Fluke 289 Application Note

2015-09-09

: Fluke Fluke-289-Application-Note-805131 fluke-289-application-note-805131 fluke pdf

Open the PDF directly: View PDF PDF.
Page Count: 7

ABCs of
multimeter safety
Multimeter safety and you
Voltage spikes—an
unavoidable hazard
As distribution systems and
loads become more complex,
the possibilities of transient
overvoltages increase. Motors,
capacitors and power con-
version equipment, such as
variable speed drives, can be
prime generators of spikes.
Lightning strikes on outdoor
transmission lines also cause
extremely hazardous high-
energy transients. If you’re
taking measurements on elec-
trical systems, these transients
are “invisible” and largely
unavoidable hazards. They
occur regularly on low-voltage
power circuits, and can reach
peak values in the many thou-
sands of volts. In these cases,
you’re dependent for protection
on the safety margin already
built into your meter. The
voltage rating alone will not
tell you how well that meter
was designed to survive high
transient impulses.
Early clues about the safety
hazard posed by spikes came
from applications involving
measurements on the supply
bus of electric commuter rail-
roads. The nominal bus voltage
was only 600 V, but multime-
ters rated at 1000 V lasted only
a few minutes when taking
measurements while the train
was operating. A close look
revealed that the train stop-
ping and starting generated
10,000 V spikes. These tran-
sients had no mercy on early
multimeter input circuits. The
lessons learned through this
investigation led to significant
improvements in multimeter
input protection circuits.
Test tool safety standards
To protect you against
transients, safety must be built
into the test equipment. What
performance specification
should you look for, especially
if you know that you could
be working on high-energy
circuits? The task of defin-
ing safety standards for test
equipment is addressed by the
International Electrotechnical
Commission (IEC). This organi-
zation develops international
safety standards for electrical
test equipment.
Meters have been used
for years by technicians and
electricians yet the fact is that
meters designed to the IEC 1010
standard offer a significantly
higher level of safety. Let’s see
how this is accomplished.
AmA COM V
TEMPERATURE
A
TRUE RMS MULTIMETER
189
400mA
FUSED
10A MAX
FUSED
CAT
1000V
Application Note
From the Fluke Digital Library @ www.fluke.com/library
Dont overlook safety—your
life may depend on it
Where safety is a concern, choosing a multi-
meter is like choosing a motorcycle helmet—if
you have a “ten dollar” head, choose a “ten
dollar” helmet. If you value your head, get a
safe helmet. The hazards of motorcycle riding
are obvious, but whats the issue with multi-
meters? As long as you choose a multimeter
with a high enough voltage rating, aren’t you
safe? Voltage is voltage, isn’t it?
Not exactly. Engineers who analyze mul-
timeter safety often discover that failed units
were subjected to a much higher voltage
than the user thought he was measuring.
There are the occasional accidents when the
meter, rated for low voltage (1000 V or less),
was used to measure medium voltage, such
as 4160 V. Just as common, the knock-out
blow had nothing to do with misuse—it was
a momentary high-voltage spike or transient
that hit the multimeter input without warning.
2 Fluke Corporation ABCs of multimeter safety
CAT 0
Transient protection
The real issue for multimeter
circuit protection is not just the
maximum steady state volt-
age range, but a combination of
both steady state and transient
overvoltage withstand capabil-
ity. Transient protection is vital.
When transients ride on high-
energy circuits, they tend to be
more dangerous because these
circuits can deliver large currents.
If a transient causes an arc-over,
the high current can sustain
the arc, producing a plasma
breakdown or explosion, which
occurs when the surrounding air
becomes ionized and conduc-
tive. The result is an arc blast, a
disastrous event which causes
more electrical injuries every year
than the better known hazard of
electric shock. (See Transients
the hidden dangeron page 4.)
