RATING
REC2S Enclosure 100A
REC2 DP Isolator & 4 Mod Enclosure 100A
REC3 TP Isolator & 4 Mod Enclosure 100A
REC4 4P Isolator & 4 Mod Enclosure 100A
A wide range of custom built variations is also available. Contact Wylex
Technical for full details.
REC2S REC4
TECHNICAL DATA
& DIMENSIONS
AC
B
D
E
Maximum
prospective
fault
current
Healthy
circuit
current
Fault
20ms 20ms
AB
GENERAL CONSTRUCTION
Wylex MCBs are of the thermal-magnetic current limiting type, having
a compact construction which has been achieved by not only
minimising the number of parts but also the number of welded joints
and connections. Critical material selection ensures reliability and
durability. Typical of this is the choice of silver graphite for the fixed
contact.
The MCB has an easy to operate handle with a trip-free toggle
mechanism – so even when the handle is held in the ‘on’ position the
MCB is free to trip.
AMBIENT TEMPERATURE CONSIDERATIONS
Wylex MCBs are calibrated to meet the requirements of BS EN 60898,
30°C Ref Calibration Temperature.
At other temperatures the following rating factors should be used:
At 60°C 0.9 At 20°C 1.0 At 0°C 1.1
Adjacent thermal-magnetic MCBs should not be continuously loaded at
or approaching their nominal rated currents when mounted in
enclosures. It is good engineering practice to apply generous derating
factors or make provision for adequate free air between devices.
In these situations, and in common with other manufacturers, we
recommend a 66% diversity factor is applied to the MCB nominal rated
current where it is intended to load the MCBs continuously (in excess
of 1 hour).
METHOD OF OPERATION
1 Moderate overload conditions
Detection of moderate overload conditions is achieved by the use of a
thermo-metal element which deflects in response to the current
passing through it. The thermo-metal element moves against the trip
bar releasing the trip mechanism.
2 Short circuit conditions
When the current flowing through the MCB reaches a predetermined
level, the solenoid directly pulls in the plunger which forcibly separates
the contacts and simultaneously releases the trip mechanism.
3 Establishment of arc between fixed and moving contacts
As the moving contact moves away from the fixed contact, an arc is
established. The arc runs along the arc runner to the arc chamber
where it is split up between the plates and extinguished.
The low inertia and consequent high speed of the moving contact has a
limiting effect on the flow of fault current. The rapid development of
the arc, together with its accelerated extinction in the arc chamber,
gives a typical operating time of 3.5–5 milliseconds.
CURRENT LIMITING ACTION
The high speed current limiting action ensures that the MCB operates
before the full prospective fault current is allowed to develop.
Under fault conditions, damage can be sustained to the installation and
associated equipment due to the amount of energy that passes before
the current is completely interrupted. The total energy let-through
depends on the value of current and the time for which it flows, and is
denoted by the symbol I2t. The high speed current limiting action of
MCBs ensures that the energy let-through and any subsequent damage
is minimised. This reduced energy let-through assists greatly with both
back-up and discrimination considerations.
CURRENT LIMITING EFFECT
MCB INTERNAL VIEW
Maximum
prospective
fault
current
Healthy
circuit
current
Fault
20ms 20ms
Thermo-element
Trip bar
Busbar aperture
Arc chamber
Arc runner
DIN clip
Box terminal
Hammer action solenoid
Moving contact
Fixed contact
Box terminal
33
MCBs - Technical Data
SHORT CIRCUIT CURRENT AS A MULTIPLE OF RATED CURRENT
OPERATING TIME IN SECONDS
2 HRS
1 HR
1,000
100
10
1.0
0.1
0.01
0.001
1 3 5 10 20 100 1,000
Type
B
Type
C
Type
D
34
MCB & RCBO – Technical Data
BACK-UP PROTECTION
Back-up protection is required only if the prospective short circuit
current at the point of installation exceeds the breaking capacity of the
MCB. When providing back-up protection consideration must be given
to discrimination between the MCB and fuse.
DISCRIMINATION
It is desirable that the protective device nearest the fault should
operate first. The low energy let through of modern MCBs provides
better discrimination with HRC fuse back-up than is given by earlier
types of MCBs.
NSB CONSUMER UNIT MCBs
British standards BS EN 60898: 1991
Rated voltage (single pole) 240V
Tripping characteristics Type B
Short circuit rating 6kA
Reference calibration temperature 30°C
Terminal capacity – outgoing cable 0.75 to 25mm2
CAT REF RATING
NSB06 6A
NSB10 10A
NSB16 16A
NSB20 20A
NSB32 32A
NSB40 40A
NSB50 50A
4x102
Prospective short circuit current Ip/A
Let-through I2t (amp2/sec)
103
6810
32346 10
4
8
In=
2
3
4
6
8
104
2
3
4
6
8
105
40 A
32 A
25 A
20 A
16 A
10 A
6 A
50 A
40 A
35 A
32 A
63 A
80 A
100 A
125 A
BS88 FUSE 160A
2
1
HW = 0.01 sec
1
2
min melting pt (pre-arching)
eg In=125A BS 88
max let-through I2t of MCB
eg 6A
1 1.5 2 3 4 5
35
6 8 10 15 20 30
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
Tripping time
Minutes
Seconds
1.13 1.45
7
Multiple of rated current
ac
NSB AND PSB DISTRIBUTION BOARD MCBs
British Standards BSEN 60898 - 1991
Rated Voltage 230/400 Volts
Tripping characteristics Type B, C and D
Short circuit rating 6kA and 10kA
Reference calibration
temperature 30˚C
Terminal capacity -
outgoing cable 0.75 to 25mm2
NSBS & PSBS RCBO (COMBINED MCB/RCD)
British Standards BSEN 61009
Rated Voltage 230 Volts
SP or SP with switched neutral
Tripping characteristics Type C
Short circuit rating 6kA and 10kA
Reference calibration
temperature 30˚C
Rated residual operating
current 30mA
Single module Type A
Two module Type AC
Terminal capacity - 0.5 to 16mm2
outgoing cable
Unique live side busbar combi-terminal allows
connection of cable up to 25mm2
Maximum neutral cable size 25mm2
35
Lifeline Range: RCDs – Technical Data
OPERATION
The RCD employs the current balance principle which involves the
supply conductors to the load (phase and neutral) being wound onto a
common transformer core to form the primary windings.
