DC Distribution Panel for NetSure Systems
Product Overview
The DC Distribution Panel for NetSure
systems is designed to provide overcur-
rent protection or separation of a single
source into multiple feeds on the output
of a DC source. This panel can be popu-
lated with up to 20 breakers and can be
wall-mounted or mounted in a 23" relay
rack. The breaker panel accepts bullet-nose style breakers from 1A to 250A. The breakers
plug into one of (20) mounting positions. Each position has a localized return landing.
Application
The DC Distribution Panel is ideal for installations where overcurrent protection or sepa-
ration of load circuits is required on the output of a rectifier or converter. This panel is
compatible with NetSure DC power systems from Emerson or as standalone.
Additional Information
Reference spec. number 545277 for additional specification, engineering or installation
information.
LOAD RETURN
CONNECTIONS
LOAD
CONNECTIONS
5/8"
5/8"
LOAD CIRCUIT BREAKERS/FUSES
F1/
CB1
F20/
CB20
1/4-20 THREADED HOLE, 80 PLACES
1"
INPUT
3/8-16 THREADED
HOLES, 12 PLACES
INPUT
RETURN
1"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
Key Features
n Flexible mounting options —
allow for relay rack or wall
mounting
n Compact panel with front
access and top feed — fits in
23" relay rack with 6U height
n Field wiring provisions, 2 hole
lug terminations — to meet
code requirements
n Bullet-nose style breakers —
provide easy installation and
removal
n Isolated Form-C alarm output
n Return bar
2
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2014.
Business-Critical Continuity, Emerson Network Power, the Emerson Network Power logo, Emerson and Consider it Solved are service marks and trade-
marks of Emerson Electric Co. EnergyMaster, eSure, NetPerform, NetReach, NetSpan, NetSure and NetXtend are trademarks of Emerson Network
Power, Energy Systems, North America, Inc. Any other product, brand, or company names or logos are the property of the respective owner.
While every precaution has been taken to ensure accuracy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. Specifications subject to
change without notice.
087D-DistPanel / 0114
DC Distribution Panel for NetSure Systems
Technical Specifications
Input / Output
DC Voltage +24VDC, -24VDC, +48VDC, -48VDC
Input Current 600A*
Environmental
Operating Temp. -40°C to 40°C
Safety Compliance UL/cUL
General
Dimensions (H x W x D) 10.375" x 23.0" x 6.5" (263mm x 584mm x 165mm)
Approx. Weight (without breakers) 34 lbs. (15.5 Kg)
Input Connections (3) 3/8"D x 1" on center per polarity, right side of panel
Output Connections (20) 1/4"D x 5/8" on center, top access
* Not to exceed 80% of each circuit breaker rating. Steady state.
Bullet-Nose Type Circuit Breakers
Ampere Electrical/Mechanical Trip Electrical Trip Ampere Electrical/Mechanical Trip Electrical Trip
Rating (Black Handle) * (White Handle) ** Rating (Black Handle) * (White Handle) **
1 101596 102272 50 101606 102282
3 101597 102273 60 101607 102283
5 101598 102274 70 101608 102284
10 101599 102275 75 101609 102285
15 101600 102276 80 121995 121996
20 101601 102277 90 147555 147554
25 101602 102278 100 101610 102286
30 101603 102279 125 516838 516991
35 101604 102280 150 516839 516993
40 101605 102281 200 *** 121832 121831
45 121997 121998 250 *** 121836 121835
NOTE: Load should not exceed 80% of device rating; 125, 150 & 200 amp devices occupy two positions; 250 amp device occupies three positions.
* Provides an alarm during an electrical or manual trip condition.
** Provides an alarm during an electrical trip condition only.
*** Ratings greater than 150 amps REQUIRE an empty mounting position between the breaker and any other overcurrent protective device.