Measurement categories
The most important single con-
cept to understand about the
standards is the Measurement
category. The standard defines
Categories 0 through IV, often
abbreviated as CAT 0, CAT II, etc.
(See Figure 1.) The division of a
power distribution system into
categories is based on the fact
that a dangerous high-energy
transient such as a lightning
strike will be attenuated or
dampened as it travels through
the impedance (ac resistance) of
the system. A higher CAT number
refers to an electrical environ-
ment with higher power available
and higher energy transients.
Thus a multimeter designed to
a CAT III standard is resistant to
much higher energy transients
than
one designed to CAT II
standards.
Within a category, a higher
voltage rating denotes a higher
transient withstand rating, e.g., a
CAT III-1000 V meter has supe-
rior protection compared to a CAT
III-600 V rated meter. The real
misunderstanding occurs if some-
one selects a CAT II-1000 V rated
meter thinking that it is superior
to a CAT III-600 V meter. (See
“When is 600 V
more than 1000 V?on page 7.)
Figure 1. Location, location, location.
Understanding categories:
Location, location, location
Table 1. Measurement categories. IEC 1010 applies to low-voltage (< 1000 V) test equipment.
Measurement
category In brief Examples
CAT IV Three-phase at
utility connection,
any outdoor
mains conductors
Refers to the “origin of installation, i.e., where low-voltage
connection is made to utility power
Electricity meters, primary overcurrent protection equipment
Outside and service entrance, service drop from pole to
building, run between meter and panel
Overhead line to detached building, underground line to well
pump
CAT III Three-phase
distribution,
including single-
phase commercial
lighting
Equipment in fixed installations, such as switchgear and
polyphase motors
Bus and feeder in industrial plants
Feeders and short branch circuits, distribution panel devices
Lighting systems in larger buildings
Appliance outlets with short connections to service entrance
CAT II Single-phase
receptacle
connected loads
Appliance, portable tools, and other household and similar
loads
Outlet and long branch circuits
Outlets at more than 10 meters (30 feet) from CAT III source
Outlets at more that 20 meters (60 feet) from CAT IV source
CAT 0 Electronic Protected electronic equipment
Equipment connected to (source) circuits in which measures
are taken to limit transient overvoltages to an appropriately
low level
Any high-voltage, low-energy source derived from a high-
winding resistance transformer, such as the high-voltage
section of a copier
ABCs of multimeter safety Fluke Corporation 3
What does the
symbol indicate?
A product is marked CE
(Conformité Européenne)
to indicate its conformance to
certain essential requirements
concerning health, safety,
environment and consumer
protection established by
the European Commission
and mandated through the
use of “directives.” There are
directives affecting many
product types, and products
from outside the European
Union can not be imported and
sold there if they do not comply
with applicable directives.
Compliance with the directive
can be achieved by proving
conformance to a relevant
technical standard, such as
IEC 61010-1 for low-voltage
products. Manufacturers are
permitted to self-certify that
they have met the standards,
issue their own Declaration
of Conformity, and mark the
product “CE.The CE mark is
not, therefore, a guarantee of
independent testing.
Its not just the
voltage level
In Figure 1, a technician working
on office equipment in a CAT 0
location could actually encounter
dc voltages much higher than the
power line ac voltages measured
by the motor electrician in the CAT
III location. Yet transients in CAT 0
electronic circuitry, whatever the
voltage, are clearly a lesser threat,
because the energy available to
an arc is quite limited. This does
not mean that there is no electri-
cal hazard present in CAT 0 or CAT
II equipment. The primary hazard
is electric shock, not transients
and arc blast. Shocks, which will
be discussed later, can be every
bit as lethal as arc blast.
To cite another example, an
overhead line run from a house
to a detached workshed might be
only 120 V or 240 V, but it’s still
technically CAT IV. Why? Any
outdoor conductor is subject to
very high energy lightning-related
transients. Even conductors buried
underground are CAT IV, because
although they will not be directly
struck by lightning, a lightning
strike nearby can induce a tran-
sient because of the presence of
high electro-magnetic fields.
