Wiring

User Manual: wiring HPS Imperator Instruction Sheets - AutomationDirect

Open the PDF directly: View PDF PDF.
Page Count: 9

The HPS Im p e r a t o r t m series of machine tool industrial molded control transformers are available in many standard offerings. This
wiring hook-up instruction sheet refers to all standard HPS Im p e r a t o r t m series part number sufxes. (Note: standard econdary fuse kits (not
installed) supplied with each transformer unless otherwise indicated; eld insatlled primary fuse kits sold separately; fuses not available from HPS.)
If you have any questions regarding these wiring diagrams or are having any difculty correctly installing our transformers, please
contact HPS customer service or technical support in the U.S. at 1-866-705-4684 or in Canada at 1-888-798-8882.
HPS Im p e r a t o r t m
Industrial Control Transformer
Wiring Diagrams
Issue Date: October 2007 rev4 Page 1 of 9
Literature Code: PHWD1-2
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings
4
1
4321
2 134
6
67
4 3 12
5
58
HV
L V
1 2 43
575V
600V
550V
115V 230V
120V 240V
110V 220V
5
2
5432
3 2456 1
1
16
56 4 2 13
7
78
L V
21 3 4
HV
5 6
575V
600V
550V
115V 230V
120V 240V
110V 220V
PH***AJ Schematic for 50, 75 and 100VA Units
PH***AJ Schematic for 150VA to 1500VA Units
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
(Primary Volts) Links Between Terminals Connect To Clips To
600 575 550 None 1, 4 Unfused
600 575 550 None 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
120 115 110 3-4, 1-2 4, 6 1-5
240 230 220 2-3 4, 6 1-5
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
(Primary Volts) Links Between Terminals Connect To Clips To
600 575 550 None 2, 5 Unfused
600 575 550 None 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 4-5, 2-3 1, 5 2-7
240 230 220 3-4 1, 5 2-7
Page 2 of 9
1
2
3
4
1234
4 3 12
67
6
1 2 43
8
5
5
3 421
2 134
HV
L V
230V 460V
240V 480V
220V 440V
115V 230V
120V 240V
110V 220V
PH***MQMJ Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
240 230 220 1-2, 3-4 1, 4 Unfused
480 460 440 2-3 1, 4 Unfused
240 230 220 1-2, 3-4 6, 7 1-5, 4-8
480 460 440 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
120 115 110 3-4, 1-2 4, 6 1-5
240 230 220 2-3 4, 6 1-5
PH***MQMJ Schematic for 150VA to 1500VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
240 230 220 2-3, 4-5 2, 5 Unfused
480 460 440 3-4 2, 5 Unfused
240 230 220 2-3, 4-5 1, 6 2-7, 5-8
480 460 440 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 4-5, 2-3 1, 5 2-7
240 230 220 3-4 1, 5 2-7
2
3
4
5
2345
16
1
8
7
7
3 2456 1 56 4 2 13
L V
21 3 4
HV
5 6 21 3 4 5 6
230V 460V
240V 480V
220V 440V
115V 230V
120V 240V
110V 220V
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
1
2
3
4
1234
4 3 12
67
6
1 2 43
8
5
5
3 421
2 134
HV
L V
115V 230V
120V 240V
110V 220V
11.5V 23V
12V 24V
11V 22V
PH***PG Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
120 115 110 1-2, 3-4 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
120 115 110 1-2, 3-4 6, 7 1-5, 4-8
240 230 220 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 3-4, 1-2 1, 4 Unfused
24 23 22 2-3 1, 4 Unfused
12 11.5 11 3-4, 1-2 4, 6 1-5
24 23 22 2-3 4, 6 1-5
Page 3 of 9
PH***PG Schematic for 150VA to 500VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
120 115 110 2-3, 4-5 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 2-3, 4-5 1, 6 2-7, 5-8
240 230 220 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 4-5, 2-3 2, 5 Unfused
24 23 22 3-4 2, 5 Unfused
12 11.5 11 4-5, 2-3 1, 5 2-7
24 23 22 3-4 1, 5 2-7
2
3
4
5
2345
1
21 3 5 64
8
7
7
3 2 1456
16
HV
L V
115V
120V
110V
11.5V
12V
11V
21 3 5 64
230V
240V
220V
3 2 1456
23V
24V
22V
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
PH***PG Schematic for 750VA and 1000VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
120 115 110 2-3, 4-5 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 2-3, 4-5 1, 6 2-7, 5-8
240 230 220 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 3-4, 1-2 1, 4 Unfused
24 23 22 2-3 1, 4 Unfused
1
2
3
4
2345
21 3 5 64
8
7
16
HV
L V
115V
120V
110V
21 3 5 64
230V
240V
220V
2 134
11.5V
12V
11V
2 134
23V
24V
22V
Note: secondary fuse clips not available on PH750PG or PH1000PG.
