Fluke 1735

Three-Phase Power Logger
Technical Data

Electrical load studies, energy
consumption testing, and
general power quality logging
The Fluke 1735 Three-Phase Power Logger
is the ideal electrician or technician’s tool for
conducting energy studies and basic power
quality logging. Set up the 1735 in seconds,
with the included flexible current probes and
color display. The 1735 logs most electrical
power parameters, harmonics and captures
voltage events.

•	 Record power and associated param-

eters for up to 45 days
•	 Monitor maximum power demand over
user-defined averaging periods
•	 Prove the benefit of efficiency improvements with energy consumption tests
•	 Measure harmonic distortion caused by
electronic loads
•	 Improve reliability by capturing voltage
dips and swells from load switching

•	 Easily confirm instrument setup with

color display of waveforms and trends

•	 Measure all three phases and neutral

with included 4 flexible current probes

•	 View graphs and generate reports with
included Power Log software

•	 Compact, rugged design with IP65 case,
600 V CAT III and two-year warranty

Applications
Load studies – verify electrical
system capacity before adding
loads
Energy assessments – quantify
energy consumption before, and
after improvements, to justify
energy saving devices
Harmonics measurements –
uncover harmonic issues that
can damage or disrupt critical
equipment
Voltage event capture – monitor for dips and swells that cause
spurious resets or nuisance
circuit breaker tripping

Log the most common
parameters
Designed to measure the most
critical three-phase power
parameters, the 1735 can log rms
voltage, rms current, phase angle,
voltage events, voltage and current THD, voltage and current
harmonics up to the 50th, active
power, reactive power, power
factor, active energy, reactive
energy, and more. With memory
for up to 45 days of data, the
1735 can uncover intermittent or
hard-to-find issues.

Conduct load studies for up
to 45 days and view saved
data on-screen or on a
computer.

Quantify energy consumption quickly on-screen or
log to memory for extended
periods.

Generate reports and view
graphs with Fluke Power
Log Software
Designed to quickly view recorded
data, the included Power Log software
displays all recorded parameters on
interactive trends. Generate a professional report with the ‘Report Writer’
function, or copy and paste images into
report document manually.

Assess voltage and current
harmonics up to the 50th.

Capture voltage events using
user-defined thresholds.
View recorded data in simple graphs and tables.

View waveforms onscreen to uncover
waveform distortion and
to verify correct voltage
and current connections.

Easy to use
The four current probes are
connected with one plug, the
instrument automatically detects,
scales and powers the probes.
These variable range current
probes are easily set to 15 A,
150 A, or 3000 A for high accuracy in nearly any application.
The voltage connections are
single leads, enabling easy and
quick setups. The color screen
provides instant confirmation that
connections are correct, and then
logging begins when you press
the RECORD button.

Easily customize the report.

Create professional reports.
 Fluke Corporation

1735 Three-Phase Power Logger

Specifications
General
Display
Quality
Memory
Interface
Sample rate
Line frequency
Power supply
Operation time with battery
Dimensions
Weight

¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable
contrast, text and graphics in color
Developed, designed and manufactured according to DIN ISO 9001
4 MB Flash memory, 3.5 MB for logging data
RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the
RS-232 interface (9-pole extension cable)
10.24 kHz
50 Hz or 60 Hz, user-selectable, with automatic synchronization
NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A)
Typical > 12 hours with backlight low and > 6 hours with backlight high
240 mm x 180 mm x 110 mm (6.1 in x 4.6 in x 2.8 in)
1.7 kg (3.75 lb), including battery

Ambient conditions
-10 °C to +50 °C (+14 °F to +122 °F)
-20 °C to +60 °C (+32 °F to +140 °F)
0 °C to +40 °C (+32 °F to +104 °F)
23 °C ± 2 °C

Working temperature range
Storage temperature range
Operating temperature range
Reference temperature range

Note: The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature
coefficient below.

Temperature coefficient
Intrinsic error
Operating error
Climatic class
Housing

± 0.1 % of the measured value per °C from the reference
Refers to reference temperature, max. deviation is guaranteed for two years.
Refers to operating temperature range, max. deviation is guaranteed for two years
C1 (IEC 654-1) -5 °C to +45 °C (+41 °F to +113 °F), 5 % to 95 % RH, no dew
Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster

EMC
Emission
Immunity

IEC/EN 61326-1:1997 class B
IEC/EN 61326-1:1997

Safety
Safety
Protection

IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2
IP65; EN60529 (refers only to the main housing without the battery compartment)

RMS values are measured with a 20 ms resolution.

