Nitra NCP1
Series

Electropneumatic Transducer (I/P)
Installation, Operation and
Maintenance Instructions

Ordering Information

Contents

NCP1 Series I/P Transducers
Part Number

Input

NCP1-20-315N

Output Range
psig

bar

4-20 mA

3-15

0.2-1.0

NCP1-20-327N

4-20 mA

3-27

0.2-1.9

NCP1-20-630N

4-20 mA

6-30

0.4-2.0

NCP1-20-260N

4-20 mA

2-60*

0.14-4.0

NCP1-20-3120N

4-20 mA

3-120*

0.2-8.0

* Output shown is as calibrated at the factory. Large span adjustment capability
allows recalibration to achieve output ranges from 3-35 psig (0.2-2.4 bar) with
2-60 psig unit to 3-145 psig (0.2-10 bar) with 3-120 psig unit.

Section

Description				Page

1.0		

Description & Installation		

2

2.0		Operation				3
3.0		Approvals				5
4.0		Maintenance				5
5.0		Troubleshooting			6
6.0		Warranty				6

AutomationDirect
3505 Hutchinson Road
Cumming, GA 30040
1-800-633-0405
NCP1 Series

Page 1

DANGER, WARNING, CAUTION and NOTE statements
DANGER

Refers to conditions or hazards which could result in serious personal injury or death.

WARNING

Refers to conditions or hazards which could result in personal injury.

CAUTION

Refers to conditions or hazards which could result in equipment or property damage.

NOTE

Alerts you to facts or special instructions.

ALL DANGER, WARNING, AND CAUTION NOTICES MUST BE COMPLIED WITH IN FULL

SPECIFICATIONS
Part No.

NCP1-20-315N

NCP1-20-327N

NCP1-20-630N

NCP1-20-260N

NCP1-20-2130N

Functional Specifications
Input

4-20 mA

Outputs (psig - BAR)
Supply Pressure (psig - bar)

3-15* (0.2-1.0)

3-27 (0.2-1.8)

6-30 (0.4-2.0)

2-60 (0.14-4.0)

3-120 (0.2-8.0)

18 min -100 max
(1.2 min - 6.7 max)

30 min - 100 max
(2.0 min - 6.7 max)

33 min - 100 max
(2.2 min - 6.7 max)

65 min - 150 max
(4.3 min - 10.0 max)

125 min - 150 max
(8.3 min - 10.0 max)

Air Consumption

0.05 scfm (1.4 Nl/min) midrange typical

0.07 scfm (2 Nl/min) midrange typical

Flow Capacity

4.5 scfm (127 Nl/min) at 25 psig (1.7 BAR) supply
12.0 scfm (340 Nl/min) at 100 psig (6.8 BAR) supply

20.0 scfm (566 Nl/min) at
150 psig (10.5 BAR) supply

Relief Capacity

2 scfm (56.6 Nl/min) at 5 psig (2.4 BAR) above 20 psig (1.3 BAR) setpoint

7 scfm (198 Nl/min) at 10 psig (0.7 BAR) above 20 psig (1.3
BAR) setpoint

Temperature Limits
Impedance

-20°F to +140°F (-30°C to +60°C)
180 Ohms

220 Ohms

220 Ohms

225 Ohms

260 Ohms

Performance Specifications
Linearity

<± 0.75% of span

<± 1.5% of span typical, ± 2.0% max.

Hysteresis and Repeatability

< 1.0% of span; < 0.5% of span

< 0.5% of span; < 0.5% of span

Supply Pressure Sensitivity

<± 0.1% of span per psig (<± 0.15% of span per 0.1 BAR)

<± 0.04% of span per 1.0 psig (0.07 BAR)

Physical Specifications
Pneumatic Port Sizes

1/4” NPT female

Media

Oil free, clean dry air filtered to 40 micron

Electrical Connections

Conduit 1/2” NPT female with 12” wire leads

Mounting

Direct or bracket (bracket included)

Housing

Chromate-treated aluminum with epoxy paint. NEMA 4X (IP65)

Elastomers

Buna-N

Trim

Stainless steel; brass; zinc-plated steel

Weight

2.1 lbs. (0.94 kg)

Approvals

FM (Haz-Loc)**

* Can be recalibrated to provide 3-9 psig or 9-15 psig for split ranging applications.
** To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

1. DESCRIPTION and INSTALLATION
1.1 Description
1.1.1 The NITRA NCP1 Series converts a current input signal to a linearly proportional pneumatic output pressure. This versatile
instrument is designed for control applications that require a high degree of reliability and repeatability at an economical cost.

NCP1 Series

Page 2

1.2 Principle of Operation
1.2.1 The NITRA NCP1 Series is a force balance device in which a coil is suspended in the field of a magnet by a flexure. Current
flowing through the coil generates axial movement of the coil and flexure. The flexure moves towards the nozzle and creates
back pressure which acts as a pilot pressure to an integral booster relay. Input signal increases cause proportional output
pressure increases.
Zero and Span are calibrated by turning adjust screws on the front face of the unit. Adjustment of the zero screw repositions
the nozzle relative to the flexure. The span adjustment is a potentiometer that controls the amount of current through the coil.

1.3 Mounting
1.3.1 Unit may be pipe, panel, or bracket mounted. Mounting may be at any angle, though may require field adjustment. High
external vibration may cause output fluctuations. Mounting in a vibration-free area is recommended.