When it comes to Overvoltage
Installation Categories, the rules
of real estate apply: it’s location,
location, location...
(For more discussion of Installation
Categories, see page 6, “Applying cat-
egories to your work.”)
Independent testing is the
key to safety compliance
Look for a symbol and listing
number of an independent test-
ing lab such as UL, CSA, TÜV or
other recognized testing organi-
zation. Beware of wording such
as “Designed to meet specifica-
tion ...” Designers plans are
never a substitute for an actual
independent test.
How can you tell if you’re
getting a genuine CAT III or CAT
II meter? Unfortunately it’s not
always that easy. It is possible
for a manufacturer to self-
certify that its meter is CAT II or
CAT III without any independent
verification. The IEC develops
and proposes standards, but it
is not responsible for enforcing
the standards.
Look for the symbol and
listing number of an indepen-
dent testing lab such as UL,
CSA, TÜV or other recognized
approval agency. That symbol
can only be used if the product
successfully completed testing
to the agency’s standard, which
is based on national/interna-
tional standards. UL 61010-1,
for example, is based on IEC
61010-1. In an imperfect world,
that is the closest you can come
to ensuring that the multimeter
you choose was actually tested
for safety.
Independent testing
Tool Tip
Non-contact voltage detectors are a
quick, inexpensive way to check for
the presence of live voltage on ac
circuits, switches and outlets before
working on them.
1. Verify the voltage detector function is working properly.
2. Make sure the detector is rated for the level of voltage being
measured and is sensitive enough for your application.
3. Make sure that you also wear the appropriate PPE based on
the environment you're in.
3. Make sure you’re grounded (through your hand, to the floor),
to complete the capacitive voltage connection.
4. Make sure the hazardous voltage is not shielded.
Use only a digital multimeter or contact type voltage tester to
test for the absence of voltage.
This meter has a built-in non-contact voltage tester.
4 Fluke Corporation ABCs of multimeter safety
Protection against two major electrical hazards
Transientsthe hidden
danger
Lets take a look at a worst-case
scenario in which a technician
is performing measurements
on a live three-phase motor
control circuit, using a meter
without the necessary safety
precautions.
Here’s what could happen:
1. A lightning strike causes a
transient on the power line,
which in turn strikes an arc
between the input terminals
inside the meter. The circuits
and components to prevent
this event have just failed or
were missing. Perhaps it was
not a CAT III rated meter.
The result is a direct short
between the two measure-
ment terminals through the
meter and the test leads.
2. A high-fault currentpossibly
several thousands of amps–
flows in the short circuit
just created. This happens
in thousandths of a second.
When the arc forms inside
the meter, a very high-pres-
sure shock wave can cause a
loud bang—very much like a
gunshot or the backre from
a car. At the same instant,
the tech sees bright blue arc
flashes at the test lead tips
the fault currents superheat
the probe tips, which start to
burn away, drawing an arc
from the contact point to the
probe.
3. The natural reaction is to
pull back, in order to break
contact with the hot circuit.
But as the tech’s hands are
pulled back, an arc is drawn
from the motor terminal to
each probe. If these two
arcs join to form a single arc,
there is now another direct
phase-to-phase short, this
time directly between the
motor terminals.
4. This arc can have a tempera-
ture approaching 6000 °C
(10000 °F), which is higher
than the temperature of
an oxyacetylene cutting
torch! As the arc grows, fed
by available short circuit
current, it superheats the
surrounding air. Both a
shock blast and a plasma
reball are created. If the
technician is lucky, the
shock blast pushes him away
and removes him from the
proximity of the arc; though
injured, his life is saved. In
the worst case, the victim
is subjected to fatal burn
injuries from the fierce heat
of the arc or plasma blast.
