EMC Departmental Switch
DS-xxB2

Guide for Installation of Switches
Into Third-Party Racks
P/N 300-000-267
Rev. A02
November 7, 2002

This document describes the requirements for installing EMC
Deparmental Switches (DS-xxB2) into both EMC and non-EMC
third-party racks.

Major sections discussed in this guide are as follows:
◆
◆
◆
◆
◆
◆
◆
◆

Overview ................................................................................................2
Device Power, Cooling, and Weight Information .............................3
Device Dimensions................................................................................3
Device Placement Requirements.........................................................4
Switch Mounting Kit (DS16B2RKLS) .................................................5
Installing the DS-xxB2 Rails.................................................................8
Installing the DS-xxB2 Switch............................................................17
Where to Get Help...............................................................................21

1

Overview

Overview
The Departmental Switch Models DS-16B2 and DS-32B2 are fibre
channel gigabit switches that support link speeds up to 2 Gb/s. Each
port can automatically negotiate to the highest common speed of all
devices connected to the port. The ports are compatible with small
form factor pluggable media (SFPs), are universal, self configuring,
and are capable of individually becoming a fabric-enabled port
(F_Port), fabric loop enabled port (FL_Port), or an expansion port
(E_Port).
The Departmental Switch Model DS-16B2 is one rack unit in height,
has an air-cooled chassis, and can be set up as a stand-alone unit or
mounted in a 19-inch rack. The Departmental Switch Model DS-32B2
is an air-cooled 1.5U chassis; can be set up as a stand-alone unit or
mounted in a standard Electronic Industries Association (EIA)
19-inch rack.
Table 1 lists the departmental switches and mounting kit model
numbers.
Table 1

Departmental Switch and Mounting Kit Model Numbers.
Device

Device Model

Mounting Kit Model

16-port Departmental Switch

DS-16B2-00

DS16B2RKLS

32-port Departmental Switch

DS-32B2-00

DS16B2RKLS

Figure 1 shows an example of the DS-xxB2.

EMC2041

Figure 1

2

DS-xxB2

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Device Power, Cooling, and Weight Information

Device Power, Cooling, and Weight Information
Table 2 lists the power and cooling requirements and weight
information for the DS-16B2 and DS32B2 switches.
Table 2

Device Power, Cooling, and Weight Information
Cooling Requirements
(Heat Dissipation)

Maximum Weight

DS-16B2 switch Voltage: 100 to 240 V ac, 47 to 63 Hz

368.5 BTU/hr

12.9 kg (28.5 lbs)

DS-32B2 switch Voltage: 100 to 240 V ac, 47 to 63 Hz

1876 BTU/hr

16.2 kg (35.8 lbs)

Device

Power Requirements

Device Dimensions
Table 3 gives the height, depth, and width for the DS-16B2 switch, the
DS-16B2 switch with rails, and the DS-32B2 switch
Table 3

Device Dimensions

Device

Height

Depth

Width

DS-16B2 switch

4.34 cm

1.71 in 61.00 cm

24.01 in

42.86 cm

16.87 in

DS-16B2 switch
with rails

1.0 U

4.44 cm

1.75 in 61.00 cm

24.01 in

43.18 cm

17.00 in

DS-32B2 switch

1.50

6.55 cm

2.58 in 58.56 cm

23.06 in

42.86 cm

16.87 in

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

3

Device Placement Requirements

Device Placement Requirements
There are no restrictions on the location of the DS-xxB2 switch in the
rack/cabinet.
Switches are typically located at the top of the rack/cabinet.

Power distribution must support the number of outlets required for
the switch and the switch power rating listed in Table 2 on page 3.

Front

Rear
EMC2056S

Figure 2

4

Sample Cabinet Installation

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Switch Mounting Kit (DS16B2RKLS)

Switch Mounting Kit
(DS16B2RKLS)
The switch mounting kit includes rails, and brackets as listed inTable
4.
Table 4

Switch Mounting Kit

Component

Use

2 switch mounting brackets (see Figure 15 on page 17)

2 per switch

2 short rail assemblies (20.5 inches to 27 inches)

2 per switch

2 long rail assemblies (27 inches to 34 inches)

2 per switch

Figure 3 illustrates these components.

