Fluke 434 Series Ii Application Note 2435490

2015-09-09

: Fluke Fluke-434-Series-Ii-Application-Note-808976 fluke-434-series-ii-application-note-808976 fluke pdf

Open the PDF directly: View PDF PDF.
Page Count: 6

There are hundreds of power quality measurements you can take
on electrical systems and equipment. These instructions focus on
four predictive maintenance (PdM) measurements and two power
consumption measurements that can help you uncover hidden
costs, protect equipment from damaging conditions, reduce
unscheduled downtime and improve system performance.
What is it? In a balanced 3-phase system, the
phase voltages should be equal or very close to
equal. Unbalance is a measurement of the inequal-
ity of the phase voltages.
What does it do? Voltage unbalance can cause
3-phase motors and other 3-phase loads to
experience poor performance or premature failure
because of the following:
Mechanical stresses in motors due to lower
than normal torque output.
Higher than normal current in motors and
3-phase rectifiers.
Unbalance current will flow in neutral
conductors in 3-phase wye systems.
simple ways to
reduce costs
with a Fluke 434 Power Quality Analyzer
6
PdM Measurement #1: Voltage Unbalance
How much does an incident cost? The major
costs are associated with motor replacement (labor
+ equipment) and lost income due to circuit protec-
tion trips.
Example Calculation
Assume the cost to replace a 50 hp motor each
year is $5000 including labor.
Assume 4 hours of downtime per year with
income loss of $6000 per hour.
Total Cost: $5000 + (4 x $6000)
= $29,000 annually
What to check? Inputs to motors, VFDs, UPSs1.
How much is ok? The EN50160 power quality
standard requires voltage unbalance, as a ratio of
negative to positive sequence components, to be
less than 2 % at the point of common coupling.
NEMA specs call for less than 5 % for motor loads.
Consult user manuals for other equipment.
How do I measure it with the Fluke 430
Series Power Quality Analyzer?
1. Connect the voltage leads of the analyzer.
2. Configure the analyzer for the appropriate
3-phase power system: delta or wye.
3. Select “Unbalance” from the main menu.
1VFD: Variable Frequency Drive; UPS: Uninterruptible Power Supply
Vneg is the ratio of negative to positive sequence voltage and Vzero is
the ratio of zero to positive sequence voltage. They are both indications
of voltage unbalance.
For more information on Fluke Predictive
Maintenance Products and Services go to
www.fluke.com/pdm
PdM Measurement #2: Total Harmonic Distortion
What is it? Total Harmonic Distortion (THD) is the
sum of the contributions of all harmonics. Harmonic
distortion is a normal consequence of a power sys-
tem supplying electronic loads such as computers,
business machines, electronic lighting ballasts, and
control systems.
What does it do? Harmonic distortion can cause:
High current to flow in neutral conductors.
Motors and transformers to run hot, shortening
their lives.
Increased susceptibility to voltage sags,
potentially causing spurious resets.
Reduced efficiency of transformer — or, a larger
unit is required to accommodate harmonics.
Audible noise.
How much does an incident cost? The major
costs are associated with shortened life of motors
and transformers. If the equipment is part of pro-
duction systems, income may be affected as well.
Example Calculation
Assume the cost to replace a 100 KVA
transformer is $7000 including labor each year.
Assume 8 hours of downtime each year with
income loss of $6000 per hour.
Total Cost: $5000 + (8 x $6000)
= $29,000 annually
What to check? Motors, transformers and neutral
conductors serving electronic loads.
How much is ok? Voltage distortion (THD)
should be investigated if it is over 5 % on any
phase. Some current distortion (THD) is normal on
any part of the system serving electronic loads.
Monitor current levels and temperature at trans-
formers to be sure that they are not overstressed.
Neutral current should not exceed the capacity of
the neutral conductor.
How do I measure with the Fluke 430
Series Power Quality Analyzer?
1. Connect the voltage and current leads of the
analyzer.
2. Configure the analyzer for the appropriate
3-phase power system: delta or wye.
3. Select “Harmonics” from the main menu.
Voltage THD should be investigated if it is higher than 5 % on any phase.
PdM Measurement #3: Increasing Phase Current
What is it? As insulation deteriorates it begins to
leak. Loads will draw slightly higher current as
they age and they may send some of this leakage
current into the grounding system. Faults within
the equipment may also cause high ground current.
The best way to check insulation is by periodically
checking equipment with an insulation tester. But
you can also check equipment while it’s in service
