Output Specifications

2000

Outputs per Module
Voltage Rating
Operating Voltage Range
Maximum Output Current

16 sourcing
24VDC
21.6-26.4 VDC
0.25 A continuous

On Voltage Drop

0.7 VDC

Maximum Inrush Current
OFF to ON Response
ON to OFF Response
Overcurrent Trip

Self-limited
0.5 ms
0.5 ms
0.6 A min., 1.2 A max.

Minimum Load Current to Avoid Open
Load Fault Detection

113µA

Overtemperature Shutdown
Load Resistance to Avoid Open Load
Fault Detection
Status Indicators
External 24V Error Indicator
Fault Condition Indicator
Commons
Fuses
External DC Power Required

Document Name
P2-16TD2P-DS

Independent to each output
<58kΩ
Logic Side (16 points)
Logic Side (1 point)
Logic Side (16 points)
1
None
24VDC @ 55mA (not including 0.25 A
per point)

Edition/Revision
1st Ed.

Date
3/16/2015

Copyright 2015, AutomationDirect.com Incorporated/All Rights Reserved Worldwide

Sales 800-633-0405

P2-16TD2P Sourcing
Protected DC Output
The P2-16TD2P DC Output Module
provides sixteen 24 VDC sourcing
outputs with short-circuit and overload
protection for use with the Productivity2000
System.
Output Specifications................................................ 1
Module Installation.................................................... 2
Wiring Options........................................................... 2
Wiring Diagram and Schematic................................. 3
QR Code................................................................... 3
Hot Swap Information................................................ 3
Warning..................................................................... 4
Removable Terminal Block
Specifications............................................................ 4
General Specifications.............................................. 4
LED Status................................................................ 4

Terminal Block sold separately, (see wiring options on page 2).
Warranty: Thirty-day money-back guarantee. Two-year limited replacement.
(See www.productivity2000.com for details).

www.productivity2000.com

1

Module Installation

Wiring Options

WARNING: Do not apply field power until
the following steps are completed. See
hot-swapping procedure for
exceptions.

­

1

2 rotate
to seated
position

ZIPLink Connection System
Cable + ZIPLink Module = Complete System
ZIPLink pre-wired
terminal block cables
0.5 m (1.6 ft) cable
1.0 m (3.3 ft) cable
2.0 m (6.6 ft) cable

Step One: Align module

catch with base slot and
rotate module into
connector.

1 Align
with slot

Step Two: Pull top locking tab
toward module face. Click indicates lock is
engaged.

ZIPLink Modules
Feed through

Locked

Terminal Block with pigtail cable

1.0 m (3.3 ft) cable
2.0 m (6.6 ft) cable

Step Three: Attach field wiring using the removable
terminal block or ZIPLink wiring
system.
WIRE STRIP
LENGTH

www.productivity2000.com

ZL-RTB20

Unlocked

2

2

ZL-P2-CBL18
ZL-P2-CBL18-1
ZL-P2-CBL18-2

3
4

Screw Terminal Block only

Spring Clamp Terminal Block only

Tech Support 770-844-4200

ZL-P2-CBL18-1P
ZL-P2-CBL18-2P

P2-RTB
(Quantity 1)

P2-RTB-1
(Quantity 1)

Wiring Diagram and Schematic
Source

+24V

QR Code

INTERNAL MODULE
DIGITAL
ISOLATION

+24VDC

L
COM

1

3

2

4

3

5

4

6

5

7

6

8

7

9 10 11 12 13 14 15 16 17 18

L
L
L
L
L
L
L
L

24V

2

L
L
L
L
L
L
L
L

1

24VDC
–
+

Sales 800-633-0405

8
COM
9
10
11
12
13
14
15
16

Use any QR Code reader application
to display the module’s product insert.

Caution: If possible, remove field power prior to
proceeding. If not, then EXTREME care MUST be taken
to prevent damage to the module, or even personal injury
due to a short circuit from the live terminal block.
Important Hot-Swap Information
The Productivity2000 supports hot-swap! Individual
modules can be taken offline, removed, and replaced
while the rest of the system continues controlling your
process. Before attempting to use the hot-swap feature,
be sure to read the hot-swap topic in the programming
software’s help file or our online documentation at
AutomationDirect.com for details on how to plan your
installation for use of this powerful feature.

www.productivity2000.com

3

WARNING: To minimize the risk of potential safety problems, you
should follow all applicable local and national codes that regulate
the installation and operation of your equipment. These codes vary
from area to area and it is your responsibility to determine which
codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of
these codes.
Equipment damage or serious injury to personnel can result
from the failure to follow all applicable codes and standards. We
do not guarantee the products described in this publication are
suitable for your particular application, nor do we assume any
responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please
call Technical Support at 770-844-4200.
This publication is based on information that was available at
the time it was printed. At AutomationDirect.com® we constantly
strive to improve our products and services, so we reserve the right
to make changes to the products and/or publications at any time
without notice and without any obligation. This publication may also
discuss features that may not be available in certain revisions of
the product.