Switch
Mounting
Brackets

Short
Rear
Rails

Front
Rails

Long
Rear
Rails
EMC2042S

Figure 3

Rails and Brackets

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

5

Switch Mounting Kit (DS16B2RKLS)

Screws, Nuts and Washers
Table 5 lists all the securing hardware that is included in the switch
mounting kit.

Table 5

Screws, Nuts and Washers

Component

6

Use
#10 flat washer (Qty. 4)

2 per rail assembly to secure adjustable
rail to the “C” channel.

M5 keps nut (Qty. 4)

2 per rail assembly to secure adjustable
rail to the “C” channel.

8-32 x 5/16-in. pan-head screw (Qty. 6)

3 per mounting bracket to secure
mounting bracket to switch.

M5 x 10-mm pan-head screw (Qty. 8)

4 per rail for DS-16B2 in round-hole
channels.

Square-hole washer (Qty. 8)

4 per rail for DS-16B2 in square-hole
channels.

M5 x 16-mm flat-head screw (Qty. 8)

4 per rail for DS-16B2 in square-hole
channels.

M3 x 8-mm pan-head screw (Qty. 2)

1 per switch mounting bracket. Used to
secure mounting brackets to the rails.

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Switch Mounting Kit (DS16B2RKLS)

Tools Required for Installation
You will need the tools shown in Figure 4 to complete the installation
of the rails and one or more switches.

Tools Required:

#1 Phillips
Screwdriver

6-mm (1/4-in.)
Nut Driver

8mm (5/16-in.)
Nut Driver
EMC2065

Figure 4

Tools Required for Installation

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

7

Installing the DS-xxB2 Rails

Installing the DS-xxB2 Rails
This section describes the installation procedures for the DS-xxB2
rails. Figure 5 shows a view of the rails installed in a 39 U
rack/cabinet.

Rear Door
Removed for
Clarity
Rear

Front
Figure 5

8

View of the Rails Installed in a 39 U Rack/Cabinet

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

EMC2071S

Installing the DS-xxB2 Rails

DS-xxB2 Rails Installation
There are two different length rails, see Figures 6 and 7. The short
rails range between 20.5 inches and 27 inches. The long rails range
between 27 inches and 34 inches. If your rail kit contains two different
length rear rail mounts, be sure to use the rail length that is
appropriate for your rack/cabinet.

To the rear
of the cabinet

EMC2059

Figure 6

DS-xxB2 Short Rear Rails

To the rear
of the cabinet

EMC2060

Figure 7

DS-xxB2 Long Rear Rails

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

9

Installing the DS-xxB2 Rails

The front and rear flanges of the DS-xxB2 rails have three screw holes.
See Figures 8 and 9.

Front
Rails
Screw
Holes

Figure 8

EMC2069

Front Flange of the DS-xxB2 Rails

Screw
Holes

Short
Rear
Rails

Long
Rear
Rails

Figure 9

10

Rear Flange of the DS-xxB2 Rails

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Screw
Holes

EMC2070

Installing the DS-xxB2 Rails

Select the appropriate length rails, and follow the steps below to
install them. The rails assembly consists of a front rail, an adjustable
rear rail, and two washers and keps nuts. Figure 10 illusrates the
complete assembly.

Keps Nut
(2)
#10 Flat
Washer
(2)
Short
Rear
Rail
Front
Rail

Front
Rail

Figure 10

Short
Rear
Rail

#10 Flat
Washer
(2)

Keps Nut
(2)
EMC2044S

DS-xxB2 Rails Assembly

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

11

Installing the DS-xxB2 Rails

Assembling the Rails
To assemble the rails:

1. Place the front rail down on a table.
2. Insert the slots of the rear adjustable rail onto the threaded posts
on the front rail. Be sure that the lip on the top of the rear
adjustable rail slides over the top of the slot on the front rail,
thereby capturing the ac power cord.
3. Secure the adjustable rail to the front rail with two #10 flat
washers and M5 keps nuts. Leave the keps nuts finger tight (see
Figure 11).