by monitoring all of the currents (phase, neutral
and ground) to make sure none of these is increas-
ing significantly over time.
What does it do?
Excessive phase currents can further damage
insulation and overheat the load, resulting in a
shortened life of the load.
Over-current will cause protection devices to
trip, resulting in unscheduled downtime.
Excessive ground current can create unsafe volt-
ages on metal chassis, cabinets, and conduit.
How much does an incident cost? Costs come
from premature motor failure and lost income due
to over-current protection devices tripping.
Example Calculation
Assuming the failure of a pump motor each
year costs $7000 to replace and causes a
$2,500,000 per year continuous process to be
shut down for 10 hours. Assume it takes two
people 6 hours to clean and restart the process
at $50 per hour each.
Lost income = 10 hours*($2,500,000 / (365
days/year * 24 hrs/ day)) = $2853
Motor replacement = $7000
Clean and restart = $600
Total Cost $10,453 annually
What to check? Any critical load, but especially
motors, VFDs and transformers.
How much is ok? The nameplate rating of the
load should never be exceeded. If you track the
phase current being drawn by a load over the
months or years, you should be able to get a sense
whether the current is changing.
How do I measure with the Fluke 430
Series Power Quality Analyzer?
1. Connect the voltage and current leads of the
analyzer.
2. Configure the analyzer for the appropriate
3-phase power system: delta or wye.
3. Select “Volt/Amp/Hertz” from the main menu.
4. Press “Save Screen” to record measurements for
comparison with future readings.
5. Monitor phase current regularly for changes.
Troubleshoot further if amps rms readings increase dramatically, or show an
increasing trend, between maintenance intervals.
Deep, frequent voltage sags can cause trouble, especially with industrial controls and computers.
PdM Measurement #4: Voltage Sags
What are they? Voltage sags are momentary
reductions in rms voltage for 1 cycle to 2 minutes.
Loads may be added without notifying plant man-
agement, and these loads may draw down system
voltage, especially if they draw high inrush cur-
rents. Also, as electrical systems age, the impedance
of the system may increase, making the system
more prone to voltage sags.
What do they do? Voltage sags can cause:
Spurious resets on electronic equipment such as
computers or controllers.
Sags on one or two phases of 3-phase loads
causing the other phase(s) to draw higher cur-
rent in an attempt to compensate. This may trip
overcurrent protection.
How much does an incident cost? The main
cost factors are lost income due to computer reset,
control system reset, VFD trip, and shortened life of
backup power system‘s UPS due to frequent cycling.
Example Calculation
Assume a voltage sag causes a VFD on a con-
veyor system to trip offline at least once a year.
No income is permanently lost, but 10 hourly
workers have to work 4 hours to make ship-
ments at $30/hour, which includes overtime.
Added Labor = 10 people * 4 hours * $30/hr
= $1200 annually
What to check? Motors, VFDs, UPSs, panels or
PDUs* serving computer equipment or industrial
controls.
How much is ok? Most loads will operate at
90 % of nominal voltage. The ITIC curve suggests
that single-phase computer equipment loads should
be able to ride through drops to 80 % of nominal
for 10 s and 70 % of nominal for 0.5 s.
How do I measure with the Fluke 430
Series Power Quality Analyzer?
1. Connect the voltage and current leads of the
analyzer.
2. Configure the analyzer for the appropriate
3-phase power system: delta or wye.
3. Select “Dips and Swells” from the main menu.
4. Monitor power over time.
5. View either as a trend display or event list.
*PDU: Power Distribution Unit
Power Measurement #1: Peak Demand
With the demand interval set correctly, the Fluke 430 Series will plot one
average demand reading for each demand interval. Your peak demand will be
the highest of these readings.
What is it? Utilities monitor the amount of power
a facility consumes and several times an hour they
calculate the average demand for that interval.
Peak demand is the highest average demand dur-
ing all of the intervals in a billing cycle.
What does it do? Utilities charge based on peak
demand because they have to maintain infrastruc-
ture large enough to supply power at peak levels.
Commercial and industrial customers can manage
the high cost of peak demand rates by staggering
load cycles to reduce total draw at any one time.
How much does an incident cost? This
depends on the rate schedule of the utility. It may
be higher during summer months and certain times
of day.
Example Calculation
Assume your normal demand is about 600 kW,
but three HVAC chillers come on at once and
