Product Data Document
420DS-2b
July 16, 2007 - Page 

Bristol® ControlWave® Remote Ethernet I/O
With the ever-increasing demand for distributed
I/O architectures Bristol® ControlWave® Remote
I/O modules, from Emerson Process Management,
are the ideal solution to minimize installation cost.
The compact DIN-rail mount modules provide an
open connectivity through 10 Mbps Ethernet and
38.4 KB serial RS 485. The wide range of module
I/O configurations brings exceptional flexibility to
network diversity. Each module is designed and
rated for harsh industrial environments, a perfect
compliment to the ControlWave Process Automation
Management Solution as well as our Network 3000
measurement and control system.

Features
•

Open Modbus (Modbus TCP) Ethernet
connectivity

•

RS 485 Modbus RTU or Modbus ASCII

•

Easy-to-use ConfigTools software configuration

•

Internal 24 V dc loop power minimizes wiring 	
cost

•

‘Hot Swap’ I/O module replacement

•

10 – 30 V dc power input

•

-30 to +70°C operating temperature range

•

CSA, UL Class I, Div. 2 Groups A-D, and CE 	
approved

Specifications
All I/O
•

Compact 4 ¾” W x 3 ¼” H x 4 1/8” D

•

10 – 30 V dc power input

•

1.2 Watt typical per module (48 mA @ 24 Vdc) 	
– varies by module and load

•

Temperature: -30 to +70°C operating
temperature range

Remote Automation Solutions
Website: www.EmersonProcess.com/Remote

•

Humidity: 5 – 95% non-condensing

•

RS 485 port Master or Slave up to 38400 baud 	
– up to 32 nodes per line

•

Up to 16,000 nodes per network

•

10Base T at 10 Mbps Ethernet port

•

1200 V RMS 1 minute isolation on Ethernet 		
port

•

ESD (Electro Static Discharge) withstand: 8KV

•

Vibration meets IEC 68-2-6

	

	

1g for 10 Hz to 150 Hz

	

.5g for 150 Hz to 2000 Hz

The ControlWave Remote Ethernet I/O series consists of seven modules
ControlWave Discrete Input Module
•

Number of inputs: 16

•

Input source or sink: Configurable

•

Input voltage: 12/24 V AC/DC

•

Input resistance: 3.6 KΩ

•

One High Speed Counter channel up to 2 KHz

•

Scan rate: 2 mS

•

Power: .75 watt

Product Data Document
420DS-2b
July 16, 2007 - Page 

Bristol® Remote Ethernet I/O

ControlWave Discrete Output Module

•

Between inputs and ground: 1200 Volts

•

Number of outputs: 16

•

•

Output voltage: 10 to 30 Vdc

Input impedance: Voltage 200 KΩ Current 100
Ohms

•

Maximum output current per channel: 1 Amp

•

Input current protection: field replaceable 		
fusible shunts

•

Maximum output current (all 8 channels): 8 Amp

•

Scan rate: 100 mS

•

Maximum off state leakage current: 0.05 mA

•

Pulse duration output: Configurable

•

Scan rate: 2 mS

ControlWave RTD/DI Input Module
•

Number of inputs: 4 RTD inputs and 4 DI

•

RTD inputs: 100 ohm platinum, -200 to +850°C

ControlWave Analog Input Module

•

A/D resolution: 16 bit (0.0031%)

•

Number of inputs: 16

•

Scan rate: 700 ms (4 RTD)

•

Input range: 4-20 mA - internal or external loop 	
powered

•

DI specifications same as for 16 DI module

•

A/D resolution: 14 bit (0.01%)

•

Scan rate: 20 ms (4 DI)

•

Full scale accuracy @ 20°C: +/-0.05%

ControlWave Mixed 8DI/8AI Input Module

•

Span and offset temp. coefficient: +/- 50 ppm
per°C

•

Number of inputs: 8 AI and 8 DI

•

Input impedance: 100 Ohms

•

Specification same as 16 AI module and 16 DI 	
module

•

Input current protection: field replaceable 		
fusible shunts

ControlWave Mixed 8DI/8DO Input Module

•

Scan rate: 5 mS

•

Number of inputs: 8 DI and 8 DO

•

Specification same as 16 DI module and 16 DO 	
modules

ControlWave Analog Instrumentation Input Module
•

Number of inputs: 8

ControlWave Mixed 8AI/4AO Module

•

Input range: Isolated Current or Thermocouple

•

Number of inputs: 8 AI and 4 AO

•

4-20 mA - internal or external loop powered

•

Specification for AI’s same as 16 AI module

•

J, K, E, R, T, B, C, N, S thermocouple Coldjunction compensated and reported as °F, °C,
or 0.1°C

