Endress and Hauser and Co FMR6XE Level Probing Radar User Manual Micropilot FMR62

Endress and Hauser GmbH and Co Level Probing Radar Micropilot FMR62

User Manual

Download: Endress and Hauser and Co FMR6XE Level Probing Radar User Manual Micropilot FMR62
Mirror Download [FCC.gov]Endress and Hauser and Co FMR6XE Level Probing Radar User Manual Micropilot FMR62
Document ID3393264
Application IDNnQfxwdLpct4AEWcs3itGA==
Document DescriptionUser Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize243.38kB (3042285 bits)
Date Submitted2017-05-16 00:00:00
Date Available2017-05-16 00:00:00
Creation Date2016-12-09 14:59:41
Producing SoftwareAntenna House PDF Output Library 2.6.0 (Windows (x64))
Document Lastmod2016-12-09 15:03:16
Document TitleMicropilot FMR62
Document CreatorAH XSL Formatter V5.3 MR5 for Windows (x64) : 5.3.6.0 (2012/12/04 12:44:48)
Document Author: 00

TI01303F/EN/12.16
Products
Solutions
Services
Technical Information
Micropilot FMR62
Free space radar
Level measurement in liquids
Application
• Continuous, non-contact level measurement of liquids,
pastes and sludges
• Integrated PEEK antenna or PTFE-plated, flush-mounted antenna
• Maximum measuring range: 80 m (262 ft)
• Temperature: –40 to +200 °C (–40 to +392 °F)
• Pressure: –1 to +25 bar (–14.5 to +362.6 psi)
• Accuracy: ± 1 mm (0.04 in)
• International explosion protection certificates; WHG
• Linearity protocol (3-point, 5-point)
Your benefits
• Reliable measurement thanks to improved focusing and small beam angle,
particularly in vessels with many internal fittings
• Compact design enables installation in the case of small vessels and small process
connections
• Easy, guided commissioning with intuitive user interface in
local language
• Reliable measurement even in variable product and process conditions
• Maximum reliability thanks to multi-echo tracking
• HistoROM configuration memory makes for easier commissioning,
maintenance and diagnostics
• SIL2 as per IEC 61508, SIL3 for homogeneous or diverse redundancy
• Easy proof testing for SIL and WHG
• Seamless integration in process control and asset management systems
• Heartbeat Technology
Micropilot FMR62
Table of contents
Important document information . . . . . . . . . . . . . . . 4
Safety symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols for certain types of information . . . . . . . . . . . . . .
Symbols in graphics . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols at the device . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . .
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 7
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Ambient temperature range . . . . . . . . . . . . . . . . . . . . .
Ambient temperature limits . . . . . . . . . . . . . . . . . . . . .
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . .
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Altitude according to IEC61010-1 Ed.3 . . . . . . . . . . . . . .
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . .
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning the antenna . . . . . . . . . . . . . . . . . . . . . . . . . .
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . .
32
32
33
33
33
33
33
33
34
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Function and system design . . . . . . . . . . . . . . . . . . . 8
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Process temperature, process pressure . . . . . . . . . . . . . . . 35
Dielectric constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mechanical construction . . . . . . . . . . . . . . . . . . . .
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating frequency . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transmission power . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protocol-specific data . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . .
Device plug connectors . . . . . . . . . . . . . . . . . . . . . . . . .
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . .
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . .
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . .
10
10
10
10
11
11
12
12
18
19
21
21
21
21
21
22
22
Performance characteristics . . . . . . . . . . . . . . . . . . 23
Reference operating conditions . . . . . . . . . . . . . . . . . . .
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . .
Measured value resolution . . . . . . . . . . . . . . . . . . . . . .
Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Influence of ambient temperature . . . . . . . . . . . . . . . . .
Influence of gas phase . . . . . . . . . . . . . . . . . . . . . . . . .
23
23
23
23
24
24
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . .
Installation: integrated antenna . . . . . . . . . . . . . . . . . . .
Installation: flush mount antenna . . . . . . . . . . . . . . . . . .
Container with heat insulation . . . . . . . . . . . . . . . . . . . .
Turning the transmitter housing . . . . . . . . . . . . . . . . . .
Turning the display module . . . . . . . . . . . . . . . . . . . . . .
25
28
29
30
31
31
V. 1, Rev. 3, 9-12-2016
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Materials: GT18 housing (stainless steel, corrosionresistant) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Materials: GT19 housing (plastic) . . . . . . . . . . . . . . . . . .
Materials: GT20 housing (die-cast aluminum, powdercoated, seawater-resistant) . . . . . . . . . . . . . . . . . . . . . .
Materials: antenna and process connection . . . . . . . . . . .
Materials: Weather protection cover . . . . . . . . . . . . . . . .
38
38
42
43
44
45
46
48
Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation with remote display and operating module
FHX50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System integration via Fieldgate . . . . . . . . . . . . . . . . . . .
49
49
Certificates and approvals . . . . . . . . . . . . . . . . . . .
53
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RCM-Tick marking . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dual seal according to ANSI/ISA 12.27.01 . . . . . . . . . . . .
Functional safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WHG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hygienic compatibility . . . . . . . . . . . . . . . . . . . . . . . . .
NACE MR 0175 / ISO 15156 . . . . . . . . . . . . . . . . . . . . .
NACE MR 0103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure equipment with allowable pressure
≤ 200 bar (2 900 psi) . . . . . . . . . . . . . . . . . . . . . . . . . .
Marine approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Radio standard EN 302729-1/2 . . . . . . . . . . . . . . . . . . .
Radio standard EN 302372-1/2 . . . . . . . . . . . . . . . . . . .
FCC / Industry Canada . . . . . . . . . . . . . . . . . . . . . . . . .
Japanese radio approval . . . . . . . . . . . . . . . . . . . . . . . .
CRN approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test, certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hard-copy product documentation . . . . . . . . . . . . . . . . .
Other standards and guidelines . . . . . . . . . . . . . . . . . . .
50
50
52
53
53
53
53
53
53
53
53
54
54
54
54
54
55
55
56
56
57
57
58
Endress+Hauser
Micropilot FMR62
Ordering information . . . . . . . . . . . . . . . . . . . . . . . 59
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . .
3-point linearity protocol . . . . . . . . . . . . . . . . . . . . . . .
5-point linearity protocol . . . . . . . . . . . . . . . . . . . . . . .
Customer-specific configuration . . . . . . . . . . . . . . . . . . .
Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
59
60
61
62
62
Application Packages . . . . . . . . . . . . . . . . . . . . . . . 63
Heartbeat Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . .
Heartbeat Verification . . . . . . . . . . . . . . . . . . . . . . . . .
Heartbeat Monitoring . . . . . . . . . . . . . . . . . . . . . . . . .
63
64
65
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Device-specific accessories . . . . . . . . . . . . . . . . . . . . . .
Communication-specific accessories . . . . . . . . . . . . . . . .
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . .
System components . . . . . . . . . . . . . . . . . . . . . . . . . . .
66
69
70
70
Supplementary documentation . . . . . . . . . . . . . . .
71
Standard documentation . . . . . . . . . . . . . . . . . . . . . . . . 71
Safety Instructions (XA) . . . . . . . . . . . . . . . . . . . . . . . . 71
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
Micropilot FMR62
Important document information
Safety symbols
Symbol
Meaning
DANGER
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
NOTICE
Electrical symbols
Symbols for certain types of
information
Symbol
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
Meaning
Symbol
Meaning
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
Symbol
Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
Symbol
Meaning
1, 2, 3 ...
Item numbers
1. , 2. , 3. …
Series of steps
A, B, C, ...
Views
A-A, B-B, C-C, ...
Sections
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Symbol
Symbols at the device
Meaning
Hazardous area
Indicates a hazardous area.
Safe area (non-hazardous area)
Indicates the non-hazardous area.
Symbol
Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
Micropilot FMR62
Terms and abbreviations
Term/abbreviation Explanation
BA
Document type "Operating Instructions"
KA
Document type "Brief Operating Instructions"
TI
Document type "Technical Information"
SD
Document type "Special Documentation"
XA
Document type "Safety Instructions"
PN
Nominal pressure
MWP
Maximum Working Pressure
The MWP can also be found on the nameplate.
ToF
Time of Flight
FieldCare
Scalable software tool for device configuration and integrated plant asset management
solutions
DeviceCare
Universal configuration software for Endress+Hauser HART, PROFIBUS,
FOUNDATION Fieldbus and Ethernet field devices
DTM
Device Type Manager
DD
Device Description for HART communication protocol
DC
Relative dielectric constant εr
Operating tool
The term "operating tool" is used in place of the following operating software:
FieldCare / DeviceCare, for operation via HART communication and PC
BD
Blocking Distance; no signals are analyzed within the BD.
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Registered trademarks
HART®
Registered trademark of the HART Communication Foundation, Austin, USA
KALREZ®, VITON®
Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA
TEFLON®
Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA
TRI CLAMP®
Registered trademark of Ladish Co. Inc., Kenosha, USA
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
Micropilot FMR62
Function and system design
Measuring principle
The Micropilot is a "downward-looking" measuring system, operating based on the frequency
modulated continuous wave method (FMCW). The antenna emits an electromagnetic wave at a
continuously varying frequency. This wave is reflected by the product and received again by the
antenna.
A0032017
1
FMCW principle: transmission and reflection of the continuous wave
Reference point of measurement
Distance between reference point and product surface
The frequency of this wave is modulated in the form of a sawtooth signal between two limit
frequencies f1 and f2:
f2
Δf
Δt
f1
A0023771
2
FMCW principle: result of frequency modulation
Transmitted signal
Received signal
This results in the following difference frequency at any time between the transmitted signal and the
received signal:
Δf = k Δt
where Δt is the run time and k is the specified increase in frequency modulation.
Δt is given by the distance D between the reference point R and the product surface:
D = (c Δt) / 2
where c is the speed of propagation of the wave.
In summary, D can be calculated from the measured difference frequency Δf. D is then used to
determine the content of the tank or silo.
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Input
Measured variable
The measured variable is the distance between the reference point and the product surface. The level
is calculated based on "E", the empty distance entered. Optionally, the level can be converted to other
variables (volume, mass) by linearization (32 value pairs).
Measuring range
Maximum measuring range
Device
Antenna 1)
Maximum measuring range
FMR62
GE:
integrated, PEEK, 20 mm / 3/4"
10 m (32.8 ft)
GF:
integrated PEEK, 40 mm / 1-1/2"
22 m (72 ft)
GM:
PTFE cladded flush mount 50 mm / 2"
50 m (164 ft)
GN:
PTFE cladded flush mount 80 mm / 3"
80 m (262 ft)
1)
Feature 070 in the product structure
Usable measuring range
The usable measuring range depends on the antenna size, the medium's reflective properties, the
installation position and any possible interference reflections.
Tables in preparation
For dielectric constants (DC values) of many media commonly used in various industries refer
to:
• the Endress+Hauser DC manual (CP01076F)
• the Endress+Hauser "DC Values App" (available for Android and iOS)
Operating frequency
Approx. 80 GHz
Several FMR6x devices can be installed in one tank thanks to the short measuring duration and the
high beam focus.
Transmission power
Endress+Hauser
• Peak pulse power: 6.3 mW
• Average output power: 63 µW
V. 1, Rev. 3, 9-12-2016
Micropilot FMR62
Output
Output signal
HART
Signal coding
FSK ±0.5 mA over current signal
Data transmission rate
1 200 Bit/s
Galvanic isolation
Yes
Switch output
For HART devices, the switch output is available as an option. See product structure, feature 20:
"Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"
Devices with PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
Switch output
Function
Open collector switching output
Switching behavior
Binary (conductive or non-conductive), switches when the programmable switch
point is reached
Failure mode
non-conductive
Electrical connection
values
U = 10.4 to 35 VDC, I = 0 to 40 mA
Internal resistance
RI < 880 Ω
The voltage drop at this internal resistance has to be taken into account on
planning the configuration. For example, the resulting voltage at a connected
relay must be sufficient to switch the relay.