In addition to using a multi-
meter rated for the appropriate
measurement category, anyone
working on live power circuits
should be protected with flame
resistant clothing, should wear
safety glasses or, better yet, a
safety face shield, and should
use insulated gloves and shoes.
A lightning strike causes a transient
on the power line, creating an arc
between the meter’s input terminal
and resulting in loud noises.
Then, a high current flows in the
closed circuit which is formed.
An arc starts at the probe tips.
If those arcs join, the
resulting high-energy
arc can create a life-
threatening situation
for the user.
When you pull the probes away
as a reaction to the loud noise,
arcs are drawn to the motor
terminals you’re probing.
4
1
1 2
3
Figure 2. A worst-case scenario—potential arc blast sequence.
ABCs of multimeter safety Fluke Corporation 5
Transients aren’t the only source of
possible short circuits and arc blast
hazard. One of the most common
misuses of handheld multimeters
can cause a similar chain of events.
Lets say a user is making
current measurements on signal
circuits. The procedure is to select
the amps function, insert the leads
in the mA or amps input termi-
nals, open the circuit and take a
series measurement. In a series
circuit, current is always the same.
The input impedance of the amps
circuit must be low enough so that
it doesn’t affect the series circuits
current. For instance, the input
impedance on the 10 A terminal
of a Fluke meter is .01 W. Compare
this with the input impedance on
the voltage terminals of 10 MW
(10,000,000 W).
If the test leads are left in the
amps terminals and then acciden-
tally connected across a voltage
source, the low input imped-
ance becomes a short circuit! It
doesn’t matter if the selector dial is
turned to volts; the leads are still
physically connected to a low-
impedance circuit.* That’s why the
amps terminals must be protected
by fuses. Those fuses are the only
thing standing between an incon-
venience–blown fuses–and a
potential disaster.
Use only a multimeter with amps
inputs protected by high-energy
fuses. Never replace a blown fuse
with the wrong fuse. Use only
the high-energy fuses specified
by the manufacturer. These fuses
are rated at a voltage and with a
short circuit interrupting capacity
designed for your safety.
Overload protection
Fuses protect against overcur-
rent. The high input impedance of
the volts/ohms terminals ensures
that an overcurrent condition is
unlikely, so fuses aren’t necessary.
Overvoltage protection, on the other
hand, is required. It is provided
by a protection circuit that clamps
high voltages to an acceptable
level. In addition, a thermal protec-
tion circuit detects an overvoltage
condition, protects the meter until
the condition is removed, and then
automatically returns to normal
operation. The most common ben-
efit is to protect the multi meter from
overloads when it is in ohms mode.
In this way, overload protection
with automatic recovery is provided
for all measurement functions as
long as the leads are in the voltage
input terminals.
AmA COM V
TEMPERATURE
A
V
AmA COM V
TEMPERATURE
A
V
TRUE RMS MULTIMETER
189
400mA
FUSED
10A MAX
FUSED
CAT
1000V
ACOM
Figure 3. Misuse of DMM in Ammeter Mode.
While most people are aware of the
danger from electric shock, few real-
ize how little current and how low a
voltage are required for a fatal shock.
Current flows as low as 30 mA can
be fatal (1 mA=1/1000 A). Lets look
at the effects of current flow through
a “typical” 68 kilogram (150 pound)
male:
At about 10 mA, muscular paraly-
sis of the arms occurs, so that he
cannot release his grip.
At about 30 mA, respiratory paraly-
sis occurs. His breathing stops and
the results are often fatal.
At about 75 to 250 mA, for exposure
exceeding five seconds, ven-
tricular fibrillation occurs, causing
incoordina tion of the heart muscles;
the heart can no longer function.
Higher currents cause fibrillation at
less than five seconds. The results
are often fatal.
