Bulletin 71.2:LR125
November 2014

Type LR125 Pressure Reducing Liquid Regulator
• Rugged design
• Reliable
• Thoroughly tested
• Internally actuated
• Compact
• 1, 2, 3, 4 in. body sizes
• Recommended for water
and oil applications
• Full SST construction
available for harsh
environments
• API 614 Compliant
Figure 1. Type LR125 Pressure Reducing Liquid Regulator

Features and Benefits

The Type LR125 pilot-operated, pressure reducing
regulator is designed for liquid industrial/commercial
applications. The Type LR125 provides smooth
operation, tight shutoff and long life. Its internally
actuated metal plug eliminates disadvantages
associated with flexible element style regulators, and
the specially engineered flow path deflects debris,
protecting the seat from damage and erosion. The
Type LR125 is used in conjunction with a Type MR95H
pilot and Type 112 restrictor. An internal inlet strainer
prevents large particles from entering the main valve,
limiting damage to internal parts.

1

Tight Shutoff—The Type LR125 uses a diaphragm
and metal plug, eliminating the disadvantages of
flexible element style regulators. When open, the
metal plug deflects particles and debris away from
the diaphragm. The result is enhanced resistance to
particle erosion, which provides excellent shutoff over
an extended life. When closed, loading pressure and
the main spring push the diaphragm onto the taperededged seat on the cage.

www.fisherregulators.com

D103575X012

Introduction

Bulletin 71.2:LR125
Specifications
The Specifications section lists the specifications for the Type LR125 regulator. Factory specification is stamped
on the nameplate fastened on the regulator at the factory.
Main Valve Body Sizes, End Connection Styles and
Structural Design Ratings(1)(2)
	
See Table 1
Maximum Inlet Pressures(1)
	
Type LR125 Main Valve: See Table 1
	
Type MR95H Pilot: See Table 2
	
Type 112 Restrictor: 1500 psig / 103 bar
Maximum Outlet Pressure
	
Type LR125 Main Valve: See Table 1
	
Type MR95H Pilot: See Table 2
Outlet (Control) Pressure Ranges
	
See Table 3
Main Valve Plug Travel
	
1 in. / DN 25: 0.37 in. / 9.4 mm
	
2 in. / DN 50: 0.68 in. / 17 mm
	
3 in. / DN 80: 0.98 in. / 25 mm
	
4 in. / DN 100: 1.19 in. / 30 mm
Main Valve Minimum Differential Pressures(1)
	
See Table 5
Temperature Capabilities(1)
	
See Table 4
Main Valve Flow Direction
	
Up through the center of the cage and down
	
through the cage slots
Main Valve Internal Inlet Strainer Sizes
	
1 in. / DN 25: 12 Mesh (0.0661 in. / 1.68 mm)(3)
	
2, 3 and 4 in. / DN 50, 80 and 100:
	
10 Mesh (0.0787 in. / 2 mm)(3)
Regulating Capacities
	
See Table 11
Flow and IEC Sizing Coefficients
	
Type LR125 Main Valve: See Table 6
	
Type MR95H Pilot: See Table 7
	
Type 112 Restrictor: See Table 8
Pressure Registration
	
External: 1/2 NPT
Spring Case Vent
	
Type Y602-12
Approximate Weights
	
See Table 9

Options
	
•  Pre-piped Pilot Supply
	
•  Travel Indicator
Construction Materials
	
Type LR125 Main Valve
	Body: WCC Steel, CF8M or CF3M Stainless Steel
	Bonnet: Steel or Stainless Steel
	
Bonnet Bushing: Steel or Stainless Steel
	Cage: Stainless steel
	Spring: Stainless steel
	
Top Plug: Stainless steel
	
Bottom Plug: Stainless steel
	
Internal Inlet Strainer: Stainless steel
	
Diaphragm: Nitrile (NBR) or Fluorocarbon (FKM)
	O-rings: Nitrile (NBR) or Fluorocarbon (FKM)
	
Flanged Locknut: Stainless Steel
	
Backup Rings: Polytetrafluoroethylene (PTFE)
	
Upper Spring Seat: Stainless steel
	
Indicator Protector and Cover: Plastic
	
Indicator Stem: Stainless steel
	
Indicator Fitting: Stainless steel
	
Travel Indicator Plug: Stainless steel
	
Type MR95H Pilot	
Body: WCC Steel or CF8M Stainless Steel
Spring Case: WCC Steel or CF8M Stainless Steel	
Orifice: Stainless Steel
	
Diaphragm: Neoprene (CR) or Fluorocarbon (FKM)
	Disk: Nitrile (NBR) or Fluorocarbon (FKM)
	
Mounting Parts
	
Pilot Mounting Pipe Nipple: Plated steel or
	  Stainless steel
	
Pipe Fittings: Plated steel or Stainless steel
	Tubing: Stainless Steel
	
Type 112 Restrictor
	Body: 15-5 Stainless Steel
	
Groove Valve: Stainless steel
	Retainer: Stainless steel
	
Pipe Plug: Stainless steel
	O-rings: Nitrile (NBR) or Fluorocarbon (FKM)

1. The pressure/temperature limits in this Bulletin and any applicable standard or code limitation should not be exceeded.
2. Ratings and end connections other than ASME standards can usually be provided; contact your local Sales Office.
3. Nominal sieve opening

2

3

Debris Protection—The specially engineered flow
path, along with the metal plug, allows flow through the
regulator without seat impingement. The addition of an
internal inlet strainer prevents large particles from entering
the regulator, minimizing damage to internal p  arts.
High Accuracy—Multiple control pressure ranges
offered by Type MR95H pilot and lower accuracy class
2

inherent to pilot operated pressure regulator design
provide the Type LR125 with tight and accurate control.
4

Long Life—The robust design of the Type LR125 with
its metal plug and specially engineered flow path allows
flow through the regulator without seat impingement.
The diaphragm design eliminates the possibility of
taking a “set”, a common problem with flexible element

Bulletin 71.2:LR125

3

7

7

W5092

W7398

TYPE MR95H PILOT

8

TRIM PACKAGE

4

11

9

TYPE MR95H PILOT

10
1

5

6

12
2

W7345

W7344

TYPE LR125 PRESSURE REDUCING REGULATOR

Figure 2. Type LR125 Features and Benefits

style regulators. To prevent damage, the diaphragm is
fully supported in both the open and closed positions.
These features enable the Type LR125 components to
work longer with less wear and tear.
5

Full Usable Capacity—Fisher® branded regulators
are laboratory tested. One hundred percent of the
published flow capacity can be used with confidence.

