Emerson Liebert Intellislot Relay Card Users Manual

2015-03-30

: Emerson Emerson-Liebert-Intellislot-Relay-Card-Users-Manual-680275 emerson-liebert-intellislot-relay-card-users-manual-680275 emerson pdf

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadEmerson Emerson-Liebert-Intellislot-Relay-Card-Users-Manual-  Emerson-liebert-intellislot-relay-card-users-manual
Open PDF In BrowserView PDF
MONITORING

INTELLISLOT™

USER MANUAL

Interface Card for
Relay Contacts

CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . 2
3.0 PIN CONFIGURATION . . . . . . . . . . . . . . . . . . . . 4
4.0 JUMPER SETUP . . . . . . . . . . . . . . . . . . . . . . . 5
5.0 CONTACTING TECHNICAL SUPPORT . . . . . . . . . 6

TABLES
Table 1

Relay contact card pin configuration. . . . . 4

Table 2

Jumper connections . . . . . . . . . . . . . . . . . . 5

i

ii

Introduction

1.0 INTRODUCTION
The Liebert Intellislot™ Interface for Relay Contacts card
provides contact closures for remote monitoring of alarm
conditions in your Liebert UPS. Delivering On Battery, On
Bypass, Low Battery, Summary Alarm, UPS Fault and On
UPS signals, the easy-to-install card integrates with other
relay contact monitoring systems.
This advanced power-management device is specially
designed to function only in the Liebert Intellislot port of the
following supported UPS units:
• Nfinity™
• Liebert NX™
• PowerSure PSI™

• UPStation GXT™
• UPStation GXT2™

In addition, the RS-232 port on the UPS remains active with
the card installed, allowing more sophisticated monitoring
with Liebert MultiLink™ software.
On supported units, the inverter shut-off command can be
controlled from the computer directly connected to the UPS
(via the factory-installed DB9 connector) and will conserve
battery power after the workstation shutdown is completed.
The Intellislot Interface for Relay Contacts card is rated for
24 VAC/DC at 1A.

Inspecting Shipment on Receipt
Upon accepting shipment, please inspect the product for any
damaged or missing parts. If damage is observed, call
Liebert at 1-800-222-5877 and select the Warranty Support
option from the menu. If components are missing, contact
your sales representative for replacement.
Items included with the shipment are:
• Intellislot Interface for Relay Contacts card protected by
an anti-static bag
• Hardwire Adapter board
• User manual
1

Installation

2.0 INSTALLATION
Parts and Tools Required
• Intellislot Interface for Relay Contacts card and required
cable assembly
• #2 (medium) Phillips or small flat-head screwdriver

Instructions

INTELLISLOT

1. Turning off the UPS prior to installation PORT ON A UPS
is suggested, although not required.
2. Locate the Intellislot port on the UPS.
The Intellislot port is on the rear of some
units (GXT, Nfinity and PowerSure PSI);
on the Liebert NX, the port is inside the
front door. Refer to your UPS user manual for port location and orientation.
3. Remove the two retaining screws from
Remove
the Intellislot port cover plate on the
screws
UPS.
NOTE: Save the screws for re-assembly (described in
Step 5).
4. The card and slot are keyed to insert in one position only.
Initially, the card should slide in freely as you carefully
align screw holes. As you feel it click into place, press
firmly to ensure solid seating in the slot.
CARD AND SLOT ORIENTATION

Incorrect

Correct

5. Using the screwdriver, secure the card to the UPS chassis
with the two retaining screws. Make sure the screws are
snug, not tight, to avoid damage to the device.
2

Installation

6. Select either interface Option 1 or 2 below (also see
Step 7 and 3.0 - Pin Configuration).
Option 1: Hardwire (terminal block pins) - Use these
guidelines for terminal block specifications:
Acceptable
Wire Size

Wire Strip
Length

Recommended
Tightening Torque

30-16 AWG

0.24-0.28 in.
(6-7mm)

1.73 lb-in
(2 kgf-cm)

Option 2: DB25 pins

Screw
M2

Remove

a. Disconnect the Hardwire
screws
Adapter board by removing
the two mounting screws,
as shown at right.
Hardwire
b. Pull the Hardwire Adapter Adapter
board away from the Relay board
Card.