1.4 Pneumatic Connections
1.4.1 The 1/4” NPT supply and output ports are marked “IN” and “OUT” respectively on the base of the unit. Clean all pipe lines
to remove contamination before installation. If thread sealer is required, use a tape type that is compatible with the media.
Liquid or paste type thread sealer is not recommended.
Clean dry instrument quality air must be used. To insure optimum performance supply pressure should be regulated. To
provide stable inlet pressure and prevent contamination of the internal section of the transducer the use of an Instrument Air
Filter Regulator is recommended.
The two unmarked ports on the base of the unit are gauge ports but may be used as alternative output ports. Any unused ports
must be plugged.
WARNING

 he I/P transducer enclosure contains aluminum and is considered to constitute a potential risk of ignition by
T
impact or friction and must be taken into account during installation.

1.5 Electrical Connections
1.5.1 Electrical connections are made to the black and white leads extending out from the 1/2” NPT conduit fitting.

Black = Positive
4-20 mA
White = Negative

		

2. OPERATION
2.1 Calibration
2.1.1 Zero and Span should always be checked after mounting. If unit is calibrated in a vertical position and then mounted at an
angle, readjustment of the zero is necessary. To calibrate use the following procedure:
		
		
		
		

1. Open protective covers to expose zero and span adjustment screws.
2. Connect the recommended air supply to the inlet of the transducer and an accurate pressure gauge to the outlet.
3. Connect the electrical input and set the input signal to 4mA.
4. Observe the output pressure. If necessary, adjust the zero screw until reaching minimum output pressure setting. Turn
zero screw counter clockwise to increase pressure, clockwise to decrease pressure.
NOTE

		

I f unable to achieve output during calibration process, follow the steps outlined in 4.1.4 to clean the orifice. Then
turn zero adjustment screw counter clockwise for up to 30 revolutions, until output pressure rises.
5. Increase electrical input signal to 20mA.

NCP1 Series

Page 3

		

6. Observe the output pressure. If necessary adjust the span screw until reaching maximum output pressure setting.
NOTE

		

 or I/P (current) input models turn span screw counter clockwise to increase pressure, clockwise to decrease
F
pressure.
7. The Zero and Span adjustments are interactive. After adjusting the span it will be necessary to recheck the zero.
Repeat steps 3-6 until both end points are at the required values.

		

2.2 Dimensional Drawings (Dimensions are inches [mm])

NCP1 Series

Page 4

3. APPROVALS
3.1 Intrinsically Safe Operation

4. MAINTENANCE
NOTE

Under normal circumstances, no maintenance should be required.

4.1 Instrument Air Filtration
4.1.1 Failures due to instrument supply air contamination are not covered by warranty.
4.1.2 Use of oil and/or water saturated instrument air can cause erratic operation.
4.1.3 Poor quality instrument air can result in unit failure. It is recommended that a filter regulator be placed upstream of each unit
where oil and/or water laded instrument air is suspected.
4.1.4 If clean, dry air is not used the orifice can become blocked. To clean, first turn off supply air, unscrew and remove orifice
assembly (large silver screw head located above the out port). Then unplug orifice by using a wire that has a smaller diamter
than 0.015 in. (0.38 mm). Use compressed air to blow out any loose particles inside the orifice assembly. Screw orifice
assembly back into unit.

NCP1 Series

Page 5

5. TROUBLESHOOTING

Problem

Look For

Solution

Zero adjustment
Supply pressure too low

Reset zero (2.1)
Increase supply pressure (see specs)

Electrical connection
Clogged orifice

Check connection/signal (1.5.1)
Clean orifice (3.1.3)

Erratic operation

Liquid/contamination in air supply

Clean air supply (1.4.4)

Works in reverse

Pressure goes down when signal
is increased

Reverse input wires (1.5.1)

Output equals supply
pressure

Insure that supply is connected to “IN” port and
Improper pneumatic connections
output is connected to “OUT” port (1.4.1)

No output or low output
Unstable / low output

Bonnet

Circuit Board
O-Ring

Lead Wire

O-Ring

Spacer

Pintle Spring
Bottom Plug

NOTE

Body Subassembly

Pilot Pressure

Supply Pressure

Atmospheric Pressure

Output Pressure

I f problems are not solved by troubleshooting procedures, contact AutomationDirect.com technical support
for further assistance at 770-844-4200.

6. WARRANTY & DISCLAIMER
See AutomationDirect.com for latest Terms & Conditions
WARNING

 hese products are intended for use in industrial compressed-air systems only. Do not use these products where
T
pressures and temperatures can exceed those listed under Specifications. Not for oxygen service.

NCP1 Series

Page 6



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Author                          : AutomationDirect
Create Date                     : 2017:07:10 09:15:24-04:00
Modify Date                     : 2017:07:10 09:36:45-04:00
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.4-c006 80.159825, 2016/09/16-03:31:08
Format                          : application/pdf
Title                           : Chapter 1 - Getting Started
Creator                         : AutomationDirect
Metadata Date                   : 2017:07:10 09:36:45-04:00
Creator Tool                    : Adobe InDesign CC 2014 (Windows)
Instance ID                     : uuid:14a97562-eac1-473d-b9fd-2c4839109cb5
Original Document ID            : xmp.did:AC8300A79C14E311B497E908AC6DEAF6
Document ID                     : xmp.id:9da14895-0176-e149-8436-97d239b2a555
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:4cd8d032-b471-bb43-98da-674e40c5146e
Derived From Document ID        : xmp.did:4cd8d032-b471-bb43-98da-674e40c5146e
Derived From Original Document ID: xmp.did:AC8300A79C14E311B497E908AC6DEAF6
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC 2014 (Windows)
History Changed                 : /
History When                    : 2017:07:10 09:15:25-04:00
Authors Position                : C-more Micro Panel EA3 Series
Producer                        : Adobe PDF Library 11.0
Trapped                         : False
Page Count                      : 6
EXIF Metadata provided by EXIF.tools

Navigation menu