your demand hits 750 kW at 4 p.m. on a
Wednesday in July.
Assume the utility demand charge is $100
per kW.
(750 kW - 600 kW) * $100.00 = $15,000 in
potential savings for July
What to check?
Find out what demand interval the utility
uses — 15 minutes is common.
Measure demand over time at the service
entrance.
Look for significant loads operating concurrently
and use demand measurement to verify read-
ings for the individual loads.
How much is OK?
There are no safety or regulatory limits other than
what the facility can afford.
How do I measure it with the 430 Series
Power Quality Analyzer?
1. Connect the voltage and current leads of the
analyzer.
2. Configure the analyzer for the appropriate 3-
phase power system: delta or wye.
3. Set the demand interval to correspond to the
one specified by your power utility. Press Setup,
Function Pref (F3). Select “Power & Energy” from
the Select Function menu. Arrow down past the
bottom of the screen until “Demand int” is high-
lighted.
4. Select “Power & Energy” from the main menu
and monitor the power for as long as necessary.
5. Use the trend display to see the peak demand.
The cursor will help you see the demand at any
time during the recording.
Power Consumption
Commercial and industrial power consumers are charged for
power consumption based on multiple variables including energy
(kWh), peak demand (kW), and power factor. Power quality ana-
lyzers can help manage utility bills by determining which loads
have a significant effect on peak demand and power factor.
Power Measurement #2: Power Factor or Reactive Demand
What is it? Power factor compares the real power
(watts) being consumed to the apparent power
(Volts-Amps) of the load. A purely resistive load
would have a power factor of 1.0.
What does it do?
The power available to perform work is called real
power (kW). Inductive loads such as motors, trans-
formers, and high-intensity lighting introduce reac-
tive power (kVARs) into a power system. The
system capacity is rated by the apparent power
(kVA) which must be large enough to accommodate
both the real power (kW) and reactive power
(kVAR). Since reactive power requires system
capacity, but performs no work, utilities and plants
try to keep net kVARs low. High reactive power
translates to low power factor.
Utilities may charge higher rates or penalties for
low power factor or high VARs.
System capacity restrictions cause voltage drops
and overheating.
Inductive VARs can be corrected by applying
capacitors or active conditioners.
What to check?
See if your utility rate plan imposes a charge
for reactive demand or power factor.
Find out how the utility measures power
factor or VARs. For example, are they looking
at peak intervals or averages?
Identify loads that are causing lagging reactive
power and develop a strategy for power factor
correction.
How much is OK?
To avoid paying higher utility fees, power factor
should be higher than .97. Capacitors may be
applied on individual loads, at a confluence of
several, or at the service entrance to improve
power factor.
Note: This varies. Some utilities charge a rate for every percentage
point between .85 and .97. Some charge a rate based on the number
of VARs you use. Some don’t charge at all.
How much does an incident cost?
Example Calculation
Assume the utility adds 1% of demand charge
for each 0.01 below PF of 0.97.
Assume your PF averages 0.86 each month and
your demand charge is $7000.
(0.97-0.86) * 100% = 11%
(11% x $7000) x 12 months = $9,240
avoidable annual cost
How do I measure it with the 430 Series
Power Quality Analyzer?
Start at the service entrance, where the utility
takes its data, and then check individual loads or
transformers.
1. Connect the voltage and current leads of the
analyzer.
2. Configure the analyzer for the appropriate
3-phase power system: delta or wye.
3. Set the demand interval to correspond to the one
specified by your power utility. Press Setup,
Function Pref (F3). Select “Power & Energy” from
the Select Function menu. Arrow down past the
bottom of the screen until “Demand int” is high-
lighted.
4. Select “Power & Energy” from the main menu
and monitor the power.
Measuring the lowest power factor for a
demand interval: Press F4 Trend and then
press F1 to toggle through the parameters until PF
is displayed.
Measuring average power factor: Take the
ratio of kWh/kVAh to get the average PF over the
recording period. In the example shown below,
2.267/2.309 = 0.9818.
Measuring kVARh:
Whether your utility charges on total power factor(PF) or total kVARh
you can see it on this screen.
Cursors can help you record the lowest (PF) over a recording session.
©2005 Fluke Corporation. All rights reserved.
Printed in U.S.A. 3/2005 2435490 A-US-N Rev A

Navigation menu