6

Thorough Laboratory Testing—Emerson Process
Management Regulator Technologies, Inc. (Emerson™)
state-of-the-art flow laboratory allows thorough testing of
all new designs. Tests are conducted on Fisher branded
regulators for performance features such as flow,
strength, shutoff and material compatibility.

7

Easy In-Line Maintenance—Top-entry design
reduces maintenance time. Trim parts can be
inspected, cleaned and replaced without removing
the body from the pipeline. No special alignment is
required when replacing the diaphragm.

8

O-ring Design—The Type LR125 uses elastomer
O-rings instead of gaskets, reducing maintenance and
assembly time.

9

In-Service Travel Indicator—The optional travel
indicator responds to the precise movement of the
diaphragm and plug assembly and shows the actual
valve position. The travel indicator makes in-service
inspection and troubleshooting easy. Also, it can be used
for remote alarming and monitoring stem position.

10

Versatility—The Type LR125 uses the E-body, making
available the standard construction materials and end
connections (ASME and EN) used by other E-body
regulators and control valves. Type MR95H can handle
inlet pressures up to 300 psig / 20.7 bar and outlet
pressures from 15 to 150 psig / 1.0 to 10.3 bar.

11

Easy-to-Maintain—The pilot is designed to allow quick
and simple in-line trim inspection and parts replacement.

3

Bulletin 71.2:LR125
TYPE MR95H PILOT

TYPE 112 RESTRICTOR

CONTROL SPRING

DIAPHRAGM

SUPPLY LINE

VALVE PLUG

MAIN SPRING
DIAPHRAGM AND
PLUG ASSEMBLY

M1215

INLET PRESSURE

INTERNAL STRAINER

OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE

TYPE LR125 WITH TYPE MR95H PILOT AND TYPE 112 RESTRICTOR

Figure 3. Type LR125 Operational Schematic
12

Powder Paint Coating—Carbon steel body is powder
paint coated providing superior impact, abrasion and
corrosion resistance.

Pilot Type Description
Type MR95H—High-pressure pressure reducing pilot
for 15 to 150 psig / 1.0 to 10.3 bar outlet pressures.
Designed to handle inlet pressures up to 300 psig /
20.7  bar.

Principle of Operation
As long as the outlet (control) pressure is above the
outlet pressure setting, the pilot valve plug or disk
remains closed (Figure 3). Force from the main spring, in
addition to inlet pressure bleeding through the restrictor,
provide downward loading pressure to keep the main
valve diaphragm and plug assembly tightly shutoff.

4

When the outlet pressure decreases below the pilot
outlet pressure setting, the pilot plug or disk assembly
opens. Loading pressure bleeds downstream through
the pilot faster than it can be replaced through the
supply line. This reduces loading pressure on top of
the main valve diaphragm and plug assembly and
lets the unbalanced force between inlet and loading
pressure overcome the main spring force to open the
Type LR125 diaphragm and plug assembly.
As the outlet pressure rises toward the outlet pressure
setting, it compresses the pilot diaphragm against
the pilot control spring and lets the pilot valve plug
or disk close. Loading pressure begins to build up
on the Type LR125 diaphragm and plug assembly.
The loading pressure, along with force from the main
spring, pushes the diaphragm and plug assembly onto
the tapered-edge seat, producing tight shutoff.

Bulletin 71.2:LR125
Table 1. Type LR125 Main Valve Body Sizes, End Connection Styles, Structural Design Ratings and Maximum Operating
Inlet Pressures(1)
MAIN VALVE BODY SIZE
In.

MAIN VALVE
BODY MATERIAL

DN

psig

25, 50, 80 and 100

CF8M Stainless steel

MAXIMUM OPERATING
INLET PRESSURE(3)

bar

psig

bar

1500

103

300

20.7

290

20.0

290

20.0

CL300 RF

750

51.7
300

20.7

NPT or SWE
(1 and 2 in. only)
CL150 RF

WCC Steel

1, 2, 3 and 4

STRUCTURAL DESIGN
RATING(3)

END CONNECTION STYLE(2)

CL600 RF

1500

103

PN 16/25/40 RF(4)
NPT
(1 and 2 in. only)
CL150 RF

580

40.0

1440

99.2

300

20.7

275

19.0

275

19.0

CL300 RF

720

49.6

CL600 RF

1440

99.2

300

20.7

PN 16/25/40 RF(4)

580

40.0

1. The pressure/temperature limits in this Bulletin and any applicable standard or code limitation should not be exceeded.
2. Ratings and end connections for other than ASME standard can usually be provided. Contact your local Sales Office for assistance.
3. Maximum cold working pressure (CWP) per ASME B16.34 or product Bulletin limit, whichever is lowest. Temperature may decrease these maximum pressures.
4. Not available for 4 in. / DN 100 body size.

Table 2. Type MR95H Pilot Maximum Cold Working Pressure(1)(2)
BODY SIZE

BODY AND SPRING CASE MATERIAL
Steel
Stainless steel

1/2 NPT

MAXIMUM INLET PRESSURE
300 psig / 20.7 bar
300 psig / 20.7 bar

MAXIMUM OUTLET PRESSURE
300 psig / 20.7 bar
300 psig / 20.7 bar

1. The pressure/temperature limits in this Bulletin, and any applicable standard or code limitation should not be exceeded.
2. Temperature and/or the body end connection may decrease these maximum pressures.

