12013.10
eSure Converter
C48/24 -1500
Key Features
1500 Watt high-efficiency
converter designed to operate
from a nominal 48V DC source
to provide 24 VDC load power
Optimized depth –
reduced footprint allows
installation in short-depth
racks and cabinets
DSP (Digital Signaling
Processor) – means fewer
components, optimized
operation and active load
sharing for increased reliability
Compliant with global
standards – delivers quality,
performance and reliability no
matter what the application or
location demands
High efficiency, approaching
96% – reduces power
consumption for lower
operating costs
Hot pluggable facilitates
future extensions
Wide input voltage range to
operate in the most
demanding environments
where input voltage changes
Wide temperature operating
range (-40°C / -40°F to +80°C /
176°F) to meet the harshest
climatic environment
requirements
In addition to reducing power consumption and
lowering operating cost, eSure high-efficiency
converters offer superior performance and
uncompromised reliability.
Description
The eSure™ C48/24-1500 high-efficiency converter is designed to operate from a
nominal 48 Vdc source to provide nominal 24Vdc load power, which is adjustable
to application needs. The C48/24-1500 is a constant power converter designed
with the latest patented switchmode technology, using DSP (Digital Signaling Processor)
functionality for efficient operation.
For a higher load capacity, converters can be connected in parallel, and intelligent
control can be added with the help of a separate controller.
Efficiency
Load
0 10 20 30 40 50 60 70 80 90 100
96
94
92
90
2013.102
eSure™ Converter C48/24-1500
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2013.
Business-Critical Continuity, Emerson Network Power, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson Electric Co.
EnergyMaster, eSure, NetPerform, NetReach, NetSpan, NetSure® and NetXtend are trademarks of Emerson Network Power Energy Systems North America.
Technical Specifications
DC Input
Input Voltage, Nominal 48 VDC
Input Voltage, Permitted Variation 41VDC to 58.5VDC
Max Input Current 39.5A
DC Output
Output Voltage, Adjustment Range 24 t o 2 8 VDC
Output Power 1500W@Vout >24VDC
Output Power,
Derated for Input VoltageSee diagram
Output Current 63A
Output Current Limit Set Point 6.3 to 63A
>95%ycneiciff E
Psophometric Noise (system) <2 mV; output noise<38dBrnc
Temperature DeratingSee diagram
Control and Monitoring
Visual Indications
Green LED: Normal Operation
Yellow LED: Alarm
Red LED: Failure
Flashing Red LED: Fan Failure
Environmental
Temperature Range, Operating -40 to +80°C, -40 to +176°F
Temperature Range, Storage -40 to +85°C, -40 to +185°F
Relative Humidity 0 to 95%
rewop lluf ta tf 0656 ,m 0002edutitlA
EMCETSI EN 300 386 class A, FCC CFR 47 Part 15 class A,
Telcordia GR-1089-CORE class A
05906 LU ,05906 NE ,05906 CEIytefaS
Mechanics
Dimensions (H x W x D)
sbl94.2/gk31.1thgie W
42x 8 4.5x252.5mm/1.65x3.33x9.94 inches
Other Parts
Controller Units See separate ACU/ACU+ and SCU/SCU+ datasheets
Ordering Information
Model Number Description
1C48241500 Converter 48VDC/24VDC 1500W
Diagrams
120
100
80
60
40
20
0-40 -20 0 20 40 60 80 100
Temperature (C°)
% of max output power
Output Power vs. Temperature
35
30
25
20
15
10
5
0
0 10 15 20 25 30 35 40 45 50 55 60 65 70 75
Output Current (A)
Output Voltage (V)
Output voltage vs. Output current
at max. output power 1500 W
Converter Alarm and Signaling Alarm and status reported via CAN bus to system controller