Under healthy circuit conditions, the current in the phase conductor is
equal to the current in the neutral, and the vector sum of the current
is zero.
In the event of an earth fault, an amount of current will flow to earth,
creating an out of balance situation in the transformer assembly.
This out of balance is detected by the secondary winding of the
transformer and at a pre-determined level of out of balance will
activate the trip mechanism.
Single phase and neutral or three phase and neutral units (suitable for
3 or 4 wire systems) are available, the latter being suitable for balanced
or unbalanced 3 phase loads.
The RCD trip mechanism will operate at a residual current of between
50–100% of its rating tripping current (sensitivity).
TRANSIENT EARTH LEAKAGE CURRENTS
All Wylex residual current devices incorporate a high level of immunity
to tripping when subjected to transient earth leakage currents.
Such transients can occur when there is a significant level of
capacitance to earth as can result from cable capacitance (particularly
MICC) or RF filter networks. Wylex RCDs are therefore less
susceptible to nuisance tripping due to transient earth leakage
currents.
RESIDUAL TRIPPING CURRENTS
10mA
Used in special applications where additional protection against contact
is essential due to the nature of the installation.
30mA
Tripping current designated by the IEE Wiring Regulations to provide
additional protection against direct contact shock, ie socket outside
the equipotential zone. TT systems, caravan installation, etc.
100mA
Suitable for use against indirect contact shock or where protection is
provided to guard against firehazard, etc, rather than to provide
additional protection to personnel, and where the earthing
requirements need supplementing by RCD protection.
100mA time delay
Suitable for use when total RCD protection is required to supplement
the system earthing and where local 30mA RCDs are used to give
additional protection against direct contact. The time delay RCD will
discriminate with the 30mA RCD.
300mA
For use in large installations where plant and equipment protection are
the main considerations and high levels of earth leakage are
experienced.
APPLICATION GUIDE FOR RESIDUAL CURRENT DEVICES
A test button is provided on all RCDs to enable the operation of the
device to be checked.
It is recommended that an RCD is tested regularly.
(See BS 7671 Regulation 514-12-02).
Scope of Protection Application Method Type
All
RCCB controlled
Circuits
consumer unit RCCB
Selected
Split load
Circuits
consumer unit RCCB
Individual
Consumer unit with RCBO controlling
Circuits
individual circuit SP or DP option available RCBO
Individual
Socket
Combined
Outlets
RCD / socket outlet SRCD
Individual
Combined
Appliances
RCD / adaptor PRCD
36
Lifeline Range RCDs – Technical Data
IEC PUBLICATION (479) CURVES WITH WYLEX RCD CHARACTERISTICS SUPERIMPOSED
TIME/CURRENT ZONES OF EFFECT OF AC CURRENT (15–100Hz) ON PERSONS
Zone Physiological effects
1Usually no reaction effects.
2Usually no harmful physiological effects.
3Usually no organic damage to be expected. Likelihood of muscular contraction and difficulty of breathing, reversible disturbances of formation and
conduction of impulses in the heart, and transient cardiac arrest without ventricular fibrillation increases with current magnitude and time.
4In addition to the effects of zone 3, probability of ventricular fibrillation increased up to 5% (Curve C2), up to 50% (Curve C3) and above 50%
beyond Curve C3. Increasing with magnitude and time, pathyphysiological effects such as cardiac arrest, breathing arrest and heavy burns may occur.
FAULT CURRENT SENSITIVITY
Semi-conductor devices are now incorporated in equipment used
throughout industry, commerce and in the home. Typically, the purpose
of these semi-conductor devices is for monitoring and controlling
industrial equipment, eg speed controls for small motors and
temperature controls, along with extensive use in computers, VDUs,
printers, washing machines, etc.
As the equipment is fed from the mains electrical supply, in the event
of an earth fault the presence of semi-conductors may result in the
normal ac waveform being replaced by a non-sinusoidal fault current. In
some cases the waveform may be rectified or chopped. These
waveforms are said to contain a pulsating dc component which can
either partially desensitise or totally disable a standard Type AC RCD.
New International standards IEC 1008 (RCCBs) and IEC 1009
(RCBOs) divide RCDs into two performance classes:
Type AC
RCDs for which tripping is ensured for residual sinusoidal alternating
currents, whether suddenly applied or slowly arising.
Type A
RCDs for which tripping is ensured for residual sinusoidal alternating
currents and residual pulsating direct currents, whether suddenly
applied or slowly arising.
To ensure the correct level of protection, check for the following
symbols:
TYPE AC
normal ac sensitivity
TYPE A
pulsating dc sensitivity
Wylex RCDs are available as both Type AC and Type A devices.
