Emerson Ae8 1385 Users Manual AE 1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors

2015-01-05

: Emerson Emerson-Ae8-1385-Users-Manual-164290 emerson-ae8-1385-users-manual-164290 emerson pdf

Open the PDF directly: View PDF PDF.
Page Count: 12

1
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Application Engineering
BULLETIN
Safety
Safety Instructions .................................................................2
Safety Icon Explanation ........................................................ 2
Instructions Pertaining to Risk of Electrical Shock, Fire,
or Injury to Persons ...............................................................3
Safety Statements .................................................................3
Introduction
Overview ...............................................................................4
Application Restrictions and Types ....................................... 4
Product Speci cations ...........................................................4
Installation
Mounting ...............................................................................4
Terminal Description ..............................................................4
Operation
Compressor Protection .........................................................4
Module LED Description ....................................................... 5
Module Operation/Code Description .....................................5
Resetting Alert Codes ........................................................... 6
Service
Module History Download ..................................................... 6
Warranty Information ............................................................. 6
Support .................................................................................. 6
Figures and Tables
Wires Pulled Through Module ............................................... 6
Module Dimensions in Millimeters ......................................... 7
Terminal Locations ................................................................7
Wiring Diagram ..................................................................... 8
Flash Code Description ......................................................... 9
LED Troubleshooting Information ...................................... 10-12
TABLE OF CONTENTS
AE8-1385
CoreSense Diagnostics
for Copeland Scroll® UltraTech® Air Conditioning Compressors
October 2011
2
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Safety Instructions
Copeland Scroll® compressors with CoreSense Diagnostics technology are manufactured according to the latest
U.S. and European Safety Standards. Particular emphasis has been placed on the user's safety. Safey icons are
explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These
instructions should be retained throughout the lifetime of the compressor. You are strongly advised to follow
these safety instructions.
Safety Icon Explanation
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous
situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
CAUTION, without the safety alert symbol, is used to address practices
not related to personal injury.
DANGER
WARNING
CAUTION
NOTICE
CAUTION
3
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
ELECTRICAL SHOCK HAZARD
• Disconnect and lock out power before servicing.
• Discharge all capacitors before servicing.
• Use compressor with grounded system only.
• Molded electrical plug must be used when required.
• Refer to original equipment wiring diagrams.
Failure to follow these warnings could result in serious personal injury.
PRESSURIZED SYSTEM HAZARD
• System contains refrigerant and oil under pressure.
• Remove refrigerant from both the high and low compressor side before
removing compressor.
• Never install a system and leave it unattended when it has no charge,
a holding charge, or with the service valves closed without electrically
locking out the system.
• Use only approved refrigerants and refrigeration oils.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in serious personal injury.
BURN HAZARD
• Do not touch the compressor until it has cooled down.
• Ensure that materials and wiring do not touch high temperature areas of
the compressor.
• Use caution when brazing system commponents.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in serious personal injury or
property damage.
COMPRESSOR HANDLING
• Use the appropriate lifting devices to move compressors.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in personal injury or
property damage.
Safety Statements
• Refrigerant compressors must be employed only for their intended use.
install, commission and maintain this equipment.
• All valid standards and codes for installing, servicing, and maintaining electrical and
refrigeration equipment must be observed.
Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons
WARNING
WARNING
WARNING
CAUTION
4
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
INTRODUCTION
Overview
CoreSense Diagnostics is a breakthrough innovation
for troubleshooting residential air conditioning and heat
pump systems. The CoreSense Diagnostics module
is easily installed in the unit electrical panel near the
compressor contactor. By using the compressor as
a sensor, CoreSense Diagnostics helps the service
technician more accurately troubleshoot system and
compressor fault conditions.
CoreSense Diagnostics also provides compressor
and system protection through its proprietary lockout
feature. Depending on the severity and frequency of
the fault that caused the trip condition, the CoreSense
Diagnostics module can lockout the compressor
contactor to prevent damage to the compressor and
system components. Less severe fault conditions
resulting in an occasional trip will not result in a lockout
condition.
Flashing LEDs communicate ALERT and LOCK codes
to the service technician.