1
3
64
7
2
3
4
1
6
5
8
5
HV
L V
Dotted line represents
supplied jumper lead.
480V/460V/440V
240V/230V/220V
208V/200V
25V/24V/23V
120V/115V/110V
PH***MLI Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
480 460 440 None 1, 3 Unfused
240 230 220 None 1, 7 Unfused
208 200 None 1, 2 Unfused
480 460 440 3-8 6, 4 1-5, 4-8
240 230 220 8-7 6, 4 1-5, 4-8
208 200 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 None 1, 4 Unfused
25 24 23 None 1, 3 Unfused
120 115 110 None 4, 6 1-5
25 24 23 None 3, 6 1-5
Page 4 of 9
PH***MLI Schematic for 750VA and 1000VA Units
2
6
15
4
3
2
4
1
7
8
Dotted line represents
supplied jumper lead.
L V
HV
480V/460V/440V
240V/230V/220V
208V/200V
25V/24V/23V
120V/115V/110V
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
480 460 440 None 2, 6 Unfused
240 230 220 None 2, 4 Unfused
208 200 None 2, 3 Unfused
480 460 440 8-6 1, 5 2-7, 5-8
240 230 220 4-8 1, 5 2-7, 5-8
208 200 3-8 1, 5 2-7, 5-8
Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 None 1, 4 Unfused
25 24 23 None 1, 2 Unfused
Note: secondary fuse clips for 24V tap not available on the PH750MLI or PH1000MLI units.
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
PH***MLI Schematic for 150VA to 500VA Units
2
6
15
4
3
3
4
2
1
7
8
7
Dotted line represents
supplied jumper lead.
L V
HV
480V/460V/440V
240V/230V/220V
208V/200V
25V/24V/23V
120V/115V/110V
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
480 460 440 None 2, 6 Unfused
240 230 220 None 2, 4 Unfused
208 200 None 2, 3 Unfused
480 460 440 8-6 1, 5 2-7, 5-8
240 230 220 4-8 1, 5 2-7, 5-8
208 200 3-8 1, 5 2-7, 5-8
Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 None 2, 4 Unfused
25 24 23 None 2, 3 Unfused
120 115 110 None 1, 4 2-7
25 24 23 None 1, 3 2-7
4
1
4321
2 134
6
67
4 3 12
5
58
HV
L V
1 2 43
575V
600V
550V
11.5V 23V
12V 24V
11V 22V
PH***AR Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
(Primary Volts) Links Between Terminals Connect To Clips To
600 575 550 None 1, 4 Unfused
600 575 550 None 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 3-4, 1-2 1, 4 Unfused
24 23 22 2-3 1, 4 Unfused
12 11.5 11 3-4, 1-2 4, 6 1-5
24 23 22 2-3 4, 6 1-5
Page 5 of 9
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
5
2
5432
3 2456 1
1
16
56 4 2 13
7
78
L V
21 3 4
HV
5 6
575V
600V
550V
11.5V 23V
12V 24V
11V 22V
PH***AR Schematic for 150VA to 500VA Units
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
(Primary Volts) Links Between Terminals Connect To Clips To
600 575 550 None 2, 5 Unfused
600 575 550 None 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 4-5, 2-3 2, 5 Unfused
24 23 22 3-4 2, 5 Unfused
12 11.5 11 4-5, 2-3 1, 5 2-7
24 23 22 3-4 1, 5 2-7
1
2
3
4
1234
4 3 12
67
6
1 2 43
8
5
5
3 421
2 134
HV
L V
230V 460V
240V 480V
220V 440V
11.5V 23V