10,000
5,000
2000
1000
500
200
100
50
20
10
0.1 0.2 0.3 0.5 1 2 3 5 10 20 30 50 100 200 300 500 1,000 2,000 10,0005,0003,000
Current in milliamperes (RMS)
100mA30mA
Typical current
Limits due to body resistance
at 230V
1 2 3 4
ab
c1 c2 c3 IEC 479
Time in milliseconds
37
NH Range Dimensions
INSULATED
BOX DIMENSIONS
A=160mm(6.3"),B=117mm(4.6"),C=102mm(4")
4 MODULE
NH204/40 NHRM204/40
NH204/63 NHRM204/63
NHRS204/40 NH4ED4
NHRS204/63
BOX DIMENSIONS
A=230mm(9"),B=187mm(7.5"),C=120mm(4.7")
7 MODULE
NH504 NHRM504
NHRS504 NHTM504
NH7ED4
BOX DIMENSIONS
A=230mm(9"),B=239mm(9.6"),C=120mm(4.7")
10 MODULE
NH804 NHRS3304
NHRS804 NHRS4204
NHRM804 NH504+3
NHSTM2404 NHRS504+3
NHSTM3304 NHRM504+3
NHSTM4204 NHTM804
NHRS2404 NH10ED4
NH11X2404 NH11X3304
BOX DIMENSIONS
A=230mm(9"),B=290mm(11.5"),C=120mm(4.7")
13 MODULE
NH1104 NHRS3604
NHRS1104 NHRS6304
NHRM1104 NHIIX5404
NHSTM3604 NHIIX4504
NHSTM4504 NH804+3
NHSTM5404 NHRS804+3
NHSTM6304 NHRM804+3
NHRS5404 NHTM1104
NHRS4504 NH13ED4
NHRS9SL
BOX DIMENSIONS
A=230mm(9"),B=340mm(13.5"),C=120mm(4.7")
16 MODULE
NH1404 NHRS9304
NHRS1404 NHIIX7504
NHRM1404 NHIIX6604
NHSTM3904 NHIIX5704
NHSTM4804 NHRSX5704
NHSTM5704 NHRSX6604
NHSTM6604 NHRSX7504
NH11X3904 NHTM1404
NH11X4804
NHSTM7504 NH804+6
NHSTM8404 NH1104+3
NHSTM9304 NHRS804+6
NHRS3904 NHRS1104+3
NHRS4804 NHRM804+6
NHRS6604 NHRM1104+3
NHRS5704 NH16ED4
NHRS7504 NHISS5504
NHRS8404
NHRS12SL
BOX DIMENSIONS
A=230mm(9"),B=435mm(17.3"),C=120mm(4.7")
21 MODULE
NH1904 NHRS71004
NHRS1904 NHRS9804
NHRM1904 NHRS8904
NHSTM12504 NHRS51204
NHSTM11604 NHIIX9804
NHSTM8904 NHIIX8904
NHSTM9804 NHRSX8904
NHSTM10704 NHRSX9804
NHSTM71004 NHRS6504+6
NHSTM61104 NHRS5604+6
NHSTM51204 NHRS7704+3
NHRS12504 NHRS8604+3
NHRS11604 NHRS6804+3
NHRS10704 NHTM1904
NHRS61104 NH21ED4
NHRS17SL NHISS8704
NH11X11604
NH11X51204
DUPLEX METAL BOX DIMENSIONS
F=241mm(9.5"), G=160mm(6.3")
NHDIS88 NHDISX88
NHDTMS88 NHDSSX88
NHDIIX88
BOX DIMENSIONS
F=292mm(11.5"), G=210mm(8.3")
NHDIS1111 NHDISX1111
NHDTMS1111 NHDSSX1111
NHDIIX1111
BOX DIMENSIONS
F=343mm(13.5"), G=260mm(10.2")
NHDIS1414 NHDISX1414
NHDTMS1414 NHDSSX1414
NHDIIX1414
BOX DIMENSIONS
F=430mm(17.2"), G=235.7mm(10.1")
NHDIS1919 NHDISX1919
NHDTMS1919 NHDSSX1919
NHDIIX1919
SINGLE METAL
BOX DIMENSIONS
209(H) 117(W) 90(D) 120(D)
4 MODULE
NH206/40 NHRS206/40
NH206/63 NHRS206/63
BOX DIMENSIONS
D=188mm(7.4"), E=107mm(4.2")
7 MODULE
NH506 NHRS506
NHTM506 NHRM506
NH7ED6
BOX DIMENSIONS
D=292mm(11.5"), E=210mm(8.3")
13 MODULE
NHRM1106 NHRS806+3
NHSTM3606 NHRS1106
NH1106 NHRS806+3
NHRS4506 NHRS5406
NHSTM5406 NH13ED6
NH806+3 NHSTM4506
NHRS5406 NHRS6306
NHRS9SLM NHTM1106
NH11X2406 NH11X3306
BOX DIMENSIONS
D=353mm(13.5"), E=260mm(10.2")
16 MODULE
NH1406 NHSTM6606
NHRS1106+3 NHRS3906
NHRS4806 NHSTM7506
NHRS1406 NHRM806+6
NHRM1106+3 NHTM1406
NHRS6606 NHRS12SLM
NHRM1406 NH16ED6
NH806+6 NH1106+3
NHRS7506 NHSTM8406
BOX DIMENSIONS
D=438mm(17.2"), E=235.7mm(10.1")
21 MODULE
NH1906 NHRS1906
NHRS61106 NHRS8906
NHRS9806 NHSTM71006
NHRS17SLM NHSTM9806
NHSTM9806 NHRS5606+6
NH21ED6 NHTM1906
NHSTM8906 NH11X51206
NH11X11606
BOX DIMENSIONS
D=241mm(9.5"), E=160mm(6.3")
10 MODULE
NHRM806 NH806
NH10ED6 NHRS806
NHRS2406 NHSTM2406
NHRS3306 NHSTM3306
NHRS4206 NHTM806
B
A
C
D 121
90
209.5
146
E
F
G
121
90.4
450
295
STANDARDS
Switches BS EN 60947-3. Double pole 240V 50Hz. Category of duty AC21.
Consumer units BS EN 60439-3.
RCDs BS EN 61008. Degree of protection IP2X. RCBOs BS EN 61009.