Insulation voltage
floating, Insulation voltage 1 350 VDC to power supply aund 500 VAC to ground
Switch point
freely programmable, separately for switch-on and switch-off point
Switching delay
freely programmable from 0 to 100 s, separately for switch-on and switch-off
point
Number of switching cycles corresponds to the measuring cycle
Signal source
device variables
•
•
•
•
•
•
Level linearized
Distance
Terminal voltage
Electronic temperature
Relative echo amplitude
Diagnostic values, Advanced diagnostics
Number of switching cycles unlimited
Signal on alarm
Depending on the interface, failure information is displayed as follows:
• Current output (for HART devices)
– Failsafe mode selectable (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA
Maximum alarm (= factory setting): 22 mA
– Failsafe mode with user-selectable value: 3.59 to 22.5 mA
• Local display
– Status signal (in accordance with NAMUR Recommendation NE 107)
– Plain text display
• Operating tool via digital communication (HART, PROFIBUS PA, FOUNDATION Fieldbus) or
service interface (CDI)
– Status signal (in accordance with NAMUR Recommendation NE 107)
– Plain text display
Linearization
The linearization function of the device allows the conversion of the measured value into any unit of
length or volume. Linearization tables for calculating the volume in cylindrical tanks are preprogrammed. Other linearization tables of up to 32 value pairs can be entered manually or semiautomatically.
10
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data
HART
Manufacturer ID
17 (0x11)
Device type ID
0x112B
HART specification
7.0
Device description files (DTM, DD)
Information and files under:
• www.endress.com
• www.hartcomm.org
HART load
min. 250 Ω
HART device variables
The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Electronic temperature
• Terminal voltage
• Relative echo amplitude
• Absolute echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Supported functions
• Burst mode
• Additional transmitter status
Wireless HART data
Endress+Hauser
Minimum start-up voltage
16 V
Start-up current
3.6 mA
Start-up time
40 s
Minimum operating voltage
12.3 V
Multidrop current
3.6 mA
Set-up time
1s
V. 1, Rev. 3, 9-12-2016
11
Micropilot FMR62
Power supply
Terminal assignment
2-wire: 4-20mA HART
2- w
4-2 ire le
HA mA
[21 RT
el
4-2
0m
ope
mm
10
4...
HA 20mA
RT
Sp
711 re pa
08x rt
xx
–
–
4...20 mA
1-c
[16
han
nel
ove
1 4-2 2
rvo
ltag
0m
pro
tec
tion
–
–
4...20 mA
A0011294
3
12
Terminal assignment 2-wire; 4-20mA HART
Without integrated overvoltage protection
With integrated overvoltage protection
Active barrier with power supply (e.g. RN221N): Observe terminal voltage
HART communication resistor (≥ 250 Ω): Observe maximum load
Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
Analog display device: Observe maximum load
Cable screen; observe cable specification
4-20mA HART (passive): Terminals 1 and 2
Overvoltage protection module
Terminal for potential equalization line
Cable entry
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
2-wire: 4-20mA HART, switch output
10
2- w
4-2 ire
HA mA
[02 RT
/03
PF
ope
1 2
10
4-
mm
++
31 -42
3+
Sp
711 re pa
08x rt
xx
4...
HA 20 mA
RT
–
≥250 Ω 4...20 mA
2 3
3+
3 4-2 4
11
2-c
han
4[17
1 4-2 2
0m
el o
erv
olta
FIE 0mA
LD
BU
pro
ge
tec
–
tion
≥250 Ω 4...20 mA
2 3
A0013759
4
10
11
Endress+Hauser
Terminal assignment 2-wire; 4-20mA HART, switch output
Without integrated overvoltage protection
With integrated overvoltage protection
Active barrier with power supply (e.g. RN221N): Observe terminal voltage
HART communication resistor (≥ 250 Ω): Observe maximum load
Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
Analog display device: Observe maximum load
Cable screen; observe cable specification
4-20mA HART (passive): Terminals 1 and 2
Switch output (open collector): Terminals 3 and 4
Terminal for potential equalization line
Cable entry for 4-20mA HART line
Cable entry for switch output line
Overvoltage protection module
V. 1, Rev. 3, 9-12-2016
13
Micropilot FMR62
2-wire: 4-20mA HART, 4-20mA
14
13
12
2- w
4-2 ire le
el
4-2
0m
–
1 "
Sp
711 re pa
08x rt
xx
1 2
10
mm
3 4
11
ope
4...
HA 20mA
RT
4...
20m
HA mA
[04 RT
/05
4...20 mA
–
2 "
4...20 mA
5 6
–
1 "
3 4-2 4
4...20 mA
10
2-c
[17
0m
han
nel
1 -
4FIE 20mA
ove
rvo
LD
ltag
ep
ro
tec
–
2 "
tion
4...20 mA
5 6
A0013923
5
10
11
12
13
14
Terminal assignment 2-wire, 4-20 mA HART, 4...20mA
Without integrated overvoltage protection
With integrated overvoltage protection
Connection current output 2
Connection current output 1
Supply voltage for current output 1 (e.g. RN221N); Observe terminal voltage
Cable screen; observe cable specification
HART communication resistor (≥ 250 Ω): Observe maximum load
Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
Analog display device ; observe maximum load
Analog display device ; observe maximum load
Supply voltage for current output 2 (e.g. RN221N); Obeserve terminal voltage
Overvoltage protection module
Current output 2: Terminals 3 and 4
Terminal for the potential equalization line
Cable entry for current output 1
Cable entry for current output 2
This version is also suited for single-channel operation. In this case, current output 1 (terminals
1 and 2) must be used.
14
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
4-wire: 4-20mA HART (10.4 to 48 VDC)
13
12
11
3 4
10
Sp
711 re pa
08x rt
xx
mm
10
L+
1 L2
ope
4...
HA 20 mA
RT
10.
4...
48
V=
2- w
4-2 ire
HA mA
[08 RT
≥250 Ω
4...20 mA
2 3
A0011340
6
10
11
12
13
Endress+Hauser
Terminal assignment 4-wire; 4-20mA HART (10.4 to 48 VDC)
Evaluation unit, e.g. PLC
HART communication resistor (≥ 250 Ω): Observe maximum load
Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
Analog display device: Observe maximum load
Signal cable including screening (if required), observe cable specification
Protective connection; do not disconnect!
Protective earth, observe cable specification
4...20mA HART (active): Terminals 3 and 4
Supply voltage: Terminals 1 and 2
Supply voltage: Observe terminal voltage, observe cable specification
Terminal for potential equalization
Cable entry for signal line
Cable entry for power supply
V. 1, Rev. 3, 9-12-2016
15
Micropilot FMR62
4-wire: 4-20mA HART (90 to 253 VAC)
13
12
11
3 4
mm
Sp
711 re pa
08x rt
xx
10
10
1 N
ope
4...
HA 20 mA
RT
..25
3V
90.
2- w
4-2 ire
HA mA
[09 RT
≥250 Ω
4...20 mA
2 3
A0018965
7
10
11
12
13
Terminal assignment 4-wire; 4-20mA HART (90 to 253 VAC)
Evaluation unit, e.g. PLC
HART communication resistor (≥ 250 Ω): Observe maximum load
Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
Analog display device: Observe maximum load
Signal cable including screening (if required), observe cable specification
Protective connection; do not disconnect!
Protective earth, observe cable specification
4...20mA HART (active): Terminals 3 and 4
Supply voltage: Terminals 1 and 2
Supply voltage: Observe terminal voltage, observe cable specification
Terminal for potential equalization
Cable entry for signal line
Cable entry for power supply
LCAUTION
To ensure electrical safety:
‣ Do not disconnect the protective connection (6).
‣ Disconnect the supply voltage before disconnecting the protective earth (7).
Connect protective earth to the internal ground terminal (7) before connecting the supply
voltage. If necessary, connect the potential matching line to the external ground terminal (11).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
An easily accessible power switch must be installed in the proximity of the device. The power
switch must be marked as a disconnector for the device (IEC/EN61010).
16
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Connection examples for the switch output
For HART devices, the switch output is available as an option. See product structure, feature 20:
"Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"
Devices with PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
3+
3+
4A0015909
8
4-
Connection of a relay
A0015910
Suitable relays (examples):
• Solid-state relay: Phoenix Contact OV-24DC/480AC/5 with mounting
rail connector UMK-1 OM-R/AMS
• Electromechanical relay: Phoenix Contact PLC-RSC-12DC/21
9
Connection of a digital input
Pull-up resistor
Digital input
For optimum interference immunity we recommend to connect an external resistor (internal
resistance of the relay or Pull-up resistor) of < 1 000 Ω.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
17
Micropilot FMR62
Device plug connectors
For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected
without opening the housing.
Pin assignment of the M12 plug connector
A0011175
Pin
Meaning
Signal +
not connected
Signal -
Ground
Pin
Meaning
Signal -
Signal +
Not connected
Screen
Pin assignment of the 7/8" plug connector
A0011176
18
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
An external power supply is necessary.
Supply voltage
Various power supply units can be ordered as an accessory from Endress+Hauser.
2-wire, 4-20mA HART, passive
"Power supply, output" 1) "Approval" 2)
Terminal voltage U at
device
Maximum load R, depending on the supply voltage U0 of the
power supply unit
A: 2-wire; 4-20mA HART •
•
•
•
14 to 35 V
R [W]
Non-hazardous
Ex nA
Ex ic
CSA GP
500
Ex ia / IS
14 to 30 V
•
•
•
•
14 to 35 V 3)
Ex d(ia) / XP
Ex ic(ia)
Ex nA(ia)
Ex ta / DIP
10
20
30
35
Ex ia + Ex d(ia) / IS + XP 14 to 30 V
1)
2)
3)
U0 [V]
25
14
A0031745
Feature 020 in the product structure
Feature 010 in the product structure
At ambient temperatures Ta≤ -20 °C, a terminal voltage U ≥ 16 V is required to start the device with the min. error current (3.6 mA).
"Power supply, output" 1)
"Approval" 2)
Terminal voltage U
at device
Maximum load R, depending on the supply voltage U0 of the
power supply unit
B: 2-wire; 4-20 mA HART,
switch output
•
•
•
•
•
•
•
•
16 to 35 V
R [W]
Non-hazardous
Ex nA
Ex nA(ia)
Ex ic
Ex ic(ia)
Ex d(ia) / XP
Ex ta / DIP
CSA GP
500
16 to 30 V
• Ex ia / IS
• Ex ia + Ex d(ia) / IS + XP
10
16
20
27
30
35
U0 [V]
A0031746
1)
2)
Feature 020 in the product structure
Feature 010 in the product structure
"Power supply, output" 1)
"Approval" 2) Terminal voltage U at device Maximum load R, depending on the supply voltage U0 of the
power supply unit
C: 2-wire; 4-20mA HART, 4-20mA All
16 to 30 V
R [W]
500
10
16
20
27
30
35
U0 [V]
A0031746
1)
2)
Feature 020 in the product structure
Feature 010 in the product structure
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
19
Micropilot FMR62
20
Integrated polarity
reversal protection
Yes
Permitted residual ripple
with f = 0 to 100 Hz
USS < 1 V
Permitted residual ripple
with f = 100 to 10000 Hz
USS < 10 mV
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
4-wire, 4-20mA HART, active
"Power supply; output" 1)
Terminal voltage U
K: 4-wire 90-253VAC; 4-20mA HART 90 to 253 VAC (50 to 60 Hz), overvoltage
category II
Maximum load Rmax
500 Ω
L: 4-wire 10.4-48VDC; 4-20mA HART 10.4 to 48 VDC
1)
Power consumption
"Power supply; Output" 1)
Power consumption
A: 2-wire; 4-20mA HART
< 0.9 W
B: 2-wire; 4-20mA HART, switch output
< 0.9 W
C: 2-wire; 4-20mA HART, 4-20mA
< 2 x 0.7 W
K: 4-wire 90-253VAC; 4-20mA HART
6 VA
L: 4-wire 10,4-48VDC; 4-20mA HART
1.3 W
1)
Current consumption
Feature 020 in the product structure
Feature 020 of the product structure
HART
Nominal current
3.6 to 22 mA, the start-up current for multidrop mode can be parametrized (is
set to 3.6 mA on delivery)
Breakdown signal
(NAMUR NE43)
adjustable: 3.59 to 22.5 mA
Power supply failure
• Configuration is retained in the HistoROM (EEPROM).
• Error messages (incl. value of operated hours counter) are stored.
Potential equalization
No special measures for potential equalization are required.
If the device is designed for hazardous areas, observe the information in the documentation
"Safety Instructions" (XA).