V-rms wye measurement
Measuring range

Intrinsic error
Operating error
Resolution

 Fluke Corporation

57 V/66 V/110 V/120 V/127 V/220 V/
230 V/240 V/260 V/277 V/347 V/
380 V/400 V/417 V/480 V ac
± (0.2 % of measured value. + 5 digits)
± (0.5 % of m. v. + 10 digit)
0.1 V

1735 Three-Phase Power Logger

V-rms delta measurement
Measuring range

Intrinsic error
Operating error
Resolution

100 V/115 V/190 V/208 V/220 V/380 V/
400 V/415 V/450 V/480 V/600 V/
660 V/690 V/720 V/830 V ac
± (0.2 % of m. v. + 5 digit)
± (0.5 % of m. v. + 10 digit)
0.1 V

A-rms measurement
Flexi set I ranges
Current clamp ranges
Resolution
Ranges

Ranges

15 A/150 A/3000 A rms (at sine)
1 A/10 A
0.01 A
150 A/3000 A and 1 A/10 A
Intrinsic error: ± (0.5 % of m. v. + 10 digit)
Operating error: ± (1 % of m. v. + 10 digit)
15 A
Intrinsic error: ± (0.5 % of m. v. + 20 digit)
Operating error: ± (1 % of m. v. + 20 digit)

The errors of the current probes are not considered.

By using Flexi-Set:
Flexi Set measuring error
Position influence
CF (typical)

± (2 % of m.v. + 10 digit)
± (3 % of m.v. + 10 digit)
2.83

conductor
lock

Note: When using Flexi Set please make sure to position the conductor opposite to
the Flexi Set-lock (refer following figure).

Flexi Set-Lock

Power measurement (P – Active, S – Apparent,
Q – Reactive, D – Distorting)
•	 Measuring range: see V rms and A rms measurement
•	 Power errors are calculated by adding the errors of
voltage and current
•	 Additional error due to power factor PF
•	 Specified error x(1-|PF|)
•	 Maximum range with voltage range 830 V deltaconnection and 3000 A current range is 2.490 MW,
higher displayed values possible when using PTs and
CTs with ratio feature
Intrinsic error
Resolution
Operating error

•	

± (0.7 % of m.v. + 15 digit)
1 kW
± (1.5 % of m.v. + 20 digit)

Typical range with voltage range 230 V wye connection
and 150 A current range is 34.50 KW.

Intrinsic error
Resolution
Operating error

± (0.7 % of m.v. + 15 digit)
1 W to 10 W
± (1.5 % of m.v. + 20 digit)

The errors of the current sensors themselves have not been considered.

 Fluke Corporation

1735 Three-Phase Power Logger

Energy measurement (kWh, kVAh, kVARh)
Intrinsic error
Resolution
Operating error

± (0.7 % of m.v.+ F variation error*
+ 15 digit)
1 W to 10 W
± (1.5 % of m.v. + F variation error* +
20 digit)

*Frequency variation error

PF (Power factor)
Range
Resolution
Accuracy

0.000 to 1.000
0.001
± 1 % of full scale

Frequency measurement
Measuring range
Intrinsic error
Operating error
Resolution

46 Hz to 54 Hz and 56 Hz to 64 Hz
± (0.2 % of m.v. + 5 digit)
± (0.5 % of m.v.+ 10 digit)
0.01 Hz

Harmonics

Events
Up to 50th harmonic (< 50 % of nom)

Measuring range

Accuracy:
Vm, Im, THDV, THDI
Vm ≥ 3 % Vnom
Vm < 3 % Vnom
Im ≥ 10 % Inom
Im < 10 % Inom
THDV
THDI

IEC 61000-4-7:2002 Class II
± 5 % Vm
± 0.15 % Vnom
± 5 % Im
± 0 5 % Inom
for THD < 3 % ± 0.15 % at Vnom
for THD ≥ 3 % ± 5  % at Vnom
for THD < 10 % ± 0.5 % at Inom
for THD ≥ 10 % ± 5 % at Inom

Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the
half period sine wave of rms.
Intrinsic error
Operating error
Resolution

± (1 % of m.v. + 10 digit)
± (2 % of m.v. + 10 digit)
0.1 V

Vnom: Nominal voltage range.
Inom: Nominal current range.
Vm and Im are measured values of harmonic m.