38
Standard Range – Dimensions
STANDARD RANGE
CAT REF DIMENSIONS Terminal
A B C Capacity
832A 62 76 30 10
860A 57 79 29 25
810X 53 94 77 35
810A 58 170 77 35
810E 76 203 76 35
CAT REF DIMENSIONS Terminal
A B C Capacity
910E 178 305 76 70
921X 72 45 48 10
921E 114 133 61 10
REC2S 78 150 65 50
REC2 100 150 65 50
REC3 100 150 65 50
REC4 100 150 65 50
METAL-MAIN SWITCH ISOLATOR
CAT REF DIMENSIONS
ABC
104 98 121 68
108/160/145 143 178 99
206 140 131 93
306 210 153 99
406 210 153 99
606 293 210 104
CAT REF DIMENSIONS
IP RATING A B
ESE2 IP40 60 153
ESE2L IP20 60 140
WBE3 IP65 85 160
ESI4 IP40 100 150
ESM6 IP40 90 225
ESM7 IP54 90 225
ESE4 IP20 77 140
WBE4 IP65 110 160
ESM11 IP54 120 225
ESM13 IP54 137 318
ESM8 IP40 120 225
INSULATED-MAIN SWITCH ISOLATOR
CAT REF DIMENSIONS
ABC
204 125 120 70
304 190 155 95
404 190 155 95
604 272 186 103
804 323 186 103
METAL-45A AND 60A SWITCHFUSES
CAT REF DIMENSIONS
ABC
106 112 131 80
108M 172 242 98
METAL-100A DOUBLE POLE SWITCHFUSE
CAT REF DIMENSIONS
ABC
110M 178 305 76
110M/80 178 305 76
110M/63 178 305 76
C
A
B
FUSES
A
B
C
A
C
B
A
B
ENCLOSURES
ISOLATORS
39
NH Switch Disconnectors
DIMENSIONS
STEEL ENCLOSURES
BOX A B C D
1 220 158 136 172.5
2 325 158 136 172.5
TECHNICAL INFORMATION
Sheet Steel Enclosure
RATING IN AMPS 20A 32A 40A 63A 63A* 100A 125A
Rated Insulation Voltage Ui (V) 800 800 800 800 800 800 800
Dielectric Strength (kV) 50 Hz 1min 3 3 3 3 3 3 3
Shock Resistance Uimp (kV) 8 8 8 8 8 8 8
OPERATIONAL CURRENT IE (A)
415 V AC - AC21A / AC21B 20 32 40 63 80 100 125
AC22A / AC22B 20 32 40 63 80 100 125
AC23A / AC23B 20 32 40 63 80 80 80
500 V AC - AC21A / AC21B 20 32 40 63 80 100 125
AC22A / AC22B 20 32 40 63 80 100 125
AC23A / AC23B 20 32 40 40 63 63 63
690 V AC - AC20A / AC20B 20 32 40 63 80 100 125
AC21A / AC21B 20 32 40 63 80 100 125
AC22A / AC22B 20 32 40 63 80 100 100
AC23A / AC23B 20 25 25 25 50 50 50
MOTOR POWER (KW) AC 23
415 V AC 7.5 11 11 15 18.5 37 40
500 V AC 7.5 11 15 18.5 22 37 37
690 V AC 11 11 18.5 18.5 25 30 30
FUSE TYPES TO BS88
OVERLOAD CAPACITY
Fuse rating gG 20 32 40 63/40 63 100 125
Short circuit current with
fuses (kA Rms) 50 50 50 20/50 50 20 15
Asymmetric short time
rating current (kA peak) 6 6 6 9 9 9 9
Admissible short time
current 1 s. (kA Rms) 1.26 1.26 1.26 1.5 1.5 1.5 1.5
MAKING & BREAKING CHARACTERISTICS
Breaking capacity (A Rms)
415 V AC 23 A 160 256 320 504 504 640 640
Making capacity (A Rms)
415 V AC 23 A 200 320 400 630 630 800 800
WITHSTAND
Mechanical
(number of operations) x 1000 100 100 100 100 30 30 30
Electrical (number of operations at
415V AC 23A) x 1000 3 3 3 3 1.5 1.5 1.5
CONNECTION
Maximum Cu cable section (mm2) Ith 16 16 16 16 50 50 50
using stranded cable (mm2)
WEIGHT (KG)
3 pole 2.00 2.00 2.00 2.00 2.50 2.50 2.50
4 pole 2.00 2.00 2.00 2.00 2.50 2.50 2.50
A
BC
D
* Box size 2 steel enclosed switch.
Dimensions are overall including screw heads.
40
NH MCB Distribution BoardsNHG125 MCCB Panelboards
Height
A
630
164.5
Height
630
164.5
200A-250A PANEL BOARDS
MODULAR HEIGHT HEIGHT (mm) A(mm) CAT REF
17 902 420 NHPB6SW250
17 902 420 NHPB8SW250
20 1060 420 NHPB12SW250
17 902 420 NHPB6CB200
17 902 420 NHPB8CB200
20 1060 420 NHPB12CB200
400A PANEL BOARDS
MODULAR HEIGHT HEIGHT (mm) A(mm) CAT REF
20 1060 577.5 NHPB6SW400
20 1060 577.5 NHPB8SW400
23 1317 577.5 NHPB12SW400
26 1375 577.5 NHPB16SW400
20 1060 577.5 NHPB6CB400
20 1060 577.5 NHPB8CB400
23 1317 577.5 NHPB12CB400
26 1375 577.5 NHPB16CB400
NH125 MODULAR MCB/DIN ENCLOSURES
MODULAR HEIGHT HEIGHT (mm) CAT REF
4 *210 TO ORDER
8 *420 TO ORDER
* Dimensions for Accessory boxes do not include end plate dimensions, this is because these 2 boxes
are add on units and are supplied without end plates.
The end plate is removed from the panel board, that is connected to the add on unit. Then fitted to
the top of the add on unit.
Top View
Top View
STANDARDS
Switches Multipole: 415V 50Hz
BSEN 60947-3 1992
Category of duty AC22A
MCBs BSEN 60898: 1991
Type B, C and D
Short circuit rating 6 & 10kA
Distribution Boards BS EN 60439-3
Degree of For indoor use only
Protection. (IP3X)
CONSTRUCTION
Wylex NH MCB distribution board
enclosures are fabricated in heavy gauge steel
and are rust protected and highly resistant to
both weathering and mechanical damage.
Incorporated in the distribution boards are
multi-terminal dual earth and neutral bars.
They are designed for ease of installation and
have ample wiring space.
The WYLEX PSB miniature circuit breakers
are rated at 10kA and are of the fault limiting
type.
When a short circuit occurs, the current
operates a solenoid which trips the mechanism
and forces the moving contact away from the
fixed contact. The arc generated is forced into
an arcing chamber which incorporates splitter
plates, to divide and cool it, reducing the total
operating time to less than 5ms, This high
speed operation substantially reduces the ‘let
through’ energy (I2t) keeping additional damage
at the point of the fault to a minimum.
Additionally this allows discrimination with
HRC fuses at high fault levels.
CAT REF DIMENSION
A mm
NHTN4 488.4
NHTN6 569.4
NHTN8 650.4
NHTN12 812.4
NHTN16 893.4
NHTN20 974.4
NHTN24 1136.4
CAT REF DIMENSION
A mm
NHTN40 650.4
NHTN60 811.8
NHTN80 811.8
NHTN120 992.2
NHTN160 992.2
NHTN200 1208.2
NHTN240 1208.2
CAT REF DIMENSIONS
A mm B mm C mm
NHSN5 210 188 105
NHSN8 210 242 105
NHSN11 210 293 105
NHSN14 210 343 105
NHSN16 210 394 105
NHSN19 210 394 105
NH8+3 210 293 105
NH8+6 210 343 105
* Revised models during 2006.