Cable entries
Connection of power supply and signal line
To be selected in feature 050 "Electrical connection"
• Gland M20; Material dependent on the approval:
– For Non-Ex, ATEX, IECEx, NEPSI Ex ia/ic:
Plastics M20x1.5 for cable ⌀5 to 10 mm (0.2 to 0.39 in)
– For Dust-Ex, FM IS, CSA IS, CSA GP, Ex nA:
Metal M20x1.5 for cable ⌀7 to 10 mm (0.28 to 0.39 in) 1)
– For Ex d:
No gland available
• Thread
– ½" NPT
– G ½"
– M20 × 1.5
• Plug M12 / Plug 7/8"
Only available for Non-Ex, Ex ic, Ex ia
Connection of remote display FHX50
Dependent on feature 030: "Display, Operation":
• "Prepared for display FHX50 + M12 connection":
M12 socket
• "Prepared for display FHX50 + custom connection":
M16 cable gland
1)
The material of the gland is dependent on the housing type; GT18 (stainless steel housing): 316L (1.4404); GT19 (plastic housing) and GT20
(aluminum housing): nickel-coated brass (CuZn).
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
21
Micropilot FMR62
Cable specification
• Devices without integrated overvoltage protection
Pluggable spring-force terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Devices with integrated overvoltage protection
Screw terminals for wire cross-sections 0.2 to 2.5 mm2 (24 to 14 AWG)
• For ambient temperature TU≥60 °C (140 °F): use cable for temperature TU +20 K.
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept of the
plant.
• For 4-wire devices: Standard device cable is sufficient for the power line.
Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires the use of
overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be ensured by an
integrated or external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as PROFIBUS PA
and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel
2 × 0.5 Ω max.
Threshold DC voltage
400 to 700 V
Threshold impulse voltage
< 800 V
Capacitance at 1 MHz
< 1.5 pF
Nominal arrest impulse voltage (8/20 μs)
10 kA
External overvoltage protection
HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection.
For detailed information please refer to the following documents:
• HAW562: TI01012K
• HAW569: TI01013K
22
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Performance characteristics
Reference operating
conditions
•
•
•
•
•
Maximum measured error
Typical data under reference operating conditions: DIN EN IEC 61298-2 / DIN EN IEC 60770-1;
percentage values in relation to the span.
Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
Humidity = 60 % ±15 %
Reflector: metal plate with diameter ≥ 1 m (40 in)
No major interference reflections inside the signal beam
Device
Value
Output
digital
FMR62
1)
analog 1)
Sum of non-linearity, non-repeatability and hysteresis
±1 mm (0.04 in)
±0.02 %
Offset/Zero
±4 mm (0.2 in)
±0.03 %
Only relevant for 4-20mA current output; add error of the analog value to the digital value
Differing values in near-range applications
∆ [mm (in)]
4 (0.16)
1 (0.04)
-1 (-0.04)
-4 (-0.16)
0.8 (2.62)
D [m (!)]
A0032636
 10
Δ
Measured value resolution
Maximum measured error in near-range applications
Maximum measured error
Reference point of the distance measurement
Distance from reference point of antenna
Dead band according to DIN EN IEC 61298-2 / DIN EN IEC 60770-1:
• Digital: 1 mm
• Analog: 1 µA
Response time
2)
The response time can be configured. The following step response times (in accordance with
DIN EN IEC 61298-2 / DIN EN IEC 60770-1) 2) are when damping is switched off:
Sampling rate
≥1.3 s–1 at UB ≥ 24 V
Response time
< 3.6 s
According to DIN EN IEC 61298-2 / DIN EN IEC 60770-1, the step response time is the time that elapses after an abrupt change in the input
signal until the change in the output signal has adopted 90% of the steady-state value for the first time.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
23
Micropilot FMR62
Influence of ambient
temperature
The measurements are performed according to DIN EN IEC 61298-3 / DIN EN IEC 60770-1
• Digital (HART, PROFIBUS PA, FOUNDATION Fieldbus): average TK = 3 mm/10 K
• Analog (current output):
– Zero point (4 mA): average TK = 0.02 %/10 K
– Span (20 mA): average TK = 0.05 %/10 K
Influence of gas phase
High pressure reduces the speed of propagation of the measuring signals in the gas/vapor above the
medium. This effect depends on the type of gas phase and its temperature. This results in a
systematic measured error that increases with increasing distance between the reference point of
the measurement (flange) and the surface of the product. The following table shows this measured
error for a few typical gases/vapors (with regard to the distance, a positive value means that a too
large distance is measured):
Gas phase
Air/nitrogen
Hydrogen
Water (saturated steam)
Temperature
Pressure
°C
°F
1 bar (14,5 psi)
10 bar (145 psi)
25 bar (362 psi)
20
68
0.00 %
0.22 %
0.58 %
200
392
–0.01 %
0.13 %
0.36 %
400
752
–0.02 %
0.08 %
0.29 %
20
68
–0.01 %
0.10 %
0.25 %
200
392
–0.02 %
0.05 %
0.17 %
400
752
–0.02 %
0.03 %
0.11 %
100
212
0.02 %
180
356
2.1 %
263
505,4
4.15 %
310
590
364
687
With a known, constant pressure, it is possible to compensate for this measured error with a
linearization, for example.
24
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Installation
Installation conditions
Orientation
A0016882
• Recommended distance A wall - nozzle outer edge: ~1/6 of the container diameter. However, the
device must not under any circumstances be mounted closer than 15 cm (5.91 in) to the tank wall.
• Not in the center (2) as interference can cause signal loss.
• Not above the filling curtain (3).
• The use of a weather protection cover (1) is recommended to protect the transmitter from direct
sunlight or rain.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
25
Micropilot FMR62
Internal container fittings
α
A0031777
Avoid the location of internal fittings (limit switches, temperature sensors, struts, vacuum rings,
heating coils, baffles etc.) inside the signal beam. Take into account the beam angle →  27.
26
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Avoiding interference echoes
α
A0031813
Metal orifice plates installed at an angle to scatter the radar signals help prevent interference
echoes.
Optimization options
• Antenna size
The larger the antenna the smaller the beam angle α,resulting in fewer interference echoes
→  27.
• Mapping
Measurement can be optimized by electronically suppressing interference echoes.
Beam angle
α
W= 2 . D . tan_
α
A0031824
 11
Endress+Hauser
Relationship between beam angle α, distance D and beamwidth diameter W
V. 1, Rev. 3, 9-12-2016
27
Micropilot FMR62
The beam angle is defined as the angle α where the energy density of the radar waves reaches half
the value of the maximum energy density (3dB width). Microwaves are also emitted outside the
signal beam and can be reflected off interfering installations.
FMR62
A0032082
A0032081
Antenna
1)
integrated
PEEK, 20
mm / 3/4"
integrated,
PEEK, 40 mm / 1-1/2"
PTFE cladded
flush mount
50 mm / 2"
PTFE cladded
flush mount 80 mm / 3"
15 °
8°
7°
4°
Beam angle α
Distance (D)
1)
Installation: integrated
antenna
Beamwidth diameter W
5 m (16 ft)
1.32 m
(4.33 ft)
0.70 m (2.29 ft)
0.61 m
(2.00 ft)
0.35 m (1.14 ft)
10 m (33 ft)
2.63 m
(8.63 ft)
1.40 m (4.58 ft)
1.22 m
(4.00 ft)
0.70 m (2.29 ft)
15 m (49 ft)
2.09 m (6.87 ft)
1.83 m
(6.01 ft)
1.05 m (3.43 ft)
20 m (66 ft)
2.79 m (9.16 ft)
2.44 m
(8.01 ft)
1.40 m (4.58 ft)
25 m (82 ft)
3.05 m
(10.02 ft)
1.74 m (5.72 ft)
30 m (98 ft)
3.66 m
(12.02 ft)
2.09 m (6.87 ft)
35 m (115 ft)
4.27 m
(14.02 ft)
2.44 m (8.01 ft)
40 m (131 ft)
4.88 m
(16.03 ft)
2.79 m (9.16 ft)
45 m (148 ft)
5.50 m
(18.03 ft)
3.14 m (10.30 ft)
50 m (164 ft)
6.11 m
(20.03 ft)
3.49 m (11.45 ft)
60 m (197 ft)
4.19 m (13.74 ft)
70 m (230 ft)
4.88 m (16.03 ft)
80 m (262 ft)
5.58 m (18.31 ft)
Order code 070
Radial alignment of the antenna
Radial alignment of the antenna is not necessary because the effect of polarization is negligible due
to the narrow beam angle.
Information concerning nozzles
The maximum nozzle length Hmax depends on the nozzle diameter D:
28
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Hmax
Micropilot FMR62
øD
A0032208
Nozzle diameterD
Maximum nozzle height Hmax
40 to 50 mm (1.5 to 2 in)
≤150 mm (6 in)
80 mm (3 in)
≤200 mm (8 in)
100 mm (4 in)
≤300 mm (12 in)
150 mm (6 in)
≤500 mm (20 in)
Note the following if the antenna does not project out of the nozzle:
• The end of the nozzle must be smooth and free from burrs. The edge of the nozzle should be
rounded if possible.
• Mapping must be performed.
• Please contact Endress+Hauser for applications with nozzles that are higher than indicated in
the table.
Information concerning threaded connections
• When screwing in, turn by the hex bolt only.
• Tool: open-ended wrench 50 mm
• Maximum permissible torque: 35 Nm (26 lbf ft)
Installation: flush mount
antenna
Aligning the antenna axis
Radial alignment of the antenna is not necessary because the effect of polarization is negligible due
to the narrow beam angle.
Hmax
Information concerning nozzles
øD
A0032206
Endress+Hauser
Nozzle diameterD
Maximum nozzle height Hmax
50 mm (2 in)
≤150 mm (6 in)
80 mm (3 in)
≤200 mm (8 in)
V. 1, Rev. 3, 9-12-2016
29
Micropilot FMR62
Nozzle diameterD
Maximum nozzle height Hmax
100 mm (4 in)
≤300 mm (12 in)
150 mm (6 in)
≤500 mm (20 in)
Note the following if the antenna does not project out of the nozzle:
• The end of the nozzle must be smooth and free from burrs. The edge of the nozzle should be
rounded if possible.
• Mapping must be performed.
• Please contact Endress+Hauser for applications with nozzles that are higher than indicated in
the table.
Mounting cladded flanges
Note the following for cladded flanges:
• Use the same number of flange screws as the number of flange bores provided.
• Tighten the screws with the necessary torque (see Table).
• Retighten after 24 hours or after the first temperature cycle.
• Depending on the process pressure and temperature, check and retighten the screws, where
necessary, at regular intervals.
The PTFE flange cladding normally acts simultaneously as a seal between the nozzle and the
device flange.
Flange size
Number of screws
Recommended tightening torque [Nm]
Minimum
Maximum
EN
DN50/PN16
45
65
DN80/PN16
40
55
DN100/PN16
40
60
DN150/PN16
75
115
2"/150lbs
40
55
3"/150lbs
65
95
4"/150lbs
45
70
6"/150lbs
85
125
10K 50A
40
60
10K 80A
25
35
10K 100A
35
55
10K 150A
75
115
ASME
JIS
Container with heat
insulation
A0032207
30
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
If process temperatures are high, the device should be included in the usual container insulation
system (2) to prevent the electronics from heating as a result of thermal radiation or convection. The
insulation should not be higher than the neck of the device (1).
Turning the transmitter
housing
To provide easier access to the connection compartment or display module, the transmitter housing
can be turned:
max. 350°
8 mm
8 mm
A0013713
1.
Unscrew the securing screw using an open-ended wrench.
2.
Rotate the housing in the desired direction.
3.
Tighten the securing screw (1,5 Nm for plastics housing; 2,5 Nm for aluminium or stainless
steel housing).
Turning the display module
–
3 mm
A0013905
Endress+Hauser
1.
If present: Loosen the screw of the securing clamp of the electronics compartment cover using
an Allen key and turn the clamp 90° conterclockwise.
2.
Unscrew cover of the electronics compartment from the transmitter housing.
3.
Pull out the display module with a gentle rotation movement.
4.
Rotate the display module into the desired position: Max. 8 × 45 ° in each direction.
5.
Feed the spiral cable into the gap between the housing and main electronics module and plug
the display module into the electronics compartment until it engages.
6.
Screw the cover of the electronics compartment firmly back onto the transmitter housing.
7.
Tighten the securing clamp again using the Allen key (Torque: 2.5 Nm).
V. 1, Rev. 3, 9-12-2016
31
Micropilot FMR62
Environment
Ambient temperature range
Measuring device
–40 to +80 °C (–40 to +176 °F)
Local display
–20 to +70 °C (–4 to +158 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
Outdoor operation in strong sunlight:
• Mount the device in the shade.
