ETA-ECM20 & ETA-ECM20M
Electrical Control Module 20A Power Conditioner

ETA-ECM20 & ETA-ECM20M
Electrical Control Module 20A Power Conditioner

1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435

	

– 1 –	
Specifications are subject to change without notice.

ETAsys.com

ETA-ECM20 & ETA-ECM20M
Electrical Control Module 20A Power Conditioner
INTRODUCTION
Thank you for purchasing the ETA Systems Electrical Control Module Raceway system. This information sheet is an overview of the
ETA-ECM20 and ETA-ECM20M control modules. Note: For your safety all electrical wiring must be done by a qualified electrician.
The ETA Systems ETA-ECM20 and ETA-ECM20M are an Electrical Control Module (ECM) 20A Power Conditioner and AC Spike
Suppressor that are designed to be used as a standalone unit or in conjunction with an ETA-ECS6RM Controller up to 1000 ft away.
The ETA-ECM20 and ETA-ECM20M are designed to be used with the ETA-RACEWY6 which can house up to 6 modules. Single
housing models (ETA-20SH and ETA-15SH) are also available. AC Spikes, or Transients, are commonly caused by utility power plant
grid switchovers. The amount of energy that can be injected into the power system can be immense with voltages reaching 6kV
or amperage peaks of 3000A. These spikes are very fast and usually only last for a very short period of time. To protect against this
potential problem, incoming AC Mains have special suppression circuitry to eliminate the unwanted energy. This circuitry is very fast
and can suppress unwanted energy within a nanosecond, while sustaining the suppression for up to 2 milliseconds, thus ensuring
virtually trouble free protection. High and low AC Main line voltages are another major contributor to equipment failures. The ECM
modules support EVS circuitry which enables the module to be shut off during extreme Low and High AC Line conditions.
The ETA-ECM20M features noise filtering for unwanted Radio Frequency Interference (RFI) and Electromagnetic Interference (EMI)
filters to reduce noise from such items as electric motors and switching power supplies. The benefit of these filters can be seen on
video products or audibly by reducing static pops and external signal interference.
High line can also be known as surges. Surges usually are a slower steady state rise in voltages ranging from 128VAC and up. They can
be caused from fluctuations from the utility company's power lines or industrial equipment turning ON and OFF, and are on the same
power leg of the building's incoming AC.
Low line is also known as brownouts. This happens when the AC Mains drops below 107VAC. Most of the time it is caused by the
utility company not being able to supply enough power during heavy utility consumption time periods, such as heat waves. Another
factor can be from voltage drops in AC lines due to long transmissions. The ETA-ECS6RM will inform you if any of these conditions
occur. Extreme variances in Unstable AC Mains voltage are one of the main reasons for equipment failure.
The ETA-ECM20 does not support the same current monitoring or EMI/RFI Filter features as the ETA-ECM20M, ETA-20SH and the
ETA-15SH models. However, it does support AC spike and surge suppression, AC mains voltage monitoring, EVS circuitry, and remote
activation.

ECM MODULES KEY FEATURES
	 •	 Manual/Auto ON/OFF switch
	 •	 Incoming AC present LED
	 •	 Active LED
	 •	 AC Fault LED (ETA-ECM20M Only)
	 •	 Clamping Spike & Surge Suppression EVS Circuitry
	 •	 AC Mains Voltage & Current monitoring (Voltage only for ETA-ECM20)
	 •	 EMI & RFI Filtering (ETA-ECM20M Only)

APPLICATIONS
	 •	 Restaurants
	 •	 Houses of Worship
	 •	 Schools
	 •	 Home Theaters
	 •	 Office Buildings
	 •	 Sports Bars
	 •	 Industrial Facilities

1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435

	

– 2 –	
Specifications are subject to change without notice.

ETAsys.com

ETA-ECM20 & ETA-ECM20M
Electrical Control Module 20A Power Conditioner

6

4
1
3

6

4
1
3
5

2

2

MODULE PANEL FEATURES

WIRING THE ETA-ECM20M MODULE

1. Trigger / Status Port Pin Identification – All signals are of 	
	 low voltage and current. DO NOT MISWIRE or damage may 	
	 occur.