Now let’s calculate the thresh hold for
a “hazardous” voltage. The approxi-
mate body resistance under the skin
from hand to hand across the body
is 1000 W. A voltage of only 30 V
across 1000 W will cause a current
flow of 30 mA. Fortunately, the skin’s
resistance is much higher. It is the
resistance of the skin, especially the
outer layer of dead cells, that protects
the body. Under wet conditions, or if
there is a cut, skin resistance drops
radically. At about 600 V, the resis-
tance of the skin ceases to exist. It is
punctured by the high voltage.
For multimeter manufacturers and
users, the objective is to prevent
accidental contact with live circuits at
all costs.
Look for:
Meters and test leads with double
insulation.
Meters with recessed input jacks
and test leads with shrouded input
connectors.
Test leads with finger guards and a
non-slip surface.
Meter and test leads made of high-
quality, durable, non-conductive
materials.
Use the right high-energy fuses
Electric shock
* Some multimeters, such as the Fluke 80 Series,
have an Input Alert which gives a warning beep
if the meter is in this configuration.
Arc blast and electric shock
6 Fluke Corporation ABCs of multimeter safety
Multiple categories
There’s one scenario that some-
times confuses people trying to
apply categories to real world
applications. In a single piece of
equipment, there is often more
than one category. For example,
in office equipment, from the
120 V/240 V side of the power
supply back to the receptacle is
CAT II. The electronic circuitry,
on the other hand, is CAT 0. In
building control systems, such
as lighting control panels, or
industrial control equipment
such as programmable con-
trollers, it is common to find
electronic circuits (CAT 0) and
power circuits (CAT III) existing
in close proximity.
What do you do in these
situations? As in all real-world
situations, use common sense.
In this case, that means using
the meter with the higher
category rating. In fact, it’s not
realistic to expect people to be
going through the category-
defining process all the time.
What is realistic, and highly
recommended, is to select a
multi meter rated to the highest
category in which it could pos-
sibly be used. In other words,
err on the side of safety.
Shortcuts to
understanding categories
Here are some quick ways to
apply the concept of categories
to your every day work:
The general rule-of-thumb
is that the closer you are to
the power source, the higher
the category number, and the
greater the potential danger
from transients.
It also follows that the greater
the short-circuit current avail-
able at a particular point, the
higher the CAT number.
Another way of saying the
same thing is the greater
the source impedance, the
lower the CAT number. Source
impedance is simply the total
impedance, including the
impedance of the wiring,
between the point where you
are measuring and the power
source. This impedance is
what dampens transients.
Finally, if you have any
experience with the applica-
tion of transient voltage surge
suppression (TVSS) devices,
you understand that a TVSS
device installed at a panel
must have higher energy-
handling capacity than one
installed right at the com-
puter. In CAT terminology, the
panelboard TVSS is a CAT III
application, and the computer
is a receptacle-connected
load and therefore, a CAT II
installation.
As you can see, the concept
of categories is not new and
exotic. It is simply an exten-
sion of the same common-sense
concepts that people who work
with electricity professionally
apply every day.
Work safely
Safety is everyone’s responsibility but ulti-
mately it’s in your hands.
No tool by itself can guarantee your safety.
Its the combination of the right tools and
safe work practices that gives you maximum
protection. Here are a few tips to help you in
your work.
Work on de-energized circuits whenever
possible. Use proper lock-out/tag-out
procedures. If these procedures are not
in place or not enforced, assume that the
circuit is live.
On live circuits, use protective gear:
Use insulated tools.
Wear safety glasses and arc rated face
shield if required
Wear insulated gloves; remove watches
or other jewelry.
Stand on an insulated mat.
Wear approved clothing, not ordinary
work clothes.
When making measurements on live
circuits:
Hook on the ground clip first, then make
contact with the hot lead. Remove the
hot lead first, the ground lead last.
Hang or rest the meter if possible. Try to
avoid holding it in your hands, to mini-
mize personal exposure to the effects of
transients.
Use the three-point test method, espe-
cially when checking to see if a circuit
is dead. First, test a known live circuit.