Application Restrictions and Types
The CoreSense Diagnostics (571-0072-00) module
is designed and quali ed for use with ZPS*K5 single-
phase Copeland Scroll® UltraTech compressors.
Product Speci cations
Operating Temp: - 40° to 150°F (- 40° to 65°C)
Storage Temp: - 40° to 175°F (- 40° to 80°C)
Supply Voltage: 18 to 28VAC , 48 to 62Hz
Module Current Sensing Range: 2 to 30A
Maximum Power Consumption: 2.5 VA (Excluding
solenoid load)
INSTALLATION
Mounting
Four #8 or #10 self tapping or sheet metal screws are
required for installation of the module. The maximum
mounting screw torque is 20 in.lbs. Locate the
module near the compressor contactor (wire routing
for compressor run, common, and start wires will be
easier in this position). The module can be mounted
in any orientation and LEDs should be visible for ease
of service.
The compressor’s run (R), common (C), and start (S)
wires are routed through the holes in the CoreSense
module marked “R”,”C”, and “S”. See Figure 1.
Terminal Description
The terminals for the CoreSense Diagnostics module
are ¼” spade terminals.
• COMMON (C)
The 24 volt common terminal for module power.
• DEMAND (Y)
The demand terminal requires a 24VAC signal
measured with respect to the COMMON (C)
terminal when there is a call for heating or
cooling. A signal above 6VAC indicates the
thermostat wants the compressor to be on, while
0-6VAC signal indicates the thermostat wants
the compressor to be off.
• SECOND STAGE DEMAND (Y2)
The demand (Y) and second stage demand
(Y2) terminals require a 24VAC signal measured
with respect to the COMMON (C) terminal when
there is a call for heating or cooling. A signal
above 10VAC indicates the thermostat wants the
Ultratech solenoid to be energized, while 0-10VAC
signal indicates the thermostat wants the Ultratech
solenoid to be deenergized.
• PROTECTION (PROT)
The protection terminal is internally connected
to the COMMON terminal through a solid state
switch.
• POWER (R)
The module requires a constant 24VAC supply
power to this terminal. The module must receive
an independent power supply in order to operate
properly. See Figure 4.
• Thermostat Communication (L)
Provides a 24V signal to an indoor thermostat
indicating the number of ALERT ashes displayed
on the module. (Reference thermostat manual for
available capability)
• Solenoid (DC SOL)
Provides a connection to the Copeland Scroll
UltraTech second stage compressor solenoid. This
solenoid is internal to the compressor, and has
a voltage range of 18 to 28VDC. Please refer to
bulletin AE-1311 for information on the Copeland
Scroll® UltraTech® compressor.
5
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
OPERATION
Compressor Protection
The CoreSense Diagnostics module utilizes proprietary
algorithms to protect the compressor and system from
repeated trips of system pressure controls and the
compressor internal overload. The protection terminal
of the module should be wired in series with the system
low pressure and high pressure cutouts, as well as
the compressor contactor. When the module detects
a series of trips as described below, it will activate a
lockout feature that opens the solid state switch in the
module, thereby cutting power to the contactor and de-
energizing the compressor.
Module LED Description
POWER LED (Green): indicates the module is
powered with 18 to 28 volts.
ALERT LED (Yellow): communicates an abnormal
system condition through a unique ash code. The
ALERT LED will ash a number of times consecutively,
pause and then repeat the process. The number of
consecutive ashes, de ned as the Flash Code,
correlates to a particular abnormal condition. Detailed
descriptions of speci c ALERT Flash Codes are
shown in Table 1.
TRIP/LOCK LED (Red): indicates either a TRIP or
LOCK condition.
TRIP: is indicated by a solid illumination of the
LED. This means the compressor is not running
and demand is present at the module.
LOCK: is indicated by a ashing LED correlating to
a LOCK condition in which the module will prevent
the compressor from starting.
Module Operation/Code Description
Code 1 – Long Run Time
The module will ash yellow one time when the
compressor operates for longer than 18 continuous
hours. This is an alert code only, and the module will
not lockout the compressor for this condition. This
code is inactive for heat-pumps.