• Avoid direct sunlight, particularly in warm climatic regions.
• Use a weather protection cover (see accessories).
The following diagrams only consider functional aspects. Additional restrictions may apply for
certified device versions. See the separate Safety Instructions for more information →  71.
Ambient temperature limits
In the event of temperature (Tp) at the process connection, the permitted ambient temperature (Ta)
is reduced as indicated in the following diagram (temperature derating) in the table header.
FMR62
Antenna 1)
• GE: integrated, PEEK, 3/4"
• GF: integrated, PEEK, 1-1/2"
• GM: PTFE cladded flush mount DN50
• GN: PTFE cladded flush mount DN80
Ta
P1
P2
P3
2)
Seal
• A6: FKM Viton GLT, –40 to 200 °C (–40 to 392 °F)
• C2: FFKM Kalrez, –20 to 200 °C (–4 to 392 °F)
• F6: PTFE cladded, –40 to 200 °C (–40 to 392 °F)
Tp
P5
P4
A0032024
Temperature specifications: °C (°F)
Housing type 3)
P1
P2
P3
P4
P5
Tp
Ta
Tp
Ta
Tp
Ta
Tp
Ta
Tp
Ta
B:
GT18 two-chamber
316L
–40
(–40)
76
(168.8)
76
(168.8)
76
(168.8)
200
(392)
63
(145.4)
200
(392)
–40
(–40)
–40
(–40)
–40
(–40)
A:
GT19 two-chamber
Plastic PBT
–40
(–40)
60 (140) 60 (140) 60 (140)
200
(392)
42
(107.6)
200
(392)
–40
(–40)
–40
(–40)
–40
(–40)
C:
GT20 two-chamber
Aluminum, coated
–40
(–40)
76
(168.8)
200
(392)
68
(154.4)
200
(392)
–40
(–40)
–40
(–40)
–40
(–40)
1)
2)
3)
32
76
(168.8)
76
(168.8)
Feature 070 in the product structure
Feature 090 in the product structure
Feature 040 in the product structure
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
FMR62
Antenna 1)
• GE: integrated, PEEK, 3/4"
• GF: integrated, PEEK, 1-1/2"
• GM: PTFE cladded flush mount DN50
• GN: PTFE cladded flush mount DN80
Ta
P1
P2
P2+
P3
Seal 2)
• A5: FKM Viton GLT, –40 to 150 °C (–40 to 302 °F)
• C1: FFKM Kalrez, –40 to 150 °C (–40 to 302 °F)
• F5: PTFE cladded, –40 to 150 °C (–40 to 302 °F)
Tp
P5
P4
A0032025
Temperature specifications: °C (°F)
Housing type 3)
P1
Tp
B:
GT18 two-chamber
316L
–40
(–40)
A:
GT19 two-chamber
Plastic PBT
–40
(–40)
C:
GT20 two-chamber
Aluminum, coated
–40
(–40)
1)
2)
3)
P2
Ta
Tp
P2+
Ta
Tp
Ta
76
76
76
109
71
(168.8) (168.8) (168.8) (228.2) (159.8)
60
(140)
60
(140)
60
(140)
127
45
(260.6) (113)
76
76
76
112
72
(168.8) (168.8) (168.8) (233.6) (161.6)
P3
P4
P5
Tp
Ta
Tp
Ta
Tp
Ta
150
(302)
47
(116.6)
150
(302)
–40
(–40)
–40
(–40)
–40
(–40)
150
(302)
24
(75.2)
150
(302)
–40
(–40)
–40
(–40)
–40
(–40)
150
(302)
55
(131)
150
(302)
–40
(–40)
–40
(–40)
–40
(–40)
Feature 070 in the product structure
Feature 090 in the product structure
Feature 040 in the product structure
Storage temperature
–40 to +80 °C (–40 to +176 °F)
Climate class
DIN EN 60068-2-38 (test Z/AD)
Altitude according to
IEC61010-1 Ed.3
• Generally up to 2 000 m (6 600 ft) above MSL.
• Above 2 000 m (6 600 ft) if the following conditions are met:
– Ordering feature 020 "Power supply; Output" = A, B, C, E or G (2-wire versions)
– Supply voltage U < 35 V
– Supply voltage of overvoltage category 1
Degree of protection
• With closed housing tested according to:
– IP68, NEMA6P (24 h at 1.83 m under water surface)
– For plastic housing with transparent cover (display module): IP68 (24 h at 1.00 m under water
surface) 3)
– IP66, NEMA4X
• With open housing: IP20, NEMA1
• Display module: IP22, NEMA2
Degree of protection IP68 NEMA6P applies for M12 PROFIBUS PA plugs only when the
PROFIBUS cable is plugged in and is also rated IP68 NEMA6P.
Vibration resistance
DIN EN 60068-2-64 / IEC 60068-2-64: 20 to 2 000 Hz, 1 (m/s2)2/Hz
Cleaning the antenna
The antenna may become contaminated depending on the application. Emission and reception of
microwaves can thus be hindered. The level of contamination leading to an error depends firstly on
the medium and secondly on the reflectivity, mainly determined by the dielectric constant εr.
If the medium tends to cause contamination and buildup, cleaning on a regular basis is
recommended. Care must be taken to ensure the antenna is not damaged in the process of
mechanical or hose-down cleaning. Material compatibility must be taken into account if cleaning
agents are used! The maximum permissible flange temperatures should not be exceeded.
3)
This restriction is valid if the following options of the product structure have been selected at the same time: 030 ("Display, Operation") = C
("SD02") or E ("SD03"); 040 ("Housing") = A ("GT19").
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
33
Micropilot FMR62
Electromagnetic
compatibility (EMC)
Electromagnetic compatibility in accordance with all of the relevant requirements outlined in the
EN 61326 series and NAMUR Recommendation EMC (NE 21). For details, please refer to the
Declaration of Conformity 4).
A normal device cable suffices if only the analog signal should be used. Use a shielded cable for
digital communication (HART/ PA/ FF).
Maximum measured error during EMC testing: < 0.5 % of the span. By way of derogation, for
devices with a plastic housing and see-through lid (integrated display SD02 or SD03) the measured
error can be up to 2 % of the span in the event of strong electromagnetic radiation in the 1 to 2 GHz
frequency range.
4)
34
Available for download at www.de.endress.com.
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Process
Process temperature, process
pressure
The pressure ranges indicated can be reduced by the choice of process connection. The nominal
pressure (PN) indicated on the nameplate refers to a reference temperature of 20 °C, and of
100 °F for ASME flanges. Observe pressure-temperature dependency.
Please refer to the following standards for the pressure values permitted at higher
temperatures:
• EN 1092-1: 2001 Tab. 18
In terms of their stability-temperature property, the materials 1.4435 and 1.4404 are
grouped in EN 1092-1 table 18 under 13E0. The chemical composition of the two materials
can be identical.
• ASME B 16.5a – 1998 Tab. 2-2.2 F316
• ASME B 16.5a – 1998 Tab. 2.3.8 N10276
• JIS B 2220
FMR62, antenna: integrated PEEK, 150°
[bar] ([psi]) p
20 (290)
0 (0)
-1 (-14.5)
-40
(-40)
-20
(-4)
(+32)
+150
(+302)
Tp
[°C]
([°F])
A0032182
 12
Feature 90, seal: A5, FKM Viton GLT
Feature 90, seal: C1, FFKM Kalrez
Feature 90 "Seal"
Process temperature range
A5:
FKM Viton GLT
–40 to +150 °C (–40 to +302 °F)
C1:
FFKM Kalrez
–20 to +150 °C (–4 to +302 °F)
1)
Endress+Hauser
FMR62: Permitted range for process temperature and process pressure of version with integrated
antenna, PEEK, 150° (feature 070)
Process pressure range
prel = –1 to 20 bar (–14.5 to 290 psi) 1)
The pressure range may be further restricted in the event of a CRN approval
V. 1, Rev. 3, 9-12-2016
35
Micropilot FMR62
FMR62, antenna: integrated PEEK, 200°
[bar] ([psi]) p
20 (290)
0 (0)
-1 (-14.5)
-40
(-40)
-20
(-4)
(+32)
+200
(+392)
Tp
[°C]
([°F])
A0032183
 13
FMR62: Permitted range for process temperature and process pressure of version with integrated
antenna, PEEK, 200° (feature 070)
Feature 90, seal: A6, FKM Viton GLT
Feature 90, seal: C2, FFKM Kalrez
Feature 90 "Seal"
Process temperature range
A6:
FKM Viton GLT
–40 to +200 °C (–40 to +392 °F)
C2:
FFKM Kalrez
–20 to +200 °C (–4 to +392 °F)
1)
Process pressure range
prel = –1 to 20 bar (–14.5 to 290 psi) 1)
The pressure range may be further restricted in the event of a CRN approval
FMR62, antenna: PTFE flush mount
[bar] ([psi]) p
25 (362.6)
0 (0)
-1 (-14.5)
-40
(-40)
(+32)
+150
(+302)
+200
(+392)
Tp
[°C]
([°F])
A0032184
 14
Feature 90, seal: F5
Feature 90, seal: F6
Feature 90 "Seal"
Process temperature range
F5:
PTFE cladded
–40 to +150 °C (–40 to +302 °F)
F6:
PTFE cladded
–40 to +200 °C (–40 to +392 °F)
1)
36
FMR62: Permitted range for process temperature and process pressure of version with flush mount PTFE
antenna (feature 070)
Process pressure range
prel = –1 to 25 bar (–14.5 to 362.6 psi) 1)
The pressure range may be further restricted in the event of a CRN approval
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Dielectric constant
• For liquids
εr ≥ 1.9
• For bulk solids
εr ≥ 1.6
For dielectric constants (DC values) of many media commonly used in various industries refer
to:
• the Endress+Hauser DC manual (CP01076F)
• the Endress+Hauser "DC Values App" (available for Android and iOS)
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
37
Micropilot FMR62
Mechanical construction
Dimensions
Dimensions of the electronics housing
R100
98 (3.86)*
90 (3.54)
144 (5.67)
141.9 (5.59)
ø10
ø108.5 (4.27)
115.25 (4.54)
3.5
(4.
07)
78 (3.07)
A0011666
 15
Housing GT18 (316L); Dimensions in mm (in)
*for devices with integrated overvoltage protection.
R100
99.5 (3.92)*
90 (3.54)
144 (5.67)
ø106 (4.17)
134.5 (5.3)
ø10
6 (4
.17
78 (3.07)
A0011346
 16
Housing GT19 (Plastics PBT); Dimensions in mm (in)
*for devices with integrated overvoltage protection.
R100
97 (3.82)*
90 (3.54)
144 (5.67)
141.5 (5.57)
117.1 (4.61)
ø104.5 (4.11)
ø108.5 (4.27)
ø10
3.5
4.0
7)
78 (3.07)
A0020751
 17
Housing GT20 (Alu coated); Dimensions in mm (in)
*for devices with integrated overvoltage protection.