12V 24V
11V 22V
PH***QR Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
240 230 220 1-2, 3-4 1, 4 Unfused
480 460 440 2-3 1, 4 Unfused
240 230 220 1-2, 3-4 6, 7 1-5, 4-8
480 460 440 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 3-4, 1-2 1, 4 Unfused
24 23 22 2-3 1, 4 Unfused
12 11.5 11 3-4, 1-2 4, 6 1-5
24 23 22 2-3 4, 6 1-5
PH***QR Schematic for 150VA to 500VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
240 230 220 2-3, 4-5 2, 5 Unfused
480 460 440 3-4 2, 5 Unfused
240 230 220 2-3, 4-5 1, 6 2-7, 5-8
480 460 440 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 4-5, 2-3 2, 5 Unfused
24 23 22 3-4 2, 5 Unfused
12 11.5 11 4-5, 2-3 1, 5 2-7
24 23 22 3-4 1, 5 2-7
2
3
4
5
2345
16
1
8
7
7
3 2456 1 56 4 2 13
L V
21 3 4
HV
5 6 21 3 4 5 6
230V 460V
240V 480V
220V 440V
11.5V 23V
12V 24V
11V 22V
Page 6 of 9
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
1
2
3
4
1234
4 3 12
67
6
1 2 43
8
5
5
3 421
2 134
HV
L V
200V 400V
208V 416V
190V 380V
115V 230V
120V 240V
110V 220V
PH***SP Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
208 200 190 1-2, 3-4 1, 4 Unfused
416 400 380 2-3 1, 4 Unfused
208 200 190 1-2, 3-4 6, 7 1-5, 4-8
416 400 380 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
120 115 110 3-4, 1-2 4, 6 1-5
240 230 220 2-3 4, 6 1-5
1
2
3
4
1234
4 3 12
67
6
1 2 43
8
5
5
3 421
2 134
HV
L V
115V 230V
120V 240V
110V 420V
115V 230V
120V 240V
110V 220V
PH***PP Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
120 115 110 1-2, 3-4 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
120 115 110 1-2, 3-4 6, 7 1-5, 4-8
240 230 220 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
120 115 110 3-4, 1-2 4, 6 1-5
240 230 220 2-3 4, 6 1-5
PH***SP Schematic for 150VA to 1000VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
208 200 190 2-3, 4-5 2, 5 Unfused
416 400 380 3-4 2, 5 Unfused
208 200 190 2-3, 4-5 1, 6 2-7, 5-8
416 400 380 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 4-5, 2-3 1, 5 2-7
240 230 220 3-4 1, 5 2-7
2
3
4
5
2345
16
1
8
7
7
3 2456 1 56 4 2 13
L V
21 3 4
HV
5 6 21 3 4 5 6
200V 400V
208V 416V
190V 380V
115V 230V
120V 240V
110V 220V
Page 7 of 9
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
PH***PP Schematic for 150VA to 1500VA Units
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
120 115 110 2-3, 4-5 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 2-3, 4-5 1, 6 2-7, 5-8
240 230 220 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
120 115 110 4-5, 2-3 1, 5 2-7
240 230 220 3-4 1, 5 2-7
2
3
4
5
2345
16
1
8
7
7
3 2456 1 56 4 2 13
L V
21 3 4
HV
5 6 21 3 4 5 6
115V 230V
120V 240V
110V 220V
115V 230V
120V 240V
110V 220V
PH***MBMH Schematic for 100VA to 1500VA Units
2
6
15
4
3
3
4
2
1
7
8
7
HV
L V
Dotted line represents
supplied jumper lead.