Code 2 – Compressor (Pressure) Trips
The module will ash yellow two times when the
compressor operates from 12 seconds to 15 minutes
followed by a trip condition lasting longer than 7
minutes. When four consecutive or ten total Code
2 events are recorded, the module will lockout the
compressor and ash red two times.
Code 3 – Pressure Switch Cycling
The module will ash yellow three times when the
compressor operates from 12 seconds to 15 minutes
followed by a trip condition lasting between 35
seconds to 7 minutes. When four consecutive or ten
total Code 3 events are recorded, the module will
lockout the compressor and ash red three times.
Code 4 – Locked Rotor Trip
The module will ash yellow four times when the
compressor trips within 12 seconds of operation and
does not reset and start within 35 seconds. When ten
consecutive Code 4 events are recorded the module
will lockout the compressor and ash red four times.
Code 5 – Compressor (Moderate Run) Trip
The module will ash yellow ve times when the
compressor has operated between 15 minutes and
18 hours, followed by a compressor trip lasting longer
than 7 minutes. When four consecutive or ten total
Code 5 events are recorded, the module will lockout
the compressor and ash red ve times.
Code 6 – Open Start Circuit
The module will lockout the compressor and ash
red six times if the module detects a demand signal
in the “Y” terminal and current in the “R” winding of
the compressor, but no current is detected in the “S”
winding of the compressor for 2 seconds.
Code 7 – Open Run Circuit
The module will lockout the compressor and ash red
seven times if the module detects a demand signal
in the “Y” terminal and current in the “S” winding of
the compressor, but no current is detected in the “R”
winding of the compressor for 2 seconds.
Code 8 – Welded Contactor
The module will ash yellow eight times if it has
detected line currents in the “S” and “R” windings and
demand is absent for 15 seconds.
Code 9 – Low Voltage
The module will ash nine times if the module supply
voltage drops below 17VAC for 2 seconds. The
module will prevent the compressor from starting until
adequate voltage is established.
Code 10 – Over-Current Protection
When the current at the PROT terminal is greater than
2A for 40ms, the module will ash a Code 10. The red
LED will ash 10 times with the yellow LED remaining
6
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
off. This event will cause a lockout of the compressor
and indicates that the module is mis-wired or the
contactor coil is shorted to ground.
NOTICE
Code 10 is not speci ed on the module label.
Resetting Alert Codes
When the CoreSense Diagnostics module has detected
a series of adverse conditions that have caused it to
lockout the compressor, and after the issue has been
resolved, it is necessary to manually reset the module
in order to clear the present alert code.
The primary way of clearing the code and resetting
the ALERT or TRIP/LOCK is to cycle the power to the
module by disengaging the COMMON (C) Terminal.
This will not clear the seven day operating history
contained in the module memory. It will only clear the
present ALERT or TRIP/LOCK and allow for normal
operation.
SERVICE
WARNING
Always disconnect and lockout the power supply
before beginning electrical troubleshooting.
Module History Download
The CoreSense Diagnostics module is capable of
communicating with a personal computer, tablet, or
laptop, via Emerson Climate Technologies computer
Figure 1
Wires Pulled Through Module
software interface and USB connection, in order to
download and store fault history and module operation
time. This information can be used to help diagnose
and review data from troubled systems in the eld. For
more information, please contact your Emerson Climate
Application Engineer.
Warranty Information
Emerson Climate Technologies, Inc. warrants its
diagnostic module to be free from defects in materials
and workmanship under normal use for a period of one
year from the date of purchase or twenty months from
manufacture, whichever comes rst. During this period,
Emerson Climate Technologies, Inc. will replace any
defective diagnostic module without charge.
For more information on product warranty please visit
www.EmersonClimate.com
Support
For more information visit www.EmersonClimate.com,
or contact Emerson Climate Technologies, Inc. at 1-888-
EMR-9950.