Removable Terminal Block Specifications
Part Number
Number of
Positions
Wire Range
Conductors
Screw Driver
Width
Screw Size
Screw Torque

4

P2-RTB

P2-RTB-1

18 Screw Terminals

18 Spring Clamp Terminals

30-16 AWG (0.051 - 1.31 mm²)
28-16 AWG (0.081 - 1.31 mm²)
Solid / Stranded Conductor
Solid / Stranded Conductor
3/64 in. (1.2 mm) Insulation Maximum 3/64 in. (1.2 mm) Insulation Maximum
1/4 in. (6-7 mm) Strip Length
19/64 in. (7-8 mm) Strip Length
“USE COPPER CONDUCTORS, 75°C” or Equivalent.
1/8 inch (3.8 mm) Maximum
M2
2.5 lb·in (0.28 N·m)

www.productivity2000.com

N/A
N/A

General Specifications
Operating Temperature
Storage Temperature
Humidity
Environmental Air
Vibration
Shock
Field to Logic Side Isolation
Insulation Resistance
Heat Dissipation
Enclosure Type

Module Keying to Backplane

0° to 60°C (32° to 140°F),
-20° to 70°C (-4° to 158°F)
5 to 95% (non-condensing)
No corrosive gases permitted
IEC60068-2-6 (Test Fc)
IEC60068-2-27 (Test Ea)
1800VAC applied for 1 second
>10MΩ @ 500VDC
2.6W
Open Equipment
UL508 file E139594, Canada & USA
CE (EN61131-2*)
Electronic

Module Location

Any I/O slot in a Productivity2000 System.

Agency Approvals

Use ZIPLink Wiring System or removable terminal
block (not included). See “Wiring Options” on
page 2.
See the “EU Directive” topic in the
EU Directive
Productivity2000 Help File. Information can also be
obtained at: www.productivity2000.com
Connector Type (not included) 18 Position Removable Terminal Block
Weight
90g (3.2oz)
Field Wiring

*Meets EMC and Safety requirements. See the D.O.C. for details.

LED Status
Fault Condition
Fault Status Indication
Missing External 24VDC V1 LED is ON
Open Load (Note 1)
F LED is ON (Note 2)
Over Temperature or
Over Load Current

Operation to Reset Fault
Apply external 24 VDC
Connect the load
Turn the output OFF or
cycle power

Note 1: O
 pen Load Fault is always enabled, but is only valid when output is OFF. If Open
Load Fault happens while output is ON, fault will not appear until you turn OFF
output.
Note 2: The SEL button cycles between the output status and fault status. If the “F” LED is
OFF the numbered LEDs are showing output status. If the “F” LED is ON the
numbered LEDs are showing fault status of each output. The “V1” LED is
independent of fault or output display.

Tech Support 770-844-4200



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Create Date                     : 2015:03:16 11:24:19-04:00
Metadata Date                   : 2015:03:16 11:24:48-04:00
Modify Date                     : 2015:03:16 11:24:48-04:00
Creator Tool                    : Adobe InDesign CC (Windows)
Instance ID                     : uuid:82d83ab6-bab8-4345-8acd-fd6bf68cb766
Original Document ID            : xmp.did:4CC8A9817BEDE311AD9E8A5FA38FC23B
Document ID                     : xmp.id:f05978bb-235a-254c-887e-bc20e51e8d9e
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:f1d9d565-ee70-634f-8130-e2dfb3298b4d
Derived From Document ID        : xmp.did:047BBF606CFCE311B967B674276BA900
Derived From Original Document ID: xmp.did:4CC8A9817BEDE311AD9E8A5FA38FC23B
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC (Windows)
History Changed                 : /
History When                    : 2015:03:16 11:24:19-04:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 11.0
Trapped                         : False
Page Count                      : 4
Creator                         : Adobe InDesign CC (Windows)
EXIF Metadata provided by EXIF.tools

Navigation menu