7. Configure the terminal block or DB25 pins, depending on
which interface option you chose in Step 6 (see figure
below and Table 1 in 3.0 - Pin Configuration).
TERMINAL BLOCK PINS
(Option 1)

DB25 PINS
(Option 2)

Hardwire Adapter
board

Intellislot
card

Pin
numbering

14

Pin
numbering

25

13

14

1

1

11
24

See Table 1 for configuration of terminal block & DB25 pins.
3

Pin Configuration

3.0 PIN CONFIGURATION
Table 1

Relay contact card pin configuration

Terminal
Block
DB25
Pin
Pin

Function

Operation

1
—
—
4

1
2
3
4

UPS Fault
Not Used
Not Used
UPS Fault

Closed if no UPS failure*

5

5

Summary Alarm**

6

6

Summary Alarm**

7

7

—
9
10

8
9
10

Signal Ground (for UPS
Any Mode Shutdown)
Not Used
Common - Low Battery
Low Battery

11

11

Low Battery

—
—

12
13

Not Used
Not Used
UPS Any Mode
Shutdown (short to pin 7)
On UPS

14

14

15

15

16

16

On Battery

17

17

Common - UPS Fault,
Summary Alarm, On UPS,
On Battery, On Bypass

18

18

On Battery

Closed if UPS fails*
Closed if SUMMARY ALARM**
occurs*
Closed if no alarm conditions
are present*

Closed if battery is OK
Closed if LOW BATTERY
point occurs.

Turn UPS output OFF
when connected to pin 7*
Closed if ON UPS (inverter) power*
Closed if ON BATTERY power
(Utility failure)

Closed if not ON Battery power
(Utility OK)

—
19
Not Used
—
20
Not Used
—
21
Not Used
—
22
Not Used
—
23
Not Used
24
24
On Bypass
Closed if ON BYPASS*
—
25
Not Used
* Feature not available on PSI products
** A Summary Alarm occurs when any of the following conditions exists:
• Utility power is out of the acceptable range (voltage and/or frequency).
• UPS is in BYPASS MODE (load not on Inverter power).
• UPS battery is LOW (<2 minutes of battery power remaining).
• UPS fault has occurred.

4

Jumper Setup

4.0 JUMPER SETUP
Refer to Table 2 and the figure below for jumper setup.
Table 2

Jumper connections

#

Connection

JP01

Pin 9
to
Pin 17

Allows all relay COMMONS to be tied
together.

Pin 7
to
Pin 17

Allows all relay COMMONS and the ANY
MODE SHUTDOWN GROUND to be tied
together.
NOTE: This jumper should be removed if
there is any external voltage source that
may intentionally or inadvertently be
connected to the DB25 pins.

JP02

Description

Jumper
JP01

Jumper
JP02

5

Contacting Technical Support

5.0 CONTACTING TECHNICAL SUPPORT
Liebert has a team of specially trained technicians waiting to
quickly assist you with any installation or troubleshooting
problems.
Refer to the back of this manual for the Technical Support
phone number.
To successfully diagnose your individual problem, our
technicians may require the following installation site and
system information. Please have it available when you call.
INSTALLATION SITE
Company Name:
Street Address:
City:
State / Principality:
ZIP / Postal Code:
Country:
INSTALLATION SITE CONTACT
Name of Contact:
Phone Number:
Fax Number:
E-Mail Address:
Fax Number:
6

MONITORING

INTELLISLOT™
The Company Behind the Products
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:
• Environmental systems—close-control air
conditioning from 1 to 60 tons
• Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
• Integrated systems that provide both
environmental and power protection in a
single, flexible package
• Monitoring and control—from systems of any
size or location, on-site or remote
• Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center
While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility
and disclaims all liability for damages resulting
from use of this information or for any errors or
omissions.
© 2005 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
SL-23210 (2/05) Rev. 1

USER MANUAL
Technical Support/Service
Web Site
www.liebert.com

Monitoring

800-222-5877
monitoring@liebert.com
Outside the US: 614-841-6755

Single-Phase UPS

800-222-5877
upstech@liebert.com
Outside the US: 614-841-6755

Three-Phase UPS

800-543-2378
powertech@liebert.com

Environmental Systems

800-543-2778

Outside the United States
614-888-0246

Locations
United States

1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229

Italy

Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257

Asia

23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Count                      : 12
Page Mode                       : UseOutlines
Has XFA                         : No
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:a75b149d-1291-4194-8d40-c03364faac80
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Create Date                     : 2005:02:04 15:14:31Z
Modify Date                     : 2005:02:11 15:14:15-05:00
Metadata Date                   : 2005:02:11 15:14:15-05:00
Creator Tool                    : FrameMaker 7.0
Document ID                     : uuid:9ecc2809-1929-4be0-ad39-efe5de96ecbe
Format                          : application/pdf
Creator                         : FrameMaker 7.0
EXIF Metadata provided by EXIF.tools

Navigation menu