•

Output range: 4 – 20 mA

•

D/A resolution: 16 bit

•

Full scale accuracy @ 20°C: +/-0.02%

•

Maximum output settling time: 5 mS

•

External loop supply: 10 – 30 V dc

•

Load resistance: 0 – 750 Ω

•

A/D resolution: 16 bit (0.0031%)

•

Full scale accuracy @ 20°C: +/-0.02%

•

Span and offset temp. coefficient: +/- 30 ppm
per°C

•

Common mode isolation:

•

Short circuit protection: Current limiting

•

Between two input terminals: +/-25 V dc

•

Scan rate: 5 mS

Remote Automation Solutions
Website: www.EmersonProcess.com/Remote

Product Data Document
420DS-2b
July 16, 2007 - Page 

Bristol® Remote Ethernet I/O

ControlWave Ethernet I/O Configuration Tools

Remote Setup Module

The ControlWave Ethernet I/O Tool Kit is a Windows
configuration utility for initial setup and testing of all
Ethernet I/O modules. This easy to use utility allows
assignment of communication paramenters

In conjunction with the configuration software, the
Remote Setup Module provides a RS 232 interface
to the PC allowing the Ethernet module base to be
initially configured with a I/P, module address RS
485 port baud rate, etc. The Setup module plugs
into any Ethernet I/O base so one Setup module
can be used for the entire system. All Ethernet I/O
modules can be configured through a local Ethernet
connection with the configuration software only or
through a Ethernet network using the Setup module.
The Setup module is most useful when configuring a RS 485 network since it allows configuration
through a RS 232 PC port rather than requiring the
RS 485 in the PC.

including I/P address, comm port baud rate and
module address. It also provides I/O setup, tag
name assignment, scaling factors, etc.
Once the module is configured it can be tested for
proper operation before being put into operation.

© 2007 Remote Automation Solutions, division of Emerson Process Management. All rights reserved.
Bristol, Inc., Bristol Babcock Ltd, Bristol Canada, BBI SA de CV and the Flow Computer Division , are wholly owned subsidiaries of Emerson Electric Co. doing business as Remote Automation Solutions (“RAS”), a division of Emerson Process Management. FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow and Helicoid are trademarks of RAS. AMS,
PlantWeb and the PlantWeb logo are marks of Emerson Electric Co. The Emerson logo is a trademark and service mark of the Emerson Electric Co. All other marks are property of their
respective owners.
The contents of this publication are presented for informational purposes only. While every effort has been made to ensure informational accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. RAS reserves the right to modify or improve the designs or
specifications of such products at any time without notice. All sales are governed by RAS’ terms and conditions which are available upon request. RAS does not assume responsibility for
the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any RAS product remains solely with the purchaser and end-user.

Emerson Process Management
Remote Automation Solutions
Watertown, CT 06795 USA		
Mississauga, ON 06795 Canada	
Worcester WR3 8YB UK		

T 1 (860) 945-2200
T 1 (905) 362-0880
T 44 (1) 905-856950

Website: www.EmersonProcess.com/Remote



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1.1-111
Create Date                     : 2007:08:24 10:11:52-04:00
Metadata Date                   : 2007:08:24 10:11:53-04:00
Modify Date                     : 2007:08:24 10:11:53-04:00
Creator Tool                    : Adobe InDesign CS2 (4.0.5)
Instance ID                     : uuid:cc28993b-7ac7-4e89-8045-602de056bece
Document ID                     : adobe:docid:indd:aa1b01b4-33c5-11dc-87f9-95872396e8d4
Rendition Class                 : proof:pdf
Derived From Instance ID        : 792e2aa9-e1d7-11da-99a9-bb55861974e9
Derived From Document ID        : adobe:docid:indd:3a2f3f5e-e122-11da-af56-ca92ad94ea34
Manifest Link Form              : ReferenceStream
Manifest Placed X Resolution    : 300.00
Manifest Placed Y Resolution    : 300.00
Manifest Placed Resolution Unit : Inches
Manifest Reference Instance ID  : uuid:DF257867182BDC11A4CBD621E1E6385A
Manifest Reference Document ID  : uuid:DE257867182BDC11A4CBD621E1E6385A
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 3
Creator                         : Adobe InDesign CS2 (4.0.5)
EXIF Metadata provided by EXIF.tools

Navigation menu