Second, test the target circuit. Third,
test the live circuit again. This verifies
that your meter worked properly before
and after the measurement.
Use the old electricians’ trick of keeping
one hand in your pocket. This lessens
the chance of a closed circuit across
your chest and through your heart.
Applying categories to your work
Always wear approved personal protective
equipment (PPE), including arc rated clothing,
leather over rubber gloves, safety glasses, and
an arc-rated face shield or hood, both with hard
hat and hearing protection.
7 Fluke Corporation ABCs of multimeter safety
Understanding voltage
withstand ratings
IEC 61010-1 test procedures
take into account three main
criteria: steady-state voltage,
peak impulse transient voltage
and source impedance. These
three criteria together will tell
you a multimeters true voltage
withstand value.
When is 600 V more than
1000 V?
Table 2 can help us understand
an instruments true voltage
withstand rating:
1. Within a category, a higher
“working voltage” (steady-
state voltage) is associated
with a higher transient,
as would be expected. For
example, a CAT III-600 V
meter is tested with 6000 V
transients while a CAT III-
1000 V meter is tested with
8000 V transients. So far, so
good.
2. What is not as obvious is the
difference between 6000 V
transient for CAT III-600 V
and the 6000 V transient for
CAT II-1000 V. They are not
the same. This is where the
source impedance comes in.
Ohm’s Law (Amps = Volts/
Ohms) tells us that the 2 W
test source for CAT III has six
times the current of the 12 W
test source for CAT II.
The CAT III-600 V meter clearly
offers superior transient pro-
tection compared to the CAT
II-1000 V meter, even though its
so-called “voltage rating” could
be perceived as being lower.
It is the combination of the
steady-state voltage (called the
working voltage), and the cat-
egory that determines the total
voltage withstand rating of the
test instrument, including the
all-important transient voltage
withstand rating.
A note on CAT IV: Test
values and design standards for
How to evaluate a multimeter’s safety rating
Category IV voltage testing are
addressed in IEC IEC 61010-1
standard.
Creepage and clearance
In addition to being tested to
an actual overvoltage tran-
sient value, multimeters are
required by IEC IEC 61010-1 to
have minimum “creepage” and
clearance” distances between
internal components and circuit
nodes. Creepage measures
distance across a surface.
Clearance measures distances
through the air. The higher the
category and working voltage
level, the greater the internal
spacing requirements.
The bottom line
If you are faced with the task of
replacing your multimeter, do
one simple task before you start
shopping: Analyze the worst-
case scenario of your job and
determine what category your
use or application fits into.
First choose a meter rated
for the highest category you
could be working in. Then,
look for a multimeter with a
voltage rating for that category
matching your needs. While
you’re at it, don’t forget the test
leads. IEC 61010-1 applies to
test leads too: they should be
certified to a category and volt-
age as high or higher than the
meter. When it comes to your
personal protection, don’t let
test leads be the weak link.
Look for category and voltage ratings of test leads and multimeters.
Working Voltage Peak Impulse
Measurement (dc or ac-rms Transient Test Source
Category to ground) (20 repetitions) (W = V/A)
CAT 0 600 V 2500 V 30 Ohm source
CAT 0 1000 V 4000 V 30 Ohm source
CAT II 600 V 4000 V 12 Ohm source
CAT II 1000 V 6000 V 12 Ohm source
CAT III 600 V 6000 V 2 Ohm source
CAT III 1000 V 8000 V 2 Ohm source
CAT IV 600 V 8000 V 2 Ohm source
Table 2: Transient test values for measurement categories. (50 V/150 V/300 V
values not included.)
Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2006-2014 Fluke Corporation.
Specifications subject to change without notice.
Printed in U.S.A. 10/2012 1263690J_EN
Modification of this document is not permitted
without written permission from Fluke Corporation.
Fluke. The Most Trusted Tools
in the World.

Navigation menu