Table 3. Outlet (Control) Pressure Ranges
PILOT
Type MR95H

OUTLET PRESSURE RANGE

SPRING WIRE DIAMETER

SPRING FREE LENGTH

psig

bar

In.

mm

In.

mm

SPRING PART NUMBER
AND COLOR

15 to 30
25 to 75
70 to 150

1.0 to 2.1
1.7 to 5.2
4.8 to 10.3

0.207
0.234
0.283

5.26
5.94
7.19

2.50
2.60
2.44

63.5
65.9
62.0

ERCA04288A0 Yellow
ERAA01910A0 Green
ERAA01911A0 Red

Table 4. Diaphragm Material Selection Information

Liquid Temperature
General Applications

17E68 NITRILE (NBR)

17E97 NITRILE (NBR)

17E88 FLUOROCARBON (FKM)

-20 to 150°F / -29 to 66°C

0 to 150°F / -18 to 66°C

0 to 250°F / -18 to 121°C(1)

Best for low pressure
differential and cold temperature
service applications.

Best for abrasive or
erosive service applications.

Best for high temperature
applications.

Fair

Excellent

Good

Heavy Particle Erosion
1. Fluorocarbon (FKM) is limited to 200°F / 93°C in hot water.

Installation

Overpressure Protection

The robust design of the Type LR125 allows this regulator
to be installed indoors or outdoors. This regulator
is designed to withstand the elements. The powder
paint coating protects regulator against minor impacts,
abrasions and c  orrosion. When installed outdoors,
the Type LR125 does not require protective housing.
However, the Type MR95H pilot should be oriented so
that the pilot spring case vent is pointed down. Otherwise,
make sure the vent is protected so that rain, moisture,
insects or any debris will not accumulate inside or block
the vent assembly. When installed indoors, install remote
venting of the pilot spring case as required by applicable
codes and regulations.

Overpressuring any portion of a regulator or associated
equipment may cause personal injury, leakage
or property damage due to bursting of pressurecontaining parts. Provide appropriate pressure relieving
or pressure limiting devices to ensure that the limits in
the Specifications section are not exceeded. Common
methods of external overpressure protection include
relief valves, monitoring regulators, shutoff devices
and series regulation. Regulator operation within
ratings does not prevent the possibility of damage from
external sources or from debris in the pipeline. Install
additional strainer or filter upstream of the regulator for
applications with high levels of debris.
5

Bulletin 71.2:LR125
CAVITATION PREDICTION
150 /
10.3
135 /
9.3
120 /
8.3

OUTLET PRESSURE (P2)
psig / bar

105 /
7.2
90 /
6.2
75 /
5.2
60 /
4.1
45 /
3.1
30 /
2.1
15 /
1.0

0

30 /
2.1

60 /
4.1

90 /
6.2

120 /
8.3

150 /
10.3

180 /
12.4

210 /
14.5

240 /
16.5

270 /
18.6

300 /
20.7

INLET PRESSURE (P1)
psig / bar

CONTINUOUS SERVICE REGION
INTERMITTENT SERVICE REGION
FULL CAVITATION REGION

Figure 4. Cavitation Sizing for Water
Table 5. Main Valve Minimum Differential Pressures(1)
MAIN VALVE
BODY SIZE
In.

DN

1

25

2

50

3

80

4

100

MINIMUM DIFFERENTIAL, PERCENT OF CAPACITY

DIAPHRAGM

For 90% Capacity

For 100% Capacity

Diaphragm Code

Diaphragm Material

psid

bar d

psid

bar d

17E68 (standard)

Nitrile (NBR), Low Minimum Differential

30

2.1

30

2.1

17E97

Nitrile (NBR), High Erosion Resistance

35

2.5

35

2.5

17E88

Fluorocarbon (FKM), High Temperature Capability

30

2.1

30

2.1

17E68 (standard)

Nitrile (NBR), Low Minimum Differential

18

1.2

19

1.3

17E97

Nitrile (NBR), High Erosion Resistance

24

1.7

24

1.7

17E88

Fluorocarbon (FKM), High Temperature Capability

18

1.2

19

1.3

17E68 (standard)

Nitrile (NBR), Low Minimum Differential

21

1.5

28

1.9

17E97

Nitrile (NBR), High Erosion Resistance

23

1.6

23

1.6

17E88

Fluorocarbon (FKM), High Temperature Capability

21

1.5

28

1.9

17E68 (standard)

Nitrile (NBR), Low Minimum Differential

16

1.1

30

2.1

17E97

Nitrile (NBR), High Erosion Resistance

16

1.1

34

2.3

17E88

Fluorocarbon (FKM), High Temperature Capability

16

1.1

30

2.1

1. See Table 1 for structural design ratings and Table 2 for Type MR95H pilot rating.

Table 6. Flow and Sizing Coefficients for Type LR125 Main Valve at 100% Capacity
MAIN VALVE BODY SIZE

6

REGULATING COEFFICIENTS

WIDE-OPEN COEFFICIENTS

In.

DN

CV

C1

CV

C1

1

25

14.8

33.4

15.2

33.5

Km
0.88

IEC SIZING COEFFICIENTS
XT

FD

FL

0.706

0.06

0.94

2

50

50.8

37.2

52.4

37.2

0.92

0.875

0.09

0.96

3

80

91.4

38.8

94.1

38.8

0.94

0.952

0.09

0.97

4

100

147

38.7

151

38.7

0.85

0.947

0.09

0.92

Bulletin 71.2:LR125
Table 7. Flow and Sizing Coefficients for Type MR95H Pilot
BODY SIZE,
IN. / DN

WIDE-OPEN COEFFICIENT

1/2 / 15

2.9

IEC SIZING COEFFICIENTS

C1

Km

35.5

0.79

Cv

XT

FD

FL

0.797

0.70

0.89

Km = FL2

Table 8. Type 112 Restrictor Flow Coefficients
RESTRICTOR SETTING

Cv

Setting 2

0.03

Setting 4

0.07

Setting 6

0.14

Setting 8

0.17

C1

35

Table 9. Approximate Weights Including Type MR95H Pilot and Restrictor
MAIN VALVE BODY,
LBS / kg

BODY SIZE
In.