The ETA-ECM20M is designed to be mated with the
ETA-RACEWY6 housing and the ETA-ECS6RM controller. The
specific job install AC power requirements and power distribution
layout will dictate how the ETA-ECM20M modules are wired into
the ETA-RACEWY6. Each ECM Module can be wired as a single
20A run or in a parallel configuration as illustrated below. Each
ECM module has dual 3-position screw terminal blocks that are in
parallel and are clearly labeled as follows:
E - Green = Ground
L - Black = Load
N - White = Neutral

	 +	 Requires 5 -24VDC to activate the module with 5mA of
current. Note: The DCV can be supplied from any source.
The EVS protection requires the ETA-ECS6RM for operation.
	 G	Circuit Ground, Must be of the same circuit as the DCV
source.
	 V	AC Voltage Status Signal, this signal reports back to the
ETA-ECS6RM the Incoming AC Mains Voltage to the ECM
module.
	 A	AC Current Status Signal, this signal reports back to the
ETA-ECS6RM the AC Mains Current draw at the ECM
module. Note: Not available on ETA-ECM20 type module.
	 D	Fault Status Signal, reports to the ETA-ECS6RM fault
conditions of an ECM module.
2. External Trigger / Manual On Switch – The ETA-ECM20M 	
	 has a manual override switch allowing it to be used as a local 	
	 Power Conditioner and Surge Suppressor. For it to be remotely 	
	 monitored and activated the switch must be in the “External 	
	 Trigger" position.
3. Incoming AC LED – This LED will illuminate Red when the 	
	 ECM has incoming AC power present at the module. This LED 	
	 must be On to operate. Note: If this LED is not illuminating 		
	 check the following: 1) The unit is plugged in, 2) The AC Mains 	
	 Breaker feeding the AC leg to the ECM module is OFF, 3) The 	
	 internal fuse has been damaged. This should only be inspected 	
	 by an authorized technician.
4. Active LED – This LED will illuminate Green when the ECM 	
	 module has sensed the proper DCV to trigger activate the 	 	
	 power on circuit. Note: If connected to the ETA-ECS6RM and
	 the EVS circuit is activated this LED will not be ON. The 	 	
	 Channel Status LED on the ETA-ECS6RM will flash indicating a
	 problem and will not turn the ECM module ON until the
	 AC Mains voltage is stable.
5. AC Fault LED – If damage to the Spike Suppression circuit 		
	 occurred this LED will illuminate Red. The module may still
	 operate but may not be protecting the items plugged into 		
	 the AC outlets. This LED will not turn off until repaired. Have 	
	 the ECM module inspected by a qualified technician.
	 Note: Not available on ETA-ECM20 type module.

Note: The above figures show the ECM wiring configuration
of one 20A AC main line coming into an ETA-ECM20M, then
paralleling with an ETA-ECM20 type module.
Note: It appears that the wiring is in series but the ECM Module
In/Out terminals are in parallel on the PCB.

6. AC Mains Outlet – Two 120V AC 20A outlets.

1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435

	

– 3 –	
Specifications are subject to change without notice.

ETAsys.com

ETA-ECM20 & ETA-ECM20M
Electrical Control Module 20A Power Conditioner
ETA-ECM20, ETA-ECM20M SPECIFICATIONS
General
	

Type: 	

Power Conditioner Suppressor Module

	

Power Requirements: 	

120V 60Hz

	

Power Consumption: 	

.5W

	

RoHS Compliant: 	

Yes

	

Safety Approval: 	

MET (UL 1449 Code)

Panel
	

Switched Outlets: 	

Two, 20A

	

Spike & Surge Suppression: 	

H-N, N-G, H-G

	

Manual Override: 	

Slide switch

	
Extreme Voltage Shutdown: 	
		

ETA-ECM20M Model only, (EVS) Below 102V or Above 	
132V AC Line (When Used With ETA-ECS6RM)

	

Connectors: 	

5 Position Phoenix Euro Block Style

	

Fuse Protection: 	

20A Slow Blow

	

DCV Remote Trigger:  	

5 – 24DCV

	

Remote Trigger: 	

SPST Contact

	
Status Signals: 	
		

Output for Voltage and Current Data
(ETA-ECM20M model only)

	

Indicators: 	

Incoming AC, Active, AC Fault (ETA-ECM20M model only)