7
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
ALERT
TRIP / LOCK
POWER
1 Long Run Time
2 Compressor (Pressure) Trip
3 Pressure Switch Cycling
4 Locked Rotor
5 Compressor (Mod Run) Trip
6 Open Start Circuit
7 Open Run Circuit
8 Welded Contactor
9 Low Voltage
DC SOL operating range: 18-28VDC
Compressor second stage is
energized when Y & Y2 are 24VAC
PROT breaks 24VAC common
leg of compressor contactor coil
Reset codes and PROT lockout
by removing 24VAC to module
Flash Event
Two Stage Control
Active Protection
C
S
R
47
37
62 112
67
Figure 2 – Module Dimensions in Millimeters
Y2
Y
Data Port
L
R
C
PROT
Solenoid
For Use With
Copeland Scroll
UltraTech
Compressors
P/N: 543-XXXX-XX
065312345
Patent: 6,615,594
Use With Class 2
Circuits Only
Supply 24VAC
50/60Hz
Power 1.5VA
Figure 3 – Terminal Locations
8
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
2-Stage
Thermostat
Indoor
Unit
Outdoor
Unit
C
R
Y1
Y2
C
R
L
Y
Y2
L
DC
Solenoid Solenoid
CoreSense
High/Low
Pressure Switch
CC
Compressor
Contactor
C
R
Y1
Y2
L
C
R
Y1
Y2
L
Prot
Figure 4
Wiring Diagram
9
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Alert Code Alert Condition Lockout Level Lockout
Indication
Normal Run
Solid Green Normal operation, no trip. N/A N/A
Code1
Yellow Flash 1
Long run time. Compressor is running for more than
18 hours at full load. (Code1 is disabled in Heat Pump
mode.)
N/A N/A
Code2
Yellow Flash 2
Compressor Pressure trip. Compressor runs for 12sec
to 15min followed by a compressor trip condition lasting
longer than 7min.
4x consecutive,
10x total Red: Flash 2
Code 3
Yellow Flash 3
Pressure switch cycling. Compressor runs for 12sec to
15min followed by a compressor trip lasting between
35sec to 7min.
4x consecutive,
10 total Red: Flash 3
Code4
Yellow Flash 4
Locked rotor. Compressor trips within a compressor run
time of 12sec and does not start within 35sec. 10x consecutive Red: Flash 4
Code5
Yellow Flash 5
Compressor moderate run trip. Compressor runs for
15min to 18hrs followed by a compressor trip lasting
longer than 7min.
4x consecutive,
10x total Red: Flash 5
Code6
Red Flash 6
Open start circuit. Module has detected Y or Y1, and
current in the R winding of the compressor and no
current in the S winding of the compressor for 2 seconds.
1 occurrence Red: Flash 6
Code7
Red Flash 7
Open run circuit. Module has detected Y or Y1, and
current in the S winding of the compressor and no current
in the R winding of the compressor for 2 seconds.
1 occurrence Red: Flash 7
Code8
Yellow Flash 8
Welded Contactor. Module has detected line currents
in R and S windings, and Y or Y1 is at 0 VAC for 15
seconds.
N/A N/A
Code9
Yellow Flash 9
Low Voltage. Module has detected a 24 VAC supply
voltage below 17 VAC +/- 1 VAC for 2 seconds
N/A N/A
Code10
Red Flash 10
Over Current Protection. PROT terminal has above a 2A
input for more than 40 milliseconds. 1 occurrence Red: Flash 10
Table 1 – Flash Code Description
10
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Status Description Troubleshooting Information
Solid Green “RUN” Module has power and
operating normally Supply voltage is present at module terminals
Solid Red “TRIP”
Thermostat demand signal Y is
present, but the compressor is
not running
1. Compressor protector is open
Check for high head pressure
Check compressor supply voltage
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken wire or connector is not making contact
5. High pressure switch open if present in system
6. Compressor contactor has failed open
“ALERT” Flash Codes
Yellow “ALERT”
Flash Code 1
Long Run Time
Low Refrigerant Charge
Compressor is running extremely
long run cycles
1. Low refrigerant charge
2. Evaporator blower is not running
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit
3. Evaporator coil is frozen
Check for low suction pressure
Check for excessively low thermostat setting
Check evaporator air ow (coil blockages or return air lter)
Check ductwork or registers for blockage
4. Faulty metering device
Check TXV bulb installation (size, location and contact)
• Check if TXV/ xed ori ce is stuck closed or defective
5. Liquid line restriction ( lter drier blocked if present in system)
6. Thermostat is malfunctioning
Check thermostat sub-base or wiring for short circuit
Check thermostat installation (location, level)
Yellow “ALERT”
Flash Code 2
Compressor (Pressure) Trip
High Refrigerant Charge
Discharge pressure out of limits
or compressor overloaded
1. Condenser fan is not running
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
2. High head pressure
Check high pressure switch if present in system
Check if system is overcharged with refrigerant
Check for non-condensable in system
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Return air duct has substantial leakage
Yellow “ALERT”
Flash Code 3
Pressure Switch Cycling
Compressor is running only
brie y due to pressure switch
cycling
1. Time delay relay or control board defective
2. If high pressure switch present go to Flash Code 2 information
Table 2 – CoreSense Diagnostics LED Troubleshooting Information
Flash Code number corresponds to the number of LED ashes, followed by a pause and then repeated.