DN

NPT or SWE

CL150 RF

CL300 RF

CL600 RF

1

25

22 / 10

24 / 11

28 / 13

32 / 15

2

50

51 / 23

54 / 24

58 / 26

65 /29

3

80

103 / 47

107 / 49

110 / 50

123 / 56

4

100

139 / 63

145 / 66

159 / 72

192 / 87

Cavitation Sizing
Note
The cavitation sizing graph in Figure 4 
applies to water only. For cavitation
sizing for other liquids, contact your
local Sales Office.
Use Figure 4 to determine cavitation sizing of
Type L
  R125. The Cavitation Prediction Curve depicts
P1 and P2 combinations where cavitation is likely
to occur. The curve shape was determined through
analysis and lab confirmation on water. Determine the
desired inlet pressure and outlet pressure of the system
and find the intersection of those values on the graph.
No Cavitation Region—Cavitation is not expected
in this region. Damage to regulator components and
piping is highly unlikely as a result of cavitation.
Note
Emerson™

denies responsibility for
damage and voids the warranty if the
product is used within the Cavitation
Region (see Figure 4).

Cavitation Region—Cavitation may occur. Damage
to regulator components and piping is possible. The
risk of damage increases as P1 and P2 move down
and to the right on the table. Cavitation damage can
be avoided by dividing the total pressure drop into
stages so that the P1 and P2 combination falls into the
“No Cavitation Region” at every stage.

Capacity Information
Note
Flow capacities are laboratory verified;
therefore, regulators may be sized for
100% flow published capacities. It is not
necessary to reduce published capacities.
The capacity information on the following pages is based
on four % droop, 10%, 20%, 30% and 40%. Droop is
the negative control deviation or pressure offset below
the setpoint of the regulator.
Table 10 shows Cv values at different % droop and
selected inlet pressures and outlet pressure settings.
Table 11 shows the liquid regulating capacities of the
Type LR125 regulator at selected inlet pressures and outlet
pressure settings. Flows are in gallons per minute (GPM)
and liters per minute (L/min) of water.

7

Bulletin 71.2:LR125
Table 10. Cv(1) at % Droop (Pressure Offset Below Setpoint)(2)
SPRING
RANGE AND
COLOR

15 to 30 psig /
1.0 to 2.1 bar
Yellow

25 to 75 psig /
1.7 to 5.2 bar
Green

OUTLET
PRESSURE
psig bar
15

1.0

20

1.4

30

2.1

25

1.7

50

3.4

75

5.2

70

4.8

100

6.9

125

8.6

150

10.3

70 to 150 psig /
4.8 to 10.3 bar
Red

INLET
psig
45
50
60
65
50
60
70
75
60
75
90
100
55
75
80
90
80
100
125
150
110
125
150
175
200
100
125
150
175
190
200
130
150
175
200
250
275
155
175
200
250
275
300
180
200
225
250
275
300

bar
3.1
3.4
4.1
4.4
3.4
4.1
4.8
5.1
4.1
5.1
6.1
6.8
3.7
5.1
5.4
6.1
5.4
6.8
8.5
10.2
7.5
8.5
10.2
11.9
13.6
6.8
8.5
10.2
11.9
12.9
13.6
8.8
10.2
11.9
13.6
17.0
18.7
10.5
11.9
13.6
17.0
18.7
20.4
12.2
13.6
15.3
17.0
18.7
20.4

1 IN. / DN 25
10%
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.7
14.2
14.8
14.8
14.7
14.6
14.5
14.5
14.8
14.8
14.8
14.8
14.2
13.9
14.8
14.8
14.8
14.8
14.7
14.5
14.8
14.8
14.8
14.8
14.8
14.8

20%
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.5
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.2
13.7
14.8
14.8
14.8
14.8
14.6
14.3
14.8
14.8
14.8
14.8
14.8
14.8

30%
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.6
14.8
14.8
14.7
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.2
13.7
14.8
14.8
14.8
14.8
14.6
14.3
14.8
14.8
14.8
14.8
14.8
14.8

2 IN. / DN 50
40%
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.5
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.8
14.2
13.7
14.8
14.8
14.8
14.8
14.6
14.3
14.8
14.8
14.8
14.8
14.8
14.8

10%
39.7
39.2
38.3
37.8
50.8
48.5
46.1
44.9
50.8
50.8
50.8
47.6
50.8
50.8
50.8
50.8
49.0
49.1
49.2
49.3
50.8
50.8
49.8
45.3
40.7
50.5
46.1
41.6
44.6
46.4
47.7
50.8
50.1
48.4
46.7
43.2
41.5
50.8
50.8
45.9
43.6
42.5
41.4
45.4
45.0
44.5
44.0
43.5
43.1

20%
44.2
44.5
44.9
45.2
50.8
50.7
50.0
49.7
50.8
50.8
50.8
50.8
50.8
50.8
50.8
50.8
50.1
50.1
50.0
50.0
50.8
50.8
49.8
46.5
43.1
49.4
46.0
42.7
46.0
47.9
49.2
50.0
49.5
48.9
48.3
47.1
46.5
50.8
50.8
47.5
46.4
45.8
45.3
47.2
46.7
46.2
45.7
45.2
44.7

30%
48.3
48.4
48.5
48.6
50.8
50.7
50.5
50.3
50.8
50.8
50.8
50.6
50.8
50.8
50.8
50.8
49.9
50.0
50.1
50.2
50.8
50.8
49.5
46.4
43.3
49.3
46.6
43.8
46.0
47.3
48.2
49.6
49.2
48.7
48.2
47.3
46.8
50.8
50.8
48.3
46.9
46.3
45.6
49.0
48.3
47.5
46.6
45.8
44.9

3 IN. / DN 80
40%
50.8
50.6
50.0
49.8
50.8
50.4
49.9
49.7
50.8
50.7
50.2
49.8
50.8
50.6
50.5
50.3
49.7
49.8
50.1
50.3
50.8
50.8
49.9
47.1
44.2
49.9
47.5
45.0
46.7
47.7
48.4
49.7
49.3
48.8
48.4
47.4
46.9
50.8
50.6
48.4
47.0
46.3
45.6
49.0
48.3
47.5
46.6
45.7
44.9