	

AC Mains Interconnect: 	

Screw terminal block

	

Technical Data:
	

Current Rating: 	

15 amps

	

Operating Voltage: 	

102 - 132 VAC

	
High Voltage Surge Protection: 	
		
	

Trigger at 133 VAC, 1ms typically
(When Used With ETA-ECS6RM) (ETA-ECM20M model only)

Spike & Surge Suppression: 	

H-N, N-G, H-G

	
Low Voltage Protection: 	
		

Trigger 101 VAC, 1ms typically
(When Used With ETA-ECS6RM) (ETA-ECM20M model only)

	

Spike Protection Modes: 	

Circuitry on incoming AC Mains.

	

Minimum Spike Clamping Voltage: 	

460 VRMS @ 3,000 amps

	

Maximum Spike Clamping Voltage: 	

6000V

	

Maximum Spike Clamping Response Time: 	

1 nanosecond

	

Spike Clamping Voltage @ 100A: 	

1250Vp for 20µs

	

Maximum surge current: 	

6,500 amps

	

Energy Rating @ 2ms: 	

600 Joules

	
Noise Attenuation EMI/RFI Sequencer: 	
		

10 dB @ 10 kHz, 40 dB @ 100 kHz, 100 dB @ 10 MHz 	
(ETA-ECM20M model only)

	

Temperature Range: 	

5º to 35º C

	

Humidity Range: 	

5% to 95% R.H.

	

Mechanical:
	

Chassis Finish: 	

Black

	

Mounting: 	

#8 5/16” self tapping screws

	

Dimensions: 	

3.0" H x 8.5" L x 3.5" W (7.6cm x 21.6 cm x 8.9cm)

	

Unit Weight: 	

ETA-ECM20=1.25 lbs(.68 kg), ETA-ECM20M=1.75 lbs(.80 kg)

©2009 ETA Systems All rights reserved. ETA003568 RevA 05/09

1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435

	

– 4 –	
Specifications are subject to change without notice.

ETAsys.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.1-c037 46.282696, Mon Apr 02 2007 18:36:56
Create Date                     : 2009:12:01 10:57:02-07:00
Metadata Date                   : 2009:12:01 10:57:04-07:00
Modify Date                     : 2009:12:01 10:57:04-07:00
Creator Tool                    : Adobe InDesign CS3 (5.0.4)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 13359 bytes, use -b option to extract)
Instance ID                     : uuid:39bb1381-09e2-e447-8826-e63f70ac3317
Document ID                     : adobe:docid:indd:a689652f-41e6-11de-8a7d-e116964914ee
Rendition Class                 : proof:pdf
Derived From Instance ID        : 707531ac-3ba7-11de-9444-d1ecdde80fce
Derived From Document ID        : adobe:docid:indd:df7554c8-b230-11dd-bace-c90392e80125
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:375CE57FC46D11DEBF1C99A69CA4B5F2, uuid:D8EB5622C46D11DEBF1C99A69CA4B5F2, uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:17817B7C356111DE9661A367D672F6FA, uuid:3BA5BDDB356111DE9661A367D672F6FA, uuid:375CE57FC46D11DEBF1C99A69CA4B5F2, uuid:D8EB5622C46D11DEBF1C99A69CA4B5F2, uuid:90D5F2793D4D11DE97AAF697A9B042CF, uuid:90D5F2793D4D11DE97AAF697A9B042CF
Manifest Reference Document ID  : uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:5A7498EF922811DEB7F1D829DA7A44A7, uuid:67BF6FD5921D11DEB7F1D829DA7A44A7, uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:17817B7B356111DE9661A367D672F6FA, uuid:3BA5BDDA356111DE9661A367D672F6FA, uuid:5A7498EF922811DEB7F1D829DA7A44A7, uuid:67BF6FD5921D11DEB7F1D829DA7A44A7, uuid:90D5F2783D4D11DE97AAF697A9B042CF, uuid:90D5F2783D4D11DE97AAF697A9B042CF
Format                          : application/pdf
Producer                        : Adobe PDF Library 8.0
Trapped                         : False
Page Count                      : 4
Creator                         : Adobe InDesign CS3 (5.0.4)
EXIF Metadata provided by EXIF.tools

Navigation menu