38
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
FMR62, antenna: integrated, PEEK 3/4" and 1-1/2"
ø60 (2.36)
ø60 (2.36)
30 (1.18)
184 (7.24)
22 (0.87)
142 (5.59)
ø32.2 (1.27)
ø23.8 (0.94)
ø54.8 (2.18)
ø42.5 (1.67)
A0031557
 18
Dimensions: mm (in)
Process connection: G3/4 or MNPT3/4 thread
Process connection: G1-1/2 or MNPT1-1/2 thread
Bottom edge of housing
FMR62, sanitary adapter DIN11851, PTFE cladded
L4
L3
L1
L2
øD1
øD2
A0032175
 19
Endress+Hauser
Dimensions: mm (in)
Seal: PTFE cladded, -40 to 150°C/-40 to 302°F
Seal: PTFE cladded, -40 to 200°C/-40 to 392°F
Bottom edge of housing
V. 1, Rev. 3, 9-12-2016
39
Micropilot FMR62
Feature 100 "Process
connection"
øD1
øD2
L1
L2
L3
L4
MRK:
48 mm
DN50 PN25 slotted nut,
(1.89 in)
PTFE>316L
65.5 mm
(2.58 in)
148 mm
(5.83 in)
193 mm
(7.60 in)
5 mm
(0.20 in)
19 mm
(0.75 in)
MTK:
75 mm
DN80 PN25 slotted nut,
(2.95 in)
PTFE>316L
97 mm
(3.82 in)
188 mm
(7.40 in)
233 mm
(9.17 in)
6 mm
(0.24 in)
32 mm
(1.26 in)
FMR62, Tri-Clamp ISO2852, PTFE cladded
1.6 (0.06)
L4
2.6 (0.10)
L1
L2
øD1
øD2
øD3
A0032176
 20
40
Dimensions: mm (in)
Seal: PTFE cladded, -40 to 150°C/-40 to 302°F
Seal: PTFE cladded, -40 to 200°C/-40 to 392°F
Bottom edge of housing
Feature 70 "Antenna"
øD1
L1
L2
L4
GM:
PTFE cladded flush mount DN50
48 mm (1.89 in) 146 mm (5.75 in) 191 mm (7.52 in) 19 mm (0.75 in)
GN:
PTFE cladded flush mount DN80
75 mm (2.95 in) 185 mm (7.28 in) 230 mm (9.06 in) 32 mm (1.26 in)
Feature 100 "Process connection"
øD2
øD3
TDK:
DN40-51 (2")
56.5 mm (2.22 in)
64 mm (2.52 in)
TFK:
DN70-76.1 (3")
83.5 mm (3.29 in)
91 mm (3.58 in)
THK:
DN101.6 (4")
110 mm (4.33 in)
119 mm (4.69 in)
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
FMR62, flange EN1092-1; ASME B16.5; JIS B2220 , PTFE cladded
L4
L3
4 (0.16)
L1
L2
øD1
øD2
øD3
A0032177
 21
Dimensions: mm (in)
Seal: PTFE cladded, -40 to 150°C/-40 to 302°F
Seal: PTFE cladded, -40 to 200°C/-40 to 392°F
Bottom edge of housing
Feature 70 "Antenna"
Endress+Hauser
øD1
L1
L2
L4
GM:
48 mm (1.89 in) 141 mm (5.55 in)
PTFE cladded flush mount DN50
186 mm (7.32 in)
19 mm (0.75 in)
GN:
186.5 mm
75 mm (2.95 in)
PTFE cladded flush mount DN80
(7.34 in)
231.5 mm
(9.11 in)
32 mm (1.26 in)
Feature 100 "Process connection"
øD2
øD3
L3
AFK:
NPS 2" Cl.150, PTFE>316/316L
92 mm (3.62 in)
152 mm (5.98 in)
19.1 mm (0.75 in)
AGK:
NPS 3" Cl.150, PTFE>316/316L
127 mm (5.00 in)
190 mm (7.48 in)
23.9 mm (0.94 in)
AHK:
NPS 4" Cl.150, PTFE>316/316L
158 mm (6.22 in)
229 mm (9.02 in)
23.9 mm (0.94 in)
AJK:
NPS 6" Cl.150, PTFE>316/316L
212 mm (8.35 in)
279 mm (10.98 in)
25.4 mm (1.00 in)
CFK:
DN50 PN10/16, PTFE>316L
102 mm (4.02 in)
165 mm (6.50 in)
18 mm (0.71 in)
CGK:
DN80 PN10/16, PTFE>316L
138 mm (5.43 in)
200 mm (7.87 in)
20 mm (0.79 in)
CHK:
DN100 PN10/16, PTFE>316L
158 mm (6.22 in)
220 mm (8.66 in)
20 mm (0.79 in)
CJK:
DN150 PN10/16, PTFE>316L
212 mm (8.35 in)
285 mm (11.22 in)
22 mm (0.87 in)
KFK:
10K 50A, PTFE>316L
96 mm (3.78 in)
155 mm (6.10 in)
16 mm (0.63 in)
V. 1, Rev. 3, 9-12-2016
41
Micropilot FMR62
Weight
Feature 100 "Process connection"
øD2
øD3
L3
KGK:
10K 80A, PTFE>316L
127 mm (5.00 in)
185 mm (7.28 in)
18 mm (0.71 in)
KHK:
10K 100A, PTFE>316L
151 mm (5.94 in)
210 mm (8.27 in)
18 mm (0.71 in)
KJK:
10K 150A, PTFE>316L
212 mm (8.35 in)
280 mm (11.02 in)
22 mm (0.87 in)
Housing
Part
Weight
GT18 housing - stainless steel
Approx.
4.5 kg (9.9 lb)
GT19 housing - plastic
Approx.
1.2 kg (2.7 lb)
GT20 housing - aluminum
Approx.
1.9 kg (4.2 lb)
Antenna and process connection
Device
FMR62
1)
2)
42
Antenna 1)
Weight of antenna/process connection
GE: integrated, PEEK, 3/4"
Max. 000 kg (000 lb) + flange weight 2)
GE: integrated, PEEK, 1-1/2"
Max. 000 kg (000 lb) + flange weight 2)
GM: PTFE cladded flush mount DN50
Max. 000 kg (000 lb) + flange weight 2)
GN: PTFE cladded flush mount DN80
Max. 000 kg (000 lb) + flange weight 2)
Order code 070
For the flange weight, see Technical Information TI00426F.
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Materials: GT18 housing
(stainless steel, corrosionresistant)
2.1
2.2
5.2
5.1
A0013788
No. Part
Material
CF3M similar to 316L/1.4404
2.1 Cover of the electronics compartment
•
•
•
•
•
2.2 Cover of the terminal compartment
• Cover: CF3M (similar to 316L/1.4404)
• Cover seal: NBR
• Thread-coating: Graphite-based lubricant varnish
Cover lock
• Screw: A4
• Clamp: 316L (1.4404)
Lock at the housing neck
• Screw: A4-70
• Clamp: 316L (1.4404)
Cover: CF3M (similar to 316L/1.4404)
Window: glass
Cover seal: NBR
Seal of the window: NBR
Thread-coating: Graphite-based lubricant varnish
5.1 Dummy plug, cable gland, adapter or plug
(depending on the device version)
• Dummy plug, depending on the device version:
– PE
– PBT-GF
• Cable gland: 316L (1.4404) or nickel-plated brass
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• M12 plug: Nickel-plated brass 1)
• 7/8" plug: 316 (1.4401) 2)
5.2 Dummy plug, cable gland or adapter (depending on
the device version)
•
•
•
•
Dummy plug or M12 socket (depending on the
device version)
• Dummy plug: 316L (1.4404)
• M12 socket: 316L (1.4404)
Pressure relief stopper
316L (1.4404)
Ground terminal
•
•
•
•
Nameplate
• Plate: 316L (1.4404)
• Groove pin: A4 (1.4571)
1)
2)
Endress+Hauser
Housing
Dummy plug: 316L (1.4404)
Cable gland: 316L (1.4404) or nickel-plated brass
Adapter: 316L (1.4404/1.4435)
Seal: EPDM
Screw: A4
Spring washer: A4
Clamp: 316L (1.4404)
Holder: 316L (1.4404)
For the version with M12 plug the sealing material is Viton.
For the version with 7/8" plug, the sealing material is NBR.
V. 1, Rev. 3, 9-12-2016
43
Micropilot FMR62
Materials: GT19 housing
(plastic)
2.1
2.2
5.2
5.1
A0013788
No. Part
Material
PBT
2.1 Cover of the electronics compartment
•
•
•
•
2.2 Cover of the terminal compartment
• Cover: PBT
• Cover seal: EPDM
• Thread-coating: Graphite-based lubricant varnish
• Screw: A4-70
• Clamp: 316L (1.4404)
Lock at the housing neck
Cover glass: PC
Cover frame: PBT-PC
Cover seal: EPDM
Thread-coating: Graphite-based lubricant varnish
5.1 Dummy plug, cable gland, adapter or plug
(depending on the device version)
• Dummy plug, depending on the device version:
– PE
– PBT-GF
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• M12 plug: Nickel-plated brass 1)
• 7/8" plug: 316 (1.4401) 2)
5.2 Dummy plug, cable gland or adapter (depending on
the device version)
• Dummy plug, depending on the device version:
– PE
– PBT-GF
– Nickel-plated steel
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
Dummy plug or M12 socket (depending on the
device version)
• Dummy plug: Nickel-plated brass (CuZn)
• M12 socket: Nickel-plated GD-Zn
Pressure relief stopper
Nickel-plated brass (CuZn)
Ground terminal
•
•
•
•
Adhesive nameplate
Plastic
1)
2)
44
Housing
Screw: A2
Spring washer: A4
Clamp: 304 (1.4301)
Holder: 304 (1.4301)
For the version with M12 plug the sealing material is Viton.
For the version with 7/8" plug, the sealing material is NBR.
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Materials: GT20 housing
(die-cast aluminum, powdercoated, seawater-resistant)
2.1
2.2
5.2
5.1
A0013788
Endress+Hauser
Nr. Part
Material
• Housing: AlSi10Mg(<0,1% Cu)
• Coating: Polyester
Housing, RAL 5012 (blue)
2.1 Cover of the electronics compartment; RAL 7035
(gray)
•
•
•
•
•
Cover: AlSi10Mg(<0,1% Cu)
Window: Glass
Cover seal: NBR
Seal of the window: NBR
Thread-coating: Graphite-based lubricant varnish
2.2 Cover of the terminal compartment; RAL 7035
(gray)
• Cover: AlSi10Mg(<0,1% Cu)
• Cover seal: NBR
• Thread-coating: Graphite-based lubricant varnish
Cover lock
• Screw: A4
• Clamp: 316L (1.4404)
Lock at the housing neck
• Screw: A4-70
• Clamp: 316L (1.4404)
5.1 Dummy plug, cable gland, adapter or plug
(depending on the device version)
• Dummy plug, depending on the device version:
– PE
– PBT-GF
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• M12 plug: Nickel-plated brass 1)
• 7/8" plug: 316 (1.4401) 2)
5.2 Dummy plug, cable gland or adapter (depending on
the device version)
• Dummy plug, depending on the device version:
– PE
– PBT-GF
– Nickel-plated steel
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
Dummy plug or M12 socket (depending on the
device version)
• Dummy plug : Nickel-plated brass (CuZn)
• M12 socket: Nickel-plated GD-Zn
Pressure relief stopper
Nickel-plated brass (CuZn)
V. 1, Rev. 3, 9-12-2016
45
Micropilot FMR62
Nr. Part
Material
Ground terminal
•
•
•
•
Adhesive nameplate
Plastic
1)
2)
Materials: antenna and
process connection
Screw: A2
Spring washer: A2
Clamp: 304 (1.4301)
Holder: 304 (1.4301)
For the version with M12 plug the sealing material is Viton.
For the version with 7/8" plug, the sealing material is NBR.
FMR62, integrated antenna
A0032019
No.
Component part
Material
Antenna
Antenna: PEEK
Antenna seal: Viton (FKM); KALREZ (FFKM)
Antenna adapter
316L / 1.4404
Housing adapter
316L / 1.4404
Housing seal
EPDM
Process connection
316L / 1.4404
Under development
FMR62; antenna cladded, flush mount
A0031815
46
No.
Component part
Material
Antenna
PTFE
Antenna seal: Viton (FKM)
Antenna adapter
316L / 1.4404
Housing adapter
316L / 1.4404
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
No.
Component part
Material
Housing seal
EPDM
Process connection
316L / 1.4404 , PTFE cladded
DIN11851 slotted nut
304L / 1.4307
Under development
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
47
Micropilot FMR62
Materials: Weather
protection cover
A0015473
48
No
Part: Material
Protection cover: 316L (1.4404)
Molded rubber part (4x): EPDM
Clamping screw: 316L (1.4404) + carbon fibre
Bracket: 316L (1.4404)
• Cheese head screw: A4-70
• Nut: A4
• Spring washer: A4
Ground terminal
• Screw: A4
• Spring washer: A4
• Clamp: 316L (1.4404)
• Holder: 316L (1.4404)
• Washer: A4
• Cheese head screw: A4-70
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Operability
Operating concept
Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Operating languages
• English
• Deutsch
• Français
• Español
• Italiano
• Nederlands
• Portuguesa
• Polski
• русский язык (Russian)
• Svenska
• Türkçe
• 中文 (Chinese)
• 日本語 (Japanese)
• 한국어 (Korean)
• Bahasa Indonesia
• tiếng Việt (Vietnamese)
• čeština (Czech)
Feature 500 of the product structure determines which of these languages is preset on delivery.
Quick and save commissioning
• Interactive wizard with graphical interface for easy commissioning via FieldCare/DeviceCare
• Menu guidance with brief explanations of the individual parameter functions
• Standardized operation at the device and in the operating tools
Integrated data storage device (HistoROM)
• Enables transfer of configuration when changing electronic modules
• Records up to 100 event messages in the device
• Records up to 1000 measured values in the device
• Saves the signal curve on commissioning which can later be used as a reference.