10%
83.0
83.3
84.1
84.5
91.4
91.4
91.4
91.2
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
86.1
80.6
91.4
87.7
82.8
85.2
86.7
87.7
91.4
91.4
90.7
88.1
82.8
80.2
91.4
91.4
88.4
85.2
83.6
82.0
89.3
88.8
88.2
87.5
86.9
86.3

20%
89.2
89.6
90.4
90.8
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
87.9
83.4
91.4
88.6
84.0
87.0
88.8
90.0
91.4
91.4
91.4
90.3
86.2
84.1
91.4
91.4
90.5
87.7
86.3
85.0
91.3
90.7
90.0
89.3
88.5
87.8

30%
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
88.0
84.0
91.4
89.5
84.9
87.2
88.5
89.5
91.4
91.4
91.4
90.4
86.5
84.5
91.4
91.4
91.2
88.2
86.7
85.2
91.4
91.4
90.9
89.9
88.9
87.9

4 IN. / DN 100
40%
91.4
91.4
91.4
91.3
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
91.4
90.9
91.4
91.4
91.4
88.7
84.6
91.4
91.4
86.6
87.9
88.8
89.3
91.4
91.4
91.4
90.4
86.5
84.6
91.4
91.4
91.2
88.1
86.6
85.1
91.4
91.4
90.9
89.8
88.6
87.4

10%
133.4
134.0
135.2
135.9
147.0
147.0
147.0
146.7
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
138.5
129.6
147.0
141.1
133.1
137.1
139.4
141.0
147.0
147.0
145.9
141.6
133.2
129.0
147.0
147.0
142.2
137.0
134.4
131.8
143.5
142.8
141.8
140.8
139.8
138.8

1. Type LR125 on liquid service with 1/2 NPT Type MR95H Pilot, 100% Cage Capacity with internal inlet strainer and Type 112 Restrictor Setting of “4”.
2. Values published in this table are laboratory tested and are presented based on % droop (negative control deviation only) or pressure offset below setpoint.
Exceeds recommended maximum pressure drop ratio of 0.65.

8

20%
143.4
144.1
145.4
146.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
141.3
134.2
147.0
142.5
135.0
139.9
142.8
144.7
147.0
147.0
147.0
145.2
138.6
135.3
147.0
147.0
145.5
141.1
138.9
136.6
146.8
145.9
144.7
143.6
142.4
141.2

30%
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
141.6
135.1
147.0
144.0
136.5
140.2
142.4
143.9
147.0
147.0
147.0
145.4
139.1
135.9
147.0
147.0
146.6
141.9
139.5
137.1
147.0
147.0
146.3
144.7
143.0
141.4

40%
147.0
147.0
147.0
146.8
147.0
147.0
147.0
146.1
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
147.0
146.2
147.0
147.0
147.0
142.6
136.0
147.0
147.0
139.2
141.4
142.8
143.7
147.0
147.0
147.0
145.3
139.2
136.1
147.0
147.0
146.7
141.8
139.3
136.8
147.0
147.0
146.2
144.4
142.5
140.6

Bulletin 71.2:LR125
Table 11. Capacity(1), Water (GPM / L/min) for 1 and 2 in. / DN 25 and 50 Bodies at % Droop (Pressure Offset Below Setpoint)(2)
SPRING
RANGE AND
COLOR

