Dupont 507 Users Manual Retrofit Guidelines For Suva(R) HFC Refrigerants
2015-02-04
: Dupont Dupont-507-Users-Manual-515051 dupont-507-users-manual-515051 dupont pdf
Open the PDF directly: View PDF .
Page Count: 20
Download | |
Open PDF In Browser | View PDF |
Technical Information ART-37 DuPont Suva ® refrigerants Retrofit Guidelines for Suva HFC Refrigerants ® Suva® 134a for R-12 Retrofit Suva® HP62 and Suva® 507 for R-502 Retrofit Suva® HP62 and Suva® 507 for R-22 Retrofit The DuPont Oval Logo, DuPont™, The miracles of science™, and Suva® are trademarks or registered trademarks of E.I. du Pont de Nemours and Company. Retrofit Guidelines for Suva® HFC Refrigerants Table of Contents Page Introduction ................................................................................................................ 1 R-12 Replacement Choices ..................................................................................... 1 R-502 Replacement Choices ................................................................................... 1 R-22 Replacement Choices ..................................................................................... 1 Using HFCs versus Service Refrigerants ............................................................ 1 Important Safety Information ................................................................................. 2 Lubricant and Filter Drier Information ................................................................ 2 Lubricants .................................................................................................................. 2 Filter Drier .................................................................................................................. 2 General Retrofit Information ................................................................................... 2 System Modifications ................................................................................................ 2 Refrigerant Recovery Information ............................................................................. 3 What to Expect Following a Retrofit .......................................................................... 3 Retrofit Summary for HFC Refrigerants .................................................................... 4 Retrofit of R-12 Systems to Suva® 134a ............................................................ 4 Retrofit of R-502 Systems to Suva® HP62 or Suva® 507 ............................... 5 Retrofit of R-22 Systems to Suva ® HP62 or Suva® 507 ................................. 6 Pressure/Temperature Charts—Introduction ........................................................ 8 How to Read the Pressure/Temperature Charts ....................................................... 8 How to Determine Suction Pressure, Superheat, and Subcool ................................. 8 Retrofit Checklist for Suva ® 134a, Suva® HP62, or Suva® 507 ...................... 9 System Data Sheet ................................................................................................. 10 Appendix Table 1. Table 2. Table 3. Table 4. Table 5. Table 6. Table 7. Table 8. Pressure/Temperature Chart—Suva® 134a/R-12 ..................................... Pressure/Temperature Chart—Suva® HP62/R-502 .................................. Pressure/Temperature Chart—Suva® 507/R-502 ..................................... Pressure/Temperature Chart—Suva® HP62/R-22 .................................... Pressure/Temperature Chart—Suva® 507/R-22 ....................................... Suva® 134a Physical Properties ............................................................... Suva® HP62 and Suva® 507 Physical Properties ..................................... Compositions of Suva® Refrigerants ........................................................ 11 12 13 14 15 16 16 16 DuPont Technical Assistance and Other Information ............................. back page Introduction • Suva® 407C (R-407C) is also an HFC retrofit option for R-502 in certain equipment. Refer to ART-34 “Retrofit Guidelines for Suva® 407C” for details. With the phaseout of CFCs and HCFCs, existing refrigeration and air-conditioning equipment operating with CFCs and HCFCs will ultimately need to be either replaced with new equipment or retrofitted with alternative refrigerants. Some service technicians and equipment owners have elected to retrofit to hydrofluorocarbon (HFC) refrigerants such as Suva® 134a, Suva® HP62, or Suva® 507. R-22 Replacement Choices Suva® HP62 (R-404A) and Suva® 507 (R-507) are HFC retrofit options for R-22 refrigeration equipment, especially for medium and low temperature applications. These products will provide similar cooling capacity at evaporator temperatures in the range of 30°F to 50°F (–1°C to 10°C). At evaporator temperatures below 30°F (–1°C), the cooling capacity is greater than R-22. At 0°F (–18°C) the capacity is about 6% higher; and at –40°F (–40°C) the capacity is about 30% higher. Using these procedures, R-12, R-502, and R-22 equipment can be safely and efficiently retrofitted with HFC-based Suva® refrigerants, allowing the equipment to continue in service for the remainder of its useful life. These retrofit guidelines are intended for equipment containing positive displacement compressors. At evaporator temperatures above 10°F (–12°C) there is an energy efficiency penalty of about 5 to 10%. At evaporator temperatures below 10°F (–12°C) Suva® HP62 and 507 have similar energy efficiency, increasing to about +20% at –40°F (–40°C). R-12 Replacement Choices Suva® 134a (R-134a) is the long-term HFC replacement for R-12 in new equipment and for retrofitting some R-12 systems such as supermarket display cases, commercial refrigeration and airconditioning equipment, appliances, and transport refrigeration equipment. In stationary equipment Suva® 134a is recommended for retrofit of equipment with evaporator temperatures above 20°F (–7°C) to ensure best performance. Suva® 134a may be used in existing equipment at lower evaporator temperatures, but it can exhibit reduced capacity compared with R-12 unless system modifications are made. Suva® HP62 and 507 will have higher discharge pressure than R-22, but lower compression ratios; and also lower discharge temperature. • Suva® 407C (R-407C) should also be considered as a retrofit option for R-22 in medium temperature equipment. It will provide similar cooling capacity and energy efficiency at evaporator temperatures above 25°F (4°C). Refer to ART-34 “Retrofit Guidelines for Suva® 407C” for details R-502 