Efficient diagnostics increase measurement reliability
• Remedy information is integrated in plain text
• Diverse simulation options and line recorder functions
Local operation
Operation
with
Pushbuttons
Touch Control
Order code for Option C "SD02"
"Display;
Operation"
Option E "SD
A0032219
Display
elements
Endress+Hauser
4-line display
A0032221
4-line display
white background lighting; switches to red in
event of device error
V. 1, Rev. 3, 9-12-2016
49
Micropilot FMR62
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
Operating
elements
local operation with 3 push buttons (, ,
)
external operation via touch control; 3 optical
keys: , , 
Operating elements also accessible in various hazardous areas
Additional
functionality
Data backup function
The device configuration can be saved in the display module.
Data comparison function
The device configuration saved in the display module can be compared to the current device
configuration.
Data transfer function
The transmitter configuration can be transmitted to another device using the display module.
Operation with remote
display and operating
module FHX50
A0013137
 22
Remote operation
FHX50 operating options
Housing of the remote display and operating module FHX50
Display and operating module SD02, push buttons; cover must be removed
Display and operating module SD03, optical keys; can be operated through the glass of the cover
Via HART protocol
A0013764
 23
50
Options for remote operation via HART protocol
PLC (programmable logic controller)
Transmitter power supply unit, e.g. RN221N (with communication resistor)
Connection for Commubox FXA191, FXA195 and Field Communicator 375, 475
Field Communicator 475
Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
Commubox FXA191 (RS232) or FXA195 (USB)
Field Xpert SFX350/SFX370
VIATOR Bluetooth modem with connecting cable
Transmitter
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Via service interface (CDI)
–
A0014019
Endress+Hauser
Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface)
Commubox FXA291
Computer with "FieldCare" operating tool
V. 1, Rev. 3, 9-12-2016
51
Micropilot FMR62
System integration via
Fieldgate
Vendor Managed Inventory
By using Fieldgates to interrogate tank or silo levels remotely, suppliers of raw materials can provide
their regular customers with information about the current supplies at any time and, for example,
account for them in their own production planning. For their part, the Fieldgates monitor the
configured level limits and, if required, automatically activate the next supply. The spectrum of
options here ranges from a simple purchasing requisition via e-mail through to fully automatic order
administration by coupling XML data into the planning systems on both sides.
Remote maintenance of measuring equipment
Fieldgates not only transfer the current measured values, they also alert the responsible standby
personnel, if required, via e-mail or SMS. In the event of an alarm or also when performing routine
checks, service technicians can diagnose and configure connected HART devices remotely. All that is
required for this is the corresponding HART operating tool (e.g. FieldCare, ...) for the connected
device. Fieldgate passes on the information transparently, so that all options for the respective
operating software are available remotely. Some on-site service operations can be avoided by using
remote diagnosis and remote configuration and all others can at least be better planned and
prepared.
ENDRESS+HAUSER
RN 221N
FXN 520
ENDRESS+HAUSER
RN 221N
20...45 VDC
A0011278
 24
The complete measuring system consists of devices and:
Fieldgate FXA520
Multidrop Connector FXN520
The number of instruments which can be connected in mutidrop mode can be calculated by the
"FieldNetCalc" program. A description of this program can be found in Technical Information TI
400F (Multidrop Conncector FXN520). The program is available form your Endress+Hauser
sales organisation or in the internet at: www.de.endress.com/Download (text search =
"Fieldnetcalc").
52
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Certificates and approvals
CE mark
The measuring system meets the legal requirements of the applicable EC guidelines. These are listed
in the corresponding EC Declaration of Conformity together with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
RoHS
The measuring system complies with the substance restrictions of the Restriction on Hazardous
Substances Directive 2011/65/EU (RoHS 2).
RCM-Tick marking
The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0029561
Ex approval
•
•
•
•
•
•
•
•
•
ATEX
IEC Ex
CSA
FM
NEPSI
KC
INMETRO
TIIS
EAC Ex
Additional safety instructions must be followed for use in hazardous areas. Please refer to the
separate "Safety Instructions" (XA) document included in the delivery. Reference to the applicable XA
can be found on the nameplate.
For details on the available certificates and associated XAs: →  71
Dual seal according to
ANSI/ISA 12.27.01
The devices have been designed according to ANSI/ISA 12.27.01 as dual seal devices, allowing the
user to waive the use and save the cost of installing external secondary process seals in the conduit
as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1 (CEC) These
instruments comply with the North-American installation practice and provide a very safe and costsaving installation for pressurized applications with hazardous fluids.
Further information can be found in the Safety Instructions (XA) of the relevant devices.
Functional safety
Use for level monitoring (MIN, MAX, range) up to SIL 3 (homogeneous or diverse redundancy),
independently evaluated by TÜV Rheinland in accordance with IEC 61508, refer to the "Functional
Safety Manual" for information.
WHG
WHG approval: No. requested
Hygienic compatibility
FMR62 with flange cladding made of PTFE complies with FDA 21 CFR 177.1550 and
USP <88> Class VI.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
53
Micropilot FMR62
3A and EHEDG approval for versions with Tri-Clamp and DIN11851 process connections. 5)
To avoid any risk of contamination, install the device according to the “Hygienic Equipment
Design Criteria (HDC)” which was published by the Subgroup "Design Principles" of the EHEDG
on April 8 2004.
Suitable fittings and seals must be used to ensure hygiene-compliant design according to the
specifications of 3-A SSI and EHEDG.
The gap-free connections can be cleaned of all residue using the usual cleaning methods within
this industry.
The 316L housing (GT18), option B in order feature 40, is not suitable for use in applications
which require a 3A approval.
NACE MR 0175 / ISO 15156
• The wetted, metal materials comply with the requirements of NACE MR 0175 / ISO 15156.
• Declaration of Conformity: see the product structure, feature 580, version JB
NACE MR 0103
• The wetted, metal materials comply with the requirements of NACE MR 0103.
• The Declaration of Conformity is based on NACE MR 0175.
The hardness and intergranular corrosion have been tested, and heat treatment (solution
annealed) has been performed. The materials used therefore meet the requirements of
NACE MR 0103.
• Declaration of Conformity: see the product structure, feature 580, version JE.
Pressure equipment with
allowable pressure
≤ 200 bar (2 900 psi)
Pressure instruments with a flange and threaded boss that do not have a pressurized housing do not
fall within the scope of the Pressure Equipment Directive, irrespective of the maximum allowable
pressure.
Reasons:
According to Article 2, point 5 of EU Directive 2014/68/EU, pressure accessories are defined as
"devices with an operational function and having pressure-bearing housings".
If a pressure instrument does not have a pressure-bearing housing (no identifiable pressure chamber
of its own), there is no pressure accessory present within the meaning of the Directive.
Note:
A partial examination shall be performed for pressure instruments that are part of safety equipment
for the protection of a pipe or vessel from exceeding allowable limits (equipment with safety
function in accordance with Pressure Equipment Directive 2014/68/EU, Article 2, point 4).
Marine approval
FMR62
1)
Radio standard
EN 302729-1/2
Marine approval 1)
Device
LF:
ABS marine
approval
LG:
LR marine approval
LH:
BV marine approval
LJ:
DNV GL marine
approval




See order code for 590 "Additional approval"
The devices FMR62 with antenna 40 mm / 2" integrated PEEK, comply with the Level Probing Radar
(LPR) radio standard EN 302729-1/2. The devices FMR62 with antenna 40 mm / 2" integrated
PEEK, are approved for unrestricted use inside and outside closed containers in countries of the EU
and the EFTA . that have already implemented this standard.
The following countries are those that have currently implemented the directive:
Belgium, Bulgaria, Germany, Denmark, Estonia, France, Greece, UK, Ireland, Iceland, Italy,
Liechtenstein, Lithuania, Latvia, Malta, The Netherlands, Norway, Austria, Poland, Portugal,
Romania, Sweden, Switzerland, Slovakia, Spain, Czech Republic and Cyprus.
Implementation is still underway in all of the countries not listed.
5)
54
Authorization pending
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Please note the following for operation of the devices outside of closed vessels:
1.
Installation must be carried out by properly trained, expert staff.
2.
The device antenna must be installed in a fixed location pointing vertically downwards.
3.
The installation site must be located at a distance of 4 km from the astronomy stations listed
below or otherwise approval must be provided by the relevant authority. If the device is
installed at a distance of 4 to 40 km from one of the listed stations, it must not be installed at a
height of more than 15 m (49 ft) above the ground.
Astronomy stations
Country
Name of the station
Latitude
Longitude
Germany
Effelsberg
50°31'32" North
06°53'00" East
Finland
Metsähovi
60°13'04" North
24°23'37" East
Tuorla
60°24'56" North
24°26'31" East
Plateau de Bure
44°38'01" North
05°54'26" East
Floirac
44°50'10" North
00°31'37" West
Cambridge
52°09'59" North
00°02'20" East
Damhall
53°09'22" North
02°32'03" West
Jodrell Bank
53°14'10" North
02°18'26" West
Knockin
52°47'24" North
02°59'45" West
Pickmere
53°17'18" North
02°26'38" West
Medicina
44°31'14" North
11°38'49" East
Noto
36°52'34" North
14°59'21" East
Sardinia
39°29'50" North
09°14'40" East
Poland
Fort Skala Krakow
50°03'18" North
19°49'36" East
Russia
Dmitrov
56°26'00" North
37°27'00" East
Kalyazin
57°13'22" North
37°54'01" East
Pushchino
54°49'00" North
37°40'00" East
Zelenchukskaya
43°49'53" North
41°35'32" East
Sweden
Onsala
57°23'45" North
11°55'35" East
Switzerland
Bleien
47°20'26" North
08°06'44" East
Spain
Yebes
40°31'27" North
03°05'22" West
Robledo
40°25'38" North
04°14'57" West
Penc
47°47'22" North
19°16'53" East
France
Great Britain
Italy
Hungary
As a general rule, the requirements outlined in EN 302729-1/2 must be observed.
Radio standard
EN 302372-1/2
The devices comply with the Tanks Level Probing Radar (TLPR) radio standard EN 302372-1/2 and
are approved for use in closed containers. For installation, points a to f in Annex B of EN 302372-1
must be taken into consideration.
FCC / Industry Canada
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
Canada CNR-Gen Section 7.1.3
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to
the following two conditions: (1) This device may not interference, and (2) this device must accept
any interference, including interference that may cause undesired operation of the device.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
55
Micropilot FMR62
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts
de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas
produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique
subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
[Any] changes or modifications not expressly approved by the party responsible for compliance could
void the user's authority to operate the equipment.
The devices are compliant with the FCC Code of Federal Regulations, CFR 47, Part 15, Sections
15.205, 15.207, 15.209.
In addition, FMR62 with antenna 40 mm / 1-1/2" integrated PEEK is compliant with Section
15.256. For these LPR (Level probe radar) applications the devices must be professionally installed
in a downward operating position. In addition, the devices are not allowed to be mounted in a zone
of 4 km around RAS stations and within a radius of 40 km around RAS stations the maxium
operation height of devices is 15 m (49 ft) above ground.
Japanese radio approval
The devices comply with Japanese Radio Law, Article 6, Section 1(1)
CRN approval
Some device versions have CRN approval. Devices are CRN approved if the following two conditions
are met:
• The device has a CSA approval (product structure: feature 010 "Approval")
• The device has a CRN-approved process connection as per the following table:
Feature 100 in the product structure
1)
Process connection
AFK
NPS 2" Cl.150, PTFE >316/316L
AGK
NPS 3" Cl.150, PTFE >316/316L
AHK
NPS 4" Cl.150, PTFE >316/316L
AJK
NPS 6" Cl.150, PTFE >316/316L
MRK
DIN11851 DN50 PN25 slotted nut, PTFE>316L
MTK
DIN11851 DN80 PN25 slotted nut, PTFE>316L
RGJ
Thread ANSI MNPT1-1/2, 316L
TDK
Tri-Clamp ISO2852 DN40-51 (2"), PTFE>316L, 3A, EHEDG
TFK
Tri-Clamp ISO2852 DN70-76.1 (3"), PTFE>316L, 3A, EHEDG 1)
THK
Tri-Clamp ISO2852 DN101.6 (4"), PTFE>316L, 3A, EHEDG 1)
The CRN certificate applies in a limited pressure range; see the following table.
• Process connections that do not have CRN approval are not listed in this table.
• Please refer to the product structure to discover which process connections are available for a
specific device type.