OUTLET
PRESSURE
psig

15

15 to 30 psig /
1.0 to 2.1 bar
Yellow

20

30

25

25 to 75 psig /
1.7 to 5.2 bar
Green

50

75

70

100

bar

1.0

1.4

2.1

1.7

3.4

5.2

4.8

6.9

70 to 150 psig /
4.8 to 10.3 bar
Red
125

150

8.6

10.3

1 IN. / DN 25

INLET

10%

20%

2 IN. / DN 50

30%

40%

10%

20%

30%

40%

psig

bar

GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min

45

3.1

83

314

85

322

87

329

89

336

223

843

254

961

284

1074

305

1154

50

3.4

89

338

91

345

93

352

95

359

237

897

274

1037

304

1151

324

1226

60

4.1

101

382

103

388

104

394

106

400

261

989

311

1178

341

1292

357

1353

65

4.4

106

402

108

408

109

414

111

419

272

1028

329

1245

359

1358

372

1409

50

3.4

84

317

86

327

89

336

91

345

287

1088

296

1121

305

1154

313

1185

60

4.1

96

363

98

372

100

380

103

388

314

1190

336

1272

344

1302

349

1323

70

4.8

107

404

109

412

111

419

113

427

333

1259

368

1392

378

1429

380

1440

75

5.1

112

423

114

430

116

438

117

445

339

1284

382

1446

393

1487

394

1493

60

4.1

85

322

89

336

92

350

96

363

292

1105

305

1154

317

1201

329

1246

75

5.1

103

388

106

400

109

412

112

423

352

1332

363

1373

373

1413

383

1449

90

6.1

117

445

120

455

123

465

126

475

403

1526

413

1562

422

1597

426

1611

100

6.8

126

479

129

488

132

498

134

507

407

1541

443

1676

450

1703

451

1707

55

3.7

84

319

88

331

91

343

94

354

290

1096

301

1138

311

1178

321

1216

75

5.1

107

406

110

415

112

425

115

434

368

1393

377

1426

385

1458

392

1484

80

5.4

112

425

115

434

117

443

119

452

385

1458

394

1490

402

1520

407

1541

90

6.1

122

460

124

469

126

477

128

485

417

1580

425

1609

433

1637

435

1648

80

5.4

88

331

94

354

99

376

105

396

290

1097

317

1200

335

1267

351

1329

100

6.8

110

415

115

434

119

452

124

469

364

1378

388

1469

403

1526

417

1579

125

8.5

132

501

136

517

140

532

144

546

440

1665

461

1746

475

1798

488

1847

150

10.2

152

574

155

588

159

601

162

613

505

1912

524

1984

538

2037

551

2086

110

7.5

96

365

105

396

112

425

119

452

331

1254

359

1360

385

1458

410

1550

125

8.5

112

425

119

452

126

477

132

501

385

1458

410

1550

433

1637

454

1720

150

10.2

134

509

140

532

146

553

152

574

452

1711

472

1787

489

1851

511

1934

175

11.9

153

577

159

601

164

620

169

639

469

1776

498

1885

514

1945

537

2031

200

13.6

164

620

171

647

177

670

180

683

469

1775

510

1932

526

1992

551

2085

100

6.8

90

341

98

372

106

400

113

427

307

1163

327

1240

352

1334

380

1438

125

8.5

117

441

123

465

129

488

135

510

363

1373

382

1447

406

1537

432

1637

150

10.2

137

519

143

541

148

560

154

582

388

1469

414

1567

440

1666

468

1772

175

11.9

154

585

161

610

166

629

171

646

472

1788

501

1898

516

1953

539

2039

190

12.9

164

620

171

648

176

665

180

682

523

1981

555

2100

562

2126

580

2196

200

13.6

170

643

178

672

182

688

186

704

558

2111

591

2236

592

2240

608

2301

130

8.8

94

354

105

396

115

434

124

469

321

1216

353

1337

384

1454

416

1575

150

10.2

115

434

124

469

132

501

140

532

388

1469

414

1567

440

1666

468

1772

175

11.9

136

517

144

546

152

574

159

601

446

1688

476

1804

499

1889

524

1983

200

13.6

155

588

162

614

169

639

175

663

489

1853

529

2002

550

2081

572

2166

250

17.0

180

681

185

700

191

723

196

742

547

2071

614

2324

634

2400

653

2472

275

18.7

189

715

191

724

197

745

202

763

565

2138

649

2458

670

2535

687

2602

155

10.5

96

365

110

415

122

460

132

501

331

1254

377

1426

417

1580

454

1720

175

11.9

117

443

128

485

138

524

148

560

402

1520

440

1665

475

1799

506

1917

200

13.6

138

524

148

560

157

594

165

626

429

1623

475

1798

512

1938

541

2046

250

17.0

174

657

181

686

189

714

196

741

512

1937

568

2151

598

2265

622

2353

275

18.7

187

708

193

731

200

757

206

779

542

2053

606

2295

633

2398

655

2479

300

20.4

198

750

203

767

209

790

214

810

567

2148

640

2424

665

2516

684

2591

180

12.2

99

376

115

434

128

485

140

532

305

1153

365

1383

424

1607

465

1761

200

13.6

119

452

132

501

144

546

155

588

363

1374

418

1582

471

1783

507

1919

225

15.3

140

532

152

574

162

614

172

651

422

1599

474

1793

520

1968

552

2088

250

17.0

159

601

169

639

178

675

187

709

472

1788

521

1972

561

2125

589

2231

275

18.7

175

663

184

697

193

730

201

762

515

1950

562

2129

597

2258

622

2354

300

20.4

190

720

199

752

207

782

214

812

553

2093

599

2267

627

2373

650

2461

1. Type LR125 on liquid service with 1/2 NPT Type MR95H Pilot, 100% Cage Capacity with internal inlet strainer and Type 112 Restrictor Setting of “4”.
2. Values published in this table are laboratory tested and are presented based on % droop (negative control deviation only) or pressure offset below setpoint.
Exceeds recommended maximum pressure drop ratio of 0.65.

- continued -

9

Bulletin 71.2:LR125
Table 11. C
 apacity(1), Water (GPM / L/min) for 3 and 4 in. / DN 80 and 100 Bodies at % Droop (Pressure Offset Below
Setpoint)(2) (continued)
SPRING
RANGE AND
COLOR