TRIP and ALERT LEDs ashing at same time means control circuit voltage is too low for operation (brown-out conditions).
11
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Yellow “ALERT”
Flash Code 4 Locked Rotor
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Measure compressor oil level
Yellow “ALERT”
Flash Code 5
Compressor (Moderate Run)
Trip
1. Evaporator blower is not running
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit
2. Faulty metering device
Check TXV bulb installation (size, location and contact)
• Check if TXV/ xed ori ce is stuck closed or defective
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Low refrigerant charge
Yellow “ALERT”
Flash Code 8
Welded Contactor
Compressor always runs
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Supply Voltage
Voltage below 18V
1. Control Circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)
“LOCKOUT” Flash Codes
Red “LOCKOUT”
Flash Code 2
Yellow Off
Compressor (Pressure) Trip
Compressor is locked out
after 4 consecutive or 10 total
compressor (pressure) trip events
1. Condenser fan is not running
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
2. High head pressure
Check high pressure switch if present in system
Check if system is overcharged with refrigerant
Check for non-condensable in system
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Return air duct has substantial leakage
Red “LOCKOUT”
Flash Code 3
Yellow Off
Pressure Switch Cycling
Compressor is locked out after 4
consecutive or 10 total pressure
cycling events
1. Time delay relay or control board defective
2. If high pressure switch present go to Flash Code 2 information
Red “LOCKOUT”
Flash Code 4
Yellow Off
Locked Rotor
Compressor is locked out after 10
consecutive locked rotor events
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low
Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Measure compressor oil level
Table 2 Continued
12
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Red “LOCKOUT”
Flash Code 5
Yellow Off
Compressor (Moderate Run)
Trip
Compressor is locked out
after 4 consecutive or 10 total
compressor (moderate run) trip
events
1. Evaporator blower is not running
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit
2. Faulty metering device
Check TXV bulb installation (size, location and contact)
• Check if TXV/ xed ori ce is stuck closed or defective
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Low refrigerant charge
Red “LOCKOUT”
Flash Code 6
Yellow Off
Open Start Circuit
Current only in run circuit
1. Run capacitor has failed
2. Open circuit in compressor start wiring or connections
Check wiring and connectors between supply and the
compressor “S” terminal
3. Compressor start winding is damaged
Check compressor motor winding resistance
Red “LOCKOUT”
Flash Code 7
Yellow Off
Open Run Circuit
Current only in start circuit
1. Open circuit in compressor run wiring or connections
Check wiring and connectors between supply and the
compressor “R” terminal. Con rm proper wire routing per
Figure 1.
2. Compressor run winding is damaged
Check compressor motor winding resistance
Red “LOCKOUT”
Flash Code 10
Over Current Protection
Current to PROT is greater than
2A mps
1. Check for contactor shorted to ground
2. Check for mis-wiring to the PROT terminal
Table 2 Continued
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability. Emerson Climate Technologies, Inc. reserves the right to modify the designs or speci cations of such products at any time without
notice. Emerson Climate Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of
any Emerson Climate Technologies, Inc. product remains solely with the purchaser and end-user.
Page 1 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 2 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 3 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 4 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 5 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 6 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 7 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 8 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 9 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 10 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 11 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual
Page 12 of 12 - Emerson Emerson-Ae8-1385-Users-Manual- AE-1385, CoreSense™ Diagnostics For Copeland Scroll® UltraTech® Air Conditioning Compressors  Emerson-ae8-1385-users-manual

Navigation menu