• CRN-approved devices bear the registration number (tbd.) on the nameplate.
An additional pressure restriction applies for the device versions listed in the table below if they
are CRN-approved. The pressure range indicated in the "Process" section →  35 continues to
apply for device versions not listed in the table below.
Table, in preparation
56
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Test, certificate
Feature 580 "Test,
certificate"
Description
JA
3.1 Material certificate, wetted metal parts, EN10204-3.1 inspection certificate
JB
Declaration of Conformity NACE MR0175, wetted metal parts
JD
3.1 Material certificate, pressurized parts, EN10204-3.1 inspection certificate
JE
Declaration of Conformity NACE MR0103, wetted metal parts
JF
Declaration of Conformity AD2000, wetted metal parts:
Material conformity for all metal wetted/pressurized parts according to AD2000 (data
sheets W2, W9, W10)
JG
Declaration of Conformity AD2000, pressurized metal parts
JJ
Declaration of Conformity FDA
JK
Declaration of Conformity, TSE Certificate of Suitability
JL
Declaration of Conformity EC1935/2004
KE
Pressure test, internal procedure, inspection certificate
KI
PMI test (XRF), internal procedure, inspection certificate
KV
Declaration of Conformity ASME B31.3:
The construction, the material used, the pressure and temperature ranges and the
labeling of the devices meet the requirements of ASME B31.3
Test reports, declarations and inspection certificates are available in electronic format in the
W@M Device Viewer:
Enter the serial number from nameplate (www.endress.com/deviceviewer)
This concerns the options for the following order codes:
• 550 "Calibration"
• 580 "Test, certificate"
• 590 "Additional approval", option LW: "CoC-ASME BPE"
Hard-copy product
documentation
Endress+Hauser
Hard-copy versions of the test reports, declarations and inspection certificates can also be order via
order code 570 "Service", option I7 "Hard-copy product documentation". The documents are then
supplied with the product.
V. 1, Rev. 3, 9-12-2016
57
Micropilot FMR62
Other standards and
guidelines
58
• EN 60529
Degrees of protection provided by enclosures (IP code)
• EN 61010-1
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use
• IEC/EN 61326
"Emission in accordance with Class A requirements". Electromagnetic compatibility (EMC
requirements).
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 107
Status classification as per NE107
• NAMUR NE 131
Requirements for field devices for standard applications.
• IEC61508
Functional safety of safety-related electric/electronic/programmable electronic systems
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Ordering information
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
59
Micropilot FMR62
The following points must be considered if option F3 (3-point linearity protocol) was selected in
feature 550 ("Calibration").
3-point linearity protocol
The 3 points of the linearity protocol are defined as follows:
500 (19.7)
6000 (236)
A0032285
 25
Points of the 3-point linearity protocol; engineering unit: mm (in)
Distance from the reference point R to the first measuring point
Reference point of measurement
First measuring point
Second measuring point (in the middle between the first and third measuring point)
Third measuring point
Measuring point
Position
1st measuring point
• At a distance A from the reference point
• A = length of antenna + 500 mm (19.7 in)
• Minimum distance: Amin = 1 000 mm (39.4 in)
2nd measuring point
In the middle between the 1st and 3rd measuring point
3rd measuring point
6 000 mm (236 in) below the reference point R
The position of the measuring points can vary by ±1 cm (±0.04 in).
The linearity check is performed under reference operating conditions.
60
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
5-point linearity protocol
The following points must be considered if option F4 (5-point linearity protocol) was selected in
feature 550 ("Calibration").
The 5 points of the linearity protocol are evenly distributed over the measuring range (0% - 100%).
Empty calibration (E) and Full calibration (F) must be specified in order to define the measuring
range 6).
The following restrictions must be considered when selecting E and F:
A0032286
Minimum distance between reference point R and
100% mark
Minimum span
Maximum value for "Empty
calibration"
A ≥ length of antenna + 200 mm (8 in)
Minimum value: 400 mm (16 in)
F ≥400 mm (16 in) E ≤24 m (79 ft)
The linearity check is performed under reference operating conditions.
The selected values for Empty calibration and Full calibration are only used to create the
linearity protocol. Afterwards, the values are reset to the default values specific for the
antenna. If values other than the default values are required, they must be ordered as a
customized parameterization →  62.
6)
If (E) and (F) are not specified, antenna-dependent default values will be used instead.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
61
Micropilot FMR62
Customer-specific
configuration
Services
7)
62
If the option IJ: "Customized parameterization HART", IK "Customized parameterization PA" or IL
"Customized parameterization FF" has been selected in feature 570 "Service", presettings that differ
from the default settings can be selected for the following parameters:
Parameters
Communication
protocol
Picklist / range of values
Setup → Unit of length
• HART
• PA
• FF
•
•
•
•
Setup → Empty calibration
• HART
• PA
• FF
max. 70 m (230 ft)
Setup → Full calibration
• HART
• PA
• FF
max. <70 m (230 ft)
Setup → Extended setup → Curr. output 1 or 2 → Damping
HART
0 to 999.9 s
Setup → Extended setup → Curr. output 1 or 2 → Failure
mode
HART
• Min
• Max
• Last valid value
Expert → Comm. → HART config. → Burst mode
HART
• Off
• On
in
ft
mm
The following services can be selected via the product structure in the Product Configurator 7):
• PWIS-free (PWIS = paint-wetting impairment substances)
• Customized parameterization HART →  62
• Customized parameterization PA →  62
• Customized parameterization FF →  62
• W/o tooling DVD (FieldCare)
• Hard-copy product documentation
Feature 570 in the product structure
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Application Packages
Heartbeat Diagnostics
Availability
Available in all device versions.
Function
• Continuous self-monitoring of the device.
• Diagnostic messages output to
– the local display.
– an asset management system (e.g. FieldCare/DeviceCare).
– an automation system (e.g. PLC).
Advantages
• Device condition information is available immediately and processed in time.
• The status signals are classified in accordance with VDI/VDE 2650 and NAMUR recommendation
NE 107 and contain information about the cause of the error and remedial action.
Detailed description
See Operating Instructions of the device (→  71); chapter "Diagnostics and trouble shooting"
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
63
Micropilot FMR62
Heartbeat Verification
Availability
Available for the following options of feature 540 "Application Package":
• EH: Heartbeat Verification + Monitoring
• EJ: Heartbeat Verification
Device functionality checked on demand
•
•
•
•
Verification of the correct functioning of the measuring device within specifications.
The verification result provides information about the condition of the device: Passed or Failed.
The results are documented in a verification report.
The automatically generated report supports the obligation to demonstrate compliance with
internal and external regulations, laws and standards.
• Verification is possible without interrupting the process.
Advantages
• No onsite presence is required to use the function.
• The DTM 8) triggers verification in the device and interprets the results. No specific knowledge is
required on the part of the user.
• The verification report can be used to prove quality measures to a third party.
• Heartbeat Verification can replace other maintenance tasks (e.g. periodic check) or extend the
test intervals.
SIL/WHG-locked devices 9)
• The Heartbeat Verification module contains a wizard for the proof test which must be performed
at appropriate intervals for the following applications:
– SIL (IEC61508/IEC61511)
– WHG (German Water Resources Act)
• To perform a proof test, the device must be locked (SIL/WHG locking).
• The wizard can be used via FieldCare, DeviceCare or a DTM-based process control system.
In the case of SIL-locked and WHG-locked devices, it is not possible to perform verification
without additional measures (e.g. by-passing of the output current) because the output current
must be simulated (Increased safety mode) or the level must be approached manually (Expert
mode) during subsequent re-locking (SIL/WHG locking).
Detailed description
SD01870F
8)
9)
64
DTM: Device Type Manager; controls device operation via DeviceCare, FieldCare or a DTM-based process control system.
Only relevant for devices with SIL or WHG approval: order code 590 ("Additional approval"), option LA ("SIL") or LC ("WHG").
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Heartbeat Monitoring
Availability
Available for the following options of feature 540 "Application Package":
EH: Heartbeat Verification + Monitoring
Function
• In addition to the verification parameters, the corresponding parameter values are also logged.
• Existing measured variables, such as the echo amplitude, are used in the Foam detection and
Build-up detection wizards.
The Foam detection and Build-up detection wizards cannot be used together.
"Foam detection" wizard
• The Heartbeat Monitoring module contains the Foam detection wizard.
• This wizard is used to configure automatic foam detection, which detects foam on the product
surface on the basis of the reduced signal amplitude. Foam detection can be linked to a switch
output in order to control a sprinkler system, for example, which dissolves the foam.
• This wizard can be used via FieldCare, DeviceCare or a DTM-based process control system.
"Build-up detection" wizard
• The Heartbeat Monitoring module contains the Build-up detection wizard.
• The wizard is used to configure automatic buildup detection, which detects the buildup of deposits
on the antenna on the basis of the increased area of the coupling signal. Buildup detection can be
linked to a switch output in order to control a compressed air system, for example, to clean the
antenna.
• This wizard can be used via FieldCare, DeviceCare or a DTM-based process control system.
Advantages
• Early detection of changes (trends) to ensure plant availability and product quality.
• Use of information for the proactive planning of measures (e.g. cleaning/maintenance).
• Identification of undesirable process conditions as the basis to optimizing the facility and the
processes.
• Automated control of measures to remove foam or buildup.
Detailed description
SD01870F
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
65
Micropilot FMR62
Accessories
Device-specific accessories
Accessory
Weather protection cover
Description
222 (8.74)
Weather protection cover
A0015466
298.5 (11.8)
255.1 (10)
273.7 (10.8)
164 (6.46)
35°
(6.1
156
65°
4)
°
55
A0015472
 26
Weather protection cover; Dimensions: mm (in)
37,8 mm (1,5 in)
54 mm (2,1 in)
weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory
 The
Enclosed", option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71162242.
66
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Remote display FHX50
Accessories
Description
Remote display FHX50
1.
2.
3.
4.
A0019128
• Material:
– Plastic PBT
– 316L/1.4404
• Degree of protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for display modules:
– SD02 (push buttons)
– SD03 (touch control)
• Connecting cable:
– Cable supplied with device up to 30 m (98 ft)
– Standard cable supplied by customer up to 60 m (196 ft)
• Ambient temperature range: –40 to 80 °C (–40 to 176 °F)
display should be used, order the device version "Prepared for display FHX50" (feature 030, version
 • IfL ortheM).remote
For the FHX50, you must select option A: "Prepared for display FHX50" under feature 050 "Measuring
device version".
• If the device version "Prepared for display FHX50" was not originally ordered and a FHX50 display is to be
retrofitted, you must select version B "Not prepared for display FHX50" under feature 050: "Measuring device
version" when ordering the FHX50. In this case, a retrofit kit for the device is supplied with the FHX50. The kit
can be used to prepare the device so that the FHX50 can be used.
of the FHX50 may be restricted for transmitters with an approval. A device can only be retrofitted with the
 Use
FHX50 if the option L or M ("Prepared for FHX50") is listed under Basic specifications, item 4 "Display, operation" in
the Safety Instructions (XA) for the device.
Also pay attention to the Safety Instructions (XA) of the FHX50.
is not possible on transmitters with:
 Retrofitting
• An approval for use in areas with flammable dust (dust ignition-proof approval)
• Ex nA type of protection
 For details, see document SD01007F.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
67
Micropilot FMR62
Overvoltage protection
Accessory
Description
Overvoltage protection for
2-wire-devices
OVP10 (1 channel)
OVP20 (2 channel)
A0021734
Technical data
• Resistance per channel: 2 * 0.5 Ωmax
• Threshold DC voltage: 400 to 700 V
• Threshold impulse voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal arrest impulse voltage (8/20 μs): 10 kA
• Suited for wire cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
with device
 Ordering
The overvoltage protection module is preferably ordered with the device. See product structure, feature 610
"Accessory mounted", option NA "Overvoltage protection". Separate ordering of the module is only necessary if a
device is to retrofitted with the overvoltage protection.
code for retrofitting
 Order
• For 1-channel devices (feature 020, option A)
OVP10: 71128617
• For 2-channel devices (feature 020, option B, C, E or G)
OVP20 : 71128619
Hosuing lid for retrofitting
In order to keep the necessary safety distances, the housing lid needs to be replaced if the device is retrofitted with
the overvoltage protection. Depending on the housing type, the order code of the suitable lid is as follows:
• GT18 housing: Lid 71185516
• GT19 housing: Lid 71185518
• GT20 housing: Lid 71185516
for retrofitting
 Restrictions
Depending on the approval of the transmitter the usage of the OVP module may be restricted. A device may only be
retrofitted with an OVP module if the option NA (overvoltage protection) is quoted unter Optional Specifications in
the Safety Instructions (XA) pertaining to the device.