OUTLET
PRESSURE
psig

15

15 to 30 psig /
1.0 to 2.1 bar
Yellow

20

30

25

25 to 75 psig /
1.7 to 5.2 bar
Green

50

75

70

100

bar

1.0

1.4

2.1

1.7

3.4

5.2

4.8

6.9

70 to 150 psig /
4.8 to 10.3 bar
Red
125

150

8.6

10.3

INLET

3 IN. / DN 80
10%

20%

4 IN. / DN 100

30%

40%

10%

20%

30%

bar

GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min GPM L/min

45

3.1

466

1762

512

1939

537

2032

548

2076

749

2835

824

3119

863

3268

882

3339

50

3.4

503

1906

552

2090

574

2174

585

2215

810

3065

888

3362

924

3497

941

3563

60

4.1

573

2171

626

2370

643

2434

653

2471

922

3491

1007

3812

1034

3915

1050

3974

65

4.4

606

2295

661

2502

675

2554

683

2586

975

3690

1063

4024

1085

4108

1099

4159

50

3.4

517

1957

533

2017

548

2076

563

2133

832

3148

857

3245

882

3339

906

3430

60

4.1

592

2242

606

2295

620

2347

633

2397

953

3606

975

3691

997

3774

1018

3855

70

4.8

659

2495

672

2542

684

2589

696

2635

1060

4013

1080

4089

1100

4164

1120

4238

75

5.1

689

2606

702

2658

714

2702

725

2746

1107

4192

1129

4274

1148

4346

1160

4390

60

4.1

525

1988

548

2076

571

2161

592

2242

844

3197

882

3339

918

3475

953

3606

75

5.1

633

2397

653

2471

672

2542

690

2612

1018

3855

1050

3974

1080

4089

1110

4201

90

6.1

725

2746

743

2811

759

2874

776

2936

1167

4417

1194

4521

1221

4622

1247

4722

100

6.8

781

2956

797

3016

812

3075

828

3133

1256

4754

1282

4851

1307

4946

1331

5039

55

3.7

521

1972

541

2047

560

2119

578

2188

838

3172

870

3292

900

3408

930

3519

75

5.1

662

2507

678

2566

693

2624

708

2680

1065

4032

1090

4127

1115

4220

1139

4310

80

5.4

693

2624

708

2680

723

2735

737

2789

1115

4220

1139

4310

1162

4399

1185

4486

90

6.1

751

2843

765

2895

778

2946

792

2996

1208

4572

1230

4656

1252

4738

1273

4819

80

5.4

541

2047

578

2188

613

2321

646

2447

870

3292

930

3519

986

3733

1039

3935

100

6.8

678

2566

708

2680

737

2789

765

2895

1090

4127

1139

4310

1185

4486

1230

4656

125

8.5

818

3095

843

3190

867

3282

891

3372

1315

4977

1355

5130

1395

5279

1433

5424

150

10.2

937

3545

959

3629

980

3710

996

3770

1506

5702

1542

5836

1576

5967

1602

6063

110

7.5

596

2256

646

2447

693

2624

737

2789

958

3628

1039

3935

1115

4220

1185

4486

125

8.5

693

2624

737

2789

778

2946

818

3095

1115

4220

1185

4486

1252

4738

1315

4977

150

10.2

830

3143

867

3282

903

3416

937

3545

1335

5054

1395

5279

1452

5495

1506

5702

175

11.9

893

3380

942

3566

974

3688

1011

3827

1436

5437

1515

5736

1567

5931

1626

6155

200

13.6

927

3511

987

3737

1020

3860

1053

3985

1492

5646

1588

6010

1640

6209

1693

6409

100

6.8

556

2105

606

2295

653

2471

696

2635

894

3385

975

3691

1050

3974

1120

4238

125

8.5

691

2614

736

2786

780

2954

833

3152

1111

4205

1184

4481

1255

4750

1339

5070

150

10.2

772

2923

814

3081

853

3228

900

3405

1242

4701

1309

4956

1372

5192

1447

5477

175

11.9

902

3414

949

3591

978

3704

1014

3839

1450

5490

1526

5776

1574

5956

1631

6175

190

12.9

977

3698

1028

3890

1051

3980

1080

4088

1571

5947

1653

6257

1691

6401

1737

6575

200

13.6

1026

3884

1080

4087

1099

4161

1123

4250

1650

6246

1737

6574

1768

6693

1806

6836

130

8.8

578

2188

646

2447

708

2680

765

2895

930

3519

1039

3935

1139

4310

1230

4656

150

10.2

708

2680

765

2895

818

3095

867

3282

1139

4310

1230

4656

1315

4977

1395

5279

175

11.9

836

3165

891

3372

937

3545

980

3710

1345

5090

1433

5424

1506

5702

1576

5967

200

13.6

924

3497

989

3743

1031

3901

1069

4047

1486

5624

1590

6019

1658

6275

1719

6509

250

17.0

1048

3967

1124

4253

1160

4392

1193

4515

1685

6380

1807

6841

1866

7063

1918

7261

275

18.7

1091

4131

1175

4447

1210

4580

1241

4696

1755

6644

1890

7153

1946

7367

1995

7553

155

10.5

596

2256

678

2566

751

2843

818

3095

958

3628

1090

4127

1208

4572

1315

4977

175

11.9

723

2735

792

2996

855

3236

914

3460

1162

4399

1273

4819

1375

5205

1470

5565

200

13.6

827

3131

905

3425

967

3660

1020

3860

1330

5035

1455

5509

1555

5887

1640

6208

250

17.0

999

3782

1074

4067

1124

4256

1166

4414

1607

6082

1728

6541

1808

6845

1875

7099

275

18.7

1065

4033

1142

4323

1188

4495

1225

4636

1714

6487

1837

6953

1910

7230

1970

7457

300

20.4

1122

4249

1201

4548

1243

4704

1276

4830

1805

6834

1932

7314

1999

7565

2052

7769

180

12.2

599

2266

707

2677

792

2996

867

3282

963

3645

1137

4306

1273

4819

1395

5279

200

13.6

716

2709

811

3072

891

3372

959

3629

1151

4357

1305

4940

1433

5424

1542

5836

225

15.3

836

3166

922

3491

996

3771

1056

3998

1345

5091

1483

5614

1602

6065

1699

6431

250

17.0

939

3554

1018

3853

1083

4100

1135

4298

1510

5716

1637

6196

1742

6593

1826

6912

275

18.7

1029

3894

1102

4172

1160

4390

1205

4562

1654

6262

1773

6711

1865

7060

1938

7337

300

20.4

1109

4198

1178

4459

1228

4648

1267

4797

1783

6751

1895

7172

1975

7476

2038

7715

1. Type LR125 on liquid service with 1/2 NPT Type MR95H Pilot, 100% Cage Capacity with internal inlet strainer and Type 112 Restrictor Setting of “4”.
2. Values published in this table are laboratory tested and are presented based on % droop (negative control deviation only) or pressure offset below setpoint.
Exceeds recommended maximum pressure drop ratio of 0.65.

10

40%

psig

Bulletin 71.2:LR125
TYPE MR95H PILOT
M

OPTIONAL
INDICATOR COVER

1/4 NPT
VENT

TYPE 112
RESTRICTOR

T

TRAVEL INDICATOR
COVER REMOVAL
CLEARANCE

1/2 NPT
CONTROL
LINE
CONNECTION

1/4 NPT PILOT
SUPPLY CONNECTION
E

D
D1

V

VALVE TRIM
REMOVAL
CLEARANCE

G

A
B
ERAA00985_B

TYPE LR125 WITH TYPE MR95H PILOT

Figure 5. Type LR125 Dimensions
Table 12. Type LR125 Dimensions
DIMENSIONS, IN. / mm

BODY SIZE
In.

DN

1

25

2

50

3

80

4

100

A
CL150 RF

CL300 RF

3.62 /
91.9
5.0 /
127.0
5.9 /
149.3
6.9 /
176.3

3.88 /
98.6
5.3 /
133.4
6.3 /
158.8
7.3 /
184.2

B
CL600 RF

CL150 RF

CL300 RF

CL600 RF

4.13 / 104.9

7.25 / 184.2

7.75 / 196.9

8.25 / 209.6

10.00 / 254.0

10.50 / 266.7

11.25 / 286.0

11.75 / 298.5

12.50 / 317.5

13.25 / 336.6

13.88 / 352.6

14.50 / 368.3

15.50 / 393.7

5.6 /
143.0
6.6 /
168.3
7.8 /
196.9

Ordering Information
Carefully review each specification, then complete
the Ordering Guide on this page. If a pilot setpoint
is not requested, the regulator will be factory set at
the approximate midrange. Please complete the
specifications worksheet at the bottom of the ordering
guide on page 12.