Contact Wylex Technical for Dimensions
*144mm
* including fixing feet which are 3.5mm high
107mm
37mm
430mm
Enclosure Top View
Cover & Door Top View
A
BC
A
125A DISTRIBUTION BOARDS
200A DISTRIBUTION BOARDS
SINGLE PHASE DISTRIBUTION BOARDS
41
NHG Panelboard MCCBs
104
105
I2t
106
107
1,000 10,000
PROSPECTIVE CURRENT
100,000
Phase Ctrs Phase Ctrs
78.50
33.50
70.50
77.50
83.50
97.00 max
Terminals Suitable for
10mm Strip or 70mm2 Cable
Operating Lever Positions
'I' Breaker Closed
'O' Breaker Open
'T' Breaker Tripped by Release
'R' Reset Positions from Tripped
I
T
O
R
26.25
26.25
Use M4
Fasteners
94.00
Fixing Ctrs
Fixing Ctrs
120.00 30.00
26.25
Interphase Barriers
Use M3
Fasteners
19.50
74.00
Fixing Ctrs
Fixing Ctrs
120.00
26.00
MAXIMUM EARTH LOOP IMPEDANCES FOR TRIPLE POLE MCCBS Zs (ohms) for Uo = 240V~
Current Rating (A) 25 32 40 50 63 80 100 125
0.4 Seconds Disconnection Time 0.17Ω 0.17Ω 0.13Ω 0.13Ω 0.13Ω 0.13Ω 0.13Ω 0.13Ω
5.00 Seconds Disconnection Time 0.96Ω 0.75Ω 0.60Ω 0.48Ω 0.38Ω 0.30Ω 0.24Ω 0.19Ω
MAXIMUM EARTH LOOP IMPEDANCES FOR SINGLE POLE MCCBS Zs (ohms) for Uo = 240V~
Current Rating (A) 25 32 40 50 63 80 100 125
0.4 Seconds Disconnection Time 0.43Ω 0.43Ω 0.27Ω 0.27Ω 0.27Ω 0.27Ω 0.17Ω 0.17Ω
5.00 Seconds Disconnection Time 0.96Ω 0.75Ω 0.60Ω 0.48Ω 0.38Ω 0.30Ω 0.24Ω 0.19Ω
NHG MCCBs TECHNICAL SPECIFICATION
NHG MCCB SPECIFICATION
Specification BSEN60947-2
Current Range 25 – 125A
Ue Rated Operation Voltage 240V SP 415V TP
Ui Rated Insulation Voltage 500V AC
Rated Frequency 50/60Hz
Release Thermal Magnetic
Adjustment None
Ambient Range -20°C to 55°C
Humidity Range 0 – 90%
Weight SP - 0.4kg TP - 0.95kg
Mechanical Duration 8000 operations
SHORT CIRCUIT BREAKING CAPACITY
Type GB GN
Ue Icu Icu
SP/TP TP
220 V 30 30
380 V 16 25
415 V 16 25
Ics = 50% Icu
INSTANTANEOUS TRIP BANDS
SP TP
25 – 32A 500A 400A
40 – 80A 800A 600A
100 – 125A 1250A 600A
Non-adjustable ±10%
TERMINALS
Front-connected clamps –
25A to 125A – 70mm2cable
– 10mm strip
AUXILIARY EQUIPMENT
NHG MCCBs
Auxiliary Contact Ratings (A)
Voltage Resistive Tungsten Load Inductive
Load (A)
NC (A) NO (A)
Load (A)
AC
125 3 0.5 0.5 3
250 3 0.5 0.5 3
DC
30 3 3 0.5 3
50 1 0.7 0.7 1
125 0.5 0.4 0.4 0.05
42
MESB Contactors
CONTACTORS
TYPE POWER (W) C(yF) I(A) MESB-20NO MESB-24NO MESB-40NO MESB-63NO
60 - 0.26 23 29 65 85
100 - 0.43 14 16 40 50
Incandescent Lamps 200 - 0.87 7 8 20 25
500 - 2.17 3 3 8 10
1000 - 4.35 1 1 4 5
18 - 0.37 22 24 90 140
Flourescent Lamps 24 - 0.35 22 24 90 140
uncorrected and 36 - 0.43 17 20 65 95
Series correction 58 - 0.67 14 17 45 70
18 - 0.11 2 x 30 2 x 40 2 x 100 2 x 150
Flourescent Lamps 24 - 0.14 2 x 24 2 x 31 2 x 78 2 x 118
lead-lag circuit 36 - 0.22 2 x 17 2 x 24 2 x 65 2 x 95
58 - 0.35 2 x 10 2 x 14 2 x 40 2 x 60
18 4.5 0.12 7 8 48 73
Flourescent Lamps 24 4.5 0.15 7 8 48 73
Parallel correction 36 4.5 0.2 7 8 48 73
58 7 0.32 4 5 31 47
1 x 18 - 0.09 25 35 100 140
1 x 36 - 0.16 15 20 52 75
Flourescent Lamps 1 x 58 - 0.25 14 19 50 72
with electronic 2 x 18 - 0.17 12 17 50 70
ballast units (EVG) 2 x 36 - 0.32 7 10 26 38
2 x 58 - 0.49 7 9 25 36
50 - 0.61 14 18 38 55
80 - 0.8 10 13 29 42
High-pressure 125 - 1.15 7 9 20 29
Mercury-vapour Lamps 250 - 2.15 4 5 10 15
uncorrected 400 - 3.25 2 3 7 10
700 - 5.4 1 2 4 6
1000 - 7.5 1 1 3 4
50 7 0.28 4 5 31 47
80 8 0.41 4 5 27 41
High Pressure 125 10 0.65 3 4 22 33
Mercury-vapour Lamps 250 18 1.22 1 2 12 18
Parallel correction 400 25 1.95 1 1 9 13
700 45 3.45 - - 5 7
1000 60 4.8 - - 4 5
35 - 0.53 18 22 43 60
70 - 1 10 12 23 32
Halogen metal-vapour 150 - 1.8 5 7 12 18
250 - 3 3 4 7 10
Lamps uncorrected 400 - 3.5 3 3 6 9
1000 - 9.5 1 1 2 3