Keps
Nut
EMC2066S

Figure 11

Location of Keps Nuts

4. Determine where in the rack/cabinet you will locate the switch.
5. Adjust the length of the rail to fit between the channels in the
rack/cabinet.

12

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Installing the DS-xxB2 Rails

Keps
Nut

Keps
Nut
EMC2045S

Figure 12

Securing the Keps Nuts
If the side skins are removed on the rack/cabinet, the keps nuts can be
tightened after the rails have been installed.

Round-Hole Channel
To install the rails assembly in the round-hole channel of the
rack/cabinet:

1. Align the holes of the front rail flange to the inside of the front
channel. The top and bottom screw holes are used for the screws.
2. Secure the rail to a round-hole channel with 2 M5 x 10-mm panhead screws (see table on Table 5 on page 6). Leave the screws
finger-tight, and tighten them after the switch is installed. See
Figure 13 on page 14.
3. Align the holes in the rear, U-shaped flange of the rail with the
holes in the rear inside channel.
4. Secure the rail to a round-hole channel with 2 M5 x 10-mm panhead screws (see table on Table 5 on page 6). Leave the screws
finger-tight, and tighten them after the switch is installed. See
Figure 13.
5. Repeat steps 1 through 4 for the other rail.
See instructions for Square-Hole Channel on page 15.

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

13

Installing the DS-xxB2 Rails

Align the rear rail
flange to the inside
of the channel.

Rack
Rear

Align the front rail
flange to the inside
of the channel.

Rack
Front

Rear

M5 x 10-mm
Pan Head
Screw
(8)
Front
EMC2046S

Figure 13

14

Installing Rails in Round-Hole Channels

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Installing the DS-xxB2 Rails

Square-Hole Channel
To install the rails assembly in the square-hole channel of the
rack/cabinet.

1. Align the holes of the front rail flange to the inside of the front
channel. The top and bottom screw holes are used for the screws
(see Figure 14 on page 16).
2. Secure the rail to a square-hole channel with two square-hole
washers and M5 x 16-mm flat-head screws (see Table 5 on
page 6). Leave the screws finger-tight, and tighten them after the
switch is installed.
3. Align the holes in the rear, U-shaped flange of the rail with the
holes in the rear inside channel, as shown in Figure 14.
4. Secure the rail to a square-hole channel with two square-hole
washers and M5 x 16-mm flat head screws (see Table 5 on page 6).
Leave the screws finger-tight, and tighten them after the switch is
installed.
5. Repeat steps 1 through 4 for the other rail.
See instructions for Round-Hole Channel on page 13.

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

15

Installing the DS-xxB2 Rails

Rack
Rear

Rack
Front

Align the rear rail
flange to the inside
of the channel.

Align the front rail
flange to the inside
of the channel.

M5 x 16-mm
flat head screw
(Qty. 8)

Square-Hole
Washer
(Qty. 8)

EMC2047S

Figure 14

16

Installing Rails in Square-Hole Channels

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Installing the DS-xxB2 Switch

Installing the DS-xxB2 Switch
This section describes the procedures for installing the DS-xxB2
switch in a rack/cabinet, including attaching the brackets on the
switch.

Mounting Bracket Installation
You must attach mounting brackets to the switch before installing it
on the rails. The mounting brackets slide into the “C” channel of the
rails.
To attach the mounting brackets to the switch:

1. Orient the L-shaped end of the bracket outward and to the power
outlet end of the switch.
2. Place the bracket against the switch. Align the three screw holes
in the bracket with three screw holes on the side of the switch (see
Figure 15 on page 17).
3. Secure the bracket with three 8-32 x 5/16-in. pan-head screws (see
Table 5 on page 6). Tighten the screws fully.
4. Repeat steps 1 through 3 for the other side of the switch to be
mounted.