Ordering Guide
Body Size (Select One)
    1 in. / DN 25***
    2 in. / DN 50***
    3 in. / DN 80***
    4 in. / DN 100***
Body Material and End Connection Style (Select One)
WCC Steel Body
    NPT (Available in 1 and 2 in. bodies only)***
    SWE (Available in 1 and 2 in. bodies only)***
    CL150 RF***
    CL300 RF***
    CL600 RF***
   PN 16/25/40 RF* (Not available in 4 in. body)
_____________ specify rating

D

D1

E

G

7.40 /
189.0
9.00 /
229.0
13.30 /
338.0
14.70 /
373.0

5.40 /
137.0
6.89 /
175.0
9.33 /
236.9
10.47 /
265.9

11.39 /
289.3
11.65 /
295.9
13.68 /
347.5
15.24 /
387.1

2.40 /
60.0
3.10 /
79.0
3.80 /
97.0
5.10 /
130.0

M
WCC
Steel
8.10 /
205.8
8.18 /
207.8
8.66 /
220.0
9.52 /
241.8

CF8M
SST
8.10 /
205.8
9.18 /
233.2
9.66 /
245.4
9.52 /
241.8

T

V

2.97 /
75.4
2.00 /
51.0
3.80 /
97.0
3.80 /
97.0

9.40 /
238.8
11.00 /
279.4
15.00 /
381.0
17.00 /
431.8

CF8M Stainless Steel Body
    NPT (Available in 1 and 2 in. bodies only)***
    CL150 RF***
    CL300 RF***
    CL600 RF***
   PN 16/25/40 RF* (Not available in 4 in. body)
_____________ specify rating
Main Valve Diaphragm Material (Select One)
   17E68 Nitrile (NBR) (low minimum differential
capability) (standard)***
    17E97 Nitrile (NBR) (high erosion resistant)***
   17E88 Fluorocarbon (FKM)
(high temperature capability)**
Main Valve O-ring Material (Select One)
    Nitrile (NBR) (standard)***
    Fluorocarbon (FKM)**
Travel Indicator (Select One)
   No (standard)***
   Yes***
Inlet Body Tap (Select One)
    Inlet body tap only (standard)***	
    Inlet body tap with pre-piped pilot supply***
    Inlet/outlet body taps only***	
   Inlet/outlet body taps with pre-piped pilot supply and
pilot bleed***
11

Bulletin 71.2:LR125
Ordering Guide (continued)
Pilot Diaphragm Material (Select One)
    Neoprene (CR) (standard)***
    Fluorocarbon (FKM)**
Pilot Valve Plug Material (Select One)
    Nitrile (NBR) (standard)***
    Fluorocarbon (FKM)***
Type MR95H Pilot Outlet Pressure Range (Select One)
    15 to 30 psig / 1.0 to 2.1 bar, Yellow***
    25 to 75 psig / 1.7 to 5.2 bar, Green***
    70 to 150 psig / 4.8 to 10.3 bar, Red***
Main Valve Replacement Parts Kit (Optional)
   Yes, send one diaphragm cartridge and O-rings kit to
match this order.
Pilot Replacement Parts Kit (Optional)
    Yes, send one replacement kit to match this order.

Regulators Quick Order Guide
***
**
*

Readily Available for Shipment
Allow Additional Time for Shipment
Special Order, Constructed from Non-Stocked Parts.
Consult your local Sales Office for Availability.

Availability of the product being ordered is determined by the component with the
longest shipping time for the requested construction.

Specification Worksheet
Application:
Specific Use____________________________________
Line Size______________________________________
Fluid Type_____________________________________
Specific Gravity_________________________________
Temperature_ __________________________________
Does the Application Require Overpressure Protection? 	
	     Yes    No
Pressure:
Maximum Inlet Pressure__________________________
Minimum Inlet Pressure___________________________
Differential Pressure_ ____________________________
Set Pressure___________________________________
Maximum Flow_ ________________________________
Accuracy Requirements:
Less Than or Equal To:
 
 5%    10%    20%    40%
Construction Material Requirements (if known):
_____________________________________________
_____________________________________________

Industrial Regulators

Natural Gas Technologies

TESCOM

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Regulator Technologies, Inc.

Emerson Process Management
Tescom Corporation

USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574

USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574

USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238
+1 800 447 1250

Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9000

Asia-Pacific
Singapore 128461, Singapore
Tel: +65 6770 8337

Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Chartres 28008, France
Tel: +33 2 37 33 47 00

Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9499

Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100

Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100

For further information visit www.fisherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC,
a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and
maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.

©Emerson Process Management Regulator Technologies, Inc., 2012, 2014; All Rights Reserved



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Create Date                     : 2014:11:14 13:53:02+08:00
Metadata Date                   : 2014:11:14 13:53:12+08:00
Modify Date                     : 2014:11:14 13:53:12+08:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:f4960c5c-cd83-4525-8c5e-7d82f8260b70
Original Document ID            : adobe:docid:indd:2dc6fcc6-6b90-11de-90f8-935b57562292
Document ID                     : xmp.id:78D6FF76C26BE411BF1D9EBF1D1A45FB
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:77D6FF76C26BE411BF1D9EBF1D1A45FB
Derived From Document ID        : xmp.did:3E24FF28C16BE41195D1B93F6A78ECAF
Derived From Original Document ID: adobe:docid:indd:2dc6fcc6-6b90-11de-90f8-935b57562292
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2014:11:14 13:53:02+08:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 12
Creator                         : Adobe InDesign CS6 (Windows)
EXIF Metadata provided by EXIF.tools

Navigation menu