2000 - 16.5 - - 1 1
35 6 0.25 5 6 36 50
70 12 0.45 2 3 18 25
Halogen metal-vapour 150 20 0.75 1 1 11 15
250 33 1.5 - 1 6 9
Lamps Parallel correction 400 35 2.5 - 1 6 8
1000 95 5.8 - - 2 3
2000 148 11.5 - - 1 2
150 - 1.8 5 6 17 22
High-pressure Sodium-vapour 250 - 3 3 4 10 13
Lamps uncorrected 400 - 4.7 2 2 6 8
1000 - 10.3 - 1 3 3
150 20 0.83 1 1 11 16
High-pressure Sodium-vapour 250 33 1.5 - 1 6 10
Lamps parallel 400 48 2.4 - - 4 6
1000 106 6.3 - - 2 3
18 - 0.35 22 27 71 90
35 - 1.5 7 9 23 30
Low-pressure 55 - 1.5 7 9 23 30
Sodium-vapour Lamps 90 - 2.4 4 5 14 19
uncorrected 135 - 3.5 3 4 10 13
180 - 3.3 3 4 10 13
18 5 0.35 6 7 44 66
35 20 0.31 1 1 11 16
Low-pressure 55 20 0.42 1 1 11 16
Sodium-vapour Lamps 90 26 0.63 1 1 8 12
Parallel correction 135 45 0.94 - - 4 7
180 40 1.16 - - 5 8
Thermal Rating per Pole Motor Rating AC3 (kW)
230V 400V
MESB-20NO 20 1.3 -
MESB-24NO 25 2.2 4
MESB-40NO 40 5.5 11
MESB-63NO 63 8.5 15
AC Ratings in accordance with BSEN60947-5-1 and BSEN 60947-4-1
Definitions: AC1 Primarily Resistive Load but may be slightly inductive AC3 Medium-Starting-duty motors, starting and switching off of squirrel-cage motors
43
NH Fuse Combination Units
DIMENSION DETAILS
Ø20 Ø20Ø25
20/32A Gland Plates
All Dimensions in mm
63-100A Gland Plates
Ø25 Ø32
Ø40
WD
D inc handle
H
D
W
Spreader Box
H
HOUSED UNIT DIMENSIONS (mm)
HOUSED UNIT H W D D inc. handle H W D
20-32A
220 210 135 200
63-100A
420 262 188 258 SPREADER BOX 105 262 183
125-200A
525 315 240 273 SPREADER BOX 105 315 210
315-400A
735 420 240 305 SPREADER BOX 210 420 240
FUSE COMPARISON DATA
CURRENT RATING BS 88 REFERENCE LAWSON GEC BUSSMAN
20/32A A1 NIT NIT NITD
63A A3, A2 TIS TIS BAO
100A A4 TCP TCP CEO
125A A4 CTFP TCP DEO
160A A4 CTFP TCP DEO
200A A4 CTFP TCP DEO
315A B3 TKF TKF ED
400A B4, B3, B2,B1 TFM TFM ED
TECHNICAL DATA
20–32A 63A 100A 125A 160A 200A 315A 400A
Mechanical Endurance 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000
Fused s/c Current kA RMS 80 80 80 80 80 80 80 80
Ratings A kW A kW A kW A kW A kW A kW A kW A kW
415V le/pe 32 15 63 30 100 55 125 75 160 90 200 110 315 160 400 220
Isolator links - NHCIL2 NHCIL3 NHCIL3 NHCIL3 NHCIL3 NHCIL4 NHCIL4
SPECIFICATION
BSEN947-3
Range of ratings 20A-400A
Pole configurations SP & N, and TP & N
Voltage rating 415V ac
Frequency rating 50/60 Hz
Fuse type BS88
List No Page No
104 24
106 24
108 24
204 24
206 24
304 24
306 24
404 24
406 24
604 24
606 24
804 24
106 RED 24
108M 24
110M 24
110M/63 24
110M/80 24
145CM 24
160C 24
160CM 24
3TPBP 13
921E 31
921X 31
B10 25
B16 25
B20 25
B32 25
B40 25
B6 25
C15 25
C20 25
C30 25
C35 25
C40 25
C45 25
C5 25
CFL05 25
CFL10 25
CFL15 25
CFL20 25
CFL30 25
CFL35 25
CFL40 25
CFL45 25
EIU 9
ESE2 29
ESE2L 29
ESE4 29
ESM11 29
ESM13 29
ESM6 29
ESM7 29
ESM8 29
FALNH10SL 8
FALNH1106 8
FALNH15SL 8
FALNH706 8
FALNHIIX10SL 8
FALNHRS1106 8
FALNHRS706 8
FC 25
FWC 25
L45 25
L60 25
LFL100 25
LFL45 25
LFL60 25
LFL80 25
M10 25
MAT1 9
MCBLDX 13
MDT2 9
MESB-20NO 9
MESB-24NO 9
MESB-40NO 9
MESB-63NO 9
MSTT-111 9
MSTT-227 9
MSTU6011R 9
MSTU6011S 9
MSTU6112R 9
MSTU8011R 9
MSTU8011S 9
MSTU8112R 9
MTS8 9
List No Page No
NH00 9
NH00 13
NH10ED4 29
NH10ED6 29
NH1104 4
NH1104+3 4
NH1106 6
NH1106+3 7
NH13ED4 29
NH13ED6 29
NH1404 4
NH1406 6
NH16ED4 29
NH16ED6 29
NH1904 4
NH1906 6
NH200TPI 13
NH204/40 4
NH204/63 4
NH206/40 6
NH206/63 6
NH21ED4 29
NH21ED6 20
NH4ED4 29
NH4ED6 29
NH4PINKIT 13
NH504 4
NH504+3 4
NH506 6
NH506+3 7
NH7ED4 29
NH7ED6 29
NH8+3 12
NH8+6 12
NH804 4
NH804+3 4
NH804+6 4
NH806 6
NH806+3 7
NH806+6 7
NHAB 13
NHAB2 13
NHAB3 13
NHAB4 13
NHAB5 13
NHCBDK11 18
NHCBDK12 18
NHCBDK15 18
NHCEKIT 13