600V/575V/550V
480V/460V/440V
240V/230V/220V
100V/95V/90V
120V/115V/110V
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
600 575 550 None 2, 6 Unfused
480 460 440 None 2, 4 Unfused
240 230 220 None 2, 3 Unfused
600 575 550 8-6 1, 5 2-7, 5-8
480 460 440 4-8 1, 5 2-7, 5-8
240 230 220 3-8 1, 5 2-7, 5-8
Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse
(Secondary Volts) Links Between Terminals Connect To Clips To
120 115 110 None 2, 4 Unfused
100 95 90 None 2, 3 Unfused
120 115 110 None 1, 4 2-7
100 95 90 None 1, 3 2-7
1
3
64
7
2
3
4
1
6
5
8
5
HV
L V
Dotted line represents
supplied jumper lead.
600V/575V/550V
480V/460V/440V
240V/230V/220V
100V/95V/90V
120V/115V/110V
PH***MBMH Schematic for 50 and 75VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
600 575 550 None 1, 3 Unfused
480 460 440 None 1, 7 Unfused
240 230 220 None 1, 2 Unfused
600 575 550 3-8 6, 4 1-5, 4-8
480 460 440 8-7 6, 4 1-5, 4-8
240 230 220 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse
(Secondary Volts) Links Between Terminals Connect To Clips To
120 115 110 None 1, 4 Unfused
100 95 90 None 1, 3 Unfused
120 115 110 None 4, 6 1-5
100 95 90 None 3, 6 1-5
Page 8 of 9
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
PH***MEMX Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
415 None 1, 3 Unfused
400 None 1, 7 Unfused
380 None 1, 2 Unfused
415 3-8 6, 4 1-5, 4-8
400 8-7 6, 4 1-5, 4-8
380 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
110 3-4, 1-2 1, 4 Unfused
220 2-3 1, 4 Unfused
110 3-4, 1-2 4, 6 1-5
220 2-3 4, 6 1-5
1
2
3
4
3
4
6
7
2
5
8
HV
415V
400V
380V
4 3 122 134
L V
110V 220V
Dotted line represents
supplied jumper lead.
1
6
5
PH***MEMX Schematic for 150VA to 1000VA Units
2
3
4
5
6
5
1
4
3
7
8
L V
110V 220V
HV
Dotted line represents
supplied jumper lead.
3 2456 1 56 4 2 13
415V
400V
380V
2
1
7
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
415 None 2, 6 Unfused
400 None 2, 4 Unfused
380 None 2, 3 Unfused
415 8-6 1, 5 2-7, 5-8
400 4-8 1, 5 2-7, 5-8
380 3-8 1, 5 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
110 4-5, 2-3 2, 5 Unfused
220 3-4 2, 5 Unfused
110 4-5, 2-3 1, 5 2-7
220 3-4 1, 5 2-7
PH***MGJ Schematic for 50, 75 and 100VA Units
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
380 None 1, 3 Unfused
277 None 1, 7 Unfused
208 None 1, 2 Unfused
380 3-8 6, 4 1-5, 4-8
277 8-7 6, 4 1-5, 4-8
208 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 3-4, 1-2 1, 4 Unfused
240 2-3 1, 4 Unfused
120 3-4, 1-2 4, 6 1-5
240 2-3 4, 6 1-5
1
2
3
4
3
4 3 12
4
6
7
2
5
2 134
8
L V
120V 240V
HV
Dotted line represents
supplied jumper lead.
380V
277V
208V
1
6
5
Page 8 of 9
HPS Im p e r a t o r t m Series - Wiring Schematic Drawings continued
PH***MGJ Schematic for 150VA to 1000VA Units
2
3
4
5
6
5
1
4
3
7
8
3 2456 1 56 4 2 13
L V
120V 240V
HV
Dotted line represents
supplied jumper lead.
380V
277V
208V
2
1
7
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
380 None 2, 6 Unfused
277 None 2, 4 Unfused
208 None 2, 3 Unfused
380 8-6 1, 5 2-7, 5-8
277 4-8 1, 5 2-7, 5-8
208 3-8 1, 5 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120 4-5, 2-3 2, 5 Unfused
240 3-4 2, 5 Unfused
120 4-5, 2-3 1, 5 2-7
240 3-4 1, 5 2-7

Navigation menu