 For details refer to SD01090F.
Gas-tight feedthrough
Accessories
Description
Gas-tight feedthrough
Chemically inert glass feedthrough; prevents gases from entering the electronics housing
To order with the device: product structure, feature 610 "Accessory mounted", option NC "Gas-tight feedthrough"
68
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Communication-specific
accessories
Accessory
Description
Commubox FXA195
HART
For intrinsically safe HART communication with FieldCare via the USB interface.
Accessory
Description
Commubox FXA291
Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser
Common Data Interface) to the USB interface of a computer.
Order code: 51516983
 For details refer to Technical Information TI00404F
 For details refer to Technical Information TI00405C
Accessory
Description
HART Loop Converter
HMX50
Evaluates the dynamic HART variables and converts them to analog current signals
or limit values.
Order code: 71063562
details refer to Technical Information TI00429F and Operating
 For
Instructions BA00371F
Accessory
Description
WirelessHART Adapter
SWA70
Connects field devices to a WirelessHART network.
The WirelessHART adapter can be mounted directly at a HART device and is easly
integrated into an existing HART network. It ensures safe data transmission and
can be operated in parallel with other wireless networks.
 For details refer to Operating Instructions BA00061S
Accessory
Description
Fieldgate FXA320
Gateway for remote monitoring of connected 4-20mA measuring devices via web
browser.
details refer to Technical Information TI00025S and Operating
 For
Instructions BA00053S
Accessory
Description
Fieldgate FXA520
Gateway for remote diagnosis and parametrization of connected HART measuring
devices via web browser.
details refer to Technical Information TI00025S and Operating
 For
Instructions BA00051S
Accessory
Description
Field Xpert SFX350
Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area.
 For details, see Operating Instructions BA01202S
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
69
Micropilot FMR62
Accessory
Description
Field Xpert SFX370
Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area and the Ex area.
 For details, see Operating Instructions BA01202S
Service-specific accessories
Accessory
Description
FieldCare / DeviceCare
Endress+Hauser's FDT-based Plant Asset Management tool.
Helps to configure and maintain all field devices of your plant. By supplying status
information it also supports the diagnosis of the devices.
 For details refer to Operating Instructions BA00027S and BA00059S.
System components
Accessory
Description
Graphic Data Manager
Memograph M
The graphic data manager Memograph M provides information on all the relevant
process variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on an SD card or USB stick.
details refer to Technical Information TI00133R and Operating
 For
Instructions BA00247R
RN221N
Active barrier with power supply for safe separation of 4 to 20 mA current circuits.
Provides bi-directional HART transmission.
details refer to Technical Information TI00073R and Operating
 For
Instructions BA00202R
RNS221
Transmitter supply for 2-wire sensors or transmitters exclusively for non-Ex areas.
Provides bi-directional communication using the HART communication sockets.
details refer to Technical Information TI00081R and Operating
 For
Instructions KA00110R
70
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
Supplementary documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer: enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2-D matrix code (QR code) on the nameplate.
The following document types are available:
In the Download Area of the Endress+Hauser Internet site: www.endress.com → Downloads
Standard documentation
Micropilot FMR62
Correlation of documentations to the device:
Device
Power supply, Communication
output
Document type
Document code
FMR62
A, B, C, K, L
Operating Instructions
BA01619F
Brief Operating Instructions
KA01252F
Description of device
parameters
GP01101F
Operating Instructions
* 1)
Brief Operating Instructions
Description of device
parameters
Operating Instructions
Brief Operating Instructions
Description of device
parameters
1)
Safety Instructions (XA)
Feature 010
HART
PROFIBUS PA
FOUNDATION Fieldbus
In preparation
Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They
are an integral part of the Operating Instructions.
Approval
Feature 020 "Power Supply; Output"
1)
B 2)
C 3)
E 4)/G 5)
K 6)/L 7)
BA
ATEX II G Ex ia IIC T6-T1 Ga
XA01549F
XA01549F
XA01549F
XA01557F
* 8)
BB
ATEX II 1/2G Ex ia IIC T6 Ga/Gb
XA01549F
XA01549F
XA01549F
XA01557F
* 8)
BC
ATEX II 1/2G Ex d [ia] IIC T6 Ga/Gb
XA01552F
XA01552F
XA01552F
XA01560F
XA01552F
8)
* 8)
ATEX II 1/2/3G Ex ic [ia Ga] IIC T6 Ga/Gb/Gc
XA01558F
BG
ATEX II 3G Ex nA IIC T6 Gc
XA01551F
XA01551F
XA01551F
XA01559F
XA01551F
BH
ATEX II 3G Ex ic IIC T6 Gc
XA01551F
XA01551F
XA01551F
XA01559F
XA01551F
8)
8)
BD
8)
8)
8)
* 8)
BL
ATEX II 1/2/3G Ex nA [ia Ga] IIC T6 Ga/Gb/Gc
XA01558F
B2
ATEX II 1/2G Ex ia IIC T6 Ga/Gb, 1/2D Ex ia IIIC Da/Db
XA01555F
XA01555F
XA01555F
XA01563F
* 8)
B3
ATEX II 1/2G Ex d [ia] IIC T6 Ga/Gb, 1/2 D Ex ta IIIC Da/Db
XA01556F
XA01556F
XA01556F
XA01564F
XA01556F
B4
ATEX II 1/2G Ex ia IIC T6 Ga/Gb, Ex d[ia] IIC T6 Ga/Gb
XA01553F
XA01553F
XA01553F
XA01561F
* 8)
CD
CSA C/US DIP Cl.II,III Div.1 Gr.E-G
* 8)
* 8)
* 8)
* 8)
* 8)
C2
CSA C/US IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 Div.2, Ex ia
* 8)
* 8)
* 8)
* 8)
* 8)
C3
CSA C/US XP Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 Div.2, Ex d
* 8)
* 8)
* 8)
* 8)
* 8)
FB
FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia, NI Cl.1 Div.2
* 8)
* 8)
* 8)
* 8)
* 8)
FD
FM XP Cl.I,II,III Div.1 Gr.A-G, AEx d, NI Cl.1 Div.2
* 8)
* 8)
* 8)
* 8)
* 8)
FE
FM DIP Cl.II,III Div.1 Gr.E-G
* 8)
* 8)
* 8)
* 8)
* 8)
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
71
Micropilot FMR62
Feature 010
Approval
Feature 020 "Power Supply; Output"
1)
2)
3)
4)
5)
6)
7)
8)
1)
B 2)
C 3)
E 4)/G 5)
K 6)/L 7)
IA
IEC Ex ia IIC T6 Ga
XA01549F
XA01549F
XA01549F
XA01557F
* 8)
IB
IEC Ex ia IIC T6 Ga/Gb
XA01549F
XA01549F
XA01549F
XA01557F
* 8)
IC
IEC Ex d[ia] IIC T6 Ga/Gb
XA01552F
XA01552F
XA01552F
XA01560F
XA01552F
ID
IEC Ex ic[ia Ga] IIC T6 Ga/Gb/Gc
* 8)
* 8)
* 8)
* 8)
* 8)
IG
IEC Ex nA IIC T6 Gc
XA01551F
XA01551F
XA01551F
XA01559F
XA01551F
IH
IEC Ex ic IIC T6 Gc
XA01551F
XA01551F
XA01551F
XA01559F
XA01551F
8)
8)
8)
8)
IL
IEC Ex nA[ia Ga] IIC T6 Ga/Gb/Gc
I2
IEC Ex ia IIC T6 Ga/Gb, Ex ia IIIC Da/Db
XA01555F
XA01555F
XA01555F
XA01563F
* 8)
I3
IEC Ex d[ia] IIC T6 Ga/Gb, Ex ta IIIC Da/Db
XA01556F
XA01556F
XA01556F
XA01564F
XA01556F
I4
IEC Ex ia IIC T6 Ga/Gb, Ex d[ia] IIC T6 Ga/Gb
XA01553F
XA01553F
XA01553F
XA01561F
* 8)
KA
KC Ex ia IIC T6 Ga
* 8)
* 8)
* 8)
* 8)
* 8)
KB
KC Ex ia IIC T6 Ga/Gb
* 8)
* 8)
* 8)
* 8)
* 8)
KC
KC Ex d[ia] IIC T6 Ga/Gb
* 8)
* 8)
* 8)
* 8)
* 8)
MA
INMETRO Ex ia IIC T6 Ga
* 8)
* 8)
* 8)
* 8)
* 8)
MC
INMETRO Ex d[ia] IIC T6 Ga/Gb
* 8)
* 8)
* 8)
* 8)
* 8)
MH
INMETRO Ex ic IIC T6 Gc
* 8)
* 8)
* 8)
* 8)
* 8)
NA
NEPSI Ex ia IIC T6 Ga
* 8)
* 8)
* 8)
* 8)
* 8)
NB
NEPSI Ex ia IIC T6 Ga/Gb
* 8)
* 8)
* 8)
* 8)
* 8)
NC
NEPSI Ex d[ia] IIC T6 Ga/Gb
* 8)
* 8)
* 8)
* 8)
* 8)
NG
NEPSI Ex nA II T6 Gc
* 8)
* 8)
* 8)
* 8)
* 8)
NH
NEPSI Ex ic IIC T6 Gc
* 8)
* 8)
* 8)
* 8)
* 8)
N2
NEPSI Ex ia IIC T6 Ga/Gb, Ex iaD 20/21 T85…90oC
* 8)
* 8)
* 8)
* 8)
* 8)
N3
NEPSI Ex d[ia] IIC T6 Ga/Gb, DIP A20/21 T85…90oC IP66
* 8)
* 8)
* 8)
* 8)
* 8)
8A
FM/CSA IS+XP Cl.I,II,III Div.1 Gr.A-G
* 8)
* 8)
* 8)
* 8)
* 8)
2-wire; 4-20mA HART
2-wire; 4-20mA HART, switch output
2-wire; 4-20mA HART, 4-20mA
2-wire; FOUNDATION Fieldbus, switch output
2-wire; PROFIBUS PA, switch output
4-wire 90-253VAC; 4-20mA HART
4-wire 10.4-48VDC; 4-20mA HART
In preparation
The nameplate indicates the Safety Instructions (XA) that are relevant to the device.
72
V. 1, Rev. 3, 9-12-2016
Endress+Hauser
Micropilot FMR62
If the device is prepared for the remote display FHX50 (product structure: feature 030: Display,
Operation", option L or M), the Ex marking of some certificates changes according to the following
table 10):
Feature 010
("Approval")
Feature 030
("Display,
Operation")
Ex marking
B3
L 1)
II 1/2 G Ex db [ia] IIC T6 Ga/Gb, II 1/2 D Ex ta [ia Db] IIIC Txx°C
Da/Db
I3
L 2)
Ex db [ia] IIC T6 Ga/Gb, Ex ta [ia Db] IIIC Txx°C Da/Db
1)
2)
10)
4-wire 10.4-48VDC; 4-20mA HART
4-wire 10.4-48VDC; 4-20mA HART
The marking of certificates not mentioned in this table are not affected by the FHX50.
Endress+Hauser
V. 1, Rev. 3, 9-12-2016
73
www.addresses.endress.com

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : Yes
Author                          : 00
Create Date                     : 2016:12:09 14:59:41+01:00
Keywords                        : Technical, Information;, Micropilot, FMR62;, Free, space, radar
Modify Date                     : 2016:12:09 15:03:16+01:00
Subject                         : Free space radar
Has XFA                         : No
Language                        : EN
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Format                          : application/pdf
Creator                         : 00
Description                     : Free space radar
Title                           : Micropilot FMR62
Creator Tool                    : AH XSL Formatter V5.3 MR5 for Windows (x64) : 5.3.6.0 (2012/12/04 12:44:48)
Metadata Date                   : 2016:12:09 15:03:16+01:00
Producer                        : Antenna House PDF Output Library 2.6.0 (Windows (x64))
Trapped                         : False
Document ID                     : uuid:fe847203-3051-418f-8bab-f63674245a69
Instance ID                     : uuid:1b47c79e-e8fd-454a-8b07-430a06ecf505
Page Mode                       : UseOutlines
Page Count                      : 76
EXIF Metadata provided by EXIF.tools
FCC ID Filing: LCGFMR6XE

Navigation menu