NHCEKIT20 13
NHCIL2 21
NHCIL3 21
NHCIL4 21
NHCL 13
NHCSB 17
NHCSB2 21
NHCSB3 21
NHCSB4 21
NHDIIX1111 8
NHDIIX1414 8
NHDIIX1919 8
NHDIIX88 8
NHDIS1111 8
NHDIS1414 8
NHDIS1919 8
NHDIS88 8
NHDISX1111 8
NHDISX1414 8
NHDISX1919 8
NHDISX88 8
NHDPDC 13
NHDSSX1111 8
NHDSSX1414 8
NHDSSX1919 8
NHDSSX88 8
NHDTMS1111 8
NHDTMS1414 8
NHDTMS1919 8
NHDTMS88 8
NHEB 13
NHEP11 13
NHFHDK17 17
NHFHDK20 17
NHG13DB 18
NHGAB 17
List No Page No
NHGPCB1001 19
NHGPCB1003 19
NHGPCB1251 19
NHGPCB1253 19
NHGPCB251 19
NHGPCB253 19
NHGPCB321 19
NHGPCB323 19
NHGPCB401 19
NHGPCB403 19
NHGPCB501 19
NHGPCB503 19
NHGPCB631 19
NHGPCB633 19
NHGPCB801 19
NHGPCB803 19
NHIIX11604 4
NHIIX11606 7
NHIIX2404 4
NHIIX2406 7
NHIIX3304 4
NHIIX3306 7
NHIIX3904 4
NHIIX4504 4
NHIIX4506 7
NHIIX4804 4
NHIIX51204 4
NHIIX51206 7
NHIIX5404 4
NHIIX5406 7
NHIIX5704 4
NHIIX5706 7
NHIIX6604 4
NHIIX6606 7
NHIIX7504 4
NHIIX7506 7
NHIIX8904 4
NHIIX8906 7
NHIIX9804 4
NHIIX9806 7
NHISS3406 8
NHISS4606 8
NHISS5504 8
NHISS5506 8
NHISS8704 8
NHISS8706 8
NHPB12CB200 17
NHPB12CB400 18
NHPB12SW250 17
NHPB12SW400 18
NHPB16CB400 18
NHPB16SW400 18
NHPB6CB200 17
NHPB6CB400 18
NHPB6SW250 17
NHPB6SW400 18
NHPB8CB200 17
NHPB8CB400 18
NHPB8SW250 17
NHPB8SW400 18
NHPBDL 13
NHPCB1TS 19
NHPCB3TS 19
NHPCBAU1 19
NHPCBAU2 19
NHPCBL 19
NHPCBLDX 19
NHRM1104 4
NHRM1104+3 4
NHRM1106 6
NHRM1404 4
NHRM1406 6
NHRM1904 4
NHRM1906 6
NHRM204/40 4
NHRM204/63 4
NHRM206/40 6
NHRM206/63 6
NHRM504 4
NHRM504+3 4
NHRM506 6
NHRM804 4
NHRM804+3 4
NHRM804+6 4
NHRM806 6
List No Page No
NHRS10704 5
NHRS10706 6
NHRS1104 4
NHRS1104+3 4
NHRS1106 6
NHRS1106+3 7
NHRS11604 5
NHRS11606 6
NHRS12504 5
NHRS12506 6
NHRS12SL 5
NHRS12SLM 7
NHRS1404 4
NHRS1406 6
NHRS17SL 5
NHRS17SLM 7
NHRS1904 4
NHRS1906 6
NHRS204/40 4
NHRS204/63 4
NHRS206/40 6
NHRS206/63 6
NHRS2404 5
NHRS2406 6
NHRS3304 5
NHRS3306 6
NHRS3604 5
NHRS3606 6
NHRS3904 5
NHRS3906 6
NHRS4204 5
NHRS4206 6
NHRS4504 5
NHRS4506 6
NHRS4804 5
NHRS4806 6
NHRS504 4
NHRS504+3 4
NHRS506 6
NHRS506+3 7
NHRS51204 5
NHRS51206 6
NHRS5404 5
NHRS5406 6
NHRS5604+6 5
NHRS5606+6 7
NHRS5704 5
NHRS5706 6
NHRS61104 5
NHRS61106 6
NHRS6304 5
NHRS6306 6
NHRS6504+6 5
NHRS6604 5
NHRS6606 6
NHRS6804+3 5
NHRS71004 5
NHRS71006 6
NHRS7504 5
NHRS7506 6
NHRS7704+3 5
NHRS7706+3 7
NHRS804 4
NHRS804+3 4
NHRS804+6 4
NHRS806 6
NHRS806+3 7
NHRS806+6 7
NHRS8404 5
NHRS8406 6
NHRS8604+3 5
NHRS8904 5
NHRS8906 6
NHRS9304 5
NHRS9306 6
NHRS9804 5
NHRS9806 6
NHRS9SL 5
NHRS9SLM 7
NHRSX5704 4
NHRSX5706 7
NHRSX6604 4
NHRSX6606 7
NHRSX7504 4
NHRSX7506 7
44
Numeric Index
Numeric Index
List No Page No
NHRSX8904 4
NHRSX8906 7
NHRSX9804 4
NHRSX9806 7
NHSN111 12
NHSN141 12
NHSN161 12
NHSN191 12
NHSN51 12
NHSN81 12
NHSPAK 13
NHSPSF100 21
NHSPSF20 21
NHSPSF32 21
NHSPSF63 21
NHSTM10704 5
NHSTM10706 7
NHSTM11604 5
NHSTM11606 7
NHSTM12504 5
NHSTM12506 7
NHSTM2404 5
NHSTM2406 7
NHSTM3304 5
NHSTM3306 7
NHSTM3604 5
NHSTM3606 7
NHSTM3904 5
NHSTM3906 7
NHSTM4204 5
NHSTM4206 7
NHSTM4504 5
NHSTM4506 7
NHSTM4804 5
NHSTM4806 7
NHSTM51204 5
NHSTM51206 7
NHSTM5404 5
NHSTM5406 7
NHSTM5704 5
NHSTM5706 7
NHSTM61104 5
NHSTM61106 7
NHSTM6304 5
NHSTM6306 7
NHSTM6604 5
NHSTM6606 7
NHSTM71004 5
NHSTM71006 7
NHSTM7504 5
NHSTM7506 7
NHSTM8404 5
NHSTM8406 7
NHSTM8904 5
NHSTM8906 7
NHSTM9304 5
NHSTM9306 7
NHSTM9804 5
NHSTM9806 7
NHSW3100 21
NHSW3125 21
NHSW320 21
NHSW332 21
NHSW340 21
NHSW363 21
NHSW363X 21
NHTM1104 4
NHTM1106 6
NHTM1404 4
NHTM1406 6
NHTM1904 4
NHTM1906 6
NHTM504 4
NHTM506 6
NHTM804 4
NHTM806 6
NHTN12 12
NHTN120 12
NHTN16 12
NHTN160 12
NHTN20 12
NHTN200 12
NHTN24 12
NHTN240 12
NHTN4 12
List No Page No
NHTN40 12
NHTN6 12
NHTN60 12
NHTN8 12
NHTN80 12
NHTPDC 13
NHTPSF100 21