Replacement Choices Using HFCs versus Service Refrigerants • Suva® HP62 (R-404A) is widely recognized as the preferred HFC replacement for R-502 in new equipment and for retrofitting R-502 systems such as supermarket and food service, industrial freezing, and some transport refrigeration. Suva® HP62 offers the closest HFC match to R-502 performance and can be used over the full R-502 operating range. Suva® HP62 also provides lower compressor discharge temperatures than R-502, which can increase compressor reliability and life. Refrigerants such as Suva® MP39, Suva® 409A, Suva® HP80 and Suva® 408A are often selected for retrofit instead of HFCs because these service refrigerants typically involve an easier and more cost-effective retrofit procedure while providing improved performance over the CFCs they replace. The compressor oil change procedures are typically less complicated with the service refrigerants, which results in lower retrofit costs. Refer to DuPont bulletin ART-36 “Retrofit Guidelines for Suva® Service Refrigerants” for full details. • Suva® 507 (R-507) is an HFC replacement option for R-502 in new equipment and for retrofitting R-502 systems. Suva® 507 can also be used over the full R-502 operating range, and provides lower compressor discharge temperatures than R-502, which can increase compressor reliability and life. 1 Important Safety Information Lubricant and Filter Drier Information ® Like CFCs, Suva refrigerants are safe when handled properly. However, any refrigerant can cause injury or even death when mishandled. Please review the following guidelines before using any refrigerant. • Do not work in high concentrations of refrigerant vapors. Always maintain adequate ventilation in the work area. Do not breathe vapors. Do not breathe lubricant mists from leaking systems. Ventilate the area well after any leak before attempting to repair equipment. Lubricants Lubricant selection is based on many factors, including compressor wear characteristics, material compatibility, and lubricant/refrigerant miscibility that can affect oil return to the compressor. Before starting a retrofit, consult the compressor manufacturer to determine the correct lubricant for your compressor. Other information sources are DuPont Refrigerant Distributors, lubricant manufacturers, and system manufacturers. • Do not use handheld leak detectors to check for breathable air. These detectors are not designed to determine if the air is safe to breathe. Use oxygen monitors to ensure adequate oxygen is available to sustain life. Polyol ester (POE) lubricants must be used with Suva® 134a, Suva® HP62 or Suva® 507 refrigerants. These lubricants are available from DuPont Refrigerant Distributors. To provide optimum oil return, equipment using mineral oil or alkylbenzene must be flushed to remove at least 95% of these oils. See the retrofit procedures below for more information. • Do not use flames or torches to search for leaks. Do not use flames in high concentrations of refrigerant. Open flames release large quantities of acidic compounds in the presence of all refrigerants, and these compounds can be hazardous. Do not use torches as leak detectors. Old halide torches detect chlorine, which may not be present with new refrigerants. Use an electronic leak detector designed to find the refrigerants you are using. Special care should be taken when handling POE lubricants because of their tendency to absorb water. Minimize contact with air and store the lubricant in a sealed container. Filter Drier Change the filter drier during the retrofit. This is a routine practice following system maintenance. There are two types of filter driers commonly used, solid core and packed bead. If you detect a visible change in the size or color of a flame when using torches to repair equipment, stop work immediately and leave the area. Ventilate the work area well and stop any refrigerant leaks before resuming work. These flame effects may be an indication of very high refrigerant concentrations, and continuing to work without adequate ventilation may result in injury or death. Replace the drier with the same type you currently use. The drier label will show which refrigerants can be used with that drier. Check with your DuPont Refrigerant Distributor for the correct drier to use in your system. General Retrofit Information Note: Any refrigerant can be hazardous if used improperly. Hazards include liquid or vapor under pressure, and frostbite from the escaping liquid. Overexposure to high concentrations of vapor can cause asphyxiation and cardiac arrest. Please read all safety information before handling any refrigerant. System Modifications The compositions of these Suva® refrigerants have been selected to provide performance comparable with the refrigerants they are replacing in terms of both capacity and energy efficiency. As a result, minimal system modifications are anticipated with retrofitting. Suva® HP62 and Suva® 507 are near-azeotropes at most temperatures, therefore the vapor composition in the refrigerant cylinder is slightly different from the liquid composition. This small difference will not affect performance in direct expansion systems, but it could affect performance in systems with flooded evaporators. For more detailed information on the properties, uses, storage, and handling of Suva® refrigerants, see DuPont Technical Bulletin P-134a or P-HP, or other literature specific to these products. Refer to the appropriate Material Safety Data Sheet (MSDS) for more safety information about each refrigerant. DuPont Safety Bulletin AS-1 gives additional information for safe handling of refrigerants. 2 In the United States, DuPont will take back for reclaim the Suva® refrigerants discussed in this bulletin. You should consult the original equipment manufacturer for recommendations concerning the compatibility of elastomers and plastics used in their system and the new refrigerant. Although many system components used with CFCs are also compatible with Suva® refrigerants, there are exceptions that, if not replaced, can cause refrigerant leakage or system failure. What to Expect Following a Retrofit These tables show approximate system performance changes following a retrofit. These values are general guidelines for system behavior, and actual performance will vary with each system. Field experience has shown that some systems retrofitted directly from R-502 to Suva® HP62 or Suva® 507 can have increased leakage due to shrinkage of elastomers (o-rings, gaskets) following removal of the R-502. This same situation might exist in an R-22 retrofit. Replacement of these elastomers may add additional cost and time to the retrofit. Suva® 134a is compared to R-12, Suva® HP62 and Suva® 507 are compared to R-502. Suva® Refrig. 134a Retrofits of R-12 or R-502 systems with other alternative refrigerants such as HCFC-22 may require more extensive modifications to the existing equipment, such as replacement of the compressor with multistage compressors or use of liquid injection. For some systems this additional cost may be large. Suva® refrigerants provide the service contractor and equipment owner with a cost-effective way to retrofit an existing system. HP62 507 Disch. Press. psi (kPa) Suct. Press. psi (kPa) Disch. Temp. °F (°C) Refrig. Cap’y. (%) +10 (69.8) +20 (+137.9) +30 (+206.8) –2 (–13.8) Same –10 (–5.6) –10 (–5.6) –15 (+8.3) –10 Same Same Same Suva® HP62 is compared to R-22 (evap. temp. = 0°F [–18°C]). Note: Suva® 507 provides performance very similar to HP62. Note: Suva® refrigerants were not designed for use in conjunction with other refrigerants or additives that have not been clearly specified by DuPont or the equipment manufacturer. Mixing Suva® refrigerants with other refrigerants, may have an adverse effect on system performance. “Topping off” a different refrigerant with any Suva® refrigerant is not recommended. Suva® Refrig. HP62 Disch. Press. psi (kPa) +45 (+310) Suct. Compression Disch. Refrig. Press. Ratio Temp. Cap’y. psi (kPa) (%) °F (°C) (%) +10 (+69.8) –5 –64 (–36) +6 How to read these tables Example: R-12 to Suva® 134a retrofit. Discharge pressure with 134a will be in the range of 10 psig higher than R-12 (using discharge pressure column above). Refrigerant Recovery Information Most recovery or recycle equipment used for R-12, R-502, or R-22 can be used for Suva® refrigerants. Use standard procedures to avoid cross-contamination when switching from one refrigerant to another. Consult the equipment manufacturer for specific recommendations. 3 operation of the system with the Suva® refrigerant. A System Data Sheet is included at the back of this document to record baseline data. Retrofit Summary for HFC Refrigerants Select the Retrofit Checklist from the Appendix for the refrigerant you are replacing. 1. Establish baseline performance with CFC/HCFC. 2. Drain mineral oil or alkylbenzene from the system and measure the volume removed. Leave the CFC refrigerant in the system. If mineral oil or alkylbenzene is the existing lubricant, it will have to be drained. This may require removing the compressor from the system, particularly with small hermetic compressors that have no oil drain port. In this case, the lubricant should be drained from the suction port on the compressor after the R-12 has been properly recovered. For an effective flush, it is important to remove at least 50% of the lubricant in all cases. Larger systems may require drainage from additional points in the system, particularly low spots around the evaporator. In systems with an oil separator, any lubricant present in the separator should also be drained. 2. Drain mineral oil or alkylbenzene (MO/ AB) from the system and measure the volume removed. Leave the CFC/HCFC refrigerant in the system. 3. Add POE lubricant; use the same volume as removed in Step 2. Start up system and operate for at least 24 hours, or more if system has complex piping. 4. Drain POE, and repeat steps 2 and 3 at least two more times. Continue flushing until MO/AB is less than 5% by weight or as recommended by compressor manufacturer. In all cases, measure the volume of lubricant removed from the system. Record this information on the Retrofit Checklist (see Appendix). Compare this volume with the compressor/ system specifications to ensure that the majority of lubricant has been removed. Consult the compressor manufacturer for recommendations on allowable residual MO/AB in POE lubricant. If poor system performance is noted on start-up, an additional lubricant change may be required. 5. Recover the CFC/HCFC charge into a proper recovery cylinder. 6. Replace the filter/drier. 7. Evacuate system and check for leaks. 8. Charge with Suva® refrigerant. Remove liquid only from charging cylinder for Suva® HP62 or Suva® 507. Typical charge is 75–90% by weight of CFC/HCFC charge. 3. Add POE lubricant; use the same volume as removed in Step 2. Start up system and operate for at least 24 hours, or more if system has complex piping. Charge the compressor with the same volume of new lubricant as the amount you removed from the system in step 2. Use a lubricant viscosity and grade recommended by the compressor manufacturer for the Suva® refrigerant you are using; or use a similar viscosity to the oil you removed if compressor information is not available. A typical viscosity is 150 SUS or ISO 32 for many compressors. 9. Start up system, adjust charge size. Label system for the refrigerant and lubricant used. Retrofit Complete Retrofit of R-12 Systems to Suva® 134a The following detailed discussion is the recommended procedure for retrofitting R-12 systems to Suva® 134a. 4. Drain POE, and repeat steps 2 and 3 at least two more times. Continue flushing until MO/ AB is less than 5% by weight or as recommended by compressor manufacturer. For an HFC refrigerant to operate properly in a retrofitted system, the residual MO/AB concentration must be very low. Repeatedly removing and replacing the POE will flush the old oil from the refrigeration system, providing that enough time is allowed with each change to circulate oil through the entire system. 1. Establish baseline performance with CFC. Collect system performance data while the R-12 is in the system. Check for correct refrigerant charge and operating conditions. The baseline data of temperatures and pressures at various points in the system (evaporator, condenser, compressor suction and discharge, superheat and subcool, etc.) at normal operating conditions will be useful when optimizing 4 5. Recover the CFC charge into a proper recovery cylinder. Use normal service practices. If the correct charge size is not known, weigh the amount of refrigerant recovered. heat, etc.). Attempting to charge until the sight glass is clear may result in overcharging the refrigerant. Please read “How to Determine Suction Pressure, Superheat and Subcool” on page 8. 6. Replace the filter/drier. It is routine practice to replace the filter/drier following system maintenance. Replacement driers are available that are compatible with Suva® refrigerants. See page 2 of this manual for additional information on driers. Retrofit of R-502 Systems to Suva® HP62 or Suva® 507 The following detailed discussion is the recommended procedure for retrofitting R-502 systems to Suva® HP62 or Suva® 507. 7. Evacuate system and check for leaks. To remove air or other noncondensables in the system, evacuate the system to near full vacuum (29.9 inHg vacuum [500 microns] or less than 10 kPa). 1. Establish baseline performance with CFC. Collect system performance data while the R-502 is in the system. Check for correct refrigerant charge and operating conditions. The baseline data of temperatures and pressures at various points in the system (evaporator, condenser, compressor suction and discharge, superheat and subcool, etc.) at normal operating conditions will be useful when optimizing operation of the system with the Suva® refrigerant. A System Data Sheet is included at the back of this document to record baseline data. 8. Charge with Suva® refrigerant. In general, the refrigeration system will require less weight of the Suva® 134a than of R-12. The optimum charge will vary depending on the system design and operating conditions. For most systems the best charge size will be 75–90% by weight of the original R-12 charge. For best results: • It is recommended that the system be initially charged with about 75% by weight of the original charge. • Add the initial charge of Suva® refrigerant to the high-pressure side of the system (compressor not running) until the system and cylinder pressures equalize. Then connect to the low-pressure side of the system, start the compressor, and load the remainder of the refrigerant slowly to the suction side of the system. 2. Drain mineral oil or alkylbenzene from the system and measure the volume removed. Leave the CFC refrigerant in the system. If mineral oil or alkylbenzene is the existing lubricant, it will have to be drained. This may require removing the compressor from the system, particularly with small hermetic compressors that have no oil drain port. In this case, the lubricant should be drained from the suction port on the compressor after the R-502 has been properly recovered. For an effective flush, it is important to remove at least 50% of the lubricant in all cases. Larger systems may require drainage from additional points in the system, particularly low spots around the evaporator. In systems with an oil separator, any lubricant present in the separator should also be drained. 9. Start up system, adjust charge size. Label system for the refrigerant and lubricant used. Start the system and let conditions stabilize. If the system is undercharged, add Suva® 134a in small amounts until the system conditions reach the desired level. See the Pressure/Temperature Charts in this bulletin to compare pressures and temperatures. In all cases, measure the volume of lubricant removed from the system. Record this information on the Retrofit Checklist (see Appendix). Compare this volume with the compressor/ system specifications to ensure that the majority of lubricant has been removed. Consult the compressor manufacturer for recommendations on allowable residual MO/AB in POE lubricant. If poor system performance is noted on start-up, an additional lubricant change may be required. Suva® refrigerants are more sensitive to charge size than CFCs. System performance will change quickly if the system is overcharged or undercharged. Sight glasses in the liquid line can be used in most cases as a guide, but system charge should also be determined by measuring system operating conditions (discharge and suction pressures, suction line temperature, compressor motor amps, super- 5 For best results: • It is recommended that the system be initially charged with about 75% by weight of the original charge. • Add the initial charge of Suva® refrigerant to the high-pressure side of the system (compressor not running) until the system and cylinder pressures equalize. Then connect to the low-pressure side of the system, start the compressor, and load the remainder of the refrigerant slowly to the suction side of the system. You should be removing liquid from the charging cylinder, and therefore should charge slowly to allow the refrigerant to flash (vaporize) before entering the compressor suction and avoid compressor damage. 3. Add POE lubricant; use the same volume as removed in Step 2. Start up system and operate for at least 24 hours, or more if system has complex piping. Charge the compressor with the same volume of new lubricant as the amount you removed from the system in step 2. Use a lubricant viscosity and grade recommended by the compressor manufacturer for the Suva® refrigerant you are using; or use a similar viscosity to the MO/AB you removed if compressor information is not available. A typical viscosity is 150 SUS or ISO 32 for many compressors. 4. Drain POE, and repeat steps 2 and 3 at least two more times. Continue flushing until MO/AB is less than 5% by weight or as recommended by compressor manufacturer. For an HFC refrigerant to operate properly in a retrofitted system, the residual MO/AB concentration must be very low. Repeatedly removing and replacing the POE will flush the old oil from the refrigeration system, providing that enough time is allowed with each change to circulate oil through the entire system. 9. Start up system, adjust charge size. Label system for the refrigerant and lubricant used. Start the system and let conditions stabilize. If the system is undercharged, add Suva® HP62 or Suva® 507 in small amounts (still removing liquid from the charging cylinder) until the system conditions reach the desired level. See the Pressure/Temperature Charts in this bulletin to compare pressures and temperatures for the Suva® refrigerant you are using. 5. Recover the CFC charge into a proper recovery cylinder. Use normal service practices. If the correct charge size is not known, weigh the amount of refrigerant recovered. Suva® refrigerants are more sensitive to charge size than CFCs. System performance will change quickly if the system is overcharged or undercharged. Sight glasses in the liquid line can be used in most cases as a guide, but system charge should also be determined by measuring system operating conditions (discharge and suction pressures, suction line temperature, compressor motor amps, superheat, etc.). Attempting to charge until the sight glass is clear may result in overcharging the refrigerant. Please read “How to Determine Suction Pressure, Superheat, and Subcool” on page 8. 6. Replace the filter/drier. It is routine practice to replace the filter/drier following system maintenance. Replacement driers are available that are compatible with Suva® refrigerants. See page 2 of this manual for additional information on driers. 7. Evacuate system and check for leaks. To remove air or other noncondensables in the system, evacuate the system to near full vacuum (29.9 inHg vacuum [500 microns] or less than 10 kPa). 8. Charge with Suva® refrigerant. Remove liquid only from charging cylinder. The proper cylinder position for liquid removal is indicated by arrows on the cylinder and cylinder box. Once liquid is removed from the cylinder, the refrigerant can be charged to the system as liquid or vapor as desired. Use the manifold gauges or a throttling valve to flash the liquid to vapor if required. Retrofit of R-22 Systems to Suva® HP62 or Suva® 507 The following detailed discussion is the recommended procedure for retrofitting R-22 systems to Suva® HP62 or Suva® 507. 1. Establish baseline performance with R-22. Collect system performance data while the R-22 is in the system. Check for correct refrigerant charge and operating conditions. The baseline data of temperatures and pressures at various points in the system (evaporator, condenser, compressor suction and discharge, superheat and subcool, etc.) at normal operating conditions will be useful when optimizing operation In general, the refrigeration system will require less weight of the Suva® refrigerant than of R-502. The optimum charge will vary depending on the system design and operating conditions, but for most systems the best charge size will be 75–90% by weight of the original charge. 6 of the system with the Suva® refrigerant. A System Data Sheet is included at the back of this document to record baseline data. from the refrigeration system, providing that enough time is allowed with each change to circulate oil through the entire system. 5. Recover the R-22 charge into a proper recovery cylinder. Use normal service practices. If the correct charge size is not known, weigh the amount of refrigerant recovered. 2. Drain mineral oil or alkylbenzene from the system and measure the volume removed. Leave the R-22 in the system. If mineral oil or alkylbenzene is the existing lubricant, it will have to be drained. This may require removing the compressor from the system, particularly with small hermetic compressors that have no oil drain port. In this case, the lubricant should be drained from the suction port on the compressor after the R-22 has been properly recovered. For an effective flush, it is important to remove at least 50% of the lubricant in all cases. Larger systems may require drainage from additional points in the system, particularly low spots around the evaporator. In systems with an oil separator, any lubricant present in the separator should also be drained. 6. Replace the filter/drier. It is routine practice to replace the filter/drier following system maintenance. Replacement driers are available that are compatible with Suva® refrigerants. See page 2 of this manual for additional information on driers. 7. Evacuate system and check for leaks. To remove air or other noncondensables in the system, evacuate the system to near full vacuum (29.9 inHg vacuum [500 microns] or less than 10 kPa). 8. Charge with Suva® refrigerant. Remove liquid only from charging cylinder. The proper cylinder position for liquid removal is indicated by arrows on the cylinder and cylinder box. Once liquid is removed from the cylinder, the refrigerant can be charged to the system as liquid or vapor as desired. Use the manifold gauges or a throttling valve to flash the liquid to vapor if required. In all cases, measure the volume of lubricant removed from the system. Record this information on the Retrofit Checklist (see Appendix). Compare this volume with the compressor/ system specifications to ensure that the majority of lubricant has been removed. Consult the compressor manufacturer for recommendations on allowable residual MO/AB in POE lubricant. If poor system performance is noted on start-up, an additional lubricant change may be required. In general, the refrigeration system will require less weight of the Suva® refrigerant than of R22. The optimum charge will vary depending on the system design and operating conditions, but for most systems the best charge size will be 75–90% by weight of the original charge. 3. Add POE lubricant; use the same volume as removed in Step 2. Start up system and operate for at least 24 hours, or more if system has complex piping. Charge the compressor with the same volume of new lubricant as the amount you removed from the system in step 2. Use a lubricant viscosity and grade recommended by the compressor manufacturer for the Suva® refrigerant you are using; or use a similar viscosity to the MO/AB you removed if compressor information is not available. A typical viscosity is 150 SUS or ISO 32 for many compressors. For best results: • It is recommended that the system be initially charged with about 75% by weight of the original charge. • Add the initial charge of Suva® refrigerant to the high-pressure side of the system (compressor not running) until the system and cylinder pressures equalize. Then connect to the low-pressure side of the system, start the compressor, and load the remainder of the refrigerant slowly to the suction side of the system. You should be removing liquid from the charging cylinder, and therefore should charge slowly to allow the refrigerant to flash (vaporize) before entering the compressor suction and avoid compressor damage. 4. Drain POE, and repeat steps 2 and 3 at least two more times. Continue flushing until MO/AB is less than 5% by weight or as recommended by compressor manufacturer. For an HFC refrigerant to operate properly in a retrofitted system, the residual MO/AB concentration must be very low. Repeatedly removing and replacing the POE will flush the old oil 7 • Head pressure controls • Crankcase pressure regulators • Others 9. Start up system, adjust charge size. Label system for the refrigerant and lubricant used. Start the system and let conditions stabilize. If the system is undercharged, add Suva® HP62 or Suva® 507 in small amounts (still removing liquid from the charging cylinder) until the system conditions reach the desired level. See the Pressure/Temperature Charts in this bulletin to compare pressures and temperatures for the Suva® refrigerant you are using. Due to the higher oil miscibility with HFCs and POE, verify proper compressor oil sump levels. Check with the compressor manufacturer for proper amperage load ratings. Pressure/Temperature Charts Introduction Suva® refrigerants are more sensitive to charge size than R-22. System performance will change quickly if the system is overcharged or undercharged. Sight glasses in the liquid line can be used in most cases as a guide, but system charge should also be determined by measuring system operating conditions (discharge and suction pressures, suction line temperature, compressor motor amps, superheat, etc.). Attempting to charge until the sight glass is clear may result in overcharging the refrigerant. Please read “How to Determine Suction Pressure, Superheat, and Subcool” below. How to Read the Pressure/Temperature Charts Tables 1 through 5 contain pressure/temperature charts for the refrigerants discussed in this bulletin. R-12, R-22 and Suva® 134a are all single component refrigerants with no temperature “glide” in the evaporator or condenser. Suva® HP62 and 507 have very small glide (less than 1F [0.6C]). For field service purposes, this glide can be neglected in calculating superheat and subcool. The evaporator temperature can be considered equal to the saturated vapor temperature at the compressor suction pressure; the condenser temperature can be considered equal to the saturated vapor temperature or the saturated liquid temperature at the compressor discharge pressure. For Suva® HP62 and 507, the saturated vapor temperatures are listed in the tables. “Helpful Hints” For Retrofit From R-22 To Suva® HP62 or 507 Both Suva® HP62 and 507 have minimal “temperature glide” and can be used in systems that have flooded evaporators and condensers, as well as those that have direct expansion evaporators. How to Determine Suction Pressure, Superheat, and Subcool Since HP62 and 507 have higher cooling capacity than R-22,at lower evaporator temperatures the expansion device may need to be adjusted or replaced to maintain proper flow control and superheat settings. Estimated capacity comparison: Evaporator Temperature Capacity 30 to 50°F (–1 to 10°C) Same 0°F (–18°C) +6% –40°F (–40°C) +30% Suction Pressure Determine the expected evaporator temperature using the R-12, R-502 or R-22 column (from the baseline data you collected prior to the retrofit). Find the same expected evaporator temperature in the column for Suva® 134a, HP62 or 507. Note the corresponding pressure for this temperature. This is the suction pressure at which the system should operate. Verify that compressor suction and discharge piping is the proper size to maintain proper refrigerant velocity and pressure drop. Superheat and Subcool Using the temperature column for Suva® 134a, HP62 and 507, the amount of superheat and subcool is calculated in the same manner as for the CFC or HCFC refrigerant. Compressor discharge temperature will be lower than R-22. The compressor discharge pressure will be higher with HP62 and 507. Various pressure switches may need to be adjusted to maintain proper operating conditions; for example: • Evaporator pressure regulators • Cut-in and cut-out pressure switches • Condenser fan cycling pressure switches Note: The amount of vapor superheat is always calculated from the actual saturated vapor temperature; the amount of liquid subcool is always calculated from the actual saturated liquid temperature. 8 Retrofit Checklist for Suva 134a, Suva® HP62, or Suva® 507 ® _____ 1. Establish baseline performance with R-12, R-502, or R-22. (See data sheet for recommended data.) _____ 2. Consult the original equipment manufacturer of the system components for recommendations on the following: • Plastics compatibility • Elastomers compatibility • Lubricant (viscosity, manufacturer) • Retrofit procedure to sustain warranty _____ 3. Drain lubricant charge from the refrigerant system (unless polyol ester lubricant is already in the system). • Remove majority of lubricant from system. • Measure amount of lubricant removed and record: _______________. _____ 4. Charge polyol ester lubricant using amount equivalent to amount of mineral oil removed. Run system with R-12, R-502, or R-22 for 24 hours, minimum. _____ 5. Repeat lubricant drain and POE charging two more times or until mineral oil content is less than 5%. _____ 6. Remove R-12, R-502, or R-22 charge from system. (Need 10–20 inHg vacuum [34–67 kPa].) _____ 7. Replace filter drier with new drier approved for use with Suva® 134a, Suva® HP62, or Suva® 507. _____ 8. Reconnect system and evacuate with vacuum pump. (Evacuate to full vacuum [29.9 inHg vacuum/0.14 kPa].) _____ 9. Leak-check system. (Reevacuate system following leak check.) _____ 10. Charge system with Suva®. • Initially charge 75% by weight of original equipment manufacturer R-12, R-502, or R-22 charge. • Amount of refrigerant charged: _______________. _____ 11. Start equipment and adjust charge until desired operating conditions are achieved. If low in charge, add in increments of 2–3% of original R-12, R-502, or R-22 charge. • Amount of refrigerant charged: _______________. • Total refrigerant charged: _______________. _____ 12. Label components and system for type of refrigerant (Suva® 134a, Suva® HP62, or Suva® 507) and lubricant (polyol ester). Retrofit is complete. 9 System Data Sheet Type of System/Location: _________________________________________________________________________________________ Equipment Mfg.: _________________________________ Compressor Mfg.: _______________________________ Model No.: _________________________________ Model No.: _______________________________ Serial No.: _________________________________ Original Charge Size: _________________________________ Serial No.: _______________________________ Original Lubricant: Type/Mfg: _______________________________ Lubricant Charge Size: _______________________________ New Lubricant: _______________________________ Type/Mfg: _______________________________ 1st Charge Size: _______________________________ 2nd Charge Size: _______________________________ Additional Charge Size: _______________________________ Drier Mfg.: _________________________________ Drier Type (check one): Model No.: _________________________________ Loose Fill: _______________________________ _________________________________ Solid Core: _______________________________ Condenser Cooling Medium (air/water): Expansion Device (check one): ________________________________________________________________________ Capillary Tube: _________________________________________________________ Expansion Valve: _______________________________________________________ If Expansion Valve: Manufacturer: _________________________________________________________________________________________ Model No.: ____________________________________________________________________________________________ Control/Set Point: _______________________________________________________________________________________ Location of Sensor: _____________________________________________________________________________________ Other System Controls (ex.: head press control), Describe: ______________________________________________________________ ___________________________________________________________________________________________________________ (circle units used where applicable) Date/Time Refrigerant Charge Size (lb, oz/g) Ambient Temp. (°F/°C) Relative Humidity Compressor: Suction T (°F/°C) Suction P (psi/kPa/bar) Discharge T (°F/°C) Discharge P (psi/kPa/bar) Box/CaseT (°F/°C) Evaporator: Refrigerant Inlet T (°F/°C) Refrigerant Outlet T (°F/°C) Coil Air/H2O In T (°F/°C) Coil Air/H2O Out T (°F/°C) Refrigerant T at Superheat Ctl. Pt. (°F/°C) Condenser: Refrigerant Inlet T (°F/°C) Refrigerant Outlet T (°F/°C) Coil Air/H2O In T (°F/°C) Coil Air/H2O Out T (°F/°C) Exp. Device Inlet T (°F/°C) Motor Amps Run/Cycle Time Comments: ________________________________________________________________________________________________ _________________________________________________________________________________________________________ 10 Appendix Table 1 Pressure/Temperature Chart Suva® 134a/R-12 Saturation Properties SI Units English Units Pressure, psi 15* 10* 5* 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 110 120 130 140 150 165 180 195 210 225 240 255 270 285 300 R-12 HFC-134a Saturation Saturation Temperature, °F Temperature, °F –49 –38 –29 –22 –9 2 10 18 26 32 38 43 48 53 58 62 66 70 74 77 81 84 87 90 96 102 107 112 117 123 130 136 141 147 152 157 162 166 170 Pressure, kPa 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 450 500 550 600 650 700 750 800 900 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 –40 –30 –22 –15 –3 7 15 22 29 35 40 45 50 54 58 62 66 69 73 76 79 82 85 88 93 98 103 107 112 118 123 129 134 139 143 148 152 156 160 *inHg, vacuum 11 R-12 HFC-134a Saturation Saturation Temperature, °C Temperature, °C –59 –45 –37 –30 –24 –20 –16 –12 –9 –6 –4 –1 2 4 6 8 12 16 19 22 25 28 30 33 37 42 49 56 62 68 73 78 82 86 90 94 98 101 104 –53 –40 –32 –26 –21 –17 –13 –10 –7 –4 –2 1 3 5 7 9 12 16 19 22 24 27 29 31 36 39 46 52 58 63 67 72 76 79 83 86 89 93 95 Table 2 Pressure/Temperature Chart Suva® HP62/R-502 Saturation Properties English Units SI Units R-502 HP62 R-502 HP62 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, kPa °C °C kPa °C °C R-502 HP62 R-502 HP62 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, psi °F °F psi °F °F 25* 20* 15* 10* 5* 4* 3* 2* 1* 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 –108 –88 –75 –65 –56 –55 –54 –53 –52 –50 –45 –40 –36 –32 –29 –25 –22 –19 –16 –13 –11 –8 –6 –3 –1 1 3 5 7 9 11 13 15 16 18 20 21 23 –107 –87 –75 –65 –57 –56 –54 –53 –52 –50 –45 –41 –37 –33 –30 –26 –23 –20 –18 –15 –12 –10 –7 –5 –3 –1 2 3 5 7 9 11 12 14 16 17 19 20 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 105 110 115 120 125 130 135 140 145 150 175 200 250 300 350 400 24 26 27 29 30 32 33 34 36 37 38 40 41 42 43 45 46 47 48 49 50 51 54 57 60 62 64 67 69 71 73 75 85 95 111 125 137 148 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 22 23 25 26 28 29 30 32 33 34 35 36 37 38 40 41 43 44 45 46 47 48 51 53 56 58 60 63 65 67 69 71 81 89 104 118 129 140 *inHg, vacuum 12 –72 –60 –52 –46 –41 –37 –33 –30 –27 –24 –22 –19 –17 –15 –13 –11 –9 –8 –6 –4 –1 2 4 7 9 11 13 15 17 19 21 23 25 26 28 29 31 32 –71 –59 –52 –46 –41 –37 –34 –30 –28 –25 –22 –20 –18 –16 –14 –12 –10 –9 –7 –6 –3 0 2 5 7 9 11 13 15 17 19 20 22 24 25 27 28 30 1450 1500 1550 1600 1650 1700 1750 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 34 35 37 38 39 41 42 43 46 48 50 52 54 56 58 60 62 64 65 31 32 34 35 36 37 38 40 42 44 46 48 50 52 54 56 57 59 61 Table 3 Pressure/Temperature Chart Suva® 507/R-502 Saturation Properties English Units SI Units R-502 507 R-502 507 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, kPa °C °C kPa °C °C R-502 507 R-502 507 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, psi °F °F psi °F °F 25* 20* 15* 10* 5* 4* 3* 2* 1* 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 –108 –88 –75 –65 –56 –55 –54 –53 –52 –50 –45 –40 –36 –32 –29 –25 –22 –19 –16 –13 –11 –8 –6 –3 –1 1 3 5 7 9 11 13 15 16 18 20 21 23 –110 –90 –77 –67 –61 –59 –58 –57 –56 –54 –48 –44 –39 –36 –32 –29 –26 –23 –20 –17 –15 –12 –10 –8 –6 –3 –1 1 3 4 6 8 10 11 13 15 16 18 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 105 110 115 120 125 130 135 140 145 150 175 200 250 300 350 400 24 26 27 29 30 32 33 34 36 37 38 40 41 42 43 45 46 47 48 49 50 51 54 57 60 62 64 67 69 71 73 75 85 95 111 125 137 148 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 550 600 650 700 750 800 850 900 950 19 21 22 24 25 26 28 29 30 32 33 34 35 37 38 39 40 41 42 43 44 46 48 51 53 55 58 60 62 64 66 69 78 87 102 115 127 137 *inHg, vacuum 13 –72 –60 –52 –46 –41 –37 –33 –30 –27 –24 –22 –19 –17 –15 –13 –11 –9 –8 –6 –4 –1 2 4 7 9 11 13 15 17 –72 –61 –53 –47 –43 –39 –35 –32 –29 –26 –24 –22 –19 –17 –15 –14 –12 –10 –9 –7 –4 –2 1 4 6 8 10 12 14 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 19 21 23 25 26 28 29 31 32 34 35 37 38 39 41 42 43 46 48 50 52 54 56 58 60 62 64 65 16 17 19 21 22 24 25 27 28 30 31 32 34 35 36 37 38 41 43 45 47 49 51 53 54 56 58 59 Table 4 Pressure/Temperature Chart Suva® HP62/R-22 Saturation Properties English Units SI Units R-22 HP62 R-22 HP62 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, kPa °C °C kPa °C °C R-22 HP62 R-22 HP62 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, psi °F °F psi °F °F 25* 20* 15* 10* 5* 4* 3* 2* 1* 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 –100 –80 –66 –56 –48 –47 –45 –44 –43 –41 –36 –32 –28 –24 –20 –17 –14 –11 –8 –5 –2 0 2 5 7 9 11 13 15 17 19 21 23 24 26 28 29 31 –107 –87 –75 –65 –57 –56 –54 –53 –52 –50 –45 –41 –37 –33 –30 –26 –23 –20 –18 –15 –12 –10 –7 –5 –3 –1 2 3 5 7 9 11 12 14 16 17 19 20 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 105 110 120 125 130 135 140 145 150 175 200 250 300 350 400 32 34 35 37 38 40 41 42 44 45 46 48 49 50 51 52 54 55 56 57 58 59 62 64 69 72 74 76 78 81 83 93 101 117 131 143 154 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 22 23 25 26 28 29 30 32 33 34 35 36 37 38 40 41 43 44 45 46 47 48 51 53 58 60 63 65 67 69 71 81 89 104 118 129 140 *inHg, vacuum 14 –67 –55 –47 –41 –36 –32 –28 –25 –22 –20 –17 –15 –12 –10 –8 –7 –5 –3 –1 0 3 6 8 11 13 15 18 20 22 23 25 27 29 30 32 33 35 36 –71 –59 –52 –46 –41 –37 –34 –30 –28 –25 –22 –20 –18 –16 –14 –12 –10 –9 –7 –6 –3 0 2 5 7 9 11 13 15 17 19 20 22 24 25 27 28 30 1450 1500 1550 1600 1650 1700 1750 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 38 39 40 42 43 44 46 47 49 51 53 56 58 59 61 63 65 67 68 31 32 34 35 36 37 38 40 42 44 46 48 50 52 54 56 57 59 61 Table 5 Pressure/Temperature Chart Suva® 507/R-22 Saturation Properties English Units SI Units R-22 507 R-22 507 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, kPa °C °C kPa °C °C R-22 507 R-22 507 Pressure, Sat. Temp, Sat. Temp, Pressure Sat. Temp, Sat. Temp, psi °F °F psi °F °F 25* 20* 15* 10* 5* 4* 3* 2* 1* 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 –100 –80 –66 –56 –48 –47 –45 –44 –43 –41 –36 –32 –28 –24 –20 –17 –14 –11 –8 –5 –2 0 2 5 7 9 11 13 15 17 19 21 23 24 26 28 29 31 –110 –90 –77 –67 –61 –59 –58 –57 –56 –54 –48 –44 –39 –36 –32 –29 –26 –23 –20 –17 –15 –12 –10 –8 –6 –3 –1 1 3 4 6 8 10 11 13 15 16 18 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 105 110 120 125 130 135 140 145 150 175 200 250 300 350 400 32 34 35 37 38 40 41 42 44 45 46 48 49 50 51 52 54 55 56 57 58 59 62 64 69 72 74 76 78 81 83 93 101 117 131 143 154 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 550 600 650 700 750 800 850 900 950 19 21 22 24 25 26 28 29 30 32 33 34 35 37 38 39 40 41 42 43 44 46 48 51 55 58 60 62 64 66 69 78 87 102 115 127 137 *inHg, vacuum 15 –67 –55 –47 –41 –36 –32 –28 –25 –22 –20 –17 –15 –12 –10 –8 –7 –5 –3 –1 0 3 6 8 11 13 15 18 20 22 –72 –61 –53 –47 –43 –39 –35 –32 –29 –26 –24 –22 –19 –17 –15 –14 –12 –10 –9 –7 –4 –2 1 4 6 8 10 12 14 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 23 25 27 29 30 32 33 35 36 38 39 40 42 43 44 46 47 49 51 53 56 58 59 61 63 65 67 68 16 17 19 21 22 24 25 27 28 30 31 32 34 35 36 37 38 41 43 45 47 49 51 53 54 56 58 59 Table 6 Suva® 134a (R-134a) Physical Properties Unit Suva® 134a (R-134a) R-12 °F °C –14.9 –26.1 –21.6 –29.8 psia kPa 96.61 666.1 94.51 651.6 Liquid Density at 77°F (25°C) lb/ft3 kg/m3 75.28 1,206 81.84 1,311 Density Sat’d Vapor at 77°F (25°C) lb/ft3 kg/m3 2.02 32.4 2.32 37.2 Ozone-Depletion Potential Compared with CFC-12 CFC-12 = 1 0 1 Global Warming Potential Compared with CO2 CO2 = 1 1300 8500 Physical Property Boiling Point at 1 atm Vapor Pressure Sat’d Liquid at 77°F (25°C) Table 7 Suva® HP62 (R-404A) and Suva® 507 (R-507) Physical Properties Unit Suva® HP62 (R-404A) Suva® 507 (R-507) R-502 R-22 °F °C –51.6 –46.5 –52.1 –46.7 –49.8 –45.4 –41.4 –40.8 psia kPa 182 1,255 187 1,287 168 1,162 151 1,041 Liquid Density at 77°F (25°C) lb/ft3 kg/m3 65.45 1,048 65.5 1,049 75.9 1,217 74.5 1193 Density Sat’d Vapor at 77°F (25°C) lb/ft3 kg/m3 4.0 64.1 4.3 68.9 4.2 67.3 2.8 44.9 Ozone-Depletion Potential Compared with R-12 R-12 = 1 0 0 0.23 0.05 Global Warming Potential Compared with CO2 CO2 = 1 3260 3300 5494 1700 Physical Property Boiling Point at 1 atm Vapor Pressure Sat’d Liquid at 77°F (25°C) Table 8 Compositions of Suva® Refrigerants Compositions, wt% HFC-125 HFC-143a Suva® HP62 (R-404A) 44 52 Suva® 507 (R-507) 50 50 ® Suva 134a (R-134a) HFC-134a 4 100 16 13 For Further Information: DuPont Fluorochemicals Wilmington, DE 19880-0711 (800) 235-SUVA www.suva.dupont.com Europe Japan DuPont de Nemours International S.A. 2 Chemin du Pavillon P.O. Box 50 CH-1218 Le Grand-Saconnex Geneva, Switzerland 41-22-717-5111 Mitsui DuPont Fluorochemicals Co., Ltd. Chiyoda Honsha Bldg. 5-18, 1-Chome Sarugakucho Chiyoda-Ku, Tokyo 101-0064 Japan 81-3-5281-5805 Canada DuPont Canada, Inc. P.O. Box 2200, Streetsville Mississauga, Ontario Canada L5M 2H3 (905) 821-3300 Mexico DuPont, S.A. de C.V. Homero 206 Col. Chapultepec Morales C.P. 11570 Mexico, D.F. 52-5-722-1100 South America DuPont do Brasil S.A. Alameda Itapecuru, 506 Alphaville 06454-080 Barueri São Paulo, Brazil 55-11-7266-8263 DuPont Argentina S.A. Casilla Correo 1888 Correo Central 1000 Buenos Aires, Argentina 54-1-311-8167 Pacific DuPont Australia P.O. Box 930 North Sydney, NSW 2060 Australia 61-2-99236111 Asia DuPont Taiwan P.O. Box 81-777 Taipei, Taiwan 886-2-514-4400 DuPont China Limited P.O. Box TST 98851 1122 New World Office Bldg. (East Wing) Tsim Sha Tsui Kowloon, Hong Kong Phone: 852-734-5398 Fax: 852-236-83516 DuPont Thailand Ltd. 9-11 Floor, Yada Bldg. 56 Silom Road Suriyawongse, Bankrak Bangkok 10500 Phone: 66-2-238-0026 Fax: 66-2-238-4396 DuPont China Ltd. Rm. 1704, Union Bldg. 100 Yenan Rd. East Shanghai, PR China 200 002 Phone: 86-21-328-3738 Telex: 33448 DCLSH CN Fax: 86-21-320-2304 DuPont Far East Inc. 6th Floor Bangunan Samudra No. 1 JLN. Kontraktor U1/14, SEK U1 Hicom-Glenmarie Industrial Park 40150 Shah Alam, Selangor Malaysia Phone 60-3-517-2534 DuPont Korea Inc. 4/5th Floor, Asia Tower #726, Yeoksam-dong, Kangnam-ku Seoul, 135-082, Korea 82-2-721-5114 DuPont Singapore Pte. Ltd. 1 Maritime Square #07 01 World Trade Centre Singapore 0409 65-273-2244 DuPont Far East, Philippines 8th Floor, Solid Bank Bldg. 777 Paseo de Roxas Makati, Metro Manila Philippines Phone: 63-2-818-9911 Fax: 63-2-818-9659 DuPont Far East Inc. 7A Murray’s Gate Road Alwarpet Madras, 600 018, India 91-44-454-029 DuPont Far East Inc.—Pakistan 9 Khayaban-E-Shaheen Defence Phase 5 Karachi, Pakistan 92-21-533-350 DuPont Far East Inc. P.O. Box 2553/Jkt Jakarta 10001, Indonesia 62-21-517-800 The information contained herein is based on technical data and tests which we believe to be reliable and is intended for use by persons having technical skill, at their own discretion and risk. Because conditions of use are outside of DuPont control, we can assume no liability for results obtained or damages incurred through the application of the data presented. (5/02) 300229B Printed in U.S.A. [Replaces: H-75326-2] Reorder No.: H-75326-3
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Encryption : Standard V1.2 (40-bit) User Access : Print, Copy, Annotate, Fill forms, Extract, Assemble, Print high-res Create Date : 2002:05:31 15:43:01Z Subject : DuPont Suva refrigerants technical literature Keywords : dupont, suva, refrigerants, retrofit, guidelines, hfc, 134a, r-12, hp62, 507, r-502, r-22 Modify Date : 2002:06:14 11:16:45-04:00 Page Count : 20 Creation Date : 2002:05:31 15:43:01Z Producer : Acrobat Distiller 3.01 for Windows Author : DuPont Fluorochemicals Mod Date : 2002:06:14 11:16:45-04:00 Description : DuPont Suva refrigerants technical literature Creator : DuPont Fluorochemicals Title : Retrofit Guidelines for Suva(R) HFC RefrigerantsEXIF Metadata provided by EXIF.tools