Ordering information
Fluke-1735	

Power Logger

Includes:
•	 Soft carrying case
•	 4 flexible current probes (15 A/150 A/3000 A)
•	 Power Log software
•	 Voltage leads and clips
•	 Color localization set
•	 PC interface cable
•	 International ac adapter (115/230 V, 50/60 Hz)
•	 Printed English manual
•	 Multi-language manual CD

Optional accessories

•	 MBX Clamp 1 A/10 A – 3 precision dual range current
clamps (1 A/10 A) for secondary CT applications

•	 MBX Clamp 5 A/50 A +N - 4 precision dual range

current clamps (5 A/50 A) for general applications

•	 C435 – Water-tight hard case with rollers

Fluke.	Keeping your world
	
up and running.™
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800) 36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2006 Fluke Corporation. All rights reserved.
Printed in U.S.A. 5/2006 2634932 D-EN-N Rev A

 Fluke Corporation

1735 Three-Phase Power Logger



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-701
About                           : 7d1eb917-b58e-11da-9453-8cc29933fa7d
Create Date                     : 2006:06:05 12:52:17-07:00
Metadata Date                   : 2006:06:05 12:54:17-07:00
Modify Date                     : 2006:06:05 12:54:17-07:00
Creator Tool                    : Adobe InDesign CS2 (4.0.2)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 8627 bytes, use -b option to extract)
Instance ID                     : uuid:129dc2a7-f4cd-11da-b1f9-000a95b26bba
Document ID                     : adobe:docid:indd:ee208c76-f460-11da-a8a1-eddeb4664aff
Rendition Class                 : proof:pdf
Derived From Instance ID        : d3843ab2-e249-11da-bee1-960f502a0b74
Derived From Document ID        : adobe:docid:indd:d3843ab1-e249-11da-bee1-960f502a0b74
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 300.12, 300.12, 300.12, 300.12, 300.12, 300.00, 72.00, 72.00, 96.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 300.12, 300.12, 300.12, 300.12, 300.12, 300.00, 72.00, 72.00, 96.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:A045356ED2D911DABFFC868218672BC8, uuid:71E35F2BC7AE11DAB134BA9C6F0005FD, uuid:5A26AEB3C7AE11DAB134BA9C6F0005FD, uuid:7B3781FCC7AE11DAB134BA9C6F0005FD, uuid:5A26AEB7C7AE11DAB134BA9C6F0005FD, uuid:71E35F2FC7AE11DAB134BA9C6F0005FD, uuid:AC5C4AEFD2DF11DABFFC868218672BC8, uuid:00C7A5E6DF3B11DA94D8F392FC3EE136, uuid:8FC23FA3C7AE11DAB134BA9C6F0005FD, uuid:279A825ADF4511DA94D8F392FC3EE136, uuid:c1c4157c-d623-11da-ad1b-000a95b26bba, uuid:AC5C4AE9D2DF11DABFFC868218672BC8
Manifest Reference Document ID  : uuid:A045356DD2D911DABFFC868218672BC8, uuid:71E35F2AC7AE11DAB134BA9C6F0005FD, uuid:5A26AEB2C7AE11DAB134BA9C6F0005FD, uuid:7B3781FBC7AE11DAB134BA9C6F0005FD, uuid:5A26AEB6C7AE11DAB134BA9C6F0005FD, uuid:71E35F2EC7AE11DAB134BA9C6F0005FD, uuid:AC5C4AEED2DF11DABFFC868218672BC8, uuid:00C7A5E5DF3B11DA94D8F392FC3EE136, uuid:8FC23FA2C7AE11DAB134BA9C6F0005FD, uuid:279A8259DF4511DA94D8F392FC3EE136, uuid:6840B6D0D77B11DAB158ED123527C1BD, uuid:AC5C4AE8D2DF11DABFFC868218672BC8
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 5
Creator                         : Adobe InDesign CS2 (4.0.2)
EXIF Metadata provided by EXIF.tools

Navigation menu