NHTPSF125 21
NHTPSF160 21
NHTPSF20 21
NHTPSF200 21
NHTPSF315 21
NHTPSF32 21
NHTPSF400 21
NHTPSF63 21
NSB06 9
NSB06-B 14
NSB06-C 14
NSB06-D 14
NSB10 9
NSB10-B 14
NSB10-C 14
NSB10-D 14
NSB16 9
NSB16-B 14
NSB16-C 14
NSB16-D 14
NSB20 9
NSB20-B 14
NSB20-C 14
NSB20-D 14
NSB306-B 14
NSB306-C 14
NSB306-D 14
NSB310-B 14
NSB310-C 14
NSB310-D 14
NSB316-B 14
NSB316-C 14
NSB316-D 14
NSB32 9
NSB320-B 14
NSB320-C 14
NSB320-D 14
NSB32-B 14
NSB32-C 14
NSB32-D 14
NSB332-B 14
NSB332-C 14
NSB332-D 14
NSB340-B 14
NSB340-C 14
NSB340-D 14
NSB350-B 14
NSB350-C 14
NSB350-D 14
NSB363-B 14
NSB363-C 14
NSB363-D 14
NSB40 9
NSB40-B 14
NSB40-C 14
NSB40-D 14
NSB50 9
NSB50-B 14
NSB50-C 14
NSB50-D 14
NSB63-B 14
NSB63-C 14
NSB63-D 14
NSBS10/1 9
NSBS10/2 9
NSBS16/1 9
NSBS16/2 9
NSBS20/1 9
NSBS20/2 9
NSBS32/1 9
NSBS32/2 9
NSBS40/1 9
NSBS40/2 9
NSBS6/1 9
NSBS6/2 9
NSC05 9
NSC10 9
NSC15 9
List No Page No
NSC20 9
NSC30 9
NSC35 9
NSC40 9
NSC45 9
PDDPL 13
PSB06-B 14
PSB06-C 14
PSB06-D 14
PSB10-B 14
PSB10-C 14
PSB10-D 14
PSB16-B 14
PSB16-C 14
PSB16-D 14
PSB206-B 14
PSB206-C 14
PSB206-D 14
PSB20-B 14
PSB20-C 14
PSB20-D 14
PSB210-B 14
PSB210-C 14
PSB210-D 14
PSB216-B 14
PSB216-C 14
PSB216-D 14
PSB220-B 14
PSB220-C 14
PSB220-D 14
PSB232-B 14
PSB232-C 14
PSB232-D 14
PSB240-B 14
PSB240-C 14
PSB240-D 14
PSB250-B 14
PSB250-C 14
PSB250-D 14
PSB263-B 14
PSB263-C 14
PSB263-D 14
PSB306-B 14
PSB306-C 14
PSB306-D 14
PSB310-B 14
PSB310-C 14
PSB310-D 14
PSB316-B 14
PSB316-C 14
PSB316-D 14
PSB320-B 14
PSB320-C 14
PSB320-D 14
PSB32-B 14
PSB32-C 14
PSB32-D 14
PSB332-B 14
PSB332-C 14
PSB332-D 14
PSB340-B 14
PSB340-C 14
PSB340-D 14
PSB350-B 14
PSB350-C 14
PSB350-D 14
PSB363-B 14
PSB363-C 14
PSB363-D 14
PSB40-B 14
PSB40-C 14
PSB40-D 14
PSB50-B 14
PSB50-C 14
PSB50-D 14
PSB63-B 14
PSB63-C 14
PSB63-D 14
PSBL1 13
PSBL3 13
PSBS10/1 15
PSBS10/2 15
PSBS16/1 15
PSBS16/2 15
PSBS20/1 15
List No Page No
PSBS20/2 15
PSBS32/1 15
PSBS32/2 15
PSBS40/1 15
PSBS40/2 15
PSBS50/1 15
PSBS6/1 15
PSBS6/2 15
PSDL 13
PSDPL 13
R15 25
R20 25
R30 25
R5 25
REC2 31
REC2S 31
REC3 31
REC4 31
WBE/BS 29
WBE3 29
WBE3/EK 29
WBE3/NK 29
WBE4 29
WBE4/EK 29
WBE4/NK 29
WME/FB 29
WPL 13
WRDM100/2 28
WRDM100/4 28
WRDM40/2 28
WRDM40/4 28
WRDM63/4 28
WRDS100/2 28
WRDS100/4 28
WRDS40/2 28
WRDS40/4 28
WRDS63/2 28
WRDS63/4 28
WRDS80/2 28
WRDVS32/2 28
WRL100/2 28
WRL100/4 28
WRL63/2 28
WRL63/4 28
WRM100/2 28
WRM100/4 28
WRM40/2 28
WRM40/4 28
WRM63/2 28
WRM63/4 28
WRM80/2 28
WRMT100/2 28
WRMT100/4 28
WRS100/2 28
WRS100/4 28
WRS16/2 28
WRS25/2 28
WRS32/2 28
WRS32/4 28
WRS40/2 28
WRS40/4 28
WRS63/2 28
WRS63/4 28
WRS80/2 28
WS101 31
WS102 13
WS102 31
WS103 13
WS103 31
WS104 13
WS104 31
WS121 31
WS122 13
WS122 31
WS123 13
WS123 31
WS124 13
WS124 31
WS601 31
WS602 31
WS603 31
WS604 31
WSB1 9
45
P44 & 45 29/12/05 11:48 am Page 3
ELECTRIUM SALES LIMITED
Commercial Centre, Lakeside Plaza,Walkmill Lane, Bridgtown, Cannock WS11 0XE.
eMail: info@electrium.co.uk Web: www.electrium.co.uk
UK SALES
Telephone: 01543 455020 Facsimile: 01543 455021 eMail: wylex.sales@electrium.co.uk
TECHNICAL
Telephone: 01543 438320 Facsimile: 01543 438321 eMail: wylex.technical@electrium.co.uk
EXPORT SALES
Telephone: +44 1543 455049 Facsimile: +44 1543 455048 eMail: export@electrium.co.uk
DUBAI OFFICE DUBLIN OFFICE
Telephone: +971 4 2666403 Facsimile:+971 4 2666031 Telephone: +353 1 4513303 Facsimile:+353 1 4513242
Although every effort has been made to ensure accuracy in the compilation of the technical detail within this publication, specifications and performance data are constantly changing. Latest details can be obtained from Wylex.
Publication No.WY 2001
Printed in England.