FUNCTION
LED SETTING
LED FUNCTION DESCRIPTION DEFAULT
SETTING for
CADET
0 0 to F 0 = slowest
F = fastest
OPENING SPEED A
1 0 to 5 0 = slowest
5 = fastest
BACK CHECK SPEED 1
2 0 to 5 0 = slowest
5 = fastest
LATCH SPEED 5
3 0 to 9 0 = slowest
9 = fastest
HOLD SPEED 2
4 1 = 2sec 6 = 12sec b = 22sec
2 = 4sec 7 = 14sec C = 24sec
3 = 6sec 8 = 16sec d = 26sec
4 = 8sec 9 = 18sec E = 28ec
5 = 10sec A = 20sec F = 30sec
ACTIVATION TIME
The time that the door remains open, starting when the
activation trigger goes OFF. 1 to 30 sec
4
5 0 = 2 sec 4 = 10 sec
1 = 4 sec 5 = 12 sec
2 = 6 sec 6 = 14 sec
3 = 8 sec 7 = 16 sec
DELAY ON OPERATE
The time delay before operating the door, starting when
activation2 trigger goes ON. 2 to 16sec - This is valid when
Setting A1 has the LED OFF.
1
6 0 = Instant trigger - extremely sensitive
1 = 1/8 sec - very sensitive
2 = 1/4 sec
3 = 3/8 sec - mid range sensitivity
4 = 1/2 sec
5 = 5/8 sec - not sensitive
PUSH AND GO SENSITIVITY
The amount of time that a push and go trigger must be
sensed before the door is triggered. A longer time makes the
door less sensitive to a push and go.
3
7 1 = 1sec 6 = 6sec b =
12sec
2 = 2sec 7 = 7sec C =
14sec
3 = 3sec 8 = 8sec d = 15sec
4 = 4sec 9 = 9sec E = 25ec
5 = 5sec A = 10sec F = 30sec
PUSH AND GO ACTIVATION TIME
The time that the door remains open starting when the Push
and Go input is triggered.
5
8 0 = 0sec
1 = .50sec
2 = 1.00sec
3 = 1.50sec
4 = 2.00sec
SAFETY 1 INHIBIT
The time that a safety1 input is ignored (inhibited), starting
when the door goes into Latch.
0 to 2 sec
0
9 0 = 0.125sec 4 = 1.50sec
1 = 0.25sec 5 = 2.00sec
2 = 0.50sec
3 = 1.00sec
STRIKE DELAY
The time between Strike ON and door starting to open. HA
board ONLY
0
CODE INDICATION ON/OFF LED = ON ON/OFF LED = OFF DEFAULT
SETTING
FUNCTION
LED SETTING LED
A 0 Safety 2 OFF at back check. Safety2 always active LED OFF
A 1 ACT N1 is connected to a push button
switch and always opens the door. ACT N2
is connected to the door and is only active
after ACT’N1 is pressed and before the door
closes and gets to the Latch point.
Activation input 1 (ACT N1) works
as an instant activation. Activation
input 2 (ACT N2) works as a
delayed activation (delay time
programmed through Function 5
.)
LED OFF
ACT N1 = instant
and
ACT N2 = delayed
activation
A 2 Lockout ON during closing Safety1 is
active if the door stops moving (from hitting
an obstruction for example). If door is moving
then Safety1 is NOT active.
Lockout OFF
Safety1 is always active
LED ON
Lockout ON
A 3
Push and Go is active. Push and Go will only
work with a door that DOES NOT have a
clutch.
Push and Go disabled LED OFF Push and
Go Disabled
A 4 In process of reading out
# of door opening
cycles
No readout LED OFF no
readout
To obtain the number of opening cycles that the door has gone through press the set button while in the Function A, Setting 4
mode. Example: Readout of 3 2 (pause) 7 0 = 3,270 door cycles
A 5 Safety1 sensor mounted on closing side of
door.
Safety1 sensor mounted overhead. LED OFF Safety1
mounted Overhead.
A5
LED OFF
(Overhead
Sensor)
Door Opening - Safety1 sensor has no effect
Door Fully Open - Safety1 sensor ON = door will not close
Door Closing - A2 setting ON. Door moving = Safety1 has no effect (door will open)
- A2 setting ON. Door stopped, Safety1 ON = door will not open
- A2 setting OFF. Safety1 ON = door will not open
Door Fully Closed - Safety1 sensor ON = door will not open
A5
LED ON
(Door mounted
Sensor)
Door Opening - Safety1 sensor has no effect
Door Fully Open - Safety1 sensor ON = door will not close
Door Closing - Safety1 sensor ON = door drives at HOLD speed
Door Fully Closed - Safety1 sensor has no effect
CODE INDICATION ON/OFF LED = ON ON/OFF LED = OFF DEFAULT
SETTING
FUNCTION
LED
SETTING LED
A 6 Safety1 sensor is a Normally Closed input
(N.C.)
Safety1 sensor is a Normally Open
input (N.O.)
LED OFF Safety1
is Normally Open
A 7 Safety2 independent of Activation 1
Safety2 is ON = door holds
Safety2 is OFF = door opens
Safety2 works with Act’n1.
For Safety2 AND Act’n1 both ON =
door holds.
If Safety2 goes OFF = door opens
If Act’n1 goes OFF = door closes.
LED OFF
Safety2 works with
Act’n1.
A 8 Fire door mode for California. Manually pulling
the door closed while it is fully open will close
the door ignoring all activation triggers including
Hold Open. Turning to OFF resets this mode.
See note1
Door will not shut when manually
pulled closed.
LED OFF
note1: When setting up Code A8 it is important to 1. Turn the overload all the way down (counter clock wise on the Potentiometer
)
and 2. To make sure that the Back Check speed is slow enough that it will not trigger the overload while the door is fully open.
PROBLEM
POSSIBLE SOLUTION
Programming function does not work.
1. Is there an ON/OFF switch connected? A switch must be connected from the
ON terminal pin to the OFF terminal pin for programming to work.
2. Slide switch must be moved to PROG for programming options to be modified.
Door does not open after being
triggered.
1. Is power connected and ON? (7 segment LEDs will light with power ON)
2. Is program/run switch in the Arun@ mode? (switch should be down)
3. Which activation situation is selected? See setting A1 - If LED is ON for program
setting A1, the Activation input 2 will only activate the door while it is closing and
has not reached Latch.
4. Is there an ON/OFF switch connected? A switch must be connected from the
ON terminal pin to the OFF terminal pin for the doors to open.
Door does not open if triggered
immediately after going into Latch.
1. Increase the Safety1 inhibit time. See Setting 9.
Push and Go function does not work.
2. Is operator equipped for Push and Go? Only an operator WITHOUT a clutch will
work for push and go. Operators with a clutch cannot provide push and go.
3. Is Push and Go function enabled? See setting A3
4. Reduce push and go sensitivity. See setting 6
Door does not delay when triggered
even when a delayed time has been
set up.
1. Which activation situation is selected? See setting A1 - If LED is ON for program
setting A1 this is a special activation situation and there is no delay
1. Only Activation Trigger 2 input (ACT=N 2) will provide a delay on opening.
Activation Trigger 1 input (and the push button on the board) will ALWAYS give
an instant trigger regardless of how the time delay has been set up
Door opens slowly
1. Check to see that the Back Check and latching magnets are adjusted properly
2. Increase the opening speed Function 0
Door will not open
My door will not close
1. Remove any obstacle from in front of the door, which is activating the sensor,
thus keeping the door open.
2. Make sure the 3 position switch (I 0 II) is set to automatic mode (I)