Switch
Mounting
Bracket

#8-32 x 5/16-in.
Pan Head Screw
(6)

Hole

Switch
Mounting
Bracket

Figure 15

EMC2048

Attaching the Switch Mounting Brackets

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

17

Installing the DS-xxB2 Switch

Installing the Switch in the Rack/Cabinet
To install the switch in the rack/cabinet:

1. Lift and orient the switch so that the fan end is to the front of the
rack/cabinet.
2. Align the bracket on each side of the switch with the “C” channel
on each fixed rail.
3. Push the switch into the rack/cabinet until the hole in the front
part of each bracket (the “L”-shaped end) aligns with the hole on
the fixed rail.

EMC2049S

Figure 16

Placing the Switch Into the Rack/Cabinet

4. Secure the brackets to the rails with two M3 x 8-mm pan-head
screws (see Table 5 on page 6), one on each side, (Figure 17 on
page 19).

18

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

Installing the DS-xxB2 Switch

M3 x 8-mm
Pan Head
Screw
(2)
Figure 17

EMC2050S

Securing the brackets to the Rails

5. Tighten the rear screws securing the rails to the rear of the
rack/cabinet (see Figure 18 on page 20).
6. Tighten the front screws securing the rails to the front of the
rack/cabinet (see Figure 18).

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

19

Installing the DS-xxB2 Switch

Rail Assembly
Screw
(4)

Rail
Assembly
Screw
(4)
Figure 18

20

Tightening the Front and Rear Rail Assembly Screws

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

EMC2051S

Where to Get Help

Where to Get Help
For questions about technical support call your local sales office or
service provider.
If you have a valid EMC service contract, contact EMC Customer
Service at:
United States: (800) 782-4362 (SVC-4EMC)
Canada:

(800) 543-4782 (543-4SVC)

Worldwide:

(508) 497-7901

Follow the voice menu prompts to open a service call and select the
applicable product support.
If you are located outside the North America, call the nearest EMC
office for technical assistance.
Sales and Customer
Service Contacts

For the list of EMC sales locations, please access the EMC home page
at:
http://www.EMC.com/contact/

For additional information on the EMC products and services
available to customers and partners, refer to the EMC Powerlink
website at:
http://powerlink.EMC.com

Your Comments

Your suggestions will help us continue to improve the accuracy,
organization, and overall quality of the user publications. Please send
a message to techpub_comments@EMC.com with your opinions of
this guide.

EMC Departmental Switch DS-xxB2 Into Third-Party Racks

21

Where to Get Help

Copyright © 2002 EMC Corporation. All Rights Reserved.
EMC believes the information in this publication is accurate as of its publication date. The information is subject to
change without notice.
THE INFORMATION IN THIS PUBLICATION IS PROVIDED "AS IS." EMC CORPORATION MAKES NO
REPRESENTATIONS OR WARRANTIES OF ANY KIND WITH RESPECT TO THE INFORMATION IN THIS
PUBLICATION, AND SPECIFICALLY DISCLAIMS IMPLIED WARRANTIES OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE.
Use, copying, and distribution of any EMC software described in this publication requires an applicable software
license.

22

EMC Departmental Switch DS-xxB2 Into Third-Party Racks



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Modify Date                     : 2002:11:08 10:16:41-05:00
Create Date                     : 1995:06:29 12:54:00Z
Creator                         : FrameMaker 6.0
Subject                         : P/N 300-000-267 Rev A02
Page Count                      : 22
Page Mode                       : UseOutlines
Producer                        : Acrobat Distiller 4.05 for Windows
Mod Date                        : 2002:11:08 10:16:41-05:00
Creation Date                   : 1995:06:29 12:54:00Z
Metadata Date                   : 2002:11:08 10:16:41-05:00
Title                           : EMC Departmental Switch DS-xxB2, Guide for Installation of Switches Into Third-Party Racks
Description                     : P/N 300-000-267 Rev A02
EXIF Metadata